You are on page 1of 19

Live Tank Circuit Breaker

Auto-PufferTM SF6
Circuit-breakers for
outdoor installation

Rated voltages
72.5-245kV
Rated currents
4000A
Rated breaking currents 50kA

Content

LTB FAMILY

Contents
I. Introduction..........................................................................................................1
II. Design Feature Auto-PufferTM ...........................................................................2
III. LTB Design Features and Advantages.............................................................4
IV.Technical Data According to ANSI................................................................12
V. Technical Data According to IEC.....................................................................13
VI. Dimensions-LTB ...............................................................................................14
VII. Shipping Data for LTB .................................................................................16

LTB FAMILY

Introduction

Introduction
Exceeding Customer Expectations -ABB Live Tank Circuit Breakers
ABB has over a century of experience in developing,
testing and manufacturing high voltage circuit
breakers. Through the years, our circuit breakers
have acquired a reputation for high reliability and
long life in all climates and in all parts of the world.
ABBs LTB circuit breaker family, with rated voltage
72.5-245 kV and breaking current up to 50 kA,
satisfies the highest demands. It is based on latest
developments in dielectric dimensioning and arc
physics research.
ABB produced the worlds first SF6 circuit breakers
with arc-assisted interrupters in the mid-1980s Auto-PufferTM.The energy required for interrupting
short circuit currents is partly taken from the arc
itself,significantly reducing the energy required

from the operating mechanism. Lower operating


energy inherently reduces mechanical stresses,
on the circuit breaker itself as well as on the
foundation, and increases circuit breaker reliability.
For many years, ABB has used operating
mechanisms with energy mechanically stored in
springs. This solution offers considerable
advantages in that the energy in the tensioned
springs is always available.
The design of the LTB is a well-proven technology
(over 20,000 units are in service).

= Brief Performance Data:


Installation
Design
Insulation
Rated Voltage
Rated Current
Breaking Current
Short Time Current
Insulators
Creepage Distance
Service Condition
Ambient Temperature
Design Altitude
Type of Operation

Outdoor/Indoor
SF6 Auto-PufferTM interrupter  spring operating mechanisms
SF6
72.5 - 245 kV
4,000 A
50 kA
50 kA/3 s
Composite or Porcelain
25 mm/kV (longer on request)
- 30to+40Operation in temperature down to -55 or up to+70
1,000 m.a.s.l.
Higher altitude on reques
Single- or Three- pole

Auto-PufferTM

LTB FAMILY

Design Feature Auto-PufferTM


Design Feature Auto-PufferTM Interrupters
Contact Parting
Closed

Main

Arcing

ValveOperation Arc Extinction

Open

1. Upper current carrier | 2. Stationary arcing contact | 3. Moving arcing contact | 4. Auto-PufferTM
volume | 5. Puffer volume | 6. Refill valve | 7. Stationary piston | 8. Nozzle | 9. Stationary main
contact | 10. Moving main contact | 11. Auto-puffer? valve | 12. Puffer cylinder | 13. Over-pressure
relief | 14. Lower current carrier

When interrupting high currents (e.g. rated shortcircuit current), Auto-PufferTM interrupters show the
advantage they were designed to provide.
On opening, the operation of an Auto-Puffer TM
interrupter at high current begins the same way as
a puffer interrupter. It is not until after arcing begins
that a difference in the operation principle is seen
between the high and low current interrupting
cases.
When the arcing contacts part, an arc is drawn
between the moving and stationary arcing contacts.
As the arc flows, it to some degree blocks the flow
of SF 6 gas through the nozzle. The arc drawn is
extremely hot and radiates a lot of heat and begins
to heat the SF6 gas in the interrupting gas volume.
Thus, the pressure inside the Auto-PufferTM and

puffer volumes increases due to the rise in


temperature as well as due to the com-pression of
gas between the puffer cylinder and stationary
piston.
Gas pressure inside the Auto-PufferTM volume
continues to increase until it is high enough to force
the Auto-PufferTM valve to the closed position. All
SF6 gas required for interruption is now trapped in
the fixed Auto-PufferTM volume and any further
increase in gas pressure in that volume is due solely
to heating from the arc. At about the same time,
the gas pressure in the puffer volume reaches a
level sufficient to push the overpressure valve open.
Since the gas in the puffer volume escapes through
the overpressure valve, Design Features AutoPufferTM Interrupters there is no need for a high
operating energy to overcome the compression of

Auto-PufferTM

LTB FAMILY

Design Feature Auto-PufferTM Interrupters


SF6 gas while at the same time maintaining the
contact speed necessary to withstand recovery
voltage.
When the current waveform crosses zero, the arc
becomes relatively weak. At this point, the
pressurized SF6 gas flows from the Auto-PufferTM
volume through the nozzle extinguishing the arc.
When interrupting low currents, Auto-PufferTM
interrupters act in much the same way as puffer
interrupters. That is, there is not sufficient gas
pressure generated to force the Auto-PufferTM valve
closed. Thus, the fixed Auto-Puffer TM volume and
puffer volume form one large puffer volume. In such
a case, the SF 6 gas pressure required for
interruption is built up by mechanical means as in
a puffer interrupter. Unlike a puffer nterrupter,
however, Auto-Puffer TM need only mechanically
generate sufficient gas pressure to interrupt a

portion of the rated short-circuit current (i.e. 20%


to 30%)
In the open position, there is sufficient distance
between the stationary and moving contacts to
withstand rated dielectric levels.
On closing, the refill valve opens so that SF6 gas
can be drawn into the Auto-PufferTM and puffer
volumes.Because interruption of low currents
requires only moderate build up of SF6 gas pressure
by mechanical means and since high current
interruption uses heating from the arc to generate
necessary gas pressure in a fixed volume, AutoPufferTM interrupters require far less operating
energy than puffer interrupters (i.e. about 50% less).
ABB Auto-PufferTM interrupter is also a single
motion design.

Design Features and Advantages

LTB FAMILY

LTB Design Features and Advantages


Design Features
LTB is available for single- or three-pole operation.
For circuit breakers with one breaking element per
pole, both modes of operation are possible.
For three-pole operation, the circuit breaker poles
and the operating mechanism are linked together
with pull rods. On every pole there is an individual
opening spring controlled by the pull rod. There is
however one exception. In the LTB D three-pole

operation case there is only one opening spring


cntrolling all three poles and it is mounted on the
pole furthest away from the operating mechanism.
Each circuit breaker pole constitutes a sealed SF6
filled unit, which includes the breaking unit, the
hollow post insulator and the mechanism housing.

9
7
4

10

Circuit Breaker type LTB D


1. Breaking Chamber
2.Support Insulator
3.Support Structure
4.Operating Mechanism type BLK
5. Trip Spring
6.Gas Tube with Protective Beam
7.Gas Supervision (On opposite side)
8. Drilled Holes for Connection to Ground
9. Pull rod with Protective Tube
10. Position Indicator
Note: 5, 6 ,9 are inside the horizontal beam
4

LTB FAMILY

The three poles of the circuit breaker can be mounted


on individual pole supports or in the case of LTB D on
a common support frame (pole beam).
BLK is used for:
LTB D 72.5-170 kV
LTB E 72.5-245 kV Single-pole operation
BLG is used for:
LTB E 72.5- 245 kV Three-pole operation

The operational reliability and the service life of an


SF6 circuit breaker is very much dependent on the
ability to ensure sealing of the SF 6 gas volume and to
neutralize the effects of moisture and decomposition
products in the gas.
The risk for gas leakage is negligible; double nitrile
rubber O-rings and X-rings are used with excellent
result.

Design Features and Advantages

Dielectric Strength
LTB has high dielectric strength even at atmospheric
SF6 pressure, due to optimized contact gap.

Controlled Switching
As option LTB circuit breakers can be used for
controlled switching by applying our controlling device
type SwitchsyncTM.For further information please see
chapter O-1Controlled Switching.

Stable Operating Times


For controlled switching it is of the utmost importance
that the functional times for closing and tripping
operations are constant. We can guarantee  1 ms
for all LTB circuit breakers.

Each breaking unit is provided with a desiccant,


which absorbs the moisture and the decomposition
products from the interruption process.
Since the interrupting capability is dependent on the
density of the SF 6 gas, the LTB circuit breaker is
provided with a density monitor.The density monitor
consists of a temperature compensated pressure
switch. Therefore, alarm signal and blocking function
are activated only if the pressure drops due to
leakage.
The design corresponds with the demands in the
standards IEC and ANSI. Special design solutions to
meet other standards and/or specifications are also
available.

Current Switching Capability


All LTB circuit breakers are capable of interrupting
short-circuit currents in a maximum of 40 ms. We can
also guarantee restrike free interruption of capacitive
currents due to optimized contact design and
movement.
For inductive current switching the over-voltages are
low as a result of optimum quenching at current zero.
5

Design Features and Advantages

LTB FAMILY

Material

Seismic Withstand Strength

The selected components of aluminum (mechanism


housings, HV-terminals, cubicles) give a high degree
of resistance to corrosion, without the need of extra
protection. For use in extreme trying environments
LTB can be delivered with a protective painting.

All LTB circuit breakers can in their standard versions,


withstand seismic accelerations up to 3 m/s2 (0.3 g),
LTBD up to 5 m/s2 in accordance with IEC 1166 and
IEEE 693.

Rating Plates
The support structure and protective tubes for the pull
rods are made of hot-dipped galvanized steel

Insulators
LTB circuit breaker is as standard delivered with
insulators that consist of high-grade brown-glazed
porcelain or composite insulators (light gray). LTB
with light gray porcelain can be delivered on request.

A rating plate, which includes data for the circuit


breaker, is placed on the operating mechanism
cubicle. The rating plate is made of stainless steel
with engraved text.

Operating Mechanism

LTB is available as standard with long creepage


distances.

The circuit breaker is operated by motor charged


spring operating mechanism(s), which is installed in a
compact splash proof and corrosion resistant housing,
attached to the structure.

Longer creepage distances can be quoted on


request.

One BLK is used for three-pole operation for LTB D


72.5 - 170 kV.

Mechanical Strength

Three BLKs are used for single pole operation for


LTB D 72.5 - 170 kV.

The mechanical durability gives a sufficient safety


margin for normal wind loads and static and dynamic
forces from conductors.

Three BLKs are used for single pole operation for


LTB E up to 245 kV.
One BLG is used for three-pole operation for LTB E
up to 245 kV.

LTB FAMILY

Design Features and Advantages

Sealing Systems for SF6 Volume


The sealing system consists of double nitrile rubber
O-rings in all static seals and double X-rings in all
dynamic seals.

breakers for more than 30 years with excellent service


record at varying climatic conditions.
The SF6 gas leakage is less than 0.5% per year.

This type of sealings has been used in our circuit

SF6 Density Monitoring


Since the interrupting capability is dependent on the
density of the SF 6 gas, the LTB circuit breaker is
provided with density monitor(s).

All LTB E circuit breakers have one density monitor


per pole.

The density monitor consists of a temperature


compensated pressure switch. Therefore, alarm signal
and blocking function are activated only if the
pressure drops due to leakage.
The standard version of LTB D for 72.5-170 kV has
one common density monitor for all three poles.
Alternatively LTB D can be provided with one density
monitor per pole.

Climatic Withstand
The LTB circuit breakers are designed for, and are
installed in, widely shifting conditions from polar to
desert climate throughout the world.

consequences, one of the following gas-mixtures is


used:

For circuit breakers installed in areas with extreme low


temperatures there is a risk of condensation of the
SF6 gas. In order to avoid condensation

SF6 and CF4

SF6 and N2

Design Features and Advantages

LTB FAMILY

Support Structure
Support structures are included in the standard versions
of the LTB circuit breakers. The support structures are
made of hot-dipped galvanized steel. The standard
versions for structures are:

D=14(4X)

40
28

LTB D 72.5-170 kV One support column per

44.5

LTB E all types One support column per pole


338

For detailed information see Dimensions


The support structures are prepared for connection to
ground by means of drilled holes on each leg.

Drilled holes for connection

High Voltage Terminals


The LTB circuit breakers are as standard equipped with
flat aluminum terminals with thickness 20 mm for LTB D
and 28 mm for LTB E.

Circuit breakers with vertically mounted breaking


elements have terminals on both sides for connection
in either direction.

The drilling pattern is in accordance with IEC and NEMA

Circuit breakers with horizontal breaking elements have


one terminal per breaking element. The terminals are
directed upwards.

standards. Other dimensions (e.g. DIN) by means of


adapters, are available on request.

125
23

40 40

44.5
22.25
40
40

14.5(13X)

28.5

44.5

LTB FAMILY

Controlled Switching Devices


The goal for controlled switching is to increase power
quality in the network systems by reducing switching
transients. All LTB circuit breakers are suitable for
controlled switching with ABBs Switchsync TM device.

Design Features and Advantages

For circuit breakers with two breaking elements per pole,


the breaking elements and the support insulators are
transported in two separate cases.
For detailed information regarding weights and
dimensions see Shipping data.

In order to obtain optimum result the switching instants


should be different for the three phases. For three-pole
operated circuit breakers this is achieved with
mechanically staggered poles.

Breaking elements as well as support insulators are filled


with SF6 gas at a slight overpressure.

Presently more than 1,000 HV live tank circuit breakers


manufactured by ABB are in operation with controlled
switching.

Arrival Inspection

Type Tests
The LTB circuit breakers have been type tested in
accordance with IEC and/or ANSI standards. Type test
reports can be presented on request.

Routine Tests
All LTB circuit breakers are routine tested before delivery.
Our test program complies with IEC and ANSI standards.

Transport
The LTB circuit breakers are normally packed and
transported in seaworthy wooden crates.The circuit
breaker poles with one breaking element per pole are
transported as com-plete units.

On arrival the packaging and contents should be


checked against packing list. In the event of damage to
the goods, contact ABB for advice, before further
handling of the goods takes place. Any damage ought
to be documented (photographed).

SF6 gas
Gas for filling up to rated pressure can be delivered in
bottles, each containing 40 kg gas.
The quantity required for each type of LTB varies from
one circuit breaker type to an-other. This information is
given in the tender.
The pressurizing equipment can be delivered on request,
and is described under Erection and Commissioning.

Design Features and Advantages

Erection and Commissioning

LTB FAMILY

The general actions are described below:


1-2 years: Ocular inspection

Assembly instructions are provided with each delivery.


Erection work at site can be done in 1-4 days depending
on LTB type and size.
Filling of SF6 gas to specified rated pressure is done by
using the following pressuri-zing equipment, which can
be delivered on request:
One special control valve, for connection to the gas
bottle, and a 20 m gas-filled hose with connectors.
A complementary control valve for connection to CF4
or N2 gas bottle (for mixed gas filling).
When using above equipment gas filling can be carried
out without gas being released into the atmosphere.
For illustration of gas filling equipment see page I-6.

Maintenance
LTB is designed for a service life of more than 30 years
or 10,000 mechanical operations. For current switching
the number of operations before service is dependent
on the interrupted current and type of application.
Inspection, maintenance and overhaul should be carried
out at regular intervals de-pending on the ambient
conditions and the number of operations.

10

7-10 years or 2,000 mechanical operations: Extended


ocular inspection and some lubrication of the operating
mechanism(s)
15-20 years or 5,000 mechanical operations Preventive
maintenance including general inspection of the circuit
breaker and operating mechanism. Operation test
including measurement of operating times and possible
adjustments.
30 years or 10,000 mechanical operation: A
comprehensive inspection is recommended to give
increased safety and continued problem-free operation.
The inspection methods and scope depend very
much on the local conditions.
For circuit breakers for special switching duties such as
switching of reactor banks overhaul of the breaking
chamber should be carried out more frequently,
approximately 5,000 operations
Overhaul and repair work must be performed by
authorized personnel only.
The instructions in the manual for operation and
maintenance should be observed.
ABB is available for discussions and advice.

LTB FAMILY

Design Features and Advantages

Recommended Spare Parts

Disposal

High operation frequency (e.g. circuit breakers for


reactor or capacitor switching) and/or large quantities
of circuit breakers:

The disposal of wasted parts should be carried out in


accordance with local legal provisions.

Complete poles
Complete operating mechanisms

The SF6 gas should not be released into the atmosphere


when the circuit breaker is scrapped. The SF6 gas can
be recycled.

Sets of contacts
Sets of gaskets
Density switches
SF6 gas

The porcelain can, after it has been crushed, be used


as fill.
The metals used in the circuit breaker can be recycled.

11

Technical Data

LTB FAMILY

12

LTB 170D1/B
365/315
365/315

LTB 245E1

310/275
310/275

1
170
60

LTB 170E1

1
145
60

LTB 72.5E1

Number of breaks per pole


1
Rated voltage
kV
72.5
Rated frequency
Hz
60
Power frequency withstand voltage
- To earth (Dry/Wet)
kV
160/140
-Across open pole(Dry/Wet)
kV
160/140
Lightning Impulse Withstand Voltage
- To earth
kV
325
-Across open pole
kV
325
Chopped Wave Impulse Withstand Voltage
To earth (2 s)
kV
452
Across open pole(2 s)
kV
452
Switching Impulse Withstand Voltage
- To earth and/between phases
kV
-Across open pole
kV
mm/kV
25
Creepage distance
Rated normal current
A
3000
Rated s.c current
kA
40
First-pole-to-clear factor
1.5
Rated closing and latching current kA
104
Duration of short time withstand circuit
s
3
Closing time
ms
< 40
Opening time
ms
22
Break time
ms
40
Dead time
ms
300
Rated Standard Operating Duty
-

LTB 145D1/B

LTB 72.5D1/B

Technical Data According to ANSI

1
72.5
60

1
170
60

1
245
60

160/140
160/140

365/315
365/315

425/350
425/350

650
650

750
750

350
350

750
750

900
900

838
838

968
968

452
452

968
968

1160
1160

25
4000
50
1.5
104
3
< 55
17
40
300

25
4000
50
1.5
104
3
< 55
17
40
300

25
25
25
3000
3000
4000
40
40
50
1.5
1.5
1.5
104
104
104
3
3
3
< 40
< 40
< 55
22
22
17
40
40
40
300
300
300
O-0.3s-CO-3min-CO or CO-15s-CO

LTB FAMILY

Technical Data

1
72.5
50

1
170
50

1
245
50

140
140

275
275

325
325

140
140

325
325

460
460

325
325

650
650

750
750

325
325

750
750

1050
1050

25
3150
40
1.5
100
3
< 40
22
40
300

25
25
25
3150
3150
4000
40
40
50
1.5
1.5
1.5
100
100
125
3
3
3
< 40
< 40
< 55
22
22
17
40
40
40
300
300
300
O-0.3s-CO-3min-CO or CO-15s-CO

25
4000
50
1.5
125
3
< 55
17
40
300

25
4000
50
1.5
125
3
< 55
17
40
300

LTB 245E1L

1
170
50

LTB 170E1

1
145
50

LTB 72.5E1

1
72.5
50

LTB 170D1/B

LTB 145D1/B

Number of breaks per pole


Rated voltage
kV
Rated frequency
Hz
1)
Power frequency withstand level
- To earth and between phases
kV
-Across open pole
kV
Lightning Impulse Withstand Level(LIWL)
- To earth and between phases
kV
-Across open pole
kV
Switching Impulse Withstand Level(SIWL)
- To earth and/between phases
kV
-Across open pole
kV
mm/kV
Creepage distance
Rated normal current
A
Rated s.c breaking current
kA
First-pole-to-clear factor
Making current peak
kA
Duration of short circuit
s
Closing time
ms
Opening time
ms
Break time
ms
Dead time
ms
Rated Operating Sequence
-

LTB 72.5D1/B

Technical Data According to IEC

13

Dimensions-LTB

LTB FAMILY

Dimensions-LTB
Dimensions -LTBD
LTB D1/B Two-Column Stand,
Three-pole Operation
Rated Voltage: 72.5 - 170 kV
Dimensions(mm)
Rated
A
B
C
D
E
F
Voltage
72.5 kV
4647
1164 670
3283 1050 3230
145 kV
5197
1164 1220 3833 1750 4630
170 kV
5808 1475 1520 4133 1750 4630
Available dimensions for phase distances
and heighes to lowest part of insulator(mm)
Rated
phase distances
Voltage
72.5 kV
1050*
1500*
1750*
2000
2500
145 kV
1500*
1750
2000
2500
170 kV
1750
2000
2500
*) Standard **)BIL550kV
ated
Height to lowest part of insulator**
Voltage
72.5 kV
1123
2503*
2945
3528
*) Standard
**) Other dimensions can be provided

F
E

E
267

C
A

D
2503
1740

2530

LTB D1/B Three-Column Stand,


Three-pole Operation
Rated Voltage: 72.5 - 170 kV
Dimensions(mm)
Rated
A
B
C
D
E
F
Voltage
72.5 kV
4647
1164 670
3283 1050 3266
145 kV
5197
1164 1220 3833 1750 4666
170 kV
5808 1475 1520 4133 1750 4666
Available dimensions for phase distances
and heighes to lowest part of insulator(mm)
Rated
phase distances
Voltage
72.5 kV
1050* 1500* 1750* 2000 2500 3000
145 kV
1500* 1750 2000 2500 3000
170 kV
1750 2000 2500 3000
*) Standard **)BIL550kV
Rated
Height to lowest part of insulator**
Voltage
72.5 kV
800
2503*
2950
3203
*) Standard
**) Other dimensions can be provided
14

F
E

267

C
A
D
2503
1750

LTB FAMILY

Dimensions-LTB

Dimensions --LTBE
LTB E1 Three-pole Operation
Rated Voltage: 72.5 - 245 kV
Dimensions(mm)
Rated
A
B
C
D
E
Voltage
72.5 kV
4790
1292 655
3244 1100
170 kV
5400
1292 1265 3854 3500
245 kV
6703
1914 1955 4544 3500
Available dimensions for phase distances
and heighes to lowest part of insulator(mm)
Rated
phase distances
Voltage
72.5 kV
1100*
1500 2500 3000 3500
170 kV
2500* 3000 3500
245 kV
2500 3000 3500
*) Standard
Rated
Height to lowest part of insulator**
Voltage
72.5-245 kV
1950
2508*
2992
3642
*) Standard

F
3590
6390
8390

4000
4000
4000

4142

LTB E1 Single-pole Operation


Rated Voltage: 72.5 - 245 kV
Rated
A
B
C
Voltage
72.5 kV
4790
1292 655
170 kV
5400
1292 1265
245 kV
6703
1914 1955
*)Recommended phase distances

3244
3854
4544

2500
2500
3500

6298
6298
8298

Available dimensions for phase distances


and heighes to lowest part of insulator(mm)
Rated
Height to lowest part of insulator**
Voltage
72.5-245 kV
1442
2508*
2992
3642
*) Standard

4142

15

Shipping Data for LTB D

LTB FAMILY

Shipping Data for LTB


Shipping Data for LTBD
LTB 72.5D1/B,Three-pole Operated, Three-Column Stand
Equipment
Breaker Poles
Operating mechanism
Support Structure
Total

Number of
cases
1
1
1
3

Dimensions
L x W x H (m)
3.26 x 1.78 x 0.72
1.18 x 1.05 x 1.00
2.40 x 0.58 x 0.44
6.0 m3

Gross Weight
(Kg)
1045
250
330
1625

LTB 145D1/B,Three-pole Operated, Three-Column Stand


Equipment
Breaker Poles
Operating mechanism
Support Structure
Total

Number of
cases
1
1
1
3

Dimensions
L x W x H (m)
3.26 x 1.78 x 0.72
1.18 x 1.05 x 1.00
2.40 x 0.58 x 0.44
6.0 m3

Gross Weight
(Kg)
1155
250
330
1735

LTB 170D1/B,Three-pole Operated, Three-Column Stand


Equipment
Breaker Poles
Operating mechanism
Support Structure
Total

Number of
cases
1
1
1
3

Dimensions
L x W x H (m)
3.90 x 1.78 x 0.72
1.18 x 1.05 x 1.00
2.40 x 0.58 x 0.44
6.9 m3

Gross Weight
(Kg)
1270
250
330
1850

LTB 170D1/B,Three-pole Operated, Three-Column Stand


Equipment
Breaker Poles
Operating mechanism
Pole Beam
Support Structure
Total

Number of
cases
1
1
1
1
3

Dimensions
L x W x H (m)
3.26 x 1.78 x 0.72
1.18 x 1.05 x 1.00
2.69 x 0.57 x 1.00
2.40 x 0.58 x 0.44
7.6 m3

Gross Weight
(Kg)
1045
250
200
220
1715

LTB 145D1/B,Three-pole Operated, Three-Column Stand


Equipment
Breaker Poles
Operating mechanism
Pole Beam
Support Structure
Total

Number of
cases
1
1
1
1
4

Dimensions
L x W x H (m)
3.26 x 1.78 x 0.72
1.18 x 1.05 x 1.00
4.09 x 0.57 x 1.00
2.40 x 0.58 x 0.44
8.4 m3

Gross Weight
(Kg)
1155
250
250
220
1875

LTB 170D1/B,Three-pole Operated, Three-Column Stand


Equipment
Breaker Poles
Operating mechanism
Pole Beam
Support Structure
Total
16

Number of
cases
1
1
1
1
4

Dimensions
L x W x H (m)
3.90 x 1.78 x 0.72
1.18 x 1.05 x 1.00
4.09 x 0.57 x 1.00
2.40 x 0.58 x 0.44
9.2 m3

Gross Weight
(Kg)
1270
250
250
220
1990

LTB FAMILY

Shipping Data for LTB E

Shipping Data for LTB


Shipping Data for LTBE
LTB 72.5 and 170E1,Three-pole Operated, Three-Column Stand
Equipment
LTB 72.5 Breaker Poles
LTB 170 Breaker Poles
Operating Mechanism
Support Structure
LTB 72.5
LTB 170

Number of
cases
1
1
1
1
3
3

Dimensions
L x W x H (m)
on request
5.90 x 1.90 x 0.97
1.80 x 0.97 x 1.07
2.38 x 1.10 x 0.36
on request
13.7 m3

Gross Weight(Kg)
72.5
170
on request
3600
550
550
280
280
on request
4430

LTB 72.5 and 170E1,Single-pole Operated, Three-Column Stand


Equipment
LTB 72.5 Breaker Poles
LTB 170 Breaker Poles
Operating Mechanism
Support Structure
LTB 72.5
LTB 170

Number of
cases
1
1
1
1
3
3

Dimensions
L x W x H (m)
on request
5.90 x 1.90 x 0.97
2.50 x 1.17 x 1.00
2.38 x 1.10 x 0.36
on request
14.7 m3

Gross Weight(Kg)
72.5
170
on request
3600
1000
1000
280
280
on request
4880

LTB 245 E1-Three-pole Operated


Equipment
Breaker Poles
Operating Mechanism
Support Structure
Total

Number of
cases
1
1
1
3

Dimensions
L x W x H (m)
5.90 x 1.90 x 0.97
1.80 x 0.97 x 1.07
2.38 x 1.10 x 0.36
13.7 m3

Gross Weight(Kg)

Dimensions
L x W x H (m)
5.90 x 1.90 x 0.97
2.50 x 1.17 x 1.00
2.38 x 1.10 x 0.36
14.7 m3

Gross Weight(Kg)

3600
550
280
4430

LTB 245 E1-Single-pole Operated


Equipment
Breaker Poles
Operating Mechanism
Support Structure
Total

Number of
cases
1
1
1
3

3600
1000
280
4880

17