You are on page 1of 28

PROJECT:

SOUTH YARAN OIL


FIELD DEVELOPMENT PROJECT
DOCUMENT TITLE :

Data Sheet for MV Switchgear and MCC

DOCUMENT NO

SYME-ELBASC-ENEL-DSEL-0002-B03

SHEET NO. :

Rev.:

1 of 28

B03

Data Sheet for MV Switchgear and MCC

B03

15-Mar-14

Issued For Design

T.Rostami

S.Garjani

A.Bodaghi

B02

25-Jan-14

Issued For Design

T.Rostami

S.Garjani

A.Bodaghi

B01

18-Nov-13

Issued For Comment

S.Garjani

S.Garjani

A.Bodaghi

Rev

Date

Description

Prepared

Checked

Approved
SAZ. POI :

This document is the property of OWNER. Any unauthorized attempt to reproduce it, in any form, is strictly prohibited.

IFD1

PROJECT:
SOUTH YARAN OIL
FIELD DEVELOPMENT PROJECT

DOCUMENT TITLE :

Data Sheet for MV Switchgear and MCC

DOCUMENT NO

SYME-ELBASC-ENEL-DSEL-0002-B03

SHEET NO.:

Rev. :

2 of 28

B03

TABULATION OF REVISED PAGES


SHEET

REVISIONS
01

02

1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
19
18
19
20
21
22
23
24

X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X

X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X

25

26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50

X
X
X
X
X
X
X

03

04

05

06

07

08

SHEET

51
52
53
54
55
56
57
58
59
60
61
62
63
64
65
66
67
68
69
70
71
72
73
74

75

X
X

76
77
78
79
80
81
82
83
84
85
86
87
88
89
90
91
92
93
94
95
96
97
98
99
100

X
X

X
X

REVISIONS
01

02

03

04

05

06

07

This document is the property of OWNER. Any unauthorized attempt to reproduce it, in any form, is strictly prohibited.

08

PROJECT:
SOUTH YARAN OIL
FIELD DEVELOPMENT PROJECT

DOCUMENT TITLE :

DataSheetforMVSwitchgearandMCC

SHEET NO.:

Rev. :

DOCUMENT NO

SYME-ELBASC-ENEL-DSEL-0002-B03

3 of 28

B03

TABLE OF CONTENTS
1

REV

Sheet No.

Contents

3
4

1-

11KV SWITCHGEAR

5
6

1-GENERAL

2-CIRCUIT BREAKER

3-CT, VT AND MEASURING DEVICES

7
8
9
10
11

4-PROTECTION RELAYS

12
13

5-INCOMING

14

15
16

9
10

6-BUS TIE

11

7-MOTOR FEEDERS (P>1000KW)

12

8-11KV SWGR FEEDERS SCHEDULE

13

17
18
19
20
21
22
23

2-

CLUSTER 33-KV SWITCHGEAR

24
25

1-GENERAL
1
GENERAL

14

2-CIRCUIT BREAKER

16

3-CT, VT AND MEASURING DEVICES

18

4-ALARM SYSTEM

19

26
27
28
29
30
31
32
33

5-INCOMING

34

6-BUS TIE

35

36

7-TRANS OUTGOING FEEDER

37
38
39

20
21
22

8-33 KV OVERHEAD LINE

23

9-33KV SWGR FEEDERS SCHEDULE

24

40
41
42
43

3-

WEALHEADS 33-KV SWITCHGEAR

44

1-GENERAL

45

46
47

25

2-LOAD BREAK SWITCH

26

NOTES

28

48
49
50

4-

51
52
53
54
55
56
57
58

This document is the property of OWNER. Any unauthorized attempt to reproduce it, in any form, is strictly prohibited.

PROJECT:
SOUTH YARAN OIL
FIELD DEVELOPMENT PROJECT

DOCUMENT TITLE :

DataSheetforMVSwitchgearandMCC

DOCUMENT NO

SYME-ELBASC-ENEL-DSEL-0002-B03

SHEET NO.:

Rev. :

4 of 28

B03

DATA SHEET FOR 11KV SWITCHBOARD


1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19

ENVIRONMENTAL CONDITIONS
Max absolute temperature
Min temperature
Maximum & Minimum Humidity
Maximum sun temperature
Max & Min Wind speed
Barometric pressure
PARTICULARS OF EQUIPMENT
MOTOR INSTALLATION CONDITION
Location type
Installation
Area Classification
Installation condition
Min& Max Temperature
GENERAL
Manufacture
Purchaser applicable specification
Standard of manufacture
Model Number

C
C
%
C
m/s
mmHg
UNITS

50
0
74 , 41
85
9.6 , 6.2
736
PURCHASER'S REQUIREMENTS

Onshore
Indoor
Safe,non-hazard
With HVAC
5 / 45

20 Type
21
22
23
24
25
26
27
28
29

Rated voltage
Rated frequency
Number of phases
Rated lightning impulse withstand voltage
Rated short duration power frequency witstand voltage
Rated short time withstand current and time
Rated peak withstand current
Internal arc fault withstand
Duration of internal arc fault test

30 Earth busbar withstand current and time


31

kV
Hz
kV (peak)
kV (rms)
kA (rms)
kA (peak)
secs
kA (rms)

Switchboard Arrangement (Single Line/Back-to-Back/LShape)


Busbar system:
Rated normal current (main busbar)
A
Phase segregated busbars
Yes / No
Busbar arrangement (Single / Duplicate)
Busbar identification
Busbar material
Busbar cross sectional area
mm2
Busbar insulation
Yes/No
Future busbar extension at either end
Yes/No
Circuit breaker type
Contactor type
0
Control supply:
Voltage
V
Total power consumption
W
Trip supply:
Voltage
V
Total power consumption
W
Spring charge motor:
Voltage
V
Maximum power consumption
W
Switchboard access type
Degree of protection (IEC 60529):
Enclosure
Thickness of steel enclosure
mm
0
Document/drawings:
Overal Single line diagram for Cluster

32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
MV and LV Metering and protection Single Line Diagram
56

VENDOR'S RESPONSE

VTA
SYME-ELBASC-ENEL-SPMC-0001
Refer to Specification
VTA
Air insulated, metal Clad,
Withdrawable (Note 1)
12
50
3
75 (phase to earth)
28 kV for 1 min
25kA, 3s
65
to IEC 62271
VTA
To be suitable for 400A for 10 secs
(Note 17)
Single line
2500
Yes
Single
Colour coded (R-Y-B)
HDHC copper (Note 15)
VTA
Flame retardant/non-hygroscopic
Yes (both)
Vacuum
N.A.
110 V DC +/-10%
VTA
110 V DC +/-10%
VTA
110 V DC +/-10%
VTA
Rear access
IP42/IP20
2.5
SYME-ELBASC-ENEL-DISL-0004
SYME-ELBASC-ENEL-DISL-0005

This document is the property of OWNER. Any unauthorized attempt to reproduce it, in any form, is strictly prohibited.

Rev.

PROJECT:
SOUTH YARAN OIL
FIELD DEVELOPMENT PROJECT

DOCUMENT TITLE :

DataSheetforMVSwitchgearandMCC

DOCUMENT NO

SYME-ELBASC-ENEL-DSEL-0002-B03

1
2
3
4
5
6
7
8
9
10
11
12

DATA SHEET FOR 11KV SWITCHBOARD


PARTICULARS OF EQUIPMENT
PURCHASER'S REQUIREMENTS
UNITS
230 V AC
Anti-condensation heaters:
Voltage
V
VTA
Power consumption
W
Yes (all cubicles)
Required
Yes
Anti-condensation heater 'ON' indication
Yes/No
Light Grey, BS 381C, No. 631
Panel exterior paint colour
Light Grey, BS 381C, No. 631
Panel interior paint colour
0
VTA (Note 7)
Paint specification
VTA
Overall dimensions of the switchboard:
(L x W x H)
mm
VTA
Total weight
kg
VTA
Largest shipping section dimensions
(L X W x H)
mm
VTA
Shipping sections (number and weights)
kg

13 Expected assembly heat dissipation at full load

VTA

14 Number of Cubicles
15
16 Earthing:
17 Method of busbar earthing
18 Rated short circuit current and time
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56

Asymmetrical peak making current capability


Busbar cross sectional area
Earth switch for all circuits including busbars
Earth switch Interlocks
TEST REQUIREMENTS
Type Test
Routine Tests
Site Tests
ACCESSORIES
Lifting Eye (Transportation Section/Cubicle)
Connectors: compression type, space for stress cones
Labels: black letters on white lamacoid
Racking crank assembly
Manual charging handle
Circuit Breaker Removal Truck
Arc chute lifting supports
Arc chute lifting plates
Test jumpers complete with plugs
Key interlock
Grounding truck
Cubicle Lights
Cubicle Mimics
Cubicle Locks and Keys
Floor Frame
Lamp Test Facilities
Voltage Present Lights (Circuit Breaker Dead Side)
Test plug for VT & CT metering and protection

VTA
To be suitable for 400A for 10 secs
(Note 17)
VTA
VTA
Yes, Note 4
Yes, Note 4

kA
kA pk
mm2
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No

Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No

Rev. :

5 of 28

B03

VENDOR'S RESPONSE

VTA

kW

SHEET NO.:

Certificate only required


Yes, see Note 4
Yes, see Note 4

Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
No
Yes
Yes
Yes
Yes
Yes
Yes
Yes

This document is the property of OWNER. Any unauthorized attempt to reproduce it, in any form, is strictly prohibited.

Rev.

PROJECT:
SOUTH YARAN OIL
FIELD DEVELOPMENT PROJECT

DOCUMENT TITLE :

DataSheetforMVSwitchgearandMCC

DOCUMENT NO

SYME-ELBASC-ENEL-DSEL-0002-B03

1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58

PARTICULARS OF EQUIPMENT

DATA SHEET FOR 11KV SWITCHBOARD


PURCHASER'S REQUIREMENTS

UNITS

SHEET NO.:

Rev. :

6 of 28

B03

VENDOR'S RESPONSE

CIRCUIT BREAKER PANEL DATA


See SYME-ELBASC-ENEL-DISL-0004
Number of circuit breakers
No.
Modular, withdrawable
Panel type
VTA
Manufacturer of Circuit Breakers
VTA
Type No.
Vacuum
Type
See SYME-ELBASC-ENEL-DISL-0004
Rated normal current
A
12
Rated voltage
kV
25kA, 3s
Rated short circuit breaking current
kA (rms)
65
Rated short circuit making current
kA (peak)
25
Rated short time withstand current
kA (rms)
Insulation levels:
75 kV across contacts
Rated lightning impulse withstand voltage
kV (peak)
28 kV across contacts for 1 min
Rated short duration power frequency withstand volta kV (rms)
110 V DC
Trip coil:
Voltage
V
VTA
Power
VA
110 V DC
Close coil:
Voltage
V
VTA
Power
VA
2 No for Incom/1 No for Outgoings
No of Trip Coil
1
No of Close Coil
Spring charged Motor/Hand Operated
Operating Mechanism
110V DC
Spring charge motor voltage
V
VTA
Spring charge motor rating
kW
O-0.3sec-CO-3min-CO
O
0.3sec CO 3min CO
Rated operating sequence of circuit breaker
VTA
Circuit breaker closing time
msecs
VTA
Circuit breaker opening time
msecs
VTA
Mechanical endurance
VTA
Electrical endurance
VTA
Minimum lifetime (No. of Operations)
Yes
Anti pumping device
Yes/No
Yes
Mechanical operations counter
Yes/No
Yes
Manual mechanical trip facility
Yes/No
Yes
Closed/open position indication
Yes/No
Yes
Charged/discharged spring indication
Yes/No
Yes (Note.11)
Emergency shutdown interposing relay
Yes/No
Circuit Breaker Status Auxiliary Switches
Minimum 4 contacts
No. of make contacts
Minimum 4 contacts
No. of break contacts
220V DC
Rated voltage
VTA
Rated Current at voltage
Circuit Breaker Position Auxiliary Switches
for Each Position
Minimum 4 contacts
Service Position No. of contacts
Minimum 4 contacts
Withdrawn Position No. of contacts
Minimum 4 contacts
Test Position No. of contacts
220V DC
Rated voltage
VTA
Rated Current at voltage
0

This document is the property of OWNER. Any unauthorized attempt to reproduce it, in any form, is strictly prohibited.

Rev.

PROJECT:
SOUTH YARAN OIL
FIELD DEVELOPMENT PROJECT

DOCUMENT TITLE :

DataSheetforMVSwitchgearandMCC

DOCUMENT NO

SYME-ELBASC-ENEL-DSEL-0002-B03

1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58

PARTICULARS OF EQUIPMENT
Two stage SF6 gas pressure switch

DATA SHEET FOR 11KV SWITCHBOARD


PURCHASER'S REQUIREMENTS
UNITS
N.A.
Yes/No

Power cable entry


Control cable entry
Gland plate

Overall dimensions of the panel:

(D x W x H)

Communications (Note 9)
Communications with PDCS/DCS/
Substation Alarm Panel/UCPs:

Protocol

DCS control inputs


PDCS control inputs

mm

Yes/No
Yes/No

CABLE EARTH SWITCH


Manufacturer and model
Rated short time withstand current
Rated short circuit making current
Rated duration of short circuit
Actuation Mechanism
Position Indicator

kA (rms)
kA (peak)
sec
Yes/No

0
0

Bottom
Bottom
Yes, Bottom, Removable undrilled
Galvanized steel/ non magnetic (for
VTA

Modbus (Relays status & setting)


Hardwire (Status & Control)
Hardwire (Substation alarm panel)
Hardwire (UCPs)
Yes, motor control only
Yes, Power Distribution CB

VTA
To be suitable for 400A (Note 17)
VTA
30
VTA
Yes

Status Auxiliary Switches


No. of make contacts
No. of break contacts
Rated voltage
Rated Current at voltage

Minimum 4 contacts
Minimum 4 contacts
220V DC
VTA

SURGE ARRESTER
Manufacturer
Model No.
Type
Max Rated Voltage
Nominal Discharge Current (class of surge arrestor)

VTA
VTA
Metal Oxide Arrester
12
10(Heavy Duty)

kV
KA

Rev. :

7 of 28

B03

VENDOR'S RESPONSE

0
0

SHEET NO.:

This document is the property of OWNER. Any unauthorized attempt to reproduce it, in any form, is strictly prohibited.

REV

PROJECT:
SOUTH YARAN OIL
FIELD DEVELOPMENT PROJECT

DOCUMENT TITLE :

DataSheetforMVSwitchgearandMCC

DOCUMENT NO

SYME-ELBASC-ENEL-DSEL-0002-B03

PARTICULARS OF EQUIPMENT
1
2 VOLTAGE TRANSFORMERS
3 Manufacturer and model no.
4 Type
No of Secondary Winding
5 Class
6 Ratio
7 Secondary voltage (Phase-Phase)
8 Rated Voltage Factor
9 Fixed/Withdrawable
10
11 CURRENT TRANSFORMERS
12 Manufacturer and model no.
13 Type
14
15 Class
16
17 Ratio
18 Rated Continuous Thermal Current
19 Secondary current
20 Meters & Measurement
21 General
22
Size
23
Accuracy
24
25 VOLTMETERS
26
Manufacturer and model no.
27
Scale
28
29 FREQUENCY METER
30
Manufacturer and model no.
31
Scale
32
33 AMMETER
34
Manufacturer and model no.
35
Scale
36
37 WATT HOUR METER
38
Manufacturer and model no.
39
Scale
37
38 WATT METER
39
Manufacturer and model no.
40
Scale
41
42 VAR METER
43
Manufacturer and model no.
44
Scale
45
46 TRANSDUCERS
47
Manufacturer and model no.
48
output accuracy
49
output
50
51
52
53
54
55
56

DATA SHEET FOR 11KV SWITCHBOARD


PURCHASER'S REQUIREMENTS
UNITS

VTA
See Note 10
5P20 for O/C and E/F
0.5F10 for Metering
See SYME-ELBASC-ENEL-DISL-0004
1.2 In
1

96 x 96
Class 1

mm

VTA
0-12kV

VTA
0-65Hz

VTA
1.5In

VTA
To be suitable for circuit rating

0
0
0

Rev. :

8 of 28

B03

VENDOR'S RESPONSE

VTA
See Note 10 (3 single phase)
2
CL 0.1+3P
11000/3/110/3/110/3
110
1.2 continuous, 1.5 for 30s
Withdrawable

SHEET NO.:

VTA
To be suitable for circuit rating

VTA
To be suitable for circuit rating

VTA
+/-0.5%
4-20mA

This document is the property of OWNER. Any unauthorized attempt to reproduce it, in any form, is strictly prohibited.

Rev.

PROJECT:
SOUTH YARAN OIL
FIELD DEVELOPMENT PROJECT

DOCUMENT TITLE :
DOCUMENT NO

1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55

DataSheetforMVSwitchgearandMCC
SYME-ELBASC-ENEL-DSEL-0002-B03

PARTICULARS OF EQUIPMENT
PROTECTION RELAYS - GENERAL
Microprocessor based with LCD
Auxiliary voltage
Auxiliary voltage range
Trip Contacts
Alarm Contacts
Contacts rating
Ingress protection

DATA SHEET FOR 11KV SWITCHBOARD


PURCHASER'S REQUIREMENTS
UNITS
Yes/No
V
%
0

SHEET NO.:

Rev. :

9 OF 28

B03

VENDOR'S RESPONSE

Yes
110V DC
+/-10%
Minimum 2 NO and 2 NC
Minimum 2 NO and 2 NC
VTA
IP51

0
0
0
0

0
0
0

This document is the property of OWNER. Any unauthorized attempt to reproduce it, in any form, is strictly prohibited.

Rev.

PROJECT:
SOUTH YARAN OIL
FIELD DEVELOPMENT PROJECT

DOCUMENT TITLE :

DataSheetforMVSwitchgearandMCC

DOCUMENT NO

SYME-ELBASC-ENEL-DSEL-0002-B03

1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16

PARTICULARS OF EQUIPMENT
11KV INCOMING FEEDER
General
Rated normal current
No. of Poles
Protection Requirements (Note 5)
Protection Relay manufacturer and model
Differential Protection
Restricted Earth Fault
Instantaneous Overcurrent
Delayed Overcurrent
Delayed Earth Fault
Instantaneous Earth Fault
Undervoltage with time delay
Standby Earth Fault (transformer neutral)

DATA SHEET FOR 11KV SWITCHBOARD


PURCHASER'S REQUIREMENTS
UNITS

17 Transformer Protection

Yes/No

18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57

Yes/No
Yes/No
Yes/No

VTA
No (It is located in 33kv side)
No (It is located in 33kv side)
Yes (alarm to PDCS)
Yes (alarm to PDCS)
Yes (alarm to PDCS)
Yes (alarm to PDCS)
Yes (alarm to PDCS)
Yes (alarm to PDCS)
At Transformer (Interface relays in
swbd)
Yes
No
Yes

Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No

Swbd
Note 13
Yes
Yes
Yes
Yes
Yes
No
No
Yes
Yes
No
Yes
Yes
Yes

PDCS
N.A.
Yes
Yes
Yes
Yes
Yes
Yes
Yes
N.A.
No
Yes
Yes
No
No

Sub. Alarm
N.A.
N.A.
N.A.
N.A.
N.A.
N.A.
N.A.
N.A.
N.A.
N.A.
N.A.
N.A.
N.A.
N.A.

Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No

Swbd
Yes
Yes
Yes
Yes
Yes
Yes
Yes

PDCS
4 - 20mA
4 - 20mA
4 - 20mA
4 - 20mA
4 - 20mA
4 - 20mA
4 - 20mA

Sub. Alarm
N.A.
N.A.
N.A.
N.A.
N.A.
N.A.
N.A.

Check sync relay (3 phase type)


External lockout relay
Control circuit supervision & DC Volts fail relay
Control and Indication
Manual/Remote/Auto Selector Switch
"Close" control pushbutton
(Green)
p
(
)
"Open" control pushbutton (Red)
"Closed" indication (Red)
"Open" indication (Green)
Fault indication (Amber)
Transformer only protection Alarm indication
Transformer only protection Trip indication
Transformer Alarm Window
Control circuit supervision & DC Volts fail
"Available" status
"Earthed" status
"In Service" status
"In Test" status
Swbd meters and remote display
Ammeters (3 separate)
Voltmeter & selector switch
Watt Meter
VAR Meter
KWH
KVARH
Power Factor
Control & aux. power consumption
CB/Contactor close (110V DC)
CB/Contactor trip (110V DC)
CB spring charge motor (110V DC)
Relays, transducers, meters, lamps, etc. (110V DC)
Anti-condensation heaters and lighting (230V AC)
Emergency shutdown Interposing Relay (ESD) trip
HV POWER CABLES/BUS DUCT
Cable/Bus Duct
Cable Type
Voltage grade
Cable Size

Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No

W
W
W
W
VA
Yes/No

kV

Rev. :

10 OF 28

B03

VENDOR'S RESPONSE

2500
3

A
No.

SHEET NO.:

VTA
VTA
VTA
VTA
VTA
Yes, 110 V DC (Note 11)
Bus Duct
N.A.
N.A.
N.A.

This document is the property of OWNER. Any unauthorized attempt to reproduce it, in any form, is strictly prohibited.

Rev.

PROJECT:
SOUTH YARAN OIL
FIELD DEVELOPMENT PROJECT

DOCUMENT TITLE :

DataSheetforMVSwitchgearandMCC

DOCUMENT NO

SYME-ELBASC-ENEL-DSEL-0002-B03

1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40

PARTICULARS OF EQUIPMENT
11KV BUS TIE
General
Rated normal current
No. of Poles

DATA SHEET FOR 11KV SWITCHBOARD


UNITS PURCHASER'S REQUIREMENTS

Protection Requirements (Note 5)


Protection Relay manufacturer and model
Delayed Overcurrent
Instantaneous Overcurrent
Instantaneous Earth Fault
Residual under voltage relay
Check sync relay (3 phase type)
External lockout relay
Control circuit supervision & DC Volts fail relay
DC Control Under voltage relay (each bus)

Yes/No
Yes/No
Yes/No
Yes/No
Yes/No

Control and Indication


Manual/Remote/Auto Selector Switch
Select to Trip Switch (Inc.A/Bus-tie/Inc.B)
"Close" control pushbutton (Green)
"Open" control pushbutton (Red)
"Closed" indication (Red)
"Open" indication (Green)
Fault indication (Amber)
Control circuit supervision & DC Volts fail
DC Control Under voltage (each bus)
"Available" status
"Earthed" status
"In Service" status
"In Test" status

Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No

Swbd
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes

PDCS
N.A.
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
No
No

Sub. Alarm
N.A.
N.A.
N.A.
N.A.
N.A.
N.A.
N.A.
N.A.
N.A.
N.A.
N.A.
N.A.
N.A.

Swbd meters and remote display


Voltmeter & selector switch (each bus)
Frequency meter (each bus)

Yes/No
Yes/No

Swbd
Yes
No

PDCS
4-20mA
No

Sub. Alarm
N.A.
N.A.

Control & aux. power consumption


CB/Contactor close (110V DC)
CB/Contactor trip (110V DC)
CB spring charge motor (110V DC)

41 Relays, transducers, meters, lamps, etc. (110V DC)

VTA
Yes
Yes
Yes
Yes (Bus A & B)
Yes
No
Yes
Yes

Yes/No
Yes/No

W
W
W
W

VTA
VTA
VTA
VTA

VA
0

VTA

42 Anti-condensation heaters and lighting (230V AC)


43
44
45
46
47
48
49
50
51
52
53
54
55
56

Emergency shutdown Interposing Relay (ESD) trip


HV CABLES
Type of cable
Voltage grade
No. of cables and conductor size

Yes/No

kV
mm

0
0

Rev. :

11 OF 28

B03

VENDOR'S RESPONSE

2500
3

A
No.

SHEET NO.:

No
N.A.
N.A.
N.A.

This document is the property of OWNER. Any unauthorized attempt to reproduce it, in any form, is strictly prohibited.

Rev.

PROJECT:
SOUTH YARAN OIL
FIELD DEVELOPMENT PROJECT

DOCUMENT TITLE :

DataSheetforMVSwitchgearandMCC

DOCUMENT NO

SYME-ELBASC-ENEL-DSEL-0002-B03

1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
37

PARTICULARS OF EQUIPMENT
11KV MOTOR (P>1000KW) (Note 20)
General
Circuit Type
Rated normal current
No. of Poles

DATA SHEET FOR 11KV SWITCHBOARD


PURCHASER'S REQUIREMENTS
UNITS

Circuit Breaker
See SYME-ELBASC-ENEL-DISL-0004
3

Motor Protection Requirements (Note 5)


Protection Relay manufacturer and model
Differential Protection (Unit)
HV Fuse
Thermal image Overcurrent
Instantaneous Earth Fault with core balance CT
Locked Rotor
Negative Phase Sequence Overcurrent
Undervoltage with time delay
Too frequent starts
Over temperature - RTD ON Winding
Over temperature - RTD ON Bearing
Integrated Thermal protection (PTC)
External lockout relay
Control circuit supervision & DC Volts fail relay

Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No

Within Multifunction Relay (MFR)


VTA
Yes
No
Yes - MFR (alarm to PDCS)
Yes (alarm to PDCS)
Yes - MFR (alarm to PDCS)
Yes - MFR (alarm to PDCS)
Yes - MFR (alarm to PDCS)
Yes - MFR (alarm to PDCS)
Yes (direct connection to DCS)
Yes (direct connection to DCS)
Yes - MFR (alarm to PDCS)
Yes
Yes

Panel Control and Indication


Local/Remote Selector Switch
"Close" control pushbutton (Green)
"Open" control stay-put type pushbutton (Red)
Permission to run
"Running" indication (Red)
"Stopped" indication (Green)
Motor Heater On Indication
Fault indication (Amber)
Control circuit supervision & DC Volts fail
"Available" status
"Earthed" status
"In Service" status
"In Test" status

Swbd
Yes/No
No
Yes/No Test only
Yes/No Test only
Yes/No
No
Yes/No
Yes
Yes/No
Yes
Yes/No
Yes
Yes/No
Yes
Yes/No
Yes
Yes/No
No
Yes/No
Yes
Yes/No
Yes
Yes/No
Yes

Swbd meters and remote display


Ammeter & selector switch

Yes/No

Swbd
Yes

DCS
N.A.
Yes
Yes
Yes
Yes
Yes
No
Yes
No
Yes
No
No
No

LCS
CT

DCS
No

PDCS
n/a
No
No
No
Yes
Yes
No
Yes
No
No
Yes
No
No

Sub. Alarm
N.A.
N.A.
N.A.
N.A.
N.A.
N.A.
N.A.
N.A.
N.A.
N.A.
N.A.
N.A.
N.A.

PDCS Sub. Alarm


4-20mA
No

38 Control & aux. power consumption


39
40
41
42
43
44

CB/Contactor close (110V DC)


CB/Contactor trip (110V DC)
CB spring charge motor (110V DC)
Relays, transducers, meters, lamps, etc. (110V DC)
Anti-condensation heaters and lighting (230V AC)
Load Shedding Interposing Relay trip

W
W
W
W
VA
Yes/No

0
0
0

VTA
VTA
VTA
VTA
VTA
N.A.

45 Emergency shutdown Interposing Relay (ESD) trip

Yes/No

Yes, 110 V DC (Note 11)

46 Surge Arrestor

Yes/No

Yes

kV
mm
kV

Power Cable
CU/XLPE/Lsh/SWA/PVC ((Note 8)
TBA
8.7/15kV (17.5kV)

47
48
49
50
51
52

HV CABLES
Cable/Bus Duct
Cable Type
Cable Size
Voltage grade

Rev. :

12 OF 28

B03

VENDOR'S RESPONSE

A
No.

LCS
Yes
Yes
Yes
No
No
No
No
No
No
No
No
No
No

SHEET NO.:

This document is the property of OWNER. Any unauthorized attempt to reproduce it, in any form, is strictly prohibited.

Rev.

PROJECT:
SOUTH YARAN OIL
FIELD DEVELOPMENT PROJECT

DOCUMENT TITLE :
DOCUMENT NO

DataSheetforMVSwitchgearandMCC
SYME-ELBASC-ENEL-DSEL-0002-B03

PARTICULARS OF EQUIPMENT
Switchgear Composition 01-SW-21
Bus bar rating
Rated peak withstand current
CB short circuit breaking current
CB short circuit making current
Bus bar cross sectional area
Earth bar cross sectional area

Position

1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57

DATA SHEET FOR 11KV SWITCHBOARD


PURCHASER'S REQUIREMENTS

SHEET NO.:

Rev. :

13 OF 23

B03

VENDOR'S RESPONSE

UNITS

(Single Line Diagram SYME-ELBASC-ENEL-DISL-0004)


2500A, 25kA for 3 seconds
65kA (peak)
25kA rms
65kA (peak)
VTA
VTA

Load Data

Item

kVA
7874
5056
574.71
1258
5056
7874
40000

A
383
246
28
61
246
383
2099

CB
Rating (
A)

Cont.
Rating (
A)

Fuse
(A)

Bus Bar

630
400
400
400
400
630
2500

N.A.
N.A.
N.A.
N.A.
N.A.
N.A.
N.A.

N.A.
VTA
VTA
N.A.
N.A.
N.A.
N.A.

A
A
A
A
A
A
A

Note18
Note18
Note18
Note18
Note18
Note18
Note18

TBA
TBA
TBA
TBA
TBA
TBA
TBA

Ref.
Power Cable
Drawing
Size

1
2
3
4
5
6
7

Spare Motor Feeder


Spare Motor Feeder
Motor feeder (Fire Water)
Motor feeder (P002B)
Motor feeder (P001B)
Motor feeder (C001A)
Incoming A

kW
7008
4500
500
1120
4500
7008
0

8
9

Bus-Tie
Bus-Riser

N.A.
N.A.

N.A.
N.A.

N.A.
N.A.

2500
N/A

N.A.
N.A.

N.A.
N.A.

N.A.
N.A.

Note18
Note18

N.A.
N.A.

10
11
12
13
2
14

Incoming B
Motor feeder (C001B)
Motor feeder (P001A)
Motor feeder (P002A)
Spare Motor Feeder
Spare Motor Feeder

0
7008
1120
4500
4500
7008

40000
7874
1258
5056
5056
7874

2099
383
61
246
246
383

2500
630
400
400
400
630

N.A.
N.A.
N.A.
N.A.
N.A.
N.A.

N.A.
N.A.
N.A.
N.A.
VTA
N.A.

A
A
A
A
A
A

Note18
Note18
Note18
Note18
Note18
Note18

TBA
TBA
TBA
TBA
TBA
TBA

0
0
0

This document is the property of OWNER. Any unauthorized attempt to reproduce it, in any form, is strictly prohibited.

Rev.

PROJECT:
SOUTH YARAN OIL
FIELD DEVELOPMENT PROJECT

DOCUMENT TITLE :

DataSheetforMVSwitchgearandMCC

DOCUMENT NO

SYME-ELBASC-ENEL-DSEL-0002-B03

1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19

DATA SHEET FOR 33KV SWITCHBOARD


ENVIRONMENTAL CONDITIONS
Max absolute temperature
50
C
Min temperature
0
C
Maximum & Minimum Humidity
74 , 41
%
Maximum sun temperature
85
C
Max & Min Wind speed
9.6 , 6.2
m/s
Barometric pressure
736
mmHg
PARTICULARS OF EQUIPMENT
PURCHASER'S REQUIREMENTS
UNITS
MOTOR INSTALLATION CONDITION
Location type
Installation
Area Classification
Installation condition
Min& Max Temperature
GENERAL
Manufacture
Purchaser applicable specification
Standard of manufacture
Model Number

21
22
23
24
25
26
27
28
29

30 Earth busbar withstand current and time


31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56

Onshore
Indoor
Safe,non-hazard
With HVAC
5 / 45

Air insulated, metal clad, withdrawable

Rated voltage
Rated frequency
Number of phases
Rated lightning impulse withstand voltage
Rated short duration power frequency withstand voltage
Rated short time withstand current and time
Rated peak withstand current
Internal arc fault withstand
Duration of internal arc fault test

kV
Hz
kV (peak)
kV (rms)
kA (rms)
kA (peak)
secs
kA (rms)

36
50
3
170 (phase to earth)
70 kV for 1 min
25kA, 3s
65
to IEC 62271
VTA
To be suitable for 400A for 10 secs
(Note 17)

Switchboard Arrangement (Single Line/Back-to-Back/LShape)


Switchboard access type
Busbar system:
Rated normal current (main busbar)
A
Phase segregated busbars
Yes / No
Busbar arrangement (Single / Duplicate)
Busbar identification
Busbar material
Busbar cross sectional area
mm2
Busbar insulation
Yes/No
Future busbar extension at either end
Yes/No
Circuit breaker type
Contactor type
0
Control supply:
Voltage
V
Total power consumption
W
Trip supply:
Voltage
V
Total power consumption
W
Spring charge motor:
Voltage
V
Maximum power consumption
W
Switchboard access type
Degree of protection (IEC 60529):
Enclosure
Thickness of steel enclosure
mm
0
Document/drawings:
Overall Single line diagram for Cluster

SYME-ELBASC-ENEL-DISL-0004

MV and LV Metering and protection Single Line Diagram

SYME-ELBASC-ENEL-DISL-0005

B03

Single line
Rear access
1600
Yes
Single
Colour coded (R-Y-B)
HDHC copper (Note 15)
VTA
Flame retardant/non-hygroscopic
Yes (both)
Vacuum
N.A.
110 V DC +/-10%
VTA
110 V DC +/-10%
VTA
110 V DC +/-10%
VTA
Front access

Rev. :

14 OF 28

B03

VENDOR'S RESPONSE

VTA
SYME-ELBASC-ENEL-SPMC-0001
Refer to Specification
VTA

20 Type

SHEET NO.:

B03

IP42/IP20
2.5

This document is the property of OWNER. Any unauthorized attempt to reproduce it, in any form, is strictly prohibited.

Rev.

PROJECT:
SOUTH YARAN OIL
FIELD DEVELOPMENT PROJECT

DOCUMENT TITLE :

DataSheetforMVSwitchgearandMCC

DOCUMENT NO

SYME-ELBASC-ENEL-DSEL-0002-B03

1
2
3
4
5
6
7
8
9
10
11
12

DATA SHEET FOR 33KV SWITCHBOARD


PURCHASER'S REQUIREMENTS
UNITS
230 V AC
V
Power consumption
VTA
W
Required
Yes (all cubicles)
Yes
Anti-condensation heater 'ON' indication
Yes/No
Light Grey, BS 381C, No. 631
Panel exterior paint colour
Light Grey, BS 381C, No. 631
Panel interior paint colour
0
VTA (Note 7)
Paint specification
VTA
Overall dimensions of the switchboard:
(L x W x H)
mm
VTA
Total weight
kg
VTA
Largest shipping section dimensions
(L X W x H)
mm
VTA
Shipping sections (number and weights)
kg
PARTICULARS OF EQUIPMENT
Voltage
Anti-condensation heaters:

13 Expected assembly heat dissipation at full load

VTA

14 Number of Cubicles
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56

Earthing:
Method of busbar earthing
Rated short circuit current and time
Asymmetrical peak making current capability
Busbar cross sectional area
Earth switch for all circuits including busbars
Earth switch Interlocks
TEST REQUIREMENTS
Type Test
Routine Tests
Site Tests
ACCESSORIES
Lifting Eye (Transportation Section/Cubicle)
Connectors: compression type, space for stress cones
Labels: black letters on white lamacoid
Racking crank assembly
Manual charging handle
Circuit Breaker Removal Truck
Arc chute lifting supports
Arc chute lifting plates
Test jumpers complete with plugs
Key interlock
Grounding truck
Cubicle Lights
Cubicle Mimics
Cubicle Locks and Keys
Floor Frame
Lamp Test Facilities
Voltage Present Lights (Circuit Breaker Dead Side)
Test plug for VT & CT metering and protection

VTA
TBA
TBA
VTA
Yes, Note 4
Yes, Note 4

kA
kA pk
mm2
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No

Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No

Rev. :

15 OF 28

B03

VENDOR'S RESPONSE

VTA

kW

SHEET NO.:

Certificate only required


Yes, see Note 4
Yes, see Note 4

Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
No
Yes
Yes
Yes
Yes
Yes
Yes
Yes

This document is the property of OWNER. Any unauthorized attempt to reproduce it, in any form, is strictly prohibited.

Rev.

PROJECT:
SOUTH YARAN OIL
FIELD DEVELOPMENT PROJECT

DOCUMENT TITLE :

DataSheetforMVSwitchgearandMCC

DOCUMENT NO

SYME-ELBASC-ENEL-DSEL-0002-B03

1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58

PARTICULARS OF EQUIPMENT

DATA SHEET FOR 33KV SWITCHBOARD


PURCHASER'S REQUIREMENTS

Rev. :

16 of 28

B03

VENDOR'S RESPONSE

UNITS

CIRCUIT BREAKER PANEL DATA


See SYME-ELBASC-ENEL-DISL-0004
Number of circuit breakers
No.
Modular, withdrawable
Panel type
VTA
Manufacturer of Circuit Breakers
VTA
Type No.
Vacuum
Type
See SYME-ELBASC-ENEL-DISL-0004
Rated normal current
A
36
Rated voltage
kV
25kA, 3s
Rated short circuit breaking current
kA (rms)
65
Rated short circuit making current
kA (peak)
25
Rated short time withstand current
kA (rms)
Insulation levels:
170 kV across contacts
Rated lightning impulse withstand voltage
kV (peak)
70 kV across contacts for 1 min
Rated short duration power frequency withstand volta kV (rms)
110 V DC
Trip coil:
Voltage
V
VTA
Power
VA
110 V DC
Close coil:
Voltage
V
VTA
Power
VA
2 No for Incom/1 No for Outgoings
No of Trip Coil
1
No of Close Coil
Spring charged Motor/Hand Operated
Operating Mechanism
110V DC
Spring charge motor voltage
V
VTA
Spring charge motor rating
kW
O-0.3sec-CO-3min-CO
O
0.3sec CO 3min CO
Rated operating sequence of circuit breaker
VTA
Circuit breaker closing time
msecs
VTA
Circuit breaker opening time
msecs
VTA
Mechanical endurance
VTA
Electrical endurance
VTA
Minimum lifetime (No. of Operations)
Yes
Anti pumping device
Yes/No
Yes
Mechanical operations counter
Yes/No
Yes
Manual mechanical trip facility
Yes/No
Yes
Closed/open position indication
Yes/No
Yes
Charged/discharged spring indication
Yes/No
Yes (Note.11)
Emergency shutdown interposing relay
Yes/No
Circuit Breaker Status Auxiliary Switches
Minimum 4 contacts
No. of make contacts
Minimum 4 contacts
No. of break contacts
220V DC
Rated voltage
VTA
Rated Current at voltage
Circuit Breaker Position Auxiliary Switches
for Each Position
Minimum 4 contacts
Service Position No. of contacts
Minimum 4 contacts
Withdrawn Position No. of contacts
Minimum 4 contacts
Test Position No. of contacts
220V DC
Rated voltage
VTA
Rated Current at voltage

SHEET NO.:

B03

This document is the property of OWNER. Any unauthorized attempt to reproduce it, in any form, is strictly prohibited.

Rev.

PROJECT:
SOUTH YARAN OIL
FIELD DEVELOPMENT PROJECT

DOCUMENT TITLE :

DataSheetforMVSwitchgearandMCC

DOCUMENT NO

SYME-ELBASC-ENEL-DSEL-0002-B03

1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58

PARTICULARS OF EQUIPMENT
Two stage SF6 gas pressure switch

DATA SHEET FOR 33KV SWITCHBOARD


PURCHASER'S REQUIREMENTS
UNITS
N.A.
Yes/No

Power cable entry


Control cable entry
Gland plate

Overall dimensions of the panel:

(D x W x H)

Communications (Note 9)
Communications with PDCS/DCS/
Substation Alarm Panel/UCPs:

Protocol

DCS control inputs


PDCS control inputs

mm

Yes/No
Yes/No

CABLE EARTH SWITCH


Manufacturer and model
Rated short time withstand current
Rated short circuit making current
Rated duration of short circuit
Actuation Mechanism
Position Indicator

kA (rms)
kA (peak)
sec
Yes/No

0
0

Bottom
Bottom
Yes, Bottom, Removable undrilled
Galvanized steel/ non magnetic (for
VTA

Modbus (Relays status & setting)


Hardwire (Status & Control)
Hardwire (Substation alarm panel)
Hardwire (UCPs)
Yes, motor control only
Yes, Power Distribution CB

VTA
To be suitable for 400A (Note 17)
VTA
30
VTA
Yes

Status Auxiliary Switches


No. of make contacts
No. of break contacts
Rated voltage
Rated Current at voltage

Minimum 4 contacts
Minimum 4 contacts
220V DC
VTA

SURGE ARRESTOR
Manufacturer
Model No.
Type
Max Rated Voltage
Nominal Discharge Current (class of surge arrestor)

VTA
VTA
Metal Oxide Arrestor
36
10(Heavy Duty)

kV
KA

Rev. :

17 of 28

B03

VENDOR'S RESPONSE

0
0

SHEET NO.:

This document is the property of OWNER. Any unauthorized attempt to reproduce it, in any form, is strictly prohibited.

REV

PROJECT:
SOUTH YARAN OIL
FIELD DEVELOPMENT PROJECT

DOCUMENT TITLE :

DataSheetforMVSwitchgearandMCC

DOCUMENT NO

SYME-ELBASC-ENEL-DSEL-0002-B03

PARTICULARS OF EQUIPMENT
1
2 VOLTAGE TRANSFORMERS
3 Manufacturer and model no.
4 Type
No of Secondary Winding
5 Class
6 Ratio
7 Secondary voltage (Phase-Phase)
8 Rated Voltage Factor
9 Fixed/Withdrawable
10
11 CURRENT TRANSFORMERS
12 Manufacturer and model no.
13 Type
14
15 Class
16
17 Ratio
18 Rated Continuous Thermal Current
19 Secondary current
20 Meters & Measurement
21 General
22
Size
23
Accuracy
24
25 VOLTMETERS
26
Manufacturer and model no.
27
Scale
28
29 FREQUENCY METER
30
Manufacturer and model no.
31
Scale
32
33 AMMETER
34
Manufacturer and model no.
35
Scale
36
37 WATT HOUR METER
38
Manufacturer and model no.
39
Scale
37
38 WATT METER
39
Manufacturer and model no.
40
Scale
41
42 VAR METER
43
Manufacturer and model no.
44
Scale
45
46 TRANSDUCERS
47
Manufacturer and model no.
48
output accuracy
49
output
50
51
52
53
54

DATA SHEET FOR 33 KV SWITCHBOARD


PURCHASER'S REQUIREMENTS
UNITS

VTA
See Note 10
Class X for Differential and REF
5P20 for O/C and E/F
0.5F10 for Metering
See SYME-ELBASC-ENEL-DISL-0004
1.2 In
1

96 x 96
Class 1

mm

VTA
0-36kV

VTA
0-65Hz

VTA
1.5In

VTA
To be suitable for circuit rating

0
0
0

Rev. :

18 OF 28

B03

VENDOR'S RESPONSE

VTA
See Note 10 (3 single phase)
2
CL 0.1+3P
33000/3/110/3/110/3
110
1.2 continuous, 1.5 for 30s
Withdrawable

SHEET NO.:

VTA
To be suitable for circuit rating

VTA
To be suitable for circuit rating

VTA
+/-0.5%
4-20mA

This document is the property of OWNER. Any unauthorized attempt to reproduce it, in any form, is strictly prohibited.

Rev.

PROJECT:
SOUTH YARAN OIL
FIELD DEVELOPMENT PROJECT

DOCUMENT TITLE :
DOCUMENT NO

1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57

DataSheetforMVSwitchgearandMCC
SYME-ELBASC-ENEL-DSEL-0002-B03

PARTICULARS OF EQUIPMENT

DATA SHEET FOR 33KV SWITCHBOARD


PURCHASER'S REQUIREMENTS
UNITS

TRANSFORMER ALARM WINDOW (33/0.42KV&33/11KV Transformers)


Number of windows
Lamp Test Pushbutton
Yes/No
Alarm Acknowledge Pushbutton
Yes/No
Alarm Reset Pushbutton
Yes/No

30
Yes
Yes
Yes

Alarms Displayed
Transformer Low Oil Level
Transformer Low Low Oil Level
Transformer High Oil Temperature
Transformer High High Oil Temperature
Transformer High Winding Temperature
Transformer High High Winding Temperature
Transformer Diaphragm Rupture
Buchholz Alarm
Buchholz Trip
Pressure Relief Valve Operation
Sudden Pressure Rise

Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes

Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No

0
0
0

Yes
110V DC
+/-10%
Minimum 2 NO and 2 NC
Minimum 2 NO and 2 NC
VTA
IP51

Yes/No
V
%

Rev. :

19 OF 28

B03

VENDOR'S RESPONSE

PROTECTION RELAYS - GENERAL


Microprocessor based with LCD
Auxiliary voltage
Auxiliary voltage range
Trip Contacts
Alarm Contacts
Contacts rating
Ingress protection

SHEET NO.:

0
0
0

This document is the property of OWNER. Any unauthorized attempt to reproduce it, in any form, is strictly prohibited.

Rev.

PROJECT:
SOUTH YARAN OIL
FIELD DEVELOPMENT PROJECT

DOCUMENT TITLE :

DataSheetforMVSwitchgearandMCC

DOCUMENT NO

SYME-ELBASC-ENEL-DSEL-0002-B03

1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18

PARTICULARS OF EQUIPMENT
33KV INCOMING FEEDER
General
Rated normal current
No. of Poles
Protection Requirements (Note 5)
Protection Relay manufacturer and model
Differential Protection
Restricted Earth Fault
Instantaneous Overcurrent
Delayed Overcurrent
Delayed Earth Fault
Instantaneous Earth Fault
Instantaneous directional Overcurrent
Delayed directional Overcurrent
Undervoltage with time delay
Standby Earth Fault (transformer neutral)

DATA SHEET FOR 33KV SWITCHBOARD


PURCHASER'S REQUIREMENTS
UNITS

1600
3

A
No.

19 Transformer Protection

Yes/No

20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59

Yes/No
Yes/No
Yes/No

Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No

Swbd
Note 13
Yes
Yes
Yes
Yes
Yes
No
No
Yes
Yes
No
Yes
Yes
Yes

PDCS
N.A.
Yes
Yes
Yes
Yes
Yes
Yes
Yes
N.A.
No
Yes
Yes
No
No

Sub. Alarm
N.A.
N.A.
N.A.
N.A.
N.A.
N.A.
N.A.
N.A.
N.A.
N.A.
N.A.
N.A.
N.A.
N.A.

Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No

Swbd
Yes
Yes
Yes
Yes
Yes
Yes
Yes

PDCS
4 - 20mA
4 - 20mA
4 - 20mA
4 - 20mA
4 - 20mA
4 - 20mA
4 - 20mA

Sub. Alarm
N.A.
N.A.
N.A.
N.A.
N.A.
N.A.
N.A.

Check sync relay (3 phase type)


External lockout relay
Control circuit supervision & DC Volts fail relay
Control and Indication
Manual/Remote/Auto Selector Switch
"Close" control pushbutton (Green)
"Open" control pushbutton (Red)
"Closed" indication (Red)
"Open" indication (Green)
Fault indication (Amber)
Transformer only protection Alarm indication
Transformer only protection Trip indication
Transformer Alarm Window
Control circuit supervision & DC Volts fail
"Available" status
"Earthed" status
"In Service" status
"In Test" status
Swbd meters and remote display
Ammeters (3 separate)
Voltmeter & selector switch
Watt Meter
VAR Meter
KWH
KVARH
Power Factor
Control & aux. power consumption
CB/Contactor close (110V DC)
CB/Contactor trip (110V DC)
CB spring charge motor (110V DC)
Relays, transducers, meters, lamps, etc. (110V DC)
Anti-condensation heaters and lighting (230V AC)
Emergency shutdown Interposing Relay (ESD) trip
HV POWER CABLES/BUS DUCT
Cable/Bus Duct
Cable Type
Voltage grade
Cable Size

W
W
W
W
VA
Yes/No

kV

Rev. :

20 OF 28

B03

VENDOR'S RESPONSE

B03

VTA
N.A.
N.A.
Yes (alarm to PDCS)
Yes (alarm to PDCS)
Yes (alarm to PDCS)
Yes (alarm to PDCS)
Yes (alarm to PDCS)
Yes (alarm to PDCS)
Yes (alarm to PDCS)
Yes (alarm to PDCS)
At Transformer (Interface relays in
swbd)
Yes
No
Yes

Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No

SHEET NO.:

VTA
VTA
VTA
VTA
VTA
Yes, 110 V DC (Note 11)
Power Cable
CU/XLPE/Lsh/SWA/PVC (Note 8)
18/30 kV (36kV)
TBA

This document is the property of OWNER. Any unauthorized attempt to reproduce it, in any form, is strictly prohibited.

Rev.

PROJECT:
SOUTH YARAN OIL
FIELD DEVELOPMENT PROJECT

DOCUMENT TITLE :

DataSheetforMVSwitchgearandMCC

DOCUMENT NO

SYME-ELBASC-ENEL-DSEL-0002-B03

1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40

PARTICULARS OF EQUIPMENT
33KV BUS TIE
General
Rated normal current
No. of Poles

DATA SHEET FOR 33KV SWITCHBOARD


UNITS PURCHASER'S REQUIREMENTS

1600
3

A
No.

Yes/No
Yes/No
Yes/No
Yes/No
Yes/No

Control and Indication


Manual/Remote/Auto Selector Switch
Select to Trip Switch (Inc.A/Bus-tie/Inc.B)
"Close" control pushbutton (Green)
"Open" control pushbutton (Red)
"Closed" indication (Red)
"Open" indication (Green)
Fault indication (Amber)
Control circuit supervision & DC Volts fail
DC Control Under voltage (each bus)
"Available" status
"Earthed" status
"In Service" status
"In Test" status

Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No

Swbd
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes

PDCS
N.A.
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
No
No

Sub. Alarm
N.A.
N.A.
N.A.
N.A.
N.A.
N.A.
N.A.
N.A.
N.A.
N.A.
N.A.
N.A.
N.A.

Swbd meters and remote display


Voltmeter & selector switch (each bus)
Frequency meter (each bus)

Yes/No
Yes/No

Swbd
Yes
No

PDCS
4-20mA
No

Sub. Alarm
N.A.
N.A.

Control & aux. power consumption


CB/Contactor close (110V DC)
CB/Contactor trip (110V DC)
CB spring charge motor (110V DC)

41 Relays, transducers, meters, lamps, etc. (110V DC)

VTA
Yes
Yes
Yes
Yes (Bus A & B)
Yes
No
Yes
Yes

Yes/No
Yes/No

W
W
W
W

VTA
VTA
VTA
VTA

VA
0

VTA

42 Anti-condensation heaters and lighting (230V AC)


43
44
45
46
47
48
49
50
51
52
53
54
55
56

Emergency shutdown Interposing Relay (ESD) trip


HV CABLES
Type of cable
Voltage grade
No. of cables and conductor size

Yes/No

kV
mm

0
0

Rev. :

21 OF 28

B03

VENDOR'S RESPONSE

B03

Protection Requirements (Note 5)


Protection Relay manufacturer and model
Delayed Overcurrent
Instantaneous Overcurrent
Instantaneous Earth Fault
Residual under voltage relay
Check sync relay (3 phase type)
External lockout relay
Control circuit supervision & DC Volts fail relay
DC Control Under voltage relay (each bus)

SHEET NO.:

No
N.A.
N.A.
N.A.

This document is the property of OWNER. Any unauthorized attempt to reproduce it, in any form, is strictly prohibited.

Rev.

PROJECT:
SOUTH YARAN OIL
FIELD DEVELOPMENT PROJECT

DOCUMENT TITLE :
DOCUMENT NO

1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18

DataSheetforMVSwitchgearandMCC
SYME-ELBASC-ENEL-DSEL-0002-B03

PARTICULARS OF EQUIPMENT

OUTGOING TRANSFORMER FEEDER(33/0.42, 33/11 KV TR)


General
Rated normal current
A
No. of Poles
No.

Instantaneous Overcurrent
Delayed Overcurrent
Instantaneous Earth fault
Delayed Earth Fault with core balance CT
Restricted earth Fault
Delayed Directional Overcurrent
Sensitive Earth fault (50G)
External lockout relay
Control circuit supervision & DC Volts fail relay

VTA
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No

Control and Indication


Local/Remote Selector Switch
"Close" control pushbutton (Green)
"Open" control pushbutton (Red)
"Closed"
Closed indication (Red)
"Open" indication (Green)
Fault indication (Amber)
Control circuit supervision & DC Volts fail
"Available" status
"Earthed" status
"In Service" status
"In Test" status

Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No

Swbd meters and remote display


Ammeters (3 separate)
Watt meter
VAR meter

Yes/No
Yes/No
Yes/No

Control & aux. power consumption


CB/Contactor close (110V DC)
CB/Contactor trip (110V DC)
CB spring charge motor (110V DC)
Relays, transducers, meters, lamps, etc. (110V DC)

43 Anti-condensation heaters and lighting (230V AC)

0
0
0
0

0
0
0

Yes/No
Yes/No

Lightning Arrestor
HV CABLES
Cable/Bus Duct
Cable Type
Cable Size
Voltage grade

0
0
0

kV
mm
kV

Sub. Alarm
N.A.
N.A.
N.A.

VTA

VA

45
46
47
48
49
50
51
52
53
54
55
56

PDCS
4-20mA
No
No

VTA
VTA
VTA
VTA

W
W
W
W

44 Emergency shutdown Interposing Relay (ESD) trip

Yes (alarm to PDCS)


Yes (alarm to PDCS)
Yes (alarm to PDCS)
Yes (alarm to PDCS)
Yes (alarm to PDCS) Note 19
No
Yes (alarm to PDCS)
Yes
Yes
Yes (alarm to PDCS) Only for
33/11KV Tr)
Swbd
PDCS
Sub. Alarm
Yes
N.A.
N.A.
Yes
Yes
N.A.
Yes
Yes
N.A.
Yes
Yes
N.A.
Yes
Yes
N.A.
Yes
Yes
N.A.
Yes
No
N.A.
No
Yes
N.A.
Yes
Yes
N.A.
Yes
No
N.A.
Yes
No
N.A.
Swbd
Yes
No
No

Rev. :

22 OF 28

B03

VENDOR'S RESPONSE

630 & 1000


3

Protection Requirements (Note 5)


Protection Relay manufacturer and model

19 Differential Protection (Unit)


20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42

DATA SHEET FOR 33KV SWITCHBOARD


PURCHASER'S REQUIREMENTS
UNITS

SHEET NO.:

Yes, 110 V DC (Note 11)


Yes
Power Cable
CU/XLPE/Lsh/SWA/PVC ((Note 8)
TBA
18/30 kV (36kV)

This document is the property of OWNER. Any unauthorized attempt to reproduce it, in any form, is strictly prohibited.

Rev.

PROJECT:
SOUTH YARAN OIL
FIELD DEVELOPMENT PROJECT

DOCUMENT TITLE :

DataSheetforMVSwitchgearandMCC

DOCUMENT NO

SYME-ELBASC-ENEL-DSEL-0002-B03

1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
37

PARTICULARS OF EQUIPMENT
33KV OVER HEAD LINE FEEDER
General
Rated normal current
No. of Poles

DATA SHEET FOR 33KV SWITCHBOARD


PURCHASER'S REQUIREMENTS
UNITS

A
No.

630
3

Protection Requirements (Note 5)


Protection Relay manufacturer and model
Instantaneous Overcurrent
Delayed Overcurrent
Instantaneous Earth fault
Delayed Earth Fault with core balance CT
Instantaneous Directional Overcurrent
Delayed Directional Overcurrent
Sensitive Earth fault (50G)
External lockout relay
Control circuit supervision & DC Volts fail relay

Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No

VTA
Yes (alarm to PDCS)
Yes (alarm to PDCS)
Yes (alarm to PDCS)
Yes (alarm to PDCS)
Yes (alarm to PDCS)
Yes (alarm to PDCS)
Yes (alarm to PDCS)
Yes
Yes

Control and Indication


Local/Remote Selector Switch
"Close" control pushbutton (Green)
"Open" control pushbutton (Red)
"Closed" indication (Red)
"Open" indication (Green)
Fault indication (Amber)
Control circuit supervision & DC Volts fail
"Available" status
"Earthed" status
"In Service" status
"In Test" status

Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No

Swbd meters and remote display


Ammeters (3 separate)
Watt meter
VAR meter

Yes/No
Yes/No
Yes/No

Control & aux. power consumption


CB/Contactor close (110V DC)
CB/Contactor trip (110V DC)
CB spring charge motor (110V DC)
Relays, transducers, meters, lamps, etc. (110V DC)

38 Anti-condensation heaters and lighting (230V AC)

0
0
0
0

0
0
0

40
41
42
43
44
45
46
47
48
49
50
51
52
53

Yes/No

Lightning Arrestor
HV CABLES
Cable/Bus Duct
Cable Type
Cable Size
Voltage grade

0
0
0

kV
mm
kV

Sub. Alarm
N.A.
N.A.
N.A.
N.A.
N.A.
N.A.
N.A.
N.A.
N.A.
N.A.
N.A.

Swbd
Yes
No
No

PDCS
4-20mA
No
No

Sub. Alarm
N.A.
N.A.
N.A.

VTA

VA
Yes/No

PDCS
N.A.
Yes
Yes
Yes
Yes
Yes
No
Yes
Yes
No
No

Rev. :

23 OF 28

B03

VENDOR'S RESPONSE

VTA
VTA
VTA
VTA

W
W
W
W

39 Emergency shutdown Interposing Relay (ESD) trip

Swbd
Yes
Yes
Yes
Yes
Yes
Yes
Yes
No
Yes
Yes
Yes

SHEET NO.:

Yes, 110 V DC (Note 11)


Yes
Power Cable
CU/XLPE/Lsh/SWA/PVC ((Note 8)
TBA
18/30 kV (36kV)

This document is the property of OWNER. Any unauthorized attempt to reproduce it, in any form, is strictly prohibited.

Rev.

PROJECT:
SOUTH YARAN OIL
FIELD DEVELOPMENT PROJECT

DOCUMENT TITLE :

DataSheetforMVSwitchgearandMCC

DOCUMENT NO

SYME-ELBASC-ENEL-DSEL-0002-B03
DATA SHEET FOR 33KV SWITCHBOARD
PURCHASER'S REQUIREMENTS

PARTICULARS OF EQUIPMENT
Switchgear Composition 01-SW-11
Bus bar rating
Rated peak withstand current
CB short circuit breaking current
CB short circuit making current
Bus bar cross sectional area
Earth bar cross sectional area

Position

1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
17
18
19
16
17
18
19
20
21
22
23
24
25
28
26
27
28
28
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50

24 OF 28

B03

(Single Line Diagram SYME-ELBASC-ENEL-DISL-0004)


1600A, 25kA for 3 seconds
65kA (peak)
25kA rms
65kA (peak)
VTA
VTA

kVA

CB
Rating (
A)

913
2500
40000
913
913
2500
2500
40000

16
44
700
16
16
44
44
700

630
630
1000
630
630
630
630
1000

N.A.
N.A.
N.A.
N.A.
N.A.
N.A.
N.A.
N.A.

N.A.
N.A.
N.A.
N.A.
N.A.
N.A.
N.A.
N.A.

A
A
A
A
A
A
A
A

Note.18
Note.18
Note.18
Note.18
Note.18
Note.18
Note.18
Note.18

TBA
TBA
TBA
TBA
TBA
TBA
TBA
TBA

Load Data

Item
kW

Fuse
(A)

Bus Bar

Ref.
Power Cable
Drawing
Size

33/0.42KV Power Transformer (01-TR-1403)


33/0.42KV Power Transformer (01-TR-1401)
33/11KV Power Transformer (01-TR-1201)

Incoming A

B03

46826

819

1600

N.A.

N.A.

Note.18

TBA

10
11

Bus-Tie
Bus-Riser

N.A.
N.A.

N.A.
N.A.

N.A.
N.A.

1250
N/A

N.A.
N.A.

N.A.
N.A.

N.A.
N.A.

Note.18
Note.18

N.A.
N.A.

Incoming B

B03
0
0
0
529.97
1004.7
0
0
1004.7

46826
40000
2500
2500
726
1376
40000
2500
1376

819
700
131
131
13
24
700
131
24

1600
1000
630
630
630
630
1000
630
630

N.A.
N.A.
N.A.
N.A.
N.A.
N.A.
N.A.
N.A.
N.A.

N.A.
N.A.
N.A.
N.A.
N.A.
N.A.
N.A.
N.A.
N.A.

B
A
B
B
B
B
A
B
B

Note.18
Note.18
Note.18
Note.18
Note.18
Note.18
Note.18
Note.18
Note.18

TBA
TBA
TBA
TBA
TBA
TBA
TBA
TBA
TBA

33/11KV Power Transformer (01-TR-1202)


33/0.42KV Power Transformer (01-TR-1402)
33/0.42KV Power Transformer (01-TR-1404)

Over Head Line Feeder


Over Head Line Feeder
Spare 33/11KV Power Transformer
Spare 33/0.42KV Power Transformer
Spare Over Head Line

666.33
0
0
666.33
0
666.33
0
0
0

Cont.
Rating (
A)

1
2
3
4
5
6
7
8

12
13
14
15
16
17
18
19
20

Spare Over Head Line


Spare 33/0.42KV Power Transformer
Spare 33/11KV Power Transformer
Over Head Line Feeder
Over Head Line Feeder

Rev. :

VENDOR'S RESPONSE

UNITS

B03

SHEET NO.:

0
0

This document is the property of OWNER. Any unauthorized attempt to reproduce it, in any form, is strictly prohibited.

Rev.

PROJECT:
SOUTH YARAN OIL
FIELD DEVELOPMENT PROJECT

DOCUMENT TITLE :

DataSheetforMVSwitchgearandMCC

DOCUMENT NO

SYME-ELBASC-ENEL-DSEL-0002-B03

1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52

DATA SHEET FOR WELLHEADS 33KV SWITCHBOARD (XX-SW-11)


ENVIRONMENTAL CONDITIONS
Max absolute temperature
50
C
Min temperature
0
C
Maximum & Minimum Humidity
74 , 41
%
Maximum sun temperature
85
C
Max & Min Wind speed
9.6 , 6.2
m/s
Barometric pressure
736
mmHg
PARTICULARS OF EQUIPMENT
PURCHASER'S REQUIREMENTS
UNITS
MOTOR INSTALLATION CONDITION
Location type
Installation
Area Classification
Installation condition
Min& Max Temperature
GENERAL
Manufacture
Purchaser applicable specification
Standard of manufacture
Model Number
Type
Rated voltage
Rated frequency
Number of phases
Rated lightning impulse withstand voltage
Rated short duration power frequency withstand voltage
Rated short time withstand current and time
Rated peak withstand current
Internal arc fault withstand
Duration of internal arc fault test
Earth busbar withstand current and time
Switchboard Arrangement (Single Line/Back-to-Back/LShape)
Busbar system:
Rated normal current (main busbar)
Phase segregated busbars
Busbar arrangement (Single / Duplicate)
Busbar identification
Busbar material
Busbar cross sectional area
Busbar insulation
Future busbar extension at either end
Circuit breaker type
Contactor type
Control supply:
Voltage
Total power consumption
Trip supply:
Voltage
Total power consumption
Spring charge motor:
Voltage
Maximum power consumption
Degree of protection (IEC 60529):
Enclosure
Thickness of steel enclosure
Document/drawings:

53 Typical Single line diagram for wellhead distribution panel


54

MV and LV Metering and protection Single Line Diagram

kV (peak)
kV (rms)
kA (rms)
kA (peak)
secs
kA (rms)

Single line
A
Yes / No

mm2
Yes/No
Yes/No

V
W
V
W
V
W

mm

25 OF 28

B03

VENDOR'S RESPONSE

VTA
SYME-ELBASC-ENEL-SPMC-0001
Refer to Specification
VTA
Air insulated, metal enclosed, Fixed
36
50
3
170 (phase to earth)
70 kV for 1 min
25kA, 1s
65
to IEC 62271
VTA
Solidly Earthed

kV
Hz

Rev. :

B03

Onshore
Indoor
Safe,non-hazard
Without HVAC
5 / 45

SHEET NO.:

400
Yes
Single
Colour coded (R-Y-B)
HDHC copper (Note 15)
VTA
Flame retardant/non-hygroscopic
Yes (both)
N.A.
N.A.
N.A.
N.A.
N.A.
N.A.
N.A.
N.A.
IP42/IP20
2.5
SYME-ELBASC-ENEL-DISL-0002
N.A.

This document is the property of OWNER. Any unauthorized attempt to reproduce it, in any form, is strictly prohibited.

Rev.

PROJECT:
SOUTH YARAN OIL
FIELD DEVELOPMENT PROJECT

DOCUMENT TITLE :

DataSheetforMVSwitchgearandMCC

DOCUMENT NO

SYME-ELBASC-ENEL-DSEL-0002-B03

1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56

DATA SHEET FOR WELLHEADS 33KV SWITCHBOARD (XX-SW-11)


PARTICULARS OF EQUIPMENT
PURCHASER'S REQUIREMENTS
UNITS
CIRCUIT BREAKER PANEL DATA
Number of Load break Switch & Fuse
No.
Panel type
Manufacturer of Load Break Switch
Type No.
Type
Rated normal current
A
Rated voltage
kV
Rated short circuit breaking current
kA (rms)
Rated short circuit making current
kA (peak)
Rated short time withstand current
kA (rms)
Insulation levels:
Rated lightning impulse withstand voltage
kV (peak)
Rated short duration power frequency withstand volta kV (rms)
Trip coil:
Voltage
V
Power
VA
Close coil:
Voltage
V
Power
VA
No of Trip Coil
No of Close Coil
Operating Mechanism
Spring charge motor voltage
V
Spring charge motor rating
kW
Rated operating sequence of circuit breaker
Load breaker Switch closing time
ms
Circuit breaker opening time
ms
Mechanical endurance
Electrical endurance
Minimum lifetime (No. of Operations)
Anti pumping device
Yes/No
Mechanical operations counter
Yes/No
Manual mechanical trip facility
Yes/No
Closed/open position indication
Yes/No
Charged/discharged spring indication
Yes/No
Emergency shutdown interposing relay
Yes/No
Circuit Breaker Status Auxiliary Switches
No. of make contacts
No. of break contacts
Rated voltage
Rated Current at voltage
Circuit Breaker Position Auxiliary Switches
for Each Position
Service Position No. of contacts
Withdrawn Position No. of contacts
Test Position No. of contacts
Rated voltage
Rated Current at voltage

Rev. :

26 OF 28

B03

B03
VENDOR'S RESPONSE

3 (PER WELLHEAD)
Fixed
VTA
VTA
Air break switch
400
36
25kA, 1s
65
25
170 kV across contacts
70 kV across contacts for 1 min
N.A.
N.A.
N.A.
N.A.
N.A.
1
Hand Operated
N.A.
N.A.
N.A.
VTA
VTA
VTA
VTA
VTA
N.A.
N.A.
N.A.
N.A.
N.A.
N.A.
Minimum 4 contacts
Minimum 4 contacts
220V DC
VTA

SHEET NO.:

Minimum 4 contacts
Minimum 4 contacts
Minimum 4 contacts
220V DC
VTA

This document is the property of OWNER. Any unauthorized attempt to reproduce it, in any form, is strictly prohibited.

Rev.

PROJECT:
SOUTH YARAN OIL
FIELD DEVELOPMENT PROJECT

DOCUMENT TITLE :

DataSheetforMVSwitchgearandMCC

DOCUMENT NO

SYME-ELBASC-ENEL-DSEL-0002-B03

DATA SHEET FOR WELLHEADS 33KV SWITCHBOARD (XX-SW-11)


PARTICULARS OF EQUIPMENT
PURCHASER'S REQUIREMENTS
1
UNITS
N.A.
2 Two stage SF6 gas pressure switch
Yes/No
3
Bottom
4 Power cable entry
Bottom
5 Control cable entry
CU/XLPE/Lsh/SWA/PVC ((Note 8)
Cable Type
18/30(36)
Cable Voltage Grade
Yes, Bottom, Removable undrilled
6 Gland plate
0
Galvanized steel/ non magnetic (for
7
single core cables)
VTA
8 Overall dimensions of the panel:
(D x W x H)
mm
9
10 Communications
N.A.
11 Communications with PDCS/DCS/
Protocol
0
N.A.
12 Substation Alarm Panel/UCPs:
N.A.
13
N.A.
14
N.A.
15
DCS control inputs
Yes/No
N.A.
16
PDCS control inputs
Yes/No
17
0
18 CABLE EARTH SWITCH
0
VTA
19 Manufacturer and model
TBA
20 Rated short time withstand current
kA (rms)
0
VTA
21 Rated short circuit making current
kA (peak)
0
3
22 Rated duration of short circuit
sec
VTA
23 Actuation Mechanism
Yes
24 Position Indicator
Yes/No
25
26 Status Auxiliary Switches
Minimum 4 contacts
27 No. of make contacts
Minimum 4 contacts
28 No. of break contacts
220V DC
29 Rated voltage
VTA
30 Rated Current at voltage
31
32
33
34 SURGE ARRESTOR
VTA
35 Manufacturer
VTA
36 Model No.
Metal Oxide Arrestor
37 Type
36
38 Max Rated Voltage
kV
10(Heavy Duty)
39 Nominal Discharge Current (class of surge arrestor)
KA
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54

SHEET NO.:

Rev. :

27 OF 28

B03

B03
VENDOR'S RESPONSE

This document is the property of OWNER. Any unauthorized attempt to reproduce it, in any form, is strictly prohibited.

REV

PROJECT:
SOUTH YARAN OIL
FIELD DEVELOPMENT PROJECT

DOCUMENT TITLE :

DataSheetforMVSwitchgearandMCC

DOCUMENT NO

SYME-ELBASC-ENEL-DSEL-0002-B03

SHEET NO.:

Rev. :

28 OF 28

B03

DATA SHEET FOR MV SWITCHBOARD


1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58

Rev.
NOTES:
1. Withdrawable circuit breakers shall be interchangeable with others of the same voltage and current rating.
2. Circuit breaker operating mechanisms shall be of the motor/manual spring charge, stored energy, manual/electrical release type.
0
3. Rated short time withstand & breaking currents for incomer & bus-tie circuit breakers shall be not less than ratings for main busbar.
4. Refer to High Voltage Switchboards specification SYME-ELBASC-ENEL-SPMC-000 for additional information.
5. Refer to Metering & Protection SLD SYME-ELBASC-ENEL-DISL-0005
6. VTA = Vendor to advise. TBA = To Be advise by Purchaser
7. Vendor to submit his painting specification for COMPANY's review/approval. Refer to SYME-ELBASC-ENEL-SPMC-0001.
8. Aluminum wire amour will be provided on single core cables
9. Control and Indication to PDCS, DCS, Gen Control Panel and to Substation Alarm Panel is hardwired. Modbus connection from
PDCS to Protection Relays only for status monitoring and setting of protection relays.
10. Voltage and Current Transformers shall be dry type with Epoxy-Resin/Butyl Rubber Moulded Insulation
11. 24V dc ESD relays will be installed in Interface Relay Panels. The volt free contact of the 24V dc ESD relay will be repeated by
a 110V dc ESD relay in the HV switchboards. 110V dc relays shall be selected with consideration of the current of the trip coils.
12. Motor differential protection CTs will be supplied by motor manufacturer.(N.A.)
13. Common Manual/Remote/Auto selector switch provided for switchboard (non-generator) incomers and bus-tie.
14. The following are the motor space heater voltages:
Less than equal to 3kW : 230V 1 ph 50Hz
Greater than 3kW : 400V 3 ph 50Hz
15. Main and cable connection busbars shall be silver plated.
17. Earth fault limited to 400A by Neutral Earthing Resistor at the supply transformers.
18. Refer to drawing number SYME-ELBASC-ENEL-DISL-0004
19. Restricted earth fault protection for 33/11KV transformers feeders is includeded in differential protection of 33KV Panel outgoings and for
33/0.42KV is includeded in LV side.
20. Regarding that there are only one motor between 150KW and 1000KW(Fire Water Pump), for omiting 6KV SWGR, we put it on 11KV bus.

0
0
0

This document is the property of OWNER. Any unauthorized attempt to reproduce it, in any form, is strictly prohibited.