You are on page 1of 39

FOR

CONSTRUCTION

23Dec-'09

For Construction

Y.Kodio

Y.Kodio

H.Asada

11June-'09

Issued For Approval

Y.Kodio

Y.Kodio

H.Asada

REV.

DATE

DESCRIPTION

PREPD

CHKD

APPD

OWNER :

Owner's Engineer :

CONTRACTOR :

Sub Supplier:

PROJECT :

CEBU POWER PLANT


Prepared By Date
Y.Kodio

Title

11June-'09

Checked By Date
Y.Kodio

11June-'09

Approved By Date
H.Asada

11June-'09

The Setting List of Generator Protection Relay

Job No.

Sub-Supplier Doc. No. :

Document No.

Rev

CEBU-P1-20-V-220003

FTA355579 Sub-Supplier Control no. :

E-13-1006

Contents
Page
1

1 Single line diagram


2 Generator specification
2.1
Generator
2.2
Excitor

2
2

3 Transformer specification
3.1
Main step-up transformer

4 System Setting list


4.1
Group A
4.2
Group B
5 Relay Setting list
5.1
Group A
5.2
Group B

Beckwith M-3425A
Beckwith M-3425A

3
4

Beckwith M-3425A
Beckwith M-3425A

5-6
6-7

6 Setting method
6.1
Generator differential protection (87GA,B)
6.2
90% Generator stator earth fault (59NA)
6.3
100% Generator stator earth fault (27TNA)
6.4
Generator overcurrent(51VB)
6.5
Reverse power (32RA,B)
6.6
Generator under excitation (40GA,B)
6.7
Generator overvoltage (59G-1A,B 59G-2A,B)
6.8
Generator under / over frequency (81O-2A,B 81U-2A,B 81U3A,B)
6.9
Generator overexcitation Volts/Hz (24G-1A,B 24G-2A,B)
6.10
Negative sequence current (46G-1A,B 46G-2A,B)
6.11
Indavertent energizing protection (50/27A,B)
6.12
Pole slip protection (78GA,B)
6.13
Backup impedance protection (21GA,B)
6.14
Neutral voltage displacement (64BGB)
6.15
Rotor earth fault (64R-1B,64R-2B)
6.16
Generator breaker failure protection (50BFA,B)
6.17
VT fuse failure (60GA,B)
6.18
Auto synchronizer & check relay

8-10
11
12
13-14
15
16-17'
18
19
20-21
22-23
24
25-26
27-28'
29
30
31
32
33

FEF555578

P. 2
2

Generator specification

2.1

Generator type : GTLR1544/59-2


130,000 kVA,

13.8kV,
179 /
26 /

0.85pf,

Xd

Xd

Xd

Tdo

Td

0.92 sec (at

95

Td

0.03 sec (at

95

Ta

0.24 sec (at

95

Rf

0.27 (at 20 0.376

60Hz,

3,600r/min

203 % (saturated / no saturated)


28 % (saturated / no saturated)

17 /
20 % (saturated / no saturated)
7.7 sec (at
95
)

Mechanical loss
2.2

5,439A,

(at 120)

1,000 kW

Exciter
Excitation Current
No load

1.9 A

130,000 MVA

13 A

MAX

26 A or less

Excitation Voltage
No load

4.7 V at 20

130,000 MVA

45 V at 125

MAX

89 V or less

Transformer specification

3.1

Main step-up transformer


100/130 MVA,

60 Hz

138 kV
%Z =
3.2

10.0

13.8 kV,
% at

#VALUE! A

Ynd5,

#VALUE! A

90 MVA

Unit auxiliary transformer


3 MVA,
11 kV
%Z =

3.3

(ONAN)

50 Hz

(ONAN)

157 A

6.3 kV,

Dyn5,

275 A

7.0 % at

3 MVA

Auxiliary transformer
2 MVA,
6.3 kV
%Z =

/
6.0 % at

50 Hz

(ONAN)

0.4 kV,

Dyn5,

183 A
2,887 A

2 MVA

FEF555578

4
4.1
4.1.1

P. 3
System Setting list
Group A Beckwith M-3425A (With I/O Expaned)
Setup Relay
C.T. Secondary Rating
1A
Nominal Frequency
60 Hz
Delta-Y transform
Delta-AB
Nominal Voltage
110.0 V
0.78 A
Nominal Current
Input Active State
1 2 3 4 5 6 7 8 9 10 11 12 13 14
Open
x
Close x
x x x x x x x x x x x x
V.T.Configuration
Line-Line
Disable
RMS
59/27 Magnitude Select
50DT Split Phase Differential
Phase Rotation
ABC
57.5 1
V.T.Phase Ratio
125.5 1
V.T.Neutral Ratio
1 1
V.T Vx Ratio
1 1
C.T.Neutral Ratio
C.T.Phase Ratio
7000 1
Relay Seal-In Time(Cycles) Out 1 150 Out 9 150 Out 17 150
Out 2 150 Out 10 150 Out 18 150
Out 3 150 Out 11 150 Out 19 150
Out 4 150 Out 12 150 Out 20 150
Out 5 150 Out 13 150 Out 21 150
Out 6 150 Out 14 150 Out 22 150
Out 7 150 Out 15 150 Out 23 150
Out 8 150 Out 16 150
Pulse Relay
1 2 3 4 5 6 7 8
9 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Latched Relay

9 10 11 12 13 14 15 16 17 18 19 20 21 22 23

4.1.2

Communication Information
1
Communication Address
9600
Baud Rate COM1
9600
Baud Rate COM2
BECO2200
Protocol COM2
BECO2200
Protocol COM3
Note For this paragraph , the communication configuration for connection between
protection relay and PC is included.
The setting value is regarded as default.

FEF555578

P. 4
4.2
4.2.1

Group B Beckwith M-3425A (With I/O Expaned)


Setup Relay
Nominal Frequency
60 Hz
C.T. Secondary Rating
1A
Nominal Voltage
110.0 V
Delta-Y transform
Delta-AB
Nominal Current
0.78 A
Input Active State
1 2 3 4 5 6 7 8 9 10 11 12 13 14
Open
x
Close x
x x x x x x x x x x x x
V.T.Configuration
Line-Line
59/27 Magnitude Select
RMS
50DT Split Phase Differential
Disable
Phase Rotation
ABC
V.T.Phase Ratio
125.5 1
V.T.Neutral Ratio
57.5 1
V.T Vx Ratio
1 1
C.T.Phase Ratio
7000 1
C.T.Neutral Ratio
1 1
Relay Seal-In Time(Cycles) Out 1 150 Out 9 150 Out 17 150
Out 2 150 Out 10 150 Out 18 150
Out 3 150 Out 11 150 Out 19 150
Out 4 150 Out 12 150 Out 20 150
Out 5 150 Out 13 150 Out 21 150
Out 6 150 Out 14 150 Out 22 150
Out 7 150 Out 15 150 Out 23 150
Out 8 150 Out 16 150
Pulse Relay
1 2 3 4 5 6 7 8
9 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Latched Relay

9 10 11 12 13 14 15 16 17 18 19 20 21 22 23

4.2.2

Communication Information
Communication Address
1
Baud Rate COM1
9600
Baud Rate COM2
9600
Protocol COM2
BECO2200
Protocol COM3
BECO2200
Note For this paragraph , the communication configuration for connection between
protection relay and PC is included.
The setting value is regarded as default.

FEF555578

P. 5
5 Relay Setting list
5.1 Group A Beckwith M-3425A (With I/O Expaned)
Pickup
Setting range
0.04-0.60A
(0.01A)
#1 Enable Pickup:
Time dilay: 1-8,160Cycles
(1Cycle)
Slope:
1-100%
(1%)
#2 Disable Pickup:
Time dilay:
Slope:
CT Correction 0.5-2.00
(0.01)
59NA
5.0-180V
(0.1V)
#1 Enable Pickup:
(59N)
Time delay: 1-8,160Cycles
(1Cycle)
#2 Disable Pickup:
Time delay:
#3 Disable Pickup:
Time delay:
20Hz Injection mode: Enable / Disable
27TNA
0.10-14.00V
(0.01V)
#1 Enable Pickup:
(27TN)
Volt. Block 5-180V
(1V)
Time delay: 1-8,160Cycles
(1Cycle)
#2 Disable Pickup:
Volt. Block
Time delay:
32RA
-3.000-+3.000PU (0.001PU)
#1 Enable Pickup:
(32)
Time dilay: 1-8,160Cycles
(1Cycle)
32R-1A
Mode:
Overpower / Underpower
Target LED: Enable / Disable
-3.000-+3.000PU (0.001PU)
#2 Enable Pickup:
Time dilay: 1-8,160Cycles
(1Cycle)
32R-2A
Mode:
Overpower / Underpower
Target LED: Enable / Disable
-3.000-+3.000PU (0.001PU)
#3 Disable Pickup:
Time dilay: -3.000-+3.000PU (1Cycle)
Mode:
Overpower / Underpower
Target LED: Enable / Disable
40GA
(0.1)
#1 Enable Diameter: 0.5-500.0
(40)
Offset:
-250.0-+250.0 (0.1)
Time dilay: 1-8,160Cycles
(1Cycle)
Voltage
Disable Time dilay: 1-8,160Cycles
(1Cycle)
control #1
5-180V
(1V)
#2 Disable Diameter:
Offset:
Time dilay:
Voltage
Disable Time dilay:
control #2
Directional Element
0-20
(1)
59GA
5-180V
(1V)
#1 Enable Pickup:
(59)
Time dilay: 1-8,160Cycles
(1Cycle)
59G-1A
Input Volt.: Phase or Positive Sequence
59G-2
5-180V
(1V)
#2 Enable Pickup:
Time dilay: 1-8,160Cycles
(1Cycle)
59G-2A
Input Volt.: Phase or Positive Sequence
#3 Disable Pickup:
Time dilay:
Input Volt.:
81UA,OA
#1 Enable Pickup:
50.00-67.00Hz
(0.01Hz)
(81)
81U3A
Time dilay: 3-65,500Cycles (1Cycle)
#2 Enable Pickup:
50.00-67.00Hz
(0.01Hz)
81U-2A
Time dilay: 3-65,500Cycles (1Cycle)
#3 Enable Pickup:
50.00-67.00Hz
(0.01Hz)
81O-2A
Time dilay: 3-65,500Cycles (1Cycle)
#4 Disable Pickup:
Time dilay:
24GA
Def. Time Enable Pickup:
100-200%
(1%)
24G-1A #1
Time delay: 30-8,160Cycles (1Cycle)
(24)
Def. Time Enable Pickup:
100-200%
(1%)
24G-2A #2
Time delay: 30-8,160Cycles (1Cycle)
Inv. Time Enable Pickup:
100-200%
(1%)
Curve:
#1-4
24G-2A
Time dial: 0.0-9.0
(1)
Reset rate: 1-999Sec
(1Sec)
46GA
Def. Time Enable Pickup:
3-100%
(1%)
(46)
46G-1A
Time dilay: 1-8,160Cycles
(1Cycle)
Inv. Time Enable Pickup:
3-100%
(1%)
Time dilay: 1-95
(1)
46G-2A
Max. time: 600-65,500Cycles (1Cycle)
Reset time: 1-600Sec
(1Sec)
( ) = Beckwith relay device
Function
87GA
(87)

Setting value
0.10A
1Cycle
10%

1.00
13.9V
300Cycles

Disable
3.48V
99V
600Cycles

-0.008PU
180Cycles
Overpower
Disable
-0.008PU
1200Cycles
Overpower
Enable
0.050PU
600Cycles
Underpower
Disable
166.0
-11.4
30Cycles
-

0
121V
300Cycles
Phase Voltage
143V
1Cycles
Phase Voltage

Block input
-

Relay output
Action
Out.1
&
Turbine Trlp

Out.1

&
Turbine Trlp

Out.1

&
Turbine Trlp

In.FL,In2(63QES) Out.5

for 52G TRIP

In.FL

Out.2

&
Turbine Trlp

In.FL

Out.2

&
Turbine Trlp

Only alarm

Out.2

&
Turbine Trlp

56.40Hz
12Cycles
56.90Hz
1200Cycles
61.90Hz
1200Cycles

In.1(52G)

Out.2

In.1(52G)

Out.2

In.1(52G)

Out.2

&
Turbine Trlp
&
Turbine Trlp
&
Turbine Trlp

105%
360Cycles
118%
30Cycles
105%
#1
1
180Sec
6%
120Cycles
8%
7
60000Cycles
1Sec

Out.2

Out.2

&
Turbine Trlp
&
Turbine Trlp

Out.2

Only alarm

Only alarm
&
Turbine Trlp

FEF555578

P. 6
Function
50/27A
(50/27)

78GA
(78)

21GA
(21)

50BFA
(50BF)
60GA
(60FL)

Pickup
Setting range
Enable Pickup:
0.10-3.00A
(0.01A)
Pickup:
5-130V
(1V)
(1Cycle)
Pickup delay1-8,160Cycles
D-out delay: 1-8,160Cycles
(1Cycle)
Enable Diameter: 0.5-500.0
(0.1)
Offset:
-500.0-+500.0 (0.1)
Blinder
0.5-250.0
(0.1)
Angle
0-90
(1)
Counter
0-20
(1)
Reset Time 1-8,160Cycles
(1Cycle)
Time delay 1-8,160Cycles
(1Cycle)
Trip on MHOEnable / Disable
Enable Diameter: 0.5-500.0
(0.1)
Offset:
-500.0-+500.0 (0.1)
Angle
0-90
(1)
Encr. Angle 1-90
(1)
(0.1 )
Encr. Reach 0.1-100.0
Time delay 1-8,160Cycles
(1Cycle)
OC SV
0.02-4.00A
(0.01A)
Phase
Enable Pickup:
0.02-2.00A
(0.01A)
Neutral
Disable Pickup:
0.02-2.00A
(0.01A)
Delay:
1-8,160Cycles
(1Cycle)
Enable Time dilay: 1-8,160Cycles
(1Cycle)
phase fuse loss
detection: Enable / Disable
Enable Time dilay: 1-8,160Cycles
(1Cycle)

50
27

74TCA
(TC)
( ) = Beckwith relay device

Setting value
1.06A
44V
300Cycles
420Cycles
60.2
-42.5
10.2
90
1
120Cycles
6Cycles
Enable
9.4
0.0
85
Disable
Disable
30Cycles
Disable
0.16A

12Cycles
2Cycles
Enable
30Cycles

Block input
In.FL

Relay output
Action
Out.2
&
Turbine Trlp

In.FL

Out.2

&
Turbine Trlp

In.FL

Out.2

&
Turbine Trlp

In.Initiate.3,4

Out.3

Lockout Relay
86BF

Out.4

Alarm &
Interlock

Alarm &
Interlock

5.2 Group B Beckwith M-3425A (With I/O Expaned)

Pickup
Setting range
Relay output
Setting value
Block input
Action
0.04-0.60A
(0.01A)
0.10A
Out.1
#1 Enable Pickup:
&
Time dilay: 1-8,160Cycles
(1Cycle)
1Cycle
Turbine Trlp
Slope:
1-100%
(1%)
10%
#2 Disable Pickup:
Time dilay:
Slope:
CT Correction 0.5-2.00
(0.01)
1.00
51VB
Enable Pickup:
0.10-2.40A
(0.01A)
1.01A
In.FL
Out.2
&
(51V)
Time dilay: 0.5-11.0
(0.1)
2
Turbine Trlp
Curve:
Definite Time / Inverse / Very
very Inverse
Inverse / Extremely Inverse /
IEC Curves
Volt. mode: Volt. Control / Volt. Restraint / Voltage restraint
Disable
32RB
-3.000-+3.000PU (0.001PU)
-0.008PU
In.FL,In2(63QES) Out.6
#1 Enable Pickup:
for 52G TRIP
(32)
Time dilay: 1-8,160Cycles
(1Cycle)
180Cycles
32R-1B
Mode:
Overpower / Underpower
Overpower
Disable
Target LED: Enable / Disable
-3.000-+3.000PU (0.001PU)
-0.008PU
In.FL
Out.2
&
#2 Enable Pickup:
Time dilay: 1-8,160Cycles
(1Cycle)
1200Cycles
Turbine Trlp
32R-2B
Mode:
Overpower / Underpower
Overpower
Enable
Target LED: Enable / Disable
-3.000-+3.000PU (0.001PU)
0.000PU
#3 Disable Pickup:
Time dilay: -3.000-+3.000PU (1Cycle)
Cycles
Mode:
Overpower / Underpower
0
Disable
Target LED: Enable / Disable
40GB
(0.1)
166.0
In.FL
Out.2
#1 Enable Diameter: 0.5-500.0
&
(40)
Offset:
-250.0-+250.0 (0.1)
-11.4
Turbine Trlp
Time dilay: 1-8,160Cycles
(1Cycle)
30Cycles
Voltage
Disable Time dilay:
0
0%
control #1
0
0%
#2 Disable Diameter:
Offset:
Time dilay:
Voltage
Disable Time dilay:
control #2
Directional Element
0-20
(1)
0
59GB
5-180V
(1V)
121V
#1 Enable Pickup:
Only alarm
(59)
Time dilay: 1-8,160Cycles
(1Cycle)
300Cycles
59G-1B
Input Volt.: Phase or Positive Sequence
Phase Voltage
59G-2
5-180V
(1V)
143V
Out.2
#2 Enable Pickup:
&
Time dilay: 1-8,160Cycles
(1Cycle)
1Cycles
Turbine Trlp
59G-2B
Input Volt.: Phase or Positive Sequence
Phase Voltage
#3 Disable Pickup:
Time dilay:
Input Volt.:
( ) = Beckwith relay device

Function
87GB
(87)

FEF555578

P. 7
Function
81UB,OB
(81)

24GB
(24)

Pickup
#1 Enable
81U3B
#2 Enable
81U-2B
#3 Enable
81O-2B
#4 Disable
Def. Time Enable
24G-1B #1
Def. Time Enable
24G-2B #2
Inv. Time Enable
24G-2B

46GB
(46)

Def. Time Enable


46G-1B
Inv. Time Enable
46G-2B

50/27B
(50/27)

50
27

Enable

78GB
(78)

Enable

21GB
(21)

Enable

64BGB
(59X)

#1 Enable
#2 Disable

64RB
(64F)

#1 Enable
64R-1B
#2 Enable
64R-2B

50BFB
(50BF)

Phase
Neutral

60GB
(60FL)

Enable
Disable
Enable

74TCB
Enable
(TC)
( ) = Beckwith relay device

Auto synchronizer
:
:
:
:
Check relay
:
:
:
:

Setting range
Pickup:
50.00-67.00Hz
(0.01Hz)
Time dilay: 3-65,500Cycles (1Cycle)
Pickup:
50.00-67.00Hz
(0.01Hz)
Time dilay: 3-65,500Cycles (1Cycle)
Pickup:
50.00-67.00Hz
(0.01Hz)
Time dilay: 3-65,500Cycles (1Cycle)
Pickup:
Time dilay:
Pickup:
100-200%
(1%)
Time delay: 30-8,160Cycles (1Cycle)
Pickup:
100-200%
(1%)
Time delay: 30-8,160Cycles (1Cycle)
Pickup:
100-200%
(1%)
Curve:
#1-4
Time dial: 0.0-9.0
(1)
Reset rate: 1-999Sec
(1Sec)
Pickup:
3-100%
(1%)
Time dilay: 1-8,160Cycles
(1Cycle)
Pickup:
3-100%
(1%)
Time dilay: 1-95
(1)
Max. time: 600-65,500Cycles (1Cycle)
Reset time: 1-600Sec
(1Sec)
Pickup:
0.10-3.00A
(0.01A)
Pickup:
5-130V
(1V)
(1Cycle)
Pickup delay1-8,160Cycles
D-out delay: 1-8,160Cycles
(1Cycle)
Diameter: 0.5-500.0
(0.1)
Offset:
-500.0-+500.0 (0.1)
Blinder
0.5-250.0
(0.1)
Angle
0-90
(1)
Counter
0-20
(1)
Reset Time 1-8,160Cycles
(1Cycle)
Time delay 1-8,160Cycles
(1Cycle)
Trip on MHOEnable / Disable
Diameter: 0.5-500.0
(0.1)
Offset:
-500.0-+500.0 (0.1)
Angle
0-90
(1)
Encr. Angle 1-90
(1)
(0.1 )
Encr. Reach 0.1-100.0
Time delay 1-8,160Cycles
(1Cycle)
OC SV
0.02-4.00A
(0.01A)
Pickup:
5-180V
(1V)
Time dilay: 1-8,160Cycles
(1Cycle)
Pickup:
Time dilay:
Pickup:
5-100k
(1)
Time dilay: 1-8,160Cycles
(1Cycle)
Pickup:
5-100k
(1)
Time dilay: 1-8,160Cycles
(1Cycle)
Injec. Freq.: 0.10-1.00Hz
(0.01Hz)
Pickup:
0.02-2.00A
(0.01A)
Pickup:
0.02-2.00A
(0.01A)
Delay:
1-8,160Cycles
(1Cycle)
Time dilay: 1-8,160Cycles
(1Cycle)
phase fuse loss
detection: Enable / Disable
Time dilay: 1-8,160Cycles
(1Cycle)

voltage diff.
frequency diff.
pulse width
pulse period

V = 1%
F = 0.1Hz
1sec
2sec

voltage diff.
frequency diff.
phase diff.
pulse width

V = 3%
F = 0.15Hz
= 15
0.5sec

Setting value
56.40Hz
12Cycles
56.90Hz
1200Cycles
61.90Hz
1200Cycles

Block input
In.1(52G)

105%
360Cycles
118%
30Cycles
105%
#1
1
180Sec
6%
120Cycles
8%
7
60000Cycles
1Sec
1.06A
44V
300Cycles
420Cycles
60.2
-42.5
10.2
90
1
120Cycles
6Cycles
Enable
9.4
0.0
85
Disable
Disable
30Cycles
Disable
22V
180Cycles

20k
300Cycle
5k
3600Cycle
0.10Hz
0.16A

12Cycles
2Cycles
Enable
30Cycles

In.1(52G)
In.1(52G)

Relay output
Action
Out.2
&
Turbine Trlp
Out.2
&
Turbine Trlp
Out.2
&
Turbine Trlp

Out.2

Out.2

Only alarm
&
Turbine Trlp
&
Turbine Trlp

Only alarm

Out.2

&
Turbine Trlp

In.FL

Out.2

&
Turbine Trlp

In.FL

Out.2

&
Turbine Trlp

In.FL

Out.2

&
Turbine Trlp

In.1(52G)

Out.4

&
Turbine Trlp

Only alarm

Out.2

&
Turbine Trlp

In.Initiate.3,4

Out.3

Lockout Relay
86BF

Out.5

Alarm &
Interlock

Alarm &
Interlock

FEF555578

P.8

6
6.1

Setting method
Generator differential protection (87GA,87GB)

a) Relay specifications
Pickup
#1,2
Time delay
#1,2
Percent Slope #1,2
Phase CT Correction

:
:
:
:

0.04-0.60A (0.01A)
1-8,160Cycles (1Cycle)
1-100% (1%)
0.5-2.00 (0.01)

b) Input specifications
Generator neutral side CT : 7,000 / 1 A , CL PX
Generator line side CT
: 7,000 / 1 A , CL PX
c) Setting method
Setting to prevent mis-operation at external 3 phase short circuit.
d) Setting calculation
The effective value Ism of the max. current at external 3 phase short circuit is expressed by the
following equation.
Ism = K (PG/3V)(100/Xd) K =
therefore Ism = 1.58

1.58

100
130,000 kVA

50,549 (A)
17
3 13.8 kV

50,549
CT secondary current Ism2 is ; Ism = 7,000 7.2
1
Rct
CT
7,000 / 1 A
CL PX

65 0.333

Rw

(A)

Rr
0.3

Rct: CT winding impedance


Rw : cable impedance (The cable length assumed 100 m.)
Rr: relay impedance
(Temporary)
Rct : 65 at 75 CL PX (Temporary)
Rw : 0.33 : One way
(Cable length 1 km & 6 sq-CV cable impedance is 3.33 /km.)
0.3 VA at 1 A)
0.3 (Burden of protection relay
Rr :

FEF555578

P.9

Therefore, CT secondary burden is


R = 65 + 0.33 + 0.30 = 65.63 ()
CT secondary voltage at short circuit current is
Vct = 7.2 (A) 65.63 () 472.5 (V) < 1200 (V)
Then CT is not saturated at short circuit current.

Phase CT Correction =

Line Side CTR


= 1.00
Neutral Side CTR

e) Setting value
Please refer to attachment (detail setting curve).
#1 Minimum pickup : 0.10 (A)
#1 Time delay D
: 16.7 msec ( 1 Cycle)
10 (%)
#1 Percent slope S :
CT Correction
: 1.00
Note ; In general, the generators minimum shot-circuit current is determined by the
voltage distribution in generator wiring is more th 50 % of the rated current.
In2 1 = 0.78 (A) 1 = 0.39 (A) > 0.04 (A) (minimum pickup)
This setting can secure normal operation of the relay.

FEF555578

(A)
2
Operating Current

1.8

1.6

1.4
slope2 (slope1x4=40%)
1.2

operation zone

slope1 (10%)
External Short-circuit (7.2A)
[when CT's error is max. 10%]

restraint zone
0.8

0.6

0.4

0.2
0.1
1

1.56

Generator differantial protection (87G)

7
Current

(A)
P.10

FE555578

P.11

6.2

90% Generator stator earth fault (59NA)

a) Relay specifications
Pickup
#1-3
: 5.0-180V (0.1V)
Time delay #1-3
: 1-8,160Cycles (1Cycle)
20Hz Injection Mode : Enable or Disable
b) Input specifications
grounding transformer
(generator neutral point)

13,800 / 240 V

c) Setting calculation
Detection of about 10 % complete earth fault
13,800
240
Main circuit voltage
0.10 = 13.86
NG.TR Ratio 0.10 =

3
3
13,800

(V)

Therefore. 13.9 (v) of complete earth fault should be detected.


Timer should be set 300 (cycles) in consideration of reducing damage to the generator
and prevention of misoperation at external earth fault
d) Set value
#1 pickup
: 13.9 (v)
5 sec ( 300 Cycles)
#1 delay
:
20Hz Injection mode : Disable

FEF555578

P.12

6.3

100% Generator stator earth fault (27TNA)

a) Relay specifications
Pickup

#1-2
Voltage Block #1-2
Time delay #1-2

: 0.10-14.00V (0.01V)
: 5-180V
(1V)
: 1-8,160Cycles (1Cycle)

b) Input specifications
grounding transformer
(generator neutral point)

13,800 / 240 V

c) Setting calculation
The 27TN setting depends on the actual third-harmonic neutral voltage level seen during operation of the
generator.The setting should be about 50% of the minimum third-harmonic voltage observed during various
loading condition.
240
0.5
13,800
(Temporary)
3.48 (v) of complete earth fault should be detected.

Third-harmonic voltage

Therefore.

NG.TR Ratio 0.5

400

3.48

(V)

Also, voltage block is 90% of Generator rated voltage.


#### 0.9 = 99 (V)
Therefore,
Time delay is 600 (cycles).
d) Set value
#1 pickup
#1 Voltage Block
#1 delay

: 3.48 (v)
: 99 (v)
: 10 sec ( 600 Cycles)

FEF555578

P. 13

6.4

Generator overcurrent(51VB)

a) Relay specifications
Pickup
Characteristic Curve
Time dial

: 0.10-2.40A (0.01A)
: Definite Time / Inverse / Very Inverse / Extremely Inverse / IEC Curves
Moderately Inverse / Very Inverse / Extremely Inverse / IEEE Curves
: 0.5-11.0 (0.1)
0.05-1.10 (0.01) [ IEC Curves ]
0.85-1.15 (0.01) [ IEEE Curves ]
: 5-180V
(1V)

Voltage Control (VC)


or
Voltage Restraint (VR) : Linear Restraint
b) Input specifications
Generator CT
Generator VT

: 7,000 / 1 A, CL PX
: 13,800 / 110 V, CL 0.2 30VA

c) Setting calculation
130 % of generator rated current.
1
Ir = In 1.3 (CT 2nd / CT 1st) = 5,439 1.3
1.01 (A)
7,000
Note : Generator load capacity is normally expressed.
Setting value : target value is

It = 41 + t ( see illustration)

ANSI-C-50-13

The figure shows a curve of allowable generator overload. The generators permanent short
circuit current Icp is ;
Icp = ( 1 / Xd ) ( Ifceil / Ifo ) P.U.
Therefore, the setting Value for the current following the point of intersection with the generator
load capacity.
d) Setting value
Current setting value is decided accompanying characteristic curve (parameters).
Pickup
Time dial
Characteristics curve
Voltage mode

: 1.01 (A)
2
:
: very Inverse
: Voltage restraint

FEF555578

P. 14

51V CHARACTASTIC CURVE


100

TIME(SEC)

GEN. OVER LOAD


GEN.SHORT CIRCUIT CURRENT
51V CURVE 100%V
51V CURVE 25%V

10

operation zone

0.1

restraint zone

0.01
0

10

12

14

16

18

20

CURRENT(PU)

1 p.u. = 0.78A

K=2

Curve =

FEF555578

P. 15

6.5

Reverse power (32RA,32RB)

a) Relay specifications
Pickup
#1-3
Time delay #1-3
Mode
#1-3

: -3.000-+3.000PU (0.001PU)
: 1-8,160Cycles (1Cycle)
: Overpower or Underpower

b) Input specifications
: 7,000 / 1 A, CL PX
: 13,800 / 110 V, CL 0.2 30VA

Generator CT
Generator VT
c) Setting calculation

Reverce power
Detection of turbine & generator mechanical loss.
Turbine mechanical loss
: 874 kW
Generator mechanical loss : 1,000 kW
1.0PU is equal to the generator MVA rating.
874 + 1000 = 1,874 kW
The value of the loss power is;
1,874 kW
= 0.0170 p.u.
130.0 MVA 0.85 (pf)
Therefore , set value is

0.008 p.u.

Delay is set to 20 sec to prevent miss-operation due to power swing at synchronous of generator.
Low forward power
Setting value : target value is generator initial load.
Generator initial load is 8 % 5 %
d) Setting value
#1 pickup
#1 Delay
#1 Mode
#2 pickup
#2 Delay
#2 Mode

-0.008 (p.u.)
:
3
180 cycles)
:
sec (
: Overpower
-0.008 (p.u.)
:
: 20 sec ( 1200 cycles)
: Overpower

#3 pickup
#3 Delay
#3 Mode

0.050 (p.u.)
:
600 cycles)
: 10 sec (
: Underpower

For GEN. CB trip (interlocked by 63QES)


(IPS Logic Delay 3.00 sec ( 180 cycles)
Reverce power protection

Low forward protection

D)Revised 01-Mar.-2007

FEF555578

P. 16

6.6

Generator under excitation (40GA,40GB)

a) Relay specifications
Circle Diameter #1,2
#1,2
Offset
Time delay
#1,2
Time delay with
Voltage Control #1,2
Voltage Control
(positive sequence)
Directional Element

: 0.5-500.0
(0.1)
: -250.0-+250.0 (0.1)
: 1-8,160Cycles (1Cycle)
: 1-8,160Cycles
: 5-180V
(1V)
: 0-20

(1Cycle)

(1)

b) Input specifications
Generator CT
Generator VT

: 7,000 / 1 A, CL PX
: 13,800 / 110 V, CL 0.2 30VA

c) Setting calculation
X
R
Xd/2

Xd

At the time excitation failure. The final terminal point of reactance as viewed from relay to
generator would lie in the reactance area between the point of one half on the generator direct
axis transient reactance (Xd/2) and the direct axis reactance (Xd). As shown in the below.
Therefore, This relay shall be set for the circle determined by the above mentioned value.
Xd (NO SAT)= 2.03 ,

Xd(NO SAT) = 0.28

PTs Ku = Un1 / Un2 = 13,800 V / 110 V = 125.5


CTs Ki = In1 / In2 = 7,000 A / 1 A = 7,000
Xa = Xd (Ugn2 / Pn) Ki / Ku
= 2.03 ( 13.8 2 / 130.0 ) 7,000 / 125.5 165.93

() 166.0 ()

Xb = Xd / 2 (Ugn2 / Pn) Ki / Ku
= 0.28 / 2 ( 13.8 2 / 130.0 ) 7,000 / 125.5 11.44 () -11.4

()

FEF555578

P. 17

d) Set value
#1 D XA

#1
VC

: 166.0 ()
: -11.4 ()
0.5 sec (
:
: Disable
0
:

30 cycles)

D)Revised 01-Mar.-2007

FEF555578

P. 18

6.7

Generator overvoltage (59G-1A,59G-2A,59G-1B,59G-2B)

a) Relay specifications
Pickup
#1-3
Time delay #1-3
Input Voltage Select

: 5-180V
(1V)
: 1-8,160Cycles (1Cycle)
: Phase or Positive Sequence

b) Input specifications
Generator VT

: 13,800 / 110 V,

CL 0.2 30VA

c) Setting calculation
The withstand voltage of the armature for generator is more than 2 times the rated voltage.
Therefore, the generator should be protected so that over voltage dose not exceed 15 % of allowance.
( 1 - 0.15 ) 2 Un > = X / 100 ( X : relay setting value % )
X 170 %
Fault to set value 110 %
10 - 20% ) at full load fault.
110 V 1.1
121 (V) (110 % Un)
Also, it should be set to 130 % so that the generator dose not operate with voltage rise (about
10 - 20% ) at full load trip.
110 V 1.3

143 (V) (130 % Un)

d) Setting value
#1 Pickup
#1 Time delay
#1 Input Voltage
#2 Pickup
#2 Time delay
#2 Input Voltage

:
:
:
:
:
:

121 (V)
5 sec ( 300 cycles)
Phase Voltage
59G-1Only Alarm
143 (V)
#### sec (
1 cycles)
Phase Voltage
59G-2Generator & Turbine Trip

D)Revised 01-Mar.-2007

FEF555578

P. 19

6.8

Generator under / over frequency (81O-2A,81U-2A,81U3A,81O-2B,81U-2B,81U3B)

a) Relay specifications
Pickup
#1-4
Time delay #1-4

: 50.00-67.00Hz (0.01Hz)
: 3-65,500Cycles (1Cycle)

Rated frequency 60Hz

b) Input specifications
Generator VT

: 13,800 / 110 V,

CL 0.2 30VA

c) Setting calculation
Limit of operating frequency for turbine.
-5 ~ +3% of rated frequency
: continuous operation
therefore,81U3 set value is Fn 1 0.06

% of rated frequency.

= 60 Hz 0.94

therefore,81U-2 set value is Fn 1 0.05

therefore,81Hset value is +

- 0.1 Hz = 56.90 (Hz)

% + 0.1 Hz of rated frequency.

= 60 Hz 1.03

0.03

= 56.40 (Hz)

% - 0.1 Hz of rated frequency.

= 60 Hz 0.95

therefore,81O-2 set value is +


Fn 1 +

+ 0.1 Hz = 61.90 (Hz)

% of rated frequency.

Fn 1 + 0.050 = 60 Hz 1.05

= 63.00 (Hz)

d) Set value
#1 Pickup (81U3)
#1 Time delay
#2 Pickup (81U-2)
#2 Time delay
#3 Pickup (81O-2)
#3 Time delay
#4 Pickup (81O)
#4 Time delay

:
:
:
:
:
:
:
:

56.40
0.2
56.90
20
61.90
20
63.00
20

(Hz)
sec(

12 cycles)

(Hz)
sec( 1200 cycles)

(Hz)
sec( 1200 cycles)

(Hz)
sec( 1,200 cycles)

D)Revised 01-Mar.-2007

FEF555578

P.20

6.9

Generator overexcitation Volts/Hz (24G-1A,24G-2A,24G-1B,24G-2B)

a) Relay specifications
Def. Time
Pickup
#1,2
Time dial #1,2
Inv. Time
Pickup
Characteristic Curve
Time dial #1
Time dial #2-4
Reset rate

: 100-200% (1%)
: 30-8,160Cycles(1Cycle)
:
:
:
:
:

100-200% (1%)
#1-4
1-100 (1)
0.0-9.0 (0.1)
1-999Sec (1Sec)

b) Input specifications
Generator VT

13,800 / 110 V,

CL 0.2 30VA

c) Setting calculation
Limit of Voltage/Hz capability depend on attachment curve.
the curve was selected # 1 .
T = 0.003K / ((M/100)-1)
: K=

d) Set value
Def. Time
#1 Pickup
#1 Time dial
#2 Pickup
#2 Time dial
Inv. Time
Pickup
Curve
Time dial
Reset rate

: 105
6
: 118
0.5

%
sec (
%
sec (

24G-1Only Alarm
360 cycles)
24G-2Generator & Turbine Trip
30

: 105 %
: # 1 (Inverse)
1
:
: 180 sec

cycles)
24G-2Generator & Turbine Trip

a) Revised '07-03-15

FEF555578

PERMISSIBLE OVERVOLTAGE AT LOAD OPERATION V.S. OPERATING TIME (24G)


U : TERMINAL VOLTAGE
f : FREQUENCY

- 25 V/Hz Trip
DT#2 0.5sec

restraint zone
V/Hz Trip =1.18pu
Def.Time #2

Curve#1
K=1
operation zone

(Pick-up) 1.05

V/Hz Alm =1.05pu


Def.Time #1
P.21

FE555578

a) Revised '07-03-15

V/Hz Alm
DT#1 6.0sec

P. 22

6.10

Negative sequence current (46G-1A,46G-2A,46G-1B,46G-2B)

a) Relay specifications
Def. Time
Pickup
Delay

: 3-100% (1%)
: 1-8,160Cycles (1Cycle)

Inv. Time
Pickup
Time delay (K=I22t)
Max. Time
Reset time

:
:
:
:

3-100% (1%)
1-95
(1)
600-65,500Cycles (1Cycle)
1-600Sec (1Sec)

b) Input specifications
Generator CT

: 7,000 / 1 A,

CL PX

c) Setting method
1) Cylindrical machine
Hydrogen indirect cooling and air cooling
(I2)t = 30
Hydrogen direct cooling
( (I2) t = 8
( 801 < 1600 MVA ) (I2) t = 10 - ( 0.00625 (MVA - ## )
2) projected pole machine
I2max = 3 phase short circuit current 3 / 2 3/ 3 ,
(I2) t = 10 at 2 phase complete short circuit.
d) Setting calculation
Percentage of I2max to the rated current is obtained from the following.
I2max = Pn /3 Un 100 / Xd 3 / 2 3 / 3
= 130,000 / ( 3 13.8 ) 100 / 17 3 / 2 3 / 3 15,996 (A)
Percentage is
I2max / In 100 = 15,996 / 5,439 100 =

294.1 (%)

e) Set value
those setting value was decided by attached characteristic curve.
Def. Time
6%
Pickup
:
46G-1Only Alarm
2 sec (
120 cycles)
Delay
:
In. Time
Pickup
Time dial
Max time
Reset time

8%
:
7
:
: 1,000 sec (
: 1 sec

46G-2Generator & Turbine Trip


60,000 cycles)

FEF555578

(46G)

Min time
0.24sec(fixed)
I2max.
(294.1%)

operation zone

K=(I 2) t=7
Alarm
2.0sec

restraint zone

Pickup 8%

Max. time
1000sec
Alarm Pickup
6%

P.23

FEF555578

P. 24

6.11

Inadvertent Energizing protection (50/27A,50/27B)

a) Relay specifications
50(Overcurrent)
27(Undervoltage)
Pickup delay
Drop-out delay

:
:
:
:

0.10-3.00A (0.01A)
5-130V
(1V)
1-8,160Cycles (1Cycle)
1-8,160Cycles (1Cycle)

b) Input specifications
Generator CT
Generator VT

: 7,000 / 1 A, CL PX
: 13,800 / 110 V, CL 0.2 30VA

c) Setting calculation
Power Line 138kV

Main step up transformer


138 / 13.8 kV
100/130 MVA
90 MVA
%Z= 10.00 % at

M-3425A
Generator
130 MVA
13.8 kV
15 %
X2=

Gen.

XT =
=

90 MVA
130 MVA (on generator base)

10.00 % at
14.44 % at

I = Es / ( X2 + XT ) = 100 / ( 15 + 14.44 )
= 3.40 P.U.
5,439 = 18,471 A
= 3.40
Set the overcurrent pickup at 40% of this value.
18,471

0.4

1 / 7,000 = 1.06 A

The undervolatge pickup should be set to 40% of the rated voltage.


110 V 0.4

44

(V)

d) Set value
50(Overcurrent)
27(Undervoltage)
Pickup delay
Drop-out delay

:
:
:
:

1.06 (A)
44 (V)
5 sec ( 300 cycles)
7 sec ( 420 cycles)

FEF555578

P. 25

6.12

Pole slip protection (78GA,78GB)

a) Relay specifications
Circle Diameter
Offset
Blinder Impedance
Impedance Angle
Pole Slip Counter
Pole Slip Reset Time
Time delay

:
:
:
:
:
:
:

0.5-500.0
(0.1)
-500.0-+500.0 (0.1)
0.5-250.0
(0.1)
0-90
(1)
0-20
(1)
1-8,160Cycles (1Cycle)
1-8,160Cycles (1Cycle)

b) Input specifications
Generator CT
Generator VT

: 7,000 / 1 A, CL PX
: 13,800 / 110 V, CL 0.2 30VA

c) Setting calculation
Power Line 138kV
138kV System
2 % at
%Z =

90 MVA (Temporary)

Main step up transformer


138 / 13.8 kV
100/130 MVA
90 MVA
%Z= 10.00 % at

M-3425A

Gen.

Generator
130 MVA
13.8 kV
Xd'= 26 %

i) Convert all the Xd to sec.


Xd = 0.26 P.U.
Xd PRI = ( kV2RATED Xd P.U. ) / MVARATED
= ( 13.8 2 0.26 ) / 130
0.381 ()
=
Xd SEC = Xd PRI ( RCT / RVT )
0.381 ( 7000 / 125.5 )
=
21.25 ()
=

FEF555578

P. 26

ii) Convert all the XT & Xsys to sec.


XT =
0.1 P.U. at
90 MVA
0.144 P.U. at
130 MVA (on generator base)
=
XTPRI = ( kV2RATED XTP.U. ) / MVARATED
= ( 13.8 2 0.144 ) / 130
0.212 ()
=
XTSEC = XTPRI ( RCT / RVT )
0.212 ( 7000 / 125.5 )
=
11.8 ()
=
Xsys =
0.02 P.U. at
90 MVA
0.02889 P.U. at
130 MVA (on generator base)
=
XsysPRI = ( kV2RATED XsysP.U. ) / MVARATED
= ( 13.8 2 0.0289 ) / 130
0.042 ()
=
XsysSEC = XsysPRI ( RCT / RVT )
0.042 ( 7000 / 125.5 )
=
2.4 ()
=
2 XTSEC + 2Xd'SEC
Circle Diameter =
= 60.2 ()
Offset = - 2Xd'SEC
= -42.5 ()
Impedance Angle = 90
Blinder Impedance = (X sysSEC + XTSEC + Xd'SEC)/2*tan(-(/2))
10.2 ()
=

120

d) Set value
D

Blinder Impedance
Impedance Angle
Pole Slip Counter
Pole Slip Reset Time
Time delay
Trip on MHO Exit

60.2 ()
:
: -42.5 ()
10.2 ()
:
90
:
1
:
2 sec ( 120 cycles)
:
0.1 sec (
6 cycles)
:
: Enable

FEF555578

P. 27

6.13

Backup impedance protection (21GA,21GB)

a) Relay specifications
Circle Diameter
Offset
Impedance Angle
Load Encr. Angle
Load Encr. R Reach
Time delay
Overcurrent SV

:
:
:
:
:
:
:

0.5-500.0
(0.1)
-500.0-+500.0 (0.1)
0-90
(1)
1-90
(1)
0.1-100.0 (0.1 )
1-8,160Cycles (1Cycle)
0.02-4.00A (0.01A)

Enable
or Disable
Enable or Disable

b) Input specifications
Generator CT
Generator VT

: 7,000 / 1 A, CL PX
: 13,800 / 110 V, CL 0.2 30VA

c) Setting calculation
PoPower Line 138kV

Main step up transformer


138 /
13.8 kV
100/130 MVA
90 MVA
%Z= 10.00 % at
Protection zone
M-3425A

Gen.

Generator
130 MVA
13.8 kV
Xd'= 26 %

The under impedance function serves as back-up protection for phase faults on the generator
and transformer unit. It is faster and more sensitive than the over current protection.
Its disadvantage is that the zone of protection is shorter than the differential protection, which
serves as the main protection.
Convert all the XT to sec.
XT =
90 MVA
0.1 P.U. at
130
0.144
=
P.U. at
MVA (on generator base)
XTPRI = ( kV2RATED XTP.U. ) / MVARATED
= ( 13.8 2 0.144 ) / 130
0.212 ()
=
XTSEC = XTPRI ( RCT / RVT )
0.212 ( 7000 / 125.5 )
=
11.8 ()
=
Circle Diameter = 0.8 XTSEC
= 9.4 ()

FEF555578

P. 28

0 ()
Offset =
Impedance Angle = 85

d) Set value
D

Impedance Angle
Load Encroachment
Time delay
Overcurrent SV

9.4 ()
:
0.0 ()
:
85
:
: Disable
0.5 sec ( 30 cycles)
:
: Disable

FEF555578

P. 29

6.14

Neutral voltage displacement (64BGB)

a) Relay specifications
Pickup
#1-2
Time delay #1-2

: 5-180V
(1V)
: 1-8,160Cycles (1Cycle)

b) Input specifications
Line side EVT

110
13,800
110
/
/
V
3
3
3

c) Setting calculation
Detection of about
110 0.2

20 % of 1-phase complete earth fault. (3V0)


=

22 V

d) Setting value
#1 Pickup
: 22 (V)
#1 Time delay : 3.0 sec ( 180

cycles)

FEF555578

P. 30

6.15

Rotor earth fault (64R-1B,64R-2B)

a) Relay specifications
Pickup
#1,2
Time delay #1,2

: 5-100k (1)
: 1-8,160Cycles (1Cycle)
Injection frequency (IF) : 0.10-1.00Hz (0.01Hz)
b) Input specifications
This relay has low frequency generator ( 15 V square wave), and shunt used
for measuring the current.
c) Setting calculation
Several (k) of earth fault resistance should be detected at earth fault on P and N
side where the sensitivity is lowest.
Setting calculation circuit diagram as below:

P side earth fault


Rgp

Vf

N side earth fault


Rgn

3 2
5
4
1

M-3921

37
35 64F Ry
36 M-3425A
Vr:15V

d) Setting value
#1 Pick up
#1 Time delay
#2 Pick up
#2 Time delay
Injection frequency

20
:
5
:
5
:
60
:
: 0.10

(k)
sec (
(k)
sec (
(Hz)

64R-1Only Alarm
300 cycles)
64R-2Generator & Turbine Trip
3600 cycles)

Warning : Injection frequency is decided by actual capacitance measurement when


Machine and field excitation should be off.

FEF555578

P. 31

6.16

Generator breaker failure protection (50BFA,50BFB)

a) Relay specifications
Phase current Pickup
Neutral current Pickup
Delay

: 0.02-2.00A (0.01A)
: 0.02-2.00A (0.01A)
: 1-8,160Cycles (1Cycle)

b) Input specifications
Generator CT

: 7,000 / 1 A,

CL PX

C) Setting calculation
20 % of generator rated current.
1
Ir = In 0.2 (CT 2nd / CT 1st) = 5,439 0.2
0.16 (A)

Setting value : target value is

7,000

Delay 4(margin) + 1(accuracy) + 5(breaker time) + 2(aux. RY) = 12 cycles.


d) Set value
Phase current Pickup
Neutral current Pickup
Delay

: 0.16 A Enable
: A Disable
0.2 sec ( 12 cycles)
:

FEF555578

P. 32

6.17

VT fuse failure (60GA,60GB)

a) Relay specifications
Alarm Time Delay
: 1-8,160Cycles (1Cycle)
Tnree Phase VT
Fuse Loss Detection : Enable or Disable
b) Input specifications
Generator VT (relay side) : 13,800 / 110 V,

CL 0.2 30VA

c) Setting method
This function can be detect fault of VT secondary fuse burn out.
d) Setting value
Input initiate
: FL
D
: 2 (cycles)
phase fuse
loss detection : Enable

FEF555578

P. 33

6.18

Auto synchronizer & check relay

a) unit specifications
Auto synchronizer

: ASY-100
input voltage Vn = 110V
setting of voltage difference 1 - 5%Vn
output pulse period 1 - 5 sec (1sec step)
output pulse width 0.1 - 1 sec (0.1sec step)
setting of freqency difference 0.1 - 0.3Hz
setting of advance time of circuit breaker 10 - 300msec (1ms step)
Vn : rated voltage of generator

Check relay

: CSY-96
setting of voltage difference 3 - 5 - 10%Vn
setting of freqency difference 0.05 - 0.3Hz (0.5Hz step)
setting of phase difference 3 - 35 (5step)

b) Setting method
AVR function of TGR : Full stroke of voltage regrator is 30%Vn per 60sec.
Terget value of voltagecontrol is assumed to be 0.5%Vn per pulse.
Then, (60sec / 0.3Vn) * 0.5Vn = 1sec per pulse
GOV function of TGR : Full stroke of frequency regrator is 100%Hz per 600sec.
Terget value of voltagecontrol is assumed to be 0.05Hz per pulse.
Then, (600sec / 60Hz) * 0.05Hz = 0.5sec per pulse
Turget value of pulse off is assumed to be 2sec.

c) Setting value
Auto synchronizer :
:
:
:

voltage diff.
frequency diff.
pulse width
pulse period

V = 1%
F = 0.1Hz
1sec
2sec

Check relay

voltage diff.
frequency diff.
phase diff.
pulse width

V = 3%
F = 0.15Hz
= 15
0.5sec

:
:
:
:

FEF555578