You are on page 1of 4

XLS200 Life Safety System

SPECIFICATION DATA

FEATURES
Modular Design Providing System Flexibility and
Easy Expansion
Ease of Operation via 8-Line (168-Character) Liquid
Crystal Display Featuring Multi-Language Capability
Optional Networking Capability
Supports Signature Series Detectors and Modules
250 Intelligent Devices Per Loop
On-Site Programming
In Compliance with ISO 9001 International
Quality Standard
UL and ULC Listed

GENERAL
The XLS200 is a pre-configured, stand-alone
microprocessor-based life safety system. It is ideally suited
to meet the requirements of medium-sized buildings such as
offices, hospitals, schools, and malls. The panel has a 250point capacity and the capability to network to other panels
making it equally suited to a multi-building or campus-style
complex.
The XLS200 System supports the Signature Series
detection devices, each of which incorporates its own
microprocessor. The detector family is comprised of both
single-element sensing (photoelectric, ionization, and
thermal) as well as various combinations of these sensing
technologies in a single unit to provide unprecedented levels
of protection.

U.S. Registered Trademark


Copyright 1998 Honeywell Inc. All Rights Reserved

The Liquid Crystal Display (LCD) operator interface provides


eight lines of 21 characters (168 total characters) to
annunciate system activity in a text format that is especially
useful in an emergency situation. In addition to date, time,
and alarm history count, the LCD is capable of displaying
both the first highest priority event and the most recent
highest priority event simultaneously. This allows the
operator to view current event information while at the same
time being aware of new alarms coming into the system.
The System Definition Utility (SDU) software is a Microsoft
Windows-based program that allows the programmer to
quickly create project-specific system software at the job
site. The SDU defines the system components;
characterizes all input/output relationships including timeevent sequences; and establishes system responses that
are mandated by local code.

74-2072-1

XLS200 LIFE SAFETY SYSTEM

DESCRIPTION

OPTIONAL DISPLAY
MODULE PANEL

LCD OPERATOR
INTERFACE

The XLS200 Life Safety System is comprised of a


microprocessor-based, pre-configured, modular controller
and an intelligent initiating circuit of up to 250 Signature
Series detection devices designed to meet the stand-alone
needs of medium-sized buildings. Optional networking
capability makes the system suitable for multi-building
complexes as well.

City
Tie
Disable

Power

CPU
Fail

Test

GND
Fault

Disable
Lamp
Test

Reset

COMMON
CONTROL
SWITCHES

The XLS200 panel consists of a Central Processor Unit


(CPU) that provides a mounting base for installing the Liquid
Crystal Display (LCD) operator interface, one Signature Data
Loop Controller module with one intelligent loop board and a
120 Vac Power Supply and monitor. A dead-front plate and
outer door is also provided that will protect the electronics.
This assembly is suitable for mounting in an XLS200B series
backbox which may be ordered separately.

Alarm
Silence

Panel
Silence

Drill
G.A.
Inhibit

General
Evacuation

8-LINE
DISPLAY
AREA

This standard panel configuration is available as well with a


230 Vac Power Supply for international locations. Specify
XLS200-2. See the Ordering section in this sheet for details.

Alarm

1
4
7

The backbox is suitable for flush, semi-flush, or surface wall


mounting.
System Components:
The XLS200 is housed in a wall box that can contain a
variety of system components.

Sup'y

2
5
8
0

The housing can be mounted flush (set back within a wall),


semi-flush (partially set into a wall), or on a wall surface. The
Local Rail Modules provide a base for installation of the LCD
Operator Interface and optional Control Display Modules.
The Inner Door Cover and Outer Door Cover protect the
components and provide an attractive finish to the system.

3
6
9

Trouble

Monitor
Previous
Message
Next
More
details
Command
Menu

M10871

LCD Operator Interface and Display Module Panel.


Panel Capacities:
XLS200 facilitates isolation of field wiring with building
wiring terminations made on local rail module removable
terminal blocks. XLS200 local rail modules include a Loop
Controller, power supply monitor module, and the main CPU
module. System design allows convenient separation of
high-voltage and power-limited wiring internal to the panel.

LCD Operator Interface:


The LCD Operator Interface provides simple-to-understand
lights (LEDs) and switches to help operators execute system
commands with confidence during an emergency situation.
Common control switches and LEDs include (at minimum) a
Reset switch and LED; Alarm Silence switch and LED; Panel
Silence switch and LED; and Drill switch and LED. Eight lines
of 21 characters (168 characters total) display emergency
information in a useful text format. The following figure
illustrates a typical layout of the module.

XLS200 can operate as a complete, stand-alone system or


as a small node in a larger network. Five module spaces are
available. The XLS200 panel can support up to two Loop
Controllers (250 devices per loop). The XLS200 panel has
space for five XLS local rail modules. Two slots are required
for the CPU panel controller module; one slot is dedicated to
the power supply monitor. A Loop Controller is installed in
Slot 4. Slot 5 is available for expansion. The 7A power
supply mounts in the cabinet behind the local rail modules.

The eight-line text display area shows current date, current


time, and number of alarms on the first line. The next lines
show the first highest priority event, the last highest priority
event, and other information as applicable, so that operators
can view alarm data without opening the door of the
XLS200.
The LCD Operator Interface also provides a Command
Menu for maintenance functions such as disabling alarms or
generating reports for use by staff or service personnel.

Signature Series Intelligent Devices:


The Signature Series of devices offers a wide range of
single- and multiple-element technology, addressable
analog detectors and input/output modules, with up to 250
devices per loop.

Display Modules:
Control/display modules provide membrane switches with
positive tactile feedback and colored LEDs giving the
emergency user the simplest of interfaces. Control/Display
module locations are independent of the underlying
connection hardware, the local rail module, to optimize
system layout flexibility.

Networks:
Using an optional RS-485 Network Board, XLS200 can
operate on a multi-priority peer-to-peer token-ring network.
The multi-priority token ring gives XLS200 an exceptional
alarm response time of less than 3 seconds across the
network, virtually independent of the total number of nodes.
Network communication is via RS-485 serial ports. This twowire circuit supports Class A or B operation. The XLS200
network meets NFPA style 7 communications standards in
the Class A configuration.

74-20721

XLS200 LIFE SAFETY SYSTEM


Alarm Annunciation:
XLS200 performs Alarm, Supervisory, Trouble, and Monitor
operations. Annunciation is through the use of LED display
strips complete with custom labels for each LED as to its
function. Where applicable, control of remote smoke control
devices is available at the control center. Switches with LEDs
provide positive feedback to the operator of remote
equipment status. See the LCD Operator Interface and
Display Module Panel figure for an example (previous
figure).

SPECIFICATIONS
Model:
XLS200 Fire Alarm System
Power Input:
The XLS200 can have one 3-PPS/M or 3-PPS/M-230 power
supply, depending on the model.
3-PPS/M
3-PPS/M-230

Support for a Wide Variety of Fire Alarm Equipment:


XLS200 supports a variety of conventional smoke detectors
with a single universal module. It also supports polarized
bells, horns, and strobes as well as hardwired supervisory
and monitor functions with latching or non-latching
operations. Any circuit located anywhere on the network on
any LCD or LED annunciator can be displayed.

120 Vac +10%, -15%, 3.0A, 50-60 Hz.


120 Vac +10%, -15%, 1.5A, 50-60 Hz.

Operating Equipment:
32 Deg. F (0 Deg. C) to 120 Deg. F (49 Deg. C), 93% RH,
non-condensing
Electrical Characteristics:
Operating Voltage; 24 Vdc
Operating Alarm Currant: 7.0 A max.

Battery Options:
Available cabinet room allows for system batteries up to 10
Ah. The power supply supports up to 7A of load with one
24V backup battery. Using a remote battery cabinet, an
XLS200 panel can support batteries up to 55 Ah to give the
system initial system cost savings as well as providing for
continuing cost saving benefits in system maintenance.

WARNING
This product must be installed and operated within its
environmental, mechanical, and electrical
specifications as contained in this document. In case
of service, use only listed/approved replacement
parts ordered directly from the manufacturer. Failure
to do so can result in loss of safety function,
degraded operation, or damage to this product.

TYPICAL WIRING
1 PR

1 PR

CC

LEGEND

HVAC MONITOR

MM

F
S1

ELEVATOR
CAPTURE

SMOKE DETECTOR
WITH RELAY BASE

CT

S1

SMOKE DETECTOR
WITH ISOLATOR BASE

NETWORK CONTROL

CT

SMOKE DETECTOR
WITH STANDARD BASE

2ND FLOOR

JUNCTION BOX

WATERFLOW
SWITCH
SPRINKLER
SUPERVISORY
SWITCH

COMBINATION
SPEAKER/STROBE

CC

CR
HVAC
CONTROL

MM

FIREFIGHTER'S
TELEPHONE

1 PR

1 PR

S1

SR
FIRE
F
DAMPER

WATER LEVER
MONITOR

MM

HVAC
MONITOR

1ST FLOOR
1 PR.

1 PR.

CC

SIGNAL MODULE

CR

CONTROL RELAY
MODULE

CT

INPUT MODULE

UM

UNIVERSAL INPUT/
OUTPUT MODULE

MM

MONITOR MODULE

2 TWISTED PAIR

CC
S1
XLS200
PANEL
PRIMARY
POWER
SOURCE

MANUAL PULL
STATION

SR

CR

2 TWISTED PAIR

HVAC CONTROL

CR

S
S

S
S

S
S

END-OF-LINE
RESISTOR
SIZE CONDUCTORS PER
APPLICATION. REFER TO
INSTALLATION MANUAL
FOR ADDITIONAL DETAILS.

CPU WITH DISPLAY, POWER SUPPLY


AND BOOSTER, DUAL LOOP MODULE,
AND BATTERIES

GROUND FLOOR

M10872

74-20721

XLS200 LIFE SAFETY SYSTEM

ORDERING
Standard Panel Configurations
Catalog Number
XSL200

XLS200R
XLS200B
XLS200B-R
XLS200-2

XLS200R-2

Description
Control panel including CPU; LCD Operator Interface with LCD; Loop Controller module with one
intelligent loop board; 120 Vac power supply and monitor; 5 LRM backbox; and white Honeywell door.
This item does NOT include a backbox. Order Backbox separately.
Same as XLS200, except with red door.
Backbox, white.
Backbox, red.
Control panel including CPU; LCD Operator Interface with LCD; Loop Controller module with one
intelligent loop board; 230 Vac power supply and monitor; 5 LRM backbox; white Honeywell door; and
Backbox.
Same as XLS200-2, except with red door.

Optional Equipment
Catalog Number
3-RS485
3-RS232
3-DSDC
3-SDC

Description
Network Communication Board (plugs into back of 3-CPU)
RS-232 Communication Board (plugs into back of 3-CPU)
Dual SIGA Data Controller (LRM)
SIGA Data Board (plugs into back of 3-DSDC)

3-LDSM
3-24R
3-24Y
3-24G
3-12SR
3-12SY
3-12SG
3-12RY
3-12/2Y
3-12/RY
3-12/S1GY
3-12/S1RY
12V10A

LED Display Support Module


24 Red LED Display Module
24 Yellow LED Display Module
24 Green LED Display Module
12 switches with 12 Red LED Display/Control Module
12 switches with 12 Yellow LED Display/Control Module
12 switches with 12 Green LED Display/Control Module
12 Red LED and 12 Yellow LED Display Module
12 groups of two Yellow LED Display Module
12 groups of one Red and one Yellow LED Display Module
12 switches with one Green and one Yellow LED per switch Display/Control Module
12 switches with one Red and one Yellow LED per switch Display/Control Module
10 Ah 12V Battery (two required)

Remote Battery Cabinet


3-BC
Space for two 20 to 55 Ah batteries. Provision for remote temperature monitoring.
Accessories
3-TAMP

Tamper switch for XLS200 enclosure. Mounts to side of cabinet.

Home and Building Control


Honeywell Inc.
Honeywell Plaza
P.O. Box 524
Minneapolis MN 55408-0524

Home and Building Control


Honeywell Limited-Honeywell Limite
155 Gordon Baker Road
North York, Ontario
M2H 3N7

Honeywell Latin American Region


480 Sawgrass Corporate Parkway
Suite 200
Sunrise FL 33325

Honeywell Europe S.A.


3 Avenue du Bourget
1140 Brussels
Belgium

74-20721 L.A. 4-98

Printed in U.S.A. on recycled


paper containing at least 10%
post-consumer paper 4
fibers.

Honeywell Asia Pacific Inc.


Room 3213-3225
Sun Hung Kai Centre
No. 30 Harbour Road
Wanchai
Hong Kong

www.honeywell.com