You are on page 1of 6

Eletromar Ltda

Av. Comandante Guaranys, 525


Jacarepagu Rio de Janeiro - RJ
22775-610 Brasil
Tel.: 21 3504-9500

Type :
MCCB h3 x160
Reference : HHAxxxB , HNAxxxU

Summary :
1

General Characteristics

-2-

Dimensional characteristics

-2-

2.1 Dimensions (mm)

-2-

Installation

-3-

Options

-5-

4.1 Accessories :

-5-

Standards

Appendix 1 : Tripping Curve

-5-6-

Eletromar Ltda
Av. Comandante Guaranys, 525
Jacarepagu Rio de Janeiro - RJ
22775-610 Brasil
Tel.: 21 3504-9500

General Characteristics

Protection against overloads and short circuits, switch control and isolation.
In commercial and industrial electrical distribution systems.
Ples :

3P, 4P

Current rating :

16 to 160 A

Voltage rating :

220 to 240V / 380 to 415V

Breaking capacity (Icu)


60947-2 :
Reference

Voltage (V)

HHA

220/240
380/415

Reference

Voltage (V)

HNA

220/240
380/415

Electrical endurance :

10 000 cycles

Mechanical endurance :

20 000 operations

Dimensional characteristics

2.1

Dimensions (mm)

Breaking
capacity (kA)
35kA
25kA
Breaking
capacity (kA)
85kA
40kA

Eletromar Ltda
Av. Comandante Guaranys, 525
Jacarepagu Rio de Janeiro - RJ
22775-610 Brasil
Tel.: 21 3504-9500

Installation

Mounting :

Din rail EN 50.022-35 (only with accessory HYA033H)


Mounting plate

Connection capacity :

Rigid conductor : 95 mm
Flexible conductor : 70 mm

Eletromar Ltda
Av. Comandante Guaranys, 525
Jacarepagu Rio de Janeiro - RJ
22775-610 Brasil
Tel.: 21 3504-9500

Tightening torque :

6,0 Nm

Type of connection :

Screw

Working position :
horizontally or flat

Product performances not affected if installed vertically,

Auxiliaries :

Yes

General Technical Characteristics:


Air humidity protection
Altitude
Category of use
Correction factor of rating current for 2 devices placed side-by-side
Correction factor of rating current for 3 devices placed side-by-side
Correction factor of rating current for 4 and 5 devices placed side-by-side
Correction factor of rating current for 6 devices placed side-by-side
Dissipated energy in cable
European directive RoHs
European directive WEEE
Frequency
Group number of the product for the heating calculation
Magnetic adjustment notch
Magnetic trip delay time
Mode de rglage magntique suivant IN ou IrTh
Operating temperature
Power loss per pole
Protection index IP
Range of the magnetic adjustment with 40C
Rated impulse withstand voltage
Rated insulation voltage
Storage temperature
Thermal protection settings range
Thermal protection trip time
Total power loss under IN
Tripmode
time of response when opening

for all climates


2000 m
A
1
1
1
1
116.9 W
voluntary compliance
not concerned
50/60 Hz
1
10
0 ms
IN
-25 to 70 C
14.1 W
4X
1000; 1250; 1600 A
8000 V
690 V
-35 to 70 C
0.63; 0.8; 1
0 ms
42.2 W
TM
10 ms

Eletromar Ltda
Av. Comandante Guaranys, 525
Jacarepagu Rio de Janeiro - RJ
22775-610 Brasil
Tel.: 21 3504-9500

Options

4.1

Accessories :
HXA002H
HXA003H
HXA004H
HXA005H
HXA013H
HXA014H
HXA015H
HXA021H
HXA024H
HXA030H
HXA031H
HXA039H
HYA005H
HYA014H
HYA023H
HYA027H
HYA033H

Shunt trip x160-x250 48V DC


Shunt trip x160-x250 100-120VAC
Shunt trip x160-x250 200-240VAC
Shunt trip x160-x250 380-450VAC
Undervoltage release x160-x250 100-120VAC
Undervoltage release x160-x250 200-240V AC
Undervoltage release x160-x250 380-450V AC
Auxiliary contact x160-x250 1NO+1NC 250V AC
Alarm contact x160-x250 1NO+1NC 250V AC
Direct rotary handle x160
Extended rotary handle x160
Padlock x160-x250
Collar terminal x160 Al 3P
Spreader x160 3P collar
Terminal cover x160 3P spreader
Terminal cover for collar terminal x160 3P
Rail Din adaptor x160 3P/4P

Standards
Complies with :

IEC 60947-2

Eletromar Ltda
Av. Comandante Guaranys, 525
Jacarepagu Rio de Janeiro - RJ
22775-610 Brasil
Tel.: 21 3504-9500

Appendix 1 : Tripping Curve