You are on page 1of 6

Table 1 (All Classes in 1 Table)

This revision combines the Delta and the Wye-Connected Tables from Revision 8 into the new Revision 9
Max
System
Voltage in
kV

Applied Test
From C57.12.00
Nominal
Table 7 in kV
System
Voltage
(V, in kV) Delta Gr Y Imp Y

Induced Test, in kV
Dist. &
Class I
Class 2, >72.5 kV
2V
3

Basic Insulation Level, in kV

One Enhanced
Hour
7200 cy Min.

Alternates

Neutral BIL, in kV
GrY

Impedance

Distribution and Class I Power Transformers, =69 kV Nominal System Voltage


1.5

1.2

10

10

10

1.4

30

45

30

30

3.5

2.5

15

15

15

2.9

45

60

45

45

6.9

19

19

19

5.8

60

75

60

60

8.7

75

75

75

75

11

26

26

26

10

75

95

17.2

15

34

26

26

17.3

95

110

26

25

50

26

34

28.9

125

150

75

95

38

34.5

70

26

50

39.8

150

200

75

125

48.3

46

95

34

70

53.1

200

250

95

150

72.5

69

140

34

95

79.7

250

350

95

200

110

250

125

400

Class II Power Transformers, > 72.5 kV Nominal System Voltage


120

115

173

34*

95*

N/A

105

120

350

450

550

145

138

207

34*

95*

N/A

125

145

450

550

650

166

161

242

34*

95*

N/A

145

170

550

650

750

244

230

345

34*

95*

N/A

210

240

750

825

900

362

345

518

34*

95*

N/A

315

360

1050

1175

550

500

N/A

34*

95*

N/A

475

550

1425

1550

765

735

N/A

34*

95*

N/A

750

850

1950

2050

800

765

N/A

34*

95*

N/A

795

885

1950

2050

Notes:
1.*
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.

14.

1675

850

110

250

110

350*

110

350*

110*

350*

110*

350*

110*

350*

110*

350*

Insulation level to conform with service requirements but never less than the level shown.
The BIL serves both as a test level for the full wave lightning impulse tests and as the primary identity of a set of
coordinated insulation levels.
Front-of-wave Impulse levels must be specified prior to design of the transformer.
Front-of-wave tests are not recommended on low voltage or tertiary windings that are not exposed to lightning.
The Insulation levels for Distribution, Class 1 and Class 2 transformers shall be selected from this table for both the highvoltage and low-voltage windings.
All test levels are line to ground.
The applied test levels are not applicable to wye-connected windings unless they have been specified to be suitable for
application on ungrounded systems.
Minimum Phase-to-Phase Induced test levels for 3 phase Distribution Transformers shall be not less than 2.0 times nominal
system voltage, and never less than the applied test level from line to ground.
Minimum Phase-to-Phase Induced test levels for 3 phase Class I Power Transformers shall be not less than 1.65 times
nominal system voltage, and never less than the applied test level from line to ground.
When specified, Y-Y connected transformers using a common solidly grounded neutral may use a neutral bushing sellected
in accordance with the requirements of the low voltage winding.
Voltages greater than Maximum System Voltage shall use the next higher voltage class test levels.
Neutral BIL shall be a minimum of 2.5 times neutral applied potential test level.
Single phase distribution and power transformers and regulating transformers for voltage ratings between terminals of 8.7
kV and below are designed for both Y and Delta connection so that a single line of transformers serves for the higher than
needed for their voltage rating.
For Series windings in transformers, such as regulating transformers, the test values to ground shall be determined by the
BIL of the series windings rather than the rated voltage between terminals.

This example shows Table 1 split into two tables by transformer class:
Table 1a (Distribution and Class 1)
This revision combines the Delta and the Wye-Connected Tables from Revision 8 into the new Revision 9
Max
System
Voltage
(kV)

Nominal
System
Voltage
(kV)

Applied Test
From C57.12.00
Table 7 (kV)
Delta

Gr Y

Induced Test in kV
2V

Imp Y

Basic Insulation Level


(kV)
Min.

Alternates

Neutral BIL (kV)


GrY

Impedance

Distribution Transformers
1.5

1.2

10

10

10

1.4

30

30

30

3.5

2.5

15

15

15

2.9

45

45

45

6.9

19

19

19

5.8

60

60

60

11

8.7

26

26

26

10

75

75

75

75

75

75

95

17.2

15

34

26

26

17.3

95

26

25

50

26

34

28.9

125

150

38

34.5

70

26

50

39.8

125

150

75

125

48.3

46

95

34

70

53.1

200

250

200

95

150

72.5

69

140

34

95

79.7

250

350

95

200

Class I Power Transformers, =69 kV Nominal System Voltage


1.5

1.2

10

10

10

1.4

30

45

30

30

3.5

2.5

15

15

15

2.9

45

60

45

45

6.9

19

19

19

5.8

60

75

60

60

11

8.7

26

26

26

10

75

95

75

75

17.2

15

34

26

26

17.3

95

110

75

75

26

25

50

26

34

28.9

150

75

95

38

34.5

70

26

50

39.8

200

75

125

48.3

46

95

34

70

53.1

200

250

95

150

72.5

69

140

34

95

79.7

250

350

95

200

Notes:
1.* Insulation level to conform with service requirements but never less than the level shown.
15. The BIL serves both as a test level for the full wave lightning impulse tests and as the primary identity of a set of coordinated
insulation levels.
16. Front-of-wave Impulse levels must be specified prior to design of the transformer.
17. Front-of-wave tests are not recommended on low voltage or tertiary windings that are not exposed to lightning.
18. The Insulation levels for Distribution, Class 1 and Class 2 transformers shall be selected from this table for both the highvoltage and low-voltage windings.
19. All test levels are line to ground.
20. The applied test levels are not applicable to wye-connected windings unless they have been specified to be suitable for
application on ungrounded systems.
21. Minimum Phase-to-Phase Induced test levels for 3 phase Distribution Transformers shall be not less than 2.0 times nominal
system voltage, and never less than the applied test level from line to ground.
22. Minimum Phase-to-Phase Induced test levels for 3 phase Class I Power Transformers shall be not less than 1.65 times nominal
system voltage, and never less than the applied test level from line to ground.
23. When specified, Y-Y connected transformers using a common solidly grounded neutral may use a neutral bushing sellected in
accordance with the requirements of the low voltage winding.
24. Voltages greater than Maximum System Voltage shall use the next higher voltage class test levels.
25. Neutral BIL shall be a minimum of 2.5 times neutral applied potential test level.
26. Single phase distribution and power transformers and regulating transformers for voltage ratings between terminals of 8.7 kV
and below are designed for both Y and Delta connection so that a single line of transformers serves for the higher than needed
for their voltage rating.
27. For Series windings in transformers, such as regulating transformers, the test values to ground shall be determined by the BIL
of the series windings rather than the rated voltage between terminals.

Table 1b (Class II Transformers)


This revision combines the Delta and the Wye-Connected Tables from Revision 8 into the new Revision 9
Applied Test
From C57.12.00
Table 7 (kV)

Max Nominal
System System
Voltage Voltage
(kV)
(kV)
Delta Gr Y Imp Y

Induced Test (kV)


Class 1
=69 kV

Class 2, >72.5 kV
One Hour

Enhanced
7200 cy.

Basic Insulation Level (kV)


Min

Alternates

Class II Power Transformers, > 72.5 kV Nominal System Voltage


95*
N/A
105
120
350
450 550

Neutral BIL (kV)


GrY

Impedance

110

250

110
110
110
110*

250
350*
350*
350*

120

115

173

34*

145
166
244
362

138
161
230
345

207
242
345
518

34*
34*
34*
34*

95*
95*
95*
95*

N/A
N/A
N/A
N/A

125
145
210
315

145
170
240
360

450
550
750
1050

550
650
825
1175

550
765

500
735

N/A
N/A

34*
34*

95*
95*

N/A
N/A

475
750

550
850

1425
1950

1550 1675
2050

110*
110*

350*
350*

800

765

N/A

34*

95*

N/A

795

885

1950

2050

110*

350*

650
750
900

850

Notes:
1.* Insulation level to conform with service requirements but never less than the level shown.
2. The BIL serves both as a test level for the full wave lightning impulse tests and as the primary identity of a set of coordinated
insulation levels.
3. Front-of-wave Impulse levels must be specified prior to design of the transformer.
4. Front-of-wave tests are not recommended on low voltage or tertiary windings that are not exposed to lightning.
5. The Insulation levels for Class 1 and Class 2 transformers shall be selected from this table for both the high-voltage and lowvoltage windings.
6. All test levels are line to ground.
7. The applied test levels are not applicable to wye-connected windings unless they have been specified to be suitable for
application on ungrounded systems.
8. Minimum Phase-to-Phase Induced test levels for 3 phase Class I Power Transformers shall be not less than 1.65 times nominal
system voltage, and never less than the applied test level from line to ground.
9. When specified, Y-Y connected transformers using a common solidly grounded neutral may use a neutral bushing sellected in
accordance with the requirements of the low voltage winding.
10. Voltages greater than Maximum System Voltage shall use the next higher voltage class test levels.
11. Neutral BIL shall be a minimum of 2.5 times neutral applied potential test level.
12. For Series windings in transformers, such as regulating transformers, the test values to ground shall be determined by the BIL
of the series windings rather than the rated voltage between terminals.

Table 2
High Frequency Test Tables
BIL
kV Crest
1.2 X 50
-sec

Chopped Wave
kV Crest
1.1*BIL

Minimum
Time to
Flashover, -sec

Front Of Wave

kV Crest

Minimum
Time to
Flashover, -sec

Switching Impulse
kV Crest
0.83*BIL

30

33

1.0

45
60
75
95
110
125

50
66
83
105
120
138

1.5
1.5
1.5
1.8
2.0
2.3

165
195
220

0.5
0.5
0.5

150
200

165
220

3.0
3.0

260
345

0.5
0.5

250

275

3.0

435

0.5

350
450
550
650

385
495
605
715

3.0
3.0
3.0
3.0

580
0.58
N/A unless specified
N/A unless specified
N/A unless specified

750
825
900
1050
1175

825
900
990
1155
1290

3.0
3.0
3.0
3.0
3.0

N/A unless specified


N/A unless specified
N/A unless specified
N/A unless specified
N/A unless specified

620
685
745
870
975

1300

1430

3.0

N/A unless specified

1080

1425
1550
1675
1800
1950

1570
1705
1845
1980
2145

3.0
3.0
3.0
3.0
3.0

N/A unless specified


N/A unless specified
N/A unless specified
N/A unless specified
N/A unless specified

1180
1290
1390
1550
1620

2050

2255

3.0

N/A unless specified

1700

280
375
460
540

Notes:
1. Front-of-Wave tests must be specified prior to the design of the transformer.
2. Front-of-wave tests are not recommended on low voltage or tertiary windings that are not exposed to lightning.
3. The Insulation levels for Distribution, Class 1 and Class 2 transformers shall be selected from this table for both the highvoltage and low-voltage windings.
4. Phase to ground specified Switching impulse levels are not always possible for low voltage windings.

Table 1b
This revision combines the Delta and the Wye-Connected Tables from Revision 8 into the new Revision 9
Max
System
Voltage (V)

Nominal
System
Voltage (V)

Applied Test
From C57.12.00
Table 7
Delta

Gr Y

Induced Test
2V

Imp Y

Basic Insulation Level


Min.

Alternates

Neutral BIL
GrY

Impedance

Distribution Transformers
1.5

1.2

10

10

10

1.4

30

30

30

3.5

2.5

15

15

15

2.9

45

45

45

6.9

19

19

19

5.8

60

60

60

11

8.7

26

26

26

10

75

75

75

75

75

75

95

17.2

15

34

26

26

17.3

95

26

25

50

26

34

28.9

125

150

38

34.5

70

26

50

39.8

125

150

75

125

48.3

46

95

34

70

53.1

200

250

200

95

150

72.5

69

140

34

95

79.7

250

350

95

200

Class I Power Transformers, < or = 69 kV Nominal System Voltage


1.5

1.2

10

10

10

1.4

30

45

30

30

3.5

2.5

15

15

15

2.9

45

60

45

45

6.9

19

19

19

5.8

60

75

60

60

11

8.7

26

26

26

10

75

95

75

75

17.2

15

34

26

26

17.3

95

110

75

75

26

25

50

26

34

28.9

150

75

95

38

34.5

70

26

50

39.8

200

75

125

48.3

46

95

34

70

53.1

200

250

95

150

72.5

69

140

34

95

79.7

250

350

95

200

Notes:
1.
Insulation level to conform with service requirements but never less than the level shown.
13. The BIL serves both as a test level for the full wave lightning impulse tests and as the primary identity of a set of coordinated
insulation levels.
14. Front-of-wave Impulse levels must be specified prior to design of the transformer.
15. Front-of-wave tests are not recommended on low voltage or tertiary windings that are not exposed to lightning.
16. The Insulation levels for Distribution, Class 1 and Class 2 transformers shall be selected from this table for both the highvoltage and low-voltage windings.
17. All test levels are line to ground.
18. The applied test levels are not applicable to wye-connected windings unless they have been specified to be suitable for
application on ungrounded systems.
19. Minimum Phase-to-Phase Induced test levels for 3 phase Distribution Transformers shall be not less than 2.0 times nominal
system voltage, and never less than the applied test level from line to ground.
20. Minimum Phase-to-Phase Induced test levels for 3 phase Class I Power Transformers shall be not less than 1.65 times nominal
system voltage, and never less than the applied test level from line to ground.
21. When specified, Y-Y connected transformers using a common solidly grounded neutral may use a neutral bushing sellected in
accordance with the requirements of the low voltage winding.
22. Voltages greater than Maximum System Voltage shall use the next higher voltage class test levels.
23. Neutral BIL shall be a minimum of 2.5 times neutral applied potential test level.
24. Single phase distribution and power transformers and regulating transformers for voltage ratings between terminals of 8.7 kV
and below are designed for both Y and Delta connection so that a single line of transformers serves for the higher than needed
for their voltage rating.
25. For Series windings in transformers, such as regulating transformers, the test values to ground shall be determined by the BIL
of the series windings rather than the rated voltage between terminals.

Table 2
High Frequency Test Tables
BIL

Chopped Wave

kV Crest
1.2 X 50
-sec

Minimum
Time to
Flashover, -sec

kV Crest

Minimum
Time to
Flashover, -sec

Switching Impulse
kV Crest
0.83*BIL

30
45

33
50

1.0
1.5

60
75
95
110
125
150
200

66
83
105
120
138
165
220

1.5
1.5
1.8
2.0
2.3
3.0
3.0

165
195
220
260
345

0.5
0.5
0.5
0.5
0.5

250

275

3.0

435

0.5

350

385

3.0

580

0.58

450
550
650
750
825
900

495
605
715
825
900
990

3.0
3.0
3.0
3.0
3.0
3.0

N/A unless specified


N/A unless specified
N/A unless specified
N/A unless specified
N/A unless specified
N/A unless specified

375
460
540
620
685
745

1050
1175

1155
1290

3.0
3.0

N/A unless specified


N/A unless specified

870
975

1300

1430

3.0

N/A unless specified

1080

1425
1550
1675
1950
1950

1570
1705
1845
2145
2145

3.0
3.0
3.0
3.0
3.0

N/A unless specified


N/A unless specified
N/A unless specified
N/A unless specified
N/A unless specified

1180
1290
1390
1550
1620

2050

2255

3.0

N/A unless specified

1700

Notes:
1.
5.
6.
7.

kV Crest
1.1*BIL

Front Of Wave

280

Front-of-Wave tests must be specified prior to the design of the transformer.


Front-of-wave tests are not recommended on low voltage or tertiary windings that are not exposed to lightning.
The Insulation levels for Distribution, Class 1 and Class 2 transformers shall be selected from this table for both the highvoltage and low-voltage windings.
Phase to ground specified Switching impulse levels are not always possible for low voltage windings.

You might also like