You are on page 1of 4

Genesis Range

Auto Reclose Relay Single Shot

Cut-Out Details

Ordering Information

Description

1. Auxiliary supply rating in DC

The relay is suitable for single and three phase auto reclosing

2. Optically isolated (status) inputs rating in DC

The relay consists of five modules viz. Front fascia, power supply,
two relay & status module and microcontroller module. All the
modules are housed in a compact 3N Non draw-out case

3. Timer range Standard or Optional

Qualification

Microcontroller does the sequence control and timing function.


Different operating functions and time setting are selected by
the DIP-Switches on the relay front fascia.

ISO 9001-2000

Case

There is a watch-dog timer in the relay which continuously


monitors the program, put off POWER ON indication and closes
annunciation contact in case the watch dog timer elapses.

3N-Non draw out with 27 terminals


PART
01

CASE
SIZE
3N

CUT OUT
A
B
104
140

BEZEL
C
D
128
170

Inputs
Two optically isolated inputs are provided to take the single
phase or three phase protection operated contact inputs to
initiate the auto reclose relay.

Note:
1. All dimensions are in mm
2. All dimensions are measured equidistant from centre line
3. Maximum depth of equipment inside panel : 200mm

MART113

When the external blocking input is initiated, the reclose function


is blocked and it energise external blocking LED, Lockout LED
and Lockout relay.
As the relay is suitable for single shot auto reclose, at the time
of first reclosing if the fault persists or further fault develops
within the reclaim time it will energises the lockout relay and its
LED indication.
Before the reclaim time elapses if the second fault occurs the
relay goes to lockout

Applications
Transmission lines
Distribution circuits
Single phase and three phase breaker reclosing schemes

In addition, one permit input is given which when energized


from check synchronizing or dead line charging function
interlocked with the breaker status permits the auto reclose
The reclose function is get blocked when the external blocking
input is initiated.

Reclose Timer

The policy of Easun Reyrolle is one of continuous improvement and development. The company therefore reserves the right to supply equipment, which may
differ slightly from that described and illustrated in this publication.

#98, Sipcot Industrial Complex,


Hosur 635 126, India.
Tel: +91 4344 401600/01/02
Fax: +91 4344 276397

SWITCHGEAR WORKS

Ernavur,
Chennai-600 057, India.
Tel: +91 44 25733715/358
Fax: +91 44 25733468
Email: switchgear@easunreyrolle.net

FACT/MART 113/12-05/REV 0

HOSUR WORKS

BANGALORE WORKS

#17/3 Arakere,
Bannerghatta Road,
Bangalore-560 076, India.
Tel: +91 80 26581023 / 3268
Fax: +91 80 26580642
Email: blrworks@easunreyrolle.net
AUTOMATION DIVISION

Ashirwad, #25, 29th Main,


4th B Cross, BTM Layout 2nd Stage,
Bangalore-560 076, India.
Tel: +91 80 26685496/51311405
Fax: +91 80 26685446
Email: smabp@easunreyrolle.net

EXPORTS DIVISION

#17/3 Arakere,
Bannerghatta Road,
Bangalore-560 076, India.
Tel: +91 80 26581023 / 3268
Fax: +91 80 26580642
Email: exports@easunreyrolle.net

Delhi

Kolkata

Bangalore

Chennai

Secunderabad

Tel: +91 22 22022270/22855415


Fax: +91 22 22825703
Email: mumbai@easunreyrolle.net
Tel: +91 80 26685496/51311405
Fax: +91 22 26685446
Email: blroffice@easunreyrolle.net
Bhopal

Telefax: +91 755 2684221


Email: bhopal@easunreyrolle.net

Tel: +91 11 25747321/25747322


Fax: +91 11 25747320
Email: delhi@easunreyrolle.net
Tel: +91 44 24346425/24347608
Fax: +91 44 24346435
Email: chennai@easunreyrolle.net

There is the common reclaim timer. It operates in series with


the reclose timers. The over all reclaim time delay from relay
energisation to relay reset is therefore reclaim timer setting
plus reclose time.

When the reclose selector switch is in OFF mode any one of the
protection operated contact input initiation condition it will
energise the lockout relay and its LED indication and it blocks
the reclose function.

Tel: +91 33 22848320


Fax: +91 33 22848326
Email: kolkata@easunreyrolle.net
Telefax: +91 40 27817847
Email: hyderabad@easunreyrolle.net

Reclaim Timer

Lockout Function

Sales Offices
Mumbai

The relay having two reclose timers one for single phase reclose
another for three phase reclose. The both timers are selected
automatically depending upon the reclose selection

Corporate Office
Easun Reyrolle Limited. 98 Sipcot Industrial Complex
Hosur 635 126 India. Tel: +91 4344 401600/01/02
Fax: +91 4344 276397
www.easunreyrolle.com

Auto Reclose Relay Single Shot MART 113

Features
Protection
Automatic tripped breaker reclosure
Suitable for single phase and three phase reclosing
Micro-controller based relay

Wiring Diagram

Switch setting = 20 to 27

Output Contacts

Single Phase Reclose Time T2 secs.

The relay has 8 output contacts and 4 status inputs


Reclose pulse relay
1 N/O
Reclose pulse alarm relay
1 N/O
Lockout relay
2 N/O
Power on relay
1 N/C
Three phase trip mode relay
2 N/C
Auto reclose initiation relay
1 C/O

Range:0.1 to 25.5secs in steps of 0.1 sec


Three Phase Reclose Time T1 secs.
Range: 0.1 to 25.5 secs in steps of 0.1 sec
Reclaim Time T0 secs.

Control

Range: 1 to 255 secs in steps of 1 sec

The relay has 8 output contacts and 4 status inputs


Reclose pulse relay
1 N/O
Reclose pulse alarm relay
1 N/O
Lockout relay
2 N/O
Power on relay
1 N/C
Three phase trip mode relay
2 N/C
Auto reclose initiation relay
1 C/O

Reclose pulse time 1 Second fixed.

Monitoring

Seven LED on the relay front fascia Indicate

Optional Setting

Green

For any Reclose and Reclaim

Yellow

Single phase reclose is initiated

Timer Setting Range in Seconds

Yellow

Three phase reclose is initiated

1. 0.25 to 63.75 in steps of 0.25

Green

Single phase reclose is completed

2. 0.5 to 127.5 in steps of 0.5

Green

Three phase reclose is completed

3. 1 to 255 in steps of 1

Red

External Blocking signal is IN

Self-monitoring facility

4. 2 to 510 in steps of 2 and

Red

Relay is in Lockout mode

User Interface

5. 4 to 1020 in steps of 4

Dip switches for parameter setting


LED indications
Sealable front cover to prevent unauthorised access

Contact Rating
Reclose Pulse Contacts

Other Features

Make a Carry for 200msec

Both DC and AC auxiliary supply available


Compact design
Non-drawout case

Technical Information
Rating
Power Supply Input Rating in DC (AUX.)
18 to 135V DC or 43 to 280 V DC

Optically Isolated Input Rating in DC (STATUS)


24V, 30V, 50V, 110V or 220V
Above 110V use external resistor

Reclose Selection

Reclose in OFF
Reclose in single phase
Reclose in three phase
Reclose in single and three phase

Time Settings
Standard Setting
Time setting (In seconds)=s x Multiples of setting
s= Sum of switch settings

Power supply is ON

Environmental
Temperature

IEC 60068-2-1/2

30A AC or DC with L/R >5msec

Operating Range
Humidity
Vibration (Sinusoidal)
Shock and Bump
Insulation

-100C to +550C
IEC 60068-2-3
IEC 60255-21-1 Class I
IEC 60255-21-2 Class I
IEC 60255-5

All Other Contacts

2.0KV rms for 1 min between all terminals and earth

Carry continuously 5A AC or DC

Make and carry 3A continuously / 250V DC Break


24V DC Resistive at 0.75Amps
48V DC Resistive at 0.5Amps
125V DC Resistive at 0.3Amps
250V DC Resistive at 0.2Amps

Burden
Power Supply Burden (AUX.)
Quotient Drain
Maximum Energised Drain

2W
8W

Optically Isolated Input Burden (STATUS)


Maximum Energised Drain

3W

Input, Outputs and Indications


Four Optically Isolated (STATUS) Inputs

Initiating signal input (From single phase protective relay


contact)
External blocking signal input
Initiating signal input (From three phase protective relay
contact)
Reclose permit input (From breaker contacts etc.)

2.0KV rms for 1 min between independent circuits


1.0KV rms for 1 min across normally open contacts

Transient Over Voltage

IEC 60255-5

5 KV, 1.2/50 S, 0.5J between all terminals and earth or between


any two terminals without damage or flashover.
High Frequency Disturbance IEC 60255-22-1 Class III
2.0 KV Common (Longitudinal) mode
1.0 KV Series (Transverse) mode
Fast Transient

IEC 60255-22-4 Class IV

4 KV, 5/50 ns, 2.5 kHz repetitive

Features
Protection
Automatic tripped breaker reclosure
Suitable for single phase and three phase reclosing
Micro-controller based relay

Wiring Diagram

Switch setting = 20 to 27

Output Contacts

Single Phase Reclose Time T2 secs.

The relay has 8 output contacts and 4 status inputs


Reclose pulse relay
1 N/O
Reclose pulse alarm relay
1 N/O
Lockout relay
2 N/O
Power on relay
1 N/C
Three phase trip mode relay
2 N/C
Auto reclose initiation relay
1 C/O

Range:0.1 to 25.5secs in steps of 0.1 sec


Three Phase Reclose Time T1 secs.
Range: 0.1 to 25.5 secs in steps of 0.1 sec
Reclaim Time T0 secs.

Control

Range: 1 to 255 secs in steps of 1 sec

The relay has 8 output contacts and 4 status inputs


Reclose pulse relay
1 N/O
Reclose pulse alarm relay
1 N/O
Lockout relay
2 N/O
Power on relay
1 N/C
Three phase trip mode relay
2 N/C
Auto reclose initiation relay
1 C/O

Reclose pulse time 1 Second fixed.

Monitoring

Seven LED on the relay front fascia Indicate

Optional Setting

Green

For any Reclose and Reclaim

Yellow

Single phase reclose is initiated

Timer Setting Range in Seconds

Yellow

Three phase reclose is initiated

1. 0.25 to 63.75 in steps of 0.25

Green

Single phase reclose is completed

2. 0.5 to 127.5 in steps of 0.5

Green

Three phase reclose is completed

3. 1 to 255 in steps of 1

Red

External Blocking signal is IN

Self-monitoring facility

4. 2 to 510 in steps of 2 and

Red

Relay is in Lockout mode

User Interface

5. 4 to 1020 in steps of 4

Dip switches for parameter setting


LED indications
Sealable front cover to prevent unauthorised access

Contact Rating
Reclose Pulse Contacts

Other Features

Make a Carry for 200msec

Both DC and AC auxiliary supply available


Compact design
Non-drawout case

Technical Information
Rating
Power Supply Input Rating in DC (AUX.)
18 to 135V DC or 43 to 280 V DC

Optically Isolated Input Rating in DC (STATUS)


24V, 30V, 50V, 110V or 220V
Above 110V use external resistor

Reclose Selection

Reclose in OFF
Reclose in single phase
Reclose in three phase
Reclose in single and three phase

Time Settings
Standard Setting
Time setting (In seconds)=s x Multiples of setting
s= Sum of switch settings

Power supply is ON

Environmental
Temperature

IEC 60068-2-1/2

30A AC or DC with L/R >5msec

Operating Range
Humidity
Vibration (Sinusoidal)
Shock and Bump
Insulation

-100C to +550C
IEC 60068-2-3
IEC 60255-21-1 Class I
IEC 60255-21-2 Class I
IEC 60255-5

All Other Contacts

2.0KV rms for 1 min between all terminals and earth

Carry continuously 5A AC or DC

Make and carry 3A continuously / 250V DC Break


24V DC Resistive at 0.75Amps
48V DC Resistive at 0.5Amps
125V DC Resistive at 0.3Amps
250V DC Resistive at 0.2Amps

Burden
Power Supply Burden (AUX.)
Quotient Drain
Maximum Energised Drain

2W
8W

Optically Isolated Input Burden (STATUS)


Maximum Energised Drain

3W

Input, Outputs and Indications


Four Optically Isolated (STATUS) Inputs

Initiating signal input (From single phase protective relay


contact)
External blocking signal input
Initiating signal input (From three phase protective relay
contact)
Reclose permit input (From breaker contacts etc.)

2.0KV rms for 1 min between independent circuits


1.0KV rms for 1 min across normally open contacts

Transient Over Voltage

IEC 60255-5

5 KV, 1.2/50 S, 0.5J between all terminals and earth or between


any two terminals without damage or flashover.
High Frequency Disturbance IEC 60255-22-1 Class III
2.0 KV Common (Longitudinal) mode
1.0 KV Series (Transverse) mode
Fast Transient

IEC 60255-22-4 Class IV

4 KV, 5/50 ns, 2.5 kHz repetitive

Genesis Range
Auto Reclose Relay Single Shot

Cut-Out Details

Ordering Information

Description

1. Auxiliary supply rating in DC

The relay is suitable for single and three phase auto reclosing

2. Optically isolated (status) inputs rating in DC

The relay consists of five modules viz. Front fascia, power supply,
two relay & status module and microcontroller module. All the
modules are housed in a compact 3N Non draw-out case

3. Timer range Standard or Optional

Qualification

Microcontroller does the sequence control and timing function.


Different operating functions and time setting are selected by
the DIP-Switches on the relay front fascia.

ISO 9001-2000

Case

There is a watch-dog timer in the relay which continuously


monitors the program, put off POWER ON indication and closes
annunciation contact in case the watch dog timer elapses.

3N-Non draw out with 27 terminals


PART
01

CASE
SIZE
3N

CUT OUT
A
B
104
140

BEZEL
C
D
128
170

Inputs
Two optically isolated inputs are provided to take the single
phase or three phase protection operated contact inputs to
initiate the auto reclose relay.

Note:
1. All dimensions are in mm
2. All dimensions are measured equidistant from centre line
3. Maximum depth of equipment inside panel : 200mm

MART113

When the external blocking input is initiated, the reclose function


is blocked and it energise external blocking LED, Lockout LED
and Lockout relay.
As the relay is suitable for single shot auto reclose, at the time
of first reclosing if the fault persists or further fault develops
within the reclaim time it will energises the lockout relay and its
LED indication.
Before the reclaim time elapses if the second fault occurs the
relay goes to lockout

Applications
Transmission lines
Distribution circuits
Single phase and three phase breaker reclosing schemes

In addition, one permit input is given which when energized


from check synchronizing or dead line charging function
interlocked with the breaker status permits the auto reclose
The reclose function is get blocked when the external blocking
input is initiated.

Reclose Timer

The policy of Easun Reyrolle is one of continuous improvement and development. The company therefore reserves the right to supply equipment, which may
differ slightly from that described and illustrated in this publication.

#98, Sipcot Industrial Complex,


Hosur 635 126, India.
Tel: +91 4344 401600/01/02
Fax: +91 4344 276397

SWITCHGEAR WORKS

Ernavur,
Chennai-600 057, India.
Tel: +91 44 25733715/358
Fax: +91 44 25733468
Email: switchgear@easunreyrolle.net

FACT/MART 113/12-05/REV 0

HOSUR WORKS

BANGALORE WORKS

#17/3 Arakere,
Bannerghatta Road,
Bangalore-560 076, India.
Tel: +91 80 26581023 / 3268
Fax: +91 80 26580642
Email: blrworks@easunreyrolle.net
AUTOMATION DIVISION

Ashirwad, #25, 29th Main,


4th B Cross, BTM Layout 2nd Stage,
Bangalore-560 076, India.
Tel: +91 80 26685496/51311405
Fax: +91 80 26685446
Email: smabp@easunreyrolle.net

EXPORTS DIVISION

#17/3 Arakere,
Bannerghatta Road,
Bangalore-560 076, India.
Tel: +91 80 26581023 / 3268
Fax: +91 80 26580642
Email: exports@easunreyrolle.net

Delhi

Kolkata

Bangalore

Chennai

Secunderabad

Tel: +91 22 22022270/22855415


Fax: +91 22 22825703
Email: mumbai@easunreyrolle.net
Tel: +91 80 26685496/51311405
Fax: +91 22 26685446
Email: blroffice@easunreyrolle.net
Bhopal

Telefax: +91 755 2684221


Email: bhopal@easunreyrolle.net

Tel: +91 11 25747321/25747322


Fax: +91 11 25747320
Email: delhi@easunreyrolle.net
Tel: +91 44 24346425/24347608
Fax: +91 44 24346435
Email: chennai@easunreyrolle.net

There is the common reclaim timer. It operates in series with


the reclose timers. The over all reclaim time delay from relay
energisation to relay reset is therefore reclaim timer setting
plus reclose time.

When the reclose selector switch is in OFF mode any one of the
protection operated contact input initiation condition it will
energise the lockout relay and its LED indication and it blocks
the reclose function.

Tel: +91 33 22848320


Fax: +91 33 22848326
Email: kolkata@easunreyrolle.net
Telefax: +91 40 27817847
Email: hyderabad@easunreyrolle.net

Reclaim Timer

Lockout Function

Sales Offices
Mumbai

The relay having two reclose timers one for single phase reclose
another for three phase reclose. The both timers are selected
automatically depending upon the reclose selection

Corporate Office
Easun Reyrolle Limited. 98 Sipcot Industrial Complex
Hosur 635 126 India. Tel: +91 4344 401600/01/02
Fax: +91 4344 276397
www.easunreyrolle.com

Auto Reclose Relay Single Shot MART 113