You are on page 1of 19

Chap6-78-97

21/06/02

9:20

Page 78

C u r r e n t a n d Vo l t a g e
Transformers
Introduction

6.1

Electromagnetic voltage
transformers

6.2

Capacitor voltage
transformers

6.3

Current transformers

6.4

Novel instrument
transformers

6.5

Chap6-78-97

21/06/02

9:20

Page 79

6 Current and Voltage


Transformers

6.1 INTRODUCTION
Whenever the values of voltage or current in a power
circuit are too high to permit convenient direct
connection of measuring instruments or relays, coupling
is made through transformers. Such 'measuring'
transformers are required to produce a scaled down
replica of the input quantity to the accuracy expected
for the particular measurement; this is made possible by
the high efficiency of the transformer. The performance
of measuring transformers during and following large
instantaneous changes in the input quantity is
important, in that this quantity may depart from the
sinusoidal waveform. The deviation may consist of a
step change in magnitude, or a transient component
that persists for an appreciable period, or both. The
resulting effect on instrument performance is usually
negligible, although for precision metering a persistent
change in the accuracy of the transformer may be
significant.
However, many protection systems are required to
operate during the period of transient disturbance in the
output of the measuring transformers that follows a
system fault. The errors in transformer output may
abnormally delay the operation of the protection, or
cause unnecessary operations. The functioning of such
transformers must, therefore, be examined analytically.
It can be shown that the transformer can be represented
by the equivalent circuit of Figure 6.1, where all
quantities are referred to the secondary side.

1/1

Rp

Lp

Rs

Ze

Figure 6.1: Equivalent circuit of transformer

Network Protection & Automation Guide

79

Ls

Burden

Chap6-78-97

21/06/02

9:20

Page 80

When the transformer is not 1/1 ratio, this condition can


be represented by energising the equivalent circuit with an
ideal transformer of the given ratio but having no losses.

voltage drops are made small, and the normal flux


density in the core is designed to be well below the
saturation density, in order that the exciting current may
be low and the exciting impedance substantially
constant with a variation of applied voltage over the
desired operating range including some degree of
overvoltage. These limitations in design result in a VT for
a given burden being much larger than a typical power
transformer of similar rating. The exciting current, in
consequence, will not be as small, relative to the rated
burden, as it would be for a typical power transformer.

6.1.1 Measuring Transformers

C u r r e n t a n d Vo l t a g e T r a n s f o r m e r s

Voltage and current transformers for low primary voltage


or current ratings are not readily distinguishable; for
higher ratings, dissimilarities of construction are usual.
Nevertheless the differences between these devices lie
principally in the way they are connected into the power
circuit. Voltage transformers are much like small power
transformers, differing only in details of design that
control ratio accuracy over the specified range of output.
Current transformers have their primary windings
connected in series with the power circuit, and so also in
series with the system impedance. The response of the
transformer is radically different in these two modes of
operation.

The ratio and phase errors of the transformer can be


calculated using the vector diagram of Figure 6.2.
The ratio error is defined as:
( K nV s )
100%
Vp

6.2 ELECTROMAGNETIC VOLTAGE TRANSFORMERS

where:
Kn is the nominal ratio

In the shunt mode, the system voltage is applied across


the input terminals of the equivalent circuit of Figure 6.1.
The vector diagram for this circuit is shown in Figure 6.2.

Vp is the primary voltage


Vs is the secondary voltage

Vp

IpXp

If the error is positive, the secondary voltage exceeds the


nominal value. The turns ratio of the transformer need
not be equal to the nominal ratio; a small turns
compensation will usually be employed, so that the error
will be positive for low burdens and negative for high
burdens.

IpRp
Ep

-V
Vs

Ic

Im

The phase error is the phase difference between the


reversed secondary and the primary voltage vectors. It is
positive when the reversed secondary voltage leads the
primary vector. Requirements in this respect are set out
in IEC 60044-2. All voltage transformers are required to
comply with one of the classes in Table 6.1.

Ie

IpL
Ie

6.2.1 Errors

For protection purposes, accuracy of voltage


measurement may be important during fault conditions,
as the system voltage might be reduced by the fault to a
low value. Voltage transformers for such types of service
must comply with the extended range of requirements
set out in Table 6.2.

E
s

Is

Ie
Im
I

Vs
IsXs

= exciting current

= phase angle error

I
Ip
Es

IsRs

s s

I
I

Accuracy
class

= secondary current

= primary current

0.1
0.2
0.5
1.0
3.0

Figure 6.2: Vector diagram for voltage transformer

The secondary output voltage Vs is required to be an


accurate scaled replica of the input voltage Vp over a
specified range of output. To this end, the winding

0.8 - 1.2 x rated voltage


0.25 - 1.0 x rated burden at 0.8pf
voltage ratio error
phase displacement
(%)
(minutes)
+/- 0.1
+/- 5
+/- 0.2
+/- 10
+/- 0.5
+/- 20
+/- 1.0
+/- 40
+/- 3.0
not specified

Table 6.1: Measuring voltage transformer error limits

80

Network Protection & Automation Guide

21/06/02

Accuracy
class
3P
6P

9:21

Page 81

0.25 - 1.0 x rated burden at 0.8pf


0.05 - Vf x rated primary voltage
voltage ratio error
phase displacement
(%)
(%)
+/- 3.0
+/- 120
+/- 6.0
+/- 240

Table 6.2: Additional limits for protection voltage transformers.

as possible. A short circuit on the secondary circuit


wiring will produce a current of many times the rated
output and cause excessive heating. Even where primary
fuses can be fitted, these will usually not clear a
secondary side short circuit because of the low value of
primary current and the minimum practicable fuse rating.

6.2.5 Construction

6.2.2 Voltage Factors


The quantity Vf in Table 6.2 is an upper limit of operating
voltage, expressed in per unit of rated voltage. This is
important for correct relay operation and operation
under unbalanced fault conditions on unearthed or
impedance earthed systems, resulting in a rise in the
voltage on the healthy phases.

The construction of a voltage transformer takes into


account the following factors:
a. output seldom more than 200-300VA. Cooling is
rarely a problem
b. insulation designed for the system impulse
voltage level. Insulation volume is often larger
than the winding volume

Voltage factors, with the permissible duration of the


maximum voltage, are given in Table 6.3.
Voltage factor
Vf

Time
rating

1.2

continuous

1.2
1.5
1.2

continuous
30 s
continuous

1.9

30 s

1.2

continuous

1.9

8 hours

Primary winding connection/system


earthing conditions
Between lines in any network.
Between transformer star point and
earth in any network
Between line and earth in an
effectively earthed network
Between line and earth in
a non-effectively earthed neutral system
with automatic earth fault tripping
Between line and earth in an isolated
neutral system without automatic earth fault
tripping, or in a resonant earthed system
without automatic earth fault tripping

c. mechanical design not usually necessary to


withstand short-circuit currents. Must be small to
fit the space available within switchgear
Three-phase units are common up to 36kV but for higher
voltages single-phase units are usual.
Voltage
transformers for medium voltage circuits will have dry
type insulation, but for high and extra high voltage
systems, oil immersed units are general. Resin
encapsulated designs are in use on systems up to 33kV.
Figure 6.3 shows a typical voltage transformer.

Table 6.3: Voltage transformers: Permissible duration


of maximum voltage

6.2.3 Secondary Leads


Voltage transformers are designed to maintain the
specified accuracy in voltage output at their secondary
terminals. To maintain this if long secondary leads are
required, a distribution box can be fitted close to the VT
to supply relay and metering burdens over separate
leads. If necessary, allowance can be made for the
resistance of the leads to individual burdens when the
particular equipment is calibrated.

Figure 6.3: Typical voltage transformer

6.2.4 Protection of Voltage Transformers

6.2.6 Residually Connected Voltage Transformers

Voltage Transformers can be protected by H.R.C. fuses on


the primary side for voltages up to 66kV. Fuses do not
usually have a sufficient interrupting capacity for use
with higher voltages. Practice varies, and in some cases
protection on the primary is omitted.

The three voltages of a balanced system summate to


zero, but this is not so when the system is subject to a
single-phase earth fault. The residual voltage of a
system is measured by connecting the secondary
windings of a VT in 'broken delta' as shown in Figure 6.4.

The secondary of a Voltage Transformer should always be


protected by fuses or a miniature circuit breaker (MCB).
The device should be located as near to the transformer

The output of the secondary windings connected in


broken delta is zero when balanced sinusoidal voltages
are applied, but under conditions of unbalance a residual

Network Protection & Automation Guide

C u r r e n t a n d Vo l t a g e T r a n s f o r m e r s

Chap6-78-97

81

Chap6-78-97

21/06/02

9:21

Page 82

voltage equal to three times the zero sequence voltage of


the system will be developed.
A

If a voltage is suddenly applied, an inrush transient will


occur, as with power transformers. The effect will,
however, be less severe than for power transformers
because of the lower flux density for which the VT is
designed. If the VT is rated to have a fairly high voltage
factor, little inrush effect will occur. An error will appear
in the first few cycles of the output current in proportion
to the inrush transient that occurs.

When the supply to a voltage transformer is interrupted,


the core flux will not readily collapse; the secondary
winding will tend to maintain the magnetising force to
sustain this flux, and will circulate a current through the
burden which will decay more or less exponentially,
possible with a superimposed audio-frequency
oscillation due to the capacitance of the winding.
Bearing in mind that the exciting quantity, expressed in
ampere-turns, may exceed the burden, the transient
current may be significant.

Residual
voltage

C u r r e n t a n d Vo l t a g e T r a n s f o r m e r s

Figure 6.4: Residual voltage connection

In order to measure this component, it is necessary for a


zero sequence flux to be set up in the VT, and for this to
be possible there must be a return path for the resultant
summated flux. The VT core must have one or more
unwound limbs linking the yokes in addition to the limbs
carrying windings.
Usually the core is made
symmetrically, with five limbs, the two outermost ones
being unwound. Alternatively, three single-phase units
can be used. It is equally necessary for the primary
winding neutral to be earthed, for without an earth, zero
sequence exciting current cannot flow.

6.2.8 Cascade Voltage Transformers


The capacitor VT (section 6.3) was developed because of
the high cost of conventional electromagnetic voltage
transformers but, as shown in Section 6.3.2, the
frequency and transient responses are less satisfactory
than those of the orthodox voltage transformers. Another
solution to the problem is the cascade VT (Figure 6.5).
A

A VT should be rated to have an appropriate voltage


factor as described in Section 6.2.2 and Table 6.3, to
cater for the voltage rise on healthy phases during earth
faults.

C
P

Voltage transformers are often provided with a normal


star-connected secondary winding and a broken-delta
connected tertiary winding. Alternatively the residual
voltage can be extracted by using a star/broken-delta
connected group of auxiliary voltage transformers
energised from the secondary winding of the main unit,
providing the main voltage transformer fulfils all the
requirements for handling a zero sequence voltage as
previously described. The auxiliary VT must also be
suitable for the appropriate voltage factor. It should be
noted that third harmonics in the primary voltage wave,
which are of zero sequence, summate in the brokendelta winding.

P - primary winding
C - coupling windings
S - secondary winding

6.2.7 Transient Performance

S
a

Transient errors cause few difficulties in the use of


conventional voltage transformers although some do
occur. Errors are generally limited to short time periods
following the sudden application or removal of voltage
from the VT primary.

Figure 6.5: Schematic diagram of typical cascade


voltage transformer

82

Network Protection & Automation Guide

21/06/02

9:21

Page 83

The conventional type of VT has a single primary winding,


the insulation of which presents a great problem for
voltages above about 132kV. The cascade VT avoids
these difficulties by breaking down the primary voltage
in several distinct and separate stages.

the normal value using a relatively inexpensive


electromagnetic transformer. The successive stages of
this reasoning are indicated in Figure 6.6.

The complete VT is made up of several individual


transformers, the primary windings of which are
connected in series, as shown in Figure 6.5. Each
magnetic core has primary windings (P) on two opposite
sides. The secondary winding (S) consists of a single
winding on the last stage only. Coupling windings (C)
connected in pairs between stages, provide low
impedance circuits for the transfer of load ampere-turns
between stages and ensure that the power frequency
voltage is equally distributed over the several primary
windings.
The potentials of the cores and coupling windings are
fixed at definite values by connecting them to selected
points on the primary windings. The insulation of each
winding is sufficient for the voltage developed in that
winding, which is a fraction of the total according to the
number of stages. The individual transformers are
mounted on a structure built of insulating material,
which provides the interstage insulation, accumulating
to a value able to withstand the full system voltage
across the complete height of the stack. The entire
assembly is contained in a hollow cylindrical porcelain
housing with external weather-sheds; the housing is
filled with oil and sealed, an expansion bellows being
included to maintain hermetic sealing and to permit
expansion with temperature change.

6.3 CAPACITOR VOLTAGE TRANSFORMERS


The size of electromagnetic voltage transformers for the
higher voltages is largely proportional to the rated
voltage; the cost tends to increase at a disproportionate
rate. The capacitor voltage transformer (CVT) is often
more economic.

C1

L
C2

Network Protection & Automation Guide

C2

Zb

(a) Basic capacitive


voltage divider

C1

Zb

(b) Capacitive divider with


inductive compensation

T
L

C2

Zb

(c) Divider with E/M VT output stage


Figure 6.6: Development of capacitor
voltage transformer

There are numerous variations of this basic circuit. The


inductance L may be a separate unit or it may be
incorporated in the form of leakage reactance in the
transformer T. Capacitors C1 and C2 cannot conveniently
be made to close tolerances, so tappings are provided for
ratio adjustment, either on the transformer T, or on a
separate auto-transformer in the secondary circuit.
Adjustment of the tuning inductance L is also needed;
this can be done with tappings, a separate tapped
inductor in the secondary circuit, by adjustment of gaps
in the iron cores, or by shunting with variable
capacitance. A simplified equivalent circuit is shown in
Figure 6.7.
C

Rp

Rs

This device is basically a capacitance potential divider.


As with resistance-type potential dividers, the output
voltage is seriously affected by load at the tapping point.
The capacitance divider differs in that its equivalent
source impedance is capacitive and can therefore be
compensated by a reactor connected in series with the
tapping point. With an ideal reactor, such an
arrangement would have no regulation and could supply
any value of output.
A reactor possesses some resistance, which limits the
output that can be obtained. For a secondary output
voltage of 110V, the capacitors would have to be very
large to provide a useful output while keeping errors
within the usual limits. The solution is to use a high
secondary voltage and further transform the output to

C1

C u r r e n t a n d Vo l t a g e T r a n s f o r m e r s

Chap6-78-97

Vi

Ze

Zb

L - tuning inductance
Rp - primary winding resistance (plus losses)
Ze - exciting impedance of transformer T
Rs - secondary circuit resistance
Zb - burden impedance
C - C1 + C2 (in Figure 6.6)
Figure 6.7: Simplified equivalent circuit
of capacitor voltage transformer

It will be seen that the basic difference between Figure


6.7 and Figure 6.1 is the presence of C and L. At normal
frequency when C and L are in resonance and therefore
83

Chap6-78-97

21/06/02

9:21

Page 84

cancel, the circuit behaves in a similar manner to a


conventional VT. At other frequencies, however, a
reactive component exists which modifies the errors.

and the capacitance of the potential divider together


form a resonant circuit that will usually oscillate at a
sub-normal frequency. If this circuit is subjected to a
voltage impulse, the resulting oscillation may pass
through a range of frequencies. If the basic frequency of
this circuit is slightly less than one-third of the system
frequency, it is possible for energy to be absorbed from
the system and cause the oscillation to build up. The
increasing flux density in the transformer core reduces
the inductance, bringing the resonant frequency nearer
to the one-third value of the system frequency.

Standards generally require a CVT used for protection to


conform to accuracy requirements of Table 6.2 within a
frequency range of 97-103% of nominal.
The
corresponding frequency range of measurement CVTs is
much less, 99%-101%, as reductions in accuracy for
frequency deviations outside this range are less
important than for protection applications.

The result is a progressive build-up until the oscillation


stabilizes as a third sub-harmonic of the system, which
can be maintained indefinitely. Depending on the values
of components, oscillations at fundamental frequency or
at other sub-harmonics or multiples of the supply
frequency are possible but the third sub-harmonic is the
one most likely to be encountered.

If the burden impedance of a CVT were to be shortcircuited, the rise in the reactor voltage would be limited
only by the reactor losses and possible saturation, that is,
to Q x E2 where E2 is the no-load tapping point voltage
and Q is the amplification factor of the resonant circuit.
This value would be excessive and is therefore limited by
a spark gap connected across the auxiliary capacitor. The
voltage on the auxiliary capacitor is higher at full rated
output than at no load, and the capacitor is rated for
continuous service at this raised value. The spark gap will
be set to flash over at about twice the full load voltage.

The principal manifestation of such an oscillation is a rise


in output voltage, the r.m.s. value being perhaps 25%50% above the normal value; the output waveform
would generally be of the form shown in Figure 6.8.

The effect of the spark gap is to limit the short-circuit


current which the VT will deliver and fuse protection of
the secondary circuit has to be carefully designed with this
point in mind. Facilities are usually provided to earth the
tapping point, either manually or automatically, before
making any adjustments to tappings or connections.

Amplitude

C u r r e n t a n d Vo l t a g e T r a n s f o r m e r s

6.3.1 Voltage Protection of Auxiliary Capacitor

6.3.2 Transient Behaviour of Capacitor Voltage


Transformers

Time

Figure 6.8: Typical secondary voltage


waveform with third sub-harmonic oscillation.

A CVT is a series resonant circuit. The introduction of the


electromagnetic transformer between the intermediate
voltage and the output makes possible further resonance
involving the exciting impedance of this unit and the
capacitance of the divider stack. When a sudden voltage
step is applied, oscillations in line with these different
modes take place, and will persist for a period governed
by the total resistive damping that is present. Any
increase in resistive burden reduces the time constant of
a transient oscillation, although the chance of a large
initial amplitude is increased.

Such oscillations are less likely to occur when the circuit


losses are high, as is the case with a resistive burden, and
can be prevented by increasing the resistive burden.
Special anti-ferro-resonance devices that use a paralleltuned circuit are sometimes built into the VT. Although
such arrangements help to suppress ferro-resonance,
they tend to impair the transient response, so that the
design is a matter of compromise.

For very high-speed protection, transient oscillations


should be minimised. Modern capacitor voltage
transformers are much better in this respect than their
earlier counterparts, but high performance protection
schemes may still be adversely affected.

Correct design will prevent a CVT that supplies a resistive


burden from exhibiting this effect, but it is possible for
non-linear inductive burdens, such as auxiliary voltage
transformers, to induce ferro-resonance. Auxiliary
voltage transformers for use with capacitor voltage
transformers should be designed with a low value of flux
density that prevents transient voltages from causing
core saturation, which in turn would bring high exciting
currents.

6.3.3 Ferro-Resonance
The exciting impedance Ze of the auxiliary transformer T
84

Network Protection & Automation Guide

Chap6-78-97

21/06/02

9:21

Page 85

6.4 CURRENT TRANSFORMERS

6.4.1 Errors

The primary winding of a current transformer is


connected in series with the power circuit and the
impedance is negligible compared with that of the power
circuit. The power system impedance governs the
current passing through the primary winding of the
current transformer. This condition can be represented
by inserting the load impedance, referred through the
turns ratio, in the input connection of Figure 6.1.

The general vector diagram (Figure 6.2) can be simplified


by the omission of details that are not of interest in
current measurement; see Figure 6.10. Errors arise
because of the shunting of the burden by the exciting
impedance. This uses a small portion of the input current
for exciting the core, reducing the amount passed to the
burden. So Is = Ip - Ie, where Ie is dependent on Ze, the
exciting impedance and the secondary e.m.f. Es, given by
the equation Es = Is (Zs + Zb), where:

This approach is developed in Figure 6.9, taking the


numerical example of a 300/5A CT applied to an 11kV power
system. The system is considered to be carrying rated
current (300A) and the CT is feeding a burden of 10VA.

Zs = the self-impedance of the secondary winding,


which can generally be taken as the resistive
component Rs only
Zb = the impedance of the burden

Z=21.2
IsRs
Burden
10VA

300/5A

Es

IsXs
(a) Physical arrangement

Iq
Ir
0.2

Z=21.2
'Ideal'
CT
E=6350V r=300/5

j50

150

Ip

Vs

0.4
Is

(b) Equivalent circuit of (a)


E2r =21.2 x 602
=76.2k

Ie

0.2
E = Secondary induced e.m.f.
Vs Secondary output voltage

Er =6350V x 60
=381kV

j50

150

0.4

Phase angle error

(c) Equivalent circuit, all quantities referred


to secondary side

C u r r e n t a n d Vo l t a g e T r a n s f o r m e r s

E=6350V

Ie
Figure 6.9: Derivation of equivalent circuit
of a current transformer

Is

Iq

Is

Figure 6.10: Vector diagram for current


transformer (referred to secondary)

A study of the final equivalent circuit of Figure 6.9(c),


taking note of the typical component values, will reveal all
the properties of a current transformer. It will be seen that:

6.4.1.1 Current or Ratio Error

a. the secondary current will not be affected by


change of the burden impedance over a
considerable range

This is the difference in magnitude between Ip and Is and is


equal to Ir, the component of Ie which is in phase with Is.

b. the secondary circuit must not be interrupted while


the primary winding is energised. The induced
secondary e.m.f. under these circumstances will be
high enough to present a danger to life and insulation

This is represented by Iq, the component of Ie in


quadrature with Is and results in the phase error .

c. the ratio and phase angle errors can be calculated


easily if the magnetising characteristics and the
burden impedance are known

Network Protection & Automation Guide

6.4.1.2 Phase Error

The values of the current error and phase error depend on


the phase displacement between Is and Ie, but neither
current nor phase error can exceed the vectorial error Ie.
It will be seen that with a moderately inductive burden,
resulting in Is and Ie approximately in phase, there will
85

Chap6-78-97

21/06/02

9:21

Page 86

be little phase error and the exciting component will


result almost entirely in ratio error.

Class

A reduction of the secondary winding by one or two


turns is often used to compensate for this. For example,
in the CT corresponding to Figure 6.9, the worst error due
to the use of an inductive burden of rated value would
be about 1.2%. If the nominal turns ratio is 2:120,
removal of one secondary turn would raise the output by
0.83% leaving the overall current error as -0.37%.

5P
10P

Table 6.5: Protection CT error limits for classes 5P and 10P

Even though the burden of a protection CT is only a few


VA at rated current, the output required from the CT may
be considerable if the accuracy limit factor is high. For
example, with an accuracy limit factor of 30 and a
burden of 10VA, the CT may have to supply 9000VA to
the secondary circuit.

For lower value burden or a different burden power


factor, the error would change in the positive direction to
a maximum of +0.7% at zero burden; the leakage
reactance of the secondary winding is assumed to be
negligible. No corresponding correction can be made for
phase error, but it should be noted that the phase error
is small for moderately reactive burdens.

Alternatively, the same CT may be subjected to a high


burden. For overcurrent and earth fault protection, with
elements of similar VA consumption at setting, the earth
fault element of an electromechanical relay set at 10%
would have 100 times the impedance of the overcurrent
elements set at 100%. Although saturation of the relay
elements somewhat modifies this aspect of the matter, it
will be seen that the earth fault element is a severe
burden, and the CT is likely to have a considerable ratio
error in this case. So it is not much use applying turns
compensation to such current transformers; it is
generally simpler to wind the CT with turns
corresponding to the nominal ratio.

C u r r e n t a n d Vo l t a g e T r a n s f o r m e r s

6.4.2 Composite Error


This is defined in IEC 60044-1 as the r.m.s. value of the
difference between the ideal secondary current and the
actual secondary current. It includes current and phase
errors and the effects of harmonics in the exciting
current. The accuracy class of measuring current
transformers is shown in Table 6.4.
Accuracy
class
0.1
0.2
0.5
1

+/- Percentage current


(ratio) error
% current 5
20
100
120
0.4
0.2
0.1
0.1
0.75 0.35
0.2
0.2
1.5
0.75
0.5
0.5
3
1.5
1.0
1.0

Current transformers are often used for the dual duty of


measurement and protection. They will then need to be
rated according to a class selected from both Tables 6.4
and 6.5. The applied burden is the total of instrument
and relay burdens. Turns compensation may well be
needed to achieve the measurement performance.
Measurement ratings are expressed in terms of rated
burden and class, for example 15VA Class 0.5. Protection
ratings are expressed in terms of rated burden, class, and
accuracy limit factor, for example 10VA Class 10P10.

+/- current (ratio) error, %


% current

3
5

+/- Phase displacement


(minutes)
5
20
100 120
15
8
5
5
30
15
10 10
90
45
30 30
180 90
60 60

(a) Limits of error accuracy for error classes 0.1 - 1.0


Accuracy
class

50
3
5

Current error at
Phase displacement
Composite error at
rated primary
at rated current
rated accuracy limit
current (%)
(minutes)
primary current (%)
+/-1
+/-60
5
+/-3
10
Standard accuracy limit factors are 5, 10, 15, 20, and 30

120
3
5

(b) Limits of error for error classes 3 and 5


Table 6.4: CT error classes

6.4.4 Class PX Current Transformers


The classification of Table 6.5 is only used for overcurrent
protection. Class PX is the definition in IEC 60044-1 for
the quasi-transient current transformers formerly
covered by Class X of BS 3938, commonly used with unit
protection schemes.

6.4.3 Accuracy Limit Current of Protection


Current Transformers
Protection equipment is intended to respond to fault
conditions, and is for this reason required to function at
current values above the normal rating. Protection class
current transformers must retain a reasonable accuracy
up to the largest relevant current. This value is known as
the accuracy limit current and may be expressed in
primary or equivalent secondary terms. The ratio of the
accuracy limit current to the rated current is known as
the 'accuracy limit factor'.

Guidance was given in the specifications to the


application of current transformers to earth fault
protection, but for this and for the majority of other
protection applications it is better to refer directly to the
maximum useful e.m.f. that can be obtained from the CT.
In this context, the 'knee-point' of the excitation curve is
defined as 'that point at which a further increase of 10%
of secondary e.m.f. would require an increment of
exciting current of 50%; see Figure 6.11.

The accuracy class of protection current transformers is


shown in Table 6.5.
86

Network Protection & Automation Guide

21/06/02

VK

9:21

Page 87

+ 10%V
V

Exciting voltage (V
Vs)

+ 50%IIeK

necessary primary insulation. In other cases, the bushing


of a circuit breaker or power transformer is used for this
purpose. At low primary current ratings it may be
difficult to obtain sufficient output at the desired
accuracy. This is because a large core section is needed
to provide enough flux to induce the secondary e.m.f. in
the small number of turns, and because the exciting
ampere-turns form a large proportion of the primary
ampere-turns available. The effect is particularly
pronounced when the core diameter has been made
large so as to fit over large EHV bushings.
6.4.5.3 Core-balance current transformers
The core-balance CT (or CBCT) is normally of the ring
type, through the centre of which is passed cable that
forms the primary winding. An earth fault relay,
connected to the secondary winding, is energised only
when there is residual current in the primary system.

IeK
Exciting voltage (IIe)
Figure 6.11: Definition of knee-point
of excitation curve

Design requirements for current transformers for general


protection purposes are frequently laid out in terms of
knee-point e.m.f., exciting current at the knee-point (or
some other specified point) and secondary winding
resistance. Such current transformers are designated
Class PX.

6.4.5 CT Winding Arrangements


A number of CT winding arrangements are used. These
are described in the following sections.
6.4.5.1 Wound primary type

The advantage in using this method of earth fault


protection lies in the fact that only one CT core is used
in place of three phase CT's whose secondary windings
are residually connected. In this way the CT magnetising
current at relay operation is reduced by approximately
three-to-one, an important consideration in sensitive
earth fault relays where a low effective setting is
required. The number of secondary turns does not need
to be related to the cable rated current because no
secondary current would flow under normal balanced
conditions. This allows the number of secondary turns to
be chosen such as to optimise the effective primary pickup current.
Core-balance transformers are normally mounted over a
cable at a point close up to the cable gland of switchgear
or other apparatus. Physically split cores ('slip-over'
types) are normally available for applications in which
the cables are already made up, as on existing
switchgear.

This type of CT has conventional windings formed of


copper wire wound round a core. It is used for auxiliary
current transformers and for many low or moderate ratio
current transformers used in switchgear of up to 11kV
rating.

6.4.5.4 Summation current transformers

6.4.5.2 Bushing or bar primary type

6.4.5.5 Air-gapped current transformers

Many current transformers have a ring-shaped core,


sometimes built up from annular stampings, but often
consisting of a single length of strip tightly wound to
form a close-turned spiral. The distributed secondary
winding forms a toroid which should occupy the whole
perimeter of the core, a small gap being left between
start and finish leads for insulation.

These are auxiliary current transformers in which a small


air gap is included in the core to produce a secondary
voltage output proportional in magnitude to current in
the primary winding. Sometimes termed 'transactors'
and 'quadrature current transformers', this form of
current transformer has been used as an auxiliary
component of unit protection schemes in which the
outputs into multiple secondary circuits must remain
linear for and proportioned to the widest practical range
of input currents.

Such current transformers normally have a single


concentrically placed primary conductor, sometimes
permanently built into the CT and provided with the

Network Protection & Automation Guide

The summation arrangement is a winding arrangement


used in a measuring relay or on an auxiliary current
transformer to give a single-phase output signal having
a specific relationship to the three-phase current input.

87

C u r r e n t a n d Vo l t a g e T r a n s f o r m e r s

Chap6-78-97

Chap6-78-97

21/06/02

15:21

Page 88

6.4.6 Line Current CTs

10mm. As its name implies the magnetic behaviour


tends to linearisation by the inclusion of this gap in the
magnetic circuit. However, the purpose of introducing
more reluctance into the magnetic circuit is to reduce
the value of magnetising reactance. This in turn reduces
the secondary time-constant of the CT, thereby reducing
the overdimensioning factor necessary for faithful
transformation. Figure 6.12 shows a typical modern CT
for use on MV systems.

CTs for measuring line currents fall into one of three types.
6.4.6.1 Overdimensioned CTs

C u r r e n t a n d Vo l t a g e T r a n s f o r m e r s

Overdimensioned CTs are capable of transforming fully


offset fault currents without distortion. In consequence,
they are very large, as can be deduced from Section
6.4.10. They are prone to errors due to remanent flux
arising, for instance, from the interruption of heavy fault
currents.

6.4.6.2 Anti-remanence CTs

6.4.7 Secondary Winding Impedance

This is a variation of the overdimensioned current


transformer and has small gap(s) in the core magnetic
circuit, thus reducing the possible remanent flux from
approximately 90% of saturation value to approximately
10%. These gap(s) are quite small, for example 0.12mm
total, and so the excitation characteristic is not
significantly changed by their presence. However, the
resulting decrease in possible remanent core flux
confines any subsequent d.c. flux excursion, resulting
from primary current asymmetry, to within the core
saturation limits. Errors in current transformation are
therefore significantly reduced when compared with
those with the gapless type of core.

As a protection CT may be required to deliver high values


of secondary current, the secondary winding resistance
must be made as low as practicable. Secondary leakage
reactance also occurs, particularly in wound primary
current transformers, although its precise measurement
is difficult. The non-linear nature of the CT magnetic
circuit makes it difficult to assess the definite ohmic
value representing secondary leakage reactance.
It is, however, normally accepted that a current
transformer is of the low reactance type provided that
the following conditions prevail:
a. the core is of the jointless ring type (including
spirally wound cores)

Transient protection current transformers are included in IEC


60044-6 as types TPX, TPY and TPZ and this specification
gives good guidance to their application and use.

b. the secondary turns are substantially evenly


distributed along the whole length of the magnetic
circuit

6.4.6.3 Linear current transformers

c. the primary conductor(s) passes through the


approximate centre of the core aperture or, if
wound, is approximately evenly distributed along
the whole length of the magnetic circuit

The 'linear' current transformer constitutes an even more


radical departure from the normal solid core CT in that it
incorporates an appreciable air gap, for example 7.5-

d. flux equalising windings, where fitted to the


requirements of the design, consist of at least four
parallel-connected coils, evenly distributed along
the whole length of the magnetic circuit, each coil
occupying one quadrant

Alternatively, when a current transformer does not


obviously comply with all of the above requirements, it
may be proved to be of low-reactance where:
e. the composite error, as measured in the accepted
way, does not exceed by a factor of 1.3 that error
obtained directly from the V-I excitation
characteristic of the secondary winding

6.4.8 Secondary Current Rating


The choice of secondary current rating is determined
largely by the secondary winding burden and the
standard practice of the user. Standard CT secondary
current ratings are 5A and 1A. The burden at rated
current imposed by digital or numerical relays or

Figure 6.12: Typical modern CT for use on MV systems

88

Network Protection & Automation Guide

21/06/02

15:21

Page 89

instruments is largely independent of the rated value of


current. This is because the winding of the device has to
develop a given number of ampere-turns at rated
current, so that the actual number of turns is inversely
proportional to the current, and the impedance of the
winding varies inversely with the square of the current
rating. However, electromechanical or static earth-fault
relays may have a burden that varies with the current
tapping used.
Interconnection leads do not share this property,
however, being commonly of standard cross-section
regardless of rating. Where the leads are long, their
resistance may be appreciable, and the resultant burden
will vary with the square of the current rating. For
example a CT lead run of the order of 200 metres, a
typical distance for outdoor EHV switchgear, could have
a loop resistance of approximately 3 ohms.

when the primary current is suddenly changed. The


effects are most important, and were first observed in
connection with balanced forms of protection, which
were liable to operate unnecessarily when short-circuit
currents were suddenly established.
6.4.10.1 Primary current transient
The power system, neglecting load circuits, is mostly
inductive, so that when a short circuit occurs, the fault
current that flows is given by:
ip =

A CT with a particular short-time current/ time rating


will carry a lower current for a longer time in inverse
proportion to the square of the ratio of current values.
The converse, however, cannot be assumed, and larger
current values than the S.T.C. rating are not permissible
for any duration unless justified by a new rating test to
prove the dynamic capability.

Network Protection & Automation Guide

Equation 6.1

Ep

= peak system e.m.f.

= system resistance

= system inductance

= initial phase angle governed by instant


of fault occurrence

= system power factor angle


= tan-1 L/R

The first term of Equation 6.1 represents the steady state


alternating current, while the second is a transient
quantity responsible for displacing the waveform
asymmetrically.
Ep
R + 2 L 2 is the steady state peak current I .
p
The maximum transient occurs when sin = ( - ) = 1;
no other condition need be examined.
So:
2

i p = I p sin t + e ( R
2

L) t

...Equation 6.2

When the current is passed through the primary winding


of a current transformer, the response can be examined
by replacing the CT with an equivalent circuit as shown
in Figure 6.9(b).
As the 'ideal' CT has no losses, it will transfer the entire
function, and all further analysis can be carried out in
terms of equivalent secondary quantities (is and Is). A
simplified solution is obtainable by neglecting the
exciting current of the CT.
The flux developed in an inductance is obtained by
integrating the applied e.m.f. through a time interval:

6.4.10 Transient Response of a Current Transformer


When accuracy of response during very short intervals is
being studied, it is necessary to examine what happens

( R L) t

where:

6.4.9 Rated Short-Time Current


A current transformer is overloaded while system shortcircuit currents are flowing and will be short-time rated.
Standard times for which the CT must be able to carry
rated short-time current (STC) are 0.25, 0.5, 1.0, 2.0 or
3.0 seconds.

R 2 + 2 L2

[ sin ( t + ) + sin ( ) e

The CT lead VA burden if a 5A CT is used would be 75VA,


to which must be added the relay burden (up to of
perhaps 10VA for an electromechanical relay, but less
than 1VA for a numerical relay), making a total of 85VA.
Such a burden would require the CT to be very large and
expensive, particularly if a high accuracy limit factor
were also applicable.
With a 1A CT secondary rating, the lead burden is
reduced to 3VA, so that with the same relay burden the
total becomes a maximum of 13VA. This can be provided
by a CT of normal dimensions, resulting in a saving in
size, weight and cost. Hence modern CTs tend to have
secondary windings of 1A rating. However, where the
primary rating is high, say above 2000A, a CT of higher
secondary rating may be used, to limit the number of
secondary turns. In such a situation secondary ratings of
2A, 5A or, in extreme cases, 20A, might be used.

Ep

t2

= K t vdt
1

Equation 6.3

For the CT equivalent circuit, the voltage is the drop on


89

C u r r e n t a n d Vo l t a g e T r a n s f o r m e r s

Chap6-78-97

Chap6-78-97

21/06/02

15:25

Page 90

the burden resistance Rb.


20

3 2
A

= KR b I s

Flux (multiples of steady value)

Integrating for each component in turn, the steady state


peak flux is given by:

sin t dt

KR b I s

The transient flux is given by:


=

= KR b I s e (

R L) t

dt =

...Equation 6.4

KR b I s L
R

C u r r e n t a n d Vo l t a g e T r a n s f o r m e r s

0.1

0.15

0.2

Figure 6.13: Response of a CT of


infinite shunt impedance to transient asymmetric
primary current

Since a CT requires a finite exciting current to maintain


a flux, it will not remain magnetised (neglecting
hysteresis), and for this reason a complete representation
of the effects can only be obtained by including the
finite inductance of the CT in the calculation. The
response of a current transformer to a transient
asymmetric current is shown in Figure 6.14.

1 +

...Equation 6.6

The term (1+X/R) has been called the 'transient factor'


(TF), the core flux being increased by this factor during
the transient asymmetric current period. From this it can
be seen that the ratio of reactance to resistance of the
power system is an important feature in the study of the
behaviour of protection relays.

1.0
0.9
-

0.8

Alternatively, L/R is the primary system time constant T,


so that the transient factor can be written:
=1 +

0.05

Time (seconds)

wL
X
=
R
R

T = 0.06s
4

T - time constant of primary circuit

The CT core has to carry both fluxes, so that:


=

where X and R are the primary system reactance and


resistance values.

12

...Equation 6.5

Hence, the ratio of the transient flux to the steady state


value is:
B

16

-1
e T

0.7

L
= 1 + T
R

1
T1

0.6

Ie

0.5

Again, fT is the time constant expressed in cycles of the


a.c. quantity T, so that:

0.4
0.3

TF = 1 + 2fT = 1 + 2T

0.2

This latter expression is particularly useful when


assessing a recording of a fault current, because the time
constant in cycles can be easily estimated and leads
directly to the transient factor. For example, a system
time constant of three cycles results in a transient factor
of (1+6), or 19.85; that is, the CT would be required to
handle almost twenty times the maximum flux produced
under steady state conditions.

0.1

i's

0
Time
-0.1
Ie = Transient exciting current

Figure 6.14: Response of a current


transformer to a transient asymmetric current

The above theory is sufficient to give a general view of


the problem. In this simplified treatment, no reverse
voltage is applied to demagnetise the CT, so that the flux
would build up as shown in Figure 6.13.
90

Network Protection & Automation Guide

21/06/02

15:25

Page 91

Let:
is = the nominal secondary current

core to retain a 'remanent' flux means that the


value of B developed in Equation 6.5 has to be
regarded as an increment of flux from any possible
remanent value positive or negative. The formula
would then be reasonable provided the applied
current transient did not produce saturation

is = the actual secondary output current


ie = the exciting current
then:
is = ie + is

...Equation 6.7

also,
Le

di e
= R b i s
dt

...Equation 6.8

whence:
di e
R i
R i
+ b e = b s
dt
Le
Le
which gives for the transient term
ie = I1

T
e t T e t T
T1 T
1

...Equation 6.9

where:
T = primary system time constant L/R
T1 = CT secondary circuit time constant Le/Rb
I1 = prospective peak secondary current
6.4.10.2 Practical conditions
Practical conditions differ from theory for the following
reasons:
a. no account has been taken of secondary leakage or
burden inductance. This is usually small compared
with Le so that it has little effect on the maximum
transient flux

It will be seen that a precise calculation of the flux and


excitation current is not feasible; the value of the study is
to explain the observed phenomena. The asymmetric (or
d.c.) component can be regarded as building up the mean
flux over a period corresponding to several cycles of the
sinusoidal component, during which period the latter
component produces a flux swing about the varying
'mean level' established by the former. The asymmetric
flux ceases to increase when the exciting current is equal
to the total asymmetric input current, since beyond this
point the output current, and hence the voltage drop
across the burden resistance, is negative. Saturation
makes the point of equality between the excitation
current and the input occur at a flux level lower than
would be expected from linear theory.
When the exponential component drives the CT into
saturation, the magnetising inductance decreases,
causing a large increase in the alternating component ie.
The total exciting current during the transient period is
of the form shown in Figure 6.15 and the corresponding
resultant distortion in the secondary current output, due
to saturation, is shown in Figure 6.16.

Exciting current

b. iron loss has not been considered. This has the


effect of reducing the secondary time constant, but
the value of the equivalent resistance is variable,
depending upon both the sine and exponential
terms. Consequently, it cannot be included in any
linear theory and is too complicated for a
satisfactory treatment to be evolved

c. the theory is based upon a linear excitation


characteristic. This is only approximately true up to
the knee-point of the excitation curve. A precise
solution allowing for non-linearity is not practicable.
Solutions have been sought by replacing the excitation
curve with a number of chords; a linear analysis can
then be made for the extent of each chord

Time

Current

Figure 6.15: Typical exciting current of CT


during transient asymmetric input current

The above theory is sufficient, however, to give a good


insight into the problem and to allow most practical
issues to be decided.

Primary current
referred to
secondary

Time

0
Secondary current
Residual flux = 0
Resistive burden
Power system T.C. = 0.05s

d. the effect of hysteresis, apart from loss as


discussed under (b) above, is not included.
Hysteresis makes the inductance different for flux
build up and decay, so that the secondary time
constant is variable. Moreover, the ability of the

Network Protection & Automation Guide

C u r r e n t a n d Vo l t a g e T r a n s f o r m e r s

Chap6-78-97

Figure 6.16: Distortion in secondary current


due to saturation

91

Chap6-78-97

21/06/02

15:25

Page 92

CT will cost more. This fact should be weighed against


the convenience achieved; very often it will be found
that the tests in question can be replaced by alternative
procedures.

C u r r e n t a n d Vo l t a g e T r a n s f o r m e r s

The presence of residual flux varies the starting point of


the transient flux excursion on the excitation
characteristic. Remanence of like polarity to the
transient will reduce the value of symmetric current of
given time constant which the CT can transform without
severe saturation; conversely, reverse remanence will
greatly increase the ability of a CT to transform transient
current.

6.5 NOVEL INSTRUMENT TRANSFORMERS


The preceding types of instrument transformers have all
been based on electromagnetic principles using a
magnetic core. There are now available several new
methods of transforming the measured quantity using
optical and mass state methods.

If the CT were the linear non-saturable device considered


in the analysis, the sine current would be transformed
without loss of accuracy. In practice the variation in
excitation inductance caused by transferring the centre
of the flux swing to other points on the excitation curve
causes an error that may be very large. The effect on
measurement is of little consequence, but for protection
equipment that is required to function during fault
conditions, the effect is more serious. The output current
is reduced during transient saturation, which may
prevent the relays from operating if the conditions are
near to the relay setting. This must not be confused with
the increased r.m.s. value of the primary current due to
the asymmetric transient, a feature which sometimes
offsets the increase ratio error. In the case of balanced
protection, during through faults the errors of the several
current transformers may differ and produce an out-ofbalance quantity, causing unwanted operation.

6.5.1 Optical Instrument Transducers


The key features of a freestanding optical instrument
transducer can be illustrated with the functional
diagram of Figure 6.17.

HV
Bus

Insulating
function
Sensor
E/O converter
+
Communication

Sensing
function

Instrument
Transformer

6.4.11 Harmonics during the Transient Period


Optical link
(fibre optics)

When a CT is required to develop a high secondary e.m.f.


under steady state conditions, the non-linearity of the
excitation impedance causes some distortion of the
output waveform; such a waveform will contain, in
addition to the fundamental current, odd harmonics only.

Electronic
interface

Communication
+
O/E converter
Secondary
output

When, however, the CT is saturated uni-directionally


while being simultaneously subjected to a small a.c.
quantity, as in the transient condition discussed above,
the output will contain both odd and even harmonics.
Usually the lower numbered harmonics are of greatest
amplitude and the second and third harmonic
components may be of considerable value. This may
affect relays that are sensitive to harmonics.

Figure 6.17: Functional diagram of


optical instrument transducer

Optical converters and optical glass fibre channels


implement the link between the sensor and the lowvoltage output. The fundamental difference between an
instrument transducer and a conventional instrument
transformer is the electronic interface needed for its
operation. This interface is required both for the sensing
function and for adapting the new sensor technology to
that of the secondary output currents and voltages.

6.4.12 Test Windings


On-site conjunctive testing of current transformers and
the apparatus that they energise is often required. It
may be difficult, however, to pass a suitable value of
current through the primary windings, because of the
scale of such current and in many cases because access
to the primary conductors is difficult. Additional
windings may be provided to make such tests easier,
these windings usually being rated at 10A. The test
winding will inevitably occupy appreciable space and the

Non-conventional optical transducers lend themselves to


smaller, lighter devices where the overall size and power
rating of the unit does not have any significant bearing
on the size and the complexity of the sensor. Small,
lightweight insulator structures may be tailor-made to
92

Network Protection & Automation Guide

21/06/02

15:14

Page 93

fit optical sensing devices as an integral part of the


insulator. Additionally, the non-linear effects and
electromagnetic interference problems in the secondary
wiring of conventional VTs and CTs are minimised.

field, it plays the role of the odd polariser. Changes in


the magnetic or electric field in which the optical sensor
is immersed are monitored as a varying intensity of the
probing light beam at the light detector. The light output
intensity fluctuates around the zero-field level equal to
50% of the reference light input. This modulation of the
light intensity due to the presence of varying fields is
converted back to time-varying currents or voltages.

Optical transducers can be separated in two families:


firstly the hybrid transducers, making use of
conventional electrical circuit techniques to which are
coupled various optical converter systems, and secondly
the all-optical transducers that are based on
fundamental, optical sensing principles.

A transducer uses a magneto-optic effect sensor for


optical current measuring applications. This reflects the
fact that the sensor is not basically sensitive to a current
but to the magnetic field generated by this current.
Although all-fibre approaches are feasible, most
commercially available optical current transducers rely
on a bulk-glass sensor. Most optical voltage transducers,
on the other hand, rely on an electro-optic effect sensor.
This reflects the fact that the sensor used is sensitive to
the imposed electric field.

6.5.1.1 Optical sensor concepts


Certain optical sensing media (glass, crystals, plastics)
show a sensitivity to electric and magnetic fields and
that some properties of a probing light beam can be
altered when passing through them. One simple optical
transducer description is given here in Figure. 6.18.
Consider the case of a beam of light passing through a
pair of polarising filters. If the input and output
polarising filters have their axes rotated 45 from each
other, only half the light will come through. The
reference light input intensity is maintained constant
over time. Now if these two polarising filters remain
fixed and a third polarising filter is placed in between
them, a random rotation of this middle polariser either
clockwise or counter-clockwise will be monitored as a
varying or modulated light output intensity at the light
detector.

6.5.1.2 Hybrid transducers


The hybrid family of non-conventional instrument
transducers can be divided in two types: those with
active sensors and those with passive sensors. The idea
behind a transducer with an active sensor is to change
the existing output of the conventional instrument
transformer into an optically isolated output by adding
an optical conversion system (Figure 6.18). This
conversion system may require a power supply of its
own: this is the active sensor type. The use of an optical
isolating system serves to de-couple the instrument
transformer output secondary voltages and currents

When a block of optical sensing material (glass or


crystal) is immersed in a varying magnetic or electric

'Odd' polariser
input
polariser

output
polariser

optical
fibre

optical
fibre

in

sensing
light
detector

out

light source
45

90
optical
sensing
medium

1.0

0.5

0.5

zero field level

1.0
+

t
reference
light input
intensity

t
modulated
light input
intensity

Figure. 6.18: Schematic representation of the concepts behind the optical sensing of varying electric and magnetic fields

Network Protection & Automation Guide

93

C u r r e n t a n d Vo l t a g e T r a n s f o r m e r s

Chap6-78-97

Chap6-78-97

21/06/02

15:14

Page 94

analysing circuitry.
In sharp contrast with a
conventional free-standing instrument transformer, the
optical instrument transformer needs an electronic
interface module in order to function. Therefore its
sensing principle (the optical material) is passive but its
operational integrity relies on the interface that is
powered in the control room (Figure 6.21).

from earthed or galvanic links. Thus the only link that


remains between the control-room and the switchyard is
a fibre optic cable.
Another type of hybrid non-conventional instrument
transformer is achieved by retrofitting a passive optical
sensing medium into a conventional hard-wire
secondary instrument transformer. This can be termed
as a passive hybrid type since no power supply of any
kind is needed at the secondary level.

'Floating'
electrode

6.5.1.3 All-optical transducers

C u r r e n t a n d Vo l t a g e T r a n s f o r m e r s

These instrument transformers are based entirely on


optical materials and are fully passive. The sensing
function is achieved directly by the sensing material and
a simple fibre optic cable running between the base of
the unit and the sensor location provides the
communication link.

Electro-optic
sensor
AC line
voltage
Optical fibres

The sensing element is made of an optical material that is


positioned in the electric or magnetic field to be sensed.
In the case of a current measuring device the sensitive
element is either located free in the magnetic field (Figure
6.19(a)) or it can be immersed in a field-shaping magnetic
gap (Figure 6.19(b)). In the case of a voltage-sensing
device (Figure 6.20) the same alternatives exist, this time
for elements that are sensitive to electric fields. The
possibility exists of combining both sensors within a
single housing, thus providing both a CT and VT within a
single compact housing that gives rise to space savings
within a substation.

(a) 'Free-field' type

Reference
electrode
Reference
electrode

Light
path

AC line
voltage

Electro-optic
sensor

(b) 'Field shaping' type

I AC line current

Reference
electrode

Optical fibres

Figure 6.20: Optical voltage sensor based


on the electrical properties of optical materials
Optical fibre
Magneto-optic sensor
Magnetic
field

Optical fibre

(a) 'Free-field' type


High voltage
sensor assembly

AC line current
I

Fibre optic cable


Magnetic field

Optical fibres
Junction
box

Gapped
Magneto-optic sensor
magnetic core
(b) 'Field-shaping' type

Optical
interface
unit

Figure 6.19: Optical current sensor based


on the magnetic properties of optical materials

In all cases there is an optical fibre that channels the


probing reference light from a source into the medium
and another fibre that channels the light back to

AC/DC source
Figure 6.21: Novel instrument transducer concept
requiring an electronic interface in the control room

94

Network Protection & Automation Guide

Chap6-78-97

21/06/02

15:15

Dome

Page 95

AC line current

Electro-optic sensor
(bulk-glass transducer)

Electro-optic sensor
('all-fibre' transducer)
AC
line I
current

H1

H2

Bulk-glass
sensing element

Light in
Optical fibres
Light out
Fibre optic
cable conduit

Liquid /solid/ gaseous


internal insulation
(a) Glass sensor approach

Insulator
column

AC line current
I

Fibre junction box

Sensor #2

Light in
Fibre
optic
cables

Optical fibres
Light out
Fibre
sensing element
(b) 'All-fibre' sensor concept

Figure 6.22: Conceptual design of a double-sensor optical CT

Similar to conventional instrument transformers there are


live tank and dead tank optical transducers. Typically,
current transducers take the shape of a closed loop of lighttransparent material, fitted around a straight conductor
carrying the line current (Figure 6.22). In this case a bulkglass sensor unit is depicted (Figure 6.22(a)), along with an
all-optical sensor example, as shown in Figure 6.22(b).
Light detectors are basically very sensitive devices and the
sensing material can thus be selected in such a way as to
scale-up readily for larger currents. All-optical voltage
transducers however do not lend themselves easily for
extremely high line voltages. Two concepts using a 'fullvoltage' sensor are shown in Figure 6.23.

Although all-optical instrument transformers were first


introduced 10-15 years ago, there are still only a few in
service nowadays. Figure 6.24 shows a field installation
of a combined optical CT/VT.

C u r r e n t a n d Vo l t a g e T r a n s f o r m e r s

Sensor #1

Conductor

(a) 'Live tank'

(b) 'Dead tank'


Figure 6.24: Field installation of a combined
optical CT/VT

Figure 6.23: Optical voltage transducer concepts,


using a full-voltage sensor

Network Protection & Automation Guide

95

Chap6-78-97

21/06/02

15:15

Page 96

of insulation material. In most cases the Rogowski coil


will be connected to an amplifier, in order to deliver
sufficient power to the connected measuring or
protection equipment and to match the input impedance
of this equipment.
The Rogowski coil requires
integration of the magnetic field and therefore has a
time and phase delay whilst the integration is completed.
This can be corrected for within a digital protection relay.
The schematic representation of the Rogowski coil sensor
is shown in Figure 6.27.

6.5.2 Other Sensing Systems


There are a number of other sensing systems that can be
used, as described below.

C u r r e n t a n d Vo l t a g e T r a n s f o r m e r s

6.5.2.1 Zero-flux (Hall Effect) current transformer

In this case the sensing element is a semi-conducting


wafer that is placed in the gap of a magnetic
concentrating ring. This type of transformer is also
sensitive to d.c. currents. The transformer requires a
power supply that is fed from the line or from a separate
power supply. The sensing current is typically 0.1% of the
current to be measured. In its simplest shape, the Hall
effect voltage is directly proportional to the magnetising
current to be measured. For more accurate and more
sensitive applications, the sensing current is fed through
a secondary, multiple-turn winding, placed around the
magnetic ring in order to balance out the gap magnetic
field. This zero-flux or null-flux version allows very
accurate current measurements in both d.c. and highfrequency applications. A schematic representation of
the sensing part is shown in Figure 6.25.

Electrical to optical
converter/transmitter
I
Burden

Optical
fibres

Current transformer
Figure 6.26: Design principle of a hybrid magnetic
current transformer fitted with an optical transmitter

Magnetic
g
concentrator
(gapped magnetic core)

Air core
toroidal coil
i

Electrical to optical
converter
V

Optical
fibres

Sensing current
Sensing element
Figure 6.25: Conceptual design of a Hall-effect
current sensing element fitted in a field-shaping gap

Current carrying
conductor
Figure 6.27: Schematic representation
of a Rogowski coil, used for current sensing

6.5.2.2 Hybrid magnetic-optical sensor


This type of transformer is mostly used in applications
such as series capacitive compensation of long
transmission lines, where a non-grounded measurement
of current is required. In this case, several current
sensors are required on each phase in order to achieve
capacitor surge protection and balance. The preferred
solution is to use small toroidally wound magnetic core
transformers connected to fibre optic isolating systems.
These sensors are usually active sensors in the sense that
the isolated systems require a power supply. This is
illustrated in Figure 6.26.
6.5.2.3 Rogowski coils
The Rogowski coil is based on the principle of an aircored current transformer with a very high load
impedance. The secondary winding is wound on a toroid

96

Network Protection & Automation Guide

You might also like