HVAC Load Calculations


for
Ceb
Pathiramulla
16000

Prepared By:
Cecb
Colombo 7
Tuesday, 23 August 2016

Rhvac is an ACCA approved Manual J and Manual D computer program.


Calculations are performed per ACCA Manual J 8th Edition, Version 2, and ACCA Manual D.

Rhvac - Residential & Light Commercial HVAC Loads


Elite Software Development
College Station, TX 77845

Elite Software Development, Inc.


NSCC
Page 2

Project Report
General Project Information
Project Title:
Designed By:
Project Date:
Client Name:
Client Address:
Client City:
Company Name:
Company Address:
Permit Number(s):

NSCC
Sanjeev
Tuesday, 23 August 2016
Ceb
Pathiramulla
16000
Cecb
Colombo 7
001

Design Data
Reference City:
Building Orientation:
Daily Temperature Range:
Latitude:
Elevation:
Altitude Factor:

Winter:
Summer:

Outdoor
Dry Bulb
23.33
35

Check Figures
Total Building Supply L/s:
Square m of Room Area:
Volume (m) of Cond. Space:

Singapore, _Singapore
Front door faces East
Medium
1 Degrees
15.8 m
0.998
Outdoor
Wet Bulb
20.81
26.11

Outdoor
Rel.Hum
n/a
50%
1,742
42
102

Building Loads
Total Heating Required Including Ventilation Air:
Total Sensible Gain:
Total Latent Gain:
Total Cooling Required Including Ventilation Air:

Indoor
Rel.Hum
50%
50%

Indoor
Grains
Dry Bulb Difference
21
-46.87
21
70

L/s Per Square m:


Square m Per Ton:

-7,900
30,619
15,147
45,766

watts
watts
watts
watts

41.659
3

-7.900
67
33
13.01

kW
%
%
Tons (Based On Sensible +
Latent)

Notes
Rhvac is an ACCA approved Manual J and Manual D computer program.
Calculations are performed per ACCA Manual J 8th Edition, Version 2, and ACCA Manual D.
All computed results are estimates as building use and weather may vary.
Be sure to select a unit that meets both sensible and latent loads according to the manufacturer's performance data at
your design conditions.

C:\Users\x550\Documents\Elite Software\Rhvac 9 Projects\nscc ceb.rh9

Tuesday, 23 August 2016, 12:29 PM

Rhvac - Residential & Light Commercial HVAC Loads


Elite Software Development
College Station, TX 77845

Elite Software Development, Inc.


NSCC
Page 3

Miscellaneous Report
System 1
Input Data
Winter:
Summer:

Outdoor
Dry Bulb
23.33
35

Outdoor
Wet Bulb
20.81
26.11

Outdoor
Rel.Hum
80%
50%

Indoor
Rel.Hum
50%
50%

Indoor
Dry Bulb
21
21

Grains
Difference
-46.87
70.17

Duct Sizing Inputs


Calculate:
Use Schedule:
Roughness Factor:
Pressure Drop:
Minimum Velocity:
Maximum Velocity:
Minimum Height:
Maximum Height:

Main Trunk
Yes
Yes
0.91440
0.0833
3.3
4.57
250
400

Pa/m
m/s
m/s
mm
mm

Runouts
Yes
Yes
3.04800
0.0833
2.29
3.81
0
0

Pa/m
m/s
m/s
mm
mm

Outside Air Data


Winter
Infiltration Specified:

Infiltration Actual:
Above Grade Volume:

Total Building Infiltration:


Total Building Ventilation:

AC/hr (rm
3.531
specified)
100 L/s
AC/hr (rm
specified)
X 102 Cu.m
360 Cu.m/hr
X 0.278
100 L/s
400 L/s
3.531

Summer
AC/hr (rm
specified)
100 L/s

3.531

AC/hr (rm
specified)
X 102 Cu.m
360 Cu.m/hr
X 0.278
100 L/s
400 L/s
3.531

---System 1--Infiltration & Ventilation Sensible Gain Multiplier:


15.37 = (1.10 X 0.998 X 14.00 Summer Temp. Difference)
Infiltration & Ventilation Latent Gain Multiplier:
47.62 = (0.68 X 0.998 X 70.17 Grains Difference)
Infiltration & Ventilation Sensible Loss Multiplier:
2.56 = (1.10 X 0.998 X 2.33 Winter Temp. Difference)
Winter Infiltration Specified:
3.531 AC/hr (rm specified) (100 L/s)
Summer Infiltration Specified: 3.531 AC/hr (rm specified) (100 L/s)

C:\Users\x550\Documents\Elite Software\Rhvac 9 Projects\nscc ceb.rh9

Tuesday, 23 August 2016, 12:29 PM

Rhvac - Residential & Light Commercial HVAC Loads


Elite Software Development
College Station, TX 77845

Elite Software Development, Inc.


NSCC
Page 4

Load Preview Report


Net
Ton

m
/Ton

Area

Sen
Gain

Lat
Gain

Net
Gain

Sen
Loss

Min
Htg
L/s

Min
Clg
L/s

Sys
Htg
L/s

Sys
Clg
L/s

Sys
Act
L/s

13.01

42

30,619

15,147

45,766

-7,900

-166

1,742

-166

1,742

1,742

13.01

42

30,619

15,147

45,766

-7,900

-166

1,742

-166

1,742

1,742

6,873

11,829

18,702

42

23,746

3,317

27,063

1,742

1,742

1,742

1168x400

1-Room 1

21

12,183

1,659

13,842

894

894

894

2--305x406

2-Room 2

21

11,563

1,659

13,222

848

848

848

2--305x406

Scope

Has
AED

Building
System 1

No

Ventilation
Humidification
Zone 1

Duct
Size

1168x400

-7,900

C:\Users\x550\Documents\Elite Software\Rhvac 9 Projects\nscc ceb.rh9

Tuesday, 23 August 2016, 12:29 PM

Rhvac - Residential & Light Commercial HVAC Loads


Elite Software Development
College Station, TX 77845

Elite Software Development, Inc.


NSCC
Page 5

Duct Size Preview


Room or
Duct Name

Source

Minimum
Velocity

Maximum
Velocity

Rough.
Factor

Design
L/100

SP
Loss

Duct
Velocity

Duct Htg
Length Flow

1-Room 1

Built-In

0.012

0.019

929.0304

0.06942

0.018

894

894

2--304.8x406.4

2-Room 2

Built-In

0.012

0.019

929.0304

0.06942

0.017

848

848

2--304.8x406.4

Built-In

0.017

0.023

278.7091

0.06942

0.019

-166

1,742

1,742

1168.4x400

Clg
Flow

Act.
Flow

Duct
Size

System 1
Supply Runouts
Zone 1

Other Ducts in
System 1
Supply Main
Trunk

Summary
System 1
Heating Flow:
Cooling Flow:

-166
1742

C:\Users\x550\Documents\Elite Software\Rhvac 9 Projects\nscc ceb.rh9

Tuesday, 23 August 2016, 12:29 PM

Rhvac - Residential & Light Commercial HVAC Loads


Elite Software Development
College Station, TX 77845

Elite Software Development, Inc.


NSCC
Page 6

Total Building Summary Loads


Component
Description
1G-cm-s: Glazing-Double pane with storm, clear, metal
frame no break, u-value 3.123, SHGC 0.62
14F-0: Wall-four inches of concrete, no board insulation
on 4 inch 140# concrete wall with stucco and interior
finish
14F-0: Wall-four inches of concrete, no board insulation
on 4 inch 140# concrete wall with stucco and interior
finish
16A-11: Roof/Ceiling-Under Attic with Insulation on Attic
Floor (also use for Knee Walls and Partition
Ceilings), Unvented Attic, No Radiant Barrier, Any
Roofing Material, Any Roof Color, R-11 insulation
22C-5pl-t: Floor-Slab on grade, Horizontal board
insulation extends 4' under slab, tile covering, R-5
insulation, passive, light dry soil
Subtotals for structure:
People:
Equipment:
Lighting:
Ductwork:
Infiltration: Winter L/s: 100, Summer L/s: 100
Ventilation: Winter L/s: 400, Summer L/s: 400
AED Excursion:

Area
Quan
4.4

Sen
Loss
0

Lat
Gain
0

Sen
Gain
600

Total
Gain
600

19.4

743

743

9.7

334

334

71.7

1,470

1,470

6.1

0
360
0

0
0
0
0

0
2,957
11,829
0

3,146
420
18,000
200
0
1,718
6,873
262

3,146
780
18,000
200
0
4,676
18,702
262

-7,900

15,147

30,619

45,766

6
200

Total Building Load Totals:


Check Figures
Total Building Supply L/s:
Square m of Room Area:
Volume (m) of Cond. Space:

1,742
42
102

Building Loads
Total Heating Required Including Ventilation Air:
Total Sensible Gain:
Total Latent Gain:
Total Cooling Required Including Ventilation Air:

L/s Per Square m:


Square m Per Ton:

-7,900
30,619
15,147
45,766

watts
watts
watts
watts

41.659
3

-7.900
67
33
13.01

kW
%
%
Tons (Based On Sensible +
Latent)

Notes
Rhvac is an ACCA approved Manual J and Manual D computer program.
Calculations are performed per ACCA Manual J 8th Edition, Version 2, and ACCA Manual D.
All computed results are estimates as building use and weather may vary.
Be sure to select a unit that meets both sensible and latent loads according to the manufacturer's performance data at
your design conditions.

C:\Users\x550\Documents\Elite Software\Rhvac 9 Projects\nscc ceb.rh9

Tuesday, 23 August 2016, 12:29 PM

Rhvac - Residential & Light Commercial HVAC Loads


Elite Software Development
College Station, TX 77845

Elite Software Development, Inc.


NSCC
Page 7

Building Pie Chart

Building
Loss
-7,900
watts

100.0%

Roof 3%
Wall 2%
Glass 1%
People 2%

AED Excursion 1%

Ventilation 41%
Building
Gain
45,766
watts Equipment 39%

Lighting 0%

C:\Users\x550\Documents\Elite Software\Rhvac 9 Projects\nscc ceb.rh9

Infiltration 10%

Tuesday, 23 August 2016, 12:29 PM

Rhvac - Residential & Light Commercial HVAC Loads


Elite Software Development
College Station, TX 77845

Elite Software Development, Inc.


NSCC
Page 8

Detailed Room Loads - Room 1 - Room 1 (Average Load Procedure)


General
Calculation Mode:
Room Length:
Room Width:
Area:
Ceiling Height:
Volume:
Number of Registers:
Runout Air:
Runout Duct Size:
Runout Air Velocity:
Runout Air Velocity:
Actual Loss:

Htg. & clg.


68.6
0.3
20.9
2.4
51.0
2
947
304.8x406.4
4
4
0.088

Item
Description
E -Wall-14F-0 4.6 X 2.4
S -Wall-14F-0 4.6 X 2.4
E -Gls-1G-cm-s shgc-1 70%S
S -Gls-1G-cm-s shgc-0.62 100%S
UP-Ceil-16A-11 117.2 X 0.3
Subtotals for Structure:
Infil.: Win.: 50.0, Sum.: 50.0
Ductwork:
AED Excursion:
People: 60 lat/per, 70 sen/per:
Equipment:
Lighting:

Occurrences:
System Number:
Zone Number:
Supply Air:
Supply Air Changes:
Req. Vent. Clg:
Actual Winter Vent.:
Percent of Supply.:
Actual Summer Vent.:
Percent of Supply:
Actual Winter Infil.:
Actual Summer Infil.:

m
m
sq.m
m
cu.m
L/s
mm
m/min.
m/min.
Pa/m

Area
Quantity
9.7
9.7
1.5
1.5
35.7

-UValue
2.500
2.500
3.123
3.123
0.460

22

1
1
1
894
63.1
200
0
0
205
23
50
50

L/s
AC/hr
L/s
L/s
%
L/s
%
L/s
L/s

Htg
HTM
0.0
0.0
0.0
0.0
0.0

Sen
Loss
0
0
0
0
0

Clg
HTM
38.3
38.3
187.2
89.7
20.5

Lat
Gain
0
0
0
0
0

Sen
Gain
371
371
274
131
732

0.000

0
0
0

38.529

0
1,479

1,880
859
0
134
210
9,000
100

180
0

100

Room Totals:

1,659

12,183

Equipment Cooling Loads

Item Name

Continuous
Output
Sensible
watts
9000

Continuous
Output
Latent
watts
0

Average
In-Use
Output
100

Total

C:\Users\x550\Documents\Elite Software\Rhvac 9 Projects\nscc ceb.rh9

Percent
Used
per Hour
100

Sensible
Load
watts
9000

Latent
Load
watts
0

9000

Tuesday, 23 August 2016, 12:29 PM

Rhvac - Residential & Light Commercial HVAC Loads


Elite Software Development
College Station, TX 77845

Elite Software Development, Inc.


NSCC
Page 9

Detailed Room Loads - Room 2 - Room 2 (Average Load Procedure)


General
Calculation Mode:
Room Length:
Room Width:
Area:
Ceiling Height:
Volume:
Number of Registers:
Runout Air:
Runout Duct Size:
Runout Air Velocity:
Runout Air Velocity:
Actual Loss:

Htg. & clg.


4.6
4.6
20.9
2.4
51.0
2
898
304.8x406.4
3
3
0.079

Item
Description
E -Wall-14F-0 4.6 X 2.4
E -Gls-1G-cm-s shgc-0.62 70%S
UP-Ceil-16A-11 118.1 X 0.3
Floor-22C-5pl 6.1 m.Per.
Subtotals for Structure:
Infil.: Win.: 50.0, Sum.: 50.0
Ductwork:
AED Excursion:
People: 60 lat/per, 70 sen/per:
Equipment:
Lighting:

Occurrences:
System Number:
Zone Number:
Supply Air:
Supply Air Changes:
Req. Vent. Clg:
Actual Winter Vent.:
Percent of Supply.:
Actual Summer Vent.:
Percent of Supply:
Actual Winter Infil.:
Actual Summer Infil.:

m
m
sq.m
m
cu.m
L/s
mm
m/min.
m/min.
Pa/m

Area
Quantity
9.7
1.5
36
6.1
11

-UValue
2.250
3.123
0.460
5.565

1
1
1
848
59.9
200
0
0
195
23
50
50

L/s
AC/hr
L/s
L/s
%
L/s
%
L/s
L/s

Htg
HTM
0.0
0.0
0.0
0.0

Sen
Loss
0
0
0
0

Clg
HTM
34.5
132.7
20.5
0.0

Lat
Gain
0
0
0
0

Sen
Gain
334
194
738
0

0.000

0
0
0

77.058

0
1,479

1,266
859
0
127
210
9,000
100

180
0

100

Room Totals:

C:\Users\x550\Documents\Elite Software\Rhvac 9 Projects\nscc ceb.rh9

1,659

11,563

Tuesday, 23 August 2016, 12:29 PM

Rhvac - Residential & Light Commercial HVAC Loads


Elite Software Development
College Station, TX 77845

Elite Software Development, Inc.


NSCC
Page 10

System 1 Room Load Summary


Room
No Name
---Zone 1--1 Room 1

Area
SF

Htg
Sens
watts

Min
Htg
L/s

21

2 Room 2

21

Ventilation
System 1 total
System 1 Main Trunk Size:
Velocity:
Loss per m:

Run
Duct
Size

Run
Duct
Vel

Clg
Sens
watts

Clg
Lat
watts

Min
Clg
L/s

Act
Sys
L/s

2305x406
0
2305x406

12,183

1,659

894

894

11,563

1,659

848

848

6,873

11,829

30,619

15,147

1,742

1,742

0
42

-7,900

-166

1168x400 mm
4 m/s
0.034 Pa

Cooling System Summary

Net Required:
Actual:

Cooling
Tons
13.01
5.12

Sensible/Latent
Split
67% / 33%
75% / 25%

Sensible
watts
30,619
46,064

Latent
watts
15,147
15,355

Total
watts
45,766
61,419

Equipment Data
Type:
Model:
Indoor Model:
Brand:
Description:
Efficiency:
Sound:
Capacity:
Sensible Capacity:
Latent Capacity:

Heating System
Natural Gas Furnace

0 AFUE
7.9
0 watts
n/a
n/a

C:\Users\x550\Documents\Elite Software\Rhvac 9 Projects\nscc ceb.rh9

Cooling System
Standard Air Conditioner
QC-C18
P14
Quikcool AP Series
Performance Efficiency Air Conditioner
14 SEER
7.9
5,275 watts
46,064 Btuh
15,355 Btuh

Tuesday, 23 August 2016, 12:29 PM