Professional Documents
Culture Documents
SUBSTATION
PROJECT WORK
UNDER THE ESTEEMED GUIDANCE OF
Mr. S.D. Guatam
Asst. Manager (technical) 220 KV P.P.K. I
Delhi Transco Limited
SUBMITTED BY:
Ishank bounthiyal
C.R.R.INSTITUTE OF TECNOLOGY
KANJHAWALA DELHI
CERTIFICATE
This is to certify that Mr. ISHANK BOUNTHIYAL (roll no. 305119),
students of diploma in (instrumentation & control) of
C.R.R.INSTITUTE OF TECNOLOGY has successfully completed their
project work at DELHI TRANCO LIMITED on Study Electrical
Design Of a 220 KV Substation under the guidance of Mr. S.D.
Guatam.The students have performed all the related activities
during 02/07/2009 to 18/07/2009 i.e of their project duration.
ACKNOWLEDGEMENT
I express my gratitude to the management of Delhi Transco
Limited for providing me with this opportunity to undergo training
in this esteemed organization.
I take the prerogative to express my gratitude to Mr.A.Guruswami ,
Asst. manager(technical), for his valuable suggestions and
guidance throughout my training period.
I also like to thank the entire staff of Delhi Transco Limited for
making my brief stay in Substation a memorable one.
Electricity in India
Electric power generation in India is done predominantly by
government sector entities. These are controlled by various central
public sector corporations, such as: National Hydroelectric Power
Corporation, National Thermal Power Corporation and various state
level corporations (state electricity boards - SEBs). The transmission
and distribution is managed by the State Electricity Boards (SEBs) or
private companies.
The current per capita power consumption is about 612 KWH per
year while the world average is 2596 KWH.
Generation
Grand Total Installed Capacity is 1,44,564.97 MW
Thermal Power
Current installed base of Thermal Power is 92,216.64 MW which
comes to 64.6% of total installed base.
Hydro Power
India was one of the pioneering states in establishing hydro-electric
power plants, The power plant at Darjeeling and Shimsa was
established in 1898 and 1902 respectively and is one of the first in
Asia. Current installed base of Hydro Power is 36,033.76 MW which
comes to 24.7% of total installed base. Today Hydro sector has
turbines as large as 250 MW and single stage projects as big as 1500
MW .
Nuclear Power
Currently, seventeen nuclear power reactors produce 4,120.00 MW
(2.9% of total installed base).
Renewable Power
Current installed base of Renewable Power is 12194.57 MW which
comes to 7.7% of total installed base.
Transmission
Transmission of electricity is defined as bulk transfer of power over
a long distance at high voltage, generally of 132kV and above.
In
India bulk transmission has increased form 3708ckm in 1950 to more
than 265,000ckm today. The entire country has been divided
into five regions for transmission systems, namely, Northern
Region, North Eastern Region, Eastern Region, Southern Region
and Western Region. The Interconnected transmission system
within each region is also called the regional grid.
The transmission system planning in the country, in the past, had
traditionally been linked to generation projects as part of the
evacuation system. Ability of the power system to safely withstand
a contingency without generation rescheduling or load-shedding was
the main criteria for planning the transmission system. However,
due to various reasons such as spatial development of load in the
network, non-commissioning of load centre generating units
originally planned and deficit in reactive compensation, certain
pockets in the power system could not safely operate even under
normal conditions. This had necessitated backing down of
generation and operating at a lower load generation balance in the
past. Transmission planning has therefore moved away from the
earlier generation evacuation system planning to integrated system
planning.
While the predominant technology for electricity transmission and
distribution has been Alternating Current (AC) technology, High
Voltage Direct Current (HVDC) technology has also been used for
interconnection of all regional grids across the country and for bulk
transmission of power over long distances.
Distribution
The total installed generating capacity in the country is over
135000MW and the total number of consumers is over 144 million.
Apart from an extensive transmission system network at 500kV
HVDC, 400kV, 220kV, 132kV and 66kV which has developed to
transmit the power from generating station to the grid substations,
a vast network of sub transmission in distribution system has also
come up for utilization of the power by the ultimate consumers.
However, due to lack of adequate investment on T&D works, the
T&D losses have been consistently on higher side, and reached to
the level of 32.86% in the year 2000-01.The reduction of these
losses was essential to bring economic viability to the State
Utilities.
As the T&D loss was not able to capture all the losses in the net
work, concept of Aggregate Technical and Commercial (AT&C) loss
was introduced. AT&C loss captures technical as well as commercial
losses in the network and is a true indicator of total losses in the
system.
High technical losses in the system are primarily due to inadequate
investments over the years for system improvement works, which
has resulted in unplanned extensions of the distribution lines,
overloading of the system elements like transformers and
conductors, and lack of adequate reactive power support.
220 KV Substation
BUS BAR
A bus bar in electrical power distribution refers to thick strips of
copper or aluminium that conduct electricity within a switchboard,
distribution board, substation, or other electrical apparatus.
The size of the busbar is important in determining the maximum
amount of current that can be safely carried. Busbars can have a
cross-sectional area of as little as 10 mm but electrical substations
may use metal tubes of 50 mm in diameter (1,000 mm) or more as
busbars.
Busbars are typically either flat strips or hollow tubes as these
shapes allow heat to dissipate more efficiently due to their high
surface area to cross-sectional area ratio. The skin effect makes 5060 Hz AC busbars more than about 8 mm (1/3 in) thick inefficient,
so hollow or flat shapes are prevalent in higher current
applications. A hollow section has higher stiffness than a solid rod,
which allows a greater span between busbar supports in outdoor
switchyards.
A busbar may either be supported on insulators, or else insulation
may completely surround it. Busbars are protected from accidental
contact either by a metal enclosure or by elevation out of normal
reach. Neutral busbars may also be insulated. Earth busbars are
typically bolted directly onto any metal chassis of their enclosure.
Busbars may be enclosed in a metal housing, in the form of bus duct
or busway, segregated-phase bus, or isolated-phase bus.
Busbars may be connected to each other and to electrical apparatus
by bolted or clamp connections. Often joints between high-current
bus sections have matching surfaces that are silver-plated to reduce
the contact resistance. At extra-high voltages (more than 300 kV) in
outdoor buses, corona around the connections becomes a source of
10
Protection
Bus bars are vital parts of a power system and so a fault should be
cleared as fast as possible. A busbar must have its own protection
although their high degrees of reliability bearing in mind the risk of
unnecessary trips, so the protection should be dependable,
selective and should be stable for external faults, called through
faults.
11
12
13
TRANSFORMER
Definition :
Transformer is
defined as A static
piece of apparatus
with two or more
windings which, by
electromagnetic
induction, transforms
a system of
alternating voltage
and current into
another system of
voltage and current
usually of different
values and at the same frequency for the purpose of transmitting
electrical power.
14
1) radiators
AUXILLARIES:
1)bushings
2)buchholz relay/oil surg relay
3)temprature indicators
4)oil level indicator
5)pressure relief device
6)marshalling box/control cubical
7)oil preservation system
8)conservators(gas sealed ,bellows/membrane sealed)
9)silica gel breather
15
16
BASIC PRINCIPLE
The transformer is based on two principles: first, that an
electric current can produce a magnetic field
(electromagnetism) and, second, that a changing magnetic field
within a coil of wire induces a voltage across the ends of the coil
(electromagnetic induction). By changing the current in the
primary coil, one changes the strength of its magnetic field;
since the secondary coil is wrapped around the same magnetic
field, a voltage is induced across the secondary
A current passing through the primary coil creates an
electromagnet; the current and its magnetic field are
proportional to one another, so that if the current changes, so
does the magnetic field. The primary and secondary coils are
wrapped around a core of very high magnetic permeability, such
as iron; this ensures that the magnetic field lines produced by
the primary current stay within the iron instead of "leaking"
out into the surrounding air and pass intact through the
secondary coil.
17
INDUCTION LAWS
The amount of voltage induced across the secondary coil may be
calculated from Faraday's law of induction, which states that,
where VS is the instantaneous voltage, NS is the number
of turns in the secondary coil and equals the total magnetic flux
through one turn of the coil. If the turns of the coil are oriented
perpendicular to the magnetic field lines, the flux is defined as the
product of the magnetic field strength B and the area A through
which it cuts
Since the same magnetic flux passes through both the primary and
secondary coils in an ideal transformer, the instantaneous voltage
across the primary winding equals
Taking the ratio of the two equations for VS and VP gives the basic
equation for stepping up or stepping down the voltage
18
CONSTRUCTION
Laminated steel core
Transformers for use at power or
audio frequencies typically have cores
made of high permeability silicon
steel. The steel has a permeability
many times that of free space, and
the core thus serves to greatly reduce
the magnetising current, and confine
the flux to a path which closely
couples the windings..Later designs
constructed the core by stacking layers of thin steel laminations, a
principle that has remained in use. Each lamination is insulated
from its neighbors by a thin non-conducting layer of insulation. The
universal transformer equation indicates a minimum crosssectional area for the core to avoid saturation
19
WINDINGS
The conducting material used
for the windings depends upon
the application, but in all
cases the individual turns must
be electrically insulated from
20
TRANSFORMER OIL
21
The oil helps cool the transformer. Because it also provides part of
the electrical insulation between internal live parts, transformer
oil must remain stable at high temperatures over an extended
period. To improve cooling of large power transformers, the oilfilled tank may have external radiators through which the oil
circulates by natural convection. Very large or high-power
transformers (with capacities of millions of watts) may also have
cooling fans, oil pumps, and even oil-to-water heat exchangers.
Large, high-voltage transformers undergo prolonged drying
processes, using electrical self-heating, the application of a
vacuum, or both to ensure that the transformer is completely free
of water vapor before the cooling oil is introduced. This helps
prevent corona formation and subsequent electrical breakdown
under load.
Oil filled transformers with conservators (an oil tank above the
transformer) tend to be equipped with Buchholz relays. These are
safety devices that can sense gas buildup inside the transformer (a
side effect of corona or an electric arc inside the windings) and
then switch off the transformer. Transformers without conservators
are usually equipped with sudden pressure relays, which perform a
similar function as the Buchholz relay.
22
Oil alternatives :
Today, nontoxic, stable silicone-based or fluorinated
hydrocarbons are used, where the added expense of a fireresistant liquid offsets additional building cost for a transformer
vault. Natural or synthetic Esters are becoming increasingly
common as alternative, to Naphthenic mineral oil too. Esters are
non toxic, readily biodegradable, and have higher flash points than
mineral oil. Prior to about 1970, polychlorinated biphenyl (PCB)
was often used as a dielectric fluid since it was not flammable
23
Most of the power transformwers use paper and oil as the main
form of insulation and during manufacture stringent efforts are
made to ensure that both are as dry as possible when the new
plant is set up.once in service the moisture content begins to
increase.excessive can put the life of the transformer at risk .it is
important to understand the source of this moisture .its effects and
the preventive measures.
SOURCE OF MOISTURE
Once in service the transformer is subjected to the following source
of moisture
External form the atmosphere
Internal form manufacture
Internal form cellulose ageing
24
25
BUCHHOLZ RELAY
In the field of electric power distribution and transmission, a
Buchholz relay, also called a gas relay or a sudden pressure
relay, is a safety device mounted on some oil-filled power
transformers and reactors, equipped with an external overhead
oil reservoir called a conservator. The Buchholz Relay is used on
conservator type oil preservation systems as a protective device
sensitive to events which occurs during dielectric failure inside
the equipment.
26
27
28
BUSHINGS
A bushing is a transformer component that insulates a high voltage
conductor passing through a metal enclosure. Bushings appear on
switchgear, transformers, circuit breakers and other high voltage
equipment.
Description
The bushing is hollow, allowing a conductor to pass along its centre
and connect at both ends to other equipment. Bushings are often
made of wet-process fired porcelain, and may be coated with a
semi-conducting glaze to assist in equalizing the electrical stress
along the length of the bushing.
The inside of the bushing may contain paper insulation and the
bushing is often filled with oil to provide additional insulation.
Bushings for medium-voltage and low-voltage apparatus may be
made of resins reinforced with paper. The use of polymer bushings
for high voltage applications is becoming more common..
29
SWITCHYARD EQUIPMENTS:
The term switchgear, used in association with the electric power
system, or grid, refers to the combination of electrical disconnects,
fuses and/or circuit breakers used to isolate electrical equipment.
Switchgear is used both to de-energize equipment to allow work to
be done and to clear faults downstream.
Typically switchgear in substations is located on both the high
voltage and the low voltage side of large power transformers. The
switchgear located on the low voltage side of the transformers in
distribution type substations, now are typically located in what is
called a Power Distribution Center (PDC). Inside this building are
typically smaller, medium-voltage (~15kV) circuit breakers feeding
the distribution system. Also contained inside these Power Control
Centers are various relays, meters, and other communication
equipment allowing for intelligent control of the substation.
A piece of switchgear may be a simple open air isolator or it may be
insulated by some other substance. An effective although more
costly form of switchgear is "gas insulated switchgear" (GIS), where
the conductors and contacts are insulated by pressurized (SF6)sulfur
hexafluoride gas. Another common type is oil insulated switchgear.
Circuit breakers are a special type of switchgear that are able to
interrupt fault currents. Their construction allows them to interrupt
fault currents of many hundreds or thousands of amps.
Lightning arrester
30
LIGHTNING ARRESTER
31
32
WIRE CABLES
Wire cables are use to transport the high voltage transmission
lines underground in case of some physical obstruction.
DESIGN:
In its most basic form the device consists of three parts:
34
PROTECTION :
A protective surge arrester/spark gap shall preferably be provided
to prevent break down of insulation by incoming surges and to limit
abnormal rise of terminal voltage of shunt capacitor, tuning
reactor, RF choke, etc. due to short circuit in transformer
secondary. The details of this arrangement (or alternative
arrangement) shall be furnished by Contractor for Employer's
review.
CVT SPECIFICATIONS:
35
Total burden -
100 MVA
Thermal burden
750 VA
Rated voltage
220/ 3^.5 kV
245 kV
Insulation level
460 kv/1050 kV
Rated freq
50 Hz
4881 pf
CURRENT TRANSFORMER
36
DESIGN:
The most common design of CT consists of
a length of wire wrapped many times
around an annular silicon steel ring passed
over the circuit being measured. The CT's
primary circuit therefore consists of a
single 'turn' of conductor, with a secondary
of many hundreds of turns.
The CT acts as a constant-current series
device with an apparent power burden a
fraction of that of the high voltage primary
circuit. Hence the primary circuit is largely
unaffected by the insertion of the CT.
Common secondaries are 1 or 5 amperes.
For example, a 4000:5 CT would provide an
output current of 5 amperes when the
primary was passing 4000 amperes. The
secondary winding can be single ratio or
multi ratio, with five taps being common
for multi ratio CTs
Current transformers can be used to supply information for
measuring power flows and the electrical inputs for the operation
of protective relays associated with the transmission and
distribution circuits or for power transformers. These current
transformers have the primary winding connected in series with the
37
CT SPECIFICATIONS:
Highest system:
Insulation level:
Rated primary current:
Rated STC:
Freq:
CT ratio:
245v
460/1050 kV
600 A
27 Ka for 1 sec
50 Hz
600-300/1/1/1/1
CIRCUIT BREAKERS
38
39
1.
2.
3.
4.
40
42
prevent trhe metal vapour reaching the envelope .In side there is a
moving and fixed contact the metalic bellows are made up of
stainless steel.
.
Gas blast applied on the arc must be able to cool it rapidly so that
gas temperature between the contacts is reduced from 20,000 K to
less than 2000 K in a few hundred microseconds, so that it is able
to withstand the transient recovery voltage that is applied across
the contacts after current interruption. Sulfur hexafluoride is
43
44
Rated freq-50 Hz
Rated normal current 3150 A
Rated closing voltage 220 V DC
Rated opening voltage 220 V DC
Gas pressure 6 kg/cm2
Relays:
45
so relays have two switch positions and they are double throw
(changeover) switches.
Relays allow one circuit to switch a second circuit which can be
completely separate from the first. For example a low voltage
battery circuit can use a relay to switch a 230V AC mains circuit.
There is no electrical connection inside the relay between the two
circuits, the link is magnetic and mechanical.
The coil of a relay passes a relatively large current, typically 30mA
for a 12V relay, but it can be as much as 100mA for relays designed
to operate from lower voltages. Most ICs (chips) cannot provide this
current and a transistor is usually used to amplify the small IC
current to the larger value required for the relay coil. The
maximum output current for the popular 555 timer IC is 200mA so
these devices can supply relay coils directly without amplification.
Relays are usuallly SPDT or DPDT but they can have many more sets
of switch contacts, for example relays with 4 sets of changeover
contacts are readily available. For further information about switch
contacts and the terms used to describe them please see the page
on switches.
Most relays are designed for PCB mounting but you can solder wires
directly to the pins providing you take care to avoid melting the
plastic case of the relay.
The supplier's catalogue should show you the relay's connections.
The coil will be obvious and it may be connected either way round.
Relay coils produce brief high voltage 'spikes' when they are
switched off and this can destroy transistors and ICs in the circuit.
To prevent damage you must connect a protection diode across the
relay coil.
46
Operation
When a current flows through the coil, the resulting magnetic field
attracts an armature that is mechanically linked to a moving
contact. The movement either makes or breaks a connection with a
fixed contact. When the current to the coil is switched off, the
armature is returned by a force approximately half as strong as the
magnetic force to its relaxed position. Usually this is a spring, but
gravity is also used commonly in industrial motor starters. Most
relays are manufactured to operate quickly. In a low voltage
application, this is to reduce noise. In a high voltage or high current
application, this is to reduce arcing.
47
Applications
Relays are used:
48
Overcurrent relay
An "Overcurrent Relay" is a type of protective relay which operates
when the load current exceeds a preset value. The ANSI Device
Designation Number is 50 for an Instantaneous OverCurrent (IOC),
51 for a Time OverCurrent (TOC). In a typical application the
overcurrent relay is used for overcurrent protection, connected to a
current transformer and calibrated to operate at or above a specific
current level. When the relay operates, one or more contacts will
operate and energize a trip coil in a Circuit Breaker and trip (open)
the Circuit Breaker.
49
Protective relay
A protective relay is a complex electromechanical apparatus, often
with more than one coil, designed to calculate operating conditions
on an electrical circuit and trip circuit breakers when a fault was
found. Unlike switching type relays with fixed and usually illdefined operating voltage thresholds and operating times,
protective relays had well-established, selectable, time/current (or
other operating parameter) curves. Such relays were very
elaborate, using arrays of induction disks, shaded-pole magnets,
operating and restraint coils, solenoid-type operators, telephonerelay style contacts, and phase-shifting networks to allow the relay
to respond to such conditions as over-current, over-voltage, reverse
power flow, over- and under- frequency, and even distance relays
that would trip for faults up to a certain distance away from a
substation but not beyond that point. An important transmission
line or generator unit would have had cubicles dedicated to
protection, with a score of individual electromechanical devices.
The various protective functions available on a given relay are
denoted by standard ANSI Device Numbers. For example, a relay
including function 51 would be a timed overcurrent protective
relay.
These protective relays provide various types of electrical
protection by detecting abnormal conditions and isolating them
from the rest of the electrical system by circuit breaker operation.
Such relays may be located at the service entrance or at major load
centers.
50
Distance relay
The most common form of feeder protection on high voltage
transmission systems is distance relay protection. Power lines have
set impedance per kilometre and using this value and comparing
voltage and current the distance to a fault can be determined. The
main types of distance relay protection schemes are
51
Ground (electricity)
In electrical engineering, the term ground or earth has several
meanings depending on the specific application areas. Ground is
the reference point in an electrical circuit from which other
voltages are measured, a common return path for electric
current (earth return or ground return), or a direct physical
connection to the Earth.
52
53
Power transmission
Some HVDC power transmission systems use the ground as second
conductor. This is especially common in schemes with submarine
cables as sea water is a good conductor. Buried grounding
electrodes are used to make the connection to the earth. The site of
these electrodes must be chosen very carefully in order to prevent
electrochemical corrosion on underground structures.
In Single Wire Earth Return (SWER) AC electrical distribution
systems, costs are saved by using just a single high voltage
conductor for the power grid, while routing the AC return current
through the earth. This system is mostly used in rural areas where
large earth currents will not otherwise cause hazards.
A particular concern in design of electrical substations is earth
potential rise. When very large fault currents are injected into the
earth, the area around the point of injection may rise to a high
potential with respect to distant points. This is due to the limited finite
conductivity of the layers of soil in the earth. The gradient of the
54
55
56
Ground mat
A ground mat or grounding mat is a flat, flexible pad used for
working on electrostatic sensitive devices. It is generally made of a
conductive plastic or metal mesh covered substrate which is
electrically attached to ground. This helps discharge any static
which a worker has built up, as well as any static on tools or
exposed components laid on the mat. It is used most commonly in
computer repair. Ground mats are also found on fuel trucks, which
are otherwise insulated from ground as they make physical contact
only with their (rubber and air) tires; obviously static discharge is
undesirable during fuel-transfer operations. Similarly, in aircraft
refueling, a ground cable connects the tanker (truck or airplane) to
the fuel-seeking craft to eliminate charge differences before fuel is
transferred.
In an electrical substation a ground mat is a mesh of conductive
material installed at places where a person would stand to operate
a switch or other apparatus; it is bonded to the local supporting
metal structure and to the handle of the switchgear, so that the
operator will not be exposed to a high differential voltage due to a
fault in the substation.
BATTERY BOX
Batteries are installed in substation to provide power to switching
components and to power the substation control equipment in
times of AC power loss. They require regular maintenance for
proper working .
57
Lead Acid Batteries are widely used for years, other alternative is
Nickel-cadmium battery
Electrochemistry
Each cell contains (in the charged state) electrodes of lead metal
(Pb) and lead (IV) dioxide (PbO2) in an electrolyte of about 33.5%
w/w (6 Molar) sulfuric acid (H2SO4). In the discharged state both
electrodes turn into lead(II) sulfate (PbSO4) and the electrolyte
loses its dissolved sulfuric acid and becomes primarily water. Due to
the freezing-point depression of water, as the battery discharges
and the concentration of sulfuric acid decreases, the electrolyte is
more likely to freeze.
The chemical reactions are (charged to discharged):
Anode (oxidation):
Cathode (reduction):
58
59