A LAB MANUAL ON

ELECTRICAL MACHINES LABORATORY - I


Subject Code: 15EEL38
(As per VTU Syllabus CBCS)

PREPARED BY
APPROVED BY

GOPINATH.B.L
A G SURESH

HOD EEE Dept.

15EEL 38 Electrical Machines 1 Laboratory Manual

BTL Institute of Technology EEE Dept.

PREFACE
The significance of the Electrical Machines Lab - I, is renowned in the
various fields of engineering applications. For an Electrical Engineer, it is
obligatory to have the practical ideas about the Electrical Machines. By this
perspective we have introduced a Laboratory manual cum Observation for
Electrical Machines Lab-I.
The manual uses the plan, cogent and simple language to explain the
fundamental aspects of Electrical Machines in practical. The manual prepared
very carefully with our level best. It gives all the steps in executing an
experiment. And validation by means of observation, Development of
theory/hypotheses, experimental validation

``

15EEL 38 Electrical Machines 1 Laboratory Manual

BTL Institute of Technology EEE Dept.

Laboratory Safety Rules


Read ALL of the following rules carefully, and remember them while working in the laboratory.
1. Never hurry. Haste causes many accidents.
2. Always see that power is connected to your equipment through a circuit breaker.
3. Connect the power source last. Disconnect the power source first.
4. Never make wiring changes on live circuits. Work deliberately and care-fully and check your work
as you proceed.
5. Before connecting the power, check your wiring carefully for agreement with the wiring diagram for
an accidental short-circuit and for loose connections.
6. Check out the supply voltage to make sure that is what you expect. For example: AC or DC, 230V,
OR 415V

``

7. Do not cause short-circuits or high currents arcs. Burn from arcs may be very severe even at a
distance of a few meters. Report all electrical burns to your instructor. Be careful to keep metallic
accessories of apparel or jewelry out of contact with live circuit parts and loose articles of clothing out
of moving machinery.
8. When using a multiple range meter always use the high range first to determine the feasibility of
using a lower range.
9. Check the current rating of all rheostats before use. Make sure that no current overload will occur as
the rheostat setting is changed.
10. Check the current rating of all rheostats before use. Make sure that no current overload will occur as
the rheostat setting is changed.
11. Never overload any electrical machinery by more than 125% of the rated voltage or current for more
than a few seconds.
12. Select ratings of a current coil (CC) and potential coil (PC) in a wattmeter properly before
connecting in a test circuit.
13. Do not permit a hot leg of a three phase 415V supply, or of a 230V supply to come in contact with
any grounded objects, as a dangerous short-circuits will result.

15EEL 38 Electrical Machines 1 Laboratory Manual

DOS & DONTS IN

BTL Institute of Technology EEE Dept.

THE LABORATORY

DOS:1) Proper dress has to be maintained while entering in the Lab. (Boys Tuck in with
apron and shoes, girls with apron)
2) All students should come to the Lab with necessary tools. (Cutting Pliers 6,
Insulation remover and phase tester)
3) Students should carry observation notes and record completed in all aspects.
4) Correct specifications of the equipment have to be mentioned in the circuit
diagram.
5) Student should be aware of operating equipment.
6) Students should be at their concerned experiment table, unnecessary moment is
restricted.
7) Student should follow the indent procedure to receive and deposit the equipment
from the Lab Store Room.
8) After completing the connections Students should verify the circuits by the Lab
Instructor.
9) The reading must be shown to the Lecturer In-Charge for verification.
`` 10) Students must ensure that all switches are in the OFF position, all the
connections are removed.
11) All patch cords and tools should be placed at their original positions.
DONTs:1) Dont come late to the Lab.
2) Dont enter into the Lab with Golden rings, bracelets and bangles.
3) Dont make or remove the connections with power ON.
4) Dont switch ON the supply without verifying by the Staff Member.
5) Dont switch OFF the machine with load.
6) Dont leave the lab without the permission of the Lecturer In-Charge.

15EEL 38 Electrical Machines 1 Laboratory Manual

``

15EEL 38 Electrical Machines 1 Laboratory Manual

BTL Institute of Technology EEE Dept.

BTL Institute of Technology EEE Dept.

INDEX
Sl No
1.
2.
3.
4.
5.
6.
7.
8.
9.

Contents
PREFACE
LABORATORY SAFETY RULES
DOS & DONTS
VTU SYLLABUS
INDEX
CERTIFICATE
INTRODUCTION
INSTRUCTION TO STUDENTS
LAB CYCLES

Page No
2
3
4
5
6
7
8
9
10

10.

OPEN CIRCUIT AND SHORT CIRCUIT TESTS ON SINGLE PHASE STEP


UP OR STEP DOWN TRANSFORMER AND PREDETERMINATION OF
(I)
EFFICIENCY AND REGULATION
(II)
CALCULATION OF PARAMETERS OF EQUIVALENT CIRCUIT

11

11.

SUMPNERS TEST ON SIMILAR TRANSFORMERS AND


DETERMINATION OF
COMBINED AND
INDIVIDUAL
TRANSFORMER EFFICIENCY.

15

12.

PARALLEL OPERATION OF TWO DISSIMILAR SINGLE-PHASE


TRANSFORMERS OF DIFFERENT KVA AND DETERMINATION OF
LOAD SHARING AND ANALYTICAL VERIFICATION GIVEN THE
SHORT CIRCUIT TEST DATA.

18

13.
``

14.
15.
16.
17.

POLARITY TEST AND CONNECTION OF 3 SINGLE-PHASE


TRANSFORMERS IN STAR DELTA AND DETERMINATION OF
EFFICIENCY AND REGULATION UNDER BALANCED
RESISTIVE LOAD.
COMPARISON OF PERFORMANCE OF 3 SINGLE-PHASE
TRANSFORMERS IN DELTA DELTA AND V-V (OPEN DELTA)
CONNECTION UNDER LOAD.
SCOTT CONNECTION WITH BALANCED AND UNBALANCED
LOADS.
SEPARATION OF HYSTERESIS AND EDDY CURRENT LOSSES
IN SINGLE PHASE TRANSFORMER.
VOLTAGE REGULATION OF AN ALTERNATOR BY EMF AND
MMF METHODS.

20

23
26
29
33

18.

VOLTAGE REGULATION OF AN ALTERNATOR BY ZPF METHOD.

38

19.

SLIP TEST MEASUREMENT OF DIRECT AND QUADRATURE


AXIS REACTANCE AND REDETERMINATION OF REGULATION
OF SALIENT POLE SYNCHRONOUS MACHINES.

40

20.

PERFORMANCE
OF
ASYNCHRONOUS
GENERATOR
CONNECTED TO INFINITE BUS, UNDER CONSTANT POWER
AND VARIABLE EXCITATION & VICE - VERSA.

43

21.
22.
23.

POWER ANGLE CURVE OF SYNCHRONOUS GENERATOR.

VIVA QUESTIONS
SAFETY & COMMON SYMBOLS

15EEL 38 Electrical Machines 1 Laboratory Manual

47
51
53

BTL Institute of Technology EEE Dept.

Department of Electrical and Electronics


Engineering

CERTIFICATE

``

This is to certify that this book is a bonafide record practical work


done in the Electrical Machines- 1 Laboratory in 3rd semester
ofyear during the year.......
Name:-
Roll. No. :-
Branch:-
Date:-

Signature of the Staff member


15EEL 38 Electrical Machines 1 Laboratory Manual

BTL Institute of Technology EEE Dept.

INTRODUCTION
A practical approach is probably the best approach to mastering a subject and gaining a clear insight.
ELECTRICAL MACHINES LABORATORY - I Sub Code: 15EEL38
Practical session covers those practical oriented Electrical AC Machines that are very essential for
the students to solidify their theoretical concepts. This workbook provides a communication bridge between
the theory and practical world of the Electrical Laboratory. The knowledge of these practical are very
essential for the engineering students. All of these practical are arranged on the modern trainer boards.
The program starts with courses of providing in-depth coverage of basic topics related to the field of
electrical machines such as Testing of transformers, rotating machines, ac power Generation. The program
then builds on the knowledge gained by the student through these basic courses to provide training
synchronous generator, and asynchronous generator technologies

This manual, teaches the basic concepts of three-phase transformer banks. Students are introduced to
the different characteristics of Single/three-phase transformer banks. They learn how to connect the
windings of three-phase transformer banks in wye or delta. Students are also determining the voltage,
current, and phase relationships between the primary windings and the secondary windings of three-phase
``
transformer banks of various configurations. They learn how to ensure proper phase relationships between

the phase windings. Students also verify the theory presented in the manual by performing circuit
measurements and calculations.

15EEL 38 Electrical Machines 1 Laboratory Manual

BTL Institute of Technology EEE Dept.

INSTRUCTIONS TO THE STUDENTS


1. WEAR SHOES COMPULSORILY
2. SHIRTS SHOULD BE TUCKED IN
3. GIRLS SHOULD PROTECT THEIR HAIR
4. DO NOT ALLOW CHAINS TO HANG
5. DO NOT LEAN OVER ROTATING MACHINERY
6. ENERGIZE THE CIRCUIT ONLY AFTER GETTING APPROVAL FROM THE FACULTYINCHARGE
7. MAKE SURE THAT THE CORRECT SWITCH HAS BEEN SWITCHED ON/OFF BEFORE/AFTER
THE EXPERIMENT.
MAKING CONNECTIONS
Make sure that the supply is OFF.
Meters should be positioned properly.
Do not connect more than one wire to each terminal of ammeters & voltmeters.
Make series connections before parallel connections.
All the connections should be tight.
Get the connections checked before switching ON.
Check the position of rheostats, autotransformers, switches before switching ON.
Never exceed the permissible values of current or voltage.
While conducting brake test, pour water on the brake drum to avoid overheating.
Show the readings to the faculty-in-charge before switching off.
ROUGH RECORD
1. Write Name of the experiment with number & date, aim, apparatus required, neat circuit diagram,
tabulations, sample calculations (for one set of readings showing the substitution of the values) and results.
No need to write principle or procedure.
``
2. Take at least six sets of readings, if possible. Each student in a group should do sample calculations for
different sets.
3. Get signature of the faculty-in-charge after completing the rough record.
FAIR RECORD
1. Write the name of the experiment on the top of the right side in capital letters
2. Experiment Number & date should be written at the top.
3. Each record should contain the following on the right side
Aim of the experiment
Apparatus required
Principle
Procedure
Sample Calculation (on the left side if possible; if calculations are too long, write onright side so that no
pages on the right side are left blank) Result (at the end)
4. On left side
Neat circuit diagram with PEN
Name plate details/specifications
Tabulations
Sample Calculation (on the left side if possible; if calculations are too long, write on the right side so that
no pages on the right side are left blank)
Graph (draw with PEN if possible; use different colors for different graphs on the same graph sheet).
DO EXPERIMENT TODAY; SUBMIT ROUGH RECORD IN THE NEXT CLASS & FAIR
RECORD IN THE THIRD CLASS.
15EEL 38 Electrical Machines 1 Laboratory Manual

10

BTL Institute of Technology EEE Dept.

ELECTRICAL MACHINES LABORATORY - I Sub Code: 15EEL38

LAB CYCLE-1
1

Open Circuit and Short circuit tests on single phase step up or step down transformer and predetermination of
(i) Efficiency and regulation (ii) Calculation of parameters of equivalent circuit.

Sumpners test on similar transformers and determination of combined and individual transformer efficiency.

Parallel operation of two dissimilar single-phase transformers of different kVA and determination of load
sharing and analytical verification given the Short circuit test data.

Polarity test and connection of 3 single-phase transformers in star delta and determination of efficiency and
regulation under balanced resistive load.

Comparison of performance of 3 single-phase transformers in delta delta and Y Y (open delta) connection
under load.

Scott connection with balanced and unbalanced loads.

Separation of hysteresis and eddy current losses in single phase transformer.

LAB CYCLE-2
8
`` 9

Voltage regulation of an alternator by EMF and MMF methods.


Voltage regulation of an alternator by ZPF method.

10

Slip test Measurement of direct and quadrature axis reactance and predetermination of Regulation of salient
pole synchronous machines.

11

Performance of synchronous generator connected to infinite bus, under constant power and variable excitation
& vice - versa.

12

Power angle curve of synchronous generator.

15EEL 38 Electrical Machines 1 Laboratory Manual

11

BTL Institute of Technology EEE Dept.

EXPERIMENT NO:-01

DATE:

O.C. TEST S.C. TEST & LOAD TEST ON A SINGLE PHASE TRANSFORMER.
Objective:
To determine the iron losses, copper losses and efficiency of a transformer at any load.
Apparatus:
Sl. No.
1
2
3
4
5

Instruments
0-1 Amps Ammeter
0-5 Amps Ammeter
0-300 Volts Voltmeter
0-200 Watts L.P.F. type Wattmeter
0-3.0 KW U.P.F. type Wattmeter

Qty.
01
01
01
01
01

Transformer Ratings:
Power: 1 KVA, Primary/Secondary :230/230 Volts. Max Current Rating : 4.43 Amps.
Circuit Diagram:

``

Procedure:
FOR O.C. TEST
1) Connect the circuit as shown.
2) Ensure that the dimmerstat Position is at zero.
3) Switch on the single phase AC. Supply.
4) Apply rated voltage of 230V, to the primary side of transformer.
5) Note the ammeter, voltmeter and wattmeter readings.

15EEL 38 Electrical Machines 1 Laboratory Manual

12

BTL Institute of Technology EEE Dept.

FOR S.C. TEST


1) Connect the circuit as shown.
2) Ensure that the dimmerstat position is at 0 (zero).
3) Switch on the single phase AC. Supply.
4) Slowly increase the output voltage of the dimmerstat till the ammeter on
primary side shows rated current of 4.35 amp.
5) Note the ammeter, voltmeter & wattmeter readings.

Precautions:
1)
2)
3)
4)
5)
6)

All the connections should be perfectly tight.


Supply should not be switched ON until& unless the connections are checked by the instructor.
Do not bend while taking the readings
No loose wires should lie on the work table.
Thick wires should be used for current circuit and flexible wires for voltage circuits.
The multiplying factor of wattmeter should be correctly used.

Observations:
FOR O.C.TEST (Read on primary side.)
Rated input Voltage
No load current
No load power
V0
I0
W0
230V

FOR S.C. TEST (Read on primary side)


Short circuit voltage
Rated primary current
Vsc
(i.e full load value)
Isc
``

Short circuit power


Wsc

4.35amp

Calculations:
FOR O.C. TEST
No load power factor =cos<Do = Wo / (Vo Io) Magnetising
component of Io = I = Io sin<Do amps.
Core loss component of Io = Ic = Io cos<Do amps.
Core loss resistance Ro = Vo/ Ic ohm.
Magnetising reactance Xo = Vo/ I ohms. FOR S.C. TEST
Short circuit power factor cos<Dsc = Wsc/ (Vsc Isc) Short circuit
impedence Zsc =Vsc / Isc Q
Short circuit resistance Rsc = Wsc / Isc2 Q
Short circuit reactance Xsc = -- Zsc2-Rsc2
Copper loss in transformer at full load =Wsc watts.
Copper loss in transformer at half full load = Wsc/4 watts.

15EEL 38 Electrical Machines 1 Laboratory Manual

13

BTL Institute of Technology EEE Dept.

EFFICIENCIES:
1) At full load and at 0.8 power factor
Full load kVA x103 x cos<D x 100
=
Full load KVA x103x cos<D +core loss +copper loss at full load
2)

All half full load and U.P.F.


Half load KVA x 103x cos<D x100

=
Half load KVA x 103 x cos<D + core loss + copper loss at half load

``

REGULATIONS:
1) At full load and 0.8 power factor lagging.
Voltage drop = Isc (Rsc cos<D + Xsc sin<D)
% Regulation =
Voltage drop x100
Rated primary voltage (Vo)
2) At full load and 0.8 power factor leading.
Voltage drop = Isc (Rsc cos<D Xsc sin<D)
Voltage drop x100
% Regulation =
Rated primary voltage (Vo)
3) At full load and U.P.F.
Voltage drop = Isc Rsc cos<D
% Regulation = Voltage drop x100
Rated primary voltage (Vo)

15EEL 38 Electrical Machines 1 Laboratory Manual

14

BTL Institute of Technology EEE Dept.

Equivalent Circuit:
Draw simplified equivalent circuit showing calculated values of all parameters on it.

Result: -

``

Full load efficiency at 0.8 p.f. =


Full load efficiency at U.P.F. =
Full load regulation at 0.8 lagging p.f. =
Full load regulation at 0.8 leading p.f. = Full load
regulation at U.P.F. =
Ro =
; Xo =
Rsc =
; Xsc =

Viva Questions: Q.1. What is the significance of O.C. & S.C. test?
Q.2. Why h.v. winding is kept open during O.C. test and 1.v. winding is shorted during S.C. test in
case of large transformers?
Q.3. In O.C. test, a voltmeter is connected across secondary winding and still it is
called as O.C. test. Why?
Q.4. What will happen if dc supply instead of ac supply is applied to a transformer? Q.5. Which is the
alternate method for finding efficiency and regulation of a
transformer other than O.C. & S.C. tests ? What are their advantages over each
other?
Q.6. What is the importance of equivalent circuit?
Q.7. Why regulation of transformer is negative for leading p.f. load?
Q.8. The wattmeter reading during O.C. test is considered as core loss while wattmeter reading during
S.C. test is considered as copper loss Justify

15EEL 38 Electrical Machines 1 Laboratory Manual

15

EXPERIMENT NO:-02

BTL Institute of Technology EEE Dept.


DATE:

Sumpners Test
Objective : To predetermine the efficiency, regulation and equivalent circuit of a given pair of
identical single - phase transformers by conducting Sumpner's test.
Name plate details of the two identical transformers:
Primary voltage : 230 Volts
Secondary voltage: 230 Volts
Primary current : 4.34 Amps
Secondary current 4.34 Amps Power
(Burden) : 1 KVA
Frequency:
50 Hz.
Apparatus:
Digital voltmeter,0 to 1000Volts
02
Digital ammeter, 0 to l0 Amps
02
wattmeter, 0 to 300 Watts
02
Digital temperature indicator, 0 to 100
01
D
Theory:
The efficiency of a transformer can be predetermined by conducting o.c. and s.c. tests. But the
rise in temperature can be found only by conducting the actual load test. It is difficult io conduct the
actual load test for large transformers. [n case of Sumpners test the efficiency, regulation and rise in
temperature can be obtained with small amount of power consumption.
In Sumpner's test, the two primary windings of the identical transformers are connected in parallel
across the supply and the two secondarys are connected in series with their polarities in opposition. One
digital wattmeter (L.P.F. type), one voltmeter and one ammeter are connected
at primary side. One digital wattmeter (U.P.F: type), one voltmeter and one ammeter are connected at
secondary side. If primaries are energized then the voltage across the two secondaries will be zero since
both the transformers are identical transformers.
The power input to the transformers at no-load is indicated by the wattmeter on the primary
side.
This
power is, equal-to the iron losses of the two transformers. An auto-transformer is connected
``
in series with the two secondarys. A small voltage is injected in the secondary circuit from a separate ac
source. It will circulate a current in the secondary side since the secondarys are in opposition, the
secondary current will cause primary current in opposite directions so that the reading of wattmeter on
primary is not affected and it will indicate the iron losses of the two transformers. The auto-transformer is
adjusted till the full load current flows in the secondary side of the transformer. At full load current the
wattmeter on the secondary side indicates the full load copper losses of the two transformers.
Procedure:
* Make all the connections as per the circuit diagram shown in fig .Z.Z.
* Keep the switch 's' open on the secondary side of the transformer.
* Keep the auto-transformer at zero position and disconnect the supply to
the auto transformer.
* Apply the normal voltage of 230Volts to the primary side.
* Check the voltmeter reading across the switch. If it reads zero, it means the secondarys are
connected in opposition. If the voltmeter reads twice the secondary rated voltage then the connections
should be reversed on the secondary side.
*
lf voltmeter reads zero close the switch .S'.
* Connect the supply to the auto-transformer and energize the secondary circuit and adjust the auto
transformer till the ammeter on the secondary side reads the rated current (4.82A).
* Record the readings of the meters on both the primary and secondary
sides.
* Calculate Req , xeq , regulation and efficiency of the transformer 0.8 pf lag, 0.8pf lead and upf for
full

15EEL 38 Electrical Machines 1 Laboratory Manual

16

Procedure:

``

BTL Institute of Technology EEE Dept.

1) Make the connections as shown in circuit diagram.


2) Keep switches S2 & S3 open and the dimmerstats at zero position.
3) Switch ON the supply and check the correctness of polarities of the two transformers.
If V2 = 0 then polarities of connected transformers are correct i.e. connections are back to back
and emf induced in secondarys are in phase opposition but if V2 = 2xKxV1, then secondary
emfs are in phase, in that case change the polarities of any one secondary winding.
4) Note down the readings of V1, I1 and W1
5) Now close switch S and increase dimmerstat output voltage gradually so that full
load current flows through secondary windings.
6) Note down V2 , I2 and W2. While doing so , the values shown by V1, I1 and W1 should not
deviate from their earlier readings.

Observation Table:
SR.
No.

Primary
voltage
V1

Primary
current
I2

Primary
power
Iron loss W1

Secondary
voltage
V2

Secondary
Current
I2

Calculations:
Wi = W1 / 2
Iron loss per transformer
Copper loss per transformer Wcu = W2 / 2
% Efficiency

Out put Power


= ------------------------------ x 100
Output Power + Losses

kVA x Cos <D


% lJ = ------------------------------------------------ x 100
kVA x Cos <D + Iron loss + Cu. Loss

15EEL 38 Electrical Machines 1 Laboratory Manual

Secondary
power
Cu. Loss W2

17

BTL Institute of Technology EEE Dept.

With the help of above equation, calculate efficiency at


1. Full load , UPF
2. Half full load and 0.8 p.f. lagging.

Results:

It is found that,
i) % Efficiency at F.L. & unity power factor =
ii) % Efficiency at half full load & 0.8 power factor (lag.) =

Viva Questions:
1.
2.
3.
4.
5.

What is the condition to be satisfied by the two transformers to be tested using this method?
What is the main advantage of this test?
Other than losses and efficiency, what else can be determined from this test?
How are the full load conditions simulated?
How are the losses separated?

``

15EEL 38 Electrical Machines 1 Laboratory Manual

18

BTL Institute of Technology EEE Dept.

EXPERIMENT NO:- 03

DATE:

Parallel Operation Of Two Single Phase Transformers


AIM:To operate the given two 2KVA,and 1 KVA 230/230 V single phase Transformers in parallel and
study the load sharing between them when supplying resistive load .
NAME PLATE DETAILS:
1 - TRANSFORMERs
T/F

T/F-1
HV side
LV side

T/F-2
HV side LV side

Rated power
Rated voltage
Rated current
Frequency
APPARATURS REQUIRED:

``

SL.
NO

Name of the
Apparatus

Type

Ammeter

MI

Ammeter

MI

Voltmeter

MI

Voltmeter

MI

Wattmeter

EDM(LPF)

Wattmeter

EDM(UPF)

Dimmerstat

Range

Quantity

THEORY

Transformers may be connected in parallel to supply currents greater than rated for each transformer. Two
requirements must be satisfied:
1) The windings to be connected in parallel must have identical output ratings;
2) The windings to be connected in parallel must have identical polarities.
Severe damage may be made to circuitry if these requirements are not satisfied , KVA Ratings may vary.
Two transformers with different kVAs, same percent impedances, are connected to one common bus. In this
situation, the current division causes each transformer to carry its rated load. There will be no circulating
currents because the voltages (turn ratios) are the same.
PROCEDURE :a) Make connections as for circuit diagram, keep the load switch and switch S open .
b) Switch on the mains , see the volt meter reading of V1 , if this reading is
460V(double the secondary voltage of both the machines) then switch of and inter
change the connections of secondary of any transformer . if reads zero then the
switch S can be closed , this way the polarities can be checked since wrong polarity
will short circuit the transformers if operated in parallel .
c) Close switch S and then close the load switch.
15EEL 38 Electrical Machines 1 Laboratory Manual

19

BTL Institute of Technology EEE Dept.

d) For various values of load current , record terminal voltage ,current in two secondarys
power supply by the two transformers and the total power,(do not exceed 10 A
for total current)
e) Switch of load and switch of main.
f) Determine the equivalent reactances and resistances of both transformers referred
to HV winding by SC test

``

CAULATIONS :-For a given load current IL at an angle the current and power
supply by each transformer can be found out by the following formula
IA= (IL)X{(ZB)/(ZA+ZB)} IB = (IL)X{(ZA)/(ZA+ZB)}
If S is the load KVA, then the KVA shared by the transformers can be found out by
SA= (S)X{(ZB)/(ZA+ZB)} SB = (S)X{(ZA)/(ZA+ZB)}
Check the result obtained with the Theoretical calculations .
RESULTS:a) With the help of phasor diagram verify if IA = IB= I.
b) Check if the load shared is proportional to the KVA capacities of the respective transformers
c) From the results state if RA /XA =RB /XB
15EEL 38 Electrical Machines 1 Laboratory Manual

20

BTL Institute of Technology EEE Dept.

EXPERIMENT NO:- 04

DATE:

STAR-DELTA CONNECTION POLARITY TEST AND STAR-DELTA CONNECTION


Aim: To test the polarity of three single phase transformers and to determine the Efficiency and Regulation
for Star-Delta connection for balanced and Unbalanced loading (UPF)
Apparatus Required:
Sl.
No.
1

Particulars

Ranges

Quantity

Ammeter (MI)

0-2.5/5 A
0-10 A
500V, 1 / 2 A
250V,2.5 A
0-500 V
0-250 V

2
2
2
2
2
2

--

Wattmeter
(UPF)

Voltmeter (MI)

Digital
Multimeter

Procedure for 3 phase Transformer Connection:


* Polarity Testing:
1) Connections are made as shown in the circuit diagrams(1).
2) Keeping load switches open and auto transformer at zero position, the supply switch is closed.
3) A small voltage (say 50 v) is applied to the primary by gradually varying single phase auto-transformer and the
``
reading of digital multimeter is noted down.
4) The single phase auto-transformer is brought back to its initial zero output position and the supply switch is
opened
5) Connections are made as shown in the circuit diagram(2).
6) Above procedure is repeated.

Three 1-Phase Transformer Connection ( Star-Delta)


1) Connections are made as shown in the Circuit diagram(3)
2) Keeping the load minimum and the 3-phase auto-transformer at zero output voltage position supply switch is
closed.
3) Rated voltage is applied by gradually varying the 3-phase auto-transformer.
4) Gradually the load is applied and at each step all the meter readings are noted down.
5) Load is applied until the rated current of transformer reached.
Gradually the load is decreased, 3-phase auto-transformer is brought back to its initial zero output voltage position
and the supply switch is opened.

15EEL 38 Electrical Machines 1 Laboratory Manual

21

CIRCUIT DIAGRAM
``

15EEL 38 Electrical Machines 1 Laboratory Manual

BTL Institute of Technology EEE Dept.

22

BTL Institute of Technology EEE Dept.

Observation Table:
No-load secondary voltage E2 = ---------- Volts
Sr.No. I1Amp V1 Volts
W1 Watts I 2 Amp
1
2
3
4
5

V2 Volts

W2 Watts

% Reg

Calculations:
O/ Power W2
% = -------------------- x 100
I/P power W1
No load voltage (E2) voltage at load (V2)
% Reg = ---------------------------------------------------------- x 100
No load voltage (E2)

Graph:

Plot the graph output Power Vs efficiency.

Precautions:

``

1)
2)
3)
4)
5)
6)

All the connection should be perfectly tight.


Supply should not be switched ON unstill & unless the connection are checked by the teacher.
Do not bend while taking the readings.
No loose wire should lie on the work-table.
Thick wire should be used for current circuit and flexible wires for voltage circuits.
The multiplying factor of wattmeter should be correctly noted.

Result:

The % efficiency & regulation of transformer at full load condition is found as follows.
Percentage efficiency = ------------------%
Percentage regulation = ------------------%

Conclusion:

Transformer efficiency initially increases as the load on transformer is increased.


After maximum efficiency if we increase the load further, the efficiency of transformer reduces.
Also terminal voltage reduces as the load is increased

Viva Questions:
1. What is the condition for max efficiency?
2. What is the condition for zero voltage regulation?
3. Which is the other method of finding efficiency and regulation?
4. Draw phasor diagram of transformer at full load and 0.5 p.f. lagging.
5. Draw phasor diagram of transformer at full load and 0.5 p.f. leading.

15EEL 38 Electrical Machines 1 Laboratory Manual

% lJ

23

BTL Institute of Technology EEE Dept.

EXPERIMENT NO:-05

DATE:

AIM:

Comparison Performance of 3 Single-Phase Transformers in Delta Delta and V - V (Open Delta)


Connection Under Load.

Open-Delta or V-V Connection (Theory)


If one of the transformers of a - is removed and 3- phase supply is connected to the primaries as
shown in Fig: A1 then 3 equal 3-phase v o l t a g e s w i l l b e available at the secondary terminals on noload.
It is employed:
1. When the three phase load is too small to warrant the installation of full three-phase transformer bank.
2. When one of the transformers in a - bank is disabled, so that service is continued although at reduced
capacity, till the faculty transformer is repaired or a new one is sustained.
3. When it is anticipated that in future the load will increase necessitating the closing of open delta.

- capacity = 3VL.IL= 3VL.( 3IS)=3VLIS


In Fig: A2 it is obvious that when - bank becomes V-V bank, the secondary line current IL becomes
equal to the secondary phase current IS.
V-V capacity = 3VL.IL=3VL.IS (Since line current and phase current are equal)

``

It means that the capacity of V-V transformer is 57.7 %( or 1/3 times) of the capacity of - conn,
The disadvantages of V-V connection are:
1. The average power factor at which the V-bank operates is less than that of the load. his power
factor is actually 86.6 of the balanced load power factor.
2. Secondary terminal voltages tend to become unbalanced to a great extent when the load is
increased, this happens even when the load is perfectly balanced.

Fig A1

15EEL 38 Electrical Machines 1 Laboratory Manual

Fig A2

24

BTL Institute of Technology EEE Dept.

``

Observation Table - for Balanced Load:


No-load secondary voltage E2 = ---------- Volts
Sr.No. I1Amp V1 Volts
W1 Watts I 2 Amp
1
2
3
4
5

15EEL 38 Electrical Machines 1 Laboratory Manual

V2 Volts

W2 Watts

% Reg

% lJ

25

BTL Institute of Technology EEE Dept.

Observation Table V V for Balanced Load:


No-load secondary voltage E2 = ---------- Volts
Sr.No. I1Amp V1 Volts
W1 Watts I 2 Amp
1
2
3
4
5

V2 Volts

W2 Watts

% Reg

% lJ

Calculations:
O/ Power W2
% = -------------------- x 100
I/P power W1
No load voltage (E2) voltage at load (V2)
% Reg = ---------------------------------------------------------- x 100
No load voltage (E2)

CONCLUSION
You set up a three phase transformer in the open configuration and observed that it supplies a 3phase
load with voltages and currents in the proper phase relationships. You also demonstrated that load power
must be reduced by 57.7% (1/3) to avoid exceeding the current rating of the phase windings

``

15EEL 38 Electrical Machines 1 Laboratory Manual

26

BTL Institute of Technology EEE Dept.

EXPERIMENT NO: 06

DATE:

SCOTT CONNECTION
AIM : To convert three phase system to two phase system with the help of scott Connection
NAME PLATE DETAILS:

T/F-1

T/F

HV side

T/F-2

LV side

HV side

LV side

Rated power
Rated voltage
Rated current
Frequency
APPARATURS REQUIRED:

``

SL.
NO

Name of the
Apparatus

Type

Ammeter

MI

Ammeter

MI

Voltmeter

MI

Voltmeter

MI

Dimmer stat

--

Range

Quantity

THEORY :Phase conversion from three to two phase is needed in special cases, such as in
supplying 2-phase electric arc furnaces.
The concept of 3/2-phase conversion follows from the voltage phasor diagram of balanced 3phase supply shown in Fig 1. If the point M midway VBC could be located , then VAM leads VBC by
90o. A 2-phase supply could thus be obtained by means of transformers; one connected across AM,
called the teaser transformer and the other connected across the
lines B and C. since VAM= (3/2) VBC , the transformer primaries must have 3 N1/2 (teaser) and N1
turns; this would mean equal voltage/turn in each transformer. A balanced 2-phase supply could then be
easily obtained by having both secondaries with equal number of turns, N2. The point M is located
midway on the primary of the transformer connected across the lines B and C. The connection of two
such transformers, known as the Scott connection, is
shown in Fig. 1(a), while the phasor diagram of the 2-phase supply on the secondary side is shown
in Fig. 1(c).
The neutral point on the 3-phase side, if required, could be located at the point N
which divides the primary winding of the tertiary in the ratio 1 : 2 (refer Fig.)

15EEL 38 Electrical Machines 1 Laboratory Manual

27

BTL Institute of Technology EEE Dept.

Theory: It should cover the following.

``

1. Explanation and mathematical proof of how a balanced two-phase supply can be obtained by using Scott
connection.
2. Phasor diagram illustrating the phase quadrature between the secondary voltages of the two transformers.

Procedure:
1.
2.
3.
4.
5.

Connect the circuit as shown.


Use 86.6% tapping for teaser transformer and 50% tapping for main transformer.
Keep both loads zero
Switch on the 3-ph. supply and take the readings.
Vary the loads as per given in observation table and take the readings

Observation Table:
[A]

FOR BALANCED LOAD


S. Load condition
No.
1.
No load
2.

Teaser transformer
I1T
I2T
V1T

1kW load on
both
transformers

15EEL 38 Electrical Machines 1 Laboratory Manual

I1M

Main transformer
I2M
V1M
V2M

28

[B]

BTL Institute of Technology EEE Dept.

FOR UNBALANCED LOAD


S. Load condition
No.
1.
1kW load on

Teaser transformer
I1T
I2T
V1T

I1M

Main transformer
I2M
V1M
V2M

Teaser
transformer
2.

1kW load on
Main
transformer

Calculations:

Conclusion:
The 3 Phase to two phase conversion was verified. i.e. 3 phase system can be converted in to two
phase system using Scott-connections.

Viva Questions:

``

1) Is it possible to obtain a 3- phase a.c. supply from 2 phase a.c. supply by using Scott-connection ?
2) Where dose the Scott-connection find its use?
3) If the two transformers used in Scott. Connection are identical, then how many primary turns of the teaser
transformer are actually used?
4) What is the ratio of number of turns on the primaries of teaser transformer in case of Scott-connection?
5) Are the two transformers connected for Scott-connection coupled magnetically?
6) Do you know any other method of conversion of 3-phese a.c. supply from 2-phese a.c. supply?

15EEL 38 Electrical Machines 1 Laboratory Manual

29

EXPERIMENT NO: 07

BTL Institute of Technology EEE Dept.


DATE:

SEPARATION OF EDDY CURRENT AND HYSTERESIS LOSSES


Objectives
To separate the eddy-current and hysteresis losses at various frequencies and flux densities using the Epstein Core
Loss Testing equipment.
Equipment
One low-power-factor (LPF) wattmeter from the stockroom.
Two digital multimeters from the stockroom.
One Epstein piece of test equipment. (It is mounted on a 3 ft3 ft slideequipped square platform stored in a cabinet and weighs 22 lbs.)
Single Phase Variac. (Of cylindrical shape, it weighs about 15 lbs, and is about 10 inches in diameter and about
12 inches tall.)
References
M. I. T. Sta, Magnetic Circuits and Transformers, pp. 144-154, John Wiley and Sons, 1985.
Vincent Del Toro, Basic Electric Machines, pp. 34-38, Prentice Hall, 1990.
Background
Designers of electrical machines must know the magnetic characteristics of the material they use in order to predict
the performance of their finished products. In this experiment core losses resulting from eddy currents and hysteresis
in steel sheets will be measured. The Epstein test frame is a special one-to-one transformer having provisions for
inserting the sample where it serves as a core. The testing procedure is specified by the American Society for Testing
Materials (ASTM).
``
Description of the Apparatus
The windings are on four sections of hollow square fiber, each 1.57 1.57 inches square and about 17.25 inches long.
Each section is wound with 150 turns of No. 18 wire. These turns are wound parallel to each other and in the same
plane so that the primary and secondary turns lie alternately adjacent to each other in order to improve their magnetic
coupling. The core material used is Armco 6M (USS Transformer 66).
The four sections are arranged to form a square. Primary turns on all sections are connected in series. The
secondary turns are also connected in series.
The sample to be tested consists of 10 kg (22 lbs) of strips 3 cm wide and 59 cm long. One half of the sample is
cut with the grain and the other half is cut across the grain. Four equal bundles are made of the specimen and each
bundle is tightly taped and placed in a section of the winding. The four ends are then butted together in the form of a
square with a piece of 0.004 inch thick paper in each joint, and all joints made as tight as possible.
Because of the tight coupling between the primary and secondary coils, the voltage induced in them by the AC
magnetic flux is the same. Since the primary winding carries the current which establishes the magnetic flux in the
core, the voltage applied to the primary winding includes the ohmic voltage drop due to the resistance of that winding.
The secondary winding, on the other hand, is open-circuited; hence, its terminal voltage is equal to the induced
voltage. The

15EEL 38 Electrical Machines 1 Laboratory Manual

30

BTL Institute of Technology EEE Dept.

``

where Kh and Ke are constants related to the material of the transformer core and its volume.
In (2.13) we see that if (W=f) is plotted against f for fixed Bm, a straight line is obtained whose slope is KeBm and yaxis intercept KhBmn. The hysteresis power loss for that value of Bm is then obtained by multiplying the y-intercept by
the frequency. The corresponding eddy-current loss is the slope multiplied by the frequency squared. The procedure is
repeated for each value of Bm.
To obtain the value of Kh, the logarithmic values of KhBmn obtained above are plotted against log Bm. The slope of
the resulting straight line is n and its y-intercept is log Kh. Thus Kh and n can be obtained. Similarly, by plotting log
KeBm2 against log Bm as a straight line of slope 2, log Ke can be obtained and, hence, Ke.
An alternator-dc motor set is used as a variable frequency AC voltage supply. The frequency can be changed by
varying the motor speed. The magnitude of voltage can be altered by varying the alternator field current.
Note: Only the instructor can change the frequency and the maximum AC voltage. The students can then obtain
fractions of the supplied voltage by turning the single-phase variac.

Eddy Current and Hysteresis Losses


1. Complete table 2.1 using (2.10).
2. Connect the circuit as shown in figure 2.1.
3. Connect the power supply from the bench panel to the INPUT of the single phase variac and connect the OUTPUT of the variac to
the circuit.

4. Wait for the instructor to adjust the frequency and maximum output voltage available for your panel.
5. Adjust the variac to obtain voltages Es as calculated in table 2.1. For each applied voltage, measure and record

Es and W in table 2.2

15EEL 38 Electrical Machines 1 Laboratory Manual

31

BTL Institute of Technology EEE Dept.

6. Perform the previous steps for frequencies of 30, 40, 50 and 60 hertz.

``

Report
1. Plot a graph of kg core loss (W/10), against the frequency f at dierent flux densities
Bm on the same graph.
2. Separate the Eddy-Current Pe and hysteresis Ph losses at dierent flux densities Bm and
frequencies f. Complete table 2.3.
3. Plot graphs for Pe and Ph against the frequencies for dierent flux densities on the
same graph.
Discussion Questions
1. Discuss how eddy-current losses and hysteresis losses can be reduced in a transformer
core.
2. Using the hysteresis loss data, compute the value for the constant n.
3. Explain why the wattmeter voltage coil must be connected across the secondary winding terminals

15EEL 38 Electrical Machines 1 Laboratory Manual

32

``

15EEL 38 Electrical Machines 1 Laboratory Manual

BTL Institute of Technology EEE Dept.

33

EXPERIMENT NO:-08

BTL Institute of Technology EEE Dept.


DATE:

REGULATION OF ALTERNATOR BY EMF AND MMF METHODS


Aim:
To pre-determine the voltage regulation of an alternator by using EMF and MMF methods.
Apparatus Required:

``

Precautions:
1. The Motor field rheostat must be kept at the minimum resistance position at the time of starting.
2. The generator field rheostat must be kept at the maximum resistance position.
3. Three point starter should be kept at the off position initially.
Procedure:
Open Circuit Test:
1. Give the connections as per the circuit diagram.
2. Close the DPST switch on the supply side.
3. The speed of DC motor is adjusted to rated speed by using the motor field rheostat.
4. Keeping the TPST switch open on alternator side vary the alternator field current in convenient steps till
rated field current of alternator.
5. Note the corresponding values of alternator field current and alternator voltage.
6. Bring the alternator field rheostat to the original position.

15EEL 38 Electrical Machines 1 Laboratory Manual

34

BTL Institute of Technology EEE Dept.

Short Circuit Test:


1. The same circuit is used.
2. The rotor TPST switch is closed.
3. The field current of the alternator is slowly increased from zero to the rated current of the alternator by
adjusting the field rheostat of the alternator.
4. The field current corresponding to the rated current of the alternator is alone noted in tabular column.
5. Reduce the field current of the alternator to zero.
6. Now open all the switches.
Armature resistance test:
1. Connections are made as per the circuit diagram.
2. The control resistance is initially kept at either maximum resistance or open position.
3. Observing the precautions the DPST switch is closed
4. The readings of ammeter and voltmeter are noted.
5. The ratio of V to I gives the value of armature resistance (R ).
a

Circuit diagram:

``

15EEL 38 Electrical Machines 1 Laboratory Manual

35

Regulation of alternator by EMF and MMF method

``

15EEL 38 Electrical Machines 1 Laboratory Manual

BTL Institute of Technology EEE Dept.

36

BTL Institute of Technology EEE Dept.

Model calculation:

HOW TO DRAW THE GRAPH FOR EMF METHOD:


i) Draw the open circuit characteristics curve (V vs. If).
ii) Draw the short circuit characteristics curve (short circuit current Vs If).
iii) From the graph find the open circuit voltage per phase ( E1(ph)) for the rated short circuit current ( Isc).
iv) By using respective formulae find the Zs, Xs, Eo and percentage regulation.
HOW TO DRAW THE GRAPH FOR MMF METHOD:
i) Draw the open circuit characteristics curve (V vs. If).
ii) Draw the short circuit characteristics curve (short circuit current Vs If).
iii) Draw the line OL to represent If, which gives the rated generated voltage (V).
``
iv) Draw the line LA at an angle (90 +or ) to represent If which gives the rated full load current (Isc) on short
circuit. {(90+) for lagging power factor and (90-) for leading power factor.
v) Join the points O and A and find the field current (if) by measuring the distance OA that gives the open circuit
voltage (Eo) from the open circuit characteristics.
vi) Find the percentage regulation by using suitable formula.
VIVA QUESTIONS:
1) What are synchronous machines?
The machines generating ac emf are called alternating or synchronous generators. While the machine accepting input
from ac supply to produce mechanical output are called synchronous motors. Both these machines work at a specific
constant speed called synchronous speed and hence in general called synchronous machines.
2) Define voltage regulation. Name two methods used to determine voltage regulation of alternators.
%Reg = E-Vrated / Vrated *100 Where E = No load voltage Vrated = Rated voltage
Two methods to determine voltage regulation:
i) EMF method
ii) MMF method
3) What are the two types of alternators?
i) Non salient pole alternator
ii) Salient pole alternator.
4) State the principle of alternator.
When the rotor is rotated by the prime mover, the stator windings or conductors are cut by the magnetic flux hence an
emf is induced in the stator conductors. (Faradays law of electromagnetic induction).

15EEL 38 Electrical Machines 1 Laboratory Manual

37

BTL Institute of Technology EEE Dept.

5) Is EMF method an accurate method?


No, it is not an accurate method because the value of synchronous impedance found is always more than the original
value.
6) Write the emf equation of an alternator.
E = 4.44f TKcKd volts
Where, f = frequency in hertz
= flux per pole
T = Number of turns in stator windings
Kc = Pitch factor
Kd = Distribution factor
4) What is known as Armature reaction?
The effect of armature flux on main flux is called as armature reaction.
5) What is meant by synchronous reactance?
Synchronous reactance Xs = Xl + Xa
Xl = leakage reactance
Xa = Armature reactance
7) Can a DC generator be converted into an alternator? How?
Yes, by providing two collector rings on end of the armature and connecting these two rings to two points in the
armature windings 180 degree apart.
8) What is the other name for EMF and MMF method?
The other name for EMF method is called as Synchronous impedance method and MMF method is called as Ampere
turn method.
EMF method Pessimistic method
MMF method Optimistic method
``

15EEL 38 Electrical Machines 1 Laboratory Manual

38

EXPERIMENT NO:-09

BTL Institute of Technology EEE Dept.


DATE:

Aim:- To find the regulation of 3 Alternator by ZPF & ASA Method, comparing the values obtained by two
methods
Name plate details:Type
Range
Qty
Apparatus Name of
``
:- S.No
the Item
1
2
3
4
5
6

Procedure:O.C Test:1) Give all connections as per the circuit diagram.


2) switch-ON the supply & by varying the starter, prime mover Speed is adjusted to rated.
3) Now keeping the field current at zero, note the induced emf in Armature duo to residual Magnetism.
4) By slowly varying the potential divider, field current is increased & corresponding emf Induced is noted up to
above 20% of rated voltage.

SC Test:
1) Give all connections as per the circuit diagram.
2) switch-ON the supply & by varying the starter, prime mover
Speed is adjusted to rated.
3) By slowly varying the potential divider, field current is increased
& corresponding short Circuit current is noted up to rated value. To find armature resistance (Ra):
Give the connections as per diagram and by slowly varying the
Rheostat, note the values of ammeter & voltmeter up to some value and average them.

15EEL 38 Electrical Machines 1 Laboratory Manual

39

BTL Institute of Technology EEE Dept.

Z.P.F Test:1) Give all connections as per the circuit diagram.


2) Verify the connections by the instructor.
2) switch-ON the supply & Start the motor with the 3-pont starter, Adjust the rated speed of prime mover by
varying the field rheostat.
3) Gradually increasing the field excitation bring the alternator voltage to rated value
4) Switch on the inductive load and adjust, so that the full load current will flow through the ammeter. In mean
time rated voltage must be maintained.

``
PROCEDURE TO DRAW THE POTIER TRIANGLE: (ZPF METHOD)
1. Draw the open circuit characteristics curve (Generated voltage per phase Vs field current).
2. Mark the point A at X axis, which is obtained from short circuit test with full load armature current.
3. From the ZPF test, mark the point B for the field current to the corresponding rated armature current and the rated
voltage.
4. Draw the ZPF curve which is passing through the point A and B in such a way parallel to the open circuit
characteristic curve.
5. Draw the tangent for the OCC from the origin (Air gap line).
6. Draw the line BC from B towards Y axis which is parallel and equal to OA.
7. Draw the parallel line for the tangent from c to the OCC curve.
8. Join the point B and D also draws a perpendicular line DE to BC.
DE = Armature leakage reactance drop
BC=Armature reaction excitation
Graph: 1) A graph is drawn b/w If and V which is known as OC curve, by taking If on X-axis and V on Y-axis.
2) A graph is drawn b/w If and ISC which is known as SC curve, by Taking If on X-axis and ISCV on Y-axis.

15EEL 38 Electrical Machines 1 Laboratory Manual

40

BTL Institute of Technology EEE Dept.

EXPERIMENT NO:-10

DATE:

SLIP TEST ON 3-PHASE SALIENT POLE SYNCHRONOUS MACHINE


AIM:
i) To conduct the slip test on 3-phase salient pole synchronous machine
ii) To determine the direct axis and quadrature axis synchronous reactances
iii) To predetermine the voltage regulation at different loads and power factors and
APPARATUS:
S.No. Name of the apparatus Type Range Quantity
1. Voltmeter MI (0-500V) 2
2. MI (0-300V) 1
3 MC (0-30V) 1
4. Ammeter MI (0-10A) 1
5. MC (0-10A) 1
6. Rheostat Wire Wound 9 8.5A 1
7. Tachometer 1
PRINCIPLE:
The direct and quadrature axis reactances can be measured by slip test. The machine is driven by a dc motor at a speed
slightly less or slightly more than synchronous speed. The field winding is kept open circuited and a low voltage 3
phase supply (about 25% of the rated voltage) is applied to the armature terminals. The direction of rotation should be
same as the direction of rotating field. If this condition is fulfilled, a small ac voltage would be indicated by the
voltmeter across the field winding. The relative velocity between armature mmf and field poles is equal to slip speed
i.e. difference between synchronous speed and rotor speed. The stator mmf moves slowly past the field poles at slip
speed. This would cause the armature current to vary cyclicallyat twice the slip frequency. When the peak of the
armature mmf is in line with the fieldpoles, the reluctance offered by the magnetic circuit is minimum, the armature
current,required for the establishment of constant air-gap flux, will be minimum. Constantapplied voltage minus the
minimum impedance voltage drop (armature current being minimum) in the leads and 3-phase variac gives maximum
armature-terminal
voltage.The ratio of maximum armature terminal voltage per phase to minimum armature current
``
per phase gives Zsd. After one quarter of slip cycle, the peak of armature mmf is in line with q-axis and the reluctance
offered by the magnetic circuit is maximum. The armature current, required for the establishment of constant air-gap
flux, will be maximum and the armature terminal voltage will be minimum. The ratio of minimum armature terminal
voltage per phase to maximum armature current per phase gives Zsq.

When the armature mmf is in line with field poles, the armature flux linkage with field winding is maximum and rate
of change of this flux linkage is zero, so that induced voltage across the field winding is zero. On the other hand,
when armature mmf is in line with q-axis, the flux linkage with field winding is minimum and rate of change of this
flux linkage is maximum, so that induced voltage across the field winding is maximum.
.

15EEL 38 Electrical Machines 1 Laboratory Manual

41

BTL Institute of Technology EEE Dept.

PROCEDURE:
SLIP TEST
Make the connections as shown in figure.
Precautions : i) Keep the autotransformer at minimum voltage position
ii) Keep DPST, TPST and SPST switches open
iii) Keep dc motor field rheostat at minimum resistance position Switch on the d.c. supply by closing the
DPST switch. Using the three point starter, start the motor. Run the motor at synchronous speed by varying the motor
field rheostat. Close the TPST switch. By adjusting the autotransformer, apply 20% to 30% of the rated voltage to the
armature of the synchronous machine. Make sure that the direction of rotation of the prime mover and the direction of
rotation of the magnetic field produced in the armature are the same by closing the SPST switch. If the voltmeter
reading across the alternator field winding is very small, both the directions are correct. If the voltmeter reading is
high, interchange the two lines of 3 phase supply after switching off the 3 phase supply. SPST switch is kept open.
The speed is slightly reduced/increased from synchronous speed, so that slip is increased and the voltmeter and
ammeter readings are oscillating. The maximum and minimum readings of voltmeter and ammeter are noted. The
above said procedure can be repeated with two more different autotransformer settings. (During slip test, it would be
observed that swing of the ammeter pointer is very wide, whereas the voltmeter has only small swing because of the
low impedance voltage drop in the leads and 3-phase autotransformer).
``

15EEL 38 Electrical Machines 1 Laboratory Manual

42

BTL Institute of Technology EEE Dept.

2. Explain the working principle of self excited induction generator.


If the rotor of the machine is driven by its prime-mover, the presence of residual flux causes a small emf to get
induced in the stator windings at a frequency proportional to the rotor speed. This voltage impresses over the 3-phase
capacitor gives rise to leading current drawn by the capacitor which is equivalent to lagging current supplied to the
generator. The flux set up by this current assists the initial residual flux. Hence the net flux will increase causing the
voltage to build up further. The steady state voltage induced on no load is given by the intersection of magnetization
characteristic of the machine and capacitance V-A characteristic. The frequency generated is slightly less than that
corresponding to the speed of rotation. The terminal voltage of the generator increases with the capacitance, but its
magnitude is limited by saturation in the iron. If the capacitance is insufficient, the generator voltage will not build
up. The capacitor bank must be able to supply at least as much reactive power as the machine normally absorbs when
operating as a motor.
``

3. In case of a line-excited induction generator, how the slip is affecting the


active power delivered?
The active power delivered to the line is directly proportional to the slip above synchronous speed. Thus, a higher
prime-mover speed produces a greater electrical output.
4. What you mean by single phasing?
Single phasing is a fault condition in which a 3 phase motor is operating with one line open (due to blowing of a fuse
in one phase). Although the 3 phase motor will not start with one line open, if the motor is running when single
phasing occurs, it will continue to run as long as the shaft load is less than 80% rated load and the remaining
single phase voltage is normal; rotation of the rotor produces a quadrature field that maintains the rotation.
.5. Draw the torque-slip characteristics of an induction
machine

15EEL 38 Electrical Machines 1 Laboratory Manual

43

BTL Institute of Technology EEE Dept.

EXPERIMENT NO. 11
SYNCHRONIZATION OF ALTERNATOR TO INFINITE BUS AND DETERMINATION OF
PERFORMANCE UNDER CONSTANT POWER AND VARIABLE EXCITATION & VICE-VERSA.

Aim
To operate the Alternator on
Infinite Bus.
Constant Power and Variable Excitation.
Variable Excitation and Constant Power.
Apparatus Required
Sl.No.

Particulars

01

Voltmeter

02

Ammeters

03

Rheostats

04

Watt meters

05

Tachometer

Range
0 500 V
0-1/2A
0-5/10A
0-750,1.2A
0-38,8.5A
10/20A,
0 600 V
-

Type

Quantity

MI
M
C
-

01
01
01
02
01

LP
F
-

02
01

Procedure
a. Operation on Infinite Bus Bar
``

1.
2.

3.

4.

5.
6.
7.
8.

Connections are made as shown in the circuit diagram (4.a)


Keeping the rheostat R1 in the field circuit of motor in cut-out position, the rheostat R2 in the
armature circuit of motor and the rheostat R3 in the field circuit of alternator in cut-in positions,
the bus bar switch (S2) and synchronizing switch (S3) in open positions, the supply switch (S1)
is closed.
The motor is brought to the synchronous speed of the alternator by gradually
cutting out the rheostat R2 and cutting in the rheostat R1, if necessary.
By gradually cutting out the rheostat R3, the alternator voltage is built-up to the bus bar
voltage.
Now, bus bar switch (S2) is closed, and the phase sequence is verified. For correct phase
sequence, all the lamps will flicker simultaneously. Otherwise, they flicker
alternately. If they flicker alternatively, the bus bar voltage switch is opened and any two
terminals of the bus bar supply are interchanged.
Repeat step number 2, 3 and 4.
By varying the rheostats R1, R2 and R3 the dark period of the lamps are obtained.
When all the lamps are in dark condition, the synchronization switch S 3 is closed and now the
alternator is connected in parallel with the bus bar.
Switches (S3) and (S2) are opened; all the rheostats are brought back to their
respective initial positions, and supply switch (S1) is opened.

15EEL 38 Electrical Machines 1 Laboratory Manual

44

``

15EEL 38 Electrical Machines 1 Laboratory Manual

BTL Institute of Technology EEE Dept.

45

BTL Institute of Technology EEE Dept.

b. Constant Power - Variable Excitation Operation


1. Connections are made as shown in the circuit diagram (4.b)
2. Follow the procedure steps 2, 3.
3. By gradually cutting out the rheostat R3, the alternator voltage is built-up to its rated voltage.
4. Apply load gradually.
5. Vary generator excitation (R3) to keep wattmeter readings constant (Total Power).
6. Tabulate the readings.
7. Bring back the load to zero, reduce the excitation to a normal value and all rheostats are brought
back to respective initial positions & supply switch (S 1) is opened.
c. Constant Excitation - Variable Power Operation
1. Connections are made as shown in the circuit diagram (4.b)
2. Follow the procedure steps 2, 3.
3. By gradually cutting out the rheostat R3, the alternator voltage is built-up to its rated voltage.
4. Apply load in steps & note down all meter readings (Excitation should be constant by
adjusting the speed of the Motor).
5. Bring back the load to zero, reduce the excitation to a normal value and all rheostats are brought
``

back to respective initial positions & supply switch (S 1) is opened.


Tabular Column
1. Constant Power - Variable Excitation Operation
Sl.
No.

If
(A)

Power
(W1+W2)

Speed
(RPM)

15EEL 38 Electrical Machines 1 Laboratory Manual

Voltage
(V)

I
L
(A)

46

BTL Institute of Technology EEE Dept.

2. Constant Excitation - Variable Power Operation


Sl.
No.

If
(A)

Power
(W1+W2)

Speed
(RPM)

``

15EEL 38 Electrical Machines 1 Laboratory Manual

Voltage
(V)

I
L
(A)

47

EXPERIMENT NO:-12

BTL Institute of Technology EEE Dept.


DATE:

POWER ANGLE CURVE OF 3-PHASE SALIENT POLE SYNCHRONOUS MACHINE


APPARATUS:
S.No. Name of the apparatus Type Range Quantity
1. Voltmeter MI (0-500V) 2
2. MI (0-300V) 1
3 MC (0-30V) 1
4. Ammeter MI (0-10A) 1
5. MC (0-10A) 1
6. Rheostat Wire Wound 9 8.5A 1
7. Tachometer 1

``

15EEL 38 Electrical Machines 1 Laboratory Manual

48

``

15EEL 38 Electrical Machines 1 Laboratory Manual

BTL Institute of Technology EEE Dept.

49

VIVA QUESTIONS

``

15EEL 38 Electrical Machines 1 Laboratory Manual

BTL Institute of Technology EEE Dept.

50

``

15EEL 38 Electrical Machines 1 Laboratory Manual

BTL Institute of Technology EEE Dept.

51

BTL Institute of Technology EEE Dept.

VIVA QUESTIONS GENERAL


1. What is a Generator?
A Generator is a machine which converts Mechanical Energy into Electrical Energy.
2. On which principle a Generator works?
Generator works on Faradays laws of Electro Magnetic Induction
3. What are Faradays laws of Electro Magnetic Induction?
First Law: Whenever a conductor cuts magnetic flux an E.M.F is induced in that conductor.
Second Law: The magnitude of the induced e.m.f. is equal to the rate of change of flux linkage.
4. What are the two main parts of an AC Generator?
1. Stator
2. Rotor
5. What is the main difference between an AC Generator and DC Generator?
In an AC Generator the field is rotating and the armature is stationary whereas in DC Generator the field is stationary and the
armature is rotating.
6. What are the advantages of stationary armature and rotating field in an AC Generator?
1. It is easy to take output from the stationary armature.
2. It is easier to insulate stationary armature for higher voltage.
3. Low voltage excitation supply can be easily supplied to the rotor through slip rings.
7.
`` What is the relation between the frequency, pole and speed of a Generator?
F = PN/120 Hz
Where P is the No.of Poles
N is the Speed in RPM.
8. In a Generator with 2 pole, and speed 3000 rpm, what is the frequency of the induced emf ?
F = PN/120
= 2 x 3000/120
= 50 Hz.
9. What is the connection of winding in a stator?
Double star connection.
10. What is the efficiency of a Generator?
98.55%
11. What is the coolant used to cool stator winding?
Demineralized water distilled water
12. What is the coolant used to cool rotor winding?
Hydrogen.

15EEL 38 Electrical Machines 1 Laboratory Manual

52

BTL Institute of Technology EEE Dept.

13. What are the advantages of Hydrogen gas as coolant over others?
1. Density is 1/14 of air.
2. Windage loss is low.
3. Low noise.
4. Heat transfer co efficient is 1.5 times higher than air.
5. Thermal conductivity is 7 times higher than air.
14. What are the losses in a Generator?
1. Stator copper
2. Stator iron
3. Rotor copper
4. Windage loss
5. Stray loss
6. Friction loss
15. What is Short Circuit Ratio (SCR) of a Generator?
It is the ratio of the field current required to produce rated voltage on open circuit to the field current required to circulate rated
current on short circuit.
16. What is the value of SCR in a 210 MW Turbo alternator?
SCR = 0.49
17.What are the disadvantages of Low Power Factor?
Low Power Factor Disadvantages: In AC circuits, power consumed depends on the power factor. Thus the power factor plays an
important role in AC circuits. For instant, we know that; Power in a Three Phase AC Circuit = P = 3 V x I Cos And Current in
a Three Phase AC Circuits = I = P / (3 V x Cos) I 1 /Cos. (1) Also, Power in a Single Phase AC Circuits = P = V x
I Cos And Current in a Three phase AC Circuits = I = P / (V x Cos) I 1/Cos (2)
it is clear from both equations (1) an (2) that...

``