TEST PARAMETERS FOR 400A CONTROL PANEL TESTING AT CPRI

InA

= 400A

UnA

= 415V AT 50 HZ

Icw

= 25 KA FOR 1 SEC

Ui

= 600V

Uimp

=4KV

T amb. =50 deg.C


DEGREE OF PROTECTION= IP 23
CONSTRUCTION = FORM 2
--------------------------------------------------------------------------------------------------------------------------InA=RATED CURRENT OF ASSEMBLY
UnA= RMS VALUE OFRATED VOLTAGE OF ASSEMBLY
Icw= RATED SHORT TIME CURRENT( RMS VALUE OF CURRENT FOR SHORT
CIRCUIT TEST FOR 1 SEC)
Ui = RATED INSULATION VOLTAGE.
U imp= RATED IMPULSE WITH STAND VOLTAGE
Tamb= AMBIENT TEMPERATURE
DESCRIPTION OF TESTS ( AS PER IEC61439 PART 1 & PART 2)
1) VERIFICATION OF DEGREE OF PROTECTION
2) VERIFICATION OF CLEARANCE & CREEPAGE
3)PROTECTION AGAINST ELECTRICAL SHOCKAND INTEGRITY OF PROTECTIVE
CIRCUITS
4) VERIFICATION OF DIELECTRIC PROPERTIES
5)VERIFICATION OF TEMPERATURE RISE
6)VERIFICATION OF SHORT CIRCUIT WITHSTAND TEST FOR 25KA FOR 1
SECOND
7)VERIFICATION OF MECHANICAL OPERATION