You are on page 1of 2

S PGV/ Work No: 16-H2-025

S bin bn/ Test report number: FC-0-006


Ni lp t/ Place: Thai Binh Thermal Power Plant
Khch hng/ Customer: PTSC (Viet Nam) Co.,LTD

Phng th nghim in ETRC


ETRC laboratory

Ngy th nghim/ Date: 5/9/2016


Loi hnh th nghim/ Type of test: Sau lp t/ After installation

BIN BN TH NGHIM/ TEST REPORT


i tng th nghim/
Object
V tr lp t/ Position

KIM TRA MCH IN CHC NNG / ELECTRICAL WIRING INSPECTION


400V UNIT 1 TURBINE MCC - 11BHA02 11PUE10AP001 F35 PRIMING
VACUUM PUMP

iu kin mi trng/ Ambient condition: 25oC, 72%


Tiu chun th nghim/ Testing standards: Tiu chun nh ch to, IEC 60255, cc quy nh, quy phm ngnh
in
Thit b th nghim/ Testing equipments:
ng h vn nng/ Multimeter:

SeriesNo:

Ngi th nghim/ Inspecter : in, Tun, Cng


Hng mc th nghim/ Test items
1. Kim tra tng quan/ Visual check.
2. Kim tra mch chc nng/ Electrical wiring Inspection.
Kt lun/ Conclusion:

Cc hng mc th nghim t yu cu k thut/ All test items passed

Trng phng th nghim


Chief of ETRC Lab

TT-5.10-RL-15-1
Ln ban hnh: 03

Pass
Pass

Gim c
Director

Page 1 of 2

S PGV/ Work No: 16-H2-025

S bin bn/ Test report number: FC-0-006


KT QU TH NGHIM/ TEST RESULTS

1. Kim tra tng quan / Visual check.


No

Hng mc kim tra/ Check items

Kim tra tn t, v tr t theo s 1 si


Name plate panel and general arrangement in accordance with SLD.
Kim tra cp ni b v cc thit b c lp t theo bn v t.
2
Check internal wiring and all equipment to installation in accordance with schematic
diagram.
Kim tra cc thit b in trong t khng b h hng.
3
All internal equiptment no damaged.
2. Kim tra mch in chc nng/ Electrical circuit function inspection.
1

No
I
1
2
3
4
5
6
7
8

Hng mc kim tra/ Check items


Kim tra mch tn hiu v mch ch th/ Signal circuit and indication circuit inspection.
Kim tra mch cp ngun AC
Check AC power supply circuit.
Kim tra mch ng, m ti local
Check circuit run, stop motor at local
Kim tra mch ng, m ti remote
Check circuit run, stop motor at remote
Kim tra mch tn hiu trng thi MCCB v role trip
Check MCCB and Relay trip status signal
Kim tra mch tn hiu ln DCS
Check signal to DCS
Kim tra tn hiu t tip im ph ca MCCB
Check signal from MCCB auxiliary
Kim tra mch ch th n trng thi ng, ct
Check lamp status circuit
Kim tra mch trip MCCB t role qu nhit
Check trip MCCB from themal relay

TT-5.10-RL-15-1
Ln ban hnh: 03

nh gi
Assessment
Pass
Pass
Pass
nh gi
Assessment
Pass
Pass
Pass
Pass
Pass
Pass
Pass
Pass
Pass