You are on page 1of 18

Installation Manual Installation Reference

Airbridge BTS3606&3606A CDMA Base Station

Table of Contents

Table of Contents
Chapter 11 BTS3606 Operating Environment Requirements..................................................11-1
11.1 Site Selection of Equipment Room................................................................................11-1
11.2 Site Construction Requirements....................................................................................11-2
11.2.1 Equipment Room Area........................................................................................11-2
11.2.2 Equipment Room Height.....................................................................................11-2
11.2.3 Bearing Capability............................................................................................... 11-3
11.2.4 Equipment Room Floor.......................................................................................11-3
11.2.5 Equipment Room Windows and Doors...............................................................11-3
11.2.6 Equipment Room Roof and Walls.......................................................................11-3
11.2.7 Internal Partition Wall.......................................................................................... 11-4
11.2.8 Dust Density........................................................................................................ 11-4
11.2.9 Corrosive Gases................................................................................................. 11-5
11.2.10 Shockproof........................................................................................................ 11-5
11.2.11 Other Requirements.......................................................................................... 11-5
11.3 Power Supply................................................................................................................ 11-5
11.3.1 DC Power Supply................................................................................................11-5
11.3.2 AC Power Supply................................................................................................11-7
11.3.3 Anti-Interference Protection.................................................................................11-8
11.4 Requirements for Illumination........................................................................................11-9
11.5 Requirements for Temperature and Humidity..............................................................11-10
11.6 Requirements for Anti-Interference..............................................................................11-10
11.7 Requirements for Fire Protection.................................................................................11-11
11.8 Requirements for Lightning-Protection and Grounding System...................................11-12
11.8.1 Lightning-Protection Measures in Equipment Room Construction....................11-12
11.8.2 Lightning-Protection Measures of AC Power Supply System............................11-12
11.8.3 Lightning-Protection Measures of Power Cables Led into Equipment Room....11-12
11.8.4 Requirements for DC Power Distribution Grounding.........................................11-13
11.8.5 Equipotential Grounding Requirements............................................................11-13
11.8.6 General Requirements for Grounding...............................................................11-13
11.8.7 Requirements for Grounding Impedance..........................................................11-14
11.8.8 Requirements for Lightning Rod........................................................................11-14
11.8.9 Requirements for Feeder Cabling and Grounding.............................................11-14
11.8.10 Requirements for Signal Cable Layout............................................................11-14
11.9 Requirements for ESD Prevention...............................................................................11-14

Huawei Technologies Proprietary


i

Installation Manual Installation Reference


Airbridge BTS3606&3606A CDMA Base Station

List of Figures

List of Figures
Figure 11-1 Internal partition wall inside the equipment room.............................................11-4
Figure 11-2 Ground grid.................................................................................................... 11-13

Huawei Technologies Proprietary


ii

Installation Manual Installation Reference


Airbridge BTS3606&3606A CDMA Base Station

List of Tables

List of Tables
Table 11-1 Requirements for dust particles in the equipment room.....................................11-4
Table 11-2 Requirements for corrosive gas concentration...................................................11-5
Table 11-3 Requirements for AC voltage.............................................................................11-8
Table 11-4 Requirements for temperature and humidity....................................................11-10

Huawei Technologies Proprietary


iii

Installation Manual Installation Reference


Airbridge BTS3606&3606A CDMA Base Station

Chapter 11 BTS3606 Operating Environment


Requirements

Chapter 11 BTS3606 Operating Environment


Requirements
This chapter introduces the BTS3606 operating environment requirements, including:

Site Selection of Equipment Room

Site Construction Requirements

Power Supply

Requirements for Illumination

Requirements for Temperature and Humidity

Requirements for Anti-Interference

Requirements for Fire Protection

Requirements for Lightning-Protection and Grounding System

Requirements for ESD Prevention

11.1 Site Selection of Equipment Room


The telecom equipment should run in a favorable environment. Its equipment room
should be located at a place free from high temperature, dust, toxic gases, explosive
materials or instable voltage, and away from great vibrations, strong noise or power
transformer stations. During project designing, consider the following factors:
hydrographic, geological, seismic, power supply and transportation. Select a site in
line with the engineering and environmental requirements for the telecom equipment.
The construction, structure, heating and ventilation, power supply, lighting and fire
fighting of the equipment room should be designed by specialized construction
designers. The equipment room shall be designed in accordance with the following
requirements:

Environment requirements for access equipment running

Requirements on industrial, environment protection, fire fighting, and civil air


defense

Current standards or regulations of the local country or region

Requirements of special technical process for building construction design.

The specific requirements for site selection of equipment room are as follows.

Keep the site far from pollution sources.


For heavy pollution sources such as the smeltery and coal mine, keep a distance
of 5 km (3.11 miles). For medium pollution sources such as the chemical, rubber
and galvanization industrials, keep a distance of 3.7 km (2.30 miles). For light
pollution sources such as packinghouse and tanyard, keep a distance of 2 km

Huawei Technologies Proprietary


1

Installation Manual Installation Reference


Airbridge BTS3606&3606A CDMA Base Station

Chapter 11 BTS3606 Operating Environment


Requirements

(1.24 miles). If these pollution sources cannot be avoided, keep the equipment
room in the perennial upwind direction of the pollution sources. In addition, adopt
the high-quality equipment room or protection product.

Keep the air vent of the equipment room away from the exhaust of city waste
pipes, big cesspools and sewage treatment tanks. Keep the equipment room in
the positive pressure state lest the corrosive gases enter the equipment room
and erode components and circuit boards.

Keep the equipment room away from the industrial and heating boilers.

It is best to locate the equipment room in or above the second floor. If this cannot
be satisfied, the ground for equipment installation in the equipment room shall be
at least 600 mm (23.62 in.) above the maximum flood level in the local record.

Keep the equipment room away from livestock farms. If this requirement cannot
be satisfied, it should be located in the perennial upwind direction of the livestock
farms.

Keep the equipment room 3.7 km (2.30 miles) away from the seaside or salt
lake. If this requirement cannot be satisfied, the equipment room should be
airtight with cooling facilities. In addition, the alkalized soil cannot be used as the
construction material. Otherwise, the equipment applicable in atrocious
environment must be adopted.

The old livestock room or the fertilizer warehouse cannot be used as the
equipment room.

The equipment room should be solid enough to withstand wind and downpour.

Keep the equipment room away from the road or sand field with dusts flying
around. If this requirement cannot be satisfied, the windows and doors of the
equipment room should be away from the pollution sources.

11.2 Site Construction Requirements


This section provides the site construction requirements in terms of area, height,
bearing capacity, floor, windows and doors, roof and walls, and so on.

11.2.1 Equipment Room Area


The equipment room area must meet the needs of:

Future capacity expansion

Feeder window installation and feeder distribution

Easy installation and maintenance

Opening of cabinet doors

Huawei Technologies Proprietary


2

Installation Manual Installation Reference


Airbridge BTS3606&3606A CDMA Base Station

Chapter 11 BTS3606 Operating Environment


Requirements

11.2.2 Equipment Room Height


The distance from the beam or the wind pipe to the floor has to be equal to or longer
than 3 m (9.84 ft). The space is necessary for installing cabling rack and laying cables
and feeder pipes.

11.2.3 Bearing Capability


Equipment bearing depends on:

Equipment weight

Equipment base area

Installation site

Equipment room structure

Ask a construction engineer to verify the bearing capacity of the equipment room. If
the capacity fails to satisfy the needs, you must have the construction strengthened.

11.2.4 Equipment Room Floor


An antistatic floor is necessary for BTS equipment room. The floor must meet the
following needs:

The resistance of antistatic raised floor must comply with the requirements for
such floors in computer equipment room.

The floor is firm and tight, with a horizontal error no greater than 2 mm (0.08 in.).

If antistatic raised floor is not available, you can use a static-conductive floor
(mass resistivity from 1.0 107 (1.0 107 ohm) to 1.0 1010 (1.0 1010
ohm)) instead.

Be sure to connect the floor to the grounding device through a current-limiting


resistor and connecting cables. The resistance of the resistor shall be 1 M
(1Mohm). Tests show that terrazzo ground (including cement ground) reaches
the standard.

Be sure to cover all the holes for cabling with lids. Make sure that the holes are
accurate in position and size for future installation.

11.2.5 Equipment Room Windows and Doors


Doors and windows of the equipment room must meet the following needs:

The minimum size of doors is: 2 m (height) 1 m (width) (6.56 ft (height) 3.28 ft
(width)).

Be sure to seal doors and windows with anti-dust rubber strips.

For windows exposed to sunshine, apply reflecting paper on the windowpane or


use colored glass. If the illumination inside the room permits, you may also block
windows.

Huawei Technologies Proprietary


3

Installation Manual Installation Reference


Airbridge BTS3606&3606A CDMA Base Station

Chapter 11 BTS3606 Operating Environment


Requirements

11.2.6 Equipment Room Roof and Walls


The roof and walls of the equipment room must meet the following needs

Make sure that the roof and walls are of enough endurance, heat insulation, and
leakage-proof capabilities.

Waterproof antenna mast and cabling holes on the roof. Make sure that the roof
is strong enough to bear the facilities.

You may paint walls with lusterless lacquer, but never with the paint that easily
chalks.

11.2.7 Internal Partition Wall


Separate the area where the equipment is installed from the equipment room door.
The partition wall can hold back some dusts. Figure 11-1 illustrate this internal
partition.
Air conditioner
Equipment

Internal partition wall

Figure 1.1 Internal partition wall inside the equipment room

11.2.8 Dust Density


The equipment room is free from explosive, conducting, permeability magnetic and
corrosive dust. Table 11-1 lists the requirement for dust concentration in the
equipment room.
Table 1.1 Requirements for dust particles in the equipment room
Mechanically active material

Unit

Content

Suspending dust

mg/m

0.01

Precipitable dust

mg/mh

10

Sand

mg/m

No obvious sand

Huawei Technologies Proprietary


4

Installation Manual Installation Reference


Airbridge BTS3606&3606A CDMA Base Station

Chapter 11 BTS3606 Operating Environment


Requirements

Mechanically active material

Unit

Content

Note:

Suspending dust: diameter 75 m

Precipitable dust: 75m diameter 150 m

Sand: 150m diameter 1000 m

11.2.9 Corrosive Gases


Besides the dust, the equipment room should be free from corrosive gases, such as
SO2, H2S, NH3. Table 11-2 lists the requirements for the corrosive gas concentration.
Table 1.1 Requirements for corrosive gas concentration
Chemically active material

Unit

Density

SO2

mg/m

1.5

H2S

mg/m

0.03

NH3

mg/m

0.15

Cl2

mg/m

0.3

11.2.10 Shockproof
The intensity requirements of shockproof design of the room shall be one degree
above the local intensity requirement.
Make sure that the equipment room meets the requirement. Strengthen it if
necessary.

11.2.11 Other Requirements


Avoid the proliferation of fungi mildew, and prohibit rodents.

11.3 Power Supply


11.3.1 DC Power Supply
The 48V DC power supply for BTS must meets the following requirements:

I. DC Power Supply

Voltage range: 40 V DC to 60 V DC

Huawei Technologies Proprietary


5

Installation Manual Installation Reference


Airbridge BTS3606&3606A CDMA Base Station

Chapter 11 BTS3606 Operating Environment


Requirements

Rectifier: If AC input voltage ranges from 85% to 110% of the nominal voltage
and the load current from 5% to 100% of the nominal current, the output voltage
of the rectifier stays at a value in the range of -46.0 V to -56.4 V. The regulated
voltage precision is equal to or less than 1%.

On/off overshoot magnitude: less than 5% over or below the rectified DC output
voltage.

Peak to peak noise voltage is equal to or less than 200 mV

Dynamic response: The restore time is shorter than 200 ms. The overshoot
value is less than 5% over or below the rectified DC output voltage.

II. DC Power Supply System

The capacity of DC power supply system is higher than the maximum dynamic
load and static load by a specific value.

Place the power supply equipment close to communications equipment to make


the DC feeder line short. The voltage drop of the loop between the port on
battery and the port on equipment shall be lower than 3.2 V. This design reduces
power consumption and installation cost.

If the exchange has a large capacity or there are more than two switching
systems, two or more independent power supply systems are required.

For a large-capacity communication center, independent power supply systems


can supply power for each floor or each equipment room.

For common exchanges, concentrated power supply with a power room and
battery compartment applies. The distributed power supply also applies.

For small-capacity exchanges, the power supply system can be integrated into
the equipment. Be cautious of corrosive gas given out by battery in the
equipment room that may damage circuit boards in the equipment.

The distributed power supply with multiple power supply systems and power
devices is advisable.

The output voltage of the DC power supply systems stays within the output
voltage range.

The AC power supply system is reliable for reliable power supply and lower
battery capacity requirement. For small-capacity exchanges that are hard to
improve the reliability, you may enhance the battery capacity.

III. High Frequency On/Off Rectifier


The capacity of the high frequency on/off rectifier shall meet the needs of
communication load power and battery charging power.
If the number of active rectifiers is less than 10, use one standby rectifier. If the
number is over 10, use one standby rectifier for every 10 active ones.

Huawei Technologies Proprietary


6

Installation Manual Installation Reference


Airbridge BTS3606&3606A CDMA Base Station

Chapter 11 BTS3606 Operating Environment


Requirements

IV. Battery
Install batteries in two or more groups. The total capacity depends on the time of
independent power supply for load of each battery group.
For most exchanges, the time of independent power supply for load of each battery
group depends on permissible power off time and complies with the following rules:

For first-rank mains supply, the battery need sustain 0.5 hour to 1 hour.

For second-rank mains supply, the battery need sustain 1 hour to 2 hours.

For third-rank mains supply, the battery need sustain 2 hour to 3 hours.

For fourth-rank mains supply, the battery need sustain 8 hour to 10 hours in one
of the following cases:
- There is only one power line from one power supply.
- The power is usually off for a whole day or a whole night.
- The power supply is not stable or up to the standards of third-rank mains
supply.

For fourth-rank mains supply, the battery need sustain 20 to 24 hours if there is
seasonal long-time power failure of if there is no mains supply.

For unattended sites, the battery must sustain long enough for the following
factors:
- The technicians need time to prepare after being informed of a power fault.
- The normal-speed drive to the site takes time.
- It takes time to handle the fault.
- The technicians do not go to unattended sites on mountaintop or suburb by
night.
- For sites with time-delay oil generators, the released energy of the battery
during the delay cannot exceed 20% of its capacity.

11.3.2 AC Power Supply


The AC power supply for BTS must meet the following requirements:

The electric network for BTS is independent and good in quality.

The AC power distribution capacity of the equipment room depends on the


working current and fault current of the equipment. Each independent device
must be equipped with independent facilities for AC power distribution protection.
The threshold of the protection switch shall be higher than the downstream
electric equipment.

Use voltage regulation devices in either case below:

Huawei Technologies Proprietary


7

Installation Manual Installation Reference


Airbridge BTS3606&3606A CDMA Base Station

Chapter 11 BTS3606 Operating Environment


Requirements

- The communications equipment is powered by mains supply directly. The


power supply voltage is 5% higher or 10% lower than the nominal voltage or out
of the permissible voltage range of the communications equipment.
- The communications equipment is not directly powered by mains supply. The
power supply voltage is 10% higher or 15% lower than the nominal voltage or out
of the permissible AC input voltage range of DC power equipment.

Apply

UPS

or

DC-to-AC

converters

to

power

supply

for

no-break

communications.

To ensure critical communications load and power load in mains failure, the
office site shall be equipped with a generator set as power supply for itself. The
capability of the set is 1.5 to 2 times of the total capability of AC non-stop electric
equipment.

Table 11-3 lists the requirements for AC voltage.


Table 1.1 Requirements for AC voltage
Input voltage

90% to 110% of nominal voltage

range
Power frequency

98% to 102% of nominal power frequency

Wave distortion

The total harmonic component shall be smaller than


10%.

11.3.3 Anti-Interference Protection


I. Interference Causes
Interference sources produce stray signals. The stray signals affect communications
quality, generate cross talk and noise, and even affect the normal operation of BTS.
Interference sources include:

Corona discharge of transmission line

Electromagnetic interference caused by transformer

Various kinds of switch apparatuses

Waveform distortion in operating large equipment

Radio-frequency interference

Natural interference such as the terrestrial magnetic field and extraneous


radiation

All the interference, in any form they might be, comes from:

Capacitance coupling

Inductive coupling

Huawei Technologies Proprietary


8

Installation Manual Installation Reference


Airbridge BTS3606&3606A CDMA Base Station

Chapter 11 BTS3606 Operating Environment


Requirements

Electromagnetic wave radiation,

Electric conduction of common impedance (including the grounding system)

Electric conduction of various conducting wires (power cables, signal cables and
output cables).

External interference enters the equipment through input signal cables, output cables,
power cables, grounding system, and space electromagnetic wave.

II. Anti-Interference Measures


External noise over anti-interference tolerance of integrated circuit of equipment leads
to misoperation of the equipment. The entire equipment cannot work normally in that
situation. It is not feasible to remove or shield all interference. However, you may take
the following measures to suppress the interference:

The high frequency interference on electric networks comes from the coupling of
primary coil to secondary coil of the power transformer through distributed
capacitor. A low pass filter on led-in power cables and a proper power
transformer can suppress the interference.

To suppress the interference generated by transient changes in electric network,


you can lead in the power directly from the main transformer and add a filter
capacitor to the line.

If BTS equipment connects to a 50 Hz mains power network where the above


interference sources exist, the voltage of the power network may sharply change
or even generate over-voltage upon a lightning strike. The interference enters
BTS and causes calculation errors to internal processors of BTS. Switch to
mains supply only when some effective measures have been taken against
electric network interference.

The key to removing the interference caused by the grounding system is to


prevent various grounds (signal ground, power ground, protection ground, and
shielding ground) from forming loops, including the loop formed by large
distributed capacitor. Otherwise, interference signals will affect the normal
operation of the BTS through the coupling of the common impedance of the
grounding system.

Protect the equipment against the electromagnetic interference from surrounding


environment and telecom lines.

In some communications buildings, there may be multiple high frequency


transmitters. Their influence on BTS equipment shall comply with the requirements of
the related EMC standards. Besides, be sure to ground, shield, and wave-filter BTSs
properly.
In high frequency electromagnetic field (external interference), a high longitudinal
voltage may be inducted in the sheath and the core of the communication cable.
Because of the asymmetry of the core, the longitudinal voltage may generate lateral

Huawei Technologies Proprietary


9

Installation Manual Installation Reference


Airbridge BTS3606&3606A CDMA Base Station

Chapter 11 BTS3606 Operating Environment


Requirements

noise voltage at the end of the core. The noise voltage causes interference. If the
metal skin of the cable sheath is grounded, the sheath produces shield function and
the longitudinal voltage will drop greatly, thus suppressing the interference voltage.
There are several other effective methods to suppress interference as follows:

Reducing the voltage and current of interference sources

Shortening wires or the interval of wires to reduce the area of the interference
loop

Placing insulated and interfered wires on the grounded surface

Using special ground return line to eliminate common impedance

Twisting the signal wire and the return line together to offset the partial external
electromagnetic interference

11.4 Requirements for Illumination


The requirements for equipment room illumination include:

Avoid direct sunshine on the equipment room to prevent circuit board and other
elements from aging and deforming.

Install gentle-light anti-explosion lamps in the battery compartment.

For unattended BTSs, use common illumination provided by the mains supply for
the equipment room.

For BTSs with large capacity and much importance, prepare an emergency
lighting system with DC power supply as standby illumination.

11.5 Requirements for Temperature and Humidity


To maintain a favorable working environment for the equipment, keep the proper
temperature and humidity in the equipment room. Table 11-4 gives the specific
requirements.
Table 1.1 Requirements for temperature and humidity
Equipment

Temperature

Relative humidity

BTS3606

5C (41F) to + 40C

15% to 85%

(+ 104F)

Note:
Before measuring the temperature and humidity, remove the protection boards
in front of and at the back of the cabinet (if any). The measurement point shall be
1.5 m (4.92 ft) above the ground and 0.4 m (1.31 ft) in front of the cabinet.

To meet the above requirements, take the following measures in the equipment room.

Huawei Technologies Proprietary


10

Installation Manual Installation Reference


Airbridge BTS3606&3606A CDMA Base Station

Chapter 11 BTS3606 Operating Environment


Requirements

Use the perennial temperature-control device no matter what the local climate is.

Mop the ground on a timed basis or use a humidifier to keep the proper humidity
in the equipment room in the dry area.

Use the dehumidifier in the place where the humidity if high.

11.6 Requirements for Anti-Interference


External noise over anti-interference tolerance of integrated circuit of equipment leads
to misoperation of the equipment. The entire equipment cannot work normally in that
situation. It is not feasible to remove or shield all interference. However, you may take
the following measures to suppress the interference:

The high frequency interference on electric networks comes from the coupling of
primary coil to secondary coil of the power transformer through distributed
capacitor. A low pass filter on led-in power cables and a proper power
transformer can suppress the interference.

To suppress the interference generated by transient changes in electric network,


you can lead in the power directly from the main transformer and add a filter
capacitor to the line.

If BTS equipment connects to a 50 Hz mains power network where the above


interference sources exist, the voltage of the power network may sharply change
or even generate over-voltage upon a lightning strike. The interference enters
BTS and causes calculation errors to internal processors of BTS. Switch to
mains supply only when some effective measures have been taken against
electric network interference.

The key to removing the interference caused by the grounding system is to


prevent various grounds (signal ground, power ground, protection ground, and
shielding ground) from forming loops, including the loop formed by large
distributed capacitor. Otherwise, interference signals will affect the normal
operation of the BTS through the coupling of the common impedance of the
grounding system.

Protect the equipment against the electromagnetic interference from surrounding


environment and telecom lines.

In some communications buildings, there may be multiple high frequency


transmitters. Their influence on BTS equipment shall comply with the requirements of
the related EMC standards. Besides, be sure to ground, shield, and wave-filter BTSs
properly.
In high frequency electromagnetic field (external interference), a high longitudinal
voltage may be inducted in the sheath and the core of the communication cable.
Because of the asymmetry of the core, the longitudinal voltage may generate lateral
noise voltage at the end of the core. The noise voltage causes interference. If the

Huawei Technologies Proprietary


11

Installation Manual Installation Reference


Airbridge BTS3606&3606A CDMA Base Station

Chapter 11 BTS3606 Operating Environment


Requirements

metal skin of the cable sheath is grounded, the sheath produces shield function and
the longitudinal voltage will drop greatly, thus suppressing the interference voltage.
There are several other effective methods to suppress interference as follows:

Reducing the voltage and current of interference sources

Shortening wires or the interval of wires to reduce the area of the interference
loop

Placing insulated and interfered wires on the grounded surface

Using special ground return line to eliminate common impedance

Twisting the signal wire and the return line together to offset the partial external
electromagnetic interference

11.7 Requirements for Fire Protection


For fire protection purpose, comply with the following rules:

The equipment room is at least 6 or 7 meters (19.68 or 22.96 ft) from any other
construction.

Keep flammable and explosive materials away from the equipment room.

Fire-extinction facilities are available on the construction site. Smoke and


temperature sensors, if any, are functional.

Mark sockets of different voltages with distinct labels.

Install safety covers on the reserved mounting holes in the floor.

You can install auto extinguishers to put out or control fire at the very start. Besides,
put portable extinguishers in the aisle outside the equipment room.
The water pool for fire extinction shall be large enough to hold water for extinguishing
fire both outside and inside the room (assumed that fire lasts for 2 hours).
Place fire hydrants in the aisle or near the staircase where they are distinct and easily
accessible. Do not place them in the room.

11.8 Requirements for Lightning-Protection and Grounding


System
11.8.1 Lightning-Protection Measures in Equipment Room Construction
Lightning-protection measures in equipment room construction include:

Construct an equipment room of reinforced concrete.

Equip the equipment room with facilities to protect the room from lightning stroke.

The lightning-protection (such as lightning rod) grounding of the equipment room


shares a grounding conductor with equipment protection grounding.

Huawei Technologies Proprietary


12

Installation Manual Installation Reference


Airbridge BTS3606&3606A CDMA Base Station

Chapter 11 BTS3606 Operating Environment


Requirements

11.8.2 Lightning-Protection Measures of AC Power Supply System


Lightning-protection measures of the AC power supply system include:

Use TN-S power supply system.

Use a dedicated power transformer for BTS. Sheath power cables with metal or
insulation materials. Lead the cables into BTS through steel pipe. Ground the
both ends of sheathes and pipes securely. Bury the grounding poles at least 15
m (49.2 ft) deep.

Add a seamless zinc oxide lightning arrester to the lower voltage side of the BTS
AC power transformer. Ground the transformer shell, AC zero line of the lower
voltage side, and metal sheath of power cables connected to the transformer
shell.

11.8.3 Lightning-Protection Measures of Power Cables Led into Equipment


Room
Power cables led into the equipment room must meet the following requirements:

Install lightning arresters on the power cables.

Do not elevate AC and DC power cables led into or out of communications sites.

Lead low-voltage power cables into the AC rectifier and AC power distribution
box in the equipment room. Add a lightning arrester for over 20 KA AC power to
the power cables. Ground the lightning arrester.
- In cities, the nominal discharge current of the lightning arrester shall be over 20
kA.
- In suburbs, the through-current capacity of the lightning arrester shall be over
40 kA.
- In mountains or solitary high buildings in cities, the maximum through-current
capacity of the lightning arrester shall be over 100 kA.

The grounding cable of its lightning arrester must be shorter than 1 m (3.28 ft).

11.8.4 Requirements for DC Power Distribution Grounding


The BTS DC working ground (48V DC power anode or 24V DC power cathode)
connects to the nearest point on the indoor grounding tandem bar. The grounding
cables must satisfy the maximum load of equipment.

11.8.5 Equipotential Grounding Requirements


Equipotential grounding requirements include:

Make protection ground for all communications devices and supporting facilities
(mobile BTSs, transmission equipment, and power unit).

Huawei Technologies Proprietary


13

Installation Manual Installation Reference


Airbridge BTS3606&3606A CDMA Base Station

Chapter 11 BTS3606 Operating Environment


Requirements

The protection ground of all devices on the site must connect to one grounding
bar. The protection ground of all devices in an equipment room must connect to
the grounding bar of the equipment room.

The working ground and protection group of all communications devices must
connect to one ground grid.

There are three ground grids for BTS equipment room, the tower, and the power
distribution transformer each. They connect in a multi-point manner under earth.
If the tower is on the rooftop of the equipment room and the power transformer is
in the equipment room, the other two ground grids can share the ground grid of
BTS equipment room, as shown in Figure 11-2.
Horizontal
grpunding body

Tower
ground grid

Vertical
grounding body

Equipment
ground grid

power distribution
transformer
ground grid

Figure 1.1 Ground grid

Ground the cable rack, suspend iron rack, BTS rack or BTS shell, metal air duct,
and metal doors and windows in the equipment room.

11.8.6 General Requirements for Grounding


General requirements for grounding include:

Never connect the neutral line of AC power cable to the protection ground of any
exchange or communications devices.

Make all ground cables as short and straight as possible.

Never add fuse or switch to ground cables.

Make sure that there is no oxidation on the grounding bar against large contact
impedance between ground cables and grounding bar. Ensure that ground
cables connect to the protection grounding bar of the equipment room securely.

11.8.7 Requirements for Grounding Impedance


The grounding impedance of BTS cannot exceed 10 ohm.

11.8.8 Requirements for Lightning Rod


Make sure that all BTS antennas stay in the effective protection range of the lightning
rod.

Huawei Technologies Proprietary


14

Installation Manual Installation Reference


Airbridge BTS3606&3606A CDMA Base Station

Chapter 11 BTS3606 Operating Environment


Requirements

The lightning rod must have a dedicated line for lightning current lead-in. The
lightning rod shall be made of 40 mm 4 mm (1.57 in. 0.16 in.) galvanized flat
steel.

11.8.9 Requirements for Feeder Cabling and Grounding


For the requirements for feeder cabling and grounding, refer to 3.5.2 "Grounding of
RF Antenna" and 3.5.3 "Grounding of GPS/GLONASS Antenna."

11.8.10 Requirements for Signal Cable Layout


Requirements for signal cable layout include:

Do not elevate signal cables on the BTS site. Lead signal cables through earth.

Sheath signal cables led into or out of the site in metal materials or pull them
through metal pipes.

If signal cables led into the site cannot run through earth, lead them through
metal tubes. Ground both ends of the tubes securely. Add signal lightning
arrester with large through-current capacity at the point where the cables led into
equipment. Make the ground cable of the lightning arrester as short as possible.
Ground the idle lines in the cable.

11.9 Requirements for ESD Prevention


The absolute value of electrostatic voltage must be less than 1,000 V.
To meet the requirement, take the following measures:

Train operators on ESD prevention.

Control the humidity in the room to reduce the impact of static electricity.

Lay antistatic floor in the room.

Wear ESD shoes and uniforms before entering the room.

Use antistatic tools such as ESD wrist straps, antistatic tweezers and extraction
tools when dealing with the equipment.

Ground all conducting materials in the room, including computer terminals.

Use antistatic worktables.

Keep non-antistatic materials (such as common bags, foams, and rubbers) at


least 30 cm (0.98 ft) away from boards and ESD-sensitive components.

Huawei Technologies Proprietary


15

You might also like