Liebert DS Thermal Management Unit

System Design Manual - 28-105kW (8-30 Tons), Downflow/Upflow, 60Hz


Floor Mounted, Air-Cooled, Water/Glycol-Cooled, GLYCOOL Economizer Coil, Dual-Cool DX with
Secondary Chilled Water Coil

TABLE OF CONTENTS
LIEBERT DS MODEL NUMBER . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
1.0

LIEBERT DS CONFIGURATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2

1.1

Cooling Configurations. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2

1.2

Blower Configurations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3

1.3

Component Location Drawings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6

2.0

LIEBERT DS AIR-COOLED SYSTEM DATA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8

3.0

LIEBERT DS WATER-COOLED SYSTEM DATA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11

4.0

LIEBERT DS GLYCOL-COOLED SYSTEM DATA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14

5.0

LIEBERT DS GLYCOOL SYSTEM DATA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17

6.0

ELECTRICAL DATA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20

6.1

Air-cooled Electrical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20

6.2

Water/Glycol-Cooled Electrical Data. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23

7.0

WEIGHTS AND DIMENSIONS. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26

7.1

Downflow Model Dimensions and Primary ConnectionsWater/Glycol/GLYCOOL


Systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37

7.2

Downflow Models with Front and/or Rear Discharge . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43

7.3

Disassembly DimensionsDownflow Air-Cooled Systems . . . . . . . . . . . . . . . . . . . . . . . . . . 46

7.4

Disassembly DimensionsDownflow, Water/Glycol/GLYCOOL Systems . . . . . . . . . . . . 52

7.5

Upflow Model Dimensions and Primary ConnectionsAir-Cooled Systems with EC


Fans. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55

7.6

Upflow Model Dimensions and Primary ConnectionsWater/Glycol/GLYCOOL


Cooled Systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65

7.7

Upflow Model Dimensions and Primary ConnectionsAir-Cooled Systems with


Forward-Curved Blowers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71

7.8

Upflow Model Dimensions and Primary ConnectionsWater/Glycol/GLYCOOL


Systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81

8.0

BLOWER OUTLET AND DECK DIMENSIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87

8.1

Disassembly DimensionsUpflow Air-Cooled Systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90

8.2

Disassembly DimensionsUpflow, Water/Glycol/GLYCOOL Systems . . . . . . . . . . . . . . . 96

9.0

ANCILLARY ITEMS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 99

9.1

Floor Stands . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 99

9.2

Plenums . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 102

9.3

Rear Return Filter Box . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 106

10.0

PIPING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .107

10.1

Piping Schematics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 109


10.1.1 Typical System ConfigurationsLiebert MC Condensers . . . . . . . . . . . . . . . . . . . . . . . . . 109
10.1.2 Typical System ConfigurationsFin/Tube . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 110

11.0

ELECTRICAL FIELD CONNECTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 119

11.1

Standard Electrical Field Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 121

11.2

Optional Electrical Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 122


i

11.3

Optional Low-Voltage Terminal Package Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . 122

12.0

HEAT REJECTIONLIEBERT MC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .123

12.1

Liebert MC Selections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 123

12.2

Liebert MCDry Weight and Additional Weight of Options . . . . . . . . . . . . . . . . . . . . . . . . 124

12.3

Sound Power Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 125

12.4

Electrical DataLiebert MC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 125

12.5

Liebert MC Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 126

12.6

Piping Connections. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 128

12.7

Electrical Field ConnectionsLiebert MC. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 130

13.0

HEAT REJECTIONLIEBERT FIN/TUBE CONDENSERS . . . . . . . . . . . . . . . . . . . . . . . . . . . 133

13.1

Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 134

13.2

Electrical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 136


13.2.1 Electrical DataFin/Tube Condensers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 136
13.2.2 Electrical Field ConnectionsLiebert Fin/Tube Condensers . . . . . . . . . . . . . . . . . . . . . . . . 137

13.3

Piping Connections. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 140

14.0

HEAT REJECTIONLIEBERT PIGGYBACK CONDENSERS, AIR-COOLED. . . . . . . . . . . . . . . 142

14.1

Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 143

14.2

Electrical Field ConnectionsLiebert Piggyback Condensers . . . . . . . . . . . . . . . . . . . . . . 145

14.3

Connection LocationsLiebert Piggyback Condensers . . . . . . . . . . . . . . . . . . . . . . . . . . . . 146

15.0

HEAT REJECTIONLIEBERT FIN/TUBE DRYCOOLERS AND PUMPS . . . . . . . . . . . . . . . . . . 147

15.1

Drycooler SelectionProp Fan Drycoolers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 147

15.2

Liebert Drycooler Data. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 147

15.3

Dimensional Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 148

15.4

Electrical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 150

15.3.1 DimensionsProp Fan Drycoolers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 148


15.4.1 Electrical DataProp Fan Drycoolers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 150

15.5

Piping Connections. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 154

16.0

HEAT REJECTIONPIGGYBACK DRYCOOLERS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 157

16.1

Drycooler SelectionIndoor Piggyback Drycoolers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 157

16.2

Electrical DataPiggyback Drycoolers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 157

16.3

DimensionsIndoor Piggyback Drycoolers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 158

16.4

Piping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 159

17.0

PUMP PACKAGES AND EXPANSION TANK . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 160

APPENDIX A - U.S. DEPARTMENT OF ENERGY (DOE) PERFORMANCE DATA . . . . . . . . . . . . . . . . 164


APPENDIX B - GUIDE SPECIFICATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 170

ii

Liebert DS Model Number

LIEBERT DS MODEL NUMBER


1

10

11

12

13

14

15

Air Distribution
DS = Downflow Standard
VS = Upflow Standard

Factory
Configuration
Number

Nominal kW
028, 035, 042, 053, 070, 077, 105
(8, 10, 12, 15, 20, 22, 30 tons)

Humidification
0 - None
I - Infrared
S - Steam Generating
Canister

Cooling Type
A = Air-Cooled
D = Dual-Cool, Air-Cooled
H = Dual-Cool, Water-Cooled
K = GLYCOOL (Liebert Economizer Coil)
W = Water/Glycol
Compressor
D - Digital Scroll, R-407C
S - Scroll, R-407C
U - Semi-Hermetic with Four-Step, R-407C
V- Semi-Hermetic with Four-Step, R407C
(DS105 water/glycol/GLYCOOL only)

Reheat Type
0 - None
E - 3-Stage Electric
S - SCR
Voltage
A - 460/3/60
B - 575/3/60
C - 208/3/60
D - 230/3/60
2 - 380/3/60

Fan Type
0 = Forward-Curved
Blowers
1 = Electronically
Commutated (EC)
Fans

Not all combinations of options are available on all units.


Digital Scroll Compressors
Not available on 077 and 105
Not compatible with SCR reheat because digital scroll provides variable capacity control
Scroll Compressors
Not available on 077 and 105 water/glycol/GLYCOOL models after 12/31/15
EC Fans, Direct-Drive
Liebert Econ-O-Coil not available on 028, 035, 042 models with 208/230V
Steam Generating Canister Humidifier
Not available on upflow (VS) configurations
Not available on EC fan configurations
575 Volt Option Limitations
Digital scroll compressors available only on 053, 070 models
GLYCOOL Liebert Economizer Models
105 model requires semi-hermetic compressors only, so as to prevent potential coil freezing
Turning Vanes
Not available on floor stands 6" (152.4mm) tall
Not available or required on units with EC fans
High Pressure Water Regulating Valve
Not available on 042 models with semi-hermetic and scroll compressors
1

Liebert DS

Liebert DS Configurations

1.0

LIEBERT DS CONFIGURATIONS

1.1

Cooling Configurations
NOTE
All field-installed piping must comply with applicable local, state and federal codes.

AIR-COOLED
Air-cooled unit piping is spun closed from the
actory and contains a nitrogen holding charge.
ach installation requires field-supplied
efrigerant and piping to a condenser.

GLYCOL-COOLED
Glycol-cooled units are factory-charged and
tested. Field-supplied and field-installed piping is
required from the unit to the drycooler and pump
package.

GLYCOOL-INTEGRATED FLUID ECONOMIZER


YCOOL units are factory-charged and tested. Field-supplied
d field-installed piping is required from the unit to the
ycooler and pump package. An additional Liebert Economizer
l is included for use when fluid temperatures are sufficiently
w (below room temperature). Economizer cooling is provided
circulating cold glycol through this second coil, reducing or
minating compressor operation.

WATER-COOLED
Water-cooled units are factory-charged and
tested. Field-supplied and field-installed
water piping is required from the unit to the
cooling tower.

DUAL-COOL
This system has all of the features of a compressorized
system, but adds a second cooling coil that is connected
to a source of chilled water. Cooling is provided by
circulating chilled water, when available, through this
second coil and reducing compressor operation.

Liebert DS

Liebert DS Configurations

1.2

Blower Configurations

Figure 1

Blower configurationsDownflow, front and rear supply models, EC fans


Return Air

Return Air

Filter

Filter

Front

Front

Coil

Coil

Supply
Air

Blower
Blower

Raised
Floor

Raised
Floor

Rear Supply, EC Fans


Applicable to installations
without raised floors

Front Supply, EC Fans


Applicable to installations
without raised floors

Figure 2

Supply
Air

Blower configurationsDownflow, bottom supply and under-floor supply models, EC fans


Return Air

Return Air

Filter

Filter

Front

Front

Coil

Coil

Blower

Blower

Raised
Floor

Raised
Floor

Supply Air

Floor
Stand
(optional)

Supply
Air

Floor Stand
(optional )
Supply
Air

Under-Floor Supply, EC Fans


(requires 24" minimum height)

Bottom Supply, EC Fans

Liebert DS

Liebert DS Configurations

Figure 3

Blower configurationsUpflow models, EC fans in plenum

Supply
Air

Supply
Air

Supply
Air

Supply
Air

EC Fan

Front

Coil

EC Fan

Front

Coil

Filter

Filter
Return Air

Return
Air

Ductwork

Upflow, Front Return, EC Fan in Plenum

Figure 4

Upflow, Rear Return, Ducted, EC Fan in Plenum

Blower configurationsUpflow, front return models, forward-curved blowers


Supply Air

Supply Air

Front

Blower

Front

Coil

Coil

Filter

Filter

Return
Air

Return
Air

Top Supply, Front Throw Forward-Curved Blowers

Liebert DS

Blower

Top Supply, Rear Throw Forward-Curved Blowers

Liebert DS Configurations

Figure 5

Blower configurationsUpflow, rear return models, forward-curved blowers


Supply Air

Front

Supply Air

Blower

Front

Coil

Blower

Coil

Filter

Filter

Return
Air

Return
Air

Ductwork

Top Supply, Front Throw, Forward-Curved Blowers

Ductwork

Top Supply, Rear Throw, Forward-Curved Blowers

Liebert DS

Liebert DS Configurations

1.3

Component Location Drawings

Figure 6

Downflow model component locations

1
2
17
16
15
3

14

4
13

5
12
11

10

8
7
6

1. Condenser Cleanout Plugs,


fluid-cooled units only
2. Filters
3. Liebert iCOM
4. Smoke Sensor, optional
5. Fan Pulley
6. Motor
7. Motor Sheave and Belts
8. Blower
9. Condensate Pump, optional

Liebert DS

18

10. Infrared Humidifier, optional


11. Econ-O-Coil Valve, GLYCOOL/Dual Cooling
12. Evaporator Coil
13. Condenser Drain Plugs, fluid-cooled units only
14. Compressor Section
15. Electric Box
16. Disconnect, optional
17. Variable Frequency Drive (optional on
digital scroll units only)
18. EC Fans, optional

18

DPN000958
Rev. 4

Liebert DS Configurations

Figure 7

Upflow model component locations

18
1

2
17

4
5

16
6
15
7

14
13

9
12

1. Condenser Cleanout Plugs


(fluid-cooled units only)
2. Blower
3. Filters - not shown for clarity
4. Fan Pulley
5. Motor Sheave and Belts
6. Liebert iCom Control Display
7. Motor
8. Evaporator Coil
9. Variable Frequency Drive (optional on
digital scroll units only)

10

11

10. Smoke Sensor (optional)


11. Infrared Humidifier (optional)
12. Condensate Pump (optional)
13. Econ-O-Coil Valve (GLYCOOL/Dual Cooling)
14. Condenser Drain Plugs ( fluid-cooled units only)
15. Electric Box
16. Compressor Section
17. Disconnect (optional)
18. EC Fans (optional)

DPN001222
Rev. 2

Liebert DS

Liebert DS Air-Cooled System Data

2.0
Table 1

LIEBERT DS AIR-COOLED SYSTEM DATA


Application dataAir-cooled, EC fan, under-floor discharge
Model Size

028

035

042

053

070

077

105

APPLICATION DATA with EC Fans


Net Application Data BTUH (kW), Standard Air Volume and Evaporator Fan Motor
Semi Hermetic Compressors (4 Step Cooling) with EC Fans
85F DB, 64.5F WB, 52.3F DP (29.4C DB, 18.1C WB) 32.4% RH
Total kBTUH (kW)
Sensible kBTUH (kW)

116.4
(34.1)

143.6
(42.1)

163.6
(47.9)

210.6
(61.7)

247.1
(72.4)

270.3
(79.2)

352.5
(103.3)

116
(34)

141.2
(41.4)

160.9
(47.9)

210.2
(61.6)

245.9
(72)

269.2
(78.9)

337.5
(98.9)

80F DB, 62.9F WB, 52.3F DP (26.7C DB, 17.1C WB) 38.2% RH

Total kBTUH (kW)

110.5
(32.4)

136.8
(40.1)

156.1
(45.7)

198.9
(58.3)

234.8
(68.8)

257.1
(75.3)

338.2
(99.1)

Sensible kBTUH (kW)

105.9
(31)

128.1
(37.5)

146.2
(45.7)

193.9
(56.8)

226.6
(66.4)

248.8
(72.9)

307.2
(90)

75F DB, 61.1F WB, 52.3F DP (23.9C DB, 16.2C WB) 45.1% RH
Total kBTUH (kW)

105.3
(30.9)

130.8
(38.3)

149.5
(43.8)

189
(55.4)

223.9
(65.6)

245.8
(72)

325
(95.2)

Sensible kBTUH (kW)

93.9
(27.5)

113.8
(33.3)

129.9
(43.8)

173.3
(50.8)

201.3
(59)

221.5
(64.9)

80
(273.1)

Net Application Data BTUH (kW), Standard Air Volume and Evaporator Fan Motor
Scroll Compressors Only

Scroll or Digital Scroll Compressors with EC Fans


85F DB, 64.5F WB, 52.3F DP (29.4C DB, 18.1C WB) 32.4% RH
Total kBTUH (kW)

120.8
(35.4)

137.1
(40.2)

155.3
(45.5)

216.8
(63.5)

258.6
(75.8)

277.6 (81.3)

353.7 (103.6)

Sensible kBTUH (kW)

120
(35.2)

136.4
(40)

154.7
(45.3)

215.7
(63.2)

255.6
(74.9)

275.1 (80.6)

338.3 (99.1)

80F DB, 62.9F WB, 52.3F DP (26.7C DB, 17.1C WB) 38.2% RH
Total kBTUH (kW)

113.9
(33.4)

130.4
(38.2)

148.1
(43.4)

206.5
(60.5)

248
(72.7)

265.8 (77.9)

340.2 (99.7)

Sensible kBTUH (kW)

108.7
(31.8)

124.6
(36.5)

141.9
(41.6)

199.1
(58.3)

235
(68.9)

253 (74.1)

308.2 (90.3)

75F DB, 61.1F WB, 52.3F DP (23.9C DB, 16.2C WB) 45.1% RH
Total kBTUH (kW)

107.8
(31.6)

124.7
(36.5)

141.9
(41.6)

197.4
(57.8)

69.9
(238.4)

255.5 (74.9)

327.8 (96)

Sensible kBTUH (kW)

96.1
(28.2)

110.8
(32.5)

126.3
(37)

177.6
(52)

209.4
(61.4)

224.9 (65.9)

274.3 (80.4)

6200
8,000
9,600
(10533.9) (13,592) (16,310)

11,000
(18,689)

13,700
(23,276)

3.75 (2.8) 3.75 (2.8) 3.4 (2.5) 5.4 (4.0)

7.9 (5.9)

10.5 (7.8)

FAN SECTION - Downflow Models - EC Models Under Floor


3

Standard Air Volume - f /m (m3/h)


0.2" external static
Standard Fan Motor hp (kW)
Number of Fans
1.
2.
3.
4.

4,400
(7,476)
3.75 (2.8)
1

5,200
(8,835)
1

Refer to Appendix A for U.S. Department of Energy Performance Data.


Application data is rated and factory-certified per ASHRAE 127-2012 with a 5% tolerance.
Some options or combinations of options may result in reduced air flowContact factory for recommendations.
Digital scroll compressors not available on 077 or 105 models; units available with semi-hermetic and standard scroll compressors only.

Liebert DS

Liebert DS Air-Cooled System Data

Application dataAir-cooled with forward-curved blowers 1

Table 2

028

Model Size

035

042

053

070

077

105

APPLICATION DATA with Forward-Curved Blowers


Net APPLICATION DATA BTUH (kW), Standard Air Volume and Evaporator Fan Motor
Semi Hermetic Compressors (4 Step Cooling) with Forward-Curved Blowers
85F DB, 64.5F WB, 52.3F DP (29.4C DB, 18.1C WB) 32.4% RH
Total kBTUH (kW)

137.6
(40.3)

140.0
(41.0)

157.6
(46.2)

205.3
(60.2)

240.6
(70.5)

262.6
(76.9)

345.6
(101.3)

Sensible kBTUH (kW)

129.6
(38.0)

137.6
(40.3)

155.3
(45.5)

203.8
(59.7)

237.9
(69.7)

259.9
(76.2)

329.6
(96.6)

80F DB, 62.9F WB, 52.3F DP (26.7C DB, 17.1C WB) 38.2% RH
Total kBTUH (kW)

131.8
(38.6)

133.3
(39.1)

150
(43.9)

195.1
(57.2)

229.3
(67.2)

250.6
(73.4)

331.5
(97.1)

Sensible kBTUH (kW)

117.2
(34.3)

124.6
(36.5)

140.5
(41.2)

187.1
(54.8)

217.7
(63.8)

238.2
(69.8)

299.4
(87.7)

75F DB, 61.1F WB, 52.3F DP (23.9C DB, 16.2C WB) 45.1% RH
Total kBTUH (kW)

126.5
(37.1)

127.2
(37.3)

143.3
(42)

185.6
(54.4)

218.9
(64.1)

239.7
(70.2)

318.4
(93.3)

Sensible kBTUH (kW)

104.2
(30.5)

110.3
(32.3)

124.2
(36.4)

166.2
(48.7)

192.9
(56.5)

210.9
(61.8)

265.4
(77.8)

Net APPLICATION DATA BTUH (kW), Standard Air Volume and Evaporator Fan Motor
Scroll Compressors Only

Scroll or Digital Scroll Compressors with Forward-Curved Blowers


85F DB, 64.5F WB, 52.3F DP (29.4C DB, 18.1C WB) 32.4% RH
Total kBTUH (kW)

116.4
(34.1)

135.5
(39.7)

149.2
(43.7)

212.1
(62.1)

252.6
(74.0)

270.1 (79.1)

346.9 (101.6)

Sensible kBTUH (kW)

136.9
(40.1)

116.0
(34.0)

148.9
(43.6)

209.3
(61.3)

246.6
(72.3)

265.6 (77.8)

330.4 (96.8)

80F DB, 62.9F WB, 52.3F DP (26.7C DB, 17.1C WB) 38.2% RH
Total kBTUH (kW)

110.5
(32.4)

130.8
(38.3)

141.9
(41.6)

202.5
(59.3)

243
(71.2)

259 (75.9)

333.5 (97.7)

Sensible kBTUH (kW)

105.9
(31.0)

123.2
(36.1)

136.1
(39.9)

191.6
(56.1)

225
(65.9)

242.6 (71.1)

300.4 (88.0)

75F DB, 61.1F WB, 52.3F DP (23.9C DB, 16.2C WB) 45.1% RH
Total kBTUH (kW)

105.3
(30.9)

125.4
(36.7)

135.7
(39.8)

194.2
(56.9)

233.9
(68.5)

249.3 (73)

321.1 (94.1)

Sensible kBTUH (kW)

93.9
(27.5)

109.4
(32.1)

120.6
(35.3)

170.4
(49.9)

200.1
(58.6)

215.2 (63.1)

266.6 (78.1)

FAN SECTION - Downflow Models - Fixed Pitch, Two Belts


3

Standard Air Volume - f /m (m3/h)


0.2" external static

4,400
(7,476)

5,200
(8,835)

6,300
(10,704)

7,500
(12,743)

9,000
(15,291)

10,400
(17,670)

13,700
(23,276)

Standard Fan Motor hp (kW)

2 (1.5)

3 (2.2)

5 (3.7)

3 (2.2)

5 (3.7)

7.5 (5.6)

10 (7.5)

Optional Fan Motor hp (kW)

3 (2.2)

5 (3.7)

7.5 (5.6)

5 (3.7)

7.5 (5.6)

10 (7.5)

15 (11.2)

Number of Fans
1.
2.
3.
4.

Refer to Appendix A for U.S. Department of Energy Performance Data.


Application data is rated and factory-certified per ASHRAE 127-2012 with a 5% tolerance.
Some options or combinations of options may result in reduced air flowContact factory for recommendations.
Digital scroll compressors not available on 077 or 105 models; units available with semi-hermetic and standard scroll compressors only.

Liebert DS

Liebert DS Air-Cooled System Data

Table 3

Physical dataAir-cooled systems


Model Size

028

035

042

053

070

077

105

EVAPORATOR COIL- A-Frame - Copper Tube/Aluminum Fin

Face Area, sq. ft. (m2) 17.1 (1.6)


Rows of Coil

17.1 (1.6)

17.1 (1.6)

24.7 (2.3)

24.7 (2.3)

24.7 (2.3)

32.3 (3.0)

85.3 (25.0)

102.4
(30.0)

REHEAT SECTION
Electric Reheat - Three-Stage, Stainless Steel Fin Tubular; capacity does not include fan motor heat

Capacity - kBTUH (kW) - Standard


51.2 (15.0) 51.2 (15.0) 51.2 (15.0) 85.3 (25.0) 85.3 (25.0)
Selection
Capacity, kBTUH (kW) - Optional
34.1 (10.0) 34.1 (10.0) 34.1 (10.0) 51.2 (15.0) 51.2 (15.0)
Selection
Electric Reheat - SCR Control, Stainless Steel Fin Tubular (optional selection)
Capacity, kBTUH (kW)

51.2
(15.0)

51.2
(15.0)

51.2
(15.0)

85.3
(25.0)

85.3
(25.0)

51.2 (15.0) 68.3 (20.0)


85.3
(25.0)

102.4
(30.0)

HUMIDIFIER SECTION
Infrared Humidifier (Steam canister humidifiers available on downflow models)

Capacity, lb./hr. (kg/h) 11.0 (5.0)

11.0 (5.0)

11.0 (5.0)

22.0 (10.0) 22.0 (10.0)

22.0 (10.0) 22.0 (10.0)

FILTER SECTION
Disposable Type - Nominal Sizes and Quantities, Standard MERV 8 or Optional MERV 11 (Filter types cannot be mixed, must
be all MERV 8 or all MERV 11.)
Downflow Models
Quantity

2 @ 25x20 2 @ 25x20 2 @ 25x20


Nominal Size, inches
4 @ 25x20 4 @ 25x20
1 @ 25x16 1 @ 25x16 1 @ 25x16

4 @ 25x20 4 @ 25x20

Upflow Models
(Front and Rear return) Filters located in separate filter box on rear return; located on lower unit panel on front return
Quantity

Nominal Size, inches


25x20
25x20
25x20
25x20
25x20
25x20
PIPING CONNECTION SIZES - Air-cooled Liebert DS Indoor Unit (Not External Line Sizes)

8
25x20

Liquid Line, O.D. Cu (2/unit)

1/2

1/2

1/2

5/8

5/8

5/8

5/8

Hot Gas Line, O.D. Cu (2/unit)

5/8

5/8

5/8

7/8

7/8

7/8

1-1/8

Infrared Humidifier, O.D. Cu

1/4

1/4

1/4

1/4

1/4

1/4

1/4

Condensate Drain, FPT

3/4

3/4

3/4

3/4

3/4

3/4

3/4

Condensate Drain w/Optional


1/2
1/2
1/2
1/2
1/2
1/2
Condensate Pump, OD
OUTDOOR AIR-COOLED CONDENSER, STANDARD 95F AMBIENT SELECTION
See Tables 23 and 33 for other selections

1/2

Model (R-407C refrigerant) MCM056_8 MCM056_8 MCM056_8 MCM056_8 MCM080_8 MCM080_8 MCL110_8
Number of Fans

DUAL-COOL UNITS DATA, Water (0% Glycol), Net Application Data kBTUH (kW)
CAUTION: CuNi coil option must be specified when Econ-O-Coil is applied to open water tower.
75F DB, 61.1 WB (23.9C DB, 16.2C WB) 45% RH, 45F EWT, 55F LWT Based on Forward-Curved Blowers

Total Capacity, kBTUH (kW)

89.2
(26.2)

101.6
(29.8)

109.8
(32.2)

170.4
(49.9)

188.8
(55.3)

196.8
(57.7)

258.8
(75.8)

Sensible Capacity, kBTUH (kW)

85 (24.9)

98.2 (28.8) 107.8 (31.6) 157.1 (46) 176.4 (51.7) 185.4 (54.3) 249.1 (73)

Flow Rate GPM (I/m) @ 10F Rise

19 (71.9)

22.4 (84.8) 25.5 (96.5)

Pressure Drop, ft. (kPa), valve, coil 6.1 (18.23) 8.3 (24.81)

36.4 (138)

41.7 (158)

10.50
(31.39)

10.40
(31.09)

13.3 (39.8)

46 (174)

59.4 (225)

15.9 (47.6) 15.9 (47.5)

Airflow, f3/m (m3/h)

4400
(7475)

5500
6600
(9344)
(11213)
Fluid Volumes

8000
(13592)

9600
(16310)

11000
(18689)

13,700
(23,256)

Econ-O-Coil Fluid Volume, gal (l)

5 (19.0)

5 (19.0)

8 (30.4)

8 (30.4)

8 (30.4)

10 (38.0)

5 (19.0)

Application data is rated per ASHRAE 127-2012 with a 5% tolerance

Liebert DS

10

Liebert DS Water-Cooled System Data

3.0

LIEBERT DS WATER-COOLED SYSTEM DATA

Table 4

Application dataWater-cooled, EC fans


Model Size

28

35

42

053

070

077

105U

105V

APPLICATION DATA WITH EC FANS


Net Application Data BTUH (kW), Standard Air Volume and Evaporator Fan Motor
Semi Hermetic Compressors (Four-Step Cooling) with EC Fans
85F DB, 64.5F WB, 52.3F DP (29.4C DB, 18.1C WB) 32.4% RH
Total kBTUH (kW)

143.8
(42.1)

132
(38.7)

171
50.1)

220
(65.1)

268.3
(78.6)

297.1
(87.1)

382.3
(112.1)

356.1
(104.3)

Sensible kBTUH (kW)

135
(39.6)

108.2
(31.7)

166.9
(48.9)

212.9
(63.4)

258.2
(75.7)

285.4
(83.6)

354.6
(103.9)

345.8
(101.3)

80F DB, 62.9F WB, 52.3F DP (26.7C DB, 17.1C WB) 38.2% RH
Total kBTUH (kW)

138.1
(40.5)

135.4
(39.7)

163.4
(47.9)

212.1
(62.2)

256.9
(75.3)

284.7
(83.4)

367.7
(107.8)

339.7
(99.5)

Sensible kBTUH (kW)

122.4
(35.9)

117.3
(34.4)

151.4
(44.4)

197.7
(58)

68.9
(235)

76
(259.5)

94.3
(321.9)

93.2
(318.2)

75F DB, 61.1F WB, 52.3F DP (23.9C DB, 16.2C WB) 45.1% RH
Total kBTUH (kW)
Sensible kBTUH (kW)

38.9
(132.7)

41.4
(141.4)

45.9
(156.7)

59.4
(202.6)

245.8
(72)

273
(80)

352.9
(103.4)

327.8
(96.0)

109.3
(32)

131.9
(38.7)

134.7
(39.5)

176.4
(51.7)

209
(61.2)

230.8
(67.6)

285.7
(83.7)

283.7
(83.1)

Net Application Data BTUH (kW), Standard Air Volume and Evaporator Fan Motor
Scroll Compressors Only
(not available after 12/31/15)

Scroll or Digital Scroll Compressors with EC Fans


85F DB, 64.5F WB, 52.3F DP (29.4C DB, 18.1C WB) 32.4% RH
Total kBTUH (kW)

120
(35.2)

143.3
(42)

162.1
(47.5)

224.1
(66.3)

275.6
(80.8)

301.9
(88.5)

379.9
(111.3)

Sensible kBTUH (kW)

119.9
(35.1)

142.1
(41.6)

161
(47.2)

215.6
(64.3)

262.6
(77)

288.3
(84.5)

353.4
(103.6)

80F DB, 62.9F WB, 52.3F DP (26.7C DB, 17.1C WB) 38.2% RH
Total kBTUH (kW)

116.1
(34)

136.7
(40.1)

154.8
(45.4)

216.1
(63.3)

264.6
(77.5)

290.2
(85)

365.9
(107.2)

Sensible kBTUH (kW)

111
(32.5)

129.4
(37.9)

147
(43.1)

200.1
(58.6)

238.9
(70)

262.3
(76.9)

321.1
(94.1)

75F DB, 61.1F WB, 52.3F DP (23.9C DB, 16.2C WB) 45.1% RH
Total kBTUH (kW)

111.8
(32.8)

131
(38.4)

148.4
(43.5)

206.5
(60.5)

253.5
(74.3)

279.1
(81.8)

352.2
(103.2)

Sensible kBTUH (kW)

99.2
(29.1)

115.2
(33.8)

130.9
(38.4)

178.3
(52.2)

212.7
(62.3)

233.6
(68.5)

285.9
(83.8)

FAN SECTION - Downflow Models - EC Fans Under Floor


Standard Air Volume f3/m (m3/h) 4,400
0.2" External Static (7,476)
Standard Fan Motor, Nominal kW (hp)
(Total for All Fans)
Number of Fans
1.
2.
3.
4.
5.

5,200
(8,835)

6200
(10534)

8,000
(13,592)

9,600
(16,310)

11,000
(18,689)

13700
(23276)

13700
(23276)

3.75
(2.8)

3.75
(2.8)

3.75
(2.8)

3.4
(2.5)

5.4
(4.0)

7.9
(5.9)

10.5
(7.8)

10.5
(7.8)

Refer to Appendix A for U.S. Department of Energy Performance Data.


Canister humidifier not available with EC fans.
Application data is rated and factory certified per ASHRAE 127-2012 with a 5% tolerance.
Some options or combinations of options may result in reduced air flowContact factory for recommendations.
Digital scroll compressors not available on 077 or 105 models; units available with semi-hermetic and standard scroll compressors only

11

Liebert DS

Liebert DS Water-Cooled System Data

Table 5

Application dataWater-cooled units with forward-curved blowers


Model Size

28

35

42

053

070

077

105U

105V

APPLICATION DATA WITH FORWARD-CURVED BLOWERS


Net Application Data, BTUH (kW), Standard Air Volume and Evaporator Fan Motor
Semi-Hermetic Compressors (Four-Step Cooling) with Forward-Curved Blowers
85F DB, 64.5F WB, 52.3F DP (29.4C DB, 18.1C WB) 32.4% RH
Total kBTUH (kW)

141.6
(41.5)

144.7
(42.4)

165.2
(48.4)

211.9
(62.1)

262.5
(76.9)

289.9
(85.0)

376.4
(110.3)

348.9
(102.2)

Sensible kBTUH (kW)

132.8
(38.9)

141.9
(41.6)

161.7
(47.4)

194.6
(57)

248.4
(72.8)

274.4
(80.4)

348.7
(102.2)

338.8
(99.3)

80F DB, 62.9F WB, 52.3F DP (26.7C DB, 17.1C WB) 38.2% RH
Total kBTUH (kW)

135.9
(39.8)

137.9
(40.4)

157.4
(46.1)

205.2
(59.7)

251.6
(73.7)

278.1
(81.5)

361.8
(106)

332.8
(97.5)

Sensible kBTUH (kW)

120.2
(35.2)

128.3
(37.6)

146.1
(42.8)

180.6
(51.9)

225.5
(66.1)

248.8
(72.9)

315.9
(92.6)

311.7
(91.3)

75F DB, 61.1F WB, 52.3F DP (23.9C DB, 16.2C WB) 45.1% RH
Total kBTUH (kW)

130.5
(38.3)

131.9
(38.6)

150.7
(44.2)

196.9
(57.2)

240.8
(70.6)

266.7
(78.2)

346.9
(101.7)

321.1
(94.1)

Sensible kBTUH (kW)

107.1
(31.4)

113.8
(33.3)

129.3
(37.9)

162.1
(46.4)

200.3
(58.7)

220.8
(64.7)

279.8
(82)

277.9
(81.4)

Net Application Data BTUH (kW), Standard Air Volume and Evaporator Fan Motor
Scroll Compressors Only
(not available after 12/31/15)

Scroll or Digital Scroll Compressors with Forward-Curved Blowers


85F DB, 64.5F WB, 52.3F DP (29.4C DB, 18.1C WB) 32.4% RH
Total kBTUH (kW)

117.8
(34.5)

139.7
(40.9)

156.3
(45.8)

219.6
(64.9)

269.6
(79.0)

295.1
(86.5)

374
(109.6)

Sensible kBTUH (kW)

117.7
(34.5)

138.5
(40.6)

155.5
(45.6)

207.9
(62.0)

252.5
(74.0)

277.3
(81.3)

347.5
(101.8)

80F DB, 62.9F WB, 52.3F DP (26.7C DB, 17.1C WB) 38.2% RH
Total kBTUH (kW)

113.9
(33.4)

133.2
(39.0)

148.8
(43.6)

212.1
(62.2)

259.1
(75.9)

283.6
(83.1)

360
(105.5)

Sensible kBTUH (kW)

108.8
(31.9)

125.8
(36.9)

141.6
(41.5)

192.6
(56.4)

229.3
(67.2)

251.5
(73.7)

315.2
(92.4)

75F DB, 61.1F WB, 52.3F DP (23.9C DB, 16.2C WB) 45% RH
Total kBTUH (kW)

109.6
(32.1)

127.5
(37.4)

142.3
(41.7)

202.9
(59.5)

248.5
(72.8)

272.9
(80)

346.3
(101.5)

Sensible kBTUH (kW)

97
(28.4)

111.7
(32.7)

125.5
(36.8)

171.5
(50.3)

203.9
(59.8)

223.7
(65.5)

280
(82.1)

FAN SECTION - Downflow Models - Fixed Pitch, Two Belts


3

Standard Air Volume f /m (m /h) 4,400


0.2" External Static (7,476)

6200
(10534)

7,500
(12,743)

9,000
(15,291)

10,400
(17,670)

13,700
(23,276)

13,700
(23,276)

Standard Fan Motor, hp (kW)

2 (1.5)

3 (2.2)

5 (3.7)

3 (2.2)

5 (3.7)

7.5 (5.6)

10 (7.5)

10 (7.5)

Optional Fan Motor, hp (kW)

3 (2.2)

5 (3.7)

7.5 (5.6)

5 (3.7)

7.5 (5.6)

10 (7.5)

15 (11.2)

15 (11.2)

Number of Fans
1.
2.
3.
4.

5,200
(8,835)

Refer to Appendix A for U.S. Department of Energy Performance Data.


Application data is rated and factory certified per ASHRAE 127-2012 with a 5% tolerance.
Some options or combinations of options may result in reduced air flowContact factory for recommendations.
Digital scroll compressors not available on 077 or 105 models; units available with semi-hermetic and standard scroll compressors only.

Liebert DS

12

Liebert DS Water-Cooled System Data

Table 6

Physical dataWater-cooled units


Model Size

028

035

042

053

070

077

105U

105V

EVAPORATOR COIL- A-Frame - Copper Tube/Aluminum Fin


Face Area, sq. ft. (sq. m) 17.1 (1.6)

17.1 (1.6)

17.1 (1.6)

24.7 (2.3)

24.7 (2.3)

24.7 (2.3)

32.3 (3.0)

32.3 (3.0)

Rows of Coil

85.3
(25.0)

102.4
(30.0)

102.4
(30.0)

20.0 (68.3)

20.0 (68.3)

102.4
(30.0)

102.4
(30.0)

22.0 (10.0)

22.0 (10.0)

REHEAT SECTION
Electric Reheat - Three-stage, Stainless Steel Fin Tubular, capacity does not include fan motor heat
Capacity, kBTUH (kW), Standard Selection

51.2
(15.0)

51.2
(15.0)

51.2
(15.0)

Capacity, kBTUH (kW), Optional Selection 34.1 (10.0) 34.1 (10.0) 34.1 (10.0)

85.3
(25.0)

85.3
(25.0)

15.0 (51.2) 15.0 (51.2) 15.0 (51.2)

Electric Reheat - SCR Control, Stainless Steel Fin Tubular (optional selection)
Capacity, kBTUH (kW)

51.2
(15.0)

51.2
(15.0)

51.2
(15.0)

85.3
(25.0)

85.3
(25.0)

85.3
(25.0)

HUMIDIFIER SECTION
Infrared Humidifier
Capacity, lb./hr. (kg/h) 11.0 (5.0)

11.0 (5.0)

11.0 (5.0)

22.0 (10.0) 22.0 (10.0) 22.0 (10.0)

FILTER SECTION
Disposable Type - Nominal Sizes and Quantities, Standard MERV 8 or Optional MERV 11 (Filter types cannot be mixed, must be all MERV 8 or all
MERV 11.)
Downflow Models
Quantity

Nominal Size, inches 2 @ 25x20 2 @ 25x20 2 @ 25x20


1 @ 25x16 1 @ 25x16 1 @ 25x16
Nominal Size, inches

25x20

25x20

25x20

4 @ 25x20 4 @ 25x20 4 @ 25x20


25x20

25x20

4 @ 25x20

4 @ 25x20

25x20

25x20

25x20

Upflow Models (Front and Rear Return)Filters located in separate filter box on rear return, located on lower unit panel on front return
Quantity

WATER COOLED SYSTEM


Semi-Hermetic Compressors, based on 75F/45% room conditions with EC Fans
Condenser Flow Requirements - Maximum design water pressure 150psi (1034kPa), 350psi (2413kPa) available as option
167.7
(49.2)

172.3
(50.5)

204.3
(59.9)

255
(74.7)

316.5
(92.7)

360.4
(105.6)

475.5
(139.3)

475.5
(139.3)

28
(105.90)

29 (109.7)

34 (128.7)

43 (162.7)

53 (200.6)

60 (227.1)

79 (299.0)

79 (299.0)

Pressure Drop, ft. of water (kPa), with valve 8.9 (26.70) 9.5 (28.4)

12.8 (38.3)

11.2 (33.5) 16.6 (49.6) 20.9 (62.5)

31.3 (93.6)

31.3 (93.6)

THR, kBTUH (kW)


83F (28.3C) EWT, GPM (l/m)

Standard Scroll Compressors Only


(not available after 12/31/15)

WATER COOLED SYSTEM - Digital Scroll Compressors, based on 75F/45% room conditions

Condenser Flow Requirements - Maximum design water pressure 150psi (1034kPa), 350psi (2413kPa) available as option; with EC Fans
THR, kBTUH (kW)

141.8
(41.6)

83F (28.3C) EWT, GPM (l/m) 24 (90.85)


Pressure Drop, ft. of water (kPa), valve 19.7 (6.6)

169.8
(49.8)

194.5
(57)

258.5
(75.8)

325.3
(95.3)

365.6
(107.2)

459.6
(134.7)

55.5
(210.1)

236.6
(62.5)

295.3
(78)

91.4 (30.6)

28.5
(107.9)

32.5 (123)

44 (166)

27.5 (9.2)

35.3 (11.8)

35 (11.7)

54.1 (18.1) 67.5 (22.6)

PIPING CONNECTION SIZES -Water-Cooled Liebert DS Indoor Unit


Water Supply, O.D. Cu 1-5/8" (41) 1-5/8" (41) 2-1/8" (54)

2-1/8" (54) 2-1/8" (54) 2-1/8" (54)

2-1/8" (54)

2-1/8" (54)

Water Return, O.D. Cu

2-1/8" (54) 2-1/8" (54) 2-1/8" (54)

2-1/8" (54)

2-1/8" (54)

1-5/8

1-5/8" (41) 2-1/8" (54)

Infrared Humidifier, O.D. Cu

1/4

1/4

1/4

1/4

1/4

1/4

1/4

1/4

Condensate Drain, FPT

3/4

3/4

3/4

3/4

3/4

3/4

3/4

3/4

Condensate Drain w/Optional Condensate


Pump, OD

1/2

1/2

1/2

1/2

1/2

1/2

1/2

1/2

Hot Water Reheat, O.D. Cu

5/8

5/8

5/8

5/8

5/8

5/8

5/8

5/8

DUAL-COOL UNITS APPLICATION DATA, Water (0% Glycol), Net Application Data kBTUH (kW)
CAUTION: CuNi coil option must be specified when Econ-O-Coil is applied to open water tower.
75F DB, 62.57 WB (23.9C DB, 16.9C WB) 45% RH, 45F EWT, 55F LWT; with EC Fans
Total Capacity, kBTUH (kW)

89.2
(26.2)

101.6
(29.8)

109.8
(32.2)

170.4
(49.9)

198.1
(58)

196.8
(57.7)

280.1
(82.1)

280.1
(82.1)

Sensible Capacity, kBTUH (kW)

85
(24.9)

98.2
(28.8)

107.8
(31.6)

157.1
(46)

181.4
(53.2)

185.4
(54.3)

63.7
(4)

63.7
(4)

Flow Rate, GPM (I/m) @ 10F Rise

19
(1.2)

22.4
(1.4)

25.5
(1.6)

36.4
(2.3)

47.2
(3.0)

46.1
(2.9)

54.9
(3.5)

54.9
(3.5)

10.50
(31.39)

10.40
(31.09)

17.2
(51.41)

15.9 (47.6)

18 (53.80)

18 (53.80)

Pressure Drop, ft. (kPa), valve, coil 6.1 (18.23) 8.3 (24.81)

FLUID VOLUMES
Econ-O-Coil Fluid Volume, gal (l)

5 (19.0)

5 (19.0)

5 (19.0)

8 (30.4)

8 (30.4)

8 (30.4)

10 (38.0)

10 (38.0)

Unit Volume, Without Econ-O-Coil, gal, (l)

4 (15.2)

4 (15.2)

4 (15.2)

7 (26.6)

7 (26.6)

7 (26.6)

8 (30.4)

8 (30.4)

13

Liebert DS

Liebert DS Glycol-Cooled System Data

4.0

LIEBERT DS GLYCOL-COOLED SYSTEM DATA

Table 7

Application dataGlycol-cooled units with EC fans


Model Size

028

035

042

053

070

077

105U

105V

APPLICATION DATA with EC Fans


Net Application Data BTUH (kW), Standard Air Volume and Evaporator Fan Motor, Semi-Hermetic Compressors
(Four-Step Cooling) with EC Fans
85F DB, 64.5F WB, 52.3F DP (29.4C DB, 18.1C WB) 32.4% RH
Total kBTUH (kW)

125.3
(36.7)

130.4
(38.2)

149.9
(43.9)

194.8
(57.1)

238.9
(70)

265.7
(77.9)

346.3
(101.5)

330.9
(97.0)

Sensible kBTUH (kW)

124.4
(36.4)

130.4
(38.2)

149.9
(43.9)

193.5
(56.7)

237.7
(69.7)

263.8
(77.3)

333.4
(97.7)

329.8
(96.6)

80F DB, 62.9F WB, 52.3F DP (26.7C DB, 17.1C WB) 38.2% RH
Total kBTUH (kW)

119.1
(34.9)

122.3
(35.8)

141
(41.3)

185.1
(54.2)

226.8
(66.5)

252.9
(74.1)

331.4
(97.1)

306.1
(89.7)

Sensible kBTUH (kW)

112.9
(33.1)

120.9
(35.4)

138.8
(40.7)

177.6
(52.1)

218.1
(63.9)

242.2
(71.0)

304
(89.1)

301.4
(88.3)

75F DB, 61.1F WB, 52.3F DP (23.9C DB, 16.2C WB) 45.1% RH
Total kBTUH (kW)

113.6
(33.3)

115.8
(33.9)

133.8
(39.2)

176
(51.6)

215.9
(63.3)

241.5
(70.8)

317.1
(92.9)

288.5
(84.5)

Sensible kBTUH (kW)

100.3
(29.4)

107.6
(31.5)

123.6
(36.2)

158.4
(46.4)

194.5
(57.0)

215.7
(63.2)

269.6
(79.0)

267.4
(78.4)

Net Application Data BTUH (kW), Standard Air Volume and Evaporator Fan Motor

Scroll Compressors Only


(not available after 12/31/15)

Scroll or Digital Scroll Compressors with EC Fans

85F DB, 64.5F WB, 52.3F DP (29.4C DB, 18.1C WB) 32.4% RH
Total kBTUH (kW)

108.7
(31.9)

128
(37.5)

145.2
(42.5)

203.6
(59.7)

244.5
(71.6)

272.6
(79.9)

344.6
(101.0)

Sensible kBTUH (kW)

108.7
(31.9)

128
(37.5)

145.2
(42.5)

203
(59.5)

242.2
(71.0)

269.2
(78.9)

332.3
(97.4)

80F DB, 62.9F WB, 52.3F DP (26.7C DB, 17.1C WB) 38.2% RH
Total kBTUH (kW)

103
(30.2)

120.6
(35.3)

136.8
(40.1)

193.4
(56.7)

233.1
(68.3)

260.5
(76.3)

330.7
(96.9)

Sensible kBTUH (kW)

102.6
(30.1)

119.6
(35.1)

135.9
(39.8)

187
(54.8)

221.1
(65.1)

246.6
(72.3)

303.6
(89.0)

75F DB, 61.1F WB, 52.3F DP (23.9C DB, 16.2C WB) 45% RH
Total kBTUH (kW)

97.6
(28.6)

114.7
(33.6)

130.2
(38.2)

184.1
(54.0)

223.2
(65.4)

249.8
(73.2)

317.6
(93.1)

Sensible kBTUH (kW)

92
(27.0)

107.1
(31.4)

121.8
(35.7)

167.2
(49.0)

198.4
(58.1)

219.7
(64.4)

270
(79.1)

11,000
(18,689)

13.700
(23,276)

13.700
(23,276)

FAN SECTION - Downflow Models - EC Fans Under Floor


3

Standard Air Volume f /m (m3/h) 4,400


5,200
6200
8,000
9,600
0.2" External Static (7,476) (8,835) (10534) (13,592) (16,310)
Standard Fan Motor, Nominal hp (kW)
(total for all fans)
Number of fans
1.
2.
3.
4.
5.

3.75
(2.8)

3.75
(2.8)

3.75
(2.8)

3.4
(2.5)

5.4
(4.0)

7.9
(5.9)

10.5
(7.8)

10.5
(7.8)

Refer to Appendix A for U.S. Department of Energy Performance Data.


Application data is rated and factory certified per ASHRAE 127-2012 with a 5% tolerance.
Some options or combinations of options may result in reduced air flowContact factory for recommendations.
Digital scroll compressors not available on 077 or 105 models; units available with semi-hermetic and standard scroll compressors only.
40% ethylene glycol

Liebert DS

14

Liebert DS Glycol-Cooled System Data

Table 8

Application dataGlycol-cooled units with forward-curved blowers 1


Model Size

028

035

042

053

070

077

105U

105V

APPLICATION DATA WITH FORWARD-CURVED BLOWERS


Net Application Data BTUH (kW), Standard Air Volume and Evaporator Fan Motor, Semi-Hermetic Compressors
Semi-Hermetic Compressors (4Step Cooling) with Forward-Curved Blowers
85F DB, 64.5F WB, 52.3F DP (29.4C DB, 18.1C WB) 32.4% RH

Total kBTUH (kW)

123.1
(36.1)

126.8
(37.2)

144.4
(42.3)

194.8
(57.1)

233.2
(68.3)

258.8
(75.9)

340.4
(99.8)

324.4
(95.1)

Sensible kBTUH (kW)

122.2
(35.8)

126.8
(37.2)

144.4
(42.3)

193.5
(56.7)

229.9
(67.4)

254.9
(74.7)

327.4
(96.0)

323.1
(94.7)

80F DB, 62.9F WB, 52.3F DP (26.7C DB, 17.1C WB) 38.2% RH

Total kBTUH (kW)

116.9
(34.2)

118.8
(34.8)

135.3
(39.6)

185.1
(54.2)

221.8
(65)

246.6
(72.3)

325.5
(95.4)

300.0
(87.9)

Sensible kBTUH (kW)

110.7
(32.4)

117.3
(34.4)

133.4
(39.1)

177.6
(52.1)

209.7
(61.5)

232.5
(68.1)

298
(87.3)

295.3
(86.5)

75F DB, 61.1F WB, 52.3F DP (23.9C DB, 16.2C WB) 45% RH

Total kBTUH (kW)

111.4
(32.7)

112.3
(32.9)

128
(37.5)

176
(51.6)

211.5
(62)

235.6
(69.1)

311.2)
(91.2

282.6
(82.8)

Sensible kBTUH (kW)

98.1)
(28.7)

104.1
(30.5)

118.3
(34.7)

158.4
(46.4)

186.4
(54.6)

206.2
(60.4)

263.7
(77.3)

262.2
(76.8)

Net Application Data BTUH (kW), Standard Air Volume and Evaporator Fan Motor
Scroll Compressors Only
(not available after 12/31/15)

Scroll or Digital Scroll Compressors with Forward-Curved Blowers


85F DB, 64.5F WB, 52.3F DP (29.4C DB, 18.1C WB) 32.4% RH
Total kBTUH (kW)

106.5
(31.2)

124.5
(36.5)

139.4
(40.8)

199.3
(58.4)

239
(70.1)

265.7
(77.9)

338.7
(99.3)

Sensible kBTUH (kW)

106.5
(31.2)

124.5
(36.5)

139.4
(40.8)

197.1
(57.8)

234.3
(68.7)

259.8
(76.1)

326.3
(95.6)

80F DB, 62.9F WB, 52.3F DP (26.7C DB, 17.1C WB) 38.2% RH
Total kBTUH (kW)

100.8
(29.6)

117
(34.3)

130.8
(38.3)

189.8
(55.6)

228.3
(66.9)

254.3
(74.5)

324.8
(95.2)

Sensible kBTUH (kW)

100.4
(29.4)

116.1
(34)

130.2
(38.1)

180.5
(52.9)

213.5
(62.6)

236.7
(69.4)

297.7
(87.2)

75F DB, 61.1F WB, 52.3F DP (23.9C DB, 16.2C WB) 45% RH
Total kBTUH (kW)
Sensible kBTUH (kW)

95.4
(28)

111.2
(32.6)

124
(36.4)

181.1
(53.1)

218.8
(64.1)

244
(71.5)

311.6
(91.3)

89.8
(26.3)

103.5
(30.3)

116.3
(34.1)

161
(47.2)

190.1
(55.7)

210.1
(61.6)

264
(77.4)

FAN SECTION - Downflow Models - Fixed Pitch, Two Belts


3

Standard Air Volume f /m (m3/h) 4,400


0.2" External Static (7,476)

6,300
(10,704)

7,500
(12,743)

9,000
(15,291)

10,400
(17,670)

13,700
(23,276)

13,700
(23,276)

Standard Fan Motor hp (kW)

2 (1.5)

3 (2.2)

5 (3.7)

3 (2.2)

5 (3.7)

7.5 (5.6)

10 (7.5)

10 (7.5)

Optional Fan Motor hp (kW)

3 (2.2)

5 (3.7)

7.5 (5.6)

5 (3.7)

7.5 (5.6)

10 (7.5)

15 (11.2)

15 (11.2)

Number of Fans
1.
2.
3.
4.
5.

5,200
(8,835)

Refer to Appendix A for U.S. Department of Energy Performance Data.


Application data is rated and factory certified per ASHRAE 127-2012 with a 5% tolerance.
Some options or combinations of options may result in reduced air flowContact factory for recommendations.
Digital scroll compressors not available on 077 or 105 models; units available with semi-hermetic and standard scroll compressors only.
40% ethylene glycol

15

Liebert DS

Liebert DS Glycol-Cooled System Data

Table 9

Physical dataGlycol-cooled units

Model Size

028

035

042

053

070

077

105U

105V

EVAPORATOR COIL - A-Frame - Copper Tube/Aluminum Fin


Face Area, sq. ft. (sq. m)
Rows of Coil

17.1 (1.6)

17.1 (1.6)

17.1 (1.6)

24.7 (2.3)

24.7 (2.3)

24.7 (2.3)

32.3 (3.0)

32.3 (3.0)

REHEAT SECTION
Electric Reheat - Three-Stage, Stainless Steel Fin Tubular, Capacity Does Not Include Fan Motor Heat
Capacity, kBTUH (kW),
Standard Selection 51.2 (15.0)

51.2 (15.0)

51.2 (15.0)

85.3 (25.0)

85.3 (25.0)

85.3 (25.0)

102.4 (30.0)

102.4) (30.0

Capacity, kBTUH (kW), 34.1 (10.0)


Optional Selection

34.1 (10.0)

34.1 (10.0)

51.2 (15.0)

51.2 (15.0)

51.2 (15.0)

20.0 (68.3)

20.0 (68.3)

85.3 (25.0)

85.3 (25.0)

30.0 (102.4)

30.0 (102.4)

22.0 (10.0)

22.0 (10.0)

22.0 (10.0)

22.0 (10.0)

Electric Reheat - SCR Control, Stainless Steel Fin Tubular (Optional Selection)
Capacity, kBTUH (kW) 51.2 (15.0)

51.2 (15.0)

51.2 (15.0)

85.3 (25.0)

HUMIDIFIER SECTION
Infrared Humidifier
Capacity, lb/hr (kg/h)

11.0 (5.0)

11.0 (5.0)

11.0 (5.0)

22.0 (10.0)

FILTER SECTION - Disposable Type - Nominal Sizes and Quantities, Standard MERV 8 or Optional MERV 11
(Filter types cannot be mixed, must be all MERV 8 or all MERV 11)

Downflow Models
Quantity

Nominal Size, inches 2 @ 25x20


1 @ 25x16

2 @ 25x20
1 @ 25x16

2 @ 25x20
1 @ 25x16

4 @ 25x20

4 @ 25x20

4 @ 25x20

4 @ 25x20

4 @ 25x20

Upflow Models (Front and Rear Return)


Filters located in separate filter box on rear return, located on lower unit panel on front return
Quantity
Nominal Size, inches

25x20

25x20

25x20

25x20

25x20

25x20

25x20

25x20

OUTDOOR DRYCOOLERS - STANDARD 95F AMBIENT SELECTION; SEE Table 49 FOR OTHER SELECTIONS
Model Number
Number of Fans

D-174

D-174

D-225

D-260

D-310

D-350

D-466

D-466

CONDENSER FLOW REQUIREMENTSwith 40% Ethylene Glycol


GLYCOL-COOLED SYSTEM -Semi-Hermetic Compressors, based on 75F/45% room conditions with EC fans
THR, kBTUH (kW) 154.9 (45.4) 159.1 (46.6)

189 (55.4)

238.3 (69.8) 297.7 (87.2) 341.8 (100.2) 456.9 (133.9) 456.9 (133.9)

104F (40C) EGT, GPM


(l/m)

32
(121.1)

33.5
(135)

39
(148)

49
(185)

62
(234.7)

70
(265)

96
(363)

96
(363)

Pressure Drop, ft. of water


(kPa),

12.9
(38.5)

14
(41.9)

18.6
(55.7)

16
(47.7)

25
(74.7)

31.3
(93.6)

50.6
(151.3)

50.6
(151.3)

GLYCOL-COOLED SYSTEM - Digital Scroll Compressors, based on 75F/45% room


conditions with EC Fans
THR, kBTUH (kW) 134.5 (39.4) 162.4 (47.6) 186.8 (54.7)
104F (40C) EGT, GPM
(l/m)

28 (106)

Pressure Drop, ft. of water 10.0 (29.8)


(kPa)

248 (72.7)

Standard Scroll Compressors


with EC Fans
(not available after 12/31/15)

311.1 (91.2) 353.7 (103.7) 440.1 (129)

33.5 (127)

39 (148)

52 (163.5)

64 (242)

73.5 (278)

91.5 (264.9)

14.0 (41.9)

18.6 (55.6)

17.9 (53.5)

26.6 (79.5)

34.4 (102.8)

46.2 (138.1)

PIPING CONNECTION SIZES - Glycol-Cooled Liebert DS Indoor Unit


Glycol Supply, O.D. Cu 1-5/8" (41)

1-5/8" (41)

2-1/8" (54)

2-1/8" (54)

2-1/8" (54)

2-1/8" (54)

2-1/8" (54)

2-1/8" (54)

Glycol Return, O.D. Cu 1-5/8" (41)

1-5/8" (41)

2-1/8" (54)

2-1/8" (54)

2-1/8" (54)

2-1/8" (54)

2-1/8" (54)

2-1/8" (54)

Infrared Humidifier, O.D. Cu

1/4

1/4

1/4

1/4

1/4

1/4

1/4

1/4

Condensate Drain, FPT

3/4

3/4

3/4

3/4

3/4

3/4

3/4

3/4

Condensate Drain w/Optional


Condensate Pump, OD

1/2

1/2

1/2

1/2

1/2

1/2

1/2

1/2

Hot Water Reheat, O.D. Cu

5/8

5/8

5/8

5/8

5/8

5/8

5/8

5/8

Liebert DS

16

Liebert DS GLYCOOL System Data

5.0

LIEBERT DS GLYCOOL

Table 10

SYSTEM DATA

Application dataGLYCOOL units with EC fans 1


Model Size

028

035

042

053

070

077

105U

105V

APPLICATION DATA with EC Fans


Net Application Data BTUH (kW), Standard Air Volume and Evaporator Fan Motor, Semi-Hermetic Compressors
(Four-Step Cooling) with EC Fans
85F DB, 64.5F WB, 52.3F DP (29.4C DB, 18.1C WB) 32.4% RH
Total kBTUH (kW)

124.6
(36.5)

129.3
(37.9)

148.4
(43.5)

197.9
(58.0)

236.3
(69.3)

263.7
(77.3)

342.6
(100.4)

327.4
(95.9)

Sensible kBTUH (kW)

123.7
(36.3)

129.3
(37.9)

148.4
(43.5)

197.8
(58.0)

235.1
(68.9)

259.7
(76.1)

328.7
(96.3)

325.1
(95.2)

80F DB, 62.9F WB, 52.3F DP (26.7C DB, 17.1C WB) 38.2% RH
Total kBTUH (kW)

118.4
(34.7)

121.2
(35.5)

139.5
(40.9)

187.4
(54.9)

224.2
(65.7)

251.5
(73.7)

327.8
(96.1)

302.7
(88.7)

Sensible kBTUH (kW)

112.3
(32.9)

119.8
(35.1)

137.2
(40.2)

182.3
(53.4)

215.5
(63.2)

237.2
(69.5)

299.1
(87.7)

296.8
(87)

75F DB, 61.1F WB, 52.3F DP (23.9C DB, 16.2C WB) 45.1% RH
Total kBTUH (kW)

112.9
(33.1)

114.7
(33.6)

132.3
(38.8)

177.7
(52.1)

213.3
(62.5)

240.5
(70.5)

313.7
(91.9)

285.3
(83.6)

Sensible kBTUH (kW)

99.6
(29.2)

106.6
(31.2)

122
(35.8)

163
(47.8)

192
(56.3)

210.9
(61.8)

265.1
(77.7)

263.5
(77.2)

Net Application Data BTUH (kW), Standard Air Volume and Evaporator Fan Motor

Scroll Compressors Only


(not available after 12/31/15)

Scroll or Digital Scroll compressors with EC Fans

85F DB, 64.5F WB, 52.3F DP (29.4C DB, 18.1C WB) 32.4% RH
Total kBTUH (kW)

108
(31.7)

127.1
(37.2)

143.5
(42.1)

201.6
(59.1)

241.9
(70.9)

263.7
(77.3)

340.9
(99.9)

Sensible kBTUH (kW)

108
(31.7)

127.1
(37.2)

143.5
(42.1)

201.1
(58.9)

239.6
(70.2)

257.9
(75.6)

327.6
(96.0)

80F DB, 62.9F WB, 52.3F DP (26.7C DB, 17.1C WB) 38.2% RH
Total kBTUH (kW)

102.4
(30)

119.6
(35.1)

135.1
(39.6)

191.4
(56.1)

230.6
(67.6)

252.3
(73.9)

327.1
(95.9)

Sensible kBTUH (kW)

102
(29.9)

118.6
(34.8)

134.1
(39.3)

185.1
(54.2)

219.5
(64.3)

234.8
(68.8)

298.8
(91.2)

75F DB, 61.1F WB, 52.3F DP (23.9C DB, 16.2C WB) 45% RH
Total kBTUH (kW)

96.9
(28.4)

113.7
(33.3)

128.5
(37.6)

182.3
(53.4)

220.7
(64.7)

242
(70.9)

314.1
(92.0)

Sensible kBTUH (kW)

91.4
(26.8)

106.1
(31.1)

120.1
(35.2)

165.5
(48.5)

195.8
(57.4)

208.3
(61.0)

265.4
(77.8)

FAN SECTION - Downflow Models - EC Fans Under Floor


3

Standard Air Volume f /m (m3/h) 4,400


0.2" External Static (7,476)
Standard Fan Motor, Nominal hp (kW)
(total for all fans)
Number of fans
1.
2.
3.
4.
5.

5,200
(8,835)

6200
(10,534)

8,000
(13,592)

9,600
(16,310)

10,400 13,500
(17670) (22937)

13,500
(22937)

3.75
(2.8)

3.75
(2.8)

3.75
(2.8)

3.4
(2.5)

5.4
(4.0)

7.9
(5.9)

10.5
(7.8)

10.5
(7.8)

Refer to Appendix A for U.S. Department of Energy Performance Data.


Application data is rated and factory certified per ASHRAE 127-2012 with a 5% tolerance.
Some options or combinations of options may result in reduced air flowContact factory for recommendations.
Digital scroll compressors not available on 077 or 105 models; units available with semi-hermetic and standard scroll compressors only.
40% ethylene glycol

17

Liebert DS

Liebert DS GLYCOOL System Data

Table 11

Application dataGLYCOOL units with forward-curved blowers 1


Model Size

028

035

042

053

070

077

105U

105V

APPLICATION DATA WITH FORWARD-CURVED BLOWERS

Net Application Data BTUH (kW), Standard Air Volume and Evaporator Fan Motor, Semi-Hermetic Compressors
Semi-Hermetic Compressors (Four-Step Cooling) with Forward-Curved Blowers
85F DB, 64.5F WB, 52.3F DP (29.4C DB, 18.1C WB) 32.4% RH

Total kBTUH (kW)

122.4
(35.9)

125.7
(36.8)

142.8
(41.9)

193.2
(56.6)

230.8
(67.6)

255.7
(74.9)

336.5
(98.6)

319.1
(93.5)

Sensible kBTUH (kW)

121.5
(35.6)

125.7
(36.8)

142.8
(41.9)

191.9
(56.2)

227.5
(66.7)

251.7
(73.8)

322.6
(94.6)

316.8
(92.8)

80F DB, 62.9F WB, 52.3F DP (26.7C DB, 17.1C WB) 38.2% RH

Total kBTUH (kW)

116.2
(34.1)

117.7
(34.5)

133.7
(39.2)

183.4
(53.8)

219.4
(64.3)

243.5
(71.4)

321.7
(94.3)

295.2
(86.5)

Sensible kBTUH (kW)

110
(32.3)

116.3
(34.1)

131.9
(38.6)

176
(51.6)

207.3
(60.8)

229.2
(67.2)

293
(89.5)

289.5
(84.8)

75F DB, 61.1F WB, 52.3F DP (23.9C DB, 16.2C WB) 45% RH

Total kBTUH (kW)

110.7
(32.5)

111.1
(32.6)

126.5
(37.1)

174.4
(51.1)

209
(61.3)

232.4
(68.1)

307.6
(90.1)

278.2
(81.5)

Sensible kBTUH (kW)

97.4
(28.5)

103
(30.2)

116.7
(34.2)

156.8
(45.9)

184
(53.9)

202.8
(59.4)

258.9
(75.9)

256.9
(75.3)

Net Application Data BTUH (kW), Standard Air Volume and Evaporator Fan Motor
Scroll Compressors Only
(not available after 12/31/15)

Scroll or Digital Scroll Compressors with Forward-Curved Blowers


85F DB, 64.5F WB, 52.3F DP (29.4C DB, 18.1C WB) 32.4% RH
Total kBTUH (kW)

105.8
(31)

123.5
(36.2)

137.8
(40.4)

197.4
(57.9)

236.6
(69.3)

262
(76.8)

334.8
(98.1)

Sensible kBTUH (kW)

105.8
(31)

123.5
(36.2)

137.8
(40.4)

195.3
(57.2)

231.8
(67.9)

256.2
(75.1)

321.5
(94.2)

80F DB, 62.9F WB, 52.3F DP (26.7C DB, 17.1C WB) 38.2% RH
Total kBTUH (kW)

100.2
(29.4)

116.1
(34)

129.3
(37.9)

187.9
(55.1)

225.9
(66.2)

250.6
(73.4)

321
(94.1)

Sensible kBTUH (kW)

99.8
(29.2)

115.1
(33.7)

128.6
(37.7)

178.8
(52.4)

211.1
(61.9)

233.1
(68.3)

292.7
(89.4)

75F DB, 61.1F WB, 52.3F DP (23.9C DB, 16.2C WB) 45% RH
Total kBTUH (kW)

94.7
(27.8)

110.2
(32.3)

122.5
(35.9)

179.1
(52.5)

216.4
(63.4)

240.3
(70.4)

307.9
(90.3)

Sensible kBTUH (kW)

89.1
(26.1)

102.5
(30)

114.7
(33.6)

159.2
(46.7)

187.6
(55)

206.6
(60.5)

259.3
(76)

13,700
(23,276)

13,700
(23,276)

FAN SECTION - Downflow Models - Fixed Pitch, Two Belts


3

Standard Air Volume f /m (m3/h) 4,400


0.2" External Static (7,476)

6,300
(10,704)

7,500
(12,743)

9,000
(15,291)

10,400
(17,670)

Standard Fan Motor hp (kW)

2 (1.5)

3 (2.2)

5 (3.7)

3 (2.2)

5 (3.7)

7.5 (5.6)

10 (7.5)

10 (7.5)

Optional Fan Motor hp (kW)

3 (2.2)

5 (3.7)

7.5 (5.6)

5 (3.7)

7.5 (5.6)

10 (7.5)

15 (11.2)

15 (11.2)

Number of Fans
1.
2.
3.
4.
5.

5,200
(8,835)

Refer to Appendix A for U.S. Department of Energy Performance Data.


Application data is rated and factory certified per ASHRAE 127-2012 with a 5% tolerance.
Some options or combinations of options may result in reduced air flowContact factory for recommendations.
Digital scroll compressors not available on 077 or 105 models; units available with semi-hermetic and standard scroll compressors only.
40% ethylene glycol

Liebert DS

18

Liebert DS GLYCOOL System Data

Table 12

Physical dataGLYCOOL units


Model Size

028

035

042

053

070

077

105U

105V

EVAPORATOR COIL - A-Frame - Copper Tube/Aluminum Fin


Face Area, sq. ft. (sq. m)
Rows of Coil

17.1 (1.6)

17.1 (1.6)

17.1 (1.6)

24.7 (2.3)

24.7 (2.3)

24.7 (2.3)

32.3 (3.0)

32.3 (3.0)

REHEAT SECTION
Electric Reheat - Three-Stage, Stainless Steel Fin Tubular, Capacity Does Not Include Fan Motor Heat
Capacity, kBTUH (kW), Standard
51.2 (15.0)
Selection

51.2 (15.0)

51.2 (15.0)

85.3 (25.0)

85.3 (25.0)

85.3 (25.0)

102.4 (30.0)

102.4 (30.0)

Capacity, kBTUH (kW), Optional


34.1 (10.0)
Selection

34.1 (10.0)

34.1 (10.0)

51.2 (15.0)

51.2 (15.0)

51.2 (15.0)

68.3 (20.0)

68.3 (20.0)

85.3 (25.0)

85.3 (25.0)

102.4 (30.0)

102.4 (30.0)

22.0 (10.0)

22.0 (10.0)

22.0 (10.0)

22.0 (10.0)

Electric Reheat - SCR Control, Stainless Steel Fin Tubular (Optional Selection)
Capacity, kBTUH (kW) 51.2 (15.0)

51.2 (15.0)

51.2 (15.0)

85.3 (25.0)

HUMIDIFIER SECTION
Infrared Humidifier
Capacity, lb/hr (kg/h)

11.0 (5.0)

11.0 (5.0)

11.0 (5.0)

22.0 (10.0)

FILTER SECTION - Disposable Type - Nominal Sizes and Quantities, Standard MERV 8 or Optional MERV 11
(filter types cannot be mixed, must be all MERV 8 or all MERV 11)
Downflow Models
Quantity

2 @ 25x20
Nominal Size, inches 1 @ 25x16

2 @ 25x20
1 @ 25x16

2 @ 25x20
1 @ 25x16

4 @ 25x20

4 @ 25x20

4 @ 25x20

4 @ 25x20

4 @ 25x20

Upflow Models (Front & Rear Return) Filters located in separate filter box on rear return, located on lower unit panel on front return
Quantity
Nominal Size, inches

25x20

25x20

25x20

25x20

25x20

25x20

25x20

25x20

OUTDOOR DRYCOOLERS - Standard 95F Ambient Selection; See Table 49 for other selections
Model Number
Number of Fans

D-174

D-174

D-225

D-260

D-310

D-350

D-466

D-466

CONDENSER FLOW REQUIREMENTS40% Ethylene Glycol


GLYCOOL SYSTEM - Semi-Hermetic Compressors, Based on 75F/45% Room Conditions with EC Fans
THR, kBTUH (kW) 154.9 (45.4)
104F (40C) EGT, GPM (l/m)

32 (121)

159 (46.6)
33 (125)

189.2 (55.5) 240.8 (70.6) 297.7 (87.2) 339.3 (99.4) 455.9 (133.6) 455.9 (133.6)
40 (151)

49 (185)

62 (235)

71 (269)

95 (360)

95 (360)

Pressure Drop, ft. of water (kPa), 12.9 (38.50) 13.6 (40.60) 19.6 (58.59) 16.0 (47.83) 25.0 (74.73) 32.2 (96.25) 49.6 (148.30) 49.6 (148.30)
GLYCOOL SYSTEM - Digital Scroll Compressors, Based on 75F/45% Room Conditions with EC
Fans
THR, kBTUH (kW) 134.5 (39.4) 162.4 (47.6) 186.8 (54.7)
104F (40C) EGT, GPM (l/m)

28 (98.4)

33.5 (127)

39 (148)

248 (72.7)
51 (193)

Scroll Compressors Only


(not available after 12/31/15)

311.1 (91.2) 351.1 (102.9) 439.1 (128.7)


64 (242)

72 (273)

89 (337)

Pressure Drop, ft. of water (kPa) 10.0 (29.89) 14.0 (41.85) 18.6 (55.60) 17.2 (51.41) 26.6 (79.51) 33.1 (98.84) 43.8 (130.92)

PIPING CONNECTION SIZES - Glycol-Cooled Liebert DS Indoor Unit


Glycol Supply, O.D. Cu 1-5/8" (41)

1-5/8" (41)

2-1/8" (54)

2-1/8" (54)

2-1/8" (54)

2-1/8" (54)

2-1/8" (54)

2-1/8" (54)

Glycol Return, O.D. Cu 1-5/8" (41)

1-5/8" (41)

2-1/8" (54)

2-1/8" (54)

2-1/8" (54)

2-1/8" (54)

2-1/8" (54)

2-1/8" (54)

Infrared Humidifier, O.D. Cu

1/4

1/4

1/4

1/4

1/4

1/4

1/4

1/4

Condensate Drain, FPT

3/4

3/4

3/4

3/4

3/4

3/4

3/4

3/4

Condensate Drain w/Optional


Condensate Pump, OD

1/2

1/2

1/2

1/2

1/2

1/2

1/2

1/2

Hot Water Reheat, O.D. Cu

5/8

5/8

5/8

5/8

5/8

5/8

5/8

5/8

ECON-O-COIL APPLICATION DATA (GLYCOOL Units), 40% Ethylene Glycol, Net Application Data, kBTUH (kW)
75F DB, 62.57FWB (23.9C, 16.9C) 45% RH, 45F EGT Room Conditions with EC Fans
Total capacity kBTUH (kW) 82.8 (24.3)

93.9 (27.5) 103.9 (30.4) 156.8 (45.9) 182.3 (53.4) 182.3 (57.2)

243.3 (71.3)

243.3 (71.3)

Sensible Capacity 82.4 (24.1)

93.9 (27.5) 103.9 (30.4) 152.6 (44.7) 176.9 (51.8) 176.9 (55.3)

238.2 (69.8)

238.2 (69.8)

89 (337)

89 (337)

Flow rate, GPM (l/m)

28 (106)

33.5 (127)

39 (148)

51 (193)

64 (242)

72 (273)

Pressure Drop, ft. of water (kPa) 18.4 (55.0) 25.7 (76.82) 33.8 (101.03) 38.9 (116.27) 59.1 (176.65) 73.5 (219.70) 75.2 (224.78) 75.2 (224.78)
FLUID VOLUMES
Unit Volume Without Econ-O-Coil,
gal (l)

4 (15.2)

4 (15.2)

4 (15.2)

7 (26.6)

7 (26.6)

7 (26.6)

8 (30.4)

8 (30.4)

Unit Volume w/Econ-O-Coil, gal (l)

9 (34.2)

9 (34.2)

9 (34.2)

14 (53.2)

14 (53.2)

14 (53.2)

17 (64.6)

17 (64.6)

19

Liebert DS

Electrical Data

6.0

ELECTRICAL DATA

6.1

Air-cooled Electrical Data

Table 13

Electrical dataAir-cooled systems with EC fans

Reheat
Options

Electric
Standard, kW

None

Electric
Standard kW

None

Electric,
Downsized kW

Electric,
Downsized kW

Humidifier
Options

Infrared

Infrared

None

None

Humidifier

No Humidifier

230 460 575 208

230 460 575 208

Model
#
Volts 208
FLA
DS028 WSA

230 460 575

208

67.3

64.8 32.1 25.5 56.3

54.1 26.9 24.2 67.3

64.8 32.1 25

43

82

78.9 39.2 31.9 60.6

58.4 29.1 25.9

78.9 39.2 30.5

47.3

49.8

DS035 WSA 86.3

83.2 40.8 31.9 68.3

66.1

83.2 40.8 31.1

55

55

70

70

FLA

78.2

DS042 WSA 95.7


OPD

78.1

92.5

46

36

85.2

83

110

50

45

110

110

32 27.1 86.3
40

30

75.9 37.7 33

90
78.2

41.2 35.8 95.7

30

60

60

30

25

70

49.8 23.7 17.8 63.1


26.2 19.7
35

25

70

69

67

80

80

75.7 37.5 29.4

64.8

64.8 31.9 25.6 78.1

92.5

46

36

71.9

71.9 35.4 28.4 85.2

83

110

50

40

110

40

30

75.9 37.7 33
41.2 35.8

26.9 20.4

35

69

67

32.7 24.8

80

80

64.8

64.8

31.9 25.6

78.4

76.4

37.8 29.6

35

25

100
89.6

DS053 WSA 145.3 140.4 69.4 53.9 117.2 112.8 56.5 45 145.3 140.4 69.4 52.8

90.6

90.62 44.9 33.4 117.2 112.8 56.5 45 110.52 107.4 53.1 40.3

50

150

150

70

50

110

110

60

45

125

125

70

50

125

FLA 129.2 125.3 59.9 46.4 127.8 123.4 58 46.4 129.2 125.3 59.9 45.7 101.2 101.2 46.4 34.8 127.8 123.4 58 46.4 101.4

125

45

25

100

70

50

70
55.3

92.1

125

110

32.7 27.1

70
56.9

45

125

35

30

100

50

45

35

60.9 29.5 25.2

82.6 40.8 30.4 109.2 104.8 52.4 42

70

110

45

30

100

150

45

90

40

82.6

150

50

80

FLA 119.9 116 57.1 43.5 109.2 104.8 52.4 42 119.9 116 57.1 43.5

OPD

110

75.9 37.7 33

80

25.6 19.9
31.1 24.1

68.2 33.4 25.5

80

30

51.9
62.8

60.9 29.5 25.2 70.7

80

35

53.5
64.8

68.2 33.4 25.5 63.1

30

70

460 575

54.1 26.9 24.2

80

45

70

230

62.8 31.1 25.9

70.7

90

30

208

21.1 16.8 56.3

FLA

90

40

43

230 460 575

47.3 23.3 18.5 64.8

OPD

OPD

80

82

230 460 575 208

35

44.1 33.5

60

45

101.2 46.9 35.7

DS070 WSA 156.9 152 72.9 55.5 138.2 133.8 62.8 50 156.9 152.0 72.9 55.5 111.6 111.6 51.2 38.4 138.2 133.8 62.8 50 122.15 119.02 56.6 43
OPD

175

175

80

60

175

175

80

FLA 139.2 134.8 61.4 50 139.2 134.8 61

60

80

60

150

50 134.9 131 61.4 47.5 112.6 112.6 49.4 38.4 139.2 134.8 61

175

175

80

60

150

150

70

50

175

175

50

112.6

150

70

50

112.6 49.4 38.4

DS077 WSA 164 159.2 74.8 57.8 151. 146.6 66.2 54 164.0 159.2 74.8 57.8 124.37 124.4 54.6 42.4 151 146.6 66.2 54 129.27 126.15 58.5 45.3
OPD

175

175

80

70

175

175

80

70

175

175

80

60

150

150

70

50

175

175

80

70

150

150

70

50

FLA 171.5 167.1 83.7 69.1 171.5 167.1 83.7 69.1 164 163.5 79.8 62.6 144.9 144.9 72.1 57.5 171.5 167.1 83.7 69.1 144.9

144.9 72.1 57.5

DS105 WSA 198.8 198.2 97.4 76.4 186.5 182.1 91.6 75.4 198.8 198.2 97.4 76.4 159.9 159.9 80 63.8 186.5 182.1 91.6 75.4 169.3

165.5 81.3 63.9

OPD
1.
2.
3.
4.
5.
6.

225

225 110 100

225

225

110 100 225

225 110 90

Reduced reheat for 028, 035, and 042 models is 10kW.


Reduced reheat for 053, 070, and 077 models is 15kW.
Consult local representative for SCR reheat values.
Reduced reheat for 105 kW models is 20kW.
SCCR - Short Circuit Current Rating 65,000 amps rms symmetrical maximum.
Steam canister humidifiers not available on models with EC fans.

Liebert DS

20

200

200 110 80

225

225

110 100

200

200

110 80

Electrical Data

Table 14

Electrical dataAir-cooled systems with forward-curved blowers

Reheat Options

Electric, Std. kW

None

Electric, Std. kW

None

Humidifier Options

Infrared or Steam
Generating Canister

Infrared or Steam
Generating Canister

None

None

Model
028

028

035

035

042

042

Motor
hp Volts
2.0

3.0

3.0

5.0

5.0

7.5

208

230

460

208

230

460

070

5.0

5.0

230

460

575

208

230

460 575

66.4

63.2

31.8 25.2 55.4

52.5

26.6 23.9 66.4

63.2

31.8 24.7 42.1

41.4 20.8 16.5

81.1

77.3

38.9 31.5 59.7

56.8

28.8 25.6 81.1

77.3

38.9 30.2 46.4

45.7

23

18.2

OPD

80

80

60

30

25

40

30

70

70

35

30

80

80

40

30

60

FLA

69.5

66.0

33.2 26.4 58.5

55.3

28.0 25.1 69.5

66.0

33.2 25.9 45.2

44.2 22.2 17.7

WSA

84.2

80.1

40.3

33

62.8

59.6

30.2 26.8 84.2

80.1

40.3 31.4 49.5

48.5 24.4 19.4

OPD

90

80

40

30

80

70

FLA

72.9

69.4

34.5 26.4 65.3

62.1

30.6 26.1 72.9

69.4

34.5 26.4 52.0

51.0 24.8 18.7

WSA

88.5

84.4

41.9 33.0 70.5

67.3

33.1 28.0 88.5

84.4

41.9 32.0 57.2

56.2 27.3 20.6

OPD

90

90

FLA

79.0

75.0

37.3 28.6 71.4

67.7

33.4 28.3 79.0

75.0

37.3 28.6 58.1

56.6 27.6 20.9

WSA

94.6

90.0

44.7 35.8 76.6

72.9

35.9 30.2 94.6

90.0

44.7 34.2 63.3

61.8 30.1 22.8

OPD

100

100

FLA

86.5

82.7

41.6 36.1 86.4

WSA

104

99.3

49.9 39.1 93.5

OPD

110

110

FLA

94.0

89.5

45

45

50

35

35

50

90

90

125

110

40

90

35

90

80

90

40

45

35

70

70

35

25

89.8

45.1 38.9 104.0 99.3

49.9 39.1 80.2

78.7 39.3 31.5

45.0 39.0 93.9

89.5

41

101.4

96

50

40

78.4 39.2 31.6

48.5 41.8 111.5 106.1 53.3 42.0 87.7

85.5 42.7 34.4


110

41

74.8

73.8 37.6 27.9

WSA 137.5 131.6 66.2 50.8 109.4 104.0 53.3 42.5 137.5 131.6 66.2 50.3 82.8

81.8 41.7 30.9

70

110

100

44.8 35.4 80.6


110

125

125

89.3

100

30

45

150

50

45.0 39.0 94.0

45

40

25

71.6 35.8 28.7

50

80

30

41.4 32.5 73.1

110

80

60

82.5

110

35

60

41.6 36.1 86.5


50

45

30

82.7

50

35

90

100

110

45

30

100

110

60

35

80

WSA 111.5 106.1 53.3 42.0 101.0 96.6

OPD
053

208

FLA

FLA 112.1 107.2 53.9


3.0

575

WSA

OPD
053

575

50

125

60

50

125

110

60

49.2 39.5 112.1 107.2 53.9

125

60

50

150

125

70

50

110

110

50

50

45

40

FLA 118.2 112.8 56.7 43.2 107.5 101.6 52.0 41.7 118.2 112.8 56.7 43.2 80.9

79.4 40.4 30.1

WSA 143.6 137.2 69.0 53.5 115.5 109.6 56.1 44.7 143.6 137.2 69.0 52.5 88.9

87.4 44.5 33.1

OPD

110

110

60

45

FLA 127.5 122.1 59.5 46.1 126.1 120.2 57.6 46.1 127.5 122.1 59.5 45.4 99.5

98

46

34.5

150

150

70

50

125

125

70

50

150

150

70

50

WSA 155.2 148.8 72.5 55.2 136.5 130.6 62.4 49.7 155.2 148.8 72.5 55.2 109.9 108.4 50.8 38.1
OPD

175

150

80

60

175

150

80

60

175

150

80

60

150

125

70

50

FLA 135.0 128.9 62.9 49.0 133.6 127.0 61.0 49.0 135.0 128.9 62.9 48.3 107.0 104.8 49.4 37.4
070

077

7.5

7.5

WSA 162.7 155.6 75.9 58.1 144.0 137.4 65.8 52.6 162.7 155.6 75.9 58.1 117.4 115.2 54.2 41.0
OPD

175

FLA

145

175

80

60

175

175

80

60

175

175

80

60

150

150

70

50

138.4 64.4 52.6 145.0 138.4 64.0 52.6 140.7 134.6 64.4 50.1 118.4 116.2 52.4 41.0

WSA 169.8 162.8 77.8 60.4 156.8 150.2 69.2 56.6 169.8 162.8 77.8 60.4 130.2 128.0 57.6 45.0
OPD

200

175

90

70

200

175

80

70

175

175

90

70

175

175

70

60

FLA 151.6 144.4 67.4 54.6 151.6 144.4 67.0 54.6 147.3 140.6 67.4 52.1 125.0 122.2 55.4 43.0
077

10.0

WSA 176.4 168.8 80.8 62.4 163.4 156.2 72.2 58.6 176.4 168.8 80.8 62.4 136.8 134.0 60.6 47.0
OPD

200

200

90

70

200

200

90

70

200

175

90

70

175

FLA 177.4 170.2 88.4 72.6 177.4 170.2 88.4 72.6 169.9 166.6 84.5 66.1 150.8
105

10.0

175
148

80

60

76.8 61.0

WSA 204.7 201.3 102.1 79.9 204.7 201.3 102.1 79.9 204.7 201.3 102.1 79.9 165.8 163.0 84.7 67.3
OPD

250

225

125

100

250

225

125

100

225

225

110

90

225

200

110

90

FLA 192.3 184.2 95.4 78.6 192.3 184.2 95.4 78.6 185.3 180.6 91.5 72.1 166.2 162.0 83.8 67.0
105

15.0

WSA 220.1 215.3 109.1 85.9 220.1 215.3 109.1 85.9 220.1 215.3 109.1 85.9 181.2 177.0 91.7 73.3
OPD

1.
2.
3.
4.
5.

250

250

125

100

250

250

125

100

250

250

125

100

225

225

110

90

Reduced reheat for 028, 035, and 042 models is 10kW.


Reduced reheat for 053, 070, and 077 models is 15kW.
Consult local representative for SCR reheat values.
Reduced reheat for 105 kW models is 20kW.
SCCR - Short Circuit Current Rating 65,000 amps rms symmetrical maximum.

21

Liebert DS

Electrical Data

Table 14

Electrical dataAir-cooled systems with forward-curved blowers (continued)


Reheat Options

Electric, Downsized kW

Humidifier Options
Model

Motor, hp

028

028

035

035

042

042

053

053

070

070

077

077

105

105
1.
2.
3.
4.
5.

2.0

3.0

3.0

5.0

5.0

7.5

3.0

5.0

5.0

7.5

7.5

10.0

10.0

15.0

Infrared or Steam Generating Canister


208

230

460

575

208

230

460

575

FLA

55.4

52.5

26.6

23.9

52.6

50.3

25.3

19.6

WSA

63.9

61.2

30.8

25.6

63.9

61.2

30.8

23.8

OPD

70

70

35

30

70

70

35

25

FLA

58.5

55.3

28

25.1

55.7

53.1

26.7

20.8

WSA

67.0

64.0

32.2

26.8

67.0

64.0

32.2

25.0

OPD

80

70

35

30

70

70

35

25

FLA

65.3

62.1

30.6

26.1

59.1

56.5

28.0

21.3

WSA

71.2

68.2

33.8

28.0

71.2

68.2

33.8

25.7

OPD

90

80

40

35

80

80

40

30

FLA

71.4

67.7

33.4

28.3

65.2

62.1

30.8

23.5

WSA

77.3

73.8

36.6

30.2

77.3

73.8

36.6

27.9

OPD

90

90

45

35

90

80

40

30

FLA

86.4

82.7

41.6

36.1

73.1

71.6

35.8

28.7

WSA

93.5

89.8

45.1

38.9

86.7

83.2

41.7

32.7

OPD

110

110

50

50

100

100

50

40

FLA

93.9

89.5

45.0

39.0

80.6

78.4

39.2

31.6

WSA

101.0

96.6

48.5

41.8

94.2

90.0

45.1

35.6

OPD

125

110

60

50

110

110

50

45

FLA

101.4

96.0

49.2

39.5

84.3

80.8

40.9

31

WSA

109.4

104.0

53.3

42.5

102.7

98.6

49.9

37.8

OPD

125

125

60

50

110

110

60

45

FLA

107.5

101.6

52.0

41.7

90.4

86.4

43.7

33.2

WSA

115.5

109.6

56.1

44.7

108.8

104.2

52.7

40.0

OPD

125

125

70

50

125

125

60

45

FLA

126.1

120.2

57.6

46.1

99.7

98

46.5

35.4

WSA

136.5

130.6

62.4

49.7

120.5

115.8

56.2

42.7

OPD

175

150

80

60

150

125

70

50

FLA

133.6

127.0

61.0

49.0

107.2

104.8

49.9

38.3

WSA

144.0

137.4

65.8

52.6

128.0

122.6

59.6

45.6

OPD

175

175

80

60

150

150

70

50

FLA

145

138.4

64.0

52.6

118.4

116.2

52.4

41.0

WSA

156.8

150.2

69.2

56.6

135.1

129.8

61.5

47.9

OPD

200

175

80

70

175

175

70

60

FLA

151.6

144.4

67.0

54.6

125.0

122.2

55.4

43.0

WSA

163.4

156.2

72.2

58.6

141.7

135.8

64.5

49.9

OPD

200

200

90

70

175

175

80

60

FLA

177.4

170.2

88.4

72.6

150.8

148

76.8

61.0

WSA

192.4

185.2

96.3

78.9

175.2

168.6

86.0

67.4

OPD

250

225

125

100

225

200

110

90

FLA

192.8

184.2

95.4

78.6

166.2

162.0

83.8

67.0

WSA

207.8

199.2

103.3

84.9

190.6

182.6

93.0

73.4

OPD

250

250

125

100

225

225

110

90

Reduced reheat for 028, 035, and 042 models is 10kW.


Reduced reheat for 053, 070, and 077 models is 15kW.
Consult local representative for SCR reheat values.
Reduced reheat for 105 kW models is 20kW.
SCCR - Short Circuit Current Rating 65,000 amps rms symmetrical maximum.

Liebert DS

None

Volts

22

Electrical Data

6.2

Water/Glycol-Cooled Electrical Data

Table 15

Electrical dataWater/glycol-cooled systems with EC fans

Reheat
Options
Humidifier
Options
Model# Volts 208
FLA
028

82

OPD

80

Infrared

Infrared

230

230 460 575 208

None

78.9 39.2 31.9 60.6 58.4 29.1 25.9


80

230

460 575 208

40

30

70

70

35

30

82
80

None

Humidifier

230 460 575 208

None

230 460 575 208

60

55

55

OPD

40

70

70

90

45

78.2 75.9 37.7

30

80

80

33

78.1 75.9 37.7 33

WSA 95.7 92.5

46

36

85.2

83

OPD

50

45

110

110

110

110

30

90

90

30

25

70

70

35

30

45

45

30

26.2 19.7
35

25

69

67

80

80

32.7 27.1
40

30

78.2 75.7 37.5 29.4 64.8 64.8 31.9 25.6 78.1 75.9 37.7 33

41.2 35.8 95.7 92.5


50

110

460 575

62.8 31.1 24.1

60

32 27.1 86.3 83.2 40.8 31.1

90

230

51.9 25.6 19.9

30

43

Electric,
Downsized kW

21.1 16.8 56.3 54.1 26.9 24.2 53.5

40

43

Electric,
Downsized kW

78.9 39.2 30.5 47.3 47.3 23.3 18.5 64.8 62.8 31.1 25.9 64.8
80

25

None

70

70.7 68.2 33.4 25.5 63.1 60.9 29.5 25.2 70.7 68.2 33.4 25.5 49.8 49.8 23.7 17.8 63.1 60.9 29.5 25.2 56.9

FLA 119.9 116


053

460 575 208

Electric
Standard kW

WSA 86.3 83.2 40.8 31.9 68.3 66.1

FLA
042

None

67.3 64.8 32.1 25.5 56.3 54.1 26.9 24.2 67.3 64.8 32.1

WSA

FLA
035

Electric
Standard, kW

110

57.1 43.5 109.2 104.8 52.4 42 119.9 116

46

36

71.9 71.9 35.4 28.4 85.2

83

50

40

100

110

100

45

70

35

25

55.3 26.9 20.4

69

67

80

80

32.7 24.8
35

25

64.8

64.8 31.9 25.6

41.2 35.8 78.4

76.4 37.8 29.6

45

100

100

57.1 43.5 82.6 82.6 40.8 30.4 109.2 104.8 52.4 42

92.1

89.6 44.1 33.5

35

110

50

45

35

WSA 145.3 140.4 69.4 53.9 117.2 112.8 56.5 45 145.3 140.4 69.4 52.8 90.6 90.62 44.9 33.4 117.2 112.8 56.5 45 110.5 107.4 53.1 40.3
OPD

150

150

70

50

125

125

70

50

150

150

70

50

110

110

60

45

125

125

70

50

125

125

60

45

FLA 129.2 125.3 59.9 46.4 127.8 123.4 58 46.4 129.2 125.3 59.9 45.7 101.2 101.2 46.4 34.8 127.8 123.4 58 46.4 101.4 101.2 46.9 35.7
070

WSA 156.9 152


OPD

175

175

72.9 55.5 138.2 133.8 62.8 50 156.9 152.0 72.9 55.5 111.6 111.6 51.2 38.4 138.2 133.8 62.8 50 122.2 119.02 56.6 43
80

FLA 139.2 134.8 61.4


077

60

175

175

80

50 139.2 134.8 61

60

175

175

50 134.9 131

80

60

150

150

70

50

175

175

80

61.4 47.5 112.6 112.6 49.4 38.4 139.2 134.8 61

60

150

150

70

50

50 112.6 112.6 49.4 38.4

WSA 164 159.2 74.8 57.8 151. 146.6 66.2 54 164.0 159.2 74.8 57.8 124.4 124.4 54.6 42.4 151 146.6 66.2 54 129.3 126.15 58.5 45.3
OPD

175

175

80

70

175

175

80

70

175

175

80

60

150

1*0

70

50

175

175

80

70

150

150

70

50

FLA 171.5 167.1 83.7 69.1 171.5 167.1 83.7 69.1 164 163.5 79.8 62.6 144.9 144.9 72.1 57.5 171.5 167.1 83.7 69.1 144.9 144.9 72.1 57.5
105U

105V
1.
2.
3.
4.
5.
6.

WSA 198.8 198.2 97.4 76.4 186.5 182.1 91.6 75.4 198.8 198.2 97.4 76.4 159.9 159.9 80 63.8 186.5 182.1 91.6 75.4 169.3 165.5 81.3 63.9
OPD

225

FLA

164 163.5 82.5 64.7 158.6 154.2 75.7 62.2 164 163.5 82.5 64.7 132

225

110 100 225

225 110 100 225

225

110

90

200

200 110 80

WSA 198.8 198.2 100.1 78.5 173.6 169.2 83.6 68.5 198.8 198.2 100.1 78.5 147

147

OPD

200 100 80

225

225

110

90

225

225 110 90

225

225

110

90

200

225

225 110 100 200

200

110 80

132 64.1 50.6 158.6 154.2 75.7 62.2 140.4 137.4 69.6 54.7
72 56.9 173.6 169.2 84 68.5 169.3 165.5
225

225 110 90

200

200

84

66

100 80

Reduced reheat for 028, 035, and 042 models is 10kW.


Reduced reheat for 053, 070, and 077 models is 15kW.
Consult local representative for SCR reheat values.
Reduced reheat for 105 kW models is 20kW.
SCCR - Short Circuit Current Rating 65,000 amps rms symmetrical maximum.
Steam canister humidifiers not available on models with EC fans.

23

Liebert DS

Electrical Data

Table 16

Electrical dataWater/glycol-cooled systems with forward-curved blowers

Reheat Options

Electric, Std. kW

None

Humidifier
Options

Infrared or Steam
Generating Canister

Infrared or Steam
Generating Canister

Model Motor hp Volts


028

028

035

035

042

042

2.0

3.0

3.0

5.0

5.0

7.5

575

208

230

460

575

208

230

460

575

208

230

460

FLA

66.4

63.2

31.8

25.2

55.4

52.5

26.6

23.9

66.4

63.2

31.8

24.7

42.1

41.4

20.8 16.5

WSA

81.1

77.3

38.9

31.5

59.7

56.8

28.8

25.6

81.1

77.3

38.9

30.2

46.4

45.7

23

18.2

OPD

80

80

40

30

70

70

35

30

80

80

40

30

60

60

30

25

FLA

69.5

66.0

33.2

26.4

58.5

55.3

28.0

25.1

69.5

66.0

33.2

25.9

45.2

44.2

22.2 17.7

WSA

84.2

80.1

40.3

33

62.8

59.6

30.2

26.8

84.2

80.1

40.3

31.4

49.5

48.5

24.4 19.4

OPD

90

80

40

30

80

70

35

30

90

80

40

30

60

60

FLA

72.9

69.4

34.5

26.4

65.3

62.1

30.6

26.1

72.9

69.4

34.5

26.4

52.0

51.0

24.8 18.7

WSA

88.5

84.4

41.9

33.0

70.5

67.3

33.1

28.0

88.5

84.4

41.9

32.0

57.2

56.2

27.3 20.6

OPD

90

90

45

35

90

80

40

35

90

90

45

35

70

70

FLA

79.0

75.0

37.3

28.6

71.4

67.7

33.4

28.3

79.0

75.0

37.3

28.6

58.1

56.6

27.6 20.9

WSA

94.6

90.0

44.7

35.8

76.6

72.9

35.9

30.2

94.6

90.0

44.7

34.2

63.3

61.8

30.1 22.8

OPD

100

100

45

35

90

90

45

35

100

100

45

35

80

80

FLA

86.5

82.7

41.6

36.1

86.4

82.7

41.6

36.1

86.5

82.5

41.4

32.5

73.1

71.6

35.8 28.7

WSA

104

99.3

49.9

39.1

93.5

89.8

45.1

38.9 104.0

99.3

49.9

39.1

80.2

78.7

39.3 31.5

OPD

110

110

50

50

110

110

50

50

110

110

50

45

100

100

FLA

94.0

89.5

45.0

39.0

93.9

89.5

45.0

39.0

94.0

89.3

44.8

35.4

80.6

78.4

39.2 31.6

WSA 111.5 106.1

53.3

42.0 101.0

41.8 111.5 106.1

53.3

42.0

87.7

85.5

42.7 34.4

60

45

110

110

077

7.5

48.5
60

112.1 107.2

53.9

41

101.4

96

49.2

39.5 112.1 107.2

53.9

41

74.8

73.8

37.6 27.9

WSA 137.5 131.6

66.2

53.3

42.5 137.5 131.6

66.2

50.3

82.8

81.8

41.7 30.9

70

50

110

110

1.
2.
3.
4.
5.

50

125

50

40

WSA 143.6 137.2

69.0

53.5 115.5 109.6

56.1

44.7 143.6 137.2

69.0

52.5

88.9

87.4

44.5 33.1

70

50

110

110

60

45

99.5

98

46

34.5

150

150

70

50

125

125

70

50

150

150

127.5 122.1

59.5

46.1 126.1 120.2

57.6

46.1 127.5 122.1

59.5

45.4

WSA 155.2 148.8

72.5

55.2 136.5 130.6

62.4

49.7 155.2 148.8

72.5

55.2 109.9 108.4 50.8 38.1

175

150

80

60

175

150

80

60

175

150

80

60

150

125

70

50

135.0 128.9

62.9

49.0 133.6 127.0

61.0

49.0 135.0 128.9

62.9

48.3 107.0 104.8 49.4 37.4

WSA 162.7 155.6

75.9

58.1 144.0 137.4

65.8

52.6 162.7 155.6

75.9

58.1 117.4 115.2 54.2 41.0

OPD

175

175

80

FLA

145

138.4

64.4

52.6 145.0 138.4

64.0

52.6 140.7 134.6

64.4

50.1 118.4 116.2 52.4 41.0

WSA 169.8 162.8

77.8

60.4 156.8 150.2

69.2

56.6 169.8 162.8

77.8

60.4 130.2 128.0 57.6 45.0

200

175

90

60

70

175

200

175

175

80

80

60

70

175

175

175

175

80

90

60

70

150

175

150

175

70

70

50

60

151.6 144.4

67.4

54.6 151.6 144.4

67.0

54.6 147.3 140.6

67.4

52.1 125.0 122.2 55.4 43.0

WSA 176.4 168.8

80.8

62.4 163.4 156.2

72.2

58.6 176.4 168.8

80.8

62.4 136.8 134.0 60.6 47.0

200

200

177.4 170.2

90
88.4

70

200

200

72.6 177.4 170.2

90
88.4

70

200

175

72.6 169.9 166.6

90
84.5

70

175

66.1 150.8

175
148

80

60

76.8 61.0

WSA 204.7 201.3 102.1 79.9 204.7 201.3 102.1 79.9 204.7 201.3 102.1 79.9 165.8 163.0 84.7 67.3
250

225

192.3 184.2

125

100

95.4

78.6 192.3 184.2

250

225

125

100

95.4

78.6 185.3 180.6

225

225

110
91.5

90

225

200

110

90

72.1 166.2 162.0 83.8 67.0

WSA 220.1 215.3 109.1 85.9 220.1 215.3 109.1 85.9 220.1 215.3 109.1 85.9 181.2 177.0 91.7 73.3
250

250

125

100

125

100

84.5

66.1 164.5 157.3

77.7

63.6 169.9 166.6

WSA 204.7 201.3 102.1 79.9 179.9 172.3

85.6

169.9 166.6
225

225

185.3 180.6

110
91.5

90

250

225

250

225

110

72.1 179.9 171.3

84.7

WSA 220.1 215.3 109.1 85.9 194.9 186.3

92.6

24

250

250

125

100

225

225

110

90

66.1 137.9 135.1 66.1 52


69.9 204.7 201.3 102.1 79.9 152.9 150.1 74 58.3
90

225

225

84.5

90
200
200 100 80
72.1 153.3 149.1 73.1 58
79.5 220.1 215.3 109.1 85.9 168.3 164.1 81 64.3
100 250
250
125 100 225
200 110 80
69.6 185.3 180.6

OPD 250
250
125 100 250
225
110
Reduced reheat for 028, 035, and 042 models is 10kW.
Reduced reheat for 053, 070, and 077 models is 15kW.
Consult local representative for SCR reheat values.
Reduced reheat for 105 kW models is 20kW.
SCCR - Short Circuit Current Rating 65,000 amps rms symmetrical maximum.

Liebert DS

150

40.4 30.1

FLA
15.0

60

79.4

OPD
105V

125

80.9

FLA
10.0

125

45

43.2

OPD
105V

50

50

56.7

FLA
15.0

50.8 109.4 104.0

110

41.7 118.2 112.8

OPD
105U

70

125

52.0

FLA
10.0

125

50

43.2 107.5 101.6

OPD
105U

150

110

56.7

FLA
10.0

125

118.2 112.8

OPD
077

40

110

FLA
7.5

50

30

96.6

OPD
070

40

25

125

FLA
5.0

35

25

50

OPD
070

30

575

60

FLA
5.0

None

460

OPD
053

None

230

FLA
3.0

None

208

OPD
053

Electric, Std. kW

110

91.5

Electrical Data

Table 16

Electrical dataWater/glycol-cooled systems with forward-curved blowers (continued)

Reheat Options
Humidifier Options
Model
Motor, hp
Volts
FLA
028
2.0
WSA
OPD
FLA
028
3.0
WSA
OPD
FLA
035
3.0
WSA
OPD
FLA
035
5.0
WSA
OPD
FLA
042
5.0
WSA
OPD
FLA
042
7.5
WSA
OPD
FLA
053
3.0
WSA
OPD
FLA
053
5.0
WSA
OPD
FLA
070
5.0
WSA
OPD
FLA
070
7.5
WSA
OPD
FLA
077
7.5
WSA
OPD
FLA
077
10.0
WSA
OPD
FLA
105U
10.0
WSA
OPD
FLA
105U
15.0
WSA
OPD
FLA
105V
10.0
WSA
OPD
FLA
105V
15.0
WSA
OPD
1.
2.
3.
4.
5.

Electric, Downsized kW
Infrared or Steam Generating Canister
208
230
460
575
208
55.4
52.5
26.6
23.9
52.6
63.9
61.2
30.8
25.6
63.9
70
70
35
30
70
58.5
55.3
28
25.1
55.7
67.0
64.0
32.2
26.8
67.0
80
70
35
30
70
65.3
62.1
30.6
26.1
59.1
71.2
68.2
33.8
28.0
71.2
90
80
40
35
80
71.4
67.7
33.4
28.3
65.2
77.3
73.8
36.6
30.2
77.3
90
90
45
35
90
86.4
82.7
41.6
36.1
73.1
93.5
89.8
45.1
38.9
86.7
110
110
50
50
100
93.9
89.5
45.0
39.0
80.6
101.0
96.6
48.5
41.8
94.2
125
110
60
50
110
101.4
96.0
49.2
39.5
84.3
109.4
104.0
53.3
42.5
102.7
125
125
60
50
110
107.5
101.6
52.0
41.7
90.4
115.5
109.6
56.1
44.7
108.8
125
125
70
50
125
126.1
120.2
57.6
46.1
99.7
136.5
130.6
62.4
49.7
120.5
175
150
80
60
150
133.6
127.0
61.0
49.0
107.2
144.0
137.4
65.8
52.6
128.0
175
175
80
60
150
145
138.4
64.0
52.6
118.4
156.8
150.2
69.2
56.6
135.1
200
175
80
70
175
151.6
144.4
67.0
54.6
125.0
163.4
156.2
72.2
58.6
141.7
200
200
90
70
175
177.4
170.2
88.4
72.6
150.8
192.4
185.2
96.3
78.9
175.2
250
225
125
100
225
192.8
184.2
95.4
78.6
166.2
207.8
199.2
103.3
84.9
190.6
250
250
125
100
225
164.5
157.3
77.7
63.6
146.3
179.5
172.3
86
69.9
175.2
225
225
110
90
200
179.9
171.3
84.7
69.6
161.7
194.9
186.3
93
75.9
190.6
250
225
110
100
225

None
230
50.3
61.2
70
53.1
64.0
70
56.5
68.2
80
62.1
73.8
80
71.6
83.2
100
78.4
90.0
110
80.8
98.6
110
86.4
104.2
125
98
115.8
125
104.8
122.6
150
116.2
129.8
175
122.2
135.8
175
148
168.6
200
162.0
182.6
225
140.5
168.6
200
154.5
182.6
225

460
25.3
30.8
35
26.7
32.2
35
28.0
33.8
40
30.8
36.6
40
35.8
41.7
50
39.2
45.1
50
40.9
49.9
60
43.7
52.7
60
46.5
56.2
70
49.9
59.6
70
52.4
61.5
70
55.4
64.5
80
76.8
86.0
110
83.8
93.0
110
71.6
86
110
78.6
93
110

575
19.6
23.8
25
20.8
25.0
25
21.3
25.7
30
23.5
27.9
30
28.7
32.7
40
31.6
35.6
45
31
37.8
45
33.2
40.0
45
35.4
42.7
50
38.3
45.6
50
41.0
47.9
60
43.0
49.9
60
61.0
67.4
90
67.0
73.4
90
56.1
67.4
80
62.1
73.4
90

Reduced reheat for 028, 035, and 042 models is 10kW.


Reduced reheat for 053, 070, and 077 models is 15kW.
Consult local representative for SCR reheat values.
Reduced reheat for 105 kW models is 20kW.
SCCR - Short Circuit Current Rating 65,000 amps rms symmetrical maximum.

25

Liebert DS

Weights and Dimensions

7.0

WEIGHTS AND DIMENSIONS

Table 17

Liebert DS shipping and unit weightsapproximate


Downflow

Model #

Compressor
Type

Scroll or
Digital Scroll
DS028-042
Semi-Hermetic

Scroll or
Digital Scroll
DS053
Semi-Hermetic

Scroll or
Digital Scroll
DS070
Semi-Hermetic

Scroll or
Digital Scroll
DS077
Semi-Hermetic

Scroll or
Digital Scroll
DS105
Semi-Hermetic

Liebert DS

Upflow

Cooling Type

EC Fan Unit
Weight lb (kg)

EC Fan Unit
Weight lb (kg)

Forward-Curved
Unit Weight, lb (kg)

Air Cooled

1470 (668)

1370 (621)

1520 (689)

Dual Cool

1620 (736)

1520 (689)

1670 (758)

Water/Glycol

1780 (809)

1680 (762)

1830 (830)

GLYCOOL/ Dual Cool

1930 (877)

1830 (830)

1980 (898)

Air Cooled

1780 (809)

1680 (762)

1830 (830)

Dual Cool

1930 (877)

1830 (830)

1980 (898)

Water/Glycol

1930 (877)

1830 (830)

1980 (898)

GLYCOOL/ Dual Cool

2080 (945)

1980 (898)

2130 (966)

Air Cooled

1920 (871)

1900 (862)

2070 (939)

Dual Cool

2100 (953)

2080 (943)

2250 (1021)

Water/Glycol

2220 (1010)

2200 (998)

2370 (1075)

GLYCOOL/ Dual Cool

2400 (1091)

2380 (1080)

2550 (1157)

Air Cooled

2350 (1069)

2180 (989)

2350 (1069)

Dual Cool

2530 (1150)

2360 (1070)

2530 (1150)

Water/Glycol

2650 (1205)

2480 (1125)

2650 (1205)

GLYCOOL/ Dual Cool

2830 (1287)

2660 (1207)

2830 (1287)

Air Cooled

1970 (894)

1900 (862)

2070 (939)

Dual Cool

2150 (975)

2080 (943)

2250 (1021)

Water/Glycol

2270 (1032)

2200 (998)

2370 (1075)

GLYCOOL/ Dual Cool

2450 (1114)

2380 (1080)

2550 (1157)

Air Cooled

2400 (1091)

2330 (1057)

2500 (1134)

Dual Cool

2580 (1173)

2510 (1139)

2680 (1216)

Water/Glycol

2700 (1228)

2630 (1193)

2800 (1270)

GLYCOOL/ Dual Cool

2880 (1310)

2810 (1275)

2980 (1352)

Air Cooled

2020 (916)

1900 (862)

2070 (939)

Dual Cool

2200 (998)

2080 (943)

2250 (1021)

Water/Glycol

2320 (1055)

2200 (998)

2370 (1075)

GLYCOOL/ Dual Cool

2500 (1137)

2380 (1080)

2550 (1157)

Air Cooled

2450 (1114)

2330 (1057)

2500 (1134)

Dual Cool

2630 (1196)

2510 (1139)

2680 (1216)

Water/Glycol

2750 (1250)

2630 (1193)

2800 (1270)

GLYCOOL/ Dual Cool

2930 (1332)

2810 (1275)

2980 (1352)

Air Cooled

2660 (1207)

2640 (1197)

2880 (1306)

Dual Cool

3015 (1368)

2970 (1347)

3210 (1456)

Water/Glycol

3030 (1374)

3010 (1365)

3250 (1474)

GLYCOOL/ Dual Cool

3385 (1535)

3340 (1515)

3580 (1624)

Air Cooled

2780 (1261)

2760 (1252)

3000 (1361)

Dual Cool

3135 (1422)

3090 (1402)

3330 (1510)

Water/Glycol

3150 (1429)

3130 (1420)

3370 (1529)

GLYCOOL/ Dual Cool

3505 (1590)

3460 (1569)

3700 (1678)

26

Weights and Dimensions

Figure 8

Cabinet and floor planning dimensionsDownflow, air-cooled, 28-42kW (8-12 tons), scroll or
digital scroll compressors with EC fans
Secondary Refrigerant
Piping Entrance
56-7/8" (1445mm)
Opening

33"
(838mm)
35"
(889mm)

Filters are accessible


through top of unit only.
Downflow electrical
connections can be made
from top or bottom of unit.
24-3/8"
(619mm)
Opening

AIR INLET OPENING


1-3/4" (44mm)
Handle

5/16"
Bezel
(8mm)
Secondary Entrance
High-Voltage Connection(s)

TOP VIEW

Secondary Entrance
Low-Voltage Connection(s)
Minimum required
for filter replacement

73" (1854mm)

5"
(127mm)

76"
(1930mm)

34" (864mm)

2"
(51mm)

Shaded area indicates a


recommended minimum
clearance from floor to top
of unit and plenum for
component access.

72" (1829mm)

DPN003131
Rev. 1

FRONT VIEW

27

Liebert DS

Weights and Dimensions

Figure 9

Primary connection locationsDownflow, air-cooled, 28-42kW (8-12 tons), EC fans, scroll or


digital scroll compressor models

NOTES:
A
1. Drawing not to scale.
2. Tolerance on all piping dimensions
is 1/2" (13mm).

A
FRONT VIEW
SECTION A-A

All dimensions from


rear corner of unit
including panels
X

R
4" (102mm)

L1 L2 G1 G2

11.19"
(284mm)

35"
(889mm)
BLOWER
OUTLET

ECS

LV1
LV2
LV3

HUM
CD
B

E1 E2 ECR

4.5"
(114mm)

73" (1854mm)

FRONT OF UNIT

Point
R
L1
L2
G1
G2

CD

HUM
ECS
ECR
HS
HR
E1
E2
LV1
LV2
LV3
B

Description
Refrigerant Access
Liquid Line System 1
Liquid Line System 2
Hot Gas Discharge 1
Hot Gas Discharge 2
Condensate Drain 1
(Infrared Humidifier or No Humidifier)
Condensate Drain 1
(Steam Generating Humidifier)
w/Optional Pump
Humidifier Supply Line
Econ-O-Coil Supply
Econ-O-Coil Return
Hot Water Reheat Supply
Hot Water Reheat Return
Electrical Connection (High-Voltage)
Electrical Connection (High-Voltage)
Electrical Connection (Low-Voltage)
Electrical Connection (Low-Voltage)
Electrical Connection (Low-Voltage)
Blower Outlet

DPN003239
Rev. 0

Connection Size / Opening

59-5/16 (1507)
69-15/16 (1776)
67-5/8 (1718)
65-1/2 (1664)
62-7/16 (1586)

14-3/4 (375)
16-13/16 (411)
16-13/16 (411)
16-13/16 (411)
16-13/16 (411)

11-3/16 x 4 (284 x 102)


1/2" Cu Sweat
1/2" Cu Sweat
5/8" Cu Sweat
5/8" Cu Sweat

46 (1168)

29-1/2 (749)

3/4" FPT

46 (1168)

29-1/2 (749)

1-1/4" FPT

46 (1168)
53-1/2 (1359)
54-7/8 (1394)
49-3/8 (1254)

55-1/2 (1410)
52-7/16 (1332)
2-1/4 (57)
2-1/4 (57)
2-1/4 (57)
4-1/2 (114)

29-1/2 (749)
1/2" Cu Sweat
29 (737)
1/4" Cu Sweat
22-9/16 (573)
1-5/8" Cu Sweat
30-3/4 (781)
1-5/8" Cu Sweat
Consult Factory
Consult Factory
31-1/4 (794)
2-1/2"
31-1/4 (794)
2-1/2"
27 (686)
7/8"
29 (737)
7/8"
31 (787)
7/8"
33 (838)
31 x 31 (787 x 787)

1. Field pitch condensate drain line a minimum of 1/8" (3.2 mm) per foot (305 mm). All units contain a factory-installed condensate trap. Do
not trap external to the unit. Drain line may contain boiling water. Select appropriate drain system materials. The drain line must comply
with all local codes.
2. Source: DPN003239, Rev. 0

Liebert DS

28

Weights and Dimensions

Figure 10

Cabinet and floor planning dimensionsDownflow, air-cooled, 28-42kW (8-12 tons),


semi-hermetic compressors with EC fans
Secondary Refrigerant
Piping Entrance

33"
(838mm)
35"
(889mm)

56-7/8"
Opening
(1445mm)

AIR INLET OPENING


1-3/4"
(44mm) Handle

24-3/8"
(619mm)
Opening

Filters are accessible


through top of unit only.
Downflow electrical
connections can be made
from top or bottom of unit.

5/16"
(8mm) Bezel
Secondary Entrance
High-Voltage Connection(s)

TOP VIEW
Secondary Entrance
Low-Voltage Connections

Minimum required
for filter replacement

86" (2184mm)
5"
(127mm)

76"
(1930mm)

34"
(864mm)

2"
(51mm)

Shaded area indicates a


recommended minimum
clearance from floor
to top of unit and plenum
for component access.

85" (2159mm)

DPN003130
Rev. 1

FRONT VIEW

29

Liebert DS

Weights and Dimensions

Figure 11

Primary connection locationsDownflow, air-cooled, 28-42kW (8-12 tons), EC fans,


semi-hermetic compressor models

NOTES:
A
1. Drawing not to scale.
2. Tolerance on all piping dimensions
is 1/2" (13mm).

All dimensions from


rear corner of unit
including panels

A
FRONT VIEW
O

R
L1 L2 G1 G2

35"
(889mm)

BLOWER
OUTLET

4" (102mm)
16-7/16"
(418mm)

ECS

LV1

HUM

LV2
CD

E1 E2 ECR

SECTION A-A
FRONT OF UNIT

86"
(2184mm)

LV3
4.5"
(114mm)

DPN003598
Rev. 0
Point
R
L1
L2
G1
G2

CD

HUM
ECS 2
ECR 2
E1
E2
LV1
LV2
LV3
B

Description
Refrigerant Access
Liquid Line System 1
Liquid Line System 2
Hot Gas Discharge 1
Hot Gas Discharge 2
Condensate Drain 1
(Infrared Humidifier or No Humidifier)
Condensate Drain 1
(Steam Generating Humidifier)
w/Optional Pump
Humidifier Supply Line
Econ-O-Coil Supply
Econ-O-Coil Return
Electrical Connection (High-Voltage)
Electrical Connection (High-Voltage)
Electrical Connection (Low-Voltage)
Electrical Connection (Low-Voltage)
Electrical Connection (Low-Voltage)
Blower Outlet

X
in. (mm)

Y
in. (mm)

Connection Size / Opening


in. (mm)

63 (1600)
79-3/16 (2011)
76-1/2 (1943)
73-7/8 (1876)
70-1/8 (1780)

13-13/16 (351)
16-3/4 (425)
16-3/4 (425)
16-3/4 (425)
16-3/4 (425)

16-7/16 x 4 (418 x 102)


1/2 Cu Sweat
1/2 Cu Sweat
5/8 Cu Sweat
5/8 Cu Sweat

46 (1168)

29-1/2 (749)

3/4 FPT

46 (1168)

29-1/2 (749)

1-1/4 FPT

46 (1168)
53-1/2 (1359)
54-7/8 (1394)
49-3/8 (1254)
55-1/2 (1410)
52-7/16 (1332)
2-1/4 (57)
2-1/4 (57)
2-1/4 (57)
4-1/2 (114)

29-1/2 (749)
29 (737)
22-9/16 (573)
30-3/4 (781)
31-1/4 (794)
31-1/4 (794)
27 (686)
29 (737)
31 (787)
33 (838)

1/2 Cu Sweat
1/4 Cu Sweat
1-5/8 Cu Sweat
1-5/8 Cu Sweat
2-1/2
2-1/2
7/8
7/8
7/8
31 x 31 (787 x 787)

1. Field pitch condensate drain line a minimum of 1/8" (3.2 mm) per foot (305 mm). All units contain a factory-installed condensate trap. Do
not trap external to the unit. Drain line may contain boiling water. Select appropriate drain system materials. The drain line must comply
with all local codes.
2. Supplied on dual cooling systems only (four-pipe system).
3. Source: DPN003598, Rev. 0

Liebert DS

30

Weights and Dimensions

Figure 12

Cabinet and floor planning dimensionsDownflow, air-cooled, 53-77kW (15-22 tons), scroll or
digital scroll compressors with EC fans
Digital scroll compressors
not available on 077 models.

Second Refrigerant
Piping Entrance
80" (2032mm)
Opening
33"
(838mm)
35"
(889mm)

Secondary Entrance
High-Voltage Connection(s)

Filters are accessible


through top of unit only.
24-5/8"
(625mm)
Opening

AIR INLET OPENING

1-3/4"
(44mm) Handle
TOP VIEW

Downflow electrical
connections can be made
from top or bottom of unit.
5/16"
(8mm)
Minimum required
Bezel
for filter replacement

Secondary Entrance
Low-Voltage Connections
5"
(127mm)

98" (2489mm)

76"
(1930mm)

34"
(864mm)

2"
(51mm)

Shaded area indicates a


recommended minimum
clearance from floor to top
DPN003138
of unit and plenum
for component access. Rev. 2

97" (2464mm)
FRONT VIEW

31

Liebert DS

Weights and Dimensions

Figure 13

Primary connection locationsDownflow, air-cooled, 53-77kW (15-22 tons), scroll or digital


scroll compressors, EC fans
Digital scroll compressors not
available on 077 models.

NOTE: Drawing not to scale.


Tolerance on
A
all piping dimensions
is 1/2" (13mm).

A
FRONT VIEW
SECTION A-A

All dimensions from


rear corner of unit
including panels

X
O

R
4" (102mm)

L1 L2

BLOWER
OUTLET

G1 G2

35"
(889mm)

12-3/16"
(310mm)
ECS ECR
CD
E1 E2

B1

LV1
LV2
LV3

HUM
98" (2489mm)

DPN002182
Rev. 3

FRONT OF UNIT
Point
R

Description
Refrigerant Access

X in. (mm)

Y in. (mm)

Connection Size / Opening in. (mm)

81-3/4 (2076)

14-3/4 (374)

12-3/16x4 (310x102)

53kW (15 tons)/ 70 & 77kW (20 & 22 tons)


L1

Liquid Line System 1

94-11/16 (2405)

16-3/4 (425)

1/2 / 5/8 Cu Sweat

L2

Liquid Line System 2

91-7/8 (2334)

16-3/4 (425)

1/2 / 5/8 Cu Sweat

G1

Hot Gas Discharge 1

88-3/4 (2254)

16-3/8 (416)

7/8 / 1-1/8 Cu Sweat

G2

Hot Gas Discharge 2

85-9/16 (2173)

16-3/8 (416)

7/8 / 1-1/8 Cu Sweat

Condensate Drain
(Infrared Humidifier or No Humidifier)

68-3/8 (1737)

31-3/8 (797)

3/4 FPT

W/ Optional Pump

68-3/8 (1737)

31-3/8 (797)

1/2 Cu Sweat

76-1/2 (1943)

29 (736)

1/4 Cu Sweat

CD 1
HUM

Humidifier Supply Line

Econ-O-Coil Supply

78-5/8 (1997)

22-1/4 (565)

2-1/8 Cu Sweat

ECR 2

Econ-O-Coil Return

73-15/16 (1862)

26-9/16 (675)

2-1/8 Cu Sweat

ECS
E1

Electrical Conn. (High-Voltage)

78-1/2 (1994)

31-1/8 (790)

2-1/2

E2

Electrical Conn. (High-Voltage)

75-3/8 (1915)

31-1/8 (790)

2-1/2

LV1

Electrical Conn. (Low-Voltage)

2 (51)

29 (737)

7/8

LV2

Electrical Conn. (Low-Voltage)

2 (51)

30-7/8 (784)

7/8

LV3

Electrical Conn. (Low-Voltage)

2 (51)

32 (813)

7/8

B1

Blower Outlet

4-1/2 (114)

33 (838)

58-3/8x30 (1483x762)

1. Field-pitch condensate drain line a minimum of 1/8" (3.2 mm) per foot (305 mm). All units contain a factory-installed condensate trap. Do
not trap external to the unit. Drain line may contain boiling water. Select appropriate drain system materials. The drain line must comply
with all local codes.
2. Supplied on dual-cool systems only (four-pipe system).
3. Digital scroll compressors not available on 077 models.
4. Piping dimensions shown are connection sizes; field piping sizes may be different, depending on distance. Refer to user manual,
SL-18826.
5. Source: DPN002182, Rev. 3

Liebert DS

32

Weights and Dimensions

Figure 14

Cabinet and floor planning dimensionsDownflow, air-cooled, 53-77kW (15-22 tons),


semi-hermetic compressors with EC fans
Second Refrigerant
Piping Entrance
80" (2032mm)
Opening

33"
(838mm)
35"
(889mm)

Secondary Entrance
High-Voltage Connection(s)

24-5/8"
(625mm)
Opening

AIR INLET OPENING

1-3/4"
(44mm) Handle

TOP VIEW

Filters are accessible


through top of unit only.
Downflow electrical
connections can be made
from top or bottom of unit.

5/16"
(8mm)
Bezel
Secondary Entrance
Low-Voltage Connections

Minimum required
for filter replacement

109" (2769mm)

5"
(125mm)

76"
(1930mm)

Shaded area indicates a


recommended minimum
clearance be provided for
component access.

108" (2743mm)
2"
(51mm)

FRONT VIEW

33

34"
(864mm)

DPN003137
Rev. 2

Liebert DS

Weights and Dimensions

Figure 15

Primary connection locationsDownflow, air-cooled 53-77kW (15-22 tons), semi-hermetic


compressors with EC fans
All dimensions from
rear corner of unit
including panels

NOTE
A
Drawing not to scale.
Tolerance on all piping
dimensions is 1/2" (13mm).

A
FRONT VIEW

SECTION A-A

R
L1 L2

4" (102mm)

G1 G2

35"
(889mm)

BLOWER
OUTLET

16-7/16"
(418mm)
ECS ECR

CD

E1

B1

LV1
LV2
LV3

HUM
109" (2769mm)

DPN002179
Rev. 1

FRONT OF UNIT

Point
R

Description
Refrigerant Access

X
in. (mm)

Y
in. (mm)

Connection Size / Opening


in. (mm)

82-3/4 (2102)

13-7/8 (352)

16-7/16 x 4 (4181x102)

53kW (15 tons) /70 & 77kw (20 & 22 tons)


L1

Liquid Line System 1

97 (2464)

16-7/8 (428)

1/2 / 5/8 Cu Sweat

L2

Liquid Line System 2

93-5/16 (2370)

16-7/8 (428)

1/2 / 5/8 Cu Sweat

G1

Hot Gas Discharge 1

90-5/8 (2302)

16-5/8 (422)

7/8 / 1-1/8 Cu Sweat

G2

Hot Gas Discharge 2

88 (2235)

16-5/8 (422)

7/8 / 1-1/8 Cu Sweat

Condensate Drain
(Infrared Humidifier or No Humidifier)

68-3/8 (1737)

31-3/8 (797)

3/4 FPT

W/ Optional Pump

68-3/8 (1737)

31-3/8 (797)

1/2 Cu Sweat

Humidifier Supply Line

76-1/2 (1943)

29 (736)

1/4 Cu Sweat

CD 1
HUM
2

Econ-O-Coil Supply

78-5/8 (1997)

22-1/4 (565)

2-1/8 Cu Sweat

ECR 2

Econ-O-Coil Return

73-15/16 (1862)

26-9/16 (675)

2-1/8 Cu Sweat

ECS
E1

Electrical Conn. (High-Voltage)

78-1/2 (1994)

31-1/8 (790)

2-1/2

E2

Electrical Conn. (High-Voltage)

75-3/8 (1915)

31-1/8 (790)

2-1/2

LV1

Electrical Conn. (Low-Voltage)

2 (51)

29 (737)

7/8

LV2

Electrical Conn. (Low-Voltage)

2 (51)

30-7/8 (784)

7/8

LV3

Electrical Conn. (Low-Voltage)

2 (51)

32 (813)

7/8

B1

Blower Outlet

4-1/2 (114)

33 (838)

58-3/8 x 30 (1483x762)

1. Field-pitch condensate drain line a minimum of 1/8" (3.2 mm) per foot (305 mm). All units contain a factory-installed condensate trap. Do
not trap external to the unit. Drain line may contain boiling water. Select appropriate drain system materials. The drain line must comply
with all local codes.
2. Supplied on dual-cool systems only (four-pipe system).
3. Piping dimensions shown are connection sizes; field piping sizes may be different, depending on distance. Refer to user manual,
SL-18826.
4. Source: DPN002179, Rev. 1

Liebert DS

34

Weights and Dimensions

Figure 16

Cabinet and floor planning dimensionsDownflow, air-cooled, 105kW (30 tons), standard
scroll and semi-hermetic compressors with EC fans
Secondary Refrigerant
Piping Entrance

33"
(838mm)
35"
(889mm)

Secondary Entrance
High-Voltage Connection(s)

102-13/16"
(2611mm) Opening

AIR INLET OPENING

TOP VIEW
1-3/4"
(44mm) Handle

Digital scroll compressors


not available on 105 models.

24-3/8"
(619mm)
Opening
5/16"
(8mm)
Bezels
Secondary Entrance
Low-Voltage Connections
Minimum required
for filter replacement

132" (3353mm)

5"
(127mm)

76"
(1930mm)

34" (864mm)
Shaded area indicates the
minimum clearance
required from floor to
top of unit and plenum for
component access.

131" (3327mm)

FRONT VIEW
Filters are accessible through top of unit only.
Downflow electrical connections can be made
from top or bottom of unit.

35

DPN0003145
Rev. 2

Liebert DS

Weights and Dimensions

Figure 17

Primary connection locationsDownflow, air-cooled, 105kW (30 tons), standard scroll and
semi-hermetic compressors with EC fans
Digital scroll compressors not
available on 105 models.

NOTE
A
Drawing not to scale.
Tolerance on all piping
dimensions is 1/2" (13mm).

A All dimensions from


rear corner of unit
including panels

FRONT OF UNIT
SECTION A-A

Y
G1 G2 R
4" (102mm)
L1 L2
16-7/16"
(418mm)

35"
(889mm)

BLOWER
OUTLET
ECS ECR
CD
E1

E2

B1

LV1
LV2
LV3

HUM
132" (3353mm)

DPN002154
Rev. 1

FRONT VIEW

X
in. (mm)

Y
in. (mm)

Connection Size / Opening


in. (mm)

109 (2769)

15-3/4 (400)

16-7/16 x 4 (418 x 102)

Liquid Line System 1

121-3/4 (3092)

16-3/4 (425)

5/8 Cu Sweat

Liquid Line System 2

118-1/8 (3000)

16-3/4 (425)

5/8 Cu Sweat

G1

Hot Gas Discharge 1

118-1/4 (3004)

14-1/4 (362)

1-1/8 Cu Sweat

G2

Hot Gas Discharge 2

115-5/8 (2937)

14-1/4 (362)

1-1/8 Cu Sweat

CD 1

Condensate Drain
(Infrared Humidifier or No Humidifier)

87-3/8 (2220)

31 (787)

3/4 FPT

W/ Optional Pump

83-13/16 (2129)

30 (762)

1/2 Cu Sweat

HUM

Humidifier Supply Line

85-5/16 (2167)

32-1/2 (825)

1/4 Cu Sweat

ECS 2

Econ-O-Coil Supply

101-7/8 (2588)

29 (737)

2-5/8 Cu Sweat

ECR 2

Econ-O-Coil Return

94-9/16 (2402)

29 (737)

2-5/8 Cu Sweat

E1

Electrical Connection (High-Voltage)

98-1/8 (2492)

31 (788)

2-1/2

E2

Electrical Connection (High-Voltage)

91 (2311)

31 (788)

2-1/2

LV1

Electrical Connection (Low-Voltage)

2 (51)

29 (737)

7/8

LV2

Electrical Connection (Low-Voltage)

2 (51)

30-7/8 (784)

7/8

LV3

Electrical Connection (Low-Voltage)

2 (51)

32 (813)

7/8

B1

Blower Outlet

4-1/2 (114)

33 (838)

77-3/8 x 30 (1965 x 762)

Point

Description

Refrigerant Access

L1
L2

1. Field-pitch condensate drain line a minimum of 1/8" (3.2mm) per foot (305 mm). All units contain a factory-installed condensate trap. Do
not trap external to the unit. Drain line may contain boiling water. Select appropriate drain system materials. The drain line must comply
with all local codes.
2. Supplied on dual-cool systems only (four-pipe system)
3. Digital scroll compressors not available on DS105
4. Piping dimensions shown are connection sizes; field piping sizes may be different, depending on distance. Refer to user manual,
SL-18826.
5. Source: DPN002154, Rev. 1

Liebert DS

36

Weights and Dimensions

7.1

Downflow Model Dimensions and Primary Connections


Water/Glycol/GLYCOOL Systems

Figure 18

Cabinet and floor planning dimensionsDownflow, water/glycol/GLYCOOL, 28-42kW


(8-12 tons), all compressors with EC fans
Condenser
Cleanout
Access

56-7/8" (1445mm)
Opening

35"
(889mm)

AIR INLET OPENING

33"
(838mm)

1-3/4"
(44mm) Handle

24-3/8"
(619mm)
Opening

5/16
(8mm)
Bezel

Secondary Condenser Fluid


Piping Entrance

TOP VIEW

Secondary Entrance
High-Voltage Connection(s)

Secondary Entrance
Low-Voltage Connections

Filters are accessible


through top of unit only.
Downflow electrical
connections can be made
from top or bottom of unit.

86" (2184mm)

Required for
condenser cleanout
24"
(610mm)

Minimum required
for filter replacement
15"
(381mm)

76"
(1930mm)

2"
(51mm)

Shaded area indicates a


recommended minimum
clearance from floor to top
of unit and plenum for
component access.

85" (2159mm)

FRONT VIEW

37

34"
(864mm)

DPN003135
Rev. 2

Liebert DS

Weights and Dimensions

Figure 19

Primary connection locationsDownflow, water/glycol/GLYCOOL, 28-42kW, EC fans, all


compressor models

NOTE
1. Drawing not to scale.
2. Tolerance on all
piping dimensions
is 1/2" (13mm).

All dimensions from


rear corner of unit
including panels

FRONT VIEW

SECTION A-A

Y
8"
(203mm)

35"
(889mm)

BLOWER
OUTLET
ECS

3-1/2"
(89mm)

HUM

CD
E1 E2 ECR

LV1
LV2
LV3
4-1/2"
(114mm)

86" (2184mm)

FRONT

Description

Point

X
in. (mm)

DPN003530
Rev. 0

Connection Size / Opening


in. (mm)

Y
in. (mm)

28-35kW (8-10 tons) / 42kW (12 tons)

Water/Glycol/GLYCOOL Access

79-15/16 (2030)

9-1/16 (230)

3-1/2 x 8 (89 x 203)

WS

Water/Glycol/GLYCOOL Supply

82-15/16 (2107)

10-15/16 (278)

1-5/8 / 2-1/8 Cu Sweat

WR

Water/Glycol/GLYCOOL Return

82-15/16 (2107)

14-1/16 (357)

1-5/8 / 2-1/8 Cu Sweat

ECS

Econ-O-Coil Supply

54-7/8 (1394)

22-9/16 (573)

1-5/8 / 2-1/8 Cu Sweat

Econ-O-Coil Return

49-13/16 (1265)

28-1/2 (724)

1-5/8 / 2-1/8 Cu Sweat

46 (1168)

29-1/2 (749)

3/4 FPT

Condensate Drain
(Steam Generating Humidifier)

46 (1168)

29-1/2 (749)

1-1/4 FPT

W/ Optional Pump

46 (1168)

29-1/2 (749)

1/2 Cu Sweat

53-1/2 (1359)

29 (737)

ECR

Condensate Drain 1
(Infrared Humidifier Or No Humidifier)
CD

HUM

Humidifier Supply Line

HS

Hot Water Reheat Supply

1/4 Cu Sweat
Consult Factory

HR

Hot Water Reheat Return

E1

Electrical Connection (High-Voltage)

55-1/2 (1410)

31-1/4 (794)

Consult Factory
2-1/2

E2

Electrical Connection (High-Voltage)

52-7/16 (1332)

31-1/4 (794)

2-1/2

LV1

Electrical Connection (Low-Voltage)

2-1/4 (57)

27 (686)

7/8

LV2

Electrical Connection (Low-Voltage)

2-1/4 (57)

29 (737)

7/8

LV3

Electrical Connection (Low-Voltage)

2-1/4 (57)

31 (787)

7/8

Blower Outlet

4-1/2 (114)

33 (838)

31 x 31 (787 x 787)

1. Field pitch condensate drain line a minimum of 1/8" (3.2 mm) per foot (305 mm). All units contain a factory-installed condensate trap. Do
not trap external to the unit. Drain line may contain boiling water. Select appropriate drain system materials. The drain line must comply
with all local codes.
2. Supplied on dual cool systems only (four-pipe systems).
3. Source: DPN003530, Rev. 0

Liebert DS

38

Weights and Dimensions

Figure 20

Cabinet and floor planning dimensionsDownflow, water/glycol/GLYCOOL, 53-77kW (15-22


tons), all compressors with EC fans
Digital scroll compressors
not available on 077 models.

Condenser Cleanout Access


80" (2032mm)
Opening
33"
(838mm)

24-5/8"
(625mm)
Opening

AIR INLET OPENING

35"
(889mm
1-3/4"
Secondary Condenser
(44mm) Handle
Fluid Piping Entrance
TOP VIEW
Secondary Entrance
High-Voltage Connection(s)

Secondary Entrance
Low-Voltage Connections

Filters are accessible


through top of unit only.
Downflow electrical
connections can be made
from top or bottom of unit.
5/16"
(8mm)
Bezel

24"
(610mm)

109"
(2769mm)

Required for
condenser cleanout

Minimum
required
for filter
replacement
5"
(127mm)

76"
(1930mm)

2"
(51mm)

34"
Shaded area indicates a
(864mm)
recommended minimum
clearance from floor to top
DPN003142
of unit and plenum
Rev. 2
for component access.

108" (2743mm)
FRONT VIEW

39

Liebert DS

Weights and Dimensions

Primary connection locationsDownflow, water/glycol/GLYCOOL, 53-77kW, all compressors


with EC fans

Figure 21

Digital scroll compressors


not available on 077 models.
NOTE: Drawing not to scale.
Tolerance on
all piping dimensions
A
is 1/2" (13mm).

FRONT VIEW
SECTION A-A

All dimensions from


rear corner of unit
including panels

3-1/2"
(89mm)

W
WS
WR

8"
(203mm)

35"
(889mm)
ECS ECR

CD

B1

LV1
LV2
LV3

E1 E2 HUM
109" (2769mm)

DPN002183
Rev. 1

FRONT OF UNIT
X
in. (mm)

Y
in. (mm)

Connection Size / Opening


in. (mm)

Water/Glycol/GLYCOOL Access

103 (2616)

9 (229)

3-1/2 x 8 (89 x 203)

WS

Water/Glycol/GLYCOOL Supply

104-3/4 (2661)

11 (279)

2-1/8 Cu Sweat

WR

Water/Glycol/GLYCOOL Return

104-3/4 (2661)

15 (381)

2-1/8 Cu Sweat

CD

Condensate Drain
(Infrared Humidifier or No Humidifier)*

69-1/4 (1759)

30 (762)

3/4 FPT

W/ Optional Pump

69-1/4 (1759)

30 (762)

1/2 Cu Sweat

HUM

Humidifier Supply Line

76-1/2 (1943)

29 (736)

1/4 Cu Sweat

ECS 3

Econ-O-Coil Supply

78-5/8 (1997)

22-1/4 (565)

2-1/8 Cu Sweat

ECR 3

Econ-O-Coil Return

73-15/16 (1862)

26-9/16 (675)

2-1/8 Cu Sweat

E1

Electrical Connection (High-Voltage)

78-1/2 (1994)

31-1/8 (790)

2-1/2

E2

Electrical Connection (High-Voltage)

75-3/8 (1915)

31-1/8 (790)

2-1/2

LV1

Electrical Connection (Low-Voltage)

2 (51)

28-1/2 (724)

7/8

LV2

Electrical Connection (Low-Voltage)

2 (51)

30-1/4 (768)

7/8

LV3

Electrical Connection (Low-Voltage)

2 (51)

32 (813)

7/8

B1

Blower Outlet

4-1/28 (114)

133 (838)

58-3/8 x 30 (1483 x 762)

Point

Description

1. Field-pitch condensate drain line a minimum of 1/8" (3.2 mm) per foot (305mm). All units contain a factory-installed condensate trap. Do
not trap external to the unit. Drain line may contain boiling water. Select appropriate drain system materials. The drain line must comply
with all local codes.
2. Digital scroll compressors not available on DS077.
3. Supplied on dual-cool systems only (four-pipe system).
4. Source: DPN002183, Rev. 0

Liebert DS

40

Weights and Dimensions

Figure 22

Cabinet and floor planning dimensionsDownflow, water/glycol/GLYCOOL, 105kW (30


tons), all compressors with EC fans
Digital scroll compressors not
available on 105 models.

Condenser Cleanout Access


102-13/16"
(2611mm) Opening
33"
(838mm)

AIR INLET OPENING

35"
(889mm)

Filters are accessible


through top of unit only.
Downflow electrical
24-3/8"
connections can be made
(619mm)
from top or bottom of unit.
Opening
5/16"
(8mm Bezel

Secondary Condenser
Fluid Entrance
Secondary Entrance
High-Voltage Connection(s)

1-3/4"
(44mm) Handle

Secondary Entrance
Low-Voltage Connections

TOP VIEW

24"
(610mm)
132" (3353mm)

Required for
condenser
cleanout
Minimum required
for filter replacement
5"
(127mm)

76"
(1930mm)

34" (864mm)
Shaded area indicates a
recommended minimum
clearance from floor
to top of unit and plenum
for component access.

131" (3327mm)

FRONT VIEW

41

DPN003146
Rev. 2

Liebert DS

Weights and Dimensions

Primary connection locationsDownflow, water/glycol/GLYCOOL 105kW (30 tons), EC fans,


semi-hermetic or standard scroll compressors

Figure 23

Digital scroll compressors


not available on 105 models

NOTES
Drawing not to scale.
Tolerance on
all piping dimensions
is 1/2" (13mm).

All dimensions from

A Rear corner of unit

FRONT VIEW

Including panels
X

SECTION A-A

W
WS
WR

8"
(203mm)

Y
35"
(889mm)

BLOWER
OUTLET

3-1/2"
(89mm)
ECS ECR
CD
E1

E2

B1

LV1
LV2
LV3

HUM
132" (3353mm)

FRONT OF UNIT

Point

Description

DPN002153
Rev. 1

X
in. (mm)

Y
in. (mm)

Connection Size / Opening


in. (mm)

Water/Glycol/GLYCOOL Access

125-15/16 (3199)

9 (229)

3-1/2 x 8 (89x203)

WS

Water/Glycol/GLYCOOL Supply

127-7/8 (3248)

10-1/16 (256)

2-1/8 Cu Sweat

WR

Water/Glycol/GLYCOOL Return

127-7/8 (3248)

13-1/4 (337)

2-1/8 Cu Sweat

CD

Condensate Drain
(Infrared Humidifier or No Humidifier) 1

87-3/8 (2220)

31 (787)

3/4 FPT

W/ Optional Pump

83-13/16 (2129)

30 (762)

1/2 Cu Sweat

HUM

Humidifier Supply Line

85-5/16 (2167)

32-1/2 (825)

1/4 Cu Sweat

ECS 2

Econ-O-Coil Supply

101-7/8 (2588)

29 (737)

2-5/8 Cu Sweat

ECR 2

Econ-O-Coil Return

94-9/16 (2402)

29 (737)

2-5/8 Cu Sweat

E1

Electrical Connection (High-Voltage)

98-1/8 (2492)

31 (788)

2-1/2

E2

Electrical Connection (High-Voltage)

91 (2311)

31 (788)

2-1/2

LV1

Electrical Connection (Low-Voltage)

2 (51)

29 (737)

7/8

LV2

Electrical Connection (Low-Voltage)

2 (51)

30-7/8 (784)

7/8

LV3

Electrical Connection (Low-Voltage)

2 (51)

32 (813)

7/8

B1

Blower Outlet

4-1/2 (114)

33 (838)

77-3/8 x 30 (1965x762)

1. Field-pitch condensate drain line a minimum of 1/8" (3.2 mm) per foot (305 mm). All units contain a factory-installed condensate trap. Do
not trap external to the unit. Drain line may contain boiling water. Select appropriate drain system materials. The drain line must comply
with all local codes.
2. Supplied on dual-cool systems only (four-pipe system).
3. Digital scroll compressors not available on 105 models.
4. Piping dimensions shown are connection sizes; field piping sizes may be different, depending on distance. Refer to user manual,
SL-18826.
5. Source: DPN002153, Rev. 1

Liebert DS

42

Weights and Dimensions

7.2

Downflow Models with Front and/or Rear Discharge

Figure 24

Cabinet and floor planning dimensionsDownflow, 28-42kW (8-12 tons), front and/or rear
discharge models with EC fans
Secondary Refrigerant
Piping Entrance

24" (610mm)

56-7/8" (1445mm)
Opening

33"
(838mm)
35"
(889mm)

Secondary Entrance
High-Voltage Connection(s)

Minimum required
for filter replacement.

Required for Condenser


cleanout on Water/Glycol
or GLYCOOL/Dual cool

AIR INLET OPENING

5"
(127mm)

24-3/8"
(619mm)
Opening

1-3/4"
(44mm) Handle

5/16"
(8mm) Bezels
Secondary Entrance
Low-Voltage Connections

TOP VIEW
A

Shaded area indicates a


recommended minimum
clearance from floor to top
of unit and plenum
for component access.

34"
(864mm)

76"
(1930mm)

33-1/2"
(851mm)

19"
(483mm) Air Outlet

Opening
2"
(51mm)

3-1/4"
(81mm)
B

3"
(76mm)
3"
(77mm)

33-3/8"
(848mm)
19"
(483mm)
Air Outlet

FRONT VIEW

Filters are accessible only through top of unit.


Customer Piping and Wiring Connections
1. For primary connection locations see standard submittals.
A floor stand at least 9" high is recommended if primary
connections locations are to be used.
2. Contact the factory to relocate connection locations.

43

Opening
3-1/4"
(81mm)

DPN003180
Rev. 1

Liebert DS

Weights and Dimensions

Figure 25

Cabinet and floor planning dimensionsDownflow, 53-77kW (15-22 tons), front and/or rear
discharge models with EC fans
Secondary Refrigerant
Piping Entrance

35"
(889mm)

24" (610mm)
80" (2032mm)
Opening

1-34"
(44mm) Handle

5/16"
(619mm) Bezel
Secondary Entrance
Low-Voltage Connections

TOP VIEW

Secondary Entrance
High-Voltage Connection(s)

Minimum required
for filter replacement.
5"
(127mm)

25-5/8"
(619mm)
Opening

AIR INLET OPENING

33"
(838mm)

Required for Condenser


cleanout on Water/Glycol or
GLYCOOL/Dual Cool.

Shaded area indicates


a recommended minimum
clearance from floor to top
of unit and plenum for
component access.

34"
(864mm)

76"
(1930mm)
15-1/8"
(384mm)
29-1/4"
(743mm)

Air Outlet
Opening

2"
(51mm)

FRONT VIEW

15-1/8"
(384mm)
29-5/8"
(752mm)

Customer Piping and Wiring Connections


1. For primary connection locations see standard submittals.
A floor stand at least 9" high is recommended if primary
connections locations are to be used.
2. Contact the factory to relocate connection locations.

15-1/8"
(384mm)
29-5/8"
(752mm)
Air Outlet
Opening

3-1/4"
(83mm)

Filters are accessible through top of unit only.

Liebert DS

3-1/8"
(79mm)

Air Outlet
Opening

3"
(76mm)

DPN003181
Rev. 1

44

3-1/4"
(83mm)

15-1/8"
(384mm)
29-1/4"
(743mm)
Air Outlet
Opening

REAR VIEW

Weights and Dimensions

Figure 26

Cabinet and floor planning dimensionsDownflow, air-cooled, 105kW (30 tons), front
discharge models with EC fans
Secondary Refrigerant
Piping Entrance
102-7/8" (2611mm)
Opening

33"
(838mm)

24-3/8"
(619mm)
Opening

AIR INLET OPENING

35"
(889mm)

Secondary Entrance
High-Voltage Connection(s)

1-34"
(44mm)
Handle

5/16"
(619mm)
Secondary Entrance
Bezel
Low-Voltage Connections

TOP VIEW

Required for Condenser cleanout


on Water/Glycol or GLYCOOL/Dual Cool.

132" (3353mm)

24"
(610mm)

Minimum required
for filter replacement.

5"
(127mm)

76"
(1930mm)
16-1/8"
(410mm)

16-1/8"
(410mm)

25-5/8"
(649mm)
Air Outlet
Opening

24-7/8"
(649mm)
Air Outlet
Opening

131" (3326mm)

16-1/8"
(410mm)
28-1/4"
(718mm)
Air Outlet
Opening

30-7/8"
(783mm)
57-1/2"
(1459mm)

FRONT VIEW
Filters are accessible through top of unit only.
Downflow electrical connections can be made
from top or bottom of unit.
Customer Piping and Wiring Connections
1. For primary connection locations see standard submittals.
A floor stand at least 9" high is recommended if primary
connections locations are to be used.
2. Contact the factory to relocate connection locations.

45

3/4"
(19mm)
34"

Shaded area indicates a


(864mm)
recommended minimum
clearance from floor to top of unit
and plenum for component access.

DPN003182
Rev. 1

Liebert DS

Weights and Dimensions

7.3

Disassembly DimensionsDownflow Air-Cooled Systems

Figure 27

Disassembly dimensionsDownflow, air-cooled, 28-42kW (8-12 tons), scroll or digital scroll


compressors with EC fans

Filter & Electric


Box Assembly

39"
(991mm)

76"
(1930mm)
Assembled
Height

Blower & Coil


Assembly

Compressor Assembly

76"
(1930mm)

59-7/16"
(1509mm)
37"
(940mm)

33"
(838mm)

13"
(330mm)

59" (1499mm)
72" (1829mm)
Assembled Length

Drawing views are simplified with panels removed to show overall dimensions.
See disassembly and handling instructions in installation manual.
Dry Weight, Approximate, lb. (kg)
Air-Cooled

Dual-Cool

Compressor Assembly

490 (223)

490 (223)

Filter and Electric Box Assembly

210 (96)

210 (96)

Blower and Coil Assembly

770 (350)

920 (418)

Component

Source: DPN000802, Rev. 2

Liebert DS

46

DPN003133
Rev. 1

Weights and Dimensions

Figure 28

Disassembly dimensionsDownflow, air-cooled, 28-42kW (8-12 tons), semi-hermetic


compressors with EC fans

Filter & Electric


Box Assembly

39"
(991mm)

76"
(1930mm)
Assembled
Height

Blower & Coil


Assembly

Compressor Assembly

76"
(1930mm)

59-7/16"
(1509mm)
37"
(940mm)

33"
(838mm)

26"
(660mm)

59" (1499mm)
85" (2159mm)
Assembled Length

Drawing views are simplified with panels removed to show overall dimensions.
See disassembly and handling instructions in installation manual.

DPN003132
Rev. 1

Dry Weight, Approximate, Including Panels, lb (kg)


Air-Cooled

Dual-Cooled

Compressor Assembly

800 (364)

800 (364)

Filter and Electric Box Assembly

210 (96)

210 (96)

Blower and Coil Assembly

770 (350)

920 (418)

Component

Source: DPN003132, Rev. 1

47

Liebert DS

Weights and Dimensions

Figure 29

Disassembly dimensionsDownflow, air-cooled, 53-77kW (15-22 tons), scroll or digital scroll 1


compressors
Digital scroll compressors
not available on 077 models.

Filter & Electric Box Assembly

39"
(991mm)

76"
(1930mm)
Assembled
Height

Compressor Assembly
Blower & Coil Assembly

76"
(1930mm)

59-7/16"
(1509mm)
37"
(940mm)

33"
(838mm)

DS053-DS077 =
15" (381mm)

82" (2083mm)
Assembled Length
DS053-DS077 = 97" (2464mm)

Drawing views are simplified with panels removed to show over all dimensions.
See disassembly and handling instructions in installation manual.

DPN003140
Rev. 1

Dry Weight, Approximate, Including Panels, lb (kg)


Air-Cooled

Dual-Cool

Compressor Assembly

540 (246)

540 (246)

Filter and Electric Box Assembly

250 (114)

250 (114)

Blower and Coil Assembly

1230 (560)

1410 (641)

Component

1. Digital scroll compressors not available on 077 models.


2. Source: DPN003140, Rev. 1

Liebert DS

48

Weights and Dimensions

Figure 30

Disassembly dimensionsDownflow, air-cooled, 53-77kW (15-22 tons), semi-hermetic


compressors

Filter & Electric


Box Assembly

39"
(991mm)

76"
(1930mm)
Assembled
Height

Compressor Assembly
Blower & Coil
Assembly

76"
(1930mm)
59-3/8"
(1507mm)
37"
(940mm)

33"
(838mm)

26"
(660mm)

82" (2083mm)

108" (2743mm)
Assembled Length
Drawing views are simplified with panels removed to show overall dimensions.
See disassembly and handling instructions in installation manual.

DPN003139
Rev. 1

Dry Weight, Approximate, Including Panels, lb (kg)


Component

Air-Cooled

Dual-Cool

Compressor Assembly

970 (441)

970 (441)

Filter and Electric Box Assembly

250 (114)

250 (114)

Blower and Coil Assembly

1230 (560)

1410 (641)

Source: DPN003139, Rev. 1

49

Liebert DS

Weights and Dimensions

Figure 31

Disassembly dimensionsDownflow, air-cooled, 105kW (30 tons), standard scroll


compressors
Digital scroll compressors
not available on 105 models.

Filter & Electric Box Assembly

39"
(991mm)
41-11/16"
(1059mm)

Compressor Assembly
76"
(1930mm)
Assembled Height

Blower & Coil


Assembly

76"
(1930mm)

59-7/16"
(1510mm)
37"
(940mm)

33"
(838mm)

105" (2667mm)

26"
(660mm)

131" (3327mm)
Assembled Length
Drawing views are simplified with panels removed to show overall dimensions.
See disassembly and handling instructions in installation manual.

DPN003148
Rev. 2

Dry Weight, Approximate Including Panels, lb (kg)


EC Fans
Air-Cooled

Dual-Cool

Compressor Assembly

830 (377)

830 (377)

Filter and Electric Box Assembly

270 (123)

270 (123)

Blower and Coil Assembly

1560 (708)

1915 (870)

Component

1. Digital scroll compressors not available on 105 models.


2. Source: DPN003148, Rev. 2

Liebert DS

50

Weights and Dimensions

Figure 32

Disassembly dimensionsDownflow, air-cooled, 105kW (30 tons), semi-hermetic


compressors

Filter and Electric Box Assembly

39"
(991mm)
41-11/16"
(1059mm)

Compressor
Assembly

76"
(1930mm)
Assembled
Height

Blower and Coil Assembly

76"
(1930mm)

59 7/16"
(1510mm)
37"
(940mm)
33"
(838mm)

26"
(660mm)

105" (2667mm)

DPN003147
Rev. 1

131" (3327mm)
Assembled Length
Dry Weight, Approximate, Including Panels, lb (kg)
EC Fans
Component
Compressor Assembly

Air-Cooled

Dual-Cool

950 (432)

950 (432)

Filter and Electric Box Assembly

270 (123)

270 (123)

Blower and Coil Assembly

1560 (708)

1915 (870)

Source: DPN003147, Rev. 1

51

Liebert DS

Weights and Dimensions

7.4

Disassembly DimensionsDownflow, Water/Glycol/GLYCOOL Systems

Figure 33

Disassembly dimensionsDownflow, water/glycol/GLYCOOL, 28-42kW (8-12 tons), all


compressors

Filter & Electric


Box Assembly

39"
(991mm)

Compressor Assembly

76"
(1930mm)
Assembled
Height

Blower & Coil


Assembly

76"
(1930mm)

59-7/16"
(1509mm)
37"
(940mm)

33"
(838mm)

26"
(660mm)

59" (1499mm)

85" (2159mm)
Assembled Length
Drawing views are simplified with panels removed to show overall dimensions.
See disassembly and handling instructions in installation manual.

DPN003136
Rev. 1

Dry Weight, Approximate, Including Panels, lb (kg)


Semi-Hermetic Compressor

Scroll or Digital Scroll Compressor

Water/Glycol

GLYCOOL/Dual-Cool

Water/Glycol

GLYCOOL/Dual-Cool

Compressor Assembly

950 (432)

950 (432)

800 (364)

800 (364)

Filter and Electric Box Assembly

210 (96)

210 (96)

210 (96)

210 (96)

Blower and Coil Assembly

770 (350)

920 (418)

770 (350)

920 (418)

Component

Source: DPN003136, Rev. 1

Liebert DS

52

Weights and Dimensions

Figure 34

Disassembly dimensionsDownflow, water/glycol/GLYCOOL, 53-77kW (15-22 tons), all


compressors
Digital scroll compressors
not available on 077 models.

Filter & Electric Box Assembly

39"
(991mm)

76"
(1930mm)
Assembled
Height

Compressor Assembly
Blower & Coil
Assembly

76"
(1930mm)
59-7/16"
(1509mm)
37"
(940mm)

26"
(660mm)

33"
(838mm)

82" (2083mm)
108" (2743mm)
Assembled Length

DPN003143
Rev. 1

Drawing views are simplified with panels removed to show overall dimensions.
See disassembly and handling instructions in installation manual.
Dry Weight, Approximate, Including Panels, lb (kg)
Semi-Hermetic Compressor
Component
Compressor Assembly

Water/Glycol GLYCOOL/Dual-Cool
1270 (578)

1270 (578)

Scroll or Digital Scroll Compressor 1


Water/Glycol

GLYCOOL/Dual-Cool

840 (382)

840 (382)

Filter and Electric Box Assembly

250 (114)

250 (114)

250 (114)

250 (114)

Blower and Coil Assembly

1230 (560)

1410 (641)

1230 (560)

1410 (641)

1. Digital scroll compressors not available on 077 models.


2. Source: DPN003143, Rev. 1

53

Liebert DS

Weights and Dimensions

Figure 35

Disassembly dimensionsDownflow, water/glycol/GLYCOOL 105kW (30 tons),


semi-hermetic or standard scroll compressors
Digital scroll compressors
not available on 105 models

Filter & Electric Box Assembly

39"
(991mm)
41-11/16"
(1059mm)

Compressor Assembly
76" (1930mm)
Assembled
Height

Blower & Coil


Assembly

76"
(1930mm)
59-7/16"
(1510mm)
37"
(940mm)

33"
(838mm)

26"
(660mm)

105" (2667mm)
131" Assembled Length
(3327mm)

DPN003150
Rev. 1

Drawing views are simplified with panels removed to show overall dimensions.
See disassembly and handling instructions in installation manual.

Dry Weight, Approximate, Including Panels, lb (kg)


Semi-Hermetic Compressor

Standard Scroll Compressor 1

Water/Glycol

GLYCOOL/Dual-Cool

Water/Glycol

GLYCOOL/Dual-Cool

Compressor Assembly

1320 (600)

1320 (600)

1200 (545)

1200 (545)

Filter and Electric Box Assembly

270 (123)

270 (123)

270 (123)

270 (123)

Blower and Coil Assembly

1560 (708)

1915 (870)

1560 (708)

1915 (870)

Component

1. Digital scroll compressors not available on 105 models.


2. Source: DPN003150, Rev. 2

Liebert DS

54

Weights and Dimensions

7.5

Upflow Model Dimensions and Primary ConnectionsAir-Cooled Systems with


EC Fans

Figure 36

Cabinet and floor planning dimensionsUpflow, air-cooled, 28-42kW (8-12 tons), scroll or
digital scroll compressors with EC fans
Alternate refrigerant
piping entrance
33"
(838mm)

34-3/4"
(883mm)

5/16"
(8mm)
Bezel

High-Voltage
Connection(s)
3-1/24"
(90mm)

1-3/4"
(44mm)
Handle

TOP VIEW

Space required for EC fan


plenum (shipped separately)
dependent on height of plenum
ordered.

Low-Voltage
Connection(s)

73-1/16" 1856mm)

75"
(1924mm)
36"
(914mm)
Shaded area indicates a
required minimum clearance from floor
to top of unit and plenum for component
access.

1-3/4"
(44mm)

72" (1829mm)

FRONT VIEW
Notes:
1. Front air return unit shown. For rear return unit, in addition to front service
area shown, also include 25" (635mm) on one side of unit for access to rear
return filter box. See DPN001196.
2. EC fan plenum is not shown. EC fans and plenum are shipped separately. DPN003495
Rev. 0
See DPN002747 for unit dimensions with EC fans plenum mounted

55

Liebert DS

Weights and Dimensions

Figure 37

Primary connection locationsUpflow, air-cooled, 28-42kW (8-12 tons), scroll or digital scroll
compressors with EC fans
All dimensions from
rear corner of unit
X
including panels

10-1/8"
(257mm)
4-1/8" (105mm)

NOTES
1. Drawing not to scale.
2. Tolerance on all piping dimensions
is 1/2" (13mm).
3. Field-routed alternatives for refrigerant
gas and liquid line connection points.
4. See submittal page DPN002747
for plenum dimensional data.

3. R1
R2

35"
(889mm)

ECR
ECS
HUM
CPD

4.

L1 L2 G1 G2

4"
(102mm)

Y
11-13/16"
(300mm)

3.

E1

LV2

E2

LV1
LV3

73" (1854mm)
Front of Unit

TOP VIEW OF UNIT


6"
(152mm)

17-3/16"
(437mm)

R3
17-1/16"
(434mm)

3.

L1 L2 G1 G2

CGD*
14-1/4"
(362mm)
15-7/8"
(403mm)

3-7/8"
(98mm)

CGD*

Factory Location

DPN002740
Rev. 0

FRONT SECTION VIEW OF UNIT


(Left Front Panel Not Shown)

LEFT SIDE SECTION VIEW OF UNIT


Description

Point
R1

Refrigerant Access (Top)

R2

Refrigerant Access (Bottom)

X
in. (mm)

Y
in. (mm)

Connection Size / Opening


in. (mm)

60-5/8 (1539)

2-13/16 (71)

10-1/8 x 4-1/8 (257 x 105)

63 (1600)

13-13/16 (351)

16-7/16 x 4 (418 x 102)

L1

Liquid Line System 1

79-3/16 (2011)

16-3/4 (425)

1/2 Cu Sweat

L2

Liquid Line System 2

76-1/2 (1943)

16-3/4 (425)

1/2 Cu Sweat

G1

Hot Gas Discharge 1

73-7/8 (1876)

16-5/8 (422)

5/8 Cu Sweat

G2

Hot Gas Discharge 2

70-1/8 (1780)

16-5/8 (422)

5/8 Cu Sweat

R3

Refrigerant Access (Side)

6 x 17-3/16 (152 x 437)

CGD 1

Condensate Gravity Drain

3/4 FPT

CPD

Condensate Pump Discharge (Optional)

56-1/4 (1429)

11-1/8 (283)

1/2 Cu Sweat

HUM

Humidifier Supply Line

56-1/4 (1429)

9-1/8 (233)

1/4 Cu Sweat

56 (1423)

7-5/16 (186)

1-5/8 Cu Sweat

ECS 2
2

Econ-O-Coil Supply

56 (1423)

4-1/2 (114)

1-5/8 Cu Sweat

E1

Electrical Connection (High-Voltage)

52-3/8 (1331)

29-15/16 (760)

2-1/2

E2

Electrical Connection (High-Voltage)

47-3/8 (1204)

29-15/16 (760)

2-1/2

LV1

Electrical Connection (Low-Voltage)

8-1/8 (207)

29-9/16 (751)

7/8

LV2

Electrical Connection (Low-Voltage)

8-1/8 (207)

31 (787)

7/8

LV3

Electrical Connection (Low-Voltage)

8-1/8 (207)

32-7/16 (824)

7/8

ECR

Econ-O-Coil Return

1. Field pitch condensate drain line a minimum of 1/8" (3.2 mm) per foot (305 mm). All units contain a factory-installed condensate trap.
Do not trap external to the unit. Drain line may contain boiling water. Select appropriate drain system materials. The drain line must
comply with all local codes.
2. Supplied on dual cool systems only.
3. Source: DPN002740, Rev. 0

Liebert DS

56

Weights and Dimensions

Figure 38

Cabinet and floor planning dimensionsUpflow, air-cooled, 28-42kW (8-12 tons),


semi-hermetic compressor models with EC fans
Alternate refrigerant
piping entrance

33"
(838mm)
34-3/4"
(883mm)

5/16"
(8mm)
Bezel

High-Voltage
Connection(s)
3-1/4"
(83mm)

1-9/16" TOP VIEW


(40mm)
Handle

Space required for EC fan


plenum (shipped separately)
dependent on height of plenum
ordered.

Low-Voltage
Connection(s)

86-1/16" (2186mm)

76"
(1930mm)
Shaded area indicates a
required minimum clearance
from floor to top of unit and
plenum for component access.

84-15/16" (2158mm)
2"
(50mm)
FRONT VIEW
Notes:
1. Front air return unit shown. For rear return unit, in addition to front service
area shown, also include 25" (635mm) on one side of unit for access to rear
return filter box. See DPN001196.
2. EC fan plenum is not shown. EC fans and plenum are shipped separately.
See DPN002747 for unit dimensions with EC fans plenum mounted

57

36"
(914mm)

DPN003494
Rev. 0

Liebert DS

Weights and Dimensions

Figure 39

Primary connection locationsUpflow air-cooled, 28-42kW, semi-hermetic compressor


models with EC fans
All dimensions from
rear corner of unit
including panels
X

22-1/2"
(572mm)
R1
15-3/16"
(386mm)

35"
NOTES:
(889mm)
1. Drawing not to scale.
2. Tolerance on all piping dimensions
4"
is 1/2" (13mm).
(102mm)
3. Field-routed alternatives for refrigerant
3.
gas and liquid line connection points.

3.

R2

ECR
ECS
HUM
CPD

4.
L1 L2 G1 G2

16-7/16"
(418mm)

E1

4. See submittal page DPN002747


for plenum dimensional data.

LV1
LV2 LV3

E2

86" (2184mm)
TOP VIEW OF UNIT

6"
(152mm)

R3
20-1/16"
(509mm)

3.

17-3/16"
(437mm)

Front of Unit

G1 G2
L1 L2

CGD*
14-1/4"
(362mm)

3-7/8"
(98mm)

CGD*
Factory Location

FRONT SECTION VIEW OF UNIT

15-7/8"
(403mm)

(Left Front Panel Not Shown)

LEFT SIDE SECTION VIEW OF UNIT

Description

Point
R1
R2

Refrigerant Access (Top)

Refrigerant Access (Bottom)

X
in. (mm)

DPN002739
Rev. 0

Y
in. (mm)

Connection Size / Opening


in. (mm)

60-11/16 (1542)

1-7/8 (48)

22-1/2 x 15-3/16 (572 x 386)

63 (1600)

13-13/16 (351)

16-7/16 x 4 (102 x 418)

L1

Liquid Line System 1

79-3/16 (2011)

16-3/4 (425)

1/2 Cu Sweat

L2

Liquid Line System 2

76-1/2 (1943)

16-3/4 (425)

1/2 Cu Sweat

G1

Hot Gas Discharge 1

73-7/8 (1876)

16-3/4 (425)

5/8 Cu Sweat

G2

Hot Gas Discharge 2

70-1/8 (1780)

16-3/4 (425)

5/8 Cu Sweat

R3

Refrigerant Access (Side)

6 x 17-3/16 (152 x 437)

CGD 1

Condensate Gravity Drain

3/4 FPT

CPD

Condensate Pump Discharge (Opt)

56-1/4 (1429)

11-1/8 (283)

1/2 Cu Sweat

HUM

Humidifier Supply Line

56-1/4 (1429)

9-1/8 (233)

1/4 Cu Sweat

ECS 2

Econ-O-coil Supply

56 (1423)

7-5/16 (186)

1-5/8 Cu Sweat

ECR**

Econ-O-coil Return

56 (1423)

4-1/2 (114)

1-5/8 Cu Sweat

E1

Electrical Connection (High-Voltage)

52-3/8 (1331)

29-15/16 (760)

2-1/2

E2

Electrical Connection (High-Voltage)

47-3/8 (1204)

29-15/16 (760)

2-1/2

LV1

Electrical Connection (Low-Voltage)

8-1/8 (207)

29-9/16 (751)

7/8

LV2

Electrical Connection (Low-Voltage)

8-1/8 (207)

31 (787)

7/8

LV3

Electrical Conn. (Low Volt)

8-1/8 (207)

32-7/16 (824)

7/8

1. Field pitch condensate drain line a minimum of 1/8" (3.2 mm) per foot (305 mm). All units contain a factory-installed condensate trap. Do
not trap external to the unit. Drain line may contain boiling water. Select appropriate drain system materials. The drain line must comply
with all local codes.
2. Supplied on dual cool systems only.
3. Source: DPN002739, Rev. 0

Liebert DS

58

Weights and Dimensions

Figure 40

Cabinet and floor planning dimensionsUpflow, air-cooled, 53-77kW (15-22 tons), scroll or
digital scroll compressor models with EC fans
Digital scroll compressors not
available on 077 models.

Alternate Refrigerant
Piping Entrance
33"
(838mm)

5/16"
(8mm)
Bezel

34-3/4"
(883mm)
High-Voltage
Connection(s)
3-1/4"
(83mm)

1-3/4"
(44mm)
Handle

Space required for EC fan


plenum (shipped separately)
dependent on height of plenum
ordered.

TOP VIEW
Low-Voltage
Connection(s)

98" (2489mm)

76"
(1930mm)

36"
(914mm)
Shaded area indicates a
required minimum clearance
from floor to top of unit and
plenum for component access.

96-15/16" (2462mm)
2"
(50mm)
FRONT VIEW
Notes:
1. Front air return unit shown. For rear return unit, in addition to front service
area shown, also include 25" (635mm) on one side of unit for access to rear
return filter box. See DPN001196.
2. EC fan plenum is not shown. EC fans and plenum are shipped separately.
See DPN002748 for unit dimensions with EC fans plenum mounted

59

DPN003498
Rev. 0

Liebert DS

Weights and Dimensions

Figure 41

Primary connection locationsUpflow, air cooled, 53-77kW (15-22 tons) with EC fans, scroll or
digital scroll compressor models with EC fans

Digital scroll compressors


not available on 105 models.
NOTES
1. Drawing not to scale.
2. Tolerance on all piping
dimensions is 1/2" (13mm).

All dimensions from


rear corner of unit
including panels

12"
(305mm)
4" (102mm)

R2

3. Field-routed alternatives for


refrigerant gas and liquid
line connections.
4. See submittal page DPN002748 for
plenums dimensions.

3.

12-13/16"
(325mm)

ECR
ECS
HUM
CPD

3. R1

L1 L2G1G2
4"
(102mm)

35"
(889mm)

LV1
LV2
LV3

E1
E2

98" (2489mm)
TOP VIEW OF UNIT

Front of Unit

6" (152mm)
R3
17-3/16"
(437mm)

3.
CGD*

17-1/16"
(433mm)

L1 L2G1G2

14-1/4"
(362mm)
15-7/8"
(403mm)

3-7/8"
(98mm)

Factory Location
CGD*

FRONT SECTION VIEW OF UNIT

LEFT SIDE SECTION VIEW OF UNIT

DPN002743
Rev. 0

(Left Front Panel Not Shown)

* Field pitch condensate drain line a minimum of 1/8" (3.2 mm) per foot (305 mm). All units contain a factory-installed
condensate trap. Do not trap external to the unit. Drain line may contain boiling water. Select appropriate drain system
materials. The drain line must comply with all local codes.
** Supplied on dual cool systems only

Description

Point
R1 3
R2 3

Refrigerant Access (Top)


Refrigerant Access (Bottom)

L1
L2
G1
G2
R3 3
CGD 1
CPD
HUM
ECS 1
ECR 1
E1
E2
LV1
LV2
LV3

Liquid Line System 1


Liquid Line System 2
Hot Gas Discharge 1
Hot Gas Discharge 2
Refrigerant Access (Side)
Condensate Gravity Drain
Condensate Pump Discharge (Optional)
Humidifier Supply Line
Econ-O-Coil Supply
Econ-O-Coil Return
Electrical Connection (High-Voltage)
Electrical Connection (High-Voltage)
Electrical Connection (Low-Voltage)
Electrical Connection (Low-Voltage)
Electrical Connection (Low-Voltage)

X
in. (mm)
83-5/8 (2124)
82-3/4 (2102)
94-11/16 (2405)
91-7/8 (2334)
88-3/4 (2254)
85-9/16 (2173)

79-5/16 (2015)
79-5-16 (2015)
78-5/8 (1998)
78-5/8 (1998)
78-1/8 (1984)
74-3/8 (1889)
2-5/8 (66)
2-5/8 (66)
2-5/8 (66)

Y
in. (mm)

Connection Size / Opening


in. (mm)

2 (51)
12 x 4 (305 x 102)
14-3/4 (374)
12-3/16 x 4 (310 x 102)
53kW (15 Tons) / 70 and 77kW (20 and 22 Tons)
16-3/4 (425)
16-3/4 (425)
16-3/8 (416)
16-3/8 (416)

11-7/8 (302)
9-7/8 (251)
7-7/8 (200)
4-5/8 (117)
30 (762)
30 (762)
28-9/16 (726)
30 (762)
31-7/16 (799)

1/2 / 5/8 Cu Sweat


1/2 / 5/8 Cu Sweat
7/8 / 1-1/8 Cu Sweat
7/8 / 1-1/8 Cu Sweat
6 x 17-3/16 (152 x 437)
3/4 FPT
1/2 Cu Sweat
1/4 Cu Sweat
2-1/8 Cu Sweat
2-1/8 Cu Sweat
2-1/2
2-1/2
7/8
7/8
7/8

1. Field pitch condensate drain line a minimum of 1/8" (3.2 mm) per foot (305 mm). All units contain a factory-installed condensate trap. Do
not trap external to the unit. Drain line may contain boiling water. Select appropriate drain system materials. The drain line must comply
with all local codes.
2. Supplied on dual cooling systems only
3. Source: DPN002743, Rev. 0

Liebert DS

60

Weights and Dimensions

Figure 42

Cabinet and floor planning dimensionsUpflow, air-cooled 53-77kW (15-22 tons),


semi-hermetic compressor models with EC fans
Alternate Refrigerant
Piping Entrance
33"
(838mm)

34-3/4"
(883mm)

5/16"
(8mm)
Bezel
High-Voltage
Connection(s)

3-1/4"
(83mm)

1-3/4"
(44mm)
Handle

TOP VIEW
Low-Voltage
Connection(s)

109" (2769mm)

Space required for EC fan


plenum (shipped separately)
dependent on height of plenum
ordered.

76"
(1930mm)

36"
(914mm)
108" (2743mm)
2"
(50mm)

FRONT VIEW

Notes:
1. Front air return unit shown. For rear return unit, in addition to front service
area shown, also include 25" (635mm) on one side of unit for access to rear
return filter box. See DPN001196.
2. EC fan plenum is not shown. EC fans and plenum are shipped separately.
See DPN002748 for unit dimensions with EC fans plenum mounted

61

Shaded area indicates a


required minimum clearance from floor
to top of unit and plenum for component
access.

DPN003497
Rev. 0

Liebert DS

Weights and Dimensions

Figure 43

Primary connection locationsUpflow, air-cooled, 53-77kW, semi-hermetic compressor


models with EC fans
All dimensions from
rear corner of unit
including panels

22-1/2"
(572mm)
NOTES:
1. Drawing not to scale.
15-3/16"
2. Tolerance on all piping dimensions
35"
(386mm)
is 1/2" (13mm).
(889mm)
3. Field-routed alternatives for
4"
refrigerant gas and liquid
(102mm) 3.
line connections.

R1 ECR
3.

R2

ECS
HUM
CPD

4.

L1 L2 G1 G2

16-7/16"
(418mm)

4. See submittal page DPN002748


for plenum dimension.

Y
E1 E2

LV1
LV2
LV3

109" 2760mm)

6"
(152mm)

Front of Unit

TOP VIEW OF UNIT


R3

17-3/16"
(437mm)

3.
CGD*
14-1/4"
(362mm)

3-7/8"
(98mm)

20-1/16"
(509mm)

15-7/8"
(403mm)

LEFT SIDE SECTION VIEW OF UNIT

G1 G2
LV1 LV2

CGD*

FACTORYLOCATION

FRONT SECTION VIEW OF UNIT


(Left Front Panel Not Shown)

Description

Point
R1

Refrigerant Access (Top)

R2

Refrigerant Access (Bottom)

DPN002742
Rev. 0

X
in. (mm)

Y
in. (mm)

Connection Size / Opening


in. (mm)

83-3/4 (2127)

1-7/8 (48)

22-1/2 x 15-3/16 (572 x 386)

86 (2184)

13-7/8 (352)

16-7/16 x 4 (418 x 102)

53kW (15 Tons) / 70 and 77kW (20 and 22 Tons)


L1

Liquid Line System 1

97 (2464)

16-3/4 (425)

1/2 / 5/8 Cu Sweat

L2

Liquid Line System 2

93-5/16 (2370)

16-3/4 (425)

1/2 / 5/8 Cu Sweat

G1

Hot Gas Discharge 1

90-5/8 (2302)

16-5/8 (422)

7/8 / 1-1/8 Cu Sweat

G2

Hot Gas Discharge 2

88 (2235)

16-5/8 (422)

7/8 / 1-1/8 Cu Sweat

R3

Refrigerant Access (Side)

6 x 17-3/16 (152 x 437)

CGD 1

Condensate Gravity Drain

3/4 FPT

CPD

Condensate Pump Discharge (Optional)

79-5/16 (2015)

11-7/8 (302)

1/2 Cu Sweat

HUM

Humidifier Supply Line

79-5/16 (2015)

9-7/8 (251)

1/4 Cu Sweat

Econ-O-Coil Supply

78-5/8 (1998)

7-7/8 (200)

2-1/8 Cu Sweat

ECS

ECR

Econ-O-Coil Return

78-5/8 (1998)

4-5/8 (117)

2-1/8 Cu Sweat

E1

Electrical Connection (High-Voltage)

78-1/8 (1984)

30 (762)

2-1/2

E2

Electrical Connection (High-Voltage)

74-3/8 (1889)

30 (762)

2-1/2

LV1

Electrical Connection (Low-Voltage)

2-5/8 (66)

28-9/16 (726)

7/8

LV2

Electrical Connection (Low-Voltage)

2-5/8 (66)

30 (762)

7/8

LV3

Electrical Connection (Low-Voltage)

2-5/8 (66)

31-7/16 (799)

7/8

1. Field pitch condensate drain line a minimum of 1/8" (3.2 mm) per foot (305 mm). All units contain a factory-installed condensate trap. Do
not trap external to the unit. Drain line may contain boiling water. Select appropriate drain system materials. The drain line must comply
with all local codes.
2. Supplied on dual cool systems only.
3. Source: DPN002742, Rev. 0

Liebert DS

62

Weights and Dimensions

Figure 44

Cabinet and floor planning dimensionsUpflow, air-cooled, 105kW (30 tons), all compressor
models with EC fans
Digital scroll compressors
not available on 105 models.

Alternate Refrigerant
Piping Entrance
33"
(838mm)
34-3/4"
(882mm)
High-Voltage
Connection(s)
3-3/16"
(81mm)
Typical

Space required for EC fan plenum


(shipped separately) dependent on
height of plenum ordered.
1-3/4"
(44mm)
Handle

TOP VIEW
Low-Voltage
Connection(s)

5/16"
(8mm)
Bezel

132-1/16" (3354mm)

76"
(1931mm)

2"
(51mm)
Shaded area indicates a
recommended minimum
clearance from floor to
ceiling for component access.

130-15/16" (3325mm)

FRONT VIEW

Note:
1. Front air return unit shown. For rear return unit, in addition to front
service area shown, also include 25" (635mm) on one side of unit
for access to rear return filter box. See DPN001196.
2. EC fans plenum is not shown. EC fans and plenum are shipped
separately. See DPN002749 for unit dimensions with EC fans
plenum mounted

63

36"
(914mm)

DPN003500
Rev. 0

Liebert DS

Weights and Dimensions

Figure 45

Primary connection locationsUpflow, air-cooled 105kW (30 tons), all compressor models
with EC fans

Digital scroll compressors


not available on 105 models.

All dimensions from


rear corner of unit
including panels

22-1/2"
(572mm)
R1

15-3/16"
(386mm)

NOTES
35"
1. Drawing not to scale.
(889mm)
2. Tolerance on all piping
dimensions is 1/2" (13mm).
4"
(102mm)
3. Field-routed alternatives for
refrigerant gas and liquid
line connections.
4. See submittal page DPN002749 for
plenums dimensions.

3. R2

ECR
ECS
HUM
CPD

4.

L1L2 G1G2

16-7/16"
(418mm)

E1

3.

LV1
LV2

E2

LV3
LV3

132" (3353mm)
Front of Unit

TOP VIEW OF UNIT

6" (152mm)
R3
17-3/16"
(437mm)

3.

3-7/8"
(98mm)

14-1/4"
(362mm)
15-7/8"
(403mm)

CGD*

20-1/16"
(509mm)

G1G2
L1L2

CGD*

Factory Location

FRONT SECTION VIEW OF UNIT


(Left Front Panel Not Shown)

LEFT SIDE SECTION VIEW OF UNIT

Description

Point

DPN002745
Rev. 0

X
in. (mm)

Y
in. (mm)

Connection Size / Opening


in. (mm)

R1

Refrigerant Access (Top)

106-7/8 (2715)

1-7/8 (48)

22-1/2 x 15-3/16 (572mm x 386mm)

R2

Refrigerant Access (Bottom)

109-1/8 (2772)

13-7/8 (352)

16-7/16 x 4 (418mm x 102mm)

L1

Liquid Line System 1

121-3/4 (3092)

16-3/4 (425)

5/8 Cu Sweat

L2

Liquid Line System 2

118-1/8 (3000)

16-3/4 (425)

5/8 Cu Sweat

G1

Hot Gas Discharge 1

118-1/4 (3004)

14-1/4 (362)

1-1/8 Cu Sweat

G2

Hot Gas Discharge 2

115-5/8 (2937)

14-1/4 (362)

1-1/8 Cu Sweat

6 x 17-3/16 (152 x 437mm)

R3

Refrigerant Access (Side)

3
1

CGD
CPD
HUM
ECS

ECR

3/4 FPT

Condensate Pump Discharge (Optional)

Condensate Gravity Drain

102-3/8 (2600)

13-5/8 (346)

1/2 Cu Sweat

Humidifier Supply Line

101-1/8 (2569)

13-1/8 (333)

1/4 Cu Sweat

Econ-O-Coil Supply

101-1/8 (2569)

10-1/4 (260)

2-5/8 Cu Sweat

Econ-O-Coil Return

101-1/8 (2569)

5-1/4 (133)

2-5/8 Cu Sweat

E1

Electrical Connection (High-Voltage)

101-5/8 (2581)

30 (762)

2-1/2

E2

Electrical Connection (High-Voltage)

97-7/8 (2486)

30 (762)

2-1/2

LV1

Electrical Connection (Low-Voltage)

34-1/8 (867)

30-1/4 (769)

7/8

LV2

Electrical Connection (Low-Voltage)

34-1/8 (867)

31-3/4 (807)

7/8

LV3

Electrical Connection (Low-Voltage)

32-5/8 (829)

28-15/16 (734)

7/8

LV4

Electrical Connection (Low-Voltage)

32-5/8 (829)

30-7/16 (772)

7/8

1. Field pitch condensate drain line a minimum of 1/8" (3.2 mm) per foot (305 mm). All units contain a factory-installed condensate trap. Do
not trap external to the unit. Drain line may contain boiling water. Select appropriate drain system materials. The drain line must comply
with all local codes.
2. Supplied on dual cool systems only.
3. Digital scroll compressors not available on 105 models.
4. Source: DPN002745, Rev. 0

Liebert DS

64

Weights and Dimensions

7.6

Upflow Model Dimensions and Primary ConnectionsWater/Glycol/GLYCOOL


Cooled Systems

Figure 46

Cabinet and floor planning dimensionsUpflow, water/glycol/GLYCOOL, 28-42kW (8-12 tons),


all compressor models with EC fans
Condenser Cleanout Access

33"
(838mm)
34-3/4"
(883mm)

Alternate Condenser Fluid


Piping Entrance
High-Voltage
Connection(s)
3-1/4"
(83mm)

5/16"
(8mm)
Bezel

1-3/4"
(44mm)
Handle

Space required for EC fan


plenum (shipped separately)
dependent on height of plenum
ordered.
24"
(610mm)

TOP VIEW

Required for
Condenser Cleanout

Low-Voltage
Connection(s)

86-1/16" (2186mm)

76"
(1930mm)

36"
(914mm)
Shaded area indicates a
required minimum clearance from floor
to top of unit and plenum for component
access.
2"
(50mm)

84-15/16" (2158mm)

FRONT VIEW

Notes:
1. Front air return unit shown. For rear return unit, in addition to front service
area shown, also include 25" (635mm) on one side of unit for access to rear
return filter box. See DPN001196.
2. EC fan plenum is not shown. EC fans and plenum are shipped separately.
See DPN002747 for unit dimensions with EC fans plenum mounted

65

DPN003496
Rev. 0

Liebert DS

Weights and Dimensions

Primary connection locationsUpflow, water/glycol/GLYCOOL, 28-42kW, all compressor


models with EC fans

Figure 47

All dimensions from rear corner


of unit including panels
1. Drawing not to scale.
2. Tolerance on all piping dimensions
is 1/2" (13mm).
3. Field-routed alternatives for
water/glycol connections.
4. See submittal page DPN002747
for plenum dimension.

W1, W2 3.
8"
(203mm)

2-7/8"
35" (73mm)
(889mm)

17-3/16"
(437mm)

Y
3-1/2"
(89mm)

3-7/8"
(98mm)

LV2

E1 E2
86" 2184mm)

3.

6"
(152mm)
W3
WS
WR

ECR
ECS
HUM
CPD

LV1
LV3

Front of Unit

TOP VIEW OF UNIT

CGD*

14-1/4"
(362mm)
15-7/8"
(403mm)

LEFT SIDE SECTION VIEW OF UNIT

CGD*

FRONT SECTION VIEW OF UNIT DPN002741


(Left Front Panel Not Shown)
Rev. 1
Connection Size / Opening
in. (mm)

Description

X
in. (mm)

Y
in. (mm)

28-35kW (8-10 Tons) /


42kW (12 Tons)

Water/Glycol/GLYCOOL Access (Bottom)

79-15/16 (2030)

9 (229)

3-1/2 x 8 (89 x 203)

Point
W1
W2

Water/Glycol/GLYCOOL Access (Top)

79-15/16 (2030)

9 (229)

3-1/2 x 8 (89 x 203)

W3

Water/Glycol/GLYCOOL Access (Side)

6 x 17-3/16 (152 x 437)

WS

Water/Glycol/GLYCOOL Supply

1-5/8 / 2-1/8 Cu Sweat

WR

1-5/8 / 2-1/8 Cu Sweat

ECS 2

Econ-O-Coil Supply

Water/Glycol/GLYCOOL Return

56 (1423)

7-5/16 (186)

1-5/8 / 2-1/8 Cu Sweat

ECR

Econ-O-Coil Return

56 (1423)

4-1/2 (114)

1-5/8 / 2-1/8 Cu Sweat

CGD

Condensate Gravity Drain

3/4 FPT

CPD

Condensate Pump Discharge (Optional)

56-1/4 (1429)

11-1/8 (282)

1/2 Cu Sweat

HUM

Humidifier Supply Line

56-1/4 (1429)

9-1/8 (232)

1/4 Cu Sweat

E1

Electrical Connection (High-Voltage)

52-3/8 (1331)

29-15/16 (760)

2-1/2

E2

Electrical Connection (High-Voltage)

47-3/8 (1204)

29-15/16 (760)

2-1/2

LV1

Electrical Connection (Low-Voltage)

8-1/8 (207)

29-9/16 (751)

7/8

LV2

Electrical Connection (Low-Voltage)

8-1/8 (207)

31 (787)

7/8

LV3

Electrical Connection (Low-Voltage)

8-1/8 (207)

32-7/16 (824)

7/8

1. Field pitch condensate drain line a minimum of 1/8" (3.2 mm) per foot (305 mm). All units contain a factory-installed condensate trap. Do
not trap external to the unit. Drain line may contain boiling water. Select appropriate drain system materials. The drain line must comply
with all local codes.
2. Supplied on dual cool systems only (four-pipe system).
3. Source: DPN002741, Rev. 1

Liebert DS

66

Weights and Dimensions

Figure 48

DimensionsUpflow, water/glycol/GLYCOOL, 53-77kW (15-22 tons), all compressor models


with EC fans
Digital scroll compressors
not available on 077 models.

Condenser Cleanout Access

Space required for EC fan plenum


(shipped separately) dependent on
height of plenum ordered

33"
(838mm)

5/16"
(8mm)
Bezels

35"
(889mm)

Alternate Refrigerant
Piping Entrance
High-Voltage Connection(s)
3-1/4"
(83mm)

1-3/4" TOP
(44mm)
Handle

Required for
condenser cleanout
24"
(610mm)

VIEW
Low-Voltage
Connection(s)

109" (2769mm)

76"
(1930mm)
36"
Shaded area indicates a
(914mm)
recommended minimum
clearance from floor to top
of unit for component access.

2"
(50mm)

108" (2743mm)

FRONT VIEW

NOTES
1. Front air return unit shown. For rear return unit, in addition to front service
area shown, also include 25" (635mm) on one side of unit for access to rear
return filter box. See DPN001196.
2. EC fans plenum is not shown. EC fans and plenum are shipped separately.
See DPN002748 for unit dimensions with EC fans plenum mounted

67

DPN003499
Rev. 0

Liebert DS

Weights and Dimensions

Primary connection locationsUpflow, water/glycol/GLYCOOL, 53-77kW (15-22 tons), all


compressor models with EC fans

Figure 49

Digital scroll compressors


not available on 077 models.

All dimensions from


rear corner of unit
including panels

8"
(203mm)

ECR
ECS
HUM
CPD

W1, W2

NOTES
35"
1. Drawing not to scale.
(889mm)
2. Tolerance on all piping
dimensions
is 1/2" (13mm).
3-1/2"
3. Field-routed alternatives for
(89mm)
water/glycol connections.
4. See submittal page DPN002748
for plenum dimensions.

3.

4.

2-7/8"
(73mm)

Y
E1 E2

LV1
LV2
LV3

109" (2769mm)
Front of Unit

TOP VIEW OF UNIT

6" (152mm)

17-3/16"
(437mm)

3-7/8"
(98mm)

W3
WS
WR
3. CGD*

14-1/4"
(362mm)
15-7/8"
(403mm)

CGD*

FRONT SECTION VIEW OF UNIT


(Left Front Panel Not Shown)

DPN002744
Rev. 0

LEFT SIDE SECTION VIEW OF UNIT

* Field pitch condensate drain line a minimum of 1/8" (3.2 mm) per foot (305 mm). All units contain a factory-installed
condensate trap. Do not trap external to the unit. Drain line may contain boiling water. Select appropriate drain system
materials. The drain line must comply with all local codes. Supplied on dual cool systems only.
** Supplied on dual cool systems only.

Point

Description

X
in. (mm)

Y
in. (mm)

Connection Size / Opening


in. (mm)
3-1/2 x 8 (89 x 203)

W1

Water/Glycol/GLYCOOL Access (Bottom)

102-15/16 (2615)

9 (229)

W2

Water/Glycol/GLYCOOL Access (Top)

102-15/16 (2615)

9 (229)

3-1/2 x 8 (89 x 203)

W3

Water/Glycol/GLYCOOL Access (Side)

6 X 17-3/16 (152 x 437)

WS

Water/Glycol/GLYCOOL Supply

2-1/8 Cu Sweat

WR

Water/Glycol/GLYCOOL Return

2-1/8 Cu Sweat

CGD
CPD
HUM
ECS

ECR

3/4 Fpt

Condensate Pump Discharge (Optional)

Condensate Gravity Drain

79-5/16 (2015)

11-7/8 (302)

1/2 Cu Sweat

Humidifier Supply Line

79-5/16 (2015)

9-7/8 (251)

1/4 Cu Sweat

Econ-O-Coil Supply

78-5/8 (1998)

7-7/8 (200)

2-1/8 Cu Sweat

Econ-O-Coil Return

78-5/8 (1998)

4-5/8 (117)

2-1/8 Cu Sweat

E1

Electrical Connection (High-Voltage)

78-1/8 (1984)

30 (762)

2-1/2

E2

Electrical Connection (High-Voltage)

74-3/8 (1889)

30 (762)

2-1/2

LV1

Electrical Connection (Low-Voltage)

2-5/8 (66)

28-9/16 (726)

7/8

LV2

Electrical Connection (Low-Voltage)

2-5/8 (66)

30 (762)

7/8

LV3

Electrical Connection (Low-Voltage)

2-5/8 (66)

31-7/16 (799)

7/8

1. Field pitch condensate drain line a minimum of 1/8" (3.2 mm) per foot (305 mm). All units contain a factory-installed condensate trap. Do
not trap external to the unit. Drain line may contain boiling water. Select appropriate drain system materials. The drain line must comply
with all local codes.
2. Supplied on dual cool systems only.
3. Digital scroll compressors not available on 077 models.
4. Source: DPN002744, Rev. 0

Liebert DS

68

Weights and Dimensions

Figure 50

Cabinet and floor planning dimensionsUpflow, water/glycol/GLYCOOL,105kW (30 tons), all


compressor models, with EC fans
Digital scroll compressors
not available on 105 models.

Alternate Refrigeration
Piping Entrance

33"
(838mm)
34-3/4"
(883mm)
Alternate Condenser
Fluid Piping Entrance
High-Voltage
Connection(s)
3-3/16"
(81mm)
Typical

5/16"
(8mm)
Bezel
Low-Voltage
Connection(s)

1-3/4" TOP VIEW


(44mm)
Handle

Space required for EC Fan Plenum


(shipped separately) dependent on
height of plenum ordered
24"
(610mm)

Required for
condenser cleanout

132-1/16" (3354mm)

76"
(1931mm)

34"
(864mm)

1-15/16"
(50mm)

130-15/16" (3325mm)

FRONT VIEW
NOTES
1. Front air return unit shown. For rear return unit, in addition to front
service area shown, also include 25" (635mm) on one side of unit
for access to rear return filter box. See DPN001196.
2. EC fans plenum not shown. EC fans and plenum shipped separately.
See DPN002749 for plenum dimensions.

69

Shaded area indicates a


recommended minimum
clearance from floor to top
of unit and plenum for component
access.

DPN003501
Rev. 0

Liebert DS

Weights and Dimensions

Primary connection locationsUpflow, water/glycol/GLYCOOL, 105kW (30 tons), all


compressor models with EC fans

Figure 51

Digital scroll compressors


not available on 105 models.

All dimensions from


rear corner of unit
including panels

8"
(203mm)

W1, W2 3.

35"
(889mm)
NOTES
1. Drawing not to scale.
2. Tolerance on all piping
3-1/2"
dimensions is 1/2" (13mm).

ECR
ECS
HUM
CPD

4.
2-7/8"
(73mm)

E1
E2

(89mm)

LV2

3. Field-routed alternatives for


water/glycol connections.
4. See submittal page DPN002746 for
plenums dimensions.

LV1 LV3

Y
LV4

132" (3353mm)
Front of Unit
TOP VIEW OF UNIT

6" (152mm)

W3
WS
WR
3.
CGD*

17-3/16"
(437mm)

14-1/4"
(362mm)
15-7/8"
(403mm)

3-7/8"
(98mm)

CGD*

FRONT SECTION VIEW OF UNIT


(Left Front Panel Not Shown)

DPN002746
Rev. 0

LEFT SIDE SECTION VIEW OF UNIT

Description

Point
W1

X
In. (mm)

Y
In. (mm)

Connection Size / Opening


In. (mm)

Water/Glycol/GLYCOOL Access (Bottom)

126-1/8 (3204)

9 (229)

3-1/2 x 8 (89 x 203)

W2

Water/Glycol/GLYCOOL Access (Top)

126-1/8 (3204)

9 (229)

3-1/2 x 8 (89 x 203)

W3

Water/Glycol/GLYCOOL Access (Side)

6 x 17-3/16 (152 x 437)

WS

Water/Glycol/GLYCOOL Supply

2-1/8 Cu Sweat

WR

Water/Glycol/GLYCOOL Return

2-1/8 Cu Sweat

CGD 1

Condensate Gravity Drain

3/4 FPT

CPD

Condensate Pump Discharge (Opt)

102-3/8 (2600)

13-5/8 (346)

1/2 Cu Sweat

HUM

Humidifier Supply Line

101-1/8 (2569)

13-1/8 (333)

1/4 Cu Sweat

Econ-O-Coil Supply

101-1/8 (2569)

10-1/4 (260)

2-5/8 Cu Sweat

ECR 2

Econ-O-Coil Return

101-1/8 (2569)

5-1/4 (133)

2-5/8 Cu Sweat

E1

Electrical Connection (High-Voltage)

101-5/8 (2581)

30 (762)

2-1/2

E2

Electrical Connection (High-Voltage)

97-7/8 (2486)

30 (762)

2-1/2

LV1

Electrical Connection (Low-Voltage)

34-1/8 (867)

30-1/4 (769)

7/8

LV2

Electrical Connection (Low-Voltage)

34-1/8 (867)

31-3/4 (807)

7/8

LV3

Electrical Connection (Low-Voltage)

32-5/8 (829)

28-15/16 (734)

7/8

LV4

Electrical Connection (Low-Voltage)

32-5/8 (829)

30-7/16 (772)

7/8

ECS

1. Field pitch condensate drain line a minimum of 1/8" (3.2 mm) per foot (305 mm). All units contain a factory-installed condensate trap. Do
not trap external to the unit. Drain line may contain boiling water. Select appropriate drain system materials. The drain line must comply
with all local codes.
2. Supplied on dual cool systems only.
3. Source: DPN002746, Rev. 0

Liebert DS

70

Weights and Dimensions

7.7

Upflow Model Dimensions and Primary ConnectionsAir-Cooled Systems with


Forward-Curved Blowers

Figure 52

DimensionsUpflow, air-cooled, 28-42kW (8-12 tons), scroll or digital scroll compressor


models with forward-curved blowers
Alternate Refrigerant
Piping Entrance

33"
(838mm)

5/16"
(8mm)
Bezel

35"
(889mm)

Minimum required
for blower replacement

High-Voltage
Connection(s)
1-1/2"
(38mm)

1-3/4"
(44mm) TOP
Handle VIEW

Low-Voltage
Connection(s)

73" (1854mm)

24"
(610mm)

76"
(1930mm)

34"
(864mm)
Shaded area indicates a
required minimum clearance from floor
to top of unit and plenum for component
access.

2"
(51mm)

72" (1829mm)

FRONT VIEW
Front air return unit shown. For rear return unit, in addition to front service
area shown, also include 25" (635mm) on one side of unit for access to rear
return filter box. See DPN001196.

71

DPN003154
Rev. 1

Liebert DS

Weights and Dimensions

Figure 53

Primary connection locationsUpflow air-cooled 28-42kW (8-12 tons) scroll compressor


models with foward-curved blowers
All dimensions from rear corner
of unit including panels
X

10-1/8"
(257mm)

1. Drawing not to scale.


4-1/8" (105mm)
2. Tolerance on all piping dimensions
is 1/2" (13mm).
3. Field-routed alternatives for refrigerant
gas and liquid line connection points.
4" (102mm)
4. Unit with forward-curved blower shown.
See submittal page DPN001120 for
35"
blower outlet and deck dimensions. (889mm)
3.

3.

R1

ECR
ECS
HUM
CPD

BLOWER
OUTLET

R2
L1 L2 G1 G2

4.
Y

11-1/8"
(283mm)

LV1
LV2
LV3

E1 E2
73" (1854mm)
R3

17-3/16"
(437mm)

3.

CGD*
3-7/8"
(98mm)

Front

TOP VIEW

6"
(152mm)

17-1/16"
(434mm)

14-1/4"
(362mm)
15-7/8"
(403mm)

L1 L2 G1 G2

CGD*

FRONT SECTION

LEFT SIDE SECTION

Point

Description

R1

Refrigerant Access (Top)

R2

Refrigerant Access (Bottom)

Factory Location
(Left Front Panel Not Shown)

DPN001119
Rev. 3

X
in. (mm)

Y
in. (mm)

Connection Size / Opening


in. (mm)

60-5/8 (1539)

2-13/16 (71)

10-1/8 x 4-1/8 (257 105)

63 (1600)

13-13/16 (351)

16-7/16 x 4 (418 x 102)

L1

Liquid Line System 1

79-3/16 (2011)

16-3/4 (425)

1/2" Cu Sweat

L2

Liquid Line System 2

76-1/2 (1943)

16-3/4 (425)

1/2" Cu Sweat

G1

Hot Gas Discharge 1

73-7/8 (1876)

16-5/8 (422)

5/8" Cu Sweat

G2

Hot Gas Discharge 2

70-1/8 (1780)

16-5/8 (422)

5/8" Cu Sweat

R3

Refrigerant Access (Side)

6 x 17-3/16 (152 x 437)

CGD*

Condensate Gravity Drain

3/4" FPT

CPD

Condensate Pump Discharge (Optional)

56-1/4 (1429)

11-1/8 (283)

1/2" Cu Sweat

HUM

Humidifier Supply Line

56-1/4 (1429)

9-1/8 (233)

1/4" Cu Sweat

ECS *

Econ-O-Coil Supply

56 (1423)

7-5/16 (186)

1-5/8" Cu Sweat

ECR 2*

Econ-O-Coil Return

56 (1423)

4-1/2 (114)

1-5/8" Cu Sweat

E1

Electrical Connection (High-Voltage)

52-3/8 (1330)

30 (762)

2-1/2"

E2

Electrical Connection (High-Voltage)

46-7/8 (1191)

30 (762)

2-1/2"

LV1

Electrical Connection (Low-Voltage)

19-1/2 (495)

29-1/16 (738)

7/8"

LV2

Electrical Connection (Low-Voltage)

19-1/2 (495)

30-1/2 (775)

7/8"

LV3

Electrical Connection (Low-Voltage)

19-1/2 (495)

31-15/16 (811)

7/8"

1. Field pitch condensate drain line a minimum of 1/8" (3.2 mm) per foot (305 mm). All units contain a factory-installed condensate trap. Do
not trap external to the unit. Drain line may contain boiling water. Select appropriate drain system materials. The drain line must comply
with all local codes.
2. Supplied on dual cool systems only.
3. Source: DPN001119, Rev. 3

Liebert DS

72

Weights and Dimensions

Figure 54

Cabinet and floor planning dimensionsUpflow, air-cooled 28-42kW (8-12 tons) semi-hermetic
compressor models with forward-curved blowers
Alternate Refrigerant
Piping Entrance

33"
(838mm)
5/16"
(8mm)
Bezel

35"
(889mm)

High-Voltage
Connection(s)
1-1/2"
(38mm)

TOP
VIEW

1-3/4"
(44mm)
Handle

Minimum required
for blower replacement

Low-Voltage
Connection(s)
24"
(610mm)

86" (2184mm)

76"
(1930mm)
34"
(864mm)
Shaded area indicates a
required minimum clearance from floor
to top of unit and plenum for component
access.

85" (2159mm)
2"
(51mm)

FRONT VIEW
Front air return unit shown. For rear return unit, in addition to front service
area shown, also include 25" (635mm) on one side of unit for access to rear
return filter box. See DPN001196.

73

DPN003153
Rev. 1

Liebert DS

Weights and Dimensions

Figure 55

Primary connection locationsUpflow, air-cooled, 28-42kW (8-12 tons), semi-hermetic


compressor models with forward-curved blowers
All dimensions from
rear corner of unit
including panels X

22-1/2"
(572mm)

NOTES:
1. Drawing not to scale.
2. Tolerance on all piping dimensions
is 1/2" (13mm).
15-3/16"
3 Field-routed alternatives for refrigerant
35" (386mm)
gas and liquid line connection points.
(889mm)
4 Forwad-curved blower shown. See
4"
submittal page DPN001120 for
(102mm)
blower outlet and deck dimensions.

R2

ECR
ECS
HUM
CPD

Blower
Outlet
4

L1 L2 G1 G2

16-7/16"
(418mm)

E1

LV1
LV2
LV3

E2

86" (2184mm)
TOP VIEW
6"
(152mm)
17-3/16"
(437mm)

R3
G1 G2

CGD *

3-7/8"
(98mm)

Point

Front of Unit

14-1/4"
(362mm)
15-7/8"
(403mm)
LEFT SIDE SECTION VIEW

Description

R1

Refrigerant Access (Top)

R2

Refrigerant Access (Bottom)

20-1/16"
(509mm)

L1 L2

CGD *

Factory Location
FRONT SECTION VIEW
(Left Front Panel Not Shown)

X
in. (mm)

DPN001114
Rev. 3

Y
in. (mm)

Connection Size / Opening


in. (mm)

60-11/16 (1542)

1-7/8 (48)

22-1/2 x 15-3/16 (572 x 386)

63 (1600)

13-13/16 (351)

16-7/16 x 4 (418 x 102)

L1

Liquid Line System 1

79-3/16 (2011)

16-3/4 (425)

1/2" Cu Sweat

L2

Liquid Line System 2

76-1/2 (1943)

16-3/4 (425)

1/2" Cu Sweat

G1

Hot Gas Discharge 1

73-7/8 (1876)

16-3/4 (425)

5/8" Cu Sweat

Hot Gas Discharge 2

70-1/8 (1780)

16-3/4 (425)

5/8" Cu Sweat

6 x 17-3/16 (152 x 437)

G2
R3

Refrigerant Access (Side)

CGD 1

Condensate Gravity Drain

3/4" FPT

CPD

Condensate Pump Discharge (Opt)

56-1/4 (1429)

11-1/8 (283)

1/2" Cu Sweat

Humidifier Supply Line

56-1/4 (1429)

9-1/8 (233)

1/4" Cu Sweat

HUM
2

Econ-O-Coil Supply

56 (1423)

7-5/16 (186)

1-5/8" Cu Sweat

ECR 2

Econ-O-Coil Return

56 (1423)

4-1/2 (114)

1-5/8" Cu Sweat

E1

Electrical Conn. (High-Voltage)

52-3/8 (1330)

30 (762mm)

2-1/2"

E2

Electrical Conn. (High-Voltage)

46-7/8 (1191)

30 (762mm)

2-1/2"

LV1

Electrical Conn. (Low-Voltage)

19-1/2 (495)

29-1/16 (738)

7/8"

LV2

Electrical Conn. (Low-Voltage)

19-1/2 (495)

30-1/2 (775)

7/8"

LV3

Electrical Conn. (Low-Voltage)

19-1/2 (495)

31-15/16 (811)

7/8"

ECS

1. Field-pitch condensate drain line a minimum of 1/8" (3.2 mm) per foot (305 mm). All units contain a factory-installed condensate trap. Do
not trap external to the unit. Drain line may contain boiling water. Select appropriate drain system materials. The drain line must comply
with all local codes.
2. Supplied on dual-cool systems only (four-pipe system).
3. Piping dimensions shown are connection sizes; field piping sizes may be different, depending on distance. Refer to user manual,
SL-18826.
4. Source: DPN001114, Rev. 3

Liebert DS

74

Weights and Dimensions

Figure 56

Cabinet and floor planning dimensionsUpflow, air-cooled, 53-77kW (15-22 tons), scroll or
digital scroll compressors with forward-curved blowers
Alternate Refrigerant
Piping Entrance

Digital scroll compressors


not available on 077 models.

33"
(838mm)
35"
(889mm)

High-Voltage
Connection(s)

5/16"
(8mm)
Bezel
1-3/4"
(44mm)
Handle

Low-Voltage
Connection(s)

TOP VIEW

1-1/2"
(38mm)

Minimum required
for blower replacement

98" (2489mm)
24"
(610mm)

76"
(1930mm)
34"
(864mm)

2"
(51mm)

Shaded area indicates a


required minimum clearance from floor
to top of unit and plenum for component
access.

97" (2464mm)

FRONT VIEW

Front air return unit shown. For rear return unit, in addition to front service
area shown, also include 25" (635mm) on one side of unit for access to rear
return filter box. See DPN001196.

75

DPN003157
Rev. 1

Liebert DS

Weights and Dimensions

Figure 57

Primary connection locationsUpflow, air-cooled, 53-77kW (15-22 tons), scroll compressor


models with forward-curved blowers
Digital scroll compressors not
available on VS 077 models.

NOTES:
12" (305mm)
1. Drawing not to scale.
2. Tolerance on all piping dimensions
is 1/2" (13mm).
4"
3. Field-routed alternatives for refrigerant
(102mm)
gas and liquid line connection points.
4"
35"
4. Forward-curved blowers shown. See
(102mm)
(889mm)
submittal page DPN001191 for
blower outlet and deck dimensions.

All dimensions from


rear corner of unit
including panels
Blower
Outlet

Blower
Outlet

12-13/16"
(325mm)

6" (152mm)

98" (2489mm)
Front of Unit

TOP VIEW OF UNIT


17-3/16"
(437mm)
CGD *
14-1/4"
(362mm)

3-7/8"
(98mm)

17-1/16"
(433mm)

15-7/8"
(403mm)

LEFT SIDE SECTION VIEW OF UNIT

CGD *

Factory
Location

DPN001213
Rev. 2

FRONT SECTION VIEW OF UNIT


(Left Front Panel Not Shown)

X
in. (mm)

Y
in. (mm)

Connection Size / Opening


in. (mm)

Refrigerant Access (Top)

83-5/8 (2124)

2 (51)

12 x 4 (305 x 102)

Refrigerant Access (Bottom)

82-3/4 (2102)

14-3/4 (374)

12-3/16 x 4 (310 x 102)

Point

Description

R1

R2

53kW (15 tons) / 70 & 77kW (20 & 22 tons)


L1

Liquid Line System 1

94-11/16 (2405)

16-3/4 (425)

1/2 / 5/8 Cu Sweat

L2

Liquid Line System 2

91-7/8 (2334)

16-3/4 (425)

1/2 / 5/8 Cu Sweat

G1

Hot Gas Discharge 1

88-3/4 (2254)

16-3/8 (416)

7/8 / 1-1/8 Cu Sweat

G2

Hot Gas Discharge 2

85-9/16 (2173)

16-3/8 (416)

7/8 / 1-1/8 Cu Sweat

R3

Refrigerant Access (Side)

6 x 17-3/16 (152 x 437)

CGD 1

Condensate Gravity Drain

3/4 FPT

CPD

Condensate Pump Discharge (Opt)

79-5/16 (2015)

11-7/8 (302)

1/2 Cu Sweat

HUM

Humidifier Supply Line

79-5-16 (2015)

9-7/8 (251)

1/4 Cu Sweat

Econ-O-Coil Supply

78-5/8 (1998)

7-7/8 (200)

2-1/8 Cu Sweat

ECR 2

Econ-O-Coil Return

78-5/8 (1998)

4-5/8 (117)

2-1/8 Cu Sweat

E1

Electrical Connection (High-Voltage)

75-3/8 (1915)

30 (762)

2-1/2

E2

Electrical Connection (High-Voltage)

69-7/8 (1775)

30 (762)

2-1/2

LV1

Electrical Connection (Low-Voltage)

19-1/2 (495)

29-1/16 (738)

7/8

LV2

Electrical Connection (Low-Voltage)

19-1/2 (495)

30-1/2 (775)

7/8

LV3

Electrical Connection (Low-Voltage)

19-1/2 (495)

31-15/16 (811)

7/8

ECS

1. Field-pitch condensate drain line a minimum of 1/8" (3.2 mm) per foot (305 mm). All units contain a factory-installed condensate trap. Do
not trap external to the unit. Drain line may contain boiling water. Select appropriate drain system materials. The drain line must comply
with all local codes.
2. Supplied on dual-cool systems only.
3. Digital scroll compressors not available on 077 models.
4. Piping dimensions shown are connection sizes; field piping sizes may be different depending, on distance. Refer to user manual,
SL-18826.
5. Source: DPN001213, Rev. 2

Liebert DS

76

Weights and Dimensions

Figure 58

Cabinet and floor plannning dimensionsUpflow air-cooled 53-77kw (15-22 tons)


semi-hermetic compressor models with forward curved blowers
Alternate Refrigerant
Piping Entrance

33"
(838mm)

5/16"
(8mm)
Bezel

35"
(889mm)
High-Voltage
Connection(s)
1-1/2"
(38mm)

1-3/4"
(44mm)
Handle

TOP
VIEW

Low-Voltage
Connection(s)

Minimum required
for blower replacement

109" (2769mm)

24"
(610mm)

76"
(1930mm)

34"
(864mm)

2"
(51mm)

Shaded area indicates a


required minimum clearance from floor
to top of unit and plenum for component
access.

108" (2743mm)

FRONT VIEW

Front air return unit shown. For rear return unit, in addition to front service
area shown, also include 25" (635mm) on one side of unit for access to rear
return filter box. See DPN001196.

77

DPN003156
Rev. 1

Liebert DS

Weights and Dimensions

Figure 59

Primary connection locationsUpflow, air-cooled 53-77kW (15-22 tons), semi-hermetic


compressor models with forward-curved blowers
All dimensions from
rear corner of unit
including panels

22-1/2"
(572mm)

NOTES:
1. Drawing not to scale.
2. Tolerance on all piping dimensions
is 1/2" (13mm).
15-3/16"
(386mm)
3. Field-routed alternatives for refrigerant 35"
gas and liquid line connection points. (889mm)
4"
4. Forward-curved fans shown. See
(102mm)
submittal page DPN001191 for
blower outlet and deck dimensions.

Blower
Outlet

Blower
Outlet

16-7/16"
(418mm)

6"
(152mm)

109" (2769mm)

TOP VIEW OF UNIT

Front of Unit

17-3/16"
(437mm)

3-7/8"
(98mm)

14-1/4"
(362mm)

20-1/16"
(509mm)

15-7/8"
(403mm)

CGD *

LEFT SIDE SECTION VIEW OF UNIT

Point

Description

R1

Refrigerant Access (Top)

R2

Refrigerant Access (Bottom)

Factory Location

FRONT SECTION VIEW OF UNIT


(Left Front Panel Not Shown)

DPN001212
Rev. 3

X
in. (mm)

Y
in. (mm)

Connection Size / Opening


in. (mm)

83-3/4 (2127)

1-7/8 (48)

22-1/2 x 15-3/16 (572 x 386)

86 (2184)

13-7/8 (352)

16-7/16 x4 (418 x102)

53kW (15 tons) / 70 & 77kW (20 & 22 tons)


L1

Liquid Line System 1

97 (2464)

16-3/4 (425)

1/2" / 5/8 Cu Sweat

L2

Liquid Line System 2

93-5/16 (2370)

16-3/4 (425)

1/2" / 5/8" Cu Sweat

G1

Hot Gas Discharge 1

90-5/8 (2302)

16-5/8 (422)

7/8" / 1-1/8" Cu Sweat

G2

Hot Gas Discharge 2

88 (2235)

16-5/8 (422)

7/8" / 1-1/8" Cu Sweat

R3

Refrigerant Access (Side)

6 x 17-3/16 (152 x 437)

CGD 1

Condensate Gravity Drain

3/4" FPT

CPD

Condensate Pump Discharge (Opt)

79-5/16 (2015)

11-7/8 (302)

1/2" Cu Sweat

HUM

Humidifier Supply Line

79-5/16 (2015)

9-7/8 (251)

1/4" Cu Sweat

ECS 2

Econ-O-Coil Supply

78-5/8 (1998)

7-7/8 (200)

2-1/8" Cu Sweat

ECR 2

Econ-O-Coil Return

78-5/8 (1998)

4-5/8 (117)

2-1/8" Cu Sweat

E1

Electrical Connection (High-Voltage)

75-3/8 (1915)

30 (762)

2-1/2"

E2

Electrical Connection (High-Voltage)

69-7/8 (1775)

30 (762)

2-1/2"

LV1

Electrical Connection (Low-Voltage)

19-1/2 (495)

29-1/16 (738)

7/8"

LV2

Electrical Connection (Low-Voltage)

19-1/2 (495)

30-1/2 (775)

7/8"

LV3

Electrical Conn. (Low-Voltage)

19-1/2 (495)

31-15/16 (811)

7/8"

1. Field-pitch condensate drain line a minimum of 1/8" (3.2 mm) per foot (305 mm). All units contain a factory-installed condensate trap. Do
not trap external to the unit. Drain line may contain boiling water. Select appropriate drain system materials. The drain line must comply
with all local codes.
2. Supplied on dual-cool systems only.
3. Piping dimensions shown are connection sizes; field piping sizes may be different, depending on distance. Refer to user manual,
SL-18826.
4. Source: DPN001212, Rev. 3

Liebert DS

78

Weights and Dimensions

Figure 60

Cabinet and floor planning dimensionsUpflow, air-cooled, 105kW (30 tons), all compressor
models with forward-curved blowers
Digital scroll compressors
not available on 105 models.

Alternate Refrigerant
Piping Entrance
33"
(838mm)
35"
(889mm)

High-Voltage
Connection(s)
1-1/2"
(38mm)

5/16"
(8mm)
Bezel

1-3/4"
(44mm)
TOP VIEW Handle

Low-Voltage
Connection(s)

Minimum required
for blower replacement

132" (3353mm)

24"
(610mm)

76"
(1930mm)

34"
(864mm)
2"
(51mm)

131" (3327mm)

FRONT VIEW

Front air return unit shown. For rear return unit, in addition to front service
area shown, also include 25" (635mm) on one side of unit for access to rear
return filter box. See DPN001196.

79

Shaded area indicates a


required minimum clearance from floor
to top of unit and plenum for component
access.
DPN003159
Rev. 1

Liebert DS

Weights and Dimensions

Figure 61

Primary connection locationsUpflow, air-cooled, 105kW (30 tons), semi-hermetic and scroll
compressor models with forward-curved blowers

Digital scroll compressors not


available on 105 models.

All dimensions from


rear corner of unit
including panels

22-1/2"
(572mm)
15-3/16"
(386mm)

R2

35"
(889mm)

ECR
ECS
HUM
CPD

Blower
Outlet

Blower
Outlet

16-7/16"
(418mm)

NOTES:
4"
1. Drawing not to scale.
(102mm)
2. Tolerance on all piping dimensions
is 1/2" (13mm).
3. Field-routed alternatives for refrigerant
gas and liquid line connection points.
4. Forward-curved fans shown. See submittal
page DPN001192 for blower outlet and
deck dimensions.
5. EC fans are field-installed in plenum.

Blower
Outlet

LV1 LV3
LV2

E1 E2

Y
LV4

132" (3353mm)

TOP VIEW

Front Of Unit

6"
(152mm)
R3
20-1/16"
(509mm)

17-3/16"
(437mm)

G2
L1 L2G1

CGD*

3-7/8"
(98mm)

14-1/4"
(362mm)
15-7/8"
(403mm)

CGD*
Factory Location

FRONT SECTION VIEW


(Left Front Panel Not Shown)

LEFT SIDE SECTION VIEW

DPN001257
Rev. 1

X, in. (mm)

Y, in. (mm)

Connection Size / Opening

Refrigerant Access (Top)

106-7/8 (2715)

1-7/8 (48)

22-1/2 x 15-3/16 (572 x 386)

Point

Description

R1

R2

Refrigerant Access (Bottom)

109-1/8 (2772)

13-7/8 (352)

16-7/16 x 4 (418 x 102)

L1

Liquid Line System 1

121-3/4 (3092)

16-3/4 (425)

5/8" Cu Sweat

L2

Liquid Line System 2

118-1/8 (3000)

16-3/4 (425)

5/8" Cu Sweat

G1

Hot Gas Discharge 1

118-1/4 (3004)

14-1/4 (362)

1-1/8" Cu Sweat

G2

Hot Gas Discharge 2

115-5/8 (2937)

14-1/4 (362)

1-1/8" Cu Sweat

R3

Refrigerant Access (Side)

6 x 17-3/16 (152 x 437)

CGD*

Condensate Gravity Drain

3/4" FPT

CPD

Condensate Pump Discharge (Opt)

102-3/8 (2600)

13-5/8 (346)

1/2" Cu Sweat

HUM

Humidifier Supply Line

101-1/8 (2569)

13-1/8 (333)

1/4" Cu Sweat

Econ-O-Coil Supply

101-1/8 (2569)

10-1/4 (260)

2-5/8" Cu Sweat

ECR 2

Econ-O-Coil Return

101-1/8 (2569)

5-1/4 (133)

2-5/8" Cu Sweat

E1

Electrical Connection (High-Voltage)

98-1/2 (2502)

30 (762)

2-1/2"

E2

Electrical Connection (High-Voltage)

93 (2362)

30 (762)

2-1/2"

LV1

Electrical Connection (Low-Voltage)

41-1/8 (1045)

30-3/8 (772)

7/8"

LV2

Electrical Connection (Low-Voltage)

38-7/8 (987)

30-3/8 (772)

7/8"

LV3

Electrical Connection (Low-Voltage)

35-1/8 (892)

30-3/8 (772)

7/8"

LV4

Electrical Connection (Low-Voltage)

31-5/8 (803)

30-3/8 (772)

7/8"

ECS

1. Field-pitch condensate drain line a minimum of 1/8" (3.2 mm) per foot (305 mm). All units contain a factory-installed condensate trap. Do
not trap external to the unit. Drain line may contain boiling water. Select appropriate drain system materials. The drain line must comply
with all local codes.
2. Supplied on dual-cool systems only.
3. Digital scroll compressors not available on 105 models.
4. Piping dimensions shown are connection sizes; field piping sizes may be different, depending on distance. Refer to user manual,
SL-18826.
5. Source: DPN001257, Rev. 1

Liebert DS

80

Weights and Dimensions

7.8

Upflow Model Dimensions and Primary ConnectionsWater/Glycol/GLYCOOL


Systems

Figure 62

Cabinet and floor planning dimensionsUpflow, water/glycol/GLYCOOL, 28-42kW (8-12 tons),


all compressor models with forward-curved blowers
Condenser Cleanout Access

33"
(838mm)

5/16"
(8mm)
Bezel Required for
condenser cleanout
Minimum required
for blower replacement

35"
(889mm)

Alternate Condenser Fluid


Piping Entra
High-Voltage
Connection(s)
1-1/2"
(38mm)

1-3/4"
(44mm)
Handle

Low-Voltage
Connection(s)

TOP VIEW

24"
(610mm)

86" (2184mm)

76"
(1930mm)
34"
(864mm)
Shaded area indicates a
required minimum clearance from floor
to top of unit and plenum for component
access.

2"
(51mm)

85" (2159mm)

FRONT VIEW
Front air return unit shown. For rear return unit, in addition to front service
area shown, also include 25" (635mm) on one side of unit for access to rear
return filter box. See DPN001196.

81

DPN003155
Rev. 1

Liebert DS

Weights and Dimensions

Primary connection locationsUpflow water/glycol/GLYCOOL 28-42kW (8-12 tons) all


compressor models with forward-curved blowers

Figure 63

1. Drawing not to scale.


2. Tolerance on all piping dimensions is 1/2" (13mm).

All dimensions from rear corner


of unit including panels

3. Field routed alternatives for water/glycol connections.

4. Unit with forward-curved fan


shown.See submittal page
DPN001120 for blower
outlet and deck dimensions.

W1, W2 3

8"
(203mm)

Blower
Outlet

ECS
ECR
HUM
CPD

35"
(889mm)

2-7/8"
(73mm)

3-1/2"
(89mm)

E2

86" (2184mm)

6"
(152mm)

Front

TOP VIEW OF UNIT

W3
WS
WR

17-3/16"
(437mm)

3-7/8"
(98mm)

E1

LV1
LV2
LV3

CGD*

14-1/4"
(362mm)
15-7/8"
(403mm)

LEFT SIDE SECTION VIEW OF UNIT

CGD*

FRONT SECTION VIEW OF UNIT

DPN001179
Rev. 6

(Left Front Panel Not Shown)

Connection Size / Opening


in. (mm)
Description

X
in. (mm)

Y
in. (mm)

28-35kW (8-10 Ton) /


42kW (12 Ton)

Water/Glycol/GLYCOOL Access (Bottom)


Water/Glycol/GLYCOOL Access (Top)
Water/Glycol/GLYCOOL Access (Side)
Water/Glycol/GLYCOOL Supply
Water/Glycol/GLYCOOL Return

79-15/16 (2030)
79-15/16 (2030)

9 (229)
9 (229)

3-1/2 x 8 (89 x 203)


3-1/2 x 8 (89 x 203)
6 x 17-3/16 (152 x 437)
1-5/8" / 2-18" Cu Sweat
1-5/8" / 2-18" Cu Sweat

56 (1423)
56 (1423)

56-1/4 (1429)
56-1/4 (1429)
52-3/8 (1330)
46-7/8 (1191)
19-1/2 (495)
19-1/2 (495)
19-1/2 (495)

7-5/16 (186)
4-1/2 (114)

11-1/8 (282)
9-1/8 (232)
30 (762)
30 (762)
29-1/16 (738)
30-1/2 (775)
31-15/16 (811)

1-5/8" / 2-18" Cu Sweat


1-5/8" / 2-18" Cu Sweat
3/4" FPT
1/2" Cu Sweat
1/4" Cu Sweat
2-1/2"
2-1/2"
7/8"
7/8"
7/8"

Point
W1 3
W2 3
W3 3
WS 3
WR 3
ECS 2
2

ECR
CGD 1
CPD
HUM
E1
E2
LV1
LV2
LV3

Econ-O-Coil Supply
Econ-O-Coil Return
Condensate Gravity Drain
Condensate Pump Discharge (Opt)
Humidifier Supply Line
Electrical Connection (High-Voltage)
Electrical Connection (High-Voltage)
Electrical Connection (Low-Voltage)
Electrical Connection (Low-Voltage)
Electrical Connection (Low-Voltage)

1. Field-pitch condensate drain line a minimum of 1/8" (3.2 mm) per foot (305 mm). All units contain a factory-installed condensate trap. Do
not trap external to the unit. Drain line may contain boiling water. Select appropriate drain system materials. The drain line must comply
with all local codes.
2. Supplied on dual-cool systems only (four-pipe system).
3. Piping dimensions shown are connection sizes; field piping sizes may be different, depending on distance. Refer to user manual,
SL-18826.
4. Source: DPN001179, Rev. 6

Liebert DS

82

Weights and Dimensions

Figure 64

Cabinet and floor planning dimensionsUpflow, water/glycol-cooled, 53-77kW (15-22 tons), all
compressor models with forward-curved blowers
Digital scroll compressors
not available on 077 models.

Condenser Cleanout Access

33"
(838mm)

5/16"
(8mm)
Bezel

35"
(889mm)
Alternate Condenser Fluid
Piping Entra
High-Voltage
Connection(s)
1-1/2"
(38mm)

1-3/4"
(44mm)
Handle

Required for
condenser cleanout
Minimum required
for blower replacement

Low-Voltage
Connection(s)

TOP VIEW
109" (2769mm)
24"
(610mm)

76"
(1930mm)

34"
(864mm)

2"
(51mm)

Shaded area indicates a


required minimum clearance from floor
to top of unit and plenum for component
access.

108" (2743mm)

FRONT VIEW

Front air return unit shown. For rear return unit, in addition to front service
area shown, also include 25" (635mm) on one side of unit for access to rear
return filter box. See DPN001196.

83

DPN003158
Rev. 1

Liebert DS

Weights and Dimensions

Primary connection locationsUpflow water/glycol/GLYCOOL 53-77kW (15-22 tons) all


compressor models with forward-curved blowers

Figure 65

Digital scroll compressors


not available on 077 models.

1. Drawing not to scale.


2. Tolerance on all piping dimensions is 1/2" (13mm).
3. Field-routed alternatives for GLYCOOL connections.
4. See submittal page DPN001191 for blower outlet and deck
dimensional data.

ECR
ECS
HUM
CPD

W1, W2
8"
(203mm)
35"
(889mm)

2-7/8"
(73mm)

All dimensions from


rear corner of unit
including panels

3.

BLOWER
OUTLET

BLOWER
OUTLET

4.

4.

Y
3-1/2"
(89mm)

LV1
LV2
LV3

E1 E2
109" (2769mm)

Front

6"
(152mm)

TOP VIEW
W3
WS
WR

17-3/16"
(437mm)

3.

CGD*

14-1/4"
(362mm)

3-7/8"
(98mm)

15-7/8"
(403mm)

FRONT SECTION VIEW


Left Front Panel Not Shown

CGD*

LEFT SIDE SECTION VIEW

Point

DPN001214
Rev. 2

Description

X
in. (mm)

Y
in. (mm)

Connection Size / Opening


in. (mm)
3-1/2 x 8 (89 x 203)

W1

Water/Glycol/GLYCOOL Access (Bottom)

102-15/16 (2615)

9 (229)

W2

Water/Glycol/GLYCOOL Access (Top)

102-15/16 (2615)

9 (229)

3-1/2 x 8 (89 x 203)

W3

Water/Glycol/GLYCOOL Access (Side)

6 x 17-3/16 (152 x 437)

WS

Water/Glycol/GLYCOOL Supply

2-1/8" Cu Sweat

WR

3
1

Water/Glycol/GLYCOOL Return

2-1/8" Cu Sweat

CGD

Condensate Gravity Drain

3/4" FPT

CPD

Condensate Pump Discharge (Opt)

78-5/8 (1998)

11-1/8 (282)

1/2" Cu Sweat

HUM

Humidifier Supply Line

78-5/8 (1998)

9-7/8 (251)

1/4" Cu Sweat

ECS

Econ-O-Coil Supply

79-5/16 (2015)

7-7/8 (200)

2-1/8" Cu Sweat

ECR

Econ-O-Coil Return

79-5/16 (2015)

4-5/8 (117)

2-1/8" Cu Sweat

E1

Electrical Connection (High-Voltage)

75-3/8 (1915)

30 (762)

2-1/2"

E2

Electrical Connection (High-Voltage)

69-7/8 (1775)

30 (762)

2-1/2"

LV1

Electrical Connection (Low-Voltage)

19-1/2 (495)

29-1/16 (738)

7/8"

LV2

Electrical Connection (Low-Voltage)

19-1/2 (495)

30-1/2 (775)

7/8"

LV3

Electrical Connection (Low-Voltage)

19-1/2 (495)

31-15/16 (811)

7/8"

1. Field-pitch condensate drain line a minimum of 1/8" (3.2 mm) per foot (305 mm). All units contain a factory-installed condensate
trap. Do not trap external to the unit. Drain line may contain boiling water. Select appropriate drain system materials. The drain
line must comply with all local codes.
2. Supplied on dual-cool systems only.
3. Source: DPN001214, Rev. 2

Liebert DS

84

Weights and Dimensions

Figure 66

Cabinet and floor planning dimensionsUpflow, water/glycol-cooled, 105kW (30 tons), all
compressor models with forward-curved blowers
Alternate Refrigerant
Piping Entrance

Digital scroll compressors


not available on 105 models.

33"
(838mm)
35"
(889mm)
Alternate Condenser Fluid
Piping Entrance
High-Voltage
Connection(s)
1-1/2"
(38mm)

5/16"
(8mm)
Bezel

1-3/4"
(44mm)
TOP VIEW Handle

Low-Voltage
Connection(s)

Required for
condenser cleanout
Minimum required
for blower replacement

132" (3353mm)

24"
(610mm)

76"
(1930mm)

34"
(864mm)
2"
(51mm)

131" (3327mm)

Shaded area indicates a


required minimum clearance from floor
to top of unit and plenum for component
access.
Front air return unit shown. For rear return unit, in addition to front service
DPN003160
area shown, also include 25" (635mm) on one side of unit for access to rear
Rev. 1
return filter box. See DPN001196.

FRONT VIEW

85

Liebert DS

Weights and Dimensions

Primary connection locationsUpflow water/glycol/GLYCOOL 105kW (30 tons) all


compressor models with forward-curved blowers

Figure 67

All dimensions from


rear corner of unit
including panels

Digital scroll compressors


not available on 105 models.
Blower
Outlet

8"
35"
(203mm)
(889mm)
2-7/8"
NOTES:
(73mm)
1. Drawing not to scale.
3-1/2"
2. Tolerance on all piping dimensions
(89mm)
is 1/2" (13mm).
3. Field routed alternatives for water/glycol
connections.
4. Forward-curved blowers shown.
See submittal page DPN001192 for
blower outlet and deck dimensional data.

Blower
Outlet

Blower
Outlet

LV1 LV3
LV2

LV4

132"
(3353mm)

Front Of Unit

TOP VIEW OF UNIT

6"
(152mm)

W3
WS
WR

17-3/16"
(437mm)

CGD*

3-7/8"
(98mm)

CGD*

14-1/4"
(362mm)

FRONT SECTION VIEW OF UNIT


(Left Front Panel Not Shown)

15-7/8"
(403mm)

DPN001258
Rev. 1

LEFT SIDE SECTION VIEW OF UNIT


Point

Description

X
in. (mm)

Y
in. (mm)

Connection Size / Opening


in. (mm)

W1

Water/Glycol/GLYCOOL Access (Bottom)

126-1/8 (3204)

9 (229)

3-1/2 x 8 (89 x 203)

W2

Water/Glycol/GLYCOOL Access (Top)

126-1/8 (3204)

9 (229)

3-1/2 x 8 (89 x 203)

W3

Water/Glycol/GLYCOOL Access (Side)

6 x 17-3/16 (152 x 437)

WS

Water/Glycol/GLYCOOL Supply

2-1/8" Cu Sweat

WR

3
1

Water/Glycol/GLYCOOL Return

2-1/8" Cu Sweat

CGD

Condensate Gravity Drain

3/4" FPT

CPD

Condensate Pump Discharge (Opt)

102-3/8 (2600)

13-5/8 (346)

1/2" Cu Sweat

Humidifier Supply Line

101-1/8 (2569)

13-1/8 (333)

1/4" Cu Sweat

HUM
ECS

Econ-O-Coil Supply

101-1/8 (2569)

10-1/4 (260

2-5/8" Cu Sweat

ECR

Econ-O-Coil Return

101-1/8 (2569)

5-1/4 (133)

2-5/8" Cu Sweat

E1

Electrical Connection (High-Voltage)

98-1/2 (2502)

30 (762)

2-1/2"

E2

Electrical Connection (High-Voltage)

93 (2362)

30 (762)

2-1/2"

LV1

Electrical Connection (Low-Voltage)

41-1/8 (1045)

30-3/8 (772)

7/8"

LV2

Electrical Connection (Low-Voltage)

38-7/8 (987)

30-3/8 (772)

7/8"

LV3

Electrical Connection (Low-Voltage)

35-1/8 (892)

30-3/8 (772)

7/8"

LV4

Electrical Connection (Low-Voltage)

31-5/8 (803)

30-3/8 (772)

7/8"

1. Field-pitch condensate drain line a minimum of 1/8" (3.2 mm) per foot (305 mm). All units contain a factory-installed condensate
trap. Do not trap external to the unit. Drain line may contain boiling water. Select appropriate drain system materials. The drain
line must comply with all local codes.
2. Supplied on dual-cool systems only.
3. Source: DPN001258, Rev. 1

Liebert DS

86

Blower Outlet and Deck Dimensions

8.0

BLOWER OUTLET AND DECK DIMENSIONS

Figure 68

Blower outlet and deck dimensionsUpflow, 28-42kW (8-12 tons) with forward-curved blowers
73" (1854mm) or 86" (2184mm) Ref
E

Blower Outlet *

35"
(889mm)
Ref

Blower Outlet Location - Top View

Front of Unit

* Duct flange not provided

Top of Unit
Blower Deck
1-1/2"
(38mm)

76"
(1930mm)
Ref

Front or Rear Throw Air Supply

DPN001120
Rev. 3

Dimensional Data in. (mm)


Models

28-42kW
(8-12 Tons)

Blower
15 x 15
15 x 15

Supply

Front Throw

15-7/8 (404)

Rear Throw

15-7/8 (404)

18-5/8 (472)

2-1/8 (54)

25-5/8 (651)

25 (635)

18-5/8 (472)

11-5/8 (295)

25-5/8 (651)

25 (635)

Front Throw

15-7/8 (404)

14-1/2 (368)

2-1/8 (54)

25-5/8 (651)

25 (635)

Rear Throw

15-7/8 (404)

14-1/2 (368)

11-5/8 (295)

25-5/8 (651)

25 (635)

Source: DPN001120, Rev. 3

87

Liebert DS

Blower Outlet and Deck Dimensions

Figure 69

Blower outlet and deck dimensionsUpflow, 53-77kW (15-22 tons) with forward-curved
blowers

98" (2449mm) or 109" (2769mm)


F
E
Blower Outlets *

35"
(889mm)
Ref

Blower Outlet Location - Top View

Front of Unit

* Duct flanges not provided.

Top of Unit
Blower Deck
D

1-1/2"
(38mm)

76"
(1930mm)
Ref.

Front or Rear Air Throw Supply

DPN001191
Rev. 6

Dimensional Data, in. (mm)


Models

53-77kW
(15-22
tons)

Blower

15 x 15
15 x 11

Supply

Front Throw 15-7/8 (404)

18-5/8 (472)

2-1/8 (54)

Rear Throw 15-7/8 (404)

18-5/8 (472)

Front Throw 15-7/8 (404) 14-11/16 (373)

25-5/8 (651) 27-3/4 (705)

55-1/2 (1410)

11-5/8 (295) 25-5/8 (651) 27-3/4 (705)

55-1/2 (1410)

2-1/8 (54)

25-5/8 (651) 31-3/8 (797) 58-7/16 (1484)

Rear Throw 15-7/8 (404) 14-11/16 (373) 11-5/8 (295) 25-5/8 (651) 31-3/8 (797) 58-7/16 (1484)

Source: DPN001191, Rev. 6

Liebert DS

88

Blower Outlet and Deck Dimensions

Figure 70

Blower outlet and deck dimensionsUpflow, 105kW (30 tons), forward-curved blowers

132" (3353mm)
G
Blower Outlets *

F
E

A
35"
(889mm)
Ref

BLOWER OUTLET LOCATION - TOP VIEW

Front of Unit

* Duct flanges not provided

TOP OF UNIT
Blower Deck
1-1/2"
(38mm)

76"
(1930mm)
Ref

DPN001192
Rev. 1

Front or Rear Throw Air Supply


Dimensional Data, in. (mm)
Blower
15 x 11

SUPPLY

Front Throw 15-7/8 (404) 14-11/16 (373)

2-1/8 (54)

25-5/8 (651) 30-3/4 (781) 54-1/2 (1384) 78-1/8 (1984)

Rear Throw 15-7/8 (404) 14-11/16 (373) 11-5/8 (295) 25-5/8 (651) 30-3/4 (781) 54-1/2 (1384) 78-1/8 (1984)

Source: DPN001192, Rev. 1

89

Liebert DS

Blower Outlet and Deck Dimensions

8.1

Disassembly DimensionsUpflow Air-Cooled Systems

Figure 71

Disassembly dimensionsUpflow, air-cooled, 28-42kW (8-12 tons), scroll compressor models

Blower & Electric


Box Assembly

31-1/4"
(794mm)

Compressor Assembly

76" (1930mm)
Assembled
Height

Filter & Coil


Assembly
76"
(1930mm)

45-13/16"
(1163mm)

33"
(838mm)

13"
(330mm)

59" (1499mm)

72" (1829mm)
Assembled Length
Drawing views are simplified with panels removed to show overall dimensions.
See disassembly and handling instructions in installation manual.

DPN003162
Rev. 1

Dry Weight, Approximate, Including Panels, lb (kg)


Air-Cooled

Dual-Cool

Compressor Assembly

490 (223)

490 (223)

Blower and Electric Box Assembly


Forward-Curved Blowers

510 (231)

510 (231)

EC Fan 1

360 (163)

360 (163)

Filter and Coil Assembly

520 (236)

670 (304)

Component

1. Fan weight not included in this weight. Fan is installed in plenum. See 313221 for plenum weight.
2. Source: DPN003162, Rev. 2

Liebert DS

90

Blower Outlet and Deck Dimensions

Figure 72

Disassembly dimensionsUpflow, air-cooled, 28-42kW (8-12 tons), semi-hermetic


compressors

Blower & Electric


Box Assembly

31-1/4"
(794mm)

Compressor Assembly
76"
(1930mm)
Assembled
Height

Filter & Coil


Assembly

76"
(1930mm)
45-13/16"
(1163mm)

33"
(838mm)

26"
(660mm)
85" (2159mm)
Assembled Length

59"
(1499mm)

Drawing views are simplified with panels removed to show overall dimensions.
See disassembly and handling instructions in installation manual.

DPN003161
Rev. 1

Dry Weight, Approximate, Including Panels, lb. (kg)


Air-Cooled

Dual-Cool

800 (364)

800 (364)

510 (231)

510 (231)

Blower and Electric Box Assembly (EC Fans )

360 (163)

360 (163)

Filter and Coil Assembly

520 (236)

670 (304)

Component
Compressor Assembly
Blower and Electric Box Assembly (Forward-Curved Fans)
1

1. Fan weight not included in this weight. Fan is installed in plenum. See 313221 for plenum weight.
2. Source: DPN003161, Rev. 1

91

Liebert DS

Blower Outlet and Deck Dimensions

Figure 73

Disassembly dimensionsUpflow, air-cooled, 53-77kw (15-22 tons), scroll or digital scroll


compressors
Digital scroll compressors not
available on 077 models.

Blower & Electric


Box Assembly

31-1/4"
(794mm)

Compressor Assembly

76"
(1930mm)
Assembled
Height

Filter & Coil


Assembly
76"
(1930mm)

45-13/16"
(1163mm)

33"
(838mm)

15"
(381mm)

82" (2083mm)
97" (2464mm)
Assembled Length

Drawing views are simplified with panels removed to show overall dimensions.
See disassembly and handling instructions in installation manual.

Model #

Dry Weight, Approximate, Including Panels, lb. (kg)


053, 070, 077
Scroll/Digital Scroll 1

Compressor
Component
Compressor Assembly
Blower and Electric Box Assembly
EC Fans 2
Blower and Electic Box Assembly
(Forward-Curved Blowers)
Filter and Coil Assembly

DPN003166
Rev. 1

Air-Cooled

Dual-Cool

540 (246)

540 (246)

600 (272)

600 (272)

770 (349)

770 (349)

760 (345)

940 (426)

1. Digital scroll compressors not available on 077 models.


2. Fan weight not included in this weight. Fans are installed in plenum. See 313221 for plenum weight.
3. Source: DPN003166, Rev. 1

Liebert DS

92

Blower Outlet and Deck Dimensions

Figure 74

Disassembly dimensionsUpflow, air-cooled, 53-77kW (15-22 tons), semi-hermetic


compressor models

Blower & Electric


Box Assembly

31-1/4"
(794mm)

Compressor Assembly

Filter & Coil


Assembly

76" (1930mm)
Assembled Height

76"
(1930mm)
45-13/16"
(1163mm)

33"
(838mm)

26"
(660mm)

82" (2083mm)
108" (2743mm)
Assembled Length

Drawing views are simplified with panels removed to show overall dimensions.
See disassembly and handling instructions in installation manual.

DPN003165
Rev. 2

Dry Weight, Approximate Including Panels, lb. (kg)


Air-Cooled

Dual-Cool

Compressor Assembly

970 (441)

970 (441)

Blower and Electric Box Assembly


(Forward-Curved Blowers)

770 (349)

770 (349)

EC Fans 1

600 (231)

600 (231)

Filter and Coil Assembly

760 (345)

940 (426)

Component

1. Fan weight not included in this weight. Fans are installed in plenum. See 313221 for plenum weight.
2. Source: DPN003165, Rev. 2

93

Liebert DS

Blower Outlet and Deck Dimensions

Figure 75

Disassembly dimensionsUpflow, air-cooled, 105kW (30 tons), standard scroll compressors


Digital scroll compressors
not available on 105 models.

Blower & Electric


Box Assembly

31-1/4"
(794mm)

Compressor
Assembly

76"
(1930mm)
Assembled
Height
Filter & Coil Assembly

76"
(1930mm)
45-13/16"
(1164mm)

33"
(838mm)

26"
(660mm)

105" (2667mm)

131" (3327mm
Assembled Length
Drawing views are simplified with panels removed to show overall dimensions.
Seee disassembly and handling instructions in installation manual.

DPN003169
Rev. 1

Dry Weight, Approximate, Including Panels, lb (kg)


Air-Cooled

Dual-Cool

Compressor Assembly

830 (376)

830 (376)

Blower and Electric Box Assembly


(Forward-Curved Blowers)

1080 (490)

1080 (490)

EC Fans 2

840 (381)

840 (381)

Filter and Coil Assembly

970 (440)

1300 (590)

Component

1. Digital scroll compressors not available on 105 models.


2. Fan weight not included in this weight. Fans are installed in plenum. See 313221 for plenum weight.
3. Source: DPN003169, Rev. 1

Liebert DS

94

Blower Outlet and Deck Dimensions

Figure 76

Disassembly dimensionsUpflow, air-cooled, 105kW (30 tons), semi-hermetic compressors

Blower & Electric


Box Assembly

31-1/4"
(794mm)

Compressor
Assembly
76"
(1930mm)
Assembled
Height

Filter & Coil


Assembly
76"
(1930mm)

45-13/16"
(1164mm)

33"
(838mm)

26"
(660mm)

105" (2667mm)

131" (3327mm
Assembled Length
Drawing views are simplified with panels removed to show overall dimensions.
See disassembly and handling instructions in installation manual.

DPN003168
Rev. 1

Dry Weight, Approximate, Including Panels, lb (kg)


Air-Cooled

Dual-Cool

Compressor Assembly

950 (431)

950 (431)

Blower and Electric Box Assembly


(Forward-Curved Blowers)

1080 (490)

1080 (490)

EC Fans 1

840 (381)

840 (381)

Filter and Coil Assembly

970 (440)

1300 (590)

Component

1. Fan weight not included in this weight. Fans are installed in plenum. See 313221 for plenum weight.
2. Source: DPN001254, Rev. 1

95

Liebert DS

Blower Outlet and Deck Dimensions

8.2

Disassembly DimensionsUpflow, Water/Glycol/GLYCOOL Systems

Figure 77

Disassembly dimensionsUpflow, water/glycol/GLYCOOL, 28-42kW (8-12 tons), all


compressors
Digital scroll compressors not
available on 077 models.

Blower & Electric


Box Assembly

31-1/4"
(794mm)

Compressor Assembly
76" (1930mm)
Assembled
Height

Filter & Coil


Assembly

76"
(1930mm)
45-13/16"
(1163mm)

33"
(838mm)

26"
(660mm)

59" (1499mm)
85" (2159mm)
Assembled Length

Drawing views are simplified with panels removed to show overall dimensions.
See disassembly and handling instructions in installation manual.

DPN003163
Rev. 1

Dry Weight, Approximate, Including Panels, lb (kg)


Semi-Hermetic Compressor

Scroll/Digital Scroll Compressor 1

Water/Glycol

GLYCOOL/Dual-Cool

Water/Glycol

GLYCOOL/Dual-Cool

Compressor Assembly

950 (432)

950 (432)

800 (364)

800 (364)

Blower and Electric Box Assembly


(Forward-Curved Blower)

510 (231)

510 (231)

510 (231)

510 (231)

Blower and Electric Box Assembly


EC Fans 2

360 (163)

360 (163)

360 (163)

360 (163)

Filter and Coil Assembly

520 (236)

670 (304)

520 (236)

670 (304)

Component

1. Digital scroll compressors not available on 077 models.


2. Fan weight not included in this weight; fans are installed in plenum. See 313221 for plenum weight.
3. Source: DPN003163, Rev. 1

Liebert DS

96

Blower Outlet and Deck Dimensions

Figure 78

Disassembly dimensionsUpflow, water/glycol/GLYCOOL, 53-77kW (15-22 tons), all


compressors

Digital scroll compressors


not available on 077 models.

Blower & Electric


Box Assembly

31-1/4"
(794mm)

Compressor Assembly

76"
(1930mm)
Assembled
Height
Filter & Coil
Assembly

76"
(1930mm)
45-13/16"
(1163mm)

33"
(838mm)

26"
(660mm)

82" (2083mm)
108" (2743mm)
Assembled Length

Drawing views are simplified with panels removed to show overall dimensions.
See disassembly and handling instructions in installation manual.

DPN003167
Rev. 1

Dry Weight, Approximate, Including Panels, lb (kg)


Semi-Hermetic Compressor

Scroll or Digital Scroll Compressor 1

Water/Glycol

GLYCOOL/Dual-cool

Water/Glycol

GLYCOOL/Dual-Cool

Compressor Assembly

1270 (578)

1270 (578)

840 (382)

840 (382)

Blower and Electric Box Assembly


Forward-Curved Fans

770 (349)

770 (349)

770 (349)

770 (349)

Blower and Electric Box Assembly


EC Fans 2

600 (272)

600 (272)

600 (272)

600 (272)

Filter and Coil Assembly

760 (345)

940 (426)

760 (345)

940 (426)

Component

1. Digital scroll compressors not available on 077 models


2. Fan weight not included in this weight; fans are installed in plenum. See 313221 for plenum weight.
3. Source: DPN003167, Rev. 2

97

Liebert DS

Blower Outlet and Deck Dimensions

Disassembly dimensionsUpflow, water/glycol/GLYCOOL, 105kW (30 Tons) all compressor


models

Figure 79

Digital scroll compressors


not available on 105 models.

Blower and Electric Box


Assembly

31-1/4"
(794mm)

Compressor Assembly

76" (1930mm)
Assembled Height

Filter and Coil


Assembly
76"
(1930mm)

45-13/16"
(1164mm)

33"
(838mm)

26"
(660mm)

105" (2667mm)
131" (3327mm)
Assembled Length
DPN003170
Rev. 1

Drawing views are simplified with panels removed to show overall dimensions.
See disassembly and handling instructions in installation manual.

Dry Weight, Approximate, Including Panels, lb (kg)


Semi-Hermetic Compressor

Scroll or Digital Scroll Compressor 2

Water/Glycol

GLYCOOL/Dual-cool

Water/Glycol

GLYCOOL/Dual-Cool

Compressor Assembly

1320 (599)

1320 (599)

1200 (544)

1200 (544)

Blower and Electric Box Assembly


Forward-Curved Fans

1080 (490)

1080 (490)

1080 (490)

1080 (490)

Blower and Electric Box Assembly


EC Fans

840 (381)

840 (381)

840 (381)

840 (381)

Filter and Coil Assembly

970 (440)

1300 (590)

970 (440)

1300 (590)

Component

1. Fan weight not included in this weight; fans are installed in plenum. See 313221 for plenum weight.
2. Digital scroll compressors not available on 105 models.
3. Source: DPN003170, Rev. 1

Liebert DS

98

Ancillary Items

9.0

ANCILLARY ITEMS

9.1

Floor Stands

Figure 80

Floor stand dimensions, downflow, 28-42kW (8-12 tons) models with EC fans

A + 1-1/2" (38mm) (with feet)


A
B

33"
(838mm)
34-1/2"
876mm
(With Feet)

1"
(35mm)
Typical

Right side of paneled unit is flush with right side of floor stand.
All other paneled sides overhang floor stand 1" (25mm).
* Leveling feet are provided with 1-1/2" (38mm) adjustment
from nominal height C.

Gussets supplied on floor stands


12" (305 mm) tall and greater

C*
1
7/8"
(23mm)

8"
(203mm)

3"
(76mm)

DPN003240
Rev. 1

Applies to 36", 42" and 48" floor stand.

Dimensions, in. (mm)


A

Floor Stand
Height C*
in. (mm)

DS028-042 Air-Cooled Semi-Hermetic and all Water/Glycol/GLYCOOL


Models

85 (2159)

27 (686)

24 (610)

DS028-042 Air-Cooled Scroll and Air-Cooled Digital Scroll Models

72 (1829)

14 (356)

30 (762)

Model

36 (914)
42 (1069)

Source: DPN003240, Rev. 1

48 (1219)

99

Liebert DS

Ancillary Items

Figure 81

Floor stand dimensions, downflow, 53-77kW (15-22 tons) models with EC fans

A
B
Piping Access Area

3/4"
(19mm)

32"
(813mm)
Center Feet

31-1/2"
(800mm)

3/4"
(19mm)

32-3/4"
(832mm)

C
Support Feet Centers

See Note 4
24" FLOOR STAND SHOWN

3/4"
(19mm)

1"
(25mm)

7/8"
(23mm)

33"
(838mm)

F*

3"
(76mm)
E
Notes
1. This floor stand should be used when EC fans are intended to be lowered under
a raised floor. The standard Liebert DS floor stand can be used if the fans are to
remain in their original raised position.
2. Right side of paneled unit is flush with right side of floor stand. All other paneled sides
overhang floor stand 1" (25mm).
3) The floor stand used with EC units is not symmetrical, and its orientation to the
Liebert DSE is critical for lowering the EC fans. The blowers will not lower into the
floor stand unless the floor stand is installed in the correct position.
4. Jack and jack support are shipped loose and are intended to be placed into position
under each fan and utilized to lower or raise that fan as needed.
* Leveling feet are provided with 1-1/2" (38mm) adjustment from nominal height F.

35" (889mm)
Overall Depth

DPN003173
Rev. 1

Dimension, in. (mm)

Leg
Height
F, in.
(mm)

Height
G, in.
(mm)

DS053-077, Air-Cooled Semi-Hermetic


and all Water/Glycol/ GLYCOOL Models

108
(2743)

26
(660)

106.5
(2705)

108
(2743)

109.5
(2781)

24 (610)

DS053-077, Air-Cooled Scroll and


Air-Cooled Digital Scroll Models

97
(2464)

15
(381)

95.5
(2426)

97
(2464)

98.5
(2502)

30 (762)

Liebert DS Model

Source: DPN003173, Rev. 1

Liebert DS

100

36 (914)

42 (1067)

11

48 (1219)

17

Ancillary Items

Figure 82

Floor stand dimensionsDownflow, 105kW (30 tons) models with EC fans, standard scroll and
semi-hermetic compressors
Digital scroll compressors
not available on 105 models.

25"
(635mm)
34-1/2"
33"
(876mm)
(with feet) (838mm)
Typ. Both Ends

132-1/2" (3366mm)
(with feet)
131" (3327mm)

35" (889mm)
(with feet)
Typ. (2) Places

74" (1880mm)

1"
(25mm Typ.)
5
19-1/4"
(489mm)

See
Note 4

Notes

7/8"
(23mm)

3" (76mm)

35"
(889mm)
Overall Depth

1. This floor stand should be used when EC fans are intended to be lowered
under a raised floor. The standard Liebert DS floor stand can be used
if the fans are to remain in their original raised position.

Height - A
in. (mm)
24 (610)
30 (762)

2. Right side of paneled unit is flush with right side of floor stand. All other paneled
sides overhang floor stand 1" (25mm).

36 (914)

3. The floor stand used with EC units is not symmetrical and its orientation to the
Liebert DS is critical for lowering the EC fans. The blowers will not lower into the floor stand
unless the floor stand is installed in the correct position.

42 (1067)
48 (1219)

4. Jack and jack support are shipped loose and are intended to be placed into
position under each fan and utilized to lower or raise that fan as needed.
5. Not applicable to 24' (610mm) x 30" (762) tall floor stands.
*Leveling feet are provided with 1-1/2" (38mm) adjustment from nominal height A.

101

DPN003174
Rev. 2

Liebert DS

Ancillary Items

9.2

Plenums

Figure 83

Plenum dimensionsUpflow VS028-VS042 with EC fans

1 Shaded area indicates a recommended


minimum clearance of 36" (914mm) for
component access from the bottom of the unit
to the top of the plenum.
2

Must have access to remove front grille


or panel to remove EC fans.

m)

32.1"
(815mm)

m
63

.6"

(14

Top duct flanges on plenum


top for supply air ducting when
solid panel plenum is used.
0.88"
(2.2mm)

57

19.7"
(500mm)

Plenum
Height

4.3" (109mm)
0.88"
(2.2mm)

Both top duct opening


and grilles shown. See
specification sheet
for specific application.

m)

0m

.7"

4
(14

1.3"
(33mm)
2

56

m)

" (1

"
1.3 m)
m
(33

33.75"
(857mm)

m
05

5
9.2

Plenum Type

Height
In. (mm)

Grille & Top Discharge

24 (610)

Top Discharge Only

30 (762)

Top Discharge Only

36 (914)

Liebert DS

DPN002747
Rev. 1

102

Ancillary Items

Figure 84

Plenum dimensionsUpflow 53-77kW (15-22 tons) with EC fans


Top duct flanges on plenum
top for supply air ducting when
solid panel plenum is used.

Shaded area indicates a recommended


minimum clearance of 36" (914mm) for
component access from the bottom of the unit
to the top of the plenum.
Must have access to remove front grille
or panel to remove EC fans.

32"
(813mm)
m)

7m

"

81

5
(20

20"
(508mm)

4" (102mm)

1"
(25mm)

Plenum
Height
Both top duct opening
and grilles shown. See
specification sheet
for specific application.

0.88"
(2.2mm)

0.88"
(2.2mm)

m)

m
32

" (2

80

mm

3
08

" (2

82

1"
(25mm)

34"
(864mm)

DPN002748
Rev. 3
Plenum Type

Height
In. (mm)

Grille & Top Discharge

24 (610)

Top Discharge Only

30 (762)

Top Discharge Only

36 (914)

103

Liebert DS

Ancillary Items

Figure 85

Plenum dimensionsUpflow 105kW (30 tons) with EC fans


1

Shaded area indicates a recommended


minimum clearance of 36" (914mm) for
component access from the bottom of the unit
to the top of the plenum.

32"
(813mm)

Top duct flanges on plenum


top for supply air ducting when
solid panel plenum is used.
0.88"
(2.2mm)

Must have access to remove front grille )


or panel to remove EC fans.
mm
41
6
(2
4"
10
20"
(508mm)

Both top duct opening


and grilles shown. See
specification sheet
for specific application.

m)

m
(51 m)
2"
9m
5
" (5
22

Plenum
Height
0.88"
(2.2mm)

4" (102mm)
1"
(25mm)
2

m)

2m

"

80

3
(20

m)

3m

5"

10
34"
(864mm)

7
(26

1"
(25mm)

DPN002749
Rev. 1

Plenum Type

Height
In. (mm)

Grille & Top Discharge

24 (610)

Top Discharge Only

30 (762)

Top Discharge Only

36 (914)

Liebert DS

104

Ancillary Items

Figure 86

Plenum dimensions28-105kW (8-30 tons), upflow with forward-curved blowers

FRONT VIEWS - CHECK ONE

REAR VIEWS - CHECK ONE

With Front Grille

With Rear Grille


Panel removable
for condenser clean
out access
(Water/Glycol/GLYCOOL
models only)

Without Grille

34"
(864mm)

Left Side Views Check One:

Without Grille
A

Right Side Views Check One:


H

1"
(25mm)

With
Grille

With Grille
76"
(1930mm)

Without
Grille

Without Grille
SIDE VIEW - UNIT WITH PLENUM

FRONT VIEW - UNIT WITH PLENUM


NOTES
1. Typical 53-77kW (15-20 Tons) unit orientation shown with grille plenum.
View varies by unit size and plenum selection.
2. Optional grille plenum kits must include front or rear grille.
DPN003164
3. Non-grille plenums are open on the top and not designed with duct flange.
Rev. 1
4. All plenums are shipped flat and must be field assembled.
Dimensions, in. (mm)

Grille Size, in. (mm) - Nominal


A
in. (mm)

B
in. (mm)

Front/Rear
Grilles

Side Grille

28-42kW (8-12 tons) Air-Cooled Scroll and


Air-Cooled Digital Scroll Models

59-1/4
(1505)

13-3/4
(349)

18 x 55
(457 x 1397)

18 x 20
(457 x 508)

28-42kW (8-12 tons) Semi-Hermetic and


all Water/Glycol/GLYCOOL Models

59-1/4
(1505)

26-3/4
(679)

18 x 55
(457 x 1397)

18 x 20
(457 x 508)

53-77kW (15-22 tons) Air-Cooled Scroll and Air-Cooled


Digital Scroll Models

82-1/4
(2089)

15-3/4
(400)

18 x 78
(457 x 1981)

18 x 20
(457 x 508)

53-77kW (15-22 tons) Semi-Hermetic and


all Water/Glycol/GLYCOOL Models

82-1/4
(2089)

26-3/4
(679)

18 x 78
(457 x 1981)

18 x 20
(457 x 508)

105kW (30 tons)All Models

105-1/4
(2673)

26-3/4
(679)

(1) 18 x 20
(457 x 508)
(1) 18 x 78
(457 x 1981)

18 x 20
(457 x 508)

Model

Source: DPN003164, Rev. 1


Plenum Configuration

Height H, in. (mm)


20 (508)

Non-grilled

24 (610)

Non-grilled, front discharge or rear discharge

36 (914)

Non-grilled

Source: DPN003164, Rev. 1

105

Liebert DS

Ancillary Items

9.3

Rear Return Filter Box

Figure 87

Rear return filter box dimensionsUpflow, air cooled 28-105kW (8-30 tons), all compressors
Digital scroll compressors not
available on 077 or 105 models.

Filter Access
Door

Filter Access
Door

7-15/16"
(202mm)

40"
(1016mm)
38-1/4"
(971mm)
Duct Size

76"
(1930mm)

3-1/2" (89mm)

D Duct Size

A
B
NOTES
1. Filters can be accessed from either side.
2. 25" (635mm) minimum clearance provided on one side for filter access.
3. Filter boxes are shipped flat and must be field assembled.

DPN001196
Rev. 1

A
in. (mm)

B
in. (mm)

C
in. (mm)

D
in. (mm)

# Filters

DS28-42kW (8-12 Tons) Air-Cooled Scroll


and Air-Cooled Digital Scroll Models

4-1/4 (108)

50-3/4 (1289)

18 (457)

47-5/8 (1210)

DS28-42kW (8-12 Tons) Semi-Hermetic and All


Water/Glycol/GLYCOOL Models

4-1/4 (108)

50-3/4 (1289)

31 (787)

47-5/8 (1210)

DS53-77kW (15-22 Tons) Air-Cooled Scroll


and Air-Cooled Digital Scroll Models 1

3-1/4 (83)

75-1/2 (1918)

19-1/4 (489)

72-3/8 (1838)

DS53-77kW (15-22 Tons) Semi-Hermetic and


All Water/Glycol/GLYCOOL Models 1

3-1/4 (83)

75-1/2 (1918)

30-1/4 (768)

72-3/8 (1838)

DS105kW (30 Tons), All Models 1

2-1/4 (57)

100-1/4 (2546)

29-1/2 (749)

97-1/8 (2467)

Model #

1. Digital scroll compressors not available on 077 or 105 models.


2. Source: DPN001196, Rev. 1

Liebert DS

106

Piping

10.0 PIPING
Table 18

Recommended refrigerant line sizes - OD copper (inches)

Standard Scroll Models (Non-Digital Scroll)


Model

028

035

042

053

070

077

105

Hot
Hot
Hot
Hot
Hot
Hot
Hot
Equivalent Gas Liquid Gas Liquid Gas Liquid Gas Liquid Gas Liquid Gas Liquid Gas Liquid
Length
Line Line Line Line Line Line Line Line Line Line Line Line Line Line
50 ft (15m)

7/8

1/2

7/8

1/2

7/8

1/2

7/8

5/8

1-1/8

7/8

1-1/8

7/8

1-3/8

7/8

100 ft (30m)

7/8

5/8

7/8

5/8

7/8

5/8

1-1/8

7/8

1-1/8

7/8

1-1/8

7/8

1-3/8

7/8

150 ft (45 m)

7/8

5/8

7/8

5/8

7/8

5/8

1-1/8

7/8

1-1/8

7/8

1-1/8

7/8

1-3/8 1-1/8

4-Step Semi-Hermetic and Digital Scroll Models


Model

028

035

042

053

077 2

070

105 2

Hot
Hot
Hot
Hot
Hot
Hot
Hot
Equivalent Gas Liquid Gas Liquid Gas Liquid Gas Liquid Gas Liquid Gas Liquid Gas Liquid
Line Line Line Line Line Line Line Line Line Line Line Line Line Line
Length
50 ft (15m)

3/4

100 ft (30m)

1/2

3/4

150 ft (45 m)

5/8

7/8

5/8

3/4

1/2

7/8

7/8

5/8

7/8

5/8

5/8

7/8
1-1/8

5/8
1

5/8

7/8
1

1-1/8

1-1/8

7/8

1-1/81

7/8

1-1/8

7/8

1-3/8

7/8

7/8

7/8

1-1/8

7/8

1-3/8

7/8

7/8

1-1/8

7/8

1-3/8 1-1/8

7/8

1-1/8
1-1/8

1. Downsize vertical riser one trade size (1-1/8" to 7/8")


2. Digital scroll compressors not available on 077 or 105 models.
3. Source: DPN000788, Rev 1

Table 19

Indoor unit approximate refrigerant charge for R-407C


Model

R-407C Charge
per Circuit, lb. (kg)

028, 035, 042

5.5 (2.5)

053, 070, 077

8.0 (3.6)

105

9.5 (4.3)

System Type
Air-Cooled

Table 20

Interconnecting piping refrigerant charge

Line Size,
O.D., in.

R-407C, lb/100 ft. (kg/30m)


Liquid Line

Hot Gas Line

1/2

6.7 (3.0)

5/8

10.8 (4.8)

0.8 (0.4)

3/4

16.1 (7.2)

1.2 (0.5)

7/8

22.3 (10.0)

1.7 (0.8)

1-1/8

38.0 (17.0)

2.9 (1.3)

1-3/8

57.9 (25.9)

4.4 (2.0)

Source: DPN003099, Rev. 0

107

Liebert DS

Piping

Table 21

Liebert MC CondenserRefrigerant required, R-407C, approximate


Dual-Circuit, lb/circuit (kg/circuit)
Condenser
Models

Condensers without
Liebert Lee-Temp

Condensers with
Liebert Lee-Temp

Approximate R-407C Refrigerant Needed


MCS056

2.2 (1.0)

21.0 (9.5)

MCM080

3.0 (1.4)

21.8 (9.9)

MCM160

7.5 (3.4)

44.5 (20.2)

MCL110

5.1 (2.3)

26.0 (11.8)

MCL220

12.2 (5.6)

53.8 (24.4)

Source: DPN002411, Rev. 7

Table 22

Liebert Fin/Tube condenserRefrigerant required, R-407C, approximate


Approximate R-407C Refrigerant Needed
Dual-Circuit lb/circuit (kg/circuit)

Standard
Condenser
Models

FSC or VFD

Lee-Temp
(includes receiver)

CD*/TCDV205

7 (3.2)

54 (24.4)

CD*/TCDV251

10 (4.6)

36 (16.3)

CD*/TCDV308

11 (5.0)

55 (24.9)

CD*/TCDV415

24 (10.9)

102 (46.2)

CD*/TCDV616

26 (11.8)

108 (49.0)

Quiet-Line Condenser Models


DCD*214

N/A

77 (34.9)

DCD*286

N/A

119 (54.0)

DCD*409

N/A

148 (67.2)

DCD*572

N/A

186 (84.4)

Liebert DS

108

Piping

10.1

Piping Schematics

10.1.1 Typical System ConfigurationsLIEBERT MC

CONDENSERS

Figure 88 shows a single refrigeration circuit diagram, displaying the indoor air conditioning unit,
the outdoor condenser (with or without Liebert Lee-Temp) and field-supplied interconnection piping.
Figure 88

Liebert MC piping schematic with and without Liebert Lee-Temp

Check Valve
Relief Valve

Service
Valve Liquid Return

Head Pressure
Control Valve
Liebert Lee-Temp Receiver

Check
Valve

Condenser
Coil

Condenser
Coil

Optional Field-Installed
Fusible Plug

Hot Gas Discharge

Liebert Lee-Temp

Internal
Inverted Trap

Liquid
Sensing
Bulb

Service
Valve

Check
Valve

For rises over 25ft. (7.6m),


trap every 20ft. (6m) or at
evenly divided distances*

Evaporator
Coil

Suction

Field installed relief valve(s) required


for 50Hz EU CE units

Service
External
Valve
Equalizer
Compressor

*Isolation
Valve
Hot Gas Discharge

Expansion Solenoid
Valve
Valve

Sight
Glass

Liquid Line

Filter Drier

Refrigerant Piping
Field Piping
Service/Schrader (Access) Connection No Valve Core
Service/Schrader (Access) Connection With Valve Core
NOTES
Single refrigeration circuit shown for clarity.
Schematic representation shown. Do not use for specific connection locations.

109

*Isolation
Valve

Trap at base
of risers
over 5ft. (1.5m)*

* Components are not supplied by


Liebert but are required for
proper circuit operation and
maintenance

DPN002188
Rev. 3

Liebert DS

Piping

10.1.2 Typical System ConfigurationsFin/Tube


Figure 90 shows a single refrigeration circuit diagram, displaying the indoor air conditioning unit,
the outdoor condenser (VFD, Fan Speed Control or Liebert Lee-Temp) and field-supplied
interconnection piping.
Figure 89
Check
Valve

Piping schematic, air-cooled with semi-hermetic compressor with fin/tube condenser

Relief Valve Service


Valve

Liebert Lee-Temp Receiver

Liquid Return
Optional
Subcooling
Coil

Head Pressure
Control Valve

Optional
Sub-Cooling
Coil

Inverted trap on discharge


and liquid lines to extend above
base of coil by a minimum of
7-1/2" (190mm).

CONDENSER
COIL
(FAN SPEED or VFD)

CONDENSER
COIL
(Liebert Lee-Temp)

Optional Field-Installed
Fusible Plug

Hot Gas Discharge


LIEBERT LEE-TEMP
For rises over
25ft. (7.6m),
trap every 20ft. (6m) or
evenly divided*

LIQUID

Service
Valve

Sensing
Bulb

Cylinder
Unloader(s)

EVAPORATOR
COIL

SUCTION

Muffler

Field-installed relief valve(s)


required for 50Hz EU CE units
rated maximum 480 PSIG (33 Bar).

COMPRESSOR Service External


Valve Equalizer
Check Valve

**Muffler

*Isolation
Valve

Hot Gas Discharge


Expansion Solenoid
Valve
Valve

Sight
Glass

Liquid Return

Filter Drier

NOTES: Two refrigeration circuits provided.


Single refrigeration circuit shown for clarity.

Trap at base of risers


over 5ft. (1.5m)*

* Components are not supplied by


Emerson but are required for
proper circuit operation and
maintenance.

Schematic representation shown.


Do not use for specific connection locations.
REFRIGERANT PIPING
FIELD PIPING
Service / Schrader (Access) Connection No Valve Core
Service / Schrader (Access) Connection With Valve Core

Liebert DS

*Isolation
Valve

110

** Components supplied by Emerson


and must be field-installed (70kW,
77 kW & 105kW models only).
DPN000797
Rev. 7

Piping

Figure 90

Piping schematic, air-cooled with scroll or digital scroll compressor with fin/tube condenser

Inverted Trap on discharge


and liquid lines to extend above
base of coil by a minimum of
7-1/2" (190mm).
Optional
Subcooling
Coil
CONDENSER
COIL
(Fanspeed or VFD)

Relief
Valve

Check
Valve

Service
Valve

Head Pressure
Liebert Lee-Temp Receiver Control Valve

Optional
Field-Installed
Fusible Plug

Hot Gas Discharge


LIEBERT LEE-TEMP
(Liebert Lee-Temp or VFD condenser
is required with digital scroll)

LIQUID
Sensing
Bulb

28-42kW Digital Solenoid Valve


53-70kW Digital
Solenoid Valve

Optional
Sub-Cooling
Coil

CONDENSER
COIL
(Liebert Lee-Temp)

Hot Gas Discharge


FANSPEED/VFD
(Liebert Lee-Temp or VFD condenser
is required with Digital Scroll)

Liquid Return

For rises over


25ft. (7.6m),
trap every 20ft.
(6m) or evenly
divided*

EVAPORATOR
COIL

SUCTION

Service
Valve
Check
External
Service
Valve
Equalizer
COMPRESSOR Valve

Field-installed relief valve(s) required


for 50Hz EU CE units rated maximum
480 PSIG (33 Bar).
*Isolation
Valve
Hot Gas Discharge

Expansion
Valve

Solenoid Sight
Filter Drier
Valve
Glass
NOTES: Two refrigeration circuits provided.
Single refrigeration circuit shown for clarity.
Schematic representation shown.
Do not use for specific connection locations.

Liquid Return
* Components are not supplied by
Emerson but are required for
proper circuit operation and
maintenance.

REFRIGERANT PIPING
FIELD PIPING

*Isolation
Valve Trap at base of risers
over 5ft. (1.5m)*

DPN000798
Rev. 7

Service / Schrader (Access) Connection No Valve Core


Service / Schrader (Access) Connection With Valve Core

111

Liebert DS

Piping

Figure 91

Piping schematicWater/glycol semi-hermetic compressor models


Optional Dual Pump System Shown
** EXPANSION
TANK

LIEBERT
HEAT REJECTION

CUSTOMER
HEAT REJECTION

* Check Valves
(on Dual Pump
Systems only)

DRYCOOLER
(Glycol)

COOLING TOWER
AND PUMP
SYSTEM
BY OTHERS

GLYCOL
PUMPS

* Pressure
Port

Aquastat
Sensing
Bulbs

* Hose
Bib * Shutoff Valve

* Gate Valves

*** Air Vents


(typical)

* Pressure Port

Flow Switch
Supplied with Dual
Pump Systems
RETURN

* Shutoff Valve

SUPPLY

* Flow-Regulating
Valve
RETURN

LIEBERT DS
(and associated piping)

RETURN

SUPPLY

LIQUID
Sensing Bulb
Cylinder
Unloader(s)

Service
Valve

SUPPLY

Optional
3-Way
Regulating
Valve

EVAPORATOR
COIL

* Shutoff Valve
* Shutoff Valve
* Hose
Bib

SUCTION

* Hose
Bib

Muffler

COMPRESSOR
Service External
Check
Valve Equalizer
Valve

Two-Way
Regulating
Valve

DISCHARGE

Bypass Valve

PARADENSER
CONDENSER

Expansion Solenoid Sight


Valve
Glass
Valve

Filter Drier
Relief valve(s) supplied
TO SECOND
with 50 Hz EU CE units rated
maximum 480 PSIG (33 Bar). REFRIGERATION

Sensor

CIRCUIT

* Components are not supplied by Emerson


but are required for proper circuit operation and
maintenance
** Field-installed at highest point in system on return
line to pumps
*** Locate at tops of all risers and any intermediate
system high points

FACTORY PIPING
FIELD PIPING
OPTIONAL FACTORY PIPING
Service / Schrader (Access) Connection No Valve Core
Service / Schrader (Access) Connection With Valve Core
NOTES: Two refrigeration circuits provided.
Single refrigeration circuit shown for clarity.

DPN000895
Rev. 5

Schematic representation shown.


Do not use for specific connection locations.

Liebert DS

112

Piping

Figure 92

Piping schematicWater/glycol scroll compressor models


LIEBERT
HEAT REJECTION

CUSTOMER
HEAT REJECTION

** EXPANSION
TANK

GLYCOL
PUMPS

* Check Valves
(on Dual Pump
Systems only)

* Gate Valves

DRYCOOLER
(Glycol)

COOLING TOWER
AND PUMP
SYSTEM
BY OTHERS

Optional Dual Pump System Shown

* Pressure
Port
Aquastat
Sensing
Bulbs

*** Air Vents


(typical)

* Hose
* Shutoff Valve
Bib

* Pressure Port
Flow Switch
Supplied with Dual
Pump Systems

* Shutoff Valve
RETURN

* Flow-Regulating
Valve

SUPPLY
RETURN

LIEBERT DS
(and associated piping)

RETURN

LIQUID
Sensing Bulb

Optional
3-Way
Regulating
Valve

EVAPORATOR
COIL

* Shutoff Valve
* Hose
Bib

SUCTION

SUPPLY

SUPPLY

* Shutoff Valve
* Hose
Bib

Service
Valve
Service
CheckCOMPRESSOR Valve
Valve

External
Equalizer

Two-Way
Regulating
Valve

DISCHARGE

Bypass Valve

PARADENSER
CONDENSER

Expansion Solenoid Sight


Valve
Valve
Glass

Filter Drier
Relief valve(s) supplied
with 50 Hz EU CE units rated
maximum 480 PSIG (33 Bar).

Sensor

To Second
Refrigeration
Circuit

FACTORY PIPING
FIELD PIPING
OPTIONAL FACTORY PIPING
Service / Schrader (Access) Connection No Valve Core
Service / Schrader (Access) Connection With Valve Core
NOTES: Two refrigeration circuits provided.
Single refrigeration circuit shown for clarity.

* Components are not supplied by


Emerson but are required for
proper circuit operation and maintenance
** Field-installed at highest point in system
on return line to pumps
*** Locate at tops of all risers and
any intermediate system high points

DPN000896
Rev. 5

Schematic representation shown.


This schematic does not imply or define elevations and
component location, unless specifically noted.

113

Liebert DS

Piping

Figure 93

Piping schematicWater/glycol with digital scroll compressor models

LIEBERT
HEAT REJECTION

CUSTOMER
HEAT REJECTION

GLYCOL
PUMPS
Check Valves*
(on Dual Pump
Systems only)

DRYCOOLER
(Glycol)

COOLING TOWER
AND PUMP
SYSTEM
BY OTHERS

Optional Dual Pump System shown

EXPANSION
TANK**

Pressure
Port*

Gate Valves*

Aquastat
Sensing
Bulbs
Hose
Bib* Shut-Off Valve*

Air Vents
(typical)***

Pressure Port*
Flow Switch
Supplied with Dual
Pump Systems

LIEBERT DS
(and associated piping)

HOT GAS REHEAT


Optional 3-Way
Motorized Ball
Valve

LIQUID
28-42kW Digital Solenoid Valve Sensing Bulb
53-70kW Digital
Solenoid Valve

Flow-Regulating
Valve*

Shut-Off Valve*

RETURN SUPPLY

RETURN

SUPPLY

RETURN

SUPPLY

Shut-Off Valve*
Hose
Bib*

EVAPORATOR
COIL

Shut-Off Valve*
Hose
Bib*

SUCTION
Hot Gas Reheat
Valve

Service
Valve

Service
Valve
Check
COMPRESSOR
Valve

External
Equalizer

2-Way
Motorized
Ball Valve

Check Valve

DISCHARGE

From
Liebert
iCOM
Control

PARADENSER
CONDENSER
Expansion Solenoid Sight
Filter Drier
Valve
Valve
Pressure
Glass
Relief valve(s) supplied Transducer
with 50 Hz EU CE units rated
maximum 480 PSIG (33 Bar).

To
Liebert
iCOM
Control
To Second
Refrigeration
Circuit
*

FACTORY PIPING
FIELD PIPING
OPTIONAL FACTORY PIPING
SERVICE / SCHRADER (ACCESS) CONNECTION NO VALVE CORE
SERVICE / SCHRADER (ACCESS) CONNECTION WITH VALVE CORE
NOTE: Two refrigeration circuits provided. Single refrigeration circuit shown for clarity
Schematic representation shown. This schematic does not imply or define elevations and
component location, unless specifically noted.

Liebert DS

114

Components are not supplied by


Emerson, but are required for
proper circuit operation and
maintenance
** Field-installed at highest point in
system on return line to pumps
*** Locate at tops of all risers and
any intermediate system high points

DPN001430
Rev. 1

Piping

Piping schematicGLYCOOL semi-hermetic compressor models

Figure 94

LIEBERT
HEAT REJECTION

Optional Dual Pump System shown

EXPANSION
TANK**

GLYCOL
PUMPS
Check Valves*
(on Dual Pump
Systems only)

Pressure
Port*

DRYCOOLER
(Glycol)

Gate Valves*

Aquastat
Sensing
Bulbs
Hose
Bib* Shutoff Valve*

Air Vents
(typical)***

Pressure Port*
Flow Switch
Supplied with Dual
Pump Systems
Flow-Regulating
Valve*

Shutoff Valve*

RETURN

LIEBERT DS
(and associated piping)

SUPPLY

Shutoff Valve*

Sensing Bulb
Cylinder
Unloader(s)

RETURN

ECON-O-COIL

LIQUID

Service
Valve

SUPPLY

EVAPORATOR
COIL

3-Way
Chilled Glycol
Valve

Thermistor

Shutoff Valve*

Hose
Bib*

Hose
Bib*

SUCTION
External
Equalizer

Muffler

COMPRESSOR
Service
Valve

Check Valve

DISCHARGE

Service
Valve

PARADENSER
CONDENSER
Expansion Solenoid Sight
Valve
Glass
Valve

Filter
Dryer
Relief valve(s) supplied
with 50Hz EU CE units rated
maximum 480 PSIG (33 Bar).

3-Way
Regulating
Valve

Sensor
To Second
Refrigeration
Circuit

Factory Piping
Field Piping
Service/Schrader (Access) Connection No Valve Core
Service/Schrader (Access) Connections With Valve Core
Notes: Schematic representation shown. This schematic does not imply or define elevations and
component location unless specifically noted.
Two refrigeration circuits provided. Single refrigeration circuit shown for clarity.

115

* Components are not supplied by


Emeron but are required for
proper circuit operation and
maintenance
** Field-installed at highest point in
system on return line to pumps
*** Locate at tops of all risers and
any intermediate system high points

DPN000897
Rev. 4

Liebert DS

Piping

Piping schematicGLYCOOL with scroll compressor models

Figure 95

EXPANSION
TANK**

LIEBERT
HEAT REJECTION
DRYCOOLER
(Glycol)

Optional Dual Pump System shown


GLYCOL PUMPS
Check Valves*
(on Dual Pump
Systems only)

Pressure
Port*

Aquastat
Sensing
Bulbs
Hose
Bib*

Shutoff Valve*

Gate Valves*

Air Vents
(typical)***

Pressure Port*
Flow Switch
Supplied with Dual
Pump Systems

Flow-Regulating
Valve*

Shutoff Valve*

RETURN

LIEBERT DS UNIT
(and associated piping)

ECON-O-COIL

RETURN

LIQUID
Sensing Bulb
Service
Valve

SUCTION

EVAPORATOR
COIL

3-Way
Chilled Glycol
Valve
Thermistor

SUPPLY

SUPPLY
Shutoff Valve*

Shutoff Valve*
Hose
Bib*

Hose
Bib*

Check
Valve

Service
Valve External
Equalizer
COMPRESSOR

DISCHARGE
Paradenser
Condenser
Expansion Solenoid Sight
Valve
Valve
Glass

3-Way
Regulating
Valve

Filter Dryer
Relief valve(s) supplied
with 50 Hz EU CE units rated To Second
maximum 480 PSIG (33 Bar). Refrigeration
Circuit

Sensor

FIELD PIPING
FACTORY PIPING
SERVICE / SCHRADER (ACCESS) CONNECTION NO VALVE CORE
SERVICE / SCHRADER (ACCESS) CONNECTION WITH VALVE CORE
NOTES: Two refrigeration circuits provided. Single refrigeration circuit shown for clarity.
Schematic representation shown. This schematic does not imply or define elevations and
component location, unless specifically noted.

* Components are not supplied


by Liebert but are required for
proper circuit operation and
maintenance
** Field installed at highest point in
system on return line to pumps
*** Locate at tops of all risers and
any intermediate system high points
DPN000898
Rev. 4

Liebert DS

116

Piping

Figure 96

Piping schematicGLYCOOL with digital scroll compressor models

LIEBERT
HEAT REJECTION

Optional Dual Pump System shown

EXPANSION
TANK**

GLYCOL
PUMPS
Check Valves*
(on Dual Pimp
Systems only)
Gate Valves*

Pressure
Port*

DRYCOOLER
(Glycol)
Aquastat
Sensing
Bulb
Hose
Bib*

Shutoff Valve*

Air Vents
(typical)***

Pressure Port*

Flow Switch
Supplied with Dual
Pump Systems
Flow-Regulating
Valve*

Shutoff Valve*

LIEBERT DS
(and associated piping)
LIQUID
28-42kW Digital Solenoid Valve
53-70kW Digital
Solenoid Valve

ECON-O-COIL

RETURN

SUPPLY

RETURN

SUPPLY

Shutoff Valve*

Sensing Bulb

EVAPORATOR
COIL

3-Way
Chilled Glycol
Valve
Thermistor

Hose
Bib*

Shutoff Valve*

Hose
Bib*

SUCTION

Service
Valve
Check
Valve COMPRESSOR

3-Way
Motorized
Ball Valve

External
Equalizer

DISCHARGE

From
Liebert
iCOM
Control

PARADENSER
CONDENSER
Expansion Solenoid Sight
Filter Drier
Valve
Valve
Pressure
Glass
Relief valve(s) supplied Transducer
with 50Hz EU CE units rated
maximum 480 PSIG (33 Bar).

To
Liebert
iCOM
Control

To Second
Refrigeration
Circuit

FACTORY PIPING
FIELD PIPING
SERVICE / SCHRADER (ACCESS) CONNECTION NO VALVE CORE
SERVICE / SCHRADER (ACCESS) CONNECTION WITH VALVE CORE
NOTE: Two refrigeration circuits provided. Single refrigeration circuit shown for clarity.
Schematic representation shown. This schematic does not imply or define elevations and
Component location, unless specifically noted.

117

Components are not supplied by


Emerson, but are required for
proper circuit operation and
maintenance
** Field installed at highest point in
system on return line to pumps
*** Locate at tops of all risers and
any intermediate system high points

DPN001432
Rev. 1

Liebert DS

Piping

Figure 97

Piping schematicOptional Econ-O-Coil


Return Supply

Return Supply
Thermistor*

Thermistor*
Actuator

Return

Return

Supply

Supply
Econ-O-Coil

Econ-O-Coil

Optional Econ-O-Coil (2-Way Valve)


Factory Piping
Field Piping

Actuator

Optional Econ-O-Coil (3-Way Valve)

*Supplied with 10 feet (3m) extra thermistor wire for installation


on field suppy line.

DPN000805
2

1. Place thermistor in location where flow is always present.


Rev.
2. Thermistor must be located out of the supply air stream.
3. On downflow units the sensor is coiled in the bottom of the
unit on the left side. On upflow units it is coiled on top of unit on the left side.

Liebert DS

118

Electrical Field Connections

11.0 ELECTRICAL FIELD CONNECTIONS


Figure 98

Electrical field connectionsUpflow and downflow models, single molded case switch
disconnect with main fuses
See 11.1 - Standard Electrical Field Connections, 11.2 Optional Electrical Connections, 11.2 - Optional Electrical
Connections and 11.3 - Optional Low-Voltage Terminal
Package Connections for keys to numbered components.

OVERCURRENT PROTECTION DEVICES

15

Liebert
IntelliSlot
Housing

Alternate
Location

P64

CONTACTORS

P67

60Hz

CONTACTORS, RELAYS, &


OVERLOAD PROTECTORS

13

17 18
82 83 88 89

24 23
58 59 84 85

Downflow

Typical orientation of components shown.


DOWNFLOW LOW-VOLTAGE SECTION
Component location varies by option and unit size.

16

22

19

NOTICE

75 76 94 95 96 97 91 92 93 80 81 11 12

21

10

20

37C38C 37B 38B 37 38 24 50 51 55 56 70 71 230 72 73

11

49-3

49-1

SH

Risk of broken or shorted low-voltage


wiring. Field-installed low-voltage wiring
must be routed with loop as shown
to allow electric box to swing.

UPFLOW
3

12

E
DPN000807
Pg. 3, Rev. 13

Item 12 Installation Conditions


Point of Hinged Low-Voltage
1. Follow all local installation codes.
Electric Box
2. Do not run CAN cables in same conduit, raceway, or
LIEBERT DS UPFLOW LOW-VOLT SECTION
chase as high voltage wires (120-600V).
3. Separate high volt wires from CAN wires by 12 inches.
4. For runs greater than 350ft(107m), contact Liebert factory.

119

Liebert DS

Electrical Field Connections

Figure 99

Electrical field connectionsUpflow and downflow models, dual-fused disconnect switches


See 11.1 - Standard Electrical Field Connections, 11.2 Optional Electrical Connections, 11.2 - Optional Electrical
Connections and 11.3 - Optional Low-Voltage Terminal
Package Connections for keys to numbered components.

OVERCURRENT PROTECTION DEVICES

15

14

60Hz

Liebert
IntelliSlot
Housing

Alternate
Alternate
Location
Location

15

P64

CONTACTORS
PRIMARY

P67

SECONDARY

13
CONTACTORS, RELAYS and
OVERLOAD PROTECTORS
E

1
17 18
82 83 88 89

Typical orientation of components shown.


Component location varies by option and unit size.

22

16

58 59 84 85

37C 38C 37B38B 37 38 24 50 51 55 56 70 71 230 72 73

NOTICE
Risk of broken or shorted low-voltage
wiring. Field-installed low-voltage wiring
must be routed with loop as shown
to allow electric box to swing.

20

10

11

49-3

49-1

SH

DOWNFLOW LOW VOLTAGE SECTION

UPFLOW
3

B
21

19

75 76 94 95 96 97 91 92 93 80 81 11 12

A
24 23

DOWNFLOW

12

Item 12 Installation Conditions


1. Follow all local installation codes.
2. Do not run CAN cables in same conduit, raceway or
chase as high-voltage wires (120-600V).
3. Separate high-voltage wires from CAN wires by 12 (305mm)
4. Contact factory for runs greater than 350ft. (107m).

Liebert DS

120

Point of Hinged Low-Voltage


Electric Box

DS UPFLOW LOW-VOLTAGE SECTION


DPN000807
Pg. 4, Rev. 13

Electrical Field Connections

11.1

Standard Electrical Field Connections


Source: DPN000807, Rev. 13
1. Primary high-voltage entrance2.50" (64mm); 1.75" (44mm); 1.375" (35mm) diameter
concentric knockouts in bottom of box.
2. Secondary high-voltage entrance2.50" (64mm); 1.75" (44mm); 1.375" (35mm) diameter
concentric knockouts in top of box.
3. Primary low-voltage entranceThree knockouts, each 1.375" (35mm) diameter in bottom of
unit.
4. Secondary low-voltage entranceThree knockouts, each 1.375" (35mm) diameter in top of
box.
5. Three-phase electrical serviceTerminals are on main fuse block (disregard if unit has
optional disconnect switch). Three-phase service not by Emerson.
6. Earth groundTerminal for field-supplied earth grounding wire. Earth grounding required for
Liebert units.
7. Remote unit shutdownReplace existing jumper between Terminals 37 and 38 with
field-supplied normally closed switch having a minimum 75VA, 24VAC rating. Use field-supplied
Class 1 wiring.
8. Customer alarm inputsTerminals for field-supplied, normally open contacts, having a
minimum 75VA, 24VAC rating, between Terminals 24 and 50, 51, 55, 56. Use field-supplied Class
1 wiring. Terminal availability varies by unit options.
9. Common alarmOn any alarm, normally open dry contact is closed across Terminals 75 and 76
for remote indication. 1A, 24VAC maximum load. Use field-supplied Class 1 wiring.
10. Heat rejection interlockOn any call for compressor operation, normally open dry contact is
closed across Terminals 70 and 71 (Circuit 1), 230 (Circuit 2) to heat rejection equipment. 1A,
24VAC maximum load. Use field-supplied Class 1 wiring. When Liebert DS is paired with a
Liebert MC series condenser, remove jumper between Terminal 71 and Terminal 230. Three
wires must connect Terminals 70, 71 and 230 of the indoor unit to Terminals 70, 71 and 230 of the
Liebert MC.

CANbus Electrical Connections


11. CANbus Connector Terminal block with Terminals 49-1 (CAN-H) and 49-3 (CAN-L) + SH
(shield connection). The terminals are used to connect the CANbus communication cable
(provided by others) from the indoor unit to the Liebert MC - Premium Model and optional Liebert
PRE.
12. CANbus CableCANbus cable provided by others to connect to the outdoor condenser and
optional Liebert PRE. No special considerations are required when the total external cable
connection between the indoor unit and outdoor unit(s) is less than 450 ft. (137m). A CANbus
isolator is required for total external cable connections greater than 450 ft. (137m) but less than
800 ft. (243m). Cable must meet the following specifications:
Conductors 22-18AWG stranded tinned copper
Twisted pair (minimum 4 twists per foot)
Braided shield or foil shield with drain wire
Low Capacitance (15pF/FT or less)
UL approved temperature rated to 75C
UL approved-voltage rated to 300V
UV-resistant and moisture-resistant if not run in conduit
Plenum-rated NEC type CMP, if required by national or local codes
Examples: Belden 89207 (plenum-rated), or Alpha Wire 6454 Category 5, 5e, or higher

121

Liebert DS

Electrical Field Connections

11.2

Optional Electrical Connections


Source: DPN000807, Rev. 13
13. Unit factory-installed disconnect switch, fuse block and main fusesTwo types of
disconnect switches are available: Non-Locking and Locking. The Non-Locking switch consists of
a non-automatic molded case switch operational from the outside of the unit. Access to the
high-voltage electric panel compartment can be obtained with the switch in either the On or Off
position. The Locking switch is identical except access to the high-voltage electric panel
compartment can be obtained only with the switch in the Off position. Units with fused
disconnects are provided with a defeater button that allows access to the electrical panel when
power is On. The molded case switch disconnect models contain separate main fuses. Units with
fused disconnects have main fuses within disconnect. Only fused disconnects are used on dual
disconnect options.
14. Secondary disconnect switch and earth ground
15. Three-phase electrical serviceTerminals are on top of disconnect switch. Three-phase
service not by Emerson.
16. Smoke sensor alarmFactory-wired dry contacts from smoke sensor are 91-common, 92-NO
and 93-NC. Supervised contacts, 80 and 81, open on sensor trouble indication. This smoke sensor
is not intended to function as, or replace, any room smoke detection system that may be required
by local or national codes. 1A, 24VAC maximum load. Use field-supplied Class 1 wiring.
17. Reheat and humidifier lockoutRemote 24VAC required at Terminals 82 and 83 for lockout
of reheat and humidifier.
18. Condensate alarm (with condensate pump option)On pump high water indication,
normally open dry contact is closed across Terminals 88 and 89 for remote indication. 1A, 24VAC
maximum load. Use field-supplied Class 1 wiring.
19. Remote humidifierOn any call for humidification, normally open dry contact is closed across
Terminals 11 and 12 to signal field-supplied remote humidifier. 1A, 24VAC maximum load. Use
field-supplied Class 1 wiring.
20. Auxiliary cool contactOn any call for Liebert Econ-O-Coil operation, normally open dry
contact is closed across Terminals 72 and 73 on dual cool units only. 1A, 24VAC maximum load.
Use field-supplied Class 1 wiring.

11.3

Optional Low-Voltage Terminal Package Connections


21. Remote unit shutdownTwo additional contact pairs available for unit shutdown (labeled as
37B and 38B, 37C and 38C). Replace jumpers with field-supplied normally closed switch having a
minimum 75VA, 24VAC rating. Use field-supplied Class 1 wiring.
22. Common alarmOn any alarm, two additional normally open dry contacts are closed across
Terminals 94 and 95 and 96 and 97 for remote indication. 1A, 24VAC maximum load. Use
field-supplied Class 1 wiring.
23. Main fan auxiliary switchOn closure of main fan contactor, normally open dry contact is
closed across Terminals 84 and 85 for remote indication. 1A, 24VAC maximum load. Use
field-supplied Class 1 wiring.
24. Liebert Liqui-tect shutdown and dry contactOn Liebert Liqui-tect activation, normally
open dry contact is closed across Terminals 58 and 59 for remote indication (Liebert Liqui-tect
sensor ordered separately). 1A, 24VAC maximum load. Use field-supplied Class 1 wiring.
Refer to specification sheet for total unit full load amps, wire size amps and maximum
overcurrent protective device size.

Liebert DS

122

Heat RejectionLiebert MC

12.0 HEAT REJECTIONLIEBERT MC


12.1

Liebert MC Selections

Table 23

75F/45RH return air conditions for traditional rooms


Outdoor Design Ambient Temperature

Model #

95F (35C)

100F (38C)

105F (41C)

110F (43C)

115F (46C)

120F (49C)

DS/VS028A

MCM056_8

MCM056_8

MCM080_8

MCL110_8

MCL110_8

MCL110_8

DS/VS035A

MCM056_8

MCM080_8

MCM080_8

MCL110_8

MCL110_8

MCL110_8

DS/VS042A

MCM056_8

MCM080_8

MCL110_8

MCL110_8

MCL110_8

MCL110_8

DS/VS053A

MCM056_8

MCM080_8

MCL110_8

MCM160_8

MCM160_8

MCL220_8

DS/VS070A

MCM080_8

MCL110_8

MCL110_8

MCM160_8

MCM160_8

MCL220_8

DS/VS077A

MCM080_8

MCL110_8

MCL110_8

MCM160_8

MCM160_8

MCL220_8

DS/VS105A

MCL110_8

MCM160_8

MCM160_8

MCL220_8

MCL220_8

MCL220_8

Table 24

85F/33RH return air conditions for Hot Aisle/Cold Aisle applications


Outdoor Design Ambient Temperature

Model #

95F (35C)

100F (38C)

105F (41C)

110F (43C)

115F (46C)

120F (49C)

DS/VS028A

MCM056_8

MCM080_8

MCL110_8

MCL110_8

MCL110_8

MCM160_8

DS/VS035A

MCM056_8

MCM080_8

MCL110_8

MCL110_8

MCM160_8

MCM160_8

DS/VS042A

MCM080_8

MCL110_8

MCL110_8

MCM160_8

MCM160_8

MCM160_8

DS/VS053A

MCL110_8

MCL110_8

MCM160_8

MCL220_8

MCL220_8

MCL220_8

DS/VS070A

MCL110_8

MCM160_8

MCM160_8

MCL220_8

MCL220_8

MCL220_8

DS/VS077A

MCL110_8

MCM160_8

MCM160_8

MCL220_8

MCL220_8

MCL220_8

DS/VS105A

MCM160_8

MCL220_8

MCL220_8

MCL220_8

MCL220_8

Table 25

T75F/45RH return air conditions Liebert QuietLine for lower sound levels
Outdoor Design Ambient Temperature

Liebert DS
Model #

95F (35C)

100F (38C)

105F (41C)

110F (43C)

115F (46C)

DS/VS028A

MCM080E8

MCM080E8

MCL110E8

MCL110E8

MCL110E8

DS/VS035A

MCM080E8

MCL110E8

MCL110E8

MCM160E8

MCM160E8

DS/VS042A

MCM080E8

MCL110E8

MCL110E8

MCM160E8

MCM160E8

DS/VS053A

MCL110E8

MCL110E8

MCM160E8

MCL220E8

MCL220E8

DS/VS070A

MCL110E8

MCM160E8

MCL220E8

MCL220E8

MCL220E8

DS/VS077A

MCL110E8

MCM160E8

MCL220E8

MCL220E8

MCL220E8

DS/VS105A

MCM160E8

MCL220E8

Consult Factory

123

Liebert DS

Heat RejectionLiebert MC

12.2

Liebert MCDry Weight and Additional Weight of Options


Total unit weight is the sum of the condenser weight with the selected legs plus the weight of any
option.
Source: DPN003034, Rev. 1

Table 26

Condenser and option net weightsSmall condensers


Condenser Model
Refrigeration Circuits

Condenser Dry
Weight, lb (kg)

MCS056
2

18" Leg

270 (122)

36" Leg

419 (190)

48" Leg

451 (205)

60" Leg

482 (219)

Additional Weight for Options, lb (kg)


Liebert Lee-Temp
Coated Coil
575 Transformer

Table 27

110 (50)
8 (4)
63 (29)

Condenser and option net weightsMedium condensers


Condenser Model

MCM080

MCM160

18" Leg

441 (200)

860 (390)

36" Leg

590 (268)

1066 (484)

48" Leg

622 (282)

1114 (505)

60" Leg

653 (296)

1160 (526)

110 (50)

220 (100)

Coated Coil

10 (5)

20 (9)

575 Transformer

63 (29)

76 (34)

Refrigeration Circuits

Condenser Dry
Weight, lb (kg)

Additional Weight for Options, lb (kg)


Liebert Lee-Temp

Table 28

Condenser and option net weightsLarge condensers


Condenser Model

MCL110

MCL220

18" Leg

602 (273)

1186 (538)

36" Leg

766 (347)

1453 (659)

48" Leg

798 (362)

1501 (681)

60" Leg

829 (376)

1547 (702)

120 (54)

240 (109)

16 (7)

32 (15)

90 (41)

134 (61)

Refrigeration Circuits

Condenser Dry
Weight, lb (kg)

Additional Weight for Options, lb (kg)


Liebert Lee-Temp
Coated Coil

Liebert DS

124

Heat RejectionLiebert MC

12.3

Sound Power Data

Table 29

Liebert MC sound power data


100% Speed - A-Weighted Sound Power, dBA
Frequency - Hz

Liebert MC
Model #

63

125

250

500

1000

2000

4000

8000

Total

MCS056

53

73

69

73

76

74

67

61

81

MCM80

52

70

76

79

81

79

72

65

85

MCM160

55

73

79

82

84

82

75

68

89

MCL110

65

74

78

83

85

83

76

69

89

MCL220

68

77

81

86

88

86

79

72

92

12.4

Electrical DataLiebert MC

Table 30

Liebert MC electrical data, three-phase, 60Hz condenser, Premium Version (EC control)
Power Requirements
FLA

WSA

Model #

Number
of Fans

208/230V

460V

575V

208/230V

460V

OPD
575V

208/230V

460V

575V

MCS056

6.0

2.8

2.3

6.8

3.3

2.8

15

15

15

MCM080

4.6

2.8

2.3

5.5

3.3

2.8

15

15

15

MCM160

9.2

5.6

4.7

9.8

6.0

5.0

15

15

15

MCL110

11.4

5.6

4.7

12.8

6.3

5.3

15

15

15

MCL220

22.8

11.2

9.3

24.2

11.9

9.9

25

15

15

1.
2.

FLA = Full Load Amps; WSA = Wire Size Amps; OPD = Maximum Overcurrent Protection Device.
208V460V premium models must be connected to Wye 3-phase systems.

125

Liebert DS

Heat RejectionLiebert MC

12.5

Liebert MC Dimensions

Figure 100 Condenser planning dimensionsMCM080, MCL110 with/without Liebert Lee-Temp


575V
Option

575V
Option

G
A*

H
Top of
Fan Guard

Liebert Lee-Temp
Entering Hot Gas
and Leaving
Liquid Piping

C
D

Anchor
Plan

Main
Electric
Box
End

Full height leg


supplied for each
Liebert Lee-Temp
Receiver Required

Left Side of Unit

Emerson recommends a clearance of


36" (915mm) on each side for proper
operation and component access.

1/2" x 1"
(13mm x 25mm)
Obround Typical

DETAIL A
Typical of all Legs

MCS056
MCM080
MCL110

FRONT VIEW
(Liebert Lee-Temp Shown)

1-7/8" (48mm)
Typical

7"
(178mm)
Typical

Liebert
Model No.

6-1/2"
(165mm) Ref
6-1/2"
Dual Circuit Only
(165mm) Ref
15-1/4"
15-1/4"
K
(387mm)
(387mm)
Dual Circuit Only

J
Liebert Lee-Temp Only

3-5/8"
(93mm)
Typical

13/16"
(21mm)
Typical

M L K

DPN003437
Rev. 1

A
in. (mm)

A*
(575V Only)
in. (mm)

C
in. (mm)

D
in. (mm)

J
Liebert Lee-Temp
Only

K
in. (mm)

L
in. (mm)

M
in. (mm)

94-7/8
(2411)
105-1/4
(2674)
124-1/8
(3152)

103-1/8
(2619)
113-7/16
(2882)
133-1/8
(3381)

88-3/8
(2245)
96-1/16
(2440)
112-1/8
(2848)

86-3/4
(2203)
94-7/16
(2398)
110-1/2
(2806)

42-1/2
(1079)
46-5/16
(1177)
54-3/8
(1381)

42-1/2
(1080)
46
(1168)
55-1/2
(1410)

40-7/8
(1038)
44-3/8
(1127)
53-7/8
(1368)

35-7/8
(910)
39-5/16
(999)
48-3/4
(1238)

Source: DPN003437, Rev. 1

Liebert Model No.


MCS 056
Dimension G, in. (mm)
Dimension H, in. (mm)
MCM080
Dimension G, in. (mm)
Dimension H, in. (mm)
MCL110
Dimension G, in. (mm)
Dimension H, in. (mm)

F 1 (Leg Height Dimensions) , in. (mm)


18 (457)
31-5/8 (803)
39-5/8 (1006)
18 (457)
31-5/8 (803)
39-5/8 (1006)

36 (914)
49-5/8 (1260)
57-5/8 (1464)
36 (914)
49-5/8 (1260)
57-5/8 (1464)

48 (1219)
61-5/8 (1565)
69-5/8 (1768)
48 (1219)
61-5/8 (1565)
69-5/8 (1768)

60 (1524)
73-5/8 (1870)
81-5/8 (2073)
60 (1524)
73-5/8 (1870)
81-5/8 (2073)

35-7/8 (911)
43-5/8 (1108)

53-7/8 (1368)
61-5/8 (1565)

65-7/8 (1673)
73-5/8 (1870)

77-7/8 (1978)
85-5/8 (2175)

1. Cross-bracing required for legs longer than 18". Number of legs varies per model and options.
2. Source: DPN003437, Rev. 1

Liebert DS

126

Heat RejectionLiebert MC

Figure 101 Condenser planning dimensionsMCM160, MCL220 with/without Liebert Lee-Temp


575V
Option

575V
Option

Lifting Eyebolts
Typ. (4) Places

A*
A

H
Top of
Fan Guard

Liebert Lee-Temp
Receiver
Entering Hot Gas
and Leaving
Liquid Piping

C
E

54-3/16
(1376mm)
Typical

A
Full height leg
supplied for each
Liebert Lee-Temp
Receiver Required

Anchor
Plan

Main
Electric
Box
End

M L K
6-1/2"
(165mm) Ref

13/16"
(21mm)
Typical

Left Side of Unit

3-5/8"
(93mm)
Typical

15-1/4"
(387mm)

FRONT VIEW

Emerson recommends a clearance of


36" (915mm) on each side for proper
operation and component access.

7"
(178mm)
Typical

6-1/2"
(165mm) Ref.
Dual Circuit Only

15-1/4"
(387mm)

Liebert Lee-Temp
Only

(Liebert Lee-Temp Shown)

1-7/8"
(48mm)
Typical
1/2" x 1"
(13mm x 25mm)
Obround Typical

DETAIL A
Typical of all Legs

DPN003439
Rev. 1

Liebert
Model No.

A
in. (mm)

A*
(575V Only)
in. (mm)

B
in. (mm)

C
D
E
in. (mm) in. (mm) in. (mm)

J
Liebert Lee-Temp
Receivers Only

MCM160

202-7/16
(5142)

210-5/8
(5350)

113-1/2
(2883)

192-1/4 94-7/16 96-3/16


(4883) (2398) (2444)

46-5/16
(1177)

46
(1168)

44-3/8
(1127)

39-5/16
(999)

MCL220

236-5/16
(6003)

245-5/16
(6231)

129-9/16 224-3/8 110-1/2 112-1/4


(3291)
(5699) (2806) (2851)

54-3/8
(1381)

55-1/2
(1410)

53-7/8
(1368)

48-3/4
(1238)

K
L
M
in. (mm) in. (mm) in. (mm)

Source: DPN003439, Rev. 1

F 1 (Leg Height Dimensions) , in. (mm)

Liebert Model No.


MCM160

18 (457)

36 (914)

48 (1219)

60 (1524)

Dimension G, in. (mm)

31-5/8 (803)

49-5/8 (1260)

61-5/8 (1565)

73-5/8 (1870)

Dimension H, in. (mm)

39-5/8 (1006

57-5/8 (1464)

69-5/8 1768)

81-5/8 (2073)

Dimension G, in. (mm)

35-7/8 (911)

53-7/8 (1368)

65-7/8 (1673)

77-7/8 (1978)

Dimension H, in. (mm)

43-5/8 (1108)

61-5/8 (1565)

73-5/8 (1870)

85-5/8 (2175)

MCL220

1. Cross-bracing required for legs longer than 18". Number of legs varies per model and options.
2. Source: DPN003439, Rev. 1

127

Liebert DS

Heat RejectionLiebert MC

12.6

Piping Connections

Figure 102 Piping connectionsLiebert MC

dual-circuit, two-fan and four-fan units

* Cover
Vertical

Inverted traps
are factory provided
inside condenser
Leaving Liquid
Line

Field Piping

Horizontal

Entering Hot
Gas Line

DETAIL A
Circuit #1

Circuit #2

Optional fusible plug service kit to


be brazed into the liquid line(s) in
either the vertical or horizontal
position (where required).
(Vertical position is suggested,
horizontal position is optional.)
For two circuit systems, one
fusible plug kit must be
installed in each circuit.

Table 31

DPN002425
Rev. 5

* Shipping cover is not necessary


for proper condenser operation and
may be recycled if field piping
interferes with proper reattachment.

Liebert MC piping connection sizesLiebert MC dual-circuit, two-fan and four-fan units


Connection Sizes, OD, in

Model #

# of
Fans

Hot Gas Line

Liquid Line

MCS056

7/8

5/8

MCM080

7/8

5/8

MCL110

1-1/8

7/8

MCM160

1-1/8

7/8

MCL220

1-3/8

1-1/8

Source: DPN002425, Rev. 5

Liebert DS

128

Heat RejectionLiebert MC

Figure 103 Piping dimensionsLiebert MC dual-circuit condensers with Liebert Lee-Temp


Hot Gas Line
To Condenser
Entering Hot
Gas Line

C View

B View
* Cover
* Shipping cover is not necessary for proper
condenser operation and may be recycled if field
piping interferes with proper reattachment
Position elbow to
direct relief valve
downward
Leaving
Liquid Line

B View

Liquid Line
From Condenser

Fasten hot gas line to cabinet


using flat surface clamps with
isolators (field-supplied)
See Detail A A
Metal Clamp

Hot Gas Line


To Condenser

Isolator
Detail AA

GENERAL ARRANGEMENT

Liebert-supplied piping assembly


will include one or two valve and check
valves, depending on condenser
capacity and refrigerant
Field Piping

Entering Hot
Gas Line

Liquid Line
From Condenser
Leaving
Liquid Line

Position elbow to
direct relief valve
downward

C View

Note:
1. The following materials are supplied by Emerson for each circuit (shipped loose with condenser)
for field installation: insulated Liebert Lee-Temp receiver tank with sight glasses, piping assembly
with head pressure control valve, check valve, rotalock valve and pressure relief valve. All other piping
and electrical wiring to be supplied and installed by others. An additional condenser leg per circuit
to be shipped with the condenser.
2. Consult factory for proper line sizing for runs longer than 150ft. (45.7m) equivalent length.

Table 32

DPN002426
Rev. 6

Piping dimensionsLiebert MC dual-circuit condensers with Liebert Lee-Temp


Condenser Connections
ODS, in.

Liebert Lee-Temp Connections


Liquid Line
to Liebert Lee-Temp
Valve ODS, In.

Receiver Out
Rotalock
IDS, in.

Model #

Circuit No.

Hot Gas

Liquid

Hot Gas Tee


IDS, in.

MCS056

7/8

5/8

7/8

5/8

5/8

MCM080

7/8

5/8

7/8

5/8

5/8

MCL110

1-1/8

7/8

1-1/8

7/8

7/8

MCM160

1-1/8

7/8

1-1/8

7/8

1-1/8

MCL220

1-3/8

1-1/8

1-3/8

1-1/8

1-1/8

Source: DPN002426, Rev. 6

129

Liebert DS

Heat RejectionLiebert MC

12.7

Electrical Field ConnectionsLiebert MC

Figure 104 Electrical field connectionsLiebert MC premium efficiency control, with and without Liebert

Lee-Temp
Fan 2

Fan 2
Liebert Lee-Temp receiver tank 1 per circuit).
NOTE: Heater pad voltage available for
120V/1ph/60Hz or 230V/1ph/60Hz
150 or 300 watt, varies by condenser.

Fan 1

Fan 1

Electrical connection
box; cover removed
for clarity

Without Liebert
Lee-Temp
Electrical service connection.

With Liebert
Lee-Temp

Pigtails in electric handy box


are factory-wired to Liebert Lee-Temp
heater pads for field-connection
of separate continuous electric
source; wire not by Emerson.

1
+

5A
5B
+

ALARM RELAY CARD


XX
XX

xxxxxxx
xxxxxxx
xxxxxxxxxxxxxx
xxxxxxx
xxxxxxx
xxxxxxxxxxxxxx
xxxxxxx
xxxxxxx
xxxxxxx
xxxxxxx
xxxxxxx
xxxxxxx
xxxxxxx
xxxxxxx
xxxxxxx
xxxxxxx
xxxxxxx
xxxxxxx
xxxxxxx

5C

xxxxxxx
xxxxxxx
xxxxxxx
xxxxxxx
xxxxxxx
xxxxxxx

xxxxxxxxxxxxxxxxxxxxxx
xxxxxxxxxxxxxxxxxxxxxx

8
12
13

Item appears only with


Liebert Lee-Temp board

Liebert DS

11
Left Knockout

3
Right Two
Knockouts

See on page 131 for key to numbered


components

70
71
230

NOTICE!
THIS HOLE FOR FIELD
SUPPLIED EXTRA LOW
VOLTAGE CONTROL WIRING

xxxxxxx
xxxxxxx
xxxxxxx
xxxxxxx

10

DPN002169
Pg. 1, Rev. 7

DPN002374
Pg. 1, Rev. 6

130

Heat RejectionLiebert MC

Key Electrical Details; Source: DPN002169, Rev. 7 and DPN002374 Rev. 6


1. Three-phase electrical serviceTerminals are on top of disconnect switch for one-fan and
two-fan units. Terminals are on bottom of disconnect switch for three-fan and four-fan units.
Three-phase service not by Emerson. See Note 5.
2. Earth groundField lug terminal for earth ground connection. Ground terminal strip for fan
motor ground connection.
3. Primary high-voltage entranceTwo knockouts, each 7/8" (22.2mm) diameter, at the bottom
of the enclosure.
4. SPD field connection terminalsHigh-voltage surge protection device (SPD) terminals. SPD
is an optional device.
5. CANbus terminal connectionsField terminals for CANbus cable connection.
5A is the CANbus connectors
TB49-1 is the input terminal for CANbus high
TB49-3 is the input terminal for CANbus low
TB50-1 is output terminal for CANbus high
TB50-3 is the output terminal for CANbus low
Each CANbus cable shield is connected to terminal SH, Item 9.
5B is the End of Line jumper.
5C is the CANbus Device Address DIP Switch. CANbus cable not by Emerson. See Note 2.
6. Remote unit shutdownReplace exiting jumper between terminals TB38-1 and TB38-2 with
field-supplied normally closed switch having a minimum 75VA 24VAC rating. Use field-supplied
Class 1 wiring. (This is an optional feature that may be owner specified.)
7. Alarm terminal connections
a. Common Alarm Relay indicates when any type of alarm occurs. TB74-1 is common; TB74-2 is
normally open; and TB74-3 is normally closed. 1 Amp 24VAC is the maximum load. Use
field-supplied Class 1 wiring.
b. Shutdown Alarm Relay indicates when condenser loses power or when a critical alarm has
occurred that shuts down the condenser unit. TB74-4 is common; TB74-5 is normally open;
and TB74-6 is normally closed. 1A 24VAC is the maximum load. Use field-supplied Class 1
wiring.
8. Indoor unit interlock and SPD alarm terminals
a. On any call for compressor operation, normally open contact is closed across Terminals 70 and
71 for Circuit 1, and normally open contact is closed across Terminals 70 and 230 for Circuit 2
from indoor room unit.
b. During SPD alarm, normally open contact is closed across Terminals 12 and13. SPD is an
optional device.
9. CANbus shield terminalTerminal for field connection of the field-supplied CANbus cables.
Shield of field-supplied CANbus cables must not be connected to ground at the condenser.
10. Primary low-voltage entranceOne knockout, 7/8" (22.2mm) diameter, that is free for
customer low-voltage wiring.
11. SPD entranceOne knockout, 7/8" (22.2mm) diameter, at the bottom of the enclosure.
High-voltage surge protective device (SPD) is optional.

131

Liebert DS

Heat RejectionLiebert MC

Notes
1. Refer to specification sheet for unit voltage rating, full load amp, and wire size amp ratings.
2. The CANbus wiring is field supplied and must be:
Conductors 22-18AWG stranded tinned copper
Twisted pair (minimum 4 twists per foot)
Braided shield or foil shield with drain wire
Shield must be wired to ground at indoor unit
Low Capacitance (15pf/ft or less)
UL approved temperature rated to 75C
UL approved voltage rated to 300V
UV-resistant and moisture-resistant if not run in conduit
Examples: Belden part number 89207(plenum rated) or Alpha Wire part number 6454 (UV
resistant outdoor rated) Category 5, 5e or higher. Do not run the CANbus cable in the same
conduit, raceway or chase as high-voltage.
3. Do not run the CANbus cable in the same conduit, raceway or chase as high-voltage.
4. No special considerations are required when the total external cable connection between the
indoor unit and outdoor unit(s) is less than 450ft. (137m). For total external cable connections
greater than 450ft. (137m) but less than 800ft. (243m), a CANbus isolator is required.
5. All wiring must be sized and selected for insulation case per NEC and other local codes.
6. Do not bend cables to less than four times the diameter of the cable.
7. Do not deform cables when securing in bundles or when hanging them.
8. Avoid running the cables by devices that may introduce noise, such as machines, fluorescent
lights and electronics.
9. Avoid stretching cables.
10. Separate high volt wires and other high-voltage sources from CAN wires by 12 inches.
11. The electrically commutated (EC) motors included in the Liebert MC Condenser are suitable for
connection to power supplies with a solidly grounded neutral. (Some platforms can accept power
supplies listed under Item b below. Contact the factory for more information.)
a. Acceptable power supplies for 208 to 575V nominal units
208V wye with solidly grounded neutral and 120V line to ground;
380V wye with solidly grounded neutral and 220V line to ground;
480V wye with solidly grounded neutral and 277V line to ground.
575V wye with solidly grounded neutral and 332V line to ground. (uses step-down
transformer)
b. Non-acceptable power supplies for 208V to 575V nominal units
wye with high resistance (or impedance) ground;
delta without ground or with floating ground;
delta with corner ground; or
delta with grounded center tap.

Liebert DS

132

Heat RejectionLiebert Fin/Tube Condensers

13.0 HEAT REJECTIONLIEBERT FIN/TUBE CONDENSERS


Table 33

Liebert DS air-cooled condenser selection, finned-tubular design, R-407C


Ambient Temperature, F (C)
Outdoor Condenser

Outdoor Quiet-Line Condenser

Liebert DS
Model

95 (35)

100 (38)

105 (41)

95 (35)

100 (38)

105 (41)

028

TCDV/CD*-205

TCDV/CD*-205

TCDV/CD*-251

TCDV/CD*-214

TCDV/CD*-214

TCDV/CD*-286

035

TCDV/CD*-205

TCDV/CD*-205

TCDV/CD*-251

TCDV/CD*-214

TCDV/CD*-214

TCDV/CD*-286

042

TCDV/CD*-205

TCDV/CD*-251

TCDV/CD*-308

TCDV/CD*-286

TCDV/CD*-286

TCDV/CD*-409

053

TCDV/CD*-251

TCDV/CD*-308

TCDV/CD*-415

TCDV/CD*-286

TCDV/CD*-409

TCDV/CD*-409

070

TCDV/CD*-308

TCDV/CD*-415

TCDV/CD*-415

TCDV/CD*-409

TCDV/CD*-572

TCDV/CD*-572

077

TCDV/CD*-308

TCDV/CD*-415

TCDV/CD*-616

TCDV/CD*-409

TCDV/CD*-572

TCDV/CD*-572

105

TCDV/CD*-415

TCDV/CD*-616

TCDV/CD*-616

TCDV/CD*-572

N/A

N/A

Table 34

Fin/tube condenser physical data and R-407C refrigerant required per condenser circuit
Connection Size,
OD, In.

Table 35
Model #

Liquid

Net Weight
lb (kg)

FSC or VFD

Liebert Lee-Temp
(includes receiver)

1-1/8
1-1/8
1-3/8
1-3/8
1-5/8

7/8
7/8
1-1/8
1-1/8
1-1/8

495 (225)
500 (227)
670 (304)
840 (381)
1380 (626)

7 (3.2)
10 (4.6)
11 (5.0)
24 (10.9)
26 (11.8)

54 (24.4)
36 (16.3)
55 (24.9)
102 (46.2)
108 (49.0)

1-1/8
1-1/8
1-5/8
2-1/8

7/8
7/8
1-1/8
1-1/8

840 (381)
1105 (501)
1380 (626)
2430 (1102)

N/A
N/A
N/A
N/A

77 (34.9)
119 (54.0)
148 (67.2)
186 (84.4)

Number
of Fans

Number
of Circuits

Hot Gas

2
3
3
4
6

2
2
2
2
2

3
4
6
8

2
2
2
2

Model #
Standard Models
TCDV/CD*205
TCDV/CD*251
TCDV/CD*308
TCDV/CD*415
TCDV/CD*616
Quiet-Line Models
TCDV/DCD*214
TCDV/DCD*286
TCDV/DCD*409
TCDV/DCD*572

Dual-Circuit
lb/circuit (kg/circuit)

DS fin/tube condenser cfm and sound data


Number
of Fans

Horsepower

CFM

Sound Power
LwA

Sound Pressure
dBA 3

Standard Models
205

3/4

10300

91.0

75.5

251

3/4

17950

94.0

77.3

308

3/4

16650

93.8

77.3

415

3/4

20650

94.4

78.5

616

3/4

33300

96.8

80.3

1/4

6400

74.8

61.3

Quiet-Line Models
214

286

1/4

8275

76.2

62.5

409

1/4

13750

78.4

64.3

572

1/4

17050

79.9

65.5

133

Liebert DS

Heat RejectionLiebert Fin/Tube Condensers

13.1

Dimensions

Figure 105 Fin/tube condenser dimensions, 2-fan model

43-9/16"
(1106mm)

Emerson recommends a
clearance of 36" (915mm) on
each side for proper operation
and component access.

91-1/2"
(2324mm)

37-7/8"
(962mm)

18"
(457mm)

84"
(2134mm)
43-3/16"
(1097mm)

Figure 106 Fin/tube condenser dimensions, 3-fan and 4-fan models


43-9/16"
(1106mm)

Emerson recommends a clearance of 36" (915mm)


on each side for proper operation and component
access.

131-1/2"
(3340mm)
37-7/8"
(962mm)

43-9/16"
(1106mm)
171-1/2"
(4356mm)

18"
(457mm)

124"
(3150mm)

70"
(1778mm)

37-7/8"
(962mm)

Eyebolts
for Lifting

43-3/16"
(1097mm)

18"
(457mm)

Note:
Overall height to the top of fan guard
43-1/8" (1095mm)

164"
(4166mm)
43-3/16"
(1097mm)

Liebert DS

134

Heat RejectionLiebert Fin/Tube Condensers

Figure 107 Fin/tube condenser dimensions, 6-fan and 8-fan models

131-1/2"
(3340mm)

87-1/8"
(2213mm)

Emerson recommends a clearance of 36" (915mm) on


each side for proper operation and component access.
87-1/8"
(2213mm)

171-1/2"
(4356mm)

37-7/8"
(962mm)

37-7/8"
(962mm)

59"
(1499mm)

18"
(457mm)

86-3/4"
(2203mm)

18"
(457mm)

124"
(3150mm)

Overalll height to the top


of the fan guard is 43-1/8 (1095mm).

70" (1778mm)
1-1/2" (38mm)
diameter hole for
rigging (typ.4)

164"
(4166mm)

86-3/4"
(2203mm)

135

Liebert DS

Heat RejectionLiebert Fin/Tube Condensers

13.2

Electrical Data

13.2.1 Electrical DataFin/Tube Condensers


Table 36

Fin/tube condenser data, 60Hz

Model #
Input
Voltage

ph

205

251, 308

415

616

2 Fans

3 Fans

4 Fans

6 Fans

FLA

WSA

OPD

FLA

WSA

OPD

FLA

WSA

OPD

FLA

WSA

OPD

8.3

9.5

15

11.8

13.0

15

15.3

16.5

20

23.6

24.8

30

4.2

4.8

15

5.9

6.5

15

7.6

8.2

15

11.8

12.4

15

3.3

3.8

15

4.7

5.2

15

6.1

6.6

15

9.4

9.9

15

7.2

8.1

15

10.7

11.6

15

14.2

15.1

20

N/A

N/A

N/A

3.5

4.0

15

5.2

5.7

15

6.9

7.4

15

N/A

N/A

N/A

Fan Speed Controlled


208/230
460

575
VFD Controlled
208/230
460

Lee-Temp Controlled/Fan-Cycling
208/230
460

575

7.0

7.9

15

10.5

11.4

15

14.0

14.9

20

21.0

21.9

25

3.4

3.8

15

5.1

5.5

15

6.8

7.2

15

10.2

10.6

15

2.8

3.2

15

4.2

4.6

15

5.6

6.0

15

8.4

8.8

15

FLA = Full Load Amps; WSA = Wire Size Amps; OPD = Maximum Overcurrent Protection Device

Table 37
Model #
Input
Voltage

Fin/tube condenser data, Liebert Quiet-Line


ph
ph

208/230
460

575

(Liebert Lee-Temp

286

409

572

3 Fans

4 Fans

6 Fans

8 Fans

FLA

WSA

OPD

FLA

WSA

OPD

FLA

WSA

OPD

FLA

WSA

OPD

5.4

5.9

15

7.2

7.7

15

10.8

11.3

15

14.4

14.9

20

2.7

2.9

15

3.6

3.8

15

5.4

5.6

15

7.2

7.4

15

2.1

2.3

15

2.8

3.0

15

4.2

4.4

15

5.6

5.8

15

Liebert Lee-Temp receiver electrical data, fin/tube condensers

Rated Voltage - Single Phase


Watts/Receiver

120
150

200/208/230
300

150

300

Full Load Amps

1.25

2.5

0.7

1.4

Wire Size Amps

1.56

3.1

0.9

1.8

15

15

15

15

Maximum Overcurrent
Protection Device, Amps

The Liebert Lee-Temp receiver requires a separate power feed for heaters. The
condenser is not designed to supply power to the receiver.

Liebert DS

controlled/fan-cycling), 60Hz

214

FLA = Full Load Amps; WSA = Wire Size Amps; OPD = Maximum Overcurrent Protection Device

Table 38

136

Heat RejectionLiebert Fin/Tube Condensers

13.2.2 Electrical Field ConnectionsLiebert Fin/Tube Condensers


Figure 108 Electrical field connections for Fan Speed Control fin/tube condensers

Electric service connection


and fuse block
Factory-wired to 24V
control circuit.
Heat Rjection
Connection 70, 71
Field-supplied
Class 2 wiring to
interlock condenser 24V
controls to Liebert indoor
unit (70, 71). Refer to the
condenser and indoor unit
electrical schematics for
termination. 7/8 in (22.2mm)
diameter hole provided in
bottom of electric box.

Electric Service Connection


terminals when factory
disconnect is NOT supplied
70

Electric Service Connection


terminals when factory
disconnect is supplied.

71

Factory-installed disconnect
switch (optional).

Factory-wired to components on
electric panel.
Electric Service Entrance.
A 7/8 in. (22.2mm) diameter hole in
a 1-1/18 in. (28.6mm) knockout
provided in bottom of electric box.

Earth Ground Bar (optional on 50Hz only).


Connection terminals with factory
ground from each high-voltage
component for field-supplied
earth grounding wire.
Earth ground connection (60Hz)
Connection terminal for fieldsupplied earth grounding wire
when factory disconnect is NOT
supplied.
Earth ground connection (60Hz)
Connection terminal for fieldsupplied earth grounding wire
when factory disconnect is supplied.

Refer to specification sheet for full load


amp and wire size amp ratings.

137

Electric Service, not by Emerson.


Single phase for condenser
models CSF, CDF with single
fan motor. Three phase for
all other condenser models.

DPN000666
Rev. 1

Liebert DS

Heat RejectionLiebert Fin/Tube Condensers

Figure 109 Electrical field connections for VFD control fin/tube condensers

Factory-wired to 24V
control circuit.
Heat Rjection
Connection 70, 71
Field-supplied
Class 1 wiring to
interlock condenser 24V
controls to Liebert indoor
unit (70, 71). Reference the
condenser and indoor unit
electrical schematics for
termination. 7/8" (22.2mm)
diameter hole provided in
bottom of electric box.

Factory installed fuse block on


60Hz units. Circuit breaker supplied
in lieu of fuse block on 50Hz units.
Electric Service Connection
terminals with factory
supplied disconnect.

70

71
11

12

13

14

V
F
D

SPD

Special Alarm Connections


Field- supplied 24V Class 1
wiring to remote alarm circuits
Surge Protection Device (SPD)
normally open alarm contact connections (11, 12).
Variable Frequency Drive (VFD)
normally closed alarm contact connections (13, 14).
Reference the indoor unit electric
diagram (RAD1-4) for termination.

Electric Service Entrance.


A 7/8" (22.2mm) diameter hole in
a 1-1/18" (28.6mm) knockout
provided in bottom of electric.

Factory-wired to components
on electric panel.
Earth Ground BAR (optional
on 50Hz only).
Connection terminals with factory
ground from each high-voltage
component for field-supplied
earth grounding wire.
Refer to specification sheet
for full load amp and wire size amp ratings
Earth Ground Connection (60Hz)
Connection terminal for fieldsupplied earth grounding wire
when factory disconnect is supplied.

Liebert DS

Factory-installed
disconnect switch

138

Electric service,
not by Emerson

DPN001051
Rev. 2

Heat RejectionLiebert Fin/Tube Condensers

Figure 110 Electrical field connections for Liebert Lee-Temp control fin/tube condensers

Liebert Lee-Temp receiver tank


(1 per circuit).
NOTE: Standard heater pads
are 150 Watts each. (Optional
300 Watts heater pads are
available.) Standard heater
pad voltage is 230V. (120V
heater pad voltage is optional.)
Electric connection box
with cover
Electrical service connection.
Pigtails in electric handy
box are factory-wired to
Liebert Lee-Temp
heater pads for field
connection of separate
continuous electric source,
wiring not by Emerson.

Electric service connection


and fuse block
Factory-wired to 24V
Class 2 control circuit.
Heat Rjection
Connection 70, 71
Field-supplied
Class 2 wiring to
interlock condenser 24V
controls to Liebert indoor
unit (70, 71). Refer to the
condenser and indoor unit
electrical schematics for
termination. 7/8 in (22.2mm)
diameter hole provided in
bottom of electric box.

70

Electric service connection


terminals when factory
disconnect is NOT supplied.

71

Electric service connection


terminals when factory
disconnect is supplied.

Factory-wired to components on
electric panel

Factory-installed disconnect
switch (optional).

Earth ground bar (optional on 50Hz only).


Connection terminals with factory
groubd from each high-voltage
component for field-supplied
earth grounding wire.

Electric Service Entrance.


A 7/8 in. (22.2mm) diameter hole in
a 1-1/18 in. (28.6mm) knockout
provided in bottom of electric box.

Earth ground connection (60Hz)


Connection terminal for fieldsupplied earth grounding wire
when factory disconnect is NOT
supplied.

Earth ground connection (60Hz)


Connection terminal for field-supplied
earth grounding wire when factory
disconnect is supplied

Refer to specification sheet for full


load amp and wire size amp ratings.

139

DPN000683
Rev. 1

Electric Service,
not by Emerson.

Liebert DS

Heat RejectionLiebert Fin/Tube Condensers

13.3

Piping Connections

Figure 111 VFD and Fan Speed Control condenser pipingFin/tube condensers

Optional fusible plug service kit to


be brazed into the liquid line(s) in
either the vertical or horizontal
position (where required).
(Vertical position is preferable,
horizontal position is optional.)
For two-circuit systems, one
fusible plug kit must to
be installed in each circuit.
Entering Hot
Gas Line

Leaving
Liquid Line

Inverted Traps (field-supplied)


to extend a minimum of
7-1/2" (190mm) above coil base
Metal
Clamp

Vertical

Horizontal

See
Detail
A-A

Fasten liquid and hot gas lines to leg using


flat surface clamps with isolators (field-supplied).
Support field piping separately to avoid coil damage
and loss of charge.

Liebert DS

140

Isolator
Detail A-A

DPN001065
Rev. 1

Heat RejectionLiebert Fin/Tube Condensers

Figure 112 Liebert Lee-Temp head pressure control condenser pipingFin/tube condensers

Metal
Clamp
Isolator
Detail A-A

This view is shown


with header cover
removed.
Discharge Line
from Unit (field-supplied)

Discharge Line
from Unit
(field-supplied)
Position elbow to direct
relief valve downward
Liquid Return
Line to Unit
(field-supplied)
Hot Gas Line
(field-supplied)
Liquid Line
(field-supplied)

Inverted Traps (field-supplied)


to extend at least 7-1/2" (190mm)
above coil base

Fasten liquid and hot gas lines


to leg using flat surface clamps
with isolators (field-supplied).
Support field piping separately
to avoid coil damage and loss
of charge. See Detail A-A.

Liquid return line to


unit (field supplied
Position elbow to direct
relief valve downward

The following materials are supplied by Emerson


for each circuit (shipped loose with condenser)
for field installation: insulated Liebert Lee-Temp
storage tank with two sight glasses, head
pressure control valve, check valve, rotalock
valve and pressure relief valve. All other
piping to be supplied and installed by others.

DPN000669
Rev. 4

141

Liebert DS

Heat RejectionLiebert Piggyback Condensers, Air-Cooled

14.0 HEAT REJECTIONLIEBERT PIGGYBACK CONDENSERS, AIR-COOLED


Table 39

Liebert DS piggyback condenser selection

Air-Cooled Condenser Selection


Condenser
Type

Ambient
Temp. F (C)

028

035

042

053

070

077

105

95 (35)

PB-925

PB-925

PB-1100

PB-1350

N/A

N/A

N/A

100 (38)

PB-1100

PB-1100

PB-1350

N/A

N/A

N/A

N/A

105 (41)

PB-1100

PB-1350

N/A

N/A

N/A

N/A

N/A

Piggyback

Table 40

Liebert DS Size

Piggyback condenser physical data, 60Hz


Number
of Circuits

Model

Connection Size, OD, In.


Hot Gas

Condenser Charge Per Circuit


R-407C, lb (kg)

Liquid

PB-350

5/8

1/2

18 8.2)

PB-550

5/8

1/2

17 (7.8)

PB-675

7/8

1/2

25 (11.2)

PB-925

7/8

1/2

22 (9.9)

PB-1100

1-1/8

5/8

34 (15.5)

PB-1350

1-1/8

5/8

34 (15.5)

Table 41

Piggyback condenser airflow, and static pressure data


HP/RPM
Ext. Static Pressure - in. (Pa)

Model

No.
of Fans

CFM / m / hr

0.25 (62.3)

0.50 (125)

0.75 (187)

1.0 (249)

PB-350A

7600/12,920

2/580

3/650

3/720

3/790

PB-550A

6600/11,200

2/575

3/650

3/725

3/800

PB-675A

6900/11,730

2/605

3/680

3/750

3/820

PB-925A

12,500/21,250

7.5/760

7.5/810

7.5/870

7.5/920

PB-1100A

12,300/20,910

7.5/780

7.5/830

7.5/890

7.5/940

PB-1350A

16,500/28,050

10/640

10/695

10/740

15/790

Values are without filter box. External Static Pressure = filter pressure drop + other static drops.
Source: DPN000695, Rev. 1

Piggyback condenser electrical data, 60 Hz, 3 phase 1

Table 42

208
hp

230
FLA

460

FLA

LRA

LRA

FLA

2.0

7.5

55

6.8

50

3.0

10.6

71

9.6

64.0

5.0

16.7

102

15.2

92

7.5

24.2

140

22.0

127

10.0

30.8

179

28.0

162.0

14.0

575
LRA

FLA

LRA

3.4

25

2.7

20

4.8

32.0

3.9

25.6

7.6

46

6.1

36.8

11.0

63.5

9.0

50.8

81

11.0

64.8

15.0
46.2
257
42.0
232
21.0
116.0
17.0
93.0
1. See Table 43 for separate power feed needed for Lee-Temp receiver heaters.
2. FLA: Full Load Amps; LRA: Lock Rotor Amps
3. Source: DPN000695, Rev. 1

Table 43

Separate electrical supply requirements for Liebert Lee-Temp receivers, 60Hz, 1 ph

Voltage

120

120

208/230

208/230

Watts/Receiver

150

300

150

300

FLA

2.5

5.0

1.4

2.8

WSA

3.1

6.2

1.8

3.6

OPD

15

15

15

15

Only one independent input power supply is needed per piggyback unit; connect to Terminals 90 & 91.

Liebert DS

142

Heat RejectionLiebert Piggyback Condensers, Air-Cooled

14.1

Dimensions

Figure 113 Piggyback condenser planning dimensions


E
K

1-1/8"
(29mm)

Overa
ll Dim
ensio
ns

sions
Dimen
Overall

Optional Fan
Discharge
Disconnect
Switch (optional)

S
H
J

35-1/8"
(892mm)

72"
(1829mm)

R
Fan Discharge
Shaded areas
indicate a recommended
clearance of 34" (864mm)
for component access.

5"
(127mm)
G

Condenser Coil Inlet


And Duct Connection
C

Drain Outlet
Opening

C
Unit Base

10" (254mm)

1"
(25.4mm)

A
Unit Base

UNIT DIMENSIONAL DATA

NOTE: A 1" (25.4mm) flange is provided on all units


for duct connection to coil duct opening and
fan air discharge opening.

Floor Level
A

DPN000695
Rev. 1

FLOOR CUTOUT DIMENSIONS


Table 44

Piggyback condenser dimensions, in. (mm)

Model

PB-350A

72
(1829)

74
(1880)

31
(787)

32
(813)

1-1/8
(29)

33
(838)

60
(1524)

8-5/8
(219)

50-3/16
(1275)

16-1/16
(408)

13-3/16
(335)

14-11/16
(373)

PB-550A

72
(1829)

74
(1880)

31
(787)

32
(813)

1-1/8
(29)

33
(838)

60
(1564)

8-5/8
(219)

50-3/16
(1275)

16-1/16
(408)

13-3/16
(335)

14-11/16
(373)

PB-675A

72
(1829)

74
(1880)

31
(787)

32
(813)

1-1/8
(29)

33
(838)

60
(1564)

8-5/8
(219)

50-3/16
(1275)

16-1/16
(408)

13-3/16
(335)

14-11/16
(373)

PB-925A

97
(2464)

99
(2515)

33
(838)

34
(864)

3-1/8
(79)

45-1/2
(1156)

85
(2159)

23-5/16
(592)

50-3/16
(1275)

16-1/16
(408)

23-1/2
(597)

14-11/16
(373)

PB-1100A

97
(2464)

99
(2515)

33
(838)

34
(864)

3-1/8
(79)

45-1/2
(1156)

85
(2159)

23-5/16
(592)

50-3/16
(1275)

16-1/16
(408)

23-1/2
(597)

14-11/16
(373)

PB-1350A

97
(2464)

99
(2515)

33
(838)

34
(864)

3-1/8
(79)

45-1/2
(1156)

85
(2159)

16-5/16
(421)

63-7/8
(1622)

19-1/8
(486)

16-13/16
(427)

11-5/8
(295)

Source: DPN000695, Rev. 1

143

Liebert DS

Heat RejectionLiebert Piggyback Condensers, Air-Cooled

Figure 114 Floor stand dimensions, piggyback condensers with forward-curved blowers

B
A

1"
(25.4mm)

* H 1-1/2" (38mm)
For height selection
refer to chart.
Center Leg Provided
on 99" Cabinets

See Table 46 for


height selection

Leg Support on Models


18, 21 & 24" High

Table 45

Floor stand dimensions, in. (mm)


A

Model

PB-350A, PB-550A PB-675A

72 (1829)

36 (914)

31 (787)

PB-925A, PB-1100A PB-1350A

97 (2464)

48-1/2 (1232)

33 (838)

Source: DPN000727, Rev. 0

Table 46

Floor stand height selection, in. (mm)

Nominal

Range (Nominal 1-1/2 *)

9 (229)

7-1/2 to 10-1/2 (191 to 267)

12 (305)

10-1/2 to 13-1/2 (267 to 343)

15 (381)

13-1/2 to 16-1/2 (343 to 419)

18 (458)

16-1/2 to 19-1/2 (419 to 495)

21 (553)

19-1/2 to 22-1/2 (495 to 572)

24 (610)

22-1/2 to 25-1/2 (572 to 648)

1. Leveling feet are provided with 1-1/2" (38mm) adjustment from nominal height H.
2. Source: DPN000727, Rev. 0

Liebert DS

144

DPN000727
Rev. 0

Heat RejectionLiebert Piggyback Condensers, Air-Cooled

14.2

Electrical Field ConnectionsLiebert Piggyback Condensers

Figure 115 Electrical field connections for Liebert piggyback condensers

Factory-installed unit
disconnect switch (optional)

Field-supplied disconnect
switch when factory-installed
unit disconnect switch is not provided.
Three phase electric
service not by
Emerson

Three-phase connection. Electric


service connection terminals
when factory disconnect switch
is supplied

Three-phase connection.
Electric service
connection terminals
when factory disconnect
switch is not supplied

Factory-installed disconnect
switch (optional)
Electric conduit knockouts
on bottom of wire raceway
Knockout sizes 1-3/8"
(34.9mm) or 1-3/4" (44.5mm)
or 2 1/2" (63.5mm)
Three-phase electric
service not by Emerson

Factory-wired to
Earth ground connection (60Hz).
components
Connection terminal for field-supplied
on electric panel.
earth grounding wire.
Liebert Lee-Temp electric
Factory-wired to components
service connection to
on electric panel
terminals supplied from
factory-wired Liebert
Control interlock Field-supplied, Class 2 wiring to
Lee-Temp heater pads
Terminals 70 & 71 to interlock condenser 24V
for field connection of separate
controls to Liebert room unit; 7/8 in. (22.2mm)
continuous electrical source,
diameter knockout provided in bottom of box
not supplied by Emerson.
DPN000697
Rev. 0
Refer to specification sheet for full load amp and wire size amp ratings.
71

70

91

90

145

Liebert DS

Heat RejectionLiebert Piggyback Condensers, Air-Cooled

14.3

Connection LocationsLiebert Piggyback Condensers

Figure 116 Piggyback condenser piping and electrical connection locations

See Note 2

See
Note 2

See Note 1

See
Note 1

A
1-13/16"
(46mm)

B
C

G
1-13

/16"

(46m

m)

E
See Note 3

D
F

D
See Note 2

3" (76mm)

3" (76mm)

1" (25mm)
Panel

1" (25mm)
Panel
3" (76mm)

3" (76mm)

See Note 2

See Note 2

3" (76mm)

See Note 1

3" (76mm)
E See Note 3

See Note 1

E See Note 3

12-5/8"
(321mm)

9-11/16"
(246mm)

12-5/8"
(321mm)

4-1/2" (114mm)

4-1/2"
(114mm)

9-11/16"
(246mm)

7-7/8"
(200mm)

7-7/8"
(200mm)

MODELS PB-350A THRU PB-1100A

MODEL PB-1350A
5-1/2" (140mm) See Note 1
3-1/4" (85mm) See Note 2

Drain Outlet
Location
1-1/4" (32mm) F.P.T.

3"
(76mm)

8"
(203mm)

6"
(152mm)
3"
(76mm)

See Note 3

ALL MODELS

1-1/2"
(38mm)

1. Multiple knockouts of 1-3/8" (35mm), 1-3/4" (45mm) and 2-1/2" (64mm) for main power supply (typical).
2. 7/8" (22.2mm) knockouts for Liebert Lee-Temp power supply (typical).
3. Cover plate for access of liquid line and hot gas line.

Table 47

DPN00696
Rev. 1

DimensionsPiggyback condensers, in. (mm)

Model

PB-350A

27-1/4 (692)

2-1/2 (64)

6 (152)

10-1/8 (267)

28-3/4 (730)

PB-550A

27-1/4 (692)

2-1/2 (64)

6 (152)

10-1/8 (267)

28-3/4 (730)

PB-675A

27-1/4 (692)

2-1/2 (64)

6 (152)

10-1/8 (267)

28-3/4 (730)

PB-925A

27-1/4 (692)

2-1/2 (64)

6 (152)

10-1/8 (267)

28-3/4 (730)

PB-1100A

27-1/4 (692)

2-1/2 (64)

6 (152)

10-1/8 (267)

28-3/4 (730)

PB-1350A

11-1/4 (286)

24 (610)

26-1/2 (673)

7 (178)

6 (152)

Table 48

Piping connection sizes, ODS, in. (mm)

Model

Liquid Line

Hot Gas Line

Drain

PB-350A

2 @ 1/2 (13)

2 @ 5/8 (16)

1-1/4 (32)

PB-550A

2 @ 1/2 (13)

2 @ 5/8 (16)

1-1/4 (32)

PB-675A

2 @ 1/2 (13)

2 @ 7/8 (22)

1-1/4 (32)

PB-925A

2 @ 1/2 (13)

2 @ 7/8 (22)

1-1/4 (32)

PB-1100A

2 @ 5/8 (16)

2 @ 1-1/8 (29)

1-1/4 (32)

PB-1350A

2 @ 5/8 (16)

2 @ 1-1/8 (29)

1-1/4 (32)

See Figures 89 and 90 for piggyback condenser piping schematic with Liebert Lee-Temp .

Liebert DS

146

Heat RejectionLiebert Fin/Tube Drycoolers and Pumps

15.0 HEAT REJECTIONLIEBERT FIN/TUBE DRYCOOLERS AND PUMPS


15.1

Drycooler SelectionProp Fan Drycoolers

Table 49

Liebert DS drycooler selection


Drycooler Type
Outdoor Drycooler

Outdoor Quiet-Line Drycooler

Liebert DS
Model

95F (35C)

100F (38C)

105F (41C)

95F (35C)

100F (38C)

105F (41C)

028

D-174

D-225-16

D-310-16

D-173-16

D-205-16

D-356-32

035

D-174

D-225-16

D-350-16

D-178-16

D-205-16

D-356-32

042

D-225-16

D-310

D-419

D-205

D-347-32

D-453-32

053

D-260

D-350

D-491-32

DD-248

D-347-32

D-453-32

070

D-310

D-419

D-620-32

D-347-32

D-453-32

D-453-32

077

D-350

D-466

D-650-40

D-347-32

D-453-32

N/A

105

D-466

D-620-32

D-880-52

D-453

N/A

N/A

15.2

Liebert Drycooler Data

Table 50

Model #
-174
-225

Liebert standard drycooler performance data, 60Hz


Number
of Fans
2

-260
-310

-350
-419
-466

-491
-620
-650
-880

6
8

Internal
Volume,
gal. (L)

Dry Weight
lb. (kg)

CFM, (l/s)
60Hz

Sound Power
LwA

Sound
Pressure
dBA

6.9 (26.2)

540 (245)

13265 (6261)

91.0

75.5

11.1 (42.1)

620 (281)

12177 (5748)

91.1

75.5

10.0 (37.8)

735 (333)

19898 (9392)

94.0

77.3

13.1 (50.0)

795 (361)

18965 (8951)

94.0

77.3

19.4 (73.3)

855 (388

17398 (8212)

94.0

77.3

17.4 (65.9)

1020 (463)

23650 (11163)

94.4

78.5

22.0 (83.3)

1050 (476)

22770 (10747)

94.4

78.5

26.3 (99.6)

1100 (499)

21700 (10242)

94.4

78.5

27.0 (102.2)

1780 (808)

37930 (17901)

96.8

80.3

33.0 (124.9)

1780 (808)

36531 (17241)

96.8

80.3

44.0 (166.5)

2330 (1058)

45500 (21474)

97.4

81.5

Sound Power
LwA

Sound
Pressure
dBA

All drycooler fan motors are 3/4 hp.

Table 51

Model #
-173
-178
-205
-248
-347
-356
-453

Liebert Quiet-Line drycooler performance data, 60Hz


Number
of Fans
3
4
6
8

Internal
Volume,
gal. (L)

Dry Weight
lb. (kg)

CFM, l/s
60Hz

13.1 (50.0)

795 (361)

8520 (14477)

74.8

61.3

19.4 (73.3)

855 (388)

7440 (12642)

74.8

61.3

13.1 (50.0)

940 (426)

11680 (19847)

76.2

62.5

17.4 (65.9)

1020 (463)

11360 (19303)

76.2

62.5

27.0 (102.2)

1780 (808)

17040 (8042)

78.4

64.3

39.3 (148.8)

1880 (854)

14880 (7023)

78.4

64.3

35.0 (132.5)

2250 (1022)

22720 (10723)

79.9

65.5

147

Liebert DS

Heat RejectionLiebert Fin/Tube Drycoolers and Pumps

15.3

Dimensional Information

15.3.1 DimensionsProp Fan Drycoolers


Figure 117 Dimensions2-fan fin/tube drycooler models
43-9/16"
(1106mm)
91-1/2"
(2324mm)

37-7/8"
(962mm)

18"
(457mm)

84"
(2134mm)
43-3/16"
(1097mm)

Emerson recommends a
clearance of 36" (915mm) on
each side for proper operation
and component access.

Figure 118 Dimensions3- and 4-fan fin/tube drycooler models


43-9/16"
(1106mm)
131-1/2"
(3340mm)
37-7/8"
(962mm)

43-9/16"
(1106mm)
171-1/2"
(4356mm)

18"
(457mm)

124"
(3150mm)

70"
(1778mm)

37-7/8"
(962mm)

Eyebolts
for Lifting

43-3/16"
(1097mm)

18"
(457mm)

Note:
Overall height to the top of fan guard
43-1/8" (1095mm)

164"
(4166mm)
43-3/16"
(1097mm)

Liebert DS

148

Emerson recommends a
clearance of 36" (915mm) on
each side for proper operation
and component access.

Heat RejectionLiebert Fin/Tube Drycoolers and Pumps

Figure 119 Dimensions6- and 8-fan fin/tube drycooler models

131-1/2"
(3340mm)

87-1/8"
(2213mm)
87-1/8"
(2213mm)

171-1/2"
(4356mm)

37-7/8"
(962mm)

37-7/8"
(962mm)

59"
(1499mm)

18"
(457mm)

86-3/4"
(2203mm)

18"
(457mm)

124"
(3150mm)

Overalll height to the top


of the fan guard is 43-1/8 (1095mm).

70" (1778mm)
1-1/2" (38mm)
diameter hole for
rigging (typ.4)
86-3/4"
(2203mm)

149

164"
(4166mm)

Emerson recommends a
clearance of 36" (915mm) on
each side for proper
operation and component

Liebert DS

Heat RejectionLiebert Fin/Tube Drycoolers and Pumps

15.4

Electrical Data

15.4.1 Electrical DataProp Fan Drycoolers


Table 52 60Hz electrical valuesProp fan drycoolers without pump controls, standard models
Drycooler Model
Voltage

Phase

208/230

460

575

Table 53

Electrical
Value

174, 225
2 Fans

260, 310, 350


3 Fans

419, 466, 491


4 Fans

620, 650
6 Fan

880
8 Fans

FLA

7.0

10.5

14.0

21.0

28.0

WSA

7.9

11.4

14.9

21.9

28.9

OPD

15

15

20

25

35

FLA

3.4

5.1

6.8

10.2

13.6

WSA

3.8

5.5

7.2

10.6

14.0

OPD

15

15

15

15

20

FLA

2.8

4.2

5.6

8.4

11.2

WSA

3.2

4.6

6.0

8.8

11.6

OPD

15

15

15

15

15

60Hz electrical valuesProp fan drycoolers without pump controls, Liebert Quiet-Line
models
Drycooler Model

Voltage

Phase

Electrical
Value

173, 178
3 Fans

205, 248
4 Fans

347, 356
6 Fans

453
8 Fans

FLA

5.4

7.2

10.8

14.4

WSA

5.9

7.7

11.3

14.9

OPD

15

15

15

20

FLA

2.7

3.6

5.4

7.2

WSA

2.9

3.8

5.6

7.4

OPD

15

15

15

15

FLA

2.1

2.8

4.2

5.6

WSA

2.3

3.0

4.4

5.8

OPD

15

15

15

15

208/230

460

575

Liebert DS

150

Heat RejectionLiebert Fin/Tube Drycoolers and Pumps

Table 54

60Hz electrical valuesStandard prop fan drycoolers with integral pump controls
Number of Fans

Model #
Pump HP

FLA

174, 225

260, 310, 350

419, 466, 491

620, 650

880

WSA

OPD

FLA

WSA

OPD

FLA

WSA

OPD

FLA

WSA

OPD

FLA

WSA

OPD

208/230/3/60
0.75

10.5

11.4

15

14.0

14.9

20

17.5

18.4

25

24.5

25.4

30

31.5

32.4

40

1.5

13.6

15.3

20

17.1

18.8

25

20.6

22.3

25

27.6

29.3

35

34.6

36.3

40

2.0

14.5

16.4

20

18.0

19.9

25

21.5

23.4

30

28.5

30.4

35

35.5

37.4

45

3.0

17.6

20.3

30

21.1

23.8

30

24.6

27.3

35

31.6

34.3

40

38.6

41.3

50

5.0

23.7

27.9

40

27.2

31.4

45

30.7

34.9

50

37.7

41.9

50

44.7

48.9

60

7.5

31.2

37.3

60

34.7

40.8

60

38.2

44.3

60

45.2

51.3

70

52.2

58.3

80

10.0

37.8

45.5

70

41.3

49.0

70

44.8

52.5

80

51.8

59.5

90

58.8

66.5

90

15

53.2

64.8

110

56.7

68.3

110

60.2

71.8

110

67.2

78.8

110

74.2

85.8

125

0.75

5.0

5.4

15

6.7

7.1

15

8.4

8.8

15

11.8

12.2

15

15.2

15.6

20

1.5

6.4

7.2

15

8.1

8.9

15

9.8

10.6

15

13.2

14.0

20

16.6

17.4

20

2.0

6.8

7.7

15

8.5

9.4

15

10.2

11.1

15

13.6

14.5

20

17.0

17.9

20

460/3/60

3.0

8.2

9.4

15

9.9

11.1

15

11.6

12.8

15

15.0

16.2

20

18.4

19.6

25

5.0

11.0

12.9

20

12.7

14.6

20

14.4

16.3

20

17.8

19.7

25

21.2

23.1

30

7.5

14.4

17.2

25

16.1

18.9

25

17.8

20.6

30

21.2

24.0

30

24.6

27.4

35

10.0

17.4

20.9

30

19.1

22.6

35

20.8

24.3

35

24.2

27.7

40

27.6

31.1

45

15

24.4

29.7

50

26.1

31.4

50

27.8

33.1

50

31.2

36.5

50

34.6

39.9

60

0.75

4.1

4.5

15

5.5

5.9

15

6.9

7.3

15

9.7

10.1

15

12.5

12.9

15

1.5

5.2

5.8

15

6.6

7.2

15

8.0

8.6

15

10.8

11.4

15

13.6

14.2

20

2.0

5.5

6.2

15

6.9

7.6

15

8.3

9.0

15

11.1

11.8

15

13.9

14.6

20

3.0

6.7

7.7

15

8.1

9.1

15

9.5

10.5

15

12.3

13.3

15

15.1

16.1

20

5.0

8.9

10.4

15

10.3

11.8

15

11.7

13.2

15

14.5

16.0

20

17.3

18.8

20

7.5

11.8

14.1

20

13.2

15.5

20

14.6

16.9

25

17.4

19.7

25

20.2

22.5

30

575/3/60

10.0

13.8

16.6

25

15.2

18.0

25

16.6

19.4

30

19.4

22.2

30

22.2

25.0

35

15

19.8

24.1

40

21.2

25.5

40

22.6

26.9

40

25.4

29.7

45

28.2

32.5

45

151

Liebert DS

Heat RejectionLiebert Fin/Tube Drycoolers and Pumps

60Hz electrical valuesLiebert Quiet-Line drycoolers with integral pump controls

Table 55

Number of Fans
Model #
Pump H.P.

FLA

173, 178

205, 248

347, 356

453

WSA

OPD

FLA

WSA

OPD

FLA

WSA

OPD

FLA

WSA

OPD

208/230/3/60
0.75

8.9

9.8

15.0

10.7

11.6

15.0

14.3

15.2

20.0

17.9

18.8

25.0

1.5

12.0

13.7

20.0

13.8

15.5

20.0

17.4

19.1

25.0

21.0

22.7

25.0

2.0

12.9

14.8

20.0

14.7

16.6

20.0

18.3

20.2

25.0

21.9

23.8

30.0

3.0

16.0

18.7

25.0

17.8

20.5

30.0

21.4

24.1

30.0

25.0

27.7

35.0

5.0

22.1

26.3

40.0

23.9

28.1

40.0

27.5

31.7

45.0

31.1

35.3

50.0

7.5 *

29.6

35.7

50.0

31.4

37.5

60.0

35.0

41.1

60.0

38.6

44.7

60.0

36.2

43.9

70.0

38.0

45.7

70.0

41.6

49.3

80.0

45.2

52.9

80.0

51.6

63.2

100.0

53.4

65.0

110.0

57.0

68.6

110.0

60.6

72.2

110.0

0.75

4.3

4.7

15.0

5.2

5.6

15.0

7.0

7.4

15.0

8.8

9.2

15.0

1.5

5.7

6.5

15.0

6.6

7.4

15.0

8.4

9.2

15.0

10.2

11.0

15.0

2.0

6.1

7.0

15.0

7.0

7.9

15.0

8.8

9.7

15.0

10.6

11.5

15.0

10.0
15

460/3/60

3.0

7.5

8.7

15.0

8.4

9.6

15.0

10.2

11.4

15.0

12.0

13.2

15.0

5.0

10.3

12.2

15.0

11.2

13.1

20.0

13.0

14.9

20.0

14.8

16.7

20.0

13.7

16.5

25.0

14.6

17.4

25.0

16.4

19.2

30.0

18.2

21.0

30.0

16.7

20.2

30.0

17.6

21.1

35.0

19.4

22.9

35.0

21.2

24.7

35.0

23.7

29.0

45.0

24.6

29.9

50.0

26.4

31.7

50.0

28.2

33.5

50.0

0.75

3.4

3.7

15.0

4.1

4.4

15.0

5.5

5.8

15.0

6.9

7.2

15.0

1.5

4.5

5.1

15.0

5.2

5.8

15.0

6.6

7.2

15.0

8.0

8.6

15.0

2.0

4.8

5.5

15.0

5.5

6.2

15.0

6.9

7.6

15.0

8.3

9.0

15.0

3.0

6.0

7.0

15.0

6.7

7.7

15.0

8.1

9.1

15.0

9.5

10.5

15.0

5.0

8.2

9.7

15.0

8.9

10.4

15.0

10.3

11.8

15.0

11.7

13.2

15.0

11.1

13.4

20.0

11.8

14.1

20.0

13.2

15.5

20.0

14.6

16.9

25.0

13.1

15.9

25.0

13.8

16.6

25.0

15.2

18.0

25.0

16.6

19.4

30.0

19.1

23.4

40.0

19.8

24.1

40.0

21.2

25.5

40.0

22.6

26.9

40.0

7.5 *
10.0
15

575/3/60

7.5

10.0

15 2

1. Values are calculated per UL 1995. Pump FLA values used are based on NEC tables for motor horsepower. OPD values may be
adjusted higher than calculations to compensate for maximum anticipated application temperatures.
2. May require electrical component(s) with higher capacity in the drycooler. Consult factory representatives for assistance before
ordering.

Liebert DS

152

Heat RejectionLiebert Fin/Tube Drycoolers and Pumps

Figure 120 Electrical field connections for fluid temperature control, direct-drive Drycoolers

Factory-wired to 24V
Class 2 control circuit

Factory-wired to components
on electric panel

Electrical service connection


terminals when factory
disconnect is not supplied.
Fuse block supplied on
DNT drycoolers.

Electric service connection


terminals when factory
disconnect is supplied.
Factory-installed
disconnect switch
(optional).

Unit Alarm Connection


Field-supplied 24V.
Class 2 wiring to
Terminals "24 & 50"
to indicate "Standby Glycol
Pump On". (Supplied
with dual pump controls
only.)

Control interlock
Field-supplied
Class 2 wiring to
interlock drycooler
24V controls to
Liebert room unit
(Not required on
CSU 3000). 7/8"
(22.2mm) diameter
hole provided in
bottom of electric box.
Flow switch connection
(Dual pump controls only)
Field-supplied 24V Class 2
wiring from terminals 74 +
77 to field mounted flow
switch.

Pump fuses & overload


heaters (shipped with
standard pump packages)
are to be field-installed in
pump fuse block(s) and
starter(s).
Earth ground bar (50Hz).
Connection terminals with factory
ground from each high voltage
component for field-supplied
earth grounding wire.

Electric service connection


terminals for power supply to
pumps when pump controls
are factory-supplied. Dual
pump connection shown. 7/8"
(22.2mm) diameter knockouts
provided in bottom
of electric box.

Earth ground connection (60 HZ).


Connection terminal for fieldsupplied earth grounding wire.

Electric service entrance.


A 7/8" (22.2mm) diameter hole
in a 1-1/8" (28.6mm) knockout
provided in bottom of electric
box.

Refer to specification sheet for full load amp and wire size amp ratings.

153

Electric service.
not by Emerson.
(Field-wired to Liebert
CSU 3000.
Interconnecting wiring
not by Emerson).

DPN000276
Rev. 1

Liebert DS

Heat RejectionLiebert Fin/Tube Drycoolers and Pumps

15.5

Piping Connections

Table 56

Standard drycooler piping connection sizes and internal volume

Drycooler

No. of
Fans

Inlet & Outlet Connection Size

Model #

No. of Internal
Coil Circuits

174

16*

225

16

260

24*

310

16

13.1 (50.0)

1/1

2-1/8

350

16

19.4 (73.3)

1/1

2-1/8

419

32*

17.4 (65.9)

1/1

2-1/8

466

40*

22.0 (83.3)

1/1

2-5/8

Internal Volume,
gal. (L)

No. of
Inlets/Outlets

OD Copper, in.

ID Sweat, in.

6.9 (26.2)

1/1

2-1/8

11.1 (42.1)

1/1

2-1/8

10.0 (37.8)

1/1

2-1/8

491

32

26.3 (99.6)

1/1

2-1/8

620

32

27.0 (102.2)

2/2

2-1/8

650

40

33.0 (124.9)

2/2

2-1/8

880

52

44.0 (166.5)

2/2

2-1/8

6
8

* = Standard Circuiting

Table 57

Liebert Quiet-Line

Drycooler

drycooler piping connection sizes and internal volume

No. of Internal
Coil Circuits

No. of
Fans

173

16, 32*

178

16, 32*

205

16

248

32*

347

32

356

32

453

32

Model #

4
6
8

Internal Volume
gal. (L)

Inlet & Outlet Connection Size


OD Copper, in.

ID Sweat, in.

13.1 (50.0)

1/1

2-1/8

19.4 (73.3)

1/1

2-1/8

13.1 (50.0)

1/1

2-1/8

17.4 (65.9)

1/1

2-1/8

27.0 (102.2)

2/2

2-1/8

39.3 (148.8)

2/2

2-1/8

35.0 (132.5)

2/2

2-1/8

* = Standard circuiting

Liebert DS

No. of
Inlets/Outlets

154

Heat RejectionLiebert Fin/Tube Drycoolers and Pumps

Figure 121 PipingDirect-drive drycoolers

Inlet Connection
(Upper Header)
Outlet Connection
(Lower Header)

DPN000275
Rev. 3

1/2" FPT Connections


EXPANSION TANK
(GLYCOOL CSU 3000
Units Supplied with
Compression Tank)

Figure 122 Piping6 and 8 fan drycoolers

Inlet
Connections

(4 Inlet, 4 Outlet
Connections Shown)
See table for actual
number provided.

DPN002429
Rev. 0

Outlet Connections

155

Liebert DS

Heat RejectionLiebert Fin/Tube Drycoolers and Pumps

Figure 123 Typical piping arrangement, multiple prop fan drycoolers and multiple indoor units
Expansion Tank
Gal. (L)

FS
Drycooler No. 1 Model
P:
GPM (L/s)

Ft (kPA)

See Note 3

Cooling Unit #
Model
GPM (L/s)
P Ft (kPa):
Cooling Unit #
Model
GPM (L/s)
P Ft (kPa):

Total
GPM
(L/s):
Pipe
Diam.:
In. (mm)
P: Ft.
(kPa)
Cooling Unit #
Model
GPM (L/s)
P Ft (kPa):

Cooling Unit #
Model
GPM (L/s)
P Ft (kPa):

Drycooler No. 2 Model


P:
GPM (L/s)

Ft (kPA)

LEGEND
Gate Valve
Check Valve
Butterfly Valve

Cooling Unit #
Model
GPM (L/s)
P Ft (kPa):
Cooling Unit #
Model
GPM (L/s)
P Ft (kPa):

Relief Valve
Union
Ball Or Flow Control Valve
FS

Flow Switch

Cooling Unit #
Model
GPM (L/s)
P Ft (kPa):

P:Pressure Drop

Strainer Filter
Notes:
1. Pressure and temperature gauges (or ports for same) are recommended to monitor
component pressure drops and performance.
2. Flow measuring devices, drain and balancing valves to be supplied by others and
located as required.
3. See product literature for installation guidelines and clearance dimensions.
4. Drawing shows dual pump package. Alternate pump packages with more pumps may be
considered, consult supplier

Liebert DS

156

Cooling Unit #
Model
GPM (L/s)
P Ft (kPa):
Cooling Unit #
Model
GPM (L/s)
P Ft (kPa):
Cooling Unit #
Model
GPM (L/s)
P Ft (kPa):
Cooling Unit #
Model
GPM (L/s)
P Ft (kPa):
Cooling Unit #
Model
GPM (L/s)
P Ft (kPa):

DPN000991
Rev. 0

Heat RejectionPiggyback Drycoolers

16.0 HEAT REJECTIONPIGGYBACK DRYCOOLERS


16.1

Drycooler SelectionIndoor Piggyback Drycoolers

Table 58

Liebert indoor piggyback drycooler/DS matchup data


Drycooler Selections

Liebert DS Model

Drycooler Type

Ambient Temp. F (C)

028

035

042

053

070

077

Piggyback
Drycooler

95 (35)
100 (38)
105 (41)

PD-133/150
PD-223
PD-333

PD-150
PD-223
PD-333

PD-223
PD-333
PD-333

PD-290
N/A
N/A

PD-333
N/A
N/A

PD-333
N/A
N/A

Table 59

Indoor piggyback airflow and static pressure data


Horsepower/rpm
Ext. Static Pressure - in. (Pa)
3

Model

No. of Fans

CFM (m /hr)

0.25 (62.3)

0.50 (125)

0.75 (187)

1.0 (249)

PD-133
PD-150

6900 (11,730

2/605

3/680

3/750

3/820

PD-223

12,500 (21,250

7.5/760

7.5/810

7.5/870

7.5/920

PD-290

12,300 (20,910

7.5/780

7.5/830

7.5/890

7.5/940

PD-333

16,500 (28,050

10/640

10/695

10/740

15/790

1. Values are without filter box. External Static Pressure = filter pressure drop + other static drops.
2. Source: DPN000695, Rev. 0

16.2

Electrical DataPiggyback Drycoolers

Table 60

Electrical data, piggyback drycoolers, 60Hz, 3 phase


Drycooler
No Pumps

Model

PD-133

PD-150

PD-223

PD-290

PD-333

Drycooler
Standard Pump Package

Total Unit

Pump Only

Drycooler - Optional
Pump Package

Total Unit

Pump
Only

Total Unit

Voltage

Blower
Motor hp

FLA

WSA

OPD

hp

FLA

FLA

WSA

OPD

hp

FLA

WSA

OPD

208

10.6

13.3

20

1.5

6.6

17.2

19.9

30

18.1

20.8

30

230

9.6

12.0

20

1.5

6.0

15.6

18

25

16.4

18.8

25

460

4.8

6.0

15

1.5

3.0

7.8

15

8.2

9.4

15

575

3.9

4.9

15

1.5

2.4

6.3

7.3

15

6.6

7.6

15

208

10.6

13.3

20

7.5

18.1

20.8

30

21.2

23.9

30

230

9.6

12.0

20

6.8

16.4

18.8

25

19.2

21.6

30

460

4.8

6.0

15

3.4

8.2

9.4

15

9.6

10.8

15

575

3.9

4.9

15

2.7

6.6

7.6

15

7.8

8.8

15

208

7.5

24.2

30.3

50

10.6

34.8

40.9

60

40.9

47

70

230

7.5

22.0

27.5

45

9.6

31.6

37.1

50

37.2

42.7

60

460

7.5

11.0

13.8

20

4.8

15.8

18.6

25

18.6

21.4

30

575

7.5

9.0

11.3

20

3.9

12.9

15.2

20

15.1

17.4

25

208

7.5

24.2

30.3

50

10.6

40.9

47

60

34.8

40.9

60

230

7.5

22.0

27.5

45

9.6

37.2

42.7

30

31.6

37.1

50

460

7.5

11.0

13.8

20

4.8

18.6

21.4

25

15.8

18.6

25

575

7.5

9.0

11.3

20

3.9

15.1

17.4

20

12.9

15.2

20

208

10

30.8

38.5

60

10.6

47.5

55.2

80

41.4

49.1

70

230

10

28.0

35.0

60

9.6

43.2

50.2

70

37.6

44.6

70

460

10

14.0

17.5

30

4.8

21.6

25.1

35

18.8

22.3

35

575

10

11.0

13.8

20

3.9

17.1

19.9

30

14.9

17.7

25

ph = phase; FLA = Full Load Amps; WSA = Wire Size Amp; OPD = Maximum Overcurrent Protection Device
Source: DPN000710, Rev. 0

157

Liebert DS

Heat RejectionPiggyback Drycoolers

16.3

DimensionsIndoor Piggyback Drycoolers

Figure 124 DimensionsIndoor piggyback drycoolers


1-1/8"
(29mm)

J
R

Overall

Optional Fan
Discharge

sions
Dimen

Over

all Dim

ensio

ns

Disconnect
Switch

H
J

35-1/8"
(892mm)

72"
(1829mm)

Fan Discharge
Shaded areas indicate
a recommended
clearance of 34" (864mm)
for component access.

5"
(127mm)
1"
(25.4mm)

Condenser Coil Inlet


and Duct Connection

C
Unit Base

10"
(254mm)
Drain Outlet
Opening

UNIT DIMENSIONS
FAN DISCHARGE DATA
REAR DISCHARGE
OPTIONAL TOP DISCHARGE

15-7/16"
(392mm)
Floor Level

PUMP PACKAGE SELECTION


SINGLE PUMP PACKAGE
DUAL PUMP PACKAGE

Rear of
Cabinet

DPN000710
Rev. 2

FLOOR CUTOUT DIMENSIONS

Table 61

A
Unit Base

DimensionsIndoor piggyback drycoolers, in (mm)


A

PD-133

72
(1829)

74
(1880)

31
(787)

32
(813)

1-1/8
(29)

33
(838)

60
(1524)

8-5/8
(219)

50-3/16
(1275)

16-1/16
(408)

13-3/16
(335)

14-11/16
(373)

PD-150

72
(1829)

74
(1880)

31
(787)

32
(813)

1-1/8
(29)

33
(838)

60
(1524)

8-5/8
(219)

50-3/16
(1275)

16-1/16
(408)

13-3/16
(335)

14-11/16
(373)

PD-223

97
(2464)

99
(2515)

33
(838)

34
(864)

3-1/8
(79)

46-1/2
(1181)

85
(2159)

23-5/16
(592)

50-3/16
(1275)

16-1/16
(408)

23-1/2
(597)

14-11/16
(373)

PD-290

97
(2464)

99
(2515)

33
(838)

34
(864)

3-1/8
(79)

46-1/2
(1181)

85
(2159)

23-5/16
(592)

50-3/16
(1275)

16-1/16
(408)

23-1/2
(597)

14-11/16
(373)

PD-333

97
(2464)

99
(2515)

33
(838)

34
(864)

3-1/8
(79)

46-1/2
(1181)

85
(2159)

16-5/16
(421)

63-7/8
(1622)

19-1/8
(486)

16-13/16
(427)

11-5/8
(295)

Model

1. A 1" (25.4mm) flange is provided on all units for duct connection to coil duct opening and fan air discharge opening.
2. Source: DPN000710, Rev. 1

Liebert DS

158

Heat RejectionPiggyback Drycoolers

16.4

Piping

Figure 125 PipingIndoor piggyback drycooler models

See
Note 4

See
Note 4

See
Note 1

See
Note 1

See Note 2

1-13/16"
(46mm)

1-13/16"
(46mm)

See Note 2

3" (76mm)

See Note 1
See Note 4

3" (76mm)

1" (25mm)
Panel
3" (76mm)

See Note 1

3" (76mm)

See Note 4

1" (25mm)
Panel
3" (76mm)
3" (76mm)

C See Note 2

12-5/8"
(321mm)

12-5/8"
(321mm)

4-1/2"
(114mm)

9-11/16"
(246mm)

See Note 2

4-1/2"
(114mm)

9-11/16"
(246mm)

7-7/8"
(200mm)

7-7/8"
(200mm)

MODELS PD-102 THRU PD-290

MODEL PD-333
5-1/2" (140mm) See Note 1
3-1/4" (85mm)
See Note 4

Drain Outlet
Location
1-1/4" (32mm) F.P.T.

3"
(76mm)
See
Note 2

NOTES
1. Multiple knockouts of 1-3/8" (35mm), 1-3/4" (45mm) and
2-1/2" (64mm) for main power supply (typical).
2. Cover plate for access of glycol piping inlet and outlet.
3. Piggyback drycooler connection sizes for supply and return
glycol lines are the same as room unit supply and return lines.
FE/FH 110G 1-5/8" (41mm); FE/FH116G - 2-1/8" (54mm).
Note applies to PD-133.
4. 7/8" (22.2mm) knockout provided.

Table 62
Model #

DimensionsIndoor piggyback drycoolers


A

6" (1

52m

3" (7

1-1/2

6mm

" (38

m)

8"
(203mm)

mm)

ALL MODELS

DPN000711
Rev. 1
Table 63

Pipe connection sizes, ODS

Model # Glycol Supply Glycol Ret.

Drain

PD-133 27-1/4 (692) 2-1/2 (64) 6 (152) 9-1/8 (232) 28-3/4 (730)

PD-133

See Note 3

PD-150 27-1/4 (692) 2-1/2 (64) 6 (152) 9-1/8 (232) 28-3/4 (730)

PD-150

2-1/8 (54)

2-1/8 (54)

1-1/4 (32)

PD-223 27-1/4 (692) 2-1/2 (64) 6 (152) 9-1/8 (232) 28-3/4 (730)

PD-223

2-1/8 (54)

2-1/8 (54)

1-1/4 (32)

PD-290 27-1/4 (692) 2-1/2 (64) 6 (152) 9-1/8 (232) 28-3/4 (730)

PD-290

2-1/8 (54)

2-1/8 (54)

1-1/4 (32)

PD-333

2-1/8 (54)

2-1/8 (54)

1-1/4 (32)

PD-333 26-1/2 (673

6 (152)

7 (178) 11-1/4 (286)

24 (610)

Source: DPN000711, Rev. 1

See Note 3 1-1/4 (32)

Source: DPN000711, Rev. 1

159

Liebert DS

Pump Packages and Expansion Tank

17.0 PUMP PACKAGES AND EXPANSION TANK


Figure 126 Single pump package piping connections and dimension
17-1/4"
(438.2mm)

SINGLE PACKAGE 0.75 - 7.5 HP

2
1
3

19"
(482.6mm)

2-7/8"
(72.9mm)

15-7/8"
(403.2mm)

1-3/4"
(44.4mm)

6-3/8"
(161.9mm)
8-3/4"
(222.3mm)

12-1/4"
(311.1mm)

30"
(762mm)

17"
(431.8mm)

PUMP PACKAGE MOUNTING ANGLES


(Angles are inside, bottom
of pump package. View used for
mounting reference.)

3" (76.2mm) diameter pump suction


connection knockouts

3" (76.2mm) diameter pump discharge


connection knockouts

3 7/8" (22.2mm) diameter electrical knockouts


4

4 1/2" (12.7mm) diameter holes for mounting

3/4"
(19mm)
C

DPN000278
Rev. 0

Table 64

Mounting hole dimensions, in. (mm)


A

Single (0.75 - 7.5hp)

15-1/4 (387.4)

2-1/2 (63.5)

22-1/2 (571.5)

Dual (0.75 - 5hp)

30-1/4 (768.4)

2-1/2 (63.5)

22-1/2 (571.5)

Dual (7.5hp)

39-5/16 (998.5)

1-3/4 (44.5)

26-7/8 (682.6)

Pump Package

Source: DPN000278, Rev. 0

Liebert DS

160

Pump Packages and Expansion Tank

Figure 127 Dual pump package piping connections and dimensions


DUAL PACKAGE 0.75 - 5 HP

See Figure 126 and Table 64 for


mounting angles and dimensions

32-1/4"
(819.2mm)

1
2

1
3

15-7/8"
(403.2mm)

4-1/8"
(104.8mm)

6-3/8"
(161.9mm) "

2-7/8"
(73mm)

8-3/4" (222.2mm)

19"
(482.6mm)

1-3/4"
(44.4mm)

12-1/4"
(311.1mm)
30"
(762mm)

23-3/4"
(603.2mm)
27-1/4"
(692.1mm)
32"
(812.8mm)

3" (76.2mm) diameter pump suction


connection knockouts

3" (76.2mm) diameter pump discharge


connection knockouts

7/8" (22.2mm) diameter electrical knockouts

5 5" (127mm) diameter pump discharge


connection hole

6 5" (127mm) diameter pump suction


connection hole
32-3/8"
(822.3mm)

DUAL PACKAGE 7.5 HP

3
5

41-1/4"
(1047.8mm)

6
5
6

19-15/16
(506.4mm)

11-7/8
(301.6mm)
15-7/8
(403.2mm)
33-3/16"
(843mm)

16-3/8"
(415.9mm)

29-3/16"
(741.4mm)

6-1/2"
(165.1mm)

41"
(1041.4mm)

161

DPN000328
Rev. 0

Liebert DS

Pump Packages and Expansion Tank

Figure 128 Pump package expansion tank

30-1/2"
(774.7mm)
9"
(228.6mm)

1/2" F.P.T.
Fitting

2-3/4"
(69.9mm)

2-1/2"
(63.5mm)

1"
(25.4mm)
1-1/2"
(38.1mm)

6-13/16"
(173mm)

1/2" F.P.T.
Fitting

17-1/4"
(438.2mm)

7"
(177.8mm)
4"
(101.6mm)

1"
(25.4mm)

1/2" (12.7mm)
8 Holes

1-1/2"
(38.1mm)

6-1/8"
(155.6mm)

8.8 gal. (33.3 L)


Expansion Tank

3"
(76.2mm)

DPN000329
Rev. 0

Expansion Tank (P/N 1C16717P1)


This tank, included in a standard pump package, has an internal volume of 8.8 gal. (33 l) and a
maximum pressure of 100 psi (690 kPa).
This tank is sized for a typical open system with a fluid volume of less than 75 gal. (280l). When
used in a closed system, volumes of up to 140 gal. (910l) can be accommodated. The use of a safety
relief valve, field-supplied, is recommended for systems closed to atmospheric venting. Other piping
accessories for filling, venting, or adjusting the fluid in the system, are recommended, but not
included.
Table 65

Glycol pump data


Connections

Electric @ 60Hz

Pump
HP

NPT Suction
Connection

Female
Discharge
Connection

ph

208 FLA

230 FLA

460 FLA

575 FLA

3/4

1-1/4"

3/4"

7.6

6.9

N/A

N/A

3/4

1-1/4"

3/4"

3.5

3.2

1.6

1.3

1-1/2

1-1/4"

3/4"

6.6

6.0

3.0

2.4

1-1/4"

3/4"

7.5

6.8

3.4

2.7

1-1/2"

1"

10.6

9.6

4.8

3.9

1-1/2"

1-1/4"

16.7

15.2

7.6

6.1

7-1/2 *

3"

3"

24.2

22.0

11.0

9.0

* May require electrical component(s) with higher capacity in the drycooler. Consult factory representative
for assistance before ordering.

To Calculate Total Pump and Drycooler Full Load Amps (FLA):


Total FLA = Pump FLA + Drycooler FLA
To Calculate Total Pump and Drycooler Wire Size Amps (WSA):
Total WSA = Largest Motor FLA x 1.25 + Sum of other Motor FLA values
To Calculate Total Pump and Drycooler Maximum Overcurrent Protective Device (OPD):
Total OPD = Largest Motor FLA x 2.25 + Sum of other Motor FLA values
Select standard fuse size (15A, 20A, 25A, 30A, etc.)

Liebert DS

162

Pump Packages and Expansion Tank

Figure 129 Pump curve, 60 Hz

180

Curve
A
B
C
D
E
F

Total Head, Feet/Water

160
140

F
120

D
100

80

60

HP
3/4 (1-ph)
3/4 (3-ph)
1.5
2
3
5
7.5

C
B
A

40
20
0

10

20

30

40

50

60

70

80

120

160

200

250

300

400

Flow Rate, GPM


Capacity data is rated and factory-certified per ASHRAE 127-2007 with a 0% tolerance.

163

Liebert DS

U.S. Department of Energy (DOE) Performance Data

APPENDIX A - U.S. DEPARTMENT OF ENERGY (DOE) PERFORMANCE DATA


Table 66

U.S. DOE performance tableLiebert DS upflow and downflow, air-cooled

Basic Model
Number

Airflow
Configuration

DS028AD*0*
DS028AD*1*

Total Cooling Capacity

Sensible Cooling Capacity

Btu/hr

kW

Btu/hr

kW

CFM

SCOP

Downflow

104499

30.63

94171

27.60

4210

2.42

Downflow

106548

31.23

96218

28.20

4199

2.62

DS028AS*0*

Downflow

104158

30.53

93830

27.50

4210

2.6

DS028AS*1*

Downflow

106207

31.13

95877

28.10

4199

2.83

DS028AU*0*

Downflow

124306

36.43

103725

30.40

4210

2.37

DS028AU*1*

Downflow

126697

37.13

106113

31.10

4199

2.54

DS028DD*0*

Downflow

103816

30.43

93489

27.40

4210

2.36

DS028DD*1*

Downflow

105865

31.03

95536

28.00

4199

2.56

DS028DU*0*

Downflow

123623

36.23

103384

30.30

4210

2.32

DS028DU*1*

Downflow

126014

36.93

105431

30.90

4199

2.48

DS035AD*0*

Downflow

119184

34.93

107137

31.40

4976

2.24

DS035AD*1*

Downflow

122940

36.03

110549

32.40

4976

2.5

DS035AS*0*

Downflow

123623

36.23

109184

32.00

4976

2.38

DS035AS*1*

Downflow

127038

37.23

112596

33.00

4976

2.66

DS035AU*0*

Downflow

124989

36.63

109866

32.20

4976

2.33

DS035AU*1*

Downflow

128746

37.73

113620

33.30

4976

2.59

DS035DD*0*

Downflow

118501

34.73

106113

31.10

4976

2.18

DS035DD*1*

Downflow

121916

35.73

109525

32.10

4976

2.42

DS035DU*0*

Downflow

123965

36.33

108843

31.90

4976

2.26

DS035DU*1*

Downflow

127721

37.43

112596

33.00

4976

2.51

DS042AD*1*

Downflow

138649

40.64

125220

36.70

5957

2.32

DS042AS*0*

Downflow

133185

39.03

120102

35.20

6029

2.1

DS042AS*1*

Downflow

139674

40.94

125903

36.90

5957

2.46

DS042AU*1*

Downflow

146504

42.94

129315

37.90

5957

2.35

DS042DD*1*

Downflow

136942

40.14

124538

36.50

6053

2.22

DS042DU*1*

Downflow

145138

42.54

128632

37.70

6053

2.26

DS053AD*0*

Downflow

184069

53.95

166506

48.80

7177

2.49

DS053AD*1*

Downflow

187484

54.95

173671

50.90

7714

2.63

DS053AS*0*

Downflow

190557

55.85

169918

49.80

7177

2.5

DS053AS*1*

Downflow

193972

56.85

177083

51.90

7714

2.63

DS053AU*0*

Downflow

182020

53.35

165482

48.50

7177

2.54

DS053AU*1*

Downflow

185435

54.35

172306

50.50

7714

2.68

DS053DD*0*

Downflow

182361

53.45

164800

48.30

7177

2.41

DS053DD*1*

Downflow

185776

54.45

171965

50.40

7714

2.54

DS053DU*0*

Downflow

180312

52.85

163776

48.00

7177

2.46

DS053DU*1*

Downflow

183727

53.85

170600

50.00

7714

2.59

DS070AD*0*

Downflow

227098

66.56

198237

58.10

8613

2.16

DS070AD*1*

Downflow

231537

67.86

207450

60.80

9277

2.3

DS070AS*0*

Downflow

231879

67.96

200626

58.80

8613

2.18

DS070AS*1*

Downflow

236318

69.26

209497

61.40

9277

2.32

Liebert DS

164

U.S. Department of Energy (DOE) Performance Data

Table 66

U.S. DOE performance tableLiebert DS upflow and downflow, air-cooled (continued)

Basic Model
Number

Airflow
Configuration

DS070AU*0*
DS070AU*1*

Total Cooling Capacity

Sensible Cooling Capacity

Btu/hr

kW

Btu/hr

kW

CFM

SCOP

Downflow

216853

63.56

193460

56.70

8613

2.27

Downflow

221634

64.96

202332

59.30

9277

2.43

DS070DD*0*

Downflow

224707

65.86

195849

57.40

8613

2.1

DS070DD*1*

Downflow

228805

67.06

204720

60.00

9277

2.21

DS070DU*0*

Downflow

214462

62.86

190731

55.90

8613

2.18

DS070DU*1*

Downflow

218902

64.16

199943

58.60

9277

2.32

DS077AS*1*

Downflow

252710

74.07

226216

66.30

10644

2.1

DS077AU*1*

Downflow

243490

71.36

221780

65.00

10644

2.15

DS077DU*1*

Downflow

241099

70.66

215638

63.20

10063

2.1

DS105AS*1*

Downflow

328182

96.18

276372

81.00

13111

1.92

DS105AU*1*

Downflow

326474

95.68

283878

83.20

13111

1.9

DS105DU*1*

Downflow

322035

94.38

270572

79.30

13087

1.9

VS028AD*0*

Upflow

105524

30.93

95195

27.90

4210

2.35

VS028AD*1*

Upflow

106548

31.23

96218

28.20

4210

2.45

VS028AS*0*

Upflow

104499

30.63

94854

27.80

4210

2.52

VS028AS*1*

Upflow

105865

31.03

95877

28.10

4210

2.63

VS028AU*0*

Upflow

125672

36.83

105090

30.80

4210

2.31

VS028AU*1*

Upflow

126697

37.13

106113

31.10

4210

2.4

VS028DD*0*

Upflow

104841

30.73

94854

27.80

4210

2.32

VS028DD*1*

Upflow

106207

31.13

95877

28.10

4210

2.42

VS028DU*0*

Upflow

125331

36.73

104748

30.70

4210

2.29

VS028DU*1*

Upflow

126355

37.03

105772

31.00

4210

2.37

VS035AD*0*

Upflow

120550

35.33

108843

31.90

4976

2.21

VS035AD*1*

Upflow

122599

35.93

110890

32.50

4976

2.35

VS035AS*0*

Upflow

127721

37.43

103042

30.20

4976

2.17

VS035AS*1*

Upflow

126697

37.13

112937

33.10

4976

2.49

VS035AU*0*

Upflow

126697

37.13

111914

32.80

4976

2.3

VS035AU*1*

Upflow

128746

37.73

113961

33.40

4976

2.44

VS035DD*0*

Upflow

119867

35.13

110208

32.30

5263

2.16

VS035DD*1*

Upflow

121916

35.73

110208

32.30

4976

2.31

VS035DU*0*

Upflow

126014

36.93

113278

33.20

5263

2.24

VS035DU*1*

Upflow

128063

37.53

113278

33.20

4976

2.4

VS042AD*0*

Upflow

135234

39.63

122491

35.90

5933

2.01

VS042AD*1*

Upflow

138649

40.64

125903

36.90

5933

2.19

VS042AS*0*

Upflow

135917

39.83

122832

36.00

5933

2.13

VS042AS*1*

Upflow

139332

40.84

126244

37.00

5933

2.33

VS042AU*0*

Upflow

143430

42.04

126585

37.10

5933

2.05

VS042AU*1*

Upflow

146845

43.04

129997

38.10

5933

2.23

VS042DD*0*

Upflow

130795

38.33

121808

35.70

6029

1.99

VS042DD*1*

Upflow

137625

40.34

125220

36.70

5933

2.15

VS042DU*0*

Upflow

142747

41.84

125903

36.90

5933

2.01

VS042DU*1*

Upflow

145821

42.74

129315

37.90

5933

2.18

165

Liebert DS

U.S. Department of Energy (DOE) Performance Data

Table 66

U.S. DOE performance tableLiebert DS upflow and downflow, air-cooled (continued)

Basic Model
Number

Airflow
Configuration

VS053AD*0*
VS053AD*1*

Total Cooling Capacity

Sensible Cooling Capacity

Btu/hr

kW

Btu/hr

kW

CFM

SCOP

Upflow

186118

54.55

172988

50.70

7656

2.45

Upflow

186801

54.75

173671

50.90

7656

2.47

VS053AS*0*

Upflow

192606

56.45

176400

51.70

7656

2.45

VS053AS*1*

Upflow

193289

56.65

177083

51.90

7656

2.48

VS053AU*0*

Upflow

184410

54.05

171965

50.40

7656

2.49

VS053AU*1*

Upflow

184752

54.15

172647

50.60

7656

2.52

VS053DD*0*

Upflow

184752

54.15

171624

50.30

7656

2.37

VS053DD*1*

Upflow

185776

54.45

171624

50.30

7656

2.47

VS053DU*0*

Upflow

182703

53.55

170600

50.00

7656

2.41

VS053DU*1*

Upflow

184069

53.95

172647

50.60

7656

2.43

VS070AD*0*

Upflow

230513

67.56

207450

60.80

9187

2.16

VS070AD*1*

Upflow

231537

67.86

208473

61.10

9187

2.2

VS070AS*0*

Upflow

235635

69.06

209838

61.50

9187

2.18

VS070AS*1*

Upflow

236660

69.36

210862

61.80

9187

2.21

VS070AU*0*

Upflow

220609

64.66

202332

59.30

9187

2.26

VS070AU*1*

Upflow

221634

64.96

203355

59.60

9187

2.3

VS070DD*0*

Upflow

229147

67.16

205744

60.30

9187

2.11

VS070DD*1*

Upflow

230171

67.46

206767

60.60

9187

2.15

VS070DU*0*

Upflow

219243

64.26

200967

58.90

9187

2.21

VS070DU*1*

Upflow

220268

64.56

201990

59.20

9187

2.25

VS077AS*0*

Upflow

253052

74.17

223486

65.50

9953

1.99

VS077AS*1*

Upflow

254076

74.47

224510

65.80

9953

2.02

VS077AU*0*

Upflow

243490

71.36

219050

64.20

9953

2.05

VS077AU*1*

Upflow

244514

71.66

220210

64.54

9953

2.08

VS077DU*0*

Upflow

241441

70.76

217003

63.60

9953

VS077DU*1*

Upflow

243148

71.26

215980

63.30

9570

2.05

VS105AS*0*

Upflow

328865

96.38

277054

81.20

13111

1.84

VS105AS*1*

Upflow

329548

96.58

275007

80.60

12633

1.87

VS105AU*0*

Upflow

326474

95.68

276031

80.90

13111

1.81

VS105AU*1*

Upflow

324425

95.08

273984

80.30

12633

1.84

VS105DU*0*

Upflow

322376

94.48

272278

79.80

13111

1.79

VS105DU*1*

Upflow

325108

95.28

269548

79.00

12250

1.81

Liebert DS

166

U.S. Department of Energy (DOE) Performance Data

Table 67

U.S. DOE performance tableLiebert DS upflow and downflow, water-cooled

Basic Model
Number

Airflow
Configuration

DS028WD*0*
DS028WD*1*

Total Cooling Capacity

Sensible Cooling Capacity

Btu/hr

kW

Btu/hr

kW

CFM

SCOP

Downflow

107914

31.63

97583.2

28.60

4210

Downflow

111329

32.63

99971.6

29.30

4210

3.29

DS028WS*0*

Downflow

106889.5

31.33

96559.6

28.30

4210

3.25

DS028WS*1*

Downflow

108938.5

31.93

98948

29.00

4210

3.59

DS028WU*0*

Downflow

129087

37.83

107478

31.50

4210

2.89

DS028WU*1*

Downflow

131477.5

38.53

109866.4

32.20

4210

3.14

DS035WD*0*

Downflow

127038

37.23

112596

33.00

4926

2.63

DS035WD*1*

Downflow

130453

38.23

116008

34.00

4926

2.96

DS035WS*0*

Downflow

122940

36.03

110548.8

32.40

4926

2.83

DS035WS*1*

Downflow

126355

37.03

113960.8

33.40

4926

3.22

DS035WU*0*

Downflow

130453

38.23

114302

33.50

4926

2.83

DS035WU*1*

Downflow

134209.5

39.33

118055.2

34.60

4926

3.2

DS042WD*1*

Downflow

147869.5

43.34

132044.4

38.70

5850

2.83

DS042WS*0*

Downflow

140015

41.04

125902.8

36.90

5950

2.52

DS042WS*1*

Downflow

131477.5

38.53

131362

38.50

5850

3.02

DS042WU*0*

Downflow

150943

44.24

129997.2

38.10

6054

2.5

DS042WU*1*

Downflow

155041

45.44

135456.4

39.70

5850

2.84

DS053WD*0*

Downflow

201826.5

59.15

172647.2

50.60

7177

3.19

DS053WD*1*

Downflow

205241.5

60.15

179471.2

52.60

7714

3.38

DS053WS*0*

Downflow

203875.5

59.75

173670.8

50.90

7177

3.19

DS053WS*1*

Downflow

207290.5

60.75

180494.8

52.90

7714

3.38

DS053WU*0*

Downflow

196704

57.65

170258.8

49.90

7177

3.18

DS053WU*1*

Downflow

200460.5

58.75

177082.8

51.90

7714

3.37

DS070WD*0*

Downflow

246904.5

72.36

205402.4

60.20

8613

2.74

DS070WD*1*

Downflow

252027

73.86

214273.6

62.80

9277

2.92

DS070WS*0*

Downflow

250319.5

73.36

207108.4

60.70

8613

2.75

DS070WS*1*

Downflow

255442

74.87

215979.6

63.30

9277

2.94

DS070WU*0*

Downflow

238025.5

69.76

201308

59.00

8613

2.77

DS070WU*1*

Downflow

243148

71.26

209838

61.50

9277

2.96

DS077WS*0*

Downflow

273883

80.27

225192

66.00

10500

2.5

DS077WS*1*

Downflow

263638

77.27

235428

69.00

10644

2.67

DS077WU*0*

Downflow

266711.5

78.17

221780

65.00

10500

2.5

DS077WU*1*

Downflow

270126.5

79.17

232016

68.00

10644

2.65

DS105WS*1*

Downflow

349013

102.29

288314

84.50

12890

2.43

DS105WU*1*

Downflow

353111

103.49

287972.8

84.40

13000

2.4

VS028WD*0*

Upflow

108597

31.83

97242

28.50

4297

2.856

VS028WD*1*

Upflow

109621.5

32.13

98265.6

28.80

4297

2.99

VS028WS*0*

Upflow

106206.5

31.13

96218.4

28.20

4297

3.092

VS028WS*1*

Upflow

107572.5

31.53

97242

28.50

4297

3.24

VS028WU*0*

Upflow

129087

37.83

107478

31.50

4297

2.78

VS028WU*1*

Upflow

130453

38.23

108501.6

31.80

4297

2.89

VS035WD*0*

Upflow

127038

37.23

112937.2

33.10

5078

2.556

167

Liebert DS

U.S. Department of Energy (DOE) Performance Data

Table 67

U.S. DOE performance tableLiebert DS upflow and downflow, water-cooled (continued)

Basic Model
Number

Airflow
Configuration

Total Cooling Capacity


Btu/hr

kW

Sensible Cooling Capacity


Btu/hr

kW

CFM

SCOP

VS035WD*1*

Upflow

129087

37.83

114643.2

33.60

5078

2.72

VS035WS*0*

Upflow

122940

36.03

110548.8

32.40

5078

2.85

VS035WS*1*

Upflow

124989

36.63

112596

33.00

5078

2.94

VS035WU*0*

Upflow

130794.5

38.33

114643.2

33.60

5078

2.75

VS035WU*1*

Upflow

132843.5

38.93

116349.2

34.10

5078

2.93

VS042WD*0*

Upflow

142747

41.84

127267.6

37.30

6054

2.386

VS042WD*1*

Upflow

146162

42.84

130679.6

38.30

6054

2.62

VS042WS*0*

Upflow

126696.5

37.13

126585.2

37.10

6054

2.526

VS042WS*1*

Upflow

144796

42.44

129656

38.00

6054

2.78

VS042WU*0*

Upflow

150260

44.04

130679.6

38.30

6054

2.41

VS042WU*1*

Upflow

153675

45.04

134091.6

39.30

6054

2.64

VS053WD*0*

Upflow

202851

59.45

177082.8

51.90

7812

3.07

VS053WD*1*

Upflow

203534

59.65

177424

52.00

7812

3.11

VS053WS*0*

Upflow

204558.5

59.95

177765.2

52.10

7812

3.066

VS053WS*1*

Upflow

205241.5

60.15

178106.4

52.20

7812

3.1

VS053WU*0*

Upflow

197728.5

57.95

174353.2

51.10

7812

3.05

VS053WU*1*

Upflow

198411.5

58.15

174694.4

51.20

7812

3.09

VS070WD*0*

Upflow

249295

73.06

211544

62.00

9374

2.69

VS070WD*1*

Upflow

250319.5

73.36

212226.4

62.20

9374

2.73

VS070WS*0*

Upflow

252368.5

73.96

213250

62.50

9374

2.7

VS070WS*1*

Upflow

253734.5

74.37

213932.4

62.70

9374

2.74

VS070WU*0*

Upflow

240416

70.46

207108.4

60.70

9374

2.71

VS070WU*1*

Upflow

241440.5

70.76

207790.8

60.90

9374

2.76

VS077WS*0*

Upflow

274566

80.47

228945.2

67.10

10156

2.51

VS077WS*1*

Upflow

276273.5

80.97

229968.8

67.40

10156

2.56

VS077WU*0*

Upflow

267394.5

78.37

225533.2

66.10

10156

2.49

VS077WU*1*

Upflow

268760.5

78.77

226215.6

66.30

10156

2.53

VS105WS*0*

Upflow

348330

102.09

286266.8

83.90

12890

2.29

VS105WS*1*

Upflow

349013

102.29

283537.2

83.10

12890

2.32

VS105WU*0*

Upflow

345256.5

101.19

285925.6

83.80

12500

2.29

VS105WU*1*

Upflow

345256.5

101.19

282854.8

82.90

12500

2.29

Liebert DS

168

U.S. Department of Energy (DOE) Performance Data

Table 68

U.S. DOE performance tableLiebert DS upflow and downflow, water-cooled with a fluid
economizer

Basic Model
Number

Airflow
Configuration

VS028*U*1*
VS028*U*0*
VS028*D*1*
VS028*D*0*

Total Cooling Capacity

Sensible Cooling Capacity

Btu/hr

kW

Btu/hr

kW

CFM

SCOP

Upflow

130111.5

38.13

108160.4

31.70

4297

2.86

Upflow

128745.5

37.73

107136.8

31.40

4297

2.75

Upflow

109280

32.03

97924.4

28.70

4297

2.94

Upflow

108255.5

31.73

96900.8

28.40

4297

2.82

VS035*U*1*

Upflow

132160.5

38.73

116008

34.00

5078

2.88

VS035*U*0*

Upflow

130111.5

38.13

114302

33.50

5078

2.71

VS035*D*1*

Upflow

129087

37.83

113960.8

33.40

5078

2.67

VS035*D*0*

Upflow

126355

37.03

112254.8

32.90

5078

2.52

VS042*U*1*

Upflow

152650.5

44.74

133068

39.00

6054

2.56

VS042*U*0*

Upflow

149577

43.84

129997.2

38.10

6054

2.37

VS042*D*1*

Upflow

145137.5

42.54

129314.8

37.90

6054

2.54

VS042*D*0*

Upflow

142064

41.64

126585.2

37.10

6054

2.34

VS053*U*1*

Upflow

197728.5

57.95

174012

51.00

7812

3.02

VS053*U*0*

Upflow

195679.5

57.35

172306

50.50

7812

2.91

VS053*D*1*

Upflow

202509.5

59.35

176400.4

51.70

7812

3.05

VS053*D*0*

Upflow

200802

58.85

175035.6

51.30

7812

2.93

VS070*U*1*

Upflow

240074.5

70.36

206426

60.50

9374

2.68

VS070*U*0*

Upflow

238708.5

69.96

205743.6

60.30

9374

2.64

VS070*D*1*

Upflow

248953.5

72.96

210861.6

61.80

9374

2.66

VS070*D*0*

Upflow

247587.5

72.56

210179.2

61.60

9374

2.62

VS077*U*1*

Upflow

266370

78.07

222121.2

65.10

9765

2.49

VS077*U*0*

Upflow

265345.5

77.77

223486

65.50

9765

2.42

VS105*U*1*

Upflow

345256.5

101.19

278419.2

81.60

12500

2.24

DS028*U*1*

Downflow

130794.5

38.33

109184

32.00

4210

3.06

DS028*U*0*

Downflow

128404

37.63

106795.6

31.30

4210

2.82

DS028*D*1*

Downflow

110646

32.43

99289.2

29.10

4210

3.2

DS028*D*0*

Downflow

108255.5

31.73

96900.8

28.40

4210

2.92

DS035*U*1*

Downflow

133185

39.03

117031.6

34.30

4976

3.09

DS035*U*0*

Downflow

129428.5

37.93

113278.4

33.20

4976

2.74

DS035*D*1*

Downflow

129428.5

37.93

115325.6

33.80

4976

2.86

DS035*D*0*

Downflow

126013.5

36.93

111572.4

32.70

4976

2.55

DS042*U*1*

Downflow

153675

45.04

134774

39.50

5957

2.72

DS042*D*1*

Downflow

146162

42.84

131362

38.50

5957

2.7

DS053*U*1*

Downflow

198753

58.25

175376.8

51.40

7714

3.23

DS053*U*0*

Downflow

195338

57.25

168552.8

49.40

7177

3.06

DS053*D*1*

Downflow

203534

59.65

177765.2

52.10

7714

3.25

DS053*D*0*

Downflow

200119

58.65

170941.2

50.10

7177

3.07

DS070*U*1*

Downflow

240416

70.46

207449.6

60.80

9277

2.82

DS070*U*0*

Downflow

235635

69.06

198578.4

58.20

8613

2.65

DS070*D*1*

Downflow

249295

73.06

211544

62.00

9277

2.79

DS070*D*0*

Downflow

244514

71.66

203014

59.50

8613

2.62

DS077*U*1*

Downflow

266711.5

78.17

224850.8

65.90

9998

2.56

169

Liebert DS

Guide Specifications

APPENDIX B - GUIDE SPECIFICATIONS


1.0

GENERAL

1.1

SUMMARY
These specifications describe requirements for a Mission Critical Cooling system. The system shall be
designed to control temperature and humidity conditions in rooms containing electronic equipment,
with good insulation and vapor barrier. The manufacturer shall design and furnish all equipment to
be fully compatible with heat dissipation requirements of the room.

1.2

DESIGN REQUIREMENTS
The Mission Critical Cooling system shall be a Liebert self-contained, factory-assembled unit with
(upflow) (downflow) air delivery. The system shall have a net total cooling capacity of ____ BTUH
(kW) with a net sensible cooling capacity of ____ BTUH (kW) based on an entering air temperature of
____ F (C) dry bulb and ____ F (C) wet bulb. The unit shall be supplied with ____ volt ____ ph
____ Hz electrical service. Net capacities shall include losses due to fan motor heat. The system
cooling capacity shall be factory-certified per ASHRAE127-2007.

1.3

SUBMITTALS
Submittals shall be provided after the agreement of the proposal and shall include: Single-Line
Diagrams; Dimensional, Electrical and Capacity Data; Piping and Electrical Connection Drawings.

2.0

PRODUCT

2.1

FRAME
The frame shall be MIG welded, formed sheet metal. It shall be protected against corrosion using the
autophoretic coating process. The frame shall be capable of being separated into three parts in the
field to accommodate rigging through small spaces.

2.1.1

Downflow Configurations

2.1.1.1 Downflow Air Supply with Discharge into Raised Floor


The supply air shall exit from the bottom of the unit directly into the raised floor. The EC fan shall be
mounted on the bottom of the unit. The fan shall be located to draw air through the filters and cooling
coil to ensure even air distribution and maximum coil performance.

2.1.1.1 Downflow Air Supply with Front Air Discharge


The supply air shall exit from the front of the cabinet opening. The EC fan shall be mounted on the
bottom of the unit. The fan shall be located to draw air through the filters and cooling coil to ensure
even air distribution and maximum coil performance.

2.1.1.2 Downflow Air Return


The return air shall enter the unit from the top.

2.1.2

Upflow Supply

2.1.2.1 Upflow Air Supply


The supply air shall exit from the top of the cabinet.

2.1.2.1 Upflow Air Supply, Front Throw


The supply air shall exit from the top of the cabinet with the air flow toward the front of the cabinet.

2.1.2.1 Upflow Air Supply, Rear Throw


The supply air shall exit from the top of the cabinet with the air flow toward the rear of the cabinet.

Liebert DS

170

Guide Specifications

2.1.2.2 Upflow Air Return, Front


The return air shall be through the front factory-installed grilles. The fan shall be above the coil and
pull air through the filters and cooling coil to ensure even air distribution and maximum coil
performance.

2.1.2.2 Upflow Air Return, Rear


The return air shall be through the rear of the cabinet, utilizing a rear return filter box. The fan shall
be above the coil and pull air through the filters and cooling coil to ensure even air distribution and
maximum coil performance.

2.1.3

Exterior Panels
The exterior panels shall be insulated with a minimum 1 in. (25mm), 1.5 lb. (0.68 kg) density fiber
insulation. The main front panel shall have captive 1/4 turn fasteners. The main unit color shall be
______.

2.1.3.1 Double-Skin PanelsOptional


The exterior panels shall be internally lined with 20 gauge sheet metal, sandwiching the insulation
between the panels, for easy cleaning.

2.2

FILTERS
The filter chamber shall be located within the cabinet, and filters shall be removable from the top of
the unit.

2.2.1

Filters, 4" MERV8 or MERV11


Filters shall be deep pleated 4" filters with an ASHRAE 52.2 MERV8 rating (45% ASHRAE 52.1) or
ASHRAE 52.2 MERV11 rating (60-65% ASHRAE 52.1).

2.2.1

Filters, 2" MERV8 Pre-Filter With 2" Filter MERV11


Filters shall be 2" ASHRAE 52.2 MERV8 (45% ASHRAE 52.1) pre-filter, with 2" ASHRAE 52.2
MERV11 (60-65% ASHRAE 52.1) efficiency filter.

2.2.2

Extra Filter Set


____ extra set(s) of filters shall be provided per system.

2.3

FAN SECTION

2.3.1

Electronically Commutated (EC) Fan


The fans shall be plug/plenum type, single inlet and shall be dynamically balanced. The drive package
shall be direct drive, electronically commutated and variable speed. The fans shall be located to draw
air over the A-frame coil to ensure even air distribution and maximum coil performance. EC fans
shall be available on downflow models, and fans may be lowered into a raised floor with a minimum
height of 24" (610mm). EC fans may operate within the Liebert DS cabinet, instead of under the floor.
EC fans shall be available on upflow models and fans shall operate outside the unit in a factory
provided plenum with a minimum height of 24" (610mm).
DS028, DS035 and DS042 fan motor(s) shall be nominal 3.7hp (2.8kW) each with a maximum
operating speed of 1230 rpm; quantity, 1. Liebert Econ-O-Coil gets a 5.4hp (4.0kW) fan for 380-480V
(maximum 1370 rpm).
DS053, DS070 and DS077 fan motors shall be nominal 4.0hp (3.0kW) each with a maximum
operating speed of 1520 rpm; quantity, 2.
DS105 fan motors shall be nominal 3.4hp (2.5kW) each, with a maximum operating speed of 1700
rpm; quantity, 3. (Power rating for 380-480V is 3.4hp (2.5kW); for 200-240V power is
3.6hp [2.7kW].)

171

Liebert DS

Guide Specifications

2.3.1 Centrifugal Blower Section


The blower section shall be designed for ___ CFM (CMH) at an external static pressure of ___ in. wg.
(Pa). The fans shall be the centrifugal type, double-width and double-inlet, and shall be dynamically
balanced as a completed assembly. The shaft shall be heavy duty steel with self-aligning,
permanently sealed, pillow block bearings with a minimum L3 life of 200,000 hours. The fans shall
draw air through the V-frame coil to ensure even air distribution and maximum coil performance. A
static regain duct shall be factory-installed on the bottom of the blower.

2.3.1.1 Motor
The fan motor shall be ____ hp (kW) at 1750 rpm @ 60Hz (1450 rpm @50Hz), mounted to an
automatic, spring-tensioning base. The motor shall be removable from the front of the cabinet.

2.3.1.1.1 Premium Efficiency Motor


The fan motor shall be Open Drip-Proof, Premium efficiency and shall meet NEMA Premium
standard. Motor efficiency shall be ____%.

2.3.1.1.1 TEFC Motor-Optional


The motor shall be Totally Enclosed Fan Cooled for protection in harsh environments.

2.3.2

Drive Package
The motor sheave and fan pulley shall be double-width fixed pitch. Two belts, sized for 200% of the
fan motor horsepower shall be provided with the drive package. An auto-tension system shall provide
constant tension on the belts. Belts, shaft, blower bearings, sheave and pulley shall be warranted for
five years (parts only).

2.4

HUMIDIFIER
A humidifier shall be factory-installed inside the unit. Bypass air slots shall be included to enable
moisture to be absorbed into the air stream. The humidifier capacity shall be ____lb./hr (kg/hr). The
humidifier shall be removable from the front of the cabinet.

2.4.1

Infrared Humidifier
The humidifier shall be of the infrared type, consisting of high-intensity quartz lamps mounted above
and out of the water supply. The humidifier pan shall be stainless steel and arranged to be removable
without disconnecting high-voltage electrical connections. The complete humidifier section shall be
pre-piped, ready for field connection to the water supply. The humidifier shall be equipped with an
automatic water supply system and shall have an adjustable water-overfeed to prevent mineral
precipitation. A high-water detector shall shut down the humidifier to prevent overflowing. A factoryprovided air-gap shall prevent backflow of the humidifier supply water.

2.4.1

Steam Generating Canister Humidifier


A canister-type steam canister shall be factory-installed in the cooling unit and shall be controlled by
the microprocessor control system. It shall be complete with disposable canister, all supply and drain
valves, steam distributor and electronic controls. The need to change the canister shall be indicated
on the microprocessor control panel. The humidifier shall be designed to operate with water
conductivity from 200-500 micromhos. An air-gap within the humidifier assembly shall prevent
backflow of the humidifier supply water.

2.5

REHEAT
The environmental control unit shall include a factory-installed reheat to control temperature during
dehumidification.

2.5.1

Three-Stage Electric Reheat


The electric reheat coils shall be low watt density, 304/304 stainless steel fin tubular construction,
protected by thermal safety switches, shall be ____ kW (____ BTUH) controlled in three stages. The
reheat elements shall be removable from the front of the cabinet.

Liebert DS

172

Guide Specifications

2.5.1

SCR Electric Reheat


The electric reheat coils shall be low watt density, 304/304 stainless steel fin tubular construction,
protected by thermal safety switches, ____ kW (____ BTUH) controlled by multiple pulses to achieve
tight temperature control. The reheat elements shall be removable from the front of the cabinet.

2.5.1

Hot Water Reheat


The hot water reheat coil shall have copper tubes and aluminum fins with a capacity of ____ BTUH
(kW) when supplied with ____ F (C) entering water temperature at ____ GPM (l/s) flow rate.
Maximum pressure drop shall be ____ psi (kPa). The hot water reheat control system shall be factory
pre-piped with a two-way modulating control valve and cleanable Y-strainer.

2.6

DUAL REFRIGERATION SYSTEM


Each unit shall include two (2) independent refrigeration circuits and shall include hot gas mufflers
(semi-hermetic compressors units only), liquid line filter dryers, refrigerant sight glass with moisture
indicator, externally equalized expansion valves and liquid line solenoid valves. Compressors shall be
located outside the airstream and shall be removable and serviceable from the front of the unit.

2.6.1

Semi-Hermetic Compressor with Four-Step Unloaders Control


The compressor shall be semi-hermetic with a suction gas cooled motor, vibration isolators, thermal
overloads, oil sight glass, automatic reset high pressure switch with control lockout after three
failures, pump-down low-pressure transducer, suction line strainer, service valves, reversible oil
pumps for forced feed lubrication, a maximum operating speed of 1750 rpm. The system shall include
cylinder unloaders on the semi-hermetic compressors. The unloaders shall be activated by solenoid
valves which are controlled from the microprocessor control. In response to the return air
temperature, the microprocessor control shall activate the unloader solenoids and the liquid line
solenoids such that four stages of refrigeration cooling are obtained. The stages shall be: 1) one
compressor, partially loaded, 2) two compressors partially loaded, 3) one compressor partially loaded,
one compressor fully loaded, 4) two compressors fully loaded. On a call for dehumidification, the
microprocessor control shall ensure that at least one compressor is on full for proper humidity control.

2.6.1

Digital Scroll Compressors


The compressor shall be scroll-type with a variable capacity operation capability. The compressor
solenoid valve shall unload the compressor and allow for variable capacity operation. The compressor
shall be suction gas cooled motor, vibration isolators, thermal overloads, automatic reset highpressure switch with lockout after three failures, rotalock service valves, pump down low pressure
transducer, suction line strainer and a maximum operating speed of 3500 rpm. Consult factory for
575V availability.

2.6.1

Scroll Compressors
The compressor shall be scroll-type. The compressor shall be suction gas cooled motor, vibration
isolators, thermal overloads, automatic reset high pressure switch with lockout after three failures,
rotalock service valves, pump down low pressure transducer, suction line strainer and a maximum
operating speed of 3500 RPM.

2.6.1.1 Crankcase Heaters


The compressors shall include crankcase heaters, powered from the indoor unit electric panel.

2.6.2

Evaporator Coil
The evaporator coil shall be A-frame design with offset orientation and have ____sq. ft. (m2) face area,
three rows deep. It shall be constructed of rifled copper tubes and aluminum fins and shall have a
maximum face velocity of ____ ft. per minute (m/s) at ____ CFM (m3). A stainless steel condensate
drain pan shall be provided.

2.6.2.1 Polymeric CoatingOptional


The coil shall be coated with a high performance polymeric coating process to provide corrosion
resistance within 2 to 12 pH range.

173

Liebert DS

Guide Specifications

2.6.3

Dual-Cooling Source
The dual-cooling source system shall consist of an air-cooled or water-cooled compressorized system
with the addition of a chilled water coil (Liebert Econ-O-Coil), a modulating control valve and a
comparative temperature sensor. The system shall be able to function either as a modulating chilled
water system or as a compressorized system, or a combination of both. The primary cooling mode
shall be chilled water. Switchover between the two cooling modes shall be performed automatically by
the microprocessor control. Four (4) pipes shall be included on water/glycol systems: Liebert Econ-OCoil supply, Liebert Econ-O-Coil return, condenser supply and condenser return.

2.6.4

Dual-Cooling Source Control Valve


The water circuit shall include a three-way modulating valve. The microprocessor positions the valve
in response to room conditions. Cooling capacity will be controlled by bypassing chilled water around
the coil. The modulating valve travel for dehumidification shall be proportional.

2.6.5

Cu-Ni Coil Optional

A 70/30 Cu-Ni Liebert Econ-O-Coil shall be provided on dual-cooling units that are connected to a
cooling tower loop or other open water system. This option shall be required on open cooling tower
applications.

2.6.6

Polymeric Coating on Liebert Econ-O-Coil

and DX Coil Optional

The coil shall be coated with a high performance polymeric coating process to provide corrosion
resistance within 2 to 12 pH range.

2.6.7

R-407C Refrigerant
The system shall be designed for use with R-407C refrigerant, which meets the EPA clean air act for
phase-out of HCFC refrigerants.

Liebert DS

174

Guide Specifications

3.0

CONTROLS

3.1

LIEBERT iCOM MICROPROCESSOR CONTROL WITH 9-INCH COLOR


TOUCHSCREEN
The Liebert iCOM shall be microprocessor-based with a 9" color touchscreen display and shall be
mounted in an ergonomic, aesthetically pleasing housing. The display and housing shall be viewable
while the front panel is open or closed. The controls shall be menu-driven. The system shall display
user menus for active alarms, event log, graphic data, unit view/status overview (including the
monitoring of room conditions, operational status in percentage of each function, date and time), total
run hours, various sensors, display setup and service contacts. A password shall be required to make
system changes. Service menus shall include setpoints, standby settings (lead/lag), timers/sleep
mode, alarm setup, sensor calibration, maintenance/wellness settings, options setup, system/network
setup, auxiliary boards and diagnostics/service mode.
Password Protection - The Liebert iCOM shall contain two unique passwords to protect
against unauthorized changes. An auto hide/show feature shall allow the user to see applicable
information based on the login used.
Unit Backup and Restore - The user shall be able to create safe copies of important control
parameters. The Liebert iCOM shall have the capacity for the user to automatically backup unit
configuration settings to internal memory or USB storage drive. Configuration settings may be
transferred to another unit for a more streamlined unit startup.
Parameter Download - The Liebert iCOM shall enable the user to download a report that
lists parameter names, factory default settings and user programmed settings in .csv format for
remote reference.
Parameter Search - The Liebert iCOM shall have search fields for efficient navigation and
parameter lookup.
Setup Wizards - The Liebert iCOM shall contain step-by-step tutorials or wizards to provide
easy setup of the control.
Context-Sensitive Help - The Liebert iCOM shall have an onboard help database. The
database shall provide context-sensitive help to assist with setup and navigation of the menus.
Display Setup - The user shall be able to configure the display information based on the
specific users preference. Language, units of measure, screen contrast, home screen layout,
backlight timer and the hide/show of certain readouts shall be configurable through the display.
Additional Readouts - The display shall enable the user to configure custom widgets on the
main screen. Widget options will include items such as fan speed, call for cooling, call for freecooling, maintenance status, call for hot water reheat, call for electric reheat, call for
dehumidification, call for humidification, airflow, static pressure, fluid flow rate and cooling
capacity.
Status LEDs - The Liebert iCOM shall show the units operating status using an integral
LED. The LED shall indicate if the unit has an active alarm; if the unit has an active alarm that
has been acknowledged; or if the unit is On, Off or in standby status.
Event Log - The Liebert iCOM shall automatically store the last 400 unit-only events
(messages, warnings, and alarms).
Service Contact Information - The Liebert iCOM shall be able to store the local service or
sales contact information.
Upgradeable - Liebert iCOM upgrades shall be performed through a USB connection.
Timers/Sleep Mode The menus shall allow various customer settings for turning the unit
On or Off.
Menu Layout - The menus shall be divided into two main menus: User and Service. The User
screen shall contain the menus to access parameters required for basic unit control and setup.

175

Liebert DS

Guide Specifications

The Service screen shall be designed for service personnel and shall provide access to advanced
control setup features and diagnostic information.
Sensor Calibration - The menus shall allow unit sensors to be calibrated with external
sensors.
Maintenance/Wellness Settings - The menus shall allow reporting of potential component
problems before they occur.
Options Setup - The menus shall provide operation settings for the installed components.
Auxiliary Boards - The menus shall allow setup of optional expansion boards.
Various Sensors: The menus shall allow setup and display of optional custom sensors. The
control shall include four customer accessible analog inputs for field-supplied sensors. The analog
inputs shall accept a 4 to 20mA signal. The user shall be able to change the input to 0 to 5VDC or
0 to 10VDC. The gains for each analog input shall be programmable from the front display. The
analog inputs shall be able to be monitored from the front display.
Diagnostics/Service Mode - The Liebert iCOM control shall be provided with self-diagnostics
to aid in troubleshooting. The microcontroller board shall be diagnosed and reported as pass/not
pass. Control inputs shall be indicated as On or Off at the front display. Control outputs shall be
able to be turned On or Off from the front display without using jumpers or a service terminal.
Each control output shall be indicated by an LED on a circuit board.

3.2

ALARMS
All unit alarms shall be annunciated through both audio and visual cues, clearly displayed on the
screen, automatically recorded in the event log and communicated to the customers Building
Management System/Building Automation System. The Liebert iCOM control shall activate an
audible and visual alarm in event of any of the following conditions:

High Temperature
Low Temperature
High Humidity
Low Humidity
EC Fan Fault
Change Filters
Loss of Air Flow
Loss of Power
Compressor Overload (Optional)
Humidifier Problem
High Head Pressure
Low Suction Pressure
Custom Alarms

Custom alarm inputs shall be provided to indicate facility-specific events. Custom alarms can be
identified with programmable labels. Frequently used alarm inputs include:
Leak Under Floor
Smoke Detected
Standby Unit On
Each alarm (unit and custom) shall be separately enabled or disabled, selected to activate the
common alarm and programmed for a time delay of 0 to 255 seconds.

Liebert DS

176

Guide Specifications

3.3

LIEBERT iCOM CONTROL METHODS AND OPTIONS


The Liebert iCOM shall be factory-set to allow precise monitoring and control of the condition of the
air entering and leaving the unit. This control shall include predictive methods to control air flow and
cooling capacity based control sensors installed. Proportional and Tunable PID shall also be userselectable options.

3.3.1

Controlling Sensor Options


Liebert iCOM shall be flexible in the sense that it shall allow for controlling the capacity and fan from
multiple different sensor selections. The sensor selections shall be:

3.3.1.1 Cooling Capacity


Supply
Remote
Return

3.3.1.2 Fan Speed


Supply
Remote
Return
Manual (for diagnostic or to receive a signal from the BMS through the Liebert remote
monitoring devices or analog input)
Static Pressure

3.3.2

Temperature Compensation
The Liebert iCOM shall be able to adjust the capacity output based on supply and return temperature
conditions to meet SLA guidelines while operating to highest efficiency.

3.3.3

Humidity Control
Dew point and relative humidity control methods shall be available (based on user preference) for
humidity control within the conditioned space.

3.4

MULTI-UNIT COORDINATION
Liebert iCOM teamwork shall save energy by preventing multiple units in an area from operating in
opposing modes. Teamwork allows the control to optimize a group of connected cooling units equipped
with Liebert iCOM using the U2U (Unit-to-Unit) network. There shall be three modes of teamwork
operation:
Teamwork Mode 1: Is best in small rooms with balanced heat loads. The controlling
temperature and humidity sensor readings of all units in operation (fan On) are collected to be
used for an average or worst-case sensor reading (user-selectable). The master unit shall send the
operating requirements to all operating units in the group. The control band (temperature, fan
and humidity) is divided and shared among the units in the group.
Teamwork Mode 2: The Liebert iCOM calculates the worse-case demand for heating, cooling
humidification and dehumidification. Based on the greatest demand within the group, each unit
operates independently, meaning that the unit may respond to the thermal load and humidity
conditions based on the units controlling sensors.
Teamwork Mode 3 - Optimized Aisle: May be employed in large and small rooms with
varying heat loads. Optimized Aisle is the most efficient teamwork mode that allows the unit to
match cooling capacity with heat load. In the Optimized Aisle mode, the fans operate in parallel.
Fans can be controlled exclusively by remote temperature or using static pressure with a
secondary remote temperature sensor(s) as an override to ensure that the inlet rack temperature
is being met. Cooling (Compressors or Economizer) is controlled through unit supply air
conditions. Liebert iCOM calculates the average or worst-case sensor reading (user-selectable) for
heating, cooling humidification and dehumidification. Based on the demand within the group,
units will be allowed to operate within that mode until room conditions are satisfied.

177

Liebert DS

Guide Specifications

3.5

STANDBY LEAD-LAG
The Liebert iCOM shall allow scheduled rotation to keep equal run time on units and provide
automated emergency rotation of operating and standby units.

3.6

STANDBY UNIT CASCADING


The Liebert iCOM cascade option shall allow the units to turn On and Off based on heat load when
utilizing Optimized Aisle, Teamwork Mode 3 and remote temperature sensors. Cascade mode
dynamically coordinates the fan speed to save energy and to meet the cooling demands. For instance,
with a Liebert iCOM group of six units and only 50% of the heat load, the Liebert iCOM shall operate
only four units at 80% fan speed and leave the other two units in standby. As the heat load increases,
the Liebert iCOM shall automatically respond to the additional load and bring on another unit,
increasing the units in operation to five. As the heat load shifts up or down, the control shall meet the
needs by cascading units On or putting them into standby.

3.7

WIRED SUPPLY SENSOR


Each Liebert iCOM shall have one factory-supplied and connected supply air sensor that may be used
as a controlling sensor or reference. When multiple sensors are applied for control purposes, the user
shall be able to control based on a maximum or average temperature reading.

3.8

VIRTUAL MASTER
As part of the robust architecture of the Liebert iCOM control, it shall allow for a virtual master that
coordinates operation. The Virtual Master function shall provide smooth control operation if the
groups communication is compromised. When the lead unit, which is in charge of component staging
in teamwork, unit staging and standby rotation, becomes disconnected from the network, the Liebert
iCOM shall automatically assign a virtual master. The virtual master shall assume the same
responsibilities as the master until communication is restored.

3.9

VIRTUAL BACK-DRAFT DAMPER


The Liebert iCOM shall allow the use of a virtual back-draft damper, eliminating the need for a
mechanical damper. This shall allow the fans to spin slower (15% or less) to act as a damper.

3.10

COMPRESSOR SHORT CYCLE CONTROL


To help maximize the life of the compressor(s), there shall be start-to-next start delay for each single
compressor. The control shall monitor the number of compressor starts in an hour. If the compressor
starts more than 10 times in 60 minutes, the local display and remote monitoring shall notify the user
through a Compressor 1 or 2 Short Cycle event.

3.11

SYSTEM AUTO RESTART


The auto restart feature shall automatically restart the system after a power failure. Time delay shall
be programmable. An optional capacitive buffer may be provided for continuous control operation
through a power failure.

3.12

SEQUENTIAL LOAD ACTIVATION


On initial startup or restart after power failure, each operational load shall be sequenced with a
minimum delay of one second to minimize total inrush current.

3.13

LOW-PRESSURE MONITORING
Units shall ship standard with low-pressure transducers for monitoring individual compressor
suction pressure. If the pressure falls due to loss of charge or other mechanical cause, the
corresponding circuit shall shut down to prevent equipment damage. The user shall be notified of the
low-pressure condition through the local display and remote monitoring.

Liebert DS

178

Guide Specifications

3.14

WINTER START TIME DELAYAIR-COOLED MODELS


An adjustable software timer shall be provided to assist with compressor starting during cold
weather. When the compressor starts, the low-pressure input shall be ignored for the period set in the
user-adjustable timer. Once the time period has elapsed after the compressor start, the low-pressure
input should remain in the normal state. If the low-pressure input does not remain in the normal
state when the time delay has elapsed, the circuit shall lock out on low pressure. The low-pressure
alarm shall be announced on the local display and communicated to remote monitoring systems.

3.15

ADVANCED FREEZE PROTECTION


Units shall ship standard with advanced freeze protection enabled. The advanced freeze protection
shall monitor the pressure of each circuit using a transducer. The control shall interact with the fan
and compressor to prevent the unit coil from freezing if circuit suction pressure drops. If a freeze
condition is detected, the user shall be notified through the local display and remote monitoring
systems.

3.16

ADVANCED HIGH-PRESSURE PROTECTIONWATER/GLYCOL-COOLED


MODELS WITH DIGITAL SCROLL COMPRESSORS
When the compressor is initially activated, the system shall be monitored for high pressure. When
high pressure is detected, the control shall alter the compressor operation to reduce the system
discharge pressure, preventing circuit shut down. If the unit is unsuccessful in correcting the problem
through this interaction, an alarm shall occur and the affected compressor shall be immediately
locked off. The control shall re-enable the compressor when the pressure returns to a safe level.

3.17

REFRIGERANT PRESSURE TRANSDUCER FAILURE


The control shall monitor the high-side and low-side refrigerant pressure transducers. If the control
senses the transducer has failed, has been disconnected, has shorted or the reading has gone out of
range, the user shall be notified through an event on the local display and remote monitoring. The
corresponding circuit that the failure has occurred on shall be disabled to prevent unit damage.

3.18

OIL RETURN PROTECTION


The control shall monitor compressor operation and staging to ensure that liquid and hot gas velocity
are maintained for proper oil return to the compressor.

3.19

DIGITAL SCROLL HIGH-TEMPERATURE PROTECTION


The control shall monitor digital scroll temperature during unit operation. A compressor temperature
limit shall be imposed to help prevent damage to the compressor. If the temperature reaches the
maximum temperature limit, the compressor shall be locked out and an alarm shall be annunciated
on the local display and through monitoring. After the initial lockout, the control shall continue to
monitor compressor temperature during the off-cycle and re-enable the circuit once a safe operating
temperature is reached. The control shall store the number of high-temperature trips. The number of
trips shall be accessible through the local display.

3.20

DIGITAL SCROLL SENSOR FAILURE


The control shall monitor the status of the digital scroll sensor(s). If the control senses that the
thermistor is disconnected, shorted or the reading goes out of range, the user shall be notified through
an event on the local display and remote monitoring.

179

Liebert DS

Guide Specifications

3.21

COMPRESSOR SEQUENCING
A user-selectable compressor sequencing parameter shall be provided and shall be accessible through
the local display. This sequencing parameter shall present the user with three choices:
Always use Compressor 1 as the lead compressor.
Always use Compressor 2 as the lead compressor.
Auto: The unit shall automatically stage compressors to keep each units run time within 8
hours of the others run time.
First priority: If the safety timings are acceptable for only one compressor, then it is the
next to be started/stopped.
Second priority: If both compressors are Off: The compressor with fewer working hours is
the next to start.
Third priority: If both compressors are in operation: the compressor that has been operating
longer since the last start is the next to be stopped.

3.22

COMPRESSOR HIGH- AND LOW-TEMPERATURE LIMIT PROTECTION


The control shall monitor the return air to ensure that the compressor(s) are operated within the
manufacturers defined window of operation. If the return air temperature deviates from the
manufacturers window of operation, the Liebert iCOM shall automatically adjust to prevent damage
to the cooling unit or reduction in its reliability.

3.23

COMPRESSOR RUN TIME MONITORING


The control shall log these compressor statistics:

Number of compressor starts


Run hours
Average run time
Starts per day
Starts per day worst
Number of high-pressure alarms
Operating phase in which the high-pressure alarm occurred
Number of low-pressure alarms
Operating phase in which the low-pressure alarm occurred
Number of compressor overloads
Number of high-temperature alarms (scroll compressors)

The user shall have the ability to monitor compressor operating temperature and pressure from the
local display to be used as a diagnostic tool.

3.24

MANUAL COMPRESSOR DISABLEMENT


The user shall have the ability to disable compressor operation using a set of either normally open or
normally closed dry contacts tied directly to the control or through remote monitoring. An additional
enable/disable feature shall be provided to allow the user to permanently disable an individual
compressor circuit for maintenance using the local display.

3.25

MANUAL COMPRESSOR OPERATION


The user shall be able to operate each compressor(s) manually from the local display. The user shall
be able to energize refrigeration components including liquid line solenoid valves, compressor
contactors, electronic expansion valves and adjust capacity for troubleshooting or repair. The control
shall monitor the compressor during manual operation and shall shut the compressor down if needed
to prevent electrical or mechanical damage.

Liebert DS

180

Guide Specifications

3.26

FLOODED START PROTECTION


The control shall isolate each compressor through a dedicated circuit liquid line solenoid valve and/or
electronic expansion valve. These devices, combined with a spring-closed discharge check valve and
compressor crankcase heater (air-cooled models), shall help ensure refrigerant does not migrate/carry
oil out of the compressor case during the off cycle.

3.27

COMPRESSOR DEHUMIDIFICATION
The control shall permit the user to specify which compressor is used for dehumidification. The
choices shall be 1st compressor, 2nd compressor, 1 or 2, or BOTH.

4.0

MISCELLANEOUS OPTIONS

4.1

NON-LOCKING DISCONNECT SWITCHOPTIONAL


The manual disconnect switch shall be mounted in the high-voltage section of the electrical panel.
The switch shall be accessible with the door closed.

4.2

LOCKING DISCONNECT SWITCHOPTIONAL


The manual disconnect switch shall be mounted in the high-voltage section of the electrical panel.
The switch shall be accessible from the outside of the unit with the door closed and shall prevent
access to the high-voltage electrical components until switched to the Off position.

4.3

HIGH TEMPERATURE SENSOROPTIONAL


The firestat shall be factory-installed in the unit and shall be factory-set to 125F (52C). It shall
immediately shut down the environmental control system when activated. The sensor shall be
mounted with the sensing element in the return air.

4.4

SMOKE SENSOROPTIONAL
The smoke sensor shall immediately shut down the environmental control system and activate the
alarm system when activated. The smoke sensor shall be mounted in the electrical panel with the
sensing element in the return air compartment. The smoke sensor is not intended to function as or
replace any room smoke detection system that may be required by local or national codes. The smoke
sensor shall include a supervision contact closure.

4.5

CONDENSATE PUMP, DUAL FLOATOPTIONAL


The condensate pump shall have a minimum capacity of 145 GPH (548 l/h) at 20 ft. (58 kPa) head. It
shall be complete with integral dual-float switches, pump-and-motor assembly and reservoir. The
secondary float shall send a signal to the local alarm and shall shut down the unit upon high water
condition.

4.6

LOW-VOLTAGE TERMINAL PACKAGEOPTIONAL


Factory-installed and factory-wired terminals shall be provided for customer connection to lock out
the reheat and humidifier upon contact closure. Two extra normally open common alarm contacts
shall be provided. Two extra remote shutdown terminals shall be provided.

4.7

REMOTE HUMIDIFIER CONTACTOPTIONAL


A pair of normally open contacts shall be provided for connection to a remote humidifier.

4.8

MAIN FAN OVERLOADOPTIONAL


A pair of normally open contacts shall be factory-installed and wired to indicate Main Fan Overload.

4.9

COMPRESSOR OVERLOADOPTIONAL
A pair of normally open contacts shall be factory-installed and factory-wired to each compressor to
indicate Compressor Overload.

181

Liebert DS

Guide Specifications

4.10

WIRED SUPPLY SENSOR(S)OPTIONAL


Each Liebert iCOM shall have up to 10 optional supply air sensors connected and used as a
controlling sensors or reference. This shall be in addition to the standard factory-supplied supply air
sensor. When multiple sensors are applied for control purposes, the user shall be able to control based
on a maximum or average temperature reading.

4.11

WIRED REMOTE SENSOR(S)OPTIONAL


Each Liebert iCOM shall have up to ten 2T sensors (20 sensor readings total) for control or reference.
As part of the U2U network, those sensors shall be shared and used to control the units and provide
greater flexibility, visibility and control using that to respond to changes in the data center. When the
sensors are used for control, the user may set the control to be based off a maximum or average of a
select highest temperature reading.

4.12

STATIC PRESSURE TRANSDUCER(S)OPTIONAL

Each Liebert iCOM shall have up to four factory-installed and factory-programmed static pressure
transducer(s). The transducer(s) may be used for control of fan speed or reference of the supply
plenum pressure. When used for control, the Liebert iCOM shall be capable of:
Sharing sensor data across multiple units in the U2U network to provide greater flexibility,
visibility and control. Only one transducer shall be required for a group of units however multiple
transducers may be applied per group and aggregated for redundancy.
Offering the user selections to control fan from either the average or lowest pressure reading
collected in the U2U network.

4.13

AIR FLOW MONITORINGOPTIONAL


The Liebert iCOM shall monitor evaporator fan airflow for monitoring purpose.

4.14

REMOTE MONITORINGOPTIONAL
A factory-installed communication card shall be provided for monitoring and/or control. The
communication card shall be capable of connecting to Building Management System/Building
Automation System using the following protocols:
BACnet IPBACnet over Internet Protocol
BACnet MSTPBACnet Master-Slave/Token-Passing (MSTP) communications protocol over
a RS-485 serial network (also known as BACnet MSTP RS-485)
Modbus RTUModbus Remote Terminal Unit (RTU) communication protocol over a RS-485
serial network (also known as Modbus RTU RS-485)
Modbus TCPModbus Transmission Control Protocol over Internet Protocol (also known as
Modbus TCP/IP)
SNMP
YDN23 - YD-T-1363 specification protocol (also known as YD/T 1363)
The communications card shall be capable of connecting to two of these protocols at once.

4.15

POWER MONITORINGOPTIONAL
The unit shall be equipped with factory-programmed/installed power meters to monitor power
characteristics for either individual components or the total unit. These meters shall allow the user to
monitor meter connection status, input undervoltage, input RMS voltage leg-to-leg and leg-to-ground,
input current for each phase, energy consumption in kilowatt hours and instantaneous power in
watts. In multi-unit applications, a phase loss protection routine shall place a unit into standby mode
in the event.

Liebert DS

182

Guide Specifications

4.16

OPTIONS-AIR-COOLED SYSTEMS - MC CONDENSER


The indoor evaporator unit shall include refrigerant piping, with a factory holding charge of nitrogen.
The hot-gas and liquid lines shall be spun shut and shall include a factory-installed Schrader valve.
Field-relief of the Schrader valve shall indicate a leak-free system.

4.16.1 Air-Cooled Condenser


Condenser shall consist of microchannel condenser coil(s), propeller fan(s) direct-driven by individual
fan motor(s), electrical controls, housing and mounting legs. The Liebert air-cooled condenser shall
provide positive refrigerant head pressure control to the indoor cooling unit by adjusting heat
rejection capacity. Microchannel coils shall provide superior heat transfer, reduce air-side pressure
drop, increase energy efficiency and significantly reduce the system refrigerant volume required. EC
fans and fan operating techniques shall provide reduced maximum sound levels. Various methods
shall be available to match indoor unit type, maximum outdoor design ambient and maximum sound
requirements.

4.16

OPTIONS-AIR-COOLED SYSTEMS - FIN TUBE CONDENSER


The indoor evaporator unit shall include refrigerant piping, with a factory holding charge of nitrogen.
The hot-gas and liquid lines shall be spun shut and shall include a factory-installed Schrader valve.
Field-relief of the Schrader valve shall indicate a leak-free system.

4.16.1 Air-Cooled Condenser


The Liebert-manufactured outdoor air-cooled condenser shall be the low profile, multiple direct drive,
propeller fan type. The condenser shall balance the heat rejection of the compressor at ____ F (C)
ambient. The condenser shall be constructed of aluminum and contain a copper tube, aluminum fin
coil arranged for (horizontal) (vertical) air discharge.

4.16.2 Fan Speed Control


The winter control system for the air-cooled condenser shall be Liebert Fan Speed Control. The
variable speed motor shall operate from 0 to 230 volts single phase, 10 to 1050 RPM. It shall be
designed with ball bearings, permanent lubrication, internal overload protection, 40C rise at full
speed, 65C rise at 10 RPM. The control system shall be complete with transducers, thermostats and
electrical control circuit, factory prepackaged in the integral condenser control box. The transducer
shall automatically sense the highest head pressure of either operating compressor and control the
variable speed fan on the air-cooled condenser to properly maintain the head pressure. The Liebert
Fan Speed Control system shall provide positive startup and operation in ambient temperatures as
low as -20F (-28.9C). The air-cooled condenser shall have a ____ volt, ____ ph ____ Hz power supply.

4.16.3 Liebert Lee-Temp System


The winter control system for the air-cooled condenser shall be Liebert Lee-Temp. The Liebert LeeTemp system shall allow startup and positive head pressure control with ambient temperatures as
low as -30F (-34.4C). The Liebert Lee-Temp package shall include the following components for each
refrigeration circuit: insulated receiver, pressure relief valve, head pressure three-way control valve
and rotalock valve for isolating the refrigerant charge. The Liebert Lee-Temp receiver shall be
factory-insulated and mounted ready for the field-connection to the air-cooled condenser. The Liebert
Lee-Temp heater shall require a separate power supply of ____ volt, single phase.

4.16.4 Quiet-Line Condenser-Optional


Fan motors shall be 12-pole, 570 RPM, equipped with rain shields and permanently sealed ball
bearings. Motors shall include built-in overload protection. Motors shall be rigidly mounted on
die-formed galvanized steel supports. Disconnect switch shall be a standard feature.

4.16.5 Condenser Disconnect Switch-Optional


A disconnect switch shall be factory-mounted and wired to the condenser control panel, accessible
from the exterior (standard on Quiet-Line models).

183

Liebert DS

Guide Specifications

4.16

OPTIONS-WATER/GLYCOL SYSTEMS

4.16.1 Paradenser Condenser


The water-cooled condensers for each circuit shall be cleanable, shell-and-tube, counter flow type. The
heads shall be removable to allow for cleaning of the water tubes. Condensers shall be rated for a
maximum refrigerant pressure of 400 psi at 200F (2758 kPa at 93.3C). The condenser shall be
capable of operating with R-22 or R-407C refrigerant. The unit shall require ____ GPM (l/m) of ____ F
(C) water and have a maximum pressure drop of ____ psi (kPa).

4.16.2 Water/Glycol Regulating Valve, Two-Way With Bypass


The condenser shall be pre-piped with a two-way regulating valve which is head pressure actuated. A
gate-valve shall bypass the regulating valve.

4.16.2 Water/Glycol Regulating Valve, Three-Way


The condenser shall be pre-piped with a three-way regulating valve which is head pressure actuated.

4.16.3 Pressure Rating, 150 psi (1034 kPa)


The condenser water circuit shall be designed for a pressure of 150 psi (1034 kPa)

4.16.3 Pressure Rating, 350 psi (2413 kPa)


The condenser water circuit shall be designed for a pressure of 350 psi (2413 kPa)

4.16

OPTIONS-GLYCOOL SYSTEMS

4.16.1 GLYCOOL Coil


The GLYCOOL (Liebert Econ-O-Coil) shall be constructed of copper tubes and aluminum fins. The
coil shall be A-frame or V-frame to minimize air pressure drop and shall be nested with the DX coil.
The Liebert Econ-O-Coil shall be upstream of the DX coil to enable pre-cooling of the air. The Liebert
Econ-O-Coil shall have a net sensible cooling capacity of ____ BTUH (kW) with 45F (7.2C) entering
glycol solution temperature. The system shall require ____ GPM (l/s) and the total unit pressure drop
shall not exceed ____ feet of water (kPa), when in the Liebert Econ-O-Coil mode of operation.

4.16.2 GLYCOOL Three-Way Control Valve


The GLYCOOL coil shall be equipped with a fully proportional three-way control valve. This
motorized control valve shall control the amount of flow to the GLYCOOL (Econ-O-Coil) coil to control
room temperature and relative humidity.

4.16.3 High Pressure System, 350 psi (2413 kPa)


The GLYCOOL system shall be designed for a pressure of 350 psi (2413 kPa).

4.16.4

Cu-Ni Econ-O-Coil
A 70/30 Cu-Ni Econ-O-Coil shall be provided for when the Liebert Econ-O-Coil is cooling tower loop or
other open water system. This option shall be required on open cooling tower applications.

Liebert DS

184

Guide Specifications

4.17 OPTIONS-DRYCOOLER
The drycooler shall be the low profile, slow speed, multiple direct drive, propeller fan type. The
drycooler shall be constructed of aluminum and contain a copper tube aluminum fin coil with an
integral electric control panel and disconnect switch. The drycooler shall be designed for ____ F (C)
ambient.

4.17.1 Pump Package


This system shall be provided with a centrifugal pump mounted in a weatherproof and vented
enclosure. The pump shall be rated for ____ GPM (l/m) at ____ ft. of head (kPa) and operate on ____
volt, 3-phase, ____ Hz.

4.17.1 Dual Pump Package

4.18

The dual pump package shall include pumps, enclosure, field-mounted flow switch and a separate,
factory-wired control box (including a lead-lag switch for the pumps). The standby pump shall
automatically start upon failure of the lead pump. Each pump shall be rated for ____ GPM (l/s) at ____
feet of head (kPa).

LIEBERT LIQUI-TECT SENSORS

Provide ____ (quantity) solid state water sensors under the raised floor.

4.19

FLOOR STAND
The floor stand shall be constructed of a welded steel frame. The floor stand shall have adjustable legs
with vibration isolation pads. The floor stand shall be ____ inches (mm) high.

4.19.1 Seismic Rated Floor Stand-Optional


The floor stand shall be seismic rated and shall be bolted to the unit frame.

4.19.1 Floor Stand Turning Vane-Optional


A turning vane shall be supplied with the floor stand and shall be designed for the specified floor
stand height.

4.20

RETURN AIR PLENUM FOR DOWNFLOW UNITS


The air plenum shall be constructed of 20 gauge steel, powder coated to match unit color. The plenum
shall be ___" (mm) high. A door shall be included in the front of the plenum to enable front filter
access. Air shall enter the plenum from the top.

4.21

DISCHARGE AIR PLENUM FOR UPFLOW UNITS, WITH DISCHARGE GRILLE(S)


The air plenum shall be constructed of 20 gauge steel, powder coated to match unit color. The plenum
shall be ___" (mm) high. Discharge air grilles shall be painted black and shall be included on the
(front), (rear), (left side) or (right side) of the plenum.

4.22

DISCHARGE AIR PLENUM FOR UPFLOW UNITS, WITHOUT DISCHARGE


GRILLE(S)
The air plenum shall be constructed of 20 gauge steel, powder-coated to match unit color. The plenum
shall be ___" (mm) high. Air shall discharge from the top of the plenum.

185

Liebert DS

Guide Specifications

5.0

EXECUTION

5.1

INSTALLATION OF THERMAL MANAGEMENT UNITS

5.1.1

General
Install Thermal Management units in accordance with manufacturers installation instructions.
Install units plumb and level, firmly anchored in locations indicated and maintain manufacturers
recommended clearances.

5.1.2

Electrical Wiring
Install and connect electrical devices furnished by manufacturer but not specified to be factorymounted. Furnish copy of manufacturers electrical connection diagram submittal to electrical
contractor.

5.1.3

Piping Connections
Install and connect devices furnished by manufacturer but not specified to be factory-mounted.
Furnish copy of manufacturers piping connection diagram submittal to piping contractor.

5.2

FIELD QUALITY CONTROL


Start Thermal Management units in accordance with manufacturers startup instructions. Test
controls and demonstrate compliance with requirements. These specifications shall describe
requirements for a computer room environmental control system. The system shall be designed to
maintain temperature and humidity conditions in the rooms containing electronic equipment.
The manufacturer shall design and furnish all equipment to be fully compatible with heat dissipation
requirements.

Liebert DS

186

Technical Support / Service


Web Site
www.liebert.com
Monitoring
liebert.monitoring@emerson.com
800-222-5877
Outside North America: +00800 1155 4499
Single-Phase UPS & Server Cabinets
liebert.upstech@emerson.com
800-222-5877
Outside North America: +00800 1155 4499
Three-Phase UPS & Power Systems
800-543-2378
Outside North America: 614-841-6598
Environmental Systems
800-543-2778
Outside the United States: 614-888-0246

Locations

While every precaution has been taken to ensure the accuracy


and completeness of this literature, Liebert Corporation assumes no
responsibility and disclaims all liability for damages resulting from use of
this information or for any errors or omissions.
2014 Liebert Corporation
All rights reserved throughout the world. Specifications subject to change
without notice.
Liebert is a registered trademark of Liebert Corporation.
All names referred to are trademarks
or registered trademarks of their respective owners.

United States
1050 Dearborn Drive
P.O. Box 29186
Columbus, OH 43229
Europe
Via Leonardo Da Vinci 8
Zona Industriale Tognana
35028 Piove Di Sacco (PD) Italy