Introduction

Fuses are need to be replaced after they operate


Circuit Breakers are designed to open automatically
when the current exceeds a threshold.
Can be opened and closed manually. Not destroyed
by its normal operation

2/15/2016

s.amirthavalli

assistant director

Switchgear and Protection/Control-Panels are installed at


each voltage levels at each switching point for

1. Normal routine switching, control and monitoring


and
2. Automatic switching during abnormal and faulty
operating conditions such as short circuits, under-voltage,
overloads.

2/15/2016

s.amirthavalli

assistant director

The main function of circuit breaker is

1. Switching during normal operating conditions


for the purpose of operation and maintenance.
2. Switching during abnormal conditions such as
short circuits and interrupting the fault currents.

2/15/2016

s.amirthavalli

assistant director

Circuit Breakers
Basically, an AC circuit breaker is a piece
of switchgear that can
withstand the momentary short-circuit current
interrupt the short-circuit current at the current
zero following contact parting
withstand the transient recovery voltage across
its open contacts

2/15/2016

s.amirthavalli

assistant director

Interrupting time
Contact parting time
Tripping
delay

Opening
time

Arcing
time

t
Initiation
of short
circuit

Trip
circuit
energized

Primary
contacts
part

Arc on
primary
contacts
extinguished

Sequence of events in AC circuit breaking: after relays


detect fault and energize trip coil, breaker contacts open,
arc is established and then extinguished at a current zero
2/15/2016

s.amirthavalli

assistant director

Types of Circuit Breakers


Low voltage (less than 1000 V) or
medium and high voltage. Molded case or
power circuit breakers
Operating medium
Low-voltage circuit breakers use air
Higher-voltage circuit breakers can use oil,
SF6 gas, or a vacuum

2/15/2016

s.amirthavalli

assistant director

Ways to Control Arcing


Arc chutes

Parallel plates placed above the contacts to


divert the arc
Arc forced into the arc chutes
Small arcs travel up the chutes Use other
mediums
Medium and high voltage
2/15/2016

s.amirthavalli

assistant director

Mediums of arc quenching


Air blast.

Force air between the contacts to


lengthen the arc.
Oil to quench the arc formation.

SF6.
Vacuum Quenches the arc.

2/15/2016

s.amirthavalli

assistant director

Arcing Problems
Inductive loads will cause substantial arcs
when knife switches are used
Arcs consist of ionized air through which
currents flow
Arcs are extinguished when the contacts are far
apart

2/15/2016

s.amirthavalli

assistant director

Ways to Limit Arcing


Speed

Springs to quickly force the contacts apart


Limits the duration and severity Arcing
contacts
Arcing leads to pitting of the contacts

Two sets of contacts


Main contacts with good conduction
Arcing contacts with heavy-duty surface
2/15/2016

s.amirthavalli

assistant director

10

METHODS OF ARC EXTINCTION

1. High resistance Interruption:


a. Lengthening the arc by means of arc runners.
b. Splitting of Arc.
c. Cooling of Arc.
2. Current Zero Interruption or Low resistance method.
3. Artificial current zero Interruption.

2/15/2016

s.amirthavalli

assistant director

11

TYPES OF CIRCUIT BREAKERS


1. AIR CIRCUIT BREAKER
a. Plain Break type
b. Magnetic blow out type
c. Air blast circuit breaker.
2. OIL CIRCUIT BREAKER
a. Bulk oil circuit breaker
b. Minimum or small oil circuit breaker.
3. SULPHUR HEXA FLORIDE CIRCUIT BREAKER
4. VACUUM CIRCUIT BREAKER.
2/15/2016

s.amirthavalli

assistant director

12

AIR CIRCUIT BREAKER


Principle:
Arc interruption process is based on natural
DEIONISATION of gases by COOLING ACTION

VARIOUS TYPES OF ACB


PLAIN BREAK TYPE

MAGNETIC BLOW-OUT TYPE


ARC SPLITTER TYPE
2/15/2016

s.amirthavalli

assistant director

13

PLAIN BREAK TYPE


The circuit breaker contacts are made in
shape of horn.
Arc strikes across the shortest distance
between
horns.

As contacts go on separating, gap


between them
increases.
when horns are fully separated arc is
lengthened and cooled arc is extinguished.
2/15/2016

s.amirthavalli

assistant director

14

2/15/2016

s.amirthavalli

assistant director

15

DIS ADVANTAGES AND LIMITATIONS


SLOWNESS OF PROCESS
ARC IS SPREADING TO ADJACENT METAL
WORK

APPLICATION:
VOLTAGE IS 500V, APPLICABLE TO LOW POWER
CIRCUITS

2/15/2016

s.amirthavalli

assistant director

16

MAGNETIC BLOW-OUT TYPE


Extinction of arc is carried out by means of
magnetic blast.
The arc is subjected to the magnetic field set
up by coils connected in series with circuit
being interrupted.
The magnetic blow out coils help the arc being
magnetically blown out.
Arc is blown into magnetically into arc chutesarc is lengthened, cooled and extinguished.
Arc shield prevents spreading of arc to
adjacent metal work.
2/15/2016

s.amirthavalli

assistant director

17

2/15/2016

s.amirthavalli

assistant director

18

ARC CHUTE
It confines the arc within a restricted space.
It provides magnetic control of the
movement of arc, so that extinction occurs
within the device.
Provides rapid cooling of gases to ensure
extinction by DEIONISATION.

2/15/2016

s.amirthavalli

assistant director

19

2/15/2016

s.amirthavalli

assistant director

20

2/15/2016

s.amirthavalli

assistant director

21

ARC SPLITTER TYPE


The blow out consists of steel inserts in the
arching chutes
It is arranged so that the magnetic field
induced in them by the current in the arc
moves upwards still faster.
Steel plates divide the arc into number of
short arc in series.
2/15/2016

s.amirthavalli

assistant director

22

ARC SPLITTER TYPE(cont..)


Distribution of voltage along length of arc
across plates are not linear and have large
voltage drop.
Voltage drop helps for quick extinction.
Arc come in contact with cool surface are of
steel plates, it gets rapidly and effectively
cooled.
2/15/2016

s.amirthavalli

assistant director

23

TRANSIENT RECOVERY VOLTAGE

2/15/2016

s.amirthavalli

assistant director

24

2/15/2016

s.amirthavalli

assistant director

25

2/15/2016

s.amirthavalli

assistant director

26

2/15/2016

s.amirthavalli

assistant director

27

2/15/2016

s.amirthavalli

assistant director

28

2/15/2016

s.amirthavalli

assistant director

29

2/15/2016

s.amirthavalli

assistant director

30

2/15/2016

s.amirthavalli

assistant director

31

MERTIS OF ABCB
Can be used at high pressure.
Reliable operation due to external source of
extinguishing energy.
Free from decomposition.
Freely available everywhere.
At high pressure, small contact travel is
enough.
2/15/2016

s.amirthavalli

assistant director

32

MERTIS OF ABCB(contd..)
Same air serves the purpose of moving the
contact and arc extinction.
Demerits:
Complex design of arc extinction champer
and OM
Problems due to switching over voltages
(reduced by inserting pre-closing resistors).
2/15/2016

s.amirthavalli

assistant director

33

DEMERITS OF ABCB
Auxiliary Hi-pressure air system is
necessary. Cost increases with several
breakers in the switch yard.
Problem arising out of compressed air
system.

2/15/2016

s.amirthavalli

assistant director

34

OIL CIRCUIT BREAKER


Absorption of Arc energy by
DECOMPOSITION.
Arc cooling by hydrogen gas- has high
diffusion rate and good heat absorption in
changing from diatomic to non atomic state.
Ability of cold oil of high electric strength
to flow into the arc space after current zero.
2/15/2016

s.amirthavalli

assistant director

35

OIL CIRCUIT BREAKER(contn..)


Natural insulation value of oil enabling
clearness to be minimized.
Demerits:
Flammability
Possible formation of explosive due to airgas mixture.
Maintenance (change of oil sludge,
purifying)
2/15/2016

s.amirthavalli

assistant director

36

2/15/2016

s.amirthavalli

assistant director

37

2/15/2016

s.amirthavalli

assistant director

38

2/15/2016

s.amirthavalli

assistant director

39

2/15/2016

s.amirthavalli

assistant director

40

2/15/2016

s.amirthavalli

assistant director

41

2/15/2016

s.amirthavalli

assistant director

42

2/15/2016

s.amirthavalli

assistant director

43

2/15/2016

s.amirthavalli

assistant director

44

2/15/2016

s.amirthavalli

assistant director

45

2/15/2016

s.amirthavalli

assistant director

46

2/15/2016

s.amirthavalli

assistant director

47

SULPHUR HEXA FLORIDE


Merits:
Less number of interrupter per pole than ABCB and
MOCB - outdoor SF6 is simple.
Less costly- maintenance free and compact.
Gas is non-inflammable, chemically stable.
Hi dielectric - insulating properties of gas.
Excellent extinguishing ability.

Non corrosive.
Odour less and colour less.
2/15/2016

s.amirthavalli

assistant director

48

Toxicity is almost zero for all practical purposes.

Heavier than air and considered to be an


advantageous.
Same gas is re circulated and hence, requirement of
SF6 gas is less. ( 30Kg - 145KV, no replacement for 5
years).
Silent and does not make sound like ABCB.
Maintenance is minimum (For electro pneumatic
control system).
Sealed construction avoids contamination by
moisture, dust, sand etc.
2/15/2016

s.amirthavalli

assistant director

49

Size and dimentsions are smaller as compared with


ABCB/OCB fo rsame KV rating- no over voltage
problems.

2/15/2016

s.amirthavalli

assistant director

50

LIQUEFACTION OF SF6 GAS

2/15/2016

s.amirthavalli

assistant director

51

ARC EXTINCTION BY SINGLE-FLOW AND DOUBLE


FLOW

2/15/2016

s.amirthavalli

assistant director

52

2/15/2016

s.amirthavalli

assistant director

53

2/15/2016

s.amirthavalli

assistant director

54

2/15/2016

s.amirthavalli

assistant director

55

2/15/2016

s.amirthavalli

assistant director

56

2/15/2016

s.amirthavalli

assistant director

57

2/15/2016

s.amirthavalli

assistant director

58

2/15/2016

s.amirthavalli

assistant director

59

2/15/2016

s.amirthavalli

assistant director

60

2/15/2016

s.amirthavalli

assistant director

61

2/15/2016

s.amirthavalli

assistant director

62

2/15/2016

s.amirthavalli

assistant director

63

2/15/2016

s.amirthavalli

assistant director

64

2/15/2016

s.amirthavalli

assistant director

65

2/15/2016

s.amirthavalli

assistant director

66

2/15/2016

s.amirthavalli

assistant director

67

2/15/2016

s.amirthavalli

assistant director

68

2/15/2016

s.amirthavalli

assistant director

69

2/15/2016

s.amirthavalli

assistant director

70

2/15/2016

s.amirthavalli

assistant director

71

2/15/2016

s.amirthavalli

assistant director

72

2/15/2016

s.amirthavalli

assistant director

73

VACUUM CIRCUIT BREAKER


ADVANTAGES:

High Interrupting speed.


Extremely low contact erosion.
Stable contact resistance.
Low operation power.
Freedom from catastrophic failures
Long life

2/15/2016

s.amirthavalli

assistant director

74

VCB-CONT..
Dramatic reduction in size and weight.
Little maintenance.
Economical in long run.
Non-inflammable and non-toxic.
Environmental safety.

2/15/2016

s.amirthavalli

assistant director

75

2/15/2016

s.amirthavalli

assistant director

76

BREAKDOWN CHARACTERISTIC OF VACUUM GAP

2/15/2016

s.amirthavalli

assistant director

77

2/15/2016

s.amirthavalli

assistant director

78

2/15/2016

s.amirthavalli

assistant director

79

2/15/2016

s.amirthavalli

assistant director

80

2/15/2016

s.amirthavalli

assistant director

81

2/15/2016

s.amirthavalli

assistant director

82

2/15/2016

s.amirthavalli

assistant director

83

2/15/2016

s.amirthavalli

assistant director

84

TYPES OF ARC
DIFFUSED ARC
CONSTRICTED ARC
DESIGN OF INTERRUPTER CONTACTS:

It should withstand the following:High short circuit breaking capacity


High dielectric strength
Small chopping current
Minimal contact piece erosion
Small contact resistance.
2/15/2016

s.amirthavalli

assistant director

85

Plain butt contacts are used when the short-circuit current is above
4KA.It will avoid the constricted arc and give diffused arc.
Segmented or Contrate contacts

2/15/2016

s.amirthavalli

assistant director

86

Segmented or Contrate contacts

2/15/2016

s.amirthavalli

assistant director

87

Self-magnetic field in segmented contact:


When the short-circuit breaking current is 10 and 50kA, the diffused
arc covers the entire surface of the contact and overheat the contact
pieces. To avoid it, slotted contact pieces are used which create
additional radial magnetic field that produces a field which drives the
arc round the arcing ring.

2/15/2016

s.amirthavalli

assistant director

88

2/15/2016

s.amirthavalli

assistant director

89

VACUUM INTERRUPTERS CONTACT


MATERIAL

COPPER-BISMUTH ALLOY
COPPER-CHROMIUM ALLOY
COPPER-BERRYLIUM ALLOY

2/15/2016

s.amirthavalli

assistant director

90

2/15/2016

s.amirthavalli

assistant director

91

2/15/2016

s.amirthavalli

assistant director

92

2/15/2016

s.amirthavalli

assistant director

93