Professional Documents
Culture Documents
BY
H.K. RAMANATH B.E (ELEC),
RETD EXCUTIVE ENGINEER,
KARNATAKA POWER CORPORATION Ltd.
1.0 EARTHING:
2.0 INTRODUCTION:
The object of earthing system is to provide as nearly as possible a surface , under and around a
substation , which shall be at , at a uniform potential and nearly zero or absolute earth potential
as possible with a view to ensure,
i) All parts of equipments (other than live parts) connected to the earthing system (through
earthing conductors) shall be at ground potential.
ii) Operators and attendants shall be at ground potential at all times.
By providing a ground surface of uniform potential under and surrounding the substation, no
difference in potential exists great enough to shock or injury to an attendant when short circuits
or abnormal occurrences take place.
The concept of good earthing of equipments is to obtain an earth resistance as low as possible.
However in a system if a ground fault currents are excessively high it is very difficult to keep
ground potential to safe limits even if the earth resistance is kept low. In order achieve a safe
potential difference , the modern practice is adopt grid or mat earthing so that a voltage gradient
control under, ground fault conditions so as to keep the potential difference between two points
within safe limits and avoid danger to attendant.
Fig 1
The MS flat is laid horizontally and vertically to form a grid or mat and buried below the
ground. Raisers are brought out from the grid and all electrical equipments including fencing
and gates of substation are connected. Usually the exposed conductors are GI flats.
3.0 DEFINITIONS:
The flow of ground fault currents results in voltage gradients on the surface of the earth in the
vicinity of the grounding system.
3.1 STEP POTENTIAL:
The voltage that exists between the two feet of a person standing on a ground is called step
potential ref Fig 2.
Rf
Rf
E step
Fig 2
The tolerable step potential E Step value of E Step (Tolerable) = (Rk +2 Rf )Ik Volts, where Rk
is
body resistance , Rf is resistance between one step & ground. For practical purpose it is
relative value of the resistivity of earth and rock . for values ref Fig 3. By neglecting the mutual
resistance between the feet and assuming equivalent radius of foot equal to 0.080 m (3 inches) &
for fault duration less than 3 sec,
E
step (Tolerable)
rock in ohm mtrs, Cs is reduction factor for de rating the nominal value of surface layer
resistivity , 1 for soil resistivity equal to crushed rock resistivity
E step Potential for sustained faults,
E step (Tolerable) = [1000 + 6 Cs (hs, k)] Volts
E step (Tolerable) = 9 + 0.054 Cs (hs, k) Volts
For grounding to be safe, for step contact under fault conditions the voltage gradient in volts per
meter on the surface of the ground should not exceed the value obtained from the above
equation.
Fig 3 Reduction factor Cs , function of reflection factor k and layer thickness hs of crushed
rock
- s
k = ----------------- = Reflection Factor
+s
3.2 TOUCH POTENTIAL:
The voltage that exists between hand and both feet of a person is called touch potential as shown
Fig 4.
The tolerable touch Potential E touch = (Rk + Rf /2) Ik Volts.
E Touch
Rf / 2
E Touch
Fig 4
Similarly for tolerable touch potential the potential difference between any point on the ground
where a person stands and any point on the equipment which can be touched simultaneously is
given by,
E touch (Tolerable) = (Rk = Rf /2) Ik
E touch (Tolerable) = (157 + 0.2355 ) / t Volts for sustained faults
E touch (Tolerable) = (9 + 0.0135 ) / t Volts
E touch (Tolerable) = (1000 + 1.5 ) 0.157/ t Volts
Similarly Tolerable touch potential with Gravel or crushed rock layer
E touch (Tolerable) = [1000 +0.235 Cs (hs, k)] / t Volts
Welded Joints
Bolted joints
Copper
Steel
Aluminum
Copper
Steel
30
50
120
91
64
143
(0.025335) (0.060804) (0.00051)
(0.032443)
(0.07246)
3
16(0.0081)
38
29(0.0146 21(0.010640 46 (0.0233)
(0.0193)
9)
7)
1
9.5(0.0048 22(0.0111) 17(0.0086
12(0.0061)
27(0.01368
)
1)
)
0.5
6.5(0.0032 16(0.0081 12(0.0061) 8.5(0.04306) 19(0.00962
9)
0)
3)
Note One Circular mill is 0.0005067 sq mm.
Aluminum
123
(0.06232)
39(0.0197
6)
25(0.0126
7)
16(0.0081
0)
1 for grid with ground rods along the perimeter or in grid corners, as well as both along
the perimeter and throughout the grid area.
1
K
ii
= ---------------(2 ) 2/n
For grids with no ground rods or a few ground rods inside the grid and not on the periphery.
kh = 1+ h/h0 h0 = 1 m for usual depth range of 0 < h 2.5 m.
K
i
= 0.656 + 0.172 n
/ 4 r + /L
touch
mesh. If E mesh value is more than E touch (Tolerable) modification in design is to be done.
5.3 Step Portential at the Pheriphery:
The value of step potential at the pheriphary
Ks Ki l
E step = -------------------------L
10
fences, or metallic piping, may also be energized at the ground potential in the
substation.
substation.
The ground potential rise (GPR) produces a dangerous potential difference between the sub
station and a remote ground connection located at a telephone company control office, remote
terminal, distant manufacturing building or other sites. Telecommunication cable damage can
occur if grounding takes place across the potential difference caused by a power fault or
lightning strike.
7.0. Fencing:
Out door substatoion except pole mounted SS shall be effectively protected by fencing not
less
there in by an un athorised persons. Generally metallic post are used for fence and burried to
a certain depth. The general practice is to provide pipe or rod earhing to the fence post
alternatively. The metallic gates of SS or also earthed by pipe earhing.
11
4) for protection against rust of urried welded joints , located in soil , the weld shall be coated
with molten bitumen and covered with bitumen impregnated tape. In case of coppwer
conductor the joints shall be tinned.
5) Before welding , the steel strips shall be clamped tightly to ensure good surface contact
between them.
6) Where the diameter of the bolt for connecting the earth bar to apparatus exceeds one
quarter of the width of the earth bar, the connection to te the bolts shall be made with a
wider piece or falg of metal jointed to the earth bar. If copper the earth bar or flags shall be
tinned at the point of connection to equipments and special care is required to ensure a
permanent low resistance contact to iron or steel.
7) The equipment earthing shall be done as per IE rules.
8) The overhead ground wires of transmission lines shall be solidly connected to the
grounding grid.
9) All the area over which the ground grid ia spread shall be covered by 7.5 cm thick crushed
rock which shall also be spread 1 to 1.5 m from the pheriphey grounding conductor.
Where the fence is connected to the main grounding system crushed rock shall be placed
outside along the pheriphery og the fence.
10)Separate earthing electrodes shall be provided in the vicinity of lightning arresters,
coupling capacitors and transformer neutrals. These electrodes shall be connected to
general earthing system so as to have minimum of impedance between the lightning
arresters , groungd terminals and the protected equippments.
@@@@@@@@@@@
12