Modulex3 Line

MX3IPG2A

Numerical integrated generator protection (Rotor and auxiliary protection):

Protection functions
Rotor earth fault detection based
on injection of a.c. low voltage
(accessory X2/IPG2A) between
the rotor winding of the protected
synchronous machine and ground.
Two independent time thresholds
measuring the resistance of the
earth fault (R<; R<<).
One independent time
overcurrent (I>) measuring the
circulating current.
Monitoring of the injected voltage.
Dedicated input for wide range
d.c. voltage measurement (d.c.
auxiliary voltage monitoring, d.c.
current measurement on Shunt).
Two independent time d.c.
undervoltage (U -<, U - <<).
Two independent time d.c.
overvoltage (U - >, U - >>).
Starting outputs (alarm),
instantaneous or delayed.
Two setting groups, switch in
operation: from HMI, Digital input
or Communication.
Measurement functions
Injected voltage.
Circulating current.
Max. circulating current.
Earth fault resistance.
D.C. voltage.

64R - 27 d.c. - 59 d.c.

Recording functions
Record of the last fault (last eight)
with date and time (YY/MM/DD hh:mm:ss.mmm) and fault values.
Record of the logical status change
(last 32) included thresholds,
digital inputs, timers, with date
and time (YY/MM/DD hh:mm:ss.mmm)
Disturbance recording with
record of all input signals and
correlated logical status;
possibility to choose the cause
determining trigger and define
the recording time before and
after trigger (for a total recording
time of 2.5 s).
Record on counters and LED's.
Monitoring and control:
digital inputs and outputs
3 freely assignable inputs
(controls, blocks, setting group
switch).
6 output relays one of which
is for diagnostic and 5 freely
assignable to the functions.

Communication
Rear serial port for connection to
Lonworks network at 1.25 Mbit/s.
Alternatively: serial port RS485
and Modbus protocol
Human Machine Interface
Local HMI with keyboard,
backlit LCD display, 12 LED's,
8 of which are freely assignable
to the functions.
Local HMI by PC connected to
the front serial port.
Remote interface by the Local
Area Network.

Characteristics
Generator rated excitation voltage
1000 V d.c.
Excitation circuit to ground
capacitance
5 F
Injected voltage (X2/IPG2A) 40 V

Output relay contacts


Rated current
5A
Breaking
0.3 A @ 110 Vd.c., L/R=40 ms
Make and carr y
30 A for 0.5 s
Mechanical life
106 operations

Rated frequency fn

Standards
EN 60255-6 IEC 255

50/60 Hz

R<
200 to 4000 ohm
Independent time
0.05 to 600 s
R<<
200 to 4000 ohm
Independent time
0.05 to 600 s
I>
10 to 100 mA
Independent time
0.05 to 600 s
D.C. voltage measurement ranges
selectable by internal bridges.
Measur. Continuous
Rated
range
withstand
voltage
0 to 0.5 V
6 V 0.03 to 0.3 V
0 to 5 V
40 V
0.3 to 3 V
0 to 50 V
150 V
3 to 30 V
0 to 500 V 500 V 30 to 300 V
Input resistance
0 to 0.5 V
0 to 5 V
0 to 50 V
0 to 500 V

1 Kohm
10 Kohm
100 Kohm
1000 Kohm

U- <
Independent time
U - <<
Independent time

0.5 to 1.2 Un
0.02 to 600 s
0.5 to 1.2 Un
0.02 to 600 s

U->
Independent time
U ->>
Independent time

0.5 to 1.2 Un
0.02 to 600 s
0.5 to 1.2 Un
0.02 to 600 s

Auxiliary supply of MX3IPG2A


Uaux:
19 to 100 Vd.c.
or:
19 to 72 Va.c.
Uaux:
64 to 300 Vd.c.
or:
64 to 275 Va.c.
Burden:
5 W/10 W d.c.
10VA/20VA a.c.
Auxiliary supply of X2/IPG2A
Uaux:
24 to 240 Va.c.
Frequency:
45 to 65 Hz
Burden:
<5 VA.