A transmission line is characterized by four


parameters:
series resistance (R) due to conductor resistivity
shunt conductance (G) due to currents along
insulator strings and corona; effect is small and
usually neglected
series inductance (L) due to magnetic field
surrounding the conductor
shunt capacitance (C) due to the electric field
between the conductors

These are distributed parameters.

The parameters and hence the characteristics of


cables differ significantly from those of overhead
lines because the conductors in a cable are
much closer to each other
surrounded by metallic bodies such as shields,
lead or aluminum sheets, and steel pipes
separated by insulating material such as
impregnated paper, oil, or inert gas

ACT - 1

1539pk

For balanced steady-state operation, the performance of


transmission lines may be analyzed in terms of singlephase equivalents.

Fig. 6.1 Voltage and current relationship of a distributed


parameter line

The general solution for voltage and current at a


distance x from the receiving end (see book: page 202)
is:
(6.8)
(6.9)

where

ACT - 2

1539pk

The constant ZC is called the characteristic


impedance and K is called the propagation constant.

The constants K and ZC are complex quantities. The


real part of the propagation constant K is called the
attenuation constant , and the imaginary part the
phase constant .

If losses are completely neglected,

ACT - 3

1539pk

For a lossless line, Equations 6.8 and 6.9 simplify to


(6.17)
(6.18)

When dealing with lightening/switching surges, HV


lines are assumed to be lossless. Hence, ZC with
losses neglected is commonly referred to as the surge
impedance.
The power delivered by a line when terminated by its
surge impedance is known as the natural load or surge
impedance load.

where V0 is the rated voltage

At SIL, Equations 6.17 and 6.18 further simplify to


(6.20)
(6.21)

ACT - 4

1539pk

Hence, for a lossless line at SIL,


V and I have constant amplitude along the line
V and I are in phase throughout the length of the line
The line neither generates nor absorbs VARS

As we will see later, the SIL serves as a convenient


reference quantity for evaluating and expressing line
performance

Typical values of SIL for overhead lines:


nominal (kV): 230
SIL (MW):
140

345
420

500
1000

765
2300

Underground cables have higher shunt capacitance;


hence, ZC is much smaller and SIL is much higher than
those for overhead lines.
for example, the SIL of a 230 kV cable is about
1400 MW
generate VARs at all loads

ACT - 5

1539pk

Table 6.1 Typical overhead transmission line parameters

Note: 1. Rated frequency is assumed to be 60 Hz


2. Bundled conductors used for all lines listed, except for the 230 kV line.
3. R, xL, and bC are per-phase values.
4. SIL and charging MVA are three-phase values.

Table 6.2 Typical cable parameters

* direct buried paper insulated lead covered (PILC) and high pressure pipe
type (PIPE)
ACT - 6

1539pk

With receiving end open, IR = 0. Assuming a


lossless line from Equations 6.17 and 6.18, we have
(6.31)
(6.32)

At the sending end (x = l),


(6.33)

where = l. The angle is referred to as the


electrical length or the line angle, and is expressed
in radians.

From Equations 6.31, 6.32, and 6.33


(6.35)
(6.36)

ACT - 7

1539pk

As an example, consider a 300 km, 500 kV line with


= 0.0013 rads/km, ZC = 250 ohms, and ES = 1.0 pu:

Base current is equal to that corresponding to SIL.


Voltage and current profiles are shown in Figure 6.5.

The only line parameter, other than line length, that


affects the results of Figure 6.5 is . Since is
practically the same for overhead lines of all voltage
levels (see Table 6.1), the results are universally
applicable, not just for a 500 kV line.

The receiving end voltage for different line lengths:


- for l = 300 km, VR = 1.081 pu
- for l = 600 km, VR = 1.407 pu
- for l = 1200 km, VR = infinity

Rise in voltage at the receiving end is because of


capacitive charging current flowing through line
inductance.
known as the "Ferranti effect".

ACT - 8

1539pk

(a) Schematic Diagram

(b) Voltage Profile

(c) Current Profile


Figure 6.5 Voltage and current profiles for a 300 km lossless
line with receiving end open-circuited
ACT - 9

1539pk

Corresponding to a load of PR+jQR at the receiving end, we


have

Assuming the line to be lossless, from Equation 6.17


with x = l

Fig. 6.7 shows the relationship between VR and PR for a


300 km line with different loads and power factors.
The load is normalized by dividing PR by P0, the natural
load (SIL), so that the results are applicable to overhead
lines of all voltage ratings.

From Figure 6.7 the following fundamental properties of ac


transmission are evident:
a) There is an inherent maximum limit of power that can be
transmitted at any load power factor. Obviously, there
has to be such a limit, since, with ES constant, the only
way to increase power is by lowering the load
impedance. This will result in increased current, but
decreased VR and large line losses. Up to a certain
point the increase of current dominates the decrease of
VR, thereby resulting in an increased PR. Finally, the
decrease in VR is such that the trend reverses.

ACT - 10

1539pk

Figure 6.7 Voltage-power characteristics of a 300 km


lossless radial line

ACT - 11

1539pk

b) Any value of power below the maximum can be


transmitted at two different values of VR. The
normal operation is at the upper value, within
narrow limits around 1.0 pu. At the lower voltage,
the current is higher and may exceed thermal
limits. The feasibility of operation at the lower
voltage also depends on load characteristics, and
may lead to voltage instability.
c) The load power factor has a significant influence
on VR and the maximum power that can be
transmitted. This means that the receiving end
voltage can be regulated by the addition of shunt
capacitive compensation.

Fig. 6.8 depicts the effect of line length:


For longer lines, VR is very sensitive to variations
in PR.
For lines longer than 600 km ( > 45), VR at
natural load is the lower of the two values which
satisfies Equation 6.46. Such operation is likely
to be unstable.

ACT - 12

1539pk

Figure 6.8 Relationship between receiving end voltage,


line length, and load of a lossless radial line

ACT - 13

1539pk

With ES and ER assumed to be equal, the following


conditions exist:
the midpoint voltage is midway in phase between
ES and ER
the power factor at midpoint is unity
with PR>P0, both ends supply reactive power to the
line; with PR<P0, both ends absorb reactive power
from the line.

Fig. 6.9 Voltage and current phase relationships with ES


equal to ER, and PR less than Po

Fig. 6.8 (developed for a radial line) may be used to


analyze how Vm varies with PR.
with the length equal to half that of the actual line,
plots of VR shown in Figure 6.8 give Vm.

ACT - 14

1539pk

Assuming a lossless line, from Equation 6.17 with


x = l, we can show that
(6.51)

where = l is the electrical length of line and is the


angle by which ES leads ER, i.e. the load angle.

If ES = ER = rated voltage, then the natural load is

and Equation 6.51 becomes

The above is valid for synchronous as well as


asynchronous load at the receiving end.

Fig. 6.10(a) shows the - PR relationship for a 400 km


line.
For comparison, the Vm - PR characteristic of the line is
shown in Fig. 6.10(b).

ACT - 15

1539pk

Figure 6.10 PR- and Vm-PR characteristics of 400 km lossless


line transmitting power between two large systems
ACT - 16

1539pk

From Equation 6.17, with x = l and ES = ER = 1.0, we can


show that

Fig. 6.11 shows the terminal reactive power


requirements of lines of different lengths as a function
of PR.
Adequate VAR sources must be available at the two
ends to operate with varying load and nearly
constant voltage.

General Comments
Analysis of transmission line performance
characteristics presented above represents a highly
idealized situation
useful in developing a conceptual understanding of
the phenomenon
dynamics of the sending-end and receiving-end
systems need to be considered for accurate
analysis.

ACT - 17

1539pk

Figure 6.11 Terminal reactive power as a function of power


transmitted for different line lengths

ACT - 18

1539pk

The concept of "line loadability" was introduced by


H.P. St. Clair in 1953

Fig. 6.13 shows the universal loadability curve for


overhead uncompensated lines applicable to all
voltage ratings

Three factors influence power transfer limits:


thermal limit (annealing and increased sag)
voltage drop limit (maximum 5% drop)
steady-state stability limit (steady-state stability
margin of 30% as shown in Fig. 6.14)

The "St. Clair Curve" provides a simple means of


visualizing power transfer capabilities of transmission
lines.
useful for developing conceptual guides to
preliminary planning of transmission systems
must be used with some caution

Large complex systems require detailed assessment


of their performance and consideration of additional
factors

ACT - 19

1539pk

Figure 6.13 Transmission line loadability curve

ACT - 20

1539pk

Figure 6.14 Steady state stability margin calculation

ACT - 21

1539pk

Consider two sources connected by an inductive


reactance as shown in Figure 6.21.
representation of two sections of a power system
interconnected by a transmission system
a purely inductive reactance is considered
because impedances of transmission elements
are predominately inductive
effects of shunt capacitances do not appear
explicitly

(a) Equivalent system diagram

= load angle
= power factor angle
(b) Phasor diagram

Figure 6.21 Power transfer between two sources

ACT - 22

1539pk

The complex power at the receiving end is

Hence,
(6.79)
(6.80)

Similarly,
(6.81)
(6.82)

Equations 6.79 to 6.82 describe the way in which


active and reactive power are transferred

Let us examine the dependence of P and Q transfer


on the source voltages, by considering separately
the effects of differences in voltage magnitudes and
angles

ACT - 23

1539pk

(a) Condition with = 0:

From Equations 6.79 to 6.82, we have

With ES > ER, QS and QR are positive


With ES < ER, QS and QR are negative

As shown in Fig. 6.22,


transmission of lagging current through an
inductive reactance causes a drop in receiving
end voltage
transmission of leading current through an
inductive reactance causes a rise in receiving
end voltage

Reactive power "consumed" in each case is

(b) ER>ES

(a) ES>ER

Figure 6.22 Phasor diagrams with = 0


ACT - 24

1539pk

(b) Condition with ES = ER and 0

From Equations 6.79 to 6.82, we now have

With positive, PS and PR are positive, i.e., active


power flows from sending to receiving end

In each case, there is no reactive power transferred


from one end to the other; instead, each end
supplies half of Q consumed by X.

(a) > 0

(b) < 0

Figure 6.23 Phasor diagram with ES = ER


ACT - 25

1539pk

(c) General case applicable to any condition:

We now have
(6.83)

(6.84)

If, in addition to X, we consider series resistance R


of the network, then
(6.85)
(6.86)

The reactive power "absorbed" by X for all


conditions is X I 2. This leads to the concept of
"reactive power loss", a companion term to active
power loss.

An increase in reactive power transmitted increases


active as well as reactive power losses. This has an
impact on efficiency and voltage regulation.

ACT - 26

1539pk

The active power transferred (PR) is a function of


voltage magnitudes and . However, for satisfactory
operation of the power system, the voltage magnitude
at any bus cannot deviate significantly from the
nominal value. Therefore, control of active power
transfer is achieved primarily through variations in
angle .

Reactive power transfer depends mainly on voltage


magnitudes. It is transmitted from the side with higher
voltage magnitude to the side with lower voltage
magnitude.

Reactive power cannot be transmitted over long


distances, since it would require a large voltage
gradient to do so.

An increase in reactive power transfer causes an


increase in active as well as reactive power losses.

Although we have considered a simple system, the general


conclusions are applicable to any practical system, In fact, the basic
characteristics of ac transmission reflected in these conclusions
have a dominant effect on the way in which we operate and control
the power system.

ACT - 27

1539pk

1. Copy of Section 6.4 from the book Power System


Stability and Control
provides background information related to
power flow analysis techniques

ACT - 28

1539pk

ACT - 29

1539pk

ACT - 30

1539pk

ACT - 31

1539pk

ACT - 32

1539pk

ACT - 33

1539pk

ACT - 34

1539pk

ACT - 35

1539pk

ACT - 36

1539pk

ACT - 37

1539pk

ACT - 38

1539pk

ACT - 39

1539pk

ACT - 40

1539pk

ACT - 41

1539pk

You might also like