ABB Oy Distribution Automation

630 series programming


Course P264
ABB Group
April 13, 2011 | Slide 1

630 series configuration training


Course content
The purpose of this course
Learn most common configuration tasks
Specify and identify the needed hardware
Lean to use PCM600 tools for IED configuration
Learn 630 series programming
Protection function
Control with interlocking
Desing a MIMIC picture
Learn other usefull tools in PCM600

ABB Group
April 13, 2011 | Slide 2

Breaks:
Breaks:
Coffee
Coffee
10:20
10:20- 10:30
10:30
Lunch
Lunch
11:45
11:45- 13:00
13:00
Coffee
Coffee
14:20
14:20- 14:30
14:30

630 series introduction

ABB Group
April 13, 2011 | Slide 3

630 series
Product overview
Feeder Protection and Control
REF630
REF630 is an all-in-one feeder
management IED for protection, control,
measurement and supervision of
incoming and outgoing feeders

Transformer Protection and Control


RET630
RET630 is an all-in-one transformer
management IED for protection, control,
measurement and supervision of twowinding power transformers and
generator-transformer blocks

Motor Protection and Control REM630


REM630 is an all-in-one motor
management IED for protection, control,
measurement and supervision of
medium and and large power
asynchronous motors

ABB Group
April 13, 2011 | Slide 4

630 series
Hardware overview
Power supply module
Optional I/O modules

Max 2 modules for the 4U half 19


housing

Analogue input module


CPM module

ABB Group
April 13, 2011 | Slide 5

630 series
Communication module
Communication interfaces
Ethernet options:

100BASE-TX with an RJ-45 connector


100BASE-FX with a fibre-optic LC connector

Detached LHMI interface


Time synchronization
IRIG-B

14 binary inputs
2 groups of 4 inputs, common ground
2 groups of 3 inputs, common ground
Adjustable threshold voltage

ABB Group
April 13, 2011 | Slide 6

630 series
Binary I/O module
9 output contacts
3 power output contacts for
tripping/control
6 signal output contacts
5 signal outputs contacts,
normally open
1 signal output contact,
changeover
9 binary inputs
8 inputs, grouped in 2 (common
ground)
1 individual input
Adjustable threshold voltage
ABB Group
April 13, 2011 | Slide 7

630 series
Power supply module
Power Supply
Variant #1 High (pins 1,3)
100 VAC .. 240 VAC 50/60 Hz
110 VDC .. 250 VDC

Variant #2 Medium (pins 1,2)


48 VDC .. 125 VDC

Variant #3 Low (pins 2,3)


Next release

IRF output for self-supervision signalling


9 Output contacts
3 trip outputs with Trip Circuit Supervision
3 power outputs for trip/control
3 signal output contacts

Battery voltage supervision


ABB Group
April 13, 2011 | Slide 8

630 Series
Analog input modules of REF630
Three options for REF630
Variant #1: AA
X101

IL1, IL2, IL3 and I0, user selectable 1 A


or 5 A
UL1, UL2, UL3, Uo and UL

Variant #2: AB
IL1, IL2 and IL3 , user selectable 1 A or
5A
I0, user selectable 0.1 A or 0.5 A
UL1, UL2, UL3, Uo and UL

X102

Variant #3: AC
IL1, IL2, IL3 and I0, user selectable 1 A
or 5 A
I0, user selectable 0.1 A or 0.5 A
UL1, UL2, UL3 and Uo

ABB Group
April 13, 2011 | Slide 9

630 Series
Analog input connector
Disconnectable connectors for
easy handling and service
Used for CT/VT connections
5 analog channels / connector
Integrated short circuit contact for
CT inputs
Different combinations of
CTs/VTs supported
Coded to prevent wrong
connections

ABB Group