Professional Documents
Culture Documents
Figure 1.
Kyle Type ME electronic recloser control
CONTENTS
Safety Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Periodic Field Inspection and Maintenance . . . . . . . 6
Servicing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Circuit Logic . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Plug-In Circuit Boards Function . . . . . . . . . . . . . . . .10
Battery Charging Board . . . . . . . . . . . . . . . . . . . .10
Phase Trip No. 1 Board . . . . . . . . . . . . . . . . . . . .11
Phase Trip No. 2 Board . . . . . . . . . . . . . . . . . . . .11
Ground Trip No. 1 and No. 2 Boards . . . . . . . . . .11
Output Board . . . . . . . . . . . . . . . . . . . . . . . . . . . .12
Diode Board . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12
Recloser-Reset Board . . . . . . . . . . . . . . . . . . . . .12
Closing Coil Control Fuse . . . . . . . . . . . . . . . . . . . . .12
Interchangeability of Boards Between Form 2,
Form 3 and Form 3A Electronic Controls . . . . . . . . .12
Troubleshooting and Testing . . . . . . . . . . . . . . . . . . .13
Detailed Circuit Checks . . . . . . . . . . . . . . . . . . . . . . .14
Input Circuits . . . . . . . . . . . . . . . . . . . . . . . . . . . .17
Internal dc Load Current Signal . . . . . . . . . . . . . .18
Service Information
S280-75-2
88936KMA
These instructions do not claim to cover all details or variations in the equipment, procedure, or process described, nor to provide direction for
meeting every possible contingency during installation, operation, or maintenance. When additional information is desired to satisfy a problem not
covered sufficiently for the users purpose, please contact your Cooper Power Systems sales engineer.
April 2002 Supersedes 12/88
SAFETY
FOR LIFE
SAFETY
FOR LIFE
Cooper Power Systems products meet or exceed all applicable industry standards relating to product safety. We actively
promote safe practices in the use and maintenance of our products through our service literature, instructional training
programs, and the continuous efforts of all Cooper Power Systems employees involved in product design, manufacture,
marketing, and service.
We strongly urge that you always follow all locally approved safety procedures and safety instructions when working
around high voltage lines and equipment and support our Safety For Life mission.
SAFETY INFORMATION
The instructions in this manual are not intended as a
substitute for proper training or adequate experience in
the safe operation of the equipment described. Only
competent technicians who are familiar with this equipment should install, operate, and service it.
A competent technician has these qualifications:
Is thoroughly familiar with these instructions.
Is trained in industry-accepted high- and low-voltage
safe operating practices and procedures.
Is trained and authorized to energize, de-energize,
clear, and ground power distribution equipment.
Is trained in the care and use of protective equipment
such as flash clothing, safety glasses, face shield,
hard hat, rubber gloves, hotstick, etc.
Following is important safety information. For safe installation and operation of this equipment, be sure to read
and understand all cautions and warnings.
Safety Instructions
Following are general caution and warning statements
that apply to this equipment. Additional statements, related to specific tasks and procedures, are located throughout the manual.
DANGER: Hazardous voltage. Contact with
hazardous voltage will cause death or severe
personal injury. Follow all locally approved safety procedures when working around high and low voltage
lines and equipment.
G103.3
WARNING: Before installing, operating, maintaining, or testing this equipment, carefully read
and understand the contents of this manual. Improper
operation, handling or maintenance can result in death,
severe personal injury, and equipment damage. G101.0
G102.1
CAUTION: Indicates a potentially hazardous situation which, if not avoided, may result in equipment damage only.
S280-75-2
INTRODUCTION
Service Information S28O-75-2 covers basic maintenance
instructions for the Type ME electronic control. The manual
includes a general description of the control, its operating
principles and instructions for periodic inspection and testing.
Service parts lists along with ordering information are included in Appendix IV.
An introduction to the Form 3A, Type ME, electronic control
is available on video cassette (KSPV3); in this program the
function of all standard operating and programming features
is explained.
The factory service department offers maintenance training
courses for Type ME controls. These classes, taught by ex-
Figure 2.
Electronic control panel.
DESCRIPTION
The Kyle Type ME electronic recloser control (Figure 1 ) is comprised of a number of programmable, solid-state electronic circuits
that perform the command functions involved in automatic recloser
operation. It is used to operate all Kyle electronically controlled
reclosers.
A swing-out front panel contains the programming and operating
elements of the control (Figure 2). The upper, black portion
88937KMA
Figure 3.
Tie board on back of front panel mounts the individual printed circuit boards.
88938KMA
S280-75-2
OPERATION
Since the understanding of the terminology and the operating sequences of an electronically controlled recloser is
important to the rest of this maintenance manual, examples
of typical operating sequences of an electronically controlled
recloser under permanent fault (Figure 4) and temporary
fault (Figure 5) conditions are given. The definition of the
terms and callouts used in Figures 4 and 5 are:
Minimum TripMinimum trip is usually set at greater
than 2 times (200%) the maximum expected load current
to help prevent nuisance tripping on inrush currents, while
still being sensitive to low level faults.
Over-CurrentAny current that exceeds the minimumtrip level of the control.
Permanent FaultAny over-current condition that persists through the operating sequence of the control.
Temporary FaultAny over-current condition that does
not persist through the operating sequence of the control.
Figure 4.
Typical operating sequence of an electronically controlled recloser under permanent fault conditions.
Figure 5.
Typical operating sequence of an electronically controlled recloser under temporary fault conditions.
Figure 6.
Functional block diagram of Type ME control.
CAUTION: In order to prevent possible, misoperation (unintentional operation) of the recloser, the
control must be removed from service prior to performing
any maintenance, testing or programming changes.
WARNING: High voltage. Contact with high voltage will cause serious personal injury or death.
Follow all locally approved safety procedures when working around high voltage lines and equipment.
S280-75-2
88939KMA
Figure 7.
View of a Form 3A tie board (back if front panel. Notations in parenthesis after callout refer to the circuit points on the tie board diagram illustrated in Figure 57.
Figure 8.
Detailed block diagram of Type ME control in lockout position. Letters in circles (A,B, etc.) refer to control cable receptacle connection pins and to test points referred to in the "Troubleshooting and Testing" section.
SERVICING
Circuit Logic
Line current conditions are monitored continuously by three
bushing-current transformers in the recloser, one on each
phase. The current transformers are connected to the controlphase matching transformers in a typical WYE to WYE configuration. Zero-sequence current is derived from the vector sum
of the phase currents and fed to a fourth ground matching transformer.
The minimum-trip resistors calibrate the overall recloser trip
current by diverting a portion of the recloser current from the
control matching transformers.
The four matching transformers isolate the various signals
from each other and deliver an ac voltage proportional to the
recloser-line current to the phase-trip No.1 end ground-trip No.
1 boards.
S280-75-2
Figure 9.
Diagram of Form 3A tie board showing plug-in circuit board location. Form 3 tie boards are similar (see Figure 18), except some of
the terminals are missing or in a slightly different location.
If the load current conditions are in the fault region, the minimum-trip portion of the phase-trip No. 2 board switches on, allowing the time-current curve circuits to start their programmed time
delay. The time-current curves are driven by the same do voltage
output of the phase-trip No. 1 board, and as a result higher faultcurrent levels will result in a shorter time delay before tripping.
Figure 10.
Battery-charging board,
10
82027aKMA
BATTERY-CHARGING BOARD
The lowest board in the rack is the battery-charging board
(Figure 10). Prior to serial number 50070 controls were equipped
with a fixed rate potential charging board (MEA 388-1 ) as standard equipment. After serial number 50070 a temperature regulated battery-charging board (MEA 1172) has been supplied as
standard. !
The fixed rate charging board consists of a full-wave bridge
rectifier, a capacitor, a reference zener diode and some resistors. The resistors control the charging rate into the battery, from
the zener supply voltage.
The temperature regulated battery-charging board also makes
use of a full-wave bridge rectifier, a capacitor, and a zener diode
(used to regulate voltage). In addition a temperature sensitive
thermistor is added to regulate the bias over a pair of transistors.
These transistors are used in the circuit output to regulate the
charging rate, in response to temperature. Several resistors are
used in the transistor bias circuit; and one resistor is used to limit
the maximum charging rate. A diode is placed in the output to
protect the circuit from reverse bias.
Energy for either battery-charging board comes from the 120or 240-Vac source,through current limiting resistance and a
potential transformer.
88940KMA
S280-75-2
PHASE-TRIP NO. 2 BOARD
The phase-trip No. 2 board (Figure 12) carries the remaining circuits for minimum-trip and the wave-shaping circuits for the timing
plugs. There are two tabs on the phase-trip No. 2 board for the
Form 3 and 3A control. one tab is labeled minimum-trip (MIN.
TRIP)* and is battery plus for normal line currents and switches to
battery minus for fault currents; the second tab marked (DIR.
BLOCK)* is an inactive tab at this time.
* In early Form 3 boards, these tabs may not be labeled.
Figure 20.
Capacitor for CT-type battery charger.
86773KMA
Figure 11.
Phase-trip No. 1 board.
88941KMA
Figure 14.
Ground-trip No. 2 board.
88943KMA
88944KMA
11
Figure 17.
Reclose-reset board.
88947KMA
Figure 15.
Output Board.
88945KMA
DlODE BOARD
The diode board (Figure16)consists of a group of diodes which
are connected to circuits on the other printed circuit boards.
These diodes connect to the timing plugs, the reset circuit, the
trip circuit, and the reclose circuit. The board also contains the
circuit related to the closing circuit fuse.
On solenoid-operated reclosers, the fuse will open the closing circuit to protect the potential closing coil in the recloser if closing
cannot be accomplished due to low closing voltage. On motoroperated reclosers, the fuse is connected in series with the closing circuit contactor in the recloser.
A Buss Type MDQ-3/8 amp, 250-volt fuse, manufactured by
Bussman Manufacturing is used and a box of five spare fuses is
supplied with each control. Fuses of similar ratings by other manufacturers have slightly different characteristics and should not be
used for replacement.
NOTE: Buss has redesigned the MDL-2.5 amp fuse that is used on controls shipped with reciosers having quick-close mechanisms such as
Type VSO and VSMT reclosers. The characteristics of the new single element MDL-2.5 fuse do not affect the application in the control. Buss will
also continue to manufacture the original dual element version of the fuse
under the new designation of MDQ-2.5. The MDQ-2.5 amp fuse will be
supplied with controls for this application. Both the MDL-2.S amp fuse
and the MDQ-2.S amp fuse are acceptable for this application.
INTERCHANGEABILITY OF BOARDS
BETWEEN FORM 2, FORM 3 AND FORM 3A
ELECTRONIC CONTROLS.
Figure 16.
Diode Board.
88946KMA
RECLOSE-RESET BOARD
The reclose-reset board ( Figure 17) carries all circuits necessary for reclosing and resetting. The various large capacitors
on this board are the C parts of an R-C circuit operating along
with unijunctions and SCRs. The large SCR on this board is
the reclose SCR.
12
S280-75-2
TROUBLESHOOTING AND TESTING
A number of relatively simple circuit tests can be made on
the ME electronic control. These tests will indicate whether
major circuits are operating properly or not, but they will not
necessarily isolate the faulty component within the circuit.
For easy reference to testing points, refer to Figures 18 and
19 for Form 3 controls and Figures 20 and 21 for Form 3A
controls. When appropriate, isolated test points will be
shown for individual circuit tests with reference to the propertie board (Figures 18 to 21).
TABLE 1
Pre-Check
Trouble
Check
1. Completely
inoperative
2. Wont close
3. Wont trip
82040KMA
Figure 18.
Form 3 electronic control tie board.The test points listed above will be covered in detail in the "Detailed Circuit Check" section of
this manual.
13
82047KMA
Figure 19.
Form 3 electronic control tie board and control back panel.The test points listed above will be covered in detail in the "Detailed
Circuit Check" section of this manual.
Pre-Check
When troubleshooting a control reported to have failed or to
have not worked properly, always check for simple problems
first.
14
S280-75-2
88948KMA
Figure 20.
Form 3A electronic control tie board.The test points listed above will be covered in detail in the "Detailed Circuit Check" section of
this manual.
A primary diode failure on the diode board can cause secondary failures on the output board or reclose set board.
NOTE Diode board short circuits are very rare in controls manufactured
after 1970.
If this does not isolate the problem, continue with the circuit
test.
15
88939KMA
Figure 21.
Form 3A electronic control back panel.The test points listed above will be covered in detail in the "Detailed Circuit Check" section of
this manual.
16
S280-75-2
INPUT CIRCUITS
WARNING: High voltage. Contact with high voltage will cause serious personal injury or death.
Follow all locally approved safety procedures when
working around high voltage lines and equipment.
Figure 23.
Block diagram of matching transformers (Table 2). See Figure 8
for complete block diagram.
Figure 22.
Measured voltage across minimum-trip resistors.
82040KMA
TABLE 2
Terminal Strip T1 Test Points for Matching Transformers
(100% Minimum-Trip) (Figures 23 and 24)
Transformer
Terminal Position
GND
A
B
C
BRORED
ORGYEL
GRNBLU
VIGRY
1.2
6.5
6.5
6.5
17
Figure 24.
Measuring voltage across matching transformers (Table 2) (control panel open, middle left hand side of control).
88950KMA
TABLE 3
Tie Board Test Points for dc-Load-Current Signal
(100% Minimum-Trip) (Figures 25, 26 and 27)
Load Current
Terminal Position
Form 3
Form 3A
+Lead -Lead +Lead
-Lead
Voltage
Readings
Vdc*
Phase
Seq.
Relay
7A
M-ph
Seq.
Relay Phase Minus
7A
6.1
Ground
Seq.
Relay
7A
M-gnd
Seq.
Relay
7A
0.78
Gnd Minus
Figure 25.
Block diagram of secondary side of matching transformers and
input bridge (Table 3). See Figure 8 for complete block diagram.
18
82040KMA
Figure 26.
Form 3 tie board test points for internal dc-load-current signal (Table
3. For relationship of terminal location on the tie board, see figures 18
and 19.
S280-75-2
INTERNAL MINIMUM TRIP SIGNAL
To check the minimum-trip signal, measure the voltage at tie
board test points listed in Table 4.
Failures to get these signals are most likely due to troubles on
the phase-trip No. 2 or ground-trip No. 2 circuit boards or possibly with the phase-trip No.1 or ground-trip No.1 boards. Battery
voltage below 21-Vdc will cause control misoperation of the minimum-trip, timing and trip signals of the control. Battery voltage
above 23 volts will operate the circuits correctly. Refer to
Battery Maintenance, page 35, for battery charging and testing
information.
TABLE 4
Tie Board Test Points for Minimum-Trip Signal
Figures 28, 29, and 30)
Minimum
Trip
Signal
88948KMA
Figure 27.
Form 3A tie board test points for internal dc-load-current signal
(Table 3). For relationship of terminal location on the tie board, see
figures 20 and 21.
Terminal Position
Form 3
Form 3A
+Lead -Lead
+Lead
-Lead
Phase
Ph
Min.
Trip
Seq.
Relay
7A
Ph
Min.
Trip
Seq.
Relay
7A
25 or 0.30 Max.
Battery
Ground
Gnd.
Min.
Trip
Seq.
Relay
7A
Seq.
Relay
7A
25 or
Battery
Gnd.
Min.
Trip
0.30 Max.
*Voltage reading will last only for the duration of the clearing time of the control
and recloser/simulator.
Figure 28.
Form 3 tie board test points for internal minimum-trip signal (Table 4). For relationship of terminal location on the tie board, see
Figures 18 and 19.
19
TABLE 5
Tie Board/TCC Socket Pin Test Points for TCC Charging
(120% Minimum-Trip) (Figures 31, 32 and 33)
TCC
Curve
Fast
Slow
Test Points
Form 3 and 3A
+Lead (Phase or
Ground TCC Plug)
No. 1 pin, No. 2 TCC
No. 1 pin, No. 2 TCC
-Lead
Sequence Relay 7A
Sequence Relay 7A
Voltage
Drop Vdc
24 - 7*
24 - 7*
* On a fast TCC curve the voltage will drop from 24-Vdc to less than 7-Vdc the
instant the fault current increases above minimum-trip.
* * On a delayed TCC plug an obvious time delay can be observed as the meter voltage slowly drops from 24-Vdc to 7-Vdc at which time the unit trips
88948KMA
Figure 29.
Form 3A tie board test points for internal minimum-trip signal
(Table 4). For relationship of terminal location on the tie board,
see Figures 20 and 21.
Figure 30.
Block diagram of internal minimum-trip signal circuit (Table
4). See Figure 8 for complete block diagram.
20
Figure 31.
Block diagram of time-current circuit (Table 5). See Figure 8 for
complete block diagram.
S280-75-2
82040KMA
Figure 32.
Form 3 test points for TCC operation (Table 5). For relationships of terminal/pin location on the tie board and rear of front panel, see
Figures 18 and 19.
88948KMA
Figure 33.
Form 3 test points for TCC operation (Table 5). For relationships of terminal/pin location on the tie board and rear of front panel, see
Figures 20 and 21.
21
Figure 34.
Typical RXE and WE series reclosers with electronic control cable connection.
Figure 35.
Typical motor operated recloser (VSAT shown) and electronic control connection.
22
S280-75-2
To check voltage changes during typical recloser-trip
operations, measure voltage at test points listed in Table 6.
Failure to get voltage readings indicated usually indicates
problems in the recloser. Consult the recloser maintenance
manual for testing and service information (see Appendix 11).
TABLE 6
Test Points for Trip Operating Circuit
(Figures 36, 37, and 38)
Test Points
Voltage Vdc
Voltage Vdc
Control Recloser Closed
Control in Lockout
No Fault
+Lead
Form 3 and 3A
-Lead
Form 3 and 3A
Tie Board A
24
Seq. Relay 7A
24
Tie Board B
24
24
2.2
24
24
24
24
* Trip signals have a time duration of only 0.04- to 0.5-seconds, depending on recloser type. If voltage on tie board B drops to 2.2-volts for longer than 5-seconds, the recloser failed to trip. Unplug the control
battery.
Figure 36.
Block diagram of trip-operating (Table 6). See Figure 8 for complete block diagram. Letters in circles (A,B, etc.) are test points
and correspond to control cable receptacle pin connection
points.
82040KMA
Figure 37.
Form 3 test points of recloser-trip operations (Table 6). For relationship of terminal test points, see Figures 2, 18 and 19.
23
88948KMA
Figure 38.
Form 3A test points for recloser-trip operation (Table 6). For
relationship of terminal tet points, see Figures 2, 20, and 21.
Figure 39.
Block diagram of closing, tripping and reclosing circuit (Table 7).
See Figure 8 for complete block diagram. Letters in circles (A, B,
etc.) are test points and correspond to control cable receptacle
pin connection points.
TABLE7
Test Points for Closing,Tripping and Reclosing Circuit
(Figures 39, 40, 41)
Test Points
+Lead
-Lead
Form 3 and 3A
Form 3 and 3A
Seq. Relay
F-1
F-2
E
F
A
8
Middle Battery
Test Terminal
Middle Battery
Test Terminal
Middle Battery
Test Terminal
Middle Battery
Test Terminal
Middle Battery
Test Terminal
Middle Battery
Test Terminal
Middle Battery
Test Terminal
Voltage Vdc
Control in Lockout
Voltage Vdc
Control Reset
Voltage Vdc
Closing* Coil Energized
Voltage Vdc
Control Closed
Voltage Vdc
Reclosed Timing
25
25
25
25
25
25
1.5**
25
25
25
1.5**
25
25
25
25
25
25
25
25
25
25
0 to15***
24
S280-75-2
82040KMA
Figure 40.
Form 3 test points for closing, tripping and reclosing operation (Table 7). For relationship of terminal test points, see Figures 2, 18
and 19.
88948KMA
Figure 41.
Form 3 test points for closing, tripping and reclosing opeation (Table 7). For relationship of terminal test points, see Figures 2, 18
and 19.
25
TABLE 8
Test Points for Trip and Reset Circuit
(Figures 42, 43 and 44).
Test Points
+Lead
Form 3
and 3A
Reset #2
Phase Trip
#2 Board,
Minimum-Trip
-Lead
Form 3
and 3A
Middle
Battery
Test
Terminal
Middle
Battery
Test
Terminal
Voltage
Vdc
Tripped
Voltage Vdc
Reclose Into
Low Level
Fault (120%
Minimum-Trip)
Voltage Vdc
Reclose Into
No Fault
0.7
0.7 to 15*
25/0
25
Figure 42.
Block diagram of trip-reset circuit (Table 8). See figure 8 for complete block diagram. Letters in circle (A,B, etc.) are test points and
correspond to control cable receptacle pin connection points.
26
S280-75-2
Figure 43.
Form 3 test points for trip-reset operation (Table 8). For relationship of terminal test points, see Figures 2, 18 and 19.
27
Figure 44.
Form 3A test points for trip-reset operation (Table 8). For relationship of terminal test points, see Figures 2, 20, and 21.
28
S280-75-2
MAJOR CONTROL DAMAGE
To verify the condition of the Form 3 and 3A tie board in the
event of major control damage, check the continuity of common
tie board terminals listed in Table 9 (Form 3) and Table 10
(Form 3A).
Failure to get continuity for any of the test points indicates tie
board failure. Failure in other circuitry is extremely rare.
TABLE 9
Form 3 Tie Board Continuity Checks (Figure 45)
Continuity from
Terminals "B+" To
Continuity from
Terminals "B-" To
LampL
A
5A
Counter C-1
N
4B
Figure 45.
Form 3 continuity checks (Table 9). For relationship of terminal test points, see Figures 2, 18, and 19.
82040KMA
29
Continuity from
Terminals "N-1" To*
Lamp
5A
Counter 1
L-2
4B
Figure 46.
Form 3A continuity checks (Table 10). For relationship of terminal test points, see Figures 20 and 21.
30
88948KMA
S280-75-2
BATTERY CHARGING
To check the battery charging operation:
1. Make sure control is in home (reset) position by moving
manual operator to CLOSE.
2. Connect a dc milliammeter into right hand pair of battery-test
terminals(l ),see Figure 47. Loosen both terminals
slightly and disconnect shorting link from between terminals.
3. With battery charger deenergized, current will flow opposite
to the direction shown by CHG. Under normal conditions,
quiescent drain will be 1-1/2-to 2-mA. However, shorter time
reset plugs and certain accessories can, as shown in Table
11, increase quiescent drain above nominal value.
TABLE 11
Quiescent-Battery Drain Above Normal*
Description
3-second reset plug
10-second reset plug
Sequence coordination accessory (if blocked in
home)
Remote minimum-trip double-supervisory contacts
closed)
Targets
Drain (mA)
2.3
0.8
0.8
6
1.9
Figure 48.
Comparison of charging rates.
* For complete list of accessory quiescent drain, see the Service Information
manual on the MET Tester, S28O-76-1.
Figure 47.
Battery test terminals.
31
Figure 49.
Block diagram of test points for battery-charging circuitry. See Figures 50 and 51 and Tale 12 for specific testing points and values.
32
S280-75-2
TABLE 12
Battery-Charging Circuitry Checks (Figures 49, 50 and 51)
Test Points
A
A
B
B1 & B2
Location
Form 3
120/240
-
120/240
120/240
120/240
-
35-38*
52-55*
120/240
C1 & C2
35-38*
52-55*
32-35*
34-36*
32-35*
If Voltage Reading Is
Not Obtained, Check:
* The actual voltage reading will depend on the type of voltmeter used. This voltage will be lower if the control battery is totally discharged. Repeat test
with a fully charged battery.
Figure 50.
Form 3 test points for battery-charging acessory circuitry (Table 12).
33
Figure 51.
Form 3A test points for battery-charging circuitry (Table 12).
34
S280-75-2
MECHANICAL AND ELECTRICAL HARDWARE
All mechanical and electrical hardware components (selector
switches, toggle switches, manual switch, operations counter,
trip sockets, phase sockets, resistor brackets, fuse receptacle,
etc.) can be visually or electrically checked. If replacement is
needed, remove wires, noting their exact placement, remove all
connecting hardware and then remove the existing component.
Install the new component by reversing procedure. See
Appendix V for connection diagrams for ME controls Form 2, 3,
and 3A.
BATTERY MAINTENANCE
Battery Specifications
Nickel-cadmium.
24-volts (20 cells in series).
1.0 Ampere hour capacity (10 hour rate).
Charging rate: 50-mA maximum.
Weight: 41.5 oz.
Length: 10.
Width: 2.
Height: 2.
2. A KA1142ME3 120-Vac battery charger is available for maintaining one ME control battery.
The KA1142ME3 battery charger provides two charging
rates, 15-mA and 50-mA. The 15-mA charging rate is used to
maintain a battery at full charge. The 50-mA rate is used to
charge a discharged battery. A battery must be charged at
the 50-mA rate for 48 hours.
Figure 52.
Field testing a battery.
35
Figure 53.
Typical voltage versus temperature characteristics of nickel-cadmium battery.
36
has this built in) across the battery for approximately 2-3 seconds. The voltage must not drop more than 3-volts below the
open circuit voltage for temperatures above 20-degrees F.
6. Make a capacity check. Discharge the battery through a 100ohm, 12-watt resistor for 3-hours. At the end of this period and
while under load, check the individual cell voltages. No cell
should read less than 1.1-volts.
7. Remove the 100-ohm resistor. Recheck the open-circuit voltage on each cell after 7-days. All cells should measure very
close to the same voltage level. Do not recharge the battery
prior to this test.
If the battery passes the above test, it is in satisfactory condition; replace the battery covers, recharge (48-hours using the
KA1142ME battery charger) and return to service.
S280-75-2
APPENDIX I
Test Sheet
NOTE: The following sample test sheet is a convenient method to systematically test the ME electronic control and then return it to its original programming condition
CIRCUIT NO.
LOCATION
TESTER
CONTROL S/N
RECLOSER S/N
GND
DIAL SETTING
GND:
LOCKOUT
C
PHASE:
1st
2nd
PHASE 1st
2nd
NORMAL RECLOSE
NON-RECLOSE
RECLOSING PLUGS
1st
2nd
3rd
RESET
MINIMUM TRIP
GND
DIAL SETTING
GND: FAST
DELAY
LOCKOUT
PHASE: FAST
DELAY
TESTS
TIMING
% AMP
FIRST SHOT
SECOND SHOT
THIRD SHOT
SHOTS
FOURTH SHOT
GND
PHASE A
PHASE B
PHASE C
RECLOSING
1st
2nd
3rd
RESET
NON-RECLOSE TEST
37
APPENDIX IV
ME Contol Parts
TABLE 13
Electronic Recloser Maintenance Manuals
Product Type
WE
VWE and VWVE
RXE (S/N 517 and above)
WE (S/N 6316 and above)
RVE (S/N 2200 and above)
WVE (S/N 1000 and above)
VSML
S280-40-8
S280-45-3
APPENDIX III
Accessory Manuals
TABLE 14
Form 3 and 3A Type ME Electronic Control Acessory
Operation, Circuitry,Testing and Field Installation Manuals
Service
Information Form
Number
2,3,3A
S280-75-4
S280-75-5
S280-75-14
S280-75-15
Accessory
Catalog No.
KA316ME4
KA304M E
KA333ME
KA1009,
KA1010
KA1011,
KA1012
S280-75-17 2
KA418ME
S280-75-19 2, 3, 3A KA287ME
S280-75-20 2 3
KA542ME
Accessory
Description
3, 3A
2, 3
2, 3, 3A
2, 3
Remote-Close
Reset-After-Reclose
Reclose-Blocking
Low Ground Fault Tripping
S280-75-21
S280-75-22
S280-75-23
S280-75-25
S280-75-26
S280-75-31
S280-75-32
S280-75-33
S280-75-34
S280-75-36
S280-75-37
S280-75-38
S280-75-39
3, 3A
2, 3
2, 3
3, 3A
2, 3
3, 3A
2, 3
3, 3A
3
3, 3A
3A
3, 3A
3A
KA1002ME
KA531ME
KA472ME
KA1037ME
KA458M E
KA1004ME
KA880ME
KA1036ME
KA418ME3
KA333M E
KA418ME7
KA639ME3
KA542ME
S280-75-40
S280-75-41
S280-75-42
S280-75-43
3A
3, 3A
3, 3A
3, 3A
S280-75-44 3, 3A
S280-75-45 3A
KA880ME
KA1137ME
KA1163ME
KA1009ME,
KA1010ME,
KA1011 ME,
KA1012ME
KA531ME
KA1174ME
Sequence Coordination
Surge Protection
ThermostaticalIy Controlled,
Heater
Minimum-Trip Doubler
Fuse-Elimination
Lockout Indicating
Instantaneous Trip
Battery-Charging
Remote Trip
DC Voltage Supply
Instantaneous Lockout
Sequence Coordination
Reclose-Blocking
Sequence Coordination
Remote Lockout
ThermostaticalIy Controlled
Heater
DC Voltage Supply
Target Annunciator
Minimum Response Time
Low Ground Fault Tripping
S280-75-47 3A
KA1021ME
S280-75-48 3A
KA1119ME,
KA1122ME
KA2003ME
S280-75-49 3, 3A
S280-75-50
S280-75-51
S280-75-52
S280-75-53
S280-75-55
S280-75-56
S280-75-57
S280-75-61
38
TABLE 15
Type ME Control Plug-In Panel Components Form 2 (Above
S/N 1900), Form 3 (Above S/N 4000), Form 3A (Above S/N
26000)
Catalog No.
KA216ME1S
KA216ME2S
KA216ME3S
KA216ME4S
KA216MESS
KA216ME6S
KA216ME7S
KA216ME8S
KA216ME9S
KA216M E11S
KA216ME13S
KA216ME14S
KA216ME15S
KA216ME16S
KA216ME17S
KA216ME18S
KA216MEKS
KA217MEAS
KA217MEBS
KA217MECS
KA217MEDS
KA217MEES
KA217MEFS
KA217MEGS
KA217MEHS
KA217MEJS
KA217MEKS
KA217MELS
KA217MEMS
KA217MENS
KA217MEPS
KA217MERS
KA217METS
KA217MEVS
KA217MEWS
KA217MEXS
KA217MEZS
KA243MEXXXS
KA244ME10SS
KA244MEXXXS
Fuse Elimination
Temperature Regulated Battery
Charger
Phase and Ground Protective
Accessory
Capacitor Backup Trip
KA244ME5.8S
KA275MEXXS
KKA301MEXXXS
KA302MEXXXS
KA101SMES
KA1016MES
Description
Ground Trip Timing Plug Curve 1
Ground Trip Timing Plug Curve 2
Ground Trip Timing Plug Curve 3
Ground Trip Timing Plug Curve 4
Ground Trip Timing Plug Curve 5
Ground Trip Timing Plug Curve 6
Ground Trip Timing Plug Curve 7
Ground Trip Timing Plug Curve 8
Ground Trip Timing Plug Curve 9
Ground Trip Timing Plug Curve 11
Ground Trip Timing Plug Curve 13
Ground Trip Timing Plug Curve 14
Ground Trip Timing Plug Curve 1S
Ground Trip Timing Plug Curve 16
Ground Trip Timing Plug Curve 17
Ground Trip Timing Plug Curve 18
Ground Trip Timing Plug Curve K
Phase Trip Timing Plug Curve A
Phase Trip Timing Plug Curve B
Phase Trip Timing Plug Curve C
Phase Trip Timing Plug Curve D
Phase Trip Timing Plug Curve E
Phase Trip Timing Plug Curve F
Phase Trip Timing Plug Curve G
Phase Trip Timing Plug Curve H
Phase Trip Timing Plug Curve J
Phase Trip Timing Plug Curve K
Phase Trip Timing Plug Curve L
Phase Trip Timing Plug Curve M
Phase Trip Timing Plug Curve N
Phase Trip Timing Plug Curve P
Phase Trip Timing Plug Curve R
Phase Trip Timing Plug Curve T
Phase Trip Timing Plug Curve V
Phase Trip Timing Plug Curve W
Phase Trip Timing Plug Curve X
Phase Trip Timing Plug Curve Z
Phase Min Trip Resistor 100,120,140,170,
200, 240, 280, 300, 340, 400, 480, 560, 600,
680, 800, 960, or 1120 Amp Yellow Label for
all Reclosers Except ME and VSMT.
Change XXX in Catalog No. to Amps.
Ex: KA243ME280S
Low Ground Min Trip Resistor 10 Amp Yellow
Label for all Reclosers Except ME and
VSMT
Ground Min Trip Resistor 25, 35, 50, 70,100,
120,140,170, 200, 240, 280, 340, 400, 480,
or 560 Amp Yellow Label for all Reclosers
Except ME and VSMT. Change XXX in
Catalog No. to Amps. Ex: KA244ME140S
Low Ground Min Trip Resistor 5.8 Amp
Yellow Label for all Reclosers Except ME
and VSMT
Reclosing Delay Single Value, INST. or 60
Sec. Change XX in Catalog No. to INST.
Ex: KA275MEINST
Phase Min Trip Resistor 200, 240, 280, 340,
400, 480, 560, 600, 680, 800, 960,1120
1200,1360 1600 1920 or 2240 Amp Blue
Label for ME and VSMT Reclosers only.
Change XXX in Catalog No. to Amps.
Ex: KA301ME800S
Ground Min Trip Resistor 100,140, 200, 240,
280, 340, 400, 480, 560, 680, 800, 960, or
1120 Amp Blue Label for ME and VSMT
Reclosers only. Change XXX in Catalog
No. to Amps. Ex: KA3O2MES60S
Reset Delay Multiple Value Plug Including
Settings for 1015, 30, 45, 60, 90,120 and
180 Seconds
Reclosing Delay Multiple Value Plug Including
Settings for 1,2,5,7,10,15,30 and 45 Seconds
S280-75-2
TABLE 16
Type ME Control Circuit Boards and Control Cables
Form 2 (Above S/N 1900), Form 3 (Above S/N 4000,
Form 3A (Above S/N 26000)
Catalog No.
KA1ME7
KA1MEXX
KA18ME20
KA18MEXX
KA251 ME
KA252ME
KA253ME
KA254ME
KA255ME
KA256ME
KA257ME
KA267ME
Description
Control Cable, 7 Ft. All Reclosers
Longer Control Cable: 8 Thru 80 Ft. for RVE RXE
VWE, VWVE, WE, WVE Reclosers. 8 Thru 19 Ft.
for CXE, ME, VSA, VSAT, VSML, VSMT
Reclosers. Replace XX With Length.
Control Cable, 20 Ft. for CXE, ME, VSA, VSAT,
VSML, VSMT Reclosers
Extra Long Control Cable: 81 Thru 125 Ft. for
RVE, RXE, VWE, VWVE, WE, WVE Reclosers.
20 Thru 35 Ft. for CXE, ME, VSA, VSAT, VSML,
VSMT Reclosers. Replace XX With Length.
Phase Trip No. 1 Circuit Board for Form 2
Phase Trip No. 2 Circuit Board for Form 2
Ground Trip No. 1 Circuit Board for Form 2
Ground Trip No. 2 Circuit Board for Form 2
Output Circuit Board
Diode Circuit Board for Form 2
Battery Charging Circuit Board for Form 2
Reclose and Reset Circuit Board for Form 2
Catalog No.
KA381MES
KA382MES
KA383MES
KA384MES
KA385MES
KA386MES
KA387MES
KA388ME1S
KA388ME2S
KA1103ME
KA1109ME8
KA1L00ME9
KA1172ME
Description
Reclose and Reset Circuit Board for Form 3
and 3A
Diode Circuit Board for Form 3 and 3A
Output Circuit Board for Form 3 and 3A
Ground Trip No. 2 Circuit Board for Form 3 and 3A
Ground Trip No. 1 Circuit Board for Form 3 and 3A
Phase Trip No. 2 Circuit Board for Form 3 and 3A
Phase Trip No. 1 Circuit Board for Form 3 and 3A
Battery Charging Circuit Board for Standard
Charger on Form 3 and 3A Below 53381
Battery Charging Circuit Board for Dual Rate
Charger on Form 3 Above 5500 and Form 3A
Tie Board for Form 3A
120-Vac Ballast and Surge Card for Fixed or
Temperature Regulated Battery Charger
240-Vac Ballast and Surge Card for Fixed or
Temperature Regulated Battery Charger
Temperature Regulated Battery Charging Board
for Form 3A
TABLE 17
Type ME Control Replacement Parts and Accessories
Form 2 (Above S/N 1900), Form 3 (Above S/N 4000), Form 3A (Above S/N 26000)
Catalog No.
KA107LS1
KA107LS2
KA234ME1
KA250ME
KA279ME
KA287ME5S
KA287ME6S
KA290ME1
KA293ME2
KA304ME1
KA304ME4
KA316ME2S
KA316ME4S
KA325ME2
KA333ME7
KA333ME8
KA333ME9
KA333ME10
KA333ME11
KA333ME12
KA406ME
KA410ME
KA418ME3
KA418ME7S
KA423MES
KA450ME2S
KA452ME
KA458ME3
KA458ME4
Description
Relay Assembly
Relay Assembly
Ground Matching Transformer (1 Per Control)
Tie Board for Form 2
Phase Matching Transformer (3 Per Control)
Form 2 and 3
24-Vdc Supply Adapter Accessory for Form 3,
from 5501 Thru 25999
24-Vdc Supply Adapter Accessory for Form 3A
Above 26000
Selector Switch and Wire Pistol Grip Form
2 and 3
Load Current Indicator Accessory Form 3,
Above 5500
Reset After Successful Reclose Accessory for
Form 2, Below 1900
Reset After Successful Reclose Accessory for All
Form 3 Controls
Remote Closing Accessory for Form 2, 1900
and Above
Remote Closing Accessory for Form 3,
Above 5500
Adapter Accessory for Form 3 Control to Form 1
Recloser
Blocking of Reclosing Accy. When Deenergized
for 120-Vac for Form 3 Above 5500 to 26000
Blocking of Reclosing Accessory When
Energized for 12O-Vac for Form 3, Above 5500
to 26000
Blocking of Reclosing Accessory When
Deenergized for 240-Vac for Form 3, Above
5500 to 26000
Blocking of Reclosing Accessory When
Energized for 240-Vac for Form 3, Above 5500
to 26000
Block of Reclosing Accy.120-Vac While
Deenergized, for F3A 26000 and Above
Block of Reclosing Accy.120-Vac While
Energized, for F3A 26000 and Above
Input Plug and Wire Harness for Form 2
Tie Board for Form 3
Sequence Coordination Accessory for Form 3,
Below 5500
Sequence Coordination Accessoryfor Form 3
5501-25999 and Form 3A, Above 26000
Circuit Boardfor Remote Closing Accessory
Battery24V, for Form 3 and 3A
Control Counter Assembly Form 1 2, 3 and 3A
Battery Charging Accessory 115-Vac for Form 3,
from 5501 Thru 25999
Battery Charging Accessory 230-Vac for Form 3
from 5501 Thru 25999
Catalog No.
KA472ME3S
KA514ME1
KA531ME3S
KA544ME1S
KA544ME2S
KA544ME3S
KA544ME4S
KA578MES
KA609ME1
KA614ME1
KA638ME1S
KA639ME3S
KA641 ME500
KA642ME500
KA682ME1
KA684ME
KA689ME920
KA703ME
KA710ME2
KA710ME3
KA712ME3
KA712ME4
KA713ME1
KA713ME2
KA713ME3
KA713ME4
KA713ME5
KA713ME6
KA713ME7
KA713ME8
Description
Lockout Indicating Contact Accy.for Form 3
Above 5500 and Form 3A
Phase Trip Protection Accessory1 Required
Per Control for Form 2, 1615 and Above; for
Form 3 Below 4100; Obsolete
Fuse Elimination Accessory for Form 2, 1900 and
Above, Form 3 and Form 3A
Heater Element Oniy 120-Vac 100-85F
Heater Element Only 240-Vac 100-85F
Heater Element only 120-Vac 60-15F
Heater Element Only 240-Vac 60-15F
Potential Battery Chargerfor Form 3 only
Target AccessoryWith Indicating Buttons,
Phase Trip only for Double Size Cabinet, for
Form 3 Below 5500; obsolete
Control Cable Locking Sleeve
Battery Test Voltmeter Portable Type
Remote Lockout Accessory for Form 3 Above
5500 and Form 3A
Single Cabinet
Double Cabinet
Standard Input Plug Board and Harness Form 3
Battery Connector
Ground Trip Sequence Selector Switch Form 2
and 3
Battery (Gould) for Form 1Obsolete
Battery Adapter Kit for Connection of Form 2
Battery to Form 3 Control, Male Receptacle
Battery Adapter Kit for Connection of Form 3
Battery to Form 2 Control, Female Receptacle
24-Vdc Supply Adapter Accy. for Field
Installation for Form 3, Below 5500
24-Vdc Supply Adapter Accessory for Field
Installation for Form 3, 5500 and Above
Field Kit for Thermostatic Heater With Surge
Protection 115-Vac, for 1900 to 12250
Field Kit for Thermostatic Heater with Surge
Protection 23O-Vac, for 1900 to 12250
Field Kit for Thermostatic Heater with Surge
Protection and Fuse Disconnect 115-Vac, from
S/N 12250 to 26000
Field Kit for Thermostatic Heater With Surge
Protection and Fuse Disconnect 230-Vac, from
S/N 12250 to 26000
Field Kit for Thermostatic Heater 120-Vac, 85/100
Degree F. Above 26000
Field Kit for Thermostatic Heater 120-Vac,
15/60 Degree F; Above 26000
Field Kit for Thermostatic Heater 240-Vac,
85/100 Degree F; Above 26000
Field Kit for Thermostatic Heater 240-Vac,
15/60 Degree F; Above 26000
39
40
Description
Reclosing Fuse Replacement Kit
120-Vac Surge Protection Field Kit
240-Vac Surge Protection Field Kit
Battery Post Installation Kit, 4000 and Above
48-Vdc Supply Adapter (AEP only 15 Amp)
125-Vdc Supply Adapter (AEP only 5 Amp)
125-Vdc Supply Adapter (AEP only 5 Amp)
48-Vdc Supply Adapter (15 Amp) from 5501 Thru
25999
125-Vdc Supply Adapter (15 Amp) from 5501
Thru 25999
125-Vdc Supply Adapter (15 Amp) from 5501
Thru 25999
48-Vdc Supply Adapter (15 Amp) 26000 and
Above
125-Vdc Supply Adapter (5 Amp) 26000 and
Above
125-Vdc Supply Adapter (15 Amp) 26000 and
Above
48-Vdc Field Kit for DC Supply15A 240-Vac
F3A
125-Vdc Field Kit for DC Supply5A 240-Vac
F3A
125-Vdc Field Kit for DC Supply15A 240-Vac
F3A
Battery Bracket Mounting Kit for GE Batteries in
Controls Below 15000
Conversion Kit to Cold Load Pickup from Form 3
to Form 3A
Retrofit Kit for Replacing Demand MetersWith
Instantaneous Indicating Elements Below
35909
Retrofit Kit for Replacing Demand Meters
Without Instantaneous Indicating Elements,
Below 35909
Battery24V, for Form 2
Phase Trip Sequence Selector Switch
Phase Trip Sequence Selector Switchfor Use
With Sequence Coodination Accessory
Standard Heater240V
Battery Charging Isolation Transformer
Minimum Trip DoublerLocal Operation
Phase only
Minimum Trip DoublerLocal Operation
Phase and Ground
Minimum Trip DoublerRemotely operated
Minimum Trip DoublerThree Wire Control to
Double Return
Remote Trip Accessory Kit
Protective Accessory Field Kit for Ground Trip
4000 to 50071, Supersedes KA921 ME4
Protective Accessory Field Kit for Phase Trip
4000 to 50071, Supersedes KA921 ME5
Protective Accessory Field Kit for Phase and
Ground Trip4000 to 50071, Supersedes
KA921 ME6
Fault IndicatorCounter Type Phase and
Ground, Above 14450
Instantaneous LockoutPhase only, Multiple
of 1.4, 2.0, 2.8, 4.0, or 5.6
Instantaneous LockoutPhase Only, Multiple
of 5.6, 8.0 11.2 16.0 or 22.4
Instantaneous LockoutPhase and Ground,
Both With Multiples of 1.4, 2.0, 2.8, 4.0, or 5.6
Instantaneous LockoutPhase and Ground,
Phase Multiple of 1.4, 2.0, 2.8, 4.0 or 5.6;
Ground Multiple of 5.6, 8.0, 11.2, 16.0, or 22.4
Instantaneous LockoutPhase and Ground
Phase Multiple of 5.6, 8.0, 11.2 1 6.0 or 22.4
Ground Multiple of 1.4, 2 0, 2.8, 4.0 or 5.6
Instantaneous LockoutPhase and Ground,
Both With Multiples of 5.6, 8.0, 11.2, 16.0, or
22.4
Instantaneous TripPhase only, Multiples
of 1.4, 2.0, 2.8, 4.0 or 5.6
Instantaneous TripPhase only, Multiples
of 5.6, 8.0, 11.2 16.0, or 22.4
Instantaneous Tr;pPhase and Ground, Both
With Multiples of 1.4, 2.0, 2.8, 4.0 or 5.6
Catalog No.
KA1037ME6S
KA1037ME7S
KA1037ME8S
KA1102ME1
KA1103ME
KA1109ME8
KA1109ME9
KA1134ME1S
KA1137ME1S
KA1137ME2S
KA1141ME1
KA1142ME3
KA1159ME
KA1160ME
KA1163MES
KA1174ME1S
KA1174ME2S
KA1193ME
KA1194ME1
KA2003MES
KA2035ME2S
KA2039ME1S
KA2039ME2S
KA2047MES
KA2070ME1S
KA2070ME2S
KA2071ME1S
KA2072MES
KA2189MES
KP457ME
KP483ME1
KP509ME
KP674ME1
KP884ME
KP894ME1
KP953ME
KP1077ME1S
KP1100ME
KP1110ME
KP1139ME1
KP2069A4
KP2069A8
KP2075A2
KP2075A4
KP2075A13
KP2075A18
KP2075A19
KP2080A1S
KP2080A2S
KP4060A12
KP4060A22
KP4061A3
K721525105018A
K999904310283A
Description
Instantaneous TripPhase and Ground. Phase
Multiple of 1.4, 2.0, 2.8, 4.0 or 5.6; Ground
Multiple of S.6, 8.0, 11.2, 16.0, or 22.4
Instantaneous TripPhase and Ground, Phase
Multiple of 5.6, 8.0, 11.2, 16.0, or 22.4: Ground
Multiple of 1.4, 2.0, 2.8, 4.0, or 5.6
Instantaneous TripPhase and Ground, Both
With Multiples of 5.6, 8.0, 11.2, 16.0, or 22.4
Standard Input Plug Board and Harness for
Form 3A
Tie Board, Form 3A
Standard Charger Board120-Vac, F3A Only
Standard Charger Board240-Vac, F3A Only
Automatic Resetting Fault Indicator Circuit Board
AnnunciatorType Target AccessoryAuto
Reset, Phase only; Above 14450
AnnunciatorType Target AccessoryAuto
Reset, Phase and Ground; Above 14450
Selector Switch and Wire Pistol Grip, Form 3A
only
Shelf Battery Charger, Portable
Ground Trip Sequence Selector SwitchForm
3A only
Operations to Lockout Sequence SwitchAl1
Controls
Minimum Response Time
Temperature Regulated Battery Charger Accy.
120-Vac, for F3A 26000 and Above
Temperature Regulated Battery Charger Accy.
240-Vac, for F3A 26000 and Above
Harness only for Standard Input Plug Board
for F3A
Standard Input Plug Board only for Form 3A
Remote Close With Cold-Load Pickup
Remote Non-Reclose and Ground Trip Block
Maintained Contact, 24V
Recloser StatusWithout Indicator Lamps
Recloser StatusWith Indicator Lamps
Battery Monitorover 30-Vdc/Under 22-Vdc
Indication
Remote Close With Cold Load Pickup Remote
Lockout and StatusWithout Indicator Lamps
Remote Close With Cold Load Pickup Remote
Lockout and StatusWith Indicator Lamps
Remote Non-Reclose and Ground Trip Block
Pulse Contact, 24V
Battery MonitorAnalog
Remote Indication of Fault Target Accessory
Mounting Strip (Conducting)
Trip Resistor Clamps
Mounting Strip Insulating
Sequence Relayfor Form 3 and 3A
Circuit Board Shield
Battery Mounting Bracket, Form 3 and 3A
Panel Locking Spring
Cover
Fuse Block Single Section
Fuse Block End Closure Unit
Flip Disc TargetComplete
Knob for Number of operations Selector
Switches (Ground, Phase or Lockout)
Manual Control Switch Handle
2 Amp FuseType AGC, Glass Tube; Min.
Qty. 5
3/4 Amp Fuse, Type AGX
15 Amp FuseType BAN, Fibre Tube; Min.
Qty. 5
3/8 Amp Fuse, Slow Blow Type MDQ, Min. Qty. 5
6 Amp Fuse, Type BAN
Plastic Battery ConnectorMale, Battery
Connechon
Plastic Battery ConnectorFemale, Control
Connection
120 Volt Relay, 2 to 60 Sec.
28 Volt Relay, 2 to 60 Sec.
28 Volt Relay, 0.15 to 1.0 Sec.
Screwfor Trip Resistors Clamps
Bulb24V, for Lockout Indicator
S280-75-2
APPENDIX V
Schematic diagrams
Form 2 Connections . . . . . . . . . . . . . . .
Form 3 Connections (below S/N 5500)
Form 3 Connections (S/N 5500-25999)
Form 3A Connections . . . . . . . . . . . . .
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.pages
.pages
.pages
.pages
42-43
44-45
46-47
48-49
41
Figure 54.
Form 2 connection diagram (below S/N 1900). Since late Form 2 and early Form 3 controls share common circuits and design,
this connection diagram is given for reference.
42
S280-75-2
Form 2 Connections - continued
Figure 54 - continued.
43
Figure 55.
Form 3 connection diagram (below S/N 5500).
44
S280-75-2
Form 3 Connections - continued
Figure 55 - continued.
45
Figure 56.
Form 3 connection diagram (S/N 5500 to 25999).
46
S280-75-2
Form 3 Connections - continued
Figure 56 - continued.
47
Figure 57.
Form 3A connection diagram.
48
S280-75-2
Form 3A Connections - continued
Figure 57 - continued.
49
KRP
1/01