Alternators
LSA 43.2 - 4 Pole
Electrical and mechanical data

LSA 43.2 - 4 Pole


SPECIALLY ADAPTED FOR APPLICATIONS
The LSA 43.2 alternator is designed to be suitable for typical generator applications, such as: backup,
standard production, cogeneration, marine applications, rental, telecommunications, etc.
COMPLIANT WITH INTERNATIONAL STANDARDS
The LSA 43.2 alternator conforms to the main international standards and regulations:
IEC 60034, NEMA MG 1.22, ISO 8528, CSA, CSA/UL, marine regulations, etc.
It can be integrated into a CE marked generator.
The LSA 43.2 is designed, manufactured and marketed in an ISO 9001 environment.
TOP OF THE RANGE ELECTRICAL PERFORMANCE
- Class H insulation.
- Standard 12-wire re-connectable winding, 2/3 pitch, type no. 6 .
- Voltage range: 220 V - 240 V and 380 V - 415 V (440 V) - 50 Hz / 208 V - 240 V and 380 V - 480 V - 60 Hz.
- High efficiency and motor starting capacity.
- Other voltages are possible with optional adapted windings:
- 50 Hz: 440 V (no. 7), 500 V (no. 9), 600 V (no. 22 or 23), 690 V (no. 10 or 52)
- 60 Hz: 380 V and 416 V (no. 8), 600 V (no. 9).
- Total harmonic content < 2%.
- R 791 interference suppression conforming to standard EN 55011 group 1 class B standard for European zone (CE marking).
EXCITATION AND REGULATION SYSTEM SUITED TO THE APPLICATION

Excitation system

Regulation options

Voltage
regulator

SHUNT

AREP

PMG

R 230

Std

R 438

Std

Std

R 448

optional

Current transformer
for paralleling

Mains paralleling

R 734

Remote voltage
potentiometer

R 726

3-phase sensing

R 731

mains paralleling
unbalanced

Voltage regulator accuracy +/- 0.5%.

PROTECTION SYSTEM SUITED TO THE ENVIRONMENT


- The LSA 43. 2 is IP 23.
- Standard winding protection for clean environments with relative humidity 95 %, including indoor marine environments.
Options:
Filters on air inlet and air outlet (IP 44).
Winding protections for harsh environments and relative humidity greater than 95%.
Space heaters.
Thermal protection for winding.
REINFORCED MECHANICAL STRUCTURE USING FINITE ELEMENT MODELLING
- Compact and rigid assembly to better withstand generator vibrations.
- Steel frame.
- Cast iron flanges and shields.
- Twin-bearing and single-bearing versions designed to be suitable for engines on the market.
- Half-key balancing.
- Greased for life bearings (regreasable bearings optional)
ACCESSIBLE TERMINAL BOX PROPORTIONED FOR OPTIONAL EQUIPMENT
- Easy access to the voltage regulator and to the connections.
- Possible clusion of accessories for paralleling, protection and measurement.
- 8 way terminal block for reconnecting voltage reconnection.

Copyright 2004 : MOTEURS LEROY-SOMER


Products and materials shown in this catalogue may, at any time, be modified in order to follow the latest technological developments, improve the design or change conditions of utilization.
Their description cannot, in any case, engage LEROY-SOMER liability. The values indicated are typical values.

LSA 43.2 - 4 Pole


Common data
Insulation class
Winding pitch
Terminals
Drip proof
Altitude
Overspeed
Air ow

H
Excitation system
2/3 ( bob 6 )
A.V.R. model
12
Voltage regulation (*)
IP 23
Sustained short-circuit current
1000 m
Total harmonic TGH / THC (**)
Waveform : NEMA = TIF
2250 min-1
0,27 m3/s (50Hz)/ 0,32 (60Hz) Wave form : I.E.C. = THF

SHUNT
A R E P or PMG
R 230
R 438
0,5 %
0,5 %
300% (3 IN) : 10s
at no load < 2 % - on load < 2 %
< 50
<2%

(*) Steady state duty. (**) Total harmonic content line to line, at no load or full rated linear and balanced load.

Ratings 50 Hz - 1500 R.P.M.


kVA / kW - Power factor = 0,8
Duty T C
Class / T K
Phase
Y

YY
kVA
43.2 S1

Continuous duty 40C


H / 125 K
3 ph.
1 ph.
380V 400V 415V 440V

Continuous duty 40C


F / 105 K
3 ph.
1 ph.
380V 400V 415V 440V

Stand-by / 40 C
H / 150 K
3 ph.
1 ph.
380V 400V 415V 440V

Stand-by / 27 C
H / 163 K
3 ph.
1 ph.
380V 400V 415V 440V

220V 230V 240V

220V 230V 240V

220V 230V 240V

220V 230V 240V

230V
220V

230V
220V

230V
220V

230V
220V

35

35

35

35

24

33

33

33

33

22

40

40

40

40

26

45

45

45

45

kW

28

28

28

28

19

26

26

26

26

18

32

32

32

32

21

36

36

36

36

27
22

43.2 S15

kVA

40

40

40

40

28

36

36

36

36

26

44

44

44

44

30

47

47

47

47

31

kW

32

32

32

32

22

29

29

29

29

21

35

35

35

35

24

38

38

38

38

25

43.2 S25

kVA

45

45

45

45

31

43

43

43

43

29

49

49

49

49

33

52

52

52

52

34

kW

36

36

36

36

25

34

34

34

34

23

39

39

39

39

26

42

42

42

42

27

43.2 S35

kVA

50

53

52

47

33

45

48

47

42

30

53

56

55

50

35

55

58

57

53

36

kW

40

42

42

38

26

36

38

38

34

24

42

45

44

40

28

44

46

45

42

29

43.2 M45

kVA

56

60

60

60

35

51

53

53

53

32

59

63

63

63

37

62

66

66

66

38

kW

45

48

48

48

28

41

42

42

42

26

47

50

50

50

30

50

53

53

53

30

43.2 L65

kVA

67

70

69

68

41

61

62

63

62

38

71

74

73

73

43

74

77

76

75

45

kW

53

56

55

55

33

49

50

50

50

30

57

59

58

58

34

59

62

61

60

36

43.2 L8

kVA

78

80

78

76

48

71

73

71

70

45

83

84

83

83

53

86

88

86

84

54

kW

62

64

63

61

38

57

58

57

56

36

66

67

66

66

42

69

70

69

67

43

Ratings 60 Hz - 1800 R.P.M.


kVA / kW - Power factor = 0,8
Duty T C
Class / T K
Phase
Y

YY
kVA
43.2 S1

Continuous duty 40C


H / 125 K
3 ph.
1 ph.
380V 416V 440V 480V

Continuous duty 40C


F / 105 K
3 ph.
1 ph.
380V 416V 440V 480V

Stand-by / 40 C
H / 150 K
3 ph.
1 ph.
380V 416V 440V 480V

Stand-by / 27 C
H / 163 K
3 ph.
1 ph.
380V 416V 440V 480V

220V 240V

220V 240V

220V 240V

220V 240V

240V

208V 220V 240V

240V

208V 220V 240V

240V

208V 220V 240V

240V

208V 220V 240V

44

44

44

44

28

40

40

40

40

25

50

50

50

50

29

56

56

56

56

kW

35

35

35

35

22

32

32

32

32

20

40

40

40

40

23

45

45

45

45

30
24

43.2 S15

kVA

50

50

50

50

31

45

45

45

45

28

54

55

55

55

33

56

59

59

59

34

kW

40

40

40

40

25

36

36

36

36

22

43

44

44

44

26

45

47

47

47

27

43.2 S25

kVA

51

54

56

56

35

47

50

50

50

32

54

58

59

59

37

56

60

62

62

38

kW

41

43

45

45

28

38

40

40

40

26

43

46

47

47

30

45

48

50

50

30

43.2 S35

kVA

53

58

60

66

36

49

53

55

59

34

57

61

64

69

39

59

63

66

73

40

kW

42

46

48

53

29

39

42

44

47

27

46

49

51

55

31

47

50

53

58

32

43.2 M45

kVA

57

62

64

71

39

53

57

59

64

36

62

66

69

75

42

64

68

71

78

43

kW

46

50

51

57

31

42

46

47

51

29

50

53

55

60

34

51

54

57

62

34

43.2 L65

kVA

67

72

75

83

45

62

66

69

74

42

72

77

80

87

48

74

80

84

91

50

kW

54

58

60

66

36

50

53

55

59

34

58

62

64

70

38

59

64

67

73

40

43.2 L8

kVA

80

85

88

95

53

73

78

81

87

49

86

91

95

102

57

88

95

99

107

59

kW

64

68

70

76

42

58

62

65

70

39

69

73

76

82

46

70

76

79

86

47

LSA 43.2 - 4 Pole


Efficiencies 50 Hz - P.F. : 1 / P.F. : 0,8
LSA 43.2 S1

94%
91,5

92

92

P.F. : 1

89,7

89,4

90

P.F. : 0,8

89,1

87,9

86

85,5

84

10

15

20

25

30

35

40

92,5

91,9

92
90

10

89,6

88,1

30

40
93,6

92

P.F. : 1

60

70 kVA

92,8

93,1

P.F. : 1

90,9

P.F. : 0,8

89,7

89,7

P.F. : 0,8

88

87,8

86,6

91,5

91

90

89,5

50

LSA 43.2 L65


93,5

91,8

88,5

89,2

86
5

10

15

20

25

30

35

40

45

10

50 kVA

LSA 43.2 S25

94%
92,2

92,4

89,7

88

60

94

93,6

91,8

91

70

93,4

90,1

90,5
89,8

P.F. : 0,8

89,2

80 kVA

P.F. : 1

91,5

90

87,9

87,4

86

40
50
LSA 43.2 L8

93,7
91,5

89

30

92

P.F. : 1

90

20

94%

91,9

92

P.F. : 0,8

88

87

86

84

10

15

20

25

30

35

40

45

50

10

55 kVA

20

30

40

50

60

70

80

90 kVA

LSA 43.2 S35

94%

92,6

92,4

92

89,3

90

89,9

91,7
P.F. : 1

89,3

88

88

87,7

86
84

20

94%

92,2

84

92

P.F. : 0,8

89

88,4

45 kVA

LSA 43.2 S15

94%

86

90,2
89

86

88

P.F. : 1
90,8

90,4

88

86,9

92,6 92,3

93,2

93,1

92

90
88

LSA 43.2 M45

94%

92,4

92,4

10

20

30

40

P.F. : 0,8

87,3

50

60 kVA

Reactances Class H / 400 V - Time constants (ms)


S1

S15

S25

S35

M45

L65

L8

Kcc

Short-circuit ratio

0,54

0,48

0,42

0,43

0,39

0,37

0,41

Xd

Direct axis synchro.reactance unsaturated

223

255

287

292

304

310

284

Xq

Quadra. axis synchr.reactance unsaturated

134

153

172

175

182

186

170

Tdo

Open circuit time constant

1131

1131

1131

1177

1270

1354

1431

Xd

Direct axis transient reactance saturated

9,8

11,2

12,6

12,4

11,9

11,4

9,9

Td

Short-Circuit transient time constant

50

50

50

50

50

50

50

X"d

Direct axis subtransient reactance saturated

4,9

5,6

6,3

6,2

5,9

5,7

T"d

Subtransient time constant

X"q

Quadra. axis subtransient reactance saturated

6,1

7,9

7,7

7,4

7,1

6,3

Xo

Zero sequence reactance unsaturated

0,5

0,8

0,1

0,7

0,5

0,8

0,1

X2

Negative sequence reactance saturated

5,6

6,3

7,1

6,7

6,4

5,7

Ta

Armature time constant

Others data - Class H / 400 V

io (A)

No load excitation current (SHUNT / AREP or PMG)

0,5/1

0,5/1

0,5/1

0,5/1

0,4/0,8

0,4/0,8

0,4/0,8

ic (A)

Full load excitation current (SHUNT / AREP or PMG)

1,3/2,6

1,5/3

1,6/3,2

1,8/3,6

1,6/3,2

1,6/3,2

1,6/3,2

uc (V)

Full load excitation voltage (SHUNT / AREP or PMG)

24/12

27/13

30/15

32/16

30/15

29/15

29/14

ms

Recovery time (U = 20 % trans.)

500

500

500

500

500

500

500

kVA

Motor start. (U = 20% sust.) or (U = 50% trans.) SHUNT

120

120

120

128

156

184

213

kVA

Motor start. (U = 20% sust.) or (U = 50% trans.) AREP

135

135

135

150

176

200

240

Transient dip (rated step load) SHUNT / PF : 0,8 LAG

13,6

14,9

16,1

15,8

15,5

15

13,9

Transient dip (rated step load) AREP / PF : 0,8 LAG

11,4

12,3

13,3

13,1

12,8

12,5

11,6

No load losses

980

980

980

1110

1120

1210

1410

Heat rejection

3410

4120

4920

5770

5890

6370

6640

LSA 43.2 - 4 Pole


Transient voltage variation 400 V - 50 Hz
Load application (Shunt excitation)
S35

S1/S15/S25

25 %

M45

Load application (AREP ou PMG excitation)


L65

L8

15
10
5

L65

L8

15
10
5

0
0

50

100

150

200 kVA

50

100

kVA at 0,8 power factor

150

S35

M45
L65

L8

25

25

% Voltage rise

30%

20
15

0
150

L8

15
10

100

L65

20

10

50

S35

S1/S15/S25

30%

250kVA

Load rejection (AREP or PMG excitation)

M45
S1/S15/S25

200

kVA at 0,8 power factor

Load rejection (Shunt excitation)

% Voltage rise

M45

20

% Voltage dip

% Voltage dip

20

S35

S1/S15/S25

25 %

200 kVA

50

100

150

200 kVA

kVA at 0,8 power factor

Motor starting (SHUNT excitation)


S35

M45

Motor starting (AREP or PMG excitation)


L65

L8

S1/S15/S25

35%

35%

30

30

25

25

% Voltage dip

% Voltage dip

S1/S15/S25

20
15

M45

L65

L8

20
15

10

10

S35

0
0

50

100

150

200

kVA Locked rotor

250

300 kVA

50

100

150

200

250

300 kVA

kVA Locked rotor

1) For a starting P.F. differing from 0,6 the starting kVA must be multiplied by (Sine /0,8)
2) For voltages other than 400V(Y) , 230V() at 50 Hz then kVA must be multiplied by (400/U)2 or (230/U)2.

LSA 43.2 - 4 Pole


Efficiencies 60 Hz - P.F. : 1 / P.F. : 0,8
LSA 43.2 S1

94%
92

92

P.F. : 1

89,7

88,9

90

P.F. : 0,8

89,4

88

86
84,2

10

15

20

25

30

35

40

45

50

55

92

91,9

P.F. : 1

88

P.F. : 0,8

89

20

25

87,7

30

35

92,3

89,6

88

40

45

50

60

70

80 kVA

93,3 93,1 P.F. : 1

91,3

91,2

90,4

90

88,6

55

10

60 kVA

20

30

40

P.F. : 0,8

50

60

70

93,2

92

91,6

91,1
P.F. : 0,8

89,8
88,1

100kVA

90,7

91,7

90

P.F. : 0,8

89,5

90

93,7 93,6 P.F. : 1

93,8

91,8
P.F. : 1

80

LSA 43.2 L8

94%

92

88,5

86

93,5

93

88

LSA 43.2 S25


91,7

90

50

86

15

92

40
LSA 43.2 L65

89,6

85,5

10

30

90

88,2

86,7

94%

88

88,7

86,4

86

84

10

20

30

40

50

60

10

70kVA

20

30

40

50

60

70

80

90

100 110 kVA

LSA 43.2 S35

94%

92,5

91,9

92

92,2

92
P.F. : 1

90

89,8

89,6

88,6

88,1

88,1

P.F. : 0,8

86,8

86
84

89,7

89,3

20

92

90

88

10
94%

92,2

91,3

87,7

60 kVA

LSA 43.2 S15


92,2

84

89,4
P.F. : 0,8

86

94%

86

88,9

89,8

88,9

P.F. : 1
90,6

90,7

85,4

92,9 92,7

92

90,7

84

93,1

92,5

90
88

LSA 43.2 M45

94%

92,3

92,1

10

20

30

40

50

60

70

80 kVA

Reactances Class H / 480 V - Time constants (ms)


S1

S15

S25

S35

M45

L65

L8

Kcc

Short-circuit ratio

0,52

0,46

0,41

0,42

0,39

0,38

0,4

Xd

Direct axis synchro.reactance unsaturated

234

265

297

303

300

306

293

Xq

Quadra. axis synchr.reactance unsaturated

140

159

178

181

180

184

176

Tdo

Open circuit time constant

1131

1131

1131

1177

1270

1354

1431

Xd

Direct axis transient reactance saturated

10,3

11,7

13,1

12,8

11,8

11,3

10,2

Td

Short circuit transient time constant

50

50

50

50

50

50

50

X"d

Direct axis subtransient reactance saturated

5,1

5,8

6,5

6,4

5,9

5,6

5,1

T"d

Subtransient time constant

X"q

Quadra. axis subtransient reactance saturated

6,4

7,3

8,2

7,3

6,3

Xo

Zero sequence reactance unsaturated

0,4

0,7

0,8

0,4

0,1

0,5

0,8

X2

Negative sequence reactance saturated

5,8

6,6

7,4

7,2

6,6

6,3

5,8

Ta

Armature time constant

Others data - Class H / 480 V

io (A)

No load excitation current (SHUNT / AREP or PMG)

0,5/1

0,5/1

0,5/1

0,5/1

0,4/0,8

0,4/0,8

0,4/0,8

ic (A)

Full load excitation current (SHUNT / AREP or PMG)

1,4/2,8

1,5/3

1,6/3,2

1,8/3,6

1,6/3,2

1,6/3,2

1,6/3,2

uc (V)

Full load excitation voltage (SHUNT / AREP or PMG)

25/12

27/14

30/15

33/16

29/14

29/14

29/14

ms

Recovery time (U = 20 % trans.)

500

500

500

500

500

500

500

kVA

Motor start. (U = 20% sust.) or (U = 50% trans.) SHUNT.

151

151

151

162

198

233

269

kVA

Motor start. (U = 20% sust.) or (U = 50% trans.) AREP

175

175

175

190

225

265

310

Transient dip (rated step load) SHUNT / PF : 0,8 LAG

Transient dip (rated step load) AREP / PF : 0,8 LAG

14

15,3

16,5

16,2

15,3

14,9

14

11,7

12,7

13,6

13,4

12,7

12,4

11,6

No load losses

1440

1440

1440

1630

1640

1770

2060

Heat rejection

4150

4910

5760

6730

6420

6970

7570

LSA 43.2 - 4 Pole


Transient voltage variation - 480 V - 60 Hz
Load application (SHUNT excitation)
S35

S1/S15/S25

25 %

M45

Load application (AREP or PMG excitation)

L65

L8

S35

15
10

L8

10
5

0
0

50

100

150

200

250 kVA

50

kVA at 0,8 power factor

100

150

S35

250 kVA

Load rejection (AREP or PMG excitation)

M45
S1/S15/S25

200

kVA at 0,8 power factor

Load rejection (SHUNT excitation)

M45
L65

L8

30%

30%

25

25

20
15

L8

20
15

10

10

L65

S35

S1/S15/S25

% Voltage rise

% Voltage rise

L65

15

0
0

50

100

150

200 kVA

50

100

S35

200 kVA

Motor starting (AREP or PMG excitation)

Motor starting (SHUNT excitation)


S1/S15/S25

150

kVA at 0,8 power factor

kVA at 0,8 power factor

M45

L65

L8

S1/S15/S25

35%

35%

30

30

25

25
% voltage dip

% voltage dip

M45

20
% Voltage dip

20
% Voltage dip

S1/S15/S25

25 %

20
15

M45

L65

L8

20
15

10

10

S35

0
0

50

100

150

200

Locked rotor

250

300 kVA

50

100

150

200

250

300

350 kVA

Locked rotor

1) For a starting P.F. differing from 0,6 the starting kVA must be multiplied by (Sine /0,8)
2) For voltages other than 480V(Y), 277V(), 240V(YY ) at 60 Hz then kVA must be multiplied by (480/U)2 or (277/U)2 or (240/U)2.

LSA 43.2 - 4 Pole


3 phase short-circuit curves at no load and rated speed (star connection Y)
10000

Current (A)

LSA 43.2 S1

Symmetrical
Asymmetrical
1000

AREP or PMG
100

SHUNT
10
1

10

100

1000

10000

time (ms)

10000

Current (A)

LSA 43.2 S15

Symmetrical
Asymmetrical
1000

AREP or PMG
100

SHUNT

10
1

10

100

1000

10000

time (ms)

10000

Current (A)

LSA 43.2 S25

Symmetrical
Asymmetrical
1000

AREP or PMG
100

SHUNT

10
1

10

100

1000

10000

time (ms)

10000

Current (A)

LSA 43.2 S35

Symmetrical
Asymmetrical
1000

AREP or PMG
100

SHUNT

10
1

10

100

1000

10000

time (ms)

LSA 43.2 - 4 Pole


3 phase short-circuit curves at no load and rated speed (star connection Y)
10000

Current (A)

LSA 43.2 M45

Symmetrical
Asymmetrical
1000

AREP or PMG
100

SHUNT

10
1

10

100

1000

10000

time (ms)

10000

Current (A)

LSA 43.2 L65

Symmetrical
Asymmetrical
1000

AREP or PMG

100

SHUNT

10
1

10

100

1000

10000

time (ms)

10000

Current (A)

LSA 43.2 L8

Symmetrical
Asymmetrical
1000

AREP or PMG

100

SHUNT

10
1

10

100

1000

10000

time (ms)

Inuence due to connexion.


Curves shown are for star (Y) connection.
For other connections, use the following multiplication factors :
- Series delta : Current value x 1,732
- Parallel star : Current value x 2

Influence due to short-circuit.


Curves are based on a three-phase short-circuit.
For other types of short-circuit, use the following multiplication factors :
3 phase

2 phase L - L.

1 phase L - N.

Instantaneous (Max)

0,87

1,3

Sustained

1,5

2,2

Max sustained duration (AREP/ PMG)

10 sec.

5 sec.

2 sec.

LSA 43.2 - 4 Pole


Single bearing dimensions
BD

L
Access to
regulator

LB
372

42

Xg

AH

456

Access to terminals

14,5 H14

PMG optional

AIR OUTLET

40
120

3
T

120

Y DIA, Qty X Eq.


Sp. on U.

96

580

142

423
BL

Frame dimensions
TYPE
L max without PMG
LSA 43.2 S1
627

LB
565

Xg
270

Weight (kg)
210

LSA 43.2 S15

627

565

270

210

LSA 43.2 S25

627

565

278

230

LSA 43.2 S35

627

565

278

230

LSA 43.2 M45

662

600

295

260

LSA 43.2 L65

747

685

315

280

LSA 43.2 L8

747

685

340

320

Flange (mm)
S.A.E.
BD
4
474

356

AIR INLET
Access to rotating diodes

20

332,5

213

BH
6

11 DIA, Qty 10 as
shown on M

+0
225 -2

373

235

15

178

- 0,050

BX - 0,100

N - 0,127

30

Cable output

Coupling

BL
452

BH
146

P
413

N
361,95

M
381

T
5

Flex plate

111/2

10

Flange S.A.E 4

Flange S.A.E 3

Flange S.A.E 2

Flex plate (mm)


S.A.E.
BX
11 1/2
352,42

U
333,38

X
8

Y
11

AH
39,6

474

452

146

450

409,575

428,625

10

314,32

295,28

11

53,8

514

492

165

490

447,675

466,725

263,52

244,48

11

62

Torsional analysis data

35

70

75

70

67

18

Xr

Lr

Gravity center : Xr (mm), Rotor length Lr (mm), Weight : M (kg), Moment of inertia : J (kgm2) : (4J = MD2)
Flex plate S.A.E. 8
Flex plate S.A.E. 10
Flex plate S.A.E. 11 1/2
TYPE
Xr
Lr
M
J
Xr
Lr
M
J
Xr
Lr
M
J
338
590
74,5
0,3446
328
590
75
0,3524
312
590
75,5
0,3634
LSA 43.2 S1
LSA 43.2 S15

338

590

74,5

0,3446

328

590

75

0,3524

312

590

75,5

0,3634

LSA 43.2 S25

338

590

74,5

0,3446

328

590

75

0,3524

312

590

75,5

0,3634

LSA 43.2 S35

341

590

78,1

0,3653

331

590

78,6

0,3731

315

590

79,1

0,3841

LSA 43.2 M45

358

625

87,7

0,4141

348

625

88,2

0,4219

332

625

88,7

0,4329

LSA 43.2 L65

386

710

100,3

0,4711

376

710

100,8

0,4789

360

710

101,3

0,4899

LSA 43.2 L8

370

742

117,1

0,5438

368

742

117,5

0,5539

367

742

117,8

0,5720

10

LSA 43.2 - 4 Pole


Two bearing dimensions
474

Access to
regulator

LB
372
82

42

Xg

Access to terminals

40
AIR OUTLET
6

Frame dimensions
TYPE
LSA 43.2 S1

120

120

14,5 H14

M10 DIA, Qty 4x2


as shown on
428,625 (SAE3)

580

213

PMG optional

96

356
AIR INLET
Access to rotating diodes

423
452

20

357,5

146
6

59

+0
225 -2

15

10

16

240

373

235

+ 0,030

178

Cable output

55 + 0,011

450

M 20 x 42

409,575 - 0,127

456

L max without PMG


672

LB
590

Xg
295

Weight (kg)
220

LSA 43.2 S15

672

590

295

220

LSA 43.2 S25

672

590

295

220

LSA 43.2 S35

672

590

303

240

LSA 43.2 M45

707

625

320

270

LSA 43.2 L65

792

710

340

290

LSA 43.2 L8

792

710

365

330

Torsional analysis data

35

70

75

70

67

60

55

Xr

Lr

Gravity center : Xr (mm), Rotor length Lr (mm), Weight : M (kg), Moment of inertia : J (kgm2) : (4J = MD2)
TYPE
LSA 43.2 S1

Xr
301

Lr
661

M
74,2

J
0,3367

LSA 43.2 S15

301

661

74,2

0,3367

LSA 43.2 S25

301

661

74,2

0,3367

LSA 43.2 S35

305

661

77,8

0,3573

LSA 43.2 M45

321

696

87,5

0,4062

LSA 43.2 L65

349

781

100,1

0,4632

LSA 43.2 L8

362

781

110,9

0,525

11

LEROY-SOMER 16015 ANGOULME CEDEX - FRANCE


RCS ANGOULME N B 671 820 223
S.A. au capital de 62 779 000

www.leroy-somer.com