Annexure-V

MCCB Setting

ANNEXURE - V
SETTING CALCULATIONS FOR MCCB

Sl. No.

1.0
2.0
3.0
4.0
5.0
6.0
7.0
8.0
9.0
10.0
11.0
12.0
13.0
14.0
15.0
16.0
17.0
18.0
19.0
20.0
21.0
22.0
23.0
24.0

MCCB Model Available Trip


Used
Rating (In)
UPB100H
UPB100H
UPB100H
UPB100H
UPB100H
UPB100H
UPB100H
UPB100H
UPB100H
UPB100H
UPB100H
UPB100H
UPB100H
UPB250H
UPB250H
UPB250H
UPB250H
UPB250H
UPB250H
UPB250H
UPB400H
UPB400H
UPB400H
UPB400H

15
16
20
25
30
32
40
50
60
63
75
80
100
125
150
160
175
200
225
250
260
270
280
290

Available Setting Range


Rated
Instantaneous
Current(Ir) Current(Im)
(0.8-1.0)xIn
(5-10)xIn
(0.8-1.0)xIn
(5-10)xIn
(0.8-1.0)xIn
(5-10)xIn
(0.8-1.0)xIn
(5-10)xIn
(0.8-1.0)xIn
(5-10)xIn
(0.8-1.0)xIn
(5-10)xIn
(0.8-1.0)xIn
(5-10)xIn
(0.8-1.0)xIn
(5-10)xIn
(0.8-1.0)xIn
(5-10)xIn
(0.8-1.0)xIn
(5-10)xIn
(0.8-1.0)xIn
(5-10)xIn
(0.8-1.0)xIn
(5-10)xIn
(0.8-1.0)xIn
(5-10)xIn
(0.8-1.0)xIn
(5-10)xIn
(0.8-1.0)xIn
(5-10)xIn
(0.8-1.0)xIn
(5-10)xIn
(0.8-1.0)xIn
(5-10)xIn
(0.8-1.0)xIn
(5-10)xIn
(0.8-1.0)xIn
(5-10)xIn
(0.8-1.0)xIn
(5-10)xIn
(3-11)xIn
(0.8-1.0)xIn
(3-11)xIn
(0.8-1.0)xIn
(3-11)xIn
(0.8-1.0)xIn
(3-11)xIn
(0.8-1.0)xIn

Setting Value
Rated
Current(Ir)
0.9xIn
0.9xIn
0.9xIn
0.9xIn
0.9xIn
0.9xIn
0.9xIn
0.9xIn
0.9xIn
0.9xIn
0.9xIn
0.9xIn
0.9xIn
0.9xIn
0.9xIn
0.9xIn
0.9xIn
0.9xIn
0.9xIn
0.9xIn
0.9xIn
0.9xIn
0.9xIn
0.9xIn

Instantaneous
Current(Im)
8xIn
8xIn
8xIn
8xIn
8xIn
8xIn
8xIn
8xIn
8xIn
8xIn
8xIn
8xIn
8xIn
8xIn
8xIn
8xIn
8xIn
8xIn
8xIn
8xIn
8xIn
8xIn
8xIn
8xIn

This table is not proper


to set MCCB.
Refer to the attached
Excel file '5.AnnexureV_MCCB Setting'.

25.0
26.0
27.0
28.0
29.0
30.0
31.0
32.0
33.0
34.0
35.0
36.0
37.0
38.0
39.0
40.0
41.0
42.0
43.0

UPB400H
UPB400H
UPB400H
UPB400H
UPB400H
UPB400H
UPB400H
UPB400H
UPB400H
UPB400H
UPB630H
UPB630H
UPB630H
UPB630H
UPB630H
UPB630H
UPB630H
UPB630H
UPB630H

300
310
320
340
350
360
370
380
390
400
420
440
460
480
500
525
550
575
630

(0.8-1.0)xIn
(0.8-1.0)xIn
(0.8-1.0)xIn
(0.8-1.0)xIn
(0.8-1.0)xIn
(0.8-1.0)xIn
(0.8-1.0)xIn
(0.8-1.0)xIn
(0.8-1.0)xIn
(0.8-1.0)xIn
(0.8-1.0)xIn
(0.8-1.0)xIn
(0.8-1.0)xIn
(0.8-1.0)xIn
(0.8-1.0)xIn
(0.8-1.0)xIn
(0.8-1.0)xIn
(0.8-1.0)xIn
(0.8-1.0)xIn

(3-11)xIn
(3-11)xIn
(3-11)xIn
(3-11)xIn
(3-11)xIn
(3-11)xIn
(3-11)xIn
(3-11)xIn
(3-11)xIn
(3-11)xIn
(3-11)xIn
(3-11)xIn
(3-11)xIn
(3-11)xIn
(3-11)xIn
(3-11)xIn
(3-11)xIn
(3-11)xIn
(3-11)xIn

0.9xIn
0.9xIn
0.9xIn
0.9xIn
0.9xIn
0.9xIn
0.9xIn
0.9xIn
0.9xIn
0.9xIn
0.9xIn
0.9xIn
0.9xIn
0.9xIn
0.9xIn
0.9xIn
0.9xIn
0.9xIn
0.9xIn

8xIn
8xIn
8xIn
8xIn
8xIn
8xIn
8xIn
8xIn
8xIn
8xIn
8xIn
8xIn
8xIn
8xIn
8xIn
8xIn
8xIn
8xIn
8xIn

This table is not proper


to set MCCB.
Refer to the attached
Excel file '5.AnnexureV_MCCB Setting'.

Notes:
1. All the normal outgoing feeder of LV switchgear/MCC/DB and certain incomer rated below 630A will be protected through MCCB.
2. All these MCCB are thermal magnetic type.
3. As the population of these feeders are very large,typical setting has been given for each type of MCCB used in this project.
If in case system demand some specific setting of any outgoing feeder, the same shall be modified at site.
4. This settings are exclusively applicable for the feeders which are being feed from DW supplied LV switchgear/MCC.
For vendor supplied feeders, vendor recommended setting will be followed.
5. MCCB short circuit rating has been choosen in such a way that it will not tripped during starting of the motor due to flow of high starting current.
6. MCCB make - Hyundai.

ANNEXURE - V
SETTING CALCULATIONS FOR MCCB
Available Setting Range
Sl. No.

MCCB Model
Used

Type

FLC

MCCB
Trip Rating
(In)

Setting
Trip Rating
(Ir)

Rated Current
(Ir)

Shot Current
(Isd)

Shot Current Time


(tsd)

Long Time
(tr)
*Long Current = Ir x 600%

Instantaneous
Current
(Im)

Thermal
Magnetic
Thermal
Magnetic
Thermal
Magnetic

~16

20

20

(0.8-0.9-1.0) x In

10 x In

16 ~ 24

30

30

(0.8-0.9-1.0) x In

10 x In

24 ~ 32

40

40

(0.8-0.9-1.0) x In

10 x In

Electronic

32 ~ 40

100

50

(Non-2-3-4-5-6-7-8-9-10) x Ir

(0.05-0.1-0.2-0.3)

6.25

11 x In

Electronic

40 ~ 50

100

63

(Non-2-3-4-5-6-7-8-9-10) x Ir

(0.05-0.1-0.2-0.3)

6.25

11 x In

Electronic

50 ~ 64

100

80

(Non-2-3-4-5-6-7-8-9-10) x Ir

(0.05-0.1-0.2-0.3)

6.25

11 x In

Electronic

64 ~ 80

100

100

(Non-2-3-4-5-6-7-8-9-10) x Ir

(0.05-0.1-0.2-0.3)

6.25

11 x In

Electronic

80~100

250

125

(Non-2-3-4-5-6-7-8-9-10) x Ir

(0.05-0.1-0.2-0.3)

6.25

11 x In

Electronic

100~128

250

160

(Non-2-3-4-5-6-7-8-9-10) x Ir

(0.05-0.1-0.2-0.3)

6.25

11 x In

10

Electronic

128~160

250

200

(Non-2-3-4-5-6-7-8-9-10) x Ir

(0.05-0.1-0.2-0.3)

6.25

11 x In

11

Electronic

160~200

250

250

(Non-2-3-4-5-6-7-8-9-10) x Ir

(0.05-0.1-0.2-0.3)

6.25

11 x In

FLC

MCCB
Trip Rating
(In)

Setting
Trip Rating
(Ir)

1
2
3
4

UPB100H

9
UPB250H

Sl. No.

MCCB Model
Used

12

Type

40-45-50-55-63-70-8090-100
40-45-50-55-63-70-8090-100
40-45-50-55-63-70-8090-100
40-45-50-55-63-70-8090-100
100-110-125-140-160175-200-225-250
100-110-125-140-160175-200-225-250
100-110-125-140-160175-200-225-250
100-110-125-140-160175-200-225-250

Ir

Io

Electronic

200~240

400

300

0.95

0.8

Electronic

200~288

400

360

0.9

14

Electronic

288~320

400

400

15

Electronic

320~344

630

430

0.85

0.8

Electronic

344~400

630

500

0.8

Electronic

400~480

630

600

0.95

13

16
17

UPB400H

UPB630H

Available Setting Range

Trip Rating (Ir)


Setting
Rated Current
(Ir)
200-215-225-240-250-255-270-290- 300-320340-360-380-400
200-215-225-240-250-255-270-290-300-320340-360-380-400
200-215-225-240-250-255-270-290-300-320340-360-380-400
320-340-360-380-400-430-450-480-500-540570-600-630
320-340-360-380-400-430-450-480- 500-540570-600-630
320-340-360-380-400-430-450-480-500-540570-600-630

Long Time
(tr)
*Long Current = Ir x 600%

Shot Current
(Isd)

Shot Current Time


(tsd)

Instantaneous
Current
(Ii)

Ground Fault
Current
(Ig)

Ground Fault
Current Time
(tg)

(2-4-6-8-12)

(Non-2-4-6-8-10) x Ir

(0.1-0.2-0.3)

(Non-3-6-8-10-11) x In

(Non-0.2-0.3-0.4) x In

(0.1-0.2-0.4-0.8)

(2-4-6-8-12)

(Non-2-4-6-8-10) x Ir

(0.1-0.2-0.3)

(Non-3-6-8-10-11) x In

(Non-0.2-0.3-0.4) x In

(0.1-0.2-0.4-0.8)

(2-4-6-8-12)

(Non-2-4-6-8-10) x Ir

(0.1-0.2-0.3)

(Non-3-6-8-10-11) x In

(Non-0.2-0.3-0.4) x In

(0.1-0.2-0.4-0.8)

(2-4-6-8-12)

(Non-2-4-6-8-10) x Ir

(0.1-0.2-0.3)

(Non-3-6-8-10-11) x In

(Non-0.2-0.3-0.4) x In

(0.1-0.2-0.4-0.8)

(2-4-6-8-12)

(Non-2-4-6-8-10) x Ir

(0.1-0.2-0.3)

(Non-3-6-8-10-11) x In

(Non-0.2-0.3-0.4) x In

(0.1-0.2-0.4-0.8)

(2-4-6-8-12)

(Non-2-4-6-8-10) x Ir

(0.1-0.2-0.3)

(Non-3-6-8-10-11) x In

(Non-0.2-0.3-0.4) x In

(0.1-0.2-0.4-0.8)

Please note that the ground fault function should be enabled.


DW have reviewed the coordinate with upstream ground fault function and recommend the setting guide as per the
next page.

.5

1K

500

Amps X 10 10BFA (Nom. kV=0.4, Plot Ref. kV=0.445)


Relay
10BFA01
10
30
50
100
300
500
1K - G
3K
5K
OC1, AREVA P127
CT Ratio 1600:1
Inst = 0.32 ((0.002 - 1) xCT Sec)
Time Delay = 0.6s

10K
1K

500

MCCB
300
Ground Pickup = 0.3 (0.3 x 630 =189Amps)
Ground Time Delay = 0.2s

300

10BBA

10BFA01
HYUNDAI U SERIES
Sensor = 3200 Plug = 2240 Amps
Ground Pickup = 0.1 (320 Amps)
Ground Band = 0.4s

100

50

100

10BBA04

50

30

Relay 10BBA04

30

10BFA01

10

HYUNDAI U SERIES
Sensor = 3200 Plug = 2240 Amps
Ground Pickup = 0.2 (640 Amps)
Ground Band = 0.16

Cable8
5

1-3/C 120

Seconds

Seconds

10

Relay 10BFA01 - G
OC1
AREVA
P127
CT Ratio 1600:1
Inst = 0.05 (0.002 - 1 xCT Sec)
Time Delay = 0.02 s

.5

.5

.3

10BFT01
2 MVA

.3

.1

.1

10BFA01
10BFA
.05

.05

.03

.03

MCCB
(630H)

Relay 10BFA01 - G - LG
48.896kA @ 0.445kV
(Sym)

.01
.5

10

30

50

100

300

500

1K

Amps X 10 10BFA (Nom. kV=0.4, Plot Ref. kV=0.445)


DAEWOO E&C
Project: Safi Independent Power Project
Location:
Contract:

10BFA I/C

3K

5K

ETAP Star 12.5.0C

SAFI ENERGY COMPANY


Date:
SN:
Rev:
Fault:

05-26-2016
LAHM-DLF1
Base
Ground

.01
10K

AUX SWGR - 1
2 MVA

Relay 10BFA01