You are on page 1of 71

CopyrightofBCA.Allrightsreserved.Nounauthorised distributionoruseincommercialmannerisallowed.

WELCOMETOINDUSTRYBRIEFINGON:

GREENMARKVERSION4.0FOR
NEW BUILDINGS
NEWBUILDINGS
1)20Sep2010(2.30 4.30pm)
2)27Sep2010(2.30 4.30pm)
3)1Oct2010(9.30 11.30am)

CopyrightofBCA.Allrightsreserved.Nounauthorised distributionoruseincommercialmannerisallowed.

Briefing Outline
1.

OverviewofBCAGreenBuildingInitiativesandImplementation
TimelineofGreenMarkVersion4.0(15mins)
BySEDOMrsGraceCheokChan

2.

KeyChangestoGreenMarkVersion4.0ResidentialCriteria(25mins)
BySEDOMsLeeSuiFung

3.

KeyChangestoGreenMarkVersion4.0NonResidentialCriteria(25
mins)
BySDOMrLimChanBoon
B SDO M Li Ch B

4.

Daylighting&GlareSimulationMethodology/SustainableConstruction
/ Sustainable Products / Carbon Footprint
/SustainableProducts/CarbonFootprint(20mins)
(20 mins)
BySDOMsOng Hui Wen

5.

Q&ASession

CopyrightofBCA.Allrightsreserved.Nounauthorised distributionoruseincommercialmannerisallowed.

OverviewofBCAGreenBuildingInitiatives
and Implementation Timeline
andImplementationTimeline
PresentedbyGraceCheokChan
GreenMarkDept(ND)
TechnologyDevelopmentDivision/BCA
/

CopyrightofBCA.Allrightsreserved.Nounauthorised distributionoruseincommercialmannerisallowed.

PresentationOutline
BCAGreenMarkScheme Updates
BCAGreenMarkGFAIncentiveScheme
BCA Green Mark GFA Incentive Scheme
PublicSectorTakingtheLeadInitiatives
LegislativeRequirementonEnvironmentalSustainability
of Buildings
ofBuildings
MinimumGreenMarkScoreof50points
GLSprogrammeandRequirements
d

. creating a more sustainable built environment

CopyrightofBCA.Allrightsreserved.Nounauthorised distributionoruseincommercialmannerisallowed.

BCA Green Mark


BCAGreenMark

L
LaunchedinJan2005
h d i J 2005

OurSingapore Brand  Agreenbuildingratingsystemto


evaluatebuildingforitsenvironmentalimpactandperformance
5

CopyrightofBCA.Allrightsreserved.Nounauthorised distributionoruseincommercialmannerisallowed.

BCA G
Green M
Mark
k
NationalYardstick
QualifyingStandardfor
Q lif i S d d f
Incentives
ComplianceMethodfor
RegulatoryRequirement

TheMainLevertodriveEnvironmentalSustainabilityinBuildingSector
h
d
l
bl
ld
6

CopyrightofBCA.Allrightsreserved.Nounauthorised distributionoruseincommercialmannerisallowed.

Wh
Whatwehaveachievedsofar.
h
hi d f

Currentlymorethan
500 projects
500projects

**Thetotalestimatedexistingbuildingfloorspaceis208millionm2
7

CopyrightofBCA.Allrightsreserved.Nounauthorised distributionoruseincommercialmannerisallowed.

GreenMarkforNewBuildings
Evolutionofthecriteriatowardsamoreholisticapproach

VersioningofGMfor
NewBuildings

GMVersion4.0
(Effectivefrom1Dec2010)

Areaofimprovements
2010
2008
Version3.0
2007
V i 20
Version2.0
2005
Version
10
1.0

Version
4.0

Greater
GreateremphasisonPassiveDesign
emphasis on Passive Design
NaturalVentilation
Daylighting
Furtherenhancingbuildingenergy
efficiencystandard
PromoteSustainableConstruction
GreaterEmphasisonGreenery
EnhancedprerequisitesforhigherGM
rating
8

CopyrightofBCA.Allrightsreserved.Nounauthorised distributionoruseincommercialmannerisallowed.

ConsultationwithIndustryontheRevision

March2010
8consultationsessions
involving120developers,
involving 120 developers,
consultantsand
Professionals

Aug2009

Circulateddraft
Ci l t d d ft
versionfor
industry
comments

GreenMarkAdvisory
CommitteeandTechnical
Taskforcescomprising
IndustryProfessionalsand
Academics

April2010

Totalof170CommentsfromIndustry
Total of 170 Comments from Industry
9

CopyrightofBCA.Allrightsreserved.Nounauthorised distributionoruseincommercialmannerisallowed.

ImplementationTimelinefor
BCA Green Mark Version 4 0
BCAGreenMarkVersion4.0

August2010
Green Mark Advisoryy
Committee and
Technical Taskforces
comprising Industry
Professionals and
Academics

April2010

Finalise and publish


BCA Green Mark
Version 4.0
(i short
(in
h t GM V4)

GM V4 with
effect from
1 Dec 2010
No longer
accept GM V3
applications

1Dec2011
Auto
migration
from GM V3
to GM V4

1Dec2010

10

CopyrightofBCA.Allrightsreserved.Nounauthorised distributionoruseincommercialmannerisallowed.

From1Dec2010
GMV3.0willnolonger
applicable

Implementation timeline for the adoption of GM V4 0 is


ImplementationtimelinefortheadoptionofGMV4.0is

basedonthedateofGMapplication

1Dec2010

1Dec2011

GM applications submitted on or after 1 Dec 2010 will be


assessed under GM V4.0

GM applications submitted
before 1 Dec 2010 will be
assessed under GM V3.0

Projects where GM applications


were submitted before 1 Dec 2010
will be assessed under GM V4
V4.0
0
from 1 Dec 2011 onwards

11

CopyrightofBCA.Allrightsreserved.Nounauthorised distributionoruseincommercialmannerisallowed.

BCAGreenMarkCertification
The
e deta
details
so
of BCA
C G
Green
ee
Mark V4.0 is incorporated in
the BCA Green Mark
Certification Standard for
CommunityNew Buildings
Buildingg

AcopyoftheStandardcanbeobtainedfromBCAwebsiteat
http://www.bca.gov.sg/EnvSusLegislation/others/GM_Certification_Std2010.pdf
12

CopyrightofBCA.Allrightsreserved.Nounauthorised distributionoruseincommercialmannerisallowed.

GreenMarkGFAIncentiveScheme

New
Buildings

ImplementedinApril2009

GreenMarkGrossFloorArea(GM
GFA)IncentiveScheme
for private sector to achieve higher Green Mark ratings

URBAN
REDEVELOPMENT
AUTHORITY

Formoreinformation
http://www.bca.gov.sg/greenMark/gmgfa.html

13

CopyrightofBCA.Allrightsreserved.Nounauthorised distributionoruseincommercialmannerisallowed.

GreenMarkGFAIncentiveScheme

New
Buildings

Green
Mark
Mark
Platinum
Green
Mark
GoldPlus

Up to 2% additional GFA
beyondMPGPR
y

Subject to cap of 5,000 sqm

Up to 1% additional GFA
beyondMPGPR

Subject to cap of 2500 sqm

14

CopyrightofBCA.Allrightsreserved.Nounauthorised distributionoruseincommercialmannerisallowed.

Eligibility GMGFAIncentive
Newprivatedevelopments,redevelopmentsandmajor

A&Adevelopments.
d l
Residential

Nonlanded,Mixed
,
residential&
commercialdevelopment

NonResidential

Commercial,office,retail,businessparks,
industrial,institutional,community
building,hotel,hospital,whitesite
development

15

CopyrightofBCA.Allrightsreserved.Nounauthorised distributionoruseincommercialmannerisallowed.

BCAGMGFAApplicationand
E l ti P
EvaluationProcess

Stage 1
Stage1

Stage 2
Stage2

Stage 3
Stage3

SubmitBCAGMGFA
Applicationand
greenbuilding
conceptplanfor
endorsement

SubmitBCA
endorsementfor
AdditionalGFAand
relevantformwith
planningsubmission
to URA for approval
toURAforapproval
Raisesecurity
depositafter
pp
g
approvalgranted

ApplyforBCAGreen
MarkAssessment
andtoobtainthe
intendedGreen
MarkRatingbefore
TOP
whichBCAGreen
MarkCriteriawillbe
k
ll b
applicable GMV3.0
orGM4.0?

16

CopyrightofBCA.Allrightsreserved.Nounauthorised distributionoruseincommercialmannerisallowed.

ImplementationtimelinefortheadoptionofGMV4.0isbasedonthe

submissiondateofBCAGMGFAapplication

Before
BCAGreenMark
Assessmentand
Certificationbased
GM V3 0
onGMV3.0

Onorafter

1Dec
2010

BCAGreenMark
Assessmentand
Certificationbased
on
GM V4 0
onGMV4.0

17

CopyrightofBCA.Allrightsreserved.Nounauthorised distributionoruseincommercialmannerisallowed.

PublicSectorTakingtheLead
New
Buildings

KeyInitiatives:

ImplementedinApril2009

NEWPublicSectorBuildingswithmorethan5000m2 air
conditionedfloorareastoachieveGreenMark
Platinumrating
l i
i
BeyondcurrentmandatoryrequirementofGMCertifiedrating

18

CopyrightofBCA.Allrightsreserved.Nounauthorised distributionoruseincommercialmannerisallowed.

PublicSectorTakingtheLead
New
Buildings

Whenitisapplicable.
1

Design and Build Project


Applicable
pp
if contract called on and after 1 Apr
p 2009

Other Building Work Project


Applicable if consultancy services called on
and after 1 Apr 2009

19

CopyrightofBCA.Allrightsreserved.Nounauthorised distributionoruseincommercialmannerisallowed.


ImplementationtimelinefortheadoptionofGMV4.0isbasedonthe

y
g
dateoftendernoticesforconsultancyordesignand
buildcontract
Projects with tenders for design
that are called before 1 Dec 2010
will be assessed and certified
using the BCA Green Mark
Criteria for new Buildings
(GM V3.0)

1Dec
1 Dec
2010

Projects with tenders for design that are called


on or after 1 Dec 2010 will be assessed and
certified using the BCA Green Mark Criteria for
new Buildings (GM V4.0)

20

CopyrightofBCA.Allrightsreserved.Nounauthorised distributionoruseincommercialmannerisallowed.

Legislation on Environmental Sustainability


LegislationonEnvironmentalSustainability

SelfDeclarationbyQPs
andAppropriate
dA
i t
Practitioners

BC(EnvironmentalSustainability)
(
y)
Regulations2008cameintooperation
on15Apr08

ApplicabletoNewBuildingsand
ExistingBuildingsundergoingMajor
RetrofittingwithGFAof2000square
metresormore

ScoringMethodologyforcompliance
basedonGreenMarkV3.0whichwas
i
incorporatedincurrentCodefor
t di
tC d f
EnvironmentalSustainabilityof
Buildings
21

CopyrightofBCA.Allrightsreserved.Nounauthorised distributionoruseincommercialmannerisallowed.

L il i
LegislationonEnvironmentalSustainability
E i
lS
i bili
The BCA
C G
Green Mark V4.0 is
incorporated in the Code for
Environmental Sustainability
of Buildings (2nd Edition)
No change to the minimum
GM score

Min 50 points

A copy of the Code can be obtained from BCA website at


AcopyoftheCodecanbeobtainedfromBCAwebsiteat
http://www.bca.gov.sg/EnvSusLegislation/others/Env_Sus_Code2010.pdf
22

CopyrightofBCA.Allrightsreserved.Nounauthorised distributionoruseincommercialmannerisallowed.

ImplementationtimelinefortheadoptionofGMV4.0isbasedonthe

1st submissiondatetoURAforplanningpermission
submission date to URA for planning permission

Onorafter

15April
2008

Scoring
Methodology
 CurrentCode
onEnvironmental
Sustainabilityof
y

Scoring
Methodology
 RevisedCode
d d
onEnvironmental
Sustainabilityof

Onorafter

1Dec
2010

Buildingswhich
comprisesBCAGM
Version3.0
Version 3.0

Buildings,2nd Edition
whichcomprises
BCAGM
Version4.0

23

CopyrightofBCA.Allrightsreserved.Nounauthorised distributionoruseincommercialmannerisallowed.

GLSProgrammes
KeyInitiatives:

New
Buildings

ImplementedinApril2009

GOVTLandSalesSitestorequirehigherTierGreenMark
ratings(PlatinumandGoldPlus)
For strategic development projects in new growth areas
Forstrategicdevelopmentprojectsinnewgrowthareas

GMGoldPlus
GMGoldPlus
G G ld l
GMGoldPlus

GMPlatinum/GoldPlus

24

CopyrightofBCA.Allrightsreserved.Nounauthorised distributionoruseincommercialmannerisallowed.

GLSProgrammes
KeyInitiatives:
Projects

In GLS

Regulationinplaceon5May2010

GOVTLandSalesSitestorequirehigherTierGreenMark
ratings(PlatinumandGoldPlus)
For strategic development projects in new growth areas
Forstrategicdevelopmentprojectsinnewgrowthareas

Anynewdevelopmentlocatedonlandsoldonorafter5
May2010undertheGLSprogrammearesubjecttobuilding
d h
b
b ld
regulatorycontrol.
Theseprojectsmustattaintheprescribedratingsunderthe
BCAGreenMarkCertificationProcessbeforeTOP/CSCcan
b
begranted.
t d

25

CopyrightofBCA.Allrightsreserved.Nounauthorised distributionoruseincommercialmannerisallowed.

GLSProgrammes
KeyInitiatives:
Projects

In GLS

Regulationinplaceon5May2010

GOVTLandSalesSitestorequirehigherTierGreenMark
GOVT
L d S l Sit t
i hi h Ti
G
M k
ratings(PlatinumandGoldPlus)
Forstrategicdevelopmentprojectsinnewgrowthareas

DeclarationsoftheGreenMarkscorefromtheQPsarenot
q
p j
requiredfortheseprojects.
InsteadQPsaretoensurethat
beforebuildingplansubmission,anapplicationis
madetoBCAfortheGreenMarkassessment
uponprojectcompletion,theappropriateGreenMark
certificationhasbeenobtainedfromBCAsothat
TOP/CSCcanbegranted
26

CopyrightofBCA.Allrightsreserved.Nounauthorised distributionoruseincommercialmannerisallowed.

ImplementationtimelinefortheadoptionofGMV4.0isbasedonthe

GLStenderclosingdateforthelandsold

Tocomplywith

Tocomplywith
GreenMarkGoldPlus
Landsold

orPlatinumRating

O
Onorafter
ft

5May
2010

GLSTender
ClosingDate

GreenMarkGoldPlus
orPlatinumRating

Onorafter

BCAGreenMark
Assessmentand
Certification based
Certificationbased
onGMV3.0

1Dec
2010

BCAGreenMark
Assessmentand
Certification based
Certificationbased
onGMV4.0

whichBCAGreen
Mark Criteria will be
MarkCriteriawillbe
applicable GMV3.0
orGM4.0?

27

CopyrightofBCA.Allrightsreserved.Nounauthorised distributionoruseincommercialmannerisallowed.

GreenMarkTool ScoreCalculator

Refertohttp://210.23.8.189/GreenMarkscorecalculator/
28

CopyrightofBCA.Allrightsreserved.Nounauthorised distributionoruseincommercialmannerisallowed.

I S
InSummary
Submission
Date of GM
Application

Based on 1st
Submission Date to
g
URA for Planning
Permission

1Dec
2010

LegislativeRequirement

BCAGreenMark

Submission Date of
BCA GM GFA
Application
BCAGreenMarkGFA
IncentiveScheme

Date of Tender
Notice for
Consultancy or
g & Build
Design
Contract
PublicSectorTakingthe
L d
Lead

MinimumEnvironmental
SustainabilityStandard
GreenMarkScoreof
50 points
50points

Date of GLS Tender


Closing Date
LegislativeRequirement
Legislative
Requirement
GLSProgrammefor
StrategicAreas

29

CopyrightofBCA.Allrightsreserved.Nounauthorised distributionoruseincommercialmannerisallowed.

30

CopyrightofBCA.Allrightsreserved.Nounauthorised distributionoruseincommercialmannerisallowed.

IndustryBriefingon
BCA G
BCAGreenMarkforNewResidentialBuildingsVersionRB/4.0
M k f N R id ti l B ildi
V i RB/4 0

31

CopyrightofBCA.Allrightsreserved.Nounauthorised distributionoruseincommercialmannerisallowed.

Agenda
1. Summary of key changes
2. Green Mark for New Residential
Buildings Version RB/4.0
3. CaseStudyonachievingGreenMarkCertifiedandGreenMarkGoldPLUS
rating
Green
Mark

Try Again

Certified

Score

049

5074

Gold
7584

Goldplus

Platinum

8589

90>90

BCA GREEN MARK

32

CopyrightofBCA.Allrightsreserved.Nounauthorised distributionoruseincommercialmannerisallowed.

SummaryofkeychangesfromRB/3.0toRB/4.0
Su
a y o ey c a ges o
/3 0 to / 0
General
1
1.
Additional pre-requisite
pre requisite requirements for Green Mark GoldPLUS and
Platinum rating:
Naturally Ventilated staircases and common lobbies
4 ticks air-con
Min Sustainable Construction scores
2.

Removal of capping of maximum scores


gy Related Requirements
q
Energy

3.

Higher weightage for good natural ventilation and passive design

4.

Additional new criteria for daylighting and revision of weightage for


artificial
tifi i l lighting
li hti

5.

Revision of weightage for ventilation in carparks and lifts

6
6.

Enhancement of scoring for renewable energy


33

CopyrightofBCA.Allrightsreserved.Nounauthorised distributionoruseincommercialmannerisallowed.

S
SummaryofkeychangesfromRB/3.0toRB/4.0
fk
h
f
RB/3 0 t RB/4 0
OtherGreenRequirements
7.

Removalofpointallocationforuseofwaterefficientfittingswithgood
rating(1tick)

8
8.

Addi i
Additionalnewcriteriaonuseofwaterefficientplants
l
i i
f
ffi i
l

9.

EnhancementofscoringonsustainableconstructionandtosupportMulti
tiersgreenproductratingssystem

10.

Enhancementofscoringongreeneryprovision,environmental
managementpracticeandpublictransportaccessibility

11
11.

Additional new criteria on stormwater management


Additionalnewcriteriaonstormwatermanagement

12.

RevisionofweightageallocationforuseoflowVOCpaintsandnaturally
ventilatedwetareas

34

CriteriaforResidential
BuildingsRB/4.0

CopyrightofBCA.Allrightsreserved.Nounauthorised distributionoruseincommercialmannerisallowed.

ToachieveGreenMarkCertified
50points

PreRequisiteRequirement

Minimum
q
requirements

All relevant prerequisite


Allrelevantpre
requisiterequirementsforthespecificGreenMarkRatingaretobe
requirements for the specific Green Mark Rating are to be
compliedwith

EnergyRelatedRequirements
gy
q
Min30points
ElectiveRequirementforEnergyImprovement
((Combinationofthefollowingitemstomeet30
g
points)

Additional
requirements

OtherGreenRequirements
Other
Green Requirements
Min20points

(Max50points)

Elective Requirement from other areas


(Combination of the following items to meet
20 points)

Part 1  EnergyEfficiency
Part1
Energy Efficiency

(Max 50 points)

11ThermalPerformanceofBuildingEnvelope
RETV
y
g
y
12NaturallyVentilatedDesignandA/CSystem
13Daylighting
14ArtificialLighting
15VentilationinCarparks
Points
1 6 Lifts
16Lifts
allocated87
allocated 87
17EnergyEfficientFeatures
18Renewableenergy

Part 2 - Water Efficiency


Part
a 3 Environmental
o e a Protection
o ec o
Part 4 - Indoor Environmental Quality
Part 5 Other Green Features
Points
allocated68
35

AdditionalprerequisiterequirementsforGoldplusandPlatinumprojects
CopyrightofBCA.Allrightsreserved.Nounauthorised distributionoruseincommercialmannerisallowed.

PrerequisiteRequirements
1.

2
2.

Building envelope design with Envelope Thermal Transfer value


(RETV) of
Gold
G
ldPLUS

 22 W/
W/m2

Platinum

 20 W/m2

Natural ventilation requirements for Platinum rating

Use of ventilation simulation software to identify most


effective building design and layout at least 80% of typical
units should have an area weighted average wind velocity
of 0.6m/s

Common areas like staircases and lobbies should be


naturally
t
ll ventilated
til t d

3.

Air-conditioners for both GoldPLUS and Platinum projects should


be 4-ticks

4.

Minimum Sustainable Construction


GoldPLUS  3 points
Platinum

 5 points
36

CopyrightofBCA.Allrightsreserved.Nounauthorised distributionoruseincommercialmannerisallowed.

Category

Version 3

Version 4

1-1 Building Envelope Thermal


Performance

15

15

12 N
1-2
Natural
t lV
Ventilation
til ti and
d A/C D
Design
i
- Option 1 (max 22 points)
- Option 2 (max 18 points)

16

22

1-3 Day Lighting (RB 4)/ Lighting (RB 3)

1-4 Artificial Lignting (RB 4)/ Lighting (RB


3)

12

10

1-5 Ventilation in Carparks

1 6 Lifts
1-6

1-7 Energy Efficient Features

1-8
1
8 Renewable Energy

20

20

65 (Cap at 50
+ 20 bonus pt)

87 (max)

(I)

Energy
E
Related
R l t d Requirements
R
i
t

Part 1 : Energy Efficiency

Category Score for Part 1 Energy


Efficiency

37

CopyrightofBCA.Allrightsreserved.Nounauthorised distributionoruseincommercialmannerisallowed.

Category

Version 3

Version 4

2-1 Water Efficient Fittings

10

10

2 2 Water Usage
2-2

2-3 Irrigation System and Landscaping

3-1 Sustainable Construction

10

3-2 Sustainable Products

3-3 Greenery Provision

3-4 Environmental Management Practice

3-5 Green Transport

NA

(II) Other Green Requirements


P t2: W
Part
Water
t Efficiency
Effi i

Part 3 : Environmental Protection

3-6 Stormwater Management

38

CopyrightofBCA.Allrightsreserved.Nounauthorised distributionoruseincommercialmannerisallowed.

Category

Version 3

Version 4

4-1 Noise Level

4-2 Indoor Air Pollutants

4-3 Waste Disposal

4 4 IIndoor
4-4
d
Ai
Air Q
Quality
lit iin W
Wett Areas
A

57 (Cap at
50))

68

120

155 (max)

(II) Other Green Requirements


Part 4 : Indoor Environmental Quality

Part 5 : Other Green Features


5 1 Green Features & Innovations
5-1
Category Score for Part 2-5
Total Points Allocated

39

CopyrightofBCA.Allrightsreserved.Nounauthorised distributionoruseincommercialmannerisallowed.

Part 1 EnergyEfficiency
Part1
Energy Efficiency
RB1-2 Naturally Ventilated Design and A/C System
Option 1 Ventilation Simulation Modelling
Use of ventilation simulation software to identify the most effective
building design and layout to achieve good natural ventilation.
ventilation
(Max 20 points)
Notes:
Th top
The
t
5 typical
t i l layouts
l
t with
ith the
th mostt units
it should
h ld be
b included
i l d d in
i
the ventilation simulation. A minimum 80% of the selected typical
units should have an weighted average wind velocity of 0.6m/s

40

CopyrightofBCA.Allrightsreserved.Nounauthorised distributionoruseincommercialmannerisallowed.

Option 22 Ventilation Design and A/C Design


For development without use of ventilation simulation software in the
design of natural ventilation.
(M 16 points)
(Max
i t )
Option2(i)VentilationDesign
Option
2 (i) Ventilation Design
Buildinglayoutandunitsdesignfor
naturalventilation(Max8points)
Buildinglayoutdesignthatutilises
prevailingwindconditionstoachieve
adequatecrossventilation.
d
t
til ti

Dwellingunitdesignthatallowsfortrue
crossventilationinthelivingroomsand
bedroomsofthedwellingunits.
41

CopyrightofBCA.Allrightsreserved.Nounauthorised distributionoruseincommercialmannerisallowed.

Option2(ii)A/CDesign
i
(ii) /
i
UseoftheairconditionersthatarecertifiedundertheSingaporeEnergy
LabellingSchemebasedonthefollowingrating.
Rating
999
9999

Point Allocation
4
8

Atleast80%ofairconditionersusedinalldwellingunitsareenergy
labelled

Note:Fordevelopmentswhereairconditionersarenotprovided,points
f O ti 2 (ii)
forOption2(ii)onA/CDesignwillbeproratedaccordingtoOption2(i)
A/C D i
ill b
t d
di t O ti 2 (i)
onventilationdesign.

42

CopyrightofBCA.Allrightsreserved.Nounauthorised distributionoruseincommercialmannerisallowed.

1) Key Changes Version 3 Vs Version 4

Part11Energy
Part1
Energy Efficiency
EnergyEfficiency
Efficiency
Part
RB 1-3 Daylighting
Version 4 Additional Criteria
(a) Use of daylighting and glare simulation analysis to ensure ambient lighting
levels meet the level stated in CP38 and SS531
(Max 3 points)
(b) Day lighting for common areas

Lift lobbies (1 point)


Staircases (1 point)
Car parks (1 point)

At least 80% of the applicable areas

RB 1-4 Artificial Lighting


Version 3
0.3
0 3 point
i t ffor every % iimprovementt
over the baseline standard
(Max 12 points)

Version 4
0.25
0 25 point
i t ffor every % iimprovementt
over the baseline standard BCA GREEN MARK
43
( Max 10 points)

CopyrightofBCA.Allrightsreserved.Nounauthorised distributionoruseincommercialmannerisallowed.

1) Key Changes Version 3 Vs Version 4

Part1 EnergyEfficiency
RB 1-5 Ventilation in Carpark
Version 3
Naturally ventilated carparks (8
points)
Use CO Sensors to regulate the
demand for mechanical ventilation
Fume
F
extract
t t (6 points)
i t )
MV with or without supply
(4 points)

Version 4
Naturally ventilated carparks (6
points)
Use CO Sensors to regulate the
demand for mechanical ventilation
Fume
F
extract
t t (4 points)
i t )
MV with or without supply
(3 points)

RB 1-6 Lifts
Version 3
Energy efficient lifts with
AC variable voltage and variable
frequency motor drive (1 point)
Sleep mode features (1 point)

Version 4
Energy Efficient lifts with AC variable
voltage and variable frequency motor
drive and sleep mode featuresBCA GREEN MARK
44
(1 point)

CopyrightofBCA.Allrightsreserved.Nounauthorised distributionoruseincommercialmannerisallowed.

1) Key Changes Version 3 Vs Version 4

Part1 EnergyEfficiency
RB 1-8 Renewable Energy
Version 3
Use of renewable energy
1
1 point for every 3 KWp of solar
energy
(Max 20 points)

Version 4
Use of renewable energy
3
3 points for every 1% replacement of
electricity (excluding households
usage) by renewable energy
(Max 20 points)

BCA GREEN MARK

45

CopyrightofBCA.Allrightsreserved.Nounauthorised distributionoruseincommercialmannerisallowed.

1) Key Changes Version 3 Vs Version 4

Part2 WaterEfficiency
RB 2-1 Water Efficient Fittings
Version 3

Version 4

Use of water fittings that are certified


under the Water Efficiency Labelling
Scheme (WELS). Points scored
based on each categories of fitting
such as WCs
WCs, basin taps
taps, sink taps
taps,
showerheads, etc

Use of water fittings that are certified


under WELS
WELS. Points scored based on
the number and water efficiency
rating of the fitting type used.
Rating

Water
Efficiency

99

Very
Good
Excellent

0.5 point for Good;


1 point for Very Good;
2.0
2 0 points for Excellent;
At least 90% of the type of fittings
(M 10 points)
(Max
i t )

999

Weightage
for Point
Allocation
8
10

((Max 10 points)
p
)
BCA GREEN MARK

46

CopyrightofBCA.Allrightsreserved.Nounauthorised distributionoruseincommercialmannerisallowed.

1) Key Changes Version 3 Vs Version 4

Part2 WaterEfficiency
RB 2-3
2 3 Irrigation System and Landscaping
Version 4 Additional Criteria
((c)) Use of p
plants that require
q
minimal watering
g for 80% of the landscape
p
areas.
(1 point)

BCA GREEN MARK

47

CopyrightofBCA.Allrightsreserved.Nounauthorised distributionoruseincommercialmannerisallowed.

1) Key Changes Version 3 Vs Version 4

Part3 EnvironmentalProtection
RB 3-1 Sustainable Construction*
Version 4 Additional Criteria
(a) Use of Sustainable and Recycled Materials
(i) Green Cements to replace Ordinary Portland Cement by at least 10% by
mass for superstructure applications (1 point)
(ii) Use of Recycled Concrete Aggregates and Washed Copper Slag to
replace coarse and fine aggregates above or equal to the minimum
usage requirements (2 points each)
Minimum Usage Requirement (RCA/ WCS)

((Max 5 p
points))

700
600

Tonnage (tons)

Tonnage = 0.03 x GFA


500
400
300
200
100

BCA GREEN MARK

0
0

2000

4000

6000

8000

10000

12000

GFA (m2)

14000

16000

18000

20000

48

CopyrightofBCA.Allrightsreserved.Nounauthorised distributionoruseincommercialmannerisallowed.

1) Key Changes Version 3 Vs Version 4

Part3 EnvironmentalProtection
RB 3-1 Sustainable Construction*
Version 3

Version 4

(a) Concrete Usage Index (CUI)

(b) Concrete Usage Index (CUI)


ProjectCUI(m3/m2)

Points

Category

CUILimit(m3/m2)

RB (15Storey)

0.55

0.70

RB(>15Storey)

0.60

0.60

0.50

0.40

0.35

0.1 point for every % reduction in


the CUI limit
(Max 4 points)

BCA GREEN MARK

49

CopyrightofBCA.Allrightsreserved.Nounauthorised distributionoruseincommercialmannerisallowed.

1) Key Changes Version 3 Vs Version 4

Part 3 EnvironmentalProtection
Part3
Environmental Protection
RB 3-1 Sustainable Construction

RB 3-2 Sustainable Product

Version 3

Version 4

(a)Use of sustainable materials and Use of environmental friendly products


products in building construction: that are certified by approved local
certification body
(i) SGLS certified products
Applicable for non-structural building
(ii) Products with 30% recycled
components
content by weight or volume.
1 point for high impact item
0.5 point for low impact item
1 point for high impact item
Higher weightage for products classified
0.5 point for low impact item
to be more environmental friendly
(Max 6 points)
Good
VeryGood
Excellent
1
( Max 8 points)

1.5

2
50

CopyrightofBCA.Allrightsreserved.Nounauthorised distributionoruseincommercialmannerisallowed.

1) Key Changes Version 3 Vs Version 4

Part3 EnvironmentalProtection
RB 3-2 Greenery
y

RB 3-3 Greenery
y Provision

Version 3

Version 4

(a) Greenery Provision (GnP) is


calculated by considering the 3D
volume covered by plants using
the Green Area Index ((GAI))
GnP

Points

2 0 to < 3
2.0
3.0
0

3.0 to < 3.5

3 5 to < 4
3.5
4.0
0

 4.0

Green Plot Ratio (GnPR) is calculated


by considering the 3D volume covered
by plants using the Leaf Area index
((LAI))
Ref: http://floraweb.nparks.gov.sg
GnP

Points

1.0 to < 2.0

2.0 to < 3.0

3.0 to < 4.0

4.0 to < 5.0

5 0 to < 6
5.0
6.0
0

 6.0

BCA GREEN MARK

51

CopyrightofBCA.Allrightsreserved.Nounauthorised distributionoruseincommercialmannerisallowed.

1) Key Changes Version 3 Vs Version 4

Part3 EnvironmentalProtection
RB 3-4 Environment Management Practice
Version 4 Additional Criteria
(b) Main builder that has track records in the adoption of sustainable,
environmentally
i
t ll friendly
f i dl practices
ti
during
d i th
the construction
t ti such
h as G
Green
and Gracious Builder Award (1 point)
RB 3
3-4
4 Environment
E i
t Management
M
t Practice
P
ti
Version 3

Version 4

(d) Project team comprises of one


Certified GM Manager (GMM)
and/or GM Professional (GMP)

(e) Project team comprises of one


Certified GMM , Green Mark Facility
Manager (GMFM) and GMP

GMM (1 point)
GMP (2 points)
(Max 3 points)

GMM (0.5 point)


GMFM (0.5 point)
GMP (1 point)
BCA GREEN MARK

(Max 1 point)

52

CopyrightofBCA.Allrightsreserved.Nounauthorised distributionoruseincommercialmannerisallowed.

1) Key Changes Version 3 Vs Version 4

Part3 EnvironmentalProtection
RB 3-5 Green Transport
Version 3

Version 4

(d) Provide adequate bicycle


parking lots
(1 point)

(d) Provide sheltered bicycle parking lots


At least 5% of dwelling units (0.5 point)
At least 10% of dwelling units (1 point)

RB 3-5 Green Transport


Version 4 Additional Criteria
(b) Provide covered walkway to facilitate connectivity and use of public
transport. (1 point)
(c) Provide hybrid/electric vehicle recharge stations within the development.
(1 point)
BCA GREEN MARK

53

CopyrightofBCA.Allrightsreserved.Nounauthorised distributionoruseincommercialmannerisallowed.

1) Key Changes Version 3 Vs Version 4

Part3 EnvironmentalProtection
RB3-6 Stormwater Management
Version 4 Additional Criteria
Encourage the treatment of stormwater run-off before discharge to public
drains Points scored based on treatment of run-off:
drains.
run off:
more than 35% of the total site area or paved area (3 points)
10% to 35% of the total site area (2 points)
to10%
up
t 10% off th
the ttotal
t l site
it area (1 point)
i t)
Note :
The treatment of stormwater runoff shall be through provision of infiltration
features or design features as recommended in PUBs ABC Water design
p
p g
g
Guidelines, refer to http://www.pub.gov.sg/abcwaters/
abcwatersdesignguidelines/Pages/default.aspx
BCA GREEN MARK

54

CopyrightofBCA.Allrightsreserved.Nounauthorised distributionoruseincommercialmannerisallowed.

1) Key Changes Version 3 Vs Version 4

Part4 IndoorEnvironmentalQaulity
RB 4-2 Indoor Air Pollutants
Version 3

Version 4

(a) Use of low volatile organic


compounds (VOC) paints for at
least 90% of the internal wall
points))
areas ((2 p

(a) Use of low volatile organic


compounds (VOC) paints for at
least 90% of the internal wall
point))
areas ((1 p

RB 4-4 Indoor Air Quality in Wet Areas


Version 3

Version 4

Provide adequate natural ventilation


and daylighting in wet areas

Provide adequate natural ventilation


and daylighting in wet areas
50% to 90% of all applicable areas
(1 point)
More
M
th
than 90% off allll applicable
li bl
areas (2 points)
BCA GREEN MARK

At least 90% of all applicable areas


((1 p
point))

55

CopyrightofBCA.Allrightsreserved.Nounauthorised distributionoruseincommercialmannerisallowed.

Examples on achieving Green mark certified rating


Item Criteria

Points
available

Actual
points
score

Remarks

Part
1

Energy
Efficiency

1-1

RETV

15

1.5

xRETV 24.5W/m2

1-2

Naturally
ventilated design
and A/C system
y

22

14

x4 ticks A/C(8)
x40% North South Orientation & 40%
units with cross ventilation ((4))
xcross ventilation in common areas
such as lift lobbies and staircase (2)

1-3
1
3

Daylighting

Using daylighting at staircase and lift


lobbies (2)

1-4

Artificial lighting

10

xusing PLC at lobbies and T8 lighting


at car park (8)

1-5

Ventilation in
carparks

xcar park with CO (3)

1-6

Lifts

xVVVF lift with sleep mode


56

CopyrightofBCA.Allrightsreserved.Nounauthorised distributionoruseincommercialmannerisallowed.

Examples on achieving Green Mark certified rating


Item Criteria

1-7

1-8

Points
available

Actual
points
score

gy efficient
Energy
features

Renewable
energy

20

87 (max)

30.5

Sub-total for
Energy
Efficiency

Remarks

Use ductless fans for basement


carpark (0.5)
Calculating EEI(0.5)
Nil

57

CopyrightofBCA.Allrightsreserved.Nounauthorised distributionoruseincommercialmannerisallowed.

Examples on achieving Green Mark certified rating


Item

Criteria

Points
Actual
available points
score

Remarks

Part
2

Water Efficiency

21
2-1

Water efficient
W
ffi i
fitting

10

xWater
W
fittings
fi i
with
i h WELS good
d rating
i

2-2

Water usage

xProvision of private metering to major


water usage such as irrigation and
swimming pool

3
2-3

Irrigation
gat o system
syste
and landscaping

xUse
Use of
o plants
p a ts that
t at require
equ e little
tt e watering
ate g

Part
3

Environment
Protection

3-1

Sustainable
construction

10

xCUI of 0.7

58

CopyrightofBCA.Allrightsreserved.Nounauthorised distributionoruseincommercialmannerisallowed.

Examples on achieving Green Mark certified rating


Item

Criteria

Points
Actual
available points
score

Remarks

3-2

Sustainable
products

xUse of environmentally friendly


products that are certified by approved
local certification body for water
proofing for internal wet areas, internal
doors, drywalls partitions and wardrobe

33
3-3

G
Greenery
provision
i i

xGreen
G
Plot
Pl t Ratio
R ti off 2.1
2 1 (2)
xUse of compost recycled from
horticulture waste (1)

3-4

Environmental
management
practice

xTender specified monitoring of energy


& water use and construction waste (1)
xCONQUAS project (1)
xBuilding
B ildi user guide
id (1)
xProvision of recycling bin at 1st
basement lobby (1)

59

CopyrightofBCA.Allrightsreserved.Nounauthorised distributionoruseincommercialmannerisallowed.

Examples on achieving Green Mark certified rating


Item

Criteria

Points
available

Actual
points
score

Remarks

3-5

Green transport

3-6

Stormwater management

Part
4

Indoor Environmental
Quality

4-1

Noise level

xTender specified design


noise level

4-2

Indoor air pollutants

xUse of low VOC paint

4-3
4
3

Waste Disposal

xLocating
Locating refuse chute at
service balcony

4-4

Indoor air quality in wet


areas

xProvision of window
opening at 50% of the units
unit s
kitchen, bathroom and
60
toilets

xWithin 500m from bus stop


(1)
xProvision of bicycle parking
lots for 10% of units(1)

CopyrightofBCA.Allrightsreserved.Nounauthorised distributionoruseincommercialmannerisallowed.

Examples on achieving Green Mark certified rating


Item

Criteria

Points
available
il bl

Part
5

Other Green Features

5-1

Other green features


Sub-total
Sub
total for other green
requirements

Actual
points
i t
score

68 (max)

20

Total Scores

Remarks

50.5

61

CopyrightofBCA.Allrightsreserved.Nounauthorised distributionoruseincommercialmannerisallowed.

Examples on achieving Green Mark GoldPLUS rating


Item Criteria

Points
available

Actual
points
score

Remarks

Part
1

Energy
Efficiency

1-1

RETV

15

13.5

1-2

Naturally
ventilated design
and A/C system
y

22

14

x4 ticks A/C(8)
x40% North South Orientation & 40%
units with cross ventilation ((4))
xcross ventilation in common areas
such as lift lobbies and staircase (2)

1-3
1
3

Daylighting

Daylight simulation (3)


Using daylighting at staircase and lift

xRETV 20.5W/m2

lobbies (2)
1-4

Artificial lighting

10

10

xusing PLC at lobbies and T5 lighting


at car park (10)

1-5

Ventilation in
carparks
k

xcar park with CO (3)

1-6

Lifts

xVVVF lift with sleep mode

62

CopyrightofBCA.Allrightsreserved.Nounauthorised distributionoruseincommercialmannerisallowed.

Examples on achieving Green Mark GoldPLUS rating


Item Criteria

Points
available

Actual
points
score

5.5

Part
1

Energy
Efficiency

1-7

Energy efficient
features

R
Renewable
bl
energy

20

87 (max)

52

18
1-8

Sub-total for
Energy
Efficiency

Remarks

Use ductless fans for basement


carpark (0.5)
Calculating EEI(0.5)
Motion sensors at staircases landing
(1)
Use lift with gearless drive (1)
Units with gas water heaters (1)
Provide 10 sun pipes (1)
Use of heat recovery at clubhouse
(0.5)
Nil

63

CopyrightofBCA.Allrightsreserved.Nounauthorised distributionoruseincommercialmannerisallowed.

Examples on achieving Green Mark GoldPLUS rating


Item

Criteria

Points
Actual
available points
score

Remarks

Part
2

Water Efficiency

21
2-1

Water efficient
W
ffi i
fitting

10

xWater
W
fittings
fi i
with
i h very good
d rating
i ffor
WCs and basin taps (4)

2-2

Water usage

xProvision of private metering to major


water usage such as irrigation and
swimming pool

3
2-3

Irrigation
gat o system
syste
and landscaping

xUse
Use of
o plants
p a ts that
t at require
equ e little
tt e watering
ate g

Part
3

Environment
Protection

3-1

Sustainable
construction

10

xCUI of 0.5 (3)

64

CopyrightofBCA.Allrightsreserved.Nounauthorised distributionoruseincommercialmannerisallowed.

Examples on achieving Green Mark GoldPLUS rating


Item

Criteria

Points
Actual
available points
score

Remarks

3-2
3
2

Sustainable
products

xUse
Use of environmentally friendly
products that are certified by approved
local certification body for water
proofing
p
g for internal wet areas,, internal
doors, drywalls partitions, wardrobe ,
ceiling board, playground equipment &
flooring, drainage, road kerb, timber
decking and club house carpets

3-3

Greenery provision

xGreen Plot Ratio of 4 (4)


Use of compost recycled from
xUse
horticulture waste 1)

3-4

Environmental
management
practice

xTender specified monitoring of energy


& water use and construction waste (1)
xCONQUAS project (1)
xBuilding user guide (1)
xProvision of recycling bin at 1st
basement lobby (1)
x Project team with GMP (1)
65

CopyrightofBCA.Allrightsreserved.Nounauthorised distributionoruseincommercialmannerisallowed.

Examples on achieving Green Mark GoldPLUS rating


Item

Criteria

Points
available

Actual
points
score

Remarks

3-5

Green transport

3-6

Stormwater management

Part
4

Indoor Environmental
Quality

4-1

Noise level

xTender specified design


noise level

4-2

Indoor air pollutants

xUse of low VOC paint

4-3
4
3

Waste Disposal

xLocating
Locating refuse chute at
service balcony

4-4

Indoor air quality in wet


areas

xProvision of window
opening at 50% of the units
unit s
kitchen, bathroom and
66
toilets

xWithin 500m from bus stop


(1)
xProvision of bicycle parking
lots for 10% of units(1)

CopyrightofBCA.Allrightsreserved.Nounauthorised distributionoruseincommercialmannerisallowed.

Examples on achieving Green Mark GoldPLUS rating


Item

Criteria

Points
available

Part
5

Other Green Features

5-1

Other green features


Sub total for other green
Sub-total
requirements
Total score

Actual
points
score

68 (max)

33

155
(
(max)
)

85

Remarks

67

CopyrightofBCA.Allrightsreserved.Nounauthorised distributionoruseincommercialmannerisallowed.

THANKYOU

68

CopyrightofBCA.Allrightsreserved.Nounauthorised distributionoruseincommercialmannerisallowed.

BCAGREENMARK
IndustryBriefing
BCAGreenMarkforNewNon
BCA
Green Mark for New Non ResidentialBuildings
Residential Buildings
VersionNRB/4.0

69

CopyrightofBCA.Allrightsreserved.Nounauthorised distributionoruseincommercialmannerisallowed.

Agenda
1. SummaryofKeyChanges
2. GreenMarkforNewNon ResidentialBuildingVersionNRB/
4.0
3. CaseStudyonAchievingCertifiedandGoldplus Rating
Green
Mark

Try Again

S
Score

49

Certified
50

74 75

Gold

Goldplus
84 85

Platinum

89 90

>90
90
BCA GREEN MARK

70

CopyrightofBCA.Allrightsreserved.Nounauthorised distributionoruseincommercialmannerisallowed.

1)SummaryofChanges

Summary of Key Changes Part 1 Energy Related Requirements:


1)RemovalofMax.50pointsCaps
)
p
p forbothEnergyRelatedRequirementsand
gy
q
OtherGreenRequirements
2)PrerequisiteRequirement
) e equ s te equ e e t  Min.prescribedairconditioningsystem
p esc bed a co d o g sys e
efficiency
3)Prerequisiterequirement
)
q
q
Permanentinstrumentation for monitoringofthe
g
watercooledchilledwaterplantefficiency
4) Additional Criteria Heatbalancesubstantiatingtest
Heat balance substantiating test forwater
for watercooled
4)AdditionalCriteria
cooled
chilledwaterplant
5) Additional Criteria NRB1
5)AdditionalCriteria
NRB 15
5Daylighting
Daylighting

BCA GREEN MARK

71

CopyrightofBCA.Allrightsreserved.Nounauthorised distributionoruseincommercialmannerisallowed.

1)SummaryofChanges

SummaryofKeyChanges OtherGreenRequirements:
1)Prerequisiterequirement Min.pointstobescoredforNRB31Sustainable
Constructionforhigherawards
2)EnhancescoringonsustainableconstructionmaterialstosupportMultitiers
Greenproductratingssystem
3)GreenPlotRatio(GnPR)computedusingprescribedLeafAreaIndex(LAI)
4)AdditionalCriteria NRB44IAQManagement
5)AdditionalCriteria
) dd
l
NRB37StormwaterManagement

BCA GREEN MARK

72

CopyrightofBCA.Allrightsreserved.Nounauthorised distributionoruseincommercialmannerisallowed.

1)SummaryofChanges

ToachieveGreenMarkAward

PrerequisiteRequirement
AllrelevantprerequisiterequirementsforthespecificGreenMarkRatingareto
b
becompliedwith
li d ith
EnergyRelatedRequirements
Min 30 points
Min30points
ElectiveRequirementforEnergyImprovement
(Combinationofthefollowingitemstomeet30
points)
(Max50points*seenote1)
Part1 EnergyEfficiency
11BuildingEnvelope ETTV
12AirConditioningSystem
13BuildingEnvelope Design/Thermal
Parameters
14NaturalVentilation/MechanicalVentilation
15Daylighting
16ArtificialLighting
17VentilationatCommonAreasandCarparks
18VentilationforCommonareas
19LiftsandEscalators
110EnergyEfficientFeatures
111Renewable/Cleanenergy

OtherGreenRequirements
Min 20 points
Min20points
ElectiveRequirementfromotherareas
(Combinationofthefollowingitemstomeet
20 points)
20points)
(Max50points)
Part 2  WaterEfficiency
Part2
Water Efficiency
Part3 EnvironmentalProtection
Part 4  IndoorEnvironmentalQuality
Part4
Indoor Environmental Quality
Part5 OtherGreenFeatures

BCA GREEN MARK

73

CopyrightofBCA.Allrightsreserved.Nounauthorised distributionoruseincommercialmannerisallowed.

Points Allocation BCA Green Mark for New NRB

Category
(I)
Energy Related Requirements
Part 1 : Energy Efficiency
1-1 Building Envelope Thermal Performance ETTV
1-2 Air-Conditioning System
S b T t l - NRB 1
Sub-Total
1-1
1 tto 1
1-2
2
1-3 Thermal Performance of Building Envelope (non a
/c)
1-4 Natural Ventilation and/or Mechanical Ventilation
(exclude carparks)
Sub-Total - NRB 1-3 to 1-4

Version 3 Version 4
Points
Points

15
27
42
29

12
30
42
35

13

20

42

55

BCA GREEN MARK

74

CopyrightofBCA.Allrightsreserved.Nounauthorised distributionoruseincommercialmannerisallowed.

1)SummaryofChanges

Points Allocation BCA Green Mark for New NRB


Category
(I)
Energy Related Requirements
Part 1 : Energy Efficiency
y g
g
15Daylighting
1-6 Artifical Lighting
1-7 Ventilation in Carparks
1-8
1
8 Ventilation in Common Areas
1-9 Lift and Escalators
1-10 Energy Efficient Practices & Features
1-11 Renewable Energy
Sub-Total - NRB 1-5 to 1-11
Total Category Score for Part 1:

Version 3 Version 4
Points
Points

12
5
5
3
12
20
57
99

6
12
4
5
2
12
20
61
116 (Max)

BCA GREEN MARK

75

CopyrightofBCA.Allrightsreserved.Nounauthorised distributionoruseincommercialmannerisallowed.

Points Allocation BCA Green Mark for New NRB


Category
(II)
Other Green Requirements
Part 2 : Water Efficiency
2-1 Water Efficient Fittings
2-2 Water Usage and Leak Detection
2 3 Irrigation
2-3
I i ti S
System
t
and
d Landscaping
L d
i
2-4 Water Consumption of Cooling Towers
Category Score for Part 2 Water Efficiency
Part 3 : Environmental Protection
3-1 Sustainable Construction
3-2 Sustainable Materials
3-3 Greenery
3
4 Environmental Management Practice
3-4
3-5 Green Transport
3-6 Refrigerants
3 7 St
37StormwaterManagement
t M
t
Category Score for Part 3 Environmental
Protection

Version3
Version
3
Points

Version4
Version
4
Points

8
2
2
2
14

10
2
3
2
17

14
6
8
2
2
32

10
8
8
7
4
2
3
42
BCA GREEN MARK
76

CopyrightofBCA.Allrightsreserved.Nounauthorised distributionoruseincommercialmannerisallowed.

Points Allocation BCA Green Mark for New NRB


Category
Part 4 : Indoor Environmental Quality
4-1 Thermal Comfort
4-2 Noise Level
4-3 Indoor Air Pollutants
4-4 Indoor Air Quality Management (IAQ)
4-5 High Frequency Ballasts
Category Score for Part 4 Indoor Environmental
Quality

Version 3 Version 4
Points
Points

Part 5 : Other Green Features


5-1 Green Features & Innovations
Category Score for Part 5 Other Green Features
Total Green Mark Score:

2
2
2
2
8

1
1
2
2
2
8

7
7
160

7
7
190 (Max)

BCA GREEN MARK

77

CopyrightofBCA.Allrightsreserved.Nounauthorised distributionoruseincommercialmannerisallowed.

2)GMNRBVersion4.0

Version3andVersion4 PrerequisiteRequirements
BCAGreenMarkGold
BCA Green Mark Goldplus andPlatinumRating
and Platinum Rating
AirConditionedBuildings
Projectsshouldachieve:
plus rating
Atleast25%energysavingstoqualifyforGMGold
gy
g
q
y
g

Atleast30%energysavingstoqualifyforGMPlatinumrating
Projectsshouldachieve:
ETTVof42W/m
ETTV of 42 W/m2 toqualifyforGMGold
to qualify for GM Goldplus rating
ETTVof40W/m2 toqualifyforGMPlatinumrating
NonAirConditionedBuildings
Simulationorwindtunneltestingtoensuregoodnaturalventilation

BCA GREEN MARK

78

CopyrightofBCA.Allrightsreserved.Nounauthorised distributionoruseincommercialmannerisallowed.

2)GMNRBVersion4.0

Version 4 AdditionalPre
Version4
Additional Prerequisite
requisiteRequirements
Requirements
AirConditionedBuildings
1)Prescribedminefficiencyofairconditioningsystem
(i)For Buildings using
(i)ForBuildingsusing

Green Mark
Rating
Certified
Gold
GoldPlus
Platinum

Watercooled Central ChilledWater Plant:


WatercooledCentralChilledWaterPlant:

Peak Building
g Cooling
g Load (ton)
(
)
< 500
 500
Efficiency (kW/ton)
0.80
0.80
0 80
0.70
0 70
0.70

0.70
0.70
0 70
0.65
0 65
0.65
BCA GREEN MARK

79

CopyrightofBCA.Allrightsreserved.Nounauthorised distributionoruseincommercialmannerisallowed.

2)GMNRBVersion4.0

2)Prescribedminefficiencyofairconditioningsystem
(ii)ForBuildingsusingChilledWaterPlantorUnitaryAir
Aircooled
Conditioners:

Green Mark
Rating
Certified
Gold
Goldplus
Platinum

Peak
P
kB
Building
ildi
Cooling
C li
L
Load
d (ton)
(t )
< 500
 500
Effi i
Efficiency
(kW/t )
(kW/ton)
0.90
0 90
0.90
0.85
0 78
0.78

0.80
Notapplicable

3)PermanentInstrumentationforMonitoringofCentralChilledWaterPlant
Efficiency
4)MinimumpointstobescoredunderNRB31SustainableConstruction
GreenMarkGold
Green Mark GoldPlus 3points
 3 points
BCA GREEN MARK

GreenMarkPlatinum5points

80

CopyrightofBCA.Allrightsreserved.Nounauthorised distributionoruseincommercialmannerisallowed.

2)GMNRBVersion4.0

NonAirConditionedBuildings
1) PlatinumRating
Useofventilationsimulationandanalysistoidentifythemosteffective
bu d g des g a d ayou
buildingdesignandlayout
Implementthesimulationresultandrecommendations
2) Minimum points to be scored under NRB 3-1 Sustainable Construction
Green Mark GoldPlus  3 points
Green Mark Platinum  5 points

BCA GREEN MARK

81

CopyrightofBCA.Allrightsreserved.Nounauthorised distributionoruseincommercialmannerisallowed.

2)GMNRBVersion4.0

Part1 EnergyEfficiency
NRB 1
1-1
1B
Building
ildi
Envelope
E
l
ETTV*
Version 3

Version 4

Maximum Permissible = 50 W/m2 Maximum Permissible = 50 W/m2


42.5 W/m2 for max. 15 points

40W/m2 for max. 12points

BCA GREEN MARK

82

CopyrightofBCA.Allrightsreserved.Nounauthorised distributionoruseincommercialmannerisallowed.

2)GMNRBVersion4.0

Part 1 EnergyEfficiency
Part1
Energy Efficiency
NRB1 2AirconditioningSystem AirConditionedPlant(WaterSide)*
V i 3
Version3

V i 4
Version4

(a) AirconditionedPlant

(a) WaterCooled ChilledWater


Plant
a t
OR

OR
(b) Unitary
UnitaryAirConditionerse.g.
AirConditioners e g
VRFsystem

Baselineefficiencyaspercode
requirements

(b) AirCooled ChilledWaterPlant/


ChilledWater Plant/
UnitaryAirConditioners

Prescribed Min.airconsystem
efficiency

Airconsystemefficiencyassessed
basingonfullinstalledcapacity
BCA GREEN MARK

83

CopyrightofBCA.Allrightsreserved.Nounauthorised distributionoruseincommercialmannerisallowed.

2)GMNRBVersion4.0

Part 1 EnergyEfficiencyNRB12AirConditioningSystem
Part1
Energy Efficiency NRB 1 2 Air Conditioning System
The efficiency of the Air-con system can be computed basing on:
1) Full installed capacity (exclude standby) OR
pected ope at g e c e cy
2) Expectedoperatingefficiency

of the system at part


part-load
load condition

*mostfrequentoccurringpartloadconditionduringthenormalbuilding
operating hours as defined:
operatinghoursasdefined:

am

BCA GREEN MARK

84

CopyrightofBCA.Allrightsreserved.Nounauthorised distributionoruseincommercialmannerisallowed.

2)GMNRBVersion4.0

Part 1 EnergyEfficiencyNRB1
Part1
Energy Efficiency NRB 12
2Air
AirConditioning
ConditioningSystem
System
Expectedoperatingefficiencyofthesystematpartloadcondition
Determinethemostfrequentoccurringpartloadcondition
h
f
l d
d

BCA GREEN MARK

85

CopyrightofBCA.Allrightsreserved.Nounauthorised distributionoruseincommercialmannerisallowed.

2)GMNRBVersion4.0

Part1 EnergyEfficiency
ff
NRB 1- 2 Air-conditioning
g System
y
Air-Conditioned Plant*
Version 4 Additional Criteria
(d) Instrumentation for Monitoring of Central Water-Cooled Chilled-Water
Plant Efficiency, in terms of kW/RT, in accordance to ASHRAE Guide 22 and
AHRI 550/590
1 Pre-requisite point
The installed instrumentation shall have the capability of calculating a
resultant plant efficiency, kW/RT, within 5% of the true value.

BCA GREEN MARK

86

CopyrightofBCA.Allrightsreserved.Nounauthorised distributionoruseincommercialmannerisallowed.

2)GMNRBVersion4.0

NRB 1- 2 Air-conditioning System Air-Conditioned Plant*


V i 4 Additional
Version
Additi
l Criteria
C it i

The instrumentation and installation are required to comply with:


1) Locationandinstallationofthemeasuringdevicestomeetthemanufacturer's
recommendation.
2) Dataacquisitionsystemshallhaveaminimumresolutionof16bit.
3)DataLoggingSoftwareinterval:AllDatashouldbetrendedat1minute
sampling time interval.
samplingtimeinterval.

BCA GREEN MARK

87

CopyrightofBCA.Allrightsreserved.Nounauthorised distributionoruseincommercialmannerisallowed.

NRB 1- 2 Air-conditioning System Air-Conditioned Plant*


V i 4 Additional
Version
Additi
l Criteria
C it i
The instrumentation and installation are required to comply with:
4) Flow meters for chilled- water and condenser water loop shall be
ultrasonic /full bore magnetic type or equivalent in terms of accuracy.
5)Temperaturesensorswithmin.accuracyof 0.05C@0C.
6) Provisionoftwosparethermowellslocatedatbothsideofthe
temperaturesensorforverification.
7)Allthermowellsshallbeinstalledtoensurethesensorscan
beindirectcontactwithfluidflow.

BCA GREEN MARK

88

CopyrightofBCA.Allrightsreserved.Nounauthorised distributionoruseincommercialmannerisallowed.

2)GMNRBVersion4.0

NRB 1- 2 Air-conditioning System Air-Conditioned Plant*


Version 4 Additional Criteria
(d) Instrumentation for Monitoring of Chilled-Water Plant Efficiency

Methodology for determining total uncertainty of measurement:


Errorrsm=
= ((U
 ( (UN)2)

Where UN =individualuncertaintyofvariableN(%)
N=massflowrate,electricalpowerinputorT
Additional 1% is to be included to the uncertainty by flow meters

BCA GREEN MARK

89

CopyrightofBCA.Allrightsreserved.Nounauthorised distributionoruseincommercialmannerisallowed.

2)GMNRBVersion4.0

NRB 1- 2 Air-conditioning System Air-Conditioned Plant*


Part1 EnergyEfficiency
gy
y
Version 4 Additional Criteria
(d) Instrumentation for Monitoring of Chilled-Water Plant Efficiency
Instrumentation Accuracy Consideration:

BCA GREEN MARK

90

CopyrightofBCA.Allrightsreserved.Nounauthorised distributionoruseincommercialmannerisallowed.

2)GMNRBVersion4.0

Part1 EnergyEfficiency
NRB 1- 2 Air-conditioning System Air-Conditioned Plant* (Heat
Balance)
V i 4 AdditionalCriteria
Version4
Additi
l C it i
(e) Heat balance substantiating test for water-cooled chilled-water plant
1 point;

BCA GREEN MARK

91

CopyrightofBCA.Allrightsreserved.Nounauthorised distributionoruseincommercialmannerisallowed.

2)GMNRBVersion4.0

Part1 EnergyEfficiency
NRB 1-4
1 4 Mechanical Ventilation
Version 4 Additional Criteria
( ) Encourage
(b)
g energy
gy efficient mechanical ventilation system
y
design
g as
preferred ventilation mode to air-conditioning in buildings.
Allowable nameplate motor power
Constant Volume

Variable Volume

/ 3/s
1.7 kW/m

2.4 kW/m
/ 3/s

0 6 points for e
0.6
every
er % impro
improvement
ement in air distribution
distrib tion ssystem
stem efficienc
efficiency.
Up to 15 points
BCA GREEN MARK

92

CopyrightofBCA.Allrightsreserved.Nounauthorised distributionoruseincommercialmannerisallowed.

Part1 EnergyEfficiency
gy
y
RB 1-8 Renewable Energy
Version 3

Version 4

EEI30kWh/m2/year
5 points for every 1% replacement of electricity (include tenants usage)
3 points for every 1% replacement of electricity (exclude tenants usage)
EEI<30kWh/m
EEI
< 30 kWh/m2/year
3pointsforevery1%replacementof
3
points for every 1% replacement of
electricity(includetenantsusage)
1.5pointsforevery1%replacementof
15 i f
1%
l
f
electricity(excludetenantsusage)
BCA GREEN MARK
93

CopyrightofBCA.Allrightsreserved.Nounauthorised distributionoruseincommercialmannerisallowed.

2)GMNRBVersion4.0

Part2 WaterEfficiency

NRB 2-4 Water Consumption of Air-conditioning Equipment


Version 3
(a) Use of cooling tower treatment
system to achieve as least 6
cycles of concentration

Version 4
(a) Use of cooling tower treatment
system to achieve as least 7
cycles of concentration

BCA GREEN MARK

94

CopyrightofBCA.Allrightsreserved.Nounauthorised distributionoruseincommercialmannerisallowed.

2)GMNRBVersion4.0

Part3 EnvironmentalProtection
l
NRB 3-5 Green Transport
Version 3
(d) Provision of adequate bicycle
parking
ki llots
t

Version 4
(d) Provision of sheltered bicycle
parking
ki llots
t with
ith shower
h
and
d
changing facilities.

0.5 point for 1.5% x [GFA/10]

point for 3% x [[GFA/10]]


1p

Min. 10 lots; Cap @ 50 lots

BCAGREENMARK

95

CopyrightofBCA.Allrightsreserved.Nounauthorised distributionoruseincommercialmannerisallowed.

2)GMNRBVersion4.0

Part4 IndoorEnvironmentalQuality
NRB 4
4-4
4 Indoor Air Quality
Q alit (IAQ) Management
Version 4 Additional Criteria
(a) Provision of filtration media and Differential Pressure monitoring for filters
in AHU as per SS 554 Clause 4.3.4.5 1 point
(b) ImplementeffectiveIAQmanagementplanafterconstructioninclusiveof
internalsurfaceconditiontesting 1point

DepositthicknesstestOR
Vacuumtest

BCA GREEN MARK

96

CopyrightofBCA.Allrightsreserved.Nounauthorised distributionoruseincommercialmannerisallowed.

3)CertifiedRating CaseStudy

(I) Energy Related


Requirements
P
Partt 1 : E
Energy Effi
Efficiency
i
1-1 Building Envelope ETTV
1-2 Air-Conditioning System

Points Points
Allocation Scored

ETTV = 50 W/m2
Chillerplantefficiency
of0.80kW/RT(12)
20%improvementin
air systems (4)
airsystems(4)

0
19
9

12
30

Remarks

Instrumentationfor
monitoringofchiller
plantefficiency(1)
VSDcontrolsforchilled
water pumps and CT fans
waterpumpsandCTfans
(1)
CO2 sensorsforregulating
th
theoutdoorairflowrate(1)
td
i fl
t (1)
BCA GREEN MARK

97

CopyrightofBCA.Allrightsreserved.Nounauthorised distributionoruseincommercialmannerisallowed.

3)CertifiedRating CaseStudy

Points
Points
(I) Energy Related Requirements Allocation Scored
1-5 Daylighting
6
0
g
g
1-6 Artificial Lighting

12

1-7 Ventilation in Car parks

1-8 Ventilation in Common Areas

1-9 Lift and Escalators


1-0 Energy Efficient Practices &
F t
Features
1-11 Renewable Energy
Category Score for Part 1
Energy Efficiency

12

20

Remarks
30% improvement
in lighting
g
gp
power
budget
Mode of ventilation
for toilets &
Staircases : MV
Development w/o
lift and escalator
Computation of
EEI

30
98

CopyrightofBCA.Allrightsreserved.Nounauthorised distributionoruseincommercialmannerisallowed.

3)CertifiedRating CaseStudy

Point
Allocations

Points
Scored

10

2-2 Water Usage and Leak


Detection

2-3 Irrigation System and


Landscaping

(II) OtherGreenRequirements
Part 2 : Water Efficiency
2-1 Water Efficient Fittings

2-4 Water Consumption of


Cooling Tower
2

CategoryScoreforPart2 Water
Efficiency

Remarks
Water fittings with
WELS g
good rating
g
Provisionofprivate
meteringtomajor
water usage
waterusage
Useofplantsthatrequir
littlewatering
Coolingtowerwater
treatment able to
treatmentableto
achieve7Cycleof
Concentration
BCA GREEN MARK

99

CopyrightofBCA.Allrightsreserved.Nounauthorised distributionoruseincommercialmannerisallowed.

Part3:EnvironmentalProtection
3-1 Sustainable Construction

Point
Allocations
10

Points
Scored
1

3-2 Sustainable Materials

Remarks
CUI=0.7m
= 0 7 m3/m2
CUI
Environmentally
friendly water proofing
friendlywaterproofing
membrane(0.5)&
internalpartition(1)
Useofprecast
concreteroadkerbs
(0.5)

3-3 Greenery Provision


8

GnPR=0.5(1)
Restorationoftrees
f
onsite(1)
Useofhorticulture
waste(1)
100

CopyrightofBCA.Allrightsreserved.Nounauthorised distributionoruseincommercialmannerisallowed.

Part3:EnvironmentalProtection
l

Point
Points
Allocations Scored

3-4 Environmental Management


Practice
4

Remarks
Effectiveenvironmental
friendlyprogrammes(1)
CONQUASproject(1)
CONQUAS
project (1)
Buildinguserguide (1)
Provisionofrecycling
bin(1)

3-5 Green Transport


p

3-6
3
6 Refrigerants

3-7 Stormwater Management


CategoryScoreforPart3
EnvironmentalProtection

Within500mfrom
bus stop (1)
busstop(1)
Refrigerantwith0ODP
(1)
Refrigerantleak
detectionsystem(1)

13

BCA GREEN MARK

101

CopyrightofBCA.Allrightsreserved.Nounauthorised distributionoruseincommercialmannerisallowed.

3)CertifiedRating CaseStudy

(II) Other Green Requirements


Part 4 : Indoor Environmental
Quality
4-1 Thermal Comfort

Point
Points
Allocations Scored

2
2

0
0

4-2 Noise Level

4-3 Indoor Air Pollutants


4-4 IAQ Management
4-5 High Frequency Ballasts

2
Category
C
t
S
Score ffor P
Partt 4
Indoor Environmental Quality

2
4

Remarks

Designforthermal
comfort
Designoccupied
spaces as per SS 553
spacesasperSS553
recommended
ambientsoundlevel

Useofhigh
frequencyballasts
BCA GREEN MARK

102

CopyrightofBCA.Allrightsreserved.Nounauthorised distributionoruseincommercialmannerisallowed.

(II) Other Green Requirements

Point
Points
Allocations Scored

Part 5 : Other Green Features


5-1 Green Features & Innovations
Category Score for Part 5 Other
Green Features

Remarks

0
0

(II) Other Green Requirements


Points Scored
C t
Category
S
Score ffor P
Partt 2 Water
W t Efficiency
Effi i
3
Category Score for Part 3 Environmental Protection
13
Category Score for Part 4 Indoor Environmental
4
Quality
Sub-total for Other Green Requirements
20

BCA GREEN MARK

103

CopyrightofBCA.Allrightsreserved.Nounauthorised distributionoruseincommercialmannerisallowed.

(I)EnergyRelatedRequirements
Part1:EnergyEfficiency
1-1 Building Envelope ETTV
1-2 Air-Conditioning System

Points
P
i t
P i t
Points
Allocation Scored
12
30

Remarks

9.6 ETTV = 42W/m2


24.8 Chiller plant efficiency
of 0.65kW/RT ((16.8))
20% improvement in
air systems (4)
Instrumentation for
monitoring of chiller
plant efficiency (1)
Heat Balance (1)
HeatBalance(1)
VSD controls for
chilled-water pumps and
CT ffans (1)
CO2 sensors for
regulating the outdoor
air flow rate (1)
BCA GREEN MARK

104

CopyrightofBCA.Allrightsreserved.Nounauthorised distributionoruseincommercialmannerisallowed.

(I)EnergyRelatedRequirements
(I)
Energy Related Requirements
1-5 Daylighting

Points
Allocation
Allocation

Points
Scored

3.5

12

12
20

2.5
0
50.4

g
g
1-6 Artificial Lighting

1-7
1
7 Ventilation in Car parks
1-8 Ventilation in Common Areas

1-9
1
9 Lift and
dE
Escalators
l t
1-0 Energy Efficient Practices &
Features
1-11 Renewable Energy
Category Score for Part 1
Energy Efficiency

Remarks
Daylighting
simulation(3)
l h
Daylightingin
staircases(0.5)
30% improvement
p
in lighting power
budget
Development
Development w/o
car park
Mode of ventilation
for toilets &
staircases: MV
Development w/o
lift and
d escalator
l t
EEI (1)
Photosensors (1.5)
BCA GREEN MARK

105

CopyrightofBCA.Allrightsreserved.Nounauthorised distributionoruseincommercialmannerisallowed.

Point
P
i t
Points
P
i t
(II) Other Green Requirements Allocations Scored
Part2:WaterEfficiency
2-1 Water Efficient Fittings
10
8

2-2 Water Usage and Leak


Detection

2-3
2
3 Irrigation System and
Landscaping
2-4 Water Consumption of
C li T
Cooling
Tower

Category Score for Part 2


Water Efficiency

Remarks
Waterfittingswith
WELSVeryGood
rating
Provision of private
metering to major
water usage (1)
Meterslinkedto
BMS (1)
Use of plants that
require little watering
Cooling tower
water
t treatment
t t
t able
bl
to achieve 7 Cycle
of Concentration

12
BCA GREEN MARK

106

CopyrightofBCA.Allrightsreserved.Nounauthorised distributionoruseincommercialmannerisallowed.

Part 3 : Environmental
Protection
3-1 Sustainable Construction

Point
Points
Allocations Scored
Remarks
3
2
10
CUI = 0.7 m /m (1)
4
Useofgreencement
(1)
UseofRCAtoreplace
coarse aggregate (2)
coarseaggregate(2)

3-2 Sustainable Materials

3 3 Greenery Provision
3-3

Environmentally
friendly water proofing
membrane (0.5) &
internal partition (1)
Use of precast
concrete road kerbs
(0.5)
GnPR=1.0(2)
G PR 1 0 (2)
Restoration of trees
onsite (1)
Use of horticulture
waste (1) BCA GREEN MARK
107

CopyrightofBCA.Allrightsreserved.Nounauthorised distributionoruseincommercialmannerisallowed.

Part 3 : Environmental Protection


Part3:EnvironmentalProtection
3-4 Environmental Management
Practice

3-5 Green Transport

3-6 Refrigerants

3-7 Stormwater Management


Category Score for Part 3
Environmental Protection

Point
Point
Points
Points
Allocations Scored
Remarks
8
4
Effective
environmental
i
t l ffriendly
i dl
programmes (1)
CONQUAS project (1)
Building user guide (1)
Provision of recycling
( )
bin (1)
4
2
Within 500m from bus
stop (1)
y p
g
( )
Bicycleparkinglots(1)
2
2
Refrigerant with 0
ODP or GWP < 100
Refrigerant leak
detection system
3
0
18

BCA GREEN MARK

108

CopyrightofBCA.Allrightsreserved.Nounauthorised distributionoruseincommercialmannerisallowed.

(II) Other Green Requirements

Point
Points
Allocations Scored

Part4:IndoorEnvironmentalQuality
P t4 I d
E i
t l Q lit
4-1 Thermal Comfort

4-2 Noise Level

4-3 Indoor Air Pollutants


4-4 IAQ Management
4 5 High Frequency Ballasts
4-5

2
2
2

0
0
2

Category Score for Part 4


I d
Indoor
Environmental
E i
t l Quality
Q lit

Remarks
Design for
thermal comfort
Design occupied
spaces as per SS
553
recommended
ambient sound
level

Use of high
frequency ballasts

4
BCA GREEN MARK

109

CopyrightofBCA.Allrightsreserved.Nounauthorised distributionoruseincommercialmannerisallowed.

85.4
(II) Other Green Requirements
Part 5 : Other Green Features
5 1 Green Features & Innovations
5-1
Category Score for Part 5 Other
G
Green
Features
F t

Point
Points
Allocations Scored
7

Remarks
Carbonfootprint
C b f
i
ofdevelopment

(II) Other Green Requirements


Category Score for Part 2 Water Efficiency
Category Score for Part 3 Environmental Protection
Category Score for Part 4 Indoor Environmental
Quality
Category Score for Part 5 Other Green Features

Points Scored
12
18
4

1
Sub-total for Other Green Requirements

35
BCA GREEN MARK

110

CopyrightofBCA.Allrightsreserved.Nounauthorised distributionoruseincommercialmannerisallowed.

BCA GREEN MARK

111

CopyrightofBCA.Allrightsreserved.Nounauthorised distributionoruseincommercialmannerisallowed.

IndustryBriefingon
BCAGreenMarkVersion4.0
k
i
Topics:1) Daylighting & Glare Simulation Methodology (RB 1-3 & NRB 1-5)
2) Sustainable
S t i bl Construction
C
t
ti
(RB 3
3-1
1 & NRB 3
3-1)
1)
3) Sustainable Products (RB 3-2 & NRB 3-2)
4) Carbon Footprint (RB 5-1 & NRB 5-1)

112

CopyrightofBCA.Allrightsreserved.Nounauthorised distributionoruseincommercialmannerisallowed.

IndustryBriefingon
BCAGreenMarkVersion4.0
Daylighting&GlareSimulationMethodology

113

CopyrightofBCA.Allrightsreserved.Nounauthorised distributionoruseincommercialmannerisallowed.

Daylighting
y g
g & Glare
Simulation

GMV4.0
Residential

Living Room

Dining Room

GMV4.0
N
Non-Residential
R id ti l

Normally Occupied
Spaces
p

114

CopyrightofBCA.Allrightsreserved.Nounauthorised distributionoruseincommercialmannerisallowed.

Residential Buildings

115

CopyrightofBCA.Allrightsreserved.Nounauthorised distributionoruseincommercialmannerisallowed.

Non Residential Buildings


NonResidentialBuildings

116

CopyrightofBCA.Allrightsreserved.Nounauthorised distributionoruseincommercialmannerisallowed.

Simulation Software
SimulationSoftware
Minimumcapabilitytocapturethefollowingcomponentsintoconsideration:

SoftwareToolExamples
Radiance,AutodeskEcotect,IntegratedEnvironmentalSolutions(IES)etc.

117

CopyrightofBCA.Allrightsreserved.Nounauthorised distributionoruseincommercialmannerisallowed.

Simulation Methodology for Daylighting Analysis


SimulationMethodologyforDaylightingAnalysis
Components

Parameters

Computation domain

Development of interest, immediate


surroundings and buildings

C
Computation
t ti coverage

All storey
t
llevels
l off each
h building
b ildi ttower

Selected date

22nd for the month of Dec, Mar, June & Sept

Sky condition

Overcast sky

Ti
Time

1300 h
hours

Computation grid

0.7m off the ground

Illuminance scale range

0 lux to 500 lux, with interval of 50 lux

118

CopyrightofBCA.Allrightsreserved.Nounauthorised distributionoruseincommercialmannerisallowed.

SSimulationMethodologyforGlareAnalysis
u at o
et odo ogy o G a e a ys s
Components

Parameters

Computation domain

Development of interest, immediate


surroundings and buildings

Computation coverage

All storey levels of each building tower

Selected date

22nd for the month of Dec, Mar, June & Sept

Sky condition

Sunny sky

Time

1000 hours & 1600 hours

No. of computation viewpoint

Determine through Sunpath analysis; at


least one viewpoint for each building faade
orientation

Viewpoint location

1.25m off the ground


119

CopyrightofBCA.Allrightsreserved.Nounauthorised distributionoruseincommercialmannerisallowed.

Computation Formula
ComputationFormula
Residential&NonResidential Buildings

120

CopyrightofBCA.Allrightsreserved.Nounauthorised distributionoruseincommercialmannerisallowed.

Non Residential Buildings


NonResidential
Buildings WorkingExample
Working Example

Unit
Type

No. of Unit
Types

Average Distance from


Faade Perimeters (m)

10

4.6

20

5.3

15

51
5.1

15

2.8

75%ofunits
achieveeffective
daylighting

Meetrequirement:Atleast75%ofunits

121

CopyrightofBCA.Allrightsreserved.Nounauthorised distributionoruseincommercialmannerisallowed.

Unit
Type

No. of Unit
Types

Average Distance from


Faade Perimeters (m)

10

4.6

20

53
5.3

15

5.1

15

28
2.8

Weightedaveragedistance(m)
=(10)(4.6)+(20)(5.3)+(15)(5.1)+(15)(2.8)
60
4.5m
=4.5m

122

CopyrightofBCA.Allrightsreserved.Nounauthorised distributionoruseincommercialmannerisallowed.

IndustryBriefingon
BCAGreenMarkVersion4.0
SustainableConstruction

123

CopyrightofBCA.Allrightsreserved.Nounauthorised distributionoruseincommercialmannerisallowed.

Residential&NonResidentialBuildings
d
l
d
l
ld
GMV4.0 Criteria

Category

Point Allocations

RB

3-1 Sustainable Construction

10

NRB

10

124

CopyrightofBCA.Allrightsreserved.Nounauthorised distributionoruseincommercialmannerisallowed.

Sustainable Construction
SustainableConstruction
Residential&NonResidentialBuildings

125

CopyrightofBCA.Allrightsreserved.Nounauthorised distributionoruseincommercialmannerisallowed.

Sustainable Construction
SustainableConstruction
Residential&NonResidentialBuildings

126

CopyrightofBCA.Allrightsreserved.Nounauthorised distributionoruseincommercialmannerisallowed.

IndustryBriefingon
BCAGreenMarkVersion4.0
SustainableProducts

127

CopyrightofBCA.Allrightsreserved.Nounauthorised distributionoruseincommercialmannerisallowed.

Sustainable Products
SustainableProducts
Residential&NonResidentialBuildings

128

CopyrightofBCA.Allrightsreserved.Nounauthorised distributionoruseincommercialmannerisallowed.

Approved Local Certification Bodies

Singapore Green
Building Council (SGBC)

Good

Very Good

SEC - Singapore Green


Labeling Scheme (SGLS)

Good

Excellent

Weightage based on Extent of


Environmental Friendliness of Products

129

CopyrightofBCA.Allrightsreserved.Nounauthorised distributionoruseincommercialmannerisallowed.

WeightagebasedonExtentof
h
b d
f
EnvironmentalFriendlinessofProducts
1.SingaporeGreenBuildingCouncil(SGBC)
1
Singapore Green Building Council (SGBC)
 focusesonbuildingproducts
Score (Based on SGBC methodology)
Score(BasedonSGBCmethodology)
5060%............

Good

6175%............

VeryGood

7685%............

Excellent

85%&above

Leader

SGBCGreen
Productlabel
Classification

Note: Scalemayvarywithspecifictoproductcategories
130

CopyrightofBCA.Allrightsreserved.Nounauthorised distributionoruseincommercialmannerisallowed.

WeightagebasedonExtentof
h
b d
f
EnvironmentalFriendlinessofProducts
Singapore Green Building Council (SGBC)
SingaporeGreenBuildingCouncil(SGBC)
8Buildingproductgroups:
1. Mechanical
2. Electrical
3. Faade&Envelope
4. Concrete&Structure
5. InteriorWorks
6. InteriorFinishes
7 RecycledMaterials
7.
Recycled Materials
8. RenewableEnergy

Productlisting:
http://www.sgbc.sg/index.php/listing
/ d t/
/products/
131

CopyrightofBCA.Allrightsreserved.Nounauthorised distributionoruseincommercialmannerisallowed.

S t i bl P d t Example
SustainableProducts
E
l

132

CopyrightofBCA.Allrightsreserved.Nounauthorised distributionoruseincommercialmannerisallowed.

Sustainable Products Example


SustainableProducts

133

CopyrightofBCA.Allrightsreserved.Nounauthorised distributionoruseincommercialmannerisallowed.

IndustryBriefingon
BCAGreenMarkVersion4.0
CarbonFootprint

134

CopyrightofBCA.Allrightsreserved.Nounauthorised distributionoruseincommercialmannerisallowed.

Residential & Non Residential Buildings


Residential&NonResidentialBuildings

135

CopyrightofBCA.Allrightsreserved.Nounauthorised distributionoruseincommercialmannerisallowed.

Carbon Footprint Objective&Requirement


CarbonFootprint
Objective & Requirement
OBJECTIVE
To calculate the carbon emissions resulted from the associated energy used
during construction and operational phase of a development.
REQUIREMENT
To produce a complete carbon footprinting report of the development EITHER
by appointing an independent carbon consultant,
consultant OR by completing a carbon
footprinting form provided by BCA.
A simple carbon footprinting form has been developed jointly by BCANUS
BCA NUS to
capture the overall energy used from the construction and building operation
phase of a development.

136

CopyrightofBCA.Allrightsreserved.Nounauthorised distributionoruseincommercialmannerisallowed.

Carbon Footprint PointAllocations


CarbonFootprint
Point Allocations
1POINTwillbeawardedforsubmissionof:
COMPLETE b f
COMPLETEcarbonfootprintingREPORTwhichincludeembodiedand
i i REPORT hi h i l d
b di d d
operationalcarbonemissionsoftheprojectdevelopment,donebyan
independentandregisteredcarbonconsultant.
OR
COMPLETEcarbonfootprintingFORM (consistof11topcommonmaterials
usedinatypicalproject)appendedintheBCAGreenMarkCertificationStandard
for New Buildings (GMV4.0).
forNewBuildings(GMV4.0).
0.5POINTwillbeawardedfor:
PARTIAL submission of at least 4 out of 11 materials data required in the
PARTIALsubmissionofatleast4outof11materialsdatarequiredinthe
carbonfootprintingform.

137

CopyrightofBCA.Allrightsreserved.Nounauthorised distributionoruseincommercialmannerisallowed.

138

CopyrightofBCA.Allrightsreserved.Nounauthorised distributionoruseincommercialmannerisallowed.

Carbon Footprint NecessaryInformation&Documentation


CarbonFootprint
Necessary Information & Documentation
Information Required

Source of Information

Energy used for the material production

Material suppliers

Quantity of materials used for construction

Bill of Quantities

Energy used on construction site

Contractors
Contractor
s book
book-keeping
keeping

Estimates on energy used on building


operation phase

EEI value

NOTE: Consultants will need to liaise closely with materials suppliers


AND
Contractors to obtain the relevant data required in the carbon
footprinting form
(e.g. Energy involved in cement production, quantity of cement used in
the project)

139

CopyrightofBCA.Allrightsreserved.Nounauthorised distributionoruseincommercialmannerisallowed.

Carbon Footprint ContactPersons


CarbonFootprint
Contact Persons
BCA Contact Person:
BCAContactPerson:
Dr.EdwardAnggadjaja
Tel:
6248 9867
62489867
Email:edward_anggadjaja@bca.gov.sg

NUSContactPerson:
Dr.EvelynTeo
Tel:
65161008
g
@
g
Email:bdgteoal@nus.edu.sg

140

CopyrightofBCA.Allrightsreserved.Nounauthorised distributionoruseincommercialmannerisallowed.

Thank You
ThankYou

141

CopyrightofBCA.Allrightsreserved.Nounauthorised distributionoruseincommercialmannerisallowed.

For more information on Green Mark Version 4.0 please refer:


FormoreinformationonGreenMarkVersion4.0,pleaserefer:
1) SustainableBuiltEnvironment
http://www.bca.gov.sg/sustain/sustain.html

2) LegislationonEnvironmentalSustainabilityforBuildings
http://www.bca.gov.sg/EnvSusLegislation/Environmental_Sustainability_Legislation.html

3) CodeforEnvironmentalSustainabilityofBuildings(2nd Edition)
http://www.bca.gov.sg/EnvSusLegislation/others/Env_Sus_Code2010.pdf

4) BCAGreenMarkCertificationStandardforNewBuildings(GMVersion4.0)
http://www.bca.gov.sg/EnvSusLegislation/others/GM_Certification_Std2010.pdf

5) BCAGreenMarkforNewResidentialBuildings(VersionRB/4.0)
BCA Green Mark for New Residential Buildings (Version RB/4 0)
http://bca.gov.sg/GreenMark/others/gm_resi_v4.pdf

6)
) BCAGreenMarkforNewNonResidentialBuildings(VersionNRB/4.0)
g (
/ )
http://bca.gov.sg/GreenMark/others/gm_nonresi_v4.pdf

142

You might also like