Professional Documents
Culture Documents
SPECIFICATION
HVAC WORKS
Job No: R.14078
Date: 10 Sep 2015
Revision 00
Rev
Description
00
Specification
Issued by
HT
Date
10/09/15
This report has been prepared for the sole benefit, use and information of the wave luxury villa project for the purposes set out in the
report.
Section:
HVAC Works
Author:
Anil Kumar
Date:
10 Sep 2015
Rev:
00
Approved:
Shaun McGonigal
Signature:
Checked
SM
23 05 00
23 05 13
23 05 29
23 05 48
23 05 53
23 05 93
23 07 00
23 08 00
23 23 00
23 31 00
23 33 00
23 34 13
23 37 13
23 0 900
23 7 200
1/1
36
6
13
15
8
21
13
5
5
17
7
7
6
7
7
1
1
1
1
Index
SECTION 23 05 00
COMMON WORK RESULTS FOR HVAC
PART 1 - GENERAL
1.1
A.
SUMMARY
This Section includes the following:
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
1.2
A.
B.
C.
D.
The contractor shall ensure during the tender stage that no discrepancy
occurs between the specifications and drawings. Should discrepancies be
discovered post tender stage, then the most onerous requirement shall be
deemed to be included.
E.
1.3
SCOPE OF WORK
1.4
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
SYSTEM DESCRIPTION
The description below highlights the specific requirement of mechanical
systems within the scope of this project.
1.6
VENTILATION
a)
b)
Kitchen Ventilation:
Kitchen exhaust system incorporating purpose made exhaust hood with
grease filters. Exhaust fan shall be either bifurcated type or direct and
suitable for high temperature application. The kitchen exhaust fan shall
be operated through a local switch in the kitchen as and when required.
Refer to drawings for identification of the system mentioned.
1.7
DESIGN REQUIREMENTS
A.
Oman
23035 North
58017 East
15 metres
46.1C db/30.8C wb
16C db/11C wb
Common Work Results
for HVAC
Rev: 0
Room Type
Summer
Design
Temp. Dry
bulb (0C)
Relative
Humidity
22+/-1
22+/-1
50-55%
Entrance halls
22+/-1
50-55%
Circulation
spaces
22+/-1
50-55%
Lobbies/Corri
dor
22+/-1
50-55%
Kitchen
24+/-1
50-55%
Bedrooms
Drawing/Dinin
g rooms
(%)
50-55%
Note:
A.
B.
The drawings shall be scale 1:100 for plans, 1:50 for side view sections,
1:20 for details such as pump room, focused details, and 1:10 for product
items such as valves, pieces, etc.
Clear legend will be accompanied all drawings to clarify all items,
dimensions, abbreviations, parts, etc.
Shop Drawings will include all details of installations coordination with
other services, supports, changes, deviations from design works,
explanations, etc.
No work will be started before approval of Shop Drawings with official
stamps.
3. Equipment installation and piping layout double line drawings of plant
rooms. Clearly indicating all fittings, supports, valves and control gear to
a scale 1:20. Submit sections and elevations as required by the
Engineer.
4. Typical floor plans indicating shafts, riser locations etc. to a scale of 1:50.
5. Builders work layout plans to a scale of 1:100/1:50.
6. Electrical wiring diagrams (NTS) and panel installation details (1:20).
7. Test and performance certificates of equipment, where required.
B. Shop drawings for controls and control systems, including diagrams and
description of the sequence of operation.
C. Co-ordinate shop drawings and space clearance between sections before
submission; note this on each shop drawing.
D. Product Data: Full details of all systems and components, including but not
limited to :
1.
All HVAC equipment such as: Fans, Fan Coil Units, Energy recovery
units
2.
3.
4.
5.
6.
7.
8.
Submit project As-Built prepared from shop drawings for all Mechanical
systems including diagrams.
J.
2.
3.
4.
5.
K. Show all technical data (length, flow rate, pressures, etc.) in metric units.
L. Product Data: For the following:
1.
2.
3.
4.
Transition fittings.
Dielectric fittings
Mechanical sleeve seals.
Escutcheons.
M. Welding certificates.
1.9
A.
B.
C.
D.
1.10
A.
B.
C.
D.
E.
F.
G.
1.11
A.
SUBMITTALS
Product Data: For the following:
1.
2.
3.
4.
B.
Transition fittings.
Dielectric fittings.
Mechanical sleeve seals.
Escutcheons.
Welding certificates.
1.12
QUALITY ASSURANCE
A.
B.
C.
D.
E.
F.
G.
Submit a copy of all above standards and maintain a document on site. The
contractor shall not proceed with the work unless such standards are made
available.
H.
1.13
A.
B.
1.14
Support to prevent
QUALIFICATIONS
A.
B.
C.
Conform to Local Authorities for Domestic and Brackish water pipe system
requirement. Provide back flow preventions on all branch connections from
mains to building. Water heaters shall be provided with pressure relief and
safety protection.
1.15
REGULATORY REQUIREMENTS
A.
B.
1.16
A.
1.17
ENVIRONMENTAL REQUIREMENTS
Do not install underground piping when bedding is wet.
EQUIPMENT REQUIREMENT AND INSTALLATION
A.
B.
C.
1.18
COORDINATION
A.
Arrange for pipe spaces, chases, slots, and openings in building structure
during progress of construction, to allow for HVAC installations.
B.
C.
Coordinate requirements for access panels and doors for HVAC items
requiring access that are concealed behind finished surfaces. Access
panels and doors are specified in Division 08 Section "Access Doors and
Frames."
PART 2 - PRODUCTS
2.1
A.
2.2
MANUFACTURERS
In other Part 2 articles where subparagraph titles below introduce lists, the
following requirements apply for product selection:
1.
2.
A.
Refer to individual Division 23 piping Sections for pipe, tube, and fitting
materials and joining methods.
B.
Pipe Threads: ASME B1.20.1 for factory-threaded pipe and pipe fittings.
2.3
JOINING MATERIALS
A.
B.
2.
C.
Full-Face Type: For flat-face, Class 125, cast-iron and castbronze flanges.
Narrow-Face Type: For raised-face, Class 250, cast-iron and
steel flanges.
D.
E.
F.
G.
Welding Filler Metals: Comply with AWS D10.12 for welding materials
appropriate for wall thickness and chemical analysis of steel pipe being
welded.
H.
I.
2.4
TRANSITION FITTINGS
A.
B.
C.
2.5
DIELECTRIC FITTINGS
A.
B.
C.
Dielectric Unions:
Factory-fabricated, union assembly, pressure and
temperature rated to suit system rating.
D.
Dielectric Flanges:
Factory-fabricated, companion-flange
pressure and temperature rated to suit system rating.
assembly,
E.
Separate companion flanges and steel bolts and nuts shall be rated to
suit system pressures and temperatures.
F.
G.
2.6
A.
2.7
SLEEVES
A.
B.
Cast Iron (Through non-fire rated beams, walls, footings and potentially wet
floors): Cast or fabricated "wall pipe" equivalent to ductile-iron pressure
pipe, with plain ends and integral waterstop, unless otherwise indicated.
C.
Prefabricated Sleeves (Through fire rated walls and floors): Prefabricated fire
rated sleeves complete with insulation and seals. UL listed assembly.
D.
2.8
A.
ESCUTCHEONS
Description: Manufactured wall and ceiling escutcheons and floor plates,
with an ID to closely fit around pipe, tube, and insulation of insulated piping
and an OD that completely covers opening.
B.
C.
D.
E.
F.
G.
H.
Split-Casting, Floor-Plate Type: Cast brass with concealed hinge and set
screw.
2.9
A.
GROUT
Description:
ASTM C 1107, Grade B, nonshrink and nonmetallic, dry
hydraulic-cement grout.
1.
2.
3.
2.10
Characteristics:
Post-hardening, volume-adjusting, nonstaining,
noncorrosive, nongaseous, and recommended for interior and exterior
applications.
Design Mix: 34.5-MPa, 28-day compressive strength.
Packaging: Premixed and factory packaged.
FLASHING
A.
B.
C.
Lead Flashing:
1.
2.
D.
Flexible Flashing: 1.2 mm (47 mil) thick sheet butyl; compatible with roofing.
E.
Caps: Steel, 0.8 mm (22 gauge) minimum; 1.5 mm (16 gauge) at fire
resistant elements.
2.11
ACCESS DOORS
A.
Co-ordinate access doors for false ceilings or spaces and access for
suspended lay-in tile ceilings for servicing of equipment and accessories or
for inspection of safety, operating or fire safety devices, with Contractor and
all other Specialist Contractors whose work may be affected.
B.
Access doors shall be flush mounted 600 x 600 mm for body and 300 x
300mm for hand entry unless otherwise noted. Doors shall open 180 have
rounded safety corners, concealed hinges, screwdriver latches and anchor
straps. Steel shall be prime coated. Door shall be of approved manufacture
with published literature.
PART 3 - EXECUTION
3.1
A.
B.
C.
D.
E.
Space pipe runs in relation to one another, other services runs and building
structure, allow for specified thickness of thermal insulation and ensure
adequate space for access to pipe joints etc. refer to table below for
recommended minimum clearances in spacing pipe runs:
BETWEEN
AND
CLEARANCE
mm
Pipeline insulated or
uninsulated
Wall finish
25
Insulated pipeline
Ceiling finish or
50
soffit
-
Floor finish
150
Uninsulated pipeline
Adjacent service
runs
25
Adjacent pipelines
both insulated
150
one insulated
75
one uninsulated
75
both uninsulated
25
F.
Install piping above accessible ceilings to allow sufficient space for ceiling
panel removal.
G.
H.
Install piping at indicated slopes or maintain gradient for draining and venting
purposes. Ensure entire pipe system is drainable.
I.
J.
K.
L.
M.
N.
Seal all open ends as installation proceeds by plugs, caps or blank flanges,
to prevent ingress of foreign matter. In the event of such precautions not
being taken, strip out pipe work adjacent to open ends to demonstrate that
fouling of bores has not occurred.
O.
P.
Install air vents as indicated on plans and at high points located on pipe
branches. Use automatic air vent valves with copper outlet pipe from the
valve to a tun-dish on adjacent drain line or another suitable location.
Q.
R.
Wrap pipe work in screed with two layers of PVC protective tapes prior to
laying or provide pipe work with PVC sleeves.
S.
T.
3.2
A.
B.
C.
D.
E.
F.
Where sleeves in concrete structural elements are omitted due to error, core
the required openings only after obtaining written permission of the
Engineer. Provide sleeves with puddle flanges resting on the concrete
surface, and non-shrink grout to fix the sleeve in position. Cutting of holes by
chiseling is not permitted.
G.
Erect sleeves, puddle flanges etc. in the formwork, perpendicular to the wall
face and rigidly to resist displacement during pouring of concrete.
H.
Ensure verticality of flange faces and alignment of bolt holes with connected
equipment (valves, etc.).
I.
Install sleeves for pipes passing through concrete and masonry walls,
gypsum-board partitions, and concrete floor and roof slabs.
1.
2.
3.
Install sleeves in new walls and slabs as new walls and slabs are
constructed.
Install sleeves that are large enough to provide 8mm annular clear
space between sleeve and pipe or pipe insulation and or to allow for
movement due to expansion and contraction. Use the following sleeve
materials:
a.
b.
c.
4.
J.
K.
L.
M.
Provide fire proprietary manufacturer stopping products for plastic piping and
cables penetrating a fire wall or slab. Install intumescent collars for sealing
pipes. Fire rating of material shall be similar to fire barriers being penetrated.
All products shall be FM certified and in accordance with ISO 9002.
N.
3.3
A.
3.4
A.
3.5
A.
Sleeves for pipes passing through RCC water storage tanks: Assembly
comprising wall sleeve, synthetic rubber expandable link seal, pressure
plates and fasteners; allowing installation of pipe after the sleeve has been
cast in the wall. Materials of construction shall be as follow, selected to suit
the environment of installation:
1.
2.
3.
4.
Fasteners
PIPE FITTINGS
Use eccentric type reductions and enlargements on horizontal pipe runs to
allow draining and venting, concentric on vertical pipes, with easy transition
and an included angle not exceeding 30 degree. Do not use bushes, except
at equipment where required size is not of standard manufacture. Where
required, use eccentric bushes to allow draining or venting; maximum aspect
ratio not to exceed two pipe sizes; above this ratio use reducing fittings. Use
square tees at venting and draining points.
FABRICATED JUNCTIONS
Do not fabricate joints unless specifically permitted. If permitted, form by
inserting a branch section of a pulled bend into the main pipe. Develop the
profiles of both the branch section the hole in the main pipe, to ensure
minimum protrusion into the main pipe. Weld or braze into position.
FABRICATED FITTINGS - NON-FERROUS
Provide pipe material and end connections to the specification of the
associated straight pipe runs.
1.
Pattern: Bends, springs, offsets and branches.
2.
Technique: Machine bend. Deformed bends will no be accepted.
a.
Fabricate branch from a section of pulled bend, profiled to match
the contour of the main to avoid overlap and protrusion into the
main. Cut and swage the main to form a raised cup to accept the
spigot end of the branch. Limit angle of the branch to 60. Join by
bronze welding on site. Apply reinforcement by plates, collars or
shoes.
3.6
A.
B.
For plumbing pipes passing through roof slab provide flashing sleeve with
integral flashing flag, clamp the roof waterproofing membrane into the
flashing clamp and fill around with approved type grout.
C.
D.
Provide curbs for mechanical roof installations 300 mm minimum high above
roofing surface. Flexible sheet flash and counter flash with galvanized sheet
metal watertight.
3.7
A.
PIPING CONNECTIONS
Make connections according to the following, unless otherwise indicated:
1.
2.
3.
4.
3.8
A.
B.
C.
3.9
A.
shall be used where changes in size and/or direction are required. The pipes
shall not be bent to create a change in direction and/or for any other reason
whatever the pipe size. The Engineers representative shall be allowed to
inspect such materials upon their delivery to the job site and prior to their
installation into the pipe system.
B.
C.
Wearing pads shall be placed at the bottom of the pipes where they are
resting in contact with the supports to avoid metal loss from the pipes
external surfaces at the contact areas due to metallic friction with the
sleepers. The said pads material shall be similar or compatible to the pipes
material with minimum thickness of 10mm and shall be seal welded to the
pipe to avoid corrosion.
D.
E.
The maximum allowable deflection of the pipe longitudinal axis is one (1.0)
degree over an ARC equal in length to the pipe diameter, or the minimum
radius of curvature shall comply with Section 406.2 of ASME B31.4.
3.10
A.
3.11
A.
Preparation :
1.
Prepare for bronze welding in accordance with BS 1724. Form pipe
ends for bell type butt joints, except where welding fittings are used.
B.
3.12
A.
Use number and diameters of bolts to standard. Fit bolts of length to give
not less than one thread, or more than 3mm protrusion beyond nut when
joint is pulled up.
B.
3.13
A.
Welded Flanges :
1.
Weld neck and bore of 'slip on' flange.
2.
Butt weld neck of welding neck flange.
B.
Screwed Flanges:
1.
Apply jointing materials. Screw on flange and expand tube into flange
with roller expander where necessary.
C.
Preparation:
1.
Ensure that flange mating faces are parallel; flange peripheries are
flush with each other; and bolt holes are correctly aligned.
D.
3.14
A.
Preparation:
1.
Ensure that plain ends are cut square. Reamer out bore at plain ends.
Screw plain ends, taper thread.
B.
3.15
GROOVED JOINTS
A.
Preparation:
1.
Cut or roll grooves in ends of pipe based on pipe and couplings
manufacturers written instructions for pipe wall thickness
2.
Lubricate ends and fasten bolts.
B.
Assemble joint with coupling, gasket and bolts. Use grooved end fittings and
rigid grooved end pipe couplings.
C.
3.16
A.
b.
B.
3.17
A.
Preparation:
1.
Ensure that plain ends are cut square. Reamer out bore at plain ends
to full bore size. Clean plain ends with fine steel wool.
B.
3.18
A.
Preparation:
1.
Prepare for brazing in accordance with BS 1723. Use manufactured
fittings not subject to degasification and suitable for application.
B.
3.19
A.
Use solvent welded joints generally, provide ring seal joints at expansion
joints and where as necessary (pipes embedded in walls etc.).
B.
Preparation:
1.
Ensure that plain ends are cut square. Reamer out bore at plain ends.
Clean plain ends with solvent cleaner.
C.
3.20
A.
Preparation :
1.
Square cut plain ends for fusion welding. Form pipe ends for socket
type joints.
2.
Use socket type joints for concealed pipe work (in walls or small shafts)
B.
1.
3.21
A.
3.22
A.
3.23
A.
B.
C.
3.24
A.
3.25
A.
1.
2.
3.
4.
3.26
A.
Arrange pipe work, valves, drains, air vents, demountable joints, supports
etc. for convenient routine maintenance and renewals. Provide all runs with
a regularly spaced pattern of demountable joints in the form of unions,
flanges, etc. and also at items of equipment to facilitate disconnection.
B.
C.
Locate vents at high level in pipe work or when there is a change in direction
forming a U bend in the vertical plain. Locate drains at lowest end of risers
as shown on the drawings.
3.27
A.
Verify excavations are to required grade, dry and not over excavated.
B.
C.
D.
Establish levels of buried pipe outside the building to ensure minimum cover
in accordance with Local authority requirements or as shown on plans.
3.28
A.
3.29
A.
ESCUTCHEONS
A. Set screw type escutcheons, with size sufficient to completely cover
exposed penetrations shall be provided at all pipe penetrations. This shall be
finished with prime coat where adjoining surface is to be filed painted, with
baked enamel white finish where adjoining surface is fiber board and chrome
finish where adjoining surface is tiled with ceramic, marble, etc.
ELECTRICAL EQUIPMENT ROOM PRECAUTIONS
Where it is unavoidable to install pipe work in Electrical rooms suitable drip
pans shall be provided under the complete length of pipe.
3.30
A.
B.
C.
D.
Install equipment to allow right of way for piping installed at required slope.
3.31
A.
CONCRETE BASES
Concrete Bases:
Anchor equipment to concrete base according to
equipment manufacturer's written instructions and according to seismic
codes at Project.
1.
2.
3.
4.
5.
6.
7.
3.32
A.
B.
C.
3.33
PAINTING
A.
General; On completion of the system and testing of all parts of the plants,
all plant and pipe work and ironwork including pipe supports and welded
joints other than that with galvanized, stainless steel, chromed or vitreous
enameled surfaces or that which are fabricated from copper, brass or
gunmetal, shall be thoroughly cleaned from all dirt, grease and scale and
shall be primed with one coat of base red oxide primer subsequently given a
second of red oxide and finished painted with two coats of an approved type
of paint. Pipes that are concealed in construction or are finished with
insulation shall be primed with a base and finish coat of red oxide only. The
insulation in all exposed areas shall be finished painted. Flexible
connections shall not be painted.
B.
Steel Pipe work Painting; Remove scale, rust or temporary protective coating
by sand blasting and wire brushing or use of approved solvents. Paint with
one coat of red oxide primer, as work proceeds. Use salt free sand with
neutral pH value when sand blasting.
C.
Steel Work Painting; Prepare supports, bearers and other uncovered steel
work as steel pipe work.
1.
Where not exposed, paint with one coat zinc chromate or red oxide
primer. Thickness of primer paint should not be less than 50 microns.
2.
Where exposed use primer and two coats of an approved type of paint.
3.34
GROUTING
A.
Mix and install grout for HVAC equipment base bearing surfaces, pump and
other equipment base plates, and anchors.
B.
C.
D.
E.
F.
Place grout on concrete bases and provide smooth bearing surface for
equipment.
G.
H.
END OF SECTION
SECTION 23 05 13
COMMON MOTOR REQUIREMENTS FOR HVAC EQUIPMENT
PART 1 - GENERAL
1.1
A.
1.2
A.
1.3
A.
RELATED DOCUMENTS
Drawings and general provisions of the Contract, including General and
Supplementary Conditions and Division 01 Specification Sections, apply to
this Section.
SUMMARY
Section includes general requirements for single-phase and polyphase,
general-purpose, horizontal, small and medium, squirrel-cage induction
motors for use on ac power systems up to 600 V and installed at equipment
manufacturer's factory or shipped separately by equipment manufacturer for
field installation.
COORDINATION
Coordinate features of motors, installed units, and accessory devices to be
compatible with the following:
1.
2.
3.
4.
1.4
Motor controllers.
Torque, speed, and horsepower requirements of the load.
Ratings and characteristics of supply circuit and required control
sequence.
Ambient and environmental conditions of installation location.
GENERAL REQUIREMENTS
A.
B.
C.
D.
E.
F.
G.
Keys: Ensure motors and drives are supplied complete with keys and
keyways.
PART 2 - PRODUCTS
2.1
A.
B.
C.
2.2
MOTOR CHARACTERISTICS
A.
B.
2.3
POLYPHASE MOTORS
A.
B.
C.
D.
For motors with 2:1 speed ratio, consequent pole, single winding.
For motors with other than 2:1 speed ratio, separate winding for each
speed.
E.
F.
G.
H.
I.
Insulation: Class F.
J.
K.
2.4
starting
Enclosure Material: Cast iron for motor frame sizes 324T and larger; rolled
steel for motor frame sizes smaller than 324T.
POLYPHASE MOTORS WITH ADDITIONAL REQUIREMENTS
A.
B.
2.
3.
4.
C.
2.5
Windings:
Copper magnet wire with moisture-resistant insulation
varnish, designed and tested to resist transient spikes, high frequencies,
and short time rise pulses produced by pulse-width modulated inverters.
Energy-and Premium-Efficient Motors:
Class B temperature rise;
Class F insulation.
Inverter-Duty Motors: Class B temperature rise; Class F insulation.
Thermal Protection: Comply with NEMA MG 1/IEC requirements for
thermally protected motors.
Severe-Duty Motors:
factor.
A.
Motor rating up to and including 0.75 kW: Provide starter with manual reset,
adjustable, inverse time delay, and ambient temperature compensated
thermal over current release to Bs 4941. Ensure over current release is
compatible with starting, accelerating and running characteristics of motor,
starter and driven machine combination. Use phase unbalance protection on
three phase equipment.
B.
Motor rating above 0.75 kW: Provide starter with sensitive discriminating
thermal magnetic over current relay with precise time/current characteristics
to BS142. Protect motor against effects of sustained and cyclic over current,
out of balance phase current, stalled condition and earth faults. Use running
load indication type overcurrent relays with accuracy of setting and indication
within plus or minus 3 per cent, expressed as a percentage of setting
indicated.
C.
D.
E.
F.
For motor rating 0.75 kW and above fit two thermistors embedded in each
phase of stator windings.
G.
H.
I.
2.6
MOTORS STARTERS
A.
B.
C.
MOTOR STARTERS SOFT STARTER TYPE: Use soft starters with three
phase motors above 3.75 kW. For details refer specification Section 262300.
D.
2.7
INDIRECT DRIVES
A.
Belts
B.
Pulleys
C.
Pulley
Adjustment :
2.8
A.
B.
C.
Mount motors on a substantial mild steel bed plate fixed to machine casing:
*
*
Separately supported.
Supported entirely from the machine casing.
D.
GUARDS: Totally protect drives and couplings. Fit around all exposed or
otherwise accessible drive shafts, pulleys, V belts or couplings, purpose
made guards.
E.
Ensure guards comply with National or Local Safety Codes, Acts and Bye
Laws and incorporate following features:
1. Construction to BS 5304 and generally of galvanized steel wire mesh.
2. Stiffening within the guards to ensure rigidity and freedom from vibration.
3. Allowance for prime mover adjustment during belt tensioning procedures.
4. Temporary access of all shafts for use of Tachometer.
2.9
A.
SINGLE-PHASE MOTORS
Motors larger than 1/20 hp shall be one of the following, to suit starting torque
and requirements of specific motor application:
1.
2.
3.
4.
Permanent-split capacitor.
Split phase.
Capacitor start, inductor run.
Capacitor start, capacitor run.
B.
C.
D.
E.
PART 3 - EXECUTION
Refer to the Mechanical Equipment Manufacturers details.
END OF SECTION
SECTION 23 05 29
HANGERS AND SUPPORTS FOR HVAC PIPING AND EQUIPMENT
PART 1 - GENERAL
1.1
A.
1.2
A.
RELATED DOCUMENTS
Drawings and general provisions of the Contract, including General and
Supplementary Conditions and Division 01 Specification Sections, apply to
this Section.
SUMMARY
Section Includes:
1.
2.
3.
4.
5.
6.
7.
B.
Related Sections:
1.
2.
3.
4.
1.3
DEFINITIONS
A.
B.
1.4
A.
PERFORMANCE REQUIREMENTS
Delegated Design: Design trapeze pipe hangers and equipment supports,
including comprehensive engineering analysis by a qualified professional
engineer, using performance requirements and design criteria indicated.
B.
2.
1.5
SUBMITTALS
A.
B.
C.
D.
Welding certificates.
E.
Samples: Provide one sample for each type of support and hangers.
1.6
QUALITY ASSURANCE
A.
B.
1.7
A.
REFERENCES
ANSI B 31.1
Power Piping.
B.
C.
D.
MSS SP 69 -
E.
MSS SP 89 Practices.
F.
BS 3382
components.
Specification
for
electroplated
coatings
on
threaded
PART 2 - PRODUCTS
2.1
A.
2.2
A.
2.3
A.
Description:
MSS SP-58, Types 1 through 58, factory-fabricated
components.
Galvanized Metallic Coatings: Pre-galvanized or hot dipped.
Nonmetallic Coatings: Plastic coating, jacket, or liner.
Padded Hangers: Hanger with fiberglass or other pipe insulation pad
or cushion to support bearing surface of piping.
Hanger Rods: Continuous-thread rod, nuts, and washer made of
carbon steel.
5.
6.
7.
Description:
Shop- or field-fabricated pipe-support assembly for
supporting multiple parallel pipes.
Standard: MFMA-4.
Channels: Continuous slotted steel channel with inturned lips.
Channel Nuts: Formed or stamped steel nuts or other devices
designed to fit into channel slot and, when tightened, prevent slipping
along channel.
Hanger Rods: Continuous-thread rod, nuts, and washer made of
carbon steel.
Metallic Coating: Hot-dipped galvanized.
Paint Coating: Epoxy
8.
B.
2.
3.
4.
5.
6.
2.4
A.
Insulation-Insert Material for Cold Piping: ASTM C 552, Type II cellular glass
with 688-kPa minimum compressive strength and vapor barrier.
B.
C.
D.
Insert Length: Extend 50 mm beyond sheet metal shield for piping operating
below ambient air temperature.
2.5
FASTENER SYSTEMS
A.
B.
Mechanical-Expansion Anchors:
Insert-wedge-type, zinc-coated steel
anchors, for use in hardened portland cement concrete; with pull-out,
tension, and shear capacities appropriate for supported loads and building
materials where used.
2.6
FLOOR SUPPORT
A.
B.
Ferrous Piping over 150mm nom. dia. for HVAC services: Cast Iron pipe roll
with base and stand. Furnish RCC/structural steel pedestals as appropriate
to locate the base. Use pipe covering protection saddle for insulated piping.
2.7
A.
Ferrous Piping: Galvanized steel riser clamps and/or offset pipe clamp. Solid
wood inserts shall be used at the supports for insulated piping.
B.
2.8
PIPE ANCHORS
A.
B.
Provide and fix all associated backing plates, nuts, washers and bolts for
attachment to or building into building structure; ensure structure is suitable
for transmitted stress. Set out and line up anchors accurately in position.
Inspect final grouting into building structure.
C.
Steel Pipes:
2.9
1.
2.
3.
PIPE STANDS
A.
B.
Compact Pipe Stand: One-piece plastic unit with integral-rod roller, pipe
clamps, or V-shaped cradle to support pipe, for roof installation without
membrane penetration.
C.
Low-Type, Single-Pipe Stand: One-piece plastic base unit with plastic roller,
for roof installation without membrane penetration.
D.
E.
F.
2.10
A.
2.11
2.
3.
4.
5.
A.
Structural Steel: ASTM A 36/A 36M, carbon-steel plates, shapes, and bars;
black and galvanized.
B.
PART 3 - EXECUTION
3.1
A.
Metal Pipe-Hanger Installation: Comply with MSS SP-69 and MSS SP-89.
Install hangers, supports, clamps, and attachments as required to properly
support piping from the building structure.
B.
2.
C.
D.
E.
F.
1.
2.
G.
H.
I.
J.
Install lateral bracing with pipe hangers and supports to prevent swaying.
K.
L.
Load Distribution: Install hangers and supports so that piping live and dead
loads and stresses from movement will not be transmitted to connected
equipment.
M.
Pipe Slopes: Install hangers and supports to provide indicated pipe slopes
and to not exceed maximum pipe deflections allowed by ASME B31.9 for
building services piping.
N.
Insulated Piping:
1.
2.
3.
Install MSS SP-58, Type 40, protective shields on cold piping with
vapor barrier. Shields shall span an arc of 180 degrees.
a.
4.
d.
e.
3.2
5.
6.
Thermal-Hanger Shields:
piping insulation.
EQUIPMENT SUPPORTS
A.
B.
Grouting: Place grout under supports for equipment and make bearing
surface smooth.
C.
3.3
METAL FABRICATIONS
A.
Cut, drill, and fit miscellaneous metal fabrications for trapeze pipe hangers
and equipment supports.
B.
C.
3.4
ADJUSTING
A.
Hanger Adjustments:
Adjust hangers to distribute loads equally on
attachments and to achieve indicated slope of pipe.
B.
3.5
A.
PAINTING
Touchup: Clean field welds and abraded areas of shop paint. Paint
exposed areas immediately after erecting hangers and supports. Use same
B.
C.
3.6
A.
B.
Comply with MSS SP-69 for pipe-hanger selections and applications that are
not specified in piping system Sections.
C.
Use hangers and supports with galvanized metallic coatings for piping and
equipment that will not have field-applied finish.
D.
E.
Use carbon-steel pipe hangers and supports metal trapeze pipe hangers
and metal framing systems and attachments for general service applications.
F.
G.
H.
I.
J.
3.
4.
10
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
15.
16.
17.
18.
19.
20.
K.
11
L.
M.
13.
14.
15.
12
N.
O.
6.
7.
8.
P.
Comply with MSS SP-69 for trapeze pipe-hanger selections and applications
that are not specified in piping system Sections.
Q.
R.
END OF SECTION
Villas Z1 & Z2, The Wave, Muscat
13
SECTION 23 05 48
VIBRATION CONTROL FOR HVAC PIPING AND EQUIPMENT
PART 1 - GENERAL
1.1
A.
1.2
A.
RELATED DOCUMENTS
Drawings and general provisions of the Contract, including General and
Supplementary Conditions and Division 01 Specification Sections, apply to
this Section.
SUMMARY
Section includes the following:
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
15.
16.
17.
1.3
Isolation pads.
Isolation mounts.
Restrained elastomeric isolation mounts.
Freestanding and restrained spring isolators.
Housed spring mounts.
Elastomeric hangers.
Spring hangers.
Spring hangers with vertical-limit stops.
Pipe riser resilient supports.
Resilient pipe guides.
Rubber Mount or Hanger
Flexible connector
Restrained vibration isolation roof-curb rails.
Restraining braces and cables.
Steel and inertia, vibration isolation equipment bases.
Noise Level(Internal and External)
Sound Attenuators
DEFINITIONS
A.
B.
1.4
PERFORMANCE REQUIREMENTS
A.
Provide vibration isolation for all mechanical services and plant as described
herein and shown on the drawings.
B.
Where fans with 7.5kw motor and above are mounted at high level, provide
spring type vibration isolation hangers.
C.
Where pumps with 7.5kw motor and above, mount on an inertia base.
D.
Provide spring type vibration isolation with neoprene pad base to all AHU
plant with fan motors equal to and exceed 7.5kw.
E.
All chillers shall be mounted on a sandwich concrete base with a cork mat
insert. All chillers shall be isolated from the concrete base by spring type
vibration isolating supplied by the chiller manufacturer.
F.
Provide flexible connections at inlet and outlet of all fans and AHUs. The
flexible connection shall meet air pressure and temperature specified.
Flexible connections at inlet and outlets of smoke exhaust fans (where
indicated) shall be fire rated to 1 hour in accordance with BS 476 part 24/ISO
6944 (refer to section 233300 for flexible duct details).
G.
H.
I.
J.
Isolate all piping within plant rooms from the structure by means of a spring
hanger isolator. The spring deflection for the 15m of piping from the chillers
and pumps shall have deflection equal to the rotating equipment. Other
support shall have 25mm deflection. Pipes supported off the floating floor
shall have 50mm deflection.
K.
The Contractor shall submit noise level reduction calculation and attenuation
selection to achieve desired space noise level based on actual equipment
selected and shop drawings for approval.
L.
REFRIGERATION
MACHINES
Slab on Grade
Elevated Slab
38
1
3
3
3
5
9
Centrifugal Chiller
PUMPS
In-Line
Under 1.5 kW (2HP)
1.5 kW (2HP) to 11.5 kW
(15HP) Over 11.5 kW (15
Villas Z1 & Z2, The Wave, Muscat
HP)
Base Mounted
Under 5.5. kW (7.5 HP)
5.5 kW (7.5 HP) & greater
5
19
19
38
Notes:
1. Table indicates required static deflection of isolators for all fans
regardless of power rating and for all other motor driven equipment
over 0.37 kW.
2. Advise Acoustical Consultant for equipment not contained in this
table and obtain clarification as to the isolation performance
requirements.
3. Steel spring isolator shall be used for all deflections 12mm and
over.
4. Neoprene isolators shall be used for deflections 6mm and under.
1.5
A.
B.
SUBMITTALS
Product Data: For the following:
1.
Include rated load, rated deflection, and overload capacity for each
vibration isolation device.
2.
3.
Interlocking Snubbers:
combined loads.
2.
3.
Welding certificates.
D.
E.
F.
1.6
QUALITY ASSURANCE
A.
B.
PART 2 - PRODUCTS
2.1
VIBRATION ISOLATORS
A.
B.
C.
Mounts:
Double-deflection type, with molded, oil-resistant rubber,
hermetically sealed compressed fiberglass, or neoprene isolator elements
with factory-drilled, encapsulated top plate for bolting to equipment and with
baseplate for bolting to structure. Color-code or otherwise identify to indicate
capacity range.
1.
2.
D.
7.
8.
9.
E.
2.
3.
4.
5.
6.
7.
8.
F.
G.
1.
2.
3.
4.
5.
6.
7.
H.
2.
3.
4.
5.
6.
7.
8.
I.
J.
K.
L.
N.
2.2
A.
2.
2.
3.
4.
5.
Fluid type: Chilled and hot water (as applicable to each system).
6.
7.
2.
3.
4.
Operating temperature : 5 oC to 50 oC
5.
6.
7.
B.
C.
2.
D.
E.
Water Seal: Galvanized sheet metal with EPDM seals at corners, attached
to upper support frame, extending down past wood nailer of lower support
assembly, and counterflashed over roof materials.
2.3
A.
Steel Bases:
1. Construct structural bases sufficiently rigid to keep deflection and
misalignment within acceptable limits as determined by the equipment
manufacturer, and to transmit design loads to the isolators and
attachment points.
2. Use height saving brackets in all mounting locations to maintain a
nominal 50mm clearance below the base.
3. Bases are to be furnished with built-in motor slide rails. Motor locations
as specified/scheduled.
4. Construct bases strictly in accordance with isolation suppliers drawings.
C.
Floating Floors:
1. Construct in strict accordance with isolation suppliers drawings. Refer to
drawings for construction details.
2. Description: The floating floor shall be panel system consisting of 50mm
thick high density pre-compressed moulded fibre glass isolation pads,
separated by low density acoustical fiberglass. The spacing of the
factory bonded and supported by compressed glass isolation pads shall
be such that uniform deflection of the floor is achieved under a wide
range of loads. Concrete shall be poured over factory bonded plywood
panels. Provide water proofing, isolated floor drains in strict accordance
with the suppliers recommendations.
3. Performance requirement:
Sound Transmission Class of STC-70
(minimum) and impact Insulation Class IIC-59. Submit certificate (from a
reputable laboratory) proving that the specified performance will be
achieved.
2.4
FACTORY FINISHES
A.
B.
Finish: Manufacturer's standard paint applied to factory-assembled and tested equipment before shipping.
1.
2.
3.
4.
2.5
A.
B.
C.
The installer shall advise the main contractor, in writing, of the details of any
item of plant which produces a sound power level greater than 85dB or a
sound pressure level greater than 75dB(A) at 1m. This advice shall be given
four weeks prior to ordering the equipment.
2.6
A.
Provide the products and materials to meet with the performance required
herein.
B.
The attenuators shown on the drawings are the minimum numbers required
to meet the specified noise levels. The specialist supplier shall select noise
control equipment to suit the plant shown on the drawings.
C.
2.7
SOUND ATTENUATOR
A.
B.
C.
The contractor's attention shall be drawn to any instance where the airway
velocity in any attenuators is in excess of 5m/s. Primary and intermediate
silencer face velocity shall not be greater than 5m/s. The transmitted and
10
regenerated noise levels from the silencers to the space shall be below the
space NC level when the cumulative effect of more than one source has
been taken into consideration. The break-out noise level from the silencers
shall be taken into account when carrying out the acoustic analysis.
D.
The absorbent fill shall be constructed so that the exposed surfaces are
bonded or covered to prevent erosion with air stream velocities up to 25m/s.
The fill shall be protected by perforated sheet metal having 50% free area,
galvanised after manufacture.
E.
F.
G.
Angle Iron
Thickness (mm)
.9 Sheet
metal
1.1
Flanges (mm)
Long form
joint
38x38x5
Acoustic splitters shall be rigidly held in place within the attenuator casing,
the attenuating materials shall be as specified elsewhere.
Protection :
1.
2.
Any damaged or soiled attenuators shall be removed from the site and
replaced with factory new equipment, at no additional cost to the
Contract. Site repairs are not acceptable.
3.
Attenuation has been based upon sound power levels shown in the
schedules.
H.
I.
J.
11
2.8
A.
B.
C.
Material: Fibre glass absorber shall be produced from strong resilient glass
fibres, free from shot and coarse fibres and provided in semi-rigid slab with
25mm nominal thickness faced with black vinyl coated fibre glass cloth. The
facing shall be factory bonded to the fibre glass absorber to one side.
D.
E.
125
0.29
250
0.45
500
0.77
1K
1.0
2K
0.93
4K
0.56
PART 3 - EXECUTION
3.1
EXAMINATION
A.
B.
C.
D.
Select isolators for motor driven fans of less than 0.35 Kw for a minimum
static deflection of 3m.
E.
F.
12
G.
H.
Provide adjustable limit stops for spring isolation mounts on equipment with
operating weights substantially different from the installed weights, such as
cooling towers, etc.
3.2
VIBRATION-CONTROL INSTALLATION
A.
B.
C.
D.
Piping Restraints:
1.
2.
3.
E.
F.
G.
H.
I.
Drilled-in Anchors:
1.
2.
13
3.
4.
5.
6.
J.
Wedge Anchors:
Protect threads from damage during anchor
installation. Heavy-duty sleeve anchors shall be installed with sleeve
fully engaged in the structural element to which anchor is to be
fastened.
Adhesive Anchors: Clean holes to remove loose material and drilling
dust prior to installation of adhesive. Place adhesive in holes
proceeding from the bottom of the hole and progressing toward the
surface in such a manner as to avoid introduction of air pockets in the
adhesive.
Set anchors to manufacturer's recommended torque, using a torque
wrench.
Install zinc-coated steel anchors for interior and stainless-steel anchors
for exterior applications.
Bases:
1.
2.
K.
On closed spring isolators, adjust so side stabilisers are clear under normal
operating conditions.
L.
M.
Install the isolators so that they provide the rated vibration isolation after
equipment start-up. Do not attach isolators to equipment o rot structure in a
fashion which impairs their isolation capabilities.
N.
O.
Before bolting isolators to the structure, start equipment and balance the
systems so that the isolators can be adjusted to the correct operating
position before installing drilled inserts.
P.
When spring isolators are used for equipment with operating weights
substantially different from installed weights, block the equipment with
temporary shims to the final heights prior to making piping connections.
When full load is applied, adjust the isolators to take up the load just enough
to allow shim removal.
Q.
R.
14
S.
For all pump installations, ensure that pumps are installed and aligned such
that no piping loads are imposed on the pump. Pumps and piping should be
independently supported and aligned prior to final connection.
T.
U.
3.3
A.
3.4
A.
B.
C.
D.
END OF SECTION
15
SECTION 23 05 53
IDENTIFICATION FOR HVAC PIPING AND EQUIPMENT
PART 1 - GENERAL
1.1
A.
1.2
A.
RELATED DOCUMENTS
Drawings and general provisions of the Contract, including General and
Supplementary Conditions and Division 01 Specification Sections, apply to
this Section.
SUMMARY
Section Includes:
1.
2.
3.
4.
5.
6.
7.
1.3
Equipment labels.
Warning signs and labels.
Pipe labels.
Duct labels.
Stencils.
Valve tags.
Warning tags.
SUBMITTALS
A.
B.
Samples: For color, letter style, and graphic representation required for each
identification material and device.
C.
D.
E.
1.4
COORDINATION
A.
B.
C.
PART 2 - PRODUCTS
2.1
A.
2.2
A.
LANGUAGE
All identification shall be in both Arabic and English
EQUIPMENT LABELS
Metal Labels for Equipment:
1.
2.
3.
4.
5.
B.
2.
3.
4.
5.
6.
7.
8.
C.
Material and Thickness: Aluminum 0.8-mm or anodized aluminum, 0.8mm minimum thickness, and having predrilled or stamped holes for
attachment hardware.
Minimum Label Size: Length and width vary for required label content,
but not less than 64 by 19 mm.
Minimum Letter Size: 6.4 mm for name of units if viewing distance is
less than 600 mm, 13 mm for viewing distances up to 1830 mm, and
proportionately larger lettering for greater viewing distances. Include
secondary lettering two-thirds to three-fourths the size of principal
lettering.
Fasteners: Stainless-steel rivets or self-tapping screws.
Adhesive: Contact-type permanent adhesive, compatible with label and
with substrate.
Label Content:
Include equipment's Drawing designation or unique
equipment number, Drawing numbers where equipment is indicated (plans,
details, and schedules), plus the Specification Section number and title where
equipment is specified.
D.
2.3
A.
B.
C.
D.
E.
Minimum Label Size: Length and width vary for required label content, but not
less than 64 by 19 mm.
F.
Minimum Letter Size: 6.4 mm for name of units if viewing distance is less than
600 mm, 13 mm for viewing distances up to 1830 mm, and proportionately
larger lettering for greater viewing distances. Include secondary lettering twothirds to three-fourths the size of principal lettering.
G.
H.
I.
2.4
PIPE LABELS
A.
General Requirements for Manufactured Pipe Labels: Preprinted, colorcoded, with lettering indicating service, and showing flow direction.
B.
C.
D.
1.
2.
2.5
DUCT LABELS
A.
B.
C.
D.
E.
Minimum Label Size: Length and width vary for required label content, but not
less than 64 by 19 mm.
F.
Minimum Letter Size: 6.4 mm for name of units if viewing distance is less 600
mm, 13 mm for viewing distances up to 1830 mm, and proportionately larger
lettering for greater viewing distances. Include secondary lettering two-thirds
to three-fourths the size of principal lettering.
G.
H.
I.
2.
2.6
A.
STENCILS
Stencils: Prepared with letter sizes according to ASME A13.1 for piping;
minimum letter height of 1-1/4 inches (32 mm) for ducts; and minimum letter
height of 3/4 inch (19 mm) for access panel and door labels, equipment labels,
and similar operational instructions.
1.
2.
3.
2.7
A.
VALVE TAGS
Valve Tags: Stamped or engraved with 6.4-mm letters for piping system
abbreviation and 13-mm numbers.
1.
2.
B.
Valve Schedules: For each piping system, on A4 bond paper. Tabulate valve
number, piping system, system abbreviation (as shown on valve tag), location
of valve (room or space), normal-operating position (open, closed, or
modulating), and variations for identification. Mark valves for emergency
shutoff and similar special uses.
1.
2.8
A.
WARNING TAGS
Warning Tags: Preprinted or partially preprinted, accident-prevention tags, of
plasticized card stock with matte finish suitable for writing.
1.
2.
3.
4.
PART 3 - EXECUTION
3.1
GENERAL
A.
All identification work shall be done after painting work has been completed.
B.
Contractor should follow typical agreed plant labeling system for the entire
development.
C.
D.
Identify air handling units, heat transfer equipment, tanks with stencil painting.
Small devices such as in-line pumps may be identified with tags.
E.
Identify control panels and major control components outside panels with
plastic name plates.
F.
G.
H.
I.
Provide ceiling tucks to locate dumpers above T-bar type panel ceilings.
Locate in corner of panel closest to equipment.
3.2
A.
3.3
PREPARATION
Clean piping and equipment surfaces of substances that could impair bond of
identification devices, including dirt, oil, grease, release agents, and
incompatible primers, paints, and encapsulants.
EQUIPMENT LABEL INSTALLATION
A.
B.
3.4
A.
B.
C.
3.
4.
5.
6.
7.
D.
Chilled-Water Piping:
a.
b.
2.
Condenser-Water Piping:
a.
b.
3.5
A.
B.
Stenciled Duct Label Option: Stenciled labels, showing service and flow
direction, may be provided instead of plastic-laminated duct labels, at
Installer's option, if lettering larger than 25 mm high is needed for proper
identification because of distance from normal location of required
identification.
C.
Locate labels near points where ducts enter into concealed spaces and at
maximum intervals of 15 m in each space where ducts are exposed or
concealed by removable ceiling system.
3.6
VALVE-TAG INSTALLATION
A.
Install tags on valves and control devices in piping systems, except check
valves; valves within factory-fabricated equipment units; shutoff valves;
faucets; convenience and lawn-watering hose connections; and HVAC
terminal devices and similar roughing-in connections of end-use fixtures and
units. List tagged valves in a valve schedule.
B.
3.7
A.
WARNING-TAG INSTALLATION
Write required message on, and attach warning tags to, equipment and other
items where required.
END OF SECTION
SECTION 230593
TESTING, ADJUSTING AND BALANCING FOR HVAC
PART 1 - GENERAL
1.1
A.
1.2
A.
RELATED DOCUMENTS
Drawings and general provisions of the Contract, including General and
Supplementary Conditions and Division 01 Specification Sections, apply to
this Section.
SUMMARY
Section Includes:
1.
1.3
A.
B.
C.
D.
1.4
DEFINITIONS
A.
B.
C.
D.
E.
1.5
SUBMITTALS
A.
B.
C.
D.
E.
F.
1.6
A.
QUALITY ASSURANCE
TAB Contractor Qualifications: Engage a TAB entity certified by AABC and
NEBB or BSRIA.
1.
2.
B.
TAB Conference: Meet with Architect on approval of the TAB strategies and
procedures plan to develop a mutual understanding of the details. Require
the participation of the TAB field supervisor and technicians. Provide 7 days'
advance notice of scheduled meeting time and location.
1.
Agenda Items:
a.
b.
c.
d.
C.
1.
2.
D.
E.
1.7
PROJECT CONDITIONS
A.
Full Owner Occupancy: Owner will occupy the site and existing building
during entire TAB period. Cooperate with Owner during TAB operations to
minimize conflicts with Owner's operations.
B.
1.8
COORDINATION
A.
Notice: Provide 2 days' advance notice for each test. Include scheduled
test dates and times.
B.
Perform TAB after leakage and pressure tests on air and water distribution
systems have been satisfactorily completed.
1.9
The contractor shall involve approved TAB agency during the production of
shop in order to accommodate any provisions required for the
Testing,
Adjusting and Balancing of all the Mechanical systems. The shop drawings
shall be signed by approved TAB agency prior to
submission
to
Engineer for approval.
EXAMINATION
A.
B.
Examine systems for installed balancing devices, such as test ports, gage
cocks, thermometer wells, flow-control devices, balancing valves and fittings,
C.
D.
E.
Examine ceiling plenums and under floor air plenums used for supply, return,
or relief air to verify that they meet the leakage class of connected ducts as
specified in Division 23 Section Metal Ducts and are properly separated from
adjacent areas. Verify that penetrations in plenum walls are sealed and firestopped if required.
F.
2.
G.
Examine system and equipment installations and verify that field qualitycontrol testing, cleaning, and adjusting specified in individual Sections have
been performed.
H.
I.
Examine HVAC equipment and filters and verify that bearings are greased,
belts are aligned and tight, and equipment with functioning controls is ready
for operation.
J.
K.
3.2
PREPARATION
A.
B.
Verify the
1.
2.
3.
4.
5.
6.
7.
3.3
A.
B.
Cut insulation, ducts, pipes, and equipment cabinets for installation of test
probes to the minimum extent necessary for TAB procedures.
1.
2.
3.
After testing and balancing, patch probe holes in ducts with same
material and thickness as used to construct ducts.
After testing and balancing, install test ports and duct access doors that
comply with requirements in Division 23 Section "Air Duct
Accessories."
Install and join new insulation that matches removed materials.
Restore insulation, coverings, vapor barrier, and finish according to
Division 23 Section "HVAC Insulation."
C.
D.
Take and report testing and balancing measurements in metric (SI) units.
3.4
A.
Prepare test reports for both fans and outlets. Obtain manufacturer's outlet
factors and recommended testing procedures. Crosscheck the summation
of required outlet volumes with required fan volumes.
B.
C.
Determine the best locations in main and branch ducts for accurate ductairflow measurements.
D.
Check airflow patterns from the outdoor-air louvers and dampers and the
return- and exhaust-air dampers through the supply-fan discharge and
mixing dampers.
E.
F.
Verify that motor starters are equipped with properly sized thermal
protection.
G.
H.
I.
J.
K.
3.5
A.
2.
b.
c.
d.
3.
Measure static pressure across each component that makes up an airhandling unit, rooftop unit, and other air-handling and -treating
equipment.
a.
4.
5.
6.
7.
B.
Adjust volume dampers for main duct, sub main ducts, and major branch
ducts to indicated airflows within specified tolerances.
1.
2.
3.
C.
D.
Adjust air outlets and inlets for each space to indicated airflows within
specified tolerances of indicated values. Make adjustments using branch
volume dampers rather than extractors and the dampers at air terminals.
1.
2.
3.6
A.
B.
C.
3.7
A.
TOLERANCES
Set HVAC system's air flow rates and water flow rates within the following
tolerances:
1.
2.
3.8
REPORTING
A.
B.
3.9
A.
FINAL REPORT
General: Prepare a certified written report; tabulate and divide the report
into separate sections for tested systems and balanced systems.
1.
2.
B.
C.
Pump curves.
Fan curves.
Manufacturers' test data.
Field test reports prepared by system and equipment installers.
Other information relative to equipment performance; do not include
Shop Drawings and product data.
Title page.
Name and address of the TAB contractor.
Project name.
Project location.
Architect's name and address.
Engineer's name and address.
Contractor's name and address.
Report date.
Signature of TAB supervisor who certifies the report.
Table of Contents with the total number of pages defined for each
section of the report. Number each page in the report.
Summary of contents including the following:
a.
b.
c.
12.
13.
14.
15.
D.
E.
Unit Data:
a.
b.
c.
d.
e.
f.
g.
h.
2.
F.
Unit identification.
Location.
Make and type.
Model number and unit size.
Manufacturer's serial number.
Unit arrangement and class.
Discharge arrangement.
Number, type, and size of filters.
Motor Data:
a.
b.
c.
d.
3.
Fan Data:
10
a.
b.
c.
d.
e.
f.
g.
h.
2.
g.
of
and
amount
of
Report Data:
a.
b.
c.
d.
e.
f.
g.
h.
i.
j.
k.
H.
amount
G.
and
Motor Data:
a.
b.
c.
d.
e.
f.
3.
System identification.
Location.
Make and type.
Model number and size.
Manufacturer's serial number.
Arrangement and class.
Sheave make, size in mm, and bore.
Center-to-center dimensions of sheave,
adjustments in mm.
Air-Terminal-Device Reports:
1.
Unit Data:
11
a.
b.
c.
d.
e.
f.
g.
h.
i.
2.
I.
Report Data:
a.
b.
c.
d.
e.
3.10
INSPECTIONS
A.
Initial Inspection:
1.
2.
After testing and balancing are complete, operate each system and
randomly check measurements to verify that the system is operating
according to the final test and balance readings documented in the final
report.
Check the following for each system:
a.
b.
c.
d.
e.
B.
Final Inspection:
12
1.
2.
3.
4.
5.
C.
TAB Work will be considered defective if it does not pass final inspections. If
TAB Work fails, proceed as follows:
1.
2.
D.
3.11
A.
B.
Seasonal Periods: If initial TAB procedures were not performed during nearpeak summer and winter conditions, perform additional TAB during nearpeak summer and winter conditions.
END OF SECTION
13
SECTION 23 07 00
HVAC INSULATION
PART 1 - GENERAL
1.1
A.
1.2
A.
RELATED DOCUMENTS
Drawings and general provisions of the Contract, including General and
Supplementary Conditions and Division 01 Specification Sections, apply to
this Section.
SUMMARY
Section Includes:
1.
Insulation Materials:
a.
b.
c.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
1.3
SUBMITTALS
A.
B.
Shop Drawings:
1.
2.
3.
Include thermal
HVAC Insulation
Rev: 0
4.
5.
6.
7.
8.
C.
Samples: For each type of insulation and jacket indicated. Identify each
Sample, describing product and intended use.
1.
Sample Sizes:
a.
b.
c.
d.
e.
D.
E.
F.
1.4
QUALITY ASSURANCE
A.
B.
HVAC Insulation
Rev: 0
C.
Piping Mockups:
a.
b.
c.
d.
e.
f.
g.
h.
i.
2.
Ductwork Mockups:
a.
b.
c.
d.
e.
3.
4.
5.
6.
7.
8.
HVAC Insulation
Rev: 0
1.5
A.
1.6
A.
B.
1.7
SCHEDULING
A.
B.
PART 2 - PRODUCTS
2.1
2.2
MATERIALS
A.
Flame/Smoke ratings: Provide composite mechanical insulation with flamespread rating of 25 or less, and smoke-developed rating of 50 or less, as
tested by ANSI/ASTM E 84 (NFPA 255) method or BS 476 Part 4.
B.
C.
Adhesive: Sheet metal adhesive meeting ASTM c916 Type IV, NFPA 90A
and 90B, 25/50 requirements, surface burning characteristics ASTM 84.
Flames spread 10 and smoke developed 25. Fire resistive in dry state.
D.
HVAC Insulation
Rev: 0
Duct Insulation
1. 50-70Kg/m3 density closed cell elastomeric foam insulation sheet
sections cut to suit the ductwork area and specified insulation
thicknesses as detailed below
1.
Thermal conductivity
<0.039 W/mK.
2.
>u5,000.
3.
Fire rating
3.
10
Thermal Conductivity
(W/m K)
Up to
0.020
Minimum Thickness
(mm)
20
20
0.021
Up to
to
0.020
0.040
20
25
35
0.021
to
0.040
Up to
0.020
0.021
to
0.040
25
30
50
HVAC Insulation
Rev: 0
10
Thermal Conductivity
(W/m K)
Up to
0.020
Minimum Thickness
(mm)
25
20
0.021
Up to
to
0.020
0.040
25
35
0.021
to
0.040
Up to
0.020
0.021
to
0.040
30
30
50
25
10
Thermal Conductivity
(W/m K)
Up to
0.020
Minimum Thickness
(mm)
30
20
0.021
Up to
to
0.020
0.040
40
40
35
0.021
to
0.040
Up to
0.020
0.021
to
0.040
50
40
50
<0.034 W/m. K at 0C
3. Fire rating
2.
>u5,000.
HVAC Insulation
Rev: 0
3.
Pipes up to 35 mm 19 mm
O.D
Pipes 42mm-60 mm 25 mm
O.D
Pipes 67mm-140 mm 25 mm
O.D
Pipe dia in mm
Pipes up to 35 mm 32 mm
O.D
Pipes 42mm-60 mm 38 mm
O.D
Pipes 67mm-140 mm 38 mm
O.D
PART 3 - EXECUTION
3.1
A.
EXAMINATION
Examine substrates and conditions for compliance with requirements for
installation and other conditions affecting performance of insulation
application.
1.
2.
3.
HVAC Insulation
Rev: 0
3.2
A.
3.3
PREPARATION
Surface Preparation: Clean and dry surfaces to receive insulation. Remove
materials that will adversely affect insulation application.
GENERAL INSTALLATION REQUIREMENTS
A.
B.
C.
Install accessories compatible with insulation materials and suitable for the
service. Install accessories that do not corrode, soften, or otherwise attack
insulation or jacket in either wet or dry state.
D.
Install insulation with longitudinal seams at top and bottom of horizontal runs.
E.
F.
G.
H.
Install insulation with tight longitudinal seams and end joints. Bond seams
and joints with adhesive recommended by insulation material manufacturer.
I.
J.
3.
4.
HVAC Insulation
Rev: 0
K.
L.
M.
N.
O.
P.
Q.
R.
Finish all insulation smooth. The outline of pipe insulation shall be a true
circular and concentric shape. The outline of fitting insulation shall be
shaped to blend with adjacent covering. All longitudinal and circumferential
and sectional joints shall be sealed with 50mm wide industrial grade selfadhesive PVC tape.
S.
T.
U.
At each hanger or support for chilled water piping, the contractor shall install
a section of high density insulation between the pipe protection saddle and
the pipe. Only the lower half of insulation, at hanger, will be replaced by an
insert of high density material so the top of pipe insulation, and vapour
barrier can be continuous. The high density insulation shall be calcium
silicate or rubber and extend 25mm beyond each end of shield. Seal with
vapour barrier mastic.
Repair joint
HVAC Insulation
Rev: 0
V.
Insulation for diesel or gas engine exhaust pipe and muffler shall be 50mm
(2") thick calcium silicate. Do not insulate expansion bellows. Insulation
shall be protected with 1.0mm aluminium cladding.
W.
X.
Insulate all valves, strainers fittings, etc. to the same standard as adjacent
pipework. Exposed iinsulated valves shall be covered with Stucco cladding
constructed in the form of valve boxes. The cladding shall be 0.7mm thick
aluminium held in place with stainless steel cam-lock fasteners or quick
release catches. Screwed, riveted or other methods of fixing that penetrate
the under-lying insulation are not permitted.
Y.
Z.
Pipework supports should fit around the outside of the insulation. The
insulation at support points should be heavy density, load-bearing preformed
sections made to the same thickness as the adjacent pipe insulation and
extending 50mm each side of the support (minimum 100mm long). The
specified finish should be continuous through the support and joints sealed.
A metal bearing plate, of minimum length 200mm, should be situated
between the insulation and the support to avoid point loading on the
insulation.
Preparation:
10
HVAC Insulation
Rev: 0
Application:
Cut insulation material to required size and apply to interior of duct
and/or plenum with horizontal surfaces overlapping vertical surfaces
and with edges tightly butted together. Insulation shall be applied to the
ductwork with a minimum 90% coverage of adhesive and mechanical
fasteners. Where mechanical fasteners penetrate factory finish and at
all joints, apply a heavy layer of seal coating. On high velocity duct
systems 20.32 m/s to 30.48 m/s apply reinforcing membrane over the
entire insulation surface. Seal off leading edge of insulation to duct
surface with reinforced seal coating.
3.4
A.
2.
3.
b.
c.
d.
e.
3.5
A.
B.
11
HVAC Insulation
Rev: 0
1.
2.
3.
4.
5.
6.
7.
END OF SECTION
12
HVAC Insulation
Rev: 0
SECTION 23 08 00
COMMISSIONING OF HVAC
PART 1 - GENERAL
1.1
A.
1.2
RELATED DOCUMENTS
Drawings and general provisions of the Contract, including General and
Supplementary Conditions and other Division 01 Specification Sections,
apply to this Section.
SUMMARY
A.
B.
Related Sections:
1.
1.3
DEFINITIONS
A.
B.
C.
Engineer:
D.
E.
1.4
A.
1.5
A.
Consultant
ALLOWANCES
Labor, instrumentation, tools, and equipment costs for technicians for the
performance of commissioning testing are covered by the "Schedule of
Allowances" Article in Division 01 Section "Allowances."
UNIT PRICES
Commissioning testing allowance may be adjusted up or down by the "List of
Unit Prices" Article in Division 01 Section "Unit Prices" when actual manhours are computed at the end of commissioning testing.
Commissioning of HVAC
Rev: 0
1.6
CONTRACTOR'S RESPONSIBILITIES
A.
B.
C.
D.
E.
F.
Provide measuring instruments and logging devices to record test data, and
provide data acquisition equipment to record data for the complete range of
testing for the required test period.
1.7
CS RESPONSIBILITIES
A.
B.
C.
D.
1.8
A.
COMMISSIONING DOCUMENTATION
Provide the following information to the CS for inclusion in the
commissioning plan:
1.
2.
3.
4.
5.
6.
7.
8.
Plan for delivery and review of submittals, systems manuals, and other
documents and reports.
Identification of installed systems, assemblies, equipment, and
components including design changes that occurred during the
construction phase.
Process and schedule for completing construction checklists and
manufacturer's prestart and startup checklists for HVAC&R systems,
assemblies, equipment, and components to be verified and tested.
Certificate of completion certifying that installation, prestart checks, and
startup procedures have been completed.
Certificate of readiness certifying that HVAC&R systems, subsystems,
equipment, and associated controls are ready for testing.
Test and inspection reports and certificates.
Corrective action documents.
Verification of testing, adjusting, and balancing reports.
Commissioning of HVAC
Rev: 0
1.9
SUBMITTALS
A.
Certificates of readiness.
B.
TESTING PREPARATION
A.
B.
C.
D.
E.
Inspect and verify the position of each device and interlock identified on
checklists.
F.
Check safety cutouts, alarms and interlocks with smoke control and lifesafety systems during each mode of operation.
G.
3.2
A.
3.3
A.
B.
Notify the CS at least 10 days in advance of testing and balancing work, and
provide access for the CS to witness testing and balancing Work.
Commissioning of HVAC
Rev: 0
C.
2.
3.
4.
3.4
A.
B.
C.
D.
E.
F.
G.
The CS may direct that set points be altered when simulating conditions is
not practical.
H.
The CS may direct that sensor values be altered with a signal generator
when design or simulating conditions and altering set points are not
practical.
Commissioning of HVAC
Rev: 0
I.
J.
3.5
HVAC&R SYSTEMS,
PROCEDURES
SUBSYSTEMS,
AND
EQUIPMENT
TESTING
A.
B.
2.
3.
4.
C.
D.
E.
Commissioning of HVAC
Rev: 0
SECTION 23 23 00
REFRIGERANT PIPING
GENERAL
1.1
RELATED DOCUMENTS
Drawings and general provisions of the Contract, including General and
Supplementary Conditions and Division 01 Specification Sections, apply to
this Section.
1.2
SUMMARY
This Section includes refrigerant piping used for air-conditioning applications.
1.1
SUBMITTALS
A.
Product Data: Product data on pipe materials, pipe fittings and accessories.
Provide manufacturers catalogue information and factory Mill Certificates.
B.
C.
D.
1.2
QUALITY ASSURANCE
A.
B.
Refrigerant Piping
Rev: 0
1.3
PRODUCTS
2.1
A.
Application
Fittings
Joint
Installation
Pressure Test
:
:
:
:
:
Refrigerant systems
Capillary fittings complying to BS 2871, Part 2.
Brazing.
Follow manufacturers recommendations
Two times working pressure of system
C.
D.
2.2
A.
REFRIGERANTS
The refrigerant shall comply requirements for both local regulation and
international standard codes.
EXECUTION
3.1
PIPING INSTALLATION
A.
B.
C.
Refrigerant Piping
Rev: 0
D.
E.
Install piping above accessible ceilings to allow sufficient space for ceiling
panel removal.
F.
G.
H.
I.
J.
K.
L.
M.
N.
O.
P.
Q.
R.
Install piping with adequate clearance between pipe and adjacent walls and
hangers or between pipes for insulation installation.
S.
T.
Refrigerant Piping
Rev: 0
U.
3.2
A.
B.
3.3
A.
B.
3.
3.4
A.
SYSTEM CHARGING
Charge system using the following procedures:
1.
2.
3.
4.
Install core in filter dryers after leak test but before evacuation.
Evacuate entire refrigerant system with a vacuum pump to 500
micrometers (67 Pa). If vacuum holds for 12 hours, system is ready for
charging.
Break vacuum with refrigerant gas, allowing pressure to build up to 2
psig (14 kPa).
Charge system with a new filter-dryer core in charging line.
Refrigerant Piping
Rev: 0
3.5
ADJUSTING
A.
B.
C.
D.
E.
F.
Replace core of replaceable filter dryer after system has been adjusted and
after design flow rates and pressures are established.
END OF SECTION
Refrigerant Piping
Rev: 0
SECTION 23 05 13
COMMON MOTOR REQUIREMENTS FOR HVAC EQUIPMENT
PART 1 - GENERAL
1.1
A.
1.2
A.
1.3
A.
RELATED DOCUMENTS
Drawings and general provisions of the Contract, including General and
Supplementary Conditions and Division 01 Specification Sections, apply to
this Section.
SUMMARY
Section includes general requirements for single-phase and polyphase,
general-purpose, horizontal, small and medium, squirrel-cage induction
motors for use on ac power systems up to 600 V and installed at equipment
manufacturer's factory or shipped separately by equipment manufacturer for
field installation.
COORDINATION
Coordinate features of motors, installed units, and accessory devices to be
compatible with the following:
1.
2.
3.
4.
1.4
Motor controllers.
Torque, speed, and horsepower requirements of the load.
Ratings and characteristics of supply circuit and required control
sequence.
Ambient and environmental conditions of installation location.
GENERAL REQUIREMENTS
A.
B.
C.
D.
E.
F.
G.
Keys: Ensure motors and drives are supplied complete with keys and
keyways.
PART 2 - PRODUCTS
2.1
A.
B.
C.
2.2
MOTOR CHARACTERISTICS
A.
B.
2.3
POLYPHASE MOTORS
A.
B.
C.
D.
For motors with 2:1 speed ratio, consequent pole, single winding.
For motors with other than 2:1 speed ratio, separate winding for each
speed.
E.
F.
G.
H.
I.
Insulation: Class F.
J.
K.
2.4
starting
Enclosure Material: Cast iron for motor frame sizes 324T and larger; rolled
steel for motor frame sizes smaller than 324T.
POLYPHASE MOTORS WITH ADDITIONAL REQUIREMENTS
A.
B.
2.
3.
4.
C.
2.5
Windings:
Copper magnet wire with moisture-resistant insulation
varnish, designed and tested to resist transient spikes, high frequencies,
and short time rise pulses produced by pulse-width modulated inverters.
Energy-and Premium-Efficient Motors:
Class B temperature rise;
Class F insulation.
Inverter-Duty Motors: Class B temperature rise; Class F insulation.
Thermal Protection: Comply with NEMA MG 1/IEC requirements for
thermally protected motors.
Severe-Duty Motors:
factor.
A.
Motor rating up to and including 0.75 kW: Provide starter with manual reset,
adjustable, inverse time delay, and ambient temperature compensated
thermal over current release to Bs 4941. Ensure over current release is
compatible with starting, accelerating and running characteristics of motor,
starter and driven machine combination. Use phase unbalance protection on
three phase equipment.
B.
Motor rating above 0.75 kW: Provide starter with sensitive discriminating
thermal magnetic over current relay with precise time/current characteristics
to BS142. Protect motor against effects of sustained and cyclic over current,
out of balance phase current, stalled condition and earth faults. Use running
load indication type overcurrent relays with accuracy of setting and indication
within plus or minus 3 per cent, expressed as a percentage of setting
indicated.
C.
D.
E.
F.
For motor rating 0.75 kW and above fit two thermistors embedded in each
phase of stator windings.
G.
H.
I.
2.6
MOTORS STARTERS
A.
B.
C.
MOTOR STARTERS SOFT STARTER TYPE: Use soft starters with three
phase motors above 3.75 kW. For details refer specification Section 262300.
D.
2.7
INDIRECT DRIVES
A.
Belts
B.
Pulleys
C.
Pulley
Adjustment :
2.8
A.
B.
C.
Mount motors on a substantial mild steel bed plate fixed to machine casing:
*
*
Separately supported.
Supported entirely from the machine casing.
D.
GUARDS: Totally protect drives and couplings. Fit around all exposed or
otherwise accessible drive shafts, pulleys, V belts or couplings, purpose
made guards.
E.
Ensure guards comply with National or Local Safety Codes, Acts and Bye
Laws and incorporate following features:
1. Construction to BS 5304 and generally of galvanized steel wire mesh.
2. Stiffening within the guards to ensure rigidity and freedom from vibration.
3. Allowance for prime mover adjustment during belt tensioning procedures.
4. Temporary access of all shafts for use of Tachometer.
2.9
A.
SINGLE-PHASE MOTORS
Motors larger than 1/20 hp shall be one of the following, to suit starting torque
and requirements of specific motor application:
1.
2.
3.
4.
Permanent-split capacitor.
Split phase.
Capacitor start, inductor run.
Capacitor start, capacitor run.
B.
C.
D.
E.
PART 3 - EXECUTION
Refer to the Mechanical Equipment Manufacturers details.
END OF SECTION
SECTION 23 33 00
AIR DUCT ACCESSORIES
PART 1 - GENERAL
1.1
A.
1.2
A.
B.
RELATED DOCUMENTS
Drawings and general provisions of the Contract, including General and
Supplementary Conditions and Division 01 Specification Sections, apply to
this Section.
SUMMARY
Section Includes:
1.
2.
Back-draft dampers
3.
4.
5.
6.
7.
Motorised dampers.
8.
9.
Related Sections:
1.
1.3
SUBMITTALS
A.
B.
clearances; and method of field assembly into duct systems and other
construction. Include the following:
a.
b.
c.
d.
e.
C.
1.4
Special fittings.
Manual volume damper installations.
Control damper installations.
Fire-damper and smoke-damper installations, including sleeves;
and duct-mounted access doors.
Wiring Diagrams: For power, signal, and control wiring.
A.
B.
PART 2 - PRODUCT
2.1
A.
General: Air turning devices shall be fitted to all rectangular ductwork bends,
Tee bends and where it is regarded necessary to reduce air flow turbulence
and air generated noise. Refer to Standard Detail drawing.
B.
2.2
BACK-DRAFT DAMPERS
A.
In general, provide gravity Back-Draft Dampers for all exhaust fans. Provide
motorised dampers for all fresh air intake fans unless shown otherwise on
drawings.
B.
2.3
A.
200 x 200 mm for hand access. 450 x 450 mm size for shoulder access, and
as indicated. Provide 100 x 100 mm for balancing dampers only. Review
locations prior to fabrication.
Construction: Fabricate in accordance with SMACNA or DW 144. Door shall be
constructed from galvanised sheet steel double walled with 25 mm thick
mineral wool insulation. Each door shall be supplied with galvanised sheet
metal frame, gasket and self tightening rotating camlocks, 2 per unit up to
350mm or 4 per unit on larger sizes. Access doors with sheet metal screw
fasteners shall be rejected. Access doors for kitchen duct shall be stainless
steel.
2.4
A.
B.
Permanent Test Holes: Factory fabricated, air tight flange fittings with screw
cap. Provide extended neck fittings to clear insulation.
2.5
A.
B.
C.
2.
Material:
3.
Insulation :
4.
Installation
length:
5.
Joints:
6.
Code
Compliance :
Flexible Ducts Connection between plant (Fans AHUs). and Duct work.
1.
Type:
2.6
2.
Performance:
3.
Length:
200 mm maximum.
4.
Joints:
5.
Supports:
A.
B.
2.7
A.
B.
Control shaft shall be constructed from 13mm diameter zinc plated steel and
shall be mounted in bronze bushing.
C.
D.
Provide lockable hand quadrant for manual operation with position indication.
E.
The dampers shall be suitable for the operating pressure of the ductwork
system.
F.
2.8
A.
B.
Comply with local and/or Royal Oman Police Directorate of Civil Defense
regulations.
C.
D.
2.9
FIRE DAMPER
A.
B.
Comply with local and/or Royal Oman Police Directorate of Civil Defense
regulations.
C.
D.
Type: Curtain shutter type suitable for high velocity systems. Fire tested to
BS 476 Part 20: 1987, 2 hour rating. Provide access doors adjacent each
fire damper.
E.
F.
Shutter: Blade housing shall be outside of the air stream. Provide hinged
blades to allow for resetting the feasible link.
G.
Materials
2.10
:
:
:
:
:
:
:
A.
Sealant :
B.
PART 3 - EXECUTION
3.1
INSTALLATION
A.
B.
C.
D.
E.
F.
3.2
A.
Where a Duct assembly penetrates a fire rated floor or wall assembly, firestop the resulting opening around the ventilation duct assembly in
accordance with BS 476: Part 24 or ANSI/UL 1479 (F & T rating).
FIELD QUALITY CONTROL
Tests and Inspections:
1.
2.
3.
4.
END OF SECTION
SECTION 233413
AXIAL HVAC FANS
PART 1 - GENERAL
1.1
A.
1.2
A.
RELATED DOCUMENTS
Drawings and general provisions of the Contract, including General and
Supplementary Conditions and Division 01 Specification Sections, apply to
this Section.
SUMMARY
This Section includes the following:
1.
2.
3.
4.
5.
6.
1.3
A.
SUBMITTALS
Product Data: Include rated capacities, furnished specialties, and
accessories for each type of product indicated and include the following:
1.
2.
3.
4.
5.
6.
B.
Axial fans.
Vane axial fan.
Mixed-flow fans
Smoke exhaust fan.
Domestic axial fan.
Bifurcated kitchen exhaust fans.
3.
C.
D.
E.
1.4
QUALITY ASSURANCE
A.
B.
C.
NEMA Compliance:
NEMA standards.
1.5
A.
B.
C.
1.6
COORDINATION
A.
B.
C.
1.7
A.
WARRANTY
Provide 2 years manufacturers warranty starting from date of fan
commissioning.
1.8
A.
SPARE PARTS
Spare parts shall be recommended by manufacturer and supplied by
contractor for two years operation, but not limited to the following.
1.
Fan motor: One set fan motor for each rated KW/frame size.
2.
Fan belt: One set V-belt for each model with belt driven arrangement.
PART 2 - PRODUCTS
2.1
GENERALLY
A.
B.
C.
2.2
AXIAL FANS
A.
General: Axial fan shall be direct driven with motor located downstream.
Fitted with inlet and outlet flanges.
B.
C.
2.3
VANEAXIAL FANS
A.
General:
Vane axial fan shall be direct driven with motor located
downstream. Fitted with inlet and outlet flanges. Blades shall be control
variable pitch. The pitch shall vary while the fan is running utilising DDC
controller. Refer to Schedule of equipment for performance requirements.
B.
C.
2.4
MIXED-FLOW FANS
A.
General: Fan shall be square section case direct driven with motor located
downstream. Fitted with inlet and outlet flanges. Removable access panel for
cleaning and inspection. Refer to Schedule of equipment for performance
details and requirements.
B.
C.
2.5
A.
General: The filtered roof supply fan shall be roof curb mounted, belt driven,
double width, forwarded curved steels and suitable for high temperature
operation. Fitted with louvered penthouse hood raised above roof level on an
integral curb cap base and hood features a hinged insulated aluminium
cover for quick access to the motor and drive assembly. Refer to Schedule
of equipment for performance details and requirements.
B.
2.6
A.
General: Fan shall be duct or roof mounted directly driven and suitable for
high temperature operation, emergency use with Class "H" motor, 200 deg.
C, 2 hour fire rating and meet ROP Oman Civil defense authority
requirements. Fitted with inlet and outlet flanges. Refer to Schedule of
equipment for performance details and requirements.
B.
C.
D.
Roof cowl: where applicable provide roof cowl suitable for smoke ventilation
incorporating air operated shutters to allow for vertical discharge. The
shutters when in closed position shall provide sealed weatherproofing.
E.
F.
Fan shall be UL listed for smoke applications and shall meet Royal Oman
Police Directorate of Civil Defense requirement.
2.7
A.
General: Duct or wall mounted fan suitable for small duty. Refer to Schedule
of equipment.
B.
2.8
A.
B.
Casing: Long type complete with motor mounted electrical terminal box, shall
be constructed from spun steel with galvanized finish suitable against
corrosive fluids. Fit with inlet and outlet flanges of quick fit type.
C.
Impeller: Aerofoil type with disc cast aluminium hub and cast aluminium
bales. Assemble impellers using plated set screws and self locking units.
D.
E.
2.9
STARTERS
A.
B.
2.10
MOTORS
A.
Totally enclosed and protected to IP55, sealed for life bearing and have
thermal overload protection. Comply with BS 5000.
B.
Insulation: Class E to 0.015 kW, Class F for motors greater than 0.015 kW,
Class H for electrical room extractor high temperature application.
C.
2.11
ANCILLARIES
A.
B.
PART 3 - EXECUTION
3.1
INSTALLATION
A.
B.
C.
Install fans as specified, with resilient mountings and flexible electrical leads.
Refer to Section 230548.
D.
E.
F.
G.
H.
I.
Fit air tight inspection doors giving access to drive motors and other
components requiring regular servicing or maintenance on all axial or
centrifugal fans.
J.
Provide control wiring from points of supply and include wiring for complete
operation of fans, including wiring to and from sensors, controllers, Building
Management Systems and Mechanical Panels.
K.
L.
3.2
A.
CONNECTIONS
Duct installation and connection requirements are specified in other
Division 23 Sections. Drawings indicate general arrangement of ducts and
duct accessories. Make final duct connections with flexible connectors.
C.
3.3
A.
3.
4.
5.
6.
7.
8.
9.
10.
B.
3.4
Test and adjust controls and safeties. Replace damaged and malfunctioning
controls and equipment.
ADJUSTING
A.
B.
Lubricate bearings.
END OF SECTION
SECTION 23 37 13
DIFFUSERS, REGISTERS AND GRILLES
PART 1 - GENERAL
1.1
A.
1.2
A.
RELATED DOCUMENTS
Drawings and general provisions of the Contract, including General and
Supplementary Conditions and Division 01 Specification Sections, apply to
this Section.
SUMMARY
Section Includes:
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
B.
Related Sections:
1.
2.
1.3
A.
SUBMITTALS
Product Data: For each type of product indicated, include the following:
1.
2.
B.
Samples for Initial Selection: For diffusers, registers, and grilles with factoryapplied color finishes.
Rev: 0
C.
D.
E.
1.4
A.
Test and rate air outlet and inlet performance in accordance with ADC 1062
and ASHRAE 70.
B.
1.5
A.
PERFORMANCE
Select diffusers to ensure space noise levels less than NC 30 in office
spaces and general areas and NC 20 in auditorium. Select diffuser to ensure
air flow velocity between 0.25 and 0.5 m/s and end of throw distance.
Establish throw distances from drawings.
PART 2 - PRODUCTS
2.1
2.2
Application
2.
Material
: Aluminium
3.
Finish
4.
Mounting
: Duct connection.
5.
Pattern
: Fully adjustable.
6.
Dampers
Application
2.
Type
4 core
Rev: 0
2.3
2.4
2.5
3.
Material
Aluminium
4.
Finish
5.
Mounting
Duct connection.
6.
Pattern
Fully adjustable.
Material
Aluminum.
2.
Finish
3.
Type
right,
4.
Slot Width
19 mm.
5.
Fabrication
6.
Frame
7.
Plenum
8.
Refer to reflected ceiling plan drawings for extent and exact location of
diffusers.
9.
Liaise with ceiling manufacturer and provide opening details and type
of fixings to ensure complete compatibility. Contractor to supply
materials. Fixing and support by others.
Application
2.
Type
thickness
3.
Material
Aluminium.
4.
Finish
5.
Frame
6.
Plenum
Application
Rev: 0
2.6
2.7
2.8
2.
Type
thickness
3.
Material
Aluminium.
4.
Finish
5.
Frame
6.
Plenum
:
control damper.
EXHAUST VALVE
1.
Application
2.
Type
3.
Fabrication
4.
Accessories
per
DOOR GRILLE
1.
Application
Air Transfer.
2.
Type
3.
Fabrication
4.
Accessories
JET DIFFUSERS
1.
Application
shown
2.
3.
4.
Material
Rev: 0
2.9
2.10
A.
2.12
2.13
LOUVERS
A.
For fresh air intake and exhaust. All aluminium construction with 2 inches
deep fixed horizontal blades (vanes). Provide a steel opposed blade damper.
Baked enamel finish. Provide sand trap for fresh air intake louver.
B.
For return air (ceiling and sidewall applications), the same as 2.13 A, except
no damper.
2.14
SWIRL DIFFUSERS
Swirl diffusers shall be variable air pattern capable of providing both horizontal
and vertical discharge. They shall comprise an outer tube casing and inner
tube assembly in a circular format. The outer casing shall incorporate a set of
fixed vanes and the adjustable inner tube with a central regulating vane to
vary the flow of air. Regulation of the inner vanes shall vary throw discharges
from fully horizontal to vertical projection. Swirl diffusers shall be provided with
factory fabricated sound attenuating plenum boxes with spigot dampers and
mating flanges. Swirl diffusers shall be constructed from polyester coated
steel. Swirl diffuser selections shall be made by the manufacturer to achieve
the required airflow distribution patterns and acoustical performance. Fixed
vane angle to be calculated based on airflow pattern and ceiling height.
Agreed angle to be set at factory.
2.15
PLENUM BOXES
Plenum boxes constructed of Galvanized steel sheet, shall be provided for
all supply air outlets. Plenum boxes shall be acoustically lined and
incorporate hidden fixings to support the diffuser. Plenum boxes shall be
factory constructed.
Rev: 0
PART 3 - EXECUTION
3.1
EXAMINATION
A.
Examine areas where diffusers, registers, and grilles are to be installed for
compliance with requirements for installation tolerances and other conditions
affecting performance of equipment.
B.
3.2
INSTALLATION
A.
B.
C.
Install diffusers, registers, and grilles with airtight connections to ducts and to
allow service and maintenance of dampers, air extractors, and fire dampers.
3.3
A.
ADJUSTING
After installation, adjust diffusers, registers, and grilles to air patterns
indicated, or as directed, before starting air balancing.
END OF SECTION
Rev: 0
SECTION 230900
Air-Cooled VRV High Ambient System Specification
1
GENERAL
The Air Conditioning Contractor shall supply, deliver, install, set to work and
commission the systems and equipment as detailed in this section of the
specification, as shown on the Tender drawings and listed in the Schedule at the end
of this section.
DESCRIPTION OF WORKS
Heating and Cooling is to be provided by utilising the Reverse cycle Air-cooled VRV
modular systems comprising a number of external condensing units connected via
refrigerant pipework to internal direct expansion fan coil units
2.1
FEATURES
The VRV system will control flow of refrigerant through the fan coil units, by means of
an electronic expansion valve fitted in each indoor unit.The system will be capable of
cooling with external ambient temperatures from 5oC to +52oC and providing
heating with ambient temperatures down to 20oC.The equipment manufacturer shall
be responsible for the manufacture of the compressor, refrigerant oil and refrigerant
used within the system to maintain integrity of design and optimise efficiency and
reliability of equipment.
The VRV system will have the ability to sustain refrigerant piping lengths of up to
165m with a level difference up to 50m between fan coil units and condensing unit if
the outdoor unit is located above the highest level indoor unit. An option shall be
available to increase the level difference of the pipe work to 90m between fan coil
units and condensing unit if the outdoor unit is located above the lowest level indoor
unit.
Each independent system shall be capable of having up to 1000m of refrigerant pipe
work installed. The system shall be capable of having up to 90m refrigerant pipe
length from the first refnet joint to the furthest indoor unit, after incorporating relevant
system design guidelines.
The VRV system shall operate with Refrigerant R410A, the refrigerant shall be a
zeotropic blend constituted of a maximum of two different refrigerants providing a
maximum temperature glide of less than 0.17K to avoid fractionation problems.
The equipment manufacturer shall be fully certified and registered to comply in the
areas of CE, Eurovent, ISO9001 and ISO14001.
All equipment shall be run tested in accordance with the following procedures prior to
Villas Z1 & Z2, The Wave, Muscat
VRV System
Rev: 0
2.2
OUTDOOR UNITS
The units shall be air-cooled type incorporating coils manufactured from copper tubes
and aluminium fins, factory treated to reduce the effect of atmospheric corrosion. The
unit casing shall be manufactured from polyester powder coated baked enamel finish
sheet steel in order to have a high corrosion resistance and to protect against salt
laden environment close to where the units may be installed. The air outlet shall
have plastic coated wire guards. The condenser coils shall be coated with an
anticorrosion coating to withstand the harsh salty environment. The coil assembly
shall be post coated with Blygold to at least 30 mm micron thickness. A spray on
application method shall be employed for full penetration.
The outdoor units shall have inverter driven compressor (Variable Frequency Drive
Compressors Scroll Compressors Only), electronically controlled and capable of
changing speed linearly to follow the variation in cooling or heating requirements.
The compressor shall be scroll type with fixed and orbiting scrolls. The low pressure
refrigerant shall be fed directly into the scroll and the discharge refrigerant shall cool
the motor windings and place the compressor shell under discharge pressure.
The lubrication oil of the compressor shall be fed through the centre of the crankshaft
and then across the complete area of the scrolls from the centre outwards to ensure
the complete contact area is positively lubricated maximising compressor efficiency
and minimising wear and tear.
The outdoor unit fan motor will be inverter driven and shall operate electronically by
sensing operational temperatures, pressures and ambient temperature and
monitoring the dictates of the indoor units.
The units shall be complete with VFD compressor, electronic expansion valve(s), oil
separator(s), suction accumulator, high pressure switches, inverter driven fan motors,
safety thermostat, over current relay, inverter overload protection, fuses, necessary
Villas Z1 & Z2, The Wave, Muscat
VRV System
Rev: 0
solenoid valves, liquid shutoff valves, gas line shut off valves, short re-cycling guard
timer and all necessary sensors for optimized, safe and trouble free operation.
The access to the internal components for maintenance purposes shall be by
removable panels.
It shall be possible to connect multiple indoor units.
The 8HP unit shall have a single inverter driven scroll compressor and an inverter
driven variable speed propeller type fan.
The 10 and 12 HP units shall have two off scroll compressors, one inverter and one
fixed speed and will be capable of operating on one compressor under emergency
condition in case the inverter compressor fails.
One compressor shall be inverter driven capable of Soft start. The other
compressor(s) shall be on/off type. These units will incorporate inverter driven
variable speed propeller type fan(s).
The fan will be capable of overcoming a minimum of 50 Pascal of external static
pressure.
The units shall be capable of being combined to provide multi systems using
combinations of two or three outdoor units connected to give the capability of higher
capacities
All refrigerant connections both internal within the unit and the external connections
to the indoor units shall be brazed on the outdoor unit.
The unit shall be capable of carrying out automatically the calculated required
additional refrigerant charge necessary to operate the system within its optimum
efficiency. This cycle shall be completely automatic and provide a warning to the
service technician to indicate when charging has been completed or the charging
cylinder is empty.
The calculated refrigerant charge shall be retained within the memory of the outdoor
PCB as a reference for a refrigerant containment check which can be carried out as
required to verify the correct refrigerant charge remains within the system.
The automatic refrigerant charging and containment check facilities shall be capable
of being used at any time during the life of the system for any alterations or service
operations which may be required.
2.3
2.3.1
INDOOR UNITS
Ducted type
The unit casing shall be manufactured from galvanised steel plate and shall be fully
insulated. The use of a polystyrene only construction for the outer casing will not be
Villas Z1 & Z2, The Wave, Muscat
VRV System
Rev: 0
acceptable.
standard.
The return air to the unit shall be through the back of the unit as
The fan shall be of the dual suction multi blade type, statically and dynamically
balanced to ensure low noise and vibration free operation.
The cooling coils shall be manufactured from copper tubes and aluminium fins. It
shall have electronic expansion valve to control refrigerant flow rate in response to
the load variation in the conditioned space. The expansion valve shall be controlled
by an integral computerised PID control system to maintain correct room
temperature. The condensate shall be drained from the unit to the nearest drain by
way of insulated drain piping with traps.
2.3.2
The unit casing shall be manufactured from galvanised steel plate and shall be fully
insulated. The use of a polystyrene only construction for the outer casing will not be
acceptable. Contractor at site shall provide Sand trap louver , prefilters and bag
filters.
The unit shall deliver the scheduled air flows and shall be connected to VRV outdoor
unit. The set point for supply air shall be as per schedule.
The fan shall be of the dual suction multi blade type, statically and dynamically
balanced to ensure low noise and vibration free operation.
The cooling coils shall be manufactured from copper tubes and aluminium fins. It
shall have electronic expansion valve to control refrigerant flow rate in response to
the load variation in the conditioned space. The expansion valve shall be controlled
by an integral computerised PID control system to maintain correct room
temperature.
The condensate shall be drained from the unit to the nearest drain.
3
ANCILLARY ITEMS
Joints and headers shall be used throughout the installation to reduce imbalance in
refrigerant flow between indoor units. Sizes to be suggested and approved by the
VRV manufacturer.
CONTROLS
Mains Power Wiring shall be the responsibility of the Electrical Contractor who shall
provide
3-phase 400V main isolators mounted on the VRV Condensing Units
and a 1-phase 230V fused spur located within 1m of fan coil units.
Controls wiring shall be the responsibility of the Air Conditioning Contractor who shall
provide system control wiring in accordance with the manufacturers
VRV System
Rev: 0
recommendations.
4.1
Controller
Each indoor unit shall have its own thermostat that will allow temperature and speed
control.
Local control shall be provided by remote controllers mounted within the occupied
space, providing individual start/stop, run/fail indication, set point adjustment and fault
code diagnosis. Time Clock control shall be flexible with seven independent day
settings, five actions per day of ON or OFF which can be can be configured in any
desired pattern. The controller shall contain an internal temperature sensor, which
can be used for system control. The controller shall have the ability to be locked
down without the need of any other external adapter PCB or Centralised device to
leave only the following functions operable:
5
REFRIGERANT PIPEWORK
The interconnecting refrigerant piping shall be manufactured from seamless quality
phosphorous dioxide soft/medium drawn copper to BS2781 Part II ASTM, DIN
1754/8905, fully tested by the eddy current method, dehydrated and capped.
The copper tubing shall be of a suitable thickness to be capable of withstanding
pressure test as detailed in the current revision of BS/EN378.
The copper tubing shall be suitably selected with a wall thickness capable of
withstanding the system operating pressures on Refrigerant R410A, all as described
within the outdoor units installation manual.
Pipework shall be supported and secured at regular intervals not exceeding 1.5m.
Preferably to create a method of adequate support ant containment, piping should be
laid on suitably supported galvanised cable tray, insulated and held in position with
plastic coated steel banding. Due care and attention shall be taken at all times to
allow pipework to expand and contract naturally.
5.1
Insulation
All Refrigerant pipework to be insulated with slip-on close cell elastomeric pipe
insulation, with a fire performance rating class O of the 1985 Building Regulations,
having a wall thickness of not less than 19mm. After commissioning, all joints to be
properly sealed to provide and adequate seal and clearly marked for ease of
identification.
Where required external insulation shall be protected with a suitable enclosure to
encase the piping, as to reduce the effects of Bird, Vermin and Environmental attack.
VRV System
Rev: 0
5.2
CONDENSATE PIPEWORK
Condensate pipework shall be installed by the suppliers approved Installer in
accordance with suppliers Design and Installation Instructions and the units
installation manual.
VRV System
Rev: 0
END OF SECTION
VRV System
Rev: 0
SECTION 237200
AIR-TO-AIR ENERGY RECOVERY EQUIPMENT
GENERAL
1.1
SUMMARY
SUBMITTALS
CLOSEOUT SUBMITTALS
1.
2.
1.4
Warranties.
Operation and Maintenance (O+M) Manuals: Include component list with
manufacturer's reference numbers, descriptions of materials and
procedures for repairing and cleaning of finishes and cleaning frequency.
QUALITY ASSURANCE
PRODUCTS
2.1
GENERAL
A. The Work of this Section includes design of energy recovery units and
components required for system installations.
B. Capacity scheduled on the Design Drawings is based on standard air
conditions. Provide capacity as scheduled on the Design Drawings.
C. This Section relates to the remaining sections of Division 23 Heating,
Ventilating and Air Conditioning (HVAC).
D. Provide complete energy recovery units on the basis of rotating heat
exchangers which is working according to the air-air principle (heat wheels) and
achieving the scope of work indicated in the Contract Documents.
2.2
PRODUCT SPECIFICATION
2.2.1
THERMAL WHEEL
A.
B.
C.
D.
Motor: Motor and drive assembly mounted on common base inside unit with
slide rails for belt adjustment.
E.
The media shall be cleanable with compressed air or light detergent without
degrading the latent recovery.
F.
Thermal efficiency: Minimum 75% overall (i.e. sensible and latent gain)
when wheel has been in operation allowing for fouling, with equal sensible
and latent heat recovery.
2.2.2
A.
B.
C.
D.
Efficiency: Not less than 75% (sensible) after 5 year in operation (maximum
fouling).
E.
F.
G.
H.
2.2.3
HEAT PIPE
A. Heat pipes shall be included within the Energy Recovery Unit and wrapped
around the main cooling coil. The external fins shall be of aluminium with a
minimum thickness of 0.15mm. Fins shall be of the continuous plate type and
louvered type.
B. Tubes shall be of refrigeration standard seamless copper C106 for heat
exchanger use. Tube diameter shall be 12mm with a grooved inner surface
and minimum root thickness of the tube shall be 0.35mm.
EXECUTION
3.1
EXAMINATION
3.2
INSTALLATION
A. General
1.
Comply with manufacturer's requirements for the installation of any
equipment.
2.
Locate equipment as indicated on the Design Drawings to provide best
possible connection arrangement and accessibility for maintenance and
servicing. Provide clearances on all sides of equipment as required by
Authorities having jurisdiction or manufacturer, whichever is greater.
3.
Install items of equipment with due regard to Architectural treatment and
ensure all items are level and finished in keeping with good workmanship.
B. Heat Recovery Units Installation
1.
Install heat recovery units where indicated, in accordance with
equipment manufacturer's published installation instructions and with
recognized industry practices, to ensure that units comply with
requirements and serve intended purposes.
2.
3.
4.
5.
6.
7.
C. Equipment Start-Up
1.
Follow
manufacturer's
instructions
and
have
manufacturer's
representative present to certify the installation.
2.
Check each item of equipment to ensure proper electrical connections,
etc. and to verify proper operation.
3.
Upon completion of installation of equipment start-up, operate equipment
to demonstrate capability and compliance with requirements. Field correct
malfunctioning units, then re-test to demonstrate compliance.
4.
Check, verify and demonstrate remote signals operation.
Villas Z1 & Z2, The Wave, Muscat
5.
3.3
DEMONSTRATION
GRILLE/DIFFUSERSCHEDULEZ1VILLA
SLOTDIFFUSER
LINEARBARREGISTER
SUPPLYAIR&RETURNAIR
SUPPLYAIR&RETURNAIR
SQUAREDIFFUSER
SUPPLYAIR
SLNO.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
FLOORREFERENCE
Groundfloor
Groundfloor
Groundfloor
Groundfloor
Groundfloor
Groundfloor
Groundfloor
Groundfloor
Groundfloor
Groundfloor
Groundfloor
Groundfloor
Groundfloor
Groundfloor
Groundfloor
Groundfloor
Groundfloor
Groundfloor
Groundfloor
Groundfloor
Groundfloor
Firstfloor
Firstfloor
Firstfloor
Firstfloor
Firstfloor
Firstfloor
Firstfloor
Firstfloor
Firstfloor
Firstfloor
Firstfloor
Firstfloor
Firstfloor
Firstfloor
Firstfloor
Roof
Roof
Roof
RETURNAIR
EXTRACTAIR
AREADESCRIPTION
Driver'sRoom
Office
OfficeWC
GuestEnsuite
GuestBedroom
FormalLiving
FormalLiving
FormalLiving
FormalLiving
Circulation
Circulation
Circulation
FormalDining
FamilyDining
ShowKitchen
WetKitchen
Laundry
MaidsRoom
MaidsWC
FamilyRoom
GuestWC
Bedroom1
Ensuite1
Bedroom2
Ensuite2
MasterBedroom
WalkinCloset
MasterEnsuite
Bedroom3
Ensuite3
Bedroom4
Ensuite4
FamilyLiving
WC
Kitchenette
Circulation
SandTrapLouver(STL)
ExhaustLouver(EXL)
KitchenExhaustLouver(KEXL)
DIFFUSERSIZE
(mmxmm)
QTY
150X150
150x150
470
413
120
DIFFUSERSIZE
QTY
(mmxmm)
150X150
150x150
300x300
300x300
300x300
DIFFUSERSIZE(mmxmm)
QTY
160mmdiadiscvave
160mmdiadiscvave
1
1
DIFFUSER
NOOFSLOT
LENGTH(mm)
SLOTWIDTH(mm)
QTY
GRILLE
LENGTH
(mm)
SPACING
GRILLE
WIDTH(mm)
QTY
8600
151WAY12mmSpacing
100
3500
151WAY12mmSpacing
100
4000
151WAY12mmSpacing
100
7500
151WAY12mmSpacing
100
3700
151WAY12mmSpacing
100
3700
151WAY12mmSpacing
100
ConnecttoKitchenHood
ConnecttoKitchenHood
150x150
160mmdiadiscvave
160mmdiadiscvave
160mmdiadiscvalve
160mmdiadiscvalve
3900
20
2450
3700
2700
3700
2700
5300
6300
2200
3300
3300
2
4
4
4
4
4
4
4
4
4
20
20
20
20
20
20
20
20
20
20
2
1
1
1
1
1
1
1
1
1
3400
20
1
1
2
160mmdiadiscvalve
160mmdiadiscvalve
160mmdiadiscvalve
160mmdiadiscvalve
150x150
1
1
4800
20
9500
20
GRILLE/DIFFUSERSCHEDULEZ2VILLA
SQUAREDIFFUSER
SUPPLYAIR
SLNO.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
FLOORREFENCE
Basement
Basement
Basement
Basement
Basement
Basement
Basement
Basement
Basement
Groundfloor
Groundfloor
Groundfloor
Groundfloor
Groundfloor
Groundfloor
Groundfloor
Groundfloor
Groundfloor
Groundfloor
Groundfloor
Groundfloor
Groundfloor
Groundfloor
Groundfloor
Groundfloor
Groundfloor
Groundfloor
Groundfloor
Groundfloor
Groundfloor
Groundfloor
Firstfloor
Firstfloor
Firstfloor
Firstfloor
Firstfloor
Firstfloor
Firstfloor
Firstfloor
Firstfloor
Firstfloor
Firstfloor
Firstfloor
Firstfloor
Secondfloor
Secondfloor
Secondfloor
Secondfloor
Roof
Roof
Roof
RETURNAIR
EXTRACTAIR
FRESHAIR
SLOTDIFFUSER
LINEARBARREGISTER
SUPPLYAIR&RETURNAIR
SUPPLYAIR&RETURNAIR
AREADESCRIPTION
Flexiblespace
Storage
MultipurposeArea
LobbyinMultipurposeArea
WCinMultipurposeArea
Maleservent'sQuarter
ToiletofMaleservent'sQuarter
BasementLobby
CarPark
Majlis
DIFFUSERSIZE
(mmxmm)
QTY
DIFFUSERSIZE
(mmxmm)
QTY
GRILLESIZE(mmxmm)
QTY
200x200
200x200
200x200
6
4
10
200x200
10
300x300
150x150
160mmdiadiscvalve
1
1
1
200x200
200x200
2
160mmdiadiscvalve
700x500
Majlislobby
Office
OfficeWC
Maidroom
Maid'sWC
Kitchenette
GuestWC
GuestBedroom
GuestEnsuite
FamilyRoom
Laundry&ServiceLobby
WetKitchen
WC
FamilyDining
FormalDining
FormalLiving
150x150
150x150
225x225
3
3
150x150
150x150
225x225
160mmdiadiscvalve
160mmdiadiscvalve
160mmdiadiscvalve
160mmdiadiscvalve
1
1
1
160mmdiadiscvalve
160mmdiadiscvalve
ConnecttoKitchenHood
160mmdiadiscvalve
ConnecttoKitchenHood
1
1
3
1
300x300
DIFFUSER
LENGTH(mm)
NOOFSLOT
SLOTWIDTH
(mm)
QTY
3000
20
8700
4400
2100
1100
1600
2
2
2
2
2
20
20
20
20
20
2
1
1
1
3
1500
20
3200
20
3400
20
2
3
Bedroom1
Ensuite1
Bedroom2
Ensuite2
Bedroom3
Ensuite3
Bedroom4
Ensuite4
MultipuposeRoom
FamilyRoom
Kitchenette
160mmdiadiscvave
160mmdiadiscvave
160mmdiadiscvave
160mmdiadiscvave
160mmdiadiscvave
450x450
225x225
2
5
4
4
4
4
20
20
20
20
GRILLE
WIDTH
(mm)
QTY
7000
7100
151WAY12mmSpacing
151WAY12mmSpacing
100
100
1
1
5700
151WAY12mmSpacing
100
5500
151WAY12mmSpacing
100
5400
151WAY12mmSpacing
100
2
1
1
1
3100
3400
3
3
20
20
2
2
5100
2800
1900
2900
4
4
4
4
20
20
20
20
2
1
4
1
Circulation
SPACING
3300
3300
3100
3300
225x225
GRILLELENGTH
(mm)
Circulation
Masterbedroom
Masterbedroom
His/herchanging
MBREnsuite
SandTrapLouver(STL)
ExhaustLouver(EXL)
KitchenExhaustLouver(KEXL)
DIFFUSERSIZE
QTY
(mmxmm)
160mmDiaDiscvalve
400x400
300x300
1
2
SCHEDULEOFEQUIPMENTZ1VILLA
SLNO.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
24
25
26
27
28
29
30
31
32
33
34
35
36
AREADESCRIPTION
FLOORREFERENCE
GuestBedroom
FamilyRoom
FormalLiving
Cirulationarea
FormalDining
FamilyDining
ShowKitchen
WetKitchen
Laundry
Maid'sroom
Driverroom
Office
Garage
Store
Bedroom1
Bedroom2
MasterBedroom
MBREnsuite
Cirulationarea
Bedroom3
Bedroom4
FamilyLiving
FreshAirHandlingunit
FreshAirHandlingunit
OutdoorUnit1
OutdoorUnit2
OutdoorUnit3
FreshAirFanAxialfan
ExtractAirFanAxialfan
Roofmounedextractfan
KitchenExhaustFanInlinefan
KitchenExhaustFanInlinefan
Groundfloor
Groundfloor
Groundfloor
Groundfloor
Groundfloor
Groundfloor
Groundfloor
Groundfloor
Groundfloor
Groundfloor
Groundfloor
Groundfloor
Groundfloor
Groundfloor
Firstfloor
Firstfloor
Firstfloor
Firstfloor
Firstfloor
Firstfloor
Firstfloor
Firstfloor
Firstfloor
Firstfloor
Roof
Roof
Roof
Roof
Roof
Basement
Roof
Roof
PlateHeatExchanger
Roof
SilencersforSupply&Exhaustfans
Roof
(roomsideonly)
MAXIMUMdBAon
NOMINALLOAD
NRLEVEL
EQUIPMENTREFERENCE
SUPPLYAIRQTY
(lps)each
TOTALCOOLING
CAPACITY(KW)each
SENSIBLECAPACITY
(KW)each
EXTERNALSTATIC
PRESSURE(Pa)
ELECTRICALDATA
(V/Ph/Hz)
QTY
3035
4045
3035
4555
3035
4555
4555
4555
4555
3035
3035
4045
4555
4555
3035
3035
3035
4045
4555
3035
3035
4045
4045
4045
70
70
70
4555
4555
4555
4555
4555
30
35
35
40
35
40
40
40
40
40
40
35
40
40
30
30
30
35
40
30
30
35
35
35
40
40
40
40
40
FCUG1
FCUG2&FCUG3
FCUG4&FCUG5
FCUG6&FCUG7
FCUG8&FCUG9
FCUG10
FCUG11
FCUG12
FCUG13
FCUG15
FCUG16
FCUG14
FCUG17
FCUG18
FCUF1
FCUF2
FCUF3
FCUF4
FCUF5&FCUF6
FCUF7
FCUF8
FCUF9
FAHU1
FAHU2
VRF1
VRF2
VRF3
FAF
EAF
RMEF
KEF1
KEF2
199
120
514
391.5
391.5
433
138
134
111
133
100
190
251
180
213
231
704
197
420
443
472
372
120
180
300
260
50
120
120
3.9
4.6
12.05
6.6
9.45
11.5
3.2
3.2
2.1
3.1
1.8
6
2.9
2.1
4
4.3
11.4
3.9
8
6.8
7.1
9
6
8
14
85
83
2.9
2.55
8.2
5.3
6.3
7.3
2.2
2.1
1.6
2.1
1.3
3.5
2.9
2.1
3
3.2
9.3
2.8
5.95
5.7
6.1
5.9
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
200
200
200
200
100
200
200
230/1/50
230/1/50
230/1/50
230/1/50
230/1/50
230/1/50
230/1/50
230/1/50
230/1/50
230/1/50
230/1/50
230/1/50
230/1/50
230/1/50
230/1/50
230/1/50
230/1/50
230/1/50
230/1/50
230/1/50
230/1/50
230/1/50
230/1/50
230/1/50
415/3/50
415/3/50
415/3/50
415/3/50
415/3/50
230/1/50
230/1/50
230/1/50
1
2
2
2
2
1
1
1
1
1
1
1
1
1
1
1
1
1
2
1
1
1
1
1
1
1
1
1
1
1
1
1
PHEX
TosuiteIndoorcondtionasperthe
specifiedNRlevels
Supply:300lps
Return:260lps
Note:
1.TheOutdoorunitdesigncapacityshallbebasedon46cDBTambienttemperature
2.ContractortoprovideExternalstaticpressurecalculationanditshallbeapprovedbyconsultant,beforeorderingtheequipment.
3.PlateHeatexchangerefficiencyshallnotbebelow75%.
4.KitchenexhaustfanstobeprovidedwithlocalON/OFFwithstatusindicatinglightnearthehood.
5.ON/OFFcoilconditionsfoFAHUshallbe46CDBT/16CDBT,FCUshallbe24CDBT/12.5CDBT
6.HeatExchangerforPHEFAHUcombinationselectionshallbematchedtoachieve16CatoutlettemperatureofFAHU.
7.AllFCUsshallbeprovidedwithaG3gradefilter.PHEtobeequippedwithG3filtersonupstreamside.
OutdoorAirTemperature:46C
ReturnAirTemperature:24C
SCHEDULEOFEQUIPMENTZ2VILLA
SLNO.
AREADESCRIPTION
FLOORREFERENCE
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
MultipurposeArea,lobby,WC
Basementlobby,lift,staircase
Flexiblespace
Maleservant'sQuarter
Storage
Majlis
MajlisLobby
Office&OfficeWC
Maidroom,WC&kitchenette
MainEntrancelobby,staircase,lift
Circulationarea
Familyroom
Guestbedroom
Formaldining
Wetkitchen
Stafflobby,Laundry&utilityroom
FormalLiving
Familydining,showkitchen
Bedroom1
Bedroom2
Familyroom,kitchenette
MultipurposeRoom
Bedroom3
Bedroom4
lift,staircase,corridor+Circulation
Lobby,lift,staircase
Masterbedroom
MBRensuite,her/hischanging
FreshAirHandlingunit
OutdoorUnit1
OutdoorUnit2
OutdoorUnit3
OutdoorUnit4
FreshAirFanAxialfan
ExtractAirFanAxialfan
Wallmounedextractfan
KitchenExhaustFanInlinefan
KitchenExhaustFanInlinefan
Basement
Basement
Basement
Basement
Basement
Groundfloor
Groundfloor
Groundfloor
Groundfloor
Groundfloor
Groundfloor
Groundfloor
Groundfloor
Groundfloor
Groundfloor
Groundfloor
Groundfloor
Groundfloor
Firstfloor
Firstfloor
Firstfloor
Firstfloor
Firstfloor
Firstfloor
Firstfloor
Secondfloor
Secondfloor
Secondfloor
Secondfloor
Secondfloorroof
Secondfloorroof
Secondfloorroof
Secondfloorroof
Roof
Roof
Basement
Roof
Roof
39
PlateHeatExchanger
Roof
40
SilencersforSupply&Exhaustfans
(roomsideonly)
Roof
MAXIMUMdBAon
NOMINALLOAD
NRLEVEL
EQUIPMENTREFERENCE
4045
4045
4045
3035
4045
4045
4045
4555
4555
4045
3035
3035
4555
4555
3035
4555
3035
3035
4045
4045
3035
3035
4555
4555
3035
3035
4045
70
70
70
70
4555
4555
4555
4555
4555
35
35
35
40
50
35
35
35
50
40
40
35
30
35
40
40
35
40
30
30
35
35
30
30
40
40
30
30
35
40
40
40
40
40
FCUB1&FCUB2
FCUB3
FCUB4
FCUB5
FCUB6
FCUG1&FCUG2
FCUG3
FCUG4
FCUG5
FCUG6
FCUG7
FCUG8&FCUG9
FCUG10
FCUG11&FCUG12
FCUG13
FCUG14
FCUG15&FCUG16
FCUG17
FCUF1
FCUF2
FCUF3&FCUF4
FCUF5
FCUF6
FCUF7
FCUF8&FCUF9
FCUS1
FCUS2&FCUS3
FCUS4
FAHU
VRF1
VRF2
VRF3
VRF4
FAF
EAF
WMEF
KEF1
KEF2
PHEX
TosuiteIndoorcondtionasper
thespecifiedNRlevels
Supply:470lps
Return:413lps
Note:
1.TheOutdoorunitdesigncapacityshallbebasedon46cDBTambienttemperature
2.ContractortoprovideExternalstaticpressurecalculationanditshallbeapprovedbyconsultant,beforeorderingtheequipment.
3.PlateHeatexchangerefficiencyshallnotbebelow75%.
4.KitchenexhaustfanstobeprovidedwithlocalON/OFFwithstatusindicatinglightnearthehood.
5.ON/OFFcoilconditionsfoFAHUshallbe46CDBT/16CDBT,FCUshallbe24CDBT/12.5CDBT
6.HeatExchangerforPHEFAHUcombinationselectionshallbematchedtoachieve16CatoutlettemperatureofFAHU.
7.AllFCUsshallbeprovidedwithaG3gradefilter.PHEtobeequippedwithG3filtersonupstreamside.
SUPPLYAIRQTY
TOTALCOOLING
(lps)each
CAPACITY(KW)each
384.5
155
263
120
137
222
159
221
163
662
571
193
200
428.5
201
150
510.5
350
358
297
199
159
396
384
544
142
305
194
470
470
413
50
120
120
10.4
2.6
6.1
2.9
1.6
6.4
4.2
6.6
3.6
11.6
10.6
5.3
5.4
13.45
5.2
2.6
8.3
7.3
5.8
5
6.1
4.4
7.7
7.6
8.2
1.6
6.65
4.6
21
21
88.8
84.5
63.3
SENSIBLECAPACITY
(KW)each
EXTERNALSTATIC
PRESSURE(Pa)
ELECTRICALDATA
(V/Ph/Hz)
QTY
6.7
2.1
4.1
1.9
1.6
3.8
2.6
3.9
2.5
9.1
8
3.25
3.3
7.7
3.3
2.1
6.75
5.3
4.7
4
3.55
2.7
5.7
5.5
6.95
1.6
4.55
3
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
200
200
200
100
200
200
230/1/50
230/1/50
230/1/50
230/1/50
230/1/50
230/1/50
230/1/50
230/1/50
230/1/50
230/1/50
230/1/50
230/1/50
230/1/50
230/1/50
230/1/50
230/1/50
230/1/50
230/1/50
230/1/50
230/1/50
230/1/50
230/1/50
230/1/50
230/1/50
230/1/50
230/1/50
230/1/50
230/1/50
230/1/50
415/3/50
415/3/50
415/3/50
415/3/50
415/3/50
415/3/50
230/1/50
230/1/50
230/1/50
2
1
1
1
1
2
1
1
1
1
1
2
1
2
1
1
2
1
1
1
2
1
1
1
2
1
2
1
1
1
1
1
1
1
1
1
1
1
OutdoorAirTemperature:46C
ReturnAirTemperature:24C