You are on page 1of 11

Energy Efficient Buildings

Energy Efficient Cooling Plants


Chiller Plant Control
A chiller plant typically includes chillers, chilled water pumps, cooling tower
pumps, and cooling towers with fans. A chiller plant with constant-speed
primary chilled water pumps and variable speed secondary chilled water
pumps is shown below.

Typical temperature design guidelines for chiller plants include:


Tevaporator = 10 F
Tcondenser = 10 F
Tchilledwatersupply = 42 F
Tcoolingtowerreturn = 80 F
The total energy use of the chiller plant includes the energy use by the
chiller, pumps and cooling tower fans. Historically, as energy efficiency
became more important, attention was originally focused on improving
chiller efficiency since the chiller was the single biggest energy user in the
chiller plant. As a consequence, chiller energy use declined over the last
thirty years from over 0.75 kW/ton to less than 0.50 kW/ton today.
As chiller efficiency improved, the energy use by supporting fans and pumps
became a larger fraction of chiller plant energy use. In addition, designers
and operators became increasingly aware of interaction effects between the
components, and the potential to drive energy use even lower by optimizing
the system rather than components. This chapter discusses chiller plant
1

control to reduce total system energy use. Specifically, it considers how the
design guidelines shown above could modified to enhance energy efficiency.

Source data: Trane, 2000, Chilled Water System Design and Operation,
CTV-SLB005-EN.

Reduce Cooling Tower Fan Energy Use


Cooling tower fan energy use can be reduced by reducing the friction loss as
air flows through the cooling tower and by reducing the flow rate of air.
Friction losses are much smaller in induced flow-cooling towers than forcedflow cooling towers. In addition, improved packing designs increase
evaporative contact area while reducing friction losses. Low-friction cooling
towers can be identified by comparing rated fan motor power per rated
cooling capacity.
Cooling tower fan energy use can also be reduced by better air flow control.
The temperature of the water leaving a cooling tower is typically controlled
by varying the air flow rate through the cooling tower. In older cooling
towers, air flow rate was varied by cycling the cooling tower fan on and off.
A more energy efficient method of control is to vary the fan speed since
friction pressure drop is lower at lower air flows; the fan affinity law of fluid
work varying with the cube of flow applies to cooling towers as well duct
systems. Two speed cooling tower fan motors approximate this type of

control. Today, full variable speed control is achieved by controlling fan


speed with a variable-frequency drive.
The table and graph below show simulated cooling tower fan electricity use
for a constant-speed on/off and variable-speed 10-hp fan motor running
continually in Dayton, OH with a 10 F temperature drop and an 80 F
condenser supply temperature. The constant-speed fan is on 47% of the
year, while the variable speed fan runs at 37% of full speed. During hot,
humid weather, the fraction energy savings from variable-speed cooling
tower fan control are less since the cooling tower fan must operate at close
to full load. However, during cool, dry conditions, the fraction energy
savings from variable-speed cooling tower fan control are significant. Overall,
fan energy was reduced by about 64%.

Reduce Cooling Tower Water Flow Rate


After cooling tower fan energy use is addressed, energy savings from
reducing cooling tower water flow rate can be explored. Cooling towers are
typically designed to operate with a fixed flow rate of water. A typical flow
rate for cooling towers is 3 gpm per rated ton of chiller capacity. However,
reducing the water flow rate reduces pumping costs and improves cooling
tower effectiveness. Moreover, if system is originally designed for less flow,
smaller pipes and pumps can reduce first costs. Consider the following
example.
Example
A cooling tower is originally designed and operated with 5 gpm of water per
ton with a 10 F temperature gain through the condenser. The required
elevation head is 10 ft H20 and the friction head is 20 ft H2O. The pump is
70% efficient and the pump motor is 90% efficient. The water flow rate is
then reduced to 3 gpm per ton. If the wet-bulb temperature of the air is 60
F, determine a) the water temperature leaving the cooling tower at 5 gpm, b)
the water temperature leaving the cooling tower at 3 gpm, c) the pumping
power at 5 gpm per ton, d) the pumping power at 3 gpm per ton, and e) the
fraction reduction in pumping power.
a) From the cooling tower performance chart for a tower operated at 5
gpm/ton, the temperature of water leaving a cooling tower is about 80 F
when the temperature range is 10 F and the wet-bulb temperature of the air
is 60 F.
b) If the tower flow rate were reduced to 3 gpm/ton, the new temperature
range can be found from an energy balance on the condenser.
Qcond = V1 p cp Tcond1 = V2 p cp Tcond2
Tcond2 = (V1 / V2) Tcond1 = (5 gpm/ton / 3 gpm/ton) 10 F = 16.7 F
From the cooling tower performance chart for a tower operated at 3 gpm/ton,
the temperature of water leaving a cooling tower when the temperature
range is 16.7 F and the wet-bulb temperature of the air is 60 F is about 78 F.
Thus, the temperature of water leaving the cooling tower declines with the
lower flow rate. As long as the temperature of water to the condenser is
greater than the minimum temperature required by the chiller, reducing the
temperature of water to the condenser improves the efficiency of the chiller.
c) The initial pump head is:
h1 = helev + hfric = 10 ft H2O + 20 ft H2O = 30 ft H2O

The electrical power supplied to the pump motor at 5 gpm/ton is:


P1 = V1 h1 / [ 3,960 (gpm-ftH20/hp) Epump Emotor ]
P1 = 5 gpm/ton 30 ftH20 / [3,960 (gpm-ftH20/hp) 0.70 0.90] x 0.746 kW/hp
P1 = 0.0449 kW/ton
d) Reducing the flow rate to 3 gpm/ton reduces the pump work to overcome
friction according to the pump affinity laws. The fluid work to overcome
friction at 5 gpm/ton was:
Wf1 = V1 hf1 / 3,960 (gpm-ftH20/hp)
Wf1 = 5 gpm/ton 20 ftH20 / 3,960 (gpm-ftH20/hp) = 0.0253 hp/ton
According to the fan affinity law, the fluid work to overcome friction at 3
gpm/ton is:
Wf2 = Wf1 (V2 / V1)3 = 0.0253 hp/ton (3 gpm/ton / 5 gpm/ton)3 = 0.00546
hp/ton
The fluid work to overcome the elevation head is:
We2 = V2 he / 3,960 (gpm-ftH20/hp) = 3 gpm/ton 10 ftH20 / 3,960 (gpmftH20/hp) = 0.00758 hp/ton
Assuming the efficiencies of the pump and motor remain the same, the total
electrical power to the pump motor at 3 gpm/ton is:
P2 = (Wf2 + We2) / (Epump Emotor)
P2 = (0.00546 hp/ton + 0.00758 hp/ton) / (0.70 x 0.90) x 0.746 kW/hp =
0.0154 kW/ton
e) Thus, reducing the flow rate from 5 gpm/ton to 3 gpm/ton reduced the
electrical power to the pump motor by
(0.0449 kW/ton - 0.0154 kW/ton) / 0.0449 kW/ton = 66%
The result in the example above indicates the savings potential from
reducing the flow rate of condenser water through the cooling tower. In
practice, this can sometimes be achieved by measuring temperature
difference of water across the condenser, and reducing flow if the
temperature difference is consistently small.

Condenser Water Temperature Control


Chiller efficiency improves with lower condenser water temperature.
However, cooling tower fan energy use increases to deliver lower condenser
water temperature. This suggests an optimum condenser water temperature
may exist which would minimize total cooling tower fan plus chiller energy
use.
The affect of condenser water temperature on total cooling tower fan plus
chiller electricity use can be modeled by solving a system of equations that
includes cooling tower and chiller performance. Input values must be known
for:
Qevap (tons) = actually cooling load
Qcap (tons) = cooling capacity of chiller
Twb (F) = ambient wet-bulb temperture
Tcsp (F) = set point temperature of cold water leaving cooling tower
DWF (gpm/ton) = design water flow rate to cooling tower
To solve the system using successive substitution, start by assuming a
temperature range Tr, across the cooling tower and then solving the
following set of equations. The chiller fraction loaded, FL, is:
1) FL = Qevap / Qcap
The minimum water temperature delivered by the cooling tower, Tc, is given
by:
2) Tc = a + b Twb + c Tr + d Twb2 + e Tr2 + f Tr Twb
However, cooling tower fans cycle on and off to maintain the water leaving
the cooling tower at a set temperature Tcsp. Thus, to incorporate cooling
tower control, Equation 2 must be followed by the following algorithm. From
an energy balance, the fraction of time the cooling tower fan runs, Fon, and
the actual entering and leaving cooling tower water temperatures Th and Tc
are:
3)
If Tc >= Tcsp then
fan runs continuously
Fon = 1
Tc = Tc
Th = Tc + Tr
Else if Tc < Tcsp then
fan cycles on and off to maintain Tcsp
Th = Tcsp + Tr
Fon = (Tcsp Th) / (Tc Th)
6

Tc = Tcsp
End if
Compressor input power per ton of evaporator cooling, KWPT, is given by:
4) KWPT = a + b FL + c FL2 + d Tc + e Tc2 + f Tc FL
Then, from an energy balance on the chiller, compressor input power,
Wcomp, heat rejected by the condenser, Qcond, volume flow rate of water
through the condenser, Vw, and temperature rise across the condenser, Tr,
are given by :
5)
6)
7)
8)

Wcomp = KWPT Qevap


Qcond = Wcomp + Qevap
Vw = DWF Qcap
Tr = Qcond / (Vw pw cpw)

where pw is the density of water and cpw is the specific heat of water. The
value for Tr can then be substituted back into the start of the algorithm and
the algorithm repeated until Tr converges. After convergence, cooling tower
fan power, Wctf, can be calculated as:
Wctf = Fon RHP FML / Emotor x 0.746 kW/hp
Where RHP is cooling tower fan rated horsepower, FML is fraction motor
loaded, Emotor is the efficiency of the motor. The total power of the cooling
tower fan and compressor is:
Wtot = Wctf + Wcomp
Example
Consider a 500-ton chiller operated at 300 tons with a 30-hp cooling tower
fan and design water flow rate of 3 gpm/ton. The fan motor is 90% efficient.
The outdoor air wet-bulb temperature is 60 F. Calculate total cooling tower
fan plus compressor electrical power for cooling tower water set point
temperatures of 80 F, 70 F and 60 F.
Use of the algorithm shown above produces the following results. The
minimum total cooling tower fan plus compressor electrical power (192 kW)
occurred at a cooling tower water set point temperature of 70 F, which is 10
F greater than the outdoor air wet bulb temperature. This suggests that
total cooling tower fan plus compressor electrical power might be minimized
over an entire year by resetting the cooling tower water set point
temperature according to outdoor air wet-bulb temperature.

When this algorithm is incorporated into an hour-by-hour simulation program,


the affect of condenser water temperature set point on total cooling tower
fan plus chiller electricity use can be tested. For example, the following
results shown below are for a 500-ton chiller operated at 300 tons with a 30hp cooling tower fan and design water flow rate of 3 gpm/ton in Dayton, OH,
and a cooling tower water set point temperature of 60 F.

The results below show total cooling tower fan energy use for both a
constant speed fan Ecsf and variable speed fan Evsf, compressor energy use,
Ec, and total energy use for various cooling tower set-point temperatures.
These results indicate that chiller plus cooling tower fan energy use can be
reduced from a design condenser water temperature of 80 F by setting the
cooling water temperature equal to the minimum condenser temperature
recommended by the chiller manufacturer. Chiller plus cooling tower fan
energy use can then be further reduced by varying cooling water
temperature with outdoor air wet-bulb temperature.
Tcsp
(F)
80
70
60
50
Twb + 10 F

Ecsf
(kWh/yr)
52,296
93,217
134,651
173,341
1,498,886

Evsf
(kWh/yr)
5,541
48,493
99,355
151,437
94,166

Ec
(kWh/yr)
1,739,450
1,542,125
1,406,825
1,328,278
1,350,674

Ecsf + Ec
(kWh/yr)
1,791,746
1,635,342
1,541,476
1,501,619
1,500,559

Evsf + Ec
(kWh/yr)
1,744,991
1,590,618
1,506,180
1,479,715
1,444,840

These results are similar to an analysis by Trane, which showed that varying
condenser water temperature with outdoor air wet-bulb temperature resulted
in lower total energy costs than the design condenser water temperature or
the minimum condenser water temperature that the chiller could accept.

Source data: Trane, 2000, Chilled Water System Design and Operation,
CTV-SLB005-EN.

All Variable Flow Cooling Plants

Traditionally, cooling plant pumps, fans and chillers were driven with
constant speed motors. Load following capability was provided by bypass,
mixing, staging and on/off control. Today, load following capability can be
provided by varying the flow of the pumps, fans and chillers with variable
frequency drives. Variable flow control can significantly reduce energy use
over traditional constant flow systems. The figure below shows an all
variable-speed cooling plant. Variable-speed cooling plants have been
documented to use as little as 0.5 kW/ton at high loads and 0.3 kW/ton at
low loads (Erpelding, Ben, 2008, Monitoring Chiller Plant Performance,
ASHRAE Journal, April, pp. 48-52.)

10

11

You might also like