OC 4000 Distributed Control System

Proprietary Information For Internal Use Only


General Electric Company 2007

Proprietary Information For Internal Use Only


General Electric Company 2007

1
June, 2006

Typical DCS Configuration


Supervisor

Supervisor

100Mbps
Redundant
Hi gh Speed
I nf o Net wor k

5 OPU

2 ENG

SIS Network
PIU

PIU

Hi gh Speed
I nf o Net wor k

5 OPU

2 ENG

100MBPS

100MBPS
SIS GTW
RS485
TCP/IP
...

2 X 84 l ar ge Scr een

InkJet
21"
21

LaserJet

17"

21
21"

SIS GTW

2 X 84 l ar ge Scr een

17"

17"

17"

LaserJet

21"

20

LaserJet
LaserJet

InkJet

21"
21

LaserJet

LaserJet

RS485
TCP/IP
...

LaserJet

LaserJet

Large Screen OPU


...

100MBPS Redundant Faul t - t ol er ant Real - t i me

RS485
TCP/IP

Bridge

Bridge

Bridge

100MBPS Redundant Faul t - t ol er ant Real - t i me

Bridge

100Mbps
Fiber
optical
transmitter
and receiver

DP
U

DP
U

...
...

Cabinet Room for


Boiler Control
Photoelectricity
multiplexor

DP
U

DP
U

...
...

DP
U

DP
U

DP
U

DP
U

Cabinet Room for


Turbine Control

DP
U

DP
U

Cabinet Room For


Turbine Control

BOP DCS
Photoelectricity
multiplexor

...
...

Cabinet Room

...
...

DP
U

Cabinet Room For


Boiler Control

CWP FCS
Cabinet Room

Photoelectricity
multiplexor

Photoelectricity
multiplexor

10Mbps

10Mbps

10Mbps

10Mbps

Fiber
optical
transmitter
and receiver

Fiber
optical
transmitter
and receiver

Fiber
optical
transmitter
and receiver

Fiber
optical
transmitter
and receiver

Remote I/O( FIO)

DP
U

Remote I/O( FIO)

Remote I/O( FIO)

Remote I/O( FIO)

Oil Pump Room( FIO)

Proprietary Information For Internal Use Only


General Electric Company 2007

2
June, 2006

Coal Fired Plant Solution


Boiler Control

Drum Level

Air Fuel Ratio

Boiler Feedpump

Mill Control

Furnace Pressure

Primary /Secondary Air

Turbine Control

Steam Temperature

Deaerator
Drum Level
Saturated Steam

Sea Water
Cooling

Condenser

Control
Main Throttle Valve
Governor Valve
Intermediate Valve
Reheat Valve

Superheated Steam

Boiler Feed Pump

Common/
BOP Control

Economizer

Air Pri/Sec
Induce Draft
Ash Handling

Protection
Overspeed
Power Load unbalance
Vibration
MFT
Loss of Hydraulic Power

Mill Control - Fuel


Force Draft

Proprietary Information For Internal Use Only


General Electric Company 2007

Coal Handling
Ash Handling
Water Treatment
FGD Flue Gas
Desulfurization

3
June, 2006

Coal Fired DCS Architecture


DCS for Unit 1

Turbine
Control

Boiler
Control

DEH

MCS

MEH

SCS

Protection

DAS
BMS/FSSS

DCS for Common

ECS
Coal/Ash
Handling
Water
Treatment

DCS for Unit 2

Turbine
Control

Boiler
Control

DEH

MCS

MEH

SCS

Protection

DAS

BOP

Proprietary Information For Internal Use Only


General Electric Company 2007

BMS/FSSS

4
June, 2006

Hydro Plant Solution

Plant
Control

Proprietary Information For Internal Use Only


Unit
General Electric Company 2007

Control

Hydraulic/
5
June, 2006
Mechanical

Hydro Station Control Architecture

Plant
Control

Hydro
For Internal Use Only
UnitProprietary Information
Mechanical/Hydraulic
General Electric Company 2007
Control

Unit
Control

6
June, 2006

Combine Cycle Plant Solution


HRSG Control and BOP Control

Gas Turbine Control

Proprietary Information For Internal Use Only


General Electric Company 2007

Steam Turbine Control

7
June, 2006

Combine Cycle Control Architecture


Steam Turbine
Control &
Protection

Gas Turbine
Control &
Protection

Operator
Interfaces
OSM

ESD

Subsystem
PLC

HRSG & BOP

HRSG &
BOP IO
Proprietary Information For Internal Use Only
General Electric Company 2007

Generator Excitation
& Protection
8
June, 2006

Solution to Multi-Units DCS


DCS for Unit 1

DCS for Common

DCS for Unit 2

MMI

Turbine
Control

Boiler
Control

DEH

MCS

MEH

SCS

Protection

DAS
BMS/FSSS

ECS
Coal/Ash
Handling
Water
Treatment

Turbine
Control

Boiler
Control

DEH

MCS

MEH

SCS

Network

Protection DAS

BOP

Proprietary Information For Internal Use Only


General Electric Company 2007

BMS/FSSS

Controller

IO level9
June, 2006

OC 4000TM Network Layer Architecture


Main
Characteristics

NODE

NODE

NODE

NODE

NODE

Ethernet Base
120 Nodes
Ring/Star

NODE

NODE

Proprietary Information For Internal Use Only


General Electric Company 2007

NODE

10
June, 2006

OC 4000TM Network Layer Architecture

Ring

Proprietary Information For Internal Use Only


General Electric Company 2007

11
June, 2006

OC 4000TM Network Layer Architecture

Star

Proprietary Information For Internal Use Only


General Electric Company 2007

12
June, 2006

Redundant, Fault-tolerant Network Virtual Fiber Ring

For a single ring, during normal operation, the switch-hub deals


with a logic break. When there is one break, the switch-hub will
close the logic break, so the network is still integral.
Only when there are two breaks, the network is divided into two
isolated parts.
Proprietary Information For Internal Use Only
General Electric Company 2007

13
June, 2006

Redundant, Fault-tolerant Network Virtual Fiber Ring

When configured with redundant ring network, even


there are three breaks, the network is still integral.

Proprietary Information For Internal Use Only


General Electric Company 2007

14
June, 2006

Control
Room

Rack Room
Remote
Site

Typical Network Architecture


Proprietary Information For Internal Use Only
General Electric Company 2007

15
June, 2006

OC 4000 Controller (DPU) Advantages


- Online program immediately changeable would
save considerable time during commissioning and
testing phases.
- Virtual DPU provides quicker delivery and a lower
risk for implementation time through pre-testing
and pre-commissioning without the controller
Simulation
hardware (Simulation)
- Parameter forcing from anywhere on control
logic page. This provides a very powerful tool for
rapid logic testing and commissioning, which is
important in retrofit or upgrade projects.
- TUV SIL3 certified TMR I/O architecture offers the
best availability, compared to other dual I/O
systems.
Proprietary Information For Internal Use Only
General Electric Company 2007

16
June, 2006

OC 4000TM DPU Architecture


NODE

I/O Bus System


Single/Redundant
10 Mbps Ethernet
Star Based
8 Drops
96 I/O Modules

Proprietary Information For Internal Use Only


General Electric Company 2007

17
June, 2006

POWER SUPPLY

ON

Power

Vdd

V dd

Vss

Vss

OFF

POWER SUPPLY

POWER SUPPLY

Power

ON

OFF

ON

OFF

Proprietary Information For Internal Use Only


General Electric Company 2007

ON

POWER SUPPLY

24 V

OFF

ON

24 V

OFF

ON

OFF

Support up to 8 I/O stations


Support up to 96 I/O modules
Resolution of high-speed sequence of event record:
1ms
Page execution cycle period: graded selection
between 20ms~60 seconds
Control page: a DPU file contains at most 512
999 control
pages
100 pre-definable control algorithms
More than 100
Simulation

POWER SUPPLY

48 V

Embedded 32 bits Real-Time OS Core: WindowsCE

POWER SUPPLY

48 V

Controller (DPU) Performance

1
2
3
4
A

18
June, 2006

Remote I/O and Remote Control


NODE
100 Mbps

NODE

100m twisted
pair wire
2KM Multi
Mode optical
cables
20KM Single
mode fiber
equipment

10
Mbps

NODE

Proprietary Information For Internal Use Only


General Electric Company 2007

19
June, 2006

Typical DPU Control Cabinet Layout


ON

POWER SUPPLY

Power

Power

V dd

Vdd

Vss

V ss

OFF

ON

POWER SUPPLY

POWER SUPPLY

48 V

OFF

ON

OFF

POWER SUPPLY

48 V

ON

OFF

POWER SUPPLY

24 V

ON

P1

P1

P1

P1

P1

P1

P2

P2

P2

P2

P2

P2

24 V

OFF

ON

OFF

AC220 V

AC220 V

POWER SUPPLY

IP32 standard(INDOOR)
IP56 standard(OUTDOOR)
700 700 2235 mm(WDH)
800 600 2200 mm(WDH)

Front

Rear

Front

Rear

Fan Unit
Proprietary Information For Internal Use Only
General Electric Company 2007

20
June, 2006

Proprietary Information For Internal Use Only


General Electric Company 2007

21
June, 2006

Automatic link

Proprietary Information For Internal Use Only


General Electric Company 2007

22
June, 2006

FUNCTION
BLOCK DIAGRAM UP TO 512 PAGES
Proprietary Information For Internal Use Only
General Electric Company 2007

23
June, 2006

I/O Modules

AI Module
AO Module
DI Module
DO Module
PI Module
LC Module
BCNET Module
VPC Module
SDP Module
LPC Module
BZT Module
SYN Module
CAI Module

Generic DCS
Generic DCS
Generic DCS
Generic DCS
Generic DCS
Drive Module
System Module
DEH Special
DEH Special
DEH Special
ECS Special
ECS Special
ECS Special

Standard
Boiler Control
Application

Steam Turbine
Control with
Protection and
Sync
Application

AI Module: 16 bits A/D; error for Small Signal 0.2% Large Signal 0.1%
Operation temperature: 0~45 Humidity 0-95%
Remote I/O Modules fully Compatible with Local I/O Modules
SOE Resolution 1ms

Proprietary Information For Internal Use Only


General Electric Company 2007

24
June, 2006

I/O Module-Overall

I/O Modules send or receive signals from field device


I/O Modules send or receive control signals from DPU
I/O Modules manufactured using SMT (Surface Mounting Technology)
Machine
High reliability / easy maintenance.

Proprietary Information For Internal Use Only


General Electric Company 2007

25
June, 2006

I/O Module-Components
I/O modules consist of
CPU: all kinds I/O modules have CPU and related
circuits to perform input/output, communication and
diagnostics.
Isolation: optical
A/D or D/A: 16 bits and A/D, 12 bits D/A
Programmable gain amplifier
Over-current or over-voltage protection
Communication circuit

Proprietary Information For Internal Use Only


General Electric Company 2007

26
June, 2006

I/O Module-Highlights
DCS has limited types of I/O modules to simplify the design of DCS,
to minimize the cost for spares.
Four Common types of I/O modules, which are AI, AO, DI, DO
can meet most requirements.
In AI module, DCS has used the same module along with different
terminal boards to interface with mA, RTD and TC signals.
Self-diagnostic to channel level
Online maintenance
Specialty Module for Steam Turbine Control and Protection
Specialty Module for Electrical System

Proprietary Information For Internal Use Only


General Electric Company 2007

27
June, 2006

VPC Valve Position Control Card


An intelligent card used for electro hydraulic servo control of steam valve
Main Characteristics
AI: 2 channel 3-wire LVDT signals; 2 channels of Current/voltage signal (0~20mA or
0~5V or 5V)
AO: 1 channel of Current/voltage signal (0~20mA or 0~5V) ; 1-channel valve control
signal (20~40mA) or Single 150mA
7- channel DI, binary isolation input; 1 channel DO, auto/manual status DO, 5000V
isolation voltage
Highly reliable design. VPC can directly control valve opening of turbine when DEH
malfunctions.

Main Throttle Valve


Governor Valve
Intermediate Valve
Reheat Valve
Proprietary Information For Internal Use Only
General Electric Company 2007

28
June, 2006

VPC Valve Position Control Card

Proprietary Information For Internal Use Only


General Electric Company 2007

29
June, 2006

SDP Speed Detection and Protection Card


A card combining functions of speed pulse signal and over-speed protection
Main Characteristics
3-channel speed input channel
8-channel DI
4-channel OPC status relay output: capacity:
240VAC/10A (103% with delay timer of 1~10sec)
4-channel AST status relay output: capacity:
240VAC/10A (110%)
3-channel speed output channel
Measurement range: 1 ~ 20,000Hz. (DEH/MEH)
2oo3 logic Output (DNV Certified SIL 3)
6-channel AI: 1~5V or 4~20mA, supplying power to
transducer (Power Load Unbalance Protection 3xTurbine Load and 3xGenerator Load)
Optoelectronic isolator is adopted with isolated voltage
more than 1500V.

Proprietary Information For Internal Use Only


General Electric Company 2007

30
June, 2006

SDP Speed Detection and Protection Card


A card combining functions of speed pulse signal and over-speed protection
DNV SIL 3 - 2oo3 Modules

Main Characteristics
3-channel speed input channel
8-channel DI
4-channel OPC status relay output: capacity:
240VAC/10A (103% with delay timer of 1~10sec)
4-channel AST status relay output: capacity:
240VAC/10A (110%)
3-channel speed output channel
Measurement range: 1 ~ 20,000Hz. (DEH/MEH)
2oo3 logic Output (DNV

Certified SIL 3)

6-channel AI: 1~5V or 4~20mA, supplying power to


transducer (Power Load Unbalance Protection 3xTurbine Load and 3xGenerator Load)
Optoelectronic isolator is adopted with isolated voltage
more than 1500V.

Proprietary Information For Internal Use Only


General Electric Company 2007

31
June, 2006

SDP Speed Detection and Protection Card


A card combining functions of speed pulse signal and over-speed protection
24VDC

Main Characteristics

24VDC

2oo3 Selection

3-channel speed input channel


8-channel DI
4-channel OPC status relay output: capacity:
240VAC/10A (103% with delay timer of 1~10sec)
4-channel AST status relay output: capacity:
240VAC/10A (110%)

SDP1

SDP2

SDP1

SDP2

SDP3

SDP3

3-channel speed output channel


Measurement range: 1 ~ 20,000Hz. (DEH/MEH)
2oo3 logic Output (DNV

Certified SIL 3)

6-channel AI: 1~5V or 4~20mA, supplying power to


transducer (Power Load Unbalance Protection 3xTurbine Load and 3xGenerator Load)
Optoelectronic isolator is adopted with isolated voltage
more than 1500V.

OPC1

OPC1

20-1/OPC
Proprietary Information For Internal Use Only
General Electric Company 2007

OPC2

OPC2

20-2/OPC

OPC1

OPC2

VPC

EMU
32
June, 2006

SDP Speed Detection and Protection Card


A card combining functions of speed pulse signal and over-speed protection
Main Characteristics
3-channel speed input channel

Power Load Unbalance (PLU)

8-channel DI
4-channel OPC status relay output: capacity:
240VAC/10A (103% with delay timer of 1~10sec)

SDP_T
SDP_S
SDP_R

Ref=3000

4-channel AST status relay output: capacity:


240VAC/10A (110%)

WS1 +

3-channel speed output channel

1
dn=0~1

IEP0

Measurement range: 1 ~ 20,000Hz. (DEH/MEH)


PP IEP1
=P
==

2oo3 logic Output (DNV Certified SIL 3)


6-channel AI: 1~5V or 4~20mA, supplying power to
transducer (Power Load Unbalance) Protection 3xTurbine Load and 3xGenerator Load)

PP MW1
==
UI
=

dn
7%

107%
+
+

0~11

OPC
1

0~1 dMW1
PLU
dMW dn
+
OPC
30%60%
107
%
0~1

MW0

2/3
2/3

100
% 30%
60% dMW

Optoelectronic isolator is adopted with isolated voltage


more than 1500V.

Proprietary Information For Internal Use Only


General Electric Company 2007

33
June, 2006

SDP Speed Detection and Protection Card


A card combining functions of speed pulse signal and over-speed protection
24VDC

24VDC

2oo3 Selection
SDP_R

SDP_S

SDP_T

SDP1

SDP2

SDP1

SDP2

SDP3

SDP3

OPC2
AST2
SDP_TB
OPC1
AST1
SDP_TB

OPC1

2/3
OPC3
AST3
SDP_TB

2/3

OPC

2/3

OPC2

AST

OPC1

20-1/OPC
Proprietary Information For Internal Use Only
General Electric Company 2007

OPC2

20-2/OPC

OPC1

OPC2

VPC

EMU
34
June, 2006

LPC Logic Protection and Control Card


A card specially designed for turbine tripping logic control
Main Characteristics
24 channel DI, isolation voltage >1500V
6 channel DO, isolation voltage >1500V
Logic is configured and built in at Card Level
Able to be used in parallel to form redundant control
(1oo2, or 2oo3)
Output with extension relay TB, the contact capacity
is AC220V7A/DC30V4A.

V
N
D

Proprietary Information For Internal Use Only


General Electric Company 2007

ie
f
i
t
er

3
L
I
dS

35
June, 2006

LPC Logic Protection and Control Card


A card specially designed for turbine tripping logic control
Main Characteristics
24 channel DI, isolation voltage >1500V
6 channel DO, isolation voltage >1500V
Logic is configured and built in at Card Level
Able to be used in parallel to form redundant control (1oo2, or 2oo3)

C
V
N

ie
f
i
t
er

3
L
I
dS

Output with extension relay TB, the contact capacity is


AC220V7A/DC30V4A.
LPC_R1

LPC_S1

Vacuum
Low 1

LPC_T1

EH Low 1
LP1
LP2
LP3
LV1
LV2
LV3
LBO1
LBO2

LBO3
OS1
OS2
OS3
TBT1
TBT2
TBT3
TBG1

1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16

17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32

1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16

2oo3

2oo3

2oo3

LPC

17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32

LPC_R

2/3
2/3

TBG2
TBG3

Vacuum
Low 2

RP1
RP2
TEST1
TEST2

EH Low 2

TEST3
RESET

TRIP_11

Trip_11

Vacuum
Low 3

TRIP_12

Trip_21

EH Low 3

TRIP_13

Trip_31
Proprietary Information For Internal Use Only
General Electric Company 2007

LPC_S

2/3
2/3

2/3

LPC_T

2/3
2/3

36
June, 2006

SYN Synchronization Card


Designed for both Power Lines switching and Power Unit Synchronization
Main Characteristics
8 channels AC signal input with voltage of 0~1.2 VAC. AC sampling error is 0.5%
8 channel DI signals
12-chnanel DO signals: dry contact
High-speed 12-bit A/D converter
Modifying operating parameters online
Automatic or Manual Synchronization will be execute/allowed when
Voltage Difference between two AC signal <2V.
Period Difference between two AC signal <0.2ms
Frequency of two AC signal are in the range of 49.5Hz and 50.5Hz.
Phase Difference of two AC signal is in the range of 10 to 350

Proprietary Information For Internal Use Only


General Electric Company 2007

37
June, 2006

CAI Intelligent AC Card


Designed for sampling AC Voltage Current of Grid Line .
Direct PT/CT reading

Main Characteristics

Converts AC current signal @ 0~5A, 50 Hz to DC


Coverts AC Voltage signal @ 0~100V, 50 Hz to DC

Six-channel input of AC current signals: 0~5 AAC (50Hz)


Six-channel input of AC voltage signals: 0~100VAC (50Hz)
I/O transformation ratio:voltage 100V / 1V, current 10A / 1V
Output load resistance per channel: 1 MOhm
I/O phase difference: < 30'
Overload capacity: voltage 300 %, current 3000 %
Channel frequency respond: 25 Hz~5 kHz
Isolation voltage: 2500 V,1 min.

Proprietary Information For Internal Use Only


General Electric Company 2007

38
June, 2006

Features/Coverage and Benefits


Features
Synchronization
Interlocking
Standby Automatic Operation
Standby Power Supply Diesel Gen
Automatic Start
Breakers Interlocking

Coverage
Generator-Transformer Unit
Monitoring and Control of 6 KV or
6.6KV Bus System
Monitoring and 380 V Bus System
Monitoring and Control of DC and UPS
System

Benefits
Electrical Load Management
Boiler Master / Turbine Master Control

Proprietary Information For Internal Use Only


General Electric Company 2007

39
June, 2006

Proprietary Information For Internal Use Only


General Electric Company 2007

40
June, 2006

Proprietary Information For Internal Use Only


General Electric Company 2007

41
June, 2006

Proprietary Information For Internal Use Only


General Electric Company 2007

42
June, 2006

OC 4000TM MMI Layer SW Architecture


Optimization
SW
Operator SW
Historical
SW

Engineering
SW

Proprietary Information For Internal Use Only


General Electric Company 2007

Simulation SW

43
June, 2006

OC 4000TM Real Time Control SW Platform

High Stability, Continuous Operation and Failure Self recovery capability

High Compression capabilities, large storage and data management capabilities


Support Multi-Server, Server Redundancy or hot backup configuration
Proprietary Information For Internal Use Only
General Electric Company 2007

44
June, 2006

Real Time Data System

Proprietary Information For Internal Use Only


General Electric Company 2007

45
June, 2006

Graphic Display - Combustion System

Proprietary Information For Internal Use Only


General Electric Company 2007

46
June, 2006

Graphic Display Co-Ordinated Control

Proprietary Information For Internal Use Only


General Electric Company 2007

47
June, 2006

Trending

Proprietary Information For Internal Use Only


General Electric Company 2007

48
June, 2006

Enhanced Alarm Management


Multiple Alarm Limits
Alarm Filtering
Alarm areas
Alarm priority
Selection of Alarms
Alarm display
Alarm print
Alarm archiving
Acknowledgement of Alarm
Repeat Alarm for beyond limit
Repeat Alarm for over time
Change of alarm limits
turn off alarm
Restriction of alarm
Alarm related chart
Self-defined display
Proprietary Information For Internal Use Only
General Electric Company 2007

49
June, 2006

Diagnostic Function

Proprietary Information For Internal Use Only


General Electric Company 2007

50
June, 2006

Historical Data System


Historical data bank of OBase platform
Support more than 100,000 points per server
Scan time less than 100 ms
Dead band compression
Swinging door compression

Interface and storage buffer mechanism


Data storage structure optimization in archives
OLEDB Driver
Redundant System

Proprietary Information For Internal Use Only


General Electric Company 2007

51
June, 2006

DCS Simulator
SIMPANEL
SIMPANEL includes,
includes,
1.
1.

Coal-fired
Coal-fired 100MW
100MW and
and below,
below, 125~330MW
125~330MW unit,
unit, Supercritical
Supercritical Unit;
Unit;

2.
2.

CFB
CFB boiler
boiler unit;
unit;

3.
3.

Combine-cycle
Combine-cycle unit;
unit;

SIMPANEL simulates the 4 parts of different domains,


1.
1.

Boiler
Boiler side
side (Nuclear
(Nuclear included):
included):

Combustion
Combustion system/Primary
system/Primary and
and secondary
secondary air
air system
system

Boiler
Boiler system/Pulverization
system/Pulverization system/Waste
system/Waste heat
heat boiler
boiler system,
system, etc.
etc.

2.
2.

Turbine
Turbine side
side (Gas
(Gas turbine
turbine included):
included):

Turbine
Turbine system/Condensate
system/Condensate system/Heater
system/Heater system
system

Circulating
Circulating system/Lubricate
system/Lubricate oil
oil system/Gland
system/Gland sealing
sealing system,
system, etc.
etc.

3.
3.

Electric
Electric side:
side:

Generator
Generator and
and transformer
transformer system/House
system/House power
power system
system

Direct
Direct current
current system/UPS
system/UPS system/Emergency
system/Emergency power
power supply
supply system,
system, etc.
etc.

4.
4.

Control
Control side:
side:

AA complete
complete copy
copy of
of site-DCS,
site-DCS, includes
includes DEH,
DEH, CCS,
CCS, DAS,
DAS, BPS,
BPS, etc.
etc.
Proprietary Information For Internal Use Only
General Electric Company 2007

52
June, 2006

Features of Simulator
1.

Simulation based learning and Training

2.

Training sessions for operators to experience cold, warm or hot start-up, shutdown,
normal, abnormal, emergency and malfunction conditions

Simulation based Troubleshooting

Identify equipment malfunction or operational mistakes and conduct targeted antiaccident drilling to improve the operating capability (directly playing the historian data
of site-DCS back into SIMPANEL)

3.

Simulation based Control and Optimization

Initial design and development for DCS GUI and logic configuration.

Control analysis, configuration tuning and optimization

Model-based optimization algorithms research

Close-loop optimization control testing

Trainer

Proprietary Information For Internal Use Only


Simulator
GeneralorElectric
Company 2007
MSP

53
June, 2006

Bi-directional Loading and Easy Updating


SIMPANEL
SIMPANEL has
has the
the same
same software
software as
as site-DCS,
site-DCS, and
and uses
uses the
the exact
exact DCS
DCS graphics
graphics and
and
configuration
configuration..
1.
1.

Both
Both graphics
graphics and
and configuration
configuration can
can easily
easily be
be transferred
transferred bi-directionally
bi-directionally between
between
simulator
simulator and
and site-DCS;
site-DCS;

2.
2.

No
No modification
modification or
or translation
translation when
when the
the development
development of
of new
new controls
controls loading
loading to
to
simulator
simulator or
or uploading
uploading to
to the
the plant.
plant.

Proprietary Information For Internal Use Only


General Electric Company 2007

54
June, 2006

Simulator

Simulation
Simulation can
can take
take advantages
advantages of
of virtual-DCS
virtual-DCS technology
technology by,
by,
1.
1.

The
The same
same hardware
hardware as
as site-DCS,
site-DCS, so
so the
the DCS
DCS components
components (DPU,
(DPU, card,
card, etc.)
etc.) can
can be
be
inserted
inserted into
into integrative
integrative minimized
minimized DCS
DCS system
system (Mini-DCS)
(Mini-DCS) for
for the
the purpose
purpose of
of diagnosis
diagnosis
or
or testing;
testing;

2.
2.

The
The same
same software
software as
as site-DCS,
site-DCS, so
so the
the GUI
GUI displays,
displays, logic
logic configuration
configuration in
in simulation
simulation
system
system can
can be
be updated
updated synchronously;
synchronously;

3.
3.

The
The same
same distributed
distributed structure
structure as
as site-DCS,
site-DCS, which
which utilizes
utilizes virtual
virtual DPUs
DPUs to
to conduct
conduct
distributed
distributed calculation
calculation more
more efficiently
efficiently than
than any
any expensive
expensive server,
server, and
and makes
makes cococommissioning
commissioning feasible.
feasible.
HMI

HMI

...

HMI

HMI

DPU

...

HMI

...

HMI
Human Machine Interface

DPU

Industrial Site
Distributed Control System

VDPU

VDPU

...

Virtual Industrial Site

IHMI
IHMI
Instructor Station

Real- time Network

Real- time Network

DPU

HMI

VDPU

SDPU

...

Virtual DCS

DPU / VDPU
Distributed Process Unit
Virtual DPU

SDPU

SDPU
Simulated DPU

Distributed Simulation
System
Proprietary Information
For Internal Use
Only based on Virtual DCS
General Electric Company 2007

55
June, 2006

Diagnostic Function
System 9
DPU

Four level diagnostic


information from
system to channel

I/O Card

Channel

Alarm and Log of malfunction


for those four level
Proprietary Information For Internal Use Only
General Electric Company 2007

56
June, 2006

Diagnostic Function - DPU

Proprietary Information For Internal Use Only


General Electric Company 2007

57
June, 2006

Diagnostic Function - Network

Proprietary Information For Internal Use Only


General Electric Company 2007

58
June, 2006

International certifications
ISO9000
FCC
(Federal Communications Commission)
CE
(Conformit Europenne)
CSA

(Canadian Standards Association)

I/O modules are designed to meet:

IEC61000-4-2
IEC61000-4-3
IEC61000-4-4
IEC61000-4-5
IEC61000-4-6
IEC61000-4-11
EN55022

Electrostatic Discharge Requirements


Radiated Electromagnetic Field Requirements
Electrical Fast Transient/Burst Requirements
Surge
Conducted Disturbances
Voltage Dips, Short Interruptions and Voltage Variations
Conducted Disturbance voltage emission and Radiated
Disturbance electromagnetic field

TUV - SIL 3
GOST

(Technischen Uberwachungsvereine, Germany)


(Russia)
Proprietary Information For Internal Use Only
General Electric Company 2007

59
June, 2006

Experience Summary
Total Systems Installed
Power Generation

2492 sets

Boiler Control Systems

728 sets

Turbine Controls Systems

1064 sets

BOP Control Systems

313 sets

Optimization Software

57 sets

CFB Boilers

144 sets

FGD Control Systems

60 sets

Power Plant Simulation

30 sets

Other Industries

94 sets

Proprietary Information For Internal Use Only


General Electric Company 2007

60
June, 2006

System Organization of 300MW coal unit


1

21

DEH Base Control

11

31

Condensate, LP HTR System

22

ATC Control

12

32

A FWP Turbine, Electric FW Pump,


Feed Water and DEA, HP HTR SYS

TSCS
3

23

A FWP Turbine MEH

13

33

24

B FWP Turbine MEH

14

34

(Generally one couple of DPU)

25

ETS

15

35

(Generally no specific DPU, shared


with TSCS)

26

BPC

16

36

17

37

18

38

CCS, Fuel, Flue Gas,


Secondary Air SYS Control

19

39

Feed Water, Steam Temperature,


Milling, Auxiliary Air SYS Control

20

40

Reserved

DEH

TDAS

TMCS
7

27

G-T, HV Unit Trans

28

6KV, 380V Circuit-Breaker

29

Reserved

10

30

Reserved

ECS

BMCS

B FWP Turbine, Vacuum, Drainage,


Lube Oil, EH Oil, Circulating WTR SYS

DEA, HP/LP HTR, and Condenser WTR


Level, Other Single Circuit SYS Control
(Generally one couple of DPU)

Proprietary Information For Internal Use Only


General Electric Company 2007

61
June, 2006

System Organization of 300MW coal unit


BSCS

BDAS

61

81

A-Side Flue Gas, Feed Water, ATTE, PCV Valve, DRUM-EMER System

62

82

B-Side Flue Gas, Drainage Water and Blow-down System

63

83

Reserved (for Desulfuration System of unit)

64

84

Reserved

65

85
(Generally no specific DPU, shared with BSCS)

66

86

67

87

68

88

69

89

70

90

FSSS
Details can be referred to Table 1

Sootblowing System, or Communication

Proprietary Information For Internal Use Only


General Electric Company 2007

62
June, 2006

System Organization of 300MW coal unit


41

Operator
Station

Large Video
Screen

OPU 2

43

OPU 3

44

OPU 4

45

OPU 5

52

ENG2(Reserved)

53

HSU1

54

HSU2(Reserved)

55

GW1

56

GW2

Performance
Calculating Station 57

PCU

SIS Interface
Station

58

SIS GW

59

Reserved

60

SLU

History
Station

Multi-Interface
Station

46

OPU 6

47

LD 1

48

LD 2

49

Reserved

50

ENG1

Engineer
Station

OPU 1

42

51

Reserved
Shift Leader
Station

80
Proprietary Information For Internal Use Only
General Electric Company 2007

DEH Simulator

63
June, 2006

System Organization of 300MW coal unit


(100-110 Reserved)
71

91

Startup-standby Trans/Common Section


PS/Common MCC

72

92

(Generally one couple of DPU)

93

Air compressor/Air conditioner


/Oil Pump station

COM ECS

73
COM System
74

Circulating
Water
Pump SYS

Gateway

75
76

94

Reserved

95

A/B CWP remote control

96

(Generally one couple of DPU)


C/D CWP remote control

111

NCU1

112

NCU2

113

NCU3

114

NCU4

Gateway

(115-120 Reserved)

77

97

Interface between COM System


and Unit System
ASDPU

78

98

79

99

121

COM ENG

122

COM HSU

123

COM MMI

COM GW1

124

COM GW2

Reserved

125

COM OPU1

Reserved

126

COM OPU2
(127 Reserved)

Proprietary Information For Internal Use Only


General Electric Company 2007

64
June, 2006

System Organization of 300MW coal unit


Table 1
Applicable to Storage Pulverized-coal Boiler, Coal Burners =<6 Layers(groups)
2 Units of DPU for Burner Management System, the Other 2 Units of DPU for Milling System
66
67
68
69

Protection and FSSS Miscellaneous Logic, One Layer(group) Oil Burner, Two Layers(groups) Coal Burners
Two Layers(groups) or Less Oil Burners, Four Layers(groups) or Less Coal Burners
Two Units of Milling System(A&B)
Two Units of Milling System(C&D)

Applicable to Direct Firing Boiler, Coal Burners/Pulverizers=<5 Layers(groups) , 3 Couples of DPU


66
67
68

Protection and FSSS Miscellaneous Logic, One Layer(group) or Less Oil Burner, One Layer(group) Coal
Burner/Pulverizer
One Layer(group) or Less Oil Burner, Two Layers(groups) Coal Burners/Pulverizers
One Layer(group) or Less Oil Burner, Two Layers(groups) Coal Burners/Pulverizers

Applicable to Direct Firing Boiler, Coal Burner/Pulverizer =<6 Layers(groups)


66
67
68
69

Protection and FSSS Miscellaneous Logic


One Layer(group) or Less Oil Burner, Two Layers(groups) Coal Burners/Pulverizers
One Layer(group) or Less Oil Burner, Two Layers(groups) Coal Burners/Pulverizers
One Layer(group) or Less Oil Burner, Two Layers(groups) Coal Burners/Pulverizers
CFB or Specific Boiler Can Be Referred to the Above Configuration
Proprietary Information For Internal Use Only
General Electric Company 2007

65
June, 2006

Network Design
(222.222.223.X)
41

42

43

44

45

51

OPU1 OPU2 OPU3 OPU4 OPU5

53

ENG

HSU

DCS03

1B-1
1A-1

57

GW1

NCU1

PCAL

A? (222.222.221.X)

1A-5
1B-5

55

111

B? (222.222.222.X)

DPU DPU
1/21 2/22

DPU DPU
3/23 4/24

DPU DPU
7/27 8/28

DEH

MEH

ECS

1A-2

1A-4
1B-4

MCS07

1B-3
SCS01

DPU DPU DPU DPU DPU DPU


11/31 12/32 13/33 15/35 16/36 17/37
TSCS

TDAS

DPU DPU DPU


66/86 67/87 68/88

NCU
2

1B-2
DCS01

FSSS

112

TMCS

Proprietary Information For Internal Use Only


General Electric Company 2007

1A-3

? SCS10

DPU DPU DPU DPU DPU


18/38 19/39 61/81 62/82 65/85
BMCS

BSCS

BDAS
66
June, 2006

Coal Fired DCS Earthing Scheme


DEH01 DEH02 DEH03 DEH04 MEH01 MEH02 MCS01 MCS02 MCS03 MCS04

P

MCS05 MCS06 MCS07 MCS08 FSSS01 FSSS02 FSSS03 FSSS04 FSSS05 FSSS06

P

SCS01 SCS02 SCS03 SCS04 SCS05 SCS06 SCS07 DAS01 DAS02 DCS01

SCS08 SCS09 SCS10 SCS11 SCS12 SCS13 SCS14 DAS03 DAS04 DCS02

ENG

HSU

PCAL

OPU1

OPU2

OPU3

GW1

GW2

CENG

ECS01 ECS02 ECS03 ECS04 COM01 COM02 COM03 COM04


>20mm2
OPU5

NCU

OPU4

SLU

IO

IO

TR01

BR01

DPU

COM06 COM07 UPS



P

>20mm2

Proprietary Information For Internal Use Only


General Electric Company 2007
>90mm2

67
June, 2006

Back up

Proprietary Information For Internal Use Only


General Electric Company 2007

68
June, 2006

Proprietary Information For Internal Use Only


General Electric Company 2007

69
June, 2006

Traditional Mechanical Governor


Proprietary Information For Internal Use Only
General Electric Company 2007

70
June, 2006

Traditional
Mechanical
Governor

Removal of Mechanical Linkages


Proprietary Information For Internal Use Only
General Electric Company 2007

71
June, 2006

EHIV
Electro
Hydraulic
Interface
Hydraulic Unit

To U
nit C
ontr
ol

Retrofitted Electro Hydraulic Governor


Proprietary Information For Internal Use Only
General Electric Company 2007

72
June, 2006

Traditional Mechanical Governor


Proprietary Information For Internal Use Only
General Electric Company 2007

73
June, 2006

Traditional
Mechanical
Governor

Proprietary Information For Internal Use Only


General Electric Company 2007

74
June, 2006

li
au
dr
Hy
cU

EHIV
Electro
Hydraulic
Interface

To Unit Control

nit

Retrofitted Electro Hydraulic Governor


Proprietary Information For Internal Use Only
General Electric Company 2007

75
June, 2006