You are on page 1of 1

Auto Reclose relay settings on ER make SEL311C type Distance relay at 220kV

Chittoor Substation on 220kV Thiruvellam feeders 1 & 2


==================================================
==================
Sl.N
o
1.

Parameter
Reclosures E79

Existing

Revised

Y
(Permissive Under
Reach Scheme)

2.

Communication assisted trip scheme


(ECOMM)

3.

Phase Distance Setting Z3P

13.83

0.95

4.

Reactive reaches (Secondary) XG3

13.75

0.94

5.

Resistive reaches (Secondary) RG3

23.82

4.41

6.

Zone-3 time delay Z3PD,Z3GD,Z3D

30 Cycles,
(0.60 Sec)

50 Cycles, (1.0Sec)

7.

Zone/level 3 direction Dir3

You might also like