Electrical Transient Analyzer Program


Short-Circuit Analysis
IEC 60909 Standard
3-Phase, LG, LL, & LLG Fault Currents

Swing

V-Control

Load

Total

XFMR2

XFMR3

Reactor

Line/Cable

Impedance

Tie PD

Total

Synchronous
Generator

Power
Grid

Synchronous
Motor

Induction
Machines

Lumped
Load

Total

Number of Machines:

System Frequency:

60.00 Hz

Unit System:

English

Project Filename:

NEWWORLD

Output Filename:

H:\NEWWORLD\Untitled.ST2

Number of Buses:

Number of Branches:

ETAP

Project:

12.6.0H

Location:
Contract:

2
11-15-2016

SN:

Engineer:
Filename:

Page:
Date:

Study Case: SM

NEWWORLD

Adjustments
Apply
Tolerance

Individual

Adjustments

/Global

Transformer Impedance:

Yes

Individual

Reactor Impedance:

Yes

Individual

Overload Heater Resistance:

No

Transmission Line Length:

No

Cable Length:

No

Apply
Temperature Correction

Percent

Individual

Adjustments

/Global

Transmission Line Resistance:

Yes

Individual

Cable Resistance:

Yes

Individual

Degree C

Revision:

Base

Config.:

Normal

ETAP

Project:

12.6.0H

Location:
Contract:

3
11-15-2016

SN:

Engineer:
Filename:

Page:
Date:

Study Case: SM

NEWWORLD

Bus Input Data

Bus
ID

Type

Initial Voltage
Nom. kV

Base kV

Sub-sys

%Mag.

Ang.
0.00

Bus1

Load

22.900

22.900

100.00

Bus2

Load

22.900

22.900

100.00

0.00

Bus4

Load

0.380

0.380

100.00

180.00

Bus5

SWNG

22.900

22.900

100.00

0.00

4 Buses Total
All voltages reported by ETAP are in % of bus Nominal kV.
Base kV values of buses are calculated and used internally by ETAP .

Revision:

Base

Config.:

Normal

ETAP

Project:

12.6.0H

Location:
Contract:

4
11-15-2016

SN:

Engineer:
Filename:

Page:
Date:

Study Case: SM

NEWWORLD

Revision:

Base

Config.:

Normal

Line/Cable Input Data

Ohms or Siemens per 1000 ft per Conductor (Cable) or per Phase (Line)
Line/Cable
ID
Cable1

Length
Library
33MCUS1

Size
50

Line / Cable resistances are listed at the specified temperatures.

Adj. (ft)
984.3

% Tol.
0.0

#/Phase
1

T (C)
75

R1

X1

Y1

R0

0.143611

0.0585216

0.0000159

0.4523748

X0
0.1439631

Y0

ETAP

Project:

12.6.0H

Location:
Contract:

5
11-15-2016

SN:

Engineer:
Filename:

Page:
Date:

Study Case: SM

NEWWORLD

Revision:

Base

Config.:

Normal

2-Winding Transformer Input Data

Transformer
ID
T1

Rating
MVA
1.250

Prim. kV
22.900

Sec. kV

Z Variation
%Z

0.380

X/R

5.00

3.50

% Tap Setting

+ 5%

- 5%

% Tol.

Prim.

Sec.

Adjusted

Phase Shift

%Z

Type

Angle

5.0000

YNyn

180.000

2-Winding Transformer Grounding Input Data


Grounding
Transformer
ID
T1

Rating
MVA
1.250

Prim. kV
22.900

Conn.
Sec. kV

Type

0.380

Y/Y

Primary
Type
Solid

kV

Secondary
Amp

Ohm

Type
Solid

kV

Amp

Ohm

ETAP

Project:

12.6.0H

Location:
Contract:

6
11-15-2016

SN:

Engineer:
Filename:

Page:
Date:

Study Case: SM

NEWWORLD

Revision:

Base

Config.:

Normal

Branch Connections
CKT/Branch

Connected Bus ID

ID

Type

From Bus

% Impedance, Pos. Seq., 100 MVAb


To Bus

T1

2W XFMR

Bus2

Bus4

106.54

372.89

387.81

Cable1

Cable

Bus1

Bus2

2.70

1.10

2.91

CB1

Tie Breakr

Bus5

Bus1

0.0081934

ETAP

Project:

12.6.0H

Location:
Contract:

7
11-15-2016

SN:

Engineer:
Filename:

Page:
Date:

Study Case: SM

NEWWORLD

Revision:

Base

Config.:

Normal

Power Grid Input Data

Power Grid

Connected Bus

ID
U1

ID
Bus5

Total Connected Power Grids ( = 1 ): 435.000 MVA

% Impedance
100 MVA Base

Rating
MVASC

kV

435.000

22.900

R
22.87442

X"
2.28744

Grounding
R/X"
10.00

Type
Wye - Solid

ETAP

Project:

12.6.0H

Location:
Contract:

Page:

Date:

11-15-2016

SN:

Engineer:
Filename:

Study Case: SM

NEWWORLD

Revision:

Base

Config.:

Normal

SHORT- CIRCUIT REPORT


Fault at bus

Bus1

Nominal kV

22.900

Voltage c Factor

= 1.10 (User-Defined)
Line-To-Line-To-Ground Fault

Contribution

% Voltage at From Bus

From Bus

To Bus

ID

ID

Va
Mag.

Current at From Bus (kA)

Vb
Ang.

Mag.
0.00

Vc
Ang.

Bus1

Total

100.00

0.0

0.0

Bus2

Bus1

100.00

0.0

0.00

0.0

U1

Bus5

100.00

0.0

100.00

-120.0

Bus4

Bus2

33.33

180.0

66.67

0.0

Bus5

Bus1

100.00

0.0

0.00

0.0

# Indicates fault current contribution is from three-winding transformers


* Indicates a zero sequence fault current contribution (3I0) from a grounded Delta- Y transformer

Mag.
0.00

Ia
Ang.

Mag.

Ib
Ang.

Ic

Sequence Current (kA)

Mag.

Ang.

Mag.

Ang.

I1

I2

I0

10.967

-125.7

10.967

114.3

7.311

3.656

3.656

0.0

0.000

0.0

0.00

0.0

0.000

0.0

0.000

0.0

0.000

0.0

0.000

0.000

0.000

100.00

120.0

0.000

0.0

10.967

-125.7

10.967

114.3

7.311

3.656

3.656

66.67

0.0

0.000

0.0

0.000

0.0

0.000

0.0

0.000

0.000

0.000

0.00

0.0

0.000

0.0

10.967

-125.7

10.967

114.3

7.311

3.656

3.656

ETAP

Project:

12.6.0H

Location:
Contract:

Page:

Date:

11-15-2016

SN:

Engineer:
Filename:

Study Case: SM

NEWWORLD

Fault at bus

Bus2

Nominal kV

22.900

Voltage c Factor

Revision:

Base

Config.:

Normal

= 1.10 (User-Defined)
Line-To-Line-To-Ground Fault

Contribution

% Voltage at From Bus

From Bus

To Bus

ID

ID

Va
Mag.

Current at From Bus (kA)

Vb

I2

I0

0.0

0.000

0.0

9.513

-124.4

9.649

109.2

6.378

3.495

2.883

100.00

0.0

13.42

-128.3

14.60

152.1

0.000

0.0

9.513

-124.4

9.649

109.2

6.378

3.495

2.883

35.40

-179.6

70.80

0.4

70.80

0.4

0.000

0.0

0.000

0.0

0.000

0.0

0.000

0.000

0.000

Bus5

100.00

0.0

100.00

-120.0

100.00

120.0

0.000

0.0

9.513

-124.4

9.649

109.2

6.378

3.495

2.883

Bus1

100.00

0.0

13.42

-128.3

14.60

152.1

0.000

0.0

9.513

-124.4

9.649

109.2

6.378

3.495

2.883

Bus2

Bus4

Bus2

U1
Bus5

# Indicates fault current contribution is from three-winding transformers


* Indicates a zero sequence fault current contribution (3I0) from a grounded Delta- Y transformer

Ang.

Mag.

Ang.

Mag.

Ang.

Mag.

Sequence Current (kA)

0.00

Bus1

Mag.

Ic

0.0

106.21

Ang.

Ib

0.00

Total

Mag.

Ia

0.4

Bus2

Ang.

Vc

Ang.

I1

ETAP

Project:

12.6.0H

Location:
Contract:

Page:

10

Date:

11-15-2016

SN:

Engineer:
Filename:

Study Case: SM

NEWWORLD

Fault at bus

Bus4

Nominal kV

0.380

Voltage c Factor

Revision:

Base

Config.:

Normal

= 1.05 (User-Defined)
Line-To-Line-To-Ground Fault

Contribution

% Voltage at From Bus

From Bus

To Bus

ID

ID

Va
Mag.

Current at From Bus (kA)

Vb
Ang.

Mag.

Vc
Ang.

Mag.

Ia
Ang.

Mag.

Ib
Ang.

Ic

Mag.

Ang.

Mag.

Sequence Current (kA)


Ang.

I1

I2

I0

Bus4

Total

100.29

-0.2

0.00

0.0

0.00

0.0

0.000

0.0

39.988

169.9

39.707

49.6

26.565

13.340

13.225

Bus2

Bus4

97.66

-177.3

94.08

61.1

102.15

-56.6

0.000

0.0

39.988

169.9

39.707

49.6

26.565

13.340

13.225

Bus1

Bus2

98.25

-177.8

94.93

61.4

101.63

-57.0

0.439

110.1

0.583

30.5

0.585

-171.2

0.441

0.221

0.219

U1

Bus5

100.00

-180.0

100.00

60.0

100.00

-60.0

0.439

110.1

0.583

30.5

0.585

-171.2

0.441

0.221

0.219

Bus1

Bus5

98.25

-177.8

94.93

61.4

101.63

-57.0

0.439

-69.9

0.583

-149.5

0.585

8.8

0.441

0.221

0.219

# Indicates fault current contribution is from three-winding transformers


* Indicates a zero sequence fault current contribution (3I0) from a grounded Delta- Y transformer

ETAP

Project:

12.6.0H

Location:
Contract:

Page:

11

Date:

11-15-2016

SN:

Engineer:
Filename:

Study Case: SM

NEWWORLD

Fault at bus

Bus5

Nominal kV

22.900

Voltage c Factor

Revision:

Base

Config.:

Normal

= 1.10 (User-Defined)
Line-To-Line-To-Ground Fault

Contribution

% Voltage at From Bus

From Bus

To Bus

ID

ID

Va
Mag.

Current at From Bus (kA)

Vb
Ang.

Mag.

Vc
Ang.

Mag.

Ia
Ang.

Mag.

Ib
Ang.

Ic

Sequence Current (kA)

Mag.

Ang.

Mag.

Ang.

I1

I2

I0

7.311

3.656

3.656

Bus5

Total

100.00

0.0

0.00

0.0

0.00

0.0

0.000

0.0

10.967

-125.7

10.967

114.3

U1

Bus5

100.00

0.0

100.00

-120.0

100.00

120.0

0.000

0.0

10.967

-125.7

10.967

114.3

7.311

3.656

3.656

Bus2

Bus1

100.00

0.0

0.00

0.0

0.00

0.0

0.000

0.0

0.000

0.0

0.000

0.0

0.000

0.000

0.000

Bus4

Bus2

33.33

180.0

66.67

0.0

66.67

0.0

0.000

0.0

0.000

0.0

0.000

0.0

0.000

0.000

0.000

Bus5

Bus1

100.00

0.0

0.00

0.0

0.00

0.0

0.000

0.0

0.000

0.0

0.000

0.0

0.000

0.000

0.000

# Indicates fault current contribution is from three-winding transformers


* Indicates a zero sequence fault current contribution (3I0) from a grounded Delta- Y transformer

ETAP

Project:

12.6.0H

Location:
Contract:

12
11-15-2016

SN:

Engineer:
Filename:

Page:
Date:

Study Case: SM

NEWWORLD

Revision:

Base

Config.:

Normal

Short-Circuit Summary Report


3-Phase, LG, LL, LLG Fault Currents
Bus
ID

3-Phase Fault
kV

Bus1

22.900

Bus2
Bus4
Bus5

I"k

Line-to-Ground Fault

ip

Ik

10.967

15.820

10.967

22.900

9.873

14.241

0.380

39.905

76.517

22.900

10.967

15.820

10.967

ip

Ib
10.967

Ik

10.967

15.820

9.873

9.221

13.301

9.221

39.905

39.790

76.296

39.790

10.967

15.820

10.967

10.967

All fault currents are in rms kA. Current ip is calculated using Method C.
* LLG fault current is the larger of the two faulted line currents.

I"k

Line-to-Line Fault

10.967

I"k

ip

*Line-to-Line-to-Ground

Ib

Ik

9.498

9.498

9.498

13.701

9.221

8.550

12.333

8.550

39.790

34.559

66.266

34.559

9.498

13.701

9.498

9.498

I"k

ip

Ib
10.967

Ik

10.967

15.820

10.967

8.550

9.649

13.919

9.649

9.649

34.559

39.988

76.675

39.988

39.988

10.967

15.820

10.967

10.967

ETAP

Project:

12.6.0H

Location:
Contract:

13
11-15-2016

SN:

Engineer:
Filename:

Page:
Date:

Study Case: SM

NEWWORLD

Revision:

Base

Config.:

Normal

Sequence Impedance Summary Report


Bus
ID

Positive Seq. Imp. (ohm)


kV

Negative Seq. Imp. (ohm)

Zero Seq. Imp. (ohm)

Fault Zf (ohm)

Resistance

Reactance

Impedance

Resistance

Reactance

Impedance

Resistance

Reactance

Impedance

Resistance

Reactance

Impedance

Bus1

22.900

1.31951

0.13195

1.32609

1.31951

0.13195

1.32609

1.31951

0.13195

1.32609

0.00000

0.00000

0.00000

Bus2

22.900

1.46086

0.18955

1.47311

1.46086

0.18955

1.47311

1.76476

0.27365

1.78585

0.00000

0.00000

0.00000

Bus4

0.380

0.00194

0.00544

0.00577

0.00194

0.00544

0.00577

0.00202

0.00546

0.00582

0.00000

0.00000

0.00000

Bus5

22.900

1.31951

0.13195

1.32609

1.31951

0.13195

1.32609

1.31951

0.13195

1.32609

0.00000

0.00000

0.00000

You might also like