You are on page 1of 4

TTR 4x.

xx

Indoor bushing current transformers

Highest voltage for equipment


[kV]
Power frequency test voltage, 1 min.
[kV]
Lighting impulse test voltage
[kV]
Rated continous thermal current
[A]
Rated short-time thermal current
[A]
Burdens, classes
[VA/cl]
Reconnectible

12
28
75
100 - 2500
60 -100
5- 30 / 0.2 - 1/5P; 10P
Secondary reconnectible
for 1 core type

Description
The TTR 4x.xx current transformers are casted in epoxi resin and designed for insulation voltages up to 12 kV.
The TTR 4x.xx transformers are configurated as bar-type, with only one or more ratios (secondary side to be
changeover) and perform the function of a bushing when installed in the switchboard.
The transformer is designed with either 1 or 2 secondary windings and, depending on the combination of
parameters (accuracy class, burden, short-circuit current, overcurrent factor) with the possibility to choose from
various sizes of the transformer.
The secondary windings are used for measurement or protection purposes. One terminal of each secondary winding
in use and one terminal of short-circuited and not used winding have to be earthed during the transformer operation.
The secondary windings are lead out into a casted-type secondary terminal board, covered with plastic cover which
may be sealed.
The transformer can be mounted in any position. The transformer position is fixed by using four screws.

Rated primary voltage ...3.6 kV; 7.2 kV; 12 kV


Rated primary currents 100;150;200;300;400;500;600;750;1000;1250;1500;2000;2500 A
Primary currents different from the above can also be agreed upon with the customer.
Rated secondary currents...5 A; 1 A (possibility to combine different values in one transformer)
Rated frequency ... 50 Hz; 60 Hz
The transformers are manufactured conformably to the following requirements and standards: IEC, VDE, ANSI, BS,
GOST and SN

Basic marking
TTR
1...up
2...up
3...up
4...up
5...up
6...up

to
to
to
to
to
to

600 A (smaller parameters)


600 A (higher parameters)
1250 A
1500 A
2000 A
2500 A

Insulation levels of TTR 4x.xx transformer


3.6 / 21 / 45 kV
7.2 / 27 / 60 kV
3.6 / 10 / 40 kV
7.2 / 20 / 60 kV

x
1...bar-type outlet

1...model series

12 / 28 / 75 kV
12 / 35 / 75 kV

Dimensions

Insulation

Type

voltage [kV]

12

TTR
TTR
TTR
TTR
TTR
TTR

41.11
42.11
43.11
44.11
45.11
46.11

Rated current

Dimensions

[A]

to 600
to 300
750-1250
1500
2000
2500

402
500
472
482
482
502

214
214
214
252
252
252

170
170
170
208
208
208

120
220
120
120
120
120

162 60
162 60
162 95
162 100
162 100
162 110

Weight

Hy

XI

XJ

XL

[kg]

30
30
30
30
30
30

16
16
20
16
20
20

6
6
10
20
20
20

71
71
71
110
110
110

156
156
156
192
192
192

136
136
136
174
174
174

160
160
160
196
196
196

10.0
17.0
11.0
15.0
21.0
24.0

Marking of current transformer outlets

a) Single-core design

b) Double-core design

d) Single-core design,
reconnectable on the secondary side

e) Double-core design,
reconnectable on the secondary side

c) Three-core design

Standartized transformers
Type Ratio
[A]

I thn
[ kA ]

Burden
[ VA ]

accuracy

FS/ALF

Type Ratio
[A]

41.11
41.11
41.11
41.11
41.11
41.11
41.11
41.11
41.11
41.11
41.11
41.11
41.11
41.11
41.11
41.11
41.11
41.11
41.11
41.11
41.11
41.11
41.11
41.11
41.11
41.11
41.11
41.11
41.11
41.11
41.11
41.11
41.11
41.11
41.11
41.11
41.11
41.11
41.11
41.11
41.11
41.11
41.11
41.11
41.11
41.11
41.11
41.11
41.11
41.11
41.11
41.11
41.11
41.11
41.11
41.11
41.11
41.11
41.11
41.11
41.11

60
60
60
60
60
60
60
60
60
60
60
60
60
60
60
60
60
60
60
60
60
60
60
60
60
60
60
60
60
60
60
60
60
60
60
60
60
60
60
60
60
60
60
60
60
60
60
60
60
60
60
60
60
60
60
60
60
60
60
60
60

5
15
10
5
15
5
10
10
15
5
10
15
30
5
15
10/10
5/10
15
45
10
15
5/5
5/10
10/5
10/10
30
60
5
15
5/5
5/10
10/5
10/10
30
60
15
30
10/5
10/15
15/5
15/15
30
90
15
30
15/5
15/10
15/15
15/5
15/10
15/15
30
120
15
30
15/5
15/10
15/30
30/5
30/10
30/30

1
3
10P
1
3
10P
10P
0,5
3
10P
10P
0,5
3
10P
10P
3/10P
0.5/10P
0.5
3
10P
10P
0.5/10P
0.5/10P
3/10P
3/10P
0.5
3
5P
5P
0.5/10P
0.5/10P
3/10P
3/10P
0.5
1
5P
5P
0.5/10P
0.5/10P
3/10P
3/10P
0.5
1
5P
5P
0.5/5P
0.5/5P
0.5/5P
3/5P
3/5P
3/5P
0.5
1
5P
5P
0.5/5P
0.5/5P
0.5/5P
5/5P
5/5P
5/5P

5
5
5
5
5
10
5
5
5
10
5
5
5
15
5
5/5
5/5
5
5
10
5
5/10
5/5
5/10
5/5
5
5
25
10
5/10
5/5
5/10
5/5
5
5
10
5
5/15
5/5
5/15
5/5
5
5
15
5
5/20
5/10
5/5
10/20
10/10
10/5
5
5
15
10
10/20
10/10
10/5
5/20
5/10
5/5

42.11
42.11
42.11
42.11
42.11
42.11
42.11
42.11
42.11
42.11
42.11
42.11
42.11
42.11
42.11
42.11
42.11
42.11
42.11
42.11
42.11
42.11
42.11
42.11
42.11
42.11
42.11
42.11
42.11
42.11
42.11
42.11
42.11
42.11
42.11
42.11

100//5
100//5
100//5/5
100//5/5
100//5/5
100//5/5
125//5
125//5
125//5/5
125//5/5
125//5/5
125//5/5
150//5
150//5
150//5/5
150//5/5
150//5/5
150//5/5
200//5
200//5
200//5/5
200//5/5
200//5/5
200//5/5
250//5
250//5
250//5/5
250//5/5
250//5/5
250//5/5
300//5
300//5
300//5/5
300//5/5
300//5/5
300//5/5

43.11
43.11
43.11
43.11
43.11
43.11
43.11
43.11
43.11
43.11
43.11

100//5
100//5
100//5
125//5
125//5
125//5
125//5
150//5
150//5
150//5
150//5
200//5
200//5
200//5
200//5
200//5/5
200//5/5
250//5
250//5
250//5
250//5
250//5/5
250//5/5
250//5/5
250//5/5
300//5
300//5
300//5
300//5
300//5/5
300//5/5
300//5/5
300//5/5
400//5
400//5
400//5
400//5
400//5/5
400//5/5
400//5/5
400//5/5
500//5
500//5
500//5
500//5
500//5/5
500//5/5
500//5/5
500//5/5
500//5/5
500//5/5
600//5
600//5
600//5
600//5
600//5/5
600//5/5
600//5/5
600//5/5
600//5/5
600//5/5

I thn
[ kA ]

Burden
[ VA ]

accuracy

FS/ALF

60
60
60
60
60
60
60
60
60
60
60
60
60
60
60
60
60
60
60
60
60
60
60
60
60
60
60
60
60
60
60
60
60
60
60
60

10
15
5/5
5/10
15/5
15/10
10
15
5/5
5/10
15/5
15/10
15
30
10/5
10/15
15/5
15/15
15
30
15/10
15/15
15/10
15/15
15
30
15/10
15/15
15/10
15/15
15
30
30/10
30/15
15/10
15/15

10P
10P
1/10P
1/10P
3/10P
3/10P
10P
10P
1/10P
1/10P
3/10P
3/10P
10P
10P
0.5/10P
0.5/10P
3/10P
3/10P
10P
10P
0.5/10P
0.5/10P
3/10P
3/10P
10P
10P
0.5/10P
0.5/10P
3/10P
3/10P
10P
10P
0.5/10P
0.5/10P
3/10P
3/10P

10
5
5/10
5/5
5/10
5/5
10
5
5/10
5/5
10/10
10/5
10
5
5/15
5/5
5/15
5/5
15
5
5/10
5/5
10/10
10/5
15
10
10/10
10/5
10/10
10/5
20
10
5/15
5/10
10/15
10/10

750//5
750//5
750//5/5
1000//5
1000//5
1000//5/5
1000//5/5
1250//5
1250//5
1250//5/5
1250//5/5

100
100
100
100
100
100
100
100
100
100
100

60
30
15/30
60
30
30/15
30/30
120
30
30/15
30/30

1
5P
0.5/5P
0.5
5P
0.5/5P
0.5/5P
0.5
5P
0.5/5P
0.5/5P

10
10
5/5
10
10
5/10
5/5
5
15
5/10
5/5

44.11
44.11
44.11
44.11

1500//5
1500//5
1500//5/5
1500//5/5

150
150
150
150

120
60
60/30
60/60

0.5
5P
0.5/5P
0.5/5P

10
10
5/10
5/5

45.11
45.11
45.11
45.11

2000//5
2000//5
2000//5/5
2000//5/5

200
200
200
200

120
60
60/30
60/60

0.5
5P
0.5/5P
0.5/5P

10
10
5/10
5/5

46.11
46.11
46.11
46.11

2500//5
2500//5
2500//5/5
2500//5/5

250
250
250
250

120
60
60/30
60/60

0.5
5P
0.5/5P
0.5/5P

10
15
5/15
5/5

TTR 4x.xx

Order form
Customer
Address
Country
Contact person

Date
Delivery required
Tel.
E-mail

Fax.

Current transformers
Project ref.:

Date

Inquiry No.:
Offer No.:

Um:
Ith:

kV
kA/1s
kA/3s
Hz
kA

freq.:
Idyn.:

Insulation level (BIL):

ratio (A)

kV/

kV

Routine test certificates


Additional name plate
Magnetisation curves
Remarks:

Indoor
Outdoor
Pos.:

kV/

Pcs.:
Class

Burden (VA)

core 1:
core 2:
core 3:
core 4:

ext 100%
ext 120%
ext 150%
ext 200%
reconnectable

add. Requirment

Yes
No

primary

secondary

Supplier's remarks
Type
Unit price
Total price
Comment

Pos.:
ratio

Pcs
Class

Burden

core 1:
core 2:
core 3:
core 4:

ext 100%
ext 120%
ext 150%
ext 200%
reconnectable

add. Requirment

Yes
No

primary

secondary

Supplier's remarks
Type
Unit price
Total price
Comment

A 3440-504-I/2000

ABB s.r.o.
Videnska 117
619 00 Brno, Czech Republic
E-mail: info.ejf@cz.abb.com
http://www.abb.com

Tel.: +420 547 152 602


+420 547 152 604
Fax: +420 547 152 626

The data and ilustrations in this catalogue are not binding.


We reserve the right to make changes of the content, in
the course of technical development of the product.

You might also like