Professional Documents
Culture Documents
Control Room
Lighting level required =350 lux
4.576
m
3.4m
13.2m
L
13.20
W
3.40
H
4.58
=
Room Cavity
Ratio
8.46
+ 5
Assume that
Pf
Pcc
Pw
0.00
0.80
0.50
from the Table
CU
=
0.35
Assume that
LLD
LDD
0.85
0.90
LLF =
LLF
E
350.00
A
44.88
N luminaire =
N
=
0.77
CU
0.350
7.15
8.00
Lamp/luminaire lm/lamp
2.00
4100.00
N=
E=
E=
391.36 Lux
LLF
0.77
Motor Room
Lighting level required = 200 lux
6.6m
8.9m
15.8m
As Motor room consisting of v shaped roof, suspended types of luminaires are used lighting the
room and the suspended height is 6.6m from the ground. Further the area comes under stair
case is removed, when calculating lux level of Motor room as separate lighting system is adopted
to light the same. Supportive documents such as luminaires specification, lux distribution and
luminaire arrangements etc. are attached (Annex: 2)
L
15.80
W
8.90
H
6.60
=
Room Cavity
Ratio
5.80
+ 5
Assume that
Pf
Pcc
Pw
0.00
0.80
0.50
from the Table
CU
=
0.43
Assume that
LLD
LDD
0.85
0.80
LLF =
LLF
E
200.00
A
140.62
N luminaire =
N
=
E=
0.68
CU
0.425
11.87
12.00
202.23 Lux
Lamp/luminaire lm/lamp
2.00
4100.00
N=
LLF
0.68
E=
5m
6.3m
12.9m
For the convenient of lighting design, Ground floor is considered as two parts (Ground Upper
Area and Ground Lower Area), so any maintenance work can be done without any problem.
Surface mount types of luminaires are used lighting the upper part Further the area comes
under stair case is removed, when calculating lux level of Ground Upper area as separate lighting
system is adopted to light the same. Supportive documents such as luminaires specification, lux
distribution and luminaire arrangements etc. are attached (Annex: 3)
L
12.90
Room Cavity
Ratio
W
6.30
H
5.00
=
5.91
+ 5
Assume that
Pf
Pcc
Pw
0.00
0.80
0.50
from the Table
CU
=
0.58
Assume that
LLD
LDD
0.85
0.80
LLF =
LLF
E
200.00
A
81.27
0.68
CU
0.580
N luminaire = 5.03
N
=
6.00
E=
238.77 Lux
Lamp/luminaire lm/lamp
2.00
4100.00
N=
LLF
0.68
E=
6m
6.3m
12.9m
Wall mount types of luminaires are used lighting the lower part as there is no supportive
structures. The mounting height is 6m from the bottom. Further the area comes under stair case
is removed, when calculating lux level of Ground Lower area as separate lighting system is
adopted to light the same. Supportive documents such as luminaires specification, lux
distribution and luminaire arrangements etc. are attached (Annex: 4)
L
12.90
W
6.30
H
6.00
=
Room Cavity
Ratio
7.09
+ 5
Assume that
Pf
Pcc
Pw
0.00
0.80
0.50
from the Table
CU
=
0.41
Assume that
LLD
LDD
0.85
0.80
LLF =
LLF
E
200.00
A
81.27
N luminaire =
N
=
E=
0.68
CU
0.410
7.11
8.00
225.04 Lux
Lamp/luminaire lm/lamp
2.00
4100.00
N=
LLF
0.68
E=
Stair Case
Lighting level required = 100 lux
2.5m
2m
6.3m
Wall mount types of luminaires are used lighting the Stair Case and mounting height is 2.5m
with angle if 55 degrees to horizontal. Here it is only considered part of the stair case to design
the lighting system, thus it can be repeated for the other parts of the stair case. Supportive
documents such as luminaires specification, lux distribution and luminaire arrangements etc.
are attached (Annex: 5)
L
6.30
W
2.00
H
2.50
=
Room Cavity
Ratio
8.23
+ 5
Assume that
Pf
Pcc
Pw
0.00
0.80
0.50
from the Table
CU
=
0.53
Assume that
LLD
LDD
0.85
0.90
LLF =
LLF
E
100.00
A
12.60
N luminaire =
N
=
E=
0.77
CU
0.530
0.98
1.00
101.59 Lux
Lamp/luminaire lm/lamp
1.00
3157.00
N=
LLF
0.77
E=
6.6m
1m
17.6m
Wall mount types of luminaires are used lighting the Corridor. Here it is only considered part of
the corridor to design the lighting system, thus it can be repeated for the other parts of the
corridor with necessary changes. Further it is included some luminaires to light the surrounding
area even those are not considered under corridor and the lux level of those area are not
calculated (fix just to light area) Supportive documents such as luminaires specification, lux
distribution and luminaire arrangements etc. are attached (Annex: 5)
L
17.60
W
1.00
H
6.60
=
Room Cavity
Ratio
34.88
+ 5
Assume that
Pf
Pcc
Pw
0.00
0.80
0.50
from the Table
CU
=
0.12
Assume that
LLD
LDD
0.85
0.80
LLF =
LLF
E
50.00
A
17.60
N luminaire =
N
=
E=
0.68
CU
0.115
7.23
8.00
55.34 Lux
Lamp/luminaire lm/lamp
1.00
1557.00
N=
LLF
0.68
E=
Fixing method
Surface Mounted
Wall Mounted
Suspended
Surface Mounted
Wall Mounted
Wall Mounted
Area
Ground
Upper part
Ground
Lower part
Machine
area
Control
room
Staircase
(total)
Corridor
(total)
Luminanc
e level
(Lux)
Lamp
lumen
(lm)
(bulb+
luminaire
) Wattage
Lamps
Lumin
aire
LLD
LDD
LBO
LLF
CU
200
4100
50
0.85
0.9
1.0
0.765
0.537
200
4100
50
0.85
0.8
1.0
0.680
0.461
200
4100
50
0.85
0.8
1.0
0.680
0.604
12
350
4100
50
0.85
0.8
1.0
0.680
0.497
100
3157
51
0.85
0.9
1.0
0.765
0.486
50
1557
28
0.85
0.8
1.0
0.680
0.11
20
Demand Calculation
Demand of lighting loads (Single Phase)
Specimen Calculation
=[
=
=
=
=
=
=
=
=
=
=
=[
Apparent power
Simultaneity
factor
Apparent power
Nominal Current
MCB
kVA
Ku
kVA
Ks1
kVA
1st
0.96
0.9
0.9
0.9
0.75
100%
0.75
1.00
0.75
3.26
0.56 ph 2nd
0.96
0.9
0.9
0.9
0.53
100%
0.53
0.80
0.42
1.83
6.00
P.F
kVA
Ku
kVA
Ks1
kVA
0.96
0.9
0.9
0.9
1.13
100%
1.13
1.00
1.13
4.89
P.F
kVA
Ku
kVA
Ks1
kVA
0.80 ph
1.20 ph
1st
power Factor
Diversity Factor
D.F.
Utilization factor
Connected Phase
Apparent power
12
Efficiency
20
P.F
POWER IN KW
Control Room
Fluorescent bulb +
Luminoir (50W*2)
0.1 kW
indoor 1ph
Fluorescent
Luminoir (28W)
0.03 kW
corridor 1ph
Motor Room
Fluorescent bulb +
Luminoir (50W*2)
0.1 kW
indoor 1ph
Ground Floor
Fluorescent bulb +
Luminoir (51W)
0.05 kW
indoor (stair case)
1ph
Fluorescent bulb +
Luminoir (50W*2)
0.1 kW
indoor (bottom
part) 1ph
Fluorescent bulb +
Luminoir (50W*2)
0.1 kW
indoor (Upper part)
1ph
0.26 ph
1st
0.96
0.9
0.9
0.9
0.24
100%
0.24
1.00
0.24
1.04
0.80 ph
1st
0.96
0.9
0.9
0.9
0.75
100%
0.75
1.00
0.75
3.26
0.60 ph
3rd
0.96
0.9
0.9
0.9
0.56
100%
0.56
1.00
0.56
2.45
Page 9 of 22
=[
=
=
=
=
=
=
=
=
=
=
=
For Single Phase (13A S/O)
=[
Page 10 of 22
Utilization factor
Apparent power
Simultaneity
factor
Apparent power
Nominal Current
MCB
Ku
100%
kVA
19.35
Ks1
0.20
kVA
3.87
A
16.82
A
20.00
P.F
X
Y
Z
0.85 100% 75% 75% 100%
kVA
11.43
Ku
100%
kVA
11.43
Ks1
0.20
kVA
2.29
A
9.94
A
10
Efficiency
Diversity Factor
D.F.
kVA
19.35
power Factor
Apparent power
Control Room
7 S/O 13A ring
cct 1ph
Motor Room
4 S/O 13A ring
cct 1ph
5 S/O 30A ring
cct 3ph
1 S/O 63A ring
cct 3ph
Ground Floor
7 S/O 13A ring
cct 1ph
7 S/O 30A ring
cct 3ph
Connected Phase
POWER IN KW
0.013
kA
20.93
ph
P.F
X
Y
Z
2nd 0.85 100% 75% 75% 100%
0.013
kA
11.96
ph
1st
0.03
kA
103.92
3 ph
97.81
100%
97.81
0.20
19.56
28.24
32
0.03
kA
20.78
3 ph
24.45
100%
24.45
1.00
24.45
35.29
40
0.013
kA
20.93
P.F
X
Y
Z
0.85 100% 75% 75% 100%
kVA
19.35
Ku
100%
kVA
19.35
Ks1
0.20
kVA
3.87
A
16.82
A
20
0.03
kA
145.49
0.20
26.90
38.82
40
ph
3rd
3 ph
Page 11 of 22
=[
=
=
=
=
=
=
=
=
=
=
=[
12
Control Room
1
Battery Bank
(100Ahrs for
8hrs 3ph
0.2
kAhrs
1.20
3 ph
Motor Room
3
4
Ground Floor
3
Motorized
Valve .4kW
3ph
2
Drainage
Pump 1.5kW
3ph
MCB
Nominal Current
Apparent power
Simultaneity
factor
Apparent power
Utilization factor
Apparent power
Efficiency
P.F
X
Y
Z
0.85 100% 50% 50%
P.F
Raw Water
Pump 3ph
Exhaust fan
3ph
Diversity Factor
D.F.
power Factor
Connected Phase
POWER IN KW
90%
kVA
0.26
Ku
20%
kVA
0.05
Ks1
1.00
kVA
0.05
A
0.08
kVA
Ku
kVA
Ks1
kVA
200
kw
600.00
3 ph
87%
0.75
kw
3.00
3 ph
85%
3.11
100%
3.11
0.90
0.4
kW
1.20
3 ph
P.F
X
Y
Z
0.85 100% 80% 60%
84%
kVA
1.34
Ku
100%
kVA
1.34
1.5
kW
3.00
3 ph
84%
3.78
100%
3.78
A
6
618.36
630
2.80
4.05
Ks1
0.50
kVA
0.67
A
0.97
0.80
3.03
4.37
13
power Factor
X
Y
Z
100% 75%
75%
100% 100% 100%
90%
80%
kVA
7.29
0.01
Ku
85%
20%
kVA
6.20
0.00
Ks1
0.80
1.00
kVA
4.96
0.00
A
21.56
0.00
phase 1st
P.F
0.96
X
Y
Z
kVA
0.01
Ku
20%
kVA
0.00
Ks1
1.00
kVA
0.00
A
0.01
phase 1st
P.F
0.96
X
Y
Z
kVA
0.03
Ku
20%
kVA
0.01
Ks1
1.00
kVA
0.01
A
0.03
Efficiency
phase 1st
phase 1st
P.F
0.8
0.96
Connected
Phase
Nominal
Current
Apparent
power
0.03
Simultaneity
factor
kW
0.01
1
1
Apparent
power
0.005
kW
6.00
0.01
Utilization
factor
Ground Floor
6 Emergency Light
1ph
0.005
kW
kW
Apparent
power
Motor Room
2 Emergency Light
1ph
3
0.005
Diversity Factor
D.F.
Control Room
2
A/C 3kW 1ph
1 Emergency Light
1ph
number of
phases
POWER IN KW
Demand calculation for the A/C system and rechargeable Emergency lights
14
15
Transformer
Total demand needed for the system
408kVA
408/0.85
480kVA
Cable selection
Lighting
Specimen Calculation
Assume ambient temperature to be 30 0C
Correction factor for ambient temperature, Ca
Ground Control Room
Assume wiring is surface mounted on the ceiling
Correction factor for method of installation, Ci
Single phase PVC insulated cable single circuit is used.
Correction factor for cable grouping, Cg
Current required
Required current carrying capacity
0.95
=
1
=
3.26A
=
I/(Ca*Ci*Cg)
=
3.26/(1*0.95*1)
=
3.43A
2
1mm PVC insulated cable is used. Same cable is used for the neutral conductor.
Voltage drop of the cable
Max allowable voltage drop
Maximum length of the circuit
=
=
=
=
44mV/A/m
13.8V
13.8*1000/ (3.26*44)
138.7m
Wiring method
Number
of circuits
Control room
indoor
Control room
corridor
Motor Room
Ground Upper area
surface mounted
on the ceiling
surface mounted
on the ceiling
On the tray
surface mounted
on the ceiling
surface mounted
on the ceiling
surface mounted
on the ceiling
surface mounted
on the ceiling
surface mounted
on the ceiling
surface mounted
on the ceiling
single
4.83
0.95
5.08
64.94
single
1.83
0.95
1.93
171.39
single
single
4.89
2.45
1
1
0.95
0.95
1
1
6.06
2.58
64.14
128.01
single
3.26
0.95
3.43
96.21
single
1.04
0.95
1.09
301.57
single
0.004348
0.95
0.00
72136.36
single
0.009058
0.95
0.01
34625.45
single
0.027174
0.95
0.03
11541.82
Current Ca Ci
required
(A)
Cg Required
I capacity
(A)
Max
length
(m)
Cable used
Max Length of a
circuit(m)
Control room
indoor
Control room
corridor
Motor Room
1 mm2 PVC
insulated
1mm2 PVC
insulated
1 mm2 PVC
insulated
1mm2 PVC
insulated
1mm2 PVC
insulated
1mm2 PVC
insulated
1mm2 PVC
insulated
1mm2 PVC
insulated
1mm2 PVC
insulated
64.94
Cable length
needed(m)
59
Metal clad
Switch
Two gang
171.39
124
Four gang
64.14
92
Three gang
128.01
58
Two gang
96.21
96
Two gang
301.57
30
72136.36
Three gang
two way
One gang
34625.45
12
One gang
11541.82
30
One gang
Total length of 1mm2 PVC insulated single core cable needed for lighting circuit including live and
neutral = 509m
Socket outlets
Specimen Calculation (control room 13A S/O)
Assume ambient temperature to be 30 0C
Correction factor for ambient temperature, Ca
Ground area
Assume wiring is embedded or buried in the wall,
Correction factor for method of installation, Ci
Single phase PVC insulated cable single circuit is used.
Correction factor for cable grouping, Cg
Current required
Required current carrying capacity
0.95
=
1
=
16.82A
=
I/(Ca*Ci*Cg)
=
16.82/(1*0.95*1)
=
17.7A
2
2.5mm PVC insulated cable is used. Same cable size is used for the neutral and earthing
conductor.
Voltage drop of the cable
=18mV/A/m
=13.8 V
=13.8*1000/ (16.82*18)
=45.6m
Control room
13A S/O
Motor Room
13A S/O
Ground Floor
13A S/O
Wiring method
Embedded or
buried in the wall
Embedded or
buried in the wall
Embedded or
buried in the wall
Number Current
of
required
circuits (A)
Ca
Ci
C
g
Require Max
dI
length
capacity (m)
(A)
single
16.82
0.95
17.71
45.58
single
9.94
0.95
12.31
77.13
single
16.82
0.95
17.71
45.58
Cable used
2.5mm2 PVC insulated
2.5mm2 PVC insulated
2.5mm2 PVC insulated
Since the live conductor size selected is less than 16mm2 neutral conductors and the protective
conductor is used as the same size.
Total 2.5mm2 PVC insulated single core cable needed including live and neutral = 336m
2.5mm2 PVC insulated single core protective conductor length needed
= 168m
Wiring method
Number
of circuits
Current
required
(A)
Ca Ci
Cg
RP
EF
MV
DP
Motor room
30A Socket
outlets
On trays
On trays
On trays
On trays
Embedded or
buried in the
wall
three
four
three
two
one
Ground Floor
30A Socket
outlets
Embedded or
buried in the
wall
63A Socket
outlets
Battery bank
Required
I capacity
(A)
339.6
1.01
0.32
2.19
28.24
1
1
1
1
1
1
1
1
1
0.95
0.85
0.85
0.85
0.85
1
399.53
1.19
0.38
2.58
29.73
one
38.82
0.95
40.86
Embedded or
buried in the
wall
one
35.29
0.95
37.15
Embedded or
buried in the
wall
one
0.08
0.95
0.08
Table 10: Cable selection and lengths for three phase loads
Area
Cable used
Total Length
required (m)
RP
40
EF
MV
DP
Motor room 30A
Socket outlets
Ground Floor 30A
Socket outlets
124
70
20
Battery bank
90
30
40
120m
80m
251m
251m
90m
90m
40m
40m
630kVA
630kVA/ (3*400)
909A
630mm2
10m
500kVA
500kVA/ (3*400)
721A
300mm2
10m
R=0.105 m /m
X=0.21 m
400mm2
Isc1
Main DB
R=0.105 m /m
X=0.21 m
400mm2,2m
Three
phase DB
Isc2
Isc3
Assuming Short circuit impedance voltage of the transformer is 4%
And infinite bus upstream of the transformer
Transformer Impedance (Zs)
=
Us2 * Usc / (Pn * 100)
=
4002 * 4 / (630 * 100)
=
10.1
Fault level (Isc1)
=
Us / (3 * Zs )
=
400/(3* 10.1 * 10-3)
=
22.7 kA
Impedance at main DB (Z2)
=
((0.105*10)2+(0.21*10)2)
=
2.34
Assuming breaker reactance as 0.15
Fault level (Isc2)
=
Us / (3 * Z )
=
400 / (3*(10.1+2.34+0.15))
=
18.34 kA
Impedance at three DB (Z3)
=
((0.105*2)2+ (0.21*2)2)
=
0.47
Assuming breaker reactance as 0.15
Fault level (Isc2)
=Us / (3 *Z)
=400 / (3*(10.1+2.34+0.47+2*0.15))
=17.48kA
NOTE
All the Raw Water Pumps are operated by sending control signals to the VSD at each motor.
Emergency buttons are installed at each motor to stop the motor operation in case of
emergency.
Even though the emergency supply is installed to the pump house, the failure of converter will
definitely shutdown the pump house as there are no control signals to control the whole
system. Thus, A battery bank is installed to supply the control panels at 45V/DC in case of
failure of A/C to D/C converter and main power supply The battery bank is selected such a
way that provide power to control panel for 8 hours without any disturbances.
The humidity level of the water pump house is higher than the normal working environment
and that will definitely affect the durability of all the electrical installations. Since control
panels are the brain of Water pump house and thus A/C was installed to control room thus
humidity level of the control panels are kept accordingly.
Emergency lights were installed in case of black out to guide the paths to exit and all the door
are rearranged such a way that exiting from pump house without any trouble.
Lighting arrangement of the Motor room was design such a way that operation of crane dose
not serious disturbance to light level.
Layout Diagrams
Description
13A socket outlets
Industrial socket outlets 30A
Industrial socket outlets 63A
Florescent lamps