Putting It in Reverse

ReversefedTransformersQuestionsAnd
Answers
Published:June2012
ByJamesG.Stallcup

articipantsatoneofmyrecentworkshopshad
questionspertainingtoreversefedtransformers
(backfed).Theinputsidewas480volts(V),
threephase,andtheoutputsidewas120/208V.They
ClickToViewFullSize
wantedtoknowiftheoutputsideof120/208V
transformercouldbeusedasaninputside,andifso,
howwastheelectriciantobondandgroundthetransformer?

August 2016:
Collaborative Design and
Construction

ECMag Live

August 2016: Focus on


Maintenance and Service

VideoLibrary

Inmyopinion,whenastepuptransformerisnecessary,itshouldbedesignedandidentifiedforsuchapplication.
Thisarticledoesnotaddresssuchproblems,butitaddressesthegeneralrequirementsthatareoutlinedinthe
NationalElectricalCode(NEC).
Thebigquestionseemedtobewhetherthegroundedconductor(usuallyaneutral)isrequiredtobeconnectedto
theXOterminationpoint.Ofcourse,theanswerisno.Whenthegroundedconductorisusedinthistypeof
installation,itmustnotbeconnectedtotheXOterminalandmustnotbebondedtotheenclosureorearthgrounded.
Foroperationalpurposes,justconnecttheungroundedphaseconductorstotheoutputterminalsthatareusually
identifiedasL1,L2andL3,respectively.Thenanequipmentgroundingconductormustberoutedwiththesupply
circuitandusedtobondandgroundthenoncurrentcarryingpartsofthetransformerenclosure.
Notethatagroundedneutralconductorcannotbederivedfromareversefedtransformerbecausestandard
transformersarenotusuallymanufacturedwithafourwireprimaryside.
Therefore,ifthe480Vsideisgrounded,oneofitsphaseconductorsmustbeconnectedtoanearthgrounded
electrodesothatthetransformerhasagroundedconductorthatwillprovideaneffectivegroundfaultpath,shoulda
groundfaultoccurononeoftheungroundedphaseconductors.Notethatoneoftheungroundedphaseconductors
isgrounded.TheNECrequiresgroundedconductorstobeidentifiedeitherwhiteorgrayinaccordancewith
sections310.110(A)and200.6(A)or(B).
Thetransformersoutputside
The480Vinputsideisnowusedastheoutputside.ThereisnoXOterminationtherefore,oneoftheungrounded
phaseconductorsmustbeconnectedtotheearthgroundiftheinstallerdesirestheelectricalsystemtobegrounded
andequippedwithagroundedconductor.
Advantages
First,cornergroundeddeltasystemswillstabilizethevoltagesoftheothertwoungroundedconductors.Second,this
setupaidsinreducingthegenerationoftransientovervoltagesand,finally,providesanadequatepathforfault
currentswhenagroundfaultconditionoccurs.
Disadvantages
Thesystemisnotabletoprovidedualvoltageserviceforlightingandpowerloads.Also,thegroundedconductor
mustbepositivelyindentifiedthroughouttheelectricalsystem.Finally,ahigherlinetogroundvoltage(byafactorof
1.732)existsontheothertwoungroundedphaseconductorsthanitdoesonawyeneutralgroundedsystem.
Theserviceequipment
Attheserviceequipmentlocation,thegroundedconductormustagainbeconnectedtotheearthgroundasoutlined
insections250.24,250.26,250.50,250.52and250.53oftheNEC.Section240.85permitstheuseofcircuit

http://www.ecmag.com/section/codesstandards/puttingitreverse

1/3

9/8/2016

PuttingItinReverse|ECMag

breakerswithastraightmarkingof480Vaslongasthenominalvoltagebetweenanytwoconductorsdoesnot
exceedthecircuitbreakerratings.Warning:Iftwopolecircuitbreakersareinstalledinacornergroundeddelta
system,theymustbemarkedtoindicatesuchsuitability.
Slashmarkedcircuitbreakerssuchas120/240Vor277/480Vmustnotbeusedoncornergroundeddeltasystems.
Section230.90(B)generallyprohibitsanovercurrentprotectiondevicetobeplacedinthegroundedconductorifit
doesnotopenallthecircuitconductorssimultaneously.
Section240.22statesthatnoovercurrentprotectiondevicecanbeinsertedinanyconductorthatisintentionally
groundedunlessthepolesofthecircuitbreakeropenallthecircuitconductorssimultaneously.However,formotor
overloadconditions,anexceptionispermitted.SeeSection430.37oftheNEC.
Reviewstandards
IsuggestedapplyingNEMAPB1andPB2,whichcoverrequirementsforinstallingdeltacornergrounded
transformersandmethodspertainingtothecornergroundedBphase.UL67,UL891,andUL489specifically
addressesdeltacornergroundedsystems.Wheninstalling,inspectingandapprovingthistypeofsystem,see
sections110.2,110.3(B)and90.7oftheNEC.
Itisagiventhatthecircuitsofacornergroundeddeltasystemareathighervoltagestressthanamorewidelyused
standardwyesystembecausethetwoungroundedphasesareconstantlyoperatingathighervoltagerelativeto
ground.Ofcourse,anysurgeactivitywouldbeinadditiontotheconstantsystemvoltagestress.

Featured Sponsors

STALLCUPistheCEOofGrayboyInc.,whichdevelopsandauthorspublicationsfortheelectricalindustryand
specializesinclassroomtrainingontheNationalElectricalCodeandotherstandards,includingthosefromOSHA.
Contacthimat817.581.2206.

Codes, NationalElectricalCode

Related Articles

Plays Well With Others


Overthelastdecadeorso,
weveseenyougrowintoa
socialbeing,amature
individualwith...
READMORE

Digital Tools Ease


Compliance

General Installation
Requirements, Part XIX

Introducing The New


Code

Historically,theNational
ElectricalCode(NEC)has
requiredmuchofthe
electricalequipment,wiring
methodsandother
electrical...

Section110.26ofthe
NationalElectricalCode
(NEC)requiresspecific
minimumsforworking
spacearoundelectrical
equipment.Section...

Everythreeyears,the
NationalElectricalCode
(NEC)isrevisedandoften
expanded.Asthe2017NEC
development...

READMORE

READMORE

READMORE

Comments

http://www.ecmag.com/section/codesstandards/puttingitreverse

2/3

9/8/2016

PuttingItinReverse|ECMag

1Comment
Recommend

ElectricalContractor

Share

Login

SortbyBest

Jointhediscussion
KielMacey9monthsago

Issinglephasingmotorspossibleoncornergroundeddeltasystems?I'mtryingto
resolveasystemproblemweinheritedfromabothercompany.Inowunderstandwhy
mycontrolcabinetisliteredwithblownfusesfromthegroundedconductor.Reading
Schneiderscornergroundeddeltapublicationtheyrecommend2polebreakerson240
cornerground.Whynot3pole?

Reply Share
Subscribe d AddDisqustoyoursiteAddDisqusAdd

Electrical Contractor

Privacy

Archives

Social

Service

DigitalEdition

2016

2015

Facebook

SiteHelp

AboutUs

2014

2013

Twitter

SiteFeedback

Contact

2012

2011

YouTube

Subscription

MediaKit

2010

2009

LinkedIn

PrivacyPolicy

Contributors

2008

2007

GooglePlus

TermsofService

2006

2005

RSS

Join Our e-Newsletter Mailing List


Pleaseenteryourinformationbelowtosubscribeto
ELECTRICALCONTRACTOR'smonthlyenewsletter.
FirstName
EMail

ViewSamples
Conventions&Shows

NECAMEI

NECANEIS

ELECTRIInternational

LastName

Submit

NECAConnection

20032016.AllRightsReserved.
ElectricalContractor:3BethesdaMetroCenter,Suite1100,Bethesda,MD.208145372|Phone:301.657.3110|Fax:301.215.4501
MOBILEVERSION

http://www.ecmag.com/section/codesstandards/puttingitreverse

3/3

You might also like