Specifications and Ordering Information

3300/52 Reverse Rotation Monitor


Description
The 3300/52 Reverse Rotation Monitor provides an early indication of a
reverse rotation event. It is particularly useful on machines such as pumps,
hydraulic turbines, and compressors which can rotate in the wrong direction
during process upset conditions and thereby damage the machine.
Warning
Bently Nevada's Reverse Rotation Monitor is not designed for use
independently as, or as a component of, a speed control or overspeed
protection system. The 3300/52 Reverse Rotation Monitor does not provide
protective redundancy and the response speed needed for reliable operation
as a speed control system. The recorder output is suitable for data logging
or chart recording purposes only. Also, speed alert setpoints are suitable for
annunciation purposes only.
Failure to take the above warnings into account constitutes a misuse of the
product and may result in property damage and/or bodily injury. When
applications require machine overspeed protection, use Bently Nevada's
3300/53 or 3500/53 Monitors instead.

Specifications
Inputs
Transducers:
Input Impedance:

Bently Nevada 3300, 7200, or 3000 Series


proximity probes.
System Keyphasor Transducers: 130 k .
External Proximity Transducers: 10 k .

Reverse Rotation
Enable:

Contact closure on signal input module enables the


reverse rotation alarm and the reverse speed
alarm.

Power:

Nominal consumption of 2 watts.

Input Frequencies:

333 Hz max with 1 event per revolution.


166 Hz max with 2 events per revolution.

Signal Conditioning
Triggering Threshold
Adjustment:

For Reference Only See Document #141513

0 to -24 Vdc.

Page 1 of 6

Triggering Hysteresis:

User-selectable from 0.2 to 2.0 Vdc.

Accuracy:

Within (0.02% of reading + 1 rpm)


for speed indication, specified at
+25C (+77F).

Speed Alarms
(Reverse or
Forward):
Alarm Relay Drives:

One Alert relay for Reverse


Rotation and one Alert relay for
Speed alarms.

OK Relay Drive:

One OK relay drive for the system


OK relay. Activates whenever the
monitor detects a transducer NOT
OK or monitor NOT OK condition.
The OK relay drive is not activated
by invalid triggering.

Outputs
Recorder:

User-programmable for +4 mA to
+20 mA, +1 Vdc to +5 Vdc, or 0 Vdc
to -10 Vdc. One recorder for
forward speed and one recorder for
reverse speed, proportional to the
respective full-scale range.

Recorder accuracy
(in addition to signal
conditioning
accuracy):

All specified at +25C (+77F).


All recorders: 1 rpm or
0.4% of displayed speed,
which ever is greatest, plus;
+4 to +20 mA: 1.8% of
signal, 0.09 mA offset.
+1 to +5 Vdc: 2.2% of signal,
10 mV offset.
0 to -10 Vdc: 2.1% of signal,
15 mV offset.

Output Impedance
(voltage outputs):

100 . Minimum load resistance is


10 k .

Voltage Compliance
(current outputs):

0 to +12 Vdc range across load.


Load resistance is 0 to 600 when
using +4 to +20 mA option.

Buffered Transducer
Outputs:

One coaxial connector per


transducer on the front panel and
one terminal connection per signal
on the rear panel. All are shortcircuit protected.

Transducer Supply
Voltage:

User-programmable in power
supply for -24 or -18 Vdc. Current
limited on individual monitor circuit
board.

Relay Modules
Location:

Alarm Setpoints:
Time Delay
Reverse Rotation:

One relay module can be installed


behind each monitor. At least one
alarm relay module must be
ordered with each 3300 System.

Display
LCD Indicators:

The front panel LCD normally


displays rpm with a five-digit
number. Alpha-numeric indicators
display "Reverse Rotation,"
"Enabled," and "Alert." Transducer
gap voltage, speed alarm setpoints,
maximum reverse speed, and
number of reverse rotations are
displayed by pressing the
appropriate front panel switches.

Numeric Character
Size:

84 mm x 38 mm (0.33 in x 0.15 in).

Shaft Rotative Speed


Range:

Resolution:
Alarms

Three shaft revolutions or one


second, whichever is longer.

0.05 to 20,000 rpm for 1 event


per revolution;
0.05 to 10,000 rpm for 2
events per revolution.
1 rpm.

LED Indicators
One alert setpoint each for forward
and reverse speed.
Two valid input triggers or 330 ms
after first valid input trigger,
whichever is longer, plus relay
actuation time.

For Reference Only See Document #141513

Trigger OK:

One constant ON green OK LED for


each transducer indicates OK
operational condition of transducers
and monitor. Constant OFF
indicates a failure of one transducer
or associated field wiring, invalid
triggering, or shaft rotation is below
0.05 rpm or above 20,000 rpm for 1

Page 2 of 6

event per revolution (10,000 rpm for


2 events per revolution) (invalid
triggering does not activate system
OK relay). LED flashing at 5Hz
indicates monitor error.
Alert:

One red LED for Reverse Rotation


and one red LED for Speed alarms.

Bypass:

One red LED indicates bypass of


Reverse Rotation and one red LED
indicates bypass of Speed alarms.

Ordering Information
For spares, order the complete catalog number as described
below. This includes a front panel assembly, monitor PWAs
with sheet metal, and appropriate relay module. This unit is
optioned, tested and ready to install in your system. Spare
relay modules can be ordered separately.
Reverse Rotation Monitor
3300/52-AXX-BXX-CXX
Option Descriptions
A: Alert Relay Option

Environmental
Limits
Operating
Temperature:

0C to +65C (+32F to +150F).

Storage
Temperature:

-40C to +85C (-40F to +185F).

Relative Humidity:

To 95%, noncondensing.

Certificate of Conformity: 158710


Certificate of Conformity: 135300

B: Agency Approval
Option

Hazardous Area
Approvals
CSA/NRTL/C
ATEX

Class 1, Division 2 Groups A,B,C,D


T4 @ Ta = 65C
EEx nC IIC
T4 @ Ta = 60C for AC power
T3 @ Ta = 60C for DC power

Physical
Rack Space
Requirements:

One rack position (any position


except 1 and 2 which are reserved
for the Power Supply and System
Monitor, respectively).

Weight:

1 kg (2.2 lbs.).

For Reference Only See Document #141513

No Relays
Epoxy-sealed
Hermetically-sealed
Spare Monitor-No SIM/SIRM

Notes:
1.
At least one relay module must be
ordered with each 3300 System. If one
common relay module per system has
been ordered, all monitors of this type
must be jumper programmed at the
factory to activate a relay bus by
ordering a Special Configuration Kit
(SCK). Contact your nearest Bently
Nevada office for information.
2.
Agency approval places limitations on
the relay module. Refer to the Relay
Module data sheet for information.

CE Mark Directives
EMC Directive
Low Voltage Directive

00
01
02
04

0 0 Not required
0 1 CSA/NRTL/C
0 2 ATEX self certification
Note: ATEX approval requires the monitor
rack be installed in a weatherproof housing.

C: Barriers Option

0 0 None
0 1 External
0 2 Internal
Note: External Safety Barriers must be
ordered separately.

Spare Relay Module


Assemblies

(Order the option in parenthesis for


ATEX approved spares)

101709-01(02)
101710-01(02)
101711-01(02)
103475-01(02)
103474-01(02)
103473-01(02)

No Relays
Dual Epoxy Relays
Dual Hermetic Relays
No Relays, Internal Barriers
Dual Epoxy Relays, Int Barriers
Dual Hermetic Relays, Int Barriers

Page 3 of 6

Field-programmable Options
These options are field-programmable via plug-in jumpers
unless otherwise noted. Bold text indicates options as
shipped from the factory.
Forward Speed
10 rpm
Recorder Full-scale
20 rpm
Range (firmware
50 rpm
programmable
100 rpm
option)
200 rpm
500 rpm
1000 rpm
2000 rpm
5000 rpm
10000 rpm
20000 rpm
Reverse Speed
Recorder Full-scale
Range (firmware
programmable
option)

10 rpm
20 rpm
50 rpm
100 rpm
200 rpm
500 rpm
1000 rpm
2000 rpm
5000 rpm
10000 rpm
20000 rpm

Recorder Output
Option

+4 to + 20 mA
+1 to + 5 Vdc
0 to -10 Vdc

Recorder Clamping
Mode (+4 to +20 mA
Option only)

NOT OK = +4 mA
NOT OK = +2 mA
Note: Clamping occurs for monitor Not OK
condition only.

Forward Speed Alarm


Mode Option

Overspeed
Underspeed

Forward Speed Alarm


Reset Option

Latching
Non-latching

Reverse Rotation
Alarm Reset Option

Latching
Non-latching

Transducer A Input
Option

External Proximitor
(3300, 7200, or 3000)
System Keyphasor Transducer 1

Transducer B Input
Option

External Proximitor
(3300, 7200, or 3000)
System Keyphasor Transducer 2
Note: Contact your nearest Bently Nevada
Sales Professional if 3000 series transducers
are to be used in a monitoring rack which
also uses 3300 and/or 7200 series
transducers.

Triggering Hysteresis
Option

0.2 Vdc
0.5 Vdc
1.0 Vdc
2.0 Vdc

First Out

Enabled
Disabled
Note: This monitor drives only the rack First
Out Alert bus.

Reverse Rotation
Alert bypass Switch

Disabled
Enabled

RPM Alert Hysteresis


band

10 rpm
5 rpm
1 rpm
0 rpm

Event per Revolution

One
Two
Note: Two events per revolution is only valid
with external transducer inputs.

Accessories
89634-01 -24V to -18V Proximitor Power Converter
128112
Galvanic Isolator Kit
02245002 External Barrier
02200214 Surge Protector

1999-2004 Bently Nevada LLC


Proximitor and Keyphasor are registered trademarks of Bently Nevada LLC

For Reference Only See Document #141513

Page 4 of 6

Figure 1a: When rotation is in the forward direction, the notch is detected first by Transducer A
and then by Transducer B. The notch must remain in view of Transducer B.
Figure 1b: Shows the probes can be offset axially to obtain proper transducer spacing.

For Reference Only See Document #141513

Page 5 of 6

Field wiring diagrams


3300/52 Reverse Rotation Monitor

3 Conductor
Shielded Cable

Proximitor A
R

Proximitor B
R

See Figure 1

3300/52

REVERSE ROTATION
MONITOR

-V T
COM
OUTPUT

RPM
WARNING
ONE SECOND DELAY
ON RPM SET POINTS.
DO NOT USE FOR
OVERSPEED
PROTECTION.

SEE MANUAL
REVERSE
ROTATION
ENABLED
ALERT

A
R
E
V
E
R
S
E

TRIGGER OK
B
OFF BELOW 0.05 RPM

R
O
T
A
T
I
O
N

ALERT
BYPASS

R
P
M

MAX
REVERSE
REVERSE
RPM

FORWARD
RPM

Transducer A
Input

PWR
COM

Reverse
Speed
Recorder

Reverse
Rotation
Relay Contacts

Shield (Green)
(To single earth
point ground) 4 pl.

IN
REC
COM
R
O E
T N
A A
T B
I L
O E
N

R
E
V
E
R
S
E
REVERSE
ROTATION

GAP
A
B
BUFFERED TRANSDUCERS

Transducer B
Input

RPM

Forward Speed
Recorder
External (User supplied)
Contact closure to Enable
Reverse Rotation and
Reverse Speed Alarm

NC
ARM
NO

Speed Alarm
Relay Contacts

NC
ARM
NO

Figure 2: Field wiring diagram for 3300/52 Reverse Rotation Monitor

For Reference Only See Document #141513