HD4
Gas insulated MV circuit-breakers
12 ... 40.5 kV - 630 ... 3600 A - 16 ... 50 kA
Index
4 1. Description
44 4. Overall dimensions
3
1. Description
General information
HD4 medium voltage circuit-breakers use sulphur hexafluoride
gas (SF6) to extinguish the electric arc and as the insulating
medium.
Breaking in SF6 gas takes place without any arc chopping
and without generation of overvoltages. These characteristics
ensure long electrical life of the circuit-breaker and limited
dynamic, dielectric and thermal stresses on the installation.
The circuit-breaker poles, which make up the breaking part,
are systems with lifelong sealed pressure (IEC 62271-100
Standards) and are maintenance-free.
The ESH type mechanical operating mechanism, with stored
energy has free release and allows opening and closing
operations independently of the operators actions.
The operating mechanism and the poles are fixed to the metal
structure which also acts as a support for the kinetics for
operating the moving contacts.
4
Circuit-breakers in the withdrawable version are fitted with a Thanks to the SF6 autopuffer breaking technique, the HD4
truck to allow racking in and racking out of the switchgear or circuit-breakers do not generate operating overvoltages, and
enclosure. are therefore also highly suitable for retrofitting, upgrading
The light and compact structure of the circuit-breaker ensures and enlarging older installations where the motor, cable, etc.
great sturdiness and excellent mechanical reliability. insulating materials may be particularly sensitive to dielectric
stresses.
Available versions
HD4 circuit-breakers are available in the fixed and Breaking technique
withdrawable version with front operating mechanism. The breaking technique of HD4 circuit-breakers is based
The withdrawable version is available for PowerCube on compression and self-blast techniques to obtain top
modules and UniGear type ZS1, ZS2, ZS3.2 switchgears. performances at all service current values, with minimum
arc times, gradual arc extinction without chopping, and no
Fields of application restriking or operating overvoltages.
HD4 circuit-breakers are used in power distribution to control The HD4 series brings to medium voltage the advantages
and protect lines, transformer and distribution substations, of the autopuffer breaking technique already used in high
motors, transformers, capacitor banks, etc. voltage.
7 3
6
4
5
1. Description
6
A
K
B L
M
C
D N
E
O
F
P
H Q
I
R
7
1. Description
Accessories
HD4 circuit-breakers have a complete range of accessories
which fulfil all installation requirements.
The operating mechanism is the same type for the whole
series and has a standardized range of accessories and spare
parts which are easy to identify and order.
Apparatus use, maintenance and service have been simplified
and require less use of resources.
8
Technical documentation
To obtain in-depth knowledge of technical and application
aspects of the HD4 circuit-breakers please ask for the
following publications:
Power Cube 1VCP000091 Modules
Powerbloc BA441/03E Modules
UniGear ZS1 1VCP000138 Switchgear
UniGear ZS2 1YTS030001 Switchgear
Unigear ZS3.2 1YHA000023 Switchgear
UniSec 1VFM200003 Switchgear
REF542plus 1VTA100001 Units
Quality System
Complies with UNI EN ISO 9001 Standards, certified by an
independent organisation.
Test Laboratory
Complies with UNI CEI EN ISO/IEC 17025 Standards,
accredited by an independent organisation.
9
2. Selection and ordering
Circuit-breaker HD4 12
Standards IEC 62271-100
Rated voltage Ur [kV] 12
Rated insulation voltage Us [kV] 12
Withstand voltage at 50 Hz Ud (1 min) [kV] 28
Impulse withstand voltage Up [kV] 75
Rated frequency fr [Hz] 50-60
Rated normal current (40 C) (1)
Ir [A] 630 1250 1600 630 1250 1600 1600 2000 2500 3150 3600
16 16 16 16 16 16
25 25 25 25 25 25 25 25 25 25
Rated breaking capacity Isc [kA]
31,5 31,5 31,5 31,5 31,5 31,5 31,5 31,5 31,5 31,5
40 40 40 40 40
50 50 50 50 50
16 16 16 16 16 16
Rated short-time 25 25 25 25 25 25 25 25 25 25
Ik [kA]
withstand current (3 s) 31,5 31,5 31,5 31,5 31,5 31,5 31,5 31,5 31,5 31,5
40 40 40 40 40
50 50 50 50 50
40 40 40 40 40 40
50 50 50 50 50 50
63 63 63 63
Making capacity Ip [kA]
80 80 80 80 80 80 80 80 80 80
100 100 100 100 100
125 125 125 125 125
Operation sequence [O-0,3s-CO-15s-CO]
Opening time [ms] 45
Arcing time [ms] 10-15
Total breaking time [ms] 55-60
Closing time [ms] 80
H [mm] 640 649 655 655
Overall W [mm] 493 618 618 730
dimensions H
D [mm] 496 496 561 603
W D Interasse poli I [mm] 150 210 210 275
Weight [Kg] 114 114 145 165
1VCD000226
(up to 25 kA) TN
Standardised table of dimensions TN 7178 TN 7163 TN 7165
TN 7177 7177
(31.5 kA)
Absolute SF6 gas pressure (2) [kPa] 380
Operating temperature [C] - 5 ... + 40 C
Tropicalization IEC: 60068-2-30, 60721-2-1
Electromagnetic compatibility IEC 62271-1
10
HD4 17 HD4 24
17,5 24
17,5 24
38 50
95 125
50-60 50-60
630 1250 1600 1600 2000 2500 3150 3600 630 1250 1600 630 1250 1600 1600 2000 2500 3150 3600
16 16 16 16 16 16 16 16 16
20 20 20 20 20 20
25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25
31,5 31,5 31,5 31,5 31,5 31,5 31,5 31,5 31,5 31,5 31,5 31,5
40 40 40 40 40 40 40 40 40 40
50 50 50 50 50
16 16 16 16 16 16 16 16 16
20 20 20 20 20 20
25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25
31,5 31,5 31,5 31,5 31,5 31,5 31,5 31,5 31,5 31,5 31,5 31,5
40 40 40 40 40 40 40 40 40 40
50 50 50 50 50
40 40 40 40 40 40 40 40 40
50 50 50 50 50 50 50 50 50
63 63 63 63 63 63 63 63 63 63 63 63 63 63 63
80 80 80 80 80 80 80 80 80 80 80 80
100 100 100 100 100 100 100 100 100 100
125 125 125 125 125
45 45
10-15 10-15
55-60 55-60
80 80
649 655 655 818 730 655 818 (3
11
2. Selection and ordering
General characteristics
of fixed circuit-breakers (36 kV)
Fixed HD4 36 kV circuit-breaker
with 350 mm pole centre distance:
Ir = 630-1250-1600 A;
Isc = 16-20 kA.
Circuit-breaker HD4 36
IEC 62271-100
Standards
VDE 0671; CEI EN 62271-100 - File 7642
Rated voltage Ur [kV] 36
Rated insulation voltage Us [kV] 36
Withstand voltage at 50 Hz Ud (1 min) [kV] 70
Impulse withstand voltage Up [kV] 170
Rated frequency fr [Hz 50-60
Rated normal current (40 C) (1)
Ir [A] 630 1250 1600
16 16 16
20 (5)
20 (5)
20 (5)
Rated breaking capacity Isc [kA]
16 16 16
Rated short-time 20 20 20
Ik [kA]
withstand current (3 s)
40 40 40
50 50 50
Making capacity Ip [kA]
[O-0.3s-CO-15s-CO]
Operation sequence
[O-0.3s-CO-3min-CO]
Opening time [ms] 45
Arcing time [ms] 10-15
Total breaking time [ms] 55-60
Closing time [ms] 80
H [mm] 730/1060 (6)
Maximum overall
dimensions without W [mm] 880/955 (6)
H
insulating screens D [mm] 695
between phases (4)
W D Pole centre distance I [mm] 350
Weight [kg] 124 128 128
Standardised table of dimensions TN 7241
Absolute SF6 gas pressure (2)
[kPa] 380
Operating temperature [C] - 5 ... + 40
Tropicalization IEC: 60068-2-30, 60721-2-1
Electromagnetic compatibility IEC 62271-1
(1) Rated normal current defined in free air
(2) Rated service value
(3) For these versions, with 275 mm pole centre distance, special insulating partitions are provided (on request)
(4) For the dimensions of the insulating partitions (available on request), see the standardised table in chapter 5
(5) Operation sequence: O - 0.3 min - CO - 3 min - CO
(6) The second distance refers to the circuit-breaker with truck (available on request)
12
Fixed HD4 36 kV circuit-breaker
with 275 mm pole centre distance:
Ir = 1250-1600 A;
Isc = 25-31.5 kA;
Ir = 2000-2500 A;
Isc = 20-25-31.5 kA.
HD4 36
36
36
70
170
50-60
1250 (3)
1600 (3)
2000 (3)
2500 (3)
20 20
25 25 25 25
31.5 31.5 31.5 31.5
20 20
25 25 25 25
31.5 31.5 31.5 31.5
50 50
63 63 63 63
80 80 80 80
45
10-15
55-60
80
790/1123 (6)
790/1123 (6)
748/805 (6)
748/805 (6)
833 833
275 275
175 175 180 190
TN 7268 TN 7315
450 450
- 5 ... + 40
13
2. Selection and ordering
Circuit-breaker HD4/P 12
Standards IEC 62271-100
Rated voltage Ur [kV] 12
Rated insulation voltage Us [kV] 12
Withstand voltage at 50 Hz Ud (1 min) [kV] 28
Impulse withstand voltage Up [kV] 75
Rated frequency fr [Hz] 50-60
Rated normal current (40 C) (1)
Ir [A] 630 1250 1250 1600 2000 2500 3150 (3)
16 16
25 25 25 25 25 25
Rated breaking capacity Isc [kA]
31,5 31,5 31,5 31,5 31,5 31,5
40 40 40 40 40
50 50 50 50
16 16
Rated short-time 25 25 25 25 25 25
Ik [kA]
withstand current (3 s) 31,5 31,5 31,5 31,5 31,5 31,5
40 40 40 40 40
50 50 50 50
40 40
63 63 63 63 63 63
Making capacity Ip [kA]
80 80 80 80 80 80
100 100 100 100 100
125 125 125 125
Operation sequence [O-0,3s-CO-15s-CO]
Opening time [ms] 45
Arcing time [ms] 10-15
Total breaking time [ms] 55-60
Closing time [ms] 80
H [mm] 628 702 702 702 746
Overall W [mm] 532 682 682 882 882
dimensions H
D [mm] 659 640 640 643 643
W D Pole centre distance I [mm] 150 210 210 275 275
Weight [kg] 120 177 177 220 230
1vcd000227 TN 7286 TN 7350 TN 7351 TN 7352 TN7371
Standardised table of dimensions
(up to 25 kA) (31.5 kA)
Absolute SF6 gas pressure (2) 380
Operating temperature [C] - 5 ... + 40
Tropicalization IEC: 60068-2-30, 60721-2-1
Electromagnetic compatibility IEC 62271-1
(1) Rated normal current with circuit-breaker in UniGear type ZS1 switchgear and 40 C ambient temperature outside the switchgear
(2) Rated service value
(3) The circuit-breaker can reach rated currents higher than 3150 A with appropriate forced ventilation of the switchgear (for further information, consult the technical catalogue of
the UniGear type ZS1 switchgear).
(4) In the standard fitting, the truck locking electromagnetic (-RL2) is included to prevent circuit-breaker racking-in with auxiliary circuits not connected (plug not inserted in the socket).
(5) Rated current in switchgear with forced ventilation; with natural ventilation the rated current is 2300 A.
14
HD4/P 17 HD4/P 24
17.5 24
17.5 24
38 50
95 125
50-60 50-60
630 1250 1250 1600 2000 2500 3150 (3)
630 1250 1250 1600 2000 2500 (5)
16 16 16 16 16
20 20 20 20 20
25 25 25 25 25 25 25 25 25 25 25
31,5 31,5 31,5 31,5 31,5 31,5 31,5 31,5 31,5 31,5
40 40 40 40 40
50 50 50 50
16 16 16 16 16
20 20 20 20 20
25 25 25 25 25 25 25 25 25 25 25
31,5 31,5 31,5 31,5 31,5 31,5 31,5 31,5 31,5 31,5
40 40 40 40 40
50 50 50 50
40 40 40 40 40
50 50 50 50 50 50 50
63 63 63 63 63 63 63 63 63
80 80 80 80 80 80 80 80 80
100 100 100 100 100
125 125 125 125
45 45
10-15 10-15
55-60 55-60
80 80
628 702 702 702 746 736 792 821 821
532 682 682 882 882 636 653 842 842
659 640 640 643 643 799 799 788 788
150 210 210 275 275 210 210 275 275
120 177 177 220 230 125 177 177 220
1vcd000227 TN 7286
TN 7350 TN 7351 TN 7352 TN7371 TN 7354 1VCD000099 TN 7355 TN 7356
(up to 25 kA) (31.5 kA)
380 380
- 5 ... + 40 - 5 ... + 40
15
380 (480 at 40 kA)
2. Selection and ordering
Circuit-breaker
Standards IEC 62271-100
Rated voltage Ur [kV]
Rated insulation voltage Us [kV]
Withstand voltage at 50 Hz Ud (1 min) [kV]
Impulse withstand voltage Up [kV]
Rated frequency fr [Hz
Rated normal current (40 C) (1)
Ir [A]
Rated short-time
Ik [kA]
withstand current (3 s)
16
HD4/Z 40.5
40.5
40.5
95
185
50-60
1250 1600 2000 2500 (3)
25 25 25 25
31.5 (4)
31.5 (4)
31.5 (4)
31.5 (4)
25 25 25 25
31.5 31.5 31.5 31.5
63 63 63 63
80 80 80 80
45
10-15
55-60
80
1575
850
686
280
280
TN 7227
550
- 5 ... + 40
17
2. Selection and ordering
18
HD4/P 17 HD4/W 17 HD4/P 17 HD4/W 24 HD4/P 24 HD4/P 24
PB1 PB1 PB2 PB2 PB2 PB2 PB2 PB3 PB2 PB2 PB3 PB4 PB4 PB4 PB5 PB5 PB5
17.5 17.5 17.5 24 24 24
17.5 17.5 17.5 24 24 24
38 38 38 50 50 50
95 95 95 125 125 125
50-60 50-60 50-60 50-60 50-60 50-60
630 1250 630 1250 1250 1600 2000 3150 (3)
1600 2000 2500 630 1250 1250 1600 2000 2500 (4)
16 16 16 16 16 16 16 16 16 16 16
20 20 20 20 20
25 25 25 25 25 25 25 25 25 25 25 25
31.5 31.5 31.5 31.5 31.5 31.5 31.5 31.5 31.5 31.5 31.5 31.5
40 40 40 40 40 40 40 40 40
50 50 50 50 50
16 16 16 16 16 16 16 16 16 16 16
20 20 20 20 20
25 25 25 25 25 25 25 25 25 25 25 25
31.5 31.5 31.5 31.5 31.5 31.5 31.5 31.5 31.5 31.5 31.5 31.5
40 40 40 40 40 40 40 40 40
50 50 50 50 50
40 40 40 40 40 40 40 40 40 40 40
50 50 50 50 50
63 63 63 63 63 63 63 63 63 63 63 63
80 80 80 80 80 80 80 80 80 80 80 80
100 100 100 100 100 100 100 100 100
125 125 125 125 125
45 45 45 45 45 45
10-15 10-15 10-15 10-15 10-15 10-15
55-60 55-60 55-60 55-60 55-60 55-60
80 80 80 80 80 80
636 702 702 702 742 702 702 702 792 792 821 821
532 682 682 682 882 682 682 882 682 641 842 842
659 640 640 640 643 640 640 643 799 799 788 788
150 210 210 210 275 210 210 275 210 210 275 275
120 120 177 177 230 177 177 220 125 177 177 220
1VCD000227 TN 7229
TN 7182 TN 7421 TN 7239 1VCD000053 TN 7350 TN 7351 TN 7352 TN 7183 TN 7354 1VCD000099 TN 7355 TN 7356
(up to 25 kA) (31.5kA)
380 380 380 380 (5)
380 (5)
19
2. Selection and ordering
Circuit-breaker
Standards IEC 62271-100
Rated voltage Ur [kV]
Rated insulation voltage Us [kV]
Withstand voltage at 50 Hz Ud (1 min) [kV]
Impulse withstand voltage Up [kV]
Rated frequency fr [Hz
Rated normal current (40 C) (1)
Ir [A]
Rated short-time
Ik [kA]
withstand current (3 s)
[O-0.3s-CO-3min-CO]
Operation sequence
[O-0.3s-CO-15s-CO]
Opening time [ms]
Arcing time [ms]
Total breaking time [ms]
Closing time [ms]
H [mm]
Maximum W [mm]
overall H
dimensions D [mm]
W D Pole centre distance I [mm]
Weight [kg]
Standardised table of dimensions
Absolute SF6 gas pressure (2)
[kPa]
Operating temperature [C]
Tropicalization IEC: 60068-2-30, 60721-2-1
Electromagnetic compatibility IEC 62271-1
(1) Rated normal current with circuit-breaker in UniGear ZS2 switch-gear and 40 C
ambient temperature outside the switchgear
(2) Rated service value
(3) 2500 A with forced ventilation of the switchgear
20
HD4/W 36
36
36
70
170
50-60
1250 1250 1600 1600 2000 2000 2500 (3)
2500 (3)
20 20 20 20
25 25 25 25
31.5 31.5 31.5 31.5
20 20 20 20
25 25 25 25
31.5 31.5 31.5 31.5
50 50 50 50
63 63 63 63
80 80 80 80
45
10-15
55-60
80
973 973 973 973
882 882 882 882
788 788 789 789
275 275 275 275
130 225 225 270
TN 7402 TN 7316 TN 7317 TN 7317
450
- 5 ... + 40
21
2. Selection and ordering
Circuit-breaker HD4/Sec 24
Standards IEC 62271-100
Rated voltage Ur [kV] 24
Rated insulation voltage Us [kV] 24
Withstand voltage at 50 Hz Ud (1 min) [kV] 50
Impulse withstand voltage Up [kV] 125
Rated frequency fr [Hz 50-60
Rated normal current (40 C) (1)
Ir [A] 630 1250
16 16
Rated breaking capacity Isc [kA] 20 20
16 16
Rated short-time
Ik [kA] 20 20
withstand current
40 40
Making capacity Ip [kA] 50 50
Operation sequence [O-0.3s-CO-15s-CO]
Opening time [ms] 45
Arcing time [ms] 10-15
Total breaking time [ms] 55-60
Closing time [ms] 80
H [mm] 800
Maximum W [mm] 682
overall H
dimensions D [mm] 739
W D Pole centre distance I [mm] 210
Truck run [mm] 200
Weight [kg] 123
Standardised table of dimensions 1VCD000220
Absolute SF 6 gas pressure (2)
[kPa] 380
Operating temperature [C] - 5 ... + 40
Tropicalization IEC: 60068-2-30, 60721-2-1
Electromagnetic compatibility IEC 62271-1
(1) Rated normal current with withdrawable circuit-breaker in switchgear
(2) Rated service value
22
General characteristics of withdrawable
circuit-breakers for UniSwitch switchgear
(CBW type units) and UniMix switchgear
(P1/E type units) (24 kV)
25 25
40 (63) (4)
40 (63) (4)
40 40
Making capacity Ip [kA] 50 (63) (4)
50 (63) (4)
50 50
63 63
Operation sequence [O-0.3s-CO-15s-CO]
Opening time [ms] 45 45
Arcing time [ms] 10-15 10-15
Total breaking time [ms] 55-60 55-60
Closing time [ms] 80 80
H [mm] 800 800
Maximum W [mm] 682 682
overall H
dimensions D [mm] 739 739
W D Pole centre distance I [mm] 210 210
Truck run [mm] 200 200
Weight [kg] 123 123
Standardised table of dimensions 1VCD000046 1VCD000046
Absolute SF 6 gas pressure (2)
[kPa] 380 380
Operating temperature [C] - 5 ... + 40 - 5 ... + 40
Tropicalization IEC: 60068-2-30, 60721-2-1
Electromagnetic compatibility IEC 62271-1
(1) Rated normal current with withdrawable circuit-breaker in switchgear
(2) Rated service value
(3) The short-time withstand current and its duration can be limited by the switchgear: see the specific UniSwitch and UniMix switchgear catalogues
(4) The values in brackets refer to the 12 kV rated voltage
(5) The activation rollers of the top shutter are supplied mounted and adjusted by the supplier of the UniSwitch switchgear
(6) The activation rollers of the top shutter of the UniMix switchgear P1/E are available on request
23
2. Selection and ordering
Standard equipment
The basic versions of the circuit-breakers are always three-
pole and fitted with:
manual operating mechanism
mechanical signalling device for closing springs charged/
discharged
mechanical signalling device for circuit-breaker open/closed
closing pushbutton
opening pushbutton
operation counter
12 to 36 kV series: set of 14 auxiliary contacts for circuit-
breaker open/closed; five closing contacts (circuit-breaker
open signalling) and seven opening contacts (circuit-breaker
closed signalling) are available for use by the customer if Terminals for fixed circuit-breaker.
the apparatus is equipped with all the electrical applications
40.5 kV series: set of 10 auxiliary contacts for circuit-
breaker open/closed; three closing contacts (circuit-breaker
open signalling) and four opening contacts (circuit-breaker
closed signalling) are available for use by the customer if
the apparatus is equipped with all the electrical applications
lever for manually charging the closing springs (the quantity
must be defined according to the number of pieces of
apparatus ordered).
24
Moreover:
for fixed circuit-breaker
connection terminals (not available for low-end circuit-
breakers)
terminal board for auxiliary circuits;
for withdrawable circuit-breaker
isolating contacts
cord with connector (plug only) for auxiliary circuits
lock to prevent racking-in of circuit-breaker with different
rated current
racking-in/out lever (the quantity must be defined
according to the number of pieces of apparatus ordered)
locking electromagnet in the truck (/P versions).
Tulip isolating contacts for withdrawable circuit-breaker.
25
2. Selection and ordering
closed.
1A 1B 1C 2 3A 3B 4 5 6A 6B 7 8
Fixed circuit-breakers
HD4 12
HD4 17
HD4 24
HD4 36
Withdrawable circuit-breakers
for UniGear type ZS1 switchgear
HD4/P 12
HD4/P 17
HD4/P 24
Withdrawable circuit-breakers for
UniGear 36 type ZS3.2 switchgear
HD4/Z 40.5
Withdrawable circuit-breakers
for PowerCube modules
HD4/W 12
HD4/W 17
HD4/W 24
HD4/W 36 (5)
Withdrawable circuit-breakers
for UniSec switchgear
HD4/SEC 24
Withdrawable circuit-breakers for
UniSwitch and UniMix switchgear
HD4/US 24
26
Withdrawable circuit-breaker transmitted contacts (installed in the
(1)
circuit-breaker truck).
10
-MAS spring charging geared motor.
11
-FCM1 thermomagnetic protection of spring charging geared motor.
Electric signalling of springs charged.
12A
Electric signalling of springs discharged.
12B
Opening pushbutton lock.
13A
Closing pushbutton lock.
13B
14
Open circuit-breaker key lock.
15
-RLE1 operating mechanism locking magnet.
(4)
(4)
(4)
16
-RLE2 truck locking magnet.
17
Interlock for fixed circuit-breaker.
18
Mechanical isolation interlock with the switchgear door.
(3)
Two-level pressure switch (2).
19A
Two-level pressure switch plus SF6 control device with three LEDs (2).
19B-C
20
Insulating partitions.
21
27
2. Selection and ordering
Optional accessories
The accessories identified with the same number are alternative to each other; consult the table at the end of the
chapter for the electrical characteristics.
supplementary shunt
opening release -MBO2
28
undervoltage release
-MBU
3 Under-voltage release -MBU 3A Undervoltage release -MBU (only for power supply
Undervoltage release -MBU opens the circuit-breaker branched on the supply side of the circuit-breaker)
when there is a sensible reduction or lack of the voltage 3B Undervoltage release -MBU with electronic time-lag
that energizes it. The circuit-breaker can only close when device -KFT (only for power supply branched on the
the release is energized (the closing lock is obtained supply side of the circuit-breaker).
mechanically). It can be used for remote release (by means Circuit-breaker closing is inhibited when the undervoltage
of a pushbutton of the normally closed type), for locking on release (equipped with electronic time-lag device -KFT) is not
automatic closing and/or opening in the absence of voltage energized. Electronic time-lag device -KFT is only designed
in the auxiliary circuits. Energized by means of the secondary to delay the tripping action of undervoltage release MBU at
output of a voltage transformer, it provides locking upon preset, adjustable times (0.5 - 1 - 1.5 - 2 - 3 s).
automatic closing/opening in the absence of voltage in the This device is consigned with the 0.5 s time setting. Consult
Medium Voltage main circuit. If shunt closing release -MBC the Chapter on circuit diagrams, note I, page 69). Electronic
and undervoltage release -MBU are energized by the same time-lag device -KFT must be installed inside the operating
supply voltage and automatic closing of the circuit-breaker enclosure of the circuit-breaker.
is required when the auxiliary voltage returns, there must To avoid tripping, use of the delayed undervoltage release is
be a delay of at least 50 ms between undervoltage release convenient when the supply network of release -MBU may
energizing and energizing of the shunt closing release to allow often be liable to brief voltage dips or tiny power outages.
the closing operation to take place. The voltage of the undervoltage release must be within the
operating range of the electronic time-lag device.
29
2. Selection and ordering
Optional accessories
30
Auxiliary contacts BGB1 and BGB2 conform to the
following standards/regulations/directives:
IEC 62271-100
IEEE C37.54
EN 61373 cat.1 class B / impact and vibration test
Germanish Loyd regulation / vibrations envisaged by the
shipping registers
UL 508
EN 60947 (DC-21A DC-22A DC-23A AC-21A)
RoHS Directive
General characteristics
Insulation voltage to standard 660 V AC
VDE 0110, Group C 800 V DC
Rated voltage 24 V ... 660 V 6B Auxiliary contacts -BB1-BB2-BB3 for the 40.5 kV
Test voltage 2 kV for 1 min withdrawable series only
Maximum rated current 10 A - 50/60 Hz Electrical signalling of circuit-breaker open/closed includes,
Breaking capacity Class 1 (IEC 62271-1) as standard equipment, a set of 10 auxiliary contacts for the
Number of contacts 5 40.5 kV withdrawable version.
Groups of contacts 10 / 16 / 20 Set of 10 circuit-breaker open/closed auxiliary contacts.
Contact travel 90 Three closing contacts (circuit-breaker open signalling) and
Actuating force 0.66 Nm four opening contacts (circuit-breaker closed signalling) are
Resistance <6.5 m available if the apparatus is equipped with all the electrical
Storage temperature 30 C ... +120 C applications.
Operating temperature
20 C ... +70 C A set of 15 auxiliary contacts for signalling circuit-breaker
(-30 ref. ANSI 37.09)
open/closed can be supplied on request. Four closing
Contact overtemperature 10 K
contacts (circuit-breaker open signalling) and four opening
Mechanical life 10,000 mechanical operations
contacts (circuit-breaker closed signalling) are available if the
Protection class IP20
apparatus is equipped with all the electrical applications.
Cable section 1 mm2
31
2. Selection and ordering
Optional accessories
7 Transient contact -BGB4 with momentary closing 8 Position contact of withdrawable circuit-breaker
during circuit-breaker opening. -BGT3
This contact closes momentarily (for about 30 ms) when the Only supplied for withdrawable circuit-breakers for UniGear
circuit-breaker opens. The transient contact is activated by ZS1 and ZS2 switchgear and PowerCube modules from 12 to
the main operating shaft, thus the indication is only provided 36 kV.
when the main contacts of the circuit-breaker effectively open. This contact is installed in the truck. It is in the closed state
when the truck is fully racked-in or fully racked-out and is in
the open state when the truck is being racked-in/racked-out.
It is used in conjunction with the locking magnet in the
operating mechanism (-RLE1) to prevent remote closing
during movement in the compartment.
It is supplied as standard equipment when locking magnet
-RLE1 is installed in the operating mechanism and truck-
mounted contacts are not required (-BGT1, -BGT2). It cannot
be supplied when truck-mounted contacts are required
(-BGT1; -BGT2).
32
General characteristics
Insulation voltage to standard 660 V a.c.
VDE 0110, Group C 800 V d.c.
Rated voltage 24 V ... 660 V a.c.
Test voltage 2 kV 50 Hz (for 1 min)
Rated overcurrent 10 A
Number of contacts 5
Contact run 6 mm ... 7 mm
Activation force 26 N
Resistance 3 m
Storage temperature 20 C ... +120 C
Operating temperature 20 C ... +70 C
Contact overtemperature 20 K
Number of cycles 10.000
Unlimited breaking capacity if used with 10 A fuse in series
9 Electrical signalling contacts for circuit-breaker
connected and isolated (-BGT1; -BGT2)
Electrical characteristics
These contacts are an alternative to the withdrawable circuit-
Un Rated current Breaking capacity
breaker position contact (-BGT3) and are recommended when
220 V a.c. Cosj = 0.7 2.5 A 25 A
there are no position contacts on the roof of the circuit-
380 V a.c. Cosj = 0.7 1.5 A 15 A
breaker compartment (for signalling circuit-breaker racked-
500 V a.c. Cosj = 0.7 1.5 A 15 A
out or racked-in). Contacts -BGT1, -BGT2 are supplied as
660 V a.c. Cosj = 0.7 1.2 A 12 A
standard equipment when locking magnet -RLE1 is installed
1 ms 10 A 12 A
in the operating mechanism and position contact BGT3
24 V d.c. 15 ms 10 A 12 A
has not been requested. Contacts -BGT1 and BGT2 have
50 ms 8A 10 A
the same general and electrical characteristics as auxiliary
200 ms 6A 7.7 A
contacts 7b. -BB1, -BB2, -BB3.
1 ms 8A 10 A
60 V d.c. 15 ms 6A 8A
50 ms 5A 6A
200 ms 4A 5.4 A
1 ms 6A 8A
15 ms 4A 5A
110 V d.c.
50 ms 2A 4.6 A
200 ms 1A 2.2 A
1 ms 1.5 A 2A
15 ms 1A 1.4 A
220 V d.c.
50 ms 0.75 A 1.2 A
200 ms 0.5 A 1A
33
2. Selection and ordering
Optional accessories
10 S pring-loading geared motor -MAS 11 Thermal magnetic protection -FCM1 of the closing
The geared motor automatically loads the closing spring of spring loading motor
the circuit-breakers operating mechanism after the circuit- Thermal magnetic protection of the closing spring loading
breaker has closed each time and until the yellow spring motor is supplied as part of the standard equipment for
loaded indicator appears. If a power cut occurs when loading 24 V DC rated voltage while it is available on request for other
is in progress, the geared motor stops and automatically voltage values. It is always supplied with electrical signalling
starts loading the springs again when the power returns. of thermal magnetic protection tripped.
Loading can always be completed in the manual mode (as
it is during maintenance work) by means of the dedicated
lever supplied. Check the power available in the supply circuit
to find out whether several motors for loading the closing electrical signalling of
springs can operate at the same time. To prevent excessive spring loaded/discharged
spring loaded/discharged
mechanical indicator
34
13 Locks and interlocks 14 Circuit-breaker open key lock (different keys or the
13 A O pening pushbutton lock (with or without padlock). same keys).
Locks the opening pushbutton with a 4 mm diameter padlock The locking action is performed by a special circular lock.
(not part of the standard equipment). The padlock is only Can be supplied with different keys or the same keys (for
supplied on request. several circuit-breakers). To apply the key lock, press the
opening pushbutton, turn the key and remove it. Local manual
closing and remote electrical closing are inhibited once the
13 B Closing pushbutton lock (with or without padlock).
key has been removed.
Locks the closing pushbutton with a 4 mm diameter padlock
(not part of the standard equipment). The padlock is only
supplied on request.
35
2. Selection and ordering
Optional accessories
locking magnet on
operating mechanism
36
Interlock to prevent circuit-breaker Interlock to prevent racking-in/
closing during racking-in/out. out when circuit-breaker is
closed.
17 Interlock for fixed circuit-breaker (for fixed apparatus 18 Mechanical isolation interlock with the door of Unigear
converted to plug-in by the customer). ZS1, ZS2 switchgear and the PowerCube enclosure.
This device can be useful when fixed circuit-breakers are This device prevents the circuit-breaker from being racked-
converted into withdrawable ones by the customer. in when the switchgear door is open. It is only intended for
It allows the customer to create a mechanical lock that inhibits circuit-breakers used in UniGear ZS1 and ZS2 switchgear
racking-out/racking-in when the circuit-breaker is closed and and in PowerCube modules (which must be equipped with a
prevents the circuit-breaker from closing during movement. dedicated actuator on the door).
Note. The device must be requested when the order is placed
since it must be assembled in the factory.
37
2. Selection and ordering
Optional accessories
19 Gas monitoring device 21 3-lobed key for manual opening and closing
Notes: operations
specify when ordering the apparatus if the pressure This accessory is only available for the 40.5 kV HD4/Z series.
switch is required since it cannot be installed by the
customer at a later date;
devices 19B and 19C are supplied without LED for the
40.5 kV HD4/Z series
19A Two-level pressure switch
19B Two-level pressure switch with two-level SF6 monitoring
device, three LEDs and supplementary shunt opening
release MO2: circuit-breaker opening and closing lock
19C Two-level pressure switch with two-level SF6 monitoring
device and three LEDs: circuit-breaker locking in the
position it has reached
38
Characteristics of electrical accessories
39
3. Specific product characteristics
HD4 circuit-breakers are unaffected by mechanically HD4 circuit-breakers are manufactured in compliance with the
generated vibrations. strictest regulations for use in hot-humid-saline climates.
For the versions approved by the naval registers, please All the most important metal components are treated against
contact us. corrosive factors according to atmospheric corrosivity class
C5 of standard BS EN 12500.
Galvanisation is carried out in accordance with UNI ISO 2081
Standards, classification code Fe/Zn 12, with a thickness of
12x10-6 m, protected by a conversion layer mainly consisting
of chromates in compliance with the UNI ISO 4520 Standards.
40
Altitude Graph for determining the Ka correction factor
according to the altitude
Example
Installation altitude 2000 m
Operation at the rated voltage of 12 kV
Withstand voltage at industrial frequency 28 kV rms
Impulse withstand voltage 75 kVp
Factor Ka obtained from graph = 1.13.
1,20
1,10
1,00
1000 1500 2000 2500 3000 3500 4000 H
H = altitude in metres;
m = value referred to industrial frequency and the
atmospheric impulse withstand voltages and those
between phase and phase.
41
3. Specific product characteristics
HD4 circuit-breakers are manufactured in accordance with The ESH operating mechanism on HD4 circuit-breakers
the ISO 14000 Standards (Guidelines for environmental (in all versions) is fitted with a mechanical anti-pumping
management). device which prevents re-closing due to either electrical or
The production processes are carried out in compliance mechanical commands.
with the Standards for environmental protection in terms of Should both the closing command and any one of the
reduction in energy consumption as well as in raw materials opening commands be active at the same time, there
and production of waste materials. All this is thanks to would be a continuous succession of opening and closing
the medium voltage apparatus manufacturing facility operations.
environmental management system. The anti-pumping device avoids this situation, ensuring that
Assessment of the environmental impact of the life cycle of each closing operation is only followed by a single opening
the product, obtained by minimising energy consumption operation and that there is no closing operation after this. To
and overall raw materials of the product, became a concrete obtain a further closing operation, the closing command must
matter during the design stage by means of targeted selection be released and then relaunched.
of the materials, processes and packing. Furthermore, the anti-pumping device only allows circuit-
This is to allow maximum recycling at the end of the useful life breaker closure if the following conditions are present at the
cycle of the apparatus. same time:
operating mechanism springs fully charged
opening pushbutton and/or opening release (-MBO1/-
MBO2) not enabled
main circuit-breaker contacts open.
42
Spare parts Ordering
Replacement can only be carried out by trained personnel For availability and ordering of spare parts, please contact our
and/or in our workshops: Service, specifying the circuit-breaker serial number.
opening springs
closing springs
complete pole
basic operating mechanism
bushings, terminals and insulating protections.
43
4. Overall dimensions
Fixed circuit-breakers
HD4 493
150 150 87 336,5 13,5
TN 1VCD000226 67,5 M12 depth 25
2XM8 depth 16
Ur 12 kV
Ir 630 A
1250 A
27
Isc 16 kA
25 kA
205
586
63
541
27
260,5
248,5
21,5
43
347 10,5 13
117 M12 depth 22
402 114,5 2XM8 depth 16
473 270
493 332
Fixed circuit-breakers
22
Ur 12 kV
Ir 630 A
1250 A
Isc 31.5 kA
317
317
28
HD4
10
22
22
YU
640
TN 7177
10
582
549.5
540
Ur 12 kV YU
Ir 1600 A 8
297.5
297.5
Q60
257.5
Isc 16 kA
25 kA
21.5
43
3
31.5 kA
347
10.5 13 120
473 270
1250A 37
493 335
1600A 630A
44
Fixed circuit-breakers
22
Ir 630 A
1250 A
22
1600 A
317
317
Isc 16 kA
10
25 kA 22 28
22
648.5
10
622
31.5 kA
558.5
YU
YU
468.5
306. 5
306.5
266.5
8
43
472 13 120
10.5
598 270 37
1250A
618 335
1600A 630A
Fixed circuit-breakers
HD4 600
578
TN 7163
210 210
Ur 12 kV
17.5 kV
Ir 1600 A
Isc 40 kA
2 x 18
50 kA
310
310
28
80
HD4
15.5 32
655
TN 7163
622
YU
Ur 12 kV
8
YU
17.5 kV
306.5
Ir 2000 A
266.5
Q6
0 8
Isc 25 kA
13
31.5 kA
43
40 kA
472 10.5 35
50 kA 2.5
20
598 322
618 385
561
45
4. Overall dimensions
Fixed circuit-breakers
349.5
Ir 2500 A
3150 A
670 min.
3600 A
15
Isc 25 kA
310
28
62
31.5 kA
40 kA 20 40
655
20
622
YU
50 kA
468.5
40
YU
20
20
HD4 8
TN 7165
266.5
4 x 18
13
Ur 24 kV
Ir 2500 A
43
20
322 35
728
3600 A 385
748 603
Isc 25 kA
31.5 kA Insulating partitions (only for 24 kV)
40 kA to be provided by the customer
(a special kit is available on request).
Fixed circuit-breakers
Isc 16 kA
670 min.
20 kA
362
362
25 kA
22
22
10
729.5
28
712
639.5
622
YU
468.5
YU
342.5
342.5
302.5
10
Q60
8
13
43
598 270
37
1250A
618 1600A 335 630A
46
Fixed circuit-breakers
Ir 630 A
1250 A
22
22
1600 A
362
362
Isc 16 kA
22
20 kA
22
25 kA
729.5
28
10
639.5
620
YU
468.5
YU
10
342.5
342.5
302.5
Q6
0 8
13
43
602 120
10.5
728 270
37
748
1250A 335
1600A 630A
Fixed circuit-breakers
HD4 730
708
TN 7174
275 275
Ur 24 kV
Ir 1600 A
Isc 31.5 kA
40 kA 2x 18
310
310
80
HD4
28
TN 7174 15.5 32
622
655
Ur 24 kV YU
8
Ir 2000 A YU
Isc 25 kA 8
306.5
266.5
31.5 kA Q6
0
40 kA 13
43
728 322
35
385
748 561
47
4. Overall dimensions
Fixed circuit-breakers
HD4 400
880
358
with truck (on request) 350 350 10
22
50
TN 7241
Ur 36 kV
Ir 630 A
362
1250 A
1600 A 22
729.5
28
712
639. 5
Isc 16 kA
539
10
20 kA
* 106 0
342.5
21
302.5
* Distance with truck 3
(if provided). * 13
* 887
755
2x 10.5 120
881 363.5 270
43
901 695.4 37
*4.9
* 348
* 13
* 855 * 13 * 200
* 355 *85
*4
* 915 *40
* 955 * 516.4
Fixed circuit-breakers
HD4 730
708
with truck (on request)
TN 7268
Ur 36 kV
Ir 1250 A
1600 A
Isc 25 kA
31.5 kA
HD4
with truck (on request)
TN 7268
Ir 2500 A
Isc 20 kA
25 kA
31.5 kA
48
Fixed circuit-breakers
HD4
with truck (on request)
TN 7315
Ur 36 kV
Ir 2500 A
Isc 20 kA
25 kA
31.5 kA
49
4. Overall dimensions
10
TN 1VCD000227
Ur 12 kV
17.5 A
Ir 630 A
98.5
1250 A
Isc 16 kA
205 1
35
618 2
619
25 kA
626
541
586
Also suitable for Power-
63
Cube PB1
260 1
247.5
19.5
154 1
22
340 25 320
21.5
4
4
456 370
503
383 53
531
416
501 437
490 558
456 2 661
150 1 150 1
55
608
50
HD4/P withdrawable circuit-breakers for UniGear type ZS1 switchgears
HD4/P 493
128
TN 7286 150 1 150 1
120 5.5
30 202
Ur 12 kV
10
17.5 kV
Ir 630 A
1250 A
67.5
Isc 31.5 kA
79
35
48
205 1
618 2
642.5
618
586
543
63
33.5
260 1
247.5
78
154 1
20
21.5
4
19.5
340
4
416
4
4
458 2
437
503
36 570 1.5 53
532
659
HD4/P 636
640
579
TN 7350 210 1 210 1 119
Ur 12 kV 272
111.5 17
44
10
17.5 kV
Ir 1250 A
Isc 40 kA
79
68
122
HD4/P 67.5
310 1
TN 7350
Ur 12 kV
691
688
686
668.5
17.5 kV
63
Ir 1600 A
543
Isc 25 kA 53.5
280 1
31.5 kA 40
245
164.5 1
89
40 kA (*) 21
50 kA (*)
19.5
20
(*) Also suitable for 550 4
21.5
29 359
4
4
51
4. Overall dimensions
HD4/P 636
640
579
TN 7351 119
210 1 210 1
Ur 12 kV 272 111.5 17
44
10
17.5 kV
Ir 2000 A
Isc 25 kA
31.5 kA
79
68
122
40 kA (*) 67.5
310 1
50 kA (*)
688
686
PowerCube PB2.
669
63
543
53.5
280 1
40
245
164.5 1
89
21
19.5
20
4
550
21.5
359
4
29
4
626 2
416
653 36 551 1.5 53
682
HD4/P 842
643
TN 7352 708
119
375
Ur 12 kV (*) 111.5 17
275 1 275 1
17.5 kV 144
10
Ir 2500 A
Isc 25 kA
31.5 kA
40 kA
109
152
67.5
50 kA
310 1
668.5
PowerCube PB3.
58
63
43.5
280 1
30
245
89
21
164.5 1
19.5
750 4
21.5
4
4
29 359
806 2
416
853
36 554 1.5 53
882
52
HD4/P withdrawable circuit-breakers for UniGear type ZS1 switchgears
HD4/P 842
708 643
TN 7371
375
Ur 12 kV 96.5 17
275 1 275 1
17.5 kV
10
Ir 3150 A (*)
Isc 25 kA
31.5 kA
40 kA
50 kA
109
152
67.5
310 1
(*) 3150 A with forced
switchgear ventilation
730
732
(consult the UniGear
730
43.5
30
280 1
245
89
164.5 1
21
19.5
4
21.5
750 29 359
4
806 2 416
853 36 554 1.5 53
882
HD4/P 636
210 1 119 23
210 1
TN 7354
272 18
20
Ur 24 kV 44
Ir 630 A
35
1250 A
Isc 16 kA (*)
20 kA
79
25 kA
310 1
67.5
(*) 630 A only.
2.5
772.5
768
763
736
645
63
12
325 1
12.5
125
253.5
198 2
25.5
4 53
4
610 2 460
4
653 36 7101.5
682
53
4. Overall dimensions
HD4/P 641
799
578
TN 1VCD000099
210 1 210 1 23
Ur 24 kV 272
67.5 44
Ir 1250 A
20
Isc 31.5 kA
92.6
310 1
28
35
792
776
718
682
63
329 1
25.5
293
125
10
550 202 1 4
19.5
21.5
610 2 460
653 36 710 1.5 53
682
20
Ur 24 kV 144 232 19
Ir 1600 A
Isc 16 kA
20 kA
25 kA
79
31.5 kA
122
67.5
310 1
814
807
733
63
700
43.5
345 1
30
310
125
11
198 1
806 2 4
4
457
853
882 36 699 1.5 53
54
HD4/P withdrawable circuit-breakers for UniGear type ZS1 switchgears
20
19
Ur 24 kV 144 232
Ir 2000 A
Isc 16 kA
20 kA
79
25 kA
31.5 kA
122
67.5
310 1
58
HD4/P
814
817.5
807
TN 7356 (**)
733
Ur 24 kV
63
700
Ir 2500 A (*)
Isc 20 kA 43.5
345 1
25 kA 30
310
125
198 1
31.5 kA 11
19.5
750
21.5
4
4
457
4
(**) Also suitable for 806 2
PowerCube PB5. 853 36 699 1 53
882
HD4/W 128
493 120
TN 7229
150 150 56
Ur 12 kV 30 202 72 5.5
17.5 kV
10
Ir 630 A
1250 A
Isc 31.5 kA
48
35
79
205 1
624.5
632
620
620
543
28
260 1
78
154 1
4
19.5
340
4
4
4
21.5
416.5
458 2
437 20
503
36 570 1.5 53
532
55
4. Overall dimensions
10
17.5 kV
Ir 630 A
1250 A
79
35
Isc 16 kA
67.5
310 1
25 kA
28
31.5 kA
688
691
688
688
636
63
640
16
280 1
29
245
89
165 1
4
550
19.5
21.5
4
359 40
6261
653 416
682 36 551 1.5 53
HD4/W 636
578
56
TN 7421 210 1 210 1
44 228 63 15
Ur 12 kV
17.5 kV 10
Ir 1250 A
Isc 40 kA
35
79
50 kA 67.5
310 1
28
688
688
691
636
63
16
280 1
245
89
165 1
4
19.5
626 2
21.5
4
4
29 359 40
653
416
682 36 551 1.5 53
640
56
HD4/W withdrawable circuit-breakers for PowerCube modules
HD4/W 636
578
TN 7239
210 1 210 1
56
Ur 12 kV 272
63 15
44
17.5 kV
Ir 1600 A
10
2000 A
Isc 16 kA
25 kA 67.5
310 1
31.5 kA 28
698
691
668.5
635.5
63
122
79
280 1
245
89
165 1
4
20
550
4
21.5
4
29 359 40
626 2
653 36 551 1.5 53
682 640
HD4/W 842
708
TN 1VCD000053
375 643
Ur 12 kV 275 1 275 1 112 16
17.5 kV 144
10
Ir 3150 A
Isc 31.5 kA
109
40 kA
50 kA
152
67.5
310 1
742
730
730
732
58
63
43.5
280 1
30
245
164.5 1
89
21
4
19.5
750 29 359
21.5
4
806 2 416
853
36 554 1.5 53
882
57
4. Overall dimensions
HD4/W 636
799
578
TN 7183 119
210 1 210 1
18
Ur 24 kV 272
23
20
44
Ir 630 A
1250 A
Isc 16 kA
20 kA
35
79
25 kA
310 1
67.5
28
772
763
772.5
736
644.5
63
325 1
12.5
125
253.5
198 1
25.5
4
610 2 460
4
Withdrawable circuit-breakers HD4/W for UniGear type ZS2 switchgear and for PowerCube module
20
Ir 1250 A
Isc 20 kA
25 kA
35
380
78
941.5
949
952
833
63
60
44
480
198
345
10
125
198
805 4
4
457
836
36 699 53
853
882
58
Withdrawable circuit-breakers HD4/W for UniGear type ZS2 switchgear and for PowerCube module
HD4/W 842
730
TN 7316 706 18
23
Ur 36 kV 275 275
35
Ir 1250 A
Isc 31.5 kA
380
953
956
973
484
125
202
805 4
456
836
30 701 57
853
882
Withdrawable circuit-breakers HD4/W for UniGear type ZS2 switchgear and for PowerCube module
20
Ur 36 kV 67.5 144 232
Ir 1600 A
2000 A
2500 A (*)
122
79
Isc 20 kA
380
25 kA
31.5 kA 78
ventilation.
952
949
903.5
833
63
60
44
480
345
125
10
198
21.5
750
20
4
4
805 457
836 36 699 53
853
882
59
4. Overall dimensions
HD4/Z/40.5 kV 840
245
280 280
TN 7227
Ur 40.5 kV
385
Ir 1250 A
2 5
1600 A
2000 A
2500 A (*)
328
Isc 25 kA
A
31.5 kA
1575
1288.5
type Powerbloc; with
27
15
forced ventilation in
20
switchgear type
100
ZS3.2.
50
900
23 23
30 40
550
43 43
485
22
16
18
120
85
45
32.5 103
100 140 150
A 25 230 200
718
1250-1600 A 35 mm 503
760
582
2000-2500 A (*) 79 mm
HD4/US withdrawable circuit-breakers for UniSwitch (CBW) and UniMix (P1/E) switchgears
1250 A
Isc 16 KA
20 kA
79
25 kA (*)
310 1
67.5
(*) Only for UniMix P1/E
28
736
644.5
8
63
435.5 2
8
325 1
253.5
25.5
550
653
4
4 53
682 36 650 1.5
60
HD4/US withdrawable circuit-breakers for UniSwitch (CBW) and UniMix (P1/E) switchgears
25
229
Ir 630 A
45
1250 A
1
Isc 16 KA
68
79
20 kA
310 1
739
35
A
644,5
734,5
435,5 2
63
36 8
325 1
254
653 25 320
19
4
681 370
382 4
650 414
210 1 210 1 687 1,5 53
19,5
36,3
25
55
DETAIL A
SCALE 1 : 2
61
5. Electric circuit diagram
Application diagrams
The following diagram (No. 1VCD400197) shows the circuits fixed circuit-breakers up to 36 kV, 350 mm pole centre
of the withdrawable circuit-breakers up to 24 kV type HD4/P, distance - No. 1VCD400192
HD4/W, HD4/US, delivered to the customer by means of withdrawable circuit-breakers for PowerCube PB6 and
connector X. UniGear tipo ZS2 - No. 1VCD400194
Specific diagrams are available for other types of circuit- HD4/z 40.5 kV - No. 1VCD400013
breakers: In any case, to take into account the evolution of the product,
fixed circuit-breakers up to 24 kV - No. 1VCD400192 it is always useful to refer to the circuit diagram provided with
fixed circuit-breakers 36 kV, 275 mm pole centre distance each circuit-breaker.
- N. 1VCD400193
Electromagnetic effect Conductors in shielded Motor (general symbol) Closing position contact
cable (two conductors (limit switch)
shown)
62
63
5. Electric circuit diagram
64
65
5. Electric circuit diagram
66
State of operation shown Contacts 21-22-24 change over when the
The diagram indicates the following conditions: gas pressure reaches a value of less than 280
circuit-breaker open and connected kPa absolute from 380 kPa absolute. If rated
circuits de-energized pressure is restored, these contacts change
closing springs discharged over again when, starting from a value of less
key lock with key inserted and held than 280 kPa absolute, the value of 310 kPa
gas pressure at rated service value (380 kPa absolute). absolute is reached.
-FCM1 = Thermomagnetic circuit-breaker for protection
of the spring-charging motor (see note F)
Caption -MAS = Motor for the closing spring charging (see note C)
= Number of diagram figure -MBC = Shunt closing release
* = See note indicated by the letter -MBO1 = First shunt opening release (see note E)
-BCR = Overcurrent release with microprocessor type -MBO2 = Second shunt opening release (see note E)
PR512 outside the circuit-breaker (see note D) -MBO3 = Opening solenoid for microprocessor release
-BER = Device for continuous control of shunt opening PR512 outside circuit-breaker (see note D).
release coil continuity (see note E -MbU = Instantaneous undervoltage release or
-BGB1, -BGB2 = Circuit-breaker auxiliary contacts undervoltage release with electronic time-delay
-BGB4 = Auxiliary passage contact (with momentary device (see note B)
closing during circuit-breaker opening) -KFI = Integrated circuit for gas pressure control,
-BGB5 = Contacts for electrical signalling of undervoltage including:
release energised/de-energised -PFG = Green lamp indicating normal gas
-BGK = Contact operated by the key lock preventing pressure
electrical opening with earthing truck connected -PFR = Red lamp indicating insufficient gas
(compulsory accessory for earthing trucks with pressure
making capacity) -PFY = Yellow lamp indicating low gas pressure
-BGS1 = Limit contacts of the spring charging motor -KFA1=Auxiliary relay to double the -BP
-BGS2 = Contact for signalling closing springs loaded- pressure-switch contacts with
discharged intervention for low gas pressure
-BGT1 = Contacts electrically signalling circuit-breaker in -KFA2=Auxiliary relay to double the -BP
the connected position (see note G) pressure-switch contacts with
-BGT2 = Contacts electrically signalling circuit-breaker in intervention for insufficient gas pressure
the isolated position (see note G) -XDB5=Connector
-BGT3 = Circuit-breaker position contact, open during -KFT = Undervoltage release electronic time-delay
the isolating travel device (see note I)
-BGT5 = Position contacts signalling circuit-breaker in the -QAB = Main circuit-breaker
racked-out position (these are contacts signalling -SFC = Pushbutton or contact for circuit-breaker
circuit-breaker isolated located in the enclosure, closing
in the fixed part: see contacts -BGT2 in diagram -SFO = Pushbutton or contact for circuit-breaker
1VCP400036 figures 5-6) opening
-BPS = Pressure-switch with two intervention -SFL1 = Contact for circuit-breaker closing lock
thresholds: -TB1,-TB2 = Rectifiers for -MBO1 and -MBO2 releases
intervention for low gas pressure. Contacts -RF = Filter (only provided with 220V d.c. voltage
11-12-14 change over, in relation to the position supply)
indicated in the diagram, when the gas pressure -RLE1 = Locking magnet. If de-energized it mechanically
reaches a value of less than 310 kPa absolute prevents circuit-breaker closing
from 380 kPa absolute. If rated pressure is -RLE2 = Locking magnet. If de-energized it mechanically
restored, these contacts change over again prevents circuit-breaker racking-in and isolation
when, starting from a value of less than 310 (it is possible to limit its consumption by
kPa absolute, the value of 340 kPa absolute is connecting a delayed pushbutton in series to
reached. enable the operation)
intervention for insufficient gas pressure. -XDB = Circuit-breaker circuit connector
-XDB1 = Switchgear terminal board (outside the circuit-
breaker)
-XDB2... -XDB62 = Accessory connectors
67
5. Electric circuit diagram
68
Notes
A) The circuit-breaker is only fitted with the accessories E) The circuit for controlling continuity of the shunt opening
listed in the order confirmation. To make out the order, release winding must only be used for this function.
please consult the catalogue of the apparatus. At a power supply lower than 220 V, connect the Control
B) The undervoltage release can be provided for power Coil Continuity device, or a relay or a signalling lamp
supply with voltage branched on the supply side of the which consumes a current not exceeding 20 mA.
circuit-breaker or from an independent source. At a power supply equal to or higher than 220 V, connect
Either the instantaneous undervoltage release or the one a delay or signalling lamp which consumes a current not
with electronic delay device can be used (delay can be exceeding 10 mA.
selected between 0.5 3 s; see note I). Circuit-breaker Other uses might jeopardise release functionality.
closing is only possible with the release energised (the F) The -FCM1 circuit-breaker in fig. 21 must always be
closing lock is made mechanically). provided when there is a 24 kV d.c. spring charging
The contact in fig. 24 or the one in fig. 25 is available on motor.
request. In case of opening caused by a fault in the motor, before
A delay of 50 ms between the moment of consent of the carrying out manual resetting, recharge the springs by
undervoltage release and energisation of the shunt closing means of the special handle.
release must be inserted when there is the same power G) The contacts (-BGT1 and -BGT2) shown in fig. 51 for
supply for the shunt closing and undervoltage releases signalling the circuit-breaker status are located on the
and automatic circuit-breaker closing on return of the circuit-breaker (moving part) and are available on request.
auxiliary power supply is required. This can be carried out However, application of these contacts on the enclosure
by means of a circuit outside the circuit-breaker, including is usually foreseen (fixed part): see diagram 1VCD400036.
a permanent closing contact, the contact indicated in fig. H) When fig. 4 is requested, the contact of pack -BGB1 to
24 and a time-delay relay. terminals 5-6 in fig. 32 is not available.
C) Check the power available on the auxiliary circuit to verify When figs. 26-27 are requested, the -BGB2 contact to
the possibility of starting several motors for charging the terminals 1-2 of fig. 32 is not available.
closing springs at the same time. To avoid excessive I) Make one of the following bridges to select the delay
consumption, it is necessary to charge the springs required (see diagram 1VCD400062):
manually before supplying the auxiliary circuit with 0.5 s: terminals 6-7
voltage. 1 s: terminals 6-8
D) Consult diagram 401530 for connections between the 1.5 s: terminals 6-9
auxiliary circuits of the circuit-breaker and the overcurrent 2 s: terminals 6-10
release with microprocessor type PR512 installed in the 3 s: no bridge.
switchgear.
69