You are on page 1of 72

Medium voltage products

HD4
Gas insulated MV circuit-breakers
12 ... 40.5 kV - 630 ... 3600 A - 16 ... 50 kA
Index

4 1. Description

1 0 2. Circuit-breaker selection and ordering

40 3. Specific product characteristics

44 4. Overall dimensions

62 5. Electric circuit diagram

3
1. Description

General information
HD4 medium voltage circuit-breakers use sulphur hexafluoride
gas (SF6) to extinguish the electric arc and as the insulating
medium.
Breaking in SF6 gas takes place without any arc chopping
and without generation of overvoltages. These characteristics
ensure long electrical life of the circuit-breaker and limited
dynamic, dielectric and thermal stresses on the installation.
The circuit-breaker poles, which make up the breaking part,
are systems with lifelong sealed pressure (IEC 62271-100
Standards) and are maintenance-free.
The ESH type mechanical operating mechanism, with stored
energy has free release and allows opening and closing
operations independently of the operators actions.
The operating mechanism and the poles are fixed to the metal
structure which also acts as a support for the kinetics for
operating the moving contacts.

Autopuffer breaking technique


Electric arc extinction without chopped current
No restriking after breaking
Rapid recovery of the dielectric properties of the means of extinction
Withstand insulation voltage even at zero relative pressure (*)
Sealed-for-life poles
Compact dimensions
Fixed and withdrawable version
Stored energy operating mechanism with anti-pumping device as
standard common to the whole circuit-breaker series
Mechanical safety locks against incorrect operations
Simple personalisation thanks to a complete range of accessories
Maintenance-free
SF6 gas pressure control device (on request).

(*) Up to 17.5 kV.

4
Circuit-breakers in the withdrawable version are fitted with a Thanks to the SF6 autopuffer breaking technique, the HD4
truck to allow racking in and racking out of the switchgear or circuit-breakers do not generate operating overvoltages, and
enclosure. are therefore also highly suitable for retrofitting, upgrading
The light and compact structure of the circuit-breaker ensures and enlarging older installations where the motor, cable, etc.
great sturdiness and excellent mechanical reliability. insulating materials may be particularly sensitive to dielectric
stresses.
Available versions
HD4 circuit-breakers are available in the fixed and Breaking technique
withdrawable version with front operating mechanism. The breaking technique of HD4 circuit-breakers is based
The withdrawable version is available for PowerCube on compression and self-blast techniques to obtain top
modules and UniGear type ZS1, ZS2, ZS3.2 switchgears. performances at all service current values, with minimum
arc times, gradual arc extinction without chopping, and no
Fields of application restriking or operating overvoltages.
HD4 circuit-breakers are used in power distribution to control The HD4 series brings to medium voltage the advantages
and protect lines, transformer and distribution substations, of the autopuffer breaking technique already used in high
motors, transformers, capacitor banks, etc. voltage.

7 3

6
4

1 Circuit-breaker Main contact Arcing contact Circuit-breaker


closed separation separation open

Main contact separation


No electric arc strikes as the current flows through the arcing contacts.
8 During its run downwards, the moving part compresses the gas contained in the lower chamber. The compressed
gas flows out of the lower chamber into the upper chamber, taking them both to the same pressure.

Arcing contact separation


The current flows thanks to the electric arc which has struck between the arcing contacts.
The gas cannot get out through the nozzle because the hole is still closed by the fixed arcing contact and
cannot get out through the inside of the moving arcing contact either because the electric arc closes this
(clogging effect).
with low currents, when the current passes through natural zero and the arc is quenched,
the gas flows through the contacts. The low pressure reached cannot chop the current and the modest
amount of compressed gas is sufficient to restore dielectric resistance between the two contacts,
2 preventing restriking on the rising front of the return voltage.
with high short-circuit currents, the pressure wave generated by the electric arc closes the valve
between the two chambers so that the circuit-breaker starts to operate as a pure self-blast. The pressure
9 increases in the upper volume thanks to heating of the gas and molecular disassociation due to the high
temperature. The increase in pressure generated is proportional to the arc current and ensures quenching
on first passage through current zero.
1 Terminal 6 Fixed arcing contact
2 Insulating case 7 Fixed contact Circuit-breaker open
3 Blasting nozzle 8 Insulating tie-rod The arc has been interrupted, the self-generated pressure in the upper volume is reduced because the gas is
4 Moving arcing contact 9 Anti-explosion valve flowing through the contacts. The valve re-opens and so a new flow of fresh gas comes into the breaking chamber.
5 Moving contact The apparatus is therefore immediately ready to close and trip again up to its maximum breaking capacity.

5
1. Description

Standards and approvals Highly reliable operating mechanisms thanks to a low


HD4 circuit-breakers comply with IEC 62271-100 Standards. number of components which are manufactured using
They have undergone the following tests and guarantee safety production systems for large quantities
and reliability of the apparatus in service in all installations. Extremely limited and simple maintenance
Type tests: heating, withstand insulation at industrial and Accessories common to the entire range
impulse frequency, short-time and peak withstand current, Electrical accessories that can be easily and quickly
mechanical duration, making and breaking of short-circuit installed or replaced thanks to wiring pre-engineered
currents; with plug-socket connectors
Individual tests: insulation with voltage at industrial Mechanical anti-pumping device is supplied as
frequency in the main circuits and insulation of the auxiliary standard
and control circuits, measurement of the main circuit Built-in closing spring charging lever
resistance, mechanical and electrical operation. Key lock with circuit-breaker open
The HD4 circuit-breakers are tested according to the require- Protective covering over the opening and closing
ments of the IEC 62271-100 Standard (classes E2, M2, C2). pushbuttons to be operated using a special tool
Versions approved according to the GOST Standard are also Padlock device on the operating pushbuttons
available (please contact us).
ESH operating mechanism
Just one device for the whole series.
Standards The same set of accessories for all the types of HD4
Safe distribution switchgear can be constructed with HD4 circuit-breaker.
circuit-breakers thanks to the full range of mechanical and Fixed strikers to facilitate assembly or replacement of
electrical locks (available on request). accessories.
The locks have been designed to prevent incorrect Accessory cabling with socket and plug.
operations and to allow the installations to be inspected while
guaranteeing maximum operator safety. Anti-racking-in locks prevent circuit-breakers with different
Key locks or padlocks enable opening and closing and/or rated currents from being racked-in and racked-out when the
racking-in and racking-out operations. circuit-breaker is closed.
The closed door racking-out device only allows the circuit- This is a stored energy mechanical actuator with manual and/
breaker to be racked in and out of the switchgear when the or motor-operated loading of the closing spring; the opening
door is closed. spring is loaded by the same actuator during the closing
operation. The opening and closing operations take place
at speeds that are independent from the operator and the
operating mode (manually using local or remote push-buttons
or by means of the opening and closing shunt releases).
When it is not equipped with a geared motor for loading the
closing springs, the operating mechanism can enable the
following sequences:
with circuit-breaker open and closing spring loaded: C - O
with circuit-breaker closed and closing spring loaded: O - C
- O.
When equipped with a geared motor for loading the closing
springs, the operating mechanism can perform repeated re-
closing operations thanks to automatic reloading after each
closing operation.

6
A
K

B L

M
C

D N

E
O

F
P

H Q

I
R

Circuit-breaker operating mechanism


A Gas monitoring device with led J Lock that prevents racking-in when door is open
B Opening pushbutton K Mechanical operation counter
C Mechanical undervoltage override L Pressure switch
D Undervoltage release M Mechanical signalling device for circuit-breaker open/closed
E Service releases (opening and closing) N Key lock removed when circuit-breaker is open
F Operating mechanism locking electromagnet O Contacts for signalling spring charged/discharged
G Closing pushbutton P Signalling device for closing springs charged/discharged
H Open/closed auxiliary contacts Q Closing spring loading motor limit switch
I Protection circuit-breaker for closing spring loading motor R Geared motor for closing spring charging

7
1. Description

Accessories
HD4 circuit-breakers have a complete range of accessories
which fulfil all installation requirements.
The operating mechanism is the same type for the whole
series and has a standardized range of accessories and spare
parts which are easy to identify and order.
Apparatus use, maintenance and service have been simplified
and require less use of resources.

8
Technical documentation
To obtain in-depth knowledge of technical and application
aspects of the HD4 circuit-breakers please ask for the
following publications:
Power Cube 1VCP000091 Modules
Powerbloc BA441/03E Modules
UniGear ZS1 1VCP000138 Switchgear
UniGear ZS2 1YTS030001 Switchgear
Unigear ZS3.2 1YHA000023 Switchgear
UniSec 1VFM200003 Switchgear
REF542plus 1VTA100001 Units

Quality System
Complies with UNI EN ISO 9001 Standards, certified by an
independent organisation.

Test Laboratory
Complies with UNI CEI EN ISO/IEC 17025 Standards,
accredited by an independent organisation.

Environmental Management System


Complies with UNI EN ISO 14001 Standards, certified by an
independent organisation.

Health and Safety Management System


Complies with OHSAS 18001 Standards, certified by an
independent organisation.

9
2. Selection and ordering

General characteristics of fixed circuit-breakers


(12 - 17.5 - 24 kV)

Circuit-breaker HD4 12
Standards IEC 62271-100
Rated voltage Ur [kV] 12
Rated insulation voltage Us [kV] 12
Withstand voltage at 50 Hz Ud (1 min) [kV] 28
Impulse withstand voltage Up [kV] 75
Rated frequency fr [Hz] 50-60
Rated normal current (40 C) (1)
Ir [A] 630 1250 1600 630 1250 1600 1600 2000 2500 3150 3600
16 16 16 16 16 16

25 25 25 25 25 25 25 25 25 25
Rated breaking capacity Isc [kA]
31,5 31,5 31,5 31,5 31,5 31,5 31,5 31,5 31,5 31,5
40 40 40 40 40
50 50 50 50 50
16 16 16 16 16 16

Rated short-time 25 25 25 25 25 25 25 25 25 25
Ik [kA]
withstand current (3 s) 31,5 31,5 31,5 31,5 31,5 31,5 31,5 31,5 31,5 31,5
40 40 40 40 40
50 50 50 50 50
40 40 40 40 40 40
50 50 50 50 50 50
63 63 63 63
Making capacity Ip [kA]
80 80 80 80 80 80 80 80 80 80
100 100 100 100 100
125 125 125 125 125
Operation sequence [O-0,3s-CO-15s-CO]
Opening time [ms] 45
Arcing time [ms] 10-15
Total breaking time [ms] 55-60
Closing time [ms] 80
H [mm] 640 649 655 655
Overall W [mm] 493 618 618 730
dimensions H
D [mm] 496 496 561 603
W D Interasse poli I [mm] 150 210 210 275
Weight [Kg] 114 114 145 165
1VCD000226
(up to 25 kA) TN
Standardised table of dimensions TN 7178 TN 7163 TN 7165
TN 7177 7177
(31.5 kA)
Absolute SF6 gas pressure (2) [kPa] 380
Operating temperature [C] - 5 ... + 40 C
Tropicalization IEC: 60068-2-30, 60721-2-1
Electromagnetic compatibility IEC 62271-1

(1) Rated normal current defined in free air.


(2) Rated service value.
(3) Including insulating shields (available on request).

10
HD4 17 HD4 24

17,5 24
17,5 24
38 50
95 125
50-60 50-60
630 1250 1600 1600 2000 2500 3150 3600 630 1250 1600 630 1250 1600 1600 2000 2500 3150 3600
16 16 16 16 16 16 16 16 16
20 20 20 20 20 20
25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25
31,5 31,5 31,5 31,5 31,5 31,5 31,5 31,5 31,5 31,5 31,5 31,5
40 40 40 40 40 40 40 40 40 40
50 50 50 50 50
16 16 16 16 16 16 16 16 16
20 20 20 20 20 20
25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25
31,5 31,5 31,5 31,5 31,5 31,5 31,5 31,5 31,5 31,5 31,5 31,5
40 40 40 40 40 40 40 40 40 40
50 50 50 50 50
40 40 40 40 40 40 40 40 40
50 50 50 50 50 50 50 50 50
63 63 63 63 63 63 63 63 63 63 63 63 63 63 63
80 80 80 80 80 80 80 80 80 80 80 80
100 100 100 100 100 100 100 100 100 100
125 125 125 125 125

45 45
10-15 10-15
55-60 55-60
80 80
649 655 655 818 730 655 818 (3

618 618 730 618 748 730 730


496 561 603 600 496 561 620 (3)

210 210 275 210 275 275 275


114 145 165 119 119 145 165

TN 7178 TN 7163 tn 7165 TN 7179 TN 7242 TN 7174 tn 7165

380 380 380 (480 at 25 kA and at 40 kA)


- 5 ... + 40 C - 5 ... + 40 C

11
2. Selection and ordering

General characteristics
of fixed circuit-breakers (36 kV)
Fixed HD4 36 kV circuit-breaker
with 350 mm pole centre distance:
Ir = 630-1250-1600 A;
Isc = 16-20 kA.

Circuit-breaker HD4 36
IEC 62271-100
Standards
VDE 0671; CEI EN 62271-100 - File 7642
Rated voltage Ur [kV] 36
Rated insulation voltage Us [kV] 36
Withstand voltage at 50 Hz Ud (1 min) [kV] 70
Impulse withstand voltage Up [kV] 170
Rated frequency fr [Hz 50-60
Rated normal current (40 C) (1)
Ir [A] 630 1250 1600
16 16 16
20 (5)
20 (5)
20 (5)
Rated breaking capacity Isc [kA]


16 16 16
Rated short-time 20 20 20
Ik [kA]
withstand current (3 s)

40 40 40
50 50 50
Making capacity Ip [kA]


[O-0.3s-CO-15s-CO]
Operation sequence
[O-0.3s-CO-3min-CO]
Opening time [ms] 45
Arcing time [ms] 10-15
Total breaking time [ms] 55-60
Closing time [ms] 80
H [mm] 730/1060 (6)

Maximum overall
dimensions without W [mm] 880/955 (6)

H
insulating screens D [mm] 695
between phases (4)
W D Pole centre distance I [mm] 350
Weight [kg] 124 128 128
Standardised table of dimensions TN 7241
Absolute SF6 gas pressure (2)
[kPa] 380
Operating temperature [C] - 5 ... + 40
Tropicalization IEC: 60068-2-30, 60721-2-1
Electromagnetic compatibility IEC 62271-1
(1) Rated normal current defined in free air
(2) Rated service value
(3) For these versions, with 275 mm pole centre distance, special insulating partitions are provided (on request)
(4) For the dimensions of the insulating partitions (available on request), see the standardised table in chapter 5
(5) Operation sequence: O - 0.3 min - CO - 3 min - CO
(6) The second distance refers to the circuit-breaker with truck (available on request)

12
Fixed HD4 36 kV circuit-breaker
with 275 mm pole centre distance:
Ir = 1250-1600 A;
Isc = 25-31.5 kA;
Ir = 2000-2500 A;
Isc = 20-25-31.5 kA.

HD4 36

36
36
70
170
50-60
1250 (3)
1600 (3)
2000 (3)
2500 (3)


20 20
25 25 25 25
31.5 31.5 31.5 31.5

20 20
25 25 25 25
31.5 31.5 31.5 31.5

50 50
63 63 63 63
80 80 80 80

45
10-15
55-60
80
790/1123 (6)
790/1123 (6)

748/805 (6)
748/805 (6)

833 833
275 275
175 175 180 190
TN 7268 TN 7315
450 450
- 5 ... + 40

13
2. Selection and ordering

General characteristics of fixed circuit-breakers


(12 - 17.5 - 24 kV)

Circuit-breaker HD4/P 12
Standards IEC 62271-100
Rated voltage Ur [kV] 12
Rated insulation voltage Us [kV] 12
Withstand voltage at 50 Hz Ud (1 min) [kV] 28
Impulse withstand voltage Up [kV] 75
Rated frequency fr [Hz] 50-60
Rated normal current (40 C) (1)
Ir [A] 630 1250 1250 1600 2000 2500 3150 (3)

16 16

25 25 25 25 25 25
Rated breaking capacity Isc [kA]
31,5 31,5 31,5 31,5 31,5 31,5
40 40 40 40 40
50 50 50 50
16 16

Rated short-time 25 25 25 25 25 25
Ik [kA]
withstand current (3 s) 31,5 31,5 31,5 31,5 31,5 31,5
40 40 40 40 40
50 50 50 50
40 40

63 63 63 63 63 63
Making capacity Ip [kA]
80 80 80 80 80 80
100 100 100 100 100
125 125 125 125
Operation sequence [O-0,3s-CO-15s-CO]
Opening time [ms] 45
Arcing time [ms] 10-15
Total breaking time [ms] 55-60
Closing time [ms] 80
H [mm] 628 702 702 702 746
Overall W [mm] 532 682 682 882 882
dimensions H
D [mm] 659 640 640 643 643
W D Pole centre distance I [mm] 150 210 210 275 275
Weight [kg] 120 177 177 220 230
1vcd000227 TN 7286 TN 7350 TN 7351 TN 7352 TN7371
Standardised table of dimensions
(up to 25 kA) (31.5 kA)
Absolute SF6 gas pressure (2) 380
Operating temperature [C] - 5 ... + 40
Tropicalization IEC: 60068-2-30, 60721-2-1
Electromagnetic compatibility IEC 62271-1
(1) Rated normal current with circuit-breaker in UniGear type ZS1 switchgear and 40 C ambient temperature outside the switchgear
(2) Rated service value
(3) The circuit-breaker can reach rated currents higher than 3150 A with appropriate forced ventilation of the switchgear (for further information, consult the technical catalogue of
the UniGear type ZS1 switchgear).
(4) In the standard fitting, the truck locking electromagnetic (-RL2) is included to prevent circuit-breaker racking-in with auxiliary circuits not connected (plug not inserted in the socket).
(5) Rated current in switchgear with forced ventilation; with natural ventilation the rated current is 2300 A.

14
HD4/P 17 HD4/P 24

17.5 24
17.5 24
38 50
95 125
50-60 50-60
630 1250 1250 1600 2000 2500 3150 (3)
630 1250 1250 1600 2000 2500 (5)

16 16 16 16 16
20 20 20 20 20
25 25 25 25 25 25 25 25 25 25 25
31,5 31,5 31,5 31,5 31,5 31,5 31,5 31,5 31,5 31,5
40 40 40 40 40
50 50 50 50
16 16 16 16 16
20 20 20 20 20
25 25 25 25 25 25 25 25 25 25 25
31,5 31,5 31,5 31,5 31,5 31,5 31,5 31,5 31,5 31,5
40 40 40 40 40
50 50 50 50
40 40 40 40 40
50 50 50 50 50 50 50
63 63 63 63 63 63 63 63 63
80 80 80 80 80 80 80 80 80
100 100 100 100 100
125 125 125 125

45 45
10-15 10-15
55-60 55-60
80 80
628 702 702 702 746 736 792 821 821
532 682 682 882 882 636 653 842 842
659 640 640 643 643 799 799 788 788
150 210 210 275 275 210 210 275 275
120 177 177 220 230 125 177 177 220
1vcd000227 TN 7286
TN 7350 TN 7351 TN 7352 TN7371 TN 7354 1VCD000099 TN 7355 TN 7356
(up to 25 kA) (31.5 kA)
380 380
- 5 ... + 40 - 5 ... + 40

15
380 (480 at 40 kA)
2. Selection and ordering

General characteristics of withdrawable circuit-breakers


for UniGear type ZS3.2 switchgear (40.5 kV)

Circuit-breaker
Standards IEC 62271-100
Rated voltage Ur [kV]
Rated insulation voltage Us [kV]
Withstand voltage at 50 Hz Ud (1 min) [kV]
Impulse withstand voltage Up [kV]
Rated frequency fr [Hz
Rated normal current (40 C) (1)
Ir [A]

Rated breaking capacity Isc [kA]

Rated short-time
Ik [kA]
withstand current (3 s)

Making capacity Ip [kA]

Operation sequence [O-0.3s-CO-15s-CO]


Opening time [ms]
Arcing time [ms]
Total breaking time [ms]
Closing time [ms]
H [mm]
Maximum W [mm]
overall H
dimensions D [mm]
W D Pole centre distance I [mm]
Weight [kg]
Standardised table of dimensions
Absolute SF6 gas pressure (2)
[kPa]
Operating temperature [C]
Tropicalization IEC: 60068-2-30, 60721-2-1
Electromagnetic compatibility IEC 62271-1
(1) Rated normal current with circuit-breaker in switchgear UniGear ZS3.2 and ambient
temperature outside the switchgear 40 C
(2) Rated service value
(3) Rated current in ZS3.2 switchgear with forced ventilation; in Powerbloc enclosure
the 2500 A rated current is guaranteed with natural ventilation.
(4) The operation sequence becomes O-0.3-CO-3min-CO for the Isc = 31.5 kA
performance.

16
HD4/Z 40.5

40.5
40.5
95
185
50-60
1250 1600 2000 2500 (3)

25 25 25 25
31.5 (4)
31.5 (4)
31.5 (4)
31.5 (4)

25 25 25 25
31.5 31.5 31.5 31.5
63 63 63 63
80 80 80 80

45
10-15
55-60
80
1575
850
686
280
280
TN 7227
550
- 5 ... + 40

17
2. Selection and ordering

General characteristics of withdrawable


circuit-breakers for PowerCube units
(12 - 17.5 - 24 kV)

Circuit-breaker HD4/P 12 HD4/W 12 HD4/P 12


PowerCube module PB1 PB1 PB2 PB2 PB2 PB2 PB2 PB3 PB2 PB2 PB3
Standards IEC 62271-100
Rated voltage Ur [kV] 12 12
Rated insulation voltage Us [kV] 12 12
Withstand voltage at 50 Hz Ud (1 min) [kV] 28 28
Impulse withstand voltage Up [kV] 75 75
Rated frequency fr [Hz] 50-60 50-60
Rated normal current (40 C) (1)
Ir [A] 630 1250 630 1250 1250 1600 2000 3150 (3)
1600 2000 2500
16 16 16 16 16 16

25 25 25 25 25 25 25
Rated breaking capacity Isc [kA]
31.5 31.5 31.5 31.5 31.5 31.5 31.5 31.5
40 40 40 40 40
50 50 50 50 50
16 16 16 16 16 16

Rated short-time 25 25 25 25 25 25 25
Ik [kA]
withstand current (3s) 31.5 31.5 31.5 31.5 31.5 31.5 31.5 31.5
40 40 40 40 40
50 50 50 50 50
40 40 40 40 40 40

63 63 63 63 63 63 63
Making capacity Ip [kA]
80 80 80 80 80 80 80 80
100 100 100 100 100
125 125 125 125 125
Operation sequence [O-0.3s-CO-15s-CO]
Opening time [ms] 45 45
Arcing time [ms] 10-15 10-15
Total breaking time [ms] 55-60 55-60
Closing time [ms] 80 80
H [mm] 636 702 702 702 742 702 702 702
Maximum w [mm] 532 682 682 682 882 682 682 882
overall H
dimensions D [mm] 659 640 640 640 643 640 640 643
W D Pole centre distance I [mm] 150 210 210 210 275 210 210 275
Weight [kg] 120 120 177 177 230 177 177 220
1VCD000227 TN 7229
Standardised table of dimensions TN 7182 TN 7421 TN 7239 1VCD000053 TN 7350 TN 7351 TN 7352
(up to 25 kA) (31,5 kA)
Absolute SF6 gas pressure (2)
[kPa] 380 380
Operating temperature [C] - 5 ... + 40 - 5 ... + 40
Tropicalization IEC: 60068-2-30, 60721-2-1
Electromagnetic compatibility IEC 62271-1
(1) Rated normal current with withdrawable circuit-breaker in switchgear
(2) Rated service value
(3) There are higher currents with forced ventilation: 3600 A with a fan installed in the PB3 and 4000 A with a further fan in the rear of the switchgear (provided by the customer);
see the PowerCube Instruction Manual
(4) 2500 A with forced ventilation
(5) 480 at 40 kA

18
HD4/P 17 HD4/W 17 HD4/P 17 HD4/W 24 HD4/P 24 HD4/P 24
PB1 PB1 PB2 PB2 PB2 PB2 PB2 PB3 PB2 PB2 PB3 PB4 PB4 PB4 PB5 PB5 PB5

17.5 17.5 17.5 24 24 24
17.5 17.5 17.5 24 24 24
38 38 38 50 50 50
95 95 95 125 125 125
50-60 50-60 50-60 50-60 50-60 50-60
630 1250 630 1250 1250 1600 2000 3150 (3)
1600 2000 2500 630 1250 1250 1600 2000 2500 (4)

16 16 16 16 16 16 16 16 16 16 16
20 20 20 20 20
25 25 25 25 25 25 25 25 25 25 25 25
31.5 31.5 31.5 31.5 31.5 31.5 31.5 31.5 31.5 31.5 31.5 31.5
40 40 40 40 40 40 40 40 40
50 50 50 50 50
16 16 16 16 16 16 16 16 16 16 16
20 20 20 20 20
25 25 25 25 25 25 25 25 25 25 25 25
31.5 31.5 31.5 31.5 31.5 31.5 31.5 31.5 31.5 31.5 31.5 31.5
40 40 40 40 40 40 40 40 40
50 50 50 50 50
40 40 40 40 40 40 40 40 40 40 40
50 50 50 50 50
63 63 63 63 63 63 63 63 63 63 63 63
80 80 80 80 80 80 80 80 80 80 80 80
100 100 100 100 100 100 100 100 100
125 125 125 125 125

45 45 45 45 45 45
10-15 10-15 10-15 10-15 10-15 10-15
55-60 55-60 55-60 55-60 55-60 55-60
80 80 80 80 80 80
636 702 702 702 742 702 702 702 792 792 821 821
532 682 682 682 882 682 682 882 682 641 842 842
659 640 640 640 643 640 640 643 799 799 788 788
150 210 210 210 275 210 210 275 210 210 275 275
120 120 177 177 230 177 177 220 125 177 177 220
1VCD000227 TN 7229
TN 7182 TN 7421 TN 7239 1VCD000053 TN 7350 TN 7351 TN 7352 TN 7183 TN 7354 1VCD000099 TN 7355 TN 7356
(up to 25 kA) (31.5kA)
380 380 380 380 (5)
380 (5)

- 5 ... + 40 - 5 ... + 40 - 5 ... + 40 - 5 ... + 40 - 5 ... + 40



19
2. Selection and ordering

General characteristics of withdrawable circuit-breakers


for PowerCube units (36 kV) and UniGear type ZS2
switchgear (36 kV)

Circuit-breaker
Standards IEC 62271-100
Rated voltage Ur [kV]
Rated insulation voltage Us [kV]
Withstand voltage at 50 Hz Ud (1 min) [kV]
Impulse withstand voltage Up [kV]
Rated frequency fr [Hz
Rated normal current (40 C) (1)
Ir [A]

Rated breaking capacity Isc [kA]

Rated short-time
Ik [kA]
withstand current (3 s)

Making capacity Ip [kA]

[O-0.3s-CO-3min-CO]
Operation sequence
[O-0.3s-CO-15s-CO]
Opening time [ms]
Arcing time [ms]
Total breaking time [ms]
Closing time [ms]
H [mm]
Maximum W [mm]
overall H
dimensions D [mm]
W D Pole centre distance I [mm]
Weight [kg]
Standardised table of dimensions
Absolute SF6 gas pressure (2)
[kPa]
Operating temperature [C]
Tropicalization IEC: 60068-2-30, 60721-2-1
Electromagnetic compatibility IEC 62271-1
(1) Rated normal current with circuit-breaker in UniGear ZS2 switch-gear and 40 C
ambient temperature outside the switchgear
(2) Rated service value
(3) 2500 A with forced ventilation of the switchgear

20
HD4/W 36

36
36
70
170
50-60
1250 1250 1600 1600 2000 2000 2500 (3)
2500 (3)

20 20 20 20
25 25 25 25
31.5 31.5 31.5 31.5
20 20 20 20
25 25 25 25
31.5 31.5 31.5 31.5
50 50 50 50
63 63 63 63
80 80 80 80


45
10-15
55-60
80
973 973 973 973
882 882 882 882
788 788 789 789
275 275 275 275
130 225 225 270
TN 7402 TN 7316 TN 7317 TN 7317
450
- 5 ... + 40

21
2. Selection and ordering

General characteristics of withdrawable


circuit-breakers for UniSec (24 kV)

Circuit-breaker HD4/Sec 24
Standards IEC 62271-100
Rated voltage Ur [kV] 24
Rated insulation voltage Us [kV] 24
Withstand voltage at 50 Hz Ud (1 min) [kV] 50
Impulse withstand voltage Up [kV] 125
Rated frequency fr [Hz 50-60
Rated normal current (40 C) (1)
Ir [A] 630 1250
16 16
Rated breaking capacity Isc [kA] 20 20

16 16
Rated short-time
Ik [kA] 20 20
withstand current

40 40
Making capacity Ip [kA] 50 50

Operation sequence [O-0.3s-CO-15s-CO]
Opening time [ms] 45
Arcing time [ms] 10-15
Total breaking time [ms] 55-60
Closing time [ms] 80
H [mm] 800
Maximum W [mm] 682
overall H
dimensions D [mm] 739
W D Pole centre distance I [mm] 210
Truck run [mm] 200
Weight [kg] 123
Standardised table of dimensions 1VCD000220
Absolute SF 6 gas pressure (2)
[kPa] 380
Operating temperature [C] - 5 ... + 40
Tropicalization IEC: 60068-2-30, 60721-2-1
Electromagnetic compatibility IEC 62271-1
(1) Rated normal current with withdrawable circuit-breaker in switchgear
(2) Rated service value

22
General characteristics of withdrawable
circuit-breakers for UniSwitch switchgear
(CBW type units) and UniMix switchgear
(P1/E type units) (24 kV)

Circuit-breaker HD4/US 24 (5)


HD4/US 24 (6)

UniSwitch / CBW type units


UniMix / P1/E type units
Standards IEC 62271-100
Rated voltage Ur [kV] 24 24
Rated insulation voltage Us [kV] 24 24
Withstand voltage at 50 Hz Ud (1 min) [kV] 50 50
Impulse withstand voltage Up [kV] 125 125
Rated frequency fr [Hz 50-60 50-60
Rated normal current (40 C) (1)
Ir [A] 630 1250 630 1250
16 (25) (4)
16 (25) (4)
16 16
Rated breaking capacity Isc [kA] 20 (25) (4)
20 (25) (4)
20 20
25 25
16 (25) (4)
16 (25) (4)
16 16
Rated short-time
Ik [kA] 20 (25) (4)
20 (25) (4)
20 20
withstand current (3 s) (3)

25 25
40 (63) (4)
40 (63) (4)
40 40
Making capacity Ip [kA] 50 (63) (4)
50 (63) (4)
50 50
63 63
Operation sequence [O-0.3s-CO-15s-CO]
Opening time [ms] 45 45
Arcing time [ms] 10-15 10-15
Total breaking time [ms] 55-60 55-60
Closing time [ms] 80 80
H [mm] 800 800
Maximum W [mm] 682 682
overall H
dimensions D [mm] 739 739
W D Pole centre distance I [mm] 210 210
Truck run [mm] 200 200
Weight [kg] 123 123
Standardised table of dimensions 1VCD000046 1VCD000046
Absolute SF 6 gas pressure (2)
[kPa] 380 380
Operating temperature [C] - 5 ... + 40 - 5 ... + 40
Tropicalization IEC: 60068-2-30, 60721-2-1
Electromagnetic compatibility IEC 62271-1
(1) Rated normal current with withdrawable circuit-breaker in switchgear
(2) Rated service value
(3) The short-time withstand current and its duration can be limited by the switchgear: see the specific UniSwitch and UniMix switchgear catalogues
(4) The values in brackets refer to the 12 kV rated voltage
(5) The activation rollers of the top shutter are supplied mounted and adjusted by the supplier of the UniSwitch switchgear
(6) The activation rollers of the top shutter of the UniMix switchgear P1/E are available on request

23
2. Selection and ordering

Standard equipment
The basic versions of the circuit-breakers are always three-
pole and fitted with:
manual operating mechanism
mechanical signalling device for closing springs charged/
discharged
mechanical signalling device for circuit-breaker open/closed
closing pushbutton
opening pushbutton
operation counter
12 to 36 kV series: set of 14 auxiliary contacts for circuit-
breaker open/closed; five closing contacts (circuit-breaker
open signalling) and seven opening contacts (circuit-breaker
closed signalling) are available for use by the customer if Terminals for fixed circuit-breaker.
the apparatus is equipped with all the electrical applications
40.5 kV series: set of 10 auxiliary contacts for circuit-
breaker open/closed; three closing contacts (circuit-breaker
open signalling) and four opening contacts (circuit-breaker
closed signalling) are available for use by the customer if
the apparatus is equipped with all the electrical applications
lever for manually charging the closing springs (the quantity
must be defined according to the number of pieces of
apparatus ordered).

Circuit-breaker racking-out/racking-in lever.

24
Moreover:
for fixed circuit-breaker
connection terminals (not available for low-end circuit-
breakers)
terminal board for auxiliary circuits;
for withdrawable circuit-breaker
isolating contacts
cord with connector (plug only) for auxiliary circuits
lock to prevent racking-in of circuit-breaker with different
rated current
racking-in/out lever (the quantity must be defined
according to the number of pieces of apparatus ordered)
locking electromagnet in the truck (/P versions).
Tulip isolating contacts for withdrawable circuit-breaker.

Manual charging lever of operating mechanism springs.

25
2. Selection and ordering

Table of availability of accessories

opening (as an alternative to the standard 10, of which up to 3 for closing

on the truck). It is compulsory if the RLE1 locking magnet is present.


-BGT3 position contact of the withdrawable circuit-breaker (installed
Set of 15 auxiliary contacts for the circuit-breaker: 4 for closing and 5 for

and 4 for opening are available, depending on the accessories required).


Set of 14 auxiliary contacts: 5 closing contacts for signalling circuit-
breaker open and 7 opening contacts for signaling circuit-breaker
-MBU undervoltage release with electronic time delay device

-BGB5 undervoltage release electric signalling (energised or


-MBU undervoltage release (power supply on supply side).
-MBO3 shunt opening release with demagnetisation.

Mechanical override of undervoltage release trip.


-MBO2 additional shunt opening release.
-MBO1 shunt opening release.

(power supply on supply side).


-MBC shunt closing release.

-BGB4 transient contact.


de-energised).

closed.
1A 1B 1C 2 3A 3B 4 5 6A 6B 7 8
Fixed circuit-breakers
HD4 12
HD4 17
HD4 24
HD4 36
Withdrawable circuit-breakers
for UniGear type ZS1 switchgear
HD4/P 12
HD4/P 17
HD4/P 24
Withdrawable circuit-breakers for
UniGear 36 type ZS3.2 switchgear
HD4/Z 40.5
Withdrawable circuit-breakers
for PowerCube modules
HD4/W 12
HD4/W 17
HD4/W 24
HD4/W 36 (5)
Withdrawable circuit-breakers
for UniSec switchgear
HD4/SEC 24
Withdrawable circuit-breakers for
UniSwitch and UniMix switchgear
HD4/US 24

(1) Standard fitting: no. 6 auxiliary contacts.


(2) Application of the pressure switch is only possible in the factory.
(3) For this version it is only available without LED.
(4) The locking electro-magnet in the truck (-RL2) to prevent the circuit-breaker being racked-in with the auxiliary circuits disconnected (plug not inserted in the socket) is included
in the standard equipment.
(5) Also suitable for UniGear type ZS2.

26
Withdrawable circuit-breaker transmitted contacts (installed in the

(1)
circuit-breaker truck).















10
-MAS spring charging geared motor.















11
-FCM1 thermomagnetic protection of spring charging geared motor.















Electric signalling of springs charged.

12A















Electric signalling of springs discharged.

12B














Opening pushbutton lock.

13A














Closing pushbutton lock.

13B















14
Open circuit-breaker key lock.















15
-RLE1 operating mechanism locking magnet.

(4)
(4)
(4)
16
-RLE2 truck locking magnet.















17
Interlock for fixed circuit-breaker.














18
Mechanical isolation interlock with the switchgear door.

(3)
Two-level pressure switch (2).
19A

Two-level pressure switch plus SF6 control device with three LEDs (2).
19B-C















20

Insulating partitions.


21

3-lobed key for manual operation.

27
2. Selection and ordering

Optional accessories
The accessories identified with the same number are alternative to each other; consult the table at the end of the
chapter for the electrical characteristics.

supplementary shunt
opening release -MBO2

shunt closing release


-MBC
shunt opening release
-MBO1

1 Shunt opening release 2 Shunt closing release -MBC


1A Shunt opening release -MBO1 Allows the closing command of the apparatus to be
Allows the opening command of the apparatus to be enabled transmitted by remote control.
by remote control. To guarantee the closing action, the current impulse must
This release is only suitable for instantaneous service; there is last at least 100 ms. This release is suitable for both
always an auxiliary contact -BGB1 to de-energize it after the instantaneous and permanent duty (an auxiliary contact that
circuit-breaker has opened. To guarantee the release action, de-energizes it after the circuit-breaker has closed is not
the current impulse must last at least 100 ms. The coil of this envisaged). Permanently energized, the release provides the
release can be controlled by any CCC (Control Coil Continuity) electrical anti-pumping function when both the opening and
device and TCS (Trip Circuit Supervision) circuit opening closing remote commands (electrical) are maintained. If shunt
supervision device. closing release -MBC and undervoltage release -MBU are
energized by the same supply voltage and automatic closing
1B Additional shunt opening release -MBO2 of the circuit-breaker is required when the auxiliary voltage
returns, there must be a delay of at least 50 ms between
Similarly to shunt opening release -MB01, this allows the
undervoltage release energizing and energizing of the shunt
opening command of the apparatus to be transmitted by
closing release to allow the closing operation to take place.
remote control. It can be energized by the same circuit as
Release functionality cannot be controlled by CCC and TCS
main shunt opening release -MB01 or by a circuit that is
devices.
completely separate from release -MB01. This release is only
This can only be done by the ABB STU device (accessory
suitable for instantaneous service. There is always an auxiliary
supplied on request).
contact -BGB1 to de-energize it after the circuit-breaker has
opened. To guarantee the release action, the current impulse
must last at least 100 ms. The coil of this release can be
controlled by any CCC (Control Coil Continuity) device and
TCS (Trip Circuit Supervision) circuit opening supervision
device.

1C Demagnetizing shunt opening release -MBO3


The opening solenoid (-MBO3) is a special demagnetizing
release for use in conjunction with protection relays against
overcurrents of the self-supplied type (e.g. the old ABB
PR521 series). It is an alternative to the additional shunt
opening release (-MBO2).

28
undervoltage release
-MBU

electronic time-lag device -KFT

3 Under-voltage release -MBU 3A Undervoltage release -MBU (only for power supply
Undervoltage release -MBU opens the circuit-breaker branched on the supply side of the circuit-breaker)
when there is a sensible reduction or lack of the voltage 3B Undervoltage release -MBU with electronic time-lag
that energizes it. The circuit-breaker can only close when device -KFT (only for power supply branched on the
the release is energized (the closing lock is obtained supply side of the circuit-breaker).
mechanically). It can be used for remote release (by means Circuit-breaker closing is inhibited when the undervoltage
of a pushbutton of the normally closed type), for locking on release (equipped with electronic time-lag device -KFT) is not
automatic closing and/or opening in the absence of voltage energized. Electronic time-lag device -KFT is only designed
in the auxiliary circuits. Energized by means of the secondary to delay the tripping action of undervoltage release MBU at
output of a voltage transformer, it provides locking upon preset, adjustable times (0.5 - 1 - 1.5 - 2 - 3 s).
automatic closing/opening in the absence of voltage in the This device is consigned with the 0.5 s time setting. Consult
Medium Voltage main circuit. If shunt closing release -MBC the Chapter on circuit diagrams, note I, page 69). Electronic
and undervoltage release -MBU are energized by the same time-lag device -KFT must be installed inside the operating
supply voltage and automatic closing of the circuit-breaker enclosure of the circuit-breaker.
is required when the auxiliary voltage returns, there must To avoid tripping, use of the delayed undervoltage release is
be a delay of at least 50 ms between undervoltage release convenient when the supply network of release -MBU may
energizing and energizing of the shunt closing release to allow often be liable to brief voltage dips or tiny power outages.
the closing operation to take place. The voltage of the undervoltage release must be within the
operating range of the electronic time-lag device.

29
2. Selection and ordering

Optional accessories

4 Mechanical override of undervoltage release tripping 6 Auxiliary and signalling contacts


with undervoltage excluded electrical signalling. 6A Auxiliary contacts BGB1,-BGB2 for all 12 kV to
The mechanical undervoltage override is a manually switched 36 kV fixed and withdrawable series
two-position device installed on the front of the circuit- Electrical signalling of circuit-breaker open/closed can be
breaker operating mechanism. Its purpose is to prevent the obtained with a set of 14 auxiliary contacts for the fixed
undervoltage release from tripping so that the circuit-breaker version and 14 auxiliary contacts for the plug-in version.
can be operated as though it were without an undervoltage Note
release. The undervoltage override is always equipped with The following contacts are available for the fixed and plug-
an electrical contact for signalling undervoltage excluded. in circuit-breaker with the standard set of fourteen auxiliary
The mechanical override is essential when the undervoltage contacts and the maximum number of electrical accessories:
release is supplied by the secondary of a transformer on the five closing contacts for signalling circuit-breaker open
load side of the circuit-breaker. In this case, the installation seven opening contacts for signalling circuit-breaker closed.
can only be energized by excluding the undervoltage. The The auxiliary contacts of fixed circuit-breakers are always
mechanical override can be operated after the circuit-breaker wired to the terminal box.
has closed so as to restore undervoltage functionality. The Please refer to the following circuit diagrams:
mechanical override is useful when inspections/maintenance 1VCD400192 for fixed circuit-breakers up to 24 kV and 36
must be performed with the circuit-breaker withdrawn from kV circuit-breakers with 350 mm pole center-distance
the switchgear and with the auxiliary circuits de-energized. 1VCD400193 for 36 kV fixed circuit-breakers with 275 mm
Specify when ordering the apparatus if the mechanical pole center-distance
override is required since it cannot be installed by the 1VCD400197 for withdrawable circuit-breakers up to 24 kV
customer at a later date. (with auxiliary contacts -BGB1,-BGB2 independent from
connected/isolated signalling contacts -BGT1,-BGT2)
1VCD400199 for withdrawable circuit-breakers up to 24 kV
(with auxiliary contacts -BGB1,-BGB2 interconnected with
connected/isolated signalling contacts -BGT1,-BGT2)
5 Electrical signalling of the state of undervoltage 1VCD400194 for 36 kV withdrawable circuit-breakers
release -BGB5 Note: The main shunt opening release and/or the additional shunt opening
An undervoltage release energized or undervoltage release release use 1 and/or 2 closing contacts a, thereby reducing the number of
auxiliary contacts available. Always check the maximum number of contacts
de-energized signalling contact can be supplied on request. available with non-standard equipment.
It must be specified when ordering the apparatus since it
cannot be installed by the customer at a later date.

30
Auxiliary contacts BGB1 and BGB2 conform to the
following standards/regulations/directives:
IEC 62271-100
IEEE C37.54
EN 61373 cat.1 class B / impact and vibration test
Germanish Loyd regulation / vibrations envisaged by the
shipping registers
UL 508
EN 60947 (DC-21A DC-22A DC-23A AC-21A)
RoHS Directive

General characteristics
Insulation voltage to standard 660 V AC
VDE 0110, Group C 800 V DC
Rated voltage 24 V ... 660 V 6B Auxiliary contacts -BB1-BB2-BB3 for the 40.5 kV
Test voltage 2 kV for 1 min withdrawable series only
Maximum rated current 10 A - 50/60 Hz Electrical signalling of circuit-breaker open/closed includes,
Breaking capacity Class 1 (IEC 62271-1) as standard equipment, a set of 10 auxiliary contacts for the
Number of contacts 5 40.5 kV withdrawable version.
Groups of contacts 10 / 16 / 20 Set of 10 circuit-breaker open/closed auxiliary contacts.
Contact travel 90 Three closing contacts (circuit-breaker open signalling) and
Actuating force 0.66 Nm four opening contacts (circuit-breaker closed signalling) are
Resistance <6.5 m available if the apparatus is equipped with all the electrical
Storage temperature 30 C ... +120 C applications.
Operating temperature
20 C ... +70 C A set of 15 auxiliary contacts for signalling circuit-breaker
(-30 ref. ANSI 37.09)
open/closed can be supplied on request. Four closing
Contact overtemperature 10 K
contacts (circuit-breaker open signalling) and four opening
Mechanical life 10,000 mechanical operations
contacts (circuit-breaker closed signalling) are available if the
Protection class IP20
apparatus is equipped with all the electrical applications.
Cable section 1 mm2

Electrical specifications of the auxiliary contacts of the 40.5 kV with-


Electrical characteristics (according to IEC 60947) drawable circuit-breaker
Rated current Un Breaking capacity (10000 interruptions) Un = 500 V~ 220 V
220 V AC Cosj = 0.70 20 A Icu = 15 A 1.5 A
220 V DC Cos j = 0.45 10 A cos = 0.4
1 ms 12 A T = 500 V~ 10 ms
24 V DC
15 ms 9A Un Rated voltage
50 ms 6A cos Power factor
Icu Breaking capacity
1 ms 10 A Ps Inrush power input (inrush duration is given between brackets)
60 V DC
15 ms 6A Pc Continuous service power consumption
T Time constant
50 ms 4,6 A
1 ms 7A
110 V DC 15 ms 4.5 A
50 ms 3.5 A
1 ms 2A
220 V DC 15 ms 1.7 A
50 ms 1.5 A
1 ms 2A
250 V DC 15 ms 1.4 A
50 ms 1.2 A

31
2. Selection and ordering

Optional accessories

7 Transient contact -BGB4 with momentary closing 8 Position contact of withdrawable circuit-breaker
during circuit-breaker opening. -BGT3
This contact closes momentarily (for about 30 ms) when the Only supplied for withdrawable circuit-breakers for UniGear
circuit-breaker opens. The transient contact is activated by ZS1 and ZS2 switchgear and PowerCube modules from 12 to
the main operating shaft, thus the indication is only provided 36 kV.
when the main contacts of the circuit-breaker effectively open. This contact is installed in the truck. It is in the closed state
when the truck is fully racked-in or fully racked-out and is in
the open state when the truck is being racked-in/racked-out.
It is used in conjunction with the locking magnet in the
operating mechanism (-RLE1) to prevent remote closing
during movement in the compartment.
It is supplied as standard equipment when locking magnet
-RLE1 is installed in the operating mechanism and truck-
mounted contacts are not required (-BGT1, -BGT2). It cannot
be supplied when truck-mounted contacts are required
(-BGT1; -BGT2).

32
General characteristics
Insulation voltage to standard 660 V a.c.
VDE 0110, Group C 800 V d.c.
Rated voltage 24 V ... 660 V a.c.
Test voltage 2 kV 50 Hz (for 1 min)
Rated overcurrent 10 A
Number of contacts 5
Contact run 6 mm ... 7 mm
Activation force 26 N
Resistance 3 m
Storage temperature 20 C ... +120 C
Operating temperature 20 C ... +70 C
Contact overtemperature 20 K
Number of cycles 10.000
Unlimited breaking capacity if used with 10 A fuse in series
9 Electrical signalling contacts for circuit-breaker
connected and isolated (-BGT1; -BGT2)
Electrical characteristics
These contacts are an alternative to the withdrawable circuit-
Un Rated current Breaking capacity
breaker position contact (-BGT3) and are recommended when
220 V a.c. Cosj = 0.7 2.5 A 25 A
there are no position contacts on the roof of the circuit-
380 V a.c. Cosj = 0.7 1.5 A 15 A
breaker compartment (for signalling circuit-breaker racked-
500 V a.c. Cosj = 0.7 1.5 A 15 A
out or racked-in). Contacts -BGT1, -BGT2 are supplied as
660 V a.c. Cosj = 0.7 1.2 A 12 A
standard equipment when locking magnet -RLE1 is installed
1 ms 10 A 12 A
in the operating mechanism and position contact BGT3
24 V d.c. 15 ms 10 A 12 A
has not been requested. Contacts -BGT1 and BGT2 have
50 ms 8A 10 A
the same general and electrical characteristics as auxiliary
200 ms 6A 7.7 A
contacts 7b. -BB1, -BB2, -BB3.
1 ms 8A 10 A
60 V d.c. 15 ms 6A 8A
50 ms 5A 6A
200 ms 4A 5.4 A
1 ms 6A 8A
15 ms 4A 5A
110 V d.c.
50 ms 2A 4.6 A
200 ms 1A 2.2 A
1 ms 1.5 A 2A
15 ms 1A 1.4 A
220 V d.c.
50 ms 0.75 A 1.2 A
200 ms 0.5 A 1A

33
2. Selection and ordering

Optional accessories

10 S pring-loading geared motor -MAS 11 Thermal magnetic protection -FCM1 of the closing
The geared motor automatically loads the closing spring of spring loading motor
the circuit-breakers operating mechanism after the circuit- Thermal magnetic protection of the closing spring loading
breaker has closed each time and until the yellow spring motor is supplied as part of the standard equipment for
loaded indicator appears. If a power cut occurs when loading 24 V DC rated voltage while it is available on request for other
is in progress, the geared motor stops and automatically voltage values. It is always supplied with electrical signalling
starts loading the springs again when the power returns. of thermal magnetic protection tripped.
Loading can always be completed in the manual mode (as
it is during maintenance work) by means of the dedicated
lever supplied. Check the power available in the supply circuit
to find out whether several motors for loading the closing electrical signalling of
springs can operate at the same time. To prevent excessive spring loaded/discharged

power consumption, especially when the installation is put


into service, it is advisable to load the springs by hand before
energizing the auxiliary circuits.

spring loaded/discharged
mechanical indicator

Contact for signalling closing spring loaded/discharged


-BGS2
This consists of a microswitch, which allows remote signalling
of the state of the closing spring of the circuit-breaker
operating mechanism.
One of the following signals can be selected:
12A contact open: electrical signalling of spring loaded
12B contact closed: spring discharged signal

34
13 Locks and interlocks 14 Circuit-breaker open key lock (different keys or the
13 A O pening pushbutton lock (with or without padlock). same keys).

Locks the opening pushbutton with a 4 mm diameter padlock The locking action is performed by a special circular lock.
(not part of the standard equipment). The padlock is only Can be supplied with different keys or the same keys (for
supplied on request. several circuit-breakers). To apply the key lock, press the
opening pushbutton, turn the key and remove it. Local manual
closing and remote electrical closing are inhibited once the
13 B Closing pushbutton lock (with or without padlock).
key has been removed.
Locks the closing pushbutton with a 4 mm diameter padlock
(not part of the standard equipment). The padlock is only
supplied on request.

35
2. Selection and ordering

Optional accessories

locking magnet on
operating mechanism

15 Locking magnet -RLE1 on operating mechanism. 16 Locking magnet -RLE2 on truck.


Local manual closing and remote electrical closing can only This accessory is mandatory in withdrawable versions for
be obtained when electromagnet RLE1 is energized. When UniGear switchgear type ZS1 and for PowerCube modules
-RLE1 is requested for a withdrawable circuit-breaker, it so as to prevent the circuit-breaker from being racked into
comes with contact -BGT2 unless contacts -BGT1, -BGT2 the switchgear when the plug of the auxiliary circuits is
have been requested. disconnected from the switchgear socket. The plug also
prevents racking-in if the rated current of the circuit-breaker
differs from that of the compartment (dedicated striker pins
prevent the plug from being plugged into the socket if the
circuit-breakers rated current is lower than the rated current
of the panel).

36
Interlock to prevent circuit-breaker Interlock to prevent racking-in/
closing during racking-in/out. out when circuit-breaker is
closed.

Example of interlock application on a plug-in circuit-breaker with truck for ABB


UniGear switchgear or PowerCube enclosure.

17 Interlock for fixed circuit-breaker (for fixed apparatus 18 Mechanical isolation interlock with the door of Unigear
converted to plug-in by the customer). ZS1, ZS2 switchgear and the PowerCube enclosure.
This device can be useful when fixed circuit-breakers are This device prevents the circuit-breaker from being racked-
converted into withdrawable ones by the customer. in when the switchgear door is open. It is only intended for
It allows the customer to create a mechanical lock that inhibits circuit-breakers used in UniGear ZS1 and ZS2 switchgear
racking-out/racking-in when the circuit-breaker is closed and and in PowerCube modules (which must be equipped with a
prevents the circuit-breaker from closing during movement. dedicated actuator on the door).
Note. The device must be requested when the order is placed
since it must be assembled in the factory.

37
2. Selection and ordering

Optional accessories

19 Gas monitoring device 21 3-lobed key for manual opening and closing
Notes: operations

specify when ordering the apparatus if the pressure This accessory is only available for the 40.5 kV HD4/Z series.
switch is required since it cannot be installed by the
customer at a later date;
devices 19B and 19C are supplied without LED for the
40.5 kV HD4/Z series
19A Two-level pressure switch
19B Two-level pressure switch with two-level SF6 monitoring
device, three LEDs and supplementary shunt opening
release MO2: circuit-breaker opening and closing lock
19C Two-level pressure switch with two-level SF6 monitoring
device and three LEDs: circuit-breaker locking in the
position it has reached

20 Insulating partitions for fixed circuit-breakers.


Consult chapter 4 for a list of the circuit-breakers for which
the partitions are available (on request. Assembly is at the
customers charge).

38
Characteristics of electrical accessories

Ps = 125 W/VA (Instantaneous service < 45 ms)


Un = 24, 30, 48, 60, 110, 125, 220, 250 V
Shunt opening release (-MBO1; -MBO2)
Un = 48, 110, 120 (127), 230 (220/240) V~ 50 Hz
Un = 110 (127), 230 (220/240) V~ 60 Hz
Ps = 250 W/VA (150 ms)
Pc = 5 W/VA (antipumping function - continuous service)
Shunt closing release (-MBC) Un = 24, 30, 48, 60, 110, 125, 220, 250 V
Un = 48, 110, 120 (127), 230 (220/240) V~ 50 Hz
Un = 110 (127), 230 (220/240) V~ 60 Hz
Ps = 250 W/VA (150 ms)
Pc = 5 W/VA (continuous service)
Undervoltage release (-MBU) Un = 24, 30, 48, 60, 110, 125, 220, 250 V
Un = 48, 110, 120 (127), 230 (220/240) V~ 50 Hz
Un = 110 (127), 230 (220/240) V~ 60 Hz
Ps = 1500 W/VA (100 ms)
Pc = 400 W/VA (spring charging time: 6 s)
Spring charging geared motor (-MAS) Un = 24, 30, 48, 60, 110, 125, 220, 250 V
Un = 48, 110, 120 (127), 230 (220/240) V~ 50 Hz
Un = 110 (127), 230 (220/240) V~ 60 Hz
Ps = 250 W/VA (150 ms)
Pc = 5 W/VA (continuous service)
Locking magnets (-RLE1; -RLE2) Un = 24, 30, 48, 60, 110, 125, 220, 250 V
Un = 48, 110, 120 (127), 230 (220/240) V~ 50 Hz
Un = 110 (127), 230 (220/240) V~ 60 Hz
Un = 24, 30, 48, 60, 110, 125, 220, 250 V
Gas control device with 3 LEDs Un = 48, 110, 120 (127), 230 (220/240) V~ 50 Hz
Un = 110 (127), 230 (220/240) V~ 60 Hz
Un = 500 V~ 220 V

Circuit-breaker auxiliary contacts Icu = 15 A 1.5 A


(only for 40 kV HD4/Z) cos = 0.4
T = 10 ms
Un Rated voltage.
Cos Power factor.
Icu Breaking capacity
Ps Inrush power consumption (the inrush time is indicated in brackets).
Pc Continuous service power consumption.
T Time constant.

39
3. Specific product characteristics

Resistance to vibrations Tropicalization

HD4 circuit-breakers are unaffected by mechanically HD4 circuit-breakers are manufactured in compliance with the
generated vibrations. strictest regulations for use in hot-humid-saline climates.
For the versions approved by the naval registers, please All the most important metal components are treated against
contact us. corrosive factors according to atmospheric corrosivity class
C5 of standard BS EN 12500.
Galvanisation is carried out in accordance with UNI ISO 2081
Standards, classification code Fe/Zn 12, with a thickness of
12x10-6 m, protected by a conversion layer mainly consisting
of chromates in compliance with the UNI ISO 4520 Standards.

40
Altitude Graph for determining the Ka correction factor
according to the altitude

Example
Installation altitude 2000 m
Operation at the rated voltage of 12 kV
Withstand voltage at industrial frequency 28 kV rms
Impulse withstand voltage 75 kVp
Factor Ka obtained from graph = 1.13.

Considering the above parameters, the apparatus will


have to withstand the following values (under test and at
zero altitude, i.e. at sea level):
withstand voltage at industrial frequency equal to:
28 x 1.13 = 31.6 kVrms
impulse withstand voltage equal to:
75 x 1.13 = 84.7 kVp.

From the above, it can be deduced that for installations


at an altitude of 2000 m above sea level, with 12 kV
service voltage, apparatus must be provided with
17.5 kV rated voltage, characterised by insulation levels
at industrial frequency of 38 kVrms with 95 kVp impulse
The insulating property of air decreases as the altitude withstand voltage.
increases, therefore this must always be taken into account
for external insulation of the apparatus (the internal insulation
does not undergo any variations as it is guaranteed by the SF6 Ka
1,50
gas).
The phenomenon must always be taken into consideration
m=1
during the design stage of the insulating components of
Ka = e m (H 1000)/8150
apparatus to be installed over 1000 m above sea level In this (IEC 60071-2)
1,40
case a correction coefficient must be considered, which can
be taken from the graph to the side, built up on the basis of
the indications in the IEC 62271-1 Standards.
The following example is a clear interpretation of the
1,30
indications given above.

1,20

1,10

1,00
1000 1500 2000 2500 3000 3500 4000 H

H = altitude in metres;
m = value referred to industrial frequency and the
atmospheric impulse withstand voltages and those
between phase and phase.

41
3. Specific product characteristics

Environmental protection programme Anti-pumping device

HD4 circuit-breakers are manufactured in accordance with The ESH operating mechanism on HD4 circuit-breakers
the ISO 14000 Standards (Guidelines for environmental (in all versions) is fitted with a mechanical anti-pumping
management). device which prevents re-closing due to either electrical or
The production processes are carried out in compliance mechanical commands.
with the Standards for environmental protection in terms of Should both the closing command and any one of the
reduction in energy consumption as well as in raw materials opening commands be active at the same time, there
and production of waste materials. All this is thanks to would be a continuous succession of opening and closing
the medium voltage apparatus manufacturing facility operations.
environmental management system. The anti-pumping device avoids this situation, ensuring that
Assessment of the environmental impact of the life cycle of each closing operation is only followed by a single opening
the product, obtained by minimising energy consumption operation and that there is no closing operation after this. To
and overall raw materials of the product, became a concrete obtain a further closing operation, the closing command must
matter during the design stage by means of targeted selection be released and then relaunched.
of the materials, processes and packing. Furthermore, the anti-pumping device only allows circuit-
This is to allow maximum recycling at the end of the useful life breaker closure if the following conditions are present at the
cycle of the apparatus. same time:
operating mechanism springs fully charged
opening pushbutton and/or opening release (-MBO1/-
MBO2) not enabled
main circuit-breaker contacts open.

42
Spare parts Ordering
Replacement can only be carried out by trained personnel For availability and ordering of spare parts, please contact our
and/or in our workshops: Service, specifying the circuit-breaker serial number.
opening springs
closing springs
complete pole
basic operating mechanism
bushings, terminals and insulating protections.

Replacement which can be carried out by the customer:


isolating contacts
geared motor limit switch contact
KFA1 instantaneous relay
KFA2 instantaneous relay.

43
4. Overall dimensions

Fixed circuit-breakers

HD4 493
150 150 87 336,5 13,5
TN 1VCD000226 67,5 M12 depth 25
2XM8 depth 16
Ur 12 kV
Ir 630 A
1250 A

27
Isc 16 kA
25 kA

205
586
63

541

27
260,5
248,5

21,5
43

347 10,5 13
117 M12 depth 22
402 114,5 2XM8 depth 16
473 270
493 332

Fixed circuit-breakers

HD4 493 161 176


150 150 44
TN 7177 92 378.5 92
44
50 10 334.5
22

22

Ur 12 kV
Ir 630 A
1250 A
Isc 31.5 kA
317
317

28
HD4
10

22
22
YU
640

TN 7177
10
582

549.5

540

Ur 12 kV YU

Ir 1600 A 8
297.5

297.5

Q60
257.5

Isc 16 kA
25 kA
21.5
43

3
31.5 kA
347
10.5 13 120
473 270
1250A 37
493 335
1600A 630A

44
Fixed circuit-breakers

HD4 600 161

TN 7178 578 92 379

Ur 12 kV 210 210 44 176


335
92
50 10 44
17.5 kV

22
Ir 630 A
1250 A

22
1600 A

317
317
Isc 16 kA

10
25 kA 22 28
22

648.5

10

622
31.5 kA

558.5
YU

YU

468.5

306. 5
306.5
266.5
8
43

472 13 120
10.5
598 270 37
1250A
618 335
1600A 630A

Fixed circuit-breakers

HD4 600
578
TN 7163
210 210
Ur 12 kV
17.5 kV
Ir 1600 A
Isc 40 kA
2 x 18
50 kA
310
310

28
80

HD4
15.5 32
655

TN 7163
622

YU

Ur 12 kV
8

YU
17.5 kV
306.5

Ir 2000 A
266.5

Q6
0 8
Isc 25 kA
13
31.5 kA
43

40 kA
472 10.5 35
50 kA 2.5
20

598 322

618 385
561

45
4. Overall dimensions

Fixed circuit-breakers

HD4 137.5 137.5 420 min.


730
TN 7165
708
Ur 12 kV
275 275 465
17.5 kV

349.5
Ir 2500 A
3150 A

670 min.
3600 A

15
Isc 25 kA

310
28

62
31.5 kA
40 kA 20 40

655

20

622
YU
50 kA

468.5
40
YU

20
20
HD4 8

TN 7165

266.5
4 x 18
13
Ur 24 kV
Ir 2500 A
43

602 10.5 115 2


3150 A

20
322 35
728
3600 A 385
748 603
Isc 25 kA
31.5 kA Insulating partitions (only for 24 kV)
40 kA to be provided by the customer
(a special kit is available on request).

Fixed circuit-breakers

HD4 600 400 min. 200


578
TN 7179 210 210 161
Ur 24 kV 105 105

Ir 630 A 92 44 399 176


92 44
50 10 355
1250 A
1600 A
22
22

Isc 16 kA
670 min.

20 kA
362

362

25 kA
22
22
10
729.5

28
712

639.5

622

YU
468.5

YU
342.5
342.5
302.5

10

Q60
8
13
43

472 10.5 120

598 270
37
1250A
618 1600A 335 630A

Insulating partitions to be provided by the


customer (a special kit is available on request).

46
Fixed circuit-breakers

HD4 730 161


708 44 176
TN 7242
275 275 92 399 92
44
Ur 24 kV 50 10 355

Ir 630 A
1250 A

22
22
1600 A

362
362
Isc 16 kA

22
20 kA

22
25 kA

729.5
28

10
639.5

620
YU

468.5
YU

10

342.5

342.5
302.5
Q6
0 8
13
43

602 120
10.5
728 270
37
748
1250A 335
1600A 630A

Fixed circuit-breakers

HD4 730
708
TN 7174
275 275
Ur 24 kV
Ir 1600 A
Isc 31.5 kA
40 kA 2x 18
310
310

80

HD4
28
TN 7174 15.5 32
622
655

Ur 24 kV YU
8

Ir 2000 A YU

Isc 25 kA 8
306.5
266.5

31.5 kA Q6
0

40 kA 13
43

602 10.5 115 3


20

728 322
35
385
748 561

47
4. Overall dimensions

Fixed circuit-breakers

HD4 400
880
358
with truck (on request) 350 350 10
22
50
TN 7241
Ur 36 kV
Ir 630 A

362
1250 A
1600 A 22

729.5
28
712

639. 5
Isc 16 kA

539
10
20 kA
* 106 0

342.5
21

302.5
* Distance with truck 3
(if provided). * 13

* 887
755
2x 10.5 120
881 363.5 270

43
901 695.4 37
*4.9

* 348
* 13

* 855 * 13 * 200
* 355 *85
*4

* 915 *40
* 955 * 516.4

Fixed circuit-breakers

HD4 730
708
with truck (on request)
TN 7268
Ur 36 kV
Ir 1250 A
1600 A
Isc 25 kA
31.5 kA

HD4
with truck (on request)
TN 7268
Ir 2500 A
Isc 20 kA
25 kA
31.5 kA

Insulating partitions to be provided by the customer


(a special kit is available on request).
* Distance with truck (if provided).

48
Fixed circuit-breakers

HD4
with truck (on request)
TN 7315
Ur 36 kV
Ir 2500 A
Isc 20 kA
25 kA
31.5 kA

Insulating partitions to be provided by the customer


(a special kit is available on request).
* Distance with truck (if provided).

49
4. Overall dimensions

HD4/P withdrawable circuit-breakers for UniGear type ZS1 switchgears

HD4/P 496 126 8


30 203 120

10
TN 1VCD000227
Ur 12 kV
17.5 A
Ir 630 A

98.5
1250 A
Isc 16 kA

205 1

35

618 2
619
25 kA
626

541
586
Also suitable for Power-

63
Cube PB1

260 1
247.5

19.5
154 1
22

340 25 320

21.5
4

4
456 370
503
383 53
531
416

501 437
490 558
456 2 661
150 1 150 1
55
608

50
HD4/P withdrawable circuit-breakers for UniGear type ZS1 switchgears

HD4/P 493
128
TN 7286 150 1 150 1
120 5.5
30 202
Ur 12 kV

10
17.5 kV
Ir 630 A
1250 A
67.5
Isc 31.5 kA

79
35
48

205 1

618 2
642.5

618

586

543
63
33.5

260 1
247.5

78
154 1
20

21.5
4

19.5
340
4

416
4

4
458 2
437
503
36 570 1.5 53
532
659

HD4/P withdrawable circuit-breakers for UniGear type ZS1 switchgears

HD4/P 636
640
579
TN 7350 210 1 210 1 119
Ur 12 kV 272
111.5 17
44

10
17.5 kV
Ir 1250 A
Isc 40 kA
79

68
122

HD4/P 67.5
310 1

TN 7350
Ur 12 kV
691

688
686

668.5

17.5 kV
63

Ir 1600 A
543

Isc 25 kA 53.5
280 1

31.5 kA 40
245

164.5 1

89

40 kA (*) 21

50 kA (*)
19.5

20
(*) Also suitable for 550 4
21.5

29 359
4
4

PowerCube PB2. 626 2


416
653
36 551 1.5 53
682

51
4. Overall dimensions

HD4/P withdrawable circuit-breakers for UniGear type ZS1 switchgears

HD4/P 636
640
579
TN 7351 119
210 1 210 1
Ur 12 kV 272 111.5 17
44

10
17.5 kV
Ir 2000 A
Isc 25 kA
31.5 kA

79
68

122
40 kA (*) 67.5

310 1
50 kA (*)

(*) Also suitable for


691

688
686

PowerCube PB2.

669
63

543
53.5

280 1
40
245

164.5 1

89
21

19.5
20
4
550

21.5
359

4
29
4

626 2
416
653 36 551 1.5 53
682

HD4/P withdrawable circuit-breakers for UniGear type ZS1 switchgears

HD4/P 842
643
TN 7352 708
119
375
Ur 12 kV (*) 111.5 17
275 1 275 1
17.5 kV 144

10
Ir 2500 A
Isc 25 kA
31.5 kA
40 kA
109

152

67.5
50 kA
310 1

(*) Also suitable for


688
691
686

668.5

PowerCube PB3.
58
63

43.5
280 1

30
245

89

21
164.5 1

19.5

750 4
21.5

4
4

29 359
806 2
416
853
36 554 1.5 53
882

52
HD4/P withdrawable circuit-breakers for UniGear type ZS1 switchgears

HD4/P 842
708 643
TN 7371
375
Ur 12 kV 96.5 17
275 1 275 1
17.5 kV

10
Ir 3150 A (*)
Isc 25 kA
31.5 kA
40 kA
50 kA

109

152
67.5

310 1
(*) 3150 A with forced
switchgear ventilation

730

732
(consult the UniGear
730

type ZS1 switchgear


technical catalogue). 58
63

43.5
30

280 1
245

89
164.5 1
21

19.5
4

21.5
750 29 359
4

806 2 416
853 36 554 1.5 53

882

HD4/P withdrawable circuit-breakers for UniGear type ZS1 switchgears

HD4/P 636
210 1 119 23
210 1
TN 7354
272 18

20
Ur 24 kV 44
Ir 630 A
35

1250 A
Isc 16 kA (*)
20 kA
79

25 kA
310 1

67.5
(*) 630 A only.
2.5
772.5

768
763

736

645
63

12
325 1

12.5
125
253.5

198 2

25.5

4 53
4

610 2 460
4

653 36 7101.5
682

53
4. Overall dimensions

HD4/P withdrawable circuit-breakers for UniGear type ZS1 switchgears

HD4/P 641
799
578
TN 1VCD000099
210 1 210 1 23
Ur 24 kV 272
67.5 44
Ir 1250 A

20
Isc 31.5 kA

92.6
310 1
28

35

792
776

718

682
63

329 1
25.5
293

125
10

550 202 1 4

19.5
21.5
610 2 460
653 36 710 1.5 53
682

HD4/P withdrawable circuit-breakers for UniGear type ZS1 switchgears

HD4/P 842 788


708
TN 7355 (*) 119 23
275 1 275 1

20
Ur 24 kV 144 232 19

Ir 1600 A
Isc 16 kA
20 kA
25 kA
79

31.5 kA
122

67.5
310 1

(*) Also suitable for


PowerCube PB5. 58
817.5

814
807

733
63

700

43.5
345 1

30
310

125

11
198 1

806 2 4
4

457
853
882 36 699 1.5 53

54
HD4/P withdrawable circuit-breakers for UniGear type ZS1 switchgears

HD4/P 842 788


708 23
TN 7356 (**) 119
275 1 275 1

20
19
Ur 24 kV 144 232

Ir 2000 A
Isc 16 kA
20 kA

79
25 kA
31.5 kA

122
67.5

310 1
58
HD4/P

814
817.5
807

TN 7356 (**)

733
Ur 24 kV
63

700
Ir 2500 A (*)
Isc 20 kA 43.5

345 1
25 kA 30
310

125
198 1
31.5 kA 11

(*) 2500 A with forced


ventilation; 2300 A
with natural ventilation. 4

19.5
750

21.5

4
4

457
4
(**) Also suitable for 806 2
PowerCube PB5. 853 36 699 1 53

882

HD4/W withdrawable circuit-breakers for PowerCube modules

HD4/W 128
493 120
TN 7229
150 150 56
Ur 12 kV 30 202 72 5.5
17.5 kV
10
Ir 630 A
1250 A
Isc 31.5 kA
48
35
79
205 1
624.5

632
620

620

543

28
260 1

78
154 1

4
19.5

340
4
4
4

21.5

416.5
458 2
437 20
503
36 570 1.5 53
532

55
4. Overall dimensions

HD4/W withdrawable circuit-breakers for PowerCube modules

HD4/W 636 119


578 111.5
TN 7182 210 1 210 1 56
Ur 12 kV 44 228 63 15

10
17.5 kV
Ir 630 A
1250 A

79
35
Isc 16 kA
67.5

310 1
25 kA
28
31.5 kA
688

691

688
688

636
63

640
16

280 1
29
245

89
165 1
4
550

19.5
21.5
4

359 40
6261
653 416
682 36 551 1.5 53

HD4/W withdrawable circuit-breakers for PowerCube modules

HD4/W 636
578
56
TN 7421 210 1 210 1
44 228 63 15
Ur 12 kV
17.5 kV 10

Ir 1250 A
Isc 40 kA
35
79

50 kA 67.5
310 1

28
688
688

691

636
63

16
280 1
245

89
165 1

4
19.5

626 2
21.5
4
4

29 359 40
653
416
682 36 551 1.5 53
640

56
HD4/W withdrawable circuit-breakers for PowerCube modules

HD4/W 636
578
TN 7239
210 1 210 1
56
Ur 12 kV 272
63 15
44
17.5 kV
Ir 1600 A

10
2000 A
Isc 16 kA
25 kA 67.5

310 1
31.5 kA 28

698
691
668.5

635.5
63

122
79
280 1
245

89
165 1
4

20
550

4
21.5
4

29 359 40
626 2
653 36 551 1.5 53
682 640

HD4/W withdrawable circuit-breakers for PowerCube modules

HD4/W 842
708
TN 1VCD000053
375 643
Ur 12 kV 275 1 275 1 112 16
17.5 kV 144

10
Ir 3150 A
Isc 31.5 kA
109

40 kA
50 kA
152

67.5
310 1
742

730
730

732

58
63

43.5
280 1

30
245

164.5 1
89

21

4
19.5

750 29 359
21.5
4

806 2 416
853
36 554 1.5 53
882

57
4. Overall dimensions

HD4/W withdrawable circuit-breakers for PowerCube modules

HD4/W 636
799
578
TN 7183 119
210 1 210 1
18
Ur 24 kV 272
23

20
44
Ir 630 A
1250 A
Isc 16 kA
20 kA

35

79
25 kA

310 1
67.5

28
772
763

772.5
736

644.5
63

325 1
12.5

125
253.5

198 1
25.5
4

610 2 460
4

653 36 710 1.5 53


682

Withdrawable circuit-breakers HD4/W for UniGear type ZS2 switchgear and for PowerCube module

HD4/W 842 788


708
TN 7402 275 275 119 23
Ur 36 kV 67.5 144 232 19

20
Ir 1250 A
Isc 20 kA
25 kA
35
380

78
941.5

949
952

833
63

60
44
480

198
345

10
125
198

805 4
4

457
836
36 699 53
853
882

58
Withdrawable circuit-breakers HD4/W for UniGear type ZS2 switchgear and for PowerCube module

HD4/W 842
730
TN 7316 706 18
23
Ur 36 kV 275 275

35
Ir 1250 A
Isc 31.5 kA

380

953
956
973
484

125
202
805 4
456
836
30 701 57
853
882

Withdrawable circuit-breakers HD4/W for UniGear type ZS2 switchgear and for PowerCube module

HD4/W 842 788


708
TN 7317 119 23
275 275
19

20
Ur 36 kV 67.5 144 232

Ir 1600 A
2000 A
2500 A (*)
122
79

Isc 20 kA
380

25 kA
31.5 kA 78

(*) With forced


941.5

ventilation.
952

949
903.5

833
63

60
44
480
345

125

10
198
21.5

750
20
4

4
805 457
836 36 699 53
853
882

59
4. Overall dimensions

HD4/Z withdrawable circuit-breakers for UniGear type ZS3.2 - 40.5 kV switchgears

HD4/Z/40.5 kV 840
245
280 280
TN 7227
Ur 40.5 kV
385
Ir 1250 A
2 5
1600 A
2000 A
2500 A (*)

328
Isc 25 kA

A
31.5 kA
1575

(*) With natural ventilation


in loose enclosure

1288.5
type Powerbloc; with
27
15

forced ventilation in
20
switchgear type
100

ZS3.2.
50

900
23 23
30 40
550

43 43

485
22
16
18
120

85

45
32.5 103
100 140 150
A 25 230 200
718
1250-1600 A 35 mm 503
760
582
2000-2500 A (*) 79 mm

HD4/US withdrawable circuit-breakers for UniSwitch (CBW) and UniMix (P1/E) switchgears

HD4/US 24 kV 626 739

TN 1VCD000046 600 305.5


9.5 296 121
Ur 24 kV 210 1 210 1
227.5
Ir 630 A
35

1250 A
Isc 16 KA
20 kA
79

25 kA (*)
310 1

67.5
(*) Only for UniMix P1/E
28
736

644.5

8
63

435.5 2

8
325 1
253.5

25.5

550
653
4

4 53
682 36 650 1.5

60
HD4/US withdrawable circuit-breakers for UniSwitch (CBW) and UniMix (P1/E) switchgears

HD4/SEC 24 kV 625 1 740


604
TN 1VCD000220 149 40
255
Ur 24 kV 307 121,5 1
37

25
229
Ir 630 A

45
1250 A

1
Isc 16 KA
68

79
20 kA

310 1

739
35
A

644,5
734,5

435,5 2
63

36 8

325 1
254

653 25 320

19

4
681 370
382 4
650 414
210 1 210 1 687 1,5 53

19,5

36,3
25
55

DETAIL A
SCALE 1 : 2

61
5. Electric circuit diagram

Application diagrams
The following diagram (No. 1VCD400197) shows the circuits fixed circuit-breakers up to 36 kV, 350 mm pole centre
of the withdrawable circuit-breakers up to 24 kV type HD4/P, distance - No. 1VCD400192
HD4/W, HD4/US, delivered to the customer by means of withdrawable circuit-breakers for PowerCube PB6 and
connector X. UniGear tipo ZS2 - No. 1VCD400194
Specific diagrams are available for other types of circuit- HD4/z 40.5 kV - No. 1VCD400013
breakers: In any case, to take into account the evolution of the product,
fixed circuit-breakers up to 24 kV - No. 1VCD400192 it is always useful to refer to the circuit diagram provided with
fixed circuit-breakers 36 kV, 275 mm pole centre distance each circuit-breaker.
- N. 1VCD400193

Graphical symbols for electrical diagrams (IEC 60617 Standards)


Thermal effect Mass, frame Capacitor (general Passing make contact
symbol) closing momentarily
during release

Electromagnetic effect Conductors in shielded Motor (general symbol) Closing position contact
cable (two conductors (limit switch)
shown)

Timing Connections Rectifier with two Opening position contact


of conductors half-waves (bridge) (limit switch)

Pushbutton control Terminal or clamp Make contact Power circuit-breaker


with automatic opening

Operated by key Socket and plug Break contact Control coil


(female and male) (general symbol)

Earth (general symbol) Resistor Change-over break Lamp (general symbol)


(general symbol) before make contact

62
63
5. Electric circuit diagram

64
65
5. Electric circuit diagram

66
State of operation shown Contacts 21-22-24 change over when the
The diagram indicates the following conditions: gas pressure reaches a value of less than 280
circuit-breaker open and connected kPa absolute from 380 kPa absolute. If rated
circuits de-energized pressure is restored, these contacts change
closing springs discharged over again when, starting from a value of less
key lock with key inserted and held than 280 kPa absolute, the value of 310 kPa
gas pressure at rated service value (380 kPa absolute). absolute is reached.
-FCM1 = Thermomagnetic circuit-breaker for protection
of the spring-charging motor (see note F)
Caption -MAS = Motor for the closing spring charging (see note C)
= Number of diagram figure -MBC = Shunt closing release
* = See note indicated by the letter -MBO1 = First shunt opening release (see note E)
-BCR = Overcurrent release with microprocessor type -MBO2 = Second shunt opening release (see note E)
PR512 outside the circuit-breaker (see note D) -MBO3 = Opening solenoid for microprocessor release
-BER = Device for continuous control of shunt opening PR512 outside circuit-breaker (see note D).
release coil continuity (see note E -MbU = Instantaneous undervoltage release or
-BGB1, -BGB2 = Circuit-breaker auxiliary contacts undervoltage release with electronic time-delay
-BGB4 = Auxiliary passage contact (with momentary device (see note B)
closing during circuit-breaker opening) -KFI = Integrated circuit for gas pressure control,
-BGB5 = Contacts for electrical signalling of undervoltage including:
release energised/de-energised -PFG = Green lamp indicating normal gas
-BGK = Contact operated by the key lock preventing pressure
electrical opening with earthing truck connected -PFR = Red lamp indicating insufficient gas
(compulsory accessory for earthing trucks with pressure
making capacity) -PFY = Yellow lamp indicating low gas pressure
-BGS1 = Limit contacts of the spring charging motor -KFA1=Auxiliary relay to double the -BP
-BGS2 = Contact for signalling closing springs loaded- pressure-switch contacts with
discharged intervention for low gas pressure
-BGT1 = Contacts electrically signalling circuit-breaker in -KFA2=Auxiliary relay to double the -BP
the connected position (see note G) pressure-switch contacts with
-BGT2 = Contacts electrically signalling circuit-breaker in intervention for insufficient gas pressure
the isolated position (see note G) -XDB5=Connector
-BGT3 = Circuit-breaker position contact, open during -KFT = Undervoltage release electronic time-delay
the isolating travel device (see note I)
-BGT5 = Position contacts signalling circuit-breaker in the -QAB = Main circuit-breaker
racked-out position (these are contacts signalling -SFC = Pushbutton or contact for circuit-breaker
circuit-breaker isolated located in the enclosure, closing
in the fixed part: see contacts -BGT2 in diagram -SFO = Pushbutton or contact for circuit-breaker
1VCP400036 figures 5-6) opening
-BPS = Pressure-switch with two intervention -SFL1 = Contact for circuit-breaker closing lock
thresholds: -TB1,-TB2 = Rectifiers for -MBO1 and -MBO2 releases
intervention for low gas pressure. Contacts -RF = Filter (only provided with 220V d.c. voltage
11-12-14 change over, in relation to the position supply)
indicated in the diagram, when the gas pressure -RLE1 = Locking magnet. If de-energized it mechanically
reaches a value of less than 310 kPa absolute prevents circuit-breaker closing
from 380 kPa absolute. If rated pressure is -RLE2 = Locking magnet. If de-energized it mechanically
restored, these contacts change over again prevents circuit-breaker racking-in and isolation
when, starting from a value of less than 310 (it is possible to limit its consumption by
kPa absolute, the value of 340 kPa absolute is connecting a delayed pushbutton in series to
reached. enable the operation)
intervention for insufficient gas pressure. -XDB = Circuit-breaker circuit connector
-XDB1 = Switchgear terminal board (outside the circuit-
breaker)
-XDB2... -XDB62 = Accessory connectors

67
5. Electric circuit diagram

Description of figures to prevent electrical opening of the earthing truck


Fig. 1 = Closing spring charging motor circuit (see note C). with making capacity racked-in (compulsory
Fig. 2 = Shunt closing release (antipumping is carried out accessory for earthing trucks with making capacity
mechanically). when the -MBO1 shunt opening release is provided).
Fig. 3 = Locking magnet on operating mechanism. If Fig. 21 = Thermomagnetic circuit-breaker for protection
energized, mechanically prevents circuit-breaker of the spring-charging motor (see note F).
from closing. Exclusion from permanent service Fig. 22 = Contact for electrically signalling closing springs
of the magnet that provides a locking action upon charged.
circuit- breaker closing is only permitted with a delay Fig. 23 = Contact for electrically signalling closing springs
of at least 0.5 s. discharged.
Fig. 4 = Locking magnet. If de-energized it mechanically Fig. 24 = Contact for electrically signalling under-voltage
prevents circuit-breaker racking-in and isolation release energized (see note B).
(it is possible to limit its consumption by connecting Fig. 25 = Contact for electrically signalling under-voltage
a time-delay pushbutton in series for enabling the release de-energized (see note B).
operation) (see note H). Fig. 26 = Contact for electrically signalling motor protection
Fig. 5 = Instantaneous undervoltage release (see note B) circuit-breaker closed.
Fig. 6 = Undervoltage release with electronic time-lag device Fig. 27 = Contact for electrically signalling motor protection
(see notes B and I). circuit-breaker open.
Fig. 7 = First shunt opening release circuit with possibility Fig. 30 = Auxiliary passing contact with momentary closing
of continuous control of the winding (see note E). during circuit-breaker opening (intervention of
Fig. 9 = Second shunt opening release circuit with possibility -MBO1, -MBO2, -MBO3 and -MBU).
of continuous control of the winding (see note E). Fig. 32 = Circuit-breaker auxiliary contacts available.
Fig. 10 = Opening solenoid for microprocessor release PR512 Fig. 51 = Contact for electrically signalling circuit-breaker in
outside circuit-breaker (see note D) the racked-in and isolated positions located on the
Fig. 11 = Gas pressure control circuit. This includes the circuit-breaker, supplied on request (see note G).
contacts for remote indication of normal, low and
insufficient gas pressure.
For -BPS pressure switch intervention values see the
caption. Incompatibility
Fig. 12 = Integrated gas pressure monitoring circuit.It
The circuits indicated by the following figures cannot be
includes:
supplied at the same time on the same circuit-breaker:
intervention for insufficient gas pressure with
circuit-breaker opening by means of the -MBO2
5 - 6 - 14 9 - 10 - 12 - 20 24 - 25
release and lock on closing and opening by
5 - 6 - 20 11 - 12 - 14 26 - 27
means of a -KFA2 relay auxiliary contact (provide
9 - 10 - 12 - 14 22 - 23 31 - 32
the locking magnet in fig. 3)
3 lamps for local indication of normal, low and
insufficient gas pressure
contacts for remote indication of normal, low and
insufficient gas pressure.
For pressure switch pressure values please refer to
circuit-breaker electrical diagram.
Fig. 14 = Gas pressure control circuit. It includes:
intervention for insufficient gas pressure with lock
on circuit-breaker closing and opening by means
of the -KFA2 relay auxiliary contacts (provide the
locking magnet in fig. 3)
3 lamps for local indication of normal, low and
insufficient gas pressure
contacts for remote indication of normal, low and
insufficient gas pressure.
For -BPS pressure switch intervention values see the
caption.
Fig. 20 = Contact operated by the key lock in closed position

68
Notes
A) The circuit-breaker is only fitted with the accessories E) The circuit for controlling continuity of the shunt opening
listed in the order confirmation. To make out the order, release winding must only be used for this function.
please consult the catalogue of the apparatus. At a power supply lower than 220 V, connect the Control
B) The undervoltage release can be provided for power Coil Continuity device, or a relay or a signalling lamp
supply with voltage branched on the supply side of the which consumes a current not exceeding 20 mA.
circuit-breaker or from an independent source. At a power supply equal to or higher than 220 V, connect
Either the instantaneous undervoltage release or the one a delay or signalling lamp which consumes a current not
with electronic delay device can be used (delay can be exceeding 10 mA.
selected between 0.5 3 s; see note I). Circuit-breaker Other uses might jeopardise release functionality.
closing is only possible with the release energised (the F) The -FCM1 circuit-breaker in fig. 21 must always be
closing lock is made mechanically). provided when there is a 24 kV d.c. spring charging
The contact in fig. 24 or the one in fig. 25 is available on motor.
request. In case of opening caused by a fault in the motor, before
A delay of 50 ms between the moment of consent of the carrying out manual resetting, recharge the springs by
undervoltage release and energisation of the shunt closing means of the special handle.
release must be inserted when there is the same power G) The contacts (-BGT1 and -BGT2) shown in fig. 51 for
supply for the shunt closing and undervoltage releases signalling the circuit-breaker status are located on the
and automatic circuit-breaker closing on return of the circuit-breaker (moving part) and are available on request.
auxiliary power supply is required. This can be carried out However, application of these contacts on the enclosure
by means of a circuit outside the circuit-breaker, including is usually foreseen (fixed part): see diagram 1VCD400036.
a permanent closing contact, the contact indicated in fig. H) When fig. 4 is requested, the contact of pack -BGB1 to
24 and a time-delay relay. terminals 5-6 in fig. 32 is not available.
C) Check the power available on the auxiliary circuit to verify When figs. 26-27 are requested, the -BGB2 contact to
the possibility of starting several motors for charging the terminals 1-2 of fig. 32 is not available.
closing springs at the same time. To avoid excessive I) Make one of the following bridges to select the delay
consumption, it is necessary to charge the springs required (see diagram 1VCD400062):
manually before supplying the auxiliary circuit with 0.5 s: terminals 6-7
voltage. 1 s: terminals 6-8
D) Consult diagram 401530 for connections between the 1.5 s: terminals 6-9
auxiliary circuits of the circuit-breaker and the overcurrent 2 s: terminals 6-10
release with microprocessor type PR512 installed in the 3 s: no bridge.
switchgear.

69
Contact us

ABB S.p.A. The data and illustrations are not binding. We reserve

1VCP000004 - Rev. P, en - Technical catalogue - 2015.09 (HD4) (gs)


the right to make changes without notice in the course
Power Products Division of technical development of the product.
Unit Operativa Sace-MV Copyright 2015 ABB. All rights reserved.
Via Friuli, 4
I-24044 Dalmine
Tel.: +39 035 6952 111
Fax: +39 035 6952 874
e-mail: info.mv@it.abb.com

www.abb.com