You are on page 1of 19

16.

DESIGN OF BASE PLATE & BOLT


REACTION SUMMARY FOR NORMAL PULL CASE
Horizontal Vertical Horizontal
Node L/C Fx Mton Fy Mton Fz Mton
Max Fx 3 1136 1(DL 0.9 8.8 -0.4
Min Fx 3 1137 1(DL -0.9 -8.6 0.4
Max Fy 2 1137 1(DL -0.2 8.9 0.2
Min Fy 3 1137 1(DL -0.9 -8.6 0.4
Max Fz 4 1110 1(DL- 0.2 -6.3 1.1
Min Fz 4 1107 1(DL -0.2 6.8 -1.1
Max Mx 1 1101 1(DL -0.4 -5.4 -0.1
Min Mx 1 1101 1(DL -0.4 -5.4 -0.1
Max My 1 1101 1(DL -0.4 -5.4 -0.1
Min My 1 1101 1(DL -0.4 -5.4 -0.1
Max Mz 1 1101 1(DL -0.4 -5.4 -0.1
Min Mz 1 1101 1(DL -0.4 -5.4 -0.1

REACTION SUMMARY FOR NORMAL SHORT CIRCUIT CASE


Horizontal Vertical Horizontal
Node L/C Fx Mton Fy Mton Fz Mton
Max Fx 1 2130 1(DL- 1.126 11.504 0.28
Min Fx 1 2127 1(DL -1.115 -11.296 -0.274
Max Fy 4 2101 1(DL -0.36 13.273 -2.101
Min Fy 1 2101 1(DL -0.954 -12.955 -0.29
Max Fz 4 2110 1(DL- 0.229 -8.393 1.414
Min Fz 4 2101 1(DL -0.36 13.273 -2.101
Max Mx 1 2101 1(DL -0.954 -12.955 -0.29
Min Mx 1 2101 1(DL -0.954 -12.955 -0.29
Max My 1 2101 1(DL -0.954 -12.955 -0.29
Min My 1 2101 1(DL -0.954 -12.955 -0.29
Max Mz 1 2101 1(DL -0.954 -12.955 -0.29
Min Mz 1 2101 1(DL -0.954 -12.955 -0.29
DESIGN OF BASE PLATE & BOLT For Max VERTICAL LOAD (Load Comb 1137)-NORMAL CASE

Design of Base Plate

From Reaction

Maximum Compressive Load 9000.00

Maximum Moment (Mx) 0.00

Max Shear 1200.00

Grade of Concrete M20

fck 20

Permissible bearing pressure = 20 x 0.25 5

Provide Base Plate D= 270

B= 270

Thickness of Base Plate provided 12

Center of foundation bolt from edge 55

No. of Bolts 3

No. of Bolts taking tension while bending 1

Diameter of bolts 20

Max Stress in concrete due to direct compression, (scc) = 1.2 Mpa. < 5.0

Ok
Check for the Individual Capacity of the Base Plate

The plate panel is analysed cons. upward uniform pressure for two side fixed case

Length of projection a = b= 135.00

Uniform upward pressure, q1 1.2

Thickness of plate, t = 12

For uniformr pressure distribution b1 = 0.307

1 q 1 b 2= 47 Mpa. < 187.5


b= 2
t

Design of foundation bolt

Tension per bolt 0.00

Shear per bolt = 1200 / 3 400.00

Diameter of bolt Property Class 4.6 considered 20

Permissible Tensile Stress 120

Permissible Shear Stress 80

Actual Tensile Stress 0.00

Actual Shear Stress Ok 15.61

Interaction factor Ok 0.20

Bond Stress of concrete 0.8

Embedment length required = 0 x 9.807/(0.8 x 3.142 x 20 x 1.33) 0.00

Required Length = 0 x 1.1 -

Provide total length of 225 mm minimum with min embedment length of 100 mm.
Kg.

Kg.-m.

Kg

Mpa.

Mpa.

mm .

MM

mm.

mm.

mm.

Mpa.
mm.

Mpa.

mm.

Mpa.

Ok

Kg.

Kg.

mm.

Mpa.

Mpa.

Mpa.

Mpa.

< 1.4

Mpa.

mm.

mm.
DESIGN OF BASE PLATE & BOLT For Tension (Load Comb 1137)-NORMAL CASE

Design of Base Plate

From Reaction

Maximum tension Load

Maximum Moment (Mz)

Max Shear

Grade of Concrete

fck

Permissible bearing pressure = 20 x 0.25

Provide Base Plate D=

B=

Thickness of Base Plate provided

Center of foundation bolt from edge

No. of Bolts

No. of Bolts taking tension while bending

Diameter of bolts

Check for the Individual Capacity of the Base Plate

Assuming tension act along the centre line of BP and two way bening along width of BP occur

therefore Moment on BP due to uplift M = P(D-2c)/14

= 102.85714286

This moment will be resisted by BP, sectional modulus of BP(Z) = Bt^2/6

6480

Therefore max stress in BP= M/Z= 158.73015873 MP <

Design of foundation bolt

Tension per bolt due to Uplift = -9000 / 3

Shear per bolt = 1200 / 3

Diameter of bolt Property Class 4.6 considered

Permissible Tensile Stress

Permissible Shear Stress

Actual Tensile Stress

Actual Shear Stress Ok

Interaction factor Ok

Bond Stress of concrete

Embedment length required = 3000 x 9.807/(0.8 x 3.142 x 20 x 1.33)

Required Length = 440.08 x 1.1


Provide total length of 725 mm minimum with min embedment length of 600 mm.
-9000.00 Kg.

0.00 Kg.-m.

1200.00 Kg

M20

20 Mpa.

5 Mpa.

270 mm .

270 MM

12 mm.

55 mm.

20 mm.

Kg-m

mm3

187.5 Mpa

OK

3000.00 Kg.

400.00 Kg.

20 mm.

120 Mpa.

80 Mpa.

117.06 Mpa.

15.61 Mpa.

1.17 < 1.4

0.8 Mpa.

440.08 mm.

500.00 mm.
DESIGN OF BASE PLATE & BOLT For Max VERTICAL LOAD (Load Comb 2101)-SHORT CIRCUIT CASE

Design of Base Plate

From Reaction

Maximum Compressive Load 13300.00

Maximum Moment (Mx) 0.00

Max Shear 2100.00

Grade of Concrete M20

fck 20

Permissible bearing pressure = 20 x 0.25" x 1.25 6.25

Provide Base Plate D= 270

B= 270

Thickness of Base Plate provided 12

Center of foundation bolt from edge 55

No. of Bolts 3

No. of Bolts taking tension while bending 1

Diameter of bolts 20

Max Stress in concrete due to direct compression, (scc) = 1.8 Mpa. < 6.3

Ok
Check for the Individual Capacity of the Base Plate

The plate panel is analysed cons. upward uniform pressure for two side fixed case

Length of projection a = b= 135.00

Uniform upward pressure, q1 1.8

Thickness of plate, t = 12

For uniformr pressure distribution b1 = 0.307

1 q 1 b 2= 70 Mpa. < 234.375


b= 2
t

Design of foundation bolt

Tension per bolt 0.00

Shear per bolt = 2100 / 3 700.00

Diameter of bolt Property Class 4.6 considered 20

Permissible Tensile Stress 150

Permissible Shear Stress 100

Actual Tensile Stress 0.00

Actual Shear Stress Ok 27.31

Interaction factor Ok 0.27

Bond Stress of concrete 0.8

Embedment length required = 0 x 9.807/(0.8 x 3.142 x 20 x 1.33) 0.00

Required Length = 0 x 1.1 -

Provide total length of 225 mm minimum with min embedment length of 100 mm.
Kg.

Kg.-m.

Kg

Mpa.

Mpa.

mm .

MM

mm.

mm.

mm.

Mpa.
mm.

Mpa.

mm.

Mpa.

Ok

Kg.

Kg.

mm.

Mpa.

Mpa.

Mpa.

Mpa.

< 1.4

Mpa.

mm.

mm.
DESIGN OF BASE PLATE & BOLT For Tension (Load Comb 2101)-SHORT CIRCUIT CASE

Design of Base Plate

From Reaction

Maximum tension Load

Maximum Moment (Mz)

Max Shear

Grade of Concrete

fck

Permissible bearing pressure = 20 x 0.25" x 1.25

Provide Base Plate D=

B=

Thickness of Base Plate provided

Center of foundation bolt from edge

No. of Bolts

No. of Bolts taking tension while bending

Diameter of bolts

Check for the Individual Capacity of the Base Plate

Assuming tension act along the centre line of BP and two way bening along width of BP occur

therefore Moment on BP due to uplift M = P(D-2c)/14

= 147.42857143

This moment will be resisted by BP, sectional modulus of BP(Z) = Bt^2/6

6480

Therefore max stress in BP= M/Z= 227.51322751 MP <

Considering 33% increase in stress due to SHORT CIRCUIT.

(Ref. IS 800:Clause 6.3)

Design of foundation bolt

Tension per bolt due to Uplift = -12900 / 3

Shear per bolt = 1500 / 3

Diameter of bolt Property Class 4.6 considered

Permissible Tensile Stress

Permissible Shear Stress

Actual Tensile Stress

Actual Shear Stress Ok

Interaction factor Ok

Bond Stress of concrete

Embedment length required = 4300 x 9.807/(0.8 x 3.142 x 20 x 1.33)

Required Length = 630.79 x 1.1


Provide total length of 925 mm minimum with min embedment length of 800 mm.
-12900.00 Kg.

0.00 Kg.-m.

1500.00 Kg

M20

20 Mpa.

6.25 Mpa.

270 mm .

270 MM

12 mm.

55 mm.

20 mm.

Kg-m

mm3

249.375 Mpa

Considering 33% increase in stress due to SHORT CIRCUIT. OK

4300.00 Kg.

500.00 Kg.

20 mm.

150 Mpa.

100 Mpa.

167.79 Mpa.

19.51 Mpa.

1.31 < 1.4

0.8 Mpa.

630.79 mm.

700.00 mm.
Horizontal Vertical Horizontal Resultant Rotational
Node L/C X mm Y mm Z mm mm rX rad
Max X 38 2137 1(DL 8.3 1.2 -9.7 12.8 0.0
Min X 38 2136 1(DL -8.0 -1.2 9.7 12.7 0.0
Max Y 37 2101 1(DL 1.1 1.4 19.1 19.2 0.0
Min Y 7 2101 1(DL -1.1 -1.5 18.3 18.4 0.0
Max Z 39 2101 1(DL -1.3 -1.4 21.6 21.7 0.0
Min Z 39 2110 1(DL- 1.0 0.8 -14.0 14.0 0.0
Max rX 39 2101 1(DL -1.3 -1.4 21.6 21.7 0.0
Min rX 39 2110 1(DL- 1.0 0.8 -14.0 14.0 0.0
Max rY 4 2116 1(DL 0.0 0.0 0.0 0.0 0.0
Min rY 4 2101 1(DL 0.0 0.0 0.0 0.0 0.0
Max rZ 7 2136 1(DL -6.9 -0.3 9.3 11.6 0.0
Min rZ 7 2137 1(DL 7.1 0.2 -9.3 11.7 0.0
Max Rst 39 2101 1(DL -1.3 -1.4 21.6 21.7 0.0
rY rad rZ rad
0.0 0.0
0.0 0.0
0.0 0.0
0.0 0.0
0.0 0.0
0.0 0.0
0.0 0.0
0.0 0.0
0.0 0.0
0.0 0.0
0.0 0.0
0.0 0.0
0.0 0.0

You might also like