You are on page 1of 298

A Note To Our Download Customers:

The last page of this publication is an oversized page. It is a 22-in. by 17-in. enlargement
of the table spanning pages 238 and 239 of the book. It can be printed from Acrobat by
selecting "Shrink oversized pages to paper size" in the Print dialog box, or simply "Fit to
Page", depending on your version of Acrobat. Landscape orientation is recommended for
that page.
HVAC DESIGN MANUAL
FOR
HOSPITALS AND CLINICS
This publication was prepared under ASHRAE Special Project SP-91 in cooperation with the
cognizant ASHRAE group, TC 9.8, Large Building Air-Conditioning Applications.

LIST OF CONTRIBUTORS
Final Voting Committee Members

Robert Cox, P.E. Farhad Memarzadeh, Ph.D., P.E.


Farnsworth Group National Institutes of Health
Paul J. DuPont, P.E. Frank A. Mills, C.Eng.
DuPont Engineering
Douglas Erickson Environmental Design Consultants Ltd., U.K.
American Society for Health Care Engineering Vince Mortimer
Kimball Ferguson, P.E. NIOSH
Duke University Health System Paul T. Ninomura, P.E.
Milton Goldman, M.D., P.E.
Mann Mechanical Co. Indian Health Service
Jeffrey Hardin, P.E. Mary Jane Phillips
U.S. Army Corps of Engineers U.S. Navy Bureau
Richard D. Hermans, P.E. of Medicine and Surgery (Ret.)
Center for Energy and Environment Anand K. Seth, P.E.
Carl N. Lawson
Duke University Medical Center Partners HealthCare System, Inc.
John Lewis, P.E. Andrew Streifel
P2S Engineers, Inc. University of Minnesota

Other Major Contributors and Reviewers


*Original members who are no longer active
**Active Corresponding Members
(Only major reviewers and contributors are listed. The committee is very thankful to
numerous individuals who freely gave their time to review several parts of this manual.)

Joseph Bonanno, Senior Engineer (Multiple Chapters) Mark Lentz, P.E.*


Richard D. Kimball Company, Inc. Lentz Engineering & Associates
Cris Copley, P.E. (Chapter 12) Olga Leon, P.E.** (All Chapters)
BR+A Partners HealthCare System, Inc.
Jason DAntona, P.E. (Appendix G) C. Glen Mayhall, M.D. (Chapter 2)
Partners HealthCare System, Inc. University of Texas Medical Branch
Richard DiRinzio (Appendix H) Howard J. Mckew, P.E., CPE (Multiple Chapters)
Engineered Solutions Richard D. Kimball Company, Inc.
Alexandra Dragan, Ph.D., P.E.* Andrew Nolfo, P.E.** (Multiple Chapters)
Department of Public Work
NEBB
Kenneth E. Gill, P.E.*
Aguirre Corp. Andrew Persily, Ph.D. (Chapter 2)
William Goode, P.E. (All Chapters) National Institute of Standards and Technology
W.J. Goode Corp. Chris Rousseau, P.E.*
Ray Grill, P.E. (Chapter 11) Newcomb & Boyd
RJA Group Anesha Morton Rumble
Darold Hanson* (Chapter 10) Formerly with NIOSH; Currently with
Formerly with Honeywell, now retired MCAQ (Mecklenburg County Air Quality)
George Hardisty, P.E. (Appendix G) Teerachai Srisirikul (Appendix H)
BR+A Partners HealthCare System, Inc.
Joe Howard*
Esmail Torkashvan, P.E.** (Multiple Chapters)
Formerly with BJC Health Systems
Leon Kloostra (Chapter 10) NIH, NCRR
Titus Corp. Marjorie Underwood (Chapter 2)
Paul Konz, P.E. (Appendix G) Mt. Diablo Medical Center, Concord, Calif.
TRO James E. Woods, Ph.D., P.E. (Chapter 2)
Mitsu Koshima, Senior Engineer (Multiple Chapters) Building Dianostic Research Institute
Richard D. Kimball Company, Inc. Mark Yankich, P.E. (Chapter 9)
John Kramer, P.E. (Chapter 10) Rogers, Lovelock, and Fritz
Staff Engineer, Duke Medical Center

Walter Grondzik, Technical Editor (All Chapters)


Florida A&M University
HVAC DESIGN MANUAL
FOR
HOSPITALS AND CLINICS

American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc.


ISBN 1-931862-26-5

2003 American Society of Heating, Refrigerating


and Air-Conditioning Engineers, Inc.
1791 Tullie Circle, N.E.
Atlanta, GA 30329
www.ashrae.org

All rights reserved.

Printed in the United States of America

Cover design by Tracy Becker.

ASHRAE has compiled this publication with care, but ASHRAE has not investigated, and ASHRAE expressly disclaims
any duty to investigate, any product, service, process, procedure, design, or the like that may be described herein. The
appearance of any technical data or editorial material in this publication does not constitute endorsement, warranty, or
guaranty by ASHRAE of any product, service, process, procedure, design, or the like. ASHRAE does not warrant that the
information in the publication is free of errors, and ASHRAE does not necessarily agree with any statement or opinion in
this publication. The entire risk of the use of any information in this publication is assumed by the user.

No part of this book may be reproduced without permission in writing from ASHRAE, except by a reviewer who may
quote brief passages or reproduce illustrations in a review with appropriate credit; nor may any part of this book be repro-
duced, stored in a retrieval system, or transmitted in any way or by any meanselectronic, photocopying, recording, or
otherwithout permission in writing from ASHRAE.

ASHRAE STAFF

SPECIAL PUBLICATIONS PUBLISHING SERVICES


Mildred Geshwiler Barry Kurian
Editor Manager

Erin S. Howard Jayne Jackson


Assistant Editor Production Assistant

Christina Helms
Assistant Editor
PUBLISHER
Michshell Phillips
Secretary W. Stephen Comstock
DEDICATION
This design manual is dedicated to our friend and colleague, John Lewis. While the manual was being prepared,
John suffered a stroke. During the final months of its preparation, we missed his keen engineering insight, insistence
on technical accuracy, and clear and understandable writing. Above all, we missed his humor and friendly presence at
our meetings. We look forward to his continuing contribution to health care engineering and HVAC design. The
ASHRAE SP 91 Committee is grateful for extraordinary effort by John Lewis in creating this document.
CONTENTS
FOREWORD . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . xiii
CHAPTER 1INTRODUCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
1.1 Preface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
1.2 Purpose . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
1.3 Intended Audience . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
1.4 Overview. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
CHAPTER 2TERMINOLOGY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
2.1 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
2.2 Terms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
CHAPTER 3FACILITY DESCRIPTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15
3.1 IntroductionHealth Care Facilities . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15
3.2 Patient Care Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16
3.3 Diagnostic and Treatment Centers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .17
3.4 Surgery Suites. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .21
3.5 Administrative Areas . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .21
3.6 Support Services . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .23
CHAPTER 4OVERVIEW OF HEALTH CARE HVAC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .27
4.1 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .27
4.2 Infection and Safety Hazards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .28
4.3 Infection Control. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .29
4.4 Criteria . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .31
4.5 Energy Efficiency and Operating Cost . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .32
4.6 Equipment Sizing for Heating and Cooling Loads. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .32
4.7 Ventilation and Outside Air Quality . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .40
4.8 Environmental Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .41
4.9 HVAC System Hygiene. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .42
4.10 Flexibility for Future Changes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .43
4.11 Integrated Design . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .43
CHAPTER 5HVAC SYSTEMS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .47
5.1 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .47
5.2 HVAC Systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .47
5.3 All-Air Systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .48

vii
viii HVAC DESIGN MANUAL FOR HOSPITALS AND CLINICS

5.4 Air and Water Systems. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53


5.5 All-Water Systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
5.6 Unitary Refrigerant-Based Systems for Air Conditioning. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
CHAPTER 6DESIGN CONSIDERATIONS FOR EXISTING FACILITIES . . . . . . . . . . . . . . . . . . . . . . . 57
6.1 General Considerations for Existing Facilities . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
6.2 Infection Control During Construction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
CHAPTER 7COOLING PLANTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
7.1 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
7.2 Design Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
7.3 Optimizing Energy Efficiency . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
7.4 Chilled Water Distribution Systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
7.5 Chiller Plant Controls and Instrumentation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69
7.6 Start-Up and Commissioning Activities . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70
7.7 Cooling Plants for Clinics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70
CHAPTER 8SPACE AND PROCESS HEATING SYSTEMS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71
8.1 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71
8.2 Heating Plant Considerations. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71
8.3 Features of Heating Equipment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74
8.4 Terminal Heating Equipment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76
8.5 Piping Systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76
8.6 Domestic Water Systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78
8.7 Sterilization and Humidification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79
CHAPTER 9AIR-HANDLING AND DISTRIBUTION SYSTEMS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87
9.1 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87
9.2 Concept Design . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87
9.3 Basic Air-Handling Unit Design Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87
9.4 Air-Handling System Alternatives . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 94
9.5 Ductwork . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 96
9.6 Terminal Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 98
9.7 Room Air Distribution . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 99
9.8 Acoustical Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 101
9.9 General Considerations for Handling Saturated Air . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 103
9.10 Desiccant Systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 103
9.11 Packaged Units. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 104
CHAPTER 10CONTROLS AND INSTRUMENTATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 105
10.1 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 105
10.2 Characteristics and Attributes of Control Methods . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 105
10.3 Pressurization, Outside Air Ventilation, and Outside Air Economizer Controls . . . . . . . . . . . . . . 106
10.4 Isolation Rooms and Similar Rooms with RDP Criteria . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 109
10.5 Operating Room Controls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 110
10.6 Laboratory Controls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 111
10.7 General Control Sequences Used in Hospitals and Clinics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 111
10.8 Control Safeties . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 112
10.9 DX System Controls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 113
CHAPTER 11SMOKE CONTROL AND LIFE SAFETY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 115
11.1 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 115
11.2 Smoke Compartments and Barriers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 117
CONTENTS ix

11.3 Passive Smoke Control. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 120


11.4 Active Smoke Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 120
11.5 Stairwell Pressurization . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 122
11.6 Elevators. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 123
11.7 Controls and Sequencing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 123
11.8 Energy Management and Smoke Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 124
11.9 Testing and Commissioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 124
11.10 Health and Life Safety . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 125
11.11 Atrium Smoke Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 126
11.12 Engineered Fire Safety Design. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 127
11.13 Climatic Effects on Building Systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 127
CHAPTER 12ROOM DESIGN . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 129
12.1 General Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 129
12.2 Role of Ventilation in Infection Control and Comfort . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 129
12.3 Health Care Room Design Criteria . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 133
CHAPTER 13CLINICS AND OTHER HEALTH CARE FACILITIES . . . . . . . . . . . . . . . . . . . . . . . . . . 143
13.1 Occupancy Classifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 143
13.2 Clinic Spaces . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 145
CHAPTER 14OPERATION AND MAINTENANCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 147
14.1 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 147
14.2 Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 147
14.3 Modern Maintenance Tools . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 149
14.4 Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 153
14.5 Complying with Joint Commission Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 153
14.6 Construction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 155
14.7 Special Maintenance Considerations for HVAC Systems/Equipment . . . . . . . . . . . . . . . . . . . . . . 160
14.8 Building Commissioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 160
14.9 Capital Investment Planning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 160
CHAPTER 15COMMISSIONING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 161
15.1 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 161
15.2 Commissioning Authority . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 161
15.3 The Commissioning Process . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 162
15.4 Documentation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 165
15.5 Construction Process and Commissioning Interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 167
15.6 Retro-Commissioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 168
15.7 Costs, Offsets, and Benefits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 170
15.8 Summary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 172
CHAPTER 16ENERGY EFFICIENT DESIGN AND
CONSERVATION OF ENERGY RESOURCES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 173
16.1 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 173
16.2 Health Care Constraints . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 173
16.3 Energy Usage in Health Care Facilities . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 174
16.4 Design of Energy Efficient HVAC Systems. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 181
16.5 Air-to-Air Heat Recovery Strategies . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 187
16.6 Design of Energy Efficient Chilled Water and Condenser Water Systems . . . . . . . . . . . . . . . . . . 189
16.7 Energy Conservation Design of Central Heating Systems. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 192
16.8 Design of Energy Efficient Building Envelopes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 195
x HVAC DESIGN MANUAL FOR HOSPITALS AND CLINICS

16.9 Operations and Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 195


16.10 Commissioning/Recommissioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 195
16.11 Financing an Energy Efficiency Program . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 195
APPENDIX AMANAGING CONSTRUCTION AND RENOVATION
TO REDUCE RISK IN HEALTH CARE FACILITIES. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 197
A.1 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 197
A.2 Risk Assessment. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 197
A.3 Planning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 198
A.4 Environmental Assessment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 198
A.5 Ventilation Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 199
A.6 Project Implementation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 199
A.7 Communication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 200
A.8 Commissioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 201
A.9 Legal Issues . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 201
APPENDIX BDISASTER MANAGEMENT. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 203
B.1 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 203
B.2 Terrorism . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 203
B.3 Disaster Classification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 204
B.4 Space Definitions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 206
B.5 Required Services in Emergency and Disaster . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 207
B.6 Summary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 208
APPENDIX CLOAD CALCULATIONS AND EQUIPMENT HEAT GAINS . . . . . . . . . . . . . . . . . . . . 213
C.1 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 213
C.2 Outdoor and Indoor Design Conditions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 213
C.3 Design Loads . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 213
C.4 Diversity Factors and Schedule of Operations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 214
C.5 Supply Air . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 215
C.6 Air Balance. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 215
C.7 HVAC Equipment Sizing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 215
APPENDIX DINFECTION CONTROL ISSUES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 217
D.1 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 217
D.2 Context for Infection Control. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 217
D.3 Nonsocomial Infection Costs and Morbidity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 217
D.4 Isolation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 218
D.5 Anterooms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 218
D.6 Infection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 219
Airborne Respiratory Diseases and Mechanical Systems
for Control of Microbes, W.J. Kowalski and William Bahnfleth . . . . . . . . . . . . . . . . . . . . . . . . . . 220
APPENDIX ELIFE-CYCLE COST ANALYSIS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 231
E.1 Life-Cycle Cost Analysis . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 231
APPENDIX FVENTILATION STANDARDS AND CURRENT TRENDS. . . . . . . . . . . . . . . . . . . . . . . 233
F.1 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 233
F.2 Ventilation Codes and Standards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 233
F.3 Ventilation Background and Details. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 234
F.4 Air Diffusion Criteria . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 237
F.5 New Trend in Ventilation System Design . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 244
F.6 Conclusions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 246
CONTENTS xi

APPENDIX GPOWER QUALITY ISSUES. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 247


G.1 Emergency Power. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 247
G.2 Variable Frequency Drives . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 248
APPENDIX HSAMPLE CONTROL STRATEGIES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 253
H.1 Sequence of Operation of 100% Outside Air-Handling Unit
with Two Supply Fans, a Common Exhaust Fan, and a Hot Water
Run-Around Loop Heat Recovery System. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 253
H.2 Sequence of Operation of 100% Outside Air-Handling Unit
with Exhaust Fan and Hot Water Run-Around Loop Heat Recovery System . . . . . . . . . . . . . . . . 255
H.3 Sequence of Operation of 100% Outside Air-Handling Unit
with Face and Bypass and Exhaust Fan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 257
H.4 Sequence of Operation of Air-Handling Unit with Return Air Fan and Air-Side Economizer . . . 258
H.5 Sequence of Operation of Hot Deck and Cold Deck Air-Handling Unit
with Return Air Fan and Air-Side Economizer
(Dehumidification and Cooling of All Supply Air with Reheat for Hot Stream) . . . . . . . . . . . . . 260
APPENDIX IOPERATING ROOM AIR DISTRIBUTION. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 263
Comparisons of Operating Room Ventilation Systems in the
Protection of the Surgical Site, Farhad Memarzadeh and Andrew P. Manning . . . . . . . . . . . . . . . 265
REFERENCES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 279
BIBLIOGRAPHY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 287
INDEX . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 291
FOREWORD
First and foremost, this document is not a standard or a guideline. It is a design manual. It provides design strat-
egies known to meet applicable standards and guidelines, whatever they may be.
The concept of the Health Care Facility Design Manual (Design Manual) was approved in 1996 at the ASHRAE
Annual Meeting in Boston. At the January Winter Meeting in San Francisco, a forum was held to explain the project
and ask the ASHRAE membership what they wanted to see in the manual. We had our first short committee meeting
in San Francisco in January 1997, after which our work began. The committee met four times a year, twice at the
national meetings and twice at other locations.
Even though we were working on a design manual, the committee identified a need for research. Some of this
research was conducted by one of the committee members and published by ASHRAE. Dr. Farhad Memarzadeh,
from the National Institutes of Health, conducted extensive research on patient room, isolation room, and operating
room air distribution. The research used both numerical and experimental techniques. Numerical technique included
computational fluid dynamics and particle tracking model. The performance of the numerical approach was success-
fully verified by comparison with an extensive set of experimental measurements. The patient room findings helped
change the ventilation rates in the Guidelines for Health Care Facilities, published by AIA. The operating room
results will be incorporated in the next edition of the ASHRAE Handbook.
As discussed in the Design Manual, temperature, humidity, and ventilation play important roles in the survival of
airborne microorganisms. Most codes that are applicable to HVAC construction, however, do not currently address
HVAC design criteria relevant to the effectiveness of ventilation, temperature, or humidity in controlling airborne
microorganisms. The problem appears to be less prevalent in North American jurisdictions but is a real and serious
problem in many parts of the world. The intent of this statement is only to point out an existing problem, which must
be corrected through other channels. We hope that the Design Manual will be adopted widely and used as a tool for
education. We also hope that it will start an open dialog with code officials, the Authority Having Jurisdiction (AHJ),
clinicians, and HVAC designers, which will lead to the adoption of reasonable standards.
I want to thank ASHRAE for giving me the opportunity and privilege to contribute in a major way to a definitive
document associated with ones profession. I also wish to thank two individuals in particular: Mark Lentz, past chair
of ASHRAE TC 9.8 (Large Building Air-Conditioning Applications), who took the lead in starting this project and
recruiting me. The other is William Seaton, who, in his position of Manager of Research for ASHRAE, provided us
with all of the needed support. I also want to thank ASHRAE and Michael Vaughn, Manager of Research and Techni-
cal Services, for continued support and confidence.
It has been my privilege to work with a group of highly talented individuals who freely and voluntarily gave their
time and incurred expenses to work on this manual. To all of them, I extend a hearty personal and ASHRAE thank
you. I have included a list of current committee members and other contributors. During the past four years while this
manual was being compiled, several committee members were forced, due to time constraints or health, to relinquish
their involvement in this work. I do not want to minimize their contribution because it was very significant. Those
contributors who were former committee members are so marked.
I thank the SP 91 committee and the many other contributors for their time and hard work.

Respectfully submitted,
Anand K. Seth, P.E.
Chair, SP 91
May 2003

xiii
CHAPTER 1
INTRODUCTION
1.1 PREFACE A fundamental premise of this manual is that a
well-designed HVAC system augments the other fac-
The design of heating, ventilating, and air-con- ets of the built environment to offer a healing envi-
ditioning (HVAC) systems for hospitals, outpatient ronment; minimizes the airborne transmission of
clinics, and other health care facilities is a special- viruses, bacteria, fungal spores, and other bioaero-
ized field of engineering. The higher filtration sols; and minimizes the impact of the building and
requirements for operating rooms and the pressure its processes on the environment. This premise, if
relationships between adjacent spaces are a few of followed, will help to establish a safe environment in
the many design issues that are especially critical to modern health care facilities.
the proper design and functioning of an HVAC sys- This manual was prepared by members of
tem in a health care facility. ASHRAE Special Projects Committee SP-91, under
Health care facilities have special design crite- the sponsorship of ASHRAE Technical Committee
ria. Knowledge of, and insight into, these criteria are (TC) 9.8, Large Building Air-Conditioning Applica-
needed to develop a design that will satisfy the tions, which believed there was a need for a manual
owner and operators of the facility. Knowledge of on this subject. The SP-91 committee began work on
regulatory requirements will minimize compliance this manual in 1997. This interdisciplinary commit-
problems. tee included design engineers, environmental health
There are special considerations for the design specialists, researchers, past and present chairper-
of operating rooms. The HVAC requirements for sons of the ASHRAE Handbook chapter on health
operating rooms include regulating temperature and care facilities, representatives from the revision task
humidity, as well as space pressurization, filtration of force for the American Institute of Architects
the supplied air, allowable recirculation of the air, Guidelines for the Design and Construction of Hos-
and the effectiveness of air delivery system options. pitals and Health Care Facilities, and the American
Society of Hospital Engineers. Contributors also
Health care facilities are environments of con- included members of the American College of Sur-
trolled hazards. Exposure to aerosolized pharmaceu- geons.
ticals, airborne contagions, and strong cleaning Knowledge and experience with basic HVAC
chemicals are examples of these hazards. systems are presumed as prerequisites for users of
Building-related illness, especially associated this manual. We assume that the reader is familiar
with airborne infectious agents, continues to be a with the theory and analysis of HVAC systems and
challenge for health care organizations that treat refrigeration equipment and processes.
infectious patients and those extremely susceptible This manual will refer the reader to other stan-
to environmental microbes such as Legionella and dard HVAC design publications (for example, the
Aspergillus. This manual will help delineate best ASHRAE Handbook series and ASHRAE special
practices for design and maintenance to optimize the publications) for basic HVAC system design infor-
safety of occupants. mation.

1
2 HVAC DESIGN MANUAL FOR HOSPITALS AND CLINICS

1.2 PURPOSE ventilation system that minimizes exposure hazards


The purpose of this manual is to provide a com- for health care providers and provides a comfortable
prehensive source for the design, installation, and working environment. HVAC systems must also pro-
commissioning of HVAC systems for hospitals and vide ventilation that minimizes the hazard exposure
clinics, including: of visitors.
Hospitals, skilled nursing facilities, and outpa-
Environmental comfort, tient surgical centers (ambulatory surgical centers)
Infection control, are the primary types of facilities addressed in this
Energy conservation, book. A more detailed list of targeted facilities is
Life safety, and provided in Chapter 3.
Operation and maintenance. Chapter 2, Terminology, provides defini-
tions for the nomenclature that one needs to under-
This manual is intended to serve as a guide to stand in order to work in this field. Many of these
the selection of HVAC systems for hospitals, clinics, terms are unique to health care facilities. The chapter
and other health care facilities and to fill a gap left by is intended to promote uniformity of usage and con-
current resources related to HVAC design for health sistency in communication relating to the mechani-
care facilities. (These include the AIA Guidelines for cal design of hospitals and the major technical
Design and Construction of Hospitals and Health issues. The terms are consistent with the ASHRAE
Care Facilities, ASHRAE HandbookHVAC Appli- Terminology of HVAC&R.
cations, and ANSI/ASHRAE Standard 62, Ventilation Chapter 3, Facility Descriptions, briefly
for Acceptable Indoor Air Quality [AIA 2001; describes the various types of patient-related health
ASHRAE 1999a, 2001c].) care facilities covered in this manual and the major
This manual is also intended to guide the design units that make up these health care facilities.
of HVAC systems to facilitate the operation and Chapter 4, Overview of Health Care
maintenance of hospitals and health care facilities. HVAC, describes the design approach from plan-
ning and design criteria through commissioning.
1.3 INTENDED AUDIENCE This chapter introduces and summarizes HVAC
The intended audience for this manual includes: design considerations and methodologies that are
particularly significant in designing systems for hos-
Engineers pitals. The design concepts introduced in Chapter 4
are developed fully in other chapters of this manual.
- Experienced hospital designers who will
The topics introduced in Chapter 4 include infection
use it as a reference
control, noninfectious airborne contaminants, air
- Established firms for training personnel in-
quality, outside air ventilation, rates of total air
house
change, room pressure relationships, dry-bulb tem-
Facility managers perature and humidity, filtration, codes, phases of
Infection control personnel design, equipment and system reliability and redun-
Facility maintenance staff dancy considerations, energy conservation, sound
Contractors and vibration, life-cycle costing, value engineering,
Owners quality assurance of engineering design, peer review,
Building officials construction management, and system commission-
Accreditation officials ing.
Licensure officials Chapter 5, HVAC Systems, discusses HVAC
systems and their applications. Hospitals require
Contractors, building officials, and owners can central systems to meet filtration and humidity
use this manual to familiarize themselves with the requirements. Constant volume systems are com-
scope of technical issues and criteria for mechanical mon. Chapters in the ASHRAE HVAC Systems and
systems in medical facilities. Equipment volume should be read in conjunction
with this chapter because a conscious effort was
1.4 OVERVIEW made to not duplicate material from the Handbook
HVAC systems for hospitals and health care except where necessary for continuity.
facilities have special requirements because of the Chapter 6, Design Considerations for Exist-
inherent nature of their functions and the unique sus- ing Facilities, covers unique requirements for
ceptibility of patients. The design must provide a health care facilities including a description of facil-
INTRODUCTION 3

ity condition assessment and infection control during infection control needs can be found in Chapter 3,
construction. Facility Descriptions.
Chapter 7, Cooling Plants, provides a broad Chapter 13, Clinics and Other Health Care
overview of issues of which designers should be Facilities, discusses the requirements for clinics
aware when designing cooling plant equipment and and other health care facilities.
systems for hospital service. It describes the types of Chapter 14, Operation and Maintenance,
systems encountered in hospitals, configuration con- discusses operation and maintenance in hospitals and
siderations, and the need for equipment redundancy clinicswhich is more extensive and critical than in
and dependability. It also covers alternative cooling most other types of occupancies. The maintenance
plant and heat rejection methods and the integration function in health care facilities can be provided in
of thermal storage systems. many different ways; some owners use in-house staff
Chapter 8, Space and Process Heating Sys- for sophisticated and sensitive maintenance services,
tems, provides a broad overview of issues of which whereas other owners perform a minimum of work
designers should be aware when designing heating in house and contract out all other needed services.
plant equipment and systems for hospital service. It All repair work, training, systems changes, and
describes the types of systems encountered in hospi- upgrades provided by the maintenance staff in
tals, configuration considerations, and the need for patient care facilities must be carefully documented.
equipment redundancy and dependability. The chap- This chapter discusses many issues facing facilities
ter also provides a fairly in-depth treatment of the managers and explains how to design for reduced
use of steam for humidification and sterilization, maintenance costs.
including a discussion of corrosion and system treat- Chapter 15, Commissioning, provides guid-
ment chemicals related to system performance and ance on commissioning and testing. Commissioning
human health. and accurate testing are especially crucial for hospi-
Chapter 9, Air-Handling and Distribution tals and clinics to ensure proper operation of HVAC
Systems, discusses design considerations for air- systems, which are typically complex and work in
handling systems and distribution equipment and close concert with the health care services provided.
emphasizes features necessary for proper installa- Chapter 16, Energy Efficient Design and
tion, operation, maintainability, noise control, and Conservation of Resources. Hospitals consume
minimization of microbial contamination. large quantities of energy. Energy-conscious HVAC
Chapter 10, Controls and Instrumentation, systems can make a dramatic difference in the ongo-
provides a background on controls and describes ing cost of facility operation. Health care facilities
specific issues unique to hospitals and clinics. also consume large amounts of other resources
Chapter 11, Smoke Control and Life such as water and consumable materialsand pro-
Safety, describes the delicate yet demanding rela- duce large volumes of waste, much of which requires
tionship of HVAC systems to engineered smoke special removal and storage techniques. This section
provides an overview of the principles and
evacuation units, smoke management systems, and
approaches for achieving energy-efficient operation
passive management of smoke. Also covered are the
and the effective use of resources to reduce operating
special design requirements for managing the move-
costs, conserve valuable resources, and reduce the
ment of smoke in health care facilities to permit con-
environmental impact of the building (including
tinuous occupancy of these buildings.
reducing harmful emissions and controlling wastes).
Chapter 12, Room Design, provides infor-
Information is included to guide building owners and
mation regarding individual rooms in hospitals. This
operators and their designers toward HVAC design
chapter describes ventilation designs for various solutions that embody energy-efficient principles
spaces in hospitals that have been used in practice to and achieve occupancy comfort, safety, and well-
restrict air movement between spaces, dilute and being.
remove airborne microorganisms and odors, and
maintain required temperature and humidity levels. Appendices
Information includes diffuser types, layout sugges-
tions, typical loads, airflow rates, and typical system A. Managing Construction and Renovation to
applications for environmental control, infection Reduce Risk in Health Care Facilities
control, and process cooling.
Information regarding the physical sizes and This appendix describes management of con-
shapes of the rooms, the typical processes they hold, struction risk to patients, health care workers, and
potential equipment, people, lighting, and specific visitors due to almost continuous construction and
4 HVAC DESIGN MANUAL FOR HOSPITALS AND CLINICS

renovation activities as health care organizations F. Ventilation Standards and Current Trends
upgrade utilities, communications, and diagnostic/
therapeutic equipment. There is currently a range of design solutions to
the ventilation of hospitals and clinics and differing
B. Disaster Management air change rates proposed by authoritative sources
such as the AIA Guidelines and ASHRAE Hand-
Appendix B addresses the concerns of hospitals
book (AIA 2001; ASHRAE 1999a). European
when subjected to either internal or external disasters
design guidance shows further differences. This
that might affect the institutions mechanical systems
appendix comments upon and compares these differ-
to the point of disrupting services. Disasters such as
ences and includes a table that summarizes best
an earthquake, train wreck, chemical spill, bioterror-
practices ventilation rates and temperature and
ism, or infectious epidemic present an added set of
humidity requirements for each functional area. The
considerations, primarily the designation of emer-
appendix provides historical background on ventila-
gency spaces for serving larger than usual numbers
tion systems for comfort and quality of the environ-
of victims. Provision of care can be greatly aided if
ment. It also gives insight into ongoing research into
spaces such as lobbies and meeting rooms have
ventilation rates and air distribution that may result
mechanical capabilities already in place that allow
in changes in the future.
them to function as emergency treatment areas.

C. Load Calculations and Equipment Heat Gains G. Power Quality Issues

This appendix is not intended to duplicate any of Appendix G provides an overview of guidelines
the chapters in the ASHRAE HandbookFundamen- for selecting areas and systems that should be served
tals on air-conditioning load calculations but rather from an emergency power source. It also describes
to highlight the specific aspects of cooling and heat- the hospital as a critical facility that must continue to
ing load calculations for health care facilities. operate during utility power outages. The main elec-
trical service to the hospital building should be as
D. Infection Control Issues reliable as possible.

This appendix describes the infection control H. Sample Control Strategies


issues in health care facilities, which are the only
places where nosocomial infections can be acquired.
This appendix includes guidelines that describe
Patients who have the worst infections wind up at a
different strategies that could be used in the opera-
hospital. The appendix contains a paper entitled
tion of 100% outside air-handling units with two
Airborne Respiratory Diseases and Mechanical
supply fans, a common exhaust fan, and a hot water
Systems for Control of Microbes, published by
run-around loop heat recovery system.
HPAC (Kowalski and Bahnfleth 1998).

E. Life-Cycle Cost Analysis I. Operating Room Air Distribution

Life-cycle cost analysis (LCCA) is a method of This appendix contains a paper entitled Com-
evaluating the economic value of design alternatives parison of Operating Room Ventilation Systems in
on a life-in-use basis, taking account of manufacture, the Protection of the Surgical Site, published by
supply, delivery to site, energy consumption, mainte- ASHRAE (Memarzadeh and Manning 2002). The
nance, and final disposal. This appendix shows how paper compares the risk of contaminant deposition
LCCA can provide a best value approach to HVAC on an operating room (OR) surgical site and back
design. table for different ventilation systems.
CHAPTER 2
TERMINOLOGY
2.1 INTRODUCTION Background: Example spaces include offices,
Today, technical issues once primarily of inter- mechanical and electrical spaces, workshops,
est to ASHRAE members impact interdisciplinary restrooms, kitchens, restaurants, cafeterias, gift
applications outside the HVAC&R industry. This shops, lobbies, waiting rooms, and janitors closets.
chapter on terminology is intended to promote uni-
form usage of terms and consistency in communica- air-cleaning system a device or combination of
tions relating to mechanical design of hospitals and devices used to reduce the concentration of airborne
health care facilities and the major technical issues. contaminants, such as microorganisms, dusts, fumes,
Some terms that are widely accepted in general respirable particles, other particulate matter, gases
HVAC&R usage have different meanings in the med- and/or vapors in air.2
ical and health care fields. Background: Some examples of air-cleaning
devices are filters in air-handling units or ducts and
2.2 TERMS fixed or freestanding portable devices that remove
airborne contaminants by recirculating air (through a
age of air the time that has elapsed after the air HEPA filter).
enters a space (at any given point).
Related term: HEPA filter.
Background: The air entering any part of the
room is a mixture of recirculated and fresh air. The
air-conditioning process in enclosed spaces, a
freshness of the air and its dilution capability at a
combined treatment of the air to control (as speci-
particular point are characterized by its age.
fied) temperature, relative humidity, velocity of
air change rate airflow in volume units per hour motion, and radiant heat energy level, including con-
divided by the building space volume in identical sideration of the need to remove airborne particles
volume units (normally expressed in air changes per and contaminant gases. Some partial air condition-
hour [ACH or ACPH]).1 ers, which may not accomplish all of these controls,
are sometimes selected for their capability to control
Background: Mean air change rate for a speci-
specific phases of air treatment.3
fied period can be measured using ASTM E 741-83,
Test Method for Determining Air Leakage Rate by
Tracer Dilution. air-conditioning system assembly of equipment
for air treatment to control simultaneously its tem-
air-conditioning general building supply supply perature, humidity, cleanliness, and distribution to
air from an air-conditioning system whose service meet the requirements of a conditioned space.4
area includes exclusively spaces that are not unique
to health care settings. 2. ASHRAE. 2001. ANSI/ASHRAE Standard 62-2001,
Ventilation for Acceptable Indoor Air Quality.
Atlanta: American Society of Heating, Refrigerating
1. ASHRAE. 1991. Terminology of HVAC&R. Atlanta: and Air-Conditioning Engineers, Inc.
American Society of Heating, Refrigerating and Air- 3. ASHRAE Terminology.
Conditioning Engineers, Inc. 4. Ibid.

5
6 HVAC DESIGN MANUAL FOR HOSPITALS AND CLINICS

air irritant a particle or volatile chemical in air Background: Airborne droplet nucleiviable or
that causes a physiological response when in contact nonviableare caused by the evaporation of mois-
with mucosa in the eye, nose, or throat. ture in which a particle is embedded. Generally such
a residual particle is smaller than 5 m after evapora-
air volume migration the volume of air that is tion of an original particle up to 150 m in diameter.
exchanged during room entry/exit (through a door- Some of these particles can be infectious, depending
way between a room and the area beyond its door).5 on the origin of the droplet.
Related term: airborne infectious agent.
air, exhaust air removed from a space and dis-
charged outside the building by mechanical or natu- airborne infection isolation room a room
ral ventilation systems.6 designed with negative pressurization to protect
patients and people outside the room from the spread
air, makeup any combination of outdoor and of microorganisms (transmitted by airborne droplet
transfer air intended to replace exhaust air and exfil- nuclei) that infect the patient inside the room.
tration.7 Background: Common airborne infectious
agents include measles, tuberculosis, and chicken
air, outdoor (1) air outside a building or taken pox. Patients who have suspected or diagnosed air-
from the outdoors and not previously circulated borne infections are placed in specially ventilated
through the system;8 (2) ambient air that enters a rooms to help contain patient-released infectious
building through a ventilation system, through inten- particles.
tional openings for natural ventilation, or by infiltra- Related terms: airborne droplet nuclei; pressur-
tion.9 ization.
Related term: ventilation effectiveness.
airborne infectious agent an airborne particle that
air, recirculated air removed from a space and can cause an infection.
reused as supply air.10 Background: Airborne transmission occurs by
dissemination of either airborne droplet nuclei or
air, supply air delivered by mechanical or natural dust particles that contain the infectious agent.
ventilation to a space that is composed of any combi- Microorganisms carried in this manner can be dis-
nation of outdoor air, recirculated air, or transfer persed widely by air currents and may become
air.11 inhaled by a susceptible host within the same room
or at a distance from the source patient, depending
on environmental factors. Special air handling and
air, transfer air moved from one indoor space to
ventilation are required to prevent airborne infec-
another.12
tious agent transmission.15
airborne droplet nuclei small-particle residue (5 Related term: airborne droplet nuclei.
m or smaller) of evaporated droplets containing
microorganisms that remain suspended in air and can airborne pathogen an airborne particle that can
be dispersed widely by air currents within a room or cause disease.
over a long distance.13,14 Background: Airborne pathogens are infectious
organisms or chemicals that can produce disease in a
5. Hayden, C.S., et al. 1998. Air volume migration from susceptible host. This term may also apply to any
negative pressure isolation rooms during entry/exit. microscopic agent that is a respiratory irritant and
Applied Occupational and Environmental Hygiene includes allergens and toxigenic fungi. Viruses, bac-
13(7): 518-527. Ohio.
6. ASHRAE. 2001. ANSI/ASHRAE Standard 62-2001, teria, fungi, and asbestos are examples of respiratory
Ventilation for Acceptable Indoor Air Quality. pathogens. The fungi and some bacteria, most nota-
Atlanta: American Society of Heating, Refrigerating bly actinomycetes, form spores. Spores can become
and Air-Conditioning Engineers, Inc.
7. Ibid. airborne and are resistant to factors that destroy
8. Ibid. viruses and bacteria. Spores are the most important
9. Ibid. cause of noncommunicable diseases.
10. Ibid.
11. Ibid.
12. Ibid. 14. Garner, J.S. 1996. Guideline for isolation precautions
13. AIA. 2001. Guidelines for Design and Construction in hospitals. Infection Control & Hospital Epidemiol-
of Hospital and Health Care Facilities. Washington, ogy 17(1):53-80.
D.C.: American Institute of Architects. 15. Ibid.
TERMINOLOGY 7

anteroom a room separating an isolation room something should happen during the labor phase, the
from a corridor. patient is transferred to a true delivery room.
Background: An isolation room setting is for Related term: delivery room.
patients who are both infectious and immunosup-
pressed. The anteroom would have ventilation con- building air infiltration uncontrolled inward leak-
trol to minimize the effects of airborne spread of age of air (that may contain entrained water vapor)
disease by manipulating door closure and ventilation through cracks and interstices in any building ele-
while protecting the patient from common airborne ment and around windows and doors of a building,
disease. Sometimes these rooms are used for gown- caused by the pressure effects of wind or the effect of
ing, washing hands, and transfer of meal trays. differences in the indoor and outdoor air density.18
Related terms: airborne infection isolation Background: This air may contain airborne con-
room; immunocompromised infectious host. taminants.
Related terms: exfiltration, infiltration, sealed
aspergillosis a fungal disease that may be present room.
with a variety of clinical symptoms; produced by
several of the Aspergillus species. CT scan (computed tomographic scan) Visualizes
Background: Individuals who are immunosup- a (body) cross-sectional single plane by computer
pressed or immunocompromised are most at risk for analysis of multidirectional X rays.
aspergillosis. A. fumigatus and A. flavus are the most Background: Tomography is a procedure, usu-
common causes of aspergillosis in human beings. ally X ray, that focuses on a single plane of an item
Related term: airborne pathogen. rather than its full thickness.

asepsis a condition of being free from microbes; community acquired infection an infection
free from infection, sterile, free from any form of present or incubating in a patient upon admission to
life.16 a hospital.
Background: From the same root: sepsis, an Related terms: nosocomial infection; occupa-
infected condition, and antisepsis, action to elimi- tionally acquired infection.
nate microbes and infection.
clean steam steam for humidification and/or steril-
bioaerosol particles or droplets suspended in air ization that is generated in a system without chemi-
that consist of or contain biological matter such as cal additives.
bacteria, pollens, fungi, skin flakes, and viruses. Related term: steam autoclave.
Background: Bioaerosols include microorgan-
contaminant (also sometimes pollutant) any
isms (culturable, nonculturable, and dead microor-
impurity, any material of an extraneous nature, asso-
ganisms) and fragments, toxins, and particulate
ciated with a chemical, a pharmaceutical prepara-
waste products from all varieties of living things.
tion, a physiologic principle, or an infectious
Bioaerosols are ubiquitous in nature and may be
agent.19
modified by human activities. All persons are repeat-
Related terms: airborne infectious agent; air-
edly exposed, day after day, to a wide variety of such
borne pathogen; local ventilation exhaust; pollutant;
materials. Individual bioaerosols range in size from
pollution; ventilation efficiency.
submicroscopic particles (<0.01 m) to particles
larger than 100 m in diameter.17 contaminant, airborne an unwanted airborne
constituent that may reduce the acceptability of air.20
birthing rooms (also LDR, LDRP) birthing
Related terms: airborne infectious agent; air-
rooms in todays hospital are a specialized version of
borne pathogen; local ventilation exhaust; pollutant;
a single-patient room.
pollution; ventilation efficiency.
Background: These areas are also called LDRs
(labor/delivery/recovery). If the patient stays in the contamination the act of contaminating, espe-
same room until discharge, the space is identified as cially the introduction of disease germs or infectious
an LDRP (labor/delivery/recovery/postpartum). material into or on normally sterile objects.
These areas are for normal, uncomplicated births. If
18. ASHRAE Terminology.
16. Tabers Cyclopedic Medical Dictionary (12th ed.). 19. Stedmans Medical Dictionary (27th ed.). 2000. Balti-
Philadelphia: F.A. Davis Company. more: Williams & Wilkins.
17. ACGIH. 2001. 20. ANSI/ASHRAE Standard 62-2001.
8 HVAC DESIGN MANUAL FOR HOSPITALS AND CLINICS

Background: Contamination is the second step Background: Irrigating fluid is conducted via
of the disease process relationship, the sheath (of the instrument) into the bladder. The
[Infection] [Dose] [virulence] [time/level cystoscopic procedure can be performed in an Oper-
of host defenses]. ating Room, Cystoscopy Room, or at the patients
Concentration of contaminants (in the air) leads bed.
to contamination of living tissue, which leads to col-
onization, which leads to infection, which leads to delivery room a room identical to a general oper-
disease.21 ating room.
Related terms: airborne infectious agent; con- Background: Delivery rooms are now used pri-
taminant; pollutant. marily for C-sections, breech births, or other compli-
cated deliveries.
control (HVAC&R) (1) a device for regulating a Related terms: birthing room; operating room.
system or component in normal operation, manually
or automatically; (2) broadly, methods and means of design conditions the values of ventilation, tem-
governing the performance of any apparatus, perature, and humidity within which a system is
machine, or system.22 designed to operate to provide conditioned air. Filter-
Background: If automatic, the implication is ing levels also may be required.
that the control is responsive to changes in pressure,
temperature, or another variable whose magnitude is diagnosis activities, including history taking,
being regulated. physical examination, and laboratory evaluation, that
determine the nature of a patients illness and its ori-
control (industrial hygiene) method(s) to isolate gin.
or remove hazards from the workplace. Related terms: diagnostic clinic; treatment.
Background: In removing contaminants and/or
pollutants, the industrial hygiene term control is diagnostic clinic a diagnostic clinic is a facility
used to describe methods that can be employed, for where patients are regularly seen on an ambulatory
example, to isolate or remove pathogen hazards from basis for diagnostic services or minor treatment but
the workplace. Three strategies of control are cus- where major treatment requiring general anesthesia
tomarily used alone or in combination: or surgery is not performed.
1. Administrative controls (example: schedules to
dialysis an external method of adjusting the levels
minimize risk).
of ions and chemicals in the blood (a process nor-
2. Engineering controls (example: ventilation mally performed by the kidneys).
design).
Background: During dialysis, the patients blood
3. Personal protective equipment (example: face is diverted to the dialysis equipment, osmotically fil-
masks for workers). tered, and then returned to the patient.
control (medical) method to eradicate or amelio- dedicated equipment connection (utilities) water,
rate a disease process (treatment and/or public health waste, steam, medical gases, chilled water, and elec-
measures). tricity.
Background: Some medical and hospital equip-
corridor (1) walkway interior within a building;
ment (such as radiation therapy) requires a dedicated
(2) public corridor: corridor not intended for use by
(not shared with other loads) supply main utility con-
in-house patients; (3) patient corridor: corridor to
nection, separate from utilities supplied to the gen-
patient rooms that would be used by patients.
eral area.
critical HVAC equipment equipment essential for Related term: equipment, medical.
HVAC operation that is connected to the emergency
power system. endoscopy a general term meaning the visualiza-
tion of body cavities and structures through an
cystoscopy examination of the bladder by an inserted optical instrument.
instrument (cystoscope) inserted via the urethra.
endoscopy area an environment for endoscopy.
21. Tabers Cyclopedic Medical Dictionary (12th ed.). Background: Some specific endoscopic proce-
22. ASHRAE Terminology. dures require anesthesia and are performed in an
TERMINOLOGY 9

operating room or an endoscopy room equipped for lates larger than 0.30 microns. See Chapter 4, Sec-
anesthesia tion 4.3.2, High Efficiency Filtration.
Related term: air cleaning system.
epidemiology study of the distribution and deter-
minants of disease. hospital (institution) an institution for treating the
Background: Not limited to infectious diseases; sick, suitably located, constructed, organized, man-
includes all human illnesses, for example, cancer and aged, and staffed to provide scientifically, economi-
metabolic diseases. cally, efficiently, and unhindered, all or any
recognized part of the complex diagnostics and treat-
equipment, medical equipment specific to a medi- ment modalities for physical and mental illnesses
cal procedure or activity. (adapted from Dorlands Illustrated Medical Dictio-
Background: Examples are specialized equip- nary25).
ment in departments such as Diagnostic Radiology, Background: A hospital is a 24-hour facility,
Therapeutic Radiology, Clinical Laboratory, Phar- equipped to perform critical and emergency surgical
macy, Administration, Central Sterile Processing, procedures and has all of the necessary support labo-
Surgery, Emergency, and Laser Surgery. ratories and services within the building to accom-
plish this, including in-bed patient care.
(emergency) exam rooms exam rooms (or treat- Related term: treatment clinic.
ment rooms) are spaces used for emergency treat-
ment of broken bones, lacerations, foreign objects, immunocompromised host (sometimes immuno-
concussions, etc. suppressed host) an individual whose immune sys-
Background: Exam rooms provide services to tem has been weakened by disease (such as AIDS) or
treat the injury or illness and then to discharge the medical treatment (such as chemotherapy).
patient, or to stabilize the patient for further observa-
tion or treatment as a hospitalized patient. immunocompromised infectious host a patient
Related term: treatment room. who is both an immunocompromised host and a
potential transmitter of infection.
exhaust air see air, exhaust. Related terms: airborne infection isolation
rooms; anteroom.
exfiltration air leakage outward through cracks
and interstices and through ceilings, floors, and walls indoor air quality the composition and character-
of a space or building.23 istics of the air in an enclosed space that affect the
Related terms: building air infiltration; infiltra- occupants of that space.26
tion; sealed room. Background: The indoor air quality of a space is
determined by the level of indoor air pollution and
filter see air cleaning system. other characteristics of the air, including those that
impact thermal comfort, such as air temperature, rel-
freestanding emergency clinic an emergency ative humidity, and air speed. Indoor air quality is of
facility that is separated from a hospital. considerable interest and relevance in health care
Background: A freestanding emergency clinic; occupancies. Indoor air quality in health care settings
includes provisions for temporary observation of must incorporate considerations for infectious and
patients until release or transfer. This type of unit other airborne contaminants.
requires special transportation planning to accom- The HVAC or ventilation system should
modate the transfer of patients.
1. provide outdoor air ventilation to provide dilution
ventilation,
hematology the study of blood and blood forming
tissues and the disorders associated with them. 2. reduce airborne particulates in the recirculated
portion of the ventilation air via filtration and have fil-
HEPA filter (absolute filter) high efficiency par- tration capabilities suitable for the contaminants of
ticulate air filter.24 concern,
Background: HEPA filter is filtration with
removal efficiencies of 99.97% or higher of particu- 25. Dorlands Illustrated Medical Dictionary (29th ed.).
2000. Philadelphia: W.B. Saunders Co.
26. ASTM. 2000. D1356-00a: Standard Terminology
23. ANSI/ASHRAE Standard 62-2001. Relating to Sampling and Analysis of Atmospheres.
24. ASHRAE Terminology. West Conshohocken, Pa.: ASTM International.
10 HVAC DESIGN MANUAL FOR HOSPITALS AND CLINICS

3. provide special airflows such as for operating makeup air see air, makeup.
rooms.
Related terms: contaminant; pollutant; pollu- medical gas oxygen, nitrogen, nitrous oxide, vac-
tion; ventilation effectiveness; ventilation efficiency. uum and medical compressed air, and vacuum and
anesthetic gas are typical medical gases used
industrial hygiene the science and art devoted to throughout hospitals.
anticipating, recognizing, evaluating, and controlling
those environmental factors or stresses that arise in minor operating room for the purpose of this
or from the workplace and may cause sickness, manual, a Class A Operating Room as defined by the
impaired health and well-being, or significant dis- American College of Surgeons.30
comfort and inefficiency among workers or among Related term: operating room.
the citizens of the community.27
Related term: control (industrial hygiene). minor surgery the classical surgical definition of
minor surgery is an operation in which a body cavity
infiltration air leakage inward through cracks and is not entered or in which a permanent device is not
interstices and through ceilings, floors, and walls of inserted by incision.
a space of a building.28
Related term: building air infiltration MRI (magnetic resonance imaging) body imag-
ing by measuring changes in energy resonance in a
intensive care rooms rooms in which the level of large magnetic field.
patient care and electronic monitoring of patients are Background: Located within an MRI room are
greatly increased over conventional patient rooms. the magnet, the housing, and the patient table. For
Background: ICU spaces today are specialized. specific space, utility, and power requirements, see
Common uses are as follows: Surgical Intensive Care Chapter 12, Section 12.3.7.
Unit (SICU), Medical Intensive Care Unit (MICU),
Cardiac Care Unit (CCU), and Post-Anesthesia Care mycosis any disease caused by fungi.
Unit (PACU).
nosocomial infection (hospital-acquired
invasive procedure for the purpose of this manual, infection) an infection that is acquired in a hospital
insertion of an instrument or device into the body and that was not present or incubating upon admission.
through the skin or body orifice for diagnosis or Also known as hospital-acquired infection.
treatment. Related terms: community acquired infection;
Related term: procedure. occupationally acquired infection.

laboratory a location equipped to perform tests nursing 24-hour-care units, acute medical/surgical
and experiments and to investigative procedures and patients units of patient care rooms that contain the
for preparing reagents, therapeutic chemicals, and majority of patient beds in todays health care facil-
radiation.29 ity.
Background: Major laboratories include Chem- Background: Rooms are limited to two patient
istry, Hematology, Microbiology, and Tissue (Pathol- beds (called semiprivate rooms); however, the cur-
ogy). There are many specialty (sub) laboratories rent trend is for these rooms to have only one bed
that are suited to particular procedures. See Chapter (called private rooms). A patient room must have a
3, Section 3.3.6. toilet directly accessible from within the room. In
most states, a patient room must have a hand wash-
local exhaust (local ventilation exhaust) local ing facility within the room proper. In semiprivate
exhausts operate on the principle of capturing an air- rooms, a cubicle curtain provides privacy between
borne contaminant or heat at or near the source. beds. All rooms must be provided with an outside
Related terms: Control (industrial hygiene); window, and, in many states, this window needs to
ventilation efficiency. be operable by a tool or key. The latest fire codes are
permitting patient room windows fixed in place,
27. NSC. 1988. Fundamentals of Industrial Hygiene.
Chicago: National Safety Council. 30. American College of Surgeons. 1976. Definition of
28. ANSI/ASHRAE Standard 62-2001. surgical microbiologic clean air. Bulletin of American
29. Stedmans Medical Dictionary (27th ed.). College of Surgeons 61:19-21.
TERMINOLOGY 11

eliminating the need for operable sashes. A standard multiple personnel, recovery room access, and a
patient unit consists of approximately 30 beds. fully controlled environment.32
Related terms: invasive procedure; procedure;
nursing 24-hour-care units, critical patients minor operating room.
(ICUs) critical care nursing units housing seri-
ously ill patients receiving the maximum of care. operating rooms, cardiac transplant operating
Background: This patient care unit is the best rooms an operating room for open heart bypass
the hospital has to offer in terms of personnel and surgery and heart transplant surgery.
technology. Critical care nursing units require spe- Background: These are similar to general oper-
cial space and equipment considerations. Not all hos- ating rooms but normally require larger room space.
pitals provide all types of critical care. Some may
have a small combined unit; others may have sepa- operating rooms, neurosurgery an operating
rate, highly specialized units. Following are exam- room for brain and/or spinal surgery.
ples of specialized critical care units: Neurological Background: This room typically has ceiling-
Intensive, Burn/Wound Intensive, Cardiopulmonary, mounted microscope equipment and viewing equip-
Surgical Intensive, Medical Intensive, Step-Down, ment. These fixture requirements (location) should
Geriatric Intensive, Pediatric Intensive, Neonatal not conflict with good air distribution practices.
Intensive, Coronary.
Related term: step-down units. opportunistic microorganism an ordinarily non-
infectious agent that becomes infectious in an immu-
nursing 24-hour-care, specialty care patients nocompromised host.
whether a freestanding specialty hospital or a unit Related term: immunocompromised host.
within a hospital, specialty care units are nursing
units that have a specific clinical function. outdoor air see air, outdoor.
Background: Most of these units are similar to a
standard nursing unit, but special design consider- outpatient surgical facility a facility for surgery
ations are required for the specific patient population (may include outpatient dental surgery) where over-
receiving treatment. For example, in a geriatric nurs- night patient care is not anticipated.
ing unit, lighting levels may need to be increased, Background: The functional program for an out-
physical barriers removed and spaces enlarged to patient surgical facility describes in detail the staff-
permit additional wheelchair use, additional hand- ing, patient types, hours of operation, function and
rails installed to assist in mobility, and ventilation space relationships, transfer provisions, and avail-
rates increased to remove odors. Following is a par- ability of offsite services. If the outpatient surgical
tial list of specialty units: Rehabilitation, Geriatric, facility is part of an acute care hospital or other med-
Dementia, Subacute Care Hospice, AIDs Units, Psy- ical facility, services may be shared to minimize spe-
chiatric, and Detoxification. cial requirements.

occupiable space an enclosed space intended for patient care units patient care units are those
human activities, excluding those spaces intended areas of health care facilities where 24-hour around-
primarily for other purposes (such as storage rooms the-clock nursing care is provided to patients.
and equipment rooms that are occupied occasionally Background: There are three typical categories
for short periods of time).31 of patient care units (see related terms). Each of
these categories has unique care delivery strategies
occupationally acquired infection an infection and consists of the patient care room or area and all
acquired while working in a medical care setting. of the necessary administrative and clinical support
Related terms: community acquired infection; space to serve the specialized needs of the patient
nosocomial infection. population.
Related terms: nursing 24-hour care units, acute
operating room a room specifically designed for medical/surgical; nursing 24-hour care units, criti-
surgical procedures. In common understanding, this cal nursing care; and nursing 24-hour care units,
means most types of surgical procedures, especially specialty nursing care.
those that involve the administration of anesthesia,
32. AIA Guidelines for Design and Construction of Hos-
31. ANSI/ASHRAE Standard 62-2001. pital and Health Care Facilities.
12 HVAC DESIGN MANUAL FOR HOSPITALS AND CLINICS

patient rooms patient rooms are normally semipri- tor is required) positively or negatively pressured
vate (two patients) or private (for individual (determined by the design). AIA Guideline 2001
patients). requires (in certain rooms) an RDP of 0.01 in. w.g. (2.5
Background: Each patient room is provided with Pa).
a private toilet/shower. Patient care is provided for Related terms: airborne infection isolation
recuperation from a procedure, patient observation, room, building air infiltration; exfiltration; infiltra-
and diagnosis. Rooms are normally contained within tion; protective environment room; sealed room.
a department and supervised by an individual or by
multiple nursing stations. A medicine preparation/ procedure treatment of a patient.
dispensing area, clean and soiled linen and holding Background: There are many diagnostic and
areas, housekeeping support, and staff facilities com- treatment procedures. Invasive and minimally inva-
plement each department. sive procedures are performed in operating rooms.
Related terms: invasive procedure; operating
pneumonia inflammation of lung tissue. room; treatment.
Background: The cause of pneumonia is gener-
ally bacterial or viral, but on occasion pneumonia protective environment rooms a patient care set-
may be caused by an opportunistic airborne fungi ting that requires positive pressurization to protect
(especially in immunocompromised hosts). There the patient from human and environmental airborne
are also noninfectious causes such as chemical or diseases.
radiation exposure. Background: This protection is needed for
patients who are immunocompromised either from
pollutant an undesired contaminant that results in treatment or from disease.
pollution. Related terms: airborne infection isolation
Background: A pollutant may or may not be an room; pressurization.
infectious agent.
Related terms: contaminant; pollution. process cooling the use of chilled water in health
care settings that is not seasonal but related to a pro-
pollution rendered unclean or unsuitable by con- cess.
tact or mixture with an undesired contaminant.33 Background: Examples of process cooling
Related terms: contaminant; pollutant. include modular cooling units (MCU), linear accel-
erators, magnetic resonance imaging, PET (Positron
pressurization a difference in pressure between a Emission Tomographic) scanners, data centers, and
space and a reference pressure. refrigeration condensers.
Background: Pressurization is important for
infection control. Positive pressurization produces a radiology the scientific (medical in this case) dis-
net flow of room air out of a space toward the refer- cipline of dealing with X rays and other forms of
ence space through any opening between the two radiant energy for imaging and treating internal body
spaces. Negative pressurization produces a net flow structures.
of air into a space from the reference space through
any opening between the two spaces. radiology rooms areas for patient X rays, conven-
tional and digital, and image processing.
1. Volumetric flow rate (VFR) criteria. This differ-
Background: These rooms are normally heavily
ence in pressure between the room and the adjacent
used, and the electronic equipment produces a vary-
architectural space(s) is accomplished under most
ing amount of heat in the space.
codes by providing differentials in volumetric flow
rates (VFR) of supply, return, and exhaust air and
recirculated air see air, recirculated.
door(s) closure.
2. Room differential pressure (RDP) criteria. Most room air distribution effectiveness a measure of
hospital rooms can be designed using only VFR crite- how effectively the ventilation system provides sup-
ria for pressurization. For areas of high-risk assess- ply air to the room to maintain acceptable air quality
ment, RDP criteria (where used) require a sealed room in the occupied zone.
(with significant differentials) for pressurization (see Related term: ventilation effectiveness.
Appendix A.5.2) so that the room remains (an indica-
sealed room a room that has minimal leakage--to
33. Stedmans Medical Dictionary (27th ed.). prevent air from being pulled through cracks around
TERMINOLOGY 13

windows, utility connections, ceilings, or other wall thermal surgical plume a convection current (of
penetrations. air) rising from the wound site due to the body heat
Related terms: building air infiltration; exfiltra- of the patient, operating room personnel, and radiant
tion; infiltration. heat from the surgical light.36
skilled nursing facility a facility that houses per- transfer air see air, transfer.
sons who need intermittent nursing services.
trauma room trauma rooms are areas that are used
skin squame a small flake of epidermal skin tis-
sue. to care for patients whose injuries or illnesses are
Background: Skin flakes carry bacteria and are more severe than can be adequately treated in con-
of concern in the sterile field of an operating room. ventional exam rooms.
Related terms: operating room; sterile field. Background: Trauma rooms are also frequently
referred to as crisis rooms or shock rooms. The
steam autoclave a sealed vessel that can hold main purpose of the trauma room is to stabilize a
items in an environment of pressurized (15 pounds seriously injured patient for additional treatment,
per square inch [103 kPa]) steam at 250F (121C) usually in an operating room.
for an extended period of time (20 minutes or more)
to kill all microorganisms, including bacterial
treatment activities taken to eradicate or amelio-
spores.34
rate a patients disease.
step-down units a group of beds used for transi- Related terms: procedure; treatment clinic.
tion from the Critical Care Unit to the Nursing Unit.
Related term: nursing 24-hour units, critical treatment clinic a facility totally detached from a
patients. hospital that serves patients, as outpatients, without
provision for overnight stays.
sterile condition of being free from all living Background: The facility has its own dedicated
microorganisms and their spores.35 HVAC systems. A treatment clinic is a facility that
provides, on an outpatient basis, major or minor
sterile field a designated sterile surface in and treatment for patients that would render them incapa-
around an invasive procedure site. The following are ble of taking action for self-preservation under emer-
considered boundaries of the sterile field in surgery: gency conditions without assistance from others.37
1. The surface of the sterile drapes down to the level (see NFPA Standard 99 1999). This facility is a new
of the operating room table. The arms and gloves are and emerging form of outpatient center that can pro-
considered to be in the sterile field. vide a wide array of outpatient diagnostic services
2. The fronts of the gowns of the operating personnel and minimally invasive procedures.
from the neck lines to the level of the table. Related term: hospital.
3. Equipment that is properly draped, such as the
Mayo stand and the horizontal surfaces of the back treatment rooms treatment rooms is a general
table(s). category for rooms where medical procedures are
performed.
4. Portions of properly draped equipment, such as
Background: Procedures include bronchoscopy,
properly draped microscopes and X-ray machines.
cryosurgery, etc.
5. The light handles but not the lights.
6. The anesthesia screen from the level of the table triage the act of determining the severity of illness/
up to the top of the screen. injury of patients so that those who have the most
emergent illnesses/injuries can be treated immedi-
Related term: operating room.

supply air see air, supply. 36. Woods, J.E., D.T. Braymen, R.W. Rasmussen, P.E.
Reynolds, and G.M. Montag. 1986. Ventilation
requirements in hospital operating roomsPart I:
swing beds a group of beds used for different nurs- Control of airborne particles. ASHRAE Transactions
ing purposes, depending on current needs. 92(2A):396-426. Atlanta: American Society of Heat-
ing, Refrigerating and Air-Conditioning Engineers,
Inc.
34. McGraw-Hill Encyclopedia of Science and Technol- 37. NFPA. 1999. Standard 99: Health Care Facilities
ogy. 1997. New York: McGraw Hill. Standard. Quincy, Mass.: National Fire Protection
35. Tabers Cyclopedic Medical Dictionary (12th ed.). Association.
14 HVAC DESIGN MANUAL FOR HOSPITALS AND CLINICS

ately and those less severely injured can be treated windows, or other intentional openings in the build-
later or in another area (see Appendix B.4.1). ing.40
Background: The fundamental functions of ven-
UV ultraviolet irradiation. tilation may also incorporate smoke control require-
Background: Ultraviolet radiation is that portion ments or removal of contaminants from known
of the electromagnetic spectrum described by wave- specific sources in a space.
lengths from 100 to 400 nm. Related term: pressurization.
Related term: UVGI.
ventilation effectiveness (E) the ability of a ven-
UVGI ultraviolet germicidal irradiation. tilation system to deliver air to the breathing (or
Background: Ultraviolet germicidal irradiation occupied) zone of a space or the workspace in such a
is that portion of the electromagnetic spectrum zone.
described by wavelengths from 200 to 270 nm. Related terms: air, outdoor; room air distribu-
Ultraviolet germicidal irradiation is a use of UV tion effectiveness.
radiation to kill or inactivate microorganisms. UVGI
lamps can be used in ceiling or wall fixtures or ventilation efficiency the ability of a system to
within air ducts of ventilation systems.38 remove contaminants generated by a source in a
Related term: UV. room.
Related term: local exhaust.
ventilation rate see air change rate.
waiting room(s) in patient areas, these are spaces
ventilation a process of supplying air to or remov- where nonpatients (i.e., family members) wait. In
ing air from a space for the purpose of controlling air clinics and in emergency departments, these are
contaminant levels, humidity, or temperature within spaces where patients who are seeking diagnosis and
the space.39 Such air may not have been conditioned. treatment wait.
Mechanical ventilation is ventilation provided Background: There may be a requirement to iso-
by mechanically powered equipment such as motor- late airborne infectious disease patients and/or
driven fans and blowers, not by devices such as receive a contaminated individual exposed to hazard-
wind-driven turbine ventilators and mechanically ous materials.
operated windows.
Natural ventilation is ventilation provided by waste anesthetic gas anesthetic gases that have
thermal, wind, or diffusion effects through doors, been delivered to the patient and are exhaled or are in
excess of the amount consumed by the patient.
38. CDC. 1994. Guidelines for preventing the transmis-
sion of mycobacterium tuberculosis in healthcare water activity water activity is an indicator of the
facilities. MMWR Recommendations and Reports: amount of water in a material that is available to sup-
43(RR-13): October 28. U.S. Department of Health port microbial growth.
and Human Services, Public Health Service, Centers
for Disease Control and Prevention, Atlanta.
39. ASHRAE Standard 62-2001. 40. Ibid.
CHAPTER 3
FACILITY DESCRIPTIONS
3.1 INTRODUCTIONHEALTH CARE continuing focal point for all needed health care ser-
FACILITIES vices. Primary care practices provide patients with
A hospital is an institution for treating and car- ready access to their own personal physician or to an
ing for four or more persons who need medical atten- established backup physician when the primary phy-
tion 24 hours a day, every day. Hospitals can be sician is not available.
classified in three ways: (1) by length of stay, (2) by Primary care practices provide health promo-
the diseases of its patients, and (3) by the type of tion, disease prevention, health maintenance, coun-
ownership. seling, patient education, and diagnosis and
treatment of acute and chronic illnesses in a variety
Short-term hospitals are those where patients of health care settings (e.g., office, inpatient, critical
stay less than 30 days. care, long-term care, home care, and day care).
Specialty hospitals, such as cancer centers, cen- Primary care practices are organized to meet the
ters for women and children, or mental health needs of patients who have undifferentiated prob-
centers, define themselves by the type of ser-
lems and where the vast majority of patient concerns
vices provided.
and needs are met in the primary care practice itself.
Ownership can be of three types: Primary care practices are generally located in the
Community owned patients community, thereby facilitating access to
Proprietary (either nonprofit or for-profit) health care while maintaining a wide variety of spe-
Government owned, as by the Department cialty and institutional consultative and referral rela-
of Defense or the Veterans Administration. tionships for specific care needs. The structure of the
primary care practice may include a team of physi-
3.1.1 Acute Care Hospital cians and non-physician health professionals.
An acute care hospital provides all types of
medical care and is where the length of a patients 3.1.4 Small Primary (Neighborhood)
stay is more than one day and less than thirty days. Outpatient Facilities
Many hospitals also have associated outpatient care
on the same campus. A small primary outpatient facility is typically a
neighborhood clinic or doctors office building.
3.1.2 Mental Health Hospital These facilities will have anywhere from one to as
many as ten different doctors offices. They are usu-
A mental health hospital is a specialty hospital
ally under 5,000 square feet (465 square meters) in
that provides psychiatric care to patients for more
area.
than one day.

3.1.3 Primary Care Outpatient Center 3.1.5 Outpatient Surgical Facilities


A primary care center serves as the patient's first There are a number of surgical procedures that
point of entry into the health care system and as the can be performed as outpatient surgery. Discharge

15
16 HVAC DESIGN MANUAL FOR HOSPITALS AND CLINICS

from the facility is expected within a reasonably bution throughout the room, and a general flow of air
short period of time. from clean to less clean areas. An airborne infectious
Classes of surgical facilities (American College isolation room may or may not have an anteroom. It
of Surgeons 1996) include: may or may not have an electronic pressure monitor-
ing and control system; a mechanical means of mea-
Class A: Provides minor surgical procedures suring the pressure relationship, however, is required
performed under topical, local, or regional anes- for all new rooms.
thesia without preoperative sedation. Excluded
are intravenous, spinal, and epidural routes; 3.2.3 Protective Environment Room
these methods are appropriate in Class B and C
A protective environment room is a patient room
facilities.
that demonstrates, by continuous or periodic testing,
Class B: Provides minor or major surgical pro-
outward air flow through all six surfaces and sus-
cedures performed in conjunction with oral,
tained positive air pressure with respect to all six sur-
parenteral, or intravenous sedation or under
faces, including the outside wall. It has specific
analgesic or dissociative drugs.
ventilation design features, including HEPA filtered
Class C: Provides major surgical procedures
supply air, from nonaspirating unidirectional flow air
that require general or regional block anesthesia
diffusers placed approximately over the bed, return
and support of vital bodily functions.
air registers placed low on the wall near the room
Outpatient surgical facilities usually are Class A entrance, and a general air flow pattern from the
facilities and may, under certain circumstances, be patient toward the door.
Class B facilities.
3.2.4 Critical Care Nursing Units.
3.1.6 Assisted Living Critical care nursing units provide intensive,
Assisted living is senior housing that provides specialized services to extremely ill patients. These
individual apartments, which may or may not have a may be specialized for cardiac, medical, coronary,
kitchenette. Facilities offer 24-hour on-site staff, neurological, or other diagnostic groupings or may,
congregate dining, and activity programs. Nursing as in many smaller institutions, be generalized. Criti-
services are provided for an additional fee. cal care beds are licensed separately from other
patient bed categories. Whether specialized or gener-
3.2 PATIENT CARE UNITS alized, programming considerations for the units are
similar, except for neonatal intensive care units.
3.2.1 General Medical and These units are also commonly referred to as
Surgical Nursing Units Intensive Care Units, a term that connotes the
The term medical and surgical nursing unit is degree of service rendered as opposed to critical
used to identify all general acute-care nursing ser- care, which denotes the condition of the patient.
vices. Units may have either medical, surgical, ortho- The distinction, while interesting, is not considered
pedic, pediatric, gynecologic, or a combination of important for the purposes of this manual.
patients. The term is also sometimes used to identify Critical care nursing is a relatively new phenom-
all noncritical care units. A distinction may also be enon that is rapidly growing in importance.
made with respect to licensing because many units Advances in medical technology have made treat-
used for specialized services fall under this generic ments possible in cases once considered incurable.
classification. For specific temperature, humidity, The use of general medical and surgical beds may
and airflow requirements refer to Table 4.1. decrease, but the need for critical care beds has
increased.
3.2.2 Airborne Infectious Isolation Rooms Another class of unit is emerging as a bridge
(AII) between Critical Care Units and general or special-
This is a patient room that demonstrates, ized medical and surgical units. The characteristics
through periodic or continuous testing, inward air of this class include relatively small numbers of beds
flow through all six surfaces and sustained negative (320), higher staffing ratios, monitoring of some or
air pressure with respect to all adjoining interior all patients, and coordination of patient care with
rooms, which has specific ventilation design fea- Critical Care Unit staff. Often referred to as Special
tures, including 100% exhaust, well-mixed air distri- Care Units or Step-Down Units, these are customar-
FACILITY DESCRIPTIONS 17

ily beds licensed under the medical and surgical delivery, and recovery. C-Section delivery also
umbrella. uses three spaces, but the delivery room is larger
and has full surgical capabilities and equipment.
3.2.5 Newborn Nurseries Alternative delivery utilizes one of two con-
cepts. The first, labor/delivery/recovery, uses a
A nursery provides care to newborn infants as an single room for all the functions provided in the
adjunct to postpartum nursing units. Three levels of traditional concept. The second, labor/delivery/
service are generally recognized: Level I for normal recovery/postpartum, uses a single room as in L/
newborns, Level II for intermediate care, and Level D/R but extends its use to include care of the
III for critically ill infants. The functional compo- mother and infant for the duration of their hospi-
nents of a Level I nursery include an admissions tal stay.
area, a well baby nursery, and a suspect nursery.
Level III Neonatal Intensive Care Units (NICU) 3.2.7 Bone Marrow Transplant (BMT) Units
are highly specialized, tertiary care facilities gener- Bone Marrow Transplant units comprise a suite
ally regulated under a state or regional plan for such of protective environment rooms set apart from the
centers. Level II NICUs are also regulated in most normal traffic patterns of the hospital and are pres-
areas; however, their frequency is much greater, and surized positively with respect to other patient wards
many hospitals that offer obstetric service have at adjacent, above, and below the BMT unit. The unit
least a few Level II beds. may have HEPA filtered air supplied to the corridors
Normal and intensive nursing operations for and patient day rooms.
infant care are much more focused at the patients
bedside than other types of nursing units. For that 3.2.8 Physical Therapy
reason, support areas for staff, including supply stor- Physical therapy provides rehabilitative ser-
age, must be located closer to the patients bedside vices for restoring musculoskeletal function. Ser-
than in other types of units. vices include evaluation and treatment and are
provided to inpatients and outpatients.
3.2.6 Labor, Delivery, and Recovery Units The scope of services offered varies widely.
(Birthing Centers) Departments located in hospitals that have specialty
orthopedic or cardiac services may have quite exten-
Labor and Delivery (L&D) Units provide
sive capabilities. In the former, speech and occupa-
services to expectant mothers before admission
tional therapy may be created as separate
for delivery, provide care to mother and infant
administrative units. In the latter, a cardiac rehabili-
during labor and delivery, and provide recovery tation department may be created.
for mothers immediately after delivery. Treatments for inpatients take place both in the
Prenatal care is generally provided to high department and at bedside. Outpatient treatments
risk mothers and may occur at intervals for take place in the department, although some hospi-
days or even weeks before delivery. Hospitals of tals may have a separate outpatient PT unit. Patient
all sizes may experience an increase in the num- visits are scheduled, and their duration is reasonably
bers of these patients due to increases in drug predictable. The department operates five or six days
addiction and AIDS and decreases in the num- per week.
bers who seek routine prenatal care.
A hospital may also offer classes for 3.2.9 Subacute Care Units
expectant parents in alternative birthing tech- A Subacute Care Unit is a portion of a general
niques. After admission, the department is hospital or long-term care facility set aside for the
responsible for labor and for delivery. Some care of patients who have non-acute conditions and
hospitals may perform cesarean deliveries in who continue to require some observation after dis-
their Surgery Department. After delivery, the charge from an inpatient service.
infant is transported to the nursery and the
mother is recovered from the effects of any 3.3 DIAGNOSTIC AND TREATMENT
anesthesia that may have been administered, CENTERS
then transported to a postpartum nursing unit.
3.3.1 Surgical Suites
With respect to the facilities required, there
are three classes of deliveries: traditional, cesar- Surgical Departments may be organized to pro-
ean section (C-Section), and alternative. Tradi- vide service to inpatients, outpatients, or both. Most
tional deliveries use separate spaces for labor, hospitals provide some facilities dedicated to outpa-
18 HVAC DESIGN MANUAL FOR HOSPITALS AND CLINICS

tient surgery. These may range from scheduling/ the highest, Level I, provides full-time specially
reception/registration only to a completely separate trained physicians, availability of a surgical suite and
outpatient Surgical Department attached to or free- team, and other specialty services.
standing from the hospital complex. The provision of emergency services, and there-
Typical components of a Surgical Department fore the Emergency Department, is an institutional
include a suite of operating rooms, anesthesia work option. The operation of an Emergency Department
areas, recovery, and staff support. Central Sterile follows a fairly standard pattern. The patient is pre-
Services (which may serve Obstetrics and Emer- sented either by EMS ambulance/helicopter, by pri-
gency as well) is a closely related function. vate motor vehicle, or by self-ambulation at one of
two portals. One of the two portals is a public
3.3.2 Cardiac Catherization Suites entrance, and the other is an ambulance/staff-only
Cardiac catheterization provides diagnostic and entrance. Arrival may be anticipated by prior notifi-
therapeutic procedures such as coronary angiograms, cation or may be unannounced and unexpected. The
electrophysiology, angioplasty, pacemaker insertion, condition of the patient is assessed by a triage nurse
and heart catheterizations. The equipment used in some departments and by a less formal method in
includes a sophisticated fluoroscopic imaging sys- others. If the patient's condition appears to warrant
tem that can operate in either a single or biplanar immediate attention, the patient is taken to an appro-
mode. Catheterization labs are normally associated priate treatment room or cubicle in the medical ser-
with open-heart surgery programs. Some procedures vice area of the department, provided that space is
require reserving an open-heart surgical team and available. If the patient's condition is not critical, the
room for emergency surgery. patient is generally asked to register and complete
other payment/medical history forms and then is
In addition to the procedure room, associated
seated in a waiting area to be treated as staff and
spaces house electrical generators, transformers and
space are available.
switchgear, system controls, computers, image-
Some patients may be transported to Diagnostic
recording devices, film processors, catheter storage,
Imaging or a portable radiographic unit brought to
and administrative staff and support functions.
the Emergency Department. A lab technician may be
Cardiac catheterization is a relatively new pro-
called to take specimens. Patients may be moved
cedure characterized by rapid development of equip-
from one treatment area to another or to holding sta-
ment, routines, and associated services. Labs
tions, so-called because they are reserved for longer-
established for five or more years may be upgraded,
term observation or for maintaining a patient in the
usually with an attendant need for greatly increased
Emergency Department until the patient can be
space and improved room environmental features.
admitted to an inpatient unit. In the case of serious
trauma or medical condition, the patient may be
3.3.3 Obstetrical Suites
transported to the Surgical Department.
Obstetrical suites are a suite of rooms including
a delivery room for surgical deliveries, an antepar- 3.3.5 Imaging Suite
tum room, a labor room, a recovery room, postpar- Diagnostic imaging includes ultrasonic, radio-
tum rooms, support areas, and possibly rooms that graphic, and electromagnetic examination of tissue
serve more than one function such as labor/delivery/ and anatomic chemistry. It is a service characterized
recovery and labor/delivery/recovery/postpartum. by rapid technological change, increasing specializa-
tion, and significant capital investment. Services of
3.3.4 Emergency/Trauma Center the department may be provided to inpatients, emer-
Emergency/Trauma Centers provide care to gency patients, and outpatients, although in some
ameliorate the effects of trauma or sudden illness. cases separate outpatient departments are estab-
They may also be the providers of only resort for lished.
primary care during evenings and on weekends and Typically, Diagnostic Imaging departments are
holidays. They may serve as a clinic or office for organized around types of equipment. Radiographic,
physicians to see patients during non-office hours, tomographic, and fluoroscopic equipment composes
and they may serve as part of the admitting route for one section, nuclear medicine a second, computer-
obstetric (labor and delivery) units. Emergency ser- ized tomography (CAT scan) a third, ultrasonogra-
vices were formerly categorized into three levels phy a fourth, and mammography a fifth. In hospitals
based on the services available. The lowest level of of 100 to 250 beds, it is not unusual for all diagnostic
service generally uses on-call physicians, whereas imaging equipment to be arranged as a single admin-
FACILITY DESCRIPTIONS 19

istrative and space-planning unit. In hospitals that Laboratory, Chemistry: Tests conducted in a Chem-
have more than 250 beds, specialization becomes istry Laboratory include general chemistries, blood
more frequent, and separate areas are planned for gas analysis, therapeutic drug testing, endocrine test-
each of several equipment groupings. ing, and comprehensive emergency toxicology and
Larger hospitals may also combine certain types psychotropic drug testing services.
of diagnostic imaging equipment into functional ser-
vice units. For example, a radiographic unit and CAT Laboratory, Gastrointestinal. The Gastrointestinal
scan system might be located in the Emergency Laboratory usually performs diagnostic hepatitis
Department, mammography and ultrasound systems virology tests other than those used for routine
located in a Women's Center, and so forth. screening of blood donors.

Typical components of the Diagnostic Imaging Laboratory, Neurochemistry/Amino Acid: The Neu-
Department include procedure rooms, procedure rochemistry /Amino Acid Laboratory diagnoses and
room direct-support spaces, other direct-support treats disorders associated with abnormal metabo-
spaces, departmental support spaces, and miscella- lism of amino acids, organic acids, and carnitine and
neous support spaces. their derivatives. The laboratory offers diagnostic
testing for patients suspected of having an inborn
3.3.6 Laboratory Suite error of metabolism. (This laboratory work would be
done in a chemistry or similar laboratory.)
A laboratory in a health care facility performs
chemical and physical tests and visual analysis of Laboratory, Thyroid/Endocrine The Thyroid/Endo-
specimens of patient body fluids and tissue. It may crine Laboratory provides full diagnostic testing, test
also be responsible for postmortem examinations or interpretation, and management consultation for
for testing and preparation of blood and its by-prod- patients with endocrine and metabolic disorder and
ucts prior to their use in treatment of patients. state-of-the-art metabolic assays for the diagnosis of
Tests are performed by machine or by techni- endocrine disorders including thyroid, pituitary,
cians using bench apparatus. The results of tests are adrenal, and bone disease. (This laboratory work
recorded manually on paper forms or electronically would be done in a chemistry or similar laboratory).
and are transmitted on paper forms, by electronic
means, or by voice communication. Laboratory, Clinical Immunology. The Clinical
Lab technicians at bedside obtain patient speci- Immunology Laboratory performs agarose gel elec-
mens from emergency and/or from surgery or from trophoresis, immunoelectrophoresis, and immuno-
fixation to detect monoclonal antibodies in serum,
outpatient drawing stations in the lab itself. Tests
urine, and cerebrospinal fluid.
are performed on the specimens according to the
specific orders of physicians or according to standing Laboratory, Hematology. The Hematology Labora-
orders. Tests may be performed on a scheduled basis tory performs cell counts on blood and other body
or on an immediate (stat) basis. fluids.
Laboratories are customarily organized in func-
tional sections. In some hospitals, an outpatient lab Laboratory, Special Clotting Section. The Special
may perform certain routine, commonly ordered out- Clotting Section laboratory provides tests for evalua-
patient tests, and the central lab performs all inpa- tion of coagulopathy. (This laboratory work would
tient tests and the less routine outpatient tests. be done in a Hematology or similar laboratory).
Examples of major lab types are:
Laboratory, Microbiology. The Microbiology Labo-
ratory provides tests in bacteriology, virology, para-
Laboratory, Acute Care (emergency laboratory): sitology, mycobacteriology, mycology, and
The Acute Care Laboratory in a health care facility is infectious diseases serology.
operated 24 hours a day, 7 days a week for emer-
gency and stat (immediate) laboratory work. Laboratory, Tissue Typing. The Tissue Typing Lab-
oratory performs tests required for bone marrow and
Laboratory, Blood Transfusion: The Blood Transfu- solid organ transplantation.
sion Laboratory is responsible for the storage and
dispensing of blood components, for patient sample 3.3.7 Renal Dialysis Suite
testing, and the preparation of frozen red cells and A suite of rooms for renal dialysis may include
other specialized components. equipment rooms for producing pure water, treat-
20 HVAC DESIGN MANUAL FOR HOSPITALS AND CLINICS

ment rooms that contain stations for patients, wait- usually sterile because of the hydrochloric acid con-
ing, administration, equipment cleaning, and other tent.
support functions. Esophagoscopy is similar to gastroscopy. Perfo-
ration of the esophagus is possible, particularly if
3.3.8 Endoscopy Suites and Rooms esophageal stricture or cancer is present. This com-
Endoscopy rooms are characterized by the par- plication would require immediate hospitalization
ticular body cavity being visualized and manipulated and possibly would require surgery; therefore, hospi-
by the insertion of optical instruments. Endoscopes tal access is required.
can be fitted with video cameras that allow visualiza- Bronchoscopy involves instrumentation of the
tion by more than one person, teaching, and record- lungs with either a rigid or a flexible instrument.
ing of images and procedures. The video equipment Coughing is induced by the insertion of the instru-
often involves dual monitors and requires added ment and by the procedures involved. The cough
space. droplets can contain highly infectious and resistant
organisms as well as M. tuberculosis. The operating
Lower Gastrointestinal Tract Endoscopy: personnel, as well as the hospital environment, have
to be protected from the droplets and from possible
Anoscopy, proctoscopy, and sigmoidoscopy can aerosolization of highly infectious organisms.
be undertaken with rigid instruments and are per-
formed in ordinary treatment rooms or doctors Urinary Tract and Other Endoscopy
offices. There is little danger of infecting the patient;
Cystoscopy (endoscopy of the urinary bladder)
the instruments, however, have been inserted into
can be done in a doctors office or at the bedside.
dirty areas and require ready access to cleaning
Infection can be introduced by the instruments;
facilities and equipment. Odor is a problem, particu-
therefore, sterilization of equipment, skin prepara-
larly if internal bleeding is encountered.
tion, and draping are important. The bladder is usu-
Colonoscopy became possible with the advent ally sterile; however, it can harbor highly resistant
of flexible fiberoptic instruments. Although per-
microorganisms that can spread by contact. Cysto-
formed via the same dirty orifice, the procedure is scopic surgery and cystoscopic x-rays often require
often not tolerated without sedation and/or anesthe-
anesthesia and are performed on a special urologic
sia, and there is a small potential of perforating the table. Because sterility of the air is not as important
colon, necessitating location within, proximity to, or
in cystoscopic surgery as it is in open surgery (sur-
quick access to hospital facilities. Biopsy, tumor gery through an incision) and because a special table
excision, and cauterization are procedures that can
is required, cystospy is ordinarily performed in a
be performed through the colonoscope. The advis- dedicated cystoscopy room, a room often much
ability of anesthesia becomes greater as the magni-
smaller than an open-surgery room. As newer proce-
tude or complexity of the procedure increases. dures become available, such as cystoscopic surgery
Flexible/fiberoptic instruments have compo- using camera and monitors, laser cystoscopic sur-
nents and seals that can be destroyed in high-pres- gery, cryoscopic (freezing) surgery, cystoscopic
sure/high-temperature environments (autoclaves). lithotripsy (ultrasonic, electrostatic, or laser stone
Sterilization of these instruments is done by gas ster- crushing), and extracorporeal lithotripsy, more and
ilization (ethylene oxide) or by soaking in germicidal more equipment is crowded into the cystoscopy
solutions. room.
Ureteroscopic surgery requires a yet different
Upper Gastrointestinal Tract Endoscopy: table, a table that allows cystoscopy and is radiolus-
Gastroscopy (endoscopy of the stomach) was cent, allowing real-time fluoroscopy of the patients
previously done with rigid scopes but now is more abdomen using a C-arm X-ray machine. Uretero-
easily done with flexible instruments. Specimens of scopic surgery can be performed in the cystoscopy
stomach and duodenal fluids are obtained for labora- room if the room is large enough to contain the spe-
tory analysis. Tissue samples are taken for histologi- cial table, the C-arm, the monitors, and a large cart of
cal (tissue) examination, and fluid and washings are ureteroscopic equipment; otherwise, it is performed
taken for cytological (cells) examination. Local in an open-surgery room.
anesthetic spray may be used to suppress the gag Nephroscopic surgery (endoscopic surgery of
reflex, which facilitates instrumentation. Transmis- the kidney) is performed either in an open-surgery
sion of infection to the patient from the environment room equipped with a C-arm or in a C-arm room
is usually not a problem. Contents of the stomach are (Radiology Department) equipped for surgery. The
FACILITY DESCRIPTIONS 21

video equipment, X-ray equipment, and the surgical Operating Room. Postoperative functions may
equipment require ample space. include recovery from general anesthesia in a sepa-
Arthroscopy and arthroscopic surgery (endos- rate recovery room and usually includes one or more
copy of joints) is done in an operating room under additional stages of recovery and postrecovery
full sterile conditions. The joint cavity is highly sus- before the patient is discharged.
ceptible to infection. Infections of the joint cavity are
difficult to eradicate and can be devastating to the 3.4.2 Inpatient Surgery Suites
patient. Surgery performed to inpatients is performed in
Abdominal endoscopic surgery, the perfor- inpatient surgery suites. These suites may be
mance of major abdominal surgery, such as gall designed differently for different types of surgery
bladder removal through endoscopic instruments, is performed.
done in an open operating room under full sterile
conditions. Generally, four monitors are used, two on 3.5 ADMINISTRATIVE AREAS
either side of the table so that the operators do not
have to twist around to view the monitors. Of the two 3.5.1 General Offices
monitors, one is for real time and the other is used Administration provides executive management
for freezing an image or for image retrieval from a for all aspects of a hospital. The administrator gener-
recording device. Lighting intensity in the room is ally supervises a second-level tier of managers
usually lowered. The room is equipped and prepared responsible for patient services, ancillary services,
to go immediately into open surgery if necessary. logistical, and other support services. Directors or
Note: The above procedures are discussed in detail managers for marketing and planning, medical staff
because they require differing environments. Other relations, and public relations may also report to the
forms of endoscopy (such as fundoscopy, cavern- senior executive.
oscopy, sinoscopy, etc.) require similar space and Larger institutions may have an umbrella orga-
equipment as those noted above and can be per- nization under which there are subsidiary for-profit
formed in rooms already constructed for the more or not-for-profit components. Each of these may fall
common procedures. under the direction of an executive director, presi-
dent, or senior vice-president, who, in essence,
3.4 SURGERY SUITES wears two hats. For the purposes of this section,
Administration includes the workspaces for those
3.4.1 Outpatient Surgery Suites managers and their administrative support staff who
Outpatient surgery, also known as day surgery manage the hospital component.
or ambulatory surgery, provides surgical service to
3.5.2 Accounting
outpatients. The configuration of this service relative
to the Surgery Department ranges from completely Accounting and Finance provides executive
freestanding to fully integrated. Freestanding facili- management for all aspects of a hospital's financial
ties include a suite of operating rooms, recovery, performance. Accounting and Finance may have
instrument preparation, patient registration and bill- administrative responsibility for functions such as a
ing spaces, and all other necessary support services. business office, data processing, and admitting. In
Integrated facilities may share some or most of those some organizations, Accounting and Finance may be
functions with the inpatient surgical service. combined with Business or with Administration. If
Some hospitals may process patients scheduled that is the case, the number of staff (and space
for postoperative admission to an inpatient nursing requirements) is usually small and can be calculated
unit through the Outpatient Surgery area. These as a part of either department.
patients may be referred to as AM admissions.
Unique functions in Outpatient Surgery include 3.5.3 Business Office
registration, dressing and preparation, postrecovery, The Business Office provides record keeping
and, in some arrangements, third-stage recovery. and operating services related to inpatient and outpa-
Registration includes check-in upon arrival, verifica- tient accounts and charges and hospital operating
tion that tests are complete, and coordination with expenses. With regard to financial affairs, it can be
billing and business services. Dressing and prepara- considered a hub through which information flows.
tion include changing into a surgical gown, preoper- The sophistication of business office activities is
ative preparation, and holding before transport to an increasing as the complexity and number of reim-
22 HVAC DESIGN MANUAL FOR HOSPITALS AND CLINICS

bursement schemes increase. In some organizations, financial and medical records. Service may be pro-
Accounting and Finance and Admitting may be com- vided to both inpatients and outpatients, or a separate
bined with the Business Office. department may be responsible for outpatients.
Emergency Department (ED) patients are generally
3.5.4 Patient Records registered within the ED; however, Admitting
Patient Records receives patient treatment infor- Department, Business Office, or other personnel may
mation, transcribes and records the information in a operate the function. Inpatients arriving after hours
predetermined format, assists in classifying informa- may be admitted at the Emergency Departments
tion, and assists in retrieving records and portions of registration area.
records for various users. A record is maintained for As outpatient services have increased in volume
each inpatient and for certain outpatients, such as and hospitals have worked to retain or capture a
those who visit the Emergency or Outpatient Surgery larger share of this workload, there has been a trend
departments. to create a physically (and sometimes administra-
Information is received in written form or tively) separate outpatient admitting/processing area.
through electronic media (such as dictation systems) The basic planning unit for Admitting is desig-
from all patient contact departments and from physi- nated as a workstation. A workstation may include a
cians. The record is maintained as a single file for registration booth, a room (office), a cubicle, or other
each patient or for each patient visit. Records of out- designated station in which the admitting process for
patient visits to diagnostic departments, such as radi- an individual inpatient takes place. In addition, the
ology and the lab, may be maintained by those Admitting department generally has workstations for
departments. personnel who verify insurance coverage, assist in
Patient Records may also be responsible for scheduling, or supervise. All of these areas are
maintaining a reference library for physicians and/or included within the definition of a workstation for
staff. This department communicates frequently with this section.
physicians and, to facilitate interaction, is often It is important to realize that the medical condi-
located adjacent to the main hospitals physician tions of the patient population and visitors in public
lounge. waiting areas are not controlled. Unless the clinical
The implementation of Diagnostic Related staff screens patients initially upon arrival, those who
Groups as a reimbursement methodology and need airborne isolation may be waiting in these open
increasing regulatory agency and consumer interest areas unmasked and nonsegregated for hours. Spe-
in the use and quality of care and patient outcomes cial HVAC treatment of such spaces may be neces-
have expanded the workload of this department. sary.
Some aspects of this increase come under the pur-
view of separate quality assurance or utilization 3.5.7 Outpatient Services
review functions that must work with the informa- Outpatient services, those delivered to patients
tion maintained in patient records. who are not admitted and who do not occupy an
inpatient bed for 24 hours or more, may include a
3.5.5 Patient Information Systems range of functions and services. At one end of the
Accurate and prompt patient information is vital range are functions related to reception, registration,
for modern patient treatment. This field is currently scheduling, and billing for medical services provided
seeing revolutionary change. Some of the important in other departments. At the other end are depart-
issues in patient information systems include ments that have a full complement of medical and
diagnostic services including limited examination,
distribution and expansion capability, consultation, and specimen-taking functions. Depart-
use of telecommunications, ments that operate as clinics would occupy the mid-
use of paperless technology, dle ground.
use of electronic medical records,
a need for specialized service closets. 3.5.8 Education Department
The Education Department provides in-service,
3.5.6 Main Lobby, Admitting, patient, and community education programs. It is
and Waiting Spaces usually associated closely with Nursing Administra-
The Admitting Department schedules and regis- tion because of its in-service training role. In some
ters patients and coordinates the initiation of their institutions, patient and community education are
FACILITY DESCRIPTIONS 23

provided by medical service departments according are grouped in separate sections of the serving area.
to their specialties. Patrons go directly to the section that contains the
There is a wide variation in the arrangement of item they desire rather than progress through a single
Education Department classroom areas. Some insti- line. In either arrangement, a short order service may
tutions use departmental conference rooms, dining be provided.
areas, and other spaces as classrooms, whereas oth- Current trends in food service are to increase the
ers provide some or all classrooms seats in dedi- number of food selection options, improve quality,
cated rooms. These variations may result from local and give the cafeteria component of the department a
factors, such as marketing, or the areas of medical more appealing environment.
service that are specialties at the hospital, such as
obstetrics. Hospitals may also have established pro- 3.6.2 Central Sterile Services
grams for seniors or cardiac rehabilitation that
require large meeting areas. Central Sterile Services cleans and prepares
instruments and equipment for use in surgical proce-
3.6 SUPPORT SERVICES dures, delivery, emergency care, and related areas. In
some hospitals, the function of the department
3.6.1 Dietary Department includes distribution of certain clean supplies.
(Cafeteria, Kitchen, and Storage) The following functions are included under
The Dietary Department provides meals for Central Sterile Services:
inpatients and employees. Inpatient meals are gener-
ally prepared for consumption in the patients room, Cleanup of surgical and obstetric case carts; sep-
although units such as psychiatric and rehabilitation aration of trash, linens, and instruments.
may have satellite dining areas. Cafeteria service Decontamination of instruments and washing of
may also be provided for visitors, physicians, and the carts.
public. Some hospitals also operate snack bars or Cleaning of instruments including ultrasonic
specialty food service shops and vending areas. cleaning and soaking and processing through a
The fixed equipment used for cooking, process- washer/sterilizer.
ing, and storage is served by electricity, gas, water, Assembly of instrument sets and supplies for
and drain lines. This makes adjustments to this
surgical packs and packaging.
department, once constructed, difficult and expen-
Sterilization of packs, labeling, and storage.
sive. The kitchen area may also be classified by
building and fire codes as a hazardous location, Preparation of case carts or sets of packs for
which requires special construction features. scheduled and emergency procedures.
A variety of systems are used to prepare, deliver, Delivery of case carts or sets of packs to served
and service inpatient meals and for cafeteria opera- departments.
tion. In large facilities, food may be prepared well in Receipt and stocking of supplies and linens to be
advance of its use and blast frozen either in serving used in packs.
portions or bulk. At the time of delivery and service, Inventory control and administration.
the food is thawed, heated, and portioned in the main
kitchen or in satellite kitchens at nursing units. An 3.6.3 Materials Management
alternative system involves preparation and cooking
Materials Management purchases, receives,
of food immediately before delivery and service. The
stocks, distributes, and inventories chargeable and
hot/cold food is portioned to individual trays or
nonchargeable supplies. It may also be responsible
plates and delivered to patients. Beverages may
accompany the tray or may be placed on the tray at a for purchasing equipment and building materials
nourishment kitchen at the nursing unit. The food used by maintenance.
may also be delivered in bulk to the nursing unit and In some hospitals, the stocking and distribution
portioned to trays in a satellite kitchen for service to of chargeable supplies (mostly patient-use items) is
patients. under a function known as Central Sterile Services.
Cafeteria service usually has either a serving The materials storage function has several com-
line or a scramble system. In the latter type, main ponents. Receiving checks in supplies delivered from
courses, salads, desserts, beverages, fast food, etc., the carrier and uncrates the boxes. Bulk items are
24 HVAC DESIGN MANUAL FOR HOSPITALS AND CLINICS

taken to a bulk storage area and boxed items to a pharmacy functions as an area to prepare special
storage section. Further unpacking may occur, and items such as IV additive solutions and as a bulk
some items may be placed in a storage section receiving, control, administrative, and storage area.
designed for unit-of-issue fulfilling.
3.6.5 Environmental and Linen Services
Supply orders from departments are picked from
the storage shelving or bins on either a scheduled or Environmental Services includes housekeeping
as-called-for basis. Supply areas in departments may and linen service. Housekeeping provides routine
be restocked by using exchange carts or a par (mini- and on-call cleaning and removal of trash from inte-
rior building areas with the usual exception of
mal) level resupply cart.
mechanical and electrical service rooms. Housekeep-
3.6.4 Pharmacy ing service may be extended to include adjacent hos-
pital-operated office buildings and outpatient
Pharmacy orders, controls, prepares for dispens- facilities.
ing, and dispenses medications for inpatients and Linen service involves changing bed linens; col-
emergency patients. It may also provide the same lecting bed linens and other soiled items such as tow-
functions for outpatients and/or employees. Certain els, blankets, pillows, and scrub suits; receiving and
bulk items, such as IV solutions, may be ordered, controlling clean linens; stocking and distributing
stored, and/or distributed by the materials manage- linen carts; and maintaining a backup stock of linens.
ment function; however, all solutions that are pre- The hospital may operate a full service laundry on or
mixed must generally be kept under the control of off campus or have small capacity washers and dry-
the hospital pharmacist even if they are stored else- ers for miscellaneous items.
where.
Linen service operates from a central area to sort
Record keeping is an integral component of the
linens and restock linen carts. Linen supplies for
department's activities, and this has encouraged a
operational areas are maintained in designated linen
trend toward computer systems for that purpose and
storage rooms or on wire carts or exchange carts in
for billing and checking prescriptions for contraindi-
clean utility rooms. Soiled linens are placed in local
cations.
collection rooms and then collected in larger carts
With respect to departmental space configura-
for removal to a central soiled linen holding area
tion, there are three prevalent systems: traditional,
before they are picked up by the laundry service.
unit dose, and satellite. The traditional system dis-
Housekeeping operates both from a central stag-
tributes medications to nursing units and patient care
ing/supply/equipment storage area and from satellite
departments in quantities that are used until
areas (janitor closets). Supplies and equipment for
exhausted. For nursing units, the medication is sepa-
housekeeping activities for a designated section of
rated into doses and administered by staff according
the building are maintained in the janitor closet, and
to the order of the prescribing physician. A bench
the assigned housekeepers operate from this base
stock may also be maintained on the unit.
during most of their shift. Personnel return to the
The unit dose system uses presorted, individu-
main area at shift change or to receive new assign-
ally packaged doses for each patient. These may be
ments. Trash collected by the housekeeper is emp-
delivered in a cassette system on a scheduled basis.
tied into large carts and taken to a dumpster,
Nursing staff opens and administers the dose at the
compactor, or incinerator.
prescribed time. There are variants of this delivery
system including labeled zip-lock bags. Each bag
3.6.6 Engineering and Maintenance Shops
contains the medication(s) to be administered to the
patient at a given time. The empty bags are returned Engineering Services operates and maintains the
as verification of administration and for billing. hospital physical plant. Operations include start-up
Under this system, a bench stock may also be and control of environmental systems for cooling,
maintained on the unit. heating, ventilation, domestic water, steam, normal
The satellite system includes small pharmacy and emergency power, lighting, and other building
units at inpatient nursing units and in certain ancil- utilities. Operations also include minor construction
lary departments, such as Emergency and Surgery. with in-house personnel and coordination with con-
These are staffed full- or part-time by a registered struction contractors, designers, and hospital staff for
pharmacist. These satellites stock a supply of the larger projects.
medications most frequently used by the depart- Maintenance includes identifying building
ments they serve. In this arrangement, the central assets, performing routine maintenance and operator
FACILITY DESCRIPTIONS 25

tests, and ensuring that contract maintenance ser- shield the public from this activity. Autopsy/morgue
vices are properly performed. Engineering is also spaces are usually located away from general traffic
responsible for grounds maintenance including in the hospital and have requirements for receiving
mowing, snow removal, placing directional signs, dead human bodies, storage, viewing, and ultimate
and care of pavements. pick up by undertakers
A separate unit, which usually falls within the Several aspects of the autopsy room require
administrative purview of Engineering Services, mechanical attention. The greatest danger dealing
inspects, tests, and repairs certain types of medical with autopsy is that the deceased patient might har-
equipment. This section is usually known as Bio- bor infective organisms that can be introduced into
medical Engineering. the environment by manipulation of tissues. M.
The Director of Engineering may also have col- tuberculosis is of particular concern. These organ-
lateral duties including safety and security. isms may or may not have been known to be present
Engineering Services requires space for mainte- prior to section (autopsy). Viable organisms persist
nance shops, for storage of maintenance materials, after death.
and for administrative support. Maintenance shops, Noxious chemicals, such as formaldehyde or
such as woodworking, painting, and welding, may phenol, may be used for tissue preservation. Such
have environmental control problems as serious as chemicals may be heavier than air, necessitating low
those of medical operations spaces. or local exhaust.
Outbuildings may be employed for storing haz-
ardous liquids, vehicles, and fuel-driven equipment. 3.6.8 Trash and Compactor Area
Health care facilities generate a lot of solid
3.6.7 Autopsy/Morgue waste. Some of the waste is Medical Waste, which
The morgue facility is a group of spaces for the must be treated in strict accordance to regulations.
preparation, storage, and dissection of human cadav- Many hospitals install local treatment systems,
ers or portions thereof, for the purpose of determin- which render this waste harmless so it then can be
ing cause of death or for teaching and research mixed with the regular solid waste. Multiple com-
purposes. Patients who die in the hospital must be pactors are usually provided to handle this waste in
transported using corridors or elevators used by oth- an efficient manner. The compactor area must be
ers. It is recommended that special care be taken to accessible to roads and large trucks.
CHAPTER 4
OVERVIEW OF HEALTH CARE HVAC
4.1 INTRODUCTION to safeguard the staff and patient population.
The HVAC system is one of several tools and
Health care facility HVAC systems are required
processes used in the control of infection.
to meet a variety of demands and applications, at a
high standard of performance, in many ways unique Environmental Control for Specific Medical
to the buildings they serve. In perhaps no other appli- Functions. Certain medical functions, treat-
cation is the HVAC system a more important, and ments, or healing processes demand controlled
integral, component of the building's processor environmental temperature and/or relative
that process more vital to human safety and health. humidity conditions that exceed the require-
The variety and level of demands placed on the ments of mere personal comfort.
HVAC systems, the nature of loads and design condi- Hazard Control. Many medical facilities include
tions, requirements for dependability and system functions where chemicals, fumes, or aerosols
hygiene, andnot leastthe necessity to interface are generated that pose health or safety hazards.
with a variety of other complex building systems, all HVAC equipment is used in such applications to
make the HVAC system design uniquely challeng- remove, contain, or dilute the environmental
ing. It is the intent of this chapter to provide an intro- concentration of such contaminants to safe lev-
duction to the demands and services required of els.
health care HVAC systems, as well as a brief discus- Life Safety. HVAC systems contribute to the
sion of the more salient design considerations. detection and containment of fire and smoke and
may be called upon to evacuate or exclude
4.1.1 Required HVAC Services smoke from atria or exit enclosures. Engineered
smoke control systems may be called for to pro-
As in other types of buildings, health care facil-
vide complex zoned pressurization control.
ity HVAC systems are required to establish comfort-
able environmental conditions through the control of
Depending upon the type of medical facility, the
temperature, air movement, relative humidity, noise,
characteristics of its patient population, and the
and objectionable odors. Environmental control is
nature of medical procedures performed, the range
important, not merely in providing personal comfort,
and criticality of services required in the above-listed
but in facilitating the healing process: simply stated,
categories will vary. Similarly, the complexity of the
a comfortable patient heals faster. In addition, health
HVAC system design and the need for close coordi-
care facility HVAC systems are called upon to sup-
nation with the design of other major building sys-
port a variety of medical functions, practices, and
tems will vary by facility.
systems critical to health and safety, including the
following:
4.1.2 Basic Classification of
Health Care Facilities
Infection Control. Medical facilities are places
where relatively high levels of pathogenic (dis- Health care facilities range widely in the nature
ease-causing) microorganisms are generated and and complexity of services they provide and (gener-
therefore require stringent practices and controls ally speaking) in the relative degree of illness or

27
28 HVAC DESIGN MANUAL FOR HOSPITALS AND CLINICS

injury of the patients treatedfrom a neighborhood In some patients, the bodys natural immune
general practitioners office to large regional or uni- system is weakened by disease, injury, or medi-
versity medical centers and specialty hospitals. As cal treatment, resulting in decreased ability to
a rule, environmental control requirements and the fight off infection. In the most severe such
relative role of the HVAC system in life safety and immune-compromised patient cases (such as
infection control become more important with bone marrow transplant patients), the body's
increasing complexity of the medical services pro- immune system may be completely dysfunc-
vided and the degree of illness of the patient popula- tional.
tion. A description of the several classifications of Contagious diseases not considered dangerous
health care facility and departmental functions is to the general public, such as measles and
provided in Chapter 3 of this manual. chicken pox, pose grave health risk to the
fetuses of pregnant mothers who may acquire
4.2 INFECTION AND SAFETY HAZARDS the infection through, for example, exposure to
Health care facilities include by their nature other patients in a waiting room.
populations and processes that produce biological,
chemical, and radiation hazards to human safety and The risk of infection is not limited to patients.
health. Additional chemical or biological hazards Visitors, and more particularly health care workers,
can enter from the natural environment or be gener- are easily exposed to contagious disease through a
ated within building materials and equipment as a variety of circumstances and means.
result of poor design or maintenance. Examples of
4.2.2 Modes of Transmission: Direct Contact
potential chemical hazards include highly volatile
and Airborne
substances and solutions used in laboratory and dis-
infection processes, leaking anesthesia gas, and car- Disease may be transmitted through two pri-
bon monoxide or other combustion gases entering mary means: direct contact (including ingestion) and
outside air intakes. Radiation hazards can result from airborne. The means of transmission is determined
improperly handled nuclear medicines or poorly by the nature of the infectious organism and/or how
shielded X-ray processes. This chapter will deal it enters or exists within the building environment.
largely with the control of the biological hazards rep- Direct contact transmission results when the
resented by the microorganisms that cause nosoco- pathogen enters the body through a wound, open
mial (acquired in the hospital) infections. The term sore, or vulnerable body location (mouth, eyes, etc.)
contaminant, however, will often be used to refer via contact with unwashed hands, infectious body
to the airborne hazards from any sources. fluids, droplets from sneezes or coughs, or other
infected objects or material. Examples of direct con-
4.2.1 Sources of Infectious Organisms tact infection opportunities include:
A primary source of pathogenic microorganisms
Hand contact, as when unwashed hands have
in the health care environment is the patient suffering
had contact with an infection source (an ill
from contagious disease. In addition, several other
patient, a contaminated equipment surface, etc.)
significant and potentially deadly sources of infec-
tion include the microbes carried on the person of and in turn transfer the organism by touching a
every human being, contaminated outside air or vulnerable part of one's own or another's body.
water supplies, and microbe amplification or Contact of a vulnerable body part with an
growth sites within the building itself. Due to these infected body fluid, such as might occur in an
factors, the health care environment will often have accidental splash of contaminated blood drop-
relatively larger concentrations of microorganisms lets from a laboratory specimen.
than are found in conventional buildings. Exposed Needle stick, whereby a health care provider
to these are those personsthe patient population accidentally sticks a contaminated syringe nee-
most susceptible to acquiring life-threatening infec- dle into his or herself.
tion via several potential pathways. Insect transmission, by bite or by direct transfer
of pathogens from a contaminated substance
Patients with open wounds from trauma, burns, (trash, animal droppings, etc.) to human food or
or surgery present an opportunity for microbes food preparation surfaces.
to bypass the bodys protective outer covering, Contact with infected liquid droplets produced
the skin. by a sneeze, cough, or talking by a person with
OVERVIEW OF HEALTH CARE HVAC 29

contagious disease. Many of these droplets are It is the airborne route of infection over which
of a mass and size (>5 microns) that cause them the HVAC system is most effective as part of the
to settle out of the air quickly, limiting infectiv- health care facilitys overall infection control effort.
ity to a radius of several feet. A single sneeze
can produce 100,000 aerosolized particles; 4.2.3 Exposure Classifications
coughing can produce on the order of 10,000 Health care authorities have established expo-
particles per minute. sure levels for a number of pathogens, representing
the number of infectious organisms, or the number
Studies indicate that the great majority of noso-
per unit volume of air, which pose significant threats
comial infections result from direct contact, the
of disease in healthy individuals. The CDC Action
greatest single cause being the unwashed hands of
Level is one such indicator of relative infection
health care providers.
potential or infectivity. For example, the CDC
Airborne transmission is usually distinguished Action Level for the Tuberculosis bacillus or the
as resulting from respiration of particles or aerosols Ebola virus is 1.0 infectious unit (a single microor-
of low mass and size (1.0-5.0 microns) that can ganism), detectable in any sampled volume of air;
remain indefinitely suspended in air. Infectious bac- these particular microorganisms are considered
teria, fungi, and viruses normally are transmitted into among the most deadly. The Infectious Dose is
the air in forms larger than the individual microbe, another such indicator and varies from a single
such as via attachment to organic or inorganic dusts microbe to thousands, depending upon the species of
and particles such as soot, skin cells, or the droplet microorganism.
nuclei that are the residual of aerosolized liquid
droplets. Particles of this size are easily respirated 4.3 INFECTION CONTROL
deeply into the lungs, where in a suitably vulnerable
host or in high enough concentration, they can over- 4.3.1 An Overall Approach
come the bodys immune system and cause disease. Health care professionals utilize a wide range of
Typical means of airborne transmission include the specialty equipment and engineering controls and
following: observe rigid operational disciplines, practices, and
techniques, to control infection. Infection control
Sneezing, coughing, and talking by an infected
equipment and practices are regulated by federal and
person produce many particles light enough to
remain suspended in air. These activities can state government authorities, which also set stan-
therefore spread infection by both the direct and dards for engineering controls. In addition, civilian
airborne infection routes. agencies such as the Joint Commission for the
Resuspension into air of in-situ microbes, settled Accreditation of Healthcare Organizations
or trapped in building dust or debris, furnishing (JCAHO), as well as in-house infection control com-
materials (including bed coverings), equipment, mittees, act as safety and infection control watch
and room finishes and released by disturbing dogs.
activities such as bed-making, maintenance, and Some common infection control approaches
construction work. include the following.
Aerosolization of contaminated water droplets
via shower heads, spray humidifiers, or evapora- Surgical, medical treatment, and invasive diag-
tive cooling equipment (including cooling tow- nostic instruments, appliances, and materials
ers). Aerosolization of infectious particles or undergo sterilization or high-level disinfecting
droplets also can occur via surgical and autopsy processes and are protected from contamination
procedures, particularly those involving pow- until used by enclosure in sterile packaging.
ered cutting or abrasion tools. Hand washing and surgical scrub stations are
Carriage on human skin flakes (squames),
provided to sanitize the hands of health care pro-
which the average person sheds into the environ-
viders before they touch a patient.
ment at a rate of about 1,000 squames per hour
(Hambraeus 1988). Gowning and other sterile garments, including
Amplification (reproduction) within HVAC air- masks, hair and foot coverings, and gloves,
flow equipment, especially areas where moisture cover the person of surgical personnel.
and dirt can accumulate, such as cooling coil Sterile Technique and Aseptic Technique
drain pans, wet filters, and porous duct linings are practiced during surgical and other invasive
exposed to direct moisture. procedures.
30 HVAC DESIGN MANUAL FOR HOSPITALS AND CLINICS

Government- and industry-regulated practices well as by controlling environmental temperature


control the handling, storage, and disposal of and relative humidity. In many applications, all or
potentially infectious materials, such as used most of these functions are performed simulta-
dressings and syringe needles, pathology speci- neously.
mens, and blood products. Regulations also Dilution ventilation, combined with contami-
define personal protective equipment require- nant exhaust, is the process of lowering the concen-
ments for health care workers. tration of airborne contaminants in a space by
Room and fixed equipment surfaces in surgical exhausting contaminated air and supplying the
and other invasive treatment or diagnostic rooms space with contaminant-free makeup air. Effective-
are sanitized prior to use. Other cleaning, sani- ness is generally proportional to the space air change
tizing, laundering, disinfection, and general rate and the relative efficiency of the air delivery sys-
good housekeeping practices are observed tem in mixing the clean air throughout the space.
throughout the health care facility. According to the specific medical application and
Facility floor and circulation plans are normally nature of the contaminants, the makeup air may con-
designed to minimize clean and dirty cross sist totally of fresh (outside) air or be a combination
traffic and provide for separate storage of con- of fresh and recirculated (properly filtered) air.
taminated and clean materials. Directional airflow is the control of airflow into
Diagnosed or suspected cases of contagious dis- or out of a room, or unidirectionally through a
ease are isolated in disease isolation spaces spe- defined clean area of a room, according to the spe-
cially designed to prevent the spread of cific functional requirement. Directional airflow has
infection. three major applications:
Patients with severely suppressed immune sys-
tems are housed or treated in protective isolation Establishment of directional airflow into or out
spaces designed to exclude airborne pathogens. of one space from the space or spaces adjoining.
Directional airflow control, filtration, exhaust, The directional control of the airflow is achieved
and dilution ventilation are applied as engineer- by the establishment of a relative differential
ing controls to minimize exposure to airborne pressure between the spaces. Directional airflow
contaminants. out of a space (positive relative pressurization)
Environmental temperature and relative humid- is utilized when there is a need to protect room
ity in surgical and other critical spaces are kept occupants or materials from airborne contami-
within ranges that help support bodily immune nants outside the space. Airflow into a space
functions and/or inhibit pathogen viability. (negative pressurization) is utilized when it is
desired to prevent contaminants released in the
This list is not complete but is intended to con- space from spreading to adjoining areas. The
vey the fact that the HVAC system is but one ele- actual achievement of a specific room pressure
ment, albeit an important one, of an overall infection differential, relative to surrounding spaces, is
control program. In addition to providing active dependent not only upon the rooms relative
infection controls, such as apply in the final four supply-return/exhaust airflow configuration but
infection control approaches listed above, a properly also upon the airtightness of the rooms con-
designed HVAC system can be an important contrib- struction. A generally accepted practice to
utor to overall building sanitation by helping to pre- ensure the achievement of directional airflow
vent envelope condensation and other building between spaces is the establishment of a mini-
conditions conducive to microbe growth. Conversely, mum 75 cfm (35 L/s) flow differential and/or a
a poorly designed HVAC system can provide numer- 0.01 in. w.g. (2.5 Pa) pressure differential.
ous opportunities not only within the building, but Within rooms, directional flow, sometimes
within the system itself, for the generation of patho- referred to as plug or laminar flow, may be
genic organisms. achieved to a limited extent with special low-
velocity, nonaspirating supply diffusers that
4.3.2 The HVAC Systems Role in Infection project unidirectional airflow for a distance into
and Hazard Control the space. In concept, this arrangement provides
The HVAC system contributes to infection and a wash of clean air to remove or exclude con-
hazard control through engineering control func- taminants from the clean zone of influence, to
tions including dilution ventilation, contaminant be exhausted at strategically located exhaust or
exhaust, directional airflow control, and filtration, as return registers; in actuality, the location of the
OVERVIEW OF HEALTH CARE HVAC 31

exhaust or return opening has a minimal effect duct-mounted and packaged UV-fan recirculation
on room airflow pattern. units are available that help eliminate viable micro-
Directional airflow control is also the principle organisms from the air supply or prevent their
utilized in laboratory fume hoods, biosafety cab- growth on irradiated equipment. Upper-level room
inets, and other specially manufactured protec- UVGI arrangements are available that continuously
tive ventilation equipment. The equipment is irradiate the upper areas of a room but avoid direct
normally designed to establish a relatively high radiation of the lower, occupied levels, where the
(usually about 100 fpm [0.5 m/s]) flow velocity radiation could be harmful. As only part of the space
over the working surface, sufficient to transport is radiated, many authorities question the effective-
and remove volatized or aerosolized contami- ness of upper-level UVGI. In general, all UVGI
nants from the workers breathing zone. More equipment must be adequately maintained to be
detailed information for such medical specialty effective; dust can reduce lamp output, and burned-
exhaust equipment may be obtained from publi- out lamps are normally not readily evident. In addi-
cations of the National Council of Government tion, UVGI is less effective when air relative humid-
Industrial Hygienists. ity exceeds about 70%. For these and possibly other
reasons, most codes and authorities will accept
High efficiency filtration is used to remove the UVGI only as supplemental protection (to HEPA
majority of microorganisms from the air supply. filtration systems) for disease and protective isola-
tion applications. Refer to Chapter 12 for additional
Filters rated 90%-95% efficiency (using the information.
ASHRAE Dust Spot Test Method) may be Space temperature and relative humidity
expected to remove 99.9% of all bacteria and influence the potential for infection in several differ-
similarly sized particles. Such filters are ent ways.
required by some codes and standards to be
installed in all patient treatment, examination, Several studies indicate that the survival rates of
and bedroom spaces. airborne microorganisms in the indoor environ-
The HEPA filter shall exhibit a minimum effi- ment are greatest in very low, or very high,
ciency of 99.97% when tested at an aerosol of ranges of relative humidity (RH), depending
0.3 micrometer diameter and is mandated by upon the nature (bacteria, virus, fungi) and spe-
some codes for protective environments and cies of the organism. Evidence seems to indicate
specialty operating rooms. In addition to being that most microorganisms are less viable, and
very effective at bacteria and mold filtration, therefore less infectious, in a middle-range RH
HEPA filters are also effective in filtering viable of 40-70%.
viruses, which, although occurring in sizes as Moderately humidified environments are
small as 0.01 micron, are normally attached to a believed to increase the settling rate of infec-
particle (such as a droplet) much larger in size. tious aerosols; a possible reason for this is that
in more humid surroundings relatively heavy
Combination HEPA filter/fan recirculation air aerosol droplets are less likely to dry, lose mass,
units, including portable models, are employed in and remain suspended in the air.
some protective environment and disease isolation Excessively dry conditions can lead to drying of
applications, particularly for existing buildings with the mucous coatings on special tissues in the
limited ventilation upgrade capability. These units upper and lower respiratory tracts, which have
supplement central ventilation systems to (in effect) the function of capturing respirated particles
achieve a greater number of air changes in the space. before they can be breathed deeply into the
The effectiveness of all filters can be compromised lungs.
by leakage at filter gaskets and frames. High temperatures in an operating room, or RH
Filter rating using Minimum Efficiency Report- levels greater than 60%, can lead to patient
ing Value (MERV) is discussed in Chapter 9. sweating, which in turn can increase the risk of
Ultraviolet germicidal irradiation (UVGI) is infection from microorganisms carried on the
being seen increasingly in microbiocidal HVAC patient's own skin.
applications. Airborne microorganisms are destroyed
by exposure to direct UVGI in the wavelength range 4.4 CRITERIA
of 200-270 nanometers, given suitable exposure con- Among the HVAC designers first tasks is to
ditions, duration, and intensity. Air-handling unit and establish the design criteria for a project. Most state
32 HVAC DESIGN MANUAL FOR HOSPITALS AND CLINICS

and federal government agencies, and many local humidity, temperature, and supplemental guidance
governments, establish criteria for the design of for many typical hospital and clinic rooms. Table 4-1
health care facilities within their jurisdictions. The illustrates the selected best practice requirements
jurisdiction may utilize its own criteria and codes or from both the 1999 ASHRAE HandbookHVAC
cite model, national, or international building codes Applications and the 2001 AIA Guidelines. Notes
or design standards. Some private health care insti- from both references regarding individual rooms are
tutions and corporations also establish design summarized with Table 4-1. These criteria should be
requirements. Frequently adopted or cited codes, used when not superseded by criteria from the owner
standards, and design guidelines relating to health or local jurisdiction.
care facility HVAC systems include: These best practice criteria are based upon
committee experience in design application of exist-
The American Institute of Architects Guide- ing criteria (Appendix F, Table F-1). Rationale for
lines for Design and Construction of Hospital design is discussed in more detail in relevant chap-
and Health Care Facilities (AIA Guidelines). ters and appendices in this manual.
Standards and handbooks of the American Soci-
ety of Heating, Refrigerating and Air-Condition- 4.5 ENERGY EFFICIENCY AND
ing Engineers (ASHRAE). OPERATING COST
National Fire Protection Association (NFPA) Health care facilities continuously face the chal-
standards. lenge, and pressure, of being cost-effective. The
The Joint Commission on Accreditation of annual operating costs of HVAC systems, including
Healthcare Organizations Environment of both energy consumption and maintenance materials
Care standards. and manpower, constitute a significant portion of
The American Conference of Governmental overall building costs. Subject to compatibility with
Industrial Hygienists publication Industrial the health care functions of the facility, including
Ventilation. considerations of redundancy and dependability of
Centers for Disease Control and Prevention service, operational cost should be a primary consid-
(CDC) guidelines and recommended practices. eration in the selection of major HVAC systems and
Model mechanical codes, including the Stan- equipment.
dard, BOCA, ICBO, and Uniform Mechanical Systems and equipment should be designed with
Codes. overall energy efficiency in mind, and consideration
given to the application of such potential energy-cost
Typical criteria for HVAC design include indoor -saving features as heat recovery, airside economiz-
and outdoor environmental design conditions, out- ers, electric demand shifting, hybrid cooling, solar
side and total air change requirements, economic energy, and heat pumps. To determine the relative
considerations for equipment selection, requirements cost-effectiveness of two or more project alterna-
for redundancy or backup equipment capacity, solar tives, the most comprehensive and straightforward
characteristics, room pressure relationships, filtra- economic method is a life-cycle cost analysis
tion, and other criteria needed for systems and equip- (LCCA). This analysis takes into consideration all
ment selection and sizing. Other factors and data cost elements associated with a capital investment
that influence the HVAC design, such as envelope during the life cycle of use of the system or equip-
and equipment insulation, glazing characteristics, ment purchase. Additional information on economic
occupancy schedules, and ventilation or conditioning analyses is provided in Appendix E of this manual.
requirements for special equipment or processes,
may be provided by specific project documentation 4.6 EQUIPMENT SIZING FOR HEATING
or may require investigation by the designer. AND COOLING LOADS
In addition to basic design criteria, the designer
is responsible for acquainting him/herself with appli- 4.6.1 Design Capacity
cable government regulations and should establish in Design criteria for health care facilities include
the projects Scope of Work who has responsibility temperature, relative humidity, and ventilation
for any permits required by the jurisdiction. requirements affecting equipment capacity and cool-
Table 4-1 provides a summary of best practice ing/heating load. In some cases it may be necessary
recommendations. These specifically address room to establish and maintain a range of room conditions,
conditions, including space pressurization, minimum with different setpoints for summer or winter opera-
outdoor and total air, exhaust, recirculation, relative tion. The HVAC design must ensure that the required
Table 4-1.

Minimum Air Minimum All Air Air


Pressure Changes of Total Air Exhausted Recirculated Relative Design
Function Space
Relationship to Outdoor Air Changes per Directly to Within Room Humidity Temperature (o)
Adjacent Areas (a) per Hour (b) Hour (c) Outdoors (m) Units (d) (n)(%) F (C)

SURGERY AND CRITICAL CARE

Operating room (recirculating air system) (e) (r) P 5 25 - No 30-60 68-75 [20-23.9]

Operating/surgical cystoscopic rooms (e), (p), (q) (r) P 5 25 No 30-60 68-75 [20-23.9]

Delivery room (p) (r) P 5 25 - No 30-60 68-75 [20-23.9]


OVERVIEW OF HEALTH CARE HVAC

Recovery room (p) - 2 6 - No 30-60 70-75 [21.1-23.9]

Critical and intensive care - 2 6 - No 30-60 70-75 [21.1-23.9]

Newborn intensive care - 2 6 - No 30-60 72-78 [22.2-25.6]

Treatment room (s) - - 6 - - 30-60 70-75 [21.1-23.9]

Nursery suite P 5 12 - No 30-60 75-80 [23.9-26.7]

Trauma room (crisis or shock) (f) (s) - 3 15 - No 30-60 70-75 [21.1-23.9]

Trauma room (conventional ED or treatment) (f) (s) P 2 6 - No 30-60 70-75 [21.1-23.9]

Anesthesia gas storage N - 8 Yes - - -

Endoscopy N 2 6 - No 30-60 68-73 [20-22.8]

Bronchoscopy (q) N 2 12 Yes No 30-60 68-73 [20-22.8]

ER waiting rooms N 2 12 Yes - 30-60 70-75 [21.1-23.9]

Triage N 2 12 Yes - - 70-75 [21.1-23.9]

Radiology waiting rooms N 2 12 Yes (t) (u) - - 70-75 [21.1-23.9]

Class A Operating (procedure) room (e) (r) N 3 15 - No 30-60 70-75 [21.1-23.9]


33
Table 4-1. (Continued)
34

Minimum Air Minimum All Air Air


Pressure Changes of Total Air Exhausted Recirculated Relative Design
Function Space
Relationship to Outdoor Air Changes per Directly to Within Room Humidity Temperature (o)
Adjacent Areas (a) per Hour (b) Hour (c) Outdoors (m) Units (d) (n)(%) F (C)

NURSING

Patient room - 2 6(v) - - 30-60 70-75 [21.1-23.9]

Toilet room (g) N Optional 10 Yes No - -

Newborn nursery suite - 2 6 - No 30-60 72-78 [22.2-25.6]

Protective environment room (i), (q), (w) P 2 12 - No - 70-75 [21.1-23.9]

Airborne infection isolation room (h),(q), (x) N 2 12 Yes (u) No - 70-75 [21.1-23.9]

Isolation alcove or anteroom (w) (x) P/N 2 10 Yes No - -

Labor/delivery/recovery/postpartum (LDRP) - 2 6(v) - - 30-60 70-75 [21.1-23.9]

Public Corridor N 2 2

Patient corridor - 2 4 - -

ANCILLARY

RADIOLOGY (y) X-ray (diagnostic and treatment) - 2 6 - - 30-60 72-78 [22.2-25.6]

X-ray (surgery/critical care and


catheterization) P 3 15 - No 30-60 70-75 [21.1-23.9]

Darkroom N 2 10 Yes (j) No - -

Laboratory, general (y) N 2 6 Yes No 30-60 70-75 [21.1-23.9]

Laboratory, bacteriology N 2 6 Yes No 30-60 70-75 [21.1-23.9]

Laboratory, biochemistry (y) P 2 6 - No 30-60 70-75 [21.1-23.9]

Laboratory, cytology N 2 6 Yes No 30-60 70-75 [21.1-23.9]

Laboratory, glasswashing N Optional 10 Yes - - -

Laboratory, histology N 2 6 Yes No 30-60 70-75 [21.1-23.9]


HVAC DESIGN MANUAL FOR HOSPITALS AND CLINICS
Table 4-1. (Continued)

Minimum Air Minimum All Air Air


Pressure Changes of Total Air Exhausted Recirculated Relative Design
Function Space
Relationship to Outdoor Air Changes per Directly to Within Room Humidity Temperature (o)
Adjacent Areas (a) per Hour (b) Hour (c) Outdoors (m) Units (d) (n)(%) F (C)

Microbiology (y) N - 6 Yes No 30-60 70-75 [21.1-23.9]

Laboratory, nuclear medicine N 2 6 Yes No 30-60 70-75 [21.1-23.9]

Laboratory, pathology N 2 6 Yes No 30-60 70-75 [21.1-23.9]

Laboratory, serology P 2 6 Yes No 30-60 70-75 [21.1-23.9]

Laboratory, sterilizing N Optional 10 Yes No 30-60 70-75 [21.1-23.9]


OVERVIEW OF HEALTH CARE HVAC

Laboratory, media transfer P 2 4 - No 30-60 70-75 [21.1-23.9]

Autopsy room (q) N 2 12 Yes No - -

Nonrefrigerated body-holding room (k) N Optional 10 Yes No - 70 [21.1]

Pharmacy P 2 4 - - 30-60 70-75 [21.1-23.9]

ADMINISTRATION

Admitting and waiting rooms N 2 6 Yes - 30-60 70-75 [21.1-23.9]

DIAGNOSTIC AND TREATMENT

Bronchoscopy, sputum collection, and pentamidine


administration N 2 12 Yes - 30-60 70-75 [21.1-23.9]

Examination room - 2 6 - - 30-60 70-75 [21.1-23.9]

Medication room P 2 4 - - 30-60 70-75 [21.1-23.9]

Treatment room - 2 6 - - 30-60 70-75 [21.1-23.9]

Physical therapy and hydrotherapy N 2 6 - - 30-60 72-80 [22.2-26.7]

Soiled workroom or soiled holding N 2 10 Yes No 30-60 72-78 [22.2-25.6]

Clean workroom or clean holding P 2 4 - -


35
Table 4-1. (Continued)
36

Minimum Air Minimum All Air Air


Pressure Changes of Total Air Exhausted Recirculated Relative Design
Function Space
Relationship to Outdoor Air Changes per Directly to Within Room Humidity Temperature (o)
Adjacent Areas (a) per Hour (b) Hour (c) Outdoors (m) Units (d) (n)(%) F (C)

STERILIZING AND SUPPLY

ETO-sterilizer room N - 10 Yes No

Sterilizer equipment room N - 10 Yes No

Central medical and surgical supply

Soiled or decontamination room N 2 6 Yes No 30-60 72-78 [22.2-25.6]

Clean workroom P 2 4 - No 30-60 72-78 [22.2-25.6]

Sterile storage P 2 4 - - 30-60 72-78 [22.2-25.6]

SERVICE

Food preparation center (l) - 2 10 Yes No

Warewashing N Optional 10 Yes No

Dietary day storage - Optional 2 - No

Laundry, general N 2 10 Yes No

Soiled linen sorting and storage N Optional 10 Yes No

Clean linen storage P 2 (Optional) 2 - -

Linen and trash chute room N Optional 10 Yes No

Bedpan room N Optional 10 Yes No

Bathroom N Optional 10 Yes No 72-78 [22.2-25.6]

Janitor's closet N Optional 10 Yes No


HVAC DESIGN MANUAL FOR HOSPITALS AND CLINICS
Table 4-1. (Continued)

Notes:
P = Positive N = Negative + = Continuous directional control not required

(a) Where continuous directional control is not required, variations should be minimized, and in no case should a lack of directional control allow the spread of infection from one area to another. Bound-
aries between functional areas (wards or departments) should have directional control. Lewis (1988) describes methods for maintaining directional control by applying air-tracking controls. Design of the
ventilation system shall provide air movement, which is generally from clean to less clean areas. If any form of variable air volume or load shedding system is used for energy conservation, it must not
compromise the pressure balancing relationships or the minimum air changes required by the table. See note z for additional information.
(b) The ventilation rates in this table cover ventilation for comfort, as well as for asepsis and odor control in areas of acute care hospitals that directly affect patient care. Ventilation rates in accordance with
ASHRAE Standard 62, Ventilation for Acceptable Indoor Air Quality, should be used for areas for which specific ventilation rates are not given. Where a higher outdoor air requirement is called for in
Standard 62 than in Table 4-1, the higher value should be used.
(c) Total air changes indicated should be either supplied or, where required, exhausted. Number of air changes can be reduced when the room is unoccupied if pressure relationship is maintained and the
number of air changes indicated is reestablished any time the space is being utilized. Air changes shown are minimum values. Higher values should be used when required to maintain room temperature
and humidity conditions based upon the cooling load of the space (lights, equipment, people, exterior walls and windows, etc.).
(d) Recirculating HEPA filter units used for infection control (without heating or cooling coils) are acceptable. Gravity-type heating or cooling units such as radiators or convectors shall not be used in oper-
OVERVIEW OF HEALTH CARE HVAC

ating rooms and other special care areas.


(e) For operating rooms, 100% outside air should be used only when codes require it and only if heat recovery devices are used.
(f) The term trauma room as used herein is a first aid room and/or emergency room used for general initial treatment of accident victims. The operating room within the trauma center that is routinely used
for emergency surgery should be treated as an operating room.
(g) See section on patient rooms in ASHRAE HandbookHVAC Applications for a discussion of design of central toilet exhaust systems.
(h) The airborne infectious isolation rooms described in this table are those that might be used for infectious patients in the average community hospital. The rooms are negatively pressurized. Some isola-
tion rooms may have a separate anteroom. Refer to the discussion in the chapter for more detailed information.
(i) Protective environment rooms are those used for immunosuppressed patients. Such rooms are positively pressurized to protect the patient. Anterooms are generally required and should be negatively
pressurized with respect to the patient room.
(j) All air need not be exhausted if darkroom equipment has scavenging exhaust duct attached and meets ventilation standards regarding NIOSH, OSHA, and local employee exposure limits.
(k) A nonrefrigerated body-holding room is only applicable to facilities that do not perform autopsies on-site and use the space for short periods while waiting for the body to be transferred.
(l) Food preparation centers should have an excess of air supply for positive pressurization when hoods are not in operation. The number of air changes may be reduced or varied for odor control when the
space is not in use. Minimum total air changes per hour should be that required to provide proper makeup air to kitchen exhaust systems. See Chapter 30, Kitchen Ventilation, 1999 ASHRAE Hand-
bookHVAC Applications. In addition care must be taken to ensure that exfiltration or infiltration to or from exit corridors does not compromise the exit corridor restrictions of NFPA 90A, the pressure
requirements of NFPA 96, or the maximum defined in the table. The number of air changes may be reduced or varied to any extent required for odor control when the space is not in use. See Section
7.31.D1.p. (2001 AIA Guidelines).
(m) Areas with contamination and/or odor problems shall be exhausted to the outside and not recirculated to other areas. Individual circumstances may require special consideration for air exhaust to the out-
side; intensive care units in which patients with pulmonary infection are treated and rooms for burn patients are examples. To satisfy exhaust needs, replacement air from the outside is necessary. Mini-
mum outside air quantities should remain constant while the system is in operation.
(n) The relative humidity ranges listed are the minimum and maximum limits where control is specifically needed. These limits are not intended to be independent of a space temperature. For example, the
relative humidity is expected to be at the higher end of the range when the temperature is also at the higher end, and vice versa.
(o) For indicated temperature ranges, the systems shall be capable of maintaining the rooms at any point within the range during normal operation. A single figure indicates a heating or cooling capacity to
at least meet the indicated temperature. This is usually applicable when patients may be undressed and require a warmer environment. Use of lower temperature is acceptable when patients' comfort and
medical conditions require those conditions.
(p) National Institute for Occupational Safety and Health (NIOSH) Criteria Documents regarding Occupational Exposure to Waste Anesthetic Gases and Vapors and Control of Occupational Exposure
37

to Nitrous Oxide indicate a need for both local exhaust (scavenging) systems and general ventilation of the areas in which the respective gases are utilized.
Table 4-1. (Continued)
38

(q) Differential pressure between space and corridors shall be a minimum of 0.01 inch water gauge (2.5 Pa). If monitoring device alarms are installed, allowances shall be made to prevent nuisance alarms.
(r) Because some surgeons or surgical procedures may require room temperatures that are outside of the indicated range, operating room design conditions should be developed in consort with all users, sur-
geons, anesthesiologists, and nursing staff. The required total air change rates are also a function of space temperature setpoint, supply air temperature, sensible and latent load in the space. For recent
research refer to Appendix I.
(s) The first aid room and/or emergency room used for initial treatment of accident victims can be ventilated as noted for the treatment room. Treatment rooms used for bronchoscopy shall be treated as
bronchoscopy rooms. Treatment rooms used for cryosurgery procedures with nitrous oxide shall contain provisions for exhausting waste gases.
(t) In a recirculating ventilation system, HEPA filters can be used in lieu of exhausting the air from these spaces to the outside. In this application, the return air shall be passed through the HEPA filters
before it is introduced into any other spaces.
(u) If exhausting the air from an airborne infection isolation room to the outside is not practical, the air may be returned through HEPA filters to an air-handling system exclusively serving the isolation
room.
(v) Total air changes per room for patient rooms and labor/delivery/recovery/postpartum rooms may be reduced to 4 when supplemental heating and/or cooling systems (radiant heating and cooling, base-
board heating, etc.) are used.
(w) The protective environment airflow design specifications protect the patient from common environmental airborne infectious microbes (i.e., Aspergillus spores). These special ventilation areas shall be
designed to provide directed airflow from the cleanest patient area to less clean areas. These rooms shall be protected with HEPA filters at 99.97 percent efficiency for 0.3 micron-sized particles in the
supply airstream. These interrupting filters protect patient rooms from maintenance-derived release of environmental microbes from the ventilation system components. Recirculation HEPA filters can
be used to increase the equivalent room air exchanges. Constant volume airflow is required for consistent ventilation for the protected environment. If the design criteria indicate that airborne infection
isolation is necessary for protective environment patients, an anteroom should be provided. Rooms with reversible airflow provisions for the purpose of switching between protective environment and
airborne infection isolation functions are not acceptable (2001 AIA Guidelines).
(x) The infectious disease isolation room described in these guidelines is to be used for isolating the airborne spread of infectious diseases, such as measles, varicella, or tuberculosis. The design of airborne
infection isolation (AII) rooms should include the provision for normal patient care during periods not requiring isolation precautions. Supplemental recirculating devices may be used in the patient room
to increase the equivalent room air exchanges; however, such recirculating devices do not provide the outside air requirements. Air may be recirculated within individual isolation rooms if HEPA filters
are used. Rooms with reversible airflow provisions for the purpose of switching between protective environment and AII functions are not acceptable (2001 AIA Guidelines).
(y) When required, appropriate hoods and exhaust devices for the removal of noxious gases or chemical vapors shall be provided (see Section 7.31.D14 and 7.31.D15 2001 AIA Guidelines and NFPA 99).
(z) A simple visual method such as smoke trail, ball-in-tube, or flutterstrip can be used for verification of airflow direction. These devices will require a minimum differential air pressure to indicate airflow
direction. In accordance with AIA 2001 Guidelines, recirculating devices with HEPA filters may have potential uses in existing facilities as interim, supplemental environmental controls to meet require-
ments for the control of airborne infectious agents. Limitations in design must be recognized. The design of either portable or fixed systems should prevent stagnation and short circuiting of airflow. The
supply and exhaust locations should direct clean air to areas where health care workers are likely to work, across the infectious source, and then to the exhaust, so that the health care worker is not posi-
tioned between the infectious source and the exhaust location. The design of such systems should also allow for easy access for scheduled preventative maintenance and cleaning.
As with the data presented in Table 4-1, these notes have been extracted from the ASHRAE HandbookHVAC Applications and the 2001 AIA Guidelines for Design and Construction of Health
Care Facilities. Material from the AIA 2001 Guidelines is used with permission.
HVAC DESIGN MANUAL FOR HOSPITALS AND CLINICS
OVERVIEW OF HEALTH CARE HVAC 39

room conditions can be established under the most Appendix C of this manual provides some basic
stringent operational or outside weather conditions guidance for estimating medical equipment loads,
defined by applicable design criteria. but medical technologyand equipmentchanges
quickly; designers should attempt to obtain the most
4.6.2 OUTSIDE DESIGN CONDITIONS up-to-date information for the actual medical equip-
Outdoor air temperature and relative humidity, ment to be provided. Heat release information is
as well as other climatic information (wind speed, often available from equipment manufacturers, and
sky clearness, ground reflectance, etc.), must be well information on the frequency of usage may come
defined to enable accurate cooling and heating load from the eventual equipment user. Another typically
calculations. Outside design temperatures are nor- good source of information is the medical equipment
mally provided by governing criteria, which either planner for each project. Manufacturers of some
provide specific temperature values to be used or high-convective-heat release equipment (such as
else cite a published weather standard (such as the sterilizers and cooking equipment) offer guidance on
ASHRAE HandbookFundamentals) and design the design of exhaust hoods for heat removal at the
severity (0.4% DB, etc.). source. Designers should also become aware of the
heat release and environmental conditioning require-
Many criteria call for use of the ASHRAE 0.4%
ments for electronic communications and data equip-
dry-bulb (DB) and mean coincident wet-bulb
ment spaces that support various medical functions.
(MWB) temperatures for cooling applications and
the 99.6% dry-bulb temperature for heating, for inpa- 4.6.4 EQUIPMENT REDUNDANCY AND
tient and some outpatient (normally surgical) facili-
SERVICE CONTINUITY
ties where environmental conditions are relatively
more critical to patient well being. Typical criteria The fundamental importance of maintaining rea-
for outpatient clinics call for using the ASHRAE 1% sonable interior conditions in critical patient applica-
and 99% design temperatures for cooling and heat- tions often dictates that some degree of backup
ing loads, respectively. Maximum cooling load can heating, and in many cases cooling and/or ventila-
occur at peak WB conditions when outside air tion, capacity should be available in the event of
demands are high; for this reason, and for sizing major HVAC equipment failure. According to the
evaporative and dehumidification equipment, design- applicable codes or criteria, inpatient and many out-
ers should consider peak total load (latent plus sensi- patient surgical facilities may be required to have up
ble) climatic conditions for each project. ASHRAE to 100% backup capability for equipment essential to
has several design weather publications and products system operation. It should be recognized that even
to aid the designer, including a Design Weather where loss of a major HVAC service does not jeopar-
Sequence Viewer CD, WYEC2 data, and ASHRAE dize life or health, it may lead to inability to continue
EXTREMES. Refer to the ASHRAE web site medical functions and unacceptable economic
(www.ashrae.org) for further information. impact to the building owner. Designers should also
For any project, the designer must be careful to recognize that routine maintenance requirements
use climatic data for the site closest to the actual will, at least on an annual or seasonal basis, require
project location. The designer must also carefully major plant equipment to be taken off line for
consider characteristic features of the building or extended periods. Even where 100% redundancy is
surroundings that can affect heating and cooling not required, it is often prudent to size and configure
loads. As an example, ventilation air drawn into a plant equipment for off season operation to enable
building from a location near a dark-colored roof extended maintenance of individual units.
may be at significantly higher temperature than the Emergency power (EP) is mandated by several
design dry-bulb for the project location. codes and standards for HVAC equipment consid-
ered essential for safety and health. Facility heating,
4.6.3 EQUIPMENT LOADS particularly for critical and patient room spaces, is
Designers new to health care facility design normally required to be connected to the EP system,
often have difficulty in estimating the cooling loads as is the cooling system in some jurisdictions. Fed-
contributed by medical equipment. Like other equip- eral government regulations and/or guidelines
ment, the heat released to the surroundings by an require that ventilation equipment serving disease
item of medical equipment is often much less than its isolation and protective isolation rooms be connected
full-load electrical rating. Heat release will also to the emergency power system. As emergency
vary according to how frequently the equipment is power generation and distribution equipment is
used and for how long each use cycle lasts. expensive, these requirements can impact the config-
40 HVAC DESIGN MANUAL FOR HOSPITALS AND CLINICS

uration and sizing of HVAC plant and air-handling 4.7.1 Ventilation Air Quantity
equipment.
Depending upon facility type, location, system Many codes and standards provide minimum
characteristics, applicable criteria, and owner outside airflow rates for individual health care facil-
desires, the following services and equipment may ity spaces, based either on a flow rate per person or
be required to be connected to the emergency power room air change rate basis. Standard 62-2001 is often
system. Refer to Appendix G for more details. cited as a minimum standard for determining outside
air quantity for individual spaces and in addition pro-
Ventilation: supply, return, and exhaust fans to vides guidance for calculating minimum outside air
maintain critical pressure relationships or to rates for central systems. Minimum total room air-
control hazards or contaminant levels. flow rates (combined outside air and recirculation)
Heating and steam generation equipment: boil- are also often mandated by codes or criteria, based
ers, pumps, fuel supply, air-handling units, and upon the cumulative dilution effect of central sys-
other equipment needed to support heating of tems serving large numbers of spaces, the air-clean-
inpatient areas, freeze protection, and supply of ing effectiveness of high efficiency filtration, or the
steam to sterilization or other critical processes. minimum flow required to ensure good air mixing
Domestic water pumps. and comfort.
Domestic hot water generation and recirculation
for patient care and dietary areas. 4.7.2 Location of Outside Air Intakes
Cooling generators, pumps, and air-handling Outside air intakes must be located an adequate
and other equipment necessary to continue cool- distance away from potential contamination sources
ing for critical inpatient or sensitive equipment to avoid intake of contaminants. Typical minimum
areas. separation requirements are 25 feet (7.6 meters),
Controls needed to support the above equip- established by the AIA Guidelines, and 30 feet (9.1
ment. meters), according to the ASHRAE Handbook
HVAC Applications. These distances should only be
In developing commissioning requirements,
considered as preliminary guides: greater separation
designers should ensure that equipment to be con-
may be required depending upon the nature of the
nected to the EP system is tested in both normal and
contaminant, the direction of prevailing winds, and
emergency power modes of operation.
the relative locations of the intake and contaminant
4.7 VENTILATION AND sources. The ASHRAE HandbookFundamentals
OUTSIDE AIR QUALITY provides further design guidance and calculation
methods to help predict airflow characteristics
Health care facilities require large amounts of around buildings, stack/exhaust outlet performance,
fresh, clean, outside air for breathing and for control and suitable locations for intakes. General guidance
of hazards and odors through dilution ventilation and that should be observed for all projects includes the
exhaust makeup. Under normal circumstances, out- following.
side air contains much lower concentrations of
microorganisms, dust, soot, and gaseous contami- Do not locate intakes in proximity to combus-
nants than indoor air. When filtered by high effi- tion equipment stacks, motor vehicle exhausts,
ciency filtration, such as is mandated by many codes, building exhausts and stack vents, and cooling
outside air can be virtually free of microorganisms towers.
and particulates. When outside air is not at an
acceptable quality level, as may occur in heavily Keep intakes well above ground level, to avoid
industrialized areas, special gas adsorption filtration contamination from such sources as wet soil or
may be required on air intakes. In addition to a good piled leaves and to avoid standing water or
source of outside air, adequate ventilation requires snowdrifts. For similar reasons, roof-mounted
the careful location of intakes to avoid contamina- intakes should terminate well above the roof
tion, exhaust of contaminants, an adequate and con- level (3-4 feet [0.9-1.2 meters] in many codes).
trolled quantity of makeup air, and good distribution Provide for adequate access to outside air intake
and mixing of the clean air throughout the spaces plenums to enable periodic inspection and
served. ASHRAE Standard 62-2001, Ventilation for cleaning. Security considerations may dictate
Acceptable Indoor Air Quality should be utilized as a that access be available only via building interi-
minimum standard for ventilation design. ors or via locked equipment room doors.
OVERVIEW OF HEALTH CARE HVAC 41

In the aftermath of the September 11, 2001, ter- tamination (dirty processing), anesthesia storage
rorist attacks, some jurisdictions are developing rooms, and disease isolation rooms. For some poten-
requirements for more remote location of outside air tially very hazardous exhausts, such as from radio-
intakes and/or other measures to minimize the possi- isotope chemical fume hoods or disease isolation
bility of access to the intakes by unauthorized per- spaces, codes or regulations may require HEPA fil-
sons. tration of the exhaust discharge, particularly if the
discharge is located too close to a pedestrian area or
4.7.3 Air Mixing and Ventilation outside air intake.
Effectiveness
In most health care applications, it is desirable 4.8 ENVIRONMENTAL CONTROL
to introduce fresh air into a space in such a manner
as to maximize distribution throughout the space. 4.8.1 The Role of Temperature and Relative
Doing so maximizes the effectiveness of the ventila- Humidity
tion, ensuring that the fresh air is available every- Previous discussions have touched upon the role
where it is needed and eliminating stagnant air of temperature and relative humidity in infection
pockets. As will be further discussed in Chapter 9, control. Temperature and relative humidity are
good distribution and mixing also contribute to over- equally important from a patient therapeutic stand-
all room comfort. Good air mixing is achieved by point and in maintaining a reasonable work environ-
careful selection of diffuser location and perfor- ment for health care professionals. In an
mance, with proper attention to room construction uncomfortable environment, the sick or injured
features (soffits for example) or perimeter exposures patient is subjected to thermal stress. Thermal stress
that can affect distribution performance. Additional may cause much more than discomfort: it can render
information is available in Chapter 9. difficult or impossible the patient's ability to properly
regulate body heat, it interferes with rest, and it may
4.7.4 Exhaust of Contaminants and Odors be psychologically harmful. In addition, poorly con-
Exhaust systems provide for removal of contam- trolled conditions can result in such problems as dry
inants and odors from the facility, preferably as close skin and mucous membranes, further increasing dis-
to the source of generation as possible. In addition, comfort and stress. Conditions of temperature and
exhaust systems are used to remove moisture and relative humidity that would be considered comfort-
flammable particles or aerosols. Examples of source able for healthy individuals dressed in normal cloth-
exhaust in health care applications include: ing may be very uncomfortable for both patients and
health care workers, for a variety of reasons, includ-
Chemical fume hoods and certain biological ing the following.
safety cabinets are used in laboratories and simi-
lar applications where health care workers must Patients in both clinical and inpatient facilities
handle highly volatile or easily aerosolized may be very scantily clad or, in some instances,
materials. unclothed and have little or no control over their
Special exhaust connections or trunk ducts are clothing.
used in surgical applications to remove waste In hospital settings, patients are exposed to the
anesthesia gases or the aerosolized particles in environment on a continuous basis, not merely
laser plumes. for short periods of time.
Wet X-ray film development machines are In a variety of cases of disease or injury, patient
normally provided with exhaust duct connec- metabolism, fever, or other conditions can inter-
tions for removal of development chemical fere with the body's ability to regulate heat.
fumes. Health care workers often must wear heavy pro-
Cough inducement booths or hoods are used tective coverings, as in surgery and the emer-
particularly in the therapy of contagious respira- gency department, and engage in strenuous,
tory disease. stressful activities.

When contaminants or odors cannot practically Table 4-1, previously referenced, provides rec-
be captured at the source, the space in which the con- ommended temperature and relative humidity ranges
taminant is generated should be exhausted. Rooms for typical health care spaces, generally selected in
typically exhausted include laboratories, soiled linen consideration of patients or health care workers. For
rooms, waste storage rooms, central sterile decon- some special medical conditions, more extreme lev-
42 HVAC DESIGN MANUAL FOR HOSPITALS AND CLINICS

els of temperature and relative humidity are some- lished for each of the eight audible octave bands. The
times employed in patient therapy, for example: higher the NC level, the more noisy the space. One
characteristic of the NC approach is that it takes into
Conditions of 90F (32C) and 35% RH have account the subjective perception of noise level by
been found beneficial in treating certain kinds of the human ear relative to the frequency of the sound,
arthritis. recognizing that low-frequency noises are better tol-
An environment of 90F (32C) and 95% RH is erated than high-frequency. Several codes and stan-
sometimes used for burn patients. dards provide maximum NC levels for typical health
A temperature in the middle 80s (F) (around care facility spaces.
30C) is sometimes called for in pediatric sur- Patient privacy can be compromised when pri-
gery. vate conversations are intelligibly transmitted
between adjoining spaces. Frequent causes of this
Such high temperatures and/or relative humidi- problem are inadequate acoustical insulation (isola-
ties are normally not practically maintainable on a tion) properties of the construction elements separat-
large space (or area) basis and, when called for, ing rooms, inadequate sound-dampening provisions
would be established in limited environmental enclo- in ductwork, and/or inadequate background room
sures or when using special equipment. sound pressure level. The HVAC ductwork design
and diffuser/register selections can greatly influence
4.8.2 Noise Control
the latter two causes, by providing a minimum level
Noise control is of high importance in the health of background sound contribution from the air distri-
care environment because of the negative impact of bution system and by ensuring effective attenuation
high noise levels on patients and staff and because of in ductwork. Chapter 9 of this manual provides more
the need to safeguard patient privacy. The typical detailed information of the causes of, and solutions
health care facility is already full of loud noises from for, HVAC noise.
a variety of communications equipment, alarms,
noisy operating hardware, and other causes without 4.9 HVAC SYSTEM HYGIENE
the noise contribution from poorly designed or
installed HVAC equipment. High noise levels Although the general topic of nosocomial infec-
hinder patient healing largely through interference tion cause and control was discussed above, the
with rest and sleep. In addition, like uncomfortable designer must be aware of the potential for infection
thermal conditions, loud noises degrade the health risks that can arise through poor design or mainte-
care provider's working environment, increase stress, nance of the HVAC equipment itself. Any location
and can cause dangerous irritation and distraction where moisture and nutrient matter collect together
during the performance of critical activities. can become a reservoir for growth of deadly micro-
Sources of excessive HVAC noise include: organisms. Generally, hard surfaces (such as sheet
metal) require the presence of liquid moisture to sup-
Direct transmission of mechanical and/or medi- port microbe growth, whereas growth in porous
cal equipment room noise to adjacent spaces. materials may require only high (> 50%) relative
Duct-borne noise generated by fans and/or high humidity. Nutrient materials are readily available
air velocities in ducts, fittings, terminal equip- from such sources as soil, environmental dust, ani-
ment, or diffusers and transmitted through duct- mal droppings, and other organic and inorganic mat-
work to adjoining occupied spaces. ter. The task of the HVAC designer is to minimize
Duct breakout noise, when loud noises in duct- the opportunity for moisture and nutrients to collect
work penetrate the walls of the duct and enter in the system, through proper design of equipment,
occupied spaces. including adequate provisions for inspection and
Duct rumble, a form of low-frequency breakout maintenance. Potential high-risk conditions in an
noise caused by the acoustical response of duct- HVAC system include:
work (particularly high-aspect-ratio, poorly
braced rectangular duct) to fan noise. Outside air intakes located too close to collected
organic debris, such as wet leaves, animal nests,
One standard means of quantifying room noise trash, wet soil, grass clippings, or low areas
levels is the noise criteria (NC) method, which where dust and moisture collect. This is a partic-
assigns a single-number noise level to a curve of ular concern with low-level intakes and a pri-
sound pressure level values (in decibels, dB) estab- mary reason for code-mandated separation
OVERVIEW OF HEALTH CARE HVAC 43

requirements between intake and ground, or replacement can occur with minimal impact on
intake and roof, discussed previously. facility operation.
Outside air intakes not properly designed to
exclude precipitation. Examples are intakes 4.11 INTEGRATED DESIGN
without intake louvers (or with improperly
designed louvers) and intakes located where 4.11.1 General
snow can form drifts or where splashing rain can In order to be successful, the HVAC design must
enter. be thoroughly coordinated with the other design dis-
Improperly designed outside air intake opening ciplines. The HVAC engineer's involvement should
ledges where the collected droppings of roosting begin not later than pre-concept design and continue
birds carry or support the growth of many dan- until design completion. This chapter has addressed
gerous species of pathogens. some of the design features essential to good air
Improperly designed cooling coil drain pans or quality, hygienic design, and comfort conditioning,
drainage traps that prevent adequate condensate but obtaining these features requires the HVAC
drainage. designer's early influence on building arrangement
Air-handling unit or duct-mounted humidifiers and floor plan features that affect equipment location
not properly designed to ensure complete evapo- and space availability. Early involvement and design
ration before impingement on downstream coordination are essential to ensure that:
equipment or fittings.
Filters and permeable duct linings, which collect Outside air intakes and building exhausts are
dust, located too close to a moisture source, such optimally located to avoid contamination of the
as a cooling coil or humidifier. building air supply.
Improper attention to maintenance during Plant and equipment rooms are well located in
design, resulting in air-handling components relation to the areas they serve, to enable eco-
that cannot be adequately accessed for inspec- nomic sizing of distribution equipment and air
tion or cleaning. and water velocities well within noise limitation
guidelines.
Designers must always bear in mind that even Plant and equipment rooms are so located that
properly designed equipment must be maintainable equipment noise will not disrupt adjacent occu-
if it is to remain in clean operating condition. Chap- pied spaces.
ter 9 of this manual provides additional information HVAC equipment room locations are coordi-
regarding the proper design of HVAC system compo- nated with electrical, communications, and
nents to minimize the potential for microbe growth. plumbing equipment rooms to minimize distri-
bution equipment (duct, piping, cable trays, con-
4.10 FLEXIBILITY FOR FUTURE duit) congestion and crossover, while providing
CHANGES adequate space for installation and maintenance
Changes in space utilization are common in of these services.
health care facilities, and periods of less than ten Sufficient vertical building space is provided for
years between complete remodelings are common- the installation and maintenance of distribution
place. The trend is normally toward more medical equipment of all trades.
equipment and increasing internal cooling loads. The Sufficient space is provided for plant and equip-
initial design should consider likely future changes, ment rooms, and vertical utility chases, to
and the design team and owner should consider a enable proper installation, operation, and main-
rational balance between providing for future contin- tenance of the equipment, including provisions
gencies and initial investment costs. Future contin- for eventual equipment replacement.
gencies may be addressed by such features as:
4.11.2 Stages of Design Development
Oversizing of ductwork and piping. The stages of design development, including the
Provision of spare equipment capacity (oversiz- number of discrete submissions, which mark the
ing) for major plant, air moving, or pumping progress of design and provide an opportunity for
equipment or provision of plant/floor space for owner comment and feedback, vary widely by facil-
future equipment installation. ity complexity, owner needs, project schedule and
Provision of interstitial utility floors, where budget, and other factors. Whether the design is
maintenance and equipment modification or conventional design-bid-build or design-build will
44 HVAC DESIGN MANUAL FOR HOSPITALS AND CLINICS

also affect the interim stages. For the purpose of several other major design disciplines with which the
emphasizing the need for early and continuous HVAC systems must functionally and physically
HVAC designer involvement in the overall project interface.
design, however, a typical five-stage design project By the completion of concept design, the floor
is outlined here. plan and overall building configuration are normally
locked down, as is the project cost estimate. Later
Programming and predesign, wherein the owner modification or enlargement of equipment space
and/or his/her agent develops the scope of becomes difficult or impossible. Therefore, during
requirements for the facility. This program concept development the HVAC designer must refine
normally defines the type of services to be pro- the preliminary load and demand calculations and
vided by the facility and the approximate num- make final system selections to enable a good esti-
ber and type of spaces to be included in each mate of the required equipment cost, capacities, con-
department. The program will normally pro- figuration, and dimensional space requirements.
vide some information regarding the required The approximate size and distribution arrangement
scope of site and utility development and plant of ductwork and piping mains (especially steam,
necessary to support the project. Appendix C condensate, or other vertically sloped systems)
provides typical load densities that can be used should be determined, to enable confirmation of the
in early evaluation and broad scoping of the adequacy of building spaces and coordination with
HVAC system requirements. other disciplines. Where final equipment or fitting
Preconcept design, which typically takes the selections are not yet determined, but where these
design to 15-20% development, involves estab- have potential space impact (attenuating equipment,
lishing the outline and orientation of the build- for example), the designer should reserve space on a
ing, preliminary elevations and consideration of worst case scenario.
envelope materials, department layout includ- For the final design stages, the HVAC designer
ing circulation spaces, and in many cases the must refine and complete the design while coordinat-
initial development of the floor plan. ing with the other design disciplines to stay abreast
Concept design, completing development of the of design refinements or changes that affect the
design to a level approaching 30-35% comple- HVAC system.
tion. This level usually includes a fully devel-
oped floor plan, an outline of specifications, and 4.11.3 Equipment Interface: Make it Fit
concept-level development of all supporting Because of the many engineering systems that
design disciplines. provide service in health care facilities, the need to
Interim final, which takes the design to the 60- ensure adequate access for future maintenance, and
65% design level, is normally provided to pro- often because of criteria restrictions on where distri-
vide an opportunity for owner review and feed- bution equipment can be installed (i.e., above circu-
back before design finalization. lation spaces), the HVAC designer must carefully
Final design: complete development of all coordinate the physical space requirements of his/her
design documentation. equipment. Health care facilities are served by a
wide variety of fire protection, electrical power,
The HVAC designer should be intimately plumbing, medical gas, and telephone, data, nurse
involved beginning with the Preconcept Design, with call, and other electronic communication and moni-
some degree of input having been provided for site toring systems. All of these must physically fit
utility and plant programming/planning. During Pre- within allowable distribution spaces along with
concept Design, the HVAC engineer's input is neces- HVAC ductwork and piping. Often, codes or criteria
sary for the architect to appreciate the energy and restrict main utility distribution to circulation spaces
physical plant implications of building orientation, in order to minimize the need for maintenance per-
configuration, envelope materials (especially fenes- sonnel access into occupied spaces and/or to control
tration), and vertical floor height. Involvement noise. Codes also restrict certain utilities from pas-
enables the HVAC engineer to influence the loca- sage over electrical and communications spaces, exit
tions and sizes of plant and equipment rooms and enclosures, and certain critical health care spaces,
strategies for service distribution, thereby enhancing such as operating rooms.
future maintainability and flexibility for change. It is the responsibility of design engineers to
Involvement at this stage also enables the HVAC ensure that the equipment they depict in design
designer to begin to coordinate the design with the drawings can be installed in the spaces indicated
OVERVIEW OF HEALTH CARE HVAC 45

with sufficient space for maintenance access, by a control representative to help assess the potential
prudent contractor using standard construction prac- risks to the patient population during construction
tices and reasonable judgment in equipment selec- activities, and jointly identify the appropriate barrier
tion, according to the provisions of his/her contract. controls and techniques. Typical barrier precautions
Where the designer knows that the availability of can include separation of construction areas by dust-
space is so limited as to require special construction tight temporary partitions, exclusion of construction
measures or very limited or proprietary equipment traffic from occupied areas, and isolation of duct sys-
selections, it is wise to make this information known
tems connecting construction with occupied spaces.
in the design documents. A prudent designer depicts
In addition, negative relative pressurization and
and dimensions the equipment on design drawings,
including ductwork and piping and showing all exhaust of construction areas may be required and, in
major fittings required for coordination (offsets, cases of severe patient vulnerability, the introduction
etc.), balancing, and operation, such that it could rea- of supplemental HEPA filtration units into patient
sonably be installed as depicted. These design rooms or other critical spaces may be considered.
responsibilities do not detract from the construction Of equal concern, designers must seek to mini-
contractor's responsibility to properly coordinate the mize the possibility of unplanned service interrup-
installation work between trades and do not supplant
tions during the construction project. Designers
his/her responsibility to execute detailed, coordi-
should become well acquainted with the existing
nated construction shop (installation) drawings.
engineering systems and building conditions to be
Most designers check the coordination of their
systems with those of other disciplines by a variety able to evaluate the impact of new construction. Site
of methods that may include multi-dimensional over- investigations should always include inspection of
lays and representative elevational views or sketches. existing equipment plants, rooms, and other equip-
The latter should be provided from at least two per- ment and building areas with reasonably available
spectives in each congested plant and equipment access. Maintenance personnel can often provide
room and at representative crowded locations in information of concealed as-built conditions, and as-
distribution areas throughout the facility. Some built drawings are often available; in many cases,
building owners require submission of such proof however, the latter are inaccurate or not up to date.
of concept documents to demonstrate satisfactory
interdisciplinary coordination. When as-built information is lacking or suspect,
designers should attempt to identify existing services
4.11.4 Special Considerations for that are installed in, or are likely to be affected by,
Retrofit/Renovation project work, to the extent feasible under the scope
Designs for the retrofit or renovation of existing of their design contract and the physical or opera-
health care facilities, particularly when health care tional limitations of building access. Building own-
functions must continue during construction in areas ers should recognize the value of accurate as-built
surrounding or adjacent to project work, require spe- information and, when not available from in-house
cial attention to factors that can affect patient health sources, contractually provide for more thorough
and safety. Designs must include provisions to mini- investigations by the design team. It is the
mize the migration of construction dust and debris designers responsibility to identify the nature of
into patient areas or the possibility of unplanned alterations of, or extensions to, existing services and
interruptions of critical engineering services. equipment, including temporary features, and any
Construction work almost invariably involves required interim or final re-balancing, commission-
the introduction or generation of relatively high lev- ing, or certification services, necessary to accommo-
els of airborne dust or debris, which, without appro-
date new building services while minimizing impact
priate barrier controls, may convey microbial and
to ongoing functions. This will often require the
other contaminants into patient care areas. Demoli-
tion activities, the transport of debris, and personnel development of a detailed phasing plan, developed in
traffic in and out of the facility can directly introduce close coordination with the building owner. The
contaminants, as can disruption of existing HVAC goal should be no surprisesno interruptions or
equipment, removal of barrier walls or partitions, diminishment of critical services to occupied areas
and disturbances of building elements and equipment that are not planned and identified to the building
within occupied areas. Project architects and engi- owner during the design process. Chapter 6 provides
neers must work closely with the owners infection more information on this topic.
CHAPTER 5
HVAC SYSTEMS
5.1 INTRODUCTION ASHRAE HandbookHVAC Systems and Equip-
A fundamental difference between conventional ment for further information regarding the general
HVAC systems design and HVAC systems for hospi- advantages and disadvantages of these systems
tals is the need for relative pressurization between [ASHRAE 2000].) Constant volume systems are
rooms/areas within the facility. Generally, airflow is often the choice for patient care areas of hospitals;
from clean to less clean areas. (Refer to Chapter 4, however, variable volume systems may be used in
Overview of Health Care HVAC, and Chapter 12, these areas with proper controls. Constant volume
Room Design, for additional information.) systems offer the simplest design approach where
relative pressure differentials between rooms are
The level of air filtration for patient care areas in
requiredfor example, in operating rooms and labo-
hospitals is higher than for most other facilities. The
ratories. (Refer to Chapter 12 for relative pressure
Guidelines for Design and Construction of Hospitals
relationships for spaces.) VAV systems are com-
and Health Care Facilities and the ASHRAE Hand-
monly used in areas where relative pressure relation-
bookHVAC Applications provide guidance and
ships between rooms need not be controlled, for
recommendations for ventilation and humidity in
example, in administrative areas.
such areas (AIA 2001; ASHRAE 1999a). Related
criteria are provided in Chapter 4, Overview of ASHRAE Standard 15 and local codes limit the
Health Care HVAC. use of direct expansion (DX) refrigerant systems in
Special considerations for operating rooms health care facilities (ASHRAE 2001b). Refer to
impose restrictions on HVAC system selection. The Chapter 7, Cooling Plants, for additional informa-
requirements for operating rooms include precise tion on this important system selection limitation.
temperature and humidity controls, as well as space
pressurization, filtration of the supply air, limits on 5.2 HVAC SYSTEMS
allowable recirculation of the air, and ventilation
ASHRAE has classified central HVAC systems
effectiveness of the air delivery system (refer to
into three basic categories: all-air systems, all-water
Chapter 12, Room Design, for details.)
systems, and air and water systems (ASHRAE
A properly designed HVAC system provides
2000a, 1993). Table 5-1 lists HVAC system types
reliable operation, for example, consistent tempera-
that fall in these basic categories.
ture, humidity, and outside air volume and adequate
accessibility to facilitate maintenance of the systems. All-air systems meet the entire sensible and
Proper maintenance of the systems will sustain latent cooling capacity through cold air supplied to
indoor air quality (IAQ) and energy efficiency. Con- the conditioned space. No supplemental heat
sidering future replacement of equipment and acces- removal is required at the zone. Heating may be
sibility for regular maintenance is an important accomplished at the central air handler or at the zone.
aspect of design. Air and water systems condition spaces by dis-
Air-based HVAC systems can be divided into tributing air and water supplies to terminal units
two fundamental categories: constant volume and installed in the spaces. The air and water are cooled
variable air volume (VAV) systems. (Refer to or heated by equipment in a central mechanical

47
48 HVAC DESIGN MANUAL FOR HOSPITALS AND CLINICS

Table 5-1. HVAC System Classifications


HVAC System Category HVAC System
Constant volume, single duct, terminal reheat
Constant volume, double duct
Multizone
VAV, single duct
All-air VAV, dual duct
Primary air with induction units
Primary air with fan coil (for Type B occupancies)
Water-source heat pump
Air and water Fan coil (limited to nonclinical spaces)
Perimeter Radiation
All-water Radiant panels
Packaged terminal air conditioners (PTACs)
Unitary (DX) Packaged split-system air conditioners

room. These systems typically involve air-and-water or exhaust using return or exhaust fans. See Figure
induction units and fan-coil units. 5.1 for general layout of an air-handling system.
All-water systems condition spaces by using
5.3.1 Constant or Variable Volume, Single
chilled water circulated from a central refrigeration
Duct, with Terminal Reheat
plant to heat exchangers or terminal units located in
or adjacent to the conditioned spaces. Heating water Constant volume with reheat systems are cur-
is supplied either through the same piping network rently most commonly used in hospitals. The vari-
or by an independent piping system. Special HVAC able volume with reheat systems are also widely
systems include thermal storage systems, desiccant used, provided pressure relationships are maintained.
systems, and heat recovery systems. Heat recovery See chapter 16 for further details. The reheat aspect
systems are often successfully integrated within the may require justification to some local jurisdictions.
HVAC system. Run-around heat recovery systems See Figure 5-2 for a constant volume reheat system
are commonly used in health care facility designs schematic and Figure 5-3 for a variable air volume
(refer to Chapter 16, Energy Efficient Design and system schematic.
Conservation of Resources).
Advantages
Table 5-2 summarizes HVAC systems typically
HVAC equipment is centralized for ease of
recommended for the functional areas in health care
maintenance
facilities. Final system selection would depend upon
Central equipment can take advantage of
actual layout and design criteria of the facility,
load diversity for optimal sizing
redundancy requirements, and life-cycle cost.
Can use air-side economizers effectively
Provides a great deal of flexibility for multi-
5.3 ALL-AIR SYSTEMS
ple zones
In an all-air system a chiller supplies chilled Provides good dehumidification control
water to one or more air-handling units. The air-han- Well suited for good control of building
dling units consist of mixing plenums where outdoor pressurization
air and return air are mixed, filters (medium or high Good control of ventilation air quantities
efficiency), cooling and/or heating coils, and fans, all Opportunity for high levels of filtration.
contained in an insulated sheet metal housing. Air is
distributed from the air handlers through ductwork Disadvantages
(often medium-pressure) to terminal units and then Reheating of cooled air in constant volume
to the space through a low-pressure distribution sys- systems is not energy-efficient
tem. The terminal units regulate heating of the air First costs can be higher than unitary equip-
with hot water, steam, or electric resistance coils in ment
response to space temperature conditions. Air is Requires mechanical space for equipment
returned from the space to the unit for recirculation rooms, shafts, etc.
HVAC SYSTEMS 49

Table 5-2. HVAC System Applicability

Functional Areaa HVAC Systemb


Constant volume, single duct, terminal reheat
Critical care Constant volume, double duct, VAV with reheat
Unitary systems (refrigerant-based)
Sensitivec [unitary not chilled water]
Constant volume, single duct, terminal reheat
Constant volume, double duct
Multizone
VAV with reheat
VAV, single duct with fan-powered boxes
Clinic Including perimeter radiation (if required)e
Constant volume, single duct, terminal reheat
Constant volume, double duct
Multizone
VAV with reheat
VAV, dual duct
VAV, single duct with fan-powered boxes
Administrative
and Fan-coil (limited to nonclinical spaces)
general support Including perimeter radiation (if required)e
Constant volume, single duct, terminal reheat
Constant volume, double duct
Multizone
VAV with reheat
Dual duct
Support areas (clinical)d Including perimeter radiation (if required)e
Constant volume, single duct, terminal reheat
Constant volume, double duct
Multizone
VAV with reheat
Dual duct
Patient care areas Including perimeter radiation (if required)e
Constant volume, single duct, terminal reheat
Constant volume, double duct
Multizone

VAV with reheat


Laboratory Including perimeter radiation (if required)e
a. Refer to Chapter 3.
b. Refer to Chapter 12 for rationale for systems.
c. Sensitive areas require special environmental controls. Examples include computer rooms, communications rooms, MRI, and other ancillary spaces.
d. Support areas (clinical) include sterile processing, central supply, and food services.
e. See 5.5.1.

5.3.2 VAV, Single Duct with discharge or variable volume. (See Chapter 9 for
Fan-Powered Boxes additional details.)

The VAV terminal units regulate the volume of Advantages


air and often heat the air with hot water, steam, or
Plant equipment is centralized for ease of
electric resistance coils in response to space temper-
maintenance
ature conditions. The terminal units are equipped
with fans (fan-powered) to recirculate room air for Central equipment can take advantage of
energy conservation and temperature control. The load diversity for optimal sizing
fan-powered boxes may be either constant volume Can use air-side economizers effectively
50 HVAC DESIGN MANUAL FOR HOSPITALS AND CLINICS

Figure 5-1 General air-handling system schematic.

Figure 5-2 Constant volume air-handling system schematic (terminal reheat systems).
HVAC SYSTEMS 51

Figure 5-3 Variable air volume air-handling system schematic (terminal reheat systems).

Variable-speed drives for fan volume con- adding zones. These systems can be either constant
trol are cost-effective volume or variable volume. See Figure 5-4 for a
Provides a great deal of flexibility for multi- dual-duct system schematic. Some design variations
ple zones are described below.
Provides good dehumidification control
Good control of ventilation air quantities Dual Fan, Dual Duct
Opportunity for high levels of filtration (Constant or Variable Air Volume)
Can use room air as first stage of reheat. A dual-fan, dual-duct (DFDD) system blends air
from two air-handling units (AHUs) to condition its
Disadvantages zones. The cold deck AHU draws outdoor air, mixes
First costs can be higher than for unitary it with return air, and cools the supply air if neces-
equipment. sary. Economizer control is commonly incorporated.
Special attention to acoustics is required. The neutral (hot deck) AHU filters and recircu-
lates return air. Heat can be added to this airstream.
5.3.3 Dual-Duct Systems
Dual-duct systems distribute air from a central Single Fan, Dual Duct (Variable Air Volume)
apparatus to the conditioned spaces through two par- A central hot air (hot deck) and a central cool air
allel ducts. One duct carries cold air and the other (cold deck) supply are ducted to the terminal unit
warm air, providing air sources for both heating and (double duct) where the cold and hot airstreams are
cooling at all times. mixed and the volume of discharge air is varied to
Dual-duct systems represent a good alternative satisfy the room temperature. The terminal units reg-
to single-duct systems. Dual-duct systems provide ulate the volume of air in response to space tempera-
good control of temperature and humidity, the ability ture conditions. Air is returned from the space to the
to accommodate a variety of zone loads, and ease of air-handling unit for recirculation or exhaust.
52 HVAC DESIGN MANUAL FOR HOSPITALS AND CLINICS

Figure 5-4 Constant volume or variable air volume air-handling system schematic (dual-duct air-handling
units).

Advantages 5.3.4 Multizone Systems


Plant equipment is centralized for ease of
In a multizone system, the requirements of the
maintenance
different building zones are met by mixing cold air
Central equipment can take advantage of
and warm air using dampers at the central air handler
load diversity for optimal sizing
in response to zone thermostats. The mixed condi-
Can use air-side economizers effectively
tioned air is distributed throughout the building by a
Variable-speed drives to control fan volume
system of single-zone ducts. A central chiller plant
are cost-effective
supplies chilled water to the central air-handling
Provides a great deal of flexibility for multi-
unit(s). The air-handling units consist of mixing ple-
ple zones
nums where outdoor air and return air are mixed, fil-
Provides good dehumidification control
ters (medium or high efficiency), cooling and/or
Well suited for good control of building
heating coils, and fans, all contained in an insulated
pressurization
sheet metal housing. Air is returned from the space
Good control of ventilation air quantities
to the air-handling unit for recirculation or exhaust.
Opportunity for high levels of filtration.

Disadvantages
Can be more expensive than unitary equip- Advantages
ment Plant equipment is centralized for ease of
May require substantial duct space that may maintenance
increase the building height Central equipment can take advantage of
Special attention to acoustics is required. load diversity for optimal sizing
HVAC SYSTEMS 53

Can use air-side economizers effectively reheat coil in the induction unit modulates hot water
Provides limited flexibility for multiple flow to maintain space temperature.
zones The following advantages and disadvantages are
Provides good dehumidification control common to all induction systems:
Control of building pressurization is possi-
Advantages
ble
No rotating parts, less maintenance
Good control of ventilation air quantities
Quiet, no noise problems
Opportunity for high levels of filtration.
Local control
Disadvantages Disadvantages
First costs can be higher than for unitary Picks return air at floor level, might pick up
equipment unwanted contaminants from floor.
Requires space for mechanical equipment No local filtration is possible. Manufactur-
rooms, shafts, etc. ers only offer lint screen as option. Certain
May require substantial duct space that may patient rooms require local filtration option.
increase the building height. Lint screen does not meet hospital filtration
standard.
5.4 AIR AND WATER SYSTEMS Requires primary air risers at outside wall.
Requires multiple shafts. Usually two units
5.4.1 Air and Water Induction Units are served from one primary air riser at each
These systems are not recommended for new level. It is expensive. Each shaft needs to be
construction or renovation. They were popular in the rated. Fire dampers may be needed at wall
past and engineers may encounter these systems in penetration.
existing facilities. The description below is for back- No local humidification is possible. Central
ground information only. air system can have humidity control
The induction system consists of an air supply Requires year-round reheat system avail-
from a central air handler, which can be either high- ability.
pressure or low-pressure, connected to a terminal Patient room is out of commission during
unit. The supply air is called primary air and is intro- routine maintenance. Unit requires sched-
duced into the terminal via nozzles. A change of uled maintenance. Deposit of particles from
pressure induces some of the room air to flow return air.
through the unit, hence the name induction. Space
temperature is maintained by coils via a control 5.4.2 Fan-Coil Units
valve controlled by the room thermostat. Variations Fan-coil system units have a finned-tube coil,
on the system, as well as the advantages and disad- filter, and fan section. The fan recirculates air contin-
vantages, are described below. uously from the space through the coil, which con-
tains either hot or chilled water. Some units have
Low-Pressure Induction Unit: Conditioned air from electric resistance heaters or steam coils. The filter is
a central air-handling system is delivered at 0.2 to usually a cleanable or replaceable low-efficiency
0.5 in. w.g. (50 to 125 Pa) pressure to a room induc- (less than 25%) filter that protects the coil from clog-
tion unit. ging with dirt and lint. (Although it is not recom-
mended, units can be connected to dampered
High-Pressure Induction Unit: Conditioned air from openings in the outside wall to provide some outdoor
a central air-handling system is delivered at more air for ventilation.) Fan coils are typically installed in
than 0.5 in. w.g. (125 Pa) pressure to a room induc- a floor-mounted configuration, but horizontal (over-
tion unit. head) models are also available. Fan coils can be
ducted to discharge through several outlets, but fan
Variable Air Volume Induction Unit static pressure capacity is usually very limited. Ven-
A variable air volume induction unit modulates tilation is usually provided by ducting tempered out-
the amount of primary air to a minimum acceptable side air to the return side of the unit or directly to the
value. An induction ratio of one volume of primary space.
air to three volumes of room air provides satisfactory The fan-coil piping system can be either a two-
room air motion and distribution. When required, a pipe or four-pipe configuration. In a four-pipe sys-
54 HVAC DESIGN MANUAL FOR HOSPITALS AND CLINICS

tem, both heating and cooling are available simulta- Advantages


neously, whereas a two-pipe system permits only Flexible to meet needs of each room and its
heating or cooling depending upon the season. specific conditions
Water can transport more heat per unit vol-
Advantages ume than air
System can economically provide many Piping can be revised if room layout is rede-
temperature control zones signed or changed
The system conserves space and is useful Multiple energy sources can be used to heat
where ceiling heights are restricted water or make steam (i.e., gas, oil, electric-
Suitable for low-water-temperature heating, ity, wood, coal, fuel cells, or solar collec-
such as with heat recovery. tors).
Disadvantages Easy to control for comfort by means of
Some fans and motors are very inefficient electric or non-electric flow control valves,
Dehumidification can be a problem where manual control valves, or even variable
high latent loads are present speed circuit pumps
Fan coils are maintenance intensive and Does not transfer contaminants from room
require regular filter replacement and fan to room
and motor lubrication; condensate drain Does not transfer noise from room to room
pans are subject to clogging and overflow Can be decorated and painted to match the
and can present infection control problems surrounding room finish color or window
if located in patient or clinical areas. mullion color.
Fans can be noisy
A two-pipe system can loose temperature Disadvantages
control capability in some seasons Heating only
Fan coil systems can have high first cost. Requires cleaning
Can present infection control problems
5.5 ALL-WATER SYSTEMS May require enclosures.
All-water systems condition spaces by using
chilled water circulated from a central refrigeration 5.5.2 Radiant Panel Systems
plant to heat exchangers or terminal units located in Radiant panels heat or cool a space through the
or adjacent to the conditioned spaces. Heating water emission and absorption of thermal radiation. During
is supplied either through the same piping network heating, the thermal energy emitted by the panels is
or by an independent piping system. All-water sys- absorbed by the objects within a space. Conversely,
tems do not, in themselves, address requirements for panels absorbing energy emitted by objects in a
ventilation, humidity, etc. space accomplish cooling. Both hydronic and elec-
tric panels are available for heating applications.
5.5.1 Perimeter Radiation Only hydronic panels are available for cooling. Radi-
Baseboard (perimeter) radiation offsets heat loss ant systems are designed to handle the sensible loads
from building envelopes. Cooler room air near the within a space; the overall supply air requirements
floor migrates toward the exterior walls and windows can therefore be limited to the fresh air ventilation
where heat loss is occurring. As the air moves to the requirements. In cooling applications, however, the
wall, it is drawn upward into and over the higher ventilation air must be sufficiently dehumidified in
temperature finned radiation element. The rate of order to absorb the latent load of the space. Concerns
heat output can be controlled by varying the temper- related to condensate formation in cooling applica-
ature of the heated media (steam or hot water) inside tions are addressed by the combined use of dew-
the tube of the finned element. The flow of heated point and moisture sensors that regulate the supply
water being pumped through the tubing can be varied water temperature and maintain it above the dew
by different control devices, creating a wider range point of the space.
of heat outputs. Baseboard enclosures are available
in a wide variety of shapes, sizes and heat outputs. Advantages
They can be wall mounted, floor mounted or Aesthetically unobtrusive and easy to clean
recessed in the wall or floor. Enclosed fin tube radia- Applicable to any ceiling type.
tion is not recommended for patient care areas. Can minimize the sensation of drafts.
HVAC SYSTEMS 55

Allow full utilization of floor area (i.e., no Does not handle interior spaces
space required for fan coils) Poor filtration
Virtually silent Less energy efficient than central systems.
Individual zone control
No infection control problems 5.6.2 Packaged Single-Zone Split System
A packaged single-zone split system uses uni-
Disadvantages tary (factory fabricated) equipment that is fully self-
Lower output than finned tube style base- contained to provide heating and cooling. The sys-
board tem consists of an indoor package and an outdoor
Requires a separate system for ventilation package that are connected with refrigerant piping
First cost can be higher than for comparable and controls. The indoor package has a supply fan,
systems filters, a direct expansion cooling coil, and heating,
Condensation can occur in cooling applica- e.g., hot water, steam, electric resistance, etc. The
tion unless the chilled-water temperature is outdoor unit has compressor(s), condenser coil, and
kept above the dew point. condenser fans. Units can be purchased as heat
pumps. Packaged single-zone split systems are typi-
5.6 UNITARY REFRIGERANT-BASED
cally controlled from a single space thermostat, and
SYSTEMS FOR AIR CONDITIONING
one unit is provided for each zone.
The model codes place restrictions on refriger-
ants in health care occupancies. (Refer to Chapter 7, Advantages
Cooling Plants, for additional information on this Low initial cost, but more than package
topic.) rooftop systems
Can be used where there is limited outside
5.6.1 Packaged Terminal Air Conditioners space available
Packaged terminal air conditioners (PTAC) are a
Disadvantages
class of commercially available equipment usually
used to heat and cool a single room. The units are Requires space inside the building
fully self-contained and consist of a fan, filter, direct Requires separate relief when economizers
expansion cooling coil, compressor, air-cooled con- are used
denser coil, and condenser fan, all encased in an Distance between indoor unit and outdoor
enclosure made for through-the-wall applications. unit is limited
Heating from PTAC units is usually from electric Limited zoning capability
resistance coils. The units can also be purchased as Poor dehumidification control
heat pumps provided with the proper refrigeration Uses more energy than a central system.
accessories. Units can be equipped with ventilation Limited capacity to handle ventilation air.
openings of limited size and capacity.
5.6.3 Packaged Rooftop VAV or
Advantages Constant Volume Unit
Low initial cost A packaged rooftop variable air volume air-con-
Very good for tenant submetering ditioning system uses unitary (factory fabricated)
Requires only small amount of space at equipment. The unit is fully self-contained and con-
perimeter of building. sists of a supply fan; a direct expansion cooling coil;
heating (when required) with a gas burner, hot water,
Disadvantages steam, or electric resistance; filters; compressors;
Poor dehumidification control condenser coils; and condenser fans. Units are usu-
No economizer operation ally equipped with outdoor air economizer sections
Increased maintenance due to multiple units that have no relief, barometric relief, or power relief
Condensate removal during periods of fans. Units are typically mounted on roof curbs but
heavy condensation can also be mounted on structural supports or on
Limited ventilation control grade. Air is distributed from the unit through duct-
Can be very noisy work (often low-pressure) to terminal units and then
Architectural impact on building envelope to the space through a low-pressure distribution sys-
Can create drafts and have poor air distribu- tem. The terminal units regulate the volume of air
tion and often heat the air with hot water or electric resis-
56 HVAC DESIGN MANUAL FOR HOSPITALS AND CLINICS

tance coils in response to space temperature condi- Better dehumidification control than pack-
tions. Sometimes, the terminal units are equipped aged single-zone systems
with fans (fan-powered) to recirculate room air for Energy efficiency available through vari-
energy conservation. Sometimes a separate central able air volume operation.
hot air (hot deck) system is ducted to the terminal
unit (double duct) where the cold and hot airstreams Disadvantages
are mixed and the volume of air is varied to satisfy Can impact building aesthetics
the room temperature. Air is returned from the space
Higher maintenance than chilled water sys-
to the unit for recirculation or exhaust. Return/
tems
exhaust fans can be used for this purpose or the sup-
ply fan can be assisted by a power exhaust (spill) fan. Limited capacity to handle ventilation air
VAV systems generally incorporate by-pass air to Limited filtration
keep the evaporator coil from freezing during low Requires structural supports and roof pene-
loads. trations
A constant volume unit will not contain the Limited pressurization capability
above-described VAV components. May not be able to provide close tempera-
ture control.
Advantages
Low initial cost for buildings that require
5.6.4 Summary
multiple zones
Compact arrangement uses no inside System selection is a complicated process that
mechanical room space and very little shaft requires input from all affected stakeholders. Refer
space to Chapters 4, 12, 14, 15, and 16 for related topics.
CHAPTER 6
DESIGN CONSIDERATIONS
FOR EXISTING FACILITIES
6.1 GENERAL CONSIDERATIONS FOR Systems may be energy-intensive.
EXISTING FACILITIES There may be a lack of sufficient clearance for
adequate maintenance.
6.1.1 Typical Existing Conditions There may be significant deferred mainte-
After their initial construction, most hospitals go nance.
through extensive remodeling, upgrading, and addi-
tions. In many cases, the HVAC systems currently 6.1.2 Facilities Condition Assessment (FCA)
installed represented the best technology available at
To understand the capabilities and limitations of
the time. Thus, most hospitals have a wide variety of
an existing HVAC infrastructure, a comprehensive
HVAC system types, ages, and conditions of equip-
evaluation and master plan are needed. Such a plan is
mentand usually physical space limitations. The
referred to as a facilities condition assessment
following are typical conditions and issues encoun-
(FCA). The facilities condition assessment is a pro-
tered in existing health care facilities.
cess in which a facilitys site utilities, architecture,
and engineering infrastructure are surveyed and eval-
Air filtration may not be up to current standards.
uated to identify deficiencies and the capital
Older equipment may not have the capacity to
resources required to correct the deficiencies (Hab-
meet new cooling loads or may be at end of its
bas and Martyak 2000). Deficiencies may cover a
life cycle.
variety of issues such as:
Controls may be olderin need of upgrade or
lacking in performance.
Indoor air quality
Ductwork may be dirty, especially return and
Deferred maintenance
exhaust ducts.
Hydronic systems may exhibit deterioration of End of life cycle
piping. Regulatory agency requirements
Systems may not be appropriate for changing Technology-driven obsolescence
functions/technology, such as required to Equipment inefficiency
change a patient room into a laboratory space. Lack of capacity
There may be a lack of balancing capability,
with resulting improper air or water flow. The following are key elements of a facilities
Systems are in dire need of retro-commissioning condition assessment:
and may not have performed from day one.
Central chiller plants may contain CFCs and/or Identify each system and the areas and sub-
need to be upgraded due to age of equipment, systems served. Assess the age, condition, and
lack of flexibility, or capacity. longevity of major systems and equipment.
Horizontal or vertical space for distribution may Identify capacities of equipment and major dis-
not be available to permit addition of new sys- tribution systems. Identify spare capacity and
tems or elements. capacity deficiencies.

57
58 HVAC DESIGN MANUAL FOR HOSPITALS AND CLINICS

Evaluate regulatory compliance issues such as 6.2 INFECTION CONTROL DURING


filtration, ventilation quantities, duct lining, life CONSTRUCTION
safety, etc.
Interview staff and develop an understanding of 6.2.1 Introduction
ongoing maintenance problems, lack of access, Construction and renovation projects in health
deferred maintenance, etc. care facilities require special attention to infection
Prepare alternatives for upgrading or replacing control due to the presence of:
systems on a priority basis. Determine the phas-
Susceptible patients, including immunosup-
ing of the implementation plan. Plan for hori-
pressed patients
zontal and vertical distribution, continuity of
Invasive surgical procedures
service, and maintaining pressure relationships
during and after construction. Integrate architec- Special hazards for workers and hospital staff
tural, electrical, and structural elements into the such as autopsy rooms, nuclear medicine, etc.
plan.
Numerous incidents reinforce the importance of
Estimate costs and time line for implementation. infection control planning. For example, in a mid-
Establish priorities based upon (1) serious life western hospital, a small two-room remodeling
safety deficiencies, mandatory regulatory com- project resulted in the death of a patient when con-
pliance requirements, replacement of failed struction dust contaminated with Aspergillus
equipment; (2) improvements in services or migrated into the patients room through a toilet
attractive rates of return; and (3) long-term room exhaust duct that was common to the patients
improvements to services and infrastructure. room and the room under construction.
Hospital construction and renovation projects
6.1.3 Considerations for Design and Con- can vary in size from major multimillion dollar addi-
struction of Renovations and Additions tions to small one- or two-room renovations. Com-
mon sense dictates that any remodeling requires the
Renovations and additions often require a use of barriers around the work site, including tem-
change or disruption to existing systems and distri- porary walls and partitionsbut the hospital envi-
bution. Continuity of service to areas served by ronment requires special care and provisions.
equipment that is not being changed must be consid-
ered. The following steps are essential for successful 6.2.2 Strategic Planning
renovations.
The AIA Guidelines for Design and Construc-
tion of Hospitals and Health Care Facilities states
Do a pre-construction air and water balance to that design and planning for such [renovation and
determine conditions before the project starts. new construction] projects shall require consultation
The idea is to return areas not changed to the from infection control and safety personnel. Early
same conditions as before the remodeling. involvement in the conceptual phase helps ascertain
Ensure that plans for remodeling include strate- the risk for susceptible patient(s) and [the risk of]
gies to protect areas not under construction from disruption of essential patient services (AIA 2001).
dust (see later discussion). This consultation in the initial stages of planning and
Ensure that HVAC systems serving areas other design is termed an infection control risk assess-
than the construction zone maintain adequate air ment (ICRA).
flows and pressure relationships during con- The ICRA should be carried out by a multidisci-
struction. plinary planning group that involves, at minimum,
Ensure that air supplied to the construction zone representatives from the Infection Control/Epidemi-
is not recirculated to other areas. ology Department, architects, engineers, contractors,
facilities, and administration. As a minimum, the
Prepare for continuity of service as mentioned in groups assessment should address the following:
Chapter 4. Plan for temporary HVAC equipment
when necessary and for timely and orderly shut- Coordination of construction preparation and
down of equipment when needed. demolition
Consider if a redesign of the mechanical room is Operating and maintaining facilities during con-
needed for compliance with refrigerant stan- struction
dards. (See section 7.2) Postconstruction cleanups
DESIGN CONSIDERATIONS FOR EXISITING FACILITIES 59

Monitoring during and after construction Demolition: Debris should be removed in


Contractor accountability in the event of a carts that have tightly fitted covers, using
breach in infection control designated traffic routes. If chutes are used
Patient risk to conduct debris outside, HEPA-filtered
Health expectations for the contractors workers fans should maintain negative pressure in
Traffic patterns during construction the chute, and chute openings should be
Transportation and disposal of waste materials sealed when not in use. Filters should be
Emergency preparedness plan bagged and sealed before being transported
out of the construction area.
There may be a need to consult environmental Exterior Windows: Windows should be
experts if the size and complexity of construction sealed to minimize infiltration.
will create considerable risk to patients because of
location, prolonged time of construction, work con- Ventilation Control
ducted in continuous shifts, or continual interruption Air-handling systems that serve areas under
of air-handling unit operations. construction should be turned off, and all supply and
return air openings in the construction area should be
6.2.3 Construction and Renovation Control sealed. If this is not practical, provide filters over all
return openings. Filters should be not less than 95%
Preparations for Demolition efficient according to ANSI/ASHRAE Standard 52.1-
Before construction begins, preparations should 1992, Gravimetric and Dust-Spot Procedures for
focus on isolating the construction/renovation area. Testing Air-Cleaning Devices Used in General Venti-
Define the type and extent of the project. Projects lation for Removing Particulate Matter. Heavy work
vary regarding time, number of workers, degree of in an area may require dampering off or otherwise
activity, and proximity to patients who have varying blocking systems during construction periods if the
degrees of risk for infection. Patient areas or units resulting temporary air imbalance does not affect
that cannot be closed or that are adjacent to a major other areas served by the system(s) (SMACNA
renovation require special planning. External excava- 1995).
tion is ideally conducted during off-hours, so that Negative Pressure: Spaces under construc-
air-handling units can be shut down and sealed to the tion should be maintained at negative pres-
extent possible. sures with respect to the adjacent areas not
under construction. This should be achieved
Dust and Debris Control by using separate construction exhaust fans
Medical Waste Containers: All medical ducted to the outside, so that recirculation is
waste containers should be removed from not possible. If the exhaust cannot be
the construction area before demolition ducted to the outside and must be returned,
starts. the exhaust should be filtered to at least
Barrier Systems: Small projects that gener- 95% before it is recirculated. Adjacent
ate minimal dust should use fire-rated plas- areas should be rebalanced to maintain pos-
tic sheeting, sealed at full ceiling height, itive pressure with respect to the construc-
and with at least 2-foot overlapping flaps tion zone.
for entry access. Any project that generates
Source Exhaust: Some pollution sources
moderate to high levels of dust requires
can be exhausted directly outdoors using
rigid, dust-proof, and fire-rated barrier
portable fans. These exhausts may require
walls with caulked seams. Large, dusty
filtration before discharging air to the atmo-
projects need an entry vestibule for clothing
changes and tool storage. This entry vesti- sphere.
bule barrier should have gasketed doors and Vibration: Core drilling or other sources of
tight seals along the entire perimeter of the vibration should be minimized.
walls and at all wall penetrations. An Monitoring: Consider providing airflow
interim plastic barrier may need to be sensing devices in construction barriers to
installed while the rigid impervious barrier signal when negative pressures are not
is being constructed. maintained.
Traffic Control: Designated entry and exit Cleanup should be done by vacuuming with
procedures must be defined. a HEPA-filtered fan device.
60 HVAC DESIGN MANUAL FOR HOSPITALS AND CLINICS

Worker Protection Training: Training must alert workers to the


Worksite Garb: Contractor personnel cloth- potential for airborne dust containing
ing should be free of loose soil and debris spores of microorganisms. Duct and piping
before leaving the construction zone. When demolition or modification may involve
workers are in invasive procedure areas, risks of fungal or other types of contamina-
they should be provided with disposable tion. Workers must be trained to work in
jump suits and head and shoe coverings. asbestos-containing areas.
Workers may need protective gear (for
Health Protection: Workers may need
example, respirators) for specific tasks.
health protection, vaccinations, skin tests
Facilities Cleaning: The work site should
for tuberculosis, testing for hepatitis, and
be cleaned routinely.
education before beginning construction.
Intermittent Operation of Services
Dust and particles are released when fans and 6.2.4 Post-Construction Cleanup
other mechanical systems start and stop. Policies
should require delaying invasive procedures until The contractor should be responsible for clean-
sufficient time has elapsed after fans and systems ing up the project, including work site clearance,
have been restarted following shutdown. cleaning, wiping down, and decontamination. The
contractor should minimize dust production while
Worker Risk Assessment and Education removing partitions around the construction area. All
Facilities staff should assist the contractor in filters should be replaced. The infection control risk
determining potential environmental risks for work- assessment should identify all post-construction
ers. cleanup requirements for the contractor.
CHAPTER 7
COOLING PLANTS
7.1 INTRODUCTION A wide variety of refrigerants is used in the air-con-
Most hospitals have one or more central chilled ditioning process, including halocarbons, ammonia,
water plants that represent a major investment in the propane, carbon dioxide, and plain water.
facility and can also be one of the primary consum- To be useful, refrigerants must have low toxic-
ers of energy. Most clinics use packaged cooling/ ity, low flammability, and a long atmospheric life.
heating equipment. Recently, refrigerants have come under increased
This chapter describes the components that scrutiny by scientific, environmental, and regulatory
make up a central chilled water plant. A wide variety communities because of the environmental impacts
of equipment is available on the market. Selecting attributed to their use.
the correct type is the first step in owning and operat- Refrigerants are classified into groups according
ing a central chilled water plant. Chilled water plants to toxicity and flammability. For toxicity, there are
are systems that meld many different components, two classes based on Permissible Exposure Limits
including chillers, heat rejection devices, pumps, (PEL) greater than 400 ppm (Class A) and less than
piping, and controls into a comprehensive entity to 400 ppm (Class B). For flammability, there are three
provide mechanical cooling to a facility. Also dis- classes ranging from Class 1 materials that do not
cussed in this chapter are design considerations for propagate flame to Class 3 materials that are highly
formulating an effective plant. The chapter briefly flammable. Refrigeration systems are also classified
looks at the instrumentation and controls that are so according to the probability that a leakage of refrig-
important to a successful plant. Finally, the start-up erant could enter a normally occupied area. In high-
and commissioning process is reviewed to empha- probability systems, leakage from a failed connec-
size how a well-designed and well-constructed plant tion, seal, or component could enter an occupied
can ensure delivery of efficiently produced chilled space. Such is the case with direct expansion cooling
water to air-condition a facility. coils and/or refrigeration components located within
the occupied space. Low-probability systems include
7.2 DESIGN CONSIDERATIONS those whose joints and connections are effectively
isolated from occupied spaces. This is the case with
7.2.1 Use of Refrigerants in a chillers, condensers, and other equipment located in
Hospital Environment refrigeration machine rooms isolated from normally
In its simplest form, refrigeration is the process occupied spaces.
of moving heat from one location to another by using ANSI/ASHRAE Standard 15, Safety Standard for
refrigerants in a closed cycle. For purposes of this Refrigeration Systems, limits the quantity of refriger-
manual, the discussion of refrigeration will be con- ant in a high-probability system based upon occu-
fined to air-conditioning applicationsas opposed to pancy group or division and the type of refrigerant
refrigeration for food storage, ice making, etc. Hos- (ASHRAE 2001b). The standard further limits the
pitals use air-conditioning to remove heat from allowable quantity of refrigerant in a high-probabil-
spaces and ventilation air to maintain comfort and a ity system for institutional occupancies (hospitals) to
healthy environment and to assist in treating patients. 50% of the values listed for other types of occu-

61
62 HVAC DESIGN MANUAL FOR HOSPITALS AND CLINICS

pancy. Many code authorities have adopted 7.2.3 Siting the Central Plant
ASHRAE Standard 15, and some have adopted even Many hospital planners are primarily focused on
more stringent rules for hospital environments. In the relationship of various medical functions and
fact, a number of jurisdictions do not allow high-
may have a tendency to minimize the importance of
probability refrigeration systems at all in the hospital
the central plant location on the long-term cost and
environment. Because of these safety concerns, cen-
flexibility of a facility. When designing a new
tral chilled water systems have been preferred for
project, the location of the central cooling plant rela-
acute care hospitals.
tive to other elements in the facility is a critical deci-
When applying any type of high-probability
sion. Numerous factors should be taken into account
refrigerant system, particularly packaged rooftop air
to determine the best location for this equipment.
conditioners, the designer should verify the quantities
Some of these factors include:
of refrigerant in the system (usually within a given cir-
cuit) and the acceptability of that volume to the author-
Locations relative to other physical elements
ity having jurisdiction. Calculating the acceptable
Maintenance considerations
quantities of refrigerant can be tricky. Refer to
Location of cooling towers and air-cooled con-
ASHRAE Standard 15 for methods and tables of
densers
acceptable quantities of refrigerant expressed in lb/
1000 ft3 (equivalent to kilograms/62 m3) of occupied
Centralizing primary mechanical equipment has
space.
advantages in operation and maintenance that may
7.2.2 Machine Room Design be obvious but are worth reviewing here. If the cool-
ing plant is located near and equidistant to the loads
ASHRAE Standard 15 requires that equipment served, cost savings are possible due to shorter and
must be located outdoors or within a machinery smaller distribution piping, and transportation
room when the quantity of refrigerant in the system energy for moving fluids to and from the loads being
exceeds established limits. Machinery rooms are also served can be reduced. There are other issues to con-
required when the aggregate compressor horsepower sider when determining the best location for the cen-
is 100 hp (75 kW) or more. A machinery room must tral plant. These include:
be designed within strict guidelines, some of which
require: Location near shipping/receiving facility
The aesthetic impact of mechanical equipment
Continuous and emergency ventilation separate
on the site
from other building systems
Ease of access for maintenance personnel
Continuous monitoring, equipment shutdowns,
and remote alarms Future expansion capability
No open flames Acoustical impact of equipment
Tight fire-rated room and door construction Safety in the event of a refrigerant discharge
Exit directly to the outdoors Locations of heat rejection devices relative to
Special signage airflow, noise, and plume abatement
Restrictions on the location of relief and exhaust
When considering the maintenance aspects of
outlets and intakes
the central plant location in the hospital, one must
The chiller plant (machine room) should not be take into account that hospitals are seldom static in
located within the same space as other mechanical or the long term. This means that the central plant must
electrical equipment, except that equipment directly be designed with some consideration to future
related to operating the chillers. The chiller plant expansion. Consideration should be given to provid-
should not be located within a boiler room, except ing space for additional machinery or replacing cool-
when the boiler combustion chamber and air supply ing equipment with larger capacity machines. This
are completely isolated from the room. When retro- may mean that space is left for future equipment or
fitting or upgrading an existing chiller plant, care that the central plant space can be expanded in the
should be taken to include an upgrade of the machin- future.
ery room where needed. This typically means that, as Another important consideration when planning
a minimum, the chiller must be enclosed separately a hospital central cooling plant is that machinery will
from the boilers and other equipment in accordance eventually need to be replaced due to age, failure, or
with the requirements of Standard 15 and that emer- changing technology. A plan for removing large
gency ventilation systems must be installed. equipment must be incorporated into the original
COOLING PLANTS 63

design. Wall or roof openings can be built that are


easily removable; cranes and other heavy equipment
must have access to the machine room; and aisles for
moving equipment should be built into the original
design. If the mechanical space is located in the
upper portions of a building, elevator access to the
mechanical space is essential because large equip-
ment, tools, and chemicals need to be brought in reg-
ularly. A fully accessible stairway to the roof is the
minimum acceptable access for roof-mounted equip-
ment. Ship ladders and roof hatches for access cost
less in the short term but are bound to result in addi-
tional long-term operating expense.
The central plant must be designed so that main- Figure 7-1 Typical chilled water plant.
tenance of equipment is the first priority. This means
that manufacturers recommended clearances around
and above equipment must be adhered to. Space effects. Considering recirculation phenomena when
must be allocated for tube pull clearances, motor selecting equipment capacities is good practice.
removal, and portable (or permanent) gantries for
compressor removal. Sufficient space must be allo- 7.2.4 Sizing the Central Plant
cated for inlet/outlet air for heat rejection equipment. When sizing a central cooling plant, keen under-
Figure 7-1 illustrates a typical large chilled water standing of chiller plant cooling loads and how they
plant. vary with time is fundamental to proper design.
When planning for cooling towers and air- Designers are encouraged to use life-cycle cost anal-
cooled condensers, consideration must be given to ysis as a basis for selecting equipment and optimiz-
their location relative to the site. Heat rejection ing the design. If an existing plant is being modified
or expanded, the ability exists to monitor the current
equipment may have significant acoustical impact.
cooling load and obtain both an accurate peak load
This is especially true when these devices are located
and a cooling load profile. The plant may have a
near residential property or within easy line-of-sight
building automation system that has trend logs for
to patient spaces. Acousticians may need to deter- monitoring peak loads. Often, a good operator can
mine if mitigation is necessary for these devices. very accurately report the percentage of full load that
Cooling towers have a tendency to create unsightly a plant experiences during peak weather conditions.
plumes during conditions of low temperature and Before a chilled water plant is designed, it is
high humidity. This may preclude locations adjacent essential to understand how the plant will be oper-
to roadways, for example. ated and what loads it will be expected to handle
The use of cooling towers has been linked to the throughout its service life. Certain key load parame-
outbreak of certain airborne diseases such as Legion- ters affect the cooling load profile and, consequently,
the nature of the plant design. The following are
ellosis. The location of building outdoor air intakes
some of these key parameters:
must be carefully considered relative to the possibil-
ity of recirculation from a cooling tower plume. The use of outdoor air economizers
Standard code minimum distances for separation are The use of 100% outdoor air units
sometimes not adequate to protect the health of Hours of operation
occupants. When cooling towers and air-cooled con- Constant loads from a process or data center
densers are located close to building elements or in
Process requirements for a fixed chilled water
wells or pits, there may be a tendency to recirculate temperature
air from the discharge back into the equipment
intakes. Such recirculation can severely degrade the The process for estimating peak cooling loads in
performance of the equipment. Even equipment new construction is explained thoroughly in Chap-
located in the open but adjacent to other similar ters 26 through 31 of the 2001 ASHRAE Handbook
devices can experience recirculation due to wind Fundamentals (ASHRAE 2001a). The basic vari-
64 HVAC DESIGN MANUAL FOR HOSPITALS AND CLINICS

ables for peak-load calculations include weather 7.2.5 Fuel Choices


conditions, building envelope, internal heat gain,
The primary equipment choices for central
ventilation, and, to a lesser extent, infiltration. Less
chilled water plants include electrically driven equip-
obvious, but nonetheless important, are diversity
among the various load elements and the effects of ment, fossil-fuel driven equipment, or a combination
thermal mass. The diversity of loads is a measure of of the two. Fossil-fuel driven equipment can employ
the simultaneous occurrence of varying peak loads. direct-fired or steam absorption chillers, or engine
In other words, it is a measure of the likelihood that driven chillers. The choice of fuel depends on many
the occupancy, lighting, and plug loads will each factors but is based primarily on life-cycle cost anal-
peak at the same time as the envelope load peaks. ysis. A life-cycle cost analysis compares different
Recent research by ASHRAE points out that peak alternatives and takes into account the first cost,
cooling conditions do not always occur at maximum annual operation and maintenance costs, future oper-
design dry-bulb temperatures (and their associated ation and maintenance cost inflation, and the time
mean coincident wet-bulb conditions) but rather at value of money.
times of peak wet-bulb temperatures and their asso- One of the most important elements of the selec-
ciated mean coincident dry-bulb conditions. This can tion process is an accurate estimate of the energy
be especially true when ventilation rates are very usage of each of the options. The appropriate level of
high as in health care facilities. accuracy and detail necessary for energy calculations
There is inherent uncertainty in the peak load depends upon the size of the project and the engi-
calculation. Any number of the following elements neering budget. Even for very small projects, chiller
can make the actual load differ from a calculated plant modeling tools accurately estimate chiller plant
load: performance. For existing projects, measured perfor-
mance data may be available for use.
Design conditions can vary depending on the
building location relative to the weather station The utility rates used in an analysis are very crit-
from which the data were taken. ical because they will vary with time and are difficult
Weather conditions can vary over time, as a to predict. Given this uncertainty, it is often neces-
result of increasing urbanization and/or changes sary to assume simply that current rates, or some-
in land use. thing similar, will be in effect during the chiller
Building envelope elements are not always what plants life cycle.Virtually all utilities charge for
were planned. energy consumption and for demand. Because chill-
Changes occur in the operation and maintenance ers are one of the largest energy users in typical
of the plant and buildings. buildings, it is essential to take demand charges
Ventilation rates can vary. properly into account. This is particularly true when
Equipment loads can significantly differ from demand charges are ratcheted, which means that the
those that were planned for and can vary over owner pays some percentage of the maximum peak
time. demand during the year, regardless of the actual
monthly demand.
For most designers, the perceived risks of under- Other factors that enter into fuel choice decision
stating the peak load condition (undersizing the cool- making include the need to operate the chiller plant
ing plant) are much greater than those of overstating during prolonged power outages and the availability
the peak load. An undersized cooling plant may not of waste heat from a cogeneration, solar, or biomass
meet the owners expectations for comfort and may
source. In some cases, the availability of a fuel or the
impact the ability to provide essential services. Con-
cost of bringing a fuel onto the site may determine
versely, oversizing the cooling plant carries an incre-
the best alternative.
mental cost penalty that is not always easy to
identify. An oversized plant may not be as energy- With the deregulation of the electric utility
efficient as a smaller plant. The tendency is for industry, more emphasis will be placed on the time
designers to maximize assumptions for peak load of day when peak loads occur. It is likely that incen-
and to add safety factors at several levels in the cal- tives for operating a cooling plant during off-peak
culation process. Conversely, diversity of loads is not hours will make thermal storage an attractive alterna-
always well understood. One must acknowledge that tive. Such cost incentives should be incorporated into
uncertainties in developing the peak cooling load and the life-cycle cost analysis to make an optimum
the annual load profile are unavoidable. chiller plant fuel selection.
COOLING PLANTS 65

7.2.6 Chiller Performance and electrically driven chillers are also expressed in
Energy Efficiency Ratings terms of kilowatts per ton (kW/kW) for peak ratings,
A number of variables determine the operating IPLV, and NPLV. This is simply another way of
characteristics and energy performance of water describing the COP [COP 3.516/(kW/ton)]. The
chillers (DuPont 2000). A chiller is selected to meet lower the kW/ton (kW/kW), the more energy-effi-
a specific requirement for maximum capacity under cient the machine.
certain design conditions, to have limited energy Table 7-1 provides a comparison of typical
consumption at these conditions, and to have specific energy efficiency ratings for various types of water
part-load operating characteristics. chillers.
Under peak design conditions, water chiller effi-
7.2.7 Heat Rejection
ciency is rated by the coefficient of performance
(COP). COP is the ratio of the rate of heat removal to One of the prime objectives of a chilled water
the rate of energy input in consistent units for a com- plant is to reject unwanted heat to the outdoors
plete refrigerating system or some specific portion of (DuPont 2000). This is accomplished in a number of
that system under designated operating conditions. different ways. Although a number of heat sinks
The higher the COP value, the more energy-efficient have been used as places to reject heat (including
the machine. ASHRAE Standard 90.1-2001 estab- cooling tower ponds, lakes, rivers, groundwater, and
lishes minimum energy efficiency standards for city water) the primary means of heat rejection in the
water chillers (ASHRAE 2001d). Many local juris- HVAC industry are the cooling tower, the air-cooled
dictions have adopted the ASHRAE standard as refrigerant condenser, and the evaporative refrigerant
code-minimum performance. condenser.
Another useful energy efficiency rating is the
integrated part-load value (IPLV). The IPLV is a Cooling Towers
single-number figure of merit based on part-load Simply put, evaporation is a cooling process.
COP or kilowatts per ton (kW energy input/ kW More specifically, the conversion of liquid water to
cooling output). The part-load efficiency for equip- the gaseous phase requires the introduction of the
ment is based on weighted operation at various load latent heat of vaporization. Cooling towers use the
capacities. The equipment COP is derived for 100%, heat from condenser water to vaporize water in an
75%, 50%, and 25% loads and IPLV is based on a adiabatic saturation process. A cooling towers
weighted number of operating hours (assumed) design exposes as much as possible of the waters
under each conditionexpressed as a single part- surface area to air in order to promote the evapora-
load efficiency number. tion of water. The performance of a cooling tower is
The non-standard part-load value (NPLV) is almost entirely a function of the ambient wet-bulb
another useful energy efficiency rating. This is used temperature. The ambient dry-bulb temperature has
to customize the IPLV when some value in the stan- an insignificant effect on the performance of a cool-
dardized IPLV calculation is changed. Efficiencies of ing tower.

Table 7-1. Energy Efficiency Ratings of Typical Water Chillers

Chiller Type Capacity Rangea COP Rangea IPLV Rangeb


50230; 400
Reciprocating (176-809; 1407) 4.25.5 4.65.8
70400; 1250
Screw (246-1407; 4396) 4.95.8 5.46.1
2002000; 10,000
Centrifugal (703-7034; 35170) 5.87.1 6.57.9
1001700
Single-effect absorption (352-5979) 0.600.70 0.630.77
1001700
Double-effect absorption (352-5979) 0.921.2 1.041.30
1003000; 10,000
Gas engine driven (352-10551; 35170) 1.51.9 1.82.3
a. Capacity range is indicated as xx-xxx, followed by the maximum sizes available; units are tons (kW); COP values are for the range of typical capaci-
ties indicated.
b. COP units are (Btu per hour output)/(Btu per hour input) (kW output/kW input).
66 HVAC DESIGN MANUAL FOR HOSPITALS AND CLINICS

Cooling towers come in a variety of shapes and Packaged air-cooled chillers are available with
configurations. A direct tower is one in which the capacities up to 400 tons (1410 kW). Air-cooled
fluid being cooled is in direct contact with the air. chillers are used for a number of reasons:
This is also known as an open tower. An indirect
tower is one in which the fluid being cooled is con- Water shortages or water quality problems.
tained within a heat exchanger or coil and the evapo- Lower first cost than water-cooled equipment.
rating water cascades over the outside of the tubes. No need for machine rooms with safety moni-
This is also known as a closed-circuit fluid cooler. toring, venting, etc., for packaged air-cooled
Tower airflow can be driven by a fan (mechanical chillers.
draft) or can be induced by a high-pressure water Less maintenance required than with cooling
spray. Mechanical draft units can blow the air towers.
through the tower (forced draft) or can pull the air Air-cooled chillers are not as energy-efficient as
through the tower (induced draft). The water in a water-cooled chillers. When comparing the
cooling tower invariably flows vertically from the energy efficiency of air-cooled to water-cooled
top down, but the air can be moved horizontally chillers, care must be taken to include the energy
through the water (cross-flow) or can be drawn verti- consumed in the water-cooled chiller by the
cally upward against the flow (counterflow). condenser water pump and cooling tower. Air-
cooled chillers have very good part-load perfor-
Chemical Treatment and mance; the COP also improves significantly as
Cleaning of Cooling Towers the air temperature drops.
Cooling towers are notorious for requiring high Evaporative Condensers
maintenance. Cooling towers have been linked with
Evaporative condensers use a pump that draws
the outbreak of Legionellosis (Legionnaires disease).
water from a sump and sprays it on the outside of a
Cooling towers are very good air scrubbers and can
coil. Air is blown (or drawn) across the coil and
accumulate substantial quantities of dirt and debris as
some of the water evaporates, causing heat transfer.
they operate. Because they are open to the atmo-
Evaporative condensers are primarily used in the
sphere, the water is oxygen-saturated, which can
industrial refrigeration sector and have little applica-
cause corrosion in the tower and associated piping.
tion in the HVAC industry. Some manufacturers,
Towers evaporate water, leaving behind calcium however, produce small packaged water chillers with
carbonate (hardness) that can precipitate out on the evaporative condensers as an integral component.
chiller condenser tubes and decrease heat transfer
The effectiveness of the heat transfer process
and energy efficiency. Towers must be cleaned and
means that for a given load, evaporative condensers
inspected regularly. Well-maintained and regularly
can have the smallest footprint of any heat rejection
cleaned cooling towers have generally not been asso-
method. An evaporative condenser produces lower
ciated with outbreaks of Legionellosis. It is best to
condensing temperatures and, consequently, is far
contract with a cooling tower chemical treatment
more efficient than air-cooled condensing. Mainte-
specialist.
nance and control requirements for evaporative con-
densers are similar to those of closed-circuit fluid
Air-Cooled Refrigerant Condensers
coolers.
Another method of heat rejection commonly
used in chiller plants is the air-cooled refrigerant 7.3 OPTIMIZING ENERGY EFFICIENCY
condenser (ASHRAE 2001b). This can be coupled Normally, chilled water plants run at peak load
with the compressor and evaporator in a packaged for only a few hours a year. During the remainder of
air-cooled chiller or can be remotely located. Remote the time, a plant operates at part load. The following
air-cooled condensers are usually located outdoors factors are key to designing a chilled water plant for
and have propeller fans and finned refrigerant coils optimum efficiency:
housed in a weatherproof casing. Some remote air-
cooled condensers have centrifugal fans and finned Number and size of chillers
refrigerant coils and are installed indoors. The maxi- Type and size of heat-rejection devices
mum size for remote air-cooled refrigerant condens- Peak and part-load efficiency of chillers
ers is about 500 tons (1760 kW), but 250 tons (880 Evaporator and condenser water temperatures
kW) is more common. Remote air-cooled condens- Temperature difference across evaporator and
ers in chilled water plants are seldom used. condenser
COOLING PLANTS 67

Type of chilled water distribution system impact on the amount of water that needs to be
Method of control pumped to meet a given load. The greater amount of
water pumped may have an impact on the sizing of
7.3.1 Number and Size of Chillers the piping or pump head and, hence, the first cost of
the project. Conversely, lowering the evaporator tem-
The number and size of chillers has significant
perature may have the opposite effect. Likewise,
impact on part-load operating performance. The load
lowering the condenser water temperature increases
profile of a building plays a very important role in
the chiller efficiency but may require more cooling
selecting the number and size of chillers. For exam-
tower fan energy.
ple, buildings that operate for long hours at low loads
may run more efficiently with multiple chillers, one
of which is sized to handle the low load. In this 7.4 CHILLED WATER
example, the use of a variable-speed drive on the DISTRIBUTION SYSTEMS
small chiller may also be cost-effective. A single The chilled water distribution system melds the
chiller may be most appropriate for small plants. chillers, pumps, piping, cooling coils, and controls
A life-cycle cost analysis based on a customized into a dynamic system that provides mechanical
load profile is a time-tested way of determining the cooling. Because it is one of the most energy-inten-
optimum number and size of chillers. Understanding sive systems used in buildings, understanding how
the first-cost implications and the energy benefits for the system components react to varying loads and the
chillers of various size is beneficial. One way to interactions among the components is essential for
secure an optimum selection is to establish a pro- designing a system that has the most effective life-
curement process that allows vendors to mix and cycle cost.
match their products across a wide range that meets
the peak load requirement. This allows pricing to 7.4.1 Constant-Flow Systems
take advantage of a particular sweet spot in a ven- The simplicity of a constant-flow chilled water
dors selections. Based upon the equipment selected, system is one of the primary attractions of this
the part-load operating characteristics can be evalu- approach. In constant-flow systems, the flow through
ated using a computer simulation model to determine the chiller(s), as well as the flow in the distribution
the annual energy impact of the selections. This can piping and at the cooling coil, is constant. Most con-
be put into a life-cycle cost analysis to determine the stant-flow systems use three-way valves at the cool-
lowest life-cycle costs for the project. ing coils. The following are examples of constant-
flow systems.
7.3.2 Type and Size of Heat-Rejection Devices
Heat-rejection devices are not readily adaptable Single Chiller Serving a Single Cooling Coil
to the chiller procurement method mentioned previ- When a single chiller serves a single cooling
ously. Water-cooled units are invariably more coil, the simplest approach is to use a constant-vol-
energy-efficient than air-cooled units, but air-cooled ume pump to circulate water between the evaporator
units may have a first-cost advantage. Again, first and the coil and to eliminate the traditional three-
costs should be analyzed along with annual energy way control valve. One caution when applying this
costs to determine the optimum life-cycle costs. approach is that manufacturers will insist on a suffi-
When selecting a cooling tower, the incremental first cient volume of water in the piping system to prevent
cost for increasing the size of a cooling tower (over- unstable temperature swings at the chiller. Often,
sizing the towers) can often be justified by the small storage tanks are required when a chiller is
increased energy efficiency of lower condenser water closely coupled to a coil.
temperatures or an increase in the number of hours
during which the fans run at low speed. Single Chiller with Multiple Cooling Coils

7.3.3 Optimizing Evaporator and When applying a single chiller with multiple
Condenser Water Temperatures cooling coils, using a constant-flow chiller with
three-way valves at the cooling coils is a simple
The energy efficiency of a water chiller is a time-tested way to achieve a long life-cycle, cost-
direct function of the temperature of the entering effective system. An energy-saving control strategy
condenser water and the leaving evaporator tempera- for this approach is to reset the water temperature
ture. Raising the evaporator temperature increases leaving the chiller based on the position of the coil
the efficiency of the cooling process but also has an valves requiring the coldest water temperature.
68 HVAC DESIGN MANUAL FOR HOSPITALS AND CLINICS

Multiple Parallel Chillers with This approach has a simplicity that makes it very
Multiple Cooling Coils attractive (see Figure 7-2).
On the surface, this approach seems simple, but There are several issues for concern. The bypass
problems arise during periods of part-load operation. valve acts against a relatively high pressure differen-
When both (or all) the chillers and pumps operate tial, so that it is susceptible to wear, cavitation, and
under a nearly full load, the system works well, but unstable operation at low loads. In some cases, the
there is little or no opportunity for pumping or cool- bypass valves are located at the ends of the distribu-
ing tower energy savings. At some point, the load is tion loops. This ensures circulation in the main loops
reduced enough so that one chiller and pump could and reduces the pressure differential across the con-
theoretically handle the load. By turning off one trol valve. If the by-pass valve maintains constant
chiller and pump, the reduction in flow from the cen- flow through the chiller(s), there will be no pump
tral plant basically starves all of the coils in the sys- energy saved as the loads vary, but pumps can be
tem. This design can still work for many shut off as chillers are disabled. Variable-speed
applications, provided that all the loads in the build- drives can be added to the primary pumps so that as
ing tend to change together; for example, no one coil the demand falls from maximum to minimum, the
demands full flow while others require very little speed can be adjusted downward, thus saving pump
flow. energy.

Primary/Secondary Variable-Flow Design


Multiple Series Chillers with Multiple Coils
Primary/secondary variable flow design has
One solution to providing multiple chillers in a
become the standard approach for designing large
constant-flow system is to arrange the chillers in
central chilled water plants using multiple chillers
series. Then, all of the flow goes through each
with multiple cooling loads (see Figure 7-3). The
machine. This method is effective for systems
beauty of the primary/secondary approach is that the
designed with a very high temperature difference.
piping loop for chillers (primary) is hydraulically
During off- peak periods, the lag machine is turned
independent (decoupled) from the piping loop for the
off, and the lead machine continues to deliver chilled
loads (secondary). The key to the design is that two
water at the correct temperature. This system works
independent piping loops share a small section of
well, although it does not provide chilled water
piping called the common pipe. A review of flow
pump energy savings during periods of low load.
patterns in the common pipe reveals that when the
two pipe loops have the same flow rate, there is no
7.4.2 Variable-Flow Systems
As can be seen from the discussion of constant-
flow systems, the idea of varying the flow in the sys-
tem has appeal in larger systems that have multiple
chillers and multiple loads. The basic advantage is
that the plant can effectively be turned down during
periods of low load, providing an opportunity for
significant energy savings. One of the most popular
design concepts for multiple-machine chiller plants
is primary/secondary pumping. Systems that use a
primary-only, variable-volume design approach are
often used because of greater simplicity and cost-
effectiveness.

Primary-Only Variable-Flow Design


Primary-only, variable-flow systems consist of
single or multiple chillers with system pumps that
move water through the chillers and distribution sys-
tem to the cooling loads (DuPont 2000). The cooling
loads are controlled with two-way valves. Typically,
a bypass line with a control valve diverts flow from
the supply piping to the return piping to maintain
either a constant flow through the chiller(s) or to Figure 7-2 Diagram of primary only, variable
maintain a minimum flow through the chiller(s). flow system.
COOLING PLANTS 69

Microcomputer-based direct digital control


(DDC) systems and networks are normally provided
in a modern chiller plant. Chiller plant controls
incorporate factory-installed instrumentation that
can be accessed through network connections. This
enables control and monitoring functions to occur
across a network. The instrumentation points must
be carefully chosen to ensure the proper level of data
so that the systems can be optimally controlled. Too
much instrumentation can be confusing to the oper-
ating staff and difficult for them to maintain. Selec-
tion of control and monitoring points should be
based on a careful analysis of the chiller plants con-
trol and operating requirements. To justify including
a particular control or monitoring point in a chilled
water plant, that point must meet at least one of the
following criteria:

It must be necessary for effective control of the


chiller plant as required by the sequence of oper-
ations established for the plant.
It must be required to gather necessary account-
ing or administrative information such as energy
use, efficiency, or running time.
Figure 7-3 Diagram of primary/secondary, vari- It must be needed by the operating staff to
able flow system. ensure that the plant is operating properly or to
notify staff that a potentially serious problem
flow in the common pipe. Depending upon which has or may soon occur.
loop has the greater flow rate, the flow direction in
the common pipe is subject to change. The primary Controllers used in the system must employ a
pumps are typically constant-volume, low-head powerful and flexible program language and have the
pumps intended to provide constant flow through the ability to be interfaced with chiller networks, vari-
chillers evaporator. The secondary pumps deliver able-frequency drives, and power-monitoring net-
the chilled water from the common pipe to coils that works. The most economical method of integrating
have two-way valves and then return it to the com- the instrumentation into the DDC system varies with
mon pipe. These pumps are variable-speed pumps manufacturer. It is advisable to specify a BACnet
controlled from differential pressure sensors located gateway between the chiller(s) and the DDC system.
remotely in the system. If for some reason BACnet is not used as the system
protocol, the chiller and controls manufacturers must
7.5 CHILLER PLANT CONTROLS AND
have an interoperable system so that there is full
INSTRUMENTATION
compatibility without a need for any special gate-
7.5.1 Controls ways or connections.
The chilled water plant is one of the most 7.5.2 Performance Monitoring
energy-intensive and function-critical spaces within
a facility. Special care must therefore be taken to Performance monitoring can help identify
ensure that the plant is operated to conserve energy opportunities for energy efficiency (DuPont 2000).
and provide long-term, reliable service. The auto- Integrating chiller plant monitoring with the control
matic control system is at the heart of this effort. system helps the plant operating staff to determine
Chillers and other plant equipment generate heat and the most efficient equipment configuration and set-
vibration that may adversely affect controls and tings for various load conditions. It also helps the
instrumentation. The control system must be selected staff to schedule maintenance activities at proper
to operate in the chiller plant environment. intervals, so that maintenance is frequent enough to
70 HVAC DESIGN MANUAL FOR HOSPITALS AND CLINICS

ensure the highest levels of efficiency but not so fre- 7.6 START-UP AND
quent that it incurs unnecessary expense. Most DDC COMMISSIONING ACTIVITIES
systems that can operate chiller plants effectively are
Most chilled water plants are custom designed
well suited to provide monitoring capabilities.
for a particular facility. The process of design and
Because chiller plant efficiency is calculated by
construction involves many skilled professionals,
comparing the chilled water energy output to the
who must perform their tasks well if the project is to
energy input (electricity, gas, or other) required to be successful. Because we are all human, errors can
produce the chilled water, efficiency monitoring occur. Commissioning is intended to achieve the fol-
requires only the following three items. lowing objectives:
Chilled Water Output
Ensure that equipment and systems are properly
Because the control instrumentation already installed and receive adequate operational
includes chilled water supply and return tempera- checkout by the installation contractors.
tures, only a flow sensor must be added to normal
Verify and document the proper operation and
chilled water plant instrumentation.
performance of equipment and systems.
Energy Input Ensure that the design intent and owners
To obtain the total energy input, it is necessary requirements for the project are met.
to install kilowatt-hour sensors on the tower fans, Ensure that the project is thoroughly docu-
condenser pumps, chillers, and chilled water pumps. mented.
It may also be possible to use only one or two kilo- Ensure that the facility operating staff is ade-
watt-hour sensors to measure the total energy used quately trained.
by the plant. To reduce instrumentation costs, it is
often acceptable to use a predetermined kilowatt Depending on the size, complexity, and budget
draw for constant-speed fans and pumps whenever for the project, the tasks involved in commissioning
they are operating. can vary widely. Consequently, there can be a number
of phases and levels in the commissioning process.
DDC Math and Trend Capabilities
(For details on commissioning, see Chapter 15.)
In addition to the instrumentation requirements,
efficiency monitoring requires that the DDC system 7.7 COOLING PLANTS FOR CLINICS
chosen have good mathematical function capabili-
ties, so that the instrumentation readings can be eas- Most clinics are served by custom-built or pack-
ily scaled, converted, calculated, displayed, and aged units with integral refrigeration components.
stored in trend logs for future reference. See section 5.6 for more details.
CHAPTER 8
SPACE AND PROCESS HEATING SYSTEMS
8.1 GENERAL fiers are often equipped with unitary point-of-use
Heating systems for medical facilities include steam generators, as central systems are often not
those required for space heating, domestic hot water life-cycle cost-effective. A dedicated steam genera-
generation, utensil sterilization, food preparation, tor may be justified for special areas due to unique
laundry, HVAC system humidification, therapeutic requirements such as a laundry, kitchen, etc. The
functions, and (in some cases) absorption refrigera- heat energy required for building heating and potable
tion. The configuration and sizing of the heating sys- water heating is often provided by indirect gas-fired
tems and plant are significantly affected by the equipment and immersion electric resistance equip-
interrelated requirements of the heat-consuming sys- ment.
tems. It is not unusual, for example, for more than
50% of peak boiler load in a general hospital, nurs- 8.2 HEATING PLANT CONSIDERATIONS
ing facility, or rehabilitation facility to be associated
with domestic, kitchen, laundry, and process require- Primary equipment must be sized and config-
ments for steam and hot water. Recently, however, ured to reliably and economically meet the maxi-
general hospital design has visualized the laundry mum heating system demands imposed by building
facility as a separate business component, with the loads. The essential nature of the services provided
laundry remote from the hospital building and not by general hospital facilities requires that redundant,
connected to the central plant. or backup, equipment be provided to ensure contin-
Based on the fundamental need for steam, these ued service during maintenance or repair of primary
facility types are often served by central steam gen- equipment. The optimum capacities and arrangement
eration plants. Figure 8-1 is a diagram of a typical of primary heating generators should be determined
steam heating plant for a general hospital. Central on the basis of redundancy, as well as simplicity of
low-temperature (<200F [93C]) heating water sys- operation and life-cycle cost-effectiveness. Although
tems are also common, with separate (direct-fired or not as critical as for general hospitals, the activities
electric) steam generation. Electric heat generation is in nursing and rehabilitation facilities also suggest
rare for large health care facilities, though sometimes some level of redundant equipment capacity to allow
encountered in smaller clinicseven in regions with for maintenance and to ensure system continuity dur-
relatively few heating degree-days and low electric- ing periods of equipment failure.
ity costs. Less frequently encountered than steam
systems are central high-temperature heating water When planning equipment room layouts,
systems, which in addition to providing space heat- designers must consider maintenance requirements;
ing can be used to generate steam in separate heat space and a means of access must be planned to per-
exchangers. High-temperature water heating is gen- mit rapid repair or replacement of equipment. The
erally applied to large campus facilities only. more limited the access space, the less likely equip-
Steam is also generally required for sterilization ment will be properly maintained. Maintenance for
and humidification. Depending upon the magnitude boilers can be relatively time-intensive, requiring a
of the requirements, however, sterilizers and humidi- single unit to be out of service for a lengthy period of

71
72 HVAC DESIGN MANUAL FOR HOSPITALS AND CLINICS

Figure 8-1 Typical steam plant schematic diagram.

time as compared to the maintenance requirements (warm-up) that is always added to steady-state peak
of boiler support equipment such as pumps. or operating loads to determine boiler and heating
system capacity. All components of the heating sys-
8.2.1 Load Considerations and Primary Plant tem must be sized for peak load plus pickup to main-
Capacity tain minimum pressure and temperature conditions
for such items as sterilizers. Some operating and heat
Primary equipment capacity must be sufficient
storage procedures can reduce pickup loads while
to meet the maximum simultaneous facility demand
minimizing standby losses. See Chapter 16 for infor-
for all systems served by the heating system, but
mation on design for energy efficiency.
equipment must also respond to periods of low load.
The load demand from the various systems can vary
8.2.2 Plant Redundancy
widely according to the hour of the day. Figure 8-2
illustrates a projected hourly heating plant profile, Key system components must be applied in mul-
during a January day, for a general hospital located tiple, parallel configurations to ensure backup capa-
in the southeastern U.S. The total connected plant bility. To provide the necessary equipment
load for this facility is approximately 31,000 lb/h redundancy, there must be at least two separate (but
(8804 kW/h). connected) boilers, boiler feedwater pumps, conden-
Space heating capacity must be sufficient to sate return pumps, fuel oil pumps, hydronic heat
meet the required indoor design temperatures estab- exchangers, hydronic water pumps, domestic hot
lished by criteria for all designated areas and spaces, water heaters, and other equipment vital for system
with minimum design outside temperature in accor- operationeach sized to meet the required demand.
dance with the ASHRAE HandbookFundamentals Redundant equipment serves not only as a replace-
(ASHRAE 2001a). If absorption refrigeration is uti- ment in the event of primary equipment failure but
lized, the summer heat generation demand may permits periodic shutdown of primary equipment for
approach winter load demand. Pickup requirements routine service and maintenance. In the hospital
are associated with any equipment or area involved environment, as a minimum, the capacity of backup
in a partial or complete shutdown (such as a cold system equipment should be sufficient to accommo-
boiler, absorption chiller, laundry equipment, or part date the systems serving critical care spaces and
of a building) that must be rapidly heated up to oper- patient room spacesincluding domestic hot water
ating temperature and/or pressure. Pickup is the for those areas, sterilizer loads, humidification, and
required heating capacity for the transient load kitchen loads. Backup capacity should also be suffi-
SPACE AND PROCESS HEATING SYSTEMS 73

Figure 8-2 Projected daily heating plant load profile.

cient to simultaneously prevent damage from possi- out of service until repairs can be implemented.
ble building freezeups in other areas of the facility. However, if the essential heat equipment is designed
Backup system capacity for space heating may not in the minimum multiple parallel configuration for
be required in some localities where the design dry- advantageous maintenance, depending on the season,
bulb temperature exceeds 25F (4C) for 99% or an outage can be withstood.
more of the total hours in any one heating month, as
established by the ASHRAE HandbookFundamen- 8.2.3 Plant Configuration
tals (Heating and Wind Design ConditionsUnited
States); however, it is a strongly encouraged design In determining the optimal plant equipment
arrangement, a designer may consider the mainte-
practice for full-service hospitals.
nance advantages of utilizing primary and backup
The ideal minimum equipment solution employs equipment of the same manufacture and capacity:
two or three separate, interconnected steam genera- simplified operation and maintenance (and operator
tors sized equally to provide the indicated redun- training) and spare parts interchangeability. At the
dancy as illustrated in Figure 8-1. A boiler feed same time, however, designers should consider the
system with dedicated pumps for each boiler should potential life-cycle cost-effectiveness of mixing
supply the steam generators. A three-boiler array equipment capacities to better match seasonal or
allows for one unit to be out of rotation for mainte- operational load profiles (including part-load opera-
nance, while two units remain available for the mini- tion and cold starts). Part loads and cold starting
mum operational capacity. Plant operators usually must be considered for major equipment, key com-
favor equally sized steam generators, as they provide ponents, and main control valves for four main rea-
the most flexibility in the event of an equipment fail- sons:
ure, and the commonality between equipment sim-
plifies maintenance. In some cases a smaller third Proper functioning/longevity of the equipment
boiler may be more efficient. This smaller boiler can and components of the system
be operated in summer when the load is minimal, Improved control of the equipment and compo-
thereby reducing standby losses. Major overhaul or nents of the system
maintenance efforts should be scheduled to avoid Time-weighted average efficiency at operating
cold system start-up and severely cold seasonal tem- points (energy conservation)
peratures. The boilers should be equipped with isola- Efficiency of low summer-load operation.
tion valves to allow maintenance and removal of a
single unit without disruption to the facility. Such considerations may, for example, suggest
Plant redundancy is not as critical in the outpa- three components in parallel sized at 20% + 40% +
tient facility environment. These facilities are gener- 40%, or 25% + 25% + 50%, of maximum required
ally considered business occupancies, and if imposed capacity instead of two components sized at 50% or
by an equipment failure, the business may be taken one sized at 100% of capacity.
74 HVAC DESIGN MANUAL FOR HOSPITALS AND CLINICS

Boiler burners can be equipped with controls increased pressures to allow for increased recovery.
providing turndown rates to 25% of full-load capac- Clean steam generators may be selected at higher
ity without a significant sacrifice in burner protec- inlet pressures to minimize the unit size. In some
tion. Equally sized boilers (50% + 50% + 50%) are applications, steam boilers for process loads and
well suited to many applications, particularly where heating hot water boilers may be separated.
a significant level of redundancy is required, as
would a configuration of 25% + 75% + 75%. Hospi- 8.3 FEATURES OF HEATING
tals of substantial size, however, may benefit from a EQUIPMENT
base-load boiler. A base-load boiler should never be
applied in a manner that leaves the plant vulnerable 8.3.1 Boilers
in terms of redundancy. Boilers used in health care facilities are charac-
terized as steam or hot water, low and medium/high
8.2.4 System Steam Pressure Requirements pressure, according to Chapter 27 of the ASHRAE
Steam pressure requirements for hospital appli- HandbookHVAC Systems and Equipment
ances and equipment vary. The plant operating pres- (ASHRAE 2000a). Pressure characterizations are
sure should consider the appliance with the highest defined as follows.
pressure requirement and a life-cycle cost justifica- Low Pressure
tion of the steam main size. Plants serving hospitals Steam boilers: less than or equal to 15 psig
with laundry facilities generally have the highest (103 kPa) steam.
pressure setpoint, corresponding to the connected Hot water boilers: less than or equal to
appliance of highest pressure. Hospitals without 160 psig (1103 kPa) hot water or less than
laundry facilities can operate at a substantially lower or equal to 250F (121C) hot water.
pressure. Significant energy saving occurs when a
plant is able to operate at a lower pressure. Life- Medium and High Pressure
cycle cost justification of increased plant pressure Steam boilers: greater than 15 psig (103 kPa)
based on a smaller main line size may, in some cases, steam.
be validated; it is risky, however, due to the natural Hot water boilers: greater than 160 psig
growth trend in most hospital facilities. (1103 kPa) hot water or greater than 250F
Typical steam pressure requirements are indi- (121C) hot water.
cated below. Designers must confirm these require- Many jurisdictions and codes define boiler oper-
ments with equipment manufacturers, building users, ator requirements according to boiler type and
and local codes. capacity. For example, depending upon their capac-
ity, medium- and high-pressure boilers may be
Steam sterilizers40 to 80 psig (276 to 552 kPa). required to be continuously supervised by a licensed
Kitchen dishwasher booster heaters15 to boiler operator. The associated personnel costs can
30 psig (103 to 207 kPa). be significant. However, low-pressure boilers and
Serving line (kitchen)5 to 15 psig (35 to smaller medium- and high-pressure boilers do not
103 kPa). require a boiler operator in most jurisdictions. For
Kitchen cooking kettles and chests15 to these reasons, smaller facilities should consider low-
30 psig (103 to 207 kPa). pressure and multiple medium/high-pressure boilers
Laundry flatwork ironers90 to 120 psig (621 to to avoid the ongoing cost of a boiler operator.
828 kPa). Rules-of-thumb for boiler efficiency are:
Humidifier clean steam generators15 to
60 psig (103 to 414 kPa). Typical efficiency of a boiler is 80% to 85%
Hydronic heat exchangers15 psig (103 kPa). Hot water condensing boilers can be as high as
Potable water heaters15 to 60 psig (103 to 95% efficient.
414 kPa). High-pressure gas boilers with an efficiency of
85% or higher are available.
Process equipment items such as sterilizers, Fire tube boilers are more efficient than water
kitchen appliances, and laundry equipment are usu- tube boilers but take more space.
ally limited to a confined operating pressure range. Economics and space comparisons between fire
HVAC and plumbing heat transfer equipment (such tube and water tube boilers show a usual break
as heat exchangers, water heaters, and clean steam point of 700 boiler horsepower (6867 kW).
generators) may be operated at a wider range of pres- Further information on energy-efficient boiler
sures. Potable water heaters may be selected at plant is included in section 16.7.
SPACE AND PROCESS HEATING SYSTEMS 75

8.3.2 Boiler Codes depending upon municipality. A high-water cutout


switch is rarely required.
Boiler construction and installation are influ-
enced by a multitude of agencies. Boiler manufactur-
8.3.4 Dual-Fuel Boilers
ers are required to carry a high value of liability
insurance to warrant their product design and essen- Fuel system redundancy should be investigated
tial performance. Applicable sections of boiler codes for hospital plant facilities. Boilers operating on a
are enforced on the basis of capacity and design combination of fuel sources are readily available
pressure. from all major manufacturers. In view of plant com-
Boiler codes are generally enforced at the local ponent redundancy requirements, the provision of
and state level. The most commonly accepted con- dual fuel sources is also recommended. Items to con-
struction standard is the American Society of sider are reliability, guaranteed continuity of service,
Mechanical Engineers Boiler and Pressure Vessel and facility disaster planning.
Code. Most states in the continental U.S. have If the plant is proposed to be served by a central
adopted its requirements. Compliance with the Con- utility natural gas service, it should be determined
trol and Safety Device Code (CSD-1) is also required whether the utility service in the area is interruptible
in most states. It outlines the essential safety and
or non-interruptible. If the service is interruptible, an
operational devices required for boilers. In addition,
alternative fuel source is warranted. Before selecting
in most jurisdictions, boilers and their components
a natural gas interruptible service, the designer
are required to be independently listed by a testing
agency such as Underwriters Laboratories (UL) and/ should perform an economic evaluation to ensure
or the American Gas Association (AGA). that the costs associated with an alternate fuel system
can be justified. Interruptible rates are usually avail-
It may be advantageous for facility owners to
comply with requirements set forth by their own able only for large users (steam flow of 30,000 lb/h
insurance underwriter. National companies such as [8520 kW] or greater).
Factory Mutual (FM) and Industrial Risk Insurers Some jurisdictions have adopted Disaster Pre-
(IRI) offer premium incentives for complying with paredness Planning programs. Fuel redundancy,
basic boiler safety features. It is prudent for the usually at the discretion of the facility owner, is
designer to discuss these considerations with a client, strongly encouraged by these programs.
prior to the execution of a project design. Most commonly applied in dual-fuel boilers are
burners equipped to fire natural gas and number-2
8.3.3 Boiler Controls grade fuel oil. The fuels are fired at different inter-
Boiler design operating pressure and capacity vals rather than simultaneously. Burners can also be
influence the application of boiler controls. Two equipped to fire other grades of fuel oil, such as
basic lines of definition exist; low-pressure boilers number-4 and number-6 grade. These heavier grade
versus medium- and high-pressure boilers and below fuels are generally less expensive but are more diffi-
400,000 Btu/h (117 kW) capacity versus above cult to pump, have a greater propensity to fouling,
400,000 Btu/h (117 kW) capacity. and have significantly higher levels of emissions.
Medium- and high-pressure boilers are required Liquefied petroleum gas (LPG) and/or mixtures of
to be equipped with a low-water cutoff (LWCO) with LPG are also available as a natural gas substitute.
automatic reset and an auxiliary low-water cutoff
with manual reset. The secondary LWCO may be a 8.3.5 Heat Recovery
probe type. Two operating controllers are also Hospital facilities use tremendous amounts of
required. The first pressure or temperature setting is
heating energy due to their ventilation and process
equipped with an automatic reset and the second (set
heat requirements. A number of heat recovery
at a higher pressure or temperature) with a manual
devices can be practically applied to the hospital
reset. Relief valves are required on each boiler to
permit the release of the total output of the boiler. A plant, many of which carry a limited capital invest-
high water limit switch is required in many applica- ment.
tions, particularly with a pressurized deaerator sys- Boiler flue gas heat recovery is commonly con-
tem, to prevent boiler operation if the water level has sidered. The flame temperature of most conventional
risen above the steam production line. forced draft burners is in the range of 1600F to
Low-pressure boilers are required to be 1800F (870C to 980C). Boiler efficiency is driven
equipped with dual low-water cutoff devices similar by an attempt to bring the boiler stack outlet temper-
to medium- and high-pressure boilers. The arrange- ature close to the boiler water temperature, without
ment of operating controllers and relief valves varies condensing. Stack temperatures are generally in the
76 HVAC DESIGN MANUAL FOR HOSPITALS AND CLINICS

range of 500F (260C). As the flue gas exits the Similar to boilers, building heat exchangers
boiler, a great amount of energy can be recovered should be applied in a multiple parallel configura-
through a flue gas economizer. Economizer units are tion. In a two-heat-exchanger configuration, each
fire tube style shell-and-tube devices or water tube should be sized to provide the heat required by criti-
style, installed in the boiler stub stack. Boiler feed- cal care spaces, patient rooms, with preferably a
water or condensate return water is generally circu- safety factor to prevent freezing in other areas.
lated through the water-side component of the Also, as with boilers, redundant heat exchange
economizer to recover some of the flue gas heat. equipment capacity is often required or desired by
This application is generally quite life-cycle cost- the building owner. One option may be to provide
effective as long as corrosion resistant materials are two heat exchangers of 75% and 100% capacities.
used.
The units should be equipped with isolation valves to
Boiler blowdown economizer units are also allow maintenance and removal of a single unit with-
applied. Boilers are equipped with surface blowdown out disruption to the facility. Steam/hot water heat
systems to decrease foaming and scaling and, there- exchangers are recommended to be equipped with
fore, corrosion at the water level. The blowdown dual steam condensate traps, each trap sized at 100%
economizer is usually a shell-and-tube device. Boiler of the connected load to allow for trap fouling and
feedwater or condensate return water is circulated
failure.
through the tube component of the heat exchanger to
acquire heat from the blowdown water. Boiler blow- 8.4 TERMINAL HEATING EQUIPMENT
down water is, however, extremely corrosion aggres-
sive. Units manufactured from stainless steel and Heating energy is used to offset winter heat loss
cupronickel alloys are required for longevity. and to provide reheat for comfort conditioning dur-
Although a large amount of heat may be recovered, ing summer. Heat is normally introduced to the air
these units are often by nature not reliable due to systems through finned tube heating coils in duct-
maintenance and replacement costs. work. The finned coils may be located in low veloc-
ity supply air ductwork and/or at air terminal box
8.3.6 Hydronic Heat Exchangers outlets. Finned heating coils are also found in air-
handling units for comfort control and for freeze pro-
Heating system equipment must be rated by
tection.
approved nationally recognized standards. Heat
Perimeter heat is also often required to offset
exchangers for building heating may be shell-and-
envelope heat loss. Heat can be provided through the
tube configuration or plate-and-frame type. Shell-
and-tube heat exchangers are commonly used for use of finned-tube radiators, convectors, fan coil
steam-to-hot water generation. They are also com- units, and radiant ceiling panels. Many jurisdictions
mon in medium/high-temperature water to low-tem- and agencies prohibit finned-tube radiators in patient
perature water generation. Shell-and-tube units are rooms and critical care spaces due to their fouling
often used considering the approach temperature of potential. Ceiling radiant heating panels are often
most steam or medium/high-temperature water used in these circumstances. Perimeter heat loss can
applications. The essential shell-and-tube unit con- also be offset directly through the building supply air
struction permits easy access to the interior equip- system with an appropriate supply air diffuser selec-
ment components and resists fouling. tion. Linear slot type diffuser performance tests have
Plate-and-frame units are found in some demonstrated effective heat loss mitigation, depend-
medium/high-temperature applications and also in ing upon the amount of heat loss.
low temperature source water applications. The
approach temperature of plate-and-frame units can 8.5 PIPING SYSTEMS
be as close as 2F (1.1C) to the medium to be gener-
ated. Plate-and-frame units are not usually applied in 8.5.1 Hot Water
steam to hot water applications. Hot water is typically piped to terminal heating
Heat exchangers are arranged in the building equipment, including baseboard heating units, radi-
heating system as indicated in the ASHRAE Hand- ant panels, or reheat coils. Two-pipe systems are
bookHVAC Systems and Equipment (Hydronic most common, whereas four-pipe arrangements are
Heating and Cooling System Design and Medium- occasionally utilized for fan-coil units. In a four-
and High-Temperature Water Heating Systems). pipe configuration, two of the four pipes are used to
SPACE AND PROCESS HEATING SYSTEMS 77

convey the heating water and two are used to convey 8.5.3 Steam Traps
chilled water. In two-pipe heating/cooling system
Steam (condensate) traps are required for steam-
arrangements, a single piping circuit conveys heating fired appliances and devices. A multitude of trap
energy and, intermittently, cooling energy, depend- products are available. Trap application is influenced
ing upon the season. The two-pipe heating/cooling primarily by the appliance or service intended and
piping system is not well suited to the hospital envi- also by the pressure available in the system. Trap
ronment. A discussion of two- versus four-pipe sys- types commonly encountered in hospital environ-
tems is provided in the ASHRAE HandbookHVAC ments are inverted bucket, float and thermostatic,
Systems and Equipment (Hydronic Heating and thermodynamic, and thermostatic. Each has a partic-
Cooling System Design). See section 5.4.2 of this ular range of service and operating characteristics. A
manual for additional information. thorough discussion of steam traps is provided in the
2000 ASHRAE HandbookHVAC Systems and
In predominantly heating climates, it may be Equipment (Steam Systems).
advantageous to provide two independent space
The operational objective of a trap is to permit
heating piping circuits, one for the building perime-
condensate, which has been condensed through a
ter heating system (e.g., baseboard radiators) and the
heat transfer process, to be drained away from an
other for the building air-side terminal boxes and/or appliance or piping system. The trap also restricts the
heating coils. The two-circuit arrangement can be passage of steam from the steam piping system into
served by independent perimeter and interior heat the condensate system to improve energy conserva-
exchangers, or it can be served through a single heat tion.
exchanger with an automatic bypass, three-way mix- Trap installation should allow, to the greatest
ing valve in the perimeter circuit. The objective is to extent possible, gravity drainage at the outlet to the
allow two independent water temperatures to be cir- condensate piping system. The pressure at the trap
culated simultaneously. The interior system gener- outlet is often relied upon by designers to elevate the
ally requires a constant hot water temperature, as condensed steam to a condensate piping system
coils configured for reheat experience constant sup- above the elevation of the collection point. When this
ply air temperatures throughout the year. The energy piping practice is employed, a water hammer effect
expended by the perimeter system, however, can be occurs upon trap element opening, as the entering
proportional to the outdoor air temperature, allowing steam impacts the dormant liquid in the condensate
the water temperature to be reset as the correspond- piping. Although not detrimental to system dynam-
ing outdoor air temperature changes. ics, this generates unwanted noise and allows the
highly corrosive condensed steam to dwell at the sys-
8.5.2 Steam tems low points.
When relying on steam pressure to elevate con-
Heating energy is also often conveyed to termi- densate, consideration should be given to whether
nal equipment through a two-pipe steam/condensate the application pressure is dependent upon a steam
system. Steam and condensate return are indepen- control valve at the appliance inlet or whether the
dently connected to all of the buildings heating application is on a steam main with no control valve.
appliances. Steam energy is rarely used directly in Intermittently operating or modulating steam control
the heating process, as the approach temperature of valves on heat exchangers, for instance, may be in
the steam to the required room temperature is exces- the open or closed position depending upon the load
sive. In addition, the maintenance of this type system requirements of the appliance. When in the closed
is greater than for a hydronic heating system. position, no pressure is available to elevate the con-
densate liquid; when the control valve opens, water
Steam condensate piping should be constructed hammer will occur. Steam main drip traps generally
of a material thickness that compensates for natu- have continuous pressure available, resulting in a
rally occurring corrosion. Generally, Schedule 80 greater level of operational predictability.
carbon steel piping is used. For a steam condensate Steam trap maintenance is essential in hospital
system that conveys steam condensate from a clean facilities to ensure system reliability and energy con-
steam (not chemically treated) system, stainless steel servation. Facilities should establish a trap testing,
piping materials should be considered. Steam con- cleaning, and replacement program. Electronic test-
densate return may be by gravity or by condensate ing products are available to detect trap failure. An
pump. annual cleaning effort ensures proper trap life cycle.
78 HVAC DESIGN MANUAL FOR HOSPITALS AND CLINICS

8.6 DOMESTIC WATER SYSTEMS management systems for system monitoring. The
building management system can also be used to
8.6.1 General Considerations cycle water heaters and pumps on and off in ambula-
The potable hot water load for a hospital can tory care facilities, based upon the operating sched-
account for up to 30% of the heating energy load. ule of the facility.
Domestic, kitchen, and laundry hot water consump-
tion rates often vary suddenly and fluctuate fre- 8.6.2 Water Heater Features
quently throughout the dayby a factor of 100% or Potable water heaters are essential equipment in
more. Because demand and consumption rates vary health care facilities. The heat losses in potable hot
so suddenly and significantly, it is appropriate to water systems must be minimized through the proper
store domestic, kitchen, and laundry hot water in application of thermal insulation. Redundant potable
tanks, providing a large capacitance for sudden water heaters are recommended in all health care
changes in flow rate and quantity. facilities. If two water heaters are proposed, each
The control of Legionella is a concern in potable should be sized for 65% of the potable hot water
hot water systems. Storing hot water at a temperature demand. If more than two water heaters are pro-
of 140F (60C) will control Legionella within the posed, each water heater should be sized for an equal
storage tank itself. Consideration of municipality percentage of the hot water demand.
requirements and design criteria is required in order The medium used to heat potable water varies;
to determine the hot water storage temperature for a electricity, steam, high-temperature hot water, and
particular facility. If potable hot water is stored at a gas are the most common. Different potable water
higher temperature than required, it must be mixed heater configurations are commercially available:
with cold water to achieve the desired system tem- storage tank type, semi-instantaneous type, and
perature at the tap. instantaneous type.
Another factor in the control of Legionella is the Storage tank water heaters are the most com-
elimination of dead-end pipe runs in a potable hot monly utilized. They must be sized to provide a
water system. This can be accomplished by effective facilitys immediate hot water demand through the
piping design and by the utilization of a hot water stored hot water. The heating of the water volume is
recirculation system. The pipe run-out to fixtures/ spread over a period of time, which can range from a
equipment should not exceed 25 lineal feet (7.6 fraction of an hour to several hours. Commonly used
meters). This measurement includes the drop from heating mediums are steam, high-temperature hot
the ceiling to the fixtures/equipment. Hot water water, gas, and electricity. One drawback to this type
recirculation system sizing procedures are presented of water heater is the standby loss associated with
in the ASHRAE HandbookHVAC Applications the storage of hot water during periods of low
(Service Water Heating) (ASHRAE 1999a). A hot demand. The input ratings of the water heaters are
water return flow must be established using the often low, however, due to storage tank size.
methods listed in the above-mentioned Handbook Legionella control is a concern (see 8.6.1 above).
chapter. A minimum hot water return flow of 10 gpm Semi-instantaneous water heaters store a small
(0.6 L/s) is recommended to facilitate a stable return amount of hot water, typically ten to twenty sec-
water pump selection. Refer to Chapter 14 for more onds of the buildings hot water demand. This allows
information regarding systems operations and main- the water heaters temperature control system to
tenance. react to sudden fluctuations in water flow. The most
Devices such as scullery equipment, dishwash- commonly used heating medium for this type of
ers, and laboratory and sterilization equipment often water heater is steam. Although the standby loss
require water at a temperature higher than provided associated with this type of heater is minimal, the
by the central potable water-heating system. Washer- input rating is high due to the immediate requirement
sterilizers and dishwashers are normally equipped for hot water. To heat the water to the water heater
with either a steam-fired or electric booster heater to setpoint, a high-demand heat input energy is
elevate the water temperature. A booster heater required.
downstream of the central potable water heater dedi- Instantaneous water heaters must have sufficient
cated to the kitchen, for example, is often used. capacity to provide the maximum hot water flow rate
Heat exchangers or tank heaters may be required at the required temperature. Instantaneous water
by local jurisdictions or codes to be double walled to heaters find their best use where the water-heating
prevent contamination of potable water by the heat- demands are constant or where space installation
ing medium. restrictions are a prime consideration. Steam and
Consideration should also be given to connect- high-temperature hot water are the most common
ing water heaters and recirculation pumps to building heating mediums for this type of water heater.
SPACE AND PROCESS HEATING SYSTEMS 79

Standby losses for instantaneous water heaters are 8.7 STERILIZATION AND
negligible. Due to the instant demand for hot water, HUMIDIFICATION
the input rating is high.
The domestic hot water heater can also be a 8.7.1 General
direct natural-gas-fired unit. Condensing-type heat- As a rough rule of thumb, humidification and
ers offer the advantage of simplified venting, in that sterilization normally account for 20% and 5%,
the outside vent need not necessarily route all the respectively, of a hospitals total heating require-
way to the building roof. ments. Both systems require a high quality (that is,
For smaller clinics, where domestic hot water relatively dry) steam supply. With steam sterilizers,
demand is limited, water heating with electric resis- excess moisture can wet packs and transport pipe
tance heaters or heat pumps is sometimes found to be scale, rust, or treatment chemicals, causing instru-
economical. ment stains and other problems. Sterilizers require
steam pressure in the range of 60-80 psi (414-552
8.6.3 Hot Water Demand kPa) to achieve corresponding saturation tempera-
tures sufficient for sterilization; saturated steam is a
Hot water demand for fixtures should be calcu- superior sterilant to superheated steam (AHA 1985).
lated in accordance with the ASHRAE Handbook Wet humidifier steam can lead to wetting the interi-
HVAC Applications, chapter on Service Water Heat- ors of ductwork, filters, and other components lead-
ing. Hot water demand for equipment not indicated ing to microbe growth. Humidifiers are normally
in the ASHRAE Handbook (i.e., laboratory and ster- served by system pressures less than 20 psig (138
ilization equipment) should be obtained from equip- kPa).
ment manufacturers.
Steam for these systems may be generated in
central plants or supplied by individual boilers (typi-
8.6.4 Water Delivery Temperature cally electric, gas-fired, or steam-to-steam) provided
Typically required temperatures at the point of with the equipment. The decision whether to provide
consumption are as follows (designers must confirm central generation or individual boilers should be
local codes and design criteria): influenced by life-cycle cost considerations includ-
ing initial equipment purchase, operation and main-
Domestic hot: 105F to 125F (41C to 52C), tenance, and replacement costs. These cost factors
temperature issues include scalding, comfort will be significantly affected by the approach taken
and therapy, washing and bathing, disinfection, to deal with corrosion and by the required purity
and janitorial. level of steam.
Kitchen dietary: 140F (60C), used by kitchen 8.7.2 Steam Classifications
staff only, so scalding temperature limit is
higher. Steam used for other than space-heating applica-
tions is commonly classified as unfiltered, fil-
Kitchen dishwashing final rinse: 180F (82C),
tered, clean, or pure, according to the makeup
for disinfection (this may not be required if
water characteristics and permissible level and
chemical disinfection is utilized).
nature of steam impurities. These classifications are
Laundry: 160F (71C). not defined by any national standard and their char-
acteristics may, therefore, vary among different
Prevention of scalding is a major issue in the authorities, but in general:
design/maintenance of a potable hot water system. If
the average adult is exposed to 140F (60C) water, Unfiltered steam normally contains some sys-
first-degree burns will occur in approximately three tem treatment chemicals, normally generated
seconds. Exposure to 120F (49C) water creates from makeup water that has been softened and
first-degree burns in approximately eight minutes. often treated by other processes (deaeration or
Infants and the elderly may have more sensitive skin; dealkalyzation, for example) to reduce corrosiv-
thus, first-degree burns can occur more rapidly. ity. The steam is not filtered prior to delivery.
Terminal mixing valves are commonly applied Filtered steam is normally generated from
in shower and bathing facilities. The valves are typi- makeup water treated similarly to unfiltered
cally a pressure balanced type, integral to the opera- steam, but it is filtered to remove all particles
tional water flow valve. Other locations for terminal larger than some established standard, normally
mixing valves include hydrotherapy rooms and labo- 1-3 microns. Filtration normally includes coa-
ratories. lescent filter removal of liquid water droplets.
80 HVAC DESIGN MANUAL FOR HOSPITALS AND CLINICS

Clean steam is normally generated in a dedi- ing magnesium and calcium carbonate, have low sol-
cated steam boiler, with limited or no treatment ubility and therefore precipitate from solution to
additives permitted, and with makeup water nor- form scale at the elevated temperatures found in boil-
mally only softened, although it can be treated ers and other heat exchangers. Scale formation
by reverse osmosis, deionization, or even distil- reduces equipment heat transfer and results in over-
lation. heating of heating coils and elements, resulting in
Pure steam is generated from deionized or dis- reduced performance and equipment failure. Water
tilled makeup water and contains no treatment with a hardness exceeding 3.5 grains per gallon (60
additives. grams per cubic meter) normally requires soften-
ing, typically by ion-transfer technology, to reduce
The majority of medical facilities utilize unfil- scale formation in heating equipment.
tered steam for sterilization. As discussed in greater
detail below, most authorities will accept the pres- Carbon Dioxide (Carbonic Acid)
ence of limited types and concentrations of system
The presence of carbon dioxide in the water sup-
treatment additives in sterilizer steam. Unfiltered
ply (from dissolved atmospheric CO2 or the break-
steam is also widely used for direct humidification,
down of carbonate and bicarbonate compounds)
although the presence of treatment chemicals is
much more of a concern due to the direct injection of results in the formation of carbolic acid, which is
the steam into environmental air, and its use is, there- very corrosive to materials (such as mild steel and
fore, banned by some authorities. Federal regulations copper alloys) commonly used in steam systems.
and industry guidelines restrict the concentrations of, Condensate piping, in particular, is subject to car-
or prohibit altogether, certain additives to which peo- bonic acid corrosion, which results in general wall
ple may be directly exposed by humidification thinning and a characteristic troughing or marked
steam. erosion of metal from the bottom of the pipe. The
iron dissolved from carbolic acid attack often
8.7.3 Corrosion Mechanisms in Steam becomes a problem by clogging boiler tubes (possi-
Generation Systems bly resulting in tube failure) and stopping up strain-
ers and traps, and it can result in red water
It is important for designers to be knowledge-
carryover and staining in sterilizers. In the presence
able of the fundamentals of steam and condensate
of dissolved oxygen, the corrosive effect of carbolic
system corrosion, so as to be aware of the implica-
acid is markedly increased.
tions of the different makeup and treatment alterna-
tives and steam purity standards. Every component
Oxidation
of the steam system, from generator to steam piping
to the condensate handling components, and all fit- Free oxygen dissolved in water is very corrosive
tings exposed to the makeup water, steam, or con- to mild steel surfaces and its presence is character-
densate, are subject to corrosion. Corrosion ized by pitting of the piping wall. As with carbolic
generates system contaminants, increases mainte- acid corrosion, condensate piping is most vulnerable
nance effort, reduces system reliability and perfor- to attack. Significant iron removal is often remarked
mance, and dictates the frequency of equipment in steam piping systems as well, due to the unavoid-
replacement. The primary considerations in steam able presence of liquid water from boiler carryover
system corrosion are the following. and line condensation. The iron dissolved by this
corrosion process, similar to that resulting from car-
Scale bolic acid attack, frequently clogs heat exchanger
Scale is formed in equipment and piping by the tubes, clogs strainers and traps, and causes stains in
precipitation of certain chemical compounds, known sterilizer packs and instrumentation.
as mineral salts, present in all natural water supplies.
The concentration of scale-forming compounds in High-Purity Water Aggressiveness
water is known as hardness, measured in parts per In some applications (rarely encountered in
million (ppm) or grains per gallon (grams per cubic health care facilities), users desire the generation of
meter). Water supplies having significant levels of clean or pure steam from water that has been
hardness are found in approximately 85% of the treated to remove most of its impurities. These
United States and Canada (Garay and Cohn 1992). reagent grade waters, processed using distillation,
Several of the more prevalent mineral salts, includ- demineralization, or reverse osmosis, typically range
SPACE AND PROCESS HEATING SYSTEMS 81

in resistivity (a measure of relative absence of dis- Dealkalyzation or Demineralization


solved ions and therefore purity) from 2 to 15 The most common source of carbon dioxide,
megohm/cm. A value of 18.25 megohm/cm at 25C and therefore of carbolic acid, in steam heating sys-
(77F) is recognized as the theoretical maximum tems is carbonate or bicarbonate, the anionic (nega-
(ASPE 1994). Water of such purity is highly corro- tively charged) components of the mineral salts
sive to many of the commonly used piping and commonly found in system makeup water. These are
equipment materials, including mild steel. Depend- the same compounds associated with water hardness.
ing upon the purity of the water, even low-grade While the sodium zeolite softening process reduces
stainless steels can be subject to significant corro- the scaling potential of these compounds, it does not
sion. High-purity water attacks not only steam gener- remove the carbonates from solution. One process
ators but also the steam and condensate piping commonly used for carbonate removal is known as
systems. As with CO2 and oxygen corrosion, prob- dealkalization in which chloride anions are
lems associated with high-purity water corrosion exchanged with the carbonate/bicarbonate anions,
include reduced equipment life, system clogging, the latter being retained by a cationic resin and
and discoloration of materials in contact with steam. removed from solution. The reverse osmosis (RO)
process, which uses pressure to filter dissolved
Galvanic Corrosion compounds and particles through an osmotic mem-
When dissimilar metals are used in steam and brane, can be up to 95% effective in removing car-
condensate systems, galvanic corrosion can occur bonates as well as other impurities from makeup
in which the least noble metal (anode) corrodes to water. The process of deionization (DI) is also very
form deposits on the more noble (cathodic) metal. effective in removing nearly all of the carbonates and
Examples of dissimilar metals are steel-copper or other minerals. However, with treatment costs in the
steel-stainless steel, in which the anodic steel cor- neighborhood of $0.01 per gallon ($0.0026 per liter)
rodes to the relatively cathodic copper or stainless and $0.1 per gallon ($0.026 per liter) for the RO and
steel. Galvanic corrosion can accelerate deterioration DI processes, respectively, these latter two are not
of piping systems, thereby reducing system life and commonly encountered in steam generation system
creating impurities in delivered steam. makeup water treatment.

8.7.4 Methods of Corrosion Control Corrosion-Resistant Materials


For steam generation and handling systems uti-
Softening (Sodium Zeolite) lizing reagent-grade makeup water, and for systems
The most common and economical method of that cannot be operated with corrosion-protecting
reducing the concentration of scale-forming com- treatment chemicals, construction using corrosion-
pounds in water is known as sodium-zeolite water resistant steel is highly recommended. This would
softening. In this process, the solubility of scale- apply to all portions of the steam generation and pip-
forming compounds is chemically increased by ing systems in direct contact with steam and conden-
replacing their magnesium or calcium cations with sate, including heat exchange surfaces, steam and
those of sodium, minimizing precipitation and scale condensate piping, traps, and other fittings. High-
formation. The sodium zeolite process can remove grade stainless steels are recommended for the con-
up to 98% of scale-producing compounds at rela- struction of all components of steam generation sys-
tively low costsranging in the thousands of gallons tems directly exposed to the steam or condensate
(liters) per dollar.
Avoidance of Dissimilar Metals
Deaeration Removal of CO2 and O2 Connections between dissimilar piping materi-
When water is heated, the solubility of dissolved als should be avoided to prevent corrosion. Dielectric
gases is decreased. Therefore, in central steam gen- couplings can be used to prevent such occurrences.
eration plants a common process for removing oxy-
gen and carbon dioxide from makeup water supplies Adequate Condensate Drainage
is the heating of the water, often under pressure (up As discussed above, the presence of oxygen and
to 20 psi [138 kPa]), in a deaerating feedwater heater. carbon dioxide in water can lead to rapid corrosion
Commercial deaerators are capable of removing dis- of commonly used piping materials, such as mild
solved oxygen to a level of 0.005 cubic centimeters steel. Also, when condensate cools, it can absorb
per liter (cc/L). higher concentrations of oxygen and carbon dioxide
82 HVAC DESIGN MANUAL FOR HOSPITALS AND CLINICS

(supplied by atmospheric piping leakage or carried or the compounds that form CO2, and these may be
over with steam-gas solubility increasing with lower transported throughout the system with the steam.
temperature) rendering it more corrosive. Steam For this reason, it is commonly necessary to add
lines, often erroneously considered to be dry, are treatment chemicals that eliminate oxygen, neutral-
exposed to more of the corrosive condensate when ize acid, or form a barrier between system materials
the liquid is inadequately trapped and removed and and the corrosion agents.
at times of low steam demand. It is, therefore, impor-
tant that system designers provide for efficient trap- Oxygen Scavengers
ping and removal of condensate from all portions of Oxygen scavengers are chemicals, such as
the system, minimizing opportunities for cooldown hydrazine and sodium sulfite, used to virtually elimi-
and continuous contact with piping. Design provi- nate or passivate any oxygen remaining in the system
sions include properly sloping steam lines (normally after deaeration of the makeup water supply. Without
in the direction of flow), avoidance of concentric deaeration, the amount of scavenging chemical
pipe fittings and other low points where condensate required to reduce dissolved oxygen would be eco-
may pool, and the provision of adequately sized and nomically and practically prohibitive. Even with effi-
located drip legs and traps. The latter are needed at cient oxygen removal from the feedwater supply,
suitable piping intervals, at the base of all risers, and atmospheric oxygen can reenter steam and conden-
immediately upstream of valves, pressure reducers, sate systems through vacuum breakers and atmo-
and other equipment connections where condensate spheric vents, condensate pumps, or flash vents,
can collect. although opportunities for this are limited in steril-
ization and humidification steam systems in which
Blow-Down and Bleed-Off condensate is not returned to the boilers.
When water boils in a steam generator, most of
the impurities contained in the water are left behind Amines
in the heat exchange reservoir. Makeup water replac- Amines are alkaline treatment chemicals devel-
ing the boiled-off steam brings in a new charge of oped to raise pH or to shield piping system materials
impurities, adding to those already present and grad- from direct corrosion agents. Two types of amines
ually increasing their overall concentration. are utilized in the steam treatment industry: neutral-
Unless the heat exchange surfaces are frequently izing and filming amines. The former act only to
cleaned of the accumulated scale and sludge, unit neutralize carbolic acid and have no protective effect
performance will be reduced and the equipment may against oxygen. The filming amines, on the other
eventually fail. To minimize the concentration of hand, act to form a molecular coating on the inside
impurities and extend the frequency of required walls of piping systems, preventing direct corrosion
maintenance, many steam generators (from large by either carbolic acid or oxygen.
plant generators to individual electric humidifier
steam generators) are equipped with an automatic 8.7.5 Treatment Chemicals and Health
blow-down or bleed-off. Typically operated on a
timed cycle, the bleed-off drains a certain volume of A number of the treatment chemicals used in
high-impurity water from the reservoir, replacing it steam systems are known, or suspected, to have
with treated makeup water to dilute the overall impu- adverse health effects upon humans exposed to suit-
rity level. ably high concentrations in ambient air, food, or
water. The opportunities for human exposure to
Chemical Treatment Additives potentially harmful treatment chemicals in sterilizer
The mechanical water treatment processes dis- steam is very limited, as only very small amounts of
cussed above do not adequately protect the most the steam are ever released into the building environ-
common piping and equipment materials (i.e., mild ment. Humidification steam, being directly injected
steel) against oxygen and CO2 corrosion. These into the building air supply, is more of a concern.
gases may enter the piping system from ambient air Authorities have established exposure limitations for
via pipe and fitting connections when portions of the selected amines and oxygen scavengers, and it
system experience vacuum due to condensing steam. appears that in common practice, with good mainte-
In addition, the treatment processes cannot be nance attention, the chemical concentrations in air
depended upon to remove all traces of dissolved gas humidified by treated steam fall well within these
SPACE AND PROCESS HEATING SYSTEMS 83

Table 8-1. Permissible Limits for the FDA Amines


ACGIH TWA OSHA PEL Odor Level
Chemical Name (ppm) (ppm) (ppm)
Morpholine 20 20 0.14
DEAE 10 10 0.04
Cyclohexylamine 10 10 0.90

limitations. Concerns remain, however, regarding the Table 8-2. Toxicity Data for the FDA Amines
dependability of the necessary maintenance, the
Dermal
potential for various environmental factors to alter Chemical Oral Exposure Exposure
the chemicals into more dangerous compounds, the Name - LD50 -LD50
potential irritant (as opposed to health endanger- Morpholine 3053 3083
ment) effects, and the legal implications of exposure DEAE 1300 1260
of building occupants to any level of potentially haz- Cyclohexalamine 319 1286
ardous chemical.
The OSHA Hazard Communication Standard
Regulatory Provisions (29 CFR 1910.1200) requires that workers in build-
ings who are exposed to hazardous chemicals, as
The United States Department of Health and defined by the regulation (and which would include
Human Services, Food and Drug Administration the FDA amines), be warned of the exposure.
(FDA), in FR 173.310 (April 1999), has limited the There is debate over whether amines introduced as
permissible concentration of treatment chemicals part of an overall mixturei.e., steamconstitute
present in steam that may be in contact with food as a hazard as defined by the standard in the concentra-
follows: tions in which they should normally be utilized in a
well-managed maintenance program (Elovitz 1993).
Cyclohexylamine 10 parts per million (ppm)
Diethylaminoethanol Nonregulatory Publications
(DEAE) 15 ppm A U.S. Navy paper published in July 1990
Hydrazine 0 ppm reported the results of a Navy-funded research
Morpholine 10 ppm project by the National Research Council that inves-
Octadecylamine 3 ppm tigated the use of amines in steam used for steriliza-
tion and humidification (NFEC 1990). The NRC
With the exception of hydrazine, which is an concluded from that study that:
oxygen scavenger, the remaining compounds are Morpholine and 2-DEAE are strong irri-
amines and have come to be regarded as the FDA tants and can convert to nitrosamines,
amines. The American Conference of Governmen- which are known animal carcinogens.
tal Industrial Hygienists (ACGIH) has established a Some amines are known to trigger asthma
permissible Time Weighted Average exposure level attacks.
(TWA) and the Occupational Safety and Health Morpholine and 2-DEAE should not be
Administration (OSHA) a Permissible Exposure used in steam where human exposure can
Level (PEL) for several amines in environmental air, occur.
as indicated in Table 8-1(ICSC 1999; ACGIH 1995). In a Health Hazard Evaluation Report of the
Also indicated in Table 8-1 (in the fourth column) is effects of airborne DEAE exposure resulting from
the odor perception level for each chemical. humidification steam in a museum, the National
Institutes of Occupational Safety and Health
To give an idea of the relative toxicity of these (NIOSH) concluded that health problems resulted
chemicals, the LD50 (mg of chemical per kg of body even though ambient concentrations of the chemical
weight of animal resulting in a 50% mortality rate) were well within the PEL (NIOSH 1983). In that
for these chemicals is shown in Table 8-2. An LD50 instance, NIOSH concluded that eye and dermal irri-
of 50 mg/kg or less is classified as highly toxic. An tation occurred in a number of occupants as a result
LD50 between 50 and 500 mg/kg is considered of contact with condensed DEAE on building sur-
toxic. faces and furnishings. NIOSH recommended that
84 HVAC DESIGN MANUAL FOR HOSPITALS AND CLINICS

DEAE be eliminated from the humidification sys- Coupons or sample ports should be provided to
tem. enable frequent checking for corrosion products. As
A letter written by the U.S. Food and Drug the several amines and other treatment chemicals
Administration (FDA) in April 1980 offered the have differing characteristics affecting their perfor-
agencys opinion that amine concentrations within mance in various parts of the steam system, careful
the limitations permitted for steam in direct contact attention must be paid to the appropriate selection of
with food could be safely used for steam steriliza- chemicals and to the location where they are intro-
tion. duced.

Field Findings/Tests Neutralizing Amines


Industry and government have published several The purpose of neutralizing amines is to neutral-
reports of field investigations into the ambient air ize carbolic acid. These amines are characterized by
concentration of treatment chemicals in buildings their vapor-to-liquid (V/L) ratio, which is an indica-
humidified with treated air. Studies have been con- tor of their availability in the steam or condensate
ducted by major chemical companies and by the phase, respectively. Depending upon the size or
Alkyl Amines Council to determine the range of extent of the steam and condensate distribution sys-
amine levels that could be expected in buildings tem, one or more different neutralizing amines, hav-
humidified by treated steam (Edgerton et al. 1989; ing different V/L ratios, may be required in order to
Grattan et al. 1989; SOCMA 1988, 1991). These protect all portions of the system. In steam distribu-
studies reported ambient air amine concentrations in tion lines, the amines tend to disappear with the con-
the range of 0.0001 to 0.066 ppm, or orders of mag- densate collected and disposed in traps; whereas
nitude less than the regulatory exposure limitations. carbon dioxide, transported along with the steam,
In another report, researchers analyzed, in a labora- continues to travel in the system. This creates a
tory setting, the air concentrations of the three potential for the carbolic acid level to rise, and the
amines (morpholine, DEAE, and cyclohexylamine) pH level to drop, with increasing distance from the
introduced by a treated steam humidification system. steam generator. For extended systems, therefore, the
Although the concentrations of the amines in the feeding of an amine with a high vapor-to-liquid ratio
steam were increased to levels exceeding the regula- will tend to better protect the more remote reaches of
tory limitations for dietary steam, the resulting air- piping. Amines with lower V/L ratios would be more
borne concentrations of the amines were found to be effective in protecting piping closer to the generator.
much below the regulatory exposure limitations. To avoid the unnecessary loss of chemical in boiler
Other sources report similar findings (NIOSH 1996). blowdown, the neutralizing amines are normally fed
However, most researchers and authorities advise directly into the steam supply header.
that these low ambient air concentration levels can
only be guaranteed with careful maintenance and Filming Amines
monitoring, including metered introduction of the Filming amines form a thin barrier on the sur-
treatment chemicals into the steam system. face of piping and equipment to guard against direct
oxygen and carbonic acid exposure. Excessive dos-
8.7.6 Practical Considerations of Treatment age of filming amine can lead to gunk ball forma-
Chemical Application tion, which clogs pumps, traps, and other equipment.
When treatment chemicals are used in steam In addition, when first added to an existing system,
systems for humidification or sterilization, a good filming amines may cause the release of large
maintenance program is required in order to control amounts of iron oxide and scale from piping sys-
the concentration of treatment chemicals in the tems, also causing plugs and fouling. Filming amines
steam, as well as to ensure that the system is ade- have limited volatility and should therefore be added
quately protected against corrosion. Excessive chem- only at the steam header to ensure their distribution
ical levels in the steam may lead to adverse health throughout the system.
effects in exposed persons (as discussed above),
8.7.7 Steam for Sterilization
while inadequate levels can cause wet steam, discol-
oration, poor performance, and equipment failure. Effective sterilization using steam requires
Slug feeding of treatment chemicals should not be direct contact between the item to be sterilized and
permitted; rather, continuous feeding of treatment saturated steam at a temperature of 250F (121C) or
chemicals via metered feed pumps, with daily check- higherfor a suitable length of time to ensure
ing and adjustment of the feed rates, is necessary. destruction of the most temperature-resistant micro-
SPACE AND PROCESS HEATING SYSTEMS 85

organisms. To achieve this temperature, steam must 8.7.8 Steam for Humidification
be delivered at 50-80 psig (345-552 kPa). The latent
energy of vaporization of saturated steam renders it a Steam is considered by most authorities and
far superior sterilant to non-condensing gases, such codes to be superior to evaporative water systems for
as high-temperature air, which is why it is important HVAC system humidification, due to its inherently
to minimize any superheating of the steam supplied sterile nature and lesser tendency to wet air-handling
to the sterilizer. surfaces and contribute to microbe growth. Steam is
normally injected into the air supply by one or more
Excessive superheat may result if the sterilizer perforated dispersion tubes mounted in an air-han-
jacket is maintained at a higher temperature than the dling unit casing or ductwork and directing the spray
chamber (an operational issue) or by excessive pres- against the direction of airflow. Controls should be
sure reduction before the sterilizer connection. Ster- provided to limit the downstream relative humidity
ilizer steam must be very dry 97% quality or better and to prevent humidifier operation when no airflow
to avoid liquid droplet carryover, which can cause is present. Steam for humidification must be of high
wetting and staining of fabrics and instruments. Con- quality and condensate-free to prevent droplet spray
densate from the sterilizing process is considered and moisture accumulation in the equipment. Most
contaminated and is not reused. manufacturers offer the steam jacketed dispersion
tube arrangement preferred by many designers,
Steam Generators wherein the actual dispersion tube is preheated by
Steam for sterilization may be generated by a incoming steam to help dry the injected steam. For
central plant, or by integral (normally electric) gen- jacketed humidifiers, an automatic shut-off valve
erators provided with each sterilizer, as determined should be located upstream of the humidifier assem-
by life-cycle cost considerations and the operational bly. This valve should be closed during periods when
requirements of individual facilities. Central plant humidification is not needed, reducing unnecessary
steam is often the most economical alternative for heat losses from the jacket into the airstream. Even
large health care facilities, particularly if steam of with these types of humidifiers, however, designers
suitable pressure is already available for heating or must carefully design to guard against water accu-
absorption coolingbut central systems require a mulation in ductwork (see additional information on
high level of maintenance capability. Sterilizer man- this subject in Chapter 9). Depending upon the qual-
ufacturers offer integral boilers of carbon steel con- ity of available steam and the permissible level of
struction for the usual filtered steam applications, treatment chemicals, humidifiers may use direct
recommending makeup water with a hardness not boiler steam or steam from a dedicated steam gener-
exceeding 3 to 8 grains per gallon (51-137 grams per ation plant. When central steam is not available or
cubic meter); stainless steel construction is normally economically feasible, humidifier manufacturers
available for applications requiring deionized or offer a variety of small electric, gas-fired, or steam-
demineralized makeup water. to-steam boilers for their equipment.
CHAPTER 9
AIR-HANDLING AND DISTRIBUTION SYSTEMS
9.1 INTRODUCTION 9.2.1 Initial Considerations
Air-handling and distribution systems provide Equipment room locations should permit easy
health care facilities with a comfortable environ- access to equipment by maintenance personnel, with
ment, ventilation to dilute and remove contaminants, outside vehicular access available where needed.
and a supply of clean air for breathing, and they Locate equipment rooms to permit the installation of
assist in controlling the transmission of airborne distribution elements and terminal equipment over
infection. In order to meet these requirements, corridors or other public spaces and to permit main-
HVAC systems must be properly designed to meet tenance personnel to access the equipment without
the applied loads and demands and facility opera- passing through or working inside of patient care
tional requirements. In addition, the systems must be
spaces. Ensure that equipment room space alloca-
properly installed, commissioned, and maintained.
tions are adequate for all equipment, including elec-
The system designer has an opportunity to heavily
trical panels and code clearance requirements.
influence the successful achievement of these fea-
tures of building construction and operation. This Consider also the approximate locations and floor
chapter will discuss aspects of the design that help to area requirements for piping and duct shafts. Lack of
ensure that the air-handling and distribution systems early consideration for equipment space can cause
perform as required throughout the life cycle of the severe redesign effort in later stages of design, often
equipment. impacting the architectural design and too often
resulting in inadequate space for equipment installa-
9.2 CONCEPT DESIGN tion or maintenance.

Design of the air-handling and distribution sys- 9.3 BASIC AIR-HANDLING UNIT
tems should begin during the schematic design phase DESIGN CONSIDERATIONS
of a medical facility to permit the HVAC engineer to
influence the location, arrangement, and size of In providing environmental comfort and ventila-
spaces intended for the installation of equipment tion for a facility, an air-handling unit simulta-
(including distribution elements). The project archi- neously performs several functions including the
tect and building owner should recognize that early intake of outside air to meet ventilation air require-
consideration of equipment requirements will ments, thermal mixing of this air with recirculated
enhance the overall functionality and economy of the air from the occupied zones, thermal conditioning,
facility, contributing to more efficient service distri- moisture control, filtration to protect equipment and
bution, reduction of maintenance traffic in occupied to remove contaminants, and attenuation of fan-gen-
areas, and enhanced flexibility for future modifica- erated noise to control ambient noise levels in occu-
tions or expansion. Postponing consideration of pied spaces.
equipment space requirements until final design
development often leads to poorly located, cramped, 9.3.1 Air-Handling Unit Casing
and inefficient systems and equipment that cannot be
installed without compromising performance or The design of an air-handling unit casing to
maintainability. minimize water and dirt accumulation, resist corro-

87
88 HVAC DESIGN MANUAL FOR HOSPITALS AND CLINICS

sion, and permit adequate access for inspection and tration and nature, the direction of prevailing winds,
maintenance is of fundamental importance. It is and building geometry. Certain airborne pathogens,
important that no open-faced insulation be used such as Legionnaires disease bacteria, are known to
where water accumulation is likely, such as down- have been transmitted much longer distances from
stream from cooling coils or humidifiers. Specifi- aerosolized sources such as cooling towers. Design-
cally, no lining is allowed after final filters in ers must apply professional judgement and, when in
accordance with the AIA Guidelines for Design and doubt, utilize analysis techniques such as those
Construction of Hospital and Health Care Facilities described in the ASHRAE HandbookFundamen-
(AIA 2001). tals, Chapter 14 (ASHRAE 2001a). Individual cir-
Fibrous air-handling unit insulation should be cumstances may justify the use of modeling
isolated from the airstream using an impermeable techniques or field simulation to select the best out-
liner, e.g., Mylar, or sandwiched double-wall sheet side air source locations.
metal construction. The primary concern is that Outside air intakes should be located a mini-
exposed fibrous insulation can collect dust and mois- mum of 8 feet (2.4 m) above grade (10 feet [3 m]
ture to form a perfect growth environment for dan- according to some codes and criteria) to avoid taking
gerous microorganisms, although the insulation in grass clippings, leaves, bird feathers, or other
media may be of inert material that will not of itself debris (often wet) that can clog intake louvers,
support microbial growth. Once contaminated, there screens, and filters and provide a reservoir for micro-
is virtually no way of effectively cleaning or disin- bial growth. When located atop buildings, intakes
fecting insulation. Some manufacturers offer liner should be located well above roof level (a minimum
coatings, which effectively prevent fiber erosion, of 3 feet [0.9 m] according to most codes) to avoid
while still other products are available with plastic or intake of debris from the roof. In cold regions,
foil coverings to exclude dirt and moisture and designers must consider locations for air intakes that
improve cleanability. These materials may not, how- will avoid the possibility of snow drifts. All intakes
ever, have the long-term durability or cleanability of should be equipped with a factory-fabricated louver
sheet metal. All interior air-handling unit surfaces designed to exclude wind-driven precipitation and
must be accessible for inspection and cleaning; liners with a bird screen to exclude birds or small mam-
or interior panels should be of a light color and inte- mals. Avoid placing an intake near horizontal sur-
rior lighting should be available to enhance the effec- faces (such as a shelf or ledge) that can cause rain
tiveness of maintenance tasks. The panels in double- splash to penetrate horizontally through the louver or
wall casings should have a thermal break construc- can become a dangerous microbe growth source
tion to prevent condensation on the outside surface in from collected bird droppings or other organic
humid summer weather. debris.

9.3.2 Outside Air Intakes 9.3.3 Freeze Protection

Designers must carefully consider the location Burst coils or automatic unit shutdown due to
of the outside air intake for an air-handling unit. exposure to subfreezing temperatures are frequent
Intakes must not be located near potential contami- occurrences in buildings and result from a number of
nant sources, such as boiler and generator stacks, factors: inadequate air mixing, unintended exposure
laboratory exhaust vents, plumbing vents, cooling of coils to 100% outside air, condensate backup in
towers, ambulance waiting and vehicle parking steam coils, and improperly located or installed
areas, loading docks, and helipads. Many sources freezestats. The time required to replace a damaged
provide generally accepted criteria for minimum coil and clean up the flooded (and possibly treat-
separation distances from the outside air intake to ment-chemical-contaminated) air-handler casing can
potential contaminant sources to ensure adequate put an air-handling unit out of service for a long
separation and dilution. These spacings vary from 10 period during the most critical environmental condi-
to 75 feet (3 to 23 m)with 25 feet (7.6 m) recom- tions. Water leakage in a casing from a damaged
mended by the AIA Guidelines and 30 feet (9.1 m) cooling coil can provide an environment suitable for
suggested by the ASHRAE HandbookHVAC Appli- microbial growth and may go undetected for an
cations (ASHRAE 1999a). Designers must use extended time. The potential impact to a health care
judgement in the application of such rules, however; facility under such conditions can be very serious
30 feet (9.1 m) may be insufficient separation from a and costly. This chapter will discuss some general
given contaminant source given the sources concen- freeze-prevention considerations and practices. It is
AIR-HANDLING AND DISTRIBUTION SYSTEMS 89

recommended that the design engineer pay particular should also be available for monitoring and alarm
attention to wintertime unit operation to ensure that generation on the system.
he/she has accurately predicted the conditions to
which the unit will be exposednot only during nor- 9.3.6 General Considerations for
mal operation but also during unoccupied, emer- Heating and Cooling Coils
gency, or control failure modes. The upstream and downstream faces of all coils
must be accessible for cleaning or combing
9.3.4 Air Mixing (straightening bent fins). Access panels are normally
Once outside air entry to an air-handling unit required for this purpose. The panel and panel door
should be large enough to enable a maintenance per-
has been successfully addressed, the designers
son to access and work on the entire face of the coil.
attention should focus on the air mixing arrangement
Coils must be constructed of noncorrosive metals,
to ensure that the outside and recirculated (where
typically copper tubing with aluminum fins. Con-
permitted) airflows are adequately mixed to avoid sider the air vent discharge location and direction of
the impingement of stratified, subfreezing tempera- automatic and manual air vents so that entrained
ture air on downstream equipment. Achievement of a water does not leak into the air-handling unit during
uniform mixed-air temperature is a function of phys- air bleeding. To enable necessary testing and balanc-
ical blending (diffusion) and heat transfer. Physical ing of the coil, ensure that pressure gauges and ther-
manipulation of the two airstreams is required to mometers (or ports for these instruments), flow
overcome the natural tendency for air layers of dif- measurement devices, and manual balancing valves
fering temperature to stratify. Manufactured air-mix- are provided on the piping connections. Up and
ing boxes are available from all major air-handling downstream air temperature sensors or sensor ports
unit manufacturers, and the manufacturer will nor- are also beneficial for unit performance monitoring
mally provide guidance as to their performance limi- and troubleshooting. Provide isolation valves and
tations. In severe climates, or where the percentage unions to facilitate coil replacement. Use caution in
of outside air is relatively high, designers should locating coils relative to the suction or discharge of
consider supplemental air-mixing equipment or the fan; if located too close, uneven velocity distribu-
arrangements. Factory-fabricated air blenders are tion across the coil face can result in loss of capacity,
available from a number of manufacturers who offer moisture carryover, or freeze-up problems. Generally
cataloged airflow mixing performance data. While the flow distribution across the coil face should not
there is presently no national standard governing the vary more than 10%.
testing of these devices, they are extensively used by
9.3.7 Preheating Coil
HVAC designers, and if installed with proper inlet
and outlet conditions, and with adequate airflow In many applications, a preheat coil is located
velocity, as recommended by their manufacturers, downstream from the prefilter and before the cooling
they can significantly improve airstream mixing. coil. Preheat coils may utilize hot water or steam and
are normally provided when the mixed air tempera-
9.3.5 Prefiltration ture is lower than the air handlers design discharge
air temperature or when it is necessary to protect
A roughing prefilter of approximately 30% downstream equipment from near- or below-freezing
dust spot efficiency (ASHRAE 1992) (or MERV 7 mixed air temperatures. In addition to considering
[ASHRAE 1999b]) is required within or immedi- performance under design conditions, designers
ately downstream of the mixing box and upstream should think about how the coil should perform
from the heating and cooling coils. This filter under the most severe conditions that it may encoun-
removes lint, dust, and other large particles from the ter. For example, a fan that is designed to operate
airstream before they can collect on or clog coils or with 100% outside air during an emergency smoke
other components. Throw-away, replaceable, car- evacuation mode should have a preheat coil properly
tridge filters require less maintenance than cleanable sized to raise the discharge air temperature above
or roll-up filters and are usually specified for this freezing. Specific coil freeze considerations include
reason. All filters should be provided with differen- the following.
tial pressure gauges mounted on the air-handling
Freeze Considerations for Steam Coils
unit, reading differential static pressure across the
filter to indicate when the filter should be changed. Frequent steam coil freeze failures have resulted
When the facility is provided with a central DDC, from exposure of the condensate-filled portions of
EMCS, or BMS system, filter pressure indication the coil to freezing air temperatures. Designers
90 HVAC DESIGN MANUAL FOR HOSPITALS AND CLINICS

should, therefore, pay particular attention to conden- damaged. Too frequently, however, improper instal-
sate drainage from the unit. Be aware that modulat- lation of the freezestat has led to damaged coils. The
ing steam control valves may cause negative freezestat consists of a long length of sensor tubing
atmospheric pressure in the coil, increasing the vol- that must be installed in a serpentine fashion across
ume of condensate backup; providing a vacuum the entire face of the coil so as to detect any localized
breaker will permit the condensate to drain by grav- freezing temperatures due to air stratification. When
ity. Many designers prefer a face-and-bypass inadequate space is provided for sensor installation,
approach for steam coil discharge temperature con- the tubing is frequently placed as a coiled bundle,
trol, keeping the steam coil control valve fully open which vastly compromises its effectiveness. For this
at all times and regulating airflow around the coil to reason, as well as to enable cleaning the upstream
maintain discharge setpoint. This arrangement, while face of the cooling coil, an upstream access panel
undoubtedly successful in many applications, does must be provided, with suitable dimensions to enable
not necessarily eliminate the danger of condensate a maintenance technician to access the entire face of
buildup in the coil. the coil.

Freeze Considerations for 9.3.9 Cooling Coils


Heating Water Coils In addition to providing sensible cooling, a cool-
When hot water coils are used, designers must ing coil acts as a dehumidifier and (for the latter pur-
determine whether to utilize an antifreeze solution in pose) must normally have a high heat transfer
the system. A solution containing a large percentage surface area consisting of at least six tubing rows
with relatively tightly spaced fins. As the heat trans-
of glycol can provide freeze protection to well below
fer surfaces remain (virtually) continuously wet,
0F (18C). In addition to reducing heat transfer
cooling coils easily collect dust and can become a
and increasing the pumping energy requirement,
microbe growth site. For this reason, an ability to
however, there are significant maintenance consider- clean the coil is extremely important. A large num-
ations associated with the use of an antifreeze solu- ber of coil rows and close fin spacing make cleaning
tion. Maintenance personnel must maintain the difficult; it is, therefore, normally recommended that
glycol/water percentage selected by the designer; coils do not exceed 6 rows or more than 12-14 fins
often this is not handled properly and the mainte- per inch (25 mm). When additional rows are
nance personnel merely guess the glycol percentage required, the cooling coil should be split into two
based on the color of the solution. Care must also be separate coils (in the direction of airflow). Both
given to using the correct antifreeze formulation; upstream and downstream faces of the cooling
there are several reported instances of maintenance coil(s) must be accessible to a maintenance worker
personnel mistakenly introducing automotive anti- using a power washer. Other cooling coil consider-
freeze into heating systems, leading to undesirable ations include the following:
deposits (gumming up) in the heating coils. When
properly used and designed, however, glycol systems Moisture Carryover
can be a very attractive freeze protection option. One In order to avoid carryover of droplets from the
of the most universally utilized freeze protection cooling coil into the air-handling unit casing, the air
approaches for heating coils, whether using anti- velocity through the cooling coil must be limited.
freeze solutions or untreated water, is the use of ded- Designers typically permit a maximum velocity of not
icated circulating pumps. The circulating pump more than 450-550 feet per minute (2.3-2.8 m/s),
maintains a continuous circulation of water in the although with special fin coatings this velocity may be
coil throughout the heating season. The combination increased to 600-625 feet per minute (3.1-3.2 m/s). If
of continuous flow and pump heat can provide a sig- capacity for future load growth (airflow increase) is
nificant degree of freeze protection. desirable, it may be reasonable to size a coil for a
velocity lower than 450 feet per minute (2.3 m/s).
9.3.8 Air-Handling Unit Freezestat Cooling coils must be provided with positively
draining pans constructed of noncorrosive materials
A freezestat is normally located on the upstream (i.e., stainless steel) for the collection and disposal of
face of the cooling coil (the location may differ, condensate and to avoid standing water. An over-
depending upon air-handling unit design and config- sized condensate drain pan can have an adverse
uration). The freezestats function is to detect sub- effect and provide locations for microbial growth.
freezing temperatures, sound an alarm, and shut Pans should reach entirely beneath the coil and
down the air-handling unit before the coil can be extend approximately 12 inches (300 mm) from the
AIR-HANDLING AND DISTRIBUTION SYSTEMS 91

discharge face. The pan should be at least 2 inches


(50 mm) deep, with a drain pipe located so that the
bottom of the pipe is flush with the bottom of the
pan. When coils are stacked vertically, a separately
trapped drain pan should be provided for each coil.
All drain pans must be properly trapped to ensure
that the condensate continues to drain during fan
operation. Trap leg dimensional and configuration
requirements will differ based upon whether the coil
is under negative (draw-through configuration) or
positive (blow-through configuration) pressure. In
both cases, maintenance of the trap seal is important
to avoid drawing sewage gases into the air-handling
unit.
Figure 9-1 illustrates a condensate drain trap for Figure 9-1 Drain trap for coil subjected to nega-
tive pressure.
a coil subjected to negative pressure. Unless the trap
is properly constructed to provide a positive gravity
head on the pan-inlet sideexceeding the negative
pressure imposed by the unit fancondensate will
not drain from the unit. Dimension A equals
B+C, where B is the maximum air-handling unit
static pressure plus 1 inch (w.g.) (250 Pa), and C is
B.
Figure 9-2 shows the proper configuration for a
drain trap for a coil under positive pressure. In this
case, the outlet leg of the trap must be high enough to
offset the positive static pressure on the inlet side,
which would otherwise blow out the trap seal.
Dimension A equals the maximum air-handling
unit static pressure plus inch (w.g.) (125 Pa), and
B is inch (13 mm) minimum. Figure 9-2 Drain trap for coil subjected to posi-
tive pressure.
9.3.10 Supply Fan Considerations
Designers should apply real world operation avoid excessive pressure losses or velocities in the
and maintenance considerations to the selection of downstream components.
an air-handling unit supply fan to help ensure satis-
factory long-term operation. The as-constructed air System Effect. Cataloged fan performance is
system pressure-flow characteristics, and, therefore, normally based upon laboratory conditions at
the fan operating point, often differ from the calcu- the fan inlet and outlet, which often cannot be
lated values. It is a good idea to ensure that the spec- duplicated in the field and which maximize the
ified fan motor horsepower is sufficient to provide performance of the fan. When conditions are
for fan operation along a broad range of the fan oper- less ideal, fan performance will be less than cat-
ating curve. Select fans so that their normal operat- aloged. The term system effect is used to
ing point will not be within the surge range. Consider describe the loss of performance resulting from
the need to attenuate fan-generated noise that may non-idealized inlet or outlet conditions. Typi-
transmit through the distribution system to occupied cally, system effect is expressed in inches of
spaces. Airfoil-bladed centrifugal fans and plenum- water pressure loss (pascals) or in multiples of
style fan arrangements tend to be less noisy than the velocity head at the fan discharge. On the
other alternatives. When final filters or coils are suction side, system effects can result from such
located downstream of the fan discharge, a discharge factors as restricted inlets, flow obstructions
air diffuser may be required (depending upon condi- (such as bearings or inlet vanes), and air pre-
tions) to equalize the outlet velocity profile and spin caused by improperly designed elbow con-
92 HVAC DESIGN MANUAL FOR HOSPITALS AND CLINICS

nections. On the discharge side, system effects 9.3.11 Return Fan Considerations
result from obstructions by fittings or equipment
(coils, elbows, takeoffs) located too close to the Return fans are normally required for air-han-
fan connection or by discharge into an open ple- dling units employing an economizer (free cool-
num. Most air-handling unit manufacturers, and ing) system. As with the supply fan, consideration
several industry references and standards, pro- must be given to fan noise generation and the need
vide guidelines for estimating the system effect for attenuation to reduce the sound transmitted
resulting from various inlet and outlet arrange- through the return ductwork to occupied spaces.
ments, one source being AMCA 201 (AMCA Ensure that adequate space is available for personnel
1990). It is very important for the design engi- access to all parts of the return fan requiring inspec-
neer to read air-handling manufacturers litera- tion or periodic maintenance. As with supply fans,
ture when selecting a fan to understand under the design engineer will need to evaluate the system
what conditions the fan was tested so that the effect (reduced fan performance) resulting from
appropriate system effects can be estimated. inlet and outlet conditions. Fan type selection must
Several manufacturers base their air-handling consider required performance and equipment space
unit fan performance on ARI Standard 430 (ARI availability for each application.
1999), which tests the fans within the factory
housing (suction plenum) but with several diam- 9.3.12 Humidifiers
eters of straight ductwork connected at the dis-
Humidifiers are often required in health care
charge. This is not true, however, in all cases.
facility air-handling systems to maintain a minimum
Belt Losses. The laboratory conditions used to level of relative humidity in the occupied spaces.
test fans normally involve the fan being driven Most criteria establish a 30% RH minimum, with
by a direct-drive dynamometer. Thus, the fan possibly higher levels in critical spaces. The com-
power information published in manufacturers plexities of humidifier design and maintenance are
catalogs will often not include the effects of belt often underestimated by designers, with the result
losses, which can consume up to 3-5% of total that the devices are frequently disconnected by main-
motor output, depending upon belt drive charac- tenance personnel or cited as a cause of contamina-
teristics, belt tension, etc. (Carrier 1997). tion and corrosion within the air-handler or
ductwork. Designers must carefully consider the
Fan selection for a given application requires selection and location of humidifiers within air-han-
designer consideration of the performance character- dling units or ductwork to avoid moisture accumula-
tion in downstream components, including filters
istics, and space requirements, of the various fan
and insulation. Humidifier design considerations
types or variants available. Centrifugal fans are nor-
include the following.
mally, but not exclusively, selected for supply fan
applications for major air-handling units. Centrifugal
Humidifier Types
fans are available with forward curved, backward
curved, and airfoil-bladed scroll vanes, each variant Most designers, and many codes, recommend
having distinctive relative speed, noise generation, steam injection type humidifiers for health care facil-
efficiency, and power (overloading versus non-over- ity applications. Steam is sterile and, therefore, elim-
loading) characteristics. In addition, centrifugal fans inates the risk of introducing viable microorganisms,
are available with open (plenum) or directed dis- such as Legionella, into the building airstream. Steam
charge arrangements, involving differing noise gen- may be generated centrally (boiler or heat exchanger)
eration, system effect, and equipment space or locally at the humidifier by a separate electrical or
considerations. steam-to-steam generator. Small gas-fired units are
also available. Regardless of the steam source, care
Vane-axial type fans are also sometimes selected must be taken to ensure that only dry steam is supplied
for supply fan applications. Formerly, these were to the steam injector. Consult manufacturers recom-
very commonly used for variable volume applica- mendation for appropriate condensate trapping and
tions. With the advent of reasonably priced variable drainage provisions and ensure that appropriate
speed drives, however, this application has become details and instructions are communicated via con-
less popular. Variable pitch vane-axial fans have struction drawings. Evaporative and spray mist evap-
many moving parts and they are prone to significant orators are also available for humidification
maintenance requirements. applicationswhere permitted by applicable codes.
AIR-HANDLING AND DISTRIBUTION SYSTEMS 93

Avoiding Wetting of Air-Handler or vided downstream to ensure complete evaporation of


Duct Components moisture droplets. Proper maintenance access is vital
When saturated, dry steam is injected into the for this type of humidifier installation.
airstream, a portion of the steam is immediately con-
densed and forms a mist or vapor trail of water Sizing and Control Considerations
particles. Unless a suitable expanse of downstream With VAV systems, most designers size air-han-
duct or air-handler casing is provided to permit dling unit humidifiers on the basis of lower winter
reevaporation, the mist will impinge on downstream season air flow and corresponding outside design
equipment and cause water buildup. Filters, exposed temperature. When operating in economizer mode, a
insulating materials, and even sheet metal can easily humidifier sized according to such criteria may be
become microbe growth sites in these circumstances, unable to achieve desired supply air RH setpoint.
and fans and other steel air-handling and ductwork
components will quickly rust. The distance required 9.3.13 Air-Handling Unit Noise Attenuation
for reevaporation is a function of air temperature, rel-
ative humidity, velocity, casing or duct dimensions, In many cases the designer will find that attenu-
and the design of the humidifier componentsand ation of fan noise (supply, return, or both) will be
can vary from a few inches (several mm) to more required in order to achieve room background noise
than 12 feet (3.6 m). levels required by design criteria. This is often a con-
cern with the double-walled air-handling units
Some designers prefer to locate humidifiers
required for health care facilities because the interior
within the air-handling unit. Sometimes this is the
sheet metal wall resists noise breakout and helps to
only location available due to space or other con-
transmit the noise through the ductwork. When
trants. As air velocities are low in an air-handling
attenuation is required, the designers only options
unit casing, use of multiple humidifier manifolds
are to provide acoustically lined ductwork, active
(see Figure 9-3) allows the steam to be readily
electronic silencers, or factory-fabricated sound
absorbed into the air. In some situations, a down-
attenuators. Packless type attenuators and active
stream moisture eliminator may be desired to pro-
silencers have limited application and efficacy, often
vide additional protection against wetting of
leaving packed-type liners and attenuators as the
downsteam air-handling components. Humidifier
only practical choice. This chapter has already dis-
installation in the air-handling unit will also nor-
cussed concerns with permitting a water-permeable,
mally allow for a final, high-efficiency filter to be
unsealed insulation surface to be exposed to the air-
installed downstream from the humidifier as an
stream. Several manufacturers, however, offer dou-
added protection against the potential presence of
ble-walled attenuating ductwork or fabricated
microbial elements.
attenuators with perforated inner sheet metal hous-
It is also common practice for a humidifier to be
ings and impermeable foil or plastic liners, which
installed outside of the air-handling unit casing in the
probably offer the best compromise between durabil-
discharge ductwork. In such cases, a suitable length
ity/sanitation concerns and the need for noise attenu-
of straight, unobstructed ductwork should be pro-
ation. The foil or plastic liners do not drastically
reduce attenuation performance. Their flame spread/
smoke generation characteristics, however, should be
checked against the limiting requirements of NFPA
90A or applicable codes. Due to installation space
limitations, and to improve the inspectability and
cleanability of the interior surfaces, fabricated atten-
uators are often chosen over attenuating ductwork.
Attenuator inlet and outlet conditions must also
be considered. The noise-attenuating properties and
pressure-flow characteristics cataloged by attenuator
manufacturers are based upon smooth inlet and out-
let duct transitions, which are normally available in
their literature lines. Many designers do not realize
that without proper transitions the pressure loss
Figure 9-3 Steam humidifier with multiple man- across a sound attenuator can be several times the
ifold. cataloged value and the attenuator can actually gen-
94 HVAC DESIGN MANUAL FOR HOSPITALS AND CLINICS

erate more noise than it attenuates. The designer lishing that profile normally requires a certain extent
needs to include suitable transition space and pro- of straight upstream duct, usually specified by the
vide appropriate details and instructions for the con- device manufacturer in terms of unit diameters, and a
tractor. smoothly transitioning discharge arrangement.
Designers should consult manufacturers recommen-
9.3.14 Second Filter Bank dations, ensure that the space requirements are taken
into account in laying out the fan room, and reflect
Many of the spaces in a health care facility
the requirements in the construction documents.
require a higher level of filtration than is provided by
Designers also need to consider the range of flow
a prefilter (typically 30% dust spot efficiency) alone.
that they intend the device to measure to ascertain
The AIA Guidelines, for example, recommend a fil-
that it is not only sufficiently accurate over that range
tration level of 95% (MERV 14-15) for all patient
but can physically sense flow at lower velocities (a
care areas, whether in clinics or in full-service hospi-
particular concern with pitot-type velocity sensing).
tals. Some codes require HEPA filtration for inpa-
tient applications, especially where patients are
9.3.16 Dehumidification Equipment
particularly vulnerable to infection, such as protec-
tive isolation rooms for immunocompromised Dehumidification by the primary cooling coil is
patients and orthopedic operating rooms. Designers often sufficient to limit relative humidity to the max-
must ensure (and require in contract documents) that imum values permitted by codes. Very stringent
space is allocated for replacing filters. All filters upper limit relative humidity requirements may dic-
should be provided with a differential pressure indi- tate supplemental dehumidification using mechani-
cating manometer mounted on the air-handling unit cal refrigeration or desiccant equipment. Some
to indicate when replacement is required. designers address this issue by providing automatic
The second filter (normally the final filter controls to reset the cooling coil discharge tempera-
installed in the air-handling unit) is (along with the ture below that required for cooling to provide dehu-
cooling coil) a determining factor in establishing the midification; such a strategy requires reheat of the air
overall dimensions of the air-handler. Design air supply for comfort conditioning.
velocity for health care facility air-handling unit fil-
ters should not exceed 500 fpm (2.5 m/s) for filters 9.4 AIR-HANDLING SYSTEM
of 95% efficiency (MERV 15) and below. HEPA and ALTERNATIVES
higher efficiency filters (MERV 17 and above)
Chapter 5 of this manual deals with the various
should be designed with a 300 fpm (1.5 m/s) velocity
limit. To ensure adequate airflow throughout the HVAC systems and where they are (or are not) typi-
range of filter resistance from clean to dirty, design- cally recommended for use. This chapter addresses
ers should use the filter manufacturers recom- only some of the major considerations involved in
mended final resistance when calculating fan selecting among the most common system alterna-
pressure requirements. If no final resistance recom- tives. Depending upon the facility department or area
mendation is available, a value of 1.4 in. w.g. (350 under consideration, single- and dual-duct systems,
Pa) is recommended for 80%-95% efficiency filters both constant and variable air volume (VAV), are fre-
(MERV 13-15). Be aware that when filters are quently encountered in health care facilities. Multi-
clean, resulting in system resistance lower than the zone systems are less frequently encountered due to
fan selection point, the fan motor must be adequately the larger number of ducts associated with these sys-
sized to accommodate the higher brake horsepower tems. Many, but not all, code authorities will permit
requirements at that operating condition. VAV systems to serve spaces that do not have spe-
cific relative pressure requirements, including exam-
9.3.15 Airflow Monitors ination rooms and normal patient bedrooms, in
Airflow monitoring arrays are often provided in addition to administrative and office spaces. Con-
the return and supply airstreams for VAV systems to stant volume systems are commonly used for spaces
enable differential supply-return fan flow control. In such as disease isolation and ICU bedrooms, operat-
addition, they are frequently employed, in both VAV ing rooms, and laboratories, where discrete pressur-
and constant volume systems, to monitor outside air ization relative to contiguous spaces must be
flow. In order to accurately measure velocity (and maintained. VAV systems should be able to perform
therefore flow volume), monitoring arrays require a in these applications given appropriate attention to
reasonably uniform entering velocity profile. Estab- pressure control and minimum ventilation require-
AIR-HANDLING AND DISTRIBUTION SYSTEMS 95

ments. When a designer has more than one system zone system mixes hot and cold airstreams at zone
alternative to consider, the choice should be influ- dampers located within the air-handling unit in
enced by life-cycle cost analysis. response to the zone temperature sensor. These sys-
tems are manufactured in configurations serving as
9.4.1 Variable Air Volume (VAV) Systems many as 12 zones per air-handler. Multizone systems
VAV systems provide fan energy savings offer the advantage of having the primary tempera-
through variation of the volumetric flow rate of con- ture controls and equipment located in a central loca-
ditioned air when loads are less than peak. These tionat the air-handling unitin lieu of being
systems may sometimes permit use of reduced fan distributed throughout the facility. With so many
sizes, as compared to constant volume systems, supply ducts branching off a single air-handling unit,
when peak loads in the areas served do not occur however, distribution space is a primary concern.
simultaneously. Fan capacity is normally modulated The multitude of duct, cable tray, and piping systems
using variable inlet vanes, or variable speed motor associated with a health care facility, coupled with
drives, in response to static pressure sensors located architectural or structural features limiting the avail-
downstream (usually two-thirds the distance) in the able vertical space, often make these systems
air distribution system. Another control strategy impractical.
using the position of terminal volume controllers
(automatic dampers) can also be considered. Single- 9.4.4 Draw-Through and Blow-Through
duct VAV systems require some means of terminal or Selection Considerations
space reheat to ensure adequate zone temperature
control. Dual-duct VAV systems, with separate In determining the type of air-handling system
heated and cooled air ducts, mix hot and cold air at to be utilized for a health care facility, the designer
the terminal unit to maintain the zone temperature often has the choice of either a draw-through or a
setpoint. blow-through fan-cooling coil arrangement. With a
draw-through arrangement the fan is located down-
With VAV systems, it is important that the termi-
stream of the cooling (and heating) coil. With a
nal unit flow rate at minimum box position be suffi-
blow-through arrangement, the locations are
cient to meet minimum ventilation rate criteria. Flow
reversed. With dual-duct and multizone systems, the
rate in the heating mode must be adequate to provide
arrangement is always blow-through. For other sys-
acceptable air distribution in the space. VAV systems
tem types however, such as the very common single-
are prohibited by some codes from serving spaces
duct constant and variable volume systems, the
with relative pressurization requirements.
choice of draw-through versus blow-through
9.4.2 Constant Volume (CAV) Systems requires careful consideration of several factors that
can adversely affect system performance and accept-
Compared to VAV systems, CAV systems typi- ability.
cally involve higher operational energy costs due to
their inability to reduce fan energy during periods of System Effect. The draw-through and blow-
low cooling demand. Their control complexity is, through arrangements can create different sys-
however, correspondingly lower, and their compara- tem effects. As discussed in section 9.3.10, poor
tively lower first cost and annual maintenance and fan inlet or discharge arrangements can result in
first costs can make CAV systems life-cycle cost lowered fan performance. Many air-handling
competitive with VAV. CAV systems are typically unit manufacturers rate their fan performances
designed to distribute a cooled air supply to terminal with the fan operating within its inlet plenum,
reheat coils (single duct) or mixing boxes (dual duct) which takes into account any adverse effects
serving individual zones. Since these systems do caused by the plenum. In such cases, the design
not reduce room airflow rate during heating mode, engineer does not need to evaluate the system
they can provide consistent room air distribution, effect of upstream modules or components,
particularly in perimeter spaces (see Section 9.8 for other than to account for their flow losses. With
further information). built-up units or special construction, however,
the design engineer must use care to evaluate the
9.4.3 Multizone Systems system effects of upstream components or con-
ditions. With a draw-through unit, care must be
Multizone systems are a type of constant vol- taken not to locate the upstream coil too close to
ume system, involving a dedicated supply duct from the fan inlet. A minimum upstream separation
the air-handling unit to each zone served. A multi- between the coil and the fan casing of fan
96 HVAC DESIGN MANUAL FOR HOSPITALS AND CLINICS

wheel diameter for single-inlet centrifugal fans coils. To help reduce the chance of wetting the
and 1 wheel diameter for double-inlet fans has filter, the cooling coil face velocity should be
been recommended (Trane 1982). With a blow- limited to 450 fpm (2.3 m/s).
through arrangement, the downstream coil can Cooling Coil Trap Design. The cooling coil con-
cause an adverse system effect if located too densate drain will be under either negative or
close to the fan discharge. In addition to lower- positive pressuredepending upon which
ing performance, a coil located too close to the arrangement is selectedwhen the fan is oper-
discharge can result in uneven velocity distribu- ating. Refer to Figures 9-1 and 9-2 for design
tion across the coil face, diminishing coil capac- recommendations.
ity and possibly creating droplet carryover.
Issues Summary. Key issues affecting the selec-
When the coil cannot be located a suitable dis-
tion of a draw-through or blow-through air-han-
tance downstream from the fan discharge, a baf-
dling configuration include:
fle plate (typically recommended to be 50%
perforated) located downstream from the fan,
Draw-through advantages: A compact unit
approximately two-thirds of the distance to the
length; more efficient fan operation when
coil, will provide a more even air distribution
across the coil face discharge is properly designed; a reduced
incidence of moisture carryover from the
Draw-Through Fan Reheat. The air leaving the cooling coil as a result of more uniform coil
cooling coil in an air-handling unit is often very face velocities.
close to the saturation point. This may also be Draw-through disadvantages: Poor mixing
the case if a humidifier is provided, although of return and outside air that may cause
controls are normally set to limit the airstream temperature stratification and tripping of
relative humidity to not more than 85%. Various the freezestat; supply air temperature down-
system factors can cause a saturated airstream to stream of the cooling coil increases due to
condense on downstream equipment, fittings, fan heat (a concern if not properly
filters, or ductwork, contributing to microbe addressed during design).
growth Many designers choose a draw-through Blow-through advantages: Heat load from
design to take advantage of the reheat high-pressure fans is absorbed by the cool-
imparted by the enthalpy input at the supply fan, ing coil, permitting a higher discharge air
thus heating the airstream a few degrees above temperature for any given space load; the
the saturation point. Blow-through fan arrange- fan more thoroughly mixes airstreams,
ments cannot take advantage of fan heat for this reducing stratification and nuisance freez-
purpose, and wetting of downstream compo- estat trips; less of the unit casing is sub-
nents can be a significant concern. jected to the high-humidity environment
Final Filter Location. Locating the final filter downstream of the cooling coil.
too close to the fan discharge, under either Blow-through disadvantages: To prevent
arrangement, can lead to uneven air distribution moisture carryover from the cooling coil,
across the filter and possible damage from face velocities must be on the order of 400-
excessively high velocities. A greater concern, 450 fpm (2.0-2.3 m/s); the unit is larger;
however, is potential wetting of the filter if more careful design is required.
located in the saturated airstream downstream
from the cooling coil or humidifier. Wet filters 9.5 DUCTWORK
easily become microbe growth sites, due to the
availability of moisture and nutrients (dirt) at the 9.5.1 General Design Considerations
same location. In addition, the capture of mois- Duct systems for health care facilities may be
ture droplets by filters can vastly increase filter designed using any of the major duct sizing
pressure drop, leading to reduced system venti- approaches described in the ASHRAE Handbook
lation performance. One major air-handling unit Fundamentals and SMACNA and other industry
manufacturer recommends against locating the publications, including the equal friction, static
final filter downstream from the cooling coil in a regain, T-method, and other approaches. Fundamen-
blow-through configuration (Trane 1996). This tals provides guidance as to velocity and pressure
may create a dilemma when code or criteria pro- loss limitations, as well as economic considerations
visions (such as the AIA Guidelines) require of the several methods. Designers should be aware
that final filters be located downstream of the that careful attention to duct system velocity limita-
AIR-HANDLING AND DISTRIBUTION SYSTEMS 97

tions is especially warranted in health care facility avoided, especially in exhaust and return sys-
design, due to the common imposition of back- tems, because they collect dust and debris, lead-
ground noise level criteria. Due to the variety of ing to reduced airflow performance.
systems required for health care service, the duct- Flexible duct use should be limited due to its
work design must be carefully coordinated with the higher pressure losses, particularly when
electrical, fire protection, plumbing and HVAC pip- crimped or coiled, and its greater susceptibility
ing, and other building services, as well as with to abuse or damage. Many designers limit flex-
architectural and structural elements, to ensure suffi- ible duct connections to a maximum length of 5-
ciency of space. Most designers recommend fully 6 feet (1.51.8 m).
ducted installations, using all-metal duct construc-
tion, particularly for inpatient facilities, and the 9.5.2 Fully Ducted versus Plenum Returns
avoidance of duct liner except when absolutely nec-
essary to attenuate ductborne noise. Other health Most designers prefer fully ducted return sys-
care facility ductwork considerations are as follows. tems in health care facilities, including outpatient
clinics, largely due to their inherently superior sani-
Various organizations, including ASHRAE and tary characteristics. Some codes mandate fully
SMACNA, publish guidelines for selecting fit- ducted systems for all inpatient facilities. Ducted
tings and determining pressure losses. The man- returns protect the airstream from direct exposure to
ufacturers of distribution equipment such as such potential plenum conditions as accumulated
diffusers, sound attenuators, fire dampers, and dust, microbes or odors generated by wet materials
inlet louvers normally publish pressure loss (from piping leaks, roof leaks, or floor leaks in
characteristics. Designers must be cautious, multi-story facilities), rodent droppings, fibers from
however, because the published pressure losses deteriorated flame proofing or equipment, and
(as well as noise output levels) often correspond smoke from smoldering wiring insulation or other
to specific idealized inlet or connection sources during a fire. To minimize the latter possibil-
arrangements that may not be possible in actual ity, NFPA codes require that electrical cables
building situations. installed in plenums utilized for air movement must
Designers should be careful to show or specify be of the plenum-rated type. Above-ceiling plenums,
the duct pressure classes for supply, return, and in particular, are prone to disturbance by mainte-
exhaust ductwork to ensure adequate construc- nance activities that could release opportunistic fungi
tion and sealing according to SMACNA stan- or allergens into a return airstream. Ducted returns
dards. in addition minimize cross-talk wherein audible
Designers must ensure that specifications or conversations are transmitted between rooms via
drawings include provisions for the necessary open return connections, particularly when room
fittings to enable testing and balancing. Splitters partitions do not extend above the ceilings.
(when allowed and permitted) and balancing
dampers must be shown or detailed wherever 9.5.3 Duct Cleaning
required. Designers should provide suitable Ductwork collects deposits of dust and can
ductwork configurations to enable accurate pitot become contaminated with microbial colonization.
traverses in main and branch ductwork. The extent of this problem varies with the level of fil-
Access openings should be provided where tration, HVAC system maintenance, geographic
required for system maintenance and inspection. location, climate, and other factors. Accumulated
These include not only suitably framed and gas- dust in ductwork has been implicated by some scien-
keted (as required) openings in the duct but also tific studies with increased occupant health com-
coordination with the architectural design to plaints, such as itchy eyes, cough, and allergic
ensure that corresponding ceiling access is pro- reactions (Brosseau 2000a). Numerous studies also
vided. Duct access doors should be provided at attribute hospital nosocomial infection outbreaks to
fire and smoke dampers, on both sides of duct- microbes growing in ductwork or air-handling equip-
mounted coils, at humidifiers, and as required ment. In addition, excessive dust buildup in ducts
by the client or codes to facilitate duct cleaning. can result in significantly reduced air system perfor-
Whenever permitted by space conditions, utilize mance, including underventilation. In recent years
long radius elbows to minimize pressure losses large numbers of companies have emerged that spe-
and improve performance and cleanliness. cialize in ductwork cleaning, and the National Air
Square elbows with turning vanes should be Duct Cleaners Association has published guidelines
98 HVAC DESIGN MANUAL FOR HOSPITALS AND CLINICS

and specifications for this work (NADCA 2002). erly trained and qualified personnel, and that all nec-
Cleaning processes require access into the interior of essary containment and protective measures be
the ductwork and involve placing the duct under vac- carefully adhered to.
uum in combination with mechanical or power In order to facilitate duct cleaning, designers
brushing, air washing, contact vacuuming, and should provide duct access door openings in accessi-
sometimes steam cleaning. In addition, microbial ble locations at periodic intervals in major ductwork
biocides and encapsulants may be utilized. The and at the fittings where dust is likely to most heavily
effectiveness of duct cleaning in reducing the inci- accumulate (as indicated above). A survey of duct-
dence of hospital nosocomial infection is in question. cleaning companies also recommended that to mini-
The process of cleaning may, particularly without mize dust accumulation, designers avoid the use of
careful coordination with the hospital staff and the interior duct linings or glass fiber ductwork.
exercise of stringent containment measures, actually The Centers for Disease Control (CDC) and
increase the level of contaminants within a health U.S. Environmental Protection Agency (EPA) advise
care facility. that there is no indication that duct cleaning results
Studies have shown that dust accumulated in in a lower incidence of infection or other health
ductwork contains large amounts of organic materi- problems (CDC 2001). It is recognized, however,
als such as human and animal hair, skin flakes, fun- that cleaning can result in improved air system per-
gal spores, insect parts, and plant materials formance. The general industry position for hospitals
(Brosseau 2000a). These materials can provide nutri- appears to be that routine duct cleaning may be justi-
tion for microbe growth and can themselves cause fied on exhaust systems, and perhaps return systems,
allergic reactions in sensitive persons. Dust buildup due to their greater potential for dust accumulation
occurs to a much greater degree in unfiltered duct and the lesser risk of redeposition of dust into the
systems, such as return or exhaust ducts, and in par- facility, but that careful consideration be given
ticular upon fittings against which the airstream before cleaning supply ductwork. For facilities with
impacts or that cause high turbulence eddies (such as inpatient spaces, and particularly for those housing
fan plenums, elbows, turning vanes, and dampers). immune-compromised patients, duct cleaning should
It is known that duct-cleaning operations can only be considered in cases of severe contamination,
release large quantities of airborne particles, and using the most carefully planned procedures, with all
high levels of chemical compounds, into the general necessary isolation and protective measures under-
hospital environment (Brosseau 2000b). Although stood and enforced by both contractor and hospital
standard procedures place the duct being cleaned staff.
under negative pressure (vacuum) during the proce-
dure, the surrounding area can become contami- 9.6 TERMINAL UNITS
nated, if the negative pressure is carelessly
Terminal units are control devices installed
maintained, by not providing adequate time for dis-
between the ductwork system and the room air distri-
infecting or encapsulant chemicals to dry or by work
bution system. Depending upon the application, they
done outside of the duct to gain access for the proce-
could be constant volume, variable volume, or fan
dure. An increase in the level of airborne particles,
powered, with or without reheat. Terminal units are
including opportunistic microbes such as Aspergillus
divided into two broad categories: constant volume
that are a frequent component of building dust, is
and variable volume. A terminal unit is considered to
known to increase the risk of nosocomial infection in
be variable volume if the airflow to the space varies.
hospitals, particularly among the immune-compro-
If variable volume is selected, the designer must
mised. Chemical applications, particularly when
ensure that minimum air flow output is adequate to
improperly applied or mixed, can result in occupant
meet outside air and total air ventilation requirement.
complaints of irritation or adverse health effects. At
Airflow is constant for constant volume terminal
least one hospital investigation correlated a higher
units.
incidence of occupant health complaints during a
duct-cleaning/disinfection procedure with symp-
9.6.1 Constant Volume Terminal Unit
toms corresponding to MSDS data for the chemicals
being used (Carlson and Streifel 1996). For these Constant volume terminals are connected to a
reasons a number of authorities and industry associa- constant volume fan system that serves multiple
tions strongly advocate that duct-cleaning projects be zones. Supply air is cooled to satisfy the zone with
carefully coordinated beforehand with the facility the largest cooling load. Air delivered to other zones
staff, that the procedure be carried out only by prop- is then reheated with heating coils (hot water, steam,
AIR-HANDLING AND DISTRIBUTION SYSTEMS 99

or electric) installed in individual zone terminals. include a reheat coil. Then, when the supply air
The reheat control is reset as required to maintain the reaches its minimum level, the valve to the reheat
space temperature. coil begins to open. Designers should note that some
authorities may not allow these units in health care
9.6.2 Variable Volume Terminal Unit applications due to possible contamination concerns.
This type of terminal, also known as a throt-
9.6.5 Plenum Fan Terminal Unit
tling terminal, has a damper in the inlet that con-
trols the flow of supply air. A reheat coil can be These units have a fan that pulls air from the
installed in the discharge for spaces requiring heat- return plenum and mixes it with the supply air. A
ing. As the temperature in the space drops below the reheat coil may be placed in the discharge to the
setpoint, the damper begins to close and reduce the space or the return plenum opening. The fan pro-
flow of air to the space. When the airflow reaches the vides a minimum level of airflow to the space. Total
minimum limit, the valve on the reheat coil begins to airflow to the space is the sum of the fan output and
open. the supply air quantity. When the space temperature
Single-duct VAV systems, which supply warm drops below the setpoint, the supply air damper
air to all zones when heating is required and cool air begins to reduce the quantity of supply air entering
to all zones when cooling is required, have limited the terminal. Once the supply damper has reached its
application and are used where heating is required minimum position, the reheat coil valve starts to
only for morning warm-up. They should not be used open.
if some zones require heating at the same time that
others on the same air-handling unit require cooling. 9.6.6 Dual-Duct Constant Volume
Terminal Unit
9.6.3 Bypass Terminal Unit The hot-duct damper and cold-duct damper in
A bypass terminal unit has a damper that diverts this terminal are linked to operate in reverse direc-
part of the supply air into the return plenum. The tions. A space thermostat positions the mixing damp-
diverting damper is controlled by space temperature. ers to mix warm and cool supply air. The discharge
When the temperature in the space drops below the air volume depends on the static pressure in each
setpoint, the bypass damper begins to open, routing supply duct at that location.
some of the supply air to the plenum, which reduces
the amount of supply air entering the space. When 9.6.7 Dual-Duct Variable Volume
the bypass is fully open, the control valve for the Terminal Unit
reheat coil opens as required to maintain the space This unit has inlet dampers on the heating and
temperature. A manual balancing damper in the cooling supply ducts. These dampers are interlinked
bypass is adjusted to match the resistance in the dis- to operate in opposite directions; usually each
charge duct. In this way, the supply of air from the requires a control actuator. A sensor in the discharge
primary system remains at a constant volume. The monitors total airflow. The space thermostat controls
maximum airflow through the bypass should be the inlet mixing dampers directly, and the airflow
restricted in order to maintain a minimum airflow controller controls the volume damper. The space
into the space. thermostat resets the airflow controller from maxi-
mum to minimum flow as the sensible load on the
9.6.4 Fan-Powered Terminal Unit conditioned area changes.
This type of unit has an integral fan that supplies
a constant volume of air to the space. In addition to 9.7 ROOM AIR DISTRIBUTION
enhancing air distribution in the space, a reheat coil At the risk of oversimplification, it may be
can be added to maintain the space temperature stated that there are two different room air distribu-
when the primary system is off. When the space is tion design approaches encountered in health care
occupied, the fan runs constantly to provide a con- facilities: (1) an approach that prioritizes the control
stant volume of air. The fan can draw air from the of air movement within the space and (2) an
return plenum to compensate for a reduced supply approach that prioritizes comfort. The former, some-
air flow. As the temperature in the space decreases times characterized as plug or laminar flow, is
below the setpoint, the supply air damper begins to normally utilized in spaces where there is a high risk
close and the fan draws more air from the return ple- of patient infection, such as surgical operating rooms
num. Units serving perimeter areas of a building can and (sometimes) protective isolation rooms. The
100 HVAC DESIGN MANUAL FOR HOSPITALS AND CLINICS

intent is to limit air turbulence and achieve some formance indicator now frequently used by designers
degree of directional uniformity from clean to to relate cooling-mode occupant thermal comfort to
dirty areas. The application and relative efficacy of space temperature and air movement is the Air Dif-
plug flow systems are discussed in more detail in fusion Performance Index (ADPI). The higher the
Chapter 12, Room Design, of this manual. This ADPI number, the greater the comfort level, with an
chapter will address the conventional approach, ADPI greater than 80% generally being considered
which seeks to maximize comfort and air change acceptable. From a ventilation standpoint, a success-
effectiveness. ful system is one that effectively distributes fresh air
throughout the space; one index for rating such ven-
9.7.1 The Importance of tilation effectiveness is the Air Change Effectiveness
Adequate Air Distribution (ACE). Findings indicate that systems designed to
maximize ADPI also have high ACE performance
Thermal comfort is of special importance in
characteristics.
health care facilities. In examination, treatment, and
diagnostic areas and bedrooms, patients are often 9.7.3 Supply Outlet Performance
garbed in scanty hospital gowns or partially disrobed
for extensive periods of time. For seriously ill or Diffuser performance is normally indicated by
injured patients, the additional stress of an uncom- throwthe horizontal distance at which a diffuser
fortable environment may retard the healing process. will project an isothermal (supply air of same tem-
Criteria for minimum and maximum space tempera- perature as room air) air flow at a given end velocity,
tures have been established, but thermal comfort 50 fpm (0.25 m/s) being a typically used parameter.
being a function not only of temperature but also of Throw performance is cataloged by manufacturers
relative humidity, air movement, radiant exposure, for their various diffuser models. The effectiveness
clothing, and metabolismcan easily be compro- of a diffuser in achieving good room air movement is
mised by poorly designed HVAC systems. In addi- dependent upon its throw performance, the dimen-
tion, adequate room ventilationthe effective sions and features of the room, and the temperature
distribution of fresh air throughout the space and the difference between the supply and room air. Throw
dilution and removal of contaminantsis dependent is reduced when supply air is above room tempera-
upon a carefully designed room air distribution sys- ture (heating mode) and increased when supply air is
tem. cooler. Throw is also reduced in VAV systems when
airflow controls lower the flow volume in response
9.7.2 System Performance to lower room load.
The ASHRAE HandbookFundamentals classi-
As discussed above, the personal perception of fies air supply outlets as shown below. The Hand-
thermal comfort is influenced by several factors in book discusses the characteristics of these diffuser
addition to temperature. Discomfort can result from types in detail, and the reader is referred to this
a lack of uniform conditions or excessive fluctuation resource for further information. Group A and E dif-
of conditions within a space. Excessive or localized fusers predominate in medical facilities due to their
drafts acting on different parts of the body, or small throw characteristics and ceiling or high-sidewall
variations in the air temperature on different portions discharge locations.
of the body, can lead to feelings of discomfort. A
well-designed room air distribution system requires Group A. Outlets mounted in or near the ceiling
careful consideration of the type and location of the that discharge air horizontally
room supply air diffuser(s) in relation to the room Group B. Outlets mounted in or near the floor
geometry and (as applicable) outside exposure, the that discharge air vertically in a nonspreading jet
volumetric flow rate of air being introduced into the Group C. Outlets mounted in or near the floor
space, and the temperature difference between sup- that discharge air vertically in a spreading jet
ply air and room air. Group D. Outlets mounted in or near the floor
Room air movement is a function of the supply that discharge air horizontally
(primary) air delivered by the diffuser and movement Group E. Outlets mounted in or near the ceiling
of room air induced by this flow. When diffuser type that project primary air vertically.
and throw characteristics are well chosen, the combi-
nation of primary and induced flow results in good ADPI ranges for various diffuser configurations
distribution of air throughout the space, avoiding for the several types of commercially available sup-
uncomfortable drafts or areas of stagnation. One per- ply diffusers are available from several resources to
AIR-HANDLING AND DISTRIBUTION SYSTEMS 101

assist designers in making good cooling mode dif- to reach the floor below. This device may lead to
fuser selections (see the HVAC Computational objectionable drafts in the cooling mode.
Fluid Dynamics chapter of ASHRAE Handbook Utilization of a temperature reset control strat-
Fundamentals). At present, there is no heating mode egy that sets the supply temperature lower in the
counterpart to ADPI that diffuser manufacturers can heating mode.
use to establish comparative performance. Design- Temperature reset combined with flow adjust-
ers, therefore, often select units based upon rules of ment to ramp the supply temperature down but
thumb or experience. For example, one major dif- increase the flow volume with decreasing room
fuser manufacturer recommends that diffusers be temperature.
selected to obtain airflow velocities not exceeding 50
fpm (0.25 m/s) and a temperature gradient not Individual project circumstances, such as room
exceeding 3F (1.7C) in the zone reaching from 6 ft features (soffits that block diffuser throw), climatic
to 6 ft 1 in. (1.83 to 1.85 m). conditions, and other factors, can result in unsatis-
factory heating mode air mixing and require designer
With properly selected supply diffusers, good
consideration of supplemental (perimeter) heating
ADPI performance is commonly achieved in the
systems. Recent research by the National Institutes
cooling mode. According to one authority, good
of Health strongly suggests that good heating-mode
ADPI may be expected from a properly chosen sup- air mixing is difficult to achieve in the typical patient
ply diffuser with a flow rate range of as much as 0.2 bedroom (with outside exposure mandated by fire
cfm/ft2 to 1.0+ cfm/ft2 (1.0 to 5.1 L/s/m2)rates that code) with less than 4 room air changes per hour,
are a norm for many interior spaces (Dupont 1999). unless perimeter heating is provided (Memarzadeh
Data indicate that, in most cases, the cooler the sup- and Manning 2000).
ply air, the better the ADPI. Since the majority of
spaces in a large health care facility are in the build- 9.8 ACOUSTICAL CONSIDERATIONS
ing interior, good ADPI is fairly easy to achieve even Health care facilities require careful attention to
with variable air volume (VAV) systems. acoustical design in order to control background
Heating mode performance is more problematic noise levels and preserve privacy. High noise levels
due to the buoyancy of the relatively hotter supply can be detrimental to the healing process, as in neo-
air, which tends to retard the flow induced by the dif- natal ICU rooms where infants are especially sensi-
fuser, preventing it from influencing the lower levels tive to background noise. High noise levels also
of the room. Cold perimeter exposures are a particu- interfere with conversation and can cause distraction
lar example where this is a problem, exacerbated and increase environmental dissatisfaction. Poorly
when VAV systems reduce the room airflow in this designed return or exhaust systems or the absence of
mode. The following are recommended practices to background white noise can lead to the intelligible
address this problem. transmission of confidential doctor-patient or other
private conversations between adjoining spaces.
The temperature difference between the heating 9.8.1 Room Noise Limitations
supply air and room temperature should not
exceed 15F (8.3C) to limit the counteracting Maximum permissible background noise levels
effect of buoyancy. for most spaces in health care facilities are estab-
lished using room criteria (RC) or noise criteria (NC)
Use high-induction ceiling slot diffuser(s) curves. Poorly designed air-handling systems can
installed parallel to and within 5 feet (1.5 m) of transmit excessively high noise levels generated by
the outside exposed wall, with approximately equipment (such as fans and terminal units) into
50% of delivery projected toward the wall and occupied spaces via ductwork. High room noise lev-
diffuser throw selected to reach the floor level. els may also result from noise generated by high air
Effective ADPI may require severely restricted velocities in ductwork, duct fittings, or connections
VAV heating-mode turndown to 0.75-1.0 cfm/ft2 and within the space at diffusers or across restric-
(3.8-5.1 L/s/m2) minimum and limit envelope tions (such as door undercuts).
loads to less than 200 Btu/h per lineal foot (192
W per lineal meter). This system may result in 9.8.2 Air-Handling System Fans
excessive floor-level drafts in the cooling mode. Air-handling system fans (supply, return, and
Provision of a supplemental, vertically project- exhaust) are a frequent source of noise and require
ing slot diffuser mounted in the ceiling in prox- careful designer consideration. Fan noise breakout
imity to the outside wall, selected with a throw from the fan casing to the mechanical equipment
102 HVAC DESIGN MANUAL FOR HOSPITALS AND CLINICS

room may be transmitted into adjoining spaces acoustical calculations indicate that integral (down-
through the room envelope elements. This may stream) sound attenuators will be required in order to
require locating fan rooms away from acoustically achieve the required room NC levels, this require-
sensitive occupied spaces or careful attention to the ment should be clearly communicated to the con-
attenuation properties of the room walls, floor, and struction contractor.
ceiling. Fan noise will travel through ductwork, from
where it may enter occupied spaces by breakout 9.8.6 Proper Installation of Equipment
from the duct into the ceiling plenum and transmis-
sion through the ceiling. Fan noise will also travel Manufacturers sound performance information
directly through the ductwork, possibly requiring for various types of fittings and equipment is based
attenuation by special duct construction (additional upon specified upstream ductwork conditions or con-
elbows, for example), acoustical duct lining, or fac- nection arrangements. Diffusers, for example, may
tory-fabricated attenuators. Designers should estab- generate much more noise than indicated by catalog
lish the sound power output of fans in order to information when the connecting ductwork is insuf-
estimate the need for downstream attenuation, spec- ficiently straight or unobstructed. Designers should
ify the maximum permissible sound power output in provide appropriate installation details and instruc-
design documents, and provide appropriate acousti- tions and verify that physical conditions will permit
cal features in the design to limit transmission to the the proper installation of such equipment.
occupied spaces.
9.8.7 Location of Dampers
9.8.3 Noise Generation in Ductwork Manual balancing dampers located on individ-
Excessive noise generation in ductwork can usu- ual duct runouts should be as remotely located from
ally be avoided by limiting the flow velocities. The the associated diffuser/register as practicable to
ASHRAE HandbookHVAC Applications provides enable the downstream duct and fitting to attenuate
guidelines for velocity limits in round and rectangu- noise generated by airflow across the damper.
lar ductwork located above ceilings, in shafts, or
within occupied spaces. 9.8.8 Noise Generated by Air Transfer

9.8.4 Noise Breakout and Unacceptably high noise levels may be gener-
Low-Frequency Rumble ated within occupied spaces by in-room HVAC
equipment, such as fan coil units, diffusers (see
Noise breakout and low-frequency rumble are above), and high-velocity air transfer across grilles
a frequent problem when large ductwork is routed and door frames. Generally, the noise generated by
over an occupied space, particularly with large- fan coil units cannot economically be attenuated to
aspect-ratio rectangular ductwork. The problem can meet typical NC or RC levels for occupied spaces.
be mitigated by stiffening the ductwork with fre- Noise produced by air transfer can be mitigated by
quent bracing or reinforcement or by using more limiting jet velocity to 400 ft/min.
structurally rigid round or spiral seam ductwork. The maintenance of patient privacy is extremely
Rooftop air-handling installations are a frequent important. Doctor-patient conversations or consulta-
cause of this problem because of the proximity of tions among health care providers should not be
noise source (fan) to the rooms served. transmissible to listeners in adjoining spaces.
Improperly designed return air connections can serve
9.8.5 VAV Terminal Units
as a transmission pathway between rooms. This
VAV terminal units can generate excessive noise cross-talk situation often arises with plenum return
when improperly selected or when exposed to an air systems above clinical spaces, particularly when
upstream static pressure higher than the designer room partitions are halted at or only slightly above
anticipated. VAV unit sizes should be selected for the ceiling level and the individual room return air regis-
actual flow rate they are intended to handle, with ters are open to the common plenum. This situation
attention to their noise characteristics when exposed normally requires the return air fixture to be spe-
to upstream static pressure calculated by design. To cially configured and extended into the air plenum
help ensure proper performance, the maximum with duct attachments incorporating one or more
sound pressure levels in each of the eight octave elbows or attenuating insulation. The problem can
bands should be specified for each VAV unit for the occur, however, even with fully ducted systems.
appropriate inlet static pressure. When the designers Designers should consider the attenuating features of
AIR-HANDLING AND DISTRIBUTION SYSTEMS 103

the duct path connecting occupied rooms to adjoin- In such systems, the desiccant is impregnated
ing spaces, including corridors. (or formed in place) in a honeycomb matrix in the
shape of a wheel. Two airstreams are separated from
9.9 GENERAL CONSIDERATIONS FOR each other by air seals as shown in Figure 9.4. The
HANDLING SATURATED AIR desiccant wheel rotates slowly (6 to 20 rph) between
these two airstreams. The incoming humid airstream
Generally speaking, microbial growth in the air-
is called the process air. The second airstream is the
handling and distribution system requires the pres-
reactivation air. As the wheel rotates, the desiccant
ence of liquid water (plus a nutrition source). High
collects moisture from the incoming humid air until
relative humidity alone does not support the prolifer-
the material becomes almost saturated. To restore its
ation of microbial organisms. Potential moisture
capacity, the desiccant continues its rotation and
problems resulting from precipitation entering out-
enters the second (reactivation) airstream. The reacti-
side air intakes, condensate formation at cooling
vation air has been preheated. Hot air heats the satu-
coils, and droplet formation at humidifiers have been
rated desiccant, drying it out. Moisture released by
discussed. In addition, moisture accumulation in fil-
the desiccant is absorbed into the reactivation air.
ters, fittings, and other air supply components fre-
Desiccant units with heated reactivation air are
quently results from thermodynamic changes to
called active desiccant dehumidifiers. This distin-
saturated air, which occur in the supply system.
guishes them from the passive desiccant wheels,
It is important for designers to realize that satu- which use the buildings dry exhaust air instead of
rated or near-saturated air is a normal condition at heated air for reactivation. Passive desiccant wheels
some point within almost any air-handling and distri- remove much less moisture but also use much less
bution systemat any time of the year. For a variety energy than active desiccant dehumidifiers.
of reasons, many poorly understood by design engi- Sometimes, an active desiccant dehumidifier
neers, saturated air may suddenly be exposed to a dries only a small portion of the supply air. Active
temperature below the saturation temperature, with desiccants dry air very deeply A small amount of
condensation formation as a result. As one example very dry air removes moisture quite effectively while
scenario, consider a duct elbow, cooled to a tempera- minimizing the size and cost of the dehumidifier.
ture of 55F (12.8C) by the air-handling unit, sud-
denly exposed to a fluctuating saturated air 9.10.1 Desiccant Dehumidifier Performance
temperature of 58F (14.4C) caused by control The amount of moisture removed by a desiccant
imprecisioncondensation will likely form on the dehumidifier depends on the following factors:
fitting. Due to such concerns, many designers advo-
cate raising the cooling coil leaving air temperature depth of the wheel,
above the saturation point by some form of reheat. rotational speed, and
One frequently utilized approach is a draw-through specific sorption characteristics of the desiccant.
fan arrangement, wherein the fan heat provides the
reheat.

9.10 DESICCANT SYSTEMS

In health care applications where a large amount


of humid outside air must be used, a desiccant sys-
tem can offer an alternative to the traditional method
of dehumidifying supply air by cooling it to satura-
tion temperature. When air passes through a desic-
cant material, the desiccant removes water from the
air in the vapor state, rather than as condensed liquid.
Humid air has a high water vapor pressure. Dry des-
iccant has a low vapor pressure. Propelled by this
pressure difference, water molecules pass out of
humid air into the desiccant. Figure 9-4 Typical desiccant system.
104 HVAC DESIGN MANUAL FOR HOSPITALS AND CLINICS

These variables are usually fixed by the manu- was originally used to evaporate the water is
facturer and the designer has little control. To predict released. The amount of heat depends upon the
performance, however, the HVAC designer only amount of water removed from the air. More dehu-
needs to define the temperature, humidity ratio, and midification releases more heat.
volume of the entering process air, the size of the
unit, and the temperature of the reactivation air. The 9.10.2 Energy Wheel
following observations regarding performance are Desiccant wheels are also used for energy trans-
made. fer between two airstreams, for example, between
outside air intake and exhaust air discharge. In this
The drier the entering air, the drier the leaving application, the device is termed an energy wheel.
air. In health care facilities, care must be taken to ensure
The cooler the entering air, the drier the leaving that contamination between the two airstreams does
air. not occur (see Chapter 16 for more details).
The hotter the reactivation air, the drier the leav-
ing air. 9.11 PACKAGED UNITS
The slower the process-air velocity, the drier the Packaged rooftop cooling-only or cooling/heat-
leaving air. ing units are commonly used for clinics (see Chapter
13). For further details, refer to the ASHRAE Hand-
As water vapor is pulled out of the process air, bookHVAC Systems and Equipment (ASHRAE
the temperature of the air rises because the heat that 2000a).
CHAPTER 10
CONTROLS AND INSTRUMENTATION
10.1 INTRODUCTION 10.2 CHARACTERISTICS AND
ATTRIBUTES OF CONTROL
This chapter describes characteristics and com- METHODS
ponents of automatic control systems for heating,
ventilating, and air-conditioning (HVAC) systems 10.2.1 Pneumatic Control Systems
often found in hospitals and other health care facili- Pneumatic control systems use compressed air
ties. General control theory and applications are dis- to operate actuators, sensors, relays, and other con-
cussed in detail in the ASHRAE Handbook trol equipment. Pneumatic controls:
Fundamentals and in the ASHRAE Handbook
HVAC Applications (ASHRAE 2001a; ASHRAE Are naturally proportional
1999a). Require clean dry air
Are explosion-proof
Controls are an essential part of any HVAC sys-
tem. They provide a comfortable and therapeutic Provide for simple, powerful, low-cost and reli-
able actuators for valves and dampers
environment for patients; contribute to infection con-
Are commonly used for simple zone (VAV box,
trol for patients, staff, and visitors; optimize energy
etc.) control
cost and consumption; improve employee productiv-
Are the simplest modulating control means.
ity; control smoke in the event of a fire; and provide
cooling for hospital equipment. Controls are essen- 10.2.2 Electric Control Systems
tial for proper and efficient operation of HVAC dis-
tribution systems and also for proper and efficient Electric controls consist of valve/damper actua-
tors, temperature/pressure/humidity controllers,
operation of central plant equipment.
relays, motor starters, and contactors. They are pow-
Automatic controls are used to maintain a set- ered by low or line voltage, depending upon the cir-
point for a variable when disturbances cause a cuit requirements. Controllers and actuators can be
change in that variable. In HVAC systems, the most wired to perform either two-position (such as on/off
commonly controlled variables are pressure, temper- or limit) or proportional, derivative, or analog control
ature, humidity, and fluid flow rate. using either spring return, or nonspring return. Elec-
tric controls:
One of the most significant changes in the 2001
edition of the Guidelines for the Design and Con- Are most commonly used for simple on-off con-
struction of Hospitals and Health Care Facilities trol
(AIA 2001) is the requirement for a minimum differ- Use integral sensor/controller
ential static pressure of 0.01 in. w.g. (2.5 Pa) in pro- Offer a simple sequence of control
tective isolation rooms, airborne infection isolation Can function within broad environmental limits
rooms, surgical cystoscopic rooms, bronchoscopy Can involve complex modulating actuators,
rooms, and autopsy rooms. especially when spring return

105
106 HVAC DESIGN MANUAL FOR HOSPITALS AND CLINICS

10.2.3 Electronic Control Systems providing historical records; supporting maintenance


In an electronic control system, an analog sensor management programs; fire alarm; security and
signal is amplified, then compared to a setpoint or access control; lighting control; and start-up of the
override signal (through a voltage or current compar- emergency generator system and transfer of power
ison via control circuits) to actuate operations. Elec- from standby to emergency.
tronic controls: A BMS provides an opportunity to track the
operation of various control points, such as discharge
Provide precise control air temperature, mixed air temperature, and valve or
Offer solid-state repeatability and reliability damper position. Such tracking can be done in real
Permit sensor locations 2 to 300 feet (1 to 91 time. The information obtained can be very valuable
meters) from a controller in troubleshooting, problem solving, system docu-
Allow simple remote setpoint adjustment mentation, and for efficient operation. Critical
Have a high per-loop cost parameters can be easily monitored and can be
alarmed if out of a specified range.
Offer packaged complete actuators and control-
lers Using a centralized system with network com-
munications and user-defined boundaries for com-
10.2.4 Microprocessor or Direct Digital Con- fort, it is possible to define setpoints globally and
trol (DDC) thereby optimize comfort and energy strategies.
Equipment can then be operated at a minimum cost,
In a microprocessor-based system, sensor input and temperatures are controlled for maximum effi-
is converted to digital form, where discrete instruc- ciency. Loads can be leveled and demand controlled
tions (algorithms) perform the comparison and con- by starting and loading the central plant based upon
trol process. Microprocessor-based controllers can the demands of the air-handling systems.
be used as stand-alone controllers or they can be Sometimes networks use the Internet or an intra-
used as controllers incorporated into a building man- net for communication. One major disadvantage of
agement system (BMS) utilizing a personal com- an Internet network is that the interconnection
puter as a host to provide additional monitoring and between systems may not be dedicated to the con-
control functions. Microprocessor-based controls: trols, may not be supervised, and could fail without
notifying the central monitor or alarm system. Inter-
Provide precise control
net hardware and software are evolving toward
Permit inherent energy management functions
robust control applications, however, that are more
Deliver inherent high order (proportional plus
reliable and lower in cost than some conventional,
integral) control
dedicated control networks. The Internet also pro-
Are compatible with building management sys- vides a means of establishing a common communi-
tems (BMS) cations protocol between different control systems. It
Can easily perform a complex sequence of con- is imperative that security be the first priority of any
trol Internet-based control system.
Support global (interloop) control via a commu-
nications bus (e.g., can optimize chillers based 10.3 PRESSURIZATION, OUTSIDE AIR
on demand of connected systems) VENTILATION, AND OUTSIDE AIR
Allow simple remote setpoint adjustment and ECONOMIZER CONTROLS
display
Can use pneumatic actuators 10.3.1 Pressurization Criteria
Two pressurization criteria are commonly used
10.2.5 Computerized Building Management
in health care facility design: volumetric flow rate
System
(VFR) or room differential pressure (RDP)
The objective of a building management system
(BMS) is to centralize and simplify the monitoring, VFR criteria: Pressurization required for a spe-
operation, and management of a building or build- cific hospital room is usually accomplished
ings. BMS functions in health care facilities typically (under most codes) by providing differentials in
include monitoring environmental conditions, sys- the volumetric flow rates of supply, return, and
tems, and plants; centralized alarm reporting; reduc- exhaust air. Under these VFR design criteria,
ing energy usage and cost through centralized only the volumetric flow rate of supply, return,
control of energy-consuming systems; data trending; and exhaust air is considered. A room is consid-
CONTROLS AND INSTRUMENTATION 107

ered positively pressurized if it has an excess of where


supply air volumetric flow rate into the room SAZ = supply air to the room,
compared to the sum of return and exhaust air REAZ = return/exhaust cfm through the return
volumetric flow rate out of the room. Negatively air duct to the return fan before it enters
pressurized rooms have less supply air than the an outside air economizer,
sum of return and exhaust air. Most hospital
EA2Z = constant volume exhaust air cfm
rooms can be designed using only VFR criteria
through a constant volume exhaust fan,
for pressurization. See Sections 10.3.2 and
and
10.3.3 for VFR criteria.
PRESSZ = room pressurization (cfm) where
RDP criteria: One of the notable changes in PRESSZ is positive when the air flows
the 2001 edition of the Guidelines for the Design out of the room or zone toward the
and Construction of Hospitals and Health Care reference space.
Facilities (AIA 2001) is the requirement for min-
The solution of this equation for constant pres-
imum room differential pressure of 0.01 in. w.g.
surization requires that (SAZ REAZ) be constant at
(2.5 Pa) for protective isolation rooms, airborne
all SAZ and RAZ flow rates. This means that REAZ
infection isolation rooms, surgical cystoscopic
must track SAZ by a constant offset(EA2Z +
rooms, bronchoscopy rooms, and autopsy rooms.
PRESSZ).
Furthermore, where there is a requirement for
positive or negative room differential pressure, 10.3.3 VFR Pressurization Criteria for a Sys-
the pressure is to remain positive or negative at tem
all times. When room differential pressure (RDP)
criteria are the design basis, it may be necessary For a system, SAS (RAS + EA1S) = EA2S +
to consider the effects of secondary factors, such PRESSS. The quantity (RAS + EA1S) is often simply
as stack effect, wind pressure, differential room called return air (or REA) because it all passes
pressure, the differential partial pressure of water, though the return fan, even though the quantity EA1S
and (especially) leakage through walls, ceilings, is the cfm exhausted in the economizer and the quan-
and floors. See Section 10.4 for RDP criteria. tity RAS is the portion that actually mixes with out-
side intake air before it passes through the coils and
supply fan. Note that if the return air cfm is mea-
10.3.2 VFR Pressurization Criteria for a Zone
sured upstream of the economizer section, then the
system is greatly simplified. The solution of this
If a room or system has constant air flow, then
equation for constant pressurization for an entire sys-
the volumetric flow rates required for room
tem requires that (SAS (RAS + EA1S)) be constant
pressurization are established and fixed when
at all variable SAS and REAS flow rates. This can be
the system is initially tested and balanced. A
accomplished on a system basis if the return fan
minimum measurable amount of air flow differ-
tracks the supply fan minus a constant offset quan-
ence is recommended. This is the most reliable
tity, (EA2S + PRESSS).
method of room pressure control.
If variable air volume is used in areas where 10.3.4 Outside Air Economizer Controls
codes require pressure relationships between An air-side economizer has three main functions
rooms, then the (supply cfm return/exhaust under normal operating conditions: free cooling,
cfm) relationship must be maintained at all VAV minimum outdoor air ventilation, and building pres-
settings. This is normally done by having the surization. Outside and exhaust air economizer
return/exhaust cfm track the supply cfm minus dampers are closed when the system is off. The
the pressure differential cfm for both the room economizer may also have an emergency smoke
and the system (Lewis 1998). (Note: Unless oth- purge mode. Three types of economizer arrange-
erwise indicated, the term cfm is used in this ments include: supply and return fan (the most com-
chapter as a shorthand for volumetric flow rate mon system), supply and relief fan, and supply fan
and does not imply a specific measurement.) with gravity relief.
For a room or zone (z) that has variable supply Proper selection of fan/economizer components
and return air and constant exhaust flow and and controls provides optimum performance with
maintains a constant pressure relationship (cfm respect to free cooling, outside air ventilation, and
differential) to an adjacent room or corridor, building pressurizationoften all simultaneously.
then SAZ REAZ = (EA2Z + PRESSZ), The selection of fan/economizer components is criti-
108 HVAC DESIGN MANUAL FOR HOSPITALS AND CLINICS

cal to maintaining the desired linear and stable per- environmental or process conditions, following
formance of fan/economizer systems. This includes which the control system cannot return them to the
proper selection of setpoints in a reasonable period of time. This can be
a design problem, or a maintenance problem, or
dampers by size and type (parallel or opposed- both. Symptoms of economizer, fan, or terminal unit
bladeopposed blade dampers provide better malfunction include whistling doors that indicate
volume control and mixing); improper room or system pressurization; hunting of
fans by size and type; fans, dampers, or mixed air temperatures; or exces-
controls: sive fan energy working against dampers. Normal
pressure, including building pressure, mix- disturbances include changes in outdoor air tempera-
ing plenum pressure, and outside of build- ture, cooling or heating load, wind pressure, stack
ing pressure; effect, opening doors, and interzonal air flows.
dampers for pressure and VFR tracking; For design of economizer systems, see ASHRAE
fan speed controls. Guideline 16, Selecting Outdoor, Return, and Relief
Although some interaction is inevitable in the Dampers for Air-Side Economizer Systems
control loops for each of the three basic economizer (ASHRAE 2003). This guideline, however, does not
control functions, this interaction should result in address tracking controls, which may be required by
minimum distortion of the three basic control func- code and should be included in some health care
tions. The undesirable effects of control interaction applications.
can be minimized, and overall economizer control
performance can be improved, by optimum design, 10.3.5 Constant or Variable Volume Box
selection, installation, and tuning. The best way to Constant and/or variable volume boxes are often
ensure proper operation is to provide separate supply used in air distribution systems for hospitals to
and return fans. Air volume measurement stations reduce duct distribution sizes through the use of a
may be needed for better control. medium-pressure duct system and to accurately con-
trol room air flow. These boxes can be controlled
economizer geometry (location of dampers and pneumatically, electrically, or by DDC and are nor-
size of mixing box or duct, etc.). mally pressure independent (i.e., provide the same
air volume regardless of duct pressure). A more
An example of optimum economizer perfor- detailed description of duct distribution systems is
mance in the free cooling mode is when exhaust and provided in Chapter 9.
outside air dampers modulate in an inversely propor-
tional and linear manner in the free cooling mode, so 10.3.6 Minimum Outside Air Ventilation
that when more outside air is used, the same amount with Constant or Variable Air Volume
of return/exhaust air is exhausted. An example of Terminals and an Economizer
optimum economizer performance in building pres-
surization mode is when the supply fan, tracking fan If variable volume boxes are used, the controls
speeds, relief dampers, relief fan, or tracking damp- must be adjusted to maintain minimum outside air
ers modulate to maintain stable building pressuriza- ventilation. This is determined from the ratio of out-
tion with minimum fan energy consumption. An side air to supply air in the outside air economizer
example of optimum economizer performance with and the minimum supply air quantity (ASHRAE
respect to outside air ventilation is when the same 2003). At minimum room or zone supply-air quan-
amount of outside air ventilation is provided no mat- tity and simultaneous minimum system supply-air
ter what building pressurization is required and no quantity, the room or zone outside air ventilation in
matter how much or little free cooling is being pro- air changes per hour is:
vided. OAACZ,min = SAACZ,min %OAS,min 60/volume,
Economizer malfunction can be interrelated
with fan or terminal unit malfunction (or controls for where
any of these systems) and can also result from dirty z = zone or room,
sensors or loss of calibration or adjustment. In such
min = minimum,
cases, one or more of the primary control functions
(building pressurization, outside air ventilation, and/ s = system,
or free cooling) and associated systems and controls OAAC = outside-air (OA) changes per hour in the
may have been disturbed by normal variations in zone,
CONTROLS AND INSTRUMENTATION 109

SAAC = supply-air changes per hour in the zone, Early warning to facility staff if space pressur-
%OA = percentage of outside air through the ization cannot be maintained.
supply fan that is introduced in the Audible and visual alarms available locally and/
outdoor air economizer, and or remotely when the room is out of user-
defined limits.
volume = volume of the zone or room. Alarms supplied with user-defined adjustable
Constant (worst case) values for minimum time delays to eliminate false alarms caused by
SAAC and %OA at the economizer can be fixed to momentary changes in conditions (such as a
ensure minimum outdoor air ventilation to each brief door opening).
room under all conditions. Alternatively, a computer- Electronic data collection to meet Centers for
ized building management system can monitor and Disease Control guidelineswhere applicable.
adjust minimum SAAC in each zone and %OA at the Elimination of the requirement for daily smoke
system economizer to ensure minimum outdoor air testing if the room is occupied by a TB patient.
ventilation to each room under all conditions. Obvi-
ously this control approach is better executed with 10.4.2 Specialized Sensors and Controllers
DDC controls. Specialized sensors and controllers are some-
times used for isolation room pressurization control
10.3.7 Dual-Duct Terminals or Variable Air in hospitals. The majority of codes require constant
Volume Induction Units volume air flow with fixed volumetric differential for
A similar approach can be used for dual-duct most situations in hospitals. Some codes now also
terminals or variable air volume induction units, con- require a minimum space pressure differential of
sidering the code requirements for each of these dif- 0.01 in. w.g. (2.5 Pa) in special rooms such as Pro-
ferent types of terminals. For example, for reheat tective Environment Isolation Rooms (PE) and Air-
induction units, some codes require that only supply borne Infectious Isolation Rooms (AII). Two control
air from the central system can pass through the strategy options are generally acceptable under hos-
induction unit reheat coil. pital codes (with some exceptions): (1) constant vol-
ume with fixed volumetric differential between
10.4 ISOLATION ROOMS AND SIMILAR supply and return/exhaust or (2) volumetric control
ROOMS WITH RDP CRITERIA (tracking) with direct pressure reset.

Constant Volume with Fixed Volumetric Differ-


10.4.1 Isolation Room Static Pressure (RDP)
ential In Isolation Rooms: This involves a con-
Criteria
stant volume of supply and return/exhaust air
A room-pressure sensor measures the differen- established when the system is initially tested
tial pressure between the room and the adjacent ref- and balanced. Protective Isolation Rooms can
erence area or room (usually a corridor or anteroom). return air to the central system. Infectious Isola-
The key to establishing and maintaining pressuriza- tion Rooms usually require 100% exhaust air
tion is eliminating leaks in the walls, ceiling, and with negative room pressurization. A fixed dif-
floor and keeping doors closed except during access. ferential (supply cfm return/exhaust cfm) is
The sensor and transmitter (or indicator) provide a maintained in the isolation room. The room may
digital readout or visual indication (such as a flutter have a constant volume supply air box with a
strip or ball-in-tube) of room pressure. A remote reheat coil. Room differential pressure may vary
alarm panel, typically located at the nurses station, somewhat, depending on the outside air condi-
can be installed and may be connected to the build- tions or the pressurization in adjacent spaces,
ing management system for immediate response by but a minimum room pressurization can be
maintenance and system operating personnel. All maintained throughout all conditions if the ini-
such systems should incorporate appropriate time tial pressurization is high enough. Variations of
delays for transient inputs. Some codes do not allow 0.03 in. w.g. (7.5 Pa) in room pressurization in a
substituting a BMS for local hardwired alarms. hospital in Minnesota have been reported
These are the advantages of a monitored system: which coincides with seasonal variations (Ste-
ifel 2000). This may be caused primarily by
Continuous space monitoring for safety of the stack effect; wind pressure and water partial
health care worker and protection for patient and pressure differential could also be factors. A
adjacent spaces. room differential pressure monitoring device or
110 HVAC DESIGN MANUAL FOR HOSPITALS AND CLINICS

visual indicator is provided to indicate the pres- requirements for the entire facility should not be dic-
sure differential between the room and the adja- tated solely by operating room cooling requirements.
cent reference area or room. One way to achieve this lower space temperature is
Volumetric Control with Direct Pressure (Cas- to install two series cooling coils. One coil is con-
cade) Reset in Isolation Rooms: Direct pressure nected to the normal building chilled water system
controls recognize and compensate for distur- and provides discharge air temperatures in the tradi-
bances such as stack effects, infiltration, and tional range. The other coil is connected to a lower-
exfiltration, but they do not, in themselves, pro- temperature cooling medium; this could be a DX
vide volumetric flow rate stability because the system or another cooling coil served from a special
system is dynamically adjusting to momentary low-temperature chiller. Another method is to pre-
variations in room pressure conditions caused cool or preheat outside makeup air using a heat
by the opening of doors and the like. These con- recovery system on the exhaust air (see Chapter 16).
ditions can draw air from or force air into adja- Still another method is a dessicant cooling system
cent rooms and cause pressure upsets in adjacent for the makeup outside air.
rooms or areas. Constant volume with a fixed
volumetric differential (as described in the pre- 10.5.2 Variable Air Volume and Room Static
vious paragraph) does not compensate for dis- Pressure Controls in Operating
turbances such as stack effect, infiltration, or Rooms and Critical Areas
exfiltration. Volumetric control with room dif- Some codes require that operating rooms have
ferential pressure reset can provide two control constant volume systems. Other codes allow two-
functions. It can reset the room point and pro- position or variable air volume control in operating
vide volume flow differential (supply-return/ rooms and some other critical areas for energy con-
exhaust cfm) within a range to maintain room servation. The latter can reduce air flow below maxi-
pressurization. mum rates as long as room air change rates are met.
Some codes allow further reduction of airflow when
10.4.3 Anteroom Monitoring the operating room or critical area is unoccupied, as
Isolation rooms with anterooms are provided long as a means is provided to automatically increase
with one monitor to measure and alarm the pressure air flow as soon as the room becomes occupied by
differential between the isolation room and the ante- interlocking controls with the light switch, etc. How-
room and another monitor to measure and alarm the ever, all codes require that directional control (pres-
differential pressure between the anteroom and the surization) be maintained constantly (whether
corridor. In Protective Environment Isolation Rooms occupied or not) where it is required to prevent the
with anterooms, a fixed constant volume offset is spread of infection from one area to another. As
usually maintained in the anteroom. This offset described previously, if a variable air volume system
makes the anteroom negative with respect to the Pro- is used, continuous room pressure monitoring and
tective Environment Isolation Room and slightly volumetric control with direct pressure reset is rec-
positive with respect to the corridor. An Infectious ommended because of the performance degradation
Isolation Room anteroom is positively pressurized of RA sensors from lint and other possible variations
in room pressurization performance. This should be
with respect to the isolation room and slightly nega-
considered for any critical room and for the entire
tive with respect to the corridor.
department or ward when a VAV system is being
10.5 OPERATING ROOM CONTROLS used.
The Guidelines for the Design and Construction
10.5.1 Temperature Controls of Hospitals and Health Care Facilities (AIA
2001) requires a minimum room static pressure
Operating rooms generally require wide ranges
of 0.01 in. w.g. (2.5 Pa) in Cystoscopic Operating
for temperature and humidity and lower than normal
Rooms.
room temperatures. Most codes require room tem-
perature adjustment throughout the entire range
10.5.3 Humidity Control in Operating
under all conditions. (e.g., 6873F [20.022.8C] in
Rooms
general operating rooms) (AIA 2001). However, it is
common in some operating rooms (such as cardiac Dehumidification requirements for operating
surgery or organ transplant rooms) for the medical rooms are often extreme and require low chilled
staff to prefer a room temperature of 60F (15.6C). water temperatures or a desiccant cooling system for
To conserve energy, the chilled water temperature makeup outside air.
CONTROLS AND INSTRUMENTATION 111

A room humidifier for each operating room may operational situations. For illustrative purposes, sev-
be required by code. The humidifier must have an eral additional examples of control sequences, along
adjustable room relative humidity setpoint, which with control diagrams used in hospitals and health
can be changed by the operating room team. Water care facilities, are described in Appendix H. It is not
treatment should be evaluated to determine if the intended to suggest that these are the only acceptable
humidifier steam is safe and sufficiently odorless control sequence options but rather to illustrate typi-
(see Chapter 8). cal applications.

10.6 LABORATORY CONTROLS 10.7.1 Supply Fan Control by Duct Static


Many hospitals and clinics have numerous types Pressure: Supply Fan Inlet Vane or
of laboratories. The most common are clinical, Motor Speed (Variable Frequency
pathological, research, and pharmaceutical laborato- Drive, VFD) Control
ries. Codes in some jurisdictions require constant The supply fan inlet vanes can be modulated or
volume controls in hospital laboratories. If a variable the VFD can control the motor speed to provide sup-
air volume system is used, it must maintain pressure ply air system static pressure control. During the
relationships between the laboratory and other hospi- start-up mode, the supply fan should slowly ramp up
tal departments. VAV control requirements are to speed to maintain the setpoint of the static pres-
affected by large swings in airflow needs for hoods sure controller (usually installed on the supply air
in the laboratory. Temperature control is affected by duct, often two-thirds to ninety percent of the dis-
major changes in airflow to the room. Humidity con- tance from the fan to the end of the longest duct). For
trol is difficult because the humidifiers must be sized dual-duct VAV systems, the supply fan pressure may
to handle swings in airflow. Flow tracking is one be controlled to the duct static pressure of the lower
method of maintaining a proper pressure in a labora- of either the cold or hot duct in single-fan systems, or
tory if supply and exhaust air volumes vary. An off- individually in dual-fan systems.
set between supply and exhaust air volume is another
approach. The return air fan can be controlled by other
strategies, such as cfm matching or offset control. A
10.6.1 Laboratory Hoods control strategy using the position of terminal vol-
ume controllers (automatic dampers) can also be
Laboratory hoods have a variety of different considered, but it is complex.
configurations. Most hoods require a minimum face
velocity to capture and confine vapors and the air 10.7.2 Fan Tracking
within. If the hood door opening size is variable, the
flow through the hood must be varied to maintain the Return and exhaust fan inlet vane or VFD track-
minimum velocity through the hood. Variable air ing control can be described as follows. Airflow sta-
volume hoods must have a local alarm at the hood to tions in the supply, return, and exhaust ducts can
warn if the face velocity drops below the minimum. provide control signals. The signal can input the vol-
umetric flow rate (cfm) to the control system. The
10.6.2 Biosafety (Microbiological and Bio- return and exhaust fans should modulate in tandem
medical) Laboratories to maintain the predetermined return air and exhaust
The CDC and NIH biosafety rules categorize air cfm volumes or cfm differentials compared to the
laboratories according to the level of risk (BSL levels supply air flow rate. Volumetric air flow rate tracking
1, 2, 3, and 4). Each BSL requires a specific combi- assists in maintaining the entire department or facil-
nation of laboratory practices and techniques, safety ity at the correct pressure relationship with respect to
equipment, and laboratory facilities. For further other connected areas (or to the outside).
information see the ASHRAE HandbookHVAC
Applications (ASHRAE 1999a) and CDC/NIH Bio- 10.7.3 Humidification
safety in Microbiological and Biomedical Laborato- The humidifier should be modulated to maintain
ries (CDC 1999). room or exhaust air humidity. As the exhaust or
room air humidity increases, the humidifier should
10.7 GENERAL CONTROL SEQUENCES modulate closed. The reverse should occur as the
USED IN HOSPITALS AND CLINICS exhaust or room air humidity decreases. A high-limit
The following control sequences can be used as humidistat should limit the signal to the humidifier if
a design guide for typically encountered health care the supply air humidity exceeds 85% (hardware
112 HVAC DESIGN MANUAL FOR HOSPITALS AND CLINICS

adjustable). Upon loss of airflow, a static pressure 10.7.7 Dual Radiator or Panel Heating and
switch should disable the system. Reheat
When a room thermostat controls both a reheat
10.7.4 Supply Air Temperature Control coil and a wall-mounted radiator, the sequencing of
Preheat, Economizer, and Cooling the operation of the devices is very important. The
Sequence most desirable condition would be that the wall-
mounted radiator or heating panel control is fully
A supply temperature control system should
operational before the duct-mounted reheat is acti-
modulate the economizer dampers, preheating
vated. Use of this control sequence may ensure that
valves, and chilled water valves in sequence. Assum-
an outside wall/window assembly will not create
ing that the economizer is at the minimum outside air
unpleasant drafts.
position and that the mixed air temperature is colder
than the desired supply air temperature, the preheat 10.7.8 Thermostat and Sensor Location
coil must provide some heating. As the mixed air
A thermostat or temperature sensor must be
temperature rises, the preheat valve modulates
installed at a location that samples an average condi-
closed. As the mixed air temperature continues to
tion of the zone. A thermostat should not be located
rise, the economizer dampers modulate toward fully
where the supply air, a cold or hot outside wall, solar
open to the outside airif the outside air enthalpy is radiation, or heat-producing equipment would affect
less than the return air enthalpy. Then, the econo- it.
mizer modulates as required to maintain the dis- Fouling of return-air flow sensors and airflow
charge air temperature. If the mixed air temperature measuring stations with lint and dirt is a significant
is higher than the required supply air temperature, problem, particularly in areas where beds are made
the chilled water valves modulate open. If the out- (such as in patient rooms). One solution to this prob-
side air enthalpy is greater than the return air lem is a special purging sensor that blows com-
enthalpy, then the economizer should return to the pressed air out of the sensor from time to time. These
minimum outside air position. The supply air cold or devices are complex and require maintenance. A pre-
hot deck temperature can sometimes be linearly reset ventive maintenance program can keep return sen-
based upon the outside air temperature if the outside sors in good working order with semiannual checks
air temperature is creating the primary load on the of the sensors.
zones in the system; however, this is not typically
done in a variable volume system. 10.8 CONTROL SAFETIES
Safeties that protect HVAC systems are partic-
10.7.5 Fan and Damper ularly important in hospitals and clinics because of
Smoke Alarm Shutdown the need for continuous operation with minimum
downtime and maximum reliability. Most safety con-
Upon detecting smoke at the supply or return trols for air-handling units and smoke detectors are
duct smoke detector, the supply and return air smoke hardwired and independent of the BMS system.
dampers should close through hardwired interlocks. These devices should shut down equipment through
The outside-air and return-air dampers should close hardwired interlocks and provide alarm status to the
and the supply, return, and exhaust fans should stop operator through the BMS front end. Safeties can
through hardwired interlocks. All control functions also be installed through software, but a hardwired
of the air-handling unit should return to normal con- interlock is more reliable because it eliminates any
dition after the smoke detector is manually reset. In error from the BMS, the software, or the operator.
some cases, an engineered smoke control system is Confirm that in hand/auto/off switch wiring, safeties
used as described below. are not overridden in any switch position.

10.8.1 Cooling Coil Freeze Protection


10.7.6 Smoke Exhaust System Controls
If the outside air temperature can be lower than
As an alternative to smoke detector shutdown, about 35F (2C), a preheat coil should be located
the system controls can go into smoke exhaust mode upstream of the cooling coil to protect the cooling
to exhaust smoke and provide positive pressurization coil from freezing. A freezestat with a sensor just
with 100% outside air to areas of egress. See Chapter upstream of the cooling coil may have a low-limit
11 of this manual for further information. safety and sense air temperature entering or leaving
CONTROLS AND INSTRUMENTATION 113

the cooling coil (set at 35F [2C]adjustable), differential pressure of less than a preset value
which should stop the supply, return and exhaust (typically 1 in. w.g. [249 Pa]) has been achieved
fans, close outside air dampers, and open chilled before closing any damper; or
water valve at temperatures below the setpoint. Note A relief damper may be placed in the side of the
that chilled water must be pumped through the coil at ductwork to relieve excessive pressure.
a significant rate of flow under such circumstances to Upon a signal to start the air-handling unit, the
reduce the possibility of freezing. In extremely cold supply and exhaust isolation dampers (as well as
conditions, this may not prevent freezing, and auto- the outside air damper and smoke dampers)
matic valves should drain the coil. Before starting should open before the fans start. Isolation
fans, activate the preheat control valve or provide a damper end-switches can prove that dampers are
time delay on the freezestat so that the fan is not open and allow the fan(s) to start through hard-
tripped off during start-up. The freezestat should be wired interlocks.
manually resettable, except in critical cases where A manual reset discharge-air high-static safety
airflow may not be interrupted. located before the supply air isolation/smoke
damper should disable both supply fans and
10.8.2 Duct Static Pressure Safeties
input to the DDC system upon sensing an
When motorized smoke, isolation, or control (adjustable) static pressure above the normal
dampers are used in a supply air system, the return- operating setpoint.
air or exhaust-air ductwork design must ensure that a A manual reset return and exhaust air low duct-
closure in the supply system does not blow apart the static pressure safety located before each return
supply ducts or collapse the return-air ducts. Duct- and exhaust fan should stop the other fans in the
work can be damaged if a variable frequency drive, system and input to the DDC system upon sens-
inlet vanes, or their controls are set improperly. The ing a static pressure below the normal operating
following steps can prevent this situation. Any delay setpoint.
in smoke damper closing, however, should be
Fire alarm shutdown: On activation of the build-
approved by the Authority Having Jurisdiction.
ing fire alarm system relay, the system should
A time delay after fan(s) shutdown: On a com- shut down or operate in the smoke exhaust
mand to shut down a fan, hard-wired time delay mode. The fire alarm should be annunciated at
relays should prevent dampers from closing for the BMS console.
30 seconds (adjustable) after the fan(s) shut off.
10.9 DX SYSTEM CONTROLS
This should prevent a buildup of pressure until
the fans spin down and prevent the fan high/low DX systems pose a challenge to the designer.
static limit from tripping; or Careful attention must be given to ensure that capac-
Upon shutdown, ensure that a differential pres- ity control is provided under changing ambient con-
sure (DP) sensor across the fan indicates that a ditions.
CHAPTER 11
SMOKE CONTROL AND LIFE SAFETY
11.1 INTRODUCTION fire zone and controls its spread by pressurizing
adjacent zones.
11.1.1 The Life Safety Approach
The third stage of this strategy, which is rarely
Hospitals present an unusual environment for required, involves using elevators or stairs to evacu-
life safety and fire protection. Most occupancies rely ate patients from the building. If the fire protection
on evacuating occupants as part of their fire protec- systems work as designed, this evacuation stage
tion and life safety approach, but a hospital must rely should never be necessary.
on the building and building systems to protect its
occupants while they remain in place. This is called a Under this compartmentation concept, the
defend-in-place strategy. Hospitals, therefore, are HVAC system plays a major role in the life safety of
well compartmented and fully sprinklered in new patients. Transport of smoke via the HVAC system
construction and provide many additional life safety within the compartment or between compartments
features that may not be found in other buildings. can overcome the defend-in-place approach.
Whether smoke control is active or passive, the basic
The defend-in-place strategy actually has three
premise is that preventing smoke spread is vital. The
stages. Ideally, a fire can be extinguished and smoke
HVAC system must, therefore, be designed in coor-
controlled in the room where the fire originated.
dination with the architectural life safety layout of
Only those occupants in the immediate fire area
the building and with the fire alarm and sprinkler
would have to be evacuated from their rooms. When
zoning. The life safety features of the building
a fire occurs in a smoke compartment, the nursing
require a coordinated effort among the entire design
staff will close the doors to all patient rooms, and
team. It is important to realize that building safety
patients can remain in relatively clean environments,
components can be rendered ineffective by improper
even though there is a fire in the same general area.
HVAC system operation during a fire. An example is
Corridor walls are built smoke-tight, if not of rated
excessive pressurization, which can prevent smoke
construction, to protect patients in their rooms during
doors from fully closing or make it difficult to open
this first stage.
doors into stair towers. Maintaining proper clear-
If evacuation of patient rooms becomes neces-
ances on meeting edges of doors and undercuts can
sary, the second stage is to relocate occupants of the
minimize air and smoke leakage from a compart-
smoke compartment where the fire originated into
ment and have a significant impact on the effective-
another compartment on the same floor. Smoke com-
ness of smoke containment.
partments are a key facet of fire protection in the
building codes and in the NFPA 101 Life Safety A smoke control system may be active or pas-
Code. They allow relocating patients horizontally sive. In hospitals, passive smoke barriers are required
and provide a safe holding area on the floor where a on almost all floors. Active smoke control may be
fire originates so that patients can be wheeled or oth- required in atria and in high-rise (or other large)
erwise relocated without using stairs or elevators. facilities, depending upon the authority having juris-
Some hospitals use an engineered smoke evacuation diction. The owner may also conclude that active
system that automatically exhausts smoke from the smoke control is desirable in the facility.

115
116 HVAC DESIGN MANUAL FOR HOSPITALS AND CLINICS

When active smoke control is implemented, the Last, the HVAC systems and other building sys-
conditions under which the system will operate in an tems can convey smoke to further portions of the
emergency must be carefully considered. Clearly building. Elevators moving up and down past a fire
labeled controls with positive feedback, as well as floor can pull smoke into the shaft and push it out
fail-safe designs should be included. The design onto other floors. The HVAC system, if not shut
should allow dampers to fail in a smoke-safe position down, can convey smoke into other areas of a build-
if control air or power to a damper is lost. This strat- ing. If the HVAC system is shut down without clos-
egy needs to be reviewed with the infection control ing dampers, the ductwork creates an open
department so that the control of airborne infections passageway. This creates an opportunity for smoke
is not compromised. The defend-in-place strategy in spread that must be considered.
a hospital must provide ample time for a prolonged
evacuation; thus, it is likely that pneumatic tubing or 11.1.3 Key Design Concepts
electrical wiring serving some devices will be com-
Developing agreement on the expected smoke
promised during a fire emergency.
control design and performance testing procedures is
11.1.2 Means of Smoke Spread of primary importance when addressing smoke con-
trol and HVAC design. This agreement should
In designing a smoke control system for a build- include the entire design teamthe owner, infection
ing, the design team must consider how smoke may control professionals, the authority having jurisdic-
spread through the building. Avenues of smoke tion, and the insurerso that there is confidence that
spread are well defined in other references, so this the design path chosen will be acceptable to all of the
chapter merely introduces the concept and relies stakeholders.
upon those other documents to provide details.
If an active smoke control system is chosen, it is
The stack effect is a primary means of smoke
important that the design documents clearly identify
spread. The stack effect is caused by the pressure
the performance of the system. These documents
gradients that result from differences between out-
must clearly express the expected performance of
side and inside air temperatures. A normal stack
each device in the system. In this case, the system
effect occurs when the interior of the building is
is not only the mechanical system but all items that
warmer than the outside air. A reverse stack effect
interface with the mechanical system. The drawings
occurs when the interior of the building is colder
should include the locations of all devices that will
than the outside air. A normal stack effect would
initiate smoke control; the locations of all devices
result in a pressure that is higher at higher elevations
within the building than at lower elevations. The involved in the smoke control process (including
stack effect is also sometimes referred to as the control dampers, fire and smoke dampers, variable
chimney effect. air volume controls, and fans); the identification of
Another means of smoke spread is buoyancy. devices provided with emergency power; the loca-
Smoke from a fire is hotter and more buoyant than tions of active and passive smoke barriers; the smoke
the ambient air around it. This physical fact must be control method being used; the capacities of fans
dealt with in attempting to limit smoke migration. involved in smoke control; the sequence of opera-
A third potential means of smoke spread is tions; and the positioning of each damper for every
weather conditions. Wind can have an impact on the fire scenario. Many of these items are described fur-
spread of smoke within a building. Wind effects can ther in this chapter, but it is important to recognize
occur as a result of operable windows, but wind has a that they all must work together to form a viable
significant impact even in closed buildings. Leakage smoke control system. It is equally important to rec-
through exterior walls and operation of exterior ognize that the smoke control system is only one part
doors can significantly alter the expected movement of the life safety system and that without coordina-
of smoke within an enclosed building. tion with these other subsystems, the life safety sys-
As air is heated, it expands. Therefore, expan- tem will not operate as anticipated.
sion also has an impact on smoke spread within a HVAC system controls and fire alarm systems
building. Pressure differences from a fire in a sprin- that are used in any way as a part of an active smoke
klered building are generally in the range of 0.02 to control system should be listed for the purpose. Such
0.03 inches of water (5 to 7.5 Pa) higher than normal listing is a common requirement of many state and
ambient pressures due to the expansion caused by regional building and fire prevention codes. Under-
heat. This tends to push the smoke away from the writers Laboratory (UL) tests equipment and pro-
fire and into other areas of the building. vides a listing under UL864 Category UUKL for
SMOKE CONTROL AND LIFE SAFETY 117

smoke control system equipment. It is important to meters), and codes limit the travel distance to a
install this equipment in strict compliance with any required smoke barrier from any point within a room
special provisions required in the UL listing that are to 200 feet (61 meters). Some codes limit the dimen-
outlined in the manufacturers installation instruc- sions of smoke compartments rather than limiting
tions. Improper installation can void such a listing. the travel distance to reach a compartment.
The quantity of outside air required for active A smoke compartment is intended to limit the
smoke control modes and the challenges of condi- number of people who need to be relocated and
tioning that volume of air under climatic extremes allows the transfer of beds or gurneys from (and into)
must be considered. A unit may normally take less adjacent compartments. It is constructed of one-hour
than 25% outside air, but in the smoke control pres- walls and has self-closing doors across barrier open-
surization mode, it is likely to take 100%. Although ings. Smoke compartment design needs to be coordi-
the loss of space conditions is of little concern during nated with HVAC smoke control provisions,
a fire, emergency systems are regularly tested, and automatic sprinkler design, and fire alarm system
the impact on the coils and space conditions during design. Generally, the HVAC system for each smoke
testing must be considered. The operation of basic compartment is treated as a separate zone. Where
safety devices, such as coil freeze protection or static ducts penetrate smoke compartment walls or barri-
limits, must be addressed during design to avoid a ers, dampers may be needed as described in the fol-
critical failure during testing or emergency opera- lowing sections. Approved fire-stopping materials
tions. must also protect piping and other penetrations of
these walls. Smoke barriers form a primary protec-
11.1.4 Codes and Standards tive strategy in a hospital building, and penetrations
must be well protected.
Codes and standards that will apply to a new
hospital building are likely to include NFPA 101, the 11.2.2 Fire Dampers
Life Safety Code, as well as other NFPA standards
Fire dampers are devices installed in an air-dis-
referenced in that code. Of primary importance to the
tribution system that are designed to close automati-
mechanical engineer will be NFPA 90A and NFPA
cally upon detecting heat. The intent of a fire damper
92A and 92B, which address air-handling systems
is to interrupt migratory airflow to restrict the pas-
and smoke control systems. NFPA 90A, 92A, and
sage of flame. Underwriters Laboratories lists these
92B cannot be used, however, without understanding
devices under UL 555, Standard for Safety: Fire
the approaches required by NFPA 101. Interconnec-
Dampers. Listed fire dampers have a label that gives
tion of the HVAC system to the building fire alarm
the manufacturers name, trademark or identifying
system will be addressed by the requirements of
symbol, damper type or model number, fire resis-
NFPA 72, National Fire Alarm Code, which requires
tance design number or type with maximum hourly
supervision of connections or fail-safe configuration
fire resistance rating, and reference to the manufac-
of controlled devices.
turers installation instructions.
The several model building codes also address
Fire dampers must close automatically and
fire protection in hospital buildings. They are not
remain closed upon the operation of a listed fusible
entirely consistent with the Life Safety Code,
link or other approved heat-activated device. The fire
although in recent years the requirements of the
damper must be able to close against maximum cal-
model building codes and the Life Safety Code have
culated airflow in the portion of the ductwork where
converged. Again, the mechanical engineer must
it is installedunless there is provision for shutting
understand the requirements of the applicable codes
down fans that serve that duct system. Fire dampers
and authority having jurisdiction before proceeding
are activated by heat and cannot be relied upon to
with design.
limit smoke movement during the early stages of a
fire, when large amounts of smoke may be trans-
11.2 SMOKE COMPARTMENTS
ferred well away from a heat source at the seat of the
AND BARRIERS
fire.
The fusible link or heat-activated device must be
11.2.1 The Smoke Compartment
able to sense an abnormal rise in temperature in a
NFPA 101 and the model building codes require duct and should have a temperature rating approxi-
separating a hospital building into smoke compart- mately 50F (28C) above the maximum tempera-
ments. In general, the smoke compartments must not ture normally encountered when the system is in
be larger than 22,500 square feet (2,090 square operation or shut down. The maximum rated temper-
118 HVAC DESIGN MANUAL FOR HOSPITALS AND CLINICS

ature of the link or heat activated device cannot Damper Location and Need
exceed 160F (71C). for Maintenance Access
Unless otherwise specifically required, fire A service opening must be provided in air ducts
resistance ratings for fire dampers are as follows:
adjacent to each fire damper. The access must be
-hour rated in 1-hour fire resistive assemblies large enough to permit required maintenance and
1-hour rated in 2-hour assemblies resetting of the device. Such service openings must
3-hour rated in assemblies rated as 3 hours or be identified using minimum -inch-tall (12.7 mm)
more letters that note the location of the fire damper.

Location of Dampers in Fire-Rated Maintenance of Dampers


Walls, Floors, and Ceilings Maintenance of fire dampers includes replacing
Fire dampers are required where ducts penetrate the heat-responsive element, operating it to demon-
or terminate at openings in occupancy separations, strate that the damper closes fully, lubricating mov-
area separations, and walls protecting horizontal exit ing parts, and checking that the latch (if provided)
egress. Local building codes typically require fire functions properly. Activating all dampers and the
dampers in penetrations in one-hour exit corridor associated hardware is a required maintenance prac-
walls unless the penetration is by a duct of not less tice that must be done at least once every four years.
than 26 gauge (0.5 mm) galvanized sheet steel and
the duct has no openings into the corridor. Fire 11.2.3 Smoke Dampers
dampers are also required in any other fire-resistive Smoke dampers are devices within the air-distri-
rated wall when other openings must be protected. bution system that are intended to control the move-
NFPA 101 does not require smoke dampers in smoke ment of smoke. These devices are activated either via
barrier walls when the HVAC system is fully ducted. the detection of smoke (by smoke detector(s) co-
If not fully ducted, smoke dampers would be located with the damper) or by a signal from the fire
required in smoke barriers. alarm system as part of the implementation of a
When air ducts extend through only one floor buildings smoke control system (see Sections 11.3
and serve only two adjacent stories, the ducts either and 11.4). When smoke detectors are co-located with
must be enclosed in fire resistive construction or fire dampers, they must be installed in accordance with
dampers must be installed at each floor penetration. NFPA 72 and the manufacturers installation instruc-
Where a duct or duct opening penetrates a rated tions, which specify limits on air velocity, required
floor/ceiling or roof/ceiling assembly, such penetra- differential pressures, and/or clearances from transi-
tion or opening must be provided with a fire damper tions or turns in the ductwork. A smoke damper may
in accordance with the design of the fire resistive serve as a fire damper where a given location lends
assembly. itself to multiple functions and the damper is listed
as a combination fire/smoke damper. Underwriters
Special Requirements for
Dampers Located in Shafts Laboratories lists smoke dampers under UL 555S,
Standard for Safety: Leakage Rated Dampers for
Fire dampers to protect openings into air shafts Use in Smoke Control Systems. A listed smoke
are required except as follows: damper has a label that gives the manufacturers or
private labelers name, model number or identifying
Where an air duct system is used only for
symbol, date of manufacture (may be in code), arrow
exhaust to the outside, serves only one story, and
showing direction of airflow, installation mode (ver-
is contained in its own dedicated shaft.
tical and/or horizontal), leakage classification, and
Where branch ducts connect to enclosed exhaust
ambient or degradation test temperature.
risers via steel sub-ducts that are a minimum of 22
Smoke dampers listed without a fire damper
inches (558 mm) long, the air flow in the shaft
moves upward, and the riser is sized to accommo- operator are closed automatically by springs and are
date the flow restriction created by the sub-duct. manually opened. Such smoke dampers are typically
used at penetrations of smoke barrier wall locations
The fire resistance rating of the enclosure (shaft) where a dynamic operating capability is not neces-
for protecting air ducts that pass through floors of sary for smoke control system operation.
buildings is required to be one hour in buildings of Smoke dampers listed with a fire damper opera-
less than four stories and two hours in buildings of tor can be closed and opened through a fire alarm or
four or more stories. building automation system. They are listed under
SMOKE CONTROL AND LIFE SAFETY 119

UL864 Category UUKL as smoke control system Building Automation System


equipment. The design must include an emergency Smoke Damper Controls
power supply for the detectors and fail-safe design in Smoke dampers may be controlled by a building
case of interruption of control air or power to the automation system provided that the system is listed
damper. These types of smoke dampers are used in for smoke control (UL864 UUKL) and has been
active smoke management systems. Such dampers installed in accordance with any special provisions
are allowed to be positioned manually from a com- required by the UL-listed manufacturers instruc-
mand station. When such dampers are installed to tions, such as transient protection, secondary power,
isolate air-handling systems whose capacity is more and hardware enclosures. The interface of the build-
than 15,000 cfm (7,080 L/s), the dampers must auto- ing automation system with smoke damper position-
matically close when the system is not in operation. ing must ensure that the fire safety protocols will
override the normal building conditioning system in
a fire emergency.
Location of Dampers in Smoke Barriers
Smoke dampers are required in each air transfer Maintenance of Smoke Dampers
opening or duct penetration in required smoke barri- A service opening must be provided in the duct-
ers. Exceptions to this requirement include: work at all smoke dampers to permit required main-
tenance. Refer to Chapter 14 (section 14.6.1) for
Ducts or transfer openings that are part of an additional discussion of maintenance requirements.
engineered (active) smoke control system. Smoke dampers must be tested at least every
When the air-handling system is designed to four years to verify that they close fully, in accor-
prevent recirculation of exhaust or return air in dance with NFPA 90A, Standard for the Installation
of Air-Conditioning and Ventilating Systems. Mov-
fire emergencies.
ing parts must be lubricated as necessary. Smoke
Where the air transfer openings or duct penetra- dampers that are part of a smoke management sys-
tions are limited to an individual smoke com- tem are required to be tested in accordance with the
partment. local building code (typically, at least once a year).
All automatic controls for smoke dampers must
Smoke dampers located in smoke barrier walls are be tested at least annually following the guidelines of
permitted to remain open when the fire warning sys- NFPA 92A (Chapter 4) or NFPA 92B (Chapter 5).
tem is activated, provided that their associated con- Smoke detectors used in conjunction with smoke
trol actuators and smoke detectors remain dampers must be maintained in accordance with
operational. NFPA 72, National Fire Alarm Code.

11.2.4 DampersOther Considerations


Special Requirements for
Combination Fire/Smoke Dampers The number of devices that must operate to
effectively control smoke will impact the reliability
In certain locations, both a fire damper and a of a system. Multiple smoke and fire dampers also
smoke damper may be required. In such situations, a drive up the cost of an HVAC system. The mechani-
device that is listed as a combination fire/smoke cal engineer, therefore, should closely coordinate the
damper may be employed. These dampers must meet routing of ducts with the locations of rated walls and
the listing requirements of both UL 555 and UL ceilings, so that the number of dampers can be mini-
555S. Such a damper will be designed to operate mized.
automatically due to heat or smoke sensed in the air- Where dampers must be positioned in a certain
stream. way to accommodate smoke control, the local code
When a combination fire/smoke damper is may also require monitoring the position of those
dampers. This will require end switches on the damp-
located in an air-handling system duct as part of an
ers and monitoring by the energy management sys-
engineered smoke control system, the temperature
tem, building automation system, or the fire alarm
rating of the fusible link or heat responsive element system. Listing and supervision requirements of the
may be 50F (28C) above the maximum operating local codes need to be followed. In most cases, if a
temperature of the smoke control system. However, device does not fail in a smoke/fire-safe condition
the temperature rating cannot exceed the UL degra- upon wire break, the control wiring must be super-
dation test temperature rating of the combination vised to within 3 feet (0.9 meter) of the controlled
fire/smoke damper or a maximum of 350F (176C). device.
120 HVAC DESIGN MANUAL FOR HOSPITALS AND CLINICS

Some codes also contain maximum time limits Some local amendments, however, require active
for repositioning of dampers. As an example, NFPA smoke control designs. Some codes require that
92A establishes a 75-second requirement. Not all high-rise hospitals or clinics (over 75 feet [23
dampers on the market can meet such time limits. meters]) have smoke control, and all U.S. model
Design specifications should address the time per- codes require active smoke control for atrium spaces.
mitted for repositioning the damper in either the Performance-based equivalencies may also require
open or closed position if that is a requirement of the an active smoke control or smoke removal system. In
design. addition, there are requirements in NFPA 99, Stan-
dard for Health Care Facilities, that operating rooms
11.2.5 Codes and Standards have the capability to prevent recirculation of smoke
Applicable codes and standards regarding fire from a fire within the OR suite. When an active
and smoke dampers for health care facilities include smoke control or smoke removal system is required,
NFPA 101, Life Safety Code; NFPA 90A, Standard the basic concepts for the design are similar from
for the Installation of Air-Conditioning and Ventilat- code to code. This section details these basics.
ing Systems; and local building, fire, and mechanical
11.4.1 Dedicated versus
codes.
Nondedicated Systems
11.3 PASSIVE SMOKE CONTROL Active smoke control design is based upon one
of the following design methods:
Since 1967, health care facilities have been
required to provide passive smoke control capabili- Exhaust
ties as an integral part of their design. Passive smoke Pressure differential
control consists primarily of smoke compartments
Opposed flow
with characteristics previously discussed. Depending
upon the local authority having jurisdiction, duct- Dedicated fans, dampers, and ductwork can be
work that penetrates smoke barrier walls may or may provided to meet smoke control criteria. This equip-
not require combination fire and smoke dampers. All ment will be used only in the smoke control mode
penetrations through a smoke barrier wall must have and will be provided with adequate redundancies and
approved through-penetration assemblies that can emergency power backup to ensure its operation in
resist the passage of smoke. an emergency.
Protection of penetrations in floors and shafts Nondedicated equipment used in smoke control
that bound or serve a smoke zone is another impor- systems will have other day-to-day functions
tant element of passive smoke control. These pene- assigned to it. A normal supply air fan may provide
trations also require a listed through-penetration makeup air to a smoke exhaust system. An econo-
assembly that can maintain the fire rating and resist mizer cycle that routes return air to the exterior may
the passage of smoke. be used as the exhaust portion of a smoke control
As with any life safety system element, passive system. Emergency power must be provided for
smoke control barriers require inspection and ongo- these nondedicated system components. Activation
ing maintenance. The barriers must be maintained at of a smoke control system using a nondedicated
a level that can resist the passage of smoke and con- smoke control arrangement requires overriding all
tain smoke in the area of fire origin. Without using other building control functions related to the non-
active smoke control, passive smoke barriers in com- dedicated equipment. Nondedicated systems have
bination with active fire suppression systems can lower equipment costs, but they may require compli-
provide a high degree of smoke compartmentation cated control equipment and programming.
and containment. Smoke barriers in unsprinklered
buildings greatly delay the spread of smoke but do 11.4.2 Smoke Control Mode of Operation
not provide long-term smoke containment. Automatic initial activation of the smoke control
sequence is essential. In a multiple-zone smoke con-
11.4 ACTIVE SMOKE CONTROL trol system, the initial operation of the system is
Defend-in-place is a primary concept for fire based on correctly locating the fire. In general, a fire
protection and life safety in health care facilities. can be located most reliably by using the automatic
NFPA 101 and the model building codes recognize sprinkler system zone information from the building
the defend-in-place approach to life safety and, in fire alarm system. This requires designing the auto-
general, do not require active smoke control systems. matic sprinkler system using sprinkler zones that
SMOKE CONTROL AND LIFE SAFETY 121

correspond to the smoke control zones. Smoke an atrium. Smoke control for an atrium usually con-
detector activation of a smoke control system is dis- sists of a smoke exhaust system. Smoke is exhausted
couraged in large multiple-zone buildings because at the upper levels of an atrium, and makeup air is
smoke that migrates to an adjacent zone before it introduced at the lower levels of the atriumbelow
reaches activation concentrations in the zone where the clear air-to-smoke interface. The mechanical
the fire originated may cause the smoke control sys- makeup air flow rate should be between 80% and
tem to first operate in the wrong configuration. Man- 90% of the mechanical exhaust rate. The remaining
ual pull stations should not be used to determine the
air flow would be provided through leakage at the
initial smoke zone because persons frequently acti-
atriums perimeter, although the amount of air that
vate them after they have left the area of the actual
fire. leaks into an atrium will depend upon the construc-
Some typical terms to be familiar with when tion tightness of the atrium enclosures.
developing the smoke control mode of operation are:
Smoke Control Zones
original zone of operation
adjacent zones In health care occupancies, smoke control sys-
nonrelated zones tems must be zoned. In very rare instances will a sin-
gle floor of a health care occupancy be considered
The design team should develop a smoke control one smoke zone. Smoke control systems usually can-
activation matrix during the design development and not totally protect the floor of a fires origin. Smoke
construction documents phases of a project. This control systems can limit and minimize the migra-
matrix should be part of the HVAC systems specifi- tion of smoke from the area of fire origin. In a
cations, building automation systems specifications, defend-in-place occupancy, such as a health care
fire detection alarm system specifications, and the
facility, passive smoke control is provided in the
automatic sprinkler system specifications. These
form of smoke barriers. If active smoke control is
four systems must be coordinated to properly acti-
vate a smoke control system. The activation matrix required, the active system should use the smoke
will identify the coordination required. barriers as the zoning configuration for its smoke
The design team should also prepare a list of all control strategy.
fans, control dampers, ductwork, door releases, fan
shutdown releases, detection device locations, smoke Controls
barrier locations, fire wall barrier locations, and
other information needed to properly test the smoke In addition to automatic control sequences, the
control system. smoke control system must have manual override
Before completing the design of the smoke con- controls. These controls will be provided in a place
trol system, the design team should prepare a testing accessible to the fire department or responding
method and manual for the system. This manual agency so they can override all automatic smoke
should incorporate the guidelines of NFPA 92A control settings. The smoke control manual override
(Chapter 4); NFPA 92B (Chapter 5); and NFPA 72 panel should be designed for ease of operation.
(Chapter 7), as appropriate for the equipment and
A smoke control system in a building is a cus-
design. This testing manual should be shared with
the contractor and the building and fire departments tom-configured system. Each local jurisdiction has
and coordinated between the design disciplines on its own requirements related to system performance
the team. This testing manual will identify perfor- and design. It is imperative that local building and
mance criteria for the smoke control system, the test- fire officials review and accept the smoke control
ing equipment needed, the testing protocol, the pass/ system design, manual override, and testing proce-
fail criteria, and the documentation required for dures before the construction documents are com-
accepting the smoke control system. pleted. NFPA 92A includes guidelines for graphics,
switches, and feedback that can be used when devel-
Atria oping a concept for local review. Even though it is
Atria are common in health care facilities. An customized for site requirements, the firefighter
atrium, by definition, is a vertical opening that con- interface panel should be UL-listed as part of a fire
nects three or more floors. In some jurisdictions, a or smoke control system experience indicates fail-
two-story vertical opening may also be classified as ure to do so is a recurring problem.
122 HVAC DESIGN MANUAL FOR HOSPITALS AND CLINICS

Activation and Deactivation of the using a commercially available variable flow rate fan
Smoke Control System or a fan bypass arrangement of ducts and dampers.
As previously noted, automatic activation of the Variable flow fans are controlled by one or more
smoke control system by a reliable means, such as static pressure sensors that sense the pressure differ-
sprinkler water flow, is desirable. The smoke control ence between a stairwell and the building. In a
system can also be activated manually through the bypass system, the air flow rate into the stairwell is
manual control panel discussed previously. The sys- varied by modulating bypass dampers, which are
tem should be deactivated only by manual means. controlled by one or more static pressure sensors as
Deactivation of the smoke control system will also just described.
require resetting the fire detection alarm system to
clear the resulting alarm. Reversal of supply and/or 11.5.3 Air Supply Source Locations
return fans is problematic and should be avoided. Choosing the location of the air supply for a
stairwell pressurization system involves numerous
11.5 STAIRWELL PRESSURIZATION
variables. The most advantageous choice is at the
11.5.1 Introduction bottom of the stair shaft, close to the ground. The
most notable advantage of a low point of supply is
Stairwell pressurization systems are designed
less likelihood of drawing contaminated air into the
to maintain a pressure differential from the stairwell
to adjacent spaces. The NFPA 101 Life Safety Code system (assuming that smoke from a fire in the build-
requires a minimum pressure differential of 0.05 ing will probably move upward). Additionally, the
in. w.g. (12.4 Pa) in sprinklered buildings and a wind effect in tall buildings is greater as you
minimum of 0.10 in. w.g. (25 Pa) in unsprinklered progress up the building, and this could have an
buildings. Additionally, the pressure difference across adverse effect on fan performance.
doors should not be more than that which permits Other considerations when locating supply
the door to begin to be opened by a force of 30 inlets include the location of other exhausts and out-
ft-lb (41 J). Depending upon the size of the door lets for the building. Care should be taken to avoid
and pressure exerted by the closing device, this
locating supply inlets near outlets from smoke shafts
generally occurs when the pressure differential
and vents of the smoke control system as well as nat-
exceeds 0.25 in. w.g. (62 Pa).
ural shaft vents such as elevator vents or other open-
Of course, many factors affect a pressurization
system, and several variables are undefined even ings that may exhaust smoke from a building.
after construction and final testing, including the
number of open doors, which can vary constantly. 11.5.4 Types of Air Supply Fans
Other factors that affect pressurization include the
Several types of fans are commonly used for
stack effect, the reverse stack effect, door leakage,
stairwell pressurization systems. The fans are basi-
wall leakage, and wind effects. Design consider-
ations for pressurization also include emergency cally either centrifugal or axial types and may be
power to the systems as required by NFPA 99 and either direct drive or indirect drive.
local codes and ensuring that the system controls All fans can be equipped with variable speed
used are listed as smoke control equipment. drives, variable inlet vanes, or dampers for changing
the airflow to a stairwell. Propeller and other axial
11.5.2 Excessive Pressure Control fans may use blades that are fixed, adjustable at
One method of compensating for changing con- standstill, or variable in operation and are, therefore,
ditions is the use of barometric relief dampers. These best suited for a stairwell pressurization system.
dampers relieve excess pressure (into the building or Controllable-pitch axial fans do not need speed or
outside) if the stairwell pressurization exceeds a vane controls.
specified value (usually 0.25 in. [62 Pa]). Concerns
associated with barometric relief dampers include Supply air fans may be stand-alone or part of a
additional maintenance to ensure proper operation building HVAC system. Additional dampers and
and the effect of adverse weather conditions in some control modules are needed, however, when using
climates. building HVAC fans as part of a stairwell pressuriza-
Modulating supply airflow systems is another tion system. This often leads to increased complica-
method of controlling excessive pressure differences. tion and maintenance and should be avoided if at all
A variable supply air flow rate can be achieved by possible.
SMOKE CONTROL AND LIFE SAFETY 123

11.5.5 Single and Multiple Injector Systems upon the amount of leakage through elevator doors
and the sensitivity of the elevator equipment to pres-
Many analyses, as well as actual tests, have been
sure differences within the shaft. Before using this
conducted to study the effects of single and multiple
approach, it is important to work with the elevator
injection point air supply systems. These studies
manufacturer and the general contractor to determine
have shown that stairwells of more than eight stories
allowable pressure differences and expected leakage
are subject to pressurization failure with single-point
of the elevator shaft.
injection. This is due to significant stack effect, as
well as to losses attributed to door openings near the If elevator recall (ANSI A17.1, Firefighter
source of the single-point injection. Phase 1 Mode) is not provided or elevators must be
used for firefighter access and patient evacuation, the
Because the top and bottom of stair shafts are
piston effect of moving elevators can enhance smoke
most susceptible to pressurization loss due to the
spread. While the mechanical engineer will not have
stack effect, it is best to avoid these locations for sin-
control over whether elevator recall is provided, it is
gle-point injection systems. Additionally, the large
a question that should be considered because it may
amount of air needed to reach sufficient pressure dif- impact the design of the smoke control system.
ferentials in tall stairwells may create pressure forces
on doors near the supply point that exceed allowable 11.7 CONTROLS AND SEQUENCING
door opening forces.
Multiple-point injection systems use one or 11.7.1 Passive Systems
more fans and a ductwork system with outlets Controls and sequences for passive systems are
throughout the stairwell. Studies have shown that relatively simple. However, the mechanical engineer
systems that have outlets on every level perform best, still must consider whether closure of dampers will
but systems that have outlets on alternate or every affect the integrity of fans and ductwork. If a fire
third level have also been effective. damper in the immediate vicinity of an exhaust or
supply fan closes (and there is only one branch of the
11.6 ELEVATORS system at that point), overpressurization or under-
Elevators and elevator shafts can impact the pressurization of the duct could occur. In that case, it
transfer of smoke between floors. Codes are incon- may be necessary to include a relief or a delay in the
sistent regarding protection of elevators and elevator damper closure.
shafts. NFPA 101 relies on quick-response automatic
sprinkler protection to limit air buoyancy and the 11.7.2 Active Systems
amount of smoke produced and, therefore, does not Controls and sequencing for active smoke con-
require elevator shaft or lobby protection. trol systems can be very complicated. Many smoke
Some of the model codes, however, require ele- control system components must work together to
vator lobbies in high-rise buildings and separating accomplish an overall purpose. A combination of
elevator openings from corridors in all buildings. All fans and dampers must start, open, or close, and that
codes require enclosing elevator shafts in two-hour sequence must occur in a way that will not damage
fire-resistive construction (with few exceptions). the HVAC system. Delays may need to be built into
If elevator lobby protection is required, gener- the system to allow fans to slow or stop before damp-
ally it is accomplished by using a one-hour-rated ele- ers are closed. The ability to properly position all
vator lobby. If an active smoke control system is VAV box dampers and control the output of variable
provided, this lobby will also often be treated as a speed drives to pressurize or exhaust a space most
passive zone, requiring that all ductwork penetrating efficiently may also be necessary.
the lobby wall employ smoke and fire dampers. For Manual controls are also necessary for an active
small elevator lobbies, it may be more convenient to system. For simple systems, control by damper and
fan may be appropriate. For the typical hospital sys-
anticipate that elevator lobby doors will be held open
tem, however, control by zone is more likely the
and that conditioning the space immediately outside
appropriate method. In this case, a single switch
the elevator lobby can achieve the necessary air would cause activation of the smoke control mode
exchange. In that way, no duct penetrations are for each zone, and a single LED will likely indicate
needed, and no dampers need to be provided. proper damper positioning for dampers within that
Some jurisdictions allow pressurization of ele- zone. Fan controls might be individually annunciated
vator shafts as a means of avoiding elevator lobbies. because they are larger portions of the system. Often,
Pressurization design for elevator shafts depends a firefighter control panel controls the system.
124 HVAC DESIGN MANUAL FOR HOSPITALS AND CLINICS

Because the fire department is expected to operate 11.9 TESTING AND COMMISSIONING
this panel, working out the design of the panel with
Regardless of the quality of design and con-
the fire department before fabricating it and specify-
struction, an acceptance test is necessary to ensure
ing the panel as UL-listed for smoke control appli-
that the smoke control system operates as intended.
cations is strongly advised.
The acceptance testing should involve two levels.
11.8 ENERGY MANAGEMENT AND The first is a functional test, which is a test of each
SMOKE CONTROL individual component to be certain it is operating
properly. The second level of testing is a perfor-
Energy management systems can add additional mance test to determine whether the system as a
complexity to a smoke control system. On the other whole works in accordance with the design.
hand, by using the energy management system to Testing will generally include measurement of
control remote devices, significant wiring can be
air flow and pressure differences in accordance with
eliminated. There are advantages and disadvantages
the testing guidelines developed by the designer. The
of tying together the building energy management
first step in the testing should be to agree on the per-
system and the smoke control system.
formance goals and to review the test criteria
Advantages included with the design.
By using the energy management system to per- ASHRAE Guideline 5 covers the commission-
form smoke control functions, replication of ing of smoke management systems and is a good ref-
wiring and controls to many devices can be erence for use in this regard. This chapter
eliminated. Instead, signals between panels, summarizes some of the information from the
generally done by dry contact, are all that would ASHRAE guideline.
be necessary.
By eliminating redundant wiring and control 11.9.1 Functional Tests
features, field priority issues can be avoided. The following items should be inspected and
Instead, priority can be dealt with at the panels. individually tested to confirm proper installation and
The energy management system is in normal operation.
use. Rather than functioning only in an emer-
gency, the system has to operate on a day-to-day Ducts should be tested for leakage and inspected
basis. This improves the reliability of the sys- for completeness and stability. In particular,
tem. ducts that traverse smoke compartments other
It has the ability to command VAV and VSD than the compartment they serve should be
devices directly to provide efficient pressuriza- closely reviewed to be sure that smoke flowing
tion or exhaust modes to a zone. through the duct will not leak into adjacent com-
It has the ability to monitor and control coils on partments.
units directly during smoke mode operations in Fan capacities, power (including emergency
order to minimize loss of space conditioning and power), speed, operation (within their curve),
equipment damage due to large outside air vol- and direction of flow should all be reviewed and
umes in extreme climatic conditions. verified.
The locations of initiation devices specified in
Disadvantages
the design should be verified, and the devices
If the energy management system is
should be tested to confirm that they operate
expected to provide smoke control func-
properly and report to the control panel. Outputs
tions, many jurisdictions will require it to
be listed as a smoke control system. Some from the control panel will be tested later (in the
energy management systems do not carry performance level stage).
such a listing. Fire and smoke dampers should be tested for
Energy management systems and life safety proper installation, operation, end switch posi-
systems are often the last systems installed tions, speed of opening and closing, adequate
in a building. The building cannot open power supply (including emergency power), and
without a life safety system. If the construc- location in accordance with the plans.
tion schedule is tight, it may be possible to Doors should be tested for proper rating, auto-
open some of the building without a prop- matic closure where appropriate, and location in
erly functioning energy management sys- accordance with the plans.
tem. By separating the systems, priority can Smoke barriers should be tested for integrity and
be provided to the life safety system. leakage.
SMOKE CONTROL AND LIFE SAFETY 125

The overall system should be reviewed for lay- 11.10 HEALTH AND LIFE SAFETY
out, including zoning and controls, and to check that
assumptions regarding temperatures and conditions 11.10.1 Maintenance
were realistic.
Besides the acceptance testing discussed in the
11.9.2 Performance Tests previous section, ongoing testing of the life safety
system and smoke control system should be con-
The first and most important step in the operat- ducted. This includes individual device testing, as
ing test is to develop a scenario of expected inputs well as overall performance testing. The ongoing
and outputs for each device. During design, a matrix reliability of smoke control systems depends upon
should have been developed that indicates, in gen- testing and maintaining systems regularly.
eral, reactions of the devices. The testing scenario
To carry out such ongoing maintenance and test-
takes that matrix one step further and indicates, by
ing, the original design and testing program must be
specific device, the actions and reactions that should
occur. For instance, a fire in Zone A should cause clearly documented. The building engineer should
Dampers 1, 2, 3, 4, 5, and 6 to open; Dampers 7, 8, 9, maintain this document, and the mechanical engineer
10, 11, and 12 to close; Fans C, D, E, and F to start; of record should also maintain a copy.
Fans G, H, I, and J to stop; Doors AA, BB, CC, and
DD to close; and a pressure difference between Zone 11.10.2 Infection Control/Sterile Areas
A and adjoining zones of 0.05 inch to be established. In a hospital, the unusual movement of air by a
The fire incident might also cause stairwell pressur- smoke control system cannot be allowed to over-
ization fans to start, annunciation on the proper pan-
come the infection control concerns necessary for
els, and operating lights to indicate proper
day-to-day operation. When air is expected to move
configuration. A detailed matrix (or scenario) by
from one zone (or room) to another during smoke
zone must be prepared to conduct these tests effec-
control system operation, it must be confirmed that
tively and efficiently.
the air is appropriate for such movement under nor-
Depending upon the type of smoke control sys- mal circumstances. Such movement will occur dur-
tem, pressure differentials or exhaust rates might be
ing a fire, during periodic inspection and testing, and
measured. Operability of all other system compo-
during unwanted alarms. The potential movement of
nents in alarm conditionsunder normal and emer-
infectious products through the operation of a smoke
gency powerwould be verified.
control system must be accounted for and avoided.
11.9.3 Equipment
11.10.3 Air Movement Considerations
A variety of tools are needed to measure smoke
In addition to the concern about spreading infec-
control system performance. Air flow from fans and
pressure differences across boundaries need to be tious diseases, there are other considerations to take
measured, door-opening forces need to be accounted into account regarding smoke control system design.
for, and air velocities may need to be measured. Most hospitals have cafeterias or kitchens, where
Some jurisdictions will also ask for a review of the fans for exhaust hoods are often quite large com-
direction of smoke movement. This may be done by pared with other air-handling devices in the vicinity.
using paper or smoke. Kitchen exhaust hoods can remain on during smoke
Artificial smoke should be used only to deter- control if they will not impact the performance of the
mine the direction of smoke flow. It does not repli- system. However, if either exhaust or makeup air
cate the hot smoke generated by a fire. Therefore, goes off and the other remains on, an imbalance of
filling a space with cold smoke to measure time to pressures and flows can easily occur. This must be
visibility or other similar performance indicators will considered under normal and emergency power con-
not serve the purpose intended. Using cold smoke to ditions.
determine the general direction of air movement is Many areas at higher or lower than standard
appropriate. pressures are found in hospitals. Operating rooms are
Many smoke detection devices do not respond to a sterile environment and need to remain so. Hyper-
cold smoke. Smoke detection testing should be done baric chambers cannot be impacted by smoke control
in accordance with NFPA 72 (Chapter 7) and the measures. These and other spaces must be consid-
manufacturers testing instructions. ered when developing smoke control concepts.
126 HVAC DESIGN MANUAL FOR HOSPITALS AND CLINICS

11.10.4 Fire Alarm System can cause smoke to pass through any openings or
gaps into adjacent spaces.
Throughout this chapter, coordination with the
fire alarm system has been stressed as a part of The flow of hot smoke into an atrium can be
smoke control system design. Zoning must be coor- summarized as follows:
dinated with both the fire alarm system and the auto-
matic sprinkler system. The handoff from the fire Hot smoke rises from a fire to the ceiling above.
alarm system to the energy management system or to Hot smoke spreads outward under the ceiling.
the smoke control system must be clear. There can be Smoke reaches an atrium and flows around the
no holes or redundancies passed on to the contractors edge of the fire floors ceiling into the atrium
for resolution. Coordinated testing of the systems void.
must be done so that inputs and outputs can be prop-
erly identified. Smoke damper locations need to be Although a glazed screen may or may not be fire
coordinated with smoke detector locations, smoke rated, it can fulfill an extremely useful role in main-
detectors in fan systems need to be coordinated with taining smoke separation between an atrium and the
the fire alarm system, and proper annunciation of the floors of the building and in assisting the displace-
smoke control equipment needs to show on either a ment ventilation system to allow incoming fresh air
smoke control panel or fire alarm panel. to force smoke out of the atrium at a high level.
Final placement and sequence of operation pro- On floors open to the atrium, a clear occupancy
gramming of duct smoke detectors provided as part zone is maintained below the smoke (approximately
of the building fire alarm system must be considered 6.5 feet [2.0 meters]) and smoke mixing is mini-
during design. Local codes may require overrides for mized as smoke and heat flow into and up the atrium
the supply duct detector air-handling unit shutdown where the smoke will rise to the atrium roof and col-
from the firefighters control panel. Further, place- lect to form a smoke cloud. By opening vents in the
ment of a return duct smoke detector may cause it to atrium roof or walls and/or by using smoke extrac-
be activated when a unit is placed in smoke purge or tion fans and ductwork, this smoke can be exhausted
exhaust mode; this must not interfere with the to the outside, thereby reducing the smoke volume
intended smoke mode operation. remaining and drawing smoke and heat away from
In addition to coordination with the fire alarm the fire zone.
system, a smoke control system needs proper emer-
gency power provisions and must be coordinated 11.11.1 Other Considerations
with rated walls, doors, and ceilings. Proper design
requires coordination among the entire design team. Occupants in a hospital are often asleep, too ill
to be mobile without assistance, and unfamiliar
11.11 ATRIUM SMOKE CONTROL with the building. The building, however, is
Many new or renovated hospitals incorporate an supervised by a trained management team. It is
atrium, or multiple atria in some cases, as central public policy that health care buildings be prop-
feature spaces. erly supervised and supported by trained staff.
An atrium in a building provides a possible The staff is trained to respond to a fire, which is
route by which smoke and fire can spread from one typically announced by the fire alarm system,
floor to another. Of course, smoke and fire could also and to follow a procedure to ensure that occu-
spread between stories in a building that does not pants are moved safely away from the fire
have an atrium, but normal horizontal compartmen- source. The problem is basically one of evacuat-
tation would provide a barrier to such spread, at least ing people safely to prevent injury from smoke
for a period of time (typically one hour). by intoxication, incapacity, unconsciousness, or
Building floor slabs help achieve fire separation, from panic.
and the whole building structure is designed to The general principle of movement of patients
remain stable for at least one hour during a fire. from areas of risk to safe areas applies, but there
However, smoke from a fire could get into an atrium are further considerations in buildings with atria.
void, bypass the floor slabs, and enter higher floors. Vertical Fire Spread. Fire, or smoke and heat
When an atrium enclosure does not confine the from a fire, may start to affect floors above the
smoke from a fire to the space in which it originated, fire. To avoid this an atrium must be depressur-
even though the building is of fire-resistant construc- ized and the neutral plane must be above the
tion, the buoyancy and expansion of the fire gases highest occupancy level. This will ensure that
SMOKE CONTROL AND LIFE SAFETY 127

air and smoke movement is toward the atrium of building systems. Wind and temperature are
rather than into the occupied areas. among the leading climatic factors that will have to
Stratification of the Smoke Layer. If the smoke be accommodated to ensure that the building sys-
from a fire cools too quickly, a cloud of cool tems operate according to their specifications. Cer-
smoke may collect within the atrium and fail to tain types of buildings and building systems are more
rise under buoyancy. Again, depressurization is vulnerable to the adverse effects of the environment.
required to draw smoke upward. Having an understanding of the potential pitfalls
Human Concerns for Safety. An atrium allows associated with the local climate will enable the
occupants on all floors to see what is happening designer to create more reliable and functional sys-
throughout the building. In a fire, smoke will tems. Conversely, if an utter lack of understanding
enter the atrium and will be seen by patients on exists, it is conceivable that inadequate or unsafe
floors above the fire floor. These patients will conditions could arise as a result of interactions
not be subject to any immediate risk, and between the building systems and the exterior envi-
ronment. This is especially true with life safety sys-
because the atrium is depressurized, they will
tems.
not come into contact with any smoke products.
Nevertheless, the sight of smoke will provoke Temperature will affect air movements and pres-
some concern and the hospital staff may have to sures to a significant degree, as is evidenced by such
move patients away from the atrium and to phenomena as the stack effect, stratification, and
assure them of safety. buoyancy. For example, a designer who is trying to
specify a pressurization system that relies on air
11.12 ENGINEERED FIRE SAFETY DESIGN flows with predictable densities, must have adequate
knowledge of the extreme winter and summer tem-
A fire safety engineering approach that takes peratures that will be experienced. Climatic data
into account the total fire safety package can often sources can provide this information. The required
provide a more fundamental and economical solu- air flow capacities to maintain pressure gradients
tion than more prescriptive approaches to fire safety. vary from summer to winter (when the greatest air
It may be the only viable means of achieving a satis- capacities are required and when the greatest interior
factory standard of fire safety in some large and to exterior temperature differences exist).
complex health care buildings. The interior climate in health care facilities is
Fire safety engineering can have many benefits. often precisely controlled. This may lead to extreme
In particular, it will: differences between the temperatures inside and out-
1. Provide a disciplined approach to fire safety side of a building. As some building systems rely
design to the designer. heavily on unconditioned exterior air, having a quali-
tative understanding of the design effects of tempera-
2. Allow comparison of the safety levels provided by
ture conditions is mandatory.
alternative designs.
Wind affects building systems principally via its
3. Provide a basis for selecting appropriate fire pro- introduction into the interior environment of the
tection systems. building as a result of leakage (observed in all build-
4. Provide opportunities for innovative design. ing constructions) as well as through more direct
5. Provide information regarding fire safety manage- means, such as air intake or exhaust openings. Air
ment for a building. intakes should be placed only after considering the
local wind characteristics and the location of exhaust
When used by persons suitably qualified and openings, lest a system be designed that introduces
experienced, a fire safety engineering approach will contaminated air into the building supply system.
provide a means of establishing acceptable levels of The key wind characteristics of which the designer
fire safety economically and without imposing must be aware are wind speed and direction. It is
unnecessary constraints on aspects of building generally true that the more prone the interior envi-
design. ronment is to exterior wind effects, the more chal-
lenging it will be to design effective building
11.13 CLIMATIC EFFECTS ON systems.
BUILDING SYSTEMS Computer models, such as CONTAM, may be
The designer is responsible for ensuring that used to quantify the varying effects of wind on the
varying climatic conditions are considered and prop- interior environment of a building. By defining leak-
erly accounted for in the design and implementation age areas and flow modes between the inside of the
128 HVAC DESIGN MANUAL FOR HOSPITALS AND CLINICS

facility and the outside, the designer can learn how orient the building with respect to its surroundings.
varying wind conditions affect air and smoke move- The source and nature of wind data must be carefully
ment and, hence, required air capacities and pressure considered to ensure that the most representative
differentials. Furthermore, the impact of wind direc- conditions are accommodated in designing the build-
tion may be analyzed with complex flow tools such ing systems.
as CONTAM, thereby allowing the designer to better
CHAPTER 12
ROOM DESIGN
12.1 GENERAL INFORMATION process is described by the biological force of infec-
This chapter describes ventilation designs for tion relationship (Heirholzer 1993):
various spaces in a health care facility. These designs Infection Dose Site Virulence
have been used in practice to restrict air movement Time Level of Host Defense
between spaces, dilute and remove airborne microor-
ganisms and odors, and maintain required tempera- This equation states that airborne infectious par-
ture and humidity levels. The designs are intended to ticles must be present in a concentration equal to or
perform their functions dependably with no more greater than the infectious dose for a long enough
than normal maintenance. See Chapter 14 for addi- time in a susceptible host for a colonization to occur
tional details. to the point where an infection begins. Infection then
The information in Chapter 4 provides a back- may or may not lead to disease.
ground for the design of ventilation for the various
spaces discussed in this chapter. Information pro- 12.2.2 What Role Can
vided herein includes diffuser types, layout sugges- Ventilation Design Play?
tions, typical loads, and system applications for Among the biological forces of infection param-
environmental control, infection control, and process eters in the above relationship, ventilation can affect
cooling. Information regarding the physical size and the infectious dose by control of the airborne infec-
shape of the rooms, the processes they may hold, tious particle concentration and the time of exposure
potential equipment, people, and lighting loads, and by lowering the mean age of air in a space. By con-
specific infection control needs can be found in centrating on the control of contaminant concentra-
Chapter 3, Facility Descriptions. tion and time of exposure, real engineering can be
accomplished with measurable results. In this way,
12.2 ROLE OF VENTILATION IN rational ventilation rates, filter efficiencies, and pres-
INFECTION CONTROL AND sure relationships can be determined (Hermans 2000).
COMFORT No single generalized ventilation design solu-
tion can solve all airborne infectious particle concen-
12.2.1 How Does Airborne Infection Occur? tration problems and be continuously cost-effective.
In order to determine the role of ventilation in Ventilation designers, who must always consider the
health care infection control, the process of acquiring cost of installation and operation of their systems,
an infection in either an open wound or via respira- need effective control strategies for air systems to
tion must be understood. Particles that are found in make a design work in practice. Unfortunately, venti-
every environment are not necessarily viable parti- lation control systems do not measure the concentra-
cles and are not necessarily infectious particles. tion of infectious particles in a space. A ventilation
Infectious particles may not necessarily cause infec- system cannot, therefore, increase airflow rates, vary
tions. Infectious particles may, if in high enough the air cleanliness, or improve air distribution in
concentrations, become an infectious dose that in response to a burst of airborne infectious particles.
turn may overwhelm a host's immune defenses. This Until a real-time and cost-effective monitor for

129
130 HVAC DESIGN MANUAL FOR HOSPITALS AND CLINICS

infectious particles (or a valid surrogate) is created, source to a susceptible person nearly anywhere in the
ventilation systems will be designed for fixed condi- distribution system if there is inadequate filtration.
tions of source generation of contaminants. Ventila- Any place where dust and dirt can accumulate in a
tion system design will be controlled by the patient room and subsequently become wet is a
traditional parameters of temperature, humidity, flow result of bad design practice. Air cooling coils
rate, and pressure. These are the tools the designer located within the patient room to cool air below its
has available to address infection and comfort con- dew point are particularly bad, due to the moisture
trol. they create mixing with the dust they collect. Any
finned element, whether cooling or heating, may
12.2.3 Which Infectious Particles become a amplifier for pathogens.
Should Be Controlled?
The choice of which particles to focus upon for 12.2.5 Ultraviolet Germicidal Irradiation
ventilation design (or for a ventilation standard), in a Room
depends entirely upon the expected clinical use of Properly maintained upper-room ultraviolet ger-
the space. Airborne candidates for control in most micidal irradiation (UVGI) lamps can kill a signifi-
common patient-occupied spaces are M. tuberculo- cant percentage of the viable particles floating in the
sis, measles virus, Varicella zoster, and some fungal air of a room. The best ventilation rates for effective
spores. These particles all have been shown to be UVGI are in the range of 10-12 ACH for winter
transported between spaces by ventilation systems (with an all-air heating system) and 6 ACH for sum-
(Riley 1980; Murray et al. 1988; Streifel et al. 1989; mer (or in winter with a convective heat source
Riley et al. 1978). below the window) (Memarzadeh 2000). Well-mixed
Patients with M. tuberculosis, measles, or air is a critical requirement for effective killing.
chicken pox should be in Airborne Infectious Isola-
tion rooms. Patients who are susceptible to infection 12.2.6 Why Is Filtered Air Important
will be in a Protective Environment. These spaces in Health Care Settings?
will require ventilation designs that are concerned
with concentration control or with protection. Of Basically, without air filtration, particle concen-
these infectious agents, M. tuberculosis is a good trations in indoor environments tend to build up.
organism for control focus simply because there has Even inert or dead particles can cause toxic effects in
been enough research to suggest a ventilation effec- some people, even normally healthy people. For
tiveness. A minimum ventilation rate is suggested in patients with respiratory problems, high particle
the next section. counts are detrimental.
Finding a design organism for the general The most compelling argument for filtration is
patient room is difficult. Although any patient room to reduce the transmission of pathogenic substances
could contain an undiagnosed infectious patient, pro- that will travel from person to person (or from the
viding ventilation to every room for such a possibil- environment to a susceptible person) and be depos-
ity would be prohibitively expensive. General patient ited either in an open wound, as in the case of an
rooms need to be cooled and heated to maintain con- invasive procedure, or into the respiratory system.
ditions described in Table 4-1 for the comfort of the Particles have a tendency to become deposited either
patient. Patient rooms need ventilation to make up in the upper respiratory tract or the lower respiratory
the exhaust from the toilet room if one is attached. tract, depending upon their size (Morrow 1980).
The physics of particle deposition probability in
12.2.4 Can Ventilation Design
the lung has been theorized to be based upon the size
Contribute to Airborne Infection?
of the particle, as shown in Figure 12-1. Upper respi-
Ventilation systems can be a source of infectious ratory tract (URT) deposition for the larger particles
particles and must be designed in such a way as to helps protect the more sensitive lower membranes of
avoid becoming amplifying sites for organisms to the lung. Notice the range of 0.2 micron to 5.0
grow and become aerosolized. Air systems are rarely micron where the deposition fraction in the upper
the original source of pathogens but can quickly tract drops off and the fraction in the lower tract
become a reservoir for amplification. All places (LRT) increases. This range of particles will tend to
where moisture and a food source can accumulate in enter the lung and become deposited in the deepest
the ducts or air-handler must be eliminated. Air sys- areas, there to colonize and potentially infect and
tems can distribute pathogens from an internal cause disease. Some particles that fall in this range
ROOM DESIGN 131

Figure 12-1 Particle deposition in the lung.

are Streptococcus, anthrax, aspergillus, diphtheria, spaced fins on tubes, but this type of coil was not
and tuberculosis. common in 1947. It is more likely that the heating
These types of organisms are dangerous to coil was a cast iron type not unlike the room radia-
healthy humans and much more so to those with sup- tors of the period (and not likely to require filters).
pressed immune systems. The likelihood of coming What remains, as a logical reason for the filter
across these kinds of pathogens is greater in hospi- requirement, is to protect the patient from airborne
tals than in a private home or on the city street. It is, contaminants present in the supply air. This is the
therefore, necessary for the health care ventilation primary reason high-efficiency filters are used today
designer to be aware of the risk of transmission of in health care ventilation systems.
these organisms through ventilation systems and of Health care ventilation filtration systems are
the opportunity to capture them on appropriate filter required to be tested using ASHRAE Standard 52
media. (ASHRAE 1992, 1999b). The minimum efficiencies
of required filters are listed in several guidelines and
12.2.7 Application of Standard 52.2 to design handbooks (ASHRAE 1999a; AIA 2001).
Health Care Ventilation Systems The Guidelines for Design and Construction of
Hospitals and Health Care Facilities provide the fil-
The requirement for air filtration in hospitals has tration requirements adopted in most states for health
a long history. In the October 22, 1947, Federal Reg- care design (AIA 2001). These requirements, con-
ister, the Public Health Service published rules for verted to equivalent MERV ratings, are shown in
construction of hospitals funded with federal funds. Table 12-1.
Commonly referred to as the Hill Burton rules, the All health care facilities, whether or not they are
requirements set minimum conditions for the envi- governed by the guidelines, should follow the above
ronments of certain critical areas inside hospitals. minimum requirements for filter efficiencies. Fol-
The rules said in part: The operating and delivery lowing are further thoughts on filtration.
rooms shall be provided with a supply ventilating
system with heaters and humidifiers which will The deposition versus particle size graph (Fig-
change the air at least eight times per hour by sup- ure 12-1) suggests filters should stop particles
plying fresh filtered air humidified to prevent static. that will pass by the upper respiratory tract
The humidifier requirement was necessary due to the (URT) and deposit on the lower respiratory tract
use of explosive anesthetics. The filter requirement is (LRT). Viruses are generally below 0.3 m in
not as obvious. Since these systems were required to diameter and, if they are free floating, they will
be 100% outside air, the intent wasn't to prevent very likely deposit deep into the lung. Not much
recirculating internally generated airborne patho- can be done about this by using filtration. Kow-
gens. The heating coils during this time may have alski et al. (1999) suggest that filter efficiencies
needed filters for protection if they used closely for virus-sized particles are difficult to deter-
132 HVAC DESIGN MANUAL FOR HOSPITALS AND CLINICS

Table 12-1. Filter Efficiencies for Central Ventilation and


Air-Conditioning Systems in General Hospitals
Filter Bed No. 1 Filter Bed No. 2
Area Designation No. Filter Beds (MERV) (MERV)
All areas for inpatient care, treatment, and diagnosis, and those
areas providing direct service or clean supplies such as sterile
and clean processing, etc. 2 8 15
Protective environment room 2 8 17a
Laboratories 1 12
Administrative, bulk storage, soiled holding areas, food
preparation areas, and laundries 1 8
Notes: Additional roughing or pre-filters should be considered to reduce maintenance for filters with efficiencies higher than 75 percent. The minimum
efficiency Reporting Value (MERV) is based on ASHRAE 52.2-1999.

a. HEPA

mine because of problems in modeling filter 12.2.8 Surgical Site Infections


performance using the diffusion model (Kowal-
ski et al. 1999). A distinction between infection and contamina-
Since the effect of filtration on free viruses is tion must be made. An infection is defined as a
not understood sufficiently to make a recom- pathologic condition of tissue characterized by signs
mendation for filter efficiencies, it has been sug- of inflammation (redness, swelling, pain, heat, puru-
gested that the best method to control virus lent secretion) with or without general bodily reac-
concentrations in room air is dilution with out- tion (fever, prostration, etc.). Contamination is
side air (Hermans and Streifel 1993). defined as the seeding of microorganisms that may
If viruses are not the particles to establish filter or may not develop into an actual infection, depend-
efficiency, then some other particle is needed. ing on such factors as susceptibility of the host, the
Bacteria fall into the size range of 0.2 m to 2.0 quantitative load and virulence of the invading
m. This particle size range is within the ability microorganisms, and other factors. A surgical wound
of present day filter media. This range is also the infection is initiated by contamination of the wound,
size particle most likely to be deposited deep in may develop within a few days after surgery, or may
the lung. Notable pathogens that fit this range be delayed and not become evident until months, or
and are communicable are Chlamydia Pneumo- even years, after contamination. Surgical wound
nia at 0.28 m and Mycobacterium tuberculosis infections may be superficial, involving skin and
at 0.64 m logmean diameter. subcuticular tissue, or deep, involving deeper subcu-
The choice of filters for patient care areas is taneous tissues, fascia, muscle, bone, joints, internal
90% by the dust spot method. However, under organs, or body cavities (peritonitis, pleuritis).
Standard 52.2 this filter may only have an effi- Sources of contamination and infection may be
ciency of 84% at the 0.3 to 1.0 m particle size endogenous (originating from the patient) or exoge-
range. Since the infectious dose for TB is as low nous (from anywhere outside the patient). Contact
as 1 bacillus (Ryan 1994), this filter would not contamination is contamination carried into the sur-
be the best choice. gical wound by touching or penetrating the raw tis-
There is a choice of filters above 90% dust spot sue of the surgical wound with contaminated surgical
efficiency. The MERV chart shows several fil- instruments or foreign body implants or by contact
ters in this range. MERV 15 is probably neces- with contaminated gloves or apparel of the surgical
sary for use in any area involving a patient team. Airborne contamination is carried into the sur-
where respiratory infections exist. Fungal spores gical wound by means of microorganisms present in
are another threat to patients. Stopping such the air. Contamination may reach an open surgical
spores is relatively easy with filters of MERV 13 wound by direct or indirect pathways. Indirect con-
and higher. These could be used with any tamination occurs when instruments are seeded by
patients having normal immune systems and no airborne microorganisms and then placed into the
open wounds. surgical wound, thereby combining airborne with
Laboratories can be served by filters of MERV contact contamination. Bioparticles are microscopic
12 and higher. particles that carry microorganisms (bacteria,
Pre-filters should be at least MERV 8. viruses, fungi, etc.). Airborne bacteria or viruses
ROOM DESIGN 133

may be carried on bioparticlessuch as dust parti- the room dew-point temperature. Provide heating by
cles, lint particles, shed skin scales (scurf)or in air or from flat and smooth radiant panels. Use no fin
moisture globules or may be airborne as actual bac- tubes or convectors. Diffusers can be of Group A and
teria or spores, singly or in clusters. Group E, but not Groups B, C, and D (refer to Chap-
No more than an estimated 2% of all surgical ter 9, Section 9.8.3). Pay close attention to the air
wound infections are attributable to airborne contam- diffuser performance. Minimum required ventilation
ination (2% of the 1-3% wound infection rate in flow rates are increased by poor air diffusion. The
clean-clean operations, or 0.02% to 0.06% of all sur- entire room volume should be well mixed with sup-
gical wound infections). Clean-clean operations are ply air. Choose diffuser throw lengths that allow no
defined as surgical operations in which no preexist- stagnant areas. Provide air volumes to offset the heat
ing infection is encountered, no break in technique gains in the room or as required by the local author-
has occurred, or in which the gastrointestinal, bil- ity having jurisdiction (AHJ), whichever is greater.
liary, gentiolurinary, or respiratory tracts have not Assume internal heat gain from a television set.
been entered. Airborne organisms assume a more
important role as a cause of wound infection when 12.3.2 Nursing Station
(1) an air-handling system becomes grossly contami-
Equipment loads should assume four ordinary
nated due to faulty design, faulty installation, poor
personal computers, two cardiac patient monitors,
maintenance, misuse, or abuse; (2) a large foreign
body is surgically implanted, as in complete joint and possibly a pneumatic tube station. Exhaust a
replacement; (3) the patient's immune mechanism is nourishment room as if it were a kitchen; makeup air
suppressed; and (4) the quantity and/or virulence of should come from the nursing station. Provide an
the invading microorganisms is overwhelming. accurate thermometer on an adjustable thermostat
for staff use.
12.3 HEALTH CARE ROOM
DESIGN CRITERIA 12.3.3 Isolation Rooms
Isolation bedrooms may generally be classified
12.3.1 Inpatient Care Units into two types: Airborne Infectious Isolation Rooms
The general medical/surgical patient room ven- (AII) for patients having an airborne-communicable
tilation design is intended for patients with near nor- disease and Protective Environment (PE) rooms for
mal immune systems that protect the patient from the patients suffering from weakened immune systems
normal airborne organisms found in the ambient and who require protection against infectious air-
environment. General patient rooms should have the borne agents. For the AII room, the HVAC system
following design parameters. functions as one of the multiple levels of infection
Ordinary or general patient rooms should have control designed to contain patient-generated infec-
neutral or slightly positive pressure differential with tious microbials within the room in order to prevent
respect to the corridor. Pressure differentials should the spread of infection to other patients and staff. In
be maintained between patient rooms and any adja- the case of the PE room, it is the patient who must be
cent sterile area, soiled utility, toilet, locker room, or protected against infectious microbials, including
isolation room. This requirement is intended to limit opportunistic pathogens that would normally not
the migration of smoke, but in the health care setting pose an infection risk to healthy individuals. Design
it has the added benefit of limiting the transfer of air- requirements for each type of isolation room follow.
borne organisms into the room. Positive pressures to
the corridor should be maintained where allowed. 12.3.4 Airborne Infectious Isolation Rooms
Exhaust all air from patient toilets at 2.0 cfm per (AII)
square foot (10.2 L/s per square meter) or at code- AII rooms are used to house patients with sus-
required flow rates, whichever is larger. Introduce pected or known respiratory diseases such as Myco-
replacement air to the toilet room, if necessary, equal bacterium tuberculosis. These rooms provide a
to or slightly less than exhausted air as part of a cen- volume within which airborne particles are con-
tral ventilation system. Provide all necessary cooling tained, diluted, and directed outside. AII rooms have
with air from a central air-handling system. Use no two major ventilation design criteria: (1) negative air
wet coils in the room, such as with fan-coil arrange- pressure relative to all adjoining spaces and (2) an air
ments. If radiant cooling panels are used, ensure that distribution pattern within the room that is favorable
the chilled water temperature always remains above to airborne infection control.
134 HVAC DESIGN MANUAL FOR HOSPITALS AND CLINICS

Negative Air Pressure AL = air leakage area, in.2


Measuring a negative differential air pressure C5 = units conversion, 0.186
between the AII room and the corridor may provide Qr = air leakage volume, cfm
evidence that all air movement is into the room. = air density, 0.0724 lbm/ft3 at normal room
There are a number of factors, however, that may temperature
well allow air to escape from an AII room in spite of CD = discharge coefficient, approximately
a negative room-to-corridor pressure relationship. 0.186
One such factor is the opening and closing of the pr = reference pressure differencefor AII,
room door. 0.01 in. w.g.
The truly significant factor in determining the The coefficient CD is a parameter that depends
amount of air volume migration (AVM) from the upon the gaps through which the air flows. An esti-
room to the corridor is the airflow volume differen- mate of this parameter has been made (and tested
tial (Hayden et al. 1998). In all cases, some air vol- empirically) to be 0.186 (ASHRAE 2001a). The
ume migration occurs through an open door when designer should estimate the leakage area using this
the air pressure difference is essentially zero. In one method from the ASHRAE Fundamentals chapter on
study, for a range of room air exhaust from 50 to 220 infiltration. If the leakage area cannot be reduced to
cfm (23 to 104 L/s), the AVM between an isolation that needed for an airflow differential of 100 cfm
room and its anteroom was found to be 35 to 65 ft3 (47.2 L/s), recalculate with the known air leakage
(1.0 to 1.8 m3) (Hayden et al. 1998). Through dilu- area and solve for Qr. Minimum Qr is 50 cfm (23.6
tion, a 500 ft3 (14 m3) anteroom (for example) with L/s) and pr is 0.01 in. w.g. (2.5 Pa). In most cases,
an AVM of 50 ft3 (1.4 m3) would experience a 90% Q must be much larger and can even equal the total
cooling supply air volume. In order to reduce the
reduction in the transmission of contaminated air to
value of Q the ventilation designer should influence
and from the isolation room. An anteroom is recom-
the envelope tightness as a means of decreasing the
mended as a means of controlling airborne contami-
leakage area. Leakage areas of 35 in.2 (22,575 mm2)
nant concentration via containment and dilution of require Q = 100 cfm (47.2 L/s) at 0.01 in. w.g. (2.5
the migrating air. Pa) (Coogan 1996). Maintaining a negative air pres-
Provide a tight envelope to maintain effective sure difference between the AII and the corridor may
control of infectious organisms generated within the not be enough to provide isolation. Since there are up
room. Walls must extend from floor to structure and to five possible shared bounding surfaces for any
all openings must be sealed. Maintain a specific dif- room, and since there may be adverse pressure rela-
ferential airflow rate. Airflow from one space to tionships across any of these surfaces, each surface
another occurs through cracks or gaps in walls, ceil- must be considered. Pressures in adjoining rooms
ings, and floors, and around doors. The sum of the may be lower than in the AII room and air may flow
areas of all these pathways is called the leakage area. out. In order to prevent such flows, the Q may need
The infiltration or exfiltration from an AII room is a to be increased beyond that required to maintain
function of the leakage area and the pressure differ- appropriate corridor flow. The value of Q must be set
ential across each of the five surfaces of the room. to ensure that the AII will pull air from all of the sur-
Isolation is maintained only when the airflow is rounding spaces. See the sample ventilation work-
inward on each of the five surfaces. Air pressure dif- sheet (Table 12-2).
ferential is a measurable quantity and should be
Air Distribution Patterns within Airborne
maintained at 0.01 in. w.g. (2.5 Pa). A reasonable Infectious Isolation (AII) Rooms
differential airflow rate for a patient room is 100 cfm
(47.2 L/s). The designer must coordinate with the Within the isolation room itself, the goal of the
architect to seal the AII room to allow a 0.01 inch HVAC system is to establish an airflow arrangement
(2.5 Pa) pressure difference with a fixed air volume that will reduce exposure of uninfected occupants
difference. This is accomplished by estimating the who visit or work in the space. The recommended
design approach favors creating maximized air mix-
maximum allowable leakage area of all uncontrolled
ing and dilution effectiveness and, thereby, maxi-
openings. The ASHRAE HandbookFundamentals
mized microorganism removal.
provides a method to estimate the allowable leakage
While laminar flow systems are of proven
area as follows:
efficacy in clean-room and other applications involv-
12 ing much higher airflow exchange rates, designers
A L = C 5 Q r ( ( 2p r ) ) C D p r cannot expect to achieve or maintain true unidirec-
ROOM DESIGN 135

Table 12-2. Example Ventilation Worksheet: AII Room with Anteroom


Room Name Airborne Infectious Isolation
Room Number: 1-100
Room Floor Area: 120 ft2 (11.2 m2)
Room Volume: 960 ft3 (27.2 m3)
Room Cooling Load: 4000 Btuh (1172 W)
A Toilet Exhaust Volume: 100 cfm (47.2 L/s)
B Room Supply Volume for Cooling: 185 cfm (87.3 L/s)
Room Leakage Area: 35 in.2 (22,575 mm2)
C Differential Air Volume: 100 cfm (47.2 L/s) for P = 0.01 in. w.g. (2.5 Pa)
D Anteroom Supply Volume: 75 cfm (35.4 L/s)
Room Exhaust: B + C + D A 260 cfm (122.7 L/s)
Room Air Change Rate: 16.25 (12 ach = 192 cfm [90.6 L/s] exh.)

Table 12-3. Example Ventilation Worksheet: PE Room with Anteroom


Room Name Airborne Infectious Isolation
Room Number: 1-100
Room Floor Area: 120 ft2 (11.2 m2)
Room Volume: 960 ft3 (27.2 m3)
Room Cooling Load: 4000 Btuh (1172 W)
A Toilet Exhaust Volume: 100 cfm (47.2 L/s)
B Room Supply Volume for Cooling: 185 cfm (87.3 L/s)
Room Leakage Area: 35 in.2 (22,575 mm2)
C Differential Air Volume: 100 cfm (47.2 L/s) for P = 0.01 in. w.g. (2.5 Pa)
D Anteroom Supply Volume: 75 cfm (35.4 L/s)
Room Supply: Larger of B or A + C + D 275 cfm (129.8 L/s)
Room Air Change Rate: 16.25 (12 ach = 192 cfm [90.6 L/s] sup.)

tional flow in infectious isolation rooms (one need dor and potentially counteracting the desired air
only consider that at an air change rate of 12 ACH, transfer pattern. Provide enough conditioned air to
the average air molecule travels about the space for satisfy the cooling loads within the room. The inter-
an average of five minutes before exiting). nal heat gains in the typical patient room demon-
The preferred design approach emphasizes air strate one possible ventilation design. These rooms
mixing effectiveness and dilution ventilation without generally have televisions like any other patient
attempting to establish unidirectional airflow. Occu- room. When totaled with two room occupants (a
pant protection is afforded by minimizing the air- patient and a caregiver), lights, solar loads, and wall
borne concentration of infectious microorganisms. conduction, heat gains easily exceed 4000 Btu/h
As discussed in more detail in the ASHRAE Hand- (1172 W). This gain will require about 185 cfm (87
bookFundamentals, ventilation effectiveness is L/s) of 55F (12.8C) air.
maximized, particularly for perimeter rooms in cool-
Provide more exhaust volume than supply in this
ing-dominated climates, by Type A ceiling-mounted,
type room. Either the supply airflow or both supply
horizontal-throw diffusers, with maximum throw
and exhaust air volumes should be controlled by a
reaching the far wall and with ceiling-mounted
relative-pressure-sensing device. The sensor should
exhaust registers. In addition to its contribution to
always be located within the wall of the patient room
ventilation effectiveness, the exhaust registerif
exit, regardless of the presence of an anteroom. If the
located over the patient bedhas the potential of
sensing device measures relative pressure, set the
increasing the system's overall efficacy by its loca-
control for 0.01 in. w.g. (2.5 Pa). See the sample ven-
tion in the path of the patient's cough-induced plume.
tilation worksheet (Table 12-3).
The designer should be cautious with supply diffuser
location and throw design, to avoid high-velocity Provide an alarm mechanism to alert clinical
throw reaching the doorway to the anteroom or corri- staff of loss of negative pressure. Supply air to the
136 HVAC DESIGN MANUAL FOR HOSPITALS AND CLINICS

room does not have to be 100% outside air. Supply erations similar to the AII room: (1) room air pressure
air must be filtered at least to the levels of the general control, in this case positive pressure with respect to
patient spaces. All air must be exhausted directly to all adjoining spaces, and (2) an air distribution pattern
the outside. Locate exhaust grilles or registers within the room that is favorable to airborne infection
directly above the patient bed. Consider locating the control, in this case for the protection of the patient.
exhaust grille near the head of the bed. Use Group A
or E outlets (see Chapter 9) for supply air. Place the Positive Air Pressure
supply diffuser in the center of the room or slightly Maintaining positive pressure, possibly with
toward the entrance. Provide high airflow rates and anterooms and continuous alarms, requires daily or
high air diffusion performance. Air in this room continuous monitoring of pressurization. Seal PE
should be well mixed. A 95% ADPI (Air Diffusion rooms to reduce air leakage area and/or increase dif-
Performance Index) can be achieved with a good ferential air volume to maintain a differential pres-
Group A diffuser moving 15 air changes per hour sure of 0.01 in. w.g. (2.5 Pa). As an example (see
and a single ceiling return (Riskowski 1996). Table 12-3), with a 35-square-inch (22,575 square
Exhaust grilles in AII rooms require special design millimeters) air leakage area, the differential air vol-
attention. Low sidewall grilles, if used, have the ume needs to be 100 cfm (47.2 L/s). The toilet room
potential of becoming clogged with lint from bed- then needs to be exhausted at 100 cfm (47.2 L/s) and
making and gowns. Failure to keep grilles clean the anteroom must be exhausted. If the anteroom is
often results in overpressurization of the AII room, exhausted at 75 cfm (35.4 m/s), the patient room
creating an effect opposite to that of containing would be supplied with a minimum of 275 cfm
infectious disease (Hermans and Streifel 1993). (129.8 L/s). This equals 17.2 air changes per hour.
The actual air flow volumes for these rooms will
Room Air Distribution
depend heavily upon the cooling load and on the size
of the leakage area. If the cooling needs are lower, A unidirectional flow approach is recom-
the air change rate can be lessdown to a minimum mended, where air is introduced at low velocity (100
of 12 air changes per hour. If the leakage area is fpm or less) from ceiling-mounted non-aspirating
larger, the exhaust must be greater to achieve the flow diffusers. Use non-aspirating unidirectional
0.01 in. w.g. (2.5 Pa) pressure differential. flow diffusers of Group E, including HEPA filters
within the diffuser. Air is exhausted at the floor level
near the entrance to the room. The intent is to estab-
12.3.5 Protective Environment (PE) Rooms
lish a vertically downward wash of clean air through
Protective Environment rooms include Bone the breathing zone of the patient, picking up contam-
Marrow Transplant, Oncology, Hematology, and inants as the air passes through the lower level of the
rooms for any condition that leaves a patient immu- room and out through the exhaust registers. This
nocompromised. The PE room has an objective very approach may require more air than the well-mixed
different from the AII room. Whereas an AII room room in order to maintain the cleanest air at the
seeks to protect uninfected occupants and the general patient. In the cooling season, some advantage can
be taken by allowing the air to dump somewhat
population outside the room from the infection source
down to the bed. However, in the heating season in
(the patient), a PE room seeks to protect the patient
colder climates, the air must be forced down to bed
from all potential airborne infectious organisms, some level at velocities around 50-75 fpm (0.25-0.38 m/s)
of which may be benign to normal immune systems. without entraining room air. A higher room tempera-
Among these otherwise harmless organisms are fun- ture can allow cooler supply air to fall to the bed
gal spores. In many climates, fungal spores are found (even in the heating season), so a radiant heat source
in the ambient air both inside and outside of environ- near the window, controlled independently from the
mentally controlled buildings. Spores from Aspergil- supply air temperature, is an advantage.
lis fumigatus, for example, are ubiquitous and exist in For example, set the room supply air tempera-
the outside environment in concentrations of several ture at a fixed temperature and vary the radiant panel
hundred colony-forming units per cubic meter of air using a room thermostat to maintain 75F to 78F
(cfu/m3). Thermo-tolerant species, i.e., those that (23.9C to 25.6C) in the heating season.
grow in cultures at 37C (98F), are particularly haz-
ardous to the immunosuppressed patient. Low con- 12.3.6 Critical Care Units
centrations (~2.0 cfu/m3) of A. fumigatus in the indoor The critical care unit environment has an impact
air surrounding such patients may cause aspergillosis on the recovery of traumatized patients. The air in
(Rhame et al. 1984). The PE room has design consid- critical care units must be nearly sterile and of low
ROOM DESIGN 137

velocity at the patient. Patients in critical care have Psychiatric Nursing Units
wounds that are still susceptible to airborne infec-
These spaces require special attention to sound
tion.
control. These spaces may require security diffusers.
Convective heating elements using fins or other
Ask the department about the patient protection
closely spaced surfaces trap dirt, dust, and lint that
needs.
can be re-aerosolized into the room air. Fin-tube con-
vectors should not be used in critical care. If perime-
Physical Therapy
ter heating is required, use radiant ceiling panels or
linear air diffusers with hot air discharged down the Such spaces need lower than normal tempera-
window. ture settings that may require a special thermostat.

General ICU Occupational Therapy


Design is similar to that of patient care rooms These areas often include working kitchens and/
with higher air change rates. Use Group A and E out- or garages that have special ventilation needs.
lets; use no fin-tube radiation. Make this a well-
mixed room. An ICU that is also an AII room must Cardiology (Telemetry) Step Down Units
be designed to the standards of AII. Avoid any equipment that may interfere with the
RF telemetry units. These rooms may have unusual
Wound Intensive Care (Burn Units)
cooling loads for monitors, ventilators, or thermal
This room type requires careful humidity con- blankets.
trol; maintain 40-60% RH. Air velocity must be
below 50 fpm (0.25 m/s) at patient bed level. Deliver 12.3.7 Surgical Suites
unidirectional airflow throughout the room, using
Operating rooms, as a class of space within
non-aspirating ceiling diffusers of Group E with
health care facilities, are very special. The operating
HEPA filtration within the diffuser. Use low sidewall
room environment is unique among patient treatment
returns near the door to the room. Keep the room
areas of a hospital. It is a special-care area where
under positive pressure at all times.
patients are put at greater risk than elsewhere.
Neonatal Intensive Care Patients are being rendered insensitive to pain by
means of general or regional anesthesia. Instruments
Air movement patterns must avoid velocities and devices are inserted into the body to conduct
above 50 fpm (0.25 m/s) at isolet levels. Provide invasive surgical procedures. Surgical procedures
Group A and E outlets; use no fin-tube radiation; use expose varying amount of exposed interior tissue to
low sidewall returns. the environment. The environment may engender its
own hazards and risks to both user and patient (Lauf-
Examination Rooms
man 1994). Airborne infectious contamination
A typical examination room may require more comes from two primary sources: (1) aerosolized
air changes than a patient room to satisfy the cooling microorganisms generated within the operating room
requirements of the space. Supply and return loca- and (2) aerosolized microorganisms introduced by
tion is not as critical as in a Trauma Room (see Sec- ventilation or infiltration.
tion 12.3.7), but distribution device locations must be The surgical suite contains operating rooms as
considered to thoroughly wash the space. Supply well as substerile rooms, clean supply, preoperative
outlets of any groups may be used. preparation, and postoperative recovery care (postan-
esthesia care unit or PACU). Common usage of the
Cast Rooms term OR is often intended to include both the sur-
Provide special ventilation and exhaust for the gical room and the above-mentioned support areas.
high concentration of plaster dust. This should be a In some hospitals, other spaces such as locker rooms,
negative pressure space. Most casts today are made doctors' lounges, control desks, anesthesia work-
of glass fiber and epoxy resin. These rooms may or rooms, and even surgical waiting areas may be
may not require special exhaust due to volatile gases. included in the general term. The OR special envi-
Ask the emergency department about the type of cast ronment, however, embraces only the restricted area
material used. of the surgical suite.
138 HVAC DESIGN MANUAL FOR HOSPITALS AND CLINICS

General Purpose OR Local gas scavenging exhausts can take the form of
either an adapted connection to the medical vacuum
Surgeons want the operating room air to be
system or a custom-ducted low-pressure system.
clean enough to not contribute to the hazard of
wound infection and tolerable enough in temperature Recovery and Pre-Op
and humidity to provide a comfortable working envi-
ronment for the surgical team and an optimal envi- These spaces within the surgical suite should
ronment for the patient (Laufman 1999). Surgeons have filtration similar to the general OR. They
may mistake high humidity in the operating room for should have positive pressure relative to the corridor.
high temperature and request a lower room tempera- Spaces such as pre- and post-op (recovery) have high
ture when, in fact, the reason for their discomfort lies equipment loads. Provide good air mixing using
in the excessive humidity. Group A ceiling diffusers and airflow rates accord-
ing to Table 4-1.
Operating rooms should be maintained at posi-
tive pressure with respect to corridors and adjacent Sterilization
areas. Positive pressure should be maintained at all
times, regardless of room occupancy. Positive pres- Substerile rooms, flash sterilizer rooms, or other
sure should be between 10% and 15% of air volume. rooms with sterilizers should be exhausted to main-
Provide ceiling diffusers of low-velocity and high- tain negative pressure relative to all adjoining spaces.
volume output. Design for lower velocity and lower Use manufacturer's information to obtain heat gains
volumetric flow rate while maintaining stable direc- from sterilizers. Place an exhaust register directly
tion and low-turbulent (low mixing) characteristics; above the sterilizer door to capture fugitive steam.
this results in less possibility of contamination
Eye Surgery
impinging upon the surgical wound and lower oper-
ating cost (Lewis 1993; Memarzadeh 2002). Provide Special environments for microscopes are
low sidewall returns. Provide Group E outlets only, required. Eye surgery requires critical air velocities
located in the ceiling and of non-aspirating type. at the eye. Provide less than 50 fpm (0.25 m/s) at the
A key design parameter for air distribution is to patient head level. Microscopes require very stable
maintain a low enough velocity at the surgical site to anchors to eliminate vibration. These anchors may
allow the wound's thermal plume to carry away any obstruct airflow.
airborne particles released into the sterile field. Dif-
fuser face air velocities should be no higher than 30 Cardiac Surgery
fpm (0/15 m/s) (Memarzadeh and Manning 2002). Expect more than the normal equipment and
Recirculate no more than 80% of the supply air back personnel in cardiovascular operations. These surgi-
through the air-handling system. Provide two stages cal rooms are generally larger than general-purpose
of filtration: MERV 8, then MERV 15. rooms. A pump room with direct access is usually
Provide occupant control of temperature and situated adjacent to the cardiovascular room.
humidity using thermostats and humidistats with a Because of the back-and-forth traffic, the quality of
wide range of control. Both thermostats and humi- the air in the pump room should be equal to that in
distats should be operable by operating room staff the adjoining OR. In some cardiac operations, sur-
through the full range of available room tempera- geons may request that the room temperature be rap-
tures and humidities. Provide individual room duct idly lowered below the usual 68F (20C) to as low
humidifiers with stainless steel duct sections and as 60F (15.6C). They may also want the room rap-
condensate drains from the duct. Provide HVAC sys- idly heated to 78F (25.6C) during the same opera-
tems that are powerful enough to offer a range of tion. Because of the power necessary to accomplish
conditions depending upon the needs of the room. such rapid changes, a supplemental cooling and heat-
Some jurisdictions require a system to provide all ing system is used. Auxiliary cooling coils can be
environmental conditions within the range of tem- used to provide such cooling for individual rooms.
perature and humidity listed in Table 4-1, e.g., 68F Such coils may require glycol-water solutions oper-
(20C) at any humidity from 30% to 60% RH ating at or below the freezing point of water to pro-
regardless of ambient conditions. Airflow should be vide the necessary air temperatures.
purposefully directed from clean (beginning at the
wound site) outward to less clean (low and at the Neuro-Surgery
room perimeter.) An anesthesia gas scavenging sys- Operating rooms in which neurological surgery
tem is necessary whenever anesthetic gases are used. is performed are usually as large as those used for
ROOM DESIGN 139

orthopedic or cardiovascular surgery. In fact, in 12.3.8 Emergency/Trauma Center


many institutions the large ORs are used inter-
changeably for all three types of surgery. Specifica- Emergency Rooms
tions for air handling for orthopedic, cardiovascular, As a point of uncontrolled entry into the hospi-
and neurological surgery ORs are virtually the same tal, the ER is a potential location for TB contact (in
Ceiling rails for mounting equipment such as micro- some geographic areas). The ER waiting area
scopes are not recommended; they increase the risk requires special consideration for directed airflow of
of particulate fallout onto the sterile field during relatively high volumes and low sidewall exhaust.
movement of the instrument. A preferable mounting Some ERs have special decontamination rooms
for an overhead microscope is a ceiling-mounted pod immediately off the entrance that require dedicated
located peripherally to the ceiling air diffuser with an exhaust.
articulated arm for positioning the microscope.
Trauma Rooms
Laser Surgery
The term Trauma Room may refer to rooms
Any procedure that creates aerosolized particles of two different uses. See Chapters 2 and 3 and Table
(such as smoke from laser surgery) should be 4-1. The HVAC systems will normally supply air to
directly exhausted as close to the source as possible. satisfy the cooling load or meet code requirements.
Local exhaust systems often consist of a flexible Air should be supplied overhead directly above the
hose and capture-bell mouth arrangement, some- patient bed, with the return grilles located at the perim-
times referred to as a snorkel exhaust. eter. Sometimes the return grilles are located at oppo-
site corners of the space at the floor. This design
Orthopedics will tend to create a sterile field around the patient
and staff.
Orthopedic surgery requires large rooms, with Shock or Crisis Rooms are frequently open to
HEPA-filtered airflow rates higher than internal heat other spaces. Space pressurization is not possible.
gains require. These spaces involve a wide range of Use a directional flow to control contaminants. Air
temperatures and large internal heat gains from peo- should be moving inward towards these rooms and
ple, lights, and equipment. Some surgeons require then totally exhausted.
laminar flow or clean-room-like systems (either
vertical or horizontal) with very high airflow rates. 12.3.9 Diagnostic Imaging/Radiology
The general operating room issues regarding
impingement of particles into the surgical site also Imaging Suite
apply to orthopedic rooms. Make sure the velocity of
The heat produced by the various equipment
the airstream is low at the surgical site.
components can require a supply airflow of substan-
tial air changes to maintain thermal conditions.
Solid Organ Transplant While typical overhead distribution can be utilized,
Transplant rooms require the highest ventilation special consideration should be given to patient loca-
concern. Transplant procedures involve open wounds tion so as to minimize drafts. If the lead shielding
for the longest time and are performed on patients extends across the ceiling, penetrations for the air
with artificially suppressed immune systems. These devices will also need to be protected.
rooms are often large and may even be paired: one
room for a donor and an adjacent room for the recip- MRI
ient. Rooms of this type have the largest internal heat Temperature and humidity requirements, cou-
gains due to lights, people, and especially equip- pled with the extensive electronics, usually require
ment. The number of people may reach as high as that a computer-room-style air-conditioning unit
12. In addition to anesthesia machines, this room serve an equipment room. Adding an auxiliary
may have heart pump machines and thermal blan- chilled water coil to a packaged DX unit is the best
kets. Room temperatures may need to be quickly method to build in required redundancy. The MRI
lowered to 65F (18.3C) (or lower) during the pro- and associated control console space could be served
cedure. Discharge air temperatures of 45F (7.2C) by the normal building HVAC systems. Some MRI
or less are required to accomplish this. Supplemental systems require chilled-water cooling for the magnet
cooling coils are typically used to lower discharge itself. All electrical and mechanical penetrations of
temperatures to these levels. the radio frequency (RF) shielding grid must be pro-
140 HVAC DESIGN MANUAL FOR HOSPITALS AND CLINICS

vided with dielectric connections for piping and be utilized, with the air supply located directly over
waveguide connections for ductwork. Air devices in the procedure table and with the exhaust inlets
the space itself must be nonferrous, usually alumi- located at the perimeter. Air can be exhausted to a
num. It is almost impossible to generalize the design general exhaust system.
of an MRI room and its supporting spaces into a typ-
ical air change rate or cfm per square foot (L/s per Interview Spaces
square meter) value. Direct airflow from behind the staff person
toward the patient, exhaust from behind the patient.
CT Scanning
Visitor Waiting Areas
As with an MRI suite, site-specific information
for the CT scan should be the basis for each design. Evaluate the facility for the potential for undiag-
Peak heat gain rate must be the basis of design. nosed TB cases appearing in the waiting area. This
space requires a large air change rate and directional
12.3.10 Other Areas flow away from the admitting/desk area.

Renal Dialysis Respiratory Therapy


Because of people and equipment concentra- This space may involve sputum collection and
tions, air supply to dialysis areas is usually greater pentamadine administration. Both of these may
than for a typical patient room. Location of the sup- require a patient hood system. If a hood is used, it
ply diffusers is important because the patients are may be recirculating with a HEPA filter or require
seated in reclining chairs throughout the treatment. venting to an exhaust. During design, ask the clinical
staff about HIV drug therapy.
Keep air velocities well below 50 fpm (0.25 m/s) at
the treatment chair. Central Sterile Supply
Environmental conditions for this space should
be identical to a patient room. Consider locating a This is a clean space. Ventilate and filter to pro-
radiant ceiling heater directly above the chair. Pro- vide air quality equal to the surgical suite. This
vide thermostats for individual patient control. Dial- space must be balanced positive to all surrounding
spaces. Provide exhausts at and around steam steril-
ysis patients are frequently cold because they are
izers, especially above the doors. There may be a gas
sedentary as well as anemic due to their condition.
sterilizer, which requires special venting either
The staff is typically too warm as they are continu-
directly from the sterilizer or from an ETO disposer
ally moving around the treatment area caring for that will burn up the gas and pass it along as hot
patients. Provide a separate zone of control for staff combustion products. Either way, a special exhaust
desk areas. system is usually required.
Cystoscopy Materials Management
Cystoscopy rooms may be located in several dif- This area usually will involve a space for haz-
ferent areas of a hospital. They may be in an inpa- ardous material storage, which may require special
tient department, in radiology, or in the surgical ventilation.
suite. These rooms should be ventilated first to
accommodate the cooling load of the equipment Loading Dock
(which may include fluoroscopic equipment). If The loading dock may contain a Red Bag stor-
located in the surgical suite, the room should be pro- age area. Consider this space a biohazard area and
vided with a balanced positive pressure. If located exhaust all air.
anywhere else, the room may be neutral or slightly
negative. Consider exhausting all air from this room Morgue and Autopsy
to control odors, regardless of where it is located.
Body holding spaces require negative pressure
and TB control protocol. There will be high internal
Endoscopy
heat gains due to refrigeration units. This space must
The endoscopy suite may require specialized be completely exhausted. Provide air velocity from
equipment for scope cleaning and storage. The room 50 to 75 fpm (0.25-0.38 m/s) at the table. Use low
must be balanced negative relative to all surrounding sidewall exhaust grills. Ventilation is well mixed to
spaces. It must be completely exhausted to the out- reduce general concentration levels in the room. Pro-
side. Conventional overhead air distribution should vide HEPA-filtered snorkel exhaust for bone dust.
ROOM DESIGN 141

Pharmacy Histology
A pharmacy may contain drug production Provide exhaust for slide trays, grossing station,
spaces. These will require a clean-room environment and chemical hoods. This space will contain a micro-
ranging from class 10,000 in the general space to scope. The grossing table will usually require a spe-
class 100 inside laminar flow hoods. A pharmacy cial exhaust connection. Countertops may also need
may also contain radiochemistry products. exhaust in the wall over the backsplash.

Film Processing Areas Cytology


Modern radiology departments are moving away
This area may contain a chemical hood.
from chemical process film developers. New film
processors are more like large photocopiers and
require no special ventilation other than removal of Hematology
the heat they generate. This area will contain blood refrigerators.
Film Library
Soiled Utility
Provide special humidifiers for film libraries.
The humidifier may be portable or duct-mounted Exhaust this area the same as a toilet. Transfer
such as in a surgical suite. air from a nearby clean utility room if possible.
CHAPTER 13
CLINICS AND OTHER
HEALTH CARE FACILITIES
13.1 OCCUPANCY CLASSIFICATIONS ing. They are traditionally open only during normal
The economic forces of managed care are shift- business hours, similar to retail stores. The services
ing the focus of the health care industry from central- are often based upon family practice or specialty
ized to decentralized facilities. Health care providers group practice. One characteristic of primary care is
are making a strategic change from the large central linkage to a secondary or tertiary care facility.
campus to a network of electronically intercon-
nected, special-purpose, freestanding facilities 13.1.2 Outpatient Surgical Facility or
located closer to patient populationsmore for dis- Ambulatory Surgery Center
ease prevention than for medical intervention. Hospi-
Some of the procedures common in busy hospi-
tals and physicians group practices have
tal-based outpatient and emergency departments may
experimented with the decentralized approach. Facil-
be performed in a same-day or ambulatory surgery
ities for sub-acute care, intermediate care, skilled
center. These include oral surgical procedures, den-
nursing, post-surgical recovery, and birthing have
tal, plastic and radiological procedures, and almost
had mixed results. Health care facilities that move
all endoscopies (Bregande 1974). Most of these pro-
out from the campus may not look like hospitals.
cedures are performed under either local or inhala-
Medical malls are providing outpatient clinics, diag-
tion anesthesia and in either a sterile or nonsterile
nostic/screening, and health-related retail services.
environment. The surgical environment in the free-
Workplace fitness centers and wellness centers are
standing surgical facility must be both sterile and
blending into the corporate and suburban landscape.
able to accommodate inhalation anesthetics, just as
In some cases, the largest distinction between
in the general hospital. These surgical facilities
hospital and clinic buildings is the life safety design.
include spaces with functions similar to the office-
Refer to Chapter 11 for a detailed analysis of life
type areas found in hospital surgical suites: a space
safety systems in these facilities. Most jurisdictions
for controlling access to sterile areas, a control desk,
want to separate life safety systems in clinics and
an admitting space, a consult room, and interview
hospitals. This usually means that ventilation sys-
rooms. Surgical preoperative screening, lab prep, and
tems must not cross occupancy separations. Clinic
radiology spaces are like hospital exam rooms.
and hospital spaces usually have different occupancy
Patient dressing areas should be treated like locker
schedules and so would benefit from separate HVAC
rooms. Post-anesthesia recovery is exactly like the
systems.
hospital space of the same name. This is an anesthe-
tizing location. Use ceiling-mounted Type A diffus-
13.1.1 Primary Care Outpatient Centers
ers and provide well-mixed air. Returns are ducted,
The primary care facility is often the first point low sidewall type.
of contact with patients. These buildings require the
least equipment and can be located within neighbor- Operating Rooms
hoods far from a hospital campus or as separate
buildings on the campus. They can be solitary, free- These rooms may not be as large, nor contain as
standing buildings or part of a medical office build- much equipment, as the hospital-based equivalent.

143
144 HVAC DESIGN MANUAL FOR HOSPITALS AND CLINICS

They are identical with respect to the ventilation erative skin-site prep, and attachment of monitor
requirements. leads occur in holding. This space is part general
Only those procedures in which there is the medical-surgical patient room and part hospital pre-
expectation of discharge from the facility within a operative room.
reasonably short period of time should be done. The
types of procedures that can be expected in this facil- 13.1.3 Freestanding Emergency Facility
ity fall into three classes (American College of Sur- (Urgent Care)
geons 1996):
The freestanding emergency center (FEC) offers
Class A: Provides for minor surgical procedures a variety of health care services to patients indepen-
performed under topical local or regional anes- dently of a hospital. Any facility with the term
thesia without preoperative sedation. Excluded Emergency in its name or advertising should be
are intravenous, spinal, and epidural routes; expected to have the capability of handling life- or
these methods are appropriate for Class B and C limb-threatening conditions (Wilk 1985). Such facil-
facilities. ities should be held to the same standard of construc-
Class B: Provides for minor or major surgical tion as the hospital emergency department. They
procedures performed in conjunction with oral, should include on-premises laboratories, radiology,
parenteral, or intravenous sedation or under oxygen and vacuum systems, trauma rooms, exam
analgesic or dissociative drugs. rooms, and treatment rooms identical to hospitals.
Class C: Provides for major surgical procedures All spaces for patient care should maintain equiva-
that require general or regional block anesthesia lent infection control and comfort control of temper-
and support of vital bodily functions. ature and humidity. These spaces are sometimes
called Urgent Care. The capabilities of Urgent Care
Class A facilities usually provide care for nor- may differ from Emergency Centers. The designer
mal healthy patients and patients who have mild sys- should be guided by the services provided, not the
temic disease that does not limit physical activity. name of the building. If the facility provides services
Class B and C facilities provide care for patients who equivalent to a hospital, hospital standards apply.
have severe systemic disease that limits normal
activity and is a constant threat to life. Moribund 13.1.4 Freestanding Birthing Center
patients, not expected to survive with or without the
operation, are not appropriate for this type facility. Freestanding birthing centers (FBC) are facili-
Operating rooms in these facilities will involve ties that provide labor, delivery, recovery, and possi-
the following support spaces: bly postpartum services. The FBC is an inpatient
facility. It is usually classified as an I occupancy
Substerile area: Exhaust this space as if it were a by most code officials and is treated as an inpatient
soiled utility from a grille directly above the hospital by local health departments. It usually con-
sterilizer door tains at least one delivery room for emergency cesar-
Scrub area: The scrub area is part of the sterile ean sections. This room is identical to a hospital
zone delivery room and provides complete inhalation
Clean workroom: This area needs positive pres- anesthetics.
sure relative to the corridor and especially the Support services, including food service, house-
soiled workroom keeping, sterile processing, pharmacy, and laundry
Soiled workroom: This area needs negative collection and storage, are also present in these cen-
pressure relative to all other spaces. ters.

These facilities require medical gas alarms, 13.1.5 Freestanding Outpatient Diagnostic
scavenging systems, positive pressure, sterilizer and/or Treatment Clinics
exhaust, specific minimum air flow rates, minimum
filtration and humidity control in exactly the same 13.1.5.1 Cancer Centers
way as the equivalent hospital space.
Patient holding is a space type unique to the Cancer centers are dominated by diagnostic
ambulatory center. The patient hold room is a non- and therapeutic radiology. Equipment heat gains
threatening environment used before surgery to stage and stringent environmental requirements dic-
patients without preoperative sedation. Most preop- tate highly sophisticated ventilation and process
erative functions such as vital signs, IV start, preop- cooling systems.
CLINICS AND OTHER HEALTH CARE FACILITIES 145

These buildings are designed to hospital 13.2.4 X-Ray


ventilation standards and contain most of the Any level of facility could have X-ray equip-
oncology services provided in inpatient facili- ment. Radiological equipment is getting smaller and
ties, such as chemotherapy, radiation treatments, more portable. The designer is cautioned to get as
CT and MRI, nuclear medicine, mammography, much information as possible about the equipment to
ultrasound, as well as exam rooms, pharmacy, determine heat gains and environmental require-
and laboratories. There are neither overnight ments.
stays nor bedrooms for patients. Some authorities having jurisdiction require
separating process cooling loads from the comfort
13.1.5.2 Dialysis Center
air-conditioning system. Radiology often uses the
Kidney dialysis centers are most notable for most process cooling in a clinic.
the unique water treatment plant used for the
dialysis process. These buildings have special 13.2.5 MRI
exhaust systems as well. All of the dialysis sta- MRI suites in outpatient settings are no different
tions should be predominantly exhausted. Air than those in hospitals. The equipment manufacturer
from the nursing station and other clean support determines the environmental requirements. These
space can be recirculated, but most of the treat- temperature and humidity requirements, coupled
ment space should be exhausted. These centers with extensive electronics, usually require this space
may also have infectious isolation dialysis to be served with a computer-room-style air-condi-
rooms that require separate exhaust systems. tioning unit. Adding an auxiliary chilled water coil to
Opportunities exist in these buildings for a packaged DX unit is the best way to build in
heat recovery from the high quantities of required redundancy. Some MRI systems require a
exhaust air. Most of the spaces require ducted chilled-water cooling source for the magnet itself.
returns for controlling odors and for effective All electrical and mechanical penetrations of the
heat recovery. shielding grid must have a dielectric connection for
piping and flexible fabric connections for ductwork.
13.2 CLINIC SPACES Air devices in the space itself must be nonmagnetic,
usually stainless steel or aluminum. It is almost
13.2.1 Exam Rooms impossible to generalize the design of an MRI room
These spaces are often used in outpatient set- and its supporting spaces into typical values for air
tings because they frequently take the place of an change rate or supply airflow per unit floor area.
inpatient bedroom. Preparation and postprocedure
recovery usually take place in rooms like these, 13.2.6 Ophthalmology and Optometry
which may have names such as Patient Hold, Patient These departments have no unusual mechanical
Cubicle, Stretcher, or Prep Registration or may be requirements beyond good filtration and low-veloc-
called Exam Rooms by some medical planners. They ity air distribution in the exam room.
all involve types of medical services that could
include local anesthesia. Exam rooms should have 13.2.7 Endoscopy
ducted returns and ventilation based on hospital stan- An endoscopy suite may require specialized
dards. equipment for scope cleaning and storage. It must
have negative air pressure relative to all surrounding
13.2.2 Laboratory
spaces and is completely exhausted to the outside.
Laboratories in clinics follow the same rules as The air supply to an Endoscopy Room would be in
for ventilation as in hospitals. the range of 610 air changes per hour. Conventional
overhead air distribution should be used. The air sup-
13.2.3 Pharmacy ply should be located directly over the procedure
The pharmacy in an outpatient setting is likely table, and the exhaust inlets should be at the perime-
to be similar to a retail pharmacy and can be venti- ter. Exhausting the air to a general exhaust system is
lated as retail. If any specialty preparations are made, suggested.
such as for chemotherapy or nuclear medicine, hos-
pital pharmacy design rules should apply. Fume 13.2.8 Bronchoscopy
hoods require attention both to exhaust and room dif- Treat a Bronchoscopy Exam Room as if it were
fusion, regardless of their location. an infectious isolation room. This may require pres-
146 HVAC DESIGN MANUAL FOR HOSPITALS AND CLINICS

sure controls and alarms. Make the room pressure the same mechanical design parameters. The design
negative, and exhaust the room completely. should comply with state and local fire and life
safety codes.
13.2.9 Cardiac Catheterization
These facilities are generally Class A type, but
and Angiography
some facilities may perform Class B procedures if an
Heart catheterization rooms are very equipment- anesthesiologist is on staff. Clinics that have only
intensive. The equipment supplier determines the general treatment rooms are not considered ambula-
environmental requirements. Treatment rooms tory surgery.
should have low sidewall returns and low-velocity,
non-aspirating ceiling supply diffusers over the
13.2.11 Surgicenter
tables. The equipment room is best served by a pro-
cess air cooler or modular cooler. The control and The surgicenter is a department somewhat
treatment rooms require close control of temperature unique to the outpatient setting. It provides the func-
and humidity and limits on the rate of change in tions of preoperative prep, postoperative recovery,
these parameters over time. and patient holding (in place of a regular patient
room). Patients who need an Intensive Care Unit are
13.2.10 Ambulatory Surgery generally not ambulatory patients. Preoperative,
Surgery is an invasive procedure, regardless of recovery, and holding should be designed with the
the general health of the patient. The surgery suite same parameters as their inpatient facility counter-
should be treated just as if it were in a hospital using parts.
CHAPTER 14
OPERATION AND MAINTENANCE
14.1 INTRODUCTION A good maintenance and operating program
must be implemented to ensure that a health care
Harteen et al. (2000) state that constructing a facilitys buildings and systems operate reliably to
building represents only 11% of total building costs provide the core mission, which is patient care.
over 40 years. Operations, on the other hand, make
up 50%. Inappropriate facility operation and mainte- 14.2 MAINTENANCE
nance can mean ignoring the largest single compo-
nent of building costs. It means wasting limited Everything that has moving parts breaks or fails
eventually. A hospital or clinic, like any other facil-
budgets on equipment replacement and higher
ity, requires maintenance. At one time, maintenance
energy costs. Worse yet, it can mean random disrup-
was considered a largely uncontrollable component
tions (even patient care disruptions) due to mechani-
of hospital operating cost. In the present climate of
cal system and equipment failure, which is not pressure on operating costs, maintenance practices
acceptable in hospitals or clinics. must be carefully reviewed. Blind acceptance of
The operating and maintenance functions in O&M schedules, such as chiller teardowns or pre-
hospitals and clinics can be provided in different ventive maintenance based simply on time intervals,
ways (Ferguson 2000). Many facilities have in-house can be very expensive. Similarly, maintenance per-
maintenance personnel who provide minimum to formed only when equipment fails (reactive mainte-
extensive maintenance, often on very sophisticated nance) can cause unacceptable loss of function.
and technically complex systems. Some facilities The four common approaches to maintenance
perform the minimum (usually the life-safety related reactive, preventive, predictive, and proactivehave
functions) in-house and outsource all other func- evolved over the years as progress in diagnostic sys-
tions. Another model is a completely outsourced tems has occurred. An Industry Week article (1994)
maintenance department. Some departments are listed the following maintenance costs per horse-
unionized and have specialized work practices, and power:
some are not unionized and are more functionally
diverse. This chapter is not intended to discuss the $18 for a reactive approach
merits of various maintenance delivery systems. The $13 for a preventive approach
intent is to show the importance of the maintenance $8 for a predictive approach.
function in health care facilities.
More detailed information on maintenance
For tasks that in-house staff cannot handle, con- approaches is provided below (adapted from Harteen
sider contractors or consultants. Ensure that the con- et al. 2000).
tractor uses the best maintenance practices and has
specific training. To save time and avoid communi- 14.2.1 Reactive Maintenance
cation problems, make sure the contractor can pro-
vide both diagnostic and corrective services. Finally, Reactive maintenance is run-to-fail mainte-
to ensure that the roots of problems are addressed, nance, replacing equipment only when it breaks.
find a contractor who takes a holistic view of the Reactive maintenance is perfectly acceptable for
facility. non-critical equipment if the cost to replace or repair

147
148 HVAC DESIGN MANUAL FOR HOSPITALS AND CLINICS

the equipment is less than the cost of monitoring it Does Not Prevent All Failures
and preventing problems. This may be the case, for Preventive maintenance fails to catch some
example, with a small motor that costs only $400 to problems. If leaking oil is weakening a belt, for
replace. It may also be the right choice for inexpen- example, a new belt will immediately begin to break
sive items such as lightbulbs. The disadvantages are down. Similarly, if imbalance or misalignment is
as follows: causing bearing wear, bearings could fail before the
next scheduled maintenance.
Costly Downtime
Machinery often fails with little or no warning, Can Introduce Problems
so equipment is out of service until replacement Preventive maintenance can actually cause new
parts arrive. If the equipment is critical to the area, problems. Every disassembly creates the potential
patient care delivery is disrupted. If parts are hard to for mistakes during reassembly or the early failure of
find, a long out-of-service period can result. Even a new component. Both events can lead to failure
inexpensive equipment can cause downtime and a sooner than if the machine were allowed to run with
significant negative business impact. its original components.

Higher Overall Maintenance Costs Requires Large Inventories


Preventive maintenance requires a large parts
Unexpected failures may result in costly over-
inventory to address all of the problems that could
time for emergency repairs. Parts costs increase
arise in a piece of equipment or could be required
because delivery may need to be expedited and there
during a scheduled teardown.
may be insufficient time for competitive bidding. In
addition, failures are more likely to be severe when
14.2.3 Predictive Maintenance
failure is unexpected, possibly damaging or destroy-
ing other parts. Just as a failed timing belt on a car Predictive maintenance checks the condition of
can cause valve damage, a failed bearing can damage equipment as it operates. Equipment condition,
shafts, couplings, impellers, fan cages and blades, rather than time intervals, determines the need for
gearing, and housings. service. If an analysis shows problems, facility man-
agers can schedule repairs before total failure occurs.
Safety Hazards Identifying problems early helps avoid unscheduled
The failure of equipment, especially vane-axial downtime and the costs of secondary damage.
fans, can injure nearby persons. For example, parts Predictive maintenance squeezes the greatest
of fan blades can cut through ductwork. possible life out of partswithout letting them fail.
By doing so, it reduces maintenance costs and down-
time. For a car, knowing that a timing belt would not
14.2.2 Preventive Maintenance
fail until 110,000 miles would allow the owner to
Preventive maintenance involves scheduling forego the scheduled replacement at 60,000 miles. In
maintenance or tasks at specific intervals. For exam- a facility, predictive maintenance allows managers to
ple, it means changing the oil in a car every 3000 eliminate scheduled overhauls when predictive tech-
miles or changing the timing belt every 60,000 miles. niques show that equipment is in good condition.
In an HVAC system, it includes such tasks as chang- The appeal of predictive maintenance is three-
ing the oil and filter and cleaning equipment. fold. First, it uncovers problems before they cause
By offering a first line of defense, preventive failures. Second, it extends service intervals for
maintenance avoids many of the problems of a reac- equipment in good condition. Finally, it determines
the condition of equipment as it operateswithout
tive approach. Unfortunately, preventive mainte-
taking the machine apart. Predictive maintenance
nance has these disadvantages:
techniques reduce expenses by revealing the optimal
time for maintenance. The following predictive tech-
Is Often Wasteful niques are used and will be described in more detail
Preventive maintenance replaces equipment that in Section 14.3.
may still have a long useful life ahead. A cars timing
belt may last 100,000 miles, so replacing it at 60,000 Vibrational analysis
to avoid failure may be wasteful. Similarly, a chiller Infrared thermographic inspection
teardown that is unnecessarily scheduled may waste Motor current analysis
approximately $15,000 or more and may end up Oil analysis
replacing perfectly good bearings. Refrigerant analysis
OPERATION AND MAINTENANCE 149

Figure 14-1 Example vibrational analysis of a chiller.

14.2.4 Proactive Maintenance tenance program because it detects a wide range of


equipment problems before they can cause failure.
Proactive maintenance relies on predictive
methods (such as vibrational analysis) to point out Misalignment and imbalance (which account for
parts that are deteriorating. Rather than being satis- 6080% of fan and pump problems)
fied with knowing when parts will fail, however, pro- Resonance and bearing defects
active maintenance eliminates the sources of failure
Gear and belt problems
altogether. For example, rather than simply replacing
Sheave and impeller problems
worn bearings, proactive maintenance seeks to elimi-
Looseness and bent shafts
nate the causes of wear. By getting at the root causes
Flow-related problems (cavitation and recircula-
of fan and pump failure (imbalance and misalign-
tion)
ment, for example), the proactive approach reduces
downtime costs, eliminates recurring problems, Electrical problems (rotor bar problems)
extends machine life, reduces energy costs, and iden-
In environments that are critical to the facility
tifies ineffective operational approaches.
mission, the greatest benefit of vibrational analysis is
that it forecasts the most appropriate time to correct
14.2.5 Computerized Maintenance Systems
machine problems, which eliminates unscheduled
Computers can be useful in implementing any downtime.
of the above maintenance approaches. Most mod-
ern hospitals have some kind of computerized work Performing Vibrational Analysis
order system that is useful in implementing required Vibrational analysis involves attaching small
maintenance on an HVAC system, controlling an sensors at predetermined locations on selected
inventory of spare parts, efficiently allocating avail- equipment. A technician connects these sensors to an
able manpower to required tasks, etc. There are sev- accelerometer. The accelerometer collects data and
eral excellent computerized maintenance converts mechanical motion (vibration) into electri-
management software systems (CMMS) and com- cal signals. Plotting these signals produces a graph
puter-aided facility management systems (CAFM) called a vibrational signature that tells technicians
available. which components are vibrating and how much.
Figure 14-1 shows a typical vibrational signa-
14.3 MODERN MAINTENANCE TOOLS ture for a chiller. Amplitude and frequency are the
two characteristics of vibration used to diagnose
The information provided here is adapted from
equipment problems. Amplitude is the amount of
Harteen et al. (2000).
vibration. It indicates the severity of a problem. The
greater the amplitude, the greater the problem.
14.3.1 Vibrational Analysis
Amplitude is measured in inches per second (ips),
Vibrational analysis is one of the most effective mils of displacement, or gs of acceleration.
techniques for analyzing the condition of rotating Frequency identifies the source of a vibration.
equipment. It is the cornerstone of a predictive main- For example, a motor shaft may vibrate at 50 Hz,
150 HVAC DESIGN MANUAL FOR HOSPITALS AND CLINICS

Figure 14-2 Vibrational trending of a chiller.

while a compressor may vibrate at 120 Hz. In addi- caused by all of the equipments problems. Measur-
tion, different mechanical problems cause vibrations ing the overall vibration of a machine quickly reveals
at different frequencies. whether it is in good condition; it does not tell you,
Frequency is measured in revolutions per minute however, what the problem is. High overall vibration
(rpm), cycles per minute (cpm), and cycles per sec- points to a need to analyze the vibrational signature
ond (cps or hertz [Hz]). Machinery rpm is a measure further.
of frequency. Under imbalance, one cycle occurs
during each revolution. Therefore, the frequency for 14.3.2 Infrared Thermographic Inspection
imbalance is 1 rpm. Different machines run at dif-
Thermography involves analyzing heat transfer
ferent rpms. A motor that operates at 1800 rpm has a
by electromagnetic radiation. All animate and inani-
frequency of imbalance of 1 rpm or 1800 cpm.
mate objects (for example, electrical control panels,
Trending Vibrational Levels motors, and boiler doors) emit electromagnetic radi-
The big picture offered by trendingmeasuring ation in the infrared spectrum. Only an infrared cam-
vibrational levels over timehelps determine more era can see such radiation. Thermographic inspection
precisely when a machine will fail. A single vibra- is an accurate, quick, and effective technique for
tional measurement gives a snapshot of a machines avoiding equipment breakdowns by gathering and
condition, but trending gives a full view of the equip- presenting thermal performance information about a
ments performance. system. It does not, however, ensure proper equip-
As shown in Figure 14-2, a machines vibration ment operation, however; other tests and proper
in August 1997 was 0.13 ips, which is within specifi- maintenance are necessary to ensure reliable perfor-
cations. Given that measurement alone, the machine mance.
has no problem. The trend chart, however, shows that An infrared scanner looks like a video camera. It
vibrational levels have been rising at an increasing records site-collected information on diskettes or on
rate, a sign of upcoming problems. standard VHS videotapes for later review and inves-
tigation. A display screen helps to identify potential
Vibrational Trending
problem areas immediately.
Trending forecasts the future condition of equip-
ment and provides time to prepare for necessary Conducting a Thermographic Inspection
maintenance. Rather than make emergency fixes,
managers can schedule repairs for planned outages In a thermographic inspection, plant equipment
on off-peak hours. Every trend measurement gath- is systematically scanned for temperature profiles in
ered reduces the risk of unscheduled downtime. The order to find and correct developing problems before
importance of the space being served by equipment equipment failure occurs. Analysis can isolate a
dictates the frequency of trend measurements. source of overheating or other problem areas. Tem-
perature anomalies in equipmentboth hot spots
Overall Vibration and cold spotscan be investigated. The relative
Overall vibration (measured in ips) is the total severity of a hot spot can be determined, and its root
vibration within a piece of equipment, the vibration cause can be isolated and identified.
OPERATION AND MAINTENANCE 151

Other Uses of Thermographic Inspection characteristics, determine whether the time interval
Electrical inspections are one of many applica- between oil changes can be extended.
tions of thermographic technology. Think of an elec- Common methods for determining oil quality
trical system as a chain. Stress causes the chain to include spectrochemical analysis, physical tests, and
break at its weakest link. In an electrical system, hot ferrography. Spectrochemical analysis identifies
spots caused by a small temperature rise weaken the wear particles (metals such as zinc, aluminum, cop-
chain. When a component deteriorates, its tempera- per, nickel, and chromium) in the oil. Friction
ture rises, and eventually it burns up or short circuits. between bearings and gears causes these metals to
wear from the surfaces and circulate in the lubricant.
14.3.3 Motor Current Analysis A high level of metals indicates that components are
wearing.
Motor current analysis is used to diagnose rotor
problems, including: Physical tests show how well a lubricant is
doing its job. Contaminated lubricants can be
Broken or cracked rotor bars or shorting rings changed before they accelerate component wear. The
Bad high-resistance joints between rotor bars most common physical tests include the following.
and shorting rings
Viscosity
Shorted rotor lamination
Viscosity is a lubricants internal resistance to
Loose or open rotor bars not making good con-
flow. It is the single most important physical prop-
tact with end rings.
erty of oil. Changes in viscosity indicate lubricant
breakdown, contamination, or improper servicing.
Current analysis eliminates the need for Variac
Each of these occurrences leads to premature com-
or Growler tests that diagnose the same problems but
ponent failure.
require turning off and disassembling the equipment.
Motor current analysis can generally be performed Water in Oil
while the equipment is running. One exception is
Water promotes oxidation and rust in compo-
high-voltage machines; these should be shut down to
nents. It also prevents a lubricant from doing its job.
avoid the risk of electrocution.
Total Acid Number
How Is a Motor Current
Total acid number (TAN) is the level of acidic
Analysis Performed?
material in a lubricant. It indicates acidic contamina-
A motor current analysis is performed with a
tion of the oil or increased oil oxidation. Both
multimeter and a motor current clamp that measures
increase the potential for corrosive wear.
the current drawn by the motor. Motor current can be
measured on either the main phase circuit or on the Ferrography is a useful technique for analyzing
secondary control circuit. The secondary circuit is centrifugal equipment with transmissions and for
safer; always use this for equipment at more than screw compressors. It determines the condition of a
600 volts. component by directly examining wear metal parti-
When performing a motor current analysis, an cles. Wear metals and contaminant particles are mag-
analyst measures the three-phase power line leads netically separated from the oil and arranged
one at a time. Then, the analyst compares the cur- according to size and composition. Direct reading
rents in each phase. The current in each phase should (DR) ferrography monitors and measures trends in
be within approximately 3% of the others. Variations the concentration of ferrous wear particles. DR fer-
higher than 3% point to stator problems such as rography trends indicate abnormal or critical wear
those listed earlier. that can be used to trigger analytical ferrography.
Direct reading ferrography is usually unnecessary if
14.3.4 Oil Analysis vibrational analysis is being used because vibrational
Oil analysis is one of the oldest, most common, analysis assesses the condition of gears more accu-
and useful predictive technologies. It helps to pre- rately.
vent failure and unscheduled downtime by display- Regular sampling is important to successful oil
ing the wear metal count and types of contaminants analysis. Sampling determines the suitability of the
in oil. The wear metal count indicates whether equip- oil for continued service. It can also provide crucial
ment is experiencing unusual wear. The types of con- information about the presence of wear metals,
taminants in the oil, as well as the oils physical acids, moisture, and other contaminants.
152 HVAC DESIGN MANUAL FOR HOSPITALS AND CLINICS

14.3.5 Refrigerant Analysis machine. This machine is the driver unit. The
Refrigerant analysis checks physical properties, machine not adjusted (because of size or other physi-
vapor-phase contaminants, and liquid-phase contam- cal constraints) is usually the stationary machine or
inants to determine the condition of a refrigerant. driven unit.
Moisture and acidity are the two most important lev- Newer alignment methods and tools make align-
els to monitor. High moisture levels lead to increases ment relatively fast and easy. Alignment methods
in acid levels. This in turn causes motor insulation to include:
deteriorate and tube metal to erode. Once acid is in Reverse indicator
the system, it migrates into the oil. In the oil, the acid Laser
accelerates the wear of rotating components such as Optical
bearings and gears. This leads to premature compo- Straightedge.
nent failures. Any alignment, even a straightedge alignment,
is better than no alignment at all.
A refrigerant analysis can also verify that the
refrigerant purchased meets acceptable standards. 14.3.7 Dynamic Balancing
ARI Standard 700-99 (ARI 1999b) is typically used
to assess refrigerant condition. An analysis should be Imbalance occurs when the center of mass of a
conducted after repairing leaks, adding refrigerant, rotating system does not coincide with the center of
or performing major repairs that have a high poten- rotation. Excessive mass on one side of the rotor
tial for moisture contamination. results in an imbalance. The centrifugal force that
The accuracy of a refrigerant test depends upon acts on the heavy side exceeds the centrifugal force
the sampling technique. It is important to not con- exerted by the unequal forces. The magnitude of the
taminate a sample with outside moisture because rotating-speed vibration due to imbalance is directly
moisture level is an important indicator of condition. proportional to the amount of imbalance. Imbalance
can be caused by a number of things, including
14.3.6 Shaft Alignment incorrect assembly, material buildup, or rotor sag.
An unbalanced rotor causes elevated vibrational
Improper alignment may be the most common levels and increased stress in the rotating element.
cause of high vibration and premature failure in Elevated vibrational levels in the rotor of an assem-
equipment. High vibrational levels lead to excessive bly affect the entire machine and cause excessive
wear on bearings, bushings, couplings, shaft seals, wear on the supporting structure, bearings, bushings,
and gears. Proper alignment can slow the deteriora- shafts, and gears.
tion of equipment. Alignment means adjusting a An unbalanced condition can be in a single
piece of equipment so that its shaft is in line with the plane (static imbalance) or multiple planes (coupled
machine to which it is coupled. When the driver and imbalance). The combination is called dynamic
driven machines are connected through a common imbalance and results in a vector that rotates with the
coupling and rotate together at operating equilib- shaft and produces a once per revolution vibrational
rium, the unit rotates along a common axis of rota- signature. Dynamically balancing a unit:
tion as one continuous unit without excessive
vibration. Extends the life of the bearings, bushings,
The three most common types of alignment are: shafts, and gears
Reduces vibration to an acceptable level that
Parallel, in which the coupling hub faces are will not accelerate equipment deterioration
parallel, but the two shaft centerlines are offset; Reduces stress that causes equipment fatigue
essentially there is a distance between the two Minimizes audible noise, operator fatigue, and
shaft centerlines. dissatisfaction
Angular, in which the coupling hub faces are not Reduces energy losses.
parallel and the shaft centerlines are not concen-
tric. Identifying Imbalance
Perfect, in which the coupling hub faces are par- Imbalance needs to be distinguished from other
allel and shaft centerlines are concentric. sources of vibration before beginning any balancing
procedure. A vibrational peak at or near the rotating
Correcting Shaft Misalignment speed of the rotor can have several causes, such as
When alignment and shimming procedures are misalignment, a bent or cracked shaft, eccentricity,
performed, the adjustments are made only to one open rotor bars, or imbalance. Verify the presence of
OPERATION AND MAINTENANCE 153

imbalance before proceeding with a balancing proce- 14.5 COMPLYING WITH JOINT
dure. Analytical techniquessuch as spectrum COMMISSION REQUIREMENTS
waveform or phase analysiscan isolate imbalance
The maintenance department works closely with
as the cause of vibration. Imbalance is characterized
other departments and a facilitys Safety Committee
by:
to obtain Joint Commission on Accreditation of
Dominant vibrational magnitude at the Healthcare Organizations (JCAHO) compliance. The
rotating speed of the rotor following are key areas of concern relative to such
Highest vibration in the radial and vertical compliance.
planes and lower vibrational levels in the
axial plane 14.5.1 Statement of Conditions (SOC)
An amplitude and phase angle of vibration The JCAHO requires that all health care facili-
that is repeatable and steady ties keep up-to-date information on the condition of
Radial versus vertical-phase-angle vibra- the facility. This document is called the Statement of
tional measurements Conditions (SOC). It lists all corrective measures in
a Plan for Correction (PFC). The SOC is a living
14.4 OPERATION document. It should be continuously updated as a
Ferguson (2000) describes the following unique facility is changed, renovated, and improved. The
operational characteristics for systems and equip- maintenance department plays a central role in pre-
ment in hospitals and clinics. paring the SOC document and carrying out the PFC.

14.4.1 Continuity of Services 14.5.2 Hospital Disaster Preparedness

Hospitals never close. They operate 24 hours per State licensure usually requires a health care
day, 7 days per week. Facilities must be designed to facility to have a disaster plan in addition to a
allow for maintenance shutdowns and adding new JCAHO mandate. The maintenance department
features to systems. Two words can easily sum up an plays an important role in formulating and imple-
appropriate design philosophy: isolation and redun- menting such a plan. This is another example of the
dancy. close collaboration required between the mainte-
nance department and other departments. A health
The procedures that are performed in outpatient
care facilitys Disaster Planning Committee usually
facilities and clinics are becoming increasingly more
includes representatives from the following:
complex. Although classified as a business occu-
pancy rather than a hospital, a facility manager
Medical staff (ER physician or trauma surgeon)
should look carefully at the requirements for each
Administration (includes risk manager)
function within this type of building. Many house
hospital-grade systems simply operate less than 24 OR nursing staff manager
hours a day. Emergency department
Security/Communications
14.4.2 Need for Collaboration Public relations
Medical records and Admissions
Close collaboration and teamwork are required
between the maintenance department and other enti- Laboratory
ties of the hospital. These entities include the infec- Radiology
tion control department, respiratory therapy, Respiratory therapy.
biomedical engineering, police and security, and/or
environmental services. 14.5.3 Interim Life Safety
For example, the maintenance department col- Creating a safe building environment is the goal
laborates with others to ensure that building systems of life safety codes and standards that cover egress,
operate properly to reduce infection. Improper use of stairs, fire detection devices, and general occupancy.
a negative pressure isolation room may allow infec- As long as the building design remains unchanged,
tious agents from the room to enter a corridor and the design integrity of life safety systems remains.
infect hospital workers, other patients, or visitors. However, health care facilities are always changing.
Improper hot water temperature may allow microbial As buildings undergo renovation and construction
growth. Improper filter application or maintenance (both planned and unplanned), the integrity of life
may create infection control problems. safety systems may diminish. This potential for a
154 HVAC DESIGN MANUAL FOR HOSPITALS AND CLINICS

decrease in life safety results in the creation of dramatically, a process called amplification. Con-
interim life safety measures. ditions favorable for amplification include:
Interim life safety is generally overlooked dur-
ing the design of renovations and is often not dealt Water temperature of 77-108F (25-42C)
with until construction actually begins. It is never too Stagnation
late to make necessary adjustments to the design and Scale and sediment
construction process. Otherwise, patients and visi- Biofilms
tors may be exposed to grave dangers. The mainte- Presence of amoebae
nance department may be called upon to support Certain materialsnatural rubber, wood, some
additional fire and evacuation drills and exercise plastics.
control over cutting, soldering, and the use of flame
in the construction process. Some maintenance Transmission to humans occurs when water that
departments issue an internal flame permit to outside contains the organism is aerosolized in respirable
contractors and secure fire alarm zones as required to droplets (1-5 microns) and inhaled by a susceptible
allow construction in existing buildings. After con- host. Infections initially occur in the upper or lower
struction is complete, the fire alarm system is respiratory tract. The risk is greater for older people,
returned to its normal operating condition. those who smoke, those who have chronic lung dis-
ease, and those who are immunosuppressed. Promis-
14.5.4 Utilities Management ing technologies for Legionella abatement or control
include treatment with chlorine dioxide, chloram-
Utilities management has become a complex
ines, or silver-copper ion injection in the domestic
function in todays health care facility. Quality
water supply.
improvements, along with trending occurrences in
It has long been known that cooling towers are a
utility systems and equipment, will help the facility
potential cause of Legionellosis. The key recommen-
manager reduce maintenance service calls due to
dations for minimizing the risk from cooling towers
recurring problems. The facilities manager of record
involve clean surfaces and a biocide program. Pro-
needs to be aware of confined-space issues as they
fessional help with chemical treatment is recom-
pertain to maintainability, safety, and code require-
mended. Mechanical filtration should be considered
ments (i.e., OSHA).
to minimize fouling. Drift eliminators should be reg-
ularly inspected, cleaned, and repaired as needed. It
14.5.5 Self-Assessment and Resolution of
is sound practice to alternate biocides used for cool-
Indoor Air Quality Problems
ing water treatment to avoid developing resistant
Indoor air quality (IAQ) problems originate strains of microbes. Weekly changes in dose and fre-
from many different sources within facilities. These quency are recommended.
sources may involve building systems, processes and Shutting down and starting a cooling tower sys-
procedures, management practices, employees, and tem requires specific attention. When a system is
outside influences. Maintenance departments usually shut down for more than three days, draining the
get the first call regarding these problems, and they entire system to waste is recommended. When not
need to follow a systematic investigative process. practical to do so, stagnant water must be pretreated
with a biocide regimen before tower start-up. Circu-
14.5.6 Prevention of Legionnaires Disease lation of water for up to six hours is suggested for
both drained and undrained system shutdowns after
Health care facilities can be prone to Legionella adding biocide and before tower fans are operated.
outbreaks. Maintenance departments are the first line
of defense against this problem. Butkus et al. (1999), 14.5.7 Pressure Monitoring Systems for
ASHE (1993, 1994), and ASHRAE (2000b) provide Isolation Rooms
an excellent discussion of this problem and potential
solutions. Legionellae are bacteria. The name of the NIOSH recommends a smoke-tube verification
disease is derived from a well-known 1976 outbreak of directional airflow as a qualitative calibration
at an American Legion convention in Philadelphia check of differential pressure. If a pressure monitor-
attributed to a cooling tower. Legionellae occur in ing system is installed, it is recommended that quan-
natural water sources and municipal water systems titative calibration be performed at some interval to
in low or undetectable concentrations. Under certain ensure that the system is accurately monitoring pres-
conditions, however, the concentration may increase sure.
OPERATION AND MAINTENANCE 155

14.5.8 First Response 14.6.1 Construction Plan Review


Coordination in preparing for unexpected shut- Maintenance departments are usually asked to
downs and system failures is essential. Careful plan- (and should) become involved in reviewing new con-
ning for those who will be available and addressing struction and renovation projects. The following
how they will communicate with health care givers is checklist can be helpful during this process.
essential. The management decision chain must be
General Mechanical and
clearly defined, and contingencies must be built in
Electrical Equipment Rooms
for personnel absences.
Ideally, mechanical rooms for major equipment
14.6 CONSTRUCTION such as air-handling equipment and chillers should
be directly accessible from the outside of the build-
Ferguson (2000) provides an excellent review of ing for ease of replacement. This feature may not,
construction issues. Many maintenance departments however, be practical. At a minimum, mechanical
provide in-house construction services for renova- room locations should minimize the intrusion of
tion or new construction projects. If well managed, maintenance personnel into the medical floors. If
they can usually provide construction at a lower cost possible, direct vehicle transport for maintenance
than outside contractors. They also have an advan- items and equipment would be desirable. Direct ele-
tage in conducting shutdowns and if needed can vator access to mechanical spaces in upper floors is
move from location to location in a short time. Con- most helpful.
struction and maintenance functions must be clearly
Roof-Mounted Equipment
defined and separated. There is always a danger that
too much construction can divert departmental Roof-mounted equipment in general should be
resources from maintenance functions. avoided for critical applications because access is
usually difficult and working conditions are not safe
Infection risk assessment by a health care facil-
for maintenance personnel. However, roof-mounted
itys infection control group should be an integral
HVAC equipment is a very cost- effective option for
part of the construction process. Always include the clinics. Also, exhaust fans, cooling towers, and other
infection control group in plan review meetings and heat rejection equipment must often be on the roof.
construction prebid meetings. See Appendix A for Whenever roof-mounted equipment is used, provid-
additional information. ing pavers or other personnel access pathways that
Assigning an owners representative to all con- will not damage the roof is highly recommended. A
struction projects is highly recommended. In most fixed ladder and/or catwalk should be considered for
instances, this is the key individual to determine any equipment that requires maintenance access
whether the owners money is well spent and how (including valves) and is not readily accessible from
well the design/construction team is performing. a 6-ft-high portable ladder. Hose bibbs and electrical
service receptacles should be included near the
This individual must know construction by the vari-
equipment.
ous trades, must understand the contract being
administered, and be flexible enough to work out
Mechanical Room Layout
inevitable coordination issues between the contractor
and owner. Shutdowns, night work, and windows of Mechanical room layout should include suffi-
opportunity for noisy activities (such as cutting and cient space for access to equipment for operation,
hammering) are coordinated through this individual, maintenance, and replacement, including permanent
catwalks or ladders for access to equipment that can-
who may also be responsible for welding and other
not be reached from the floor. Verify that practical
hot-work permits.
means are provided for removing/replacing the larg-
A small team from the maintenance department est and/or heaviest equipment item(s) located in the
working with the owners representative can identify facility and that pull space is provided for all coils,
performance and maintenance concerns before ceil- heat exchangers, chillers, boiler tubes, and filters.
ings and walls are closed in. An on-site inspection by
the maintenance group is highly recommended. This Chillers and Boilers
inspection should be controlled and scheduled by the Provisions should be made for moving these
owners representative or the maintenance office. units in and out of the building. For large chillers,
156 HVAC DESIGN MANUAL FOR HOSPITALS AND CLINICS

consider installing a beam attached to the structure to also wastes water, so a treatment program for boilers
move or replace large compressors or motors. is needed as well.
Test coupons placed at strategic locations should
General Personnel Access be retrieved and checked on a routine basis. Chemi-
Safe and practical means of personnel access cal shot feeders should be located in an area that is
should be provided. A minimum of 2 ft (0.6 m) of easily accessed and can be washed down. Air-han-
clearance is generally required at all service points to dling unit drain pans should be treated regularly with
mechanical equipment to allow personnel access and biocide tablets. The product drums typically weight
working space. Greater space may be required for 60 lb (28 kilograms), so a means for moving and lift-
particular equipment and maintenance applications. ing them is needed.
During plan review, serviceability requirements for
equipment for mechanical equipment rooms, corri- Cooling Coils
dors, occupied spaces, behind walls, above ceiling, Coil thickness should not exceed six rows to
and/or buried in the ground should be verified. facilitate cleaning. Coils finer than 14 fins per inch
are increasingly more difficult to clean with indus-
Separate Energy Plants trial coil cleaning compounds. These cleaners are
When chilled water, heating water, or steam typically applied on the upstream side of the coil and
generators are located in a separate energy plant allowed to penetrate into the rows of the coil. Once
exterior to the primary facility, installing the con- the cleaner has done its job by softening scale and
necting utility lines in a tunnel or other accessible removing biological growth, a high-pressure washer
enclosure to provide maintenance and inspection is used for final cleanup. When more than six rows
access and protection from the elements is highly are required to effect dehumidification, the coil
desirable. Accessibility to the entire utility main runs could be separated into two 4- or 6-row units with
is desirable to facilitate inspection and repairs of access provided to both upstream and downstream
insulation, fittings, thermal expansion compensation, coil faces. Typically, a 24-in. (610 mm) space
air vents, etc., as well as to facilitate future replace- between coils is adequate.
ment or expansion. Safe and convenient accessibility
is essential for those elements that require periodic Stainless Steel Drain Pans
inspection or service, including isolation valves, con- Stainless steel drain pans should be provided to
densate drainage traps (both manual and automatic), optimize cleaning and reduce microbial growth. To
sump pumps, and ventilation fans. ensure pan drainage, facilities managers should
review the dimensions of the traps to verify that they
Cooling Towers compensate for the effects of fan static pressure.
Cooling tower location and placement should be
reviewed. The spray or plume could be a source of Freeze Protection Features
Legionella. Determine the distance to the nearest air Freeze protection is a very important feature.
handler intakes. Do not accept the prevailing wind Freezestats are designed to protect air-handling
excuse if it is too close; have it relocated. Stainless equipment and coils from freezing. If this system is
steel pans are recommended for their long service not designed and installed correctly, the air-handling
life and help in restricting microbial growth. Review equipment would frequently trip off and shut down.
with the designers the service options for motor This nuisance tripping causes a loss of airflow pres-
removal. Look at different options for basin heating, sure control and can also be a safety hazard. Many
including controls for the heaters. Be careful that maintenance personnel attempt to compensate for
they are not running year-round. Refer to Chapter 7 this situation by increasing the supply air tempera-
for additional information. ture. The resulting high temperature causes difficulty
in providing cooling.
Chemical Treatment
Chemical treatment is an integral part of ensur- Balancing Features
ing that the piping systems in the physical plant are To facilitate future troubleshooting or system
in good internal condition. Dirty pipes cost energy balancing, check for measurement devices and bal-
and can lead to lower system efficiencies and dis- ancing dampers in all HVAC equipment. This may
comfort for occupants. Improper water treatment on include temperature and pressure measurement ports
the condenser-water side can lead to excessive bleed- or devices on inlet and outlet connections to all coils,
off and wasted water. Too much boiler blowdown as well as balancing valves, flow measurement appa-
OPERATION AND MAINTENANCE 157

ratus, and temperature-measuring ports or devices at The second part of the acceptance testing is per-
various locations in the air-handling unit. Pressure formance oriented. This portion of the testing deter-
ports or gauges upstream and downstream of the fan mines whether the entire system performs under all
and ports for pitot traverse and airflow should also be required modes of operation.
provided. To facilitate periodic rebalancing or future Note that the model codes (including building,
modification, manual balancing dampers should be mechanical, and fire prevention codes) contain
provided on all branch duct runouts, located as far requirements for testing, inspecting, and maintaining
upstream from the terminal fixture (diffuser, register) smoke control systems. In addition, ANSI/NFPA
as practicable to reduce air-generated noise. 92A and 92B contain guidelines for testing.
After the installation is approved, the contractor
Central Station Air-Handling Units should supply a certificate indicating that the smoke
To reduce the possibility of microbial growth in control system was installed in compliance with the
unit insulation, air-handling units used in medical code and that all of the acceptance tests were per-
facilities should be the internally insulated, double- formed. ANSI/NFPA 92A requires that a copy of all
wall type with a corrosion-resistant inner wall. Per- operational testing documentation be provided to the
forated inner wall surfaces are not generally recom- owner.
mended. When final filtration is provided in an air- Periodic testing and maintenance is essential to
handling unit that is downstream from cooling coils, ensure that a smoke control system works as
provision must be made to avoid wetting the filters. intended in a fire scenario. Components, including
Carefully evaluate a draw-through versus a blow-
initiating devices, fans, dampers, controls, and doors,
through design.
must be tested on a scheduled basis. ANSI/NFPA
92A recommends testing dedicated systems semian-
Ductwork Design Considerations
nually and nondedicated systems annually. The fol-
Access panels for inspection or servicing of
lowing standards prescribe the requirements for
duct-mounted equipment (including fire dampers,
smoke dampers, and controls) and to facilitate peri- these systems.
odic cleaning or disinfecting must be properly sized ANSI/NFPA 92A. 2000. Recommended
and installed in accessible locations. Turning vanes Practice for Smoke-Control Systems.
should not be installed in return and exhaust duct- National Fire Protection Association,
work. Refer to Chapter 9 for additional information. Quincy, MA.
ANSI/NFPA 92B. 2000. Guide for Smoke
Smoke Dampers and Smoke Control Systems Management Systems in Malls, Atria, and
Even though this issue may be part of commis- Large Areas. National Fire Protection Asso-
sioning, it is important to restate that an initial accep- ciation, Quincy, MA.
tance testing must be performed to ensure that a
smoke control system operates as intended. The first Fire Dampers/Smoke Dampers
part of the testing includes the functional aspects of The NFPA requires damper maintenance and
the system, which involve two areas. First, the pas- inspection every five years. JCAHO inspectors look
sive fire protection systems (completeness and integ- at proper fire damper installation, performance, and
rity of fire-rated assemblies, firestopping, fire doors, maintenance records. They require testing a portion
etc.) must be evaluated. Then, the following sub-
of the dampers for proper operation. This operation
systems must be tested to the extent that they affect
requires replacing the fusible link. Once the link has
the operation of the smoke control system:
been removed, the spring-loaded damper should
Fire protective signaling system
drop immediately. Moving the damper back into
Building management system position is difficult and typically requires two peo-
HVAC equipment ple. Therefore, access panels should be installed on
Electrical equipment each side of a fire damper. Usually, one person gets
Temperature control system on each side of the damper, and together they push
Power sources the damper back into place using a wood stud or sim-
Standby power ilar lever; then the fusible link is reinstalled. This is a
Automatic suppression systems complicated, labor-intensive task.
Automatically operating doors and closures Attempt to minimize the number of fire and
Emergency elevator operation smoke dampers through the design process. Indicate
158 HVAC DESIGN MANUAL FOR HOSPITALS AND CLINICS

and provide access on both sides of the dampers generator specifications. It is common for specifica-
whenever possible. Breakaway connections at duct tions to name NFPA 70, National Electrical Code, as
risers are generally overlooked for access. Adequate part of the generator specification, but NFPA 110,
access doors must be provided for utility shafts. Standard for Emergency and Standby Power Sys-
tems, is referred to by NFPA 70 and has some very
Duct Cleaning When specific requirements for emergency generator con-
Existing Ducts Are Used struction and operation (NFPA 2002a, 2003). Review
Before embarking on a duct-cleaning project, these documents carefully, and adjust the specifica-
carefully investigate the cost and benefit versus risk. tions if needed.
Consult a hygienist and send samples of the offend-
ing material to the lab for analysis. Cleaning duct- Emergency Recovery Plan
work may give mixed results. Lined ductwork Determine whether the health care facility can
typically should be replaced rather than cleaned, run its entire operation on emergency power. It is
when possible. The cleaning process strips away the also not uncommon to find that there is simply not
insulating inner liner. Externally insulating an exist- enough fuel storage to run the building(s) for an
ing duct is labor-intensive and in some cases impos- extended period. The facility manager should care-
sible without removing all surrounding utilities. fully review the facilitys requirements and codes for
required run times.
Pumps
There are several configurations for pumps: end Outside Air Intakes
suction, vertical split case, vertical inline, etc. Space Improper location of outside air louvers near a
constraints, cost, mechanical room layout, and effi- contamination source can cause IAQ problems. Do
ciency all dictate pump configuration. Provide pres- not allow the architect to place fresh air louvers near
sure taps and trumpet valves so that maintenance a loading dock. Similarly, do not allow the architect
personnel can check pump performance. Specify to put the diesel generator near fresh air louvers. Die-
training for maintenance personnel for each pump sel exhaust is detectable by humans in concentra-
type. If very large motors (more than 15 hp [11 kW]) tions as low as 6 parts per billion! Medical vacuum
and pumps are installed, provide a beam or rail sys- pumps discharge many unknowns. Finding a safe
tem for removing these heavy items over or out of a location for vacuum pump discharge is typically
crowded mechanical room. overlooked.

Fire Protection Systems Domestic Water Pumps


The trend of oversizing these systems has The use of variable speed drives for domestic
resulted in large and expensive overpressure relief water pumps must be carefully evaluated; otherwise
piping. Examine the submittals carefully, and be cer- the system may not respond properly to rapid
tain that street pressure has been properly accounted changes in building water demand.
for in the calculations. A bypass line with a flow
meter is a good option and saves tremendous Water Heaters
amounts of water because hospital systems must be Quality units are stainless steel or glass-lined
checked weekly. and thermally efficient. Inspection ports must be
accessible. Temperature and pressure gauges should
Emergency Generators be provided on the outlet and inlet of each unit.
The facility manager must determine if cogener- Water flows must be properly balanced. Venting is a
ation, load-sharing programs, or leak shaving will be major concern for gas-fired units. Gas-fired units
part of the emergency power system. may not share space with refrigeration equipment.
Generator placement is extremely important but
is generally dictated by architectural issues rather Redundancy
than performance or ventilation concerns. Diesel In a hospital, 100% redundancy is often advised.
engine discharge at ground level is nearly always an Multiple electrical services and HVAC systems are
odor problem. Take generator exhaust to the roof recommended. At the same time, space for future
whenever possible. Cooling louvers should be growth is recommended because growth is inevita-
located in an area that provides the free area recom- ble. An example whereby redundancy in mechanical
mended by the manufacturer. Be very cautious about systems can be achieved is in the use of looping pip-
OPERATION AND MAINTENANCE 159

ing systems. Two paths of distribution within the vated charcoal may also be used for odor control in
plant allow more options in case of emergency. air supply systems where required within medical
Looping can be used effectively for gases and liq- care facilities.
uids. Examine your requirements carefully, and look Efficiencies are listed by dust spot efficiency as
at costs as well. rated under ASHRAE Standard 52.1-1992. As
ASHRAE Standard 52.2 (which deals with testing
Valves filters based on particle size versus efficiency)
There are never enough valves. Let us qualify becomes the common methodology, the filters for
that statement by saying that valves are seldom in the typical applications will have minimum efficiency
right locations to isolate equipment properly for rating values (MERVs) of MERV 7 before the coil
maintenance. Valves are inexpensive by comparison and MERV 14 as the final or secondary filter.
to the alternative. An emergency stop valve (or emer- Additionally, AIA Guidelines recommend air
gency line plug) is typically 100 times more expen- intake locations and air outlet requirements. Outdoor
sive than a valve in the same location. It is typical to intakes should be located as far as possible above the
provide a valve between each piece of equipment on groundat a minimum level of 6 ft (1.8 m). Roof
a loop or header but almost never on the header. level intakes should be located at least 3 ft (0.9 m)
above the roof. Outdoor intakes must also be at least
Filter Replacement 25 ft (7.6 m) from any exhausts or combustion
Filtration requirements for medical facilities are equipment (venting). Room air supplies should be
not a new concept. The original requirements were located at or near ceiling height.
published in 1947 under the HillBurton Act. In the
50 or more years since then, the requirements have Maintenance Considerations
been modified to current technologies for filtration Air handlers: The frequency of changing air
and microbial contamination control. handler filters is a function of the filter replacement
Guidelines for the Design and Construction of costs, air handler fan curve, local electrical costs,
Hospitals and Health Care Facilities (AIA 2001) labor costs, and the terminal static pressure of the fil-
publishes requirements for minimum levels of air fil- ter in use. As static pressure increases, the costs of
tration efficiency (AIA 2001). The requirements also running the units fans also increase. The costs must
define filtration by area and note additional items be measured against the labor and material costs of
such as required air changes per hour, recommended replacing filters. The optimum loading for a particu-
temperatures, recommended relative humidity, and lar filter type is available from filter manufacturers.
room pressure relative to the rest of the facility. HEPA: Bag-in/bag-out filter housings and filters
Medical facility HVAC systems are unusual in should be changed by mechanics who are trained and
that two filter beds are recommended, one upstream certified in infection control and bag-in/bag-out tech-
of the coil and a final filter bank downstream of the niques for the housing and seals in use.
coil. Standard HVAC systems place both stages The maintenance manager should be made
upstream of the coil. aware of odd size filters during the construction pro-
In orthopedic, bone marrow transplant, and cess. This item can be covered in the contract filter
organ transplant suites and recovery rooms, an addi- specifications in the general mechanical conditions
tional stage of HEPA filtration is recommended at but is often missed for smaller pieces of equipment.
the air outlets. HEPA filters are also recommended Filter selection may also be influenced by direct con-
for TB isolation rooms where recirculation is versation with the mechanical contractors who bid
employed to maintain the high air change require- on the project.
ments or where 100% exhaust to the outside is not
possible. See Chapter 9 for additional information on 14.6.2 Construction Project Acceptance
the subject. Fast-track construction seems to be the norm,
Rigid filters are preferred in hospitals. Bag fil- rather than the exception, in todays construction
ters collapse during normal maintenance of the air market. Maintenance departments are more often
handler. When bag filters collapse, particles of dust being asked to accept a project that has not been
on the outer surface of the filter media are released completed before users begin to move in.
into the airstream. Rigid filters by their nature do not So-called beneficial occupancy is becoming
have this problem. prevalent. Beneficial occupancy tends to muddy the
Typically, charcoal filters are used for odor con- contract waters by introducing confusion over the
trol of external sources such as diesel exhaust. Acti- dates on which an owner actually takes possession of
160 HVAC DESIGN MANUAL FOR HOSPITALS AND CLINICS

the building, when owner-conducted maintenance Secondary Air Systems


begins, and when the warranty periods provided by An example of this type of system is a laminar
contractors end. When a decision for early occu- flow system in an Orthopedic Operating Room or a
pancy is made, the owner must review the conse- HEPA-filtered recirculating unit for a Bone Marrow
quences of the contractual arrangements with the Transplant Unit. These may be provided with filters
contractor, with input from the design team. that need to be replaced, as well as a motor that may
Multi-phase projects are particularly difficult to require periodic service or replacement.
close out. A contract must spell out clearly what is to
be provided at the end of each phase. Phased projects 14.8 BUILDING COMMISSIONING
can go on for years, so it is necessary that as-built
Commissioning is a quality-focused process for
drawings, operating and maintenance manuals, and
achieving, validating, and documenting that a facility
spare materials for each phase be delivered to the and its systems are planned, designed, installed,
owner as each phase is completed. tested, and capable of being operated and maintained
Finally, retaining a firm to commission a build- to perform in conformity with the design intent. The
ing will improve owner representation, field inspec- commissioning process extends through all phases of
tion for each trade, suggested design guidance, a new or renovation project, from conceptualization
maintainability, proof of proper operation, and field to occupancy and operation, and has checks at each
inspection of materials and equipment bought for the stage of the process to ensure validation of perfor-
project. See Chapter 15, Commissioning, for more mance to meet the owner's design requirements.
detailed information. These are the fundamental objectives of the
commissioning process:
14.7 SPECIAL MAINTENANCE
CONSIDERATIONS FOR HVAC To verify and provide documentation that the
SYSTEMS /EQUIPMENT performance of the facility and its systems
Ferguson (2000) provides the following descrip- meets the owner's requirements
tions of special maintenance considerations for To enhance communication by documenting
health care equipment and systems. information and decisions throughout all phases
of the project
Fan-Coil Units To validate and report that building system per-
Each fan-coil unit with a cooling coil has a drain formance meets the design intent
pan that could become a reservoir for microbial
growth. Periodic inspection of the condensate pan is The active and ongoing participation of mainte-
necessary to avoid stoppages that may cause over- nance and operations personnel in the commission-
flows and wet surrounding materials, thereby creat- ing process is critical to its success. For an expanded
ing additional sites for microbial amplification. discussion of commissioning, see Chapter 15.
Because these units are typically located within the
spaces served, maintenance personnel will need 14.9 CAPITAL INVESTMENT PLANNING
access to occupied areas. Ferguson (2000) notes that maintenance depart-
ments generally are responsible for budgeting for a
Fin-Tube Radiation and Convection Units facilitys infrastructural upgrade. Careful attention
These units also require frequent cleaning to must be paid to assessing a facilitys need for future
minimize the collection of dirt and debris. This growth as presented in a capital budget. Maintenance
equipment also requires frequent access for mainte- departments should also request funding for repair-
nance personnel to occupied spaces. ing and/or replacing mechanical and electrical items
that must be replaced regularly.
Fan-Powered Terminal Units Understand the medical communitys needs
Fan-powered terminal units require inspection when upgrading systems or equipment. For example,
and maintenance. Frequent access to filters is replacing a Bone Marrow Unit would require bring-
required. These units have a fan motor and fan that ing the current unit down, relocating patients to
may need to be replaced. Separate ventilation air and another area, and returning them. These types of sec-
primary air supplies may be provided and should be ondary costs are often overlooked, but they must be
periodically checked. included during budgeting.
CHAPTER 15
COMMISSIONING
15.1 INTRODUCTION elements of the major components of commissioning
described below.
Commissioning is a quality assurance, quality
control process that provides the essential documen- This chapter presents a framework for the com-
tation, testing, and training to ensure that a system missioning process and outlines general require-
meets both its design intent and operational needs. ments that can be adapted to health care facilities.
Commissioning practices may be implemented to ASHRAE Guideline 1 (ASHRAE 1996) is the most
various degrees for a particular project depending widely cited document on commissioning. Many
upon its specific needs and requirements. commissioning projects involve building systems
Commissioning practices have proven beneficial beyond heating, ventilating, and air-conditioning. In
because of the increasing overall complexity of this manner, a well-conceived commissioning pro-
mechanical and electrical systems and the fast gram can serve as an overall quality assurance mea-
track mode of much construction. Commissioning sure to integrate complex building systems. Such
adds tangible value by implementing a quality additional building systems could include the build-
review process throughout a project, along with ing envelope, electrical systems, power and commu-
detailed documentation, testing, and systematic nications systems, transport systems, fire and life
training. safety systems, water systems, areas requiring spe-
cialized control, and building management systems.
Commissioning has been defined as a system-
atic process that begins in the predesign phase and
15.2 COMMISSIONING AUTHORITY
continues until at least a year after construction is
completed. Properly executed, the process includes The commissioning authority (CA) is the person
preparing the facilitys staff to operate systems and (or entity) who leads the commissioning process.
ensuring (through documented verification) that all The CA assembles the commissioning team, coordi-
building systems perform individually and interac- nates all commissioning activities, writes the com-
tively according to documented design intent and the missioning plan, and develops the commissioning
owners operational needs. Commissioning is most specifications. The commissioning authority must
valuable when system performance is evaluated develop the commissioning schedule, make it a part
under a full range of load and climatic conditions. of the overall construction schedule, and develop
Assessing system performance under part-load or agendas for and conduct monthly or weekly commis-
extreme conditions is often the best way to discover sioning meetings.
problems in buildings and correct them before occu- The CA must be an excellent communicator
pancy. both orally and in writing. The individual must
Commissioning is a team effort. The partici- understand the systems and facilities that are to be
pants include the owner, design professionals, the commissioned but will typically not be in a position
contractor, and a commissioning team leader or spe- to know everything about a facility. This is the rea-
cialist. The objective of the commissioning team is son that commissioning of complex facilities
to guide the process of quality control and quality requires a teamso that someone on the team knows
assurance. This is accomplished by implementing and understands all the building systems.

161
162 HVAC DESIGN MANUAL FOR HOSPITALS AND CLINICS

Because commissioning does not clearly come general contractors work through spot checks and
under the purview of any single design discipline, a quality assurance of the contractors commissioning
commissioning authority with broad experience with efforts. By doing this, however, the owner may gen-
building systems is recommended as the responsible erate animosity and ill will because exercising this
party to guide the commissioning process. An inde- authority will directly undermine the activities of the
pendent commissioning authority who reports general contractor as the commissioning authority.
directly to the building owner is essential to effective
commissioning. 15.2.4 The Engineer of Record
The advantages of using the design engineer as
15.2.1 The Owner as Commissioning the commissioning authority include that fact that
Authority
the engineer has full knowledge of the system design
Owners are often the most obvious choice to act and is intimately familiar with its sequence of opera-
as commissioning authority because they have a tion. This could achieve significant economies of
vested interest in ensuring that work is held to the time. There is a potential conflict of interest, how-
highest quality standards. By using in-house staff as ever, because design engineers may not acknowledge
commissioning authority, the owner can take control problems that are in fact design errors for which they
of the commissioning process to ensure that the con- are responsible. In addition, a major benefit of com-
tractor delivers the building properly. Disadvantages missioning, that of outside peer review, is lost using
of this approach are that permanent staff must be this approach. Areas of design that could be deficient
assigned to deal with ongoing projects (which may may not be captured because the engineer may not
result in delays in other areas of the project) and/or see them as deficient.
in-house staff may lack the appropriate expertise to
serve effectively as a CA. 15.3 THE COMMISSIONING PROCESS

15.2.2 An Outside Expert 15.3.1 Phase 1: Predesign


The owner can still act as commissioning The building/HVAC commissioning process
authority by hiring an outside expert to serve in the begins by
role of the CA. The expert would report directly to
the owner on the contractors performance and pro- designating a commissioning authority (CA),
vide effective monitoring of the commissioning establishing the parameters for design and
progress. This requires giving the outside consultant acceptance,
appropriate authority to coordinate outside subcon- designating the responsibilities of the various
tractors to undertake many of the required commis- parties,
sioning activities. For an effective program, the line delineating the documentation requirements for
of authority from the owner to the commissioning the entire project.
authority must be clearly defined.
The CA, the design team, and the owner review
15.2.3 The General Contractor the building program and identify the information
It is logical to hold the contractor accountable required for effective design and the criteria for sys-
for quality control, which takes into account many of tem and building acceptance.
the activities required for effective commissioning of
15.3.2 Phase II: Design
a building. Furthermore, it is the general contractor
who is responsible for construction sequencing and The commissioning authority is often thought of
who can effectively police the quality of workman- as a quality control element for the design team. As
ship on the job. The general contractor has a stake in such, the CA is responsible for reviewing and docu-
the successful completion and timely delivery of the menting discrepancies between architectural/HVAC
entire project. There is also direct financial benefit if design and specifications and the owners building
the general contractor can reduce warranty and ser- system performance criteria. As the design review
vice calls. Of course, the major drawback is the pos- proceeds, the CA is also responsible for reviewing
sibility of a conflict of interest because the contractor value-engineering proposals for conformance to
would be responsible for replacing any items found codes, occupant needs, and general reasonableness
deficient. To try to avoid such conflict of interest, the and for providing an opinion regarding the resulting
owner could retain the prerogative of approving the effects of such changes.
COMMISSIONING 163

Early in the design phase, the CA is responsible that is provided to support this is critical because
for preparing and distributing a commissioning plan it will clearly show the completeness of the
that identifies the responsibilities of each of the key engineers design.
members of the team and schedules commissioning Specify acceptance criteria. It is essential to
activities and deliverables. This plan should be in
present the acceptance criteria in clear, unam-
sufficient detail so that the required submittals will
biguous terms. Where possible, the acceptance
designate parties and instrumentation that need to be
criteria should be quantitative, and the accuracy
present for each test. In addition, the master con-
and precision required should be consistent with
struction schedule should include the schedule of
commissioning activities and link commissioning the limitations of the equipment and system
activities with other construction activities. design.
The commissioning authority must ensure that
the design team takes explicit responsibility for doc- 15.3.3 Phase III: Construction
umenting the following items: During the construction phase, the commission-
ing authority is responsible for on-site inspection of
Design Criteria and Underlying Assumptions
materials, workmanship, and installation of building/
The design criteria should address all of the fol- HVAC systems and components (including verifica-
lowing environmental considerations: tion of pressure tests of piping and duct systems).
The CA should also observe and/or independently
Thermal conditions Special loads
audit testing, adjusting, and balancing; fire stopping
Humidity Air quality design criteria
of walls; calibrating of system components; and
Occupancy Pressurization and
(hours and levels of activity) infiltration pressure testing of specialty rooms.
requirements Other activities that an effective commissioning
Lighting Fire safety authority performs during the construction phase
Vibration Energy efficiency include (1) reviewing warranty and retaining policies
Total and outside air requirements Maintainability
before the completion of construction, (2) reviewing
Code requirements and impact
copies of the contractors approved equipment sub-
on design
mittals, (3) ensuring that effective construction con-
Functional Performance Test Specifications tainment techniques are used, and (4) documenting
and reporting discrepancies for the owner.
These specifications are developed during the
design phase and allow the design team to better Finally, it is essential that personnel who will be
anticipate the commissioning process requirements. responsible for operating the completed systems
These test specifications are required, at a minimum, receive adequate training before system acceptance.
to do the following. This is best done during the construction phase. The
commissioning authority should take responsibility
Describe the equipment or systems to be tested. to ensure that appropriate personnel (often equip-
The HVAC system description includes type, ment manufacturers, through the design engineer)
components, intended operation, capacity, tem- provide this training for the numerous components
perature control, and sequences of operation. of the HVAC system(s).
Identify the functions to be tested. Operation and
performance data should address each seasonal 15.3.4 Training
mode, seasonal changeover, and part-load oper-
ational strategies, as well as the design setpoints The successful transition from construction to
of the control system(s) and the range of permis- owner occupancy and use largely depends on com-
sible adjustments. Other items to be considered plete and competent training. Often, operations and
include the life safety modes of operation and maintenance personnel are excluded from the project
any applicable energy conservation procedures. during the planning and construction phases. An
Define the conditions under which the test is to effective commissioning program avoids this prob-
be performed. It is important to consider all pos- lem. The operations and maintenance (O&M) staff
sible operating modes, for example, full and par- must be well versed in all aspects of operation and
tial loads and the extremes of operating maintenance of building systems to maintain an
temperatures and pressures. The documentation appropriate level of serviceability and functionality.
164 HVAC DESIGN MANUAL FOR HOSPITALS AND CLINICS

The commissioning team interacts with O&M conditions or during design extremes. The commis-
personnel throughout a project, culminating in a sioning authority should document the building
training program that offers key personnel the advan- operators adjusted setpoints to ensure that they are
tage of both classroom and hands-on training. The consistent with the original design. Where differ-
training program includes a system overview by the ences exist, the CA should evaluate the impact of
design professional supported by narratives, flow such deviations and reconcile their effects in a writ-
diagrams, one-line diagrams, and appropriate speci- ten report.
fications sections. It is augmented by training from
qualified instructors on individual systems and 15.3.7 Overview of the Process
equipment, supported by operations and mainte-
nance manuals, wiring diagrams, audiovisual equip- Hospitals are one of the most difficult facility
ment, and calibration and troubleshooting devices, in types encountered in commissioning work. Even
addition to actual hands-on demonstrations. though many of the tasks are the same as in the com-
missioning of office buildings or schools, they are
15.3.5 Phase IV: Acceptance more complex. In hospitals, there are pressurization
Acceptance should follow the commissioning issues, infection issues, immunocompromised
patients, isolation room issues, specialty gases and
plan established during the design phase. The func-
equipment, along with energy concerns. For a com-
tional performance test specifications form the basis
missioning project to be a true success, commission-
for documenting the performance tests. The commis-
ing must start with the owners desire to build the
sioning authority either conducts or observes the
facility. Then, the owner must support the effort to
appropriate parties testing the functional perfor-
the fullest extent.
mance of each system. This testing should start at the
lowest reasonable level (system components), then The commissioning authority should be selected
move on to subsystems, then finally systems, until before (or not later than when) the design team is
every piece of equipment has been tested. The CA chosen and should work with the team and the owner
must also ensure that all essential activities involve in developing the owners program and design intent.
valid performance tests (e.g., hydrostatic testing, Both of these documents must become an integral
testing and air balancing [TAB] work, and calibra- part of the commissioning plan to be developed by
tion of automatic controls) and that the tests have the commissioning authority. The designer must also
been completed to a satisfactory conclusion before develop a basis of design, a document that details the
starting the acceptance verification procedures. It is reasons why certain systems and equipment have
critical to test in all modes of system operation, been selected.
including full load and emergency conditions. Once the owners program and intent, along
All required documentation should be compiled with the basis of design, have been finalized, the
to form the basis of the system operating manual. commissioning authority develops commissioning
Furthermore, as-built documents should be revised specifications. These specifications outline the con-
to ensure that accurate drawings are available, show- tractual responsibilities and duties of the commis-
ing all relevant control points and values. sioning authority, owner, and the contractors who
The commissioning authority will produce and will be responsible for systems to be commissioned
distribute to appropriate parties a document detailing (such as the mechanical, electrical, and fire protec-
all discovered deficiencies in the form of an action tion systems). The mechanical contractors contract
list. After the required work has been completed, the should assign responsibility for the HVAC&R con-
CA will revisit the site and perform follow-up per- trols, medical gas, plumbing, sheet metal, piping,
HVAC equipment, insulation, etc. The electrical con-
formance testing, where required, to verify that all
tractor will be responsible for the generator, fire
action list items have been successfully resolved.
alarm, and all of the electrical wiring and electrical
15.3.6 Phase V: Post-acceptance apparatus. The fire protection contractor will be
responsible for the sprinkler system, hose reels, and
The post-acceptance phase can best be thought all fire apparatus. All of these contractors should
of as an ongoing audit of the buildings systems and have a working contract with the general contractor
the buildings occupancies. Periodic retesting is or construction manager that defines commissioning
often advisable, especially during the first year. This responsibilities. It is imperative to spell out the
can be particularly important during extreme sea- working relationships between the responsible con-
sonal variations from the original commissioning tractors, general contractor, and commissioning
COMMISSIONING 165

authority in the respective contracts between the par- dynamic operation. The details of functional testing
ties. of building systems vary from system to system and
Once contracts have been awarded, it is critical are subject to the type and intended use of the facility
that the commissioning authority hold an initial com- or process. The following systems are typically sub-
missioning meeting and review the responsibilities jected to functional performance testing.
of the various contractors.

15.4 DOCUMENTATION Mechanical Electrical


The overall success of a project may depend on HVAC air-handling systems Substations
how well and accurately decisions, criteria, and con- Specialty ventilation systems
cepts are documented. From the basis of design to Exhaust systems Distribution equipment
the functional testing protocols for mechanical and Energy recovery loop systems Motor control centers
electrical systems, it is essential that all phases of a Chilled water systems Grounding systems
project include appropriate documentation. The Boiler systems Automatic transfer switches
commissioning team coordinates, reviews, commu- Pumping systems Intercommunication systems
nicates, and archives documentation to substantiate Smoke/fire protection systems
that system integrity is acceptable and meets the Heating systems Fire alarm systems
owners requirements. Commissioning may include Domestic hot/cold water Smoke management systems
assistance with developing and quality review of any systems
or all of the following: Cooling tower systems Delayed exiting systems
Waste and vent systems Security systems
Basis of design documentation Medical gas systems
Design development documents Specialty gas systems Closed-circuit television
Construction documents (plans and specifica- systems
tions) Natural gas systems Emergency generator systems
Meeting notes and project correspondence Fire protection systems Uninterruptible power supply
systems
Shop drawings
Process cooling water systems Process control systems
Product data submittals
Installation procedures HVAC&R control systems Nurse call systems
Construction practices High-purity water systems Isolated power systems
Static testing procedures (duct, pipe, equipment) Specialty process systems Lighting systems
Cleaning procedures (systems) Sterile processing systems
Functional performance testing procedures Plumbing systems Variable speed drives
Training procedures Smoke/fire protection systems Automatic doors
Testing and balancing procedures and reports
Operating and maintenance manuals. 15.4.2 Commissioning Plan
A commissioning plan is a document that out-
15.4.1 Functional Performance lines the various commissioning activities and
Testing Protocols responsibilities in detail. The commissioning plan
Often components of a system are tested indi- also includes the different forms that are to be used.
vidually or are assumed to be factory calibrated There should be a prefunctional and functional per-
and are not tested at all. When a system is turned formance testing form for each piece of equipment.
over to the owner and operated under actual condi- The prefunctional form should have line items for
tions, it frequently falls short of expectations. This is installation, specifications, and start-up of the equip-
generally evidenced by negative feedback from ment The functional performance test form should
building occupants or process users. By subjecting identify how a particular piece of equipment is to
mechanical and electrical systems to functional per- operate individually and how it operates as part of a
formance testing, the commissioning team observes, total system.
evaluates, identifies deficiencies and recommends The HVAC&R control, fire alarm, and smoke
modifications, tunes, and documents systems and control systems have to be verified, and their opera-
system equipment performance over a range of loads tion with the various other building systems has to be
and functional levels. documented. The test form should outline in step-by-
A functional performance test protocol is a step- step detail how the systems are to function. The vari-
by-step procedure developed to advance building ous stages and steps of testing and verification have
systems from a state of substantial completion to full to be identified.
166 HVAC DESIGN MANUAL FOR HOSPITALS AND CLINICS

The commissioning plan must identify the vari- These are examples of user groups who should
ous parties to commissioning and the responsibilities attend the initial commissioning meeting:
of each. The parties should include the following, as
a minimum: Administration
Financial
Owner Chief Operating Officer
Facility Manager Department Assistant Operating Officer
Operations and Maintenance Personnel Chairman of Respective Department
Authority Having Jurisdiction (or designee)
Plan Reviewer Operating Rooms Supervisor
Inspector Chief of Staff (for respective services)
Licensure Authority Chief of Medicine
Architect Pharmacy
Engineers Food Service
General Contractor Housekeeping
Mechanical Contractor Laundry
Electrical Contractor Maintenance
Control Contractor Emergency Department
Test and Balance Contractor Central Sterile Supply
Laboratories
15.4.3 Owner Information Systems
Biomedical (Clinical Engineering)
The owner is involved in commissioning docu-
Radiology
mentation in one or more of the following roles:
Security
A single entity, a corporation, or a board Pediatrics
The person who gives the A/E design and opera- Specialty area representatives
tional criteria for the facility Orthopedic
A person whom the owner designates as a repre- Coronary Care
sentative. That person can be the facility man- Isolation Personnel
ager, chief engineer, building operator, or Transplantation
another party. This person should have authori- Intensive Care
zation from the owner to make decisions for the Americans with Disabilities Act (ADA)
owner up to a certain dollar value that must be Transportation (vertical and horizontal)
documented. The owners representative must
Infectious Control
attend commissioning meetings and construc-
Risk Management
tion progress meetings. The representative must
Patient Relationships
report directly to the owner and advise the
Public Relationships
owner of the progress of the project. The repre-
All of these disciplines may not attend every
sentative may also be charged to review and
meeting, but they should attend the design meeting
approve monthly pay requests. The representa-
to ensure that their needs are met. They may not
tive must also be responsible for meeting with
attend all commissioning meetings, but they should
the A/E and contractors as needed. The repre-
be kept informed, and an invitation to attend the
sentative must become familiar with the contract
commissioning meetings must be extended. The
documents so that binding decisions can be ren-
users should be involved in all decisions relating to
dered.
substitutions and to their departments, as deemed
The owner must provide infectious control spec-
necessary.
ifications on projects where applicable.
Additional meetings may have to be scheduled
On a health care project, the facility users to keep people continually involved and informed.
should attend the initial commissioning meeting and Minutes of meetings should be taken and forwarded
should be involved in the design review. When satis- (with supporting documentation) to all parties who
fied, they should sign off on the drawings and speci- participated in the initial meetings, plus department
fications to indicate that they accept or agree to the heads and others who are considered important to the
design of their particular area. project.
COMMISSIONING 167

15.4.4 Architect/Engineer (A/E) the various review stages. The designer should fur-
nish, at the next stage of review, highlighted docu-
The A/E is responsible (with the owners input)
ments for comparison and verification that previous
for developing the design intent, the basis of design,
comments have been incorporated into the current
and the contract documents. The design profession-
documents. During the design phase, the owner may
als must assign a representative from each discipline
want to engage a test and balance contractor to
to make design decisions on their behalf. The repre-
review the documents for system test and balancing
sentatives must attend construction progress meet-
capabilities.
ings and commissioning meetings.
They architect and engineer(s) must also visit During this phase, there is an opportunity to
the site monthly and issue a report based upon their investigate the possibility of obtaining a guaranteed
findings and observations. These reports should be maximum price (GMP) from selected contractors. If
filed with the owner and the commissioning author- this option is adopted, the commissioning authority
ity (this must be spelled out in the contracts) within should be involved.
72 hours of each visit to the site. The A/E must During the design phase, a set of commissioning
address a request for information (RFI) within 5 cal- specifications must be developed and inserted into
endar days and a change order request (COR) within the contract documents. These specifications must
10 calendar days (this must also be spelled out in the convey to the contractors that commissioning will be
contract documents). These response requirements conducted and must include the responsibilities of
are critical for compliance with the construction the owner, designer, general contractor, and subcon-
schedule. tractors relative to commissioning activities.

15.5 CONSTRUCTION PROCESS AND 15.5.3 Construction Phase


COMMISSIONING INTERFACE
During the construction phase, the main objec-
15.5.1 Predesign Phase tive is to build the building on time and within bud-
get. During this phase, the various contractors must
This is the phase when the owner decides submit commissioning (test) plans that explain how
whether to build a facility or remodel an area of an they are going to commission their particular por-
existing facility. This is when the owner commences tions of the project. The subcontractors must have
to think about the wants, needs, and requirements of their vendors furnish delivery schedules for materials
the proposed facility. The owner also must start to and equipment and include these schedules in the
think about the professional design team and issue a overall commissioning plan and project schedule.
request for qualifications (RFQ). Once the owner has The submittal process should require that submittals
received the RFQs, a meeting is set up to determine a go the commissioning authority and the A/E simulta-
short list and, after this is accomplished, a short list neously so they can be reviewed for compliance with
is prepared. From the short list, interviews are estab- the commissioning objectives. Should the commis-
lished and the design team is selected. Once this is sioning authority have substantive comments or
accomplished, the owner in conjunction with the comments of noncompliance, the submittals should
design team develops the design. be returned to the subcontractor for corrective action
Once the owners program has been accepted, and resubmitted through the same process.
the A/E must develop design intent, a basis of Once the submittals have been accepted, they
design, and the design documents. The design intent can be returned to the various contractors and sub-
must clearly state how systems are to operate. contractors so that equipment and materials can be
Design intent must be developed for operating ordered. Once the equipment and materials have
rooms, the emergency department, patient rooms, been ordered, the subcontractors should prepare
food service, housekeeping, etc. Once the design coordination drawings and submit them for approval.
intent has been developed and accepted, the design Coordination drawings must be developed and
can commence. reviewed by the respective contractors, i.e., mechani-
cal and electrical. These drawings should be overlaid
15.5.2 Design Phase
to determine if there is interference among water
During the design phase, the commissioning pipes, ductwork, conduit, lights, equipment, etc. The
authority should review the contract documents at commissioning authority and the A/E must approve
various stages (35%, 50%, 75%, and 100% comple- these drawings. Once these drawings have been
tion). Comments on the design should be issued at approved, they must be used to install the systems.
168 HVAC DESIGN MANUAL FOR HOSPITALS AND CLINICS

During the construction phase, the commission- 15.5.4 Special Health Care Facility
ing authority must attend project coordination meet- Considerations
ings and be on the agenda. The CA must also
Maintaining a clean worksite can be an issue on
conduct commissioning meetings. These are com-
all projects but is especially critical on health care
monly held the day before the coordination meetings
projects. The responsibility for maintaining the
so that commissioning issues can be documented and
mechanical work in a relatively clean state belongs
recorded in the minutes of the coordination meet-
to the contractors. The designers and the commis-
ings, along with commissioning meeting minutes.
sioning authorityas well as the contractorsneed
The commissioning authority must inspect and to be cognizant of the effects of cleanliness on the
verify that equipment and systems are installed in completed systems.
accordance with the submittals, coordination draw- Construction dust and debris and moisture in
ings, and contract documents. Deficiencies must be uncompleted systems are issues on all projects. In
brought to the attention of the respective contractors most cases, ducts and piping systems are normally
in written form and the contractors must answer left open-ended until the next phase of activity. As
within five calendar days with a resolution. If the an example, a supply air system is being installed.
deficiency cannot be corrected within the allotted The first activity would probably have the main ducts
time, the response should tell the commissioning installed. A second pass would install the air ter-
authority when it will be corrected and should con- minal units, connect them to the main ducts, and then
tain appropriate backup data. install low-velocity distribution ducts downstream of
During the construction phase, the commission- the terminal units. The final pass would be to
ing authority must develop pre-functional and func- install the air devices in the final locations and con-
tional testing plans. In the pre-functional tests, nect the devices to the low-velocity distribution
equipment is to be started up and systems flushed ducts. Days, weeks, or months may have transpired
and cleaned in accordance with the contract docu- between each of these phases. If the system was left
ments. The pre-functional test forms should be trans- open-ended at the completion of each day, shift, or
mitted to the contractor for completion and sign-off. activity phase, it can, and will, collect anything and
The commissioning authority initials and forwards everything from construction dirt and drywall dust to
the forms to the general contractor or construction leaves, sandwich wrappers, and wind-blown rain.
manager for signature. When the pre-functional test This example can be applied to other compo-
forms are completed and signed, they are given back nents of the mechanical systems, such as the air-han-
to the commissioning authority to verify that there dling equipment, medical gas piping, etc. Storage of
are no outstanding issues. The commissioning construction materials can also be a major concern.
authority signs off and accepts this portion of the Air terminal units are normally shipped to a project
process. Upon acceptance of the pre-functional tests, on pallets and covered with plastic shrink-wrap.
the respective contractor and general contractor (or This is an excellent method of protecting the equip-
construction manager), along with the commission- ment until installation. Once the plastic is removed
ing authority, agree that the systems have been to install the first air terminal, the remainder of the
started up, ductwork has been cleaned, water pipes terminals on the pallet are then exposed to the same
have been flushed, controls are functioning, and sys- ambient conditions as open-ended duct and piping.
tems have been debugged. The pre-functional tests
verify that equipment and systems are in satisfactory 15.6 RETRO-COMMISSIONING
operational condition and are ready for functional
Retro-commissioning is a process that evaluates
testing.
the means by which functional requirements in an
The commissioning authority must maintain a existing (uncommissioned) facility are met. Func-
presence on the construction site once equipment has tional evaluation is a subset of performance evalua-
been set in place and testing has started. The CA tion. Retro-commissioning is generally performed by
must also continually review the quality of the con- a third-party commissioning authority to avoid con-
struction under the contract. Systems that have not flicts of interest. A similar process in a previously
been designed or contracted for cannot be commis- commissioned facility is typically termed re-com-
sioned. missioning or continuous commissioning.
COMMISSIONING 169

Such performance evaluation (testing, metering/ Commissioning personnel are seldom available
monitoring, and troubleshooting) of existing system on an ongoing basis to adapt their recommenda-
operations is conducted to establish conformance tions and strategies to changing conditions.
with design intent, optimized energy utilization tar- Operational staff is frequently not apprised of
gets, and current operational requirements. It is an the underlying logic motivating strategies, mak-
application of expertise, rather than an application of ing in-house detection and correction of perfor-
technology to reduce costs. mance slippage difficult.

Typical retro-commissioning projects might Successful retro-commissioning projects require


include: the following elements:

Evaluation and adjustment of automation or Staff buy-in: It is imperative that operations staff
control system parameters. understand the what, why, and how of retro-
Implementation of alternative operational strate- commissioning strategies. Without operations
gies. staff buy-in, any strategy predicated on new or
Optimized equipment staging and sequencing. counterintuitive operational practices will lapse.
Identification of undetected equipment impair- The commissioning authority must work closely
ment and/or failure. and cooperatively with operations staff.
Damper actuator optimization, economizer
Data and information collection: The informa-
rehabilitation.
tion required to monitor operational performance
Variable speed drive control adjustments.
may not correspond with existing indicators of func-
Reset and changeover strategies. tional performance. Identify bellwether status indica-
Tailored equipment scheduling and sequencing. tors that are simple and direct for each major
General automation tweaks. strategy.
Retro-commissioning projects involve numer- Status indicators should be actionable and
ous benefits, such as: unambiguous (not open to conflicting interpreta-
tion). Structure data to indicate operational qual-
Low cost. ity and/or relative significance.
Generally little or no capital expenditure
Do not over-collect data or collect data that
required to implement savings opportunities.
require follow-up operator evaluation and post-
Recommendations can be carried out through processing. This will eventually result in aban-
control sequence modifications and/or conven- donment of monitoring efforts.
tional maintenance work in many instances.
Rapid payback (payback on program cost is typ- Simple indicative monitoring practices that are
ically much less than one year). put to use surpass sophisticated practices that are
Efforts can typically be self-funded through the not used.
operational budget.
Similar projects have demonstrated proven Operational tools: Integrate persistence-enhanc-
results. ing monitoring and diagnostic tools into the reg-
ular operational routine to ingrain monitoring
Annual operational cost savings of 3% to 7% are
processes.
common, with early savings often higher.
Attempt to utilize or augment existing practices
Although retro-commissioning can be very where possible. Do not create new work.
attractive, there are several potential shortfalls: Tools should automatically perform necessary
data manipulation. Summarization of bellwether
The primary difficulty with retro-commission- indicators should be embedded in the process
ing efforts is maintenance of benefits (savings and be conveniently generated for staff review.
persistence). Tools should be simple to use and understand.
Performance slippage is unavoidable in any Something that looks like a BAS front end (or
dynamically operated facilityparts wear, an F-16 control panel) is too idiosyncratic for
activities change, schedules are modified. ongoing use by general operations personnel.
Performance slippage can often occur without Data validation routines should be used to
affecting system functional behavior. screen for bad data and prevent false alarms.
170 HVAC DESIGN MANUAL FOR HOSPITALS AND CLINICS

Ongoing retention of the benefits of retro-com- 15.7.3 Payment Schedule


missioning can be enhanced through the following Based on Time Estimates
actions: Use a payment schedule based on time estimates
provided to the owner by the commissioning author-
Staff must understand, be included in, and buy ity. In these types of projects, it is important that all
into the program agenda. parties agree in writing as to what constitutes a com-
Information that reflects system performance pleted commissioning plan, as well as an appropriate
should be collected and reviewed on an ongoing payment schedule.
basis. As needed, develop data relationships that
signify performance quality. 15.7.4 Commissioning Offsets
Concise monitoring and evaluation tools should McCarthy and Dykens (2000) provide a good
be available to, and understood by, staff. discussion of the commissioning offset, which can
Data manipulation should be automated. be summarized as follows.
Historic data should be available on demand. Although commissioning is often seen as an
Data should be presented graphically for trend added cost to a project, owners experienced with
detection. commissioning do not find an overall cost increase
when constructing buildings. The commissioning
Findings and results should be shared.
costs discussed above compare favorably with other
cost parameters normally associated with building
15.7 COSTS, OFFSETS, AND BENEFITS
construction. For example, 26% of M/E project cost
There is currently no standard approach to cost- compares favorably with the 918% range for
ing commissioning services. Some of the more com- change orders and claims generally encountered on
mon methods are discussed below. No matter which capital projects.
budgeting approach is selected, contracts with the In addition to the benefits cited earlier, experi-
general and specialized contractors must clearly state ence shows that an effective commissioning program
that although the commissioning authority is initially can also
paid by the owner, additional charges incurred by the
reduce change orders and claims by 50% to 90%;
CA will be paid by the contractors if systems fail or
provide energy savings in the first year of opera-
cause delays in the established commissioning or
tion that generally exceed the cost of commis-
project schedules.
sioning;
reduce overall system maintenance costs during
15.7.1 Budget a Percentage of the
the first year by an amount that is comparable to
Total Mechanical/Electrical
(and often exceeds) the cost of the commission-
Cost of a Project
ing program.
A range of 1.5% to 6.0% is generally considered
reasonable. The higher percentages are generally 15.7.5 Commissioning Benefits
used for those projects that are smaller in scope or Levin (1997) lists the benefits of commissioning
those that are more complex, such as a health care reported by an extensive survey that included 146
facility. case studies. The results are reproduced in Tables 15-
1, 15-2, and 15-3. The data reported in these tables
15.7.2 A Separate Commissioning Budget clearly indicate that commissioning programs pro-
Independent of the Project Budget vide important economic and operational benefits to
an owner.
This approach is often useful when an owner has Data do not exist to conclusively demonstrate
an ongoing construction program, such as that found improvements in worker productivity or reduced ill-
in many health care facilities. Setting aside a com- ness rates due to commissioning activities, although
missioning budget that represents between $0.10 and such benefits are anecdotally reported. Many groups
$0.28 per square foot ($1.10 and $3.00 per square have extensively evaluated the impacts of commis-
meter) allows carrying out work on a number of sioning on energy conservation or energy efficiency
projects during a years time. Most owners use an measures. Piette and Nordman (1996) studied the
operations budget, although some do capitalize this commissioning of energy conservation programs in
work. 16 buildings in the Pacific Northwest and found that
COMMISSIONING 171

Table 15-1. Benefits of Commissioning


Percentage of Survey Respondents
Benefits of Commissioning Reporting the Benefit
Energy savingsa 82
Thermal comfort 46
Improved operation and maintenance 42
Indoor air quality 25
Improved occupant morale 8
Improved productivity 8
Reduced change orders 8
Timely project completion 7
Liability avoidance 6
Reprinted from PECI (1996).
a. More than 70% energy savings was documented by metering or monitoring.

Table 15-2. Thermal Comfort Benefits of Commissioning


Percentage of Survey Respondents
Benefit Reporting the Benefit
Improved thermal control 90
Reduced humidity control requirements 52
Improved air balances 30
Reduced occupant complaints 30
Reprinted from PECI (1996).

Table 15-3. Indoor Air Quality Benefits of Commissioning


Percentage of Survey Respondents
Benefit Reporting the Benefit
Improved ventilation 70
Better contaminant control 22
Improved carbon dioxide levels 19
Improved moisture control 11
Improved containment: clean rooms or laboratories 8
Reprinted from PECI (1996).

the investment in commissioning was cost-effective and procedures. They are more involved in problem
based on energy savings alone. identification and resolution. Because of on-time
All participantsowners, design team, and con- project completion and cost savings, owner satisfac-
tractorscan realize the benefits of commissioning tion with the design team is improved.
the building systems on a project. Commissioning The contractor can identify problems early and
achieves a win-win-win situation for all team mem- meet the project schedule. There is less reactive
bers. repair at project completion and fewer callbacks.
The owner receives documentation and training There is increased efficiency in system installation,
resulting in increased knowledge of building sys- start-up, operation, testing, and training, which
tems, installations, and operations. Because of test- results in cost savings.
ing, upon occupancy the owner experiences fewer The value of commissioning is most often cited
operational problems, less dependence on the con- with respect to new building construction projects.
tractor, and increased satisfaction with the project. Part of HVAC commissioning involves formally doc-
Projects are more often completed on time and with umenting performance objectives. Basing acceptance
an overall cost saving (when typically required first- upon these performance objectives, from construc-
year remedial actions are considered). tion through to system operation, results in a better
The design team becomes more familiar with functioning building. These procedures can be
owner requirements, system installation techniques, equally valuable in renovation projects and energy
172 HVAC DESIGN MANUAL FOR HOSPITALS AND CLINICS

conservation programs. Many times, the start-up, ductivity and morale of health care workers.
control, and operational problems that occur due to Furthermore, the reduction in occupant and
minor changes in local areas can compromise the patient complaints of discomfort minimizes ser-
performance or efficiency of entire buildings. Fur- vice calls to building operators during the life of
thermore, when one considers the impact that defi- the building.
ciently operating HVAC systems can have on indoor Better infection control.
air quality and health, the benefit of incorporating Reduced potential for liability and litigation.
proper building commissioning activities in all This is true for owners (from personal injury
HVAC-related projects is obvious. cases) and for engineers and contractors (due to
Specific benefits that can be realized from a suc- claims from owners).
cessful commissioning program include:
15.8 SUMMARY
Higher quality building systems and the knowl-
edge that a facility operates consistently with the Commissioning is a systematic, detailed process
owners design intent and meets occupant needs. that requires the mutual commitment of the owner
Identification of system faults and discrepancies and the commissioning authority to ensure its suc-
early in the construction process so that they can cess. The goal of commissioning is to turn over to
be resolved in a timely manner while appropri- the owner a building that meets the design intent
ate contractors are still on the job. This will with appropriate safeguards (such as operator train-
reduce the number of contractor callbacks. ing and required documentation) to ensure that it will
Improved documentation, training, and educa- continue to function properly. As owners, contrac-
tion for operators and facility managers to tors, architects, and engineers see the benefits of
ensure longer equipment life and improved per- commissioning, they are incorporating it into their
formance. building projects. Although there are many defini-
Increased equipment reliability by discovering tions of commissioning, it is important to bear in
system problems during construction. In this mind that this is the ultimate quality assurance pro-
way, commissioning prevents costly downtime gram in the life of a building. As such, it must clearly
due to premature equipment failure and reduces and unequivocally set the standards of acceptability.
wear and tear on equipment by ensuring that it The commissioning authority has a responsibility to
operates properly. the owner and to the community of professionals
Reduced operating and maintenance costs. involved in the building process to ensure that the
Improved occupant comfort and indoor air qual- highest standards are met and to ensure that a build-
ity. Managing these factors effectively can ing performs according to the owners project
reduce employee absenteeism and improve pro- requirements and its occupants needs.
CHAPTER 16
ENERGY EFFICIENT DESIGN AND
CONSERVATION OF ENERGY RESOURCES
16.1 INTRODUCTION 16.2 HEALTH CARE CONSTRAINTS
According to the U.S. Department of Energy
(1998) the average health care facility consumes 2.7 16.2.1 Health Care Functions
times the energy per unit floor area as the average
commercial building. The department (USDOE) has The particular functions and requirements of
documented the average energy consumption of health care facilities provide unique opportunities for
health care facilities in the U.S. as 240,400 Btu per implementing energy design alternatives. The imple-
square foot per year (75 kWh per square meter per mentation of energy efficiency opportunities in
year) with an average cost of approximately $2.26 health care facilities, however, must not adversely
per square foot per year. The average acute care, full- affect or compromise health care objectives or func-
service hospital is documented to have an even tions (including diagnosis, treatment, recovery and
higher average consumption of about 330,000 Btu recuperation, infection control, and a wide variety of
per square foot per year (1040 kWh per square meter support functions). The energy efficiency opportuni-
per year) with an average cost of approximately $3 ties must also be addressed in such a manner as to
per square foot per year ($32 per square meter per maintain the safety and comfort of patients, staff, and
year). visitors and support the maintenance of environmen-
Energy efficiency is the efficient use of the tal conditions necessary for operation of hospital
energy resources consumed by a health care facility. equipment.
Resource optimization is efficiently utilizing all the
Energy efficiency considerations for health care
available energy resources, including recoverable,
facilities are similar to those in other types of com-
nonrenewable, and renewable resources. Energy effi-
ciency opportunities (EEOs) are strategies that use mercial and institutional facilities. Energy efficient
improved design and operation of systems, equip- design alternatives are especially effective in health
ment, building characteristics, and energy manage- care facilities, however, due to unique health care
ment systems to efficiently utilize the available functions. Health care functions and requirements
energy resources. These strategies are important that result in significant energy use include 24/7
means to achieving the goal of reducing the cost of occupancy, strict indoor air quality and high ventila-
health care facilities operations within a reasonable tion air requirements, and intensive (strict) room
return-on-investment and while conserving precious temperature and humidity requirements.
global energy resources.
This chapter will present energy efficient design 16.2.2 Hospital Mission
concepts that can be applied in the design of new
health care facility buildings, systems, and equip- Some areas of hospitals (such as emergency,
ment or can be applied in the retrofit of existing labor/delivery, surgery, and cardiac and intensive
health care buildings, systems, and equipment. These care) must maintain a status of constant readiness for
energy efficient design strategies will reduce the con- urgent health care needs and emergencies. Most hos-
sumption of energy resources while maintaining all pitals are also part of a disaster response system. The
the important health, safety, and comfort constraints implementation of energy conservation opportunities
unique to health care facilities. must not compromise these missions.

173
174 HVAC DESIGN MANUAL FOR HOSPITALS AND CLINICS

16.3 ENERGY USAGE IN (Farnsworth 2001). The facility was modeled using
HEALTH CARE FACILITIES climate files for different geographical locations to
In order to best understand how to reduce con- investigate how different climates would affect
sumption of energy resources in new health care energy consumption (using TMY weather files from
facilities, or to retrofit existing health care facilities the U.S. Department of Energy).
to be more energy efficient, it is important to under- Tables 16-1 through 16-5 provide a definitive
stand where energy is normally consumed in a typi- breakdown of energy usage patterns for a prototypi-
cal heath care facility. cal health care facility. Table 16.1 lists typical elec-
trical energy usage components and their
16.3.1 Study of an Example Facility relationship to total electrical energy consumption.
Table 16-2 lists typical primary cooling energy usage
The example facility is a 350,000 ft2 (32,500
2), components and their percentage of total cooling
m full-service metropolitan health care facility
energy. Table 16-3 lists typical thermal energy usage
with all the typical health care facility functions: sur-
gery suites, recovery suites, labor/delivery areas breakdown by component and their relationship to
including nurseries and c-section suites, cardiac total thermal energy consumption. Table 16-4 lists
catherization areas, radiology, mammography, typical primary heating energy consumption compo-
nuclear medicine areas, laboratory areas, physical nents and their contribution to total heating energy.
and occupational therapy areas, outpatient examina- Table 16-5 shows a typical breakdown of annual
tion and surgery areas, dietary, laundry, nursing costs by all energy-using components.
floors, emergency room and waiting areas, mainte- The tables illustrate how energy is used in typi-
nance services, offices, and special services. cal health care facilities in various climates and the
This example facility is heated and cooled by 27 percentages of a health care facility's total energy
constant volume air-handling systems with chilled expenditures that are spent on given energy-consum-
water cooling coils, steam heating coils, and steam ing components. The distributions of energy con-
humidification. All of the air-handling systems have sumption and utility costs will vary somewhat from
enthalpy-based air-side economizer controls. About facility to facility, but the percentages listed in these
50% of the HVAC systems are constant volume dual- tables may be considered generally accurate in their
duct systems and 50% are constant volume reheat portrayal of how energy is used in a typical health
systems. The HVAC systems introduce a varying care facility, whether small or large, in a range of dif-
percentage of minimum outdoor air, from 10% to ferent geographic locales.
100% of the total HVAC system airflow quantity. Although the information in Tables 16-1
Total supply air volume was 420,000 cfm (198,200 through 16-5 is based upon this prototypical facility,
L/s). DOE-2 models of a 750,000 ft2 (69,700 m2) subur-
This example facility has a central Energy Cen- ban health care facility, a 260,000 ft2 (24,200 m2)
ter with electrical centrifugal chillers, primary and regional health care facility, and a 175,000 ft2
secondary chilled water pumping systems with some (16,300 m2) eye institute/general hospital show very
variable speed pumps, constant speed cooling tower similar results.
fans, and constant speed condenser water pumps. Table 16-5 was developed using the noted
The Energy Center also contains steam boilers that $16.15/MMBtu ($0.055/kWh) utility rates for elec-
produce steam for heating, sterilization, and humidi- tricity and $5.00/MMBtu ($0.017/kWh) for natural
fication. gas throughout the country. Utility rate structures are
Heating water for reheat coils and finned-tube actually different in the varying locales listed in the
radiation is produced using steam-to-water heat table, but for comparison a uniform set of rates was
exchangers. The heating water pumping systems are used for each location. In fact, these rates would be
constant speed systems. considered quite low compared to most rate struc-
The lighting in the facility had been partially ret- tures on the East and West coasts. The accuracy of
rofitted by conversion to T-8 fluorescent lamps and the table will still apply as long as the ratio of electri-
energy efficient electronic ballasts. A fairly consci- cal costs to natural gas costs remains the same.
entious lighting management program is also in
place.
16.3.2 Important Assumptions for the
The energy rates for the example facility are
Existing Facility and Discussion of
$0.055/kWh (or $16.15/MMBtu) for electricity and
Results
$0.50/therm (or $5.00/MMBtu [$0.017/kWh]) for
natural gas. Some important assumptions should be noted
The following tables illustrating facility energy that will affect the distribution of energy usage by
usage were developed using a DOE 2.1 computer components in any individual facility versus those
model of an actual health care facility in the Midwest listed in Tables 16-1 through 16-5.
Table 16-1. Typical Hospital Electrical Usage Profile (% of kWh/year) By Component (1)
%ofElectricalEnergyUse
NE Mid-Atl. SE Florida Midwest Upper Ctrl. North South Ctrl. Southwest S. Calif. Northwest
Component (Boston) (Phila.) (Atlanta) (Miami) (St. Louis) (Chicago) (Minneapolis) (Houston) (Tucson) (L.A.) (Seattle)
Lighting
(retrofitted T-8 lamps/
electronic ballasts/
lighting control) 18 17 16 13 17 17 17 14 16 16 14
kWh 1,626,240 1,626,240 1,626,240 1,626,240 1,626,240 1,626,240 1,626,240 1,626,240 1,626,240 1,626,240 1,626,240
Miscellaneous Electrical
(receptacle load,
computers, equipment,
exterior lighting, etc.) 19 19 17 14 18 19 19 15 18 18 24
kWh 1,797,417 1,797,417 1,797,417 1,797,417 1,797,417 1,797,417 1,797,417 1,797,417 1,797,417 1,797,417 1,797,417
Primary Cooling 14 16 21 33 15 14 13 27 20 20 10
OA Cooling
(% of Total Cooling) 1 1 3 8 1 1 1 5 1 6 1
kWh 84,096 133,693 343,848 1,031,842 153,100 133,670 105,000 642,234 106,073 598,958 133,643
Space Cooling
(% of Total Cooling) 11 12 14 20 11 10 10 17 16 11 7
kWh 973,997 1,147,738 1,502,227 2,591,141 1,070,418 997,426 993,870 2,044,687 1,553,618 1,097,039 569,684
Fan Heat/Losses/
Thermal Mixing
(% of Total Cooling) 2 3 4 5 3 3 2 5 3 3 2
kWh 243,499 286,934 375,557 647,785 267,505 249,386 233,468 511,172 388,424 274,260 142,431
Cooling Towers/
Condenser Water
Pumping
(Constant Vol.) 5 6 7 10 6 6 5 9 6 6 4
kWh 453,406 568,150 744,834 1,304,571 553,260 537,667 498,391 1,049,951 629,035 617,175 327,548
ENERGY EFFICIENT DESIGN AND CONSERVATION OF ENERGY RESOURCES

Chilled Water/ Heating


Water Pumping
(Constant Vol.) 6 6 7 6 6 6 6 6 7 7 6
kWh 584,225 580,989 662,380 778,035 617,651 595,278 600,501 719,087 670,367 681,012 527,946
Ventilation Fans
(100% CAV) 29 28 26 21 28 29 29 24 28 28 35
kWh 2,700,503 2,700,503 2,700,503 2,700,503 2,700,503 2,700,503 2,700,503 2,700,503 2,700,503 2,700,503 2,700,503
Heating Auxiliaries 9 8 6 3 10 9 11 5 5 5 7
kWh 793,872 734,333 675,958 424,435 944,037 889,788 797,322 636,050 509,542 487,756 610,730
175

TOTAL 100 100 100 100 100 100 100 100 100 100 100
kWh 9,257,255 9,575,997 10,428,964 12,901,969 9,730,131 9,527,375 9,352,712 11,727,341 9,981,219 9,880,360 8,436,142
Table 16-2. Typical Hospital Electrical Usage Profile (% of kWh/year) By Component (1)
176

NE Mid-Atl. SE Florida Midwest Upper Ctrl. North South Ctrl. Southwest S. Calif. Northwest
Component (Boston) (Phila.) (Atlanta) (Miami) (St. Louis) (Chicago) (Minapls.) (Houston) (Tucson) (L.A.) (Seattle)
Primary Primary Primary Primary Primary Primary Primary Primary Primary Primary Primary
Cooling % Cooling % Cooling % Cooling % Cooling % Cooling % Cooling % Cooling % Cooling % Cooling % Cooling %
Primary Cooling
OA Cooling
(% of Total Cooling) 6 9 18 24 10 10 8 20 5 30 16
Space Cooling
(% of Total Cooling) 75 73 68 61 72 72 73 64 76 56 67
Fan Heat/Losses/
Thermal Mixing
(% of Total Cooling) 19 18 14 15 18 18 19 16 19 14 17
TOTAL 100 100 100 100 100 100 100 100 100 100 100
HVAC DESIGN MANUAL FOR HOSPITALS AND CLINICS
Table 16-3. Typical Hospital Thermal Energy Usage Profile (% of Total Btu/year) By Component
% of Thermal Energy Use
NE Mid-Atl. SE Florida Midwest Upper Ctrl. North South Ctrl. Southwest S. Calif. Northwest
Component (Boston) (Phila.) (Atlanta) (Miami) (St. Louis) (Chicago) (Minpls.) (Houston) (Tucson) (L.A.) (Seattle)
% % % % % % % % % % %
Primary Heating Use 90 89 88 86 90 90 90 87 87 87 89
OA Heating
(% Total Thermal Use) 13 11 11 4 15 15 17 7 5 5 9
Therms 62,643 48,417 41,048 11,262 73,461 74,299 92,113 21,432 16,439 2,970 37,200
Reheating/Thermal
Mixing
(% Total Thermal Use) 56 58 59 69 55 55 53 65 58 69 61
Therms 267,792 255,384 218,987 182,175 269,426 266,803 282,298 206,156 182,644 223,116 256,350
Space Sensible Heating
(% of Total Thermal
Use) 21 20 18 13 20 20 20 15 24 13 19
Therms 95,113 89,044 66,504 34,869 96,350 97,630 110,619 49,484 73,324 55,678 73,324
DHW Heating 2 2 3 5 3 3 2 3 3 3 3
Therms 7,790 7,790 7,790 7,790 7,790 7,790 7,790 7,790 7,790 7,790 7,790
Dietary/Sterilizers 4 4 4 4 3 4 4 5 5 5 3
Therms 17,840 17,840 17,840 17,840 17,840 17,840 17,840 17,840 17,840 17,840 17,840
Distribution System/
Losses 4 5 5 5 4 3 4 5 5 5 5
Therms 23,470 22,085 18,535 13,365 24,467 24,440 26,877 15,930 15,686 16,179 20,668
TOTAL 100 100 100 100 100 100 100 100 100 100 100
Therms 474,648 440,560 370,704 267,301 489,334 488,802 537,537 318,632 313,723 323,573 413,172
ENERGY EFFICIENT DESIGN AND CONSERVATION OF ENERGY RESOURCES
177
Table 16-4. Primary Heating Energy Usage (% of Total Btu/year) By Component
178

Upper
NE Mid-Atl. SE Florida Midwest Ctrl. North South Ctrl. Southwest S. Calif. Northwest
Component (Boston) (Phila.) (Atlanta) (Miami) (St. Louis) (Chicago) (Minpls.) (Houston) (Tucson) (L.A.) (Seattle)
Primary Primary Primary Primary Primary Primary Primary Primary Primary Primary Primary
Heating % Heating % Heating % Heating % Heating % Heating % Heating % Heating % Heating % Heating % Heating %
Primary Heating Use
OA Heating
(% Total Heating Use) 15 12 13 5 17 17 19 8 6 6 10
Reheating/Thermal Mixing
(% Total Heating Use) 63 65 67 80 61 61 58 74 67 79 70
Space Sensor Heating
(% of Total Cooling) 22 23 20 15 22 22 23 18 27 15 20
TOTAL 100 100 100 100 100 100 100 100 100 100 100
HVAC DESIGN MANUAL FOR HOSPITALS AND CLINICS
Table 16-5. Typical Hospital Energy Costs By Component
% of Total Annual Energy Costs
Upper South
NE Mid-Atlantic SE Florida Midwest Central North Central SW S. Calif. NW
Component (Boston) (Philadelphia) (Atlanta) (Miami) (St. Louis) (Chicago) (Minneapolis) (Houston) (Tucson) (L.A.) (Seattle)
Lighting (T-8 Lamps) 12% 12% 12% 11% 11% 12% 11% 11% 13% 13% 13%
Miscellaneous
Electrical 13% 13% 13% 12% 13% 13% 13% 12% 14% 14% 15%
OA Cooling 1% 1% 2% 7% 1% 1% 1% 5% 1% 4% 1%
Space Sensible
Cooling 7% 8% 11% 17% 7% 7% 6% 14% 12% 9% 5%
CoolingFan Heat/
Thermal Mixing 2% 2% 3% 4% 2% 2% 2% 3% 3% 2% 2%
OA Heating 4% 3% 3% 1% 5% 5% 6% 1% 1% 1% 3%
Reheating/Thermal
Mixing 18% 18% 14% 11% 17% 17% 18% 14% 13% 15% 19%
Space Heating 6% 6% 4% 2% 6% 6% 7% 3% 5% 4% 5%
Cooling Towers/
Condenser Water
Pumping 3% 4% 5% 8% 4% 4% 3% 7% 5% 5% 3%
Chilled Water/Heating
Water Pumping 4% 4% 5% 5% 4% 4% 4% 5% 5% 5% 4%
Ventilation Fans 20% 20% 20% 17% 19% 19% 19% 18% 21% 21% 22%
Heating Auxiliaries 6% 5% 5% 2% 7% 6% 7% 4% 4% 4% 5%
DHW Heating/
Sterilizers/
Humidification 1% 1% 1% 1% 1% 1% 1% 1% 1% 1% 1%
ENERGY EFFICIENT DESIGN AND CONSERVATION OF ENERGY RESOURCES

Dietary/Sterilizers 1% 1% 1% 1% 1% 1% 1% 1% 1% 1% 1%
Thermal Distribution 2% 2% 1% 1% 2% 2% 2% 1% 1% 1% 2%
Total 100% 100% 100% 100% 100% 100% 100% 100% 100% 100% 100%
179
180 HVAC DESIGN MANUAL FOR HOSPITALS AND CLINICS

If some of the air-handling systems in a facility The minimum outdoor air quantities provided
are variable air volume (VAV) systems and are for the air-handling units in this prototypical
designed for reduced static pressure loss, the facility varied from 10% of the total airflow to
total ventilation fan energy usage may be 100% of the total airflow, depending upon the
reduced to as low as 15-20% of the total electri- areas served. Makeup air units for patient wings
cal energy usage and as low as 14% of the total were 100% outdoor air. If a health care facility
energy cost of the facility. In most existing has a larger percentage of 100% outdoor air
health care facilities, only about 20% of the air- units, the energy consumption cost for outdoor
handling units are variable volume systems. In air cooling, dehumidifying, humidifying, and
the example facility, the air-handling systems heating will be much greater.
were all constant volume.
Component energy cost percentages will vary
In existing health care facilities, many of the air- from the example facility if there is a signifi-
handling systems are constant volume, dual- cantly different ratio of natural gas costs to elec-
path, thermal mixing systems (dual-duct or mul- tricity costs at another facility than illustrated
tizone systems), with fixed cooling coil and here. The ratio for the prototype facility has
heating coil discharge temperatures. In these electricity costing approximately 3.3 times more
cases, the cooling and reheating thermal mixing per 106 Btu (1.06 106 kJ) than natural gas. If
energy consumption would be much higher than electrical rates in a given area are significantly
listed in Tables 16.1-16.5. Most new facility higher than indicated in this example and natural
HVAC systems are designed as either constant gas rates are similar, then the electrical energy
volume or variable volume reheat systems. Fifty end-use components will have a greater cost
percent of the systems in this representative effect. If the natural gas rates are significantly
facility were constant volume dual-duct or mul- higher and electrical rates are similar, then the
tizone systems and fifty percent were constant thermal energy end-use components will have a
volume reheat systems. greater cost effect.
Lighting system energy consumption could be
much higher than in this representative facility, The example facility had electrical centrifugal
if lighting management techniques are not being chilled water plants with medium efficiency
employed or if energy efficient ballasts are not chillers (0.75 kW/ton [0.21 kW/kW]). Other
used. The lighting in the representative facility types of electrical cooling with more or less effi-
had been retrofit, using energy efficient T-8 flu- cient performance (or the use of absorption
orescent lamps and electronic ballasts. chillers or gas-engine-driven centrifugal chill-
The chilled water and heating water pumping ers) would cause the electrical and thermal
systems in this representative facility had pri- energy cost percentage profiles to change.
mary-secondary pumping configurations with
variable speed control of secondary pumps. The Even if the energy cost percentages vary some-
energy consumption for these use categories what from health care facility to health care facility
will be significantly higher if variable speed and with geographic location, several important
pumping control systems are not implemented. observations can be extracted from a review of the
These strategies are, in fact, typically not imple- data in these tables. First, because of the significant
mented in health care facilities. The cooling minimum total air change requirements and mini-
tower fans and condenser water pumps in the mum outdoor air change code requirements for
modeled facility were constant speed/constant health care facilities, between 31% and 41% of the
volume systems. annual energy cost of the typical facility is used for
The primary cooling energy use percentages are ventilation fan energy and for overcooling and then
representative of a facility where approximately reheating space ventilation air in excess of that
70% of the air-handling systems used air-side required to heat or cool the space. Additionally,
enthalpy based free cooling economizer sys- another 13-20% of the annual energy cost of the
tems. If these free-cooling strategies are not facility is used for auxiliary or parasitic energy
implemented in a facility, the primary cooling usage components, composed of pumping energy
energy consumption would be higher and the and cooling tower energy. Between 5% and 10% of
energy consumption required for heating and the annual energy costs are required for outdoor air
cooling of outdoor air would be much higher heating, cooling, humidification, and dehumidifica-
than listed for the prototypical facility. tion, depending upon location.
ENERGY EFFICIENT DESIGN AND CONSERVATION OF ENERGY RESOURCES 181

These observations provide a roadmap for deter- C. Requirements for continuous directional con-
mining the types of energy efficiency improvements trolpositive, negative, neutral, or no require-
that should be incorporated into any health care ment (see Table 4-1 in Chapter 4).
facility. Such improvements can be easily made in a For example, in spaces that are occupied 24
manner that will make a significant impact on energy hours daily (i.e., emergency rooms, 24-hour labora-
consumption without affecting space comfort, tory or pharmacy areas, intensive care units, nurser-
health, or life safety requirements. ies, etc.) and/or where the space sensible cooling air
flow requirements are not significantly greater than
16.4 DESIGN OF ENERGY EFFICIENT the minimum ventilation air change rate require-
HVAC SYSTEMS ments, reducing air flow will probably not reduce
As illustrated by the energy usage tables in the energy consumption greatly.
previous section, between 36% and 46% of the However, in spaces where
annual energy costs of the typical health care facility 1. no continuous directional control or minimum
are related to the operation of the HVAC systems. ventilation air change rates are required, or
This includes ventilation fan energy, outdoor air
2. there are significant unoccupied hours, or
cooling and dehumidification, outdoor air heating
and humidification, as well as thermal mixing and 3. where space sensible cooling air flow require-
reheating required to maintain space comfort. For ments are significantly greater than the minimum
this reason, it is especially important to implement ventilation air requirements,
energy efficient strategies in the design of new (or then significant reductions in energy consumption
retrofit) HVAC systems. (See Appendix H for sam- can be achieved through use of variable volume con-
ple control strategies.) trol of the HVAC systems. Most spaces in health care
facilities fall into these categories, including:
16.4.1 Variable Air Volume (VAV) System
Application Opportunity Most surgery and recovery suites
In most locations, state health codes may allow a C-section suites
reduction in minimum total air flow rates and mini- Radiology, X-ray, mammogram, nuclear medi-
mum outdoor air flow rates during unoccupied peri- cine, CAT scan, ultrasound, MRI, and PET areas
ods (see Table 4-1). This reduction can apply to any Physical/occupational therapy areas
of the spaces in a health care facility that are in unoc- Office areas
cupied status as long as the required directional pres- Dietary areas
surization control is maintained for the space. Laundries
Significant energy savings can be achieved by Outpatient areas and surgeries
designing the air-handling systems serving these Cardiac catherization areas
spaces as variable air volume systems. The AIA Waiting areas
(American Institute of Architects) and ASHRAE Maintenance departments and other support
allow ventilation rates to be reduced to 25% of the areas
occupied period rates as long as continuous direc- Examination rooms and treatment rooms
tional control and space pressurization are main-
tained at all times and the full (occupied) ventilation In a typical health care facility, only about 20%
air change rates can be reestablished any time the of the facility is occupied more than 60-70 hours per
space is being utilized (see further discussion below week. Operating suites and surgical prep areas are
under unoccupied period control strategies). rarely used more than 60-80 hours per week, except
A designer should consider the following factors for a few operating suites, recovery areas, and radiol-
when evaluating how effective a variable volume ogy areas dedicated to emergency services. Such
HVAC system will be in a health care facility: spaces usually only constitute about 20% of the total
surgery areas in a facility. Typical schedules are
A. Hours of operation of the spaces being served by
illustrated in Table 16-6, using data derived from
the HVAC system.
multiple field surveys.
B. Magnitude of the difference between the mini- A variable volume air-handling system should
mum ventilation air changes per hour (see Table be provided with variable frequency controllers for
4-1 in Chapter 4) and the air flow required to meet the supply air and return/relief air fans. The design
space sensible cooling load requirements. should also include a separate minimum outdoor air
182 HVAC DESIGN MANUAL FOR HOSPITALS AND CLINICS

Table 16-6. Typical Occupancy Patterns for Various Health Care Facility Spaces
Spaces Typical Occupied Hours/Week
80% of rooms normally occupied 24 hours,
Patient Rooms 7 days/week
75% of rooms normally occupied 24 hours,
ICU Rooms 7 days/week
Nurses Stations 24 hours, 7 days/week
Emergency Room Areas/Exam Rooms 24 hours, 7 days/week
Labs Areas (normally 50% of total areas) 24 hours, 7 days/week
Emergency Radiology Areas (normally 10%-20% of total areas) 24 hours, 7 days/week
Emergency Surgery/Recovery Areas (normally 10%-20% of total areas) 24 hours, 7 days/week
Autopsy 24 hours, 7 days/week
Central Sterile Supply 24 hours, 7 days/week
Nursery 24 hours, 7 days/week
Corridors/Waiting Areas 24 hours, 7 days/week
Medical Records 24 hours, 7 days/week
Receiving 60 hours/week
Clean Linen Storage 50 hours/week
Purchasing 50 hours/week
Maintenance Offices 50 hours/week
Ultrasound Areas General 50 hours/week
Mammography Areas General 50 hours/week
Nuclear Medicine Areas General 50 hours/week
Fluoroscopy Areas General 60 hours/week
Endoscopy Areas General 60 hours/week
X-Ray Areas General 60 hours/week
Surgery Prep Areas General 65 hours/week
Operating Rooms General 65 hours/week
Outpatient Operating Rooms General 50 hours/week
C-Section Operating Rooms 40 hours/week
Administration Offices/Conference Rooms 50 hours/week
Recovery General 55 hours/week
Physical/Occupational Therapy 60 hours/week
Outpatient Exam/Office Areas 65 hours/week
Cardiac Catherization Labs 55 hours/week
Dietary 98 hours/week
Dining Areas 98 hours/week
Laundry 60 hours/week
ENERGY EFFICIENT DESIGN AND CONSERVATION OF ENERGY RESOURCES 183

Figure 16-1 Variable air volume air-handling unit schematic. Dual-duct or multizone air-handing units.

control damper for control of minimum outside air apply to reheat systems. Figure 16-2 illustrates how
(see Table 4-1) separate from control of outside air an existing dual-duct terminal unit can be easily ret-
for free-cooling economizer operation. In an rofit to variable volume operation. Figures 16-3 and
energy retrofit application, the dampers should be 16-4 indicate how an existing multizone system can
separated if there is currently only one damper. The be easily retrofit to variable volume operation.
building automation system (BAS) should include In cases where critical care areas require a cer-
supply ductwork static pressure sensors and control tain minimum total ventilation air change rate (see
sequences to vary the supply fan speed and return air Table 4-1), the terminal unit maximum and mini-
ductwork static pressure sensors and control mum airflow setpoints may need to be the same dur-
sequences to vary return/relief air fan speed. Space ing occupied periods and the terminal unit be
pressurization control in critical spaces can be main- programmed to act like a constant volume terminal
tained by using return air terminal units as discussed unit during occupied periods.
in Section 16.4.4.
In critical spaces where pressure relationships
must be maintained, the designer should note the
16.4.2 VAV Systems for Existing Hospitals possibility of lint accumulation on the return air ter-
In hospitals that experienced substantial build- minal volume measurement element. This condition
ing construction during the 1960s and 1970s, exist- may affect pressure relationship.
ing air-handling systems are most likely either Documented energy retrofit experiences with
constant volume single-duct, dual-duct, or some- existing health care facility air-handling systems are
times even constant volume multizone. Facilities very favorable. Generally, a three- to four-year sim-
with substantial construction in the 1980s and 1990s ple payback can be achieved for an energy retrofit
will more likely have air-handling systems with con- conversion of dual-duct and multizone air-handling
stant volume reheat operation. Most new facilities systems, and a two- to four-year simple payback can
are currently designed with either constant volume be achieved for an energy retrofit conversion of con-
or variable volume reheat air-handling systems. All stant volume reheat systems using utility rates as dis-
of these systems can be easily retrofit to VAV opera- cussed for the prototypical facility. Higher utility
tion with significant reductions in ventilation fan rates may produce an even quicker return on invest-
energy, thermal mixing and reheating energy, and ment. In new construction, the additional incremen-
cooling energy use. Figure 16-1 indicates retrofit tal cost to add variable frequency controllers,
modifications to a typical dual-duct or multizone air- additional building automation controls, return air
handling unit, although these modifications will also terminal units, and dampers to change from constant
184 HVAC DESIGN MANUAL FOR HOSPITALS AND CLINICS

Figure 16-2 Modified dual-duct terminal units for variable volume operation.
ENERGY EFFICIENT DESIGN AND CONSERVATION OF ENERGY RESOURCES 185

Figure 16-3 Multizone, variable air volume control ductwork schematic.

Figure 16-4 Modified constant volume, multizone systems for variable volume operation.
186 HVAC DESIGN MANUAL FOR HOSPITALS AND CLINICS

volume reheat systems to variable volume reheat minimum airflow setpoints to their unoccupied
systems generally shows a simple payback of only period minimum airflow values. These unoccu-
one to two years. pied period minimum airflow setpoints should
provide only as much air as required to make up
16.4.3 Variable Volume Occupied and for exhaust or pressurization requirements. The
Unoccupied Period Control for unoccupied period minimum airflow setpoint
Noncritical Care Spaces could be zero if no exhaust or pressurization
requirements exist. This will produce a significant
Many of the spaces in a health care facility (such reduction in reheat energy usage, cooling energy
as dietary and dining areas, outpatient administrative usage, and ventilation fan energy usage.
offices, outpatient treatment areas, many radiology
3. During unoccupied periods, the BAS should also
and outpatient therapy areas, and many common
reset the HVAC system minimum outdoor air set-
areas) do not have continuous pressurization control
point to a new unoccupied period value to adjust
requirements. These areas can be easily served by a
for the reduced occupancy of the spaces. This will
traditional VAV air-handling system, which can sub-
produce a significant reduction in the energy
stantially reduce energy consumption through use of
required for cooling, heating, dehumidifying, and/
several occupied and unoccupied period control
or humidifying minimum outdoor air.
strategies.
1. During occupied periods, the DDC building auto- 16.4.4 Variable Volume Occupied and
mation system (BAS) will modulate air flow from Unoccupied Period Control for
terminal unit maximum occupied air flow set- Critical Care Spaces
points to minimum occupied period air flow set-
In areas of a health care facility where continu-
points to maintain space temperature setpoint.
ous directional pressurization control is required
Minimum occupied period airflow setpoints
(either positive or negative) and significant minimum
should be established to provide adequate ventila-
air flow rates are required during occupied periods,
tion effectiveness and adequate indoor air quality
substantial reductions in energy usage and costs can
for occupants and to provide makeup air for
be achieved by reducing air flow rates during unoc-
exhaust or pressurization requirements.
cupied periods. (See Table 4-1 in Chapter 4, which
2. During unoccupied periods, the BAS will modu- illustrates the changes that can be made to ventila-
late airflow to maintain space temperature in the tion rates during unoccupied periods according to
same manner; however, the DDC building auto- ASHRAE [1999a], AIA [2001], and most state
mation system should reduce all terminal unit departments of health.) Figure 16-5 illustrates a

Figure 16-5 Critical care area schematic. Typical for directional pressurization control.
ENERGY EFFICIENT DESIGN AND CONSERVATION OF ENERGY RESOURCES 187

method for achieving these savings by retrofitting a During unoccupied periods, the return air con-
constant volume reheat system or using a new vari- troller tracks the supply air controller in the
able volume reheat tracking system. The same proce- same manner as discussed above, except using
dures would apply equally well to dual-duct or different setpoints.
multizone systems.
The BAS will control the minimum outside air
In critical care areas, significant reductions in controller in the air-handling system to provide
ventilation fan energy usage, reheat or thermal mix- adequate minimum outside air to meet all of the
ing energy usage, space cooling energy usage, and unoccupied period minimum outside air space
energy usage for treatment of outdoor air can be ventilation requirements (Table 4-1).
achieved during unoccupied periods by designing
new air-handling systems or modifying existing air- 16.5 AIR-TO-AIR HEAT RECOVERY
handling systems to meet the following building STRATEGIES
automation control strategies.
Due to the significant amount of outside air
During occupied periods, the DDC building required to meet code requirements in health care
automation systems will control the terminal facilities, air-to-air heat recovery strategies are a very
unit to maintain space temperature setpoint by cost-effective means of reducing energy consump-
modulating the airflow between maximum air- tion. Specific savings will depend upon the percent-
flow setpoint and minimum airflow setpoint. age of minimum outdoor air used for a facility and
The VAV supply air controller/damper assembly its geographic location/climate.
will provide the required supply air from the air- There are four air-to-air heat recovery systems
handler to meet the space sensible cooling load that are commonly used; runaround coil systems,
requirement or to provide the minimum occu- fixed plate heat exchanger systems, heat pipe sys-
pied period total space ventilation requirements tems, and rotary desiccant heat exchanger systems
(Table 4-1), whichever is greater. The minimum (heat wheels). These system types are illustrated in
airflow setpoint of the terminal unit controller Figure 16-6.
should be set for the occupied minimum total The effectiveness of these systems depends
space air changes per hour (Table 4-1). This may upon the temperature differences between the air-
require the terminal unit to act as a constant vol- streams, latent energy differences, air flow, device
ume terminal during occupied periods. efficiency, and hours of operation. Increased mainte-
During occupied periods, the BAS will control nance may be required with the implementation of
the VAV return air controller/damper assembly such systems, and a ventilation fan energy penalty
to track the supply air controller, providing the will be incurred.
required return air from the space to maintain
either a constant positive or negative air volume 16.5.1 Runaround Coil System
offset in the space or a space differential pres- This system is composed of two or more
sure (positive or negative) setpoint. extended-surface coils installed in air ducts and
The BAS will control the minimum outside air interconnected by a piping system. The heat
controller in the air-handling system serving exchanger fluid, usually consisting of ethylene gly-
these spaces to provide adequate minimum out- col and water, is circulated through the system by a
side air to meet all of the occupied period mini- pump, removing heat from the hot airstream and
mum space outside air ventilation (Table 4.1) transferring it to the cold airstream. A runaround-coil
requirements. system may be used in winter to recover heat from
During unoccupied periods, the BAS will con- warm exhaust air in order to preheat cold outdoor air
trol the supply air control/damper assembly to and in summer to cool hot outdoor air by transferring
provide the required supply air to meet the space heat to cooler exhaust air.
sensible cooling load requirement or the mini- Runaround coil systems normally have a heat
mum unoccupied period total space ventilation transfer efficiency of between 60% and 80% of the
requirements (Table 4-1), whichever is greater. sensible heat available. These systems are frequently
The minimum airflow setpoint of the terminal the only practical heat recovery option in retrofit sit-
unit controller is set for the unoccupied mini- uations, as the other options need to have the outdoor
mum total air changes per hour (Table 4-1). air and exhaust/relief ducts close to each other. Run-
188 HVAC DESIGN MANUAL FOR HOSPITALS AND CLINICS

o~=i=E`F e~=m=e~=b~

o~=e~=b~

c=m~=e~=b~

Graphics Source: ASHRAE. 2000.


2000 ASHRAE HandbookHVAC
Systems and Equipment. Atlanta:
American Society of Heating,
Refrigerating and Air-Condition-
ing Engineers, Inc.
Figure 16-6 Energy recovery technologies.

around systems usually have a 3-5 year simple pay- difficult to implement in a retrofit application unless
back if implemented in an energy retrofit application the airstreams are very close together and the duct-
and usually have a 0.5-2 year payback if imple- work can be modified to facilitate installation.
mented as part of a new design projectespecially if
overall heating and cooling plant sizes can be 16.5.3 Plate Heat Exchanger
reduced as a result of the heat recovery. Plate-type air-to-air heat exchangers transfer
heat from one airstream to another via indirect con-
16.5.2 Heat Pipe Systems tact through a metal heat-transfer surface. The sys-
Heat pipe systems are composed of extended- tems have no crossover flow. Plate heat exchangers
surface finned tubes extending between adjacent air require that supply and exhaust ducts be installed
ducts. The tubes are continuous on the same horizon- side by side.
tal plane from one duct to the other. Each tube con- These systems also have an efficiency of
tains liquid refrigerant that evaporates at the warm between 60% and 80% of the sensible heat available.
end (absorbing heat from the warmer airstream) and New technologies allow latent heat transfer as well.
migrates as a gas to the cold end where it condenses They have simple paybacks, similar to the runaround
(and releases heat into the cold airstream). The con- coil systems, but may be difficult to implement in a
densed liquid then runs back to the hot end of the retrofit application unless the airstreams are very
tube to complete the cycle. These systems require close together and the ductwork can be modified to
that supply and exhaust ducts be installed side by facilitate installation.
side.
Heat pipe systems also usually have an effi- 16.5.4 Heat Wheels
ciency of between 60% and 80% of the sensible heat Rotating heat wheels are an air-to-air heat
available. They have simple paybacks on investment, recovery system that can transfer both sensible heat
similar to the runaround coil systems, but may be and water vapor between airstreams.
ENERGY EFFICIENT DESIGN AND CONSERVATION OF ENERGY RESOURCES 189

If properly designed, these systems can achieve ence rooms, offices, etc.) served by two-pipe or four-
up to 80% efficiency in recovering the total (sensible pipe fan-coil systems or air-handling systems with-
and latent) heat available. These systems have the out air-side (free cooling) economizers, many of
added benefit of dehumidifying and cooling incom- which need cooling a significant part of the year.
ing hot and humid air in cooling months and humidi- This normally requires some percentage of the
fying and warming incoming cold dry air in heating chiller capacity to be in use all year. In many cli-
months. The payback for installing these systems, mates with low wet-bulb temperatures in winter
like the other air-to-air heat recovery systems, is months (usually November-April), water-side free-
highly dependent upon climate and hours of opera- cooling for these spaces, using cooling tower water
tion. In health care applications, however, these sys- as the heat exchange medium, can be easily accom-
tems can have a three- to five-year simple payback if plished. This system can be controlled, based on out-
installed in a retrofit application (although ductwork side wet-bulb temperature and condenser water
for exhaust and outdoor airstreams must be close supply temperature, to use the heat exchanger during
together or a separate heat recovery unit used). If appropriate periods and switch to chiller operation
incorporated into a new design, the simple payback during periods when the wet-bulb temperature and
can be as low as 0.5-1.5 years, especially if the cen- condenser water supply temperature are too high.
tral heating and cooling plant sizes can be reduced This scenario will require the use of variable fre-
due to the installation of the heat recovery system. quency controllers for the cooling tower fans and
It is essential that heat wheel systems be prop- installation of a cooling tower bypass valve to bypass
erly designed to minimize any possibility of cross- the condenser water return from the cooling tower
contamination between airstreams and that the air hot water basins in cold weather.
entering both sides is properly filtered. An essential
This strategy can also be used in design of new
component of heat wheel design requires that the
health care facilities in lieu of an air-side free cool-
outdoor air be introduced with a fan blowing into the
ing economizer, obviously depending upon geo-
inlet side of the wheel (positive) and the exhaust air
graphic location and climate. If this strategy is
removed from the building with an exhaust fan on
the leaving side of the wheel (negative). In this man- installed as part of a new project, the incremental
ner, potential leakage will always flow from the fresh simple payback will usually only be 0.5-2 years,
air (positive) side to the exhaust air (negative) side of depending on the climate. In energy retrofit projects,
the heat exchanger. it normally has a two- to four-year simple payback.
Figures 16-8 and 16-9 illustrate the implementation
It should be noted that the AIA Guidelines for
of this energy conservation strategy.
Design and Construction of Hospital and Health
Care Facilities (section 7.31.D2) prohibits use of a
heat wheel for infectious isolation rooms. 16.6.2 Variable Speed Control of Chilled
Water and Condenser Water
16.6 DESIGN OF ENERGY EFFICIENT Pumping Systems
CHILLED WATER AND CONDENSER
WATER SYSTEMS Many existing health care facilities, especially
those designed over 10 years ago, have chilled water
The energy use analysis discussed earlier in this and condenser water piping systems configured as
chapter indicates that a significant portion of the indicated in Figures 16-7 and 16-9. Such systems are
annual energy costs of a typical hospital is related to parallel pumping systems that are sized for the peak
primary cooling systems. Energy conservative strate- load of the plant and include control strategies for
gies related to the design, operation, and control of chilled water delivery that require all of the pumping
these systems can dramatically reduce the annual to be operated since the cooling coil control valves
energy usage of these systems in both new and exist- are three-way-type bypass valves that do not vary
ing health care facilities. flow to the coil. These systems often operate with a
very low chilled water temperature difference (3-4F
16.6.1 Water-side Free-Cooling
[1.4-1.9C]) at the chillers, requiring several chillers
Economizer
to operate at part-load conditions. Additionally,
Many existing health care facilities have signifi- when fewer than the total number of parallel pumps
cant areas (i.e., patient rooms, ICU rooms, confer- are operating, the operating pumps will flow more
190 HVAC DESIGN MANUAL FOR HOSPITALS AND CLINICS

Figure 16-7 Energy Center chilled water flow diagrampre-retrofit.

Figure 16-8 Energy Center chilled water flow diagrampost-retrofit.


ENERGY EFFICIENT DESIGN AND CONSERVATION OF ENERGY RESOURCES 191

Figure 16-9 Energy Center condenser water flow diagrampre-retrofit.

Figure 16-10 Energy Center condenser water flow diagrampost-retrofit.


192 HVAC DESIGN MANUAL FOR HOSPITALS AND CLINICS

water than required and use more energy than 16.6.3 Variable Speed Cooling Tower Fan
required. Control/Condenser Water Reset
An initial (or retrofit) system design that allows The use of variable speed cooling tower fans to
for variable chilled water and condenser water flow control condenser water supply temperature to the
will reduce pumping energy consumption dramati- chillers improves condenser water temperature con-
cally and will also improve chiller operating effi- trol and is an excellent opportunity to reduce electri-
ciency, since each chiller will be operating at more cal energy consumption. This strategy will have a
efficient loading points more often. These designs two- to three-year simple payback as a retrofit
are illustrated in Figures 16-8 and 16-9. The follow- project and usually less than a year simple payback if
ing strategies should be implemented: implemented as part of a new design. Chillers of
recent vintage can operate with as low as 65-70F
1. Provide new variable frequency controllers for (18.3-21.1C) entering condenser water tempera-
condenser water pumps. Vary the condenser water tures when wet-bulb conditions are favorable, dra-
flow to maintain the desired differential head pres- matically reducing energy consumption of the
sure required by the chiller manufacturer, except chiller. The cooling tower fans should operate to
always maintain the minimum condenser water maintain as low an entering condenser water temper-
flow required by the manufacturer. Use only the ature as possible.
number of pumps required to meet the overall
flow requirements and switch to additional pumps 16.6.4 Variable Speed Chiller Control
as additional chillers are started. The condenser Variable speed control of chillers can also be an
water flow must be maintained at a minimum flow excellent energy efficient design feature if the chill-
rate or minimum chiller differential pressure set- ers need to operate at low load conditions (usually
point as prescribed by the chiller manufacturer. less than 60% of chiller capacity) for a significant
number of hours. Variable speed control of chillers
2. Have the cooling tower fan variable frequency also allows operation at low condenser water enter-
controllers modulate to maintain the coldest con- ing temperatures, improving the efficiency of the
denser water temperature allowed by the chiller chillers. Careful evaluation of this measure requires
manufacturer (usually as low as 68-75F [20.0- an understanding of the load profile on the chillers
23.9C]). with regard to the chiller operating hours at various
chiller load points.
3. Provide new two-way modulating control valves
for each air-handling system and fan-coil unit 16.7 ENERGY CONSERVATION DESIGN
cooling coil, or shut off operation of the three-way OF CENTRAL HEATING SYSTEMS
bypass on the existing control valves (if allowed
by the manufacturer). 16.7.1 High Efficiency Condensing Boilers
4. Provide new variable frequency controllers for High efficiency or condensing heating water
each chilled water pump and vary chilled water boilers can be an excellent energy-conserving design
flow to meet the differential pressure setpoint con- feature in health care facility hot water space heating
trollers located in the chilled water system. If the systems. These boilers can have combustion efficien-
flow reaches the minimum allowed through the cies as high as 88-92%. Since health care facilities
chiller or chillers by the manufacturer, the variable have steam requirements for domestic water heating,
frequency controllers will not vary speed any dietary needs, sterilization, laundries, and humidifi-
lower and the chilled water bypass controller will cation, use of high efficiency hot water boilers will
modulate to maintain the differential pressure set- require separate steam systems for these other hospi-
tal thermal requirements (see 16.6.3). High effi-
point and minimum flow rate through the chillers.
ciency heating water boilers usually come in
When implemented as part of the design of a new relatively small sizes and therefore may be impracti-
health care facility, these strategies will have a one- to cal for use in large health care facilities.
three-year simple payback. As an energy retrofit for an
existing facility, the simple payback usually averages 16.7.2 Boiler Economizers
three to five years, depending upon the hours of oper- Boiler economizers are an excellent energy-con-
ation of the chiller plant and whether air-side or water- serving design feature that can be implemented in
side economizer systems are available. existing health care heating plants as an energy retro-
ENERGY EFFICIENT DESIGN AND CONSERVATION OF ENERGY RESOURCES 193

fit project or incorporated into new heating plant 16.7.5 High-Temperature Hot Water Heating
designs. A boiler economizer is an air-to-water heat Systems
exchanger that takes heat from the exhaust flue gas In large new health care environments, high-
stream leaving the boiler and uses it to preheat boiler temperature heating water systems with large tem-
feed water or other water sources (domestic hot perature differentials (usually greater than 350F
water, etc.). Boiler economizers can usually save [176C]) can reduce pumping horsepower and be an
approximately 3-8% of total heating energy if a con- effective energy efficiency measure.
sistent heat sink is available. Care in design is neces-
sary to ensure that the economizer control prevents 16.7.6 Steam Turbine Generators Versus
condensation in the flue gas exhaust ductwork. Pressure-Reducing Valves
These projects will usually have a two-to four-year
simple payback when implemented as a retrofit In many health care operations, different steam
project and a one- to three-year simple payback pressures are required for different health care func-
when implemented as part of a new design. The pay- tions: dietary, laundry, sterilization, humidification,
back will be dependent upon the operating hours of and space heating and reheating. Higher pressure
the boiler system and the boiler system load profile, requirements may be needed at 60 psig to 80 psig
as well as the ability to effectively use the heat for (414-552 kPa), while space heating and reheating are
another heating load. most usually accomplished with 15 psig (103 kPa)
steam.
16.7.3 Dedicated Steam Boilers for DHW In many large health care facilities, only one
Heating, Humidification, Steriliza- central steam system is used, and multiple pressure
tion, and Laundry Requirements reductions are required to meet the various needs. In
these cases, the use of small steam turbine generators
Health care facilities have consistent thermal for steam pressure reductions from the highest pres-
loads that are not weather related. These include sure to the space-heating pressure may be an effec-
heating for dietary, sterilization, laundry, humidifica- tive energy efficiency opportunity.
tion, and domestic hot water applications. These
loads may frequently require higher operating steam 16.7.7 Variable Speed Pumping
pressures than needed for space heating loads and for Heating Systems
are usually (depending upon the climate) a small per-
Most existing health care facilities have heating
centage of the peak heating plant capacity for space
water piping systems configured as indicated in Fig-
heating and reheating. When this is the case, the
ure 16-11. In a manner similar to chilled water sys-
heating plant will operate very inefficiently during
tems, a three-way control valve setup requires
nonheating months, when very low loads are
constant volume heating water flow even at very low
imposed on large boilers. Therefore, it is often an
loads and operates the boilers at very low tempera-
excellent energy conservation measure to provide a
ture differences, which are inefficient.
separate dedicated boiler system for these non-
space-heating loads and a separate heating system A system design that allows for variable heating
(frequently designed as a hot water system instead of water flow will reduce heating water pumping
steam) for space heating and reheating loads. Pay- energy consumption and improve boiler operating
backs for boiler optimization projects will vary efficiency, since only the required number of boilers
depending upon the ratio of space heating loads to will be operating, and they will be operating more
non-space-heating loads but frequently can be in the efficiently.
range of a three- to six-year simple payback. The following strategies should be imple-
mented:
16.7.4 Central Heating Plant Vs. Distributed
Provide new variable frequency controllers for
Heating Plants
heating water pumps. Vary the flow to maintain
In campus-type health care facilities, an evalua- the desired differential pressure setpoint in the
tion should be made of multiple distributed or pro- heating water piping system, except that the
cess stream plants in lieu of a central large steam/ minimum acceptable flow through the boiler or
high-temperature hot water/energy plant and associ- boilers must be maintained. When minimum
ated distribution system. Use of a large central sys- flow is reached, the variable frequency control-
tem can be energy inefficient, especially during low- lers will not vary speed any lower and the differ-
load conditions, due to distribution losses. ential pressure bypass valve will modulate to
194 HVAC DESIGN MANUAL FOR HOSPITALS AND CLINICS

Figure 16-11 Energy Center hot water flow diagrampre-retrofit.

Figure 16-12 Energy Center hot water flow diagrampost-retrofit.


ENERGY EFFICIENT DESIGN AND CONSERVATION OF ENERGY RESOURCES 195

maintain the differential pressure setpoint and 16.11 FINANCING AN ENERGY


minimum flow rate through the boilers. EFFICIENCY PROGRAM
Provide new two-way valve controls for fan-coil Many financing options exist to assist health
unit heating coils or shut off operation of the care facility owners in implementing energy effi-
bypass on the existing heating control valves. ciency programs in new construction and for retrofit
of existing facilities.
These retrofits are illustrated in Figure 16-12.
When implemented as part of a new project, this Internal Financing
strategy will have a one- to two-year simple payback.
This method often proves to be the most cost-
In energy retrofit case studies, the simple payback is
effective approach to energy savings. The building
usually three to six years.
owner, manager, or occupant simply makes a deci-
sion to finance the modifications internally, taking
16.8 DESIGN OF ENERGY EFFICIENT
advantage of all the savings and assuming all the
BUILDING ENVELOPES
risk.
Energy efficient building envelopesconsider-
ing items such as orientation, building shape, glazing Shared Savings Contracts
selection, insulation, passive solar features, shading, Under this approach, independent contractors
reflection, and effective use of materialsshould be typically install energy-related modifications at their
considered as part of any new building design strat- expense. The building owner then pays a prearranged
egy. Incorporating these features in a new building fee, which is usually related to the savings achieved.
often has an infinite return on investment, since they The length of these contracts runs from several years
will reduce annual operating costs with minimal or to as long as 20 years. The terms and conditions of
no increase in initial building construction costs. the contract must be carefully documented in
Energy retrofit projects incorporating these features advance. In particular, methods of determining
often have very long paybacks if viewed as only an energy savings and of accounting for other influ-
isolated effort. Paybacks can be immensely ences on energy consumption must be carefully and
improved, however, if envelope retrofits are incorpo- precisely described. In using this approach, there is a
rated into a boiler or chiller replacement project need for caution regarding potential fraud and over-
where the envelope project permits purchase of pricing of construction costs since the contractors
smaller central heating or cooling equipment. have complete control of the assigned prices.
16.9 OPERATIONS AND MAINTENANCE Guaranteed Savings Contracts
Continuous maintenance of building HVAC sys- These are similar to shared savings contracts,
tems (including control systems) is essential to except that the costs of the modifications are speci-
energy-conservative operation of a health care facil- fied up front. Energy savings are guaranteed, usually
ity. If systems are allowed to operate in an un-main- on an annual basis. The owner can pay for the retrofit
tained state, energy-efficient features of the design at the beginning of the contract and finance it over a
will degrade and the energy consumption of the period of years or have the contractor finance it with
facility will increase. See Chapter 14 for operations repayment out of the savings. If greater savings are
and maintenance procedures. achieved, some contracts require that a bonus be paid
to the contractor. If less than the guaranteed savings
16.10 COMMISSIONING/ are realized, the owner is reimbursed for the differ-
RECOMMISSIONING ence. The owner should enter into these agreements
Commissioning new health care HVAC systems, carefully, with an understanding of the financial lia-
or recommissioning existing HVAC systems, almost bility if the savings do not materialize and the con-
always provides a quick payback from energy sav- tractor is unable to make good on the guarantee.
ings. The commissioning process is even more With this type of contract, the performance record of
essential today than in the past because of the use of the contractor should be examined.
sophisticated computerized strategies to control
health care HVAC systems. Subtle changes in these Demand Side Management
strategies can have significant effects on building Demand side management (DSM) programs are
energy consumption. See Chapter 15 for commis- offered by many utilities and commonly subsidize
sioning and recommissioning information. the installation of energy modifications. These pro-
196 HVAC DESIGN MANUAL FOR HOSPITALS AND CLINICS

grams usually take the form of rebates to contractors the beginning of a project to ensure that the highest
or building owners for the installation of specified potential rebates are obtained.
equipment, and are often carried out by subcontrac-
tors or unregulated subsidiaries of utilities. The pur- Government Programs
pose of these programs is to reduce demand or There are numerous federal, state, and local
consumption of the particular form of energy sup- government programs that provide subsidies or tax
plied by the utility. Contact the applicable utilities at credits for certain energy modifications.
APPENDIX A
MANAGING CONSTRUCTION AND
RENOVATION TO REDUCE RISK IN
HEALTH CARE FACILITIES
A.1 INTRODUCTION asked regarding construction projects or mainte-
Risk implies a probability that harm, injury, or nance efforts:
disease will occur. Such a probability is obvious
Which patient groups and employees are sus-
when one takes risks beyond reason, for example,
ceptible to risks from the proposed construction
accelerating an automobile to 100 mph (161 km/h) in
process?
a 30-mph (48 km/h) speed zone. Risk management
in todays health care facilities is usually responsive Which ventilation systems may be involved and
to medical-legal considerations in patient care relat- how close are they to the construction?
ing to patient harm from medication, surgical proce- What effect on pressure relationships in the
dures, or misdiagnosis. Safety relating to building may occur when ventilation systems
construction and renovation in health care facilities are interrupted?
has focused upon fire and life safety and rarely on Are the current ventilation controls operating
infection control. The hazard of ill health to a patient according to original design intent?
is presented to the health system team that defines an Will supplemental ventilation be required during
illness and returns the patient to good health. During the project?
treatment, patients are exposed to a variety of haz- How will fire code and interim life safety
ards common to the respective diagnostic and thera- requirements during construction affect ventila-
peutic treatments. Health care is truly an industry of tion requirements?
hazard management. The health care professional Is special ventilation for infectious disease pre-
must understand the extent of the hazards and imple- vention (tuberculosis or aspergillosis) affected
ment procedures for patient and employee safety. during construction?
Construction and renovation are continuous in What impact will noise and vibration have on
health care facilities as organizations upgrade utili- occupants? Will sound or vibration affect sensi-
ties, communications, and diagnostic/therapeutic tive procedures or equipment?
equipment. As medical technology advances, more How will perceptions affect patients during vari-
hospitals are providing modern treatment modalities ous noisy or odorous procedures?
for severely ill individuals. Immunocompromising Is there a history of water damage in renovated
treatments that result from this advancement make areas?
opportunistic infectious environmental microbes an
emerging threat to patients. It is necessary, therefore, Project planning can find and implement meth-
to recognize the risks and investigate the effects on ods and procedures to reduce the risks of construc-
the users of health care facilities (AIA 2001). tion hazards. Such risks can be circumvented by
good communication. That generally means two-
A.2 RISK ASSESSMENT way, routine communication with the occupants and
Health care risk assessment must be based upon a means to question or complain to the construction
potential for harm to patients and occupants (Streifel management. This communication must not need-
and Hendrikson 2002). These questions should be lessly interfere with a project but must be taken seri-

197
198 HVAC DESIGN MANUAL FOR HOSPITALS AND CLINICS

ously by the designated owners representative so Employee at-risk groups include:


that hazards can be controlled. Once a hazard is rec-
ognized, a procedure should be in place for investi- Employees with solid organ transplants,
gating it immediately or temporarily stopping the Atopic/allergic employees,
project (Streifel 1997). HIV-infected employees.

A.3 PLANNING Areas with chemical or physical hazard include:


As a project is conceptualized, a plan is started
Medicated aerosol treatment areas,
to program the project for the users. The decision to
Vapor or fumes from disinfection or steriliza-
build new or renovate is often made at this stage. The
tion,
impact of a renovation on current occupants should
Electrocautery smoke plume,
be considered. Factoring in such concerns at this
Laboratory hoods,
stage is up to the members of the planning team.
Surgical pathology/morgue.
Often the program plan does not fully consider the
impacts on occupants of a health care building. The Mechanical system interventions with high risk
team should be multidisciplinary and capable of potential include:
understanding the impact of construction on build-
ings. This includes outages necessary for utility Ventilation maintenance or repair,
work, how work will be conducted to modify Fire management testing,
mechanical systems, ventilation management in crit- Plumbing outages.
ical areas during phasing, barrier management for
airflow, and traffic control. The cost of such planning Planning for construction demolition must
and subsequent implementation of the control mea- address:
sures is always a factor that administrators consider
important to the feasibility of a project. Although at Dust control,
first imposing, the costs can be controlled by appro- Internal versus external projects,
priate experience and preplanning. A contractor Filter integrity.
experienced in health care construction has the
opportunity to develop a routine, which includes rec- A.4 ENVIRONMENTAL ASSESSMENT
ognizing and handling hazards through routine inter- The patient care environment should be evalu-
ventions. For example, a contractor assigned to ated before construction to determine if deficiencies
replace a CT scanner in Diagnostic Radiology under- exist in critical areas. Ventilation of protective and
stands that substantial barriers are needed along with airborne infection isolation areas is essential to
portable HEPA filtration for certain hospital patients. ensure infection control. Measles, chicken pox, and
The bid acceptance procedure should not be based tuberculosis are airborne infectious diseases that are
entirely upon low bids. The bid procedure should be disseminated when droplets from sneezes or coughs
based on experience in health care construction and evaporate to create droplet nuclei (which are less
ability to work in that environment. than 5.0 m in diameter). These droplet nuclei are
concentrations of infectious particles, which are
A.3.1 At-Risk Groups/Areas/Activities aerodynamically buoyant and remain airborne for
long periods. Buoyant airborne particles increase the
The risk from environmental, opportunistic probability of inhalation (University of Minnesota
microorganisms is paramount for certain patients. 2001).
Current medical practice can include procedures that Airborne environmental-opportunistic spore-
severely compromise a patients ability to resist forming fungi such as Aspergillus fumigatus are a
infection. threat to severely immunocompromised patients.
Patient groups at high risk can include: These patients are being treated for malignant hema-
tological or solid tumor disorders, solid organ trans-
Patients who receive solid organ transplants, plants, or other immune-deficient treatments that
Premature birth babies, render them susceptible to common airborne fungi.
Patients who receive bone marrow transplants, The case fatality rate for aspergillosis in these patient
Oncology patients, groups is high due to the difficulty in diagnosing and
Patents who receive steroid therapy. treating this disease. These fungi are common
MANAGING CONSTRUCTION AND RENOVATION TO REDUCE RISK IN HEALTH CARE FACILITIES 199

indoors and outdoors, and it is a challenge to exclude cially ventilated patient care areas are occupied
them from the critical patients environment. (ASHRAE 1999a).
The location of diffusers and the type of air
A.5 VENTILATION CONTROL throw are also important in managing airborne par-
Rooms for airborne infection isolation (AII) ticles and controlling gas or fumes. Open doors and
should have definable ventilation parameters. These windows can negate special ventilation requirements
parameters include room air exchanges, filtration, for infection control. Sufficient outside air should be
and airflow direction (pressurization). The parame- provided to ensure recommended fresh air require-
ters for these rooms have been recommended as part ments.
of prudent practice. The criteria that define the
benchmark parameters for these special ventilation A.5.2 Pressure or Airflow Direction
rooms are important to understand. The differences Room pressurization is often described as airflow
for AII rooms and PE rooms pertain to exhaust for in or out of respective special ventilation areas.
all air in the AII setting and filtration requirements These special ventilation rooms should have self-clos-
for the supply air in the PE room, or, if air is recircu- ing doors to ensure the special ventilation require-
lated from the AII room, it should be HEPA filtered. ments can be maintained. Pressure criteria should be
The following is a list of recommended parame- defined via a performance range. The range for special
ters for all special ventilation rooms: ventilation rooms should be between 0.01 and 0.03 in.
w.g. (2.5 to 7.5 Pa). Maintaining such pressure
Air exchanges per hour: >12
requires a tight room and an offset of supply or
Filtration: 90% dust spot efficiency or MERV 14
exhaust/return ventilation. The room tightness can be
Pressurization: 0.010.03 in. w.g. (2.5 to 7.5 Pa)
defined in square feet of openings. For example, if
filtration verification
there are 0.5 ft2 (0.004 m2) of openings, there should
It is essential for the protective environment that be an offset of 125 cfm (59 L/s) to provide 0.01 in. w.g.
a reduction of particles be verified after filtration. If a (2.5 Pa) pressure differential. Leakage, which can pre-
HEPA (99.97% efficient for a 0.3-m particle) filter vent proper pressurization, can occur around plumb-
is used, PE room criteria should be provided. These ing penetrations, light fixtures, and windows.
criteria would establish a rank order of particle con- These ventilation parameters should be evalu-
centration. The analysis can be of viable or nonvia- ated and altered to conform to infection control crite-
ble particles. The viable particle is important, but the ria before a project begins in critical health care
incubation time to get the data requires more than areas. Too often, administrators who are unfamiliar
seven days for analysis. What good are the data after with the infection risk of construction and mainte-
that time should be the question. Efforts to bench- nance activities make uninformed management deci-
mark performance before occupancy are ideal when sions that impact safe patient care.
using viable culture methods. Using comparison
sampling of areas, results should indicate that areas A.6 PROJECT IMPLEMENTATION
with the highest level of filtration have the lowest A project is conducted either internally or exter-
particle countsboth viable and nonviable. The nal to a facility. The impact of any project must be
advantage of using an optical or laser particle categorized. A project risk assessment should
counter is real-time data retrieval. Particle-count include the impact of demolition and excavation on
information does not indicate whether airborne parti- the integrity of the buildings exterior and building
cles are opportunistic microbial agents, but a particle penetrations. If windows are deteriorating, for exam-
count will demonstrate particle removal that ensures ple, they should be sealed. Air filtration should be
ventilation integrity. ensured before a project begins. Filters that are
improperly installed in a filter housing can allow air
A.5.1 Room Air Exchanges to bypass the filter. During excavation, particles can
Air exchanges for critical rooms should be as pass significantly around improperly maintained fil-
specified by design guidelines established by the ters and cause patient infections. Methods to deter-
American Institute of Architects and the American mine filter leaks have been developed using particle
Society of Heating, Refrigerating and Air-Condition- counters to ensure that the filtration efficacy is simi-
ing Engineers, Inc., for health care construction. lar to the filter rating. During internal, and at times
Refer to Table 4-1 in this manual for air exchange external, projects, barrier protection is important for
rates. These rates should be site-verified before spe- preventing movement of dirty-to-clean construction
200 HVAC DESIGN MANUAL FOR HOSPITALS AND CLINICS

air. Therefore, a smoke barrier is essential for pre- ened construction manager for the unusual
venting smoke and construction aerosol movement occurrence (Kuehn et al. 1996).
into critical health care spaces. Due to the chimney
effect, unfiltered air can enter high-rise buildings via A.7 COMMUNICATION
underground utility tunnels during demolition and Communication during construction should be
excavation. considered a given, but there are essential elements
that must be defined. For example, who has the
Risk assessment in anticipation of emergencies
authority to stop a project and under what condi-
is difficult. When a gas leak occurs, what should be
tions? Such issues must be addressed before a
done if patients are receiving invasive therapies, such project begins. Who will handle complaints about
as kidney dialysis or oral surgery? Such accidents the project? The complaint might be about excessive
happen during complex demolition projects in areas vibration affecting microscope-assisted brain surgery
where plans showing buried utilities are not readily or an odor in the bone marrow transplant unit. Which
available. Fires, water main breaks, and crumbling one is potentially an infection control issue? What
buildings can all contribute risks to complex demoli- response is appropriate during such conditions? The
tion and construction projects in health care settings. project team should develop construction implemen-
An infection control tool in the form of a check list tation logic before project work begins. The team
(Table A-1) should be developed to provide guidance should consist of infection control, safety, construc-
and documentation for respective projects. Commu- tion administration, facilities management, and con-
nication and planning will help to prepare an enlight- tractors representatives. The team should prepare a

Table A-1. Sample Infection Control Monitoring Checklist


Infection Control Yes No Comments
All barriers are in place and integrity is maintained.
Airflow is maintained from clean to dirty.
There is compliance with traffic patterns.
There is compliance with covering clothing requirements when
appropriate for infection control.
Equipment is in place to prevent airborne particles from migrating to
PT areas: portable HEPA filters, HEPA filter vacuums, exhaust fans,
self-closing construction entrance doors, exhaust fans, or debris chutes.
Doors closed to project and properly signed.
Appropriate debris transport: covered cart, dedicated elevator,
designated route, etc.
All windows, doors, and debris chutes to the outside are secured when
not in use.
Carpet or other track-dirt compliance aids are in place at the doors
leading to the hospital/clinic/support space. Housekeeping is notified
for as needed cleaning.
Areas are cleaned at the end of the day; trash is removed.
Water leakage is handled as it occurs in occupied clinical areas. There is
immediate notification of facilities management. Immediate action is
taken to ensure drying in less than 72 hours.
Pest control: no visible signs of mice, insects, birds, squirrels, or other
vermin.
Roof protection is in place.
Other Notes:
MANAGING CONSTRUCTION AND RENOVATION TO REDUCE RISK IN HEALTH CARE FACILITIES 201

safe plan or project implementation for the shared the bid documentation. Disputes regarding critical
mission of occupant protection from certain expo- ventilation issues should be avoided by providing
sures due to a disrupted health care environment. Bid direction to the architect, construction manager, and
document and specification language should be con- contractors as part of the commissioning process.
sistent with expectations. Radio and phone contact The owner should provide commissioning informa-
must be available to critical team members to prevent tion from the perspectives of infection control and
confusion and to facilitate corrective action when safety. The AIA, and the CDCs Guideline for Envi-
emergencies occur. ronmental Infection Control (2001), address infec-
Perception plays a large role in how people react tion control design and construction issues (AIA
to risk. If someone in an operating room smells 2001; JCAHO 2002).
something like smoke, the first instinct is avoiding
risk to the surgical patient. This perception usually A.9 LEGAL ISSUES
results in a delay in the procedure and ultimately This contentious topic must be addressed. If liti-
causes problems with scheduling in a busy operating gation occurs due to perceived or real infection con-
room. If, however, the construction management trol factors, resources will be used either to defend or
notifies the OR control supervisor that odors due to accuse. Recently, a lawsuit that resulted from con-
welding may occur on a given shift, the issue could struction and fungal infection problems was settled
be understood and schedules maintained. This out of court in Massachusetts (Verdicts and Settle-
applies to noise and vibration, construction traffic, ments 1999). The hospital settled because critical
utility outage, and ventilation adjustment in almost environmental factors were not acted upon as a result
any area of a health care facility. of construction-related issues associated with envi-
Construction meetings during most projects are ronmental testing, construction practice, and air bal-
generally routine. Who participates in the meetings ance. Plaintiffs and defendants are currently
and the protocols for information dissemination, litigating to resolve disputes through the use of
however, are not routine. These issues vary accord- definable environmental parameters. Neglect or
ing to the size of the project. Reducing risk by using competence in the management of engineering con-
clearly understood communication pathways will trols in the health care environment is often subject
help to avoid confusion and help focus on logical to legal interpretation (Laurel et al. 1999).
ways of reducing risk when and if an emergency In construction and renovation, it is often chal-
develops. lenging to provide a finished product on time. The
dynamic nature of health care and the essential ele-
A.8 COMMISSIONING ment of safety in continuously occupied facilities
Specially ventilated areas should have their provide even more challenge. The concepts of risk
operating parameters verified before acceptance by assessment, communication, and emergency prepa-
the owner. Commissioning can accomplish such ver- ration are essential in providing a safe environment
ification. Verification requirements should be part of for patient care (Davis 1998).
APPENDIX B
DISASTER MANAGEMENT
B.1 INTRODUCTION Healthcare Organizations advises in its Standards
overview that planning and designing is consistent
Health care organizations are subject to both
with the hospitals mission and vision (JCAHO
internal and external disasters that might affect an
1997).
institutions mechanical systems to the point of dis-
rupting services. Hospital reactions to internal disas- Emergency protocols are set into motion by a
ters such as fire are published in NFPA 101, Life designated member of the hospital staff. Trauma
Safety Code (NFPA 2000). JCAHO Standard EC.1.4 disaster is immediately evident by the size of the
requires that a hospital plan address emergency man- occurrence and the number of people involved. A
agement (JCAHO 2000). Item l states, An alterna- recognition of biological disasters, on the other hand,
tive means of meeting essential building utility needs might be delayed. A cluster of patients who have
(for example, electricity, water, ventilation, fuel bizarre or unexplained symptoms might trigger the
sources, medical gas/vacuum systems) when the hos- suspicion of biological disaster. Once disaster is
pital is designated by its emergency plan to provide declared, necessary personnel must be contacted to
continuous service during a disaster or emergency. come to the hospital. If ordinary communication
The AIA Guidelines, Section 1.4, addresses disasters routes are out of commission, alternate emergency
that affect the hospital itself (AIA 1996). communication capabilities must be available. In
some cases, local law enforcement agencies or hos-
An external or community disaster such as an
pital maintenance vehicles may be needed to bring
earthquake, train wreck, chemical spill, bioterrorism,
personnel to the hospital.
or infectious epidemic presents an added set of con-
Traumatic, chemical, nuclear, and biological
siderations, primarily the designation of emergency
disasters will not preclude using normal hospital treat-
spaces to serve larger than usual numbers of victims.
ment areas, unless (1) available hospital beds and
Hospital staffs are remarkably resourceful and inno-
areas are inadequate to handle the number of victims
vative when confronted with emergencies; neverthe-
or (2) the hospital itself is damaged by the disaster, as
less, their provision of care can be greatly aided if
in seismic or terrorist disasters. Emergency stores
spaces such as lobbies and meeting rooms have
(water, food, medication, fuel) might be required if a
mechanical capabilities already in place that allow
disaster occurs within the hospital or to a portion of the
them to function as emergency treatment areas.
hospital itself, if ordinary external supply mechanisms
Some communities may be located near chemical
are hindered, or if patients from a damaged hospital
plants, nuclear plants, or other industrial complexes
must be evacuated to a host hospital.
that could predispose the community to contamina-
tion or to industrial injuries. Terrorist attack, explo-
B.2 TERRORISM
sion, biological threat, chemical spill, or multiple
shootings can strike any place, possibly in areas The events of September 11, 2001, have brought
where few suspect such threats. Hospital governing the realities of terrorism to our doorstep. Disaster
bodies and communities can decide if their hospitals preparation for our institutions and our communities
are to be prepared to respond to community disas- is no longer an afterthought. Community facilities
ters. The Joint Commission on Accreditation of such as schools, buses, and hospitals are likely tar-

203
204 HVAC DESIGN MANUAL FOR HOSPITALS AND CLINICS

gets of terrorism. Terrorists have a tendency to hit the bon filtration would protect from chemical attack.
most vulnerable, the most populous, and the most Does the possibility of such attacks warrant the
emotionally charged targets. Many governmental expenditures for sophisticated filtration systems and
and institutional committees are presently working permanently increased fan power for all hospitals?
on recommendations for protection. In the mean- Perhaps the air intake could simply be closed off
time, the following aspects of the problem can be until the cloud passes. Perhaps minimally recirculat-
considered, as well as the recommendations in the ing air could be augmented by bottled oxygen.
following sections. Detecting noxious air and predicting hospital
Basically, three types of terrorism delivery involvement would be necessary to institute these
routes are available: (1) delivery from afar (nuclear, measures. Purging (noxious air removal) from the
chemical, biological bombs); (2) delivery from hospital is a valid defense, particularly in cases of
within (sabotage or contamination of water, food, or localized contamination. Ordinary smoke control
air) where the culprits try to save themselves; and (3) systems and defend-in-place strategies can be used
delivery by suicidal fanatics. for purging, but this would require planning and edu-
Prevention is the most effective remedy for ter- cation of personnel.
rorist activity, just as prevention is the most effective The second case, delivery from within, presents
remedy for disease. In the case of delivery from afar, a different set of considerations. The recent anthrax
military/intelligence interception is the most effec- disaster taught a very valuable lesson: in-place deliv-
tive protection. If a terrorist organization has gone to ery systems can be used for transmitting deadly
the trouble and the expense of inserting many opera- microbes as well as explosives (the Unabomber).
tives into an area, it is unlikely that it would destroy Irradiation of mail will probably protect us from
its own organization by a generally lethal airborne microbe dissemination. Irradiation is a possible pro-
attack. On the other hand, suppose that such insanity tection for all mail and package delivery systems, not
does indeed exist and that smallpox is released into only for the U.S. Mail. Hospitals can protect them-
the air of a community (terrorist operatives might selves by ensuring that air intakes are inaccessible to
consider themselves protected by immunization). the public, ventilation in public areas is isolated,
The first problem would be detection. There are, as mechanical rooms are protected by heightened secu-
yet, no electronic sensors that detect smallpox in the rity, and supplies (water, food, medicines) are pro-
air. Detection would result from recognition that a tected by heightened security. The ability to purge
cluster of unusual cases is smallpox, diagnoses that affected areas is advisable.
will not be easy or rapid. Instituting protective mea- The third case, delivery by suicidal fanatic,
sures at this point would be shutting the barn door would initiate the same hospital responses as the first
after the horse has gone. Should this cluster of two cases: detection, identification, notification of
patients be evacuated? Should the hospital be evacu- authorities, isolation if the malady is communicable
ated? Should the community be evacuated? Evacua- (or undiagnosed), treatment, immunization in cases
tion raises the possibility of infecting other, such as smallpox, prophylactic antibiotics in cases
previously uninfected, areas. This raises the specter such as anthrax, and possible evacuation if the com-
of quarantine. Should the hospital outside air intake munity is no longer viable. It may be less likely that
be protected by HEPA filtration, by carbon filtration, suicide fanatics can be recruited to undergo a slow
or by UV radiation? The original cluster of patients and painful entry into paradise by disease rather than
contracted the disease outside the hospital. All of the by explosion.
hospital workers left the hospital and circulated in
the community during the several days between the B.3 DISASTER CLASSIFICATION
release of the virus and its detection. Very little
This classification is developed for this publica-
would be achieved by sterilizing the hospitals out-
tion and is not an institutionally recognized classifi-
side air intake. In the case of smallpox, the disease
cation system.
enters the hospital through the emergency room, not
through the air intake. Universal immunization
B.3.1 Internal Disasters
seems a better option than equipping all hospital out-
side air intakes with fan-power-consuming HEPA An internal disaster is one that affects the hospi-
and carbon filtration. tal itself, its patients, its systems, its personnel, and/
On the other hand, a cloud of contamination or its spaces. A fire within the hospital, for example,
could drift over the hospital. HEPA filtration would is an internal disaster. A hurricane, on the other hand,
protect the hospital from microbial attack, and car- is an external disaster, but it might affect internal
DISASTER MANAGEMENT 205

hospital systems such as the power supply. In such a Chemical disasters


case, internal disaster contingencies would be initi- a. Accidental (train wreck involving chemical
ated, and the emergency generators would be tank car)
switched on. The following are possible internal b. Terrorist (water supply contamination, air-
disasters that require planned emergency and/or borne/explosive, food contamination)
backup planning:
1. Fire Biological disasters
a. Unidentified severe illness, possibly infec-
2. Power disruption
tious
3. Water supply disruption or contamination b. Epidemic (waterborne, airborne, insect vec-
4. Ventilation system failure or contamination tor)
5. Heating system failure c. Terrorist (water supply contamination, air-
borne/explosive, food contamination)
6. Fuel supply disruption
7. Medical gas system disruption Nuclear disasters
8. Steam supply disruption resulting in inoperable a. Accidental (industrial)
autoclaves and humidification failure b. Terrorist
9. Nosocomial infection outbreaks (possible pressur- Evacuation disaster
ization failure)
a. Accommodation of patients and staff from an
10. Loss of internal communications evacuated health care facility
11. Loss of external communications
B.3.2.1 Trauma Disasters
12. Structural failure (earthquake, flood, tornado,
Readiness for trauma disasters is the basic
explosion)
and minimum degree of preparation for disaster
13. Supplies deficit (food, drugs, linens, medical readiness, and, it is mandated by the JCAHO
gases, blood products) Hospital Accreditation Standards (1997). A sud-
14. Terrorist attack on the hospital itself (chemical, den volume of trauma victims, a volume larger
biological, explosive) than can be accommodated by the hospitals
normal emergency facilities, requires a triage
15. Elevator failure
area, treatment areas (first aid, medical, surgical,
See Paragraph 1.4.C, 1996-97 Guidelines for and casting), sterilization capability, observation
Design and Construction of Hospital and -Health- space, convalescent space, in-hospital communi-
care Facilities (AIA). cations, extra-hospital communications, in-hos-
pital transportation, extra-hospital
B.3.2 External Disasters transportation, and supplies of water, medicines,
Disasters such as large or multiple vehicular cots, stretchers, food, fuel, clothing, medical
accidents, accidental release of gaseous chemicals gases, and first aid.
into the community, and multiple trauma due to natu- B.3.2.2 Chemical Disasters
ral disasters and large fires can happen in any com-
munity. Some communities may be near chemical Readiness for chemical disasters requires
plants, nuclear plants, or other industrial complexes. the basic (trauma) preparations listed in B.3.2.1
plus decontamination (wash) and special waste
External disasters might produce so many victims
containment capabilities. Preparation of the
that the normal hospital treatment areas and proto-
decontamination area is clearly outlined in Man-
cols are overwhelmed and alternate emergency
aging Hazardous Materials Incidents, Volume
spaces and procedures must be used. The following
II, Hospital Emergency Departments (USDHS
is a suggested classification of external disasters: 1992), obtainable on the U.S. Centers for Dis-
ease Control and Prevention web site: http:/won-
Multiple trauma disasters
der.cdc.gov/wonder/prevguid/p0000019/
a. Accidental (vehicular pile-up, hurricane, tor- p0000019.asp.
nado, fire, earthquake) Although diseases due to chemical expo-
b. Terrorist (explosion) sure are not contagious, ventilation isolation is
206 HVAC DESIGN MANUAL FOR HOSPITALS AND CLINICS

advisable to prevent entry of deleterious chemi- vices. Special areas are obviously not
cals from contaminated clothing, debris, or air. required, but communication and transporta-
tion (of patients) capabilities are critical. Ele-
B.3.2.3 Biological Disasters vator service in a multistory building is
essential.
Unidentified severe illness, possibly infec-
tious (such as Hanta or Ebola viruses): This b. Evacuation Reception. A nearby hospital may
classification is more of a potential disaster become nonfunctional and need to evacuate
when it is recognized than a disaster that its patients to a receiving facility. That facility
involves many victims. Lack of recognition may already be full with its own patients and
and lack of proper handling can then predis- therefore require the use of alternate patient
pose a hospital to a disaster that involves care spaces. These spaces require all of the
many victims, particularly hospital person- mechanical and supply services that are nec-
nel and patients. Initial isolation and height- essary in ordinary treatment and convalescent
ened suspicion are paramount in this areas. Communication and transportation
situation. See Bioterrorism Readiness Plan. capabilities are paramount.

Epidemic (Hospital Infection Control Prac- B.4 SPACE DEFINITIONS


tices Advisory Committee 1996): An epi-
demic is a disaster that involves multiple B.4.1 Triage Space
victims of a possibly contagious disease.
Victims of a disaster are brought to a triage area
This situation requires basic preparations
where those who have the most life-threatening inju-
(B.3.2.1) as well as isolation protocols,
waste isolation, and separate ventilation. ries are identified for immediate treatment. In
Patients should be isolated from the general nuclear exposure and chemical exposure, victims
hospital population but not necessarily from must first be brought through a total body cleaning
each other; thus, a single large space with and clothing disposal area before entering triage.
multiple beds (and screens) can be used Workers in the bathing area must have appropriate
(see Simon 1997). protective clothing. The triage area of a hospital is
usually the emergency room. The emergency rooms
Bioterrorism (Simon 1997): The prepara- waiting room and/or other hospital waiting rooms
tions for a bioterrorism disaster are similar can be used for additional triage space if they are
to those for chemical disasters. Basic prepa- accessible to the outside and are equipped with iso-
rations (B.3.2.1) plus decontamination lated ventilation, electricity, water, communications,
(wash) procedures, waste containment, and etc. (see Sections B.5.1 to B.5.6).
ventilation isolation are required.
B.4.2 Wash Area (Decontamination)
B.3.2.4 Nuclear Disasters
Nuclear disasters require total body washing and
Wash/decontamination facilities are the total clothing change of all exposed victims (ambula-
central component of nuclear disaster readiness. tory and non-ambulatory) whether admitted into the
As in chemical disasters, specialized protective facility or not. Decontamination facilities are located
gear and clothing are necessary for workers in
outside the facility and can be collapsible tent-like
the wash area, in this case, radiation protective
enclosures.
gear and clothing. As in chemical disasters,
everyone in the community exposed to the radia- Total body washing and new clothing are also
tion must be decontaminated and supplied with necessary in massive chemical exposures and in ter-
safe clothing. Basic preparations (B.3.2.1) and rorist biological exposures. Special protective gear
nuclear waste containment capabilities are also and clothing are necessary for the wash area person-
required. Communication with outside authori- nel. Note that not only will victims require decon-
ties and community rescue teams is essential tamination but so, too, will those in the community
(FEMA 1984; Ricks 1984). who have responded to the emergency, such as fire-
men, EMS personnel, and other civil agents.
B.3.2.5 Evacuation Disasters
a. Hospital Evacuation. The hospital may B.4.3 Waste Isolation
become dysfunctional and require evacuation Trauma disasters: Waste/clothing can be dis-
due to destruction or failure of internal ser- posed of in the usual manner.
DISASTER MANAGEMENT 207

Chemical disasters: Waste/clothing must be B.5 REQUIRED SERVICES IN


held in such a manner that all personnel are safe EMERGENCY AND DISASTER
from contact with the waste. In chemical terrorism, The following are the initial emergency priori-
the waste must be retained and made available for ties in managing a critically ill or injured patient:
examination by the proper authorities.
1. Establish an airway (breathing and heartbeat, i.e.,
resuscitation),
Nuclear disasters: Waste/clothing must be held
2. Stop bleeding,
in a radiation-shielded area and disposed of later in a
manner dictated by the proper authorities. Incinera- 3. Establish vascular access (fluids, blood products,
medications),
tion is not an option because of the possibility of
introducing radioactive molecules into the air. 4. Establish vascular stability (treat shock),
5. Diagnostic procedures (monitoring, X ray, ECG,
Biological disasters: In an epidemic of an iden- lab),
tified disease, waste/clothing can be disposed of 6. Surgery and/or treatment.
according to standard isolation and disposal tech-
niques. In bioterrorism, waste must be held isolated All mechanical services necessary for these pro-
for examination by proper authorities. In the case of cedures must be in place for optimal and successful
unidentified infective agents, waste must be held iso- emergency response.
lated for examination by proper authorities and by
B.5.1 Power
appropriate laboratories.
Guidelines exist for design of emergency power
grids (NFPA 2000; JCAHO 2000; AIA 2001). Power
B.4.4 Isolation Space
must be supplied to all of the designated auxiliary
A space other than the triage area and the gen- emergency treatment areas. The triage area requires
eral hospital can be designated for isolation of power for light, ventilation, communication, diag-
patients thought to be infectious. The designated iso- nostic equipment, suction machines, defibrillators,
monitors, portable X-ray machines, IV pumps, respi-
lation area should have total exhaust and negative
ratory therapy equipment, and possibly for steriliza-
pressurization. Care must be taken that air is
tion equipment. Power outlets for these uses must be
exhausted well away from habitable areas.
available in spaces designed for alternate treatment
areas (see Paragraph 1.4.A1, 1996-97 Guidelines for
B.4.5 Treatment Space Design and Construction of Hospital and Healthcare
Facilities).
Ordinarily, emergency rooms and operating
rooms serve as treatment areas and should be suffi- B.5.2 Water
cient for serving as disaster treatment areas, unless
Uncontaminated water is necessary for washing
they are damaged by the disaster. Delivery rooms can
(hands, patients, instruments, equipment), food prep-
be taken over as disaster treatment and operating
aration, sterilization, and possibly medicinal prepa-
rooms. If the hospital medical staff is large (more
ration. Disruption or contamination of the ordinary
available doctors than existing treatment rooms),
hospital water supply requires access to an alternate
auxiliary areas can be designated as disaster treat-
supply. This alternate supply can be from a well or
ment areas and should be equipped with clean air
from storage tanks. The capacity should be sufficient
and emergency power.
to last for four continuous days (see Paragraph 1.4.C,
Sterilization capability (autoclave) is a critical 1996-97 Guidelines for Design and Construction of
component of the treatment area. Designated auxil- Hospital and Healthcare Facilities).
iary treatment areas as well as existing treatment
areas must have access to fail-safe sterilization capa- B.5.3 Ventilation
bility. This may consist of an emergency autoclave Paragraph 7.9D2, 1996-97 Guidelines for
fueled by the emergency electrical system or by liq- Design and Construction of Hospital and Healthcare
uid petroleum. Gas sterilization systems are unac- Facilities requires that the triage area (of the ordi-
ceptable as the only method of sterilization in nary hospital emergency facility) be designed and
disaster situations because of the increased time they ventilated to reduce exposure of staff, patients and
require for sterilization and for evacuating gas. families to airborne infectious diseases. This is best
208 HVAC DESIGN MANUAL FOR HOSPITALS AND CLINICS

accomplished by 100% exhaust and transfer or by of the elevators may be damaged or not functioning
intake of uncontaminated air. Recirculating 99.7% during an emergency. One cannot predict which ele-
HEPA-filtered air is an acceptable alternative but vators will fail.
would require more fan power. Extra-hospital transportation capability is neces-
sary to bring patients into the hospital setting, to
B.5.4 Sterilization transfer patients to other facilities, to bring in sup-
Sterilization can become a problem if the hospi- plies, to transport laboratory specimens, and to bring
tals steam generation capability is interrupted. Auto- in extra and off-duty staff.
claves that use an alternative energy source are
B.6 SUMMARY
required. Sterilization is necessary for surgical
instruments, fluids, linens, and reusable equipment.
B.6.1 General Principles of Management
B.5.5 Communication The mechanical services required to manage the
various types of disasters are remarkably similar.
Communications and transport of data within a
Several general considerations are helpful in plan-
hospital are very important to day-to-day operations
ning:
but become critical during extraordinary circum-
stances such as a disaster. 1. Designate alternative diagnostic and treatment
In a disaster, extra-hospital communications areas for use when ordinary hospital areas are
overrun or out of commission.
become critical. Communications with rescue vehi-
cles and teams, hospital vehicles, police, laborato- 2. Install exhaust capability in areas that might be
ries, federal agencies such as the FBI and the CDC, used to treat people who have communicable dis-
fire department, and off-duty hospital personnel are ease and in areas accessible to the general public.
critical. 3. Designate large areas for use that already have
ventilation isolation, such as lobbies or waiting
B.5.6 Transportation areas.
A hospital functions very much like a factory. Its 4. Install external wash/decontamination capability.
product, the patient, must be transported from 5. Provide redundant storage of ordinary supplies,
function to function, sometimes rapidly (triage to food, water, medicines, cots, etc.
surgery). Pure mechanical transport of patients 6. Provide redundant communication and transporta-
(assembly line) is unacceptable. Patients are trans- tion capabilities.
ported by people, often by several people if life sup-
port equipment is involved. The greater the distances 7. Provide redundant sterilization capability.
between stations (triage to X-ray, for instance), the 8. Use existing smoke-control systems and defend-
greater will be delays in treatment and the greater in-place procedures in cases of internal chemical
will be the need for transport personnel. Functioning or biological contamination.
elevators are essential. All hospital elevators must be 9. Provide security for hospital air intakes, mechani-
on the emergency electrical grid and must be large cal equipment, and entrances for people and
enough to transport patients on stretchers since some materials.
Table B-1. Mechanical Services Required in Disaster Situations
Mechanical Services Required
Ventilation

Heat
Food

Water
Clothing

Eyewash
Medical Gases

Hot Water (G)


Waste Isolation

Protective Gear

Sterilization (D)
Surgical Supplies

First Aid Supplies

Emergency Power
Hepa Filtration
Total Body Washing

Positive Pressure
Respiratory Therapy

Total Exhaust (L)


Negative Pressure
DISASTER MANAGEMENT

Ventilation Isolation
Transportation In-Hosp

Communication In-Hosp
Transportation Extra-Hosp

Medicines (Drugs, IVs, etc.)


Communication Extra-Hosp

Disaster Type Space Designation


Basic Triage + B B B + + + + + + + + + + + + + + +
Surgery + + + + + + + + + + +
Observation + + + + + + + + +
Accidental or
Multiple trauma If hospital Convalescent + + + + + + + + + +
terrorism
involved Storage + + + + + + +
Lab, X-ray + + + + +
Food Prep (E), Pharmacy (A) + + + + + + +
Wash/Decontam + + + + + + + ++(F) + + + ++ + + +
Basic
Triage + + + + + + + + + + + + + + + +
If event is too Treatment + + + + + + + + + + +
large to be Observation + + + + + + + + +
Accidental or absorbed by
Chemical
terrorism hospital Convalescent + + + + + + + + + +
Storage + + + + + + +
If hospital
Lab, X-ray + + + + + +
involved (C)
Food Prep (E), Pharmacy (A) + + + + + + +
209
Table B-1. Mechanical Services Required in Disaster Situations (Continued)
210

Wash/Decontam + + + + H + + + ++ + + + + ++ + + + +
Isolation + + + + H + + + + + + + + + +
Treatment + + + + H + + + + + + + + + + + + +
Unknown Basic Lab, X-ray (I) + + + + H + + + + + + + +
epidemic or
Triage + L J + + + + + + + + + + + + + + + +
terrorism with
hospital involved Storage L J + + + + + + +
Epidemic too Observation + + + + + + + + + + +
large to be
absorbed by Convalescent + L J + + + + + + + + + + +
Biological hospital Food Prep (E), Pharmacy (A) + + + + + + +
Wash/Decontam + L K + + + + ++ + + + ++ + + +
Basic Triage + L K + + + + + + + + + + + + + +
Treatment + L K + + + + + + + + + + + + +
Terrorism, Observation + L K + + + + + + + + + +
hospital not
involved Convalescent + L K + + + + + + + + + + +
Storage + + + + + + +
If too large to be
absorbed by Lab, X-ray (I) + L K + + + + + + +
hospital Food Prep (E), Pharmacy (A) + + + + + + +
Wash/Decontam + + + + + ++ + + + ++ + + +
Basic Triage + + + + + + + + + + + + + + +
Treatment + + + + + + + + + + + +
Observation + + + + + + + +
Convalescent + + + + + + + + + +
Storage + + + + + +
If too large to be
absorbed by Lab, X-ray + + + + +
Nuclear hospital Food Prep (E), Pharmacy (A) + + + + + + +
HVAC DESIGN MANUAL FOR HOSPITALS AND CLINICS
Table B-1. Mechanical Services Required in Disaster Situations (Continued)
Table B-1 Notes H. HEPA filtration is most necessary in situations of unknown infective agents. Ventilation
A. Food Prep: Alternate area for food preparation if hospital kitchen is too small or damaged. isolation (separation) may be sufficient in other biological emergency situations.
Pharmacy: Alternate area for medication preparation if hospital pharmacy is damaged. I. In this case, the X-ray machine or facility should be separate from the main X-ray depart-
Emergency food and medicine supplies are included under storage. ment whether the main X-ray department is down or not.
B. The triage area ventilation should be isolated (total exhaust, treated or filtered return) because hospital ventilation generally J. A biological spill or attack within the hospital can be handled by the same defend-in-place
should be protected against return air from uncontrolled areas and from potentially contaminated public areas. strategy as in chemical or smoke control, i.e., evacuation (and isolation in this case) of people,
C. Local release of noxious chemicals in a hospital can be devastating. The defence for such a release is similar to the NFPA evacuation of air, and pressurization of other areas.
defend-in-place strategy for fire and smoke control in health care facilities (see Chapter 11); i.e., evacuation of people from affected K. The necessity for ventilation isolation may be determined by the agent involved. In cases
area, air evacuation, and pressurization of unaffected areas. such as anthrax, where the victim is not contagious, ventilation isolation might not be necessary
D. Sterilization capability is a paramount feature of hospitals, especially in emergency conditions. An independent form of steril- once the victim is decontaminated. In cases of more infectious and secondarily transmitted or
DISASTER MANAGEMENT

ization will be necessary should central hospital services fail. unknown agents, ventilation isolation is necessary.

E. Backup cooking fuel source is needed. L. Listing Total Exhaust, Ventilation Isolation, and Negative Pressurization seems
somewhat redundant. Total Exhaust is listed because it is probably the least expensive method
F. Double-plus sign emphasizes importance under these circumstances.
of achieving both ventilation isolation and negative pressurization. Care must be taken, however,
G. Hand washing is by far the most effective means of preventing the spread of microbes and other pathogenic materials. Wash- to exhaust possibly contaminated air well away from people and from air intakes.
ing facilities should, therefore, be easily available in all hospital areas and to all personnel. Hand washing is more comfortable with
warm water, but can be done with only cold water. Items marked here are those that need hot waterover and above that needed for
hand washing.
211
APPENDIX C
LOAD CALCULATIONS AND
EQUIPMENT HEAT GAINS
C.1 INTRODUCTION Refer to Chapter 4 for general design criteria
and approach and to Chapters 12 and 13 for specific
This appendix is not intended to duplicate any of indoor design criteria for various types of spaces.
the chapters in the ASHRAE HandbookFundamen-
tals on air-conditioning load calculations or the thou- C.3 DESIGN LOADS
sands of pages written in support of DOE-2 or
commercially available computer load programs. C.3.1 Lighting Loads
The intention is to highlight specific aspects of cool- Intensive lighting must be installed in many
ing and heating load calculations for health care health care facility spaces to facilitate medical proce-
facilities. dures. These loads, apart from general lighting,
could be of short duration or may very well last for
C.2 OUTDOOR AND INDOOR DESIGN hours. Most of the time, the schedule for use of these
CONDITIONS lights is uncertain. Therefore, it is prudent to incor-
porate them into load calculations at their peak load
The outdoor design conditions (temperature, conditions and to design the system flexibly enough
humidity, and other factors) relate to the location of to operate without wasting energy at lower loads.
the building. They are the given, based upon histori-
C.3.2 Occupancy Loads
cal climatic data, and must be clearly defined in the
project design criteria or basis of design. To calculate Sensible and latent heat gains from people in
cooling and heating loads, the design summer and different states of activity that are specific to health
winter conditions will suffice. To select a system care facilities must be considered. Design uncertain-
based on life-cycle cost analysis or to design a cen- ties may result from a high population density occur-
tral plant where the cooling and heating might inter- ring for an unknown or difficult-to-predict period of
twine, however, climatic conditions during an entire time. This is true for waiting rooms, surgery rooms,
year must be considered. Annual cooling and heating and the emergency department. Again, it is prudent
loads and daily load profiles are typically calculated to incorporate these as peak loads in the calculations,
and the system design must be flexible enough to
using energy analysis computer programs.
operate without wasting energy at reduced loadings.
The indoor design conditions are the conditions
under which the building must operate. They are C.3.3 Medical Equipment Loads
established as design criteria early in design; they are A major portion of the internal cooling load in a
not statistically derived but are established according health care facility is due to the heat produced by med-
to the occupancy needs of each space in a building. ical equipment installed in the various spaces. These
Variations in indoor design conditions over time loads, based upon manufacturers data, must be eval-
must also be established in accordance with the uated in detail and documented during design. Data
schedule of operation of the individual spaces. for selected equipment may be found in Table C-1.

213
214 HVAC DESIGN MANUAL FOR HOSPITALS AND CLINICS

Table C-1. Typical Medical Equipment Heat Gains


Equipment Type Peak Watts Average Watts
Anesthesia System 177 166
Blood Warmer 204 114
Blood Pressure Meter 33 29
Blanket Warmer 504 221
Endoscope 605 596
Electrosurgery 147 109
ECG/RESP 54 50
Harmonical Scalpel 60 59
Hysteroscopic Pump 35 34
Laser Sonics 256 229
Optical Microscope 65 63
Pulse Oximeter 21 20
Stress Treadmill 198 173
X-Ray (Portable C-Arm) 534 480
X-Ray (GX-PAN) 82
X-Ray (Portable) 18
Vacuum Suction (Portable) 337 302
Ultra-Sound System 1063 1050

Film Viewer, 4 bank 0.3-0.6 kW


Angiographic Injector 0.6-1.5 kW
Laser Imager 2.4-3.5 kW
Film Viewer, Motorized 1.5-2.0 kW
Bi-Plane Angiographic Imager 7.0-10.5 kW
CathLab Computer 0.6-1.2 kW

C.3.4 Ventilation Loads most difficult factor to determine and the least pre-
cise to calculate.
A significant component of the cooling and
heating load is a result of the outside air that has to There are two methods for calculating the heat-
be brought in to ventilate a space. Many of the health ing/cooling loads in these spaces. Both methods
care facility spaces have specific requirements must be applied with caution and must be based on
regarding minimum outside air, mandatory require- an in-depth analysis of the operation of the equip-
ment in the space.
ments regarding the rate of exhaust air, and manda-
tory requirements regarding the pressure
relationships between rooms. These requirements The Diversity Factor Method
must be established as design criteria based upon the The diversity factor is defined as the ratio of the
occupancy of each space. Specific data can be found average use of a group of heat-producing equipment
in Chapter 4 and Chapter 12. items and the sum of their peak heat releases. A
diversity factor is determined on the basis of experi-
C.4 DIVERSITY FACTORS AND ence or published data and is applied to the sum of
SCHEDULE OF OPERATIONS the maximum heat releases of all equipment items.
Many rooms in health care facilities house sev-
The Schedule of Operation Method
eral pieces of heat-releasing equipment. The result-
ing internal loads are time dependent. Variations in A schedule of operation is assigned to each
the operating schedules of the lighting and heat-pro- piece of equipment, and the hourly loads thus result-
ducing equipment located in the same room greatly ing are added, hour by hour, to determine the peak
affect the peak load of a space.This is probably the load of the space at each hour of the day.
LOAD CALCULATIONS AND EQUIPMENT HEAT GAINS 215

C.5 SUPPLY AIR or heating equipment can be determined only after


The quantity of conditioned air that has to be all of the air quantities have been calculated and the
delivered to a space to satisfy its sensible load is cal- entire building has been air balanced.
culated from the formula:
C.7 HVAC EQUIPMENT SIZING
cfm = Qmax / 1.1 DT [L/s = Qmax/1.2 DT]
Numerous factors involved in load calculations,
where such as weather data and heat transmission coeffi-
cients for building materials and assemblies, involve
Q is the sensible load expressed in Btu/h (W), uncertainty. Characteristics of the materials used in
DT is the difference between the room tempera- the actual construction may be different from those
ture and the temperature of the supply air in F assumed during design. The quality of construction
(C), and differs from one building to another. Buildings are
1.1 is the product of the specific weight of dry operated in different ways. Occupancy patterns and
air at sea level (0.075 lb/ft3 [1.2 kg/m3]), the the operating schedules of heat-producing equipment
specific heat of moist air at 55F dry bulb (24.4 are uncertain most of the time. All of these factors
Btu/F.lb dry air [1000 J/kgK]), and 60 min/h. make calculation of air-conditioning load numeri-
cally imprecise. The best a designer can do is to pro-
In regular building occupancies, the supply tem- vide a good estimate of the load. For this reason, a
perature is predetermined, and the load establishes 10% safety margin added to the calculated load is
the air quantity to be delivered to the space. In health good engineering practice.
care facilities, many spaces have to follow code Two methods can be used to account for the
requirements regarding the minimum quantity of air additional uncertainty of pick-up or transient loads
to be supplied to the room, or room air has to be (such as warm-up or cool-down):
exhausted to the outside at a minimum rate, or a cer-
tain pressure differential must be maintained Load calculations that take into account the
between rooms. These conditions could make the degree of setback and the necessary recovery
supply air quantity larger than calculated on the basis time, or
of the space load or could require that the systems Estimates that increase the design loads by a
that serve such spaces be constant volume instead of certain percentage. Californias energy stan-
variable volume systems. dards, for example, allow a maximum 30%
adjustment for heating and 10% for cooling.
C.6 AIR BALANCE
For reasons previously discussed, system air Furthermore, equipment sizing should follow
balance plays an important role in determining the principles enunciated in Chapter 4 for reliability,
health care facility cooling and heating loads. Final redundancy, and flexibility, according to the use of
calculations of the loads that are seen by the cooling the space being served.
APPENDIX D
INFECTION CONTROL ISSUES
D.1 INTRODUCTION most vulnerable and susceptible loved ones. It is
Airborne transmission of disease has been a incumbent upon us as citizens, hospital workers,
problem since mankind has lived indoors. Sunlight architects, and engineers to do our utmost to prevent
(UV radiation) kills most microbes that cause dis- the spread and proliferation of infection.
ease in humans. Many respiratory pathogens have
D.2 CONTEXT FOR
adapted to our comfortable indoor environments,
INFECTION CONTROL
thereby escaping the deadly sunlight. Airborne
pathogens have always been a problem. Current con- Our current health care system has a few quirks
cerns, such as microbial resistance to antibiotics, the that might discourage all-out infection control. Hos-
incidence of other nosocomial infections, and the pitals are not compensated directly for the costs of
high cost and morbidity of nosocomial infections, instituting infection control programs. Also, hospital
magnify the problem. revenues are higher as infections and complications
Robert Bazell of NBC News reported on increase. The incentive for hospitals to control infec-
December 27, 2000: Its a danger of staggering pro- tions is lacking in the milieu of running hospitals
portions. Every year, one in twenty Americans8 like businesses. The situation is similar to the
million peopledevelop an infection, with 88,000 of change-order mechanism in design-construction.
them dying. The biggest threat: supergerms resis- Hospital stays are becoming shorter, so infections
tant to antibiotics. (and other complications) may not become evident
Although HVAC engineers are primarily con- until after a patient is discharged. Thus, an infection
cerned with problems that are airborne (respiratory might be treated outside of the hospital and therefore
infections), other nosocomial infections can be ame- not be reported in hospital infection statistics. Hospi-
liorated by engineering and/or architectural consid- tal infection statistics are difficult to obtain because
erations. Kowalski and Bahnfleth produced a superb many hospitals consider that data proprietary infor-
review of airborne respiratory disease, control of mation.
microbes, and mechanical systems published by
HPAC in July 1998. The paper is reproduced at the D.3 NOSOCOMIAL INFECTION COSTS
end of this appendix. AND MORBIDITY
Health care facilities are the only places where
nosocomial infections can be acquired. Patients who The total number of nosocomial and other
have the worst infections wind up at a hospital. institutional infections exceeds 4 million per year, a
Patients who have the most drug-resistant organisms number substantially larger than the total number of
wind up at a hospital. Infected patients without regu- admissions for all cancer, accidents and acute myo-
lar medical care (without medical insurance) wind cardial infarctions combined (Martone et al. 1998).
up in hospital emergency rooms (and waiting rooms) Table D-1, reflecting the costs of nosocomial infec-
after they have put off seeking help as long as possi- tions, is taken from Chapter 30 in Hospital Infections
ble. A communitys worst and most drug-resistant (Martone et al. 1998).
infections are, therefore, concentrated in a single The numbers in the table do not reflect the extra
community locationthe hospital where we take our pain and suffering that patients and their families

217
218 HVAC DESIGN MANUAL FOR HOSPITALS AND CLINICS

Table D-1. Estimated Extra Days, Extra Charges, and Deaths Attributable to Nosocomial
Infections Annually in U.S. Hospitals
Extra Charges Deaths Directly
Caused by Deaths Contributed
Extra Days Avg. per Avg. per Infections by Infection
Avg. per Est. U.S. infection infection Est. U.S. total Est. U.S. Est. U.S.
infectiona totalb [1975]a [1992]c [1992]b [%]d totalb [%]d Totalb
Surgical wound
infection 7.3 3,726,000 $ 838.00 $ 3,152.00 $1,609,000,000.00 0.64 3,251 1.91 9,726
Pneumonia 5.9 1,339,000 $1,511.00 $ 5,683.00 $1,290,000,000.00 3.12 7,087 10.13 22,983
Bacteremia 7.4 762,000 $ 935.00 $ 3,517.00 $ 362,000,000.00 4.37 4,496 8.59 8,844
Urinary tract
infection 1.0 903,000 $ 181.00 $ 680.00 $ 615,000,000.00 0.10 947 0.72 6,503
Other site 4.8 1,946,000 $ 430.00 $11,617.00 $ 656,000,000.00 0.80 3,246 2.48 10,036
All sites 4.0 8,676,000 $ 560.00 $ 2,100.00 $4,532,000,000.00 0.90 19,027 2.70 58,092
a. Adapted from R.W. Haley et al., American Journal of Medicine, 1981, 70:51.
b. Estimated by multiplying the total number of nosocomial infections estimated in the SENIC Project [American Journal of Epidemiology 1985,
121:159] by the average extra days, average extra charges, or percentage of infections causing or contributing to death, respectively.
c. Estimated from Haley et al., American Journal of Medicine 1981; 70:51, by pooling data and adjusting for inflation.
d. Unpublished analysis of data reported to the National Nosocomial Infections Surveillance System in 1980-1982, J.M. Hughes et al.

must undergo when these infections occur, nor do D.5 ANTEROOMS


they reflect such things as 6-12 months of waiting, The incidence of nosocomial tuberculosis infec-
while debilitated, before an orthopedic prosthesis tions rose steadily until 1993. Improved ventilation
can be replaced. techniques are responsible for significantly reversing
that trend in the past several years. Ventilation strate-
D.4 ISOLATION gies make a difference. Infectious patients are placed
in rooms that are negatively pressurized to prevent
Patients who have infectious diseases are placed infecting microbes from spreading. Immunosup-
in isolation after they have been diagnosed. Undiag- pressed patients are placed in positively pressurized
nosed patients are transported through hospital corri- rooms to prevent them from coming into contact with
dors and to imaging labs before being diagnosed as infectious organisms. Immunosuppressed patients
infectious. More and more invasive procedures are who are also infected are placed in rooms that have
being performed in imaging labs, even though those anterooms.
labs have not been designed for sterile procedures Why not place all infectious patients and immu-
and have not been designed for adequate cleaning nosuppressed patients in rooms with anterooms?
and disinfecting after serving infected patients. Hos- After all, many infected patients, particularly, tuber-
pital personnel make multiple contacts with undiag- culosis patients, are somewhat immunosuppressed
nosed patients before they are recognized as from debilitation and are highly susceptible to sec-
infectious. Less trained hospital workers make inap- ondary infections. Likewise many immunosup-
propriate contact with infected patients even while in pressed patients, particularly AIDS patients, already
isolation. harbor communicable secondary infections. It makes
Hospitals are hiring more and more untrained no difference whether their room is negatively pres-
surized or positively pressurized. The important
people for patient care because of cost concerns.
point is that their air is separated from everybody
Hospital turnover often outpaces universal infection
elses airwhich anterooms can do. Undiagnosed
control training. Hand washing is by far the most
patients should be placed, upon admission, in rooms
important procedure in infection control. Hand-
with anterooms, so that there is less chance of
washing sinks or supplies, however, are often not
spreading organisms before diagnosis. This would
placed conveniently near the exits of patients rooms.
require more anterooms and higher first costs, but it
Obviously, all of these problems do not exist in all
would cut down the confusion of pressurization, cut
hospitals.
down the number of room transfers, afford flexibility
The growing cost and morbidity of nosocomial in the number of available isolation rooms, decrease
infections to society suggests that a concerted multi- the spread of organisms before diagnosis, and, prob-
disciplinary approach to solutions is necessary. Solu- ably prevent a few cases of nosocomial infection.
tions that may have significantly high first costs More infections are spread by the droplet route
should not be rejected out of hand. and by contact than by the airborne route. Anterooms
INFECTION CONTROL ISSUES 219

prevent infection from spreading by the airborne tom of the food chain. Some microorganisms are
routeand also by the droplet and contact routes. even necessary within our own bodies (coliforms
Anterooms control access to patient rooms. Food such as E. coli) to break down unneeded materials.
service personnel leave patients trays in the ante- We humans (and all other organisms that inhabit
rooms rather than taking them to the patients bed- our planet) have developed elaborate protections
sides and then going directly to another bedside. against the invasion of disease-producing (pathologi-
Only trained personnel are allowed into the room cal) microorganisms. Some of our protective mea-
proper. Although more breaks in isolation technique sures are skin; an immune system; white blood cells
result from personnel error than from HVAC or that act like protozoans themselves and devour bac-
architectural inadequacy, anterooms and designs teria; mucus in our digestive and respiratory systems;
cognizant of infection dangers can augment and ear wax; strong acids in our stomachs; colonization
enforce compliance with isolation techniques. Ante- of friendly bacteria (Lactobacillus); tears; micro-
rooms allow easy access to isolation materials: sinks, scopic hairs that line our respiratory systems and
masks, gowns, gloves, and soap. Anterooms that are carry away debris and microbes; and, brains that
positively pressurized to both the patient room and to have learned how to make antibiotics, develop isola-
the corridorcombined with patient room air supply tion protocols, and design protective ventilation sys-
over the patients bed and exhaust low between the tems. Breakdown of any one of these protections can
bed and the doorachieve effective isolation in all result in successful invasion by destructive microor-
circumstances. ganisms. Many microorganisms (virulent microor-
ganisms) can invade us, even if all of our protective
D.6 INFECTION mechanisms are intact.
Infections are caused by microorganisms, not by In this manual, we are primarily concerned with
just any microorganism, but microorganisms that the last mentioned item, that is, the provision of safe
have evolved to use us (humans) as a place to live or ventilation in health care facilitiesair movement
as something to eat without regard to our ultimate that is not laden with noxious microorganisms,
well-being or survival. Microorganisms (viruses, chemicals, odors, or particles; air movement that
rickettsia, bacteria, protozoa, fungi) predate us by does not transfer disease from one person to another.
hundreds of millions of years and will no doubt post- This goal can better be accomplished with knowl-
date us as well. Our ability to eradicate microorgan- edge and understanding of how disease spreads (epi-
isms is far overshadowed by their ability to eradicate demiology); with understanding of how hospitals
us. Microorganisms evolve rapidly into new forms or house, board, transport, and manage diseased
into old forms with new processes to adapt to what- patients; and with realization that health care provi-
ever environment they enter or to whatever environ- sion scenarios are changing, population and crowd-
mental danger (antibiotics) they encounter. They ing are increasing, intercontinental travel and
accomplish this by replicating themselves (and commerce are increasing, hospital stays are shorten-
mutating) at warp speeds compared to our ability to ing, inpatients are more debilitated, the costs and
replicate ourselves. Microorganisms can evolve into morbidity resulting from hospital-acquired infec-
resistant forms faster than we can develop and test tions are staggering, and microorganism resistance to
antibiotics and faster than we can develop measures antibiotics is increasing. It is the hospital that we all
of protection and treatment. turn to in cases of disease and disaster. It behooves
Most microorganisms are not harmful to human- us to make this last bastion of our health as safe as
ity. Many microorganisms are necessary for our possible. Perhaps we should not reject measures of
well-being, not just those that produce our wine, our infection protection because they have not yet proven
bread, our cheese, and our medicines, but those that to be effective but, rather, reject them only when they
make our soil fertile and those that enter at the bot- have proven to be ineffective.
Airborne Respiratory Diseases
and Mechanical Systems for
CONTROL OF MICROBES
1 Airborne transmission of respiratory
diseases in indoor environments re-
mains a problem of indoor air quality
(IAQ) with few engineering alternatives
and for which performance goals and de-
transmission that they lack any ability
to survive outdoors for long.1
In contrast, the non-contagious
pathogens, including the fungi, environ-
mental bacteria, and some animal
Airborne sign parameters are unclear. The engineer pathogens, have maintained the ability
who attempts to deal with microbial IAQ to survive in the environment. Even so,
respiratory finds that pertinent microbiological infor- direct sunlight is rapidly fatal to almost
mation exists in abundance but not in eas- anything but spores.1
pathogens and ily digestible forms. This article summa-
diseases in rizes the relevant literature of medical Classification of pathogens
microbiology and aerobiology in a manner Pathogens are any disease-causing mi-
health care that engineers may find useful and infor- croorganism, but the term applies to any
mative and that will facilitate the design microbial agent of respiratory irritation,
facilities are of HVAC systems intended to reduce the including allergens or toxigenic fungi. Res-
numerous threat. The general principles presented piratory pathogens fall into three major
here can be applied to any indoor environ- taxonomic groups: viruses, bacteria, and
and dangerous. ment, including office buildings, schools, fungi. The fungi and some bacteria, most
HVAC systems residences, hospitals, and isolation wards. notably the actinomycetes, form spores.
Since spores are characteristically larger
are critical in Origin of respiratory diseases and more resistant to factors that will de-
The first indoor environments, built by stroy viruses and bacteria, the engineer
controlling man over half a million years ago, in- may find it more convenient to consider
them. cluded caves with leather-draped interi- spores a definitive and separate category.
ors, fur-carpeted tents, and huts covered The single most important physical
with animal hides. Microbial predators ex- characteristic by which to classify airborne
isted from time immemorial, but trans- pathogens is size since it directly impacts
mission had always required direct con- filtration efficiency. 2 Fig. 1 presents a
tact because they could not tolerate the graphic comparison of airborne respira-
sunlight and temperature extremes out- tory pathogens in which the spores, bacte-
doors. Mans cozy new habitats made it ria, and viruses can be observed to differ-
possible for these ancient parasites to sur- entiate well, based on size alone. The left
vive short airborne trips between hosts. axis indicates the average or typical di-
Animal husbandry seems to have re- ameter or width. The areas of the circles do
sulted in a number of pathogens jumping not represent the actual sizes of the mi-
species and then becoming adapted to in- crobes, but each represents the diameter
By W. J. Kowalski, PE, door transmission to the exclusion of in proportion to one another. The span of
Graduate Researcher, and outdoor transmission. These include rhi- diameters is seen to be almost four orders
William Bahnfleth, PhD, PE, noviruses, diphtheria, TB, smallpox, of magnitude. Some microbes are oval or
Assistant Professor, measles, and influenza, which appear to rod-shaped, and for these only, the smaller
The Pennsylvania State have come variously from horses, cows, dimension is indicated.
University, Architectural dogs, pigs, and chickens. Most conta-
1
Engineering Dept., gious human pathogens have evolved to Superscript numerals indicate references
University Park, Pa. such dependence on mans habitats for listed at end of article.

This article originally was published in HPAC Engineering in July 1998. Some corrections and slight
34 HPAC Heating/Piping/AirConditioning July 1998 modifications were made in collaboration with the authors during the republication process.
C O N T R O L L I N G M I C R O B E S

Perhaps the most important classifica- by the airborne route will be subject to the
tion is that of communicable versus non- same principles and removal processes de-
communicable, a distinction that has both scribed in this article.
medical and engineering relevance. The
term communicable is synonymous with Communicable diseases
the term contagious. Communicable dis- Table 1 lists all the main respiratory dis-
eases come mainly from humans, while eases that can transmit between human
non-communicable diseases hail mostly hosts via the airborne route. Humans are
from the environment. However, many mi- the natural reservoir for most contagious
crobes that are endogenous to humans or pathogens but some notable exceptions
are environmentally common may cause exist. Pneumonic plague and Arenavirus
opportunistic infections in those whose epidemics originate with rodents or other
health has been compromised. These occur mammals.1 In regards to the mysterious
primarily as nosocomial, or hospital-ac- origin of Influenza, humans apparently
quired, infections. These three categories share the function of natural reservoir
then define all airborne pathogens: with birds and pigs, as strains of this Figure 1. Relative
Communicable virus periodically jump between species.3 size of airborne
Non-communicable continued on page 37
respiratory pathogens.
Primarily nosocomial
Table 1 lists all respiratory
pathogens under these three cat-
egories, along with major dis-
eases, common sources, and aver-
age diameters. In the column
identifying microbial group, the
term actinomycetes refers only to
the spore-forming actinomycetes.
Some general observations can be
made from these charts such as
the fact that most contagious
pathogens come from humans,
most non-contagious pathogens
come from the environment, and
most primarily nosocomial infec-
tions tend to be endogenous.
These tables are not necessarily
inclusive since a number of
pathogens, such as E. coli, Bacil-
lus subtilis, and some other
strains of Legionella, can, on rare
occasions, cause respiratory dis-
ease or allergic reactions. 3 The
abbreviation spp. denotes that
infections may be caused by more
than one species of the genera but
does not imply that all species are
pathogenic.
Table 1 lists only respiratory
pathogens, although non-respira-
tory pathogens can also be air-
borne. Certain infections of the
skin or eyes, nosocomial infections
of open wounds and burns, and
contamination of medical equip-
ment may occur by the airborne
route. Although these types of in-
fections have not been well stud-
ied, any pathogen that transmits

July 1998 HPAC Heating/Piping/AirConditioning 35


M I C R O B E S

continued from page 35


Many contagious respiratory pathogens
also transmit by direct contact through the
exchange of infectious droplets or particles
called fomites.4 The eyes and nasal pas-
sages are vulnerable to fomite transmis-
sion. The predominance of these direct
routes in comparison with the inhalation
route has not been well established but can
be very species-dependent.5 Infectivity is
also lost upon drying, and therefore hand
or surface contact may require the ex-
change of moisture as well as an infectious
dose.1,6
Barely 20 pathogens account for the
overwhelming number of contagious respi-
ratory infections. Table 2 lists the charac-
teristics of these infections, while the typi-
cal course of these infections is depicted in
Fig. 2. The infection rate refers to the frac-
tion of those exposed to an infectious dose
who contract the disease. This type of in-
formation can be useful to engineers at-
tempting risk assessment or procedural
control of infectious occupants or patients.
Few infectious doses have been estab-
lished, but for purposes of making rough or
conservative estimations, as few as 1-10
TB bacilli can be infectious for humans
while a total of 200 Rhinovirus virions may
be required to cause a cold.4
Most respiratory parasites induce their
hosts to aerosolize large quantities of infec-
tious bioaerosols by nasopharyngeal irrita-
tion, which causes coughing and sneez-
ing.4,5 Consider the profiles of the particle
sizes shown in Fig. 3. A single sneeze can
generate a hundred thousand floating
bioaerosol particles, and many may con-
tain viable microorganisms. 7 A single
cough typically produces about one per-
cent of this amount, but coughs occur
about 10 times more frequently than
sneezes.7 Bioaerosols produced by talking
are negligible, but extended shouting and
singing can transmit infections.
Some limited data from Duguid 7 is
available in generation rates stating that
A TB infective can produce 1-249 bacilli
per hr,8 while a person in the infectious
stage of a cold may produce 6200 droplet
nuclei per hr containing viable viruses
that remain airborne longer than 10 min.
In one measles epidemic, 5480 virions
were generated per hr.8
The dose received from an airborne con-
centration of microbes could be considered
a factor under engineering control since it

July 1998 HPAC Heating/Piping/AirConditioning 37


C O N T R O L L I N G M I C R O B E S

depends on the local air change rate and Susceptibility of the individual
Figure 2. Generic degree of mixing as well as the generation (immunity).
curve for duration of rate. The successful transmission of an in- Duration of exposure.
symptoms of respira- fection, however, depends on all of the fol- Concentration of infectious agent.
tory infections lowing factors: Virulence of infectious agent.
Breathing rate.
Route of infection (inhalation, eyes,
nasopharynx, etc.).
None of these factors is necessarily an
absolute determinant. Health and degree
of immunity can be as important as the
dose received from prolonged exposure.
Computations of infectious airborne
doses can be fraught with uncertainty.
Epidemiological studies on colds avoid
these problems by computing actual risks.
Fig. 4 shows how duration and proximity
to an infectious person can increase the
likelihood of infection, based on data from
Lidwells studies of the common cold. 9
These data suggest that there may be a
threshold distance beyond which risk de-
creases sharply. This risk may result from
local airborne concentrations but may also
include the risk of contact with fomites.

Non-communicable diseases
The list of non-communicable pathogens
in Table 1 includes all known that cause
respiratory infections, allergic reactions,
and toxic reactions. Included among the
diseases are EAA and HP (see notes),
continued on page 40

Figure 3. Profile of particle sizes


produced by an infectious person.
Based on data from Duguid et al 1945.

38 HPAC Heating/Piping/AirConditioning July 1998


C O N T R O L L I N G M I C R O B E S

in agricultural facilities, although most


tend to occur inside barns and work-
sheds.11,12
Indoor air spore levels can differ from
outdoor air in both concentration and com-
position of spores. In normal, dry build-
ings, spore levels tend to be anywhere from
10 to 100 percent of outdoor spore levels11
and are mostly less than 200 colony form-
ing units (CFU) per cu meter. Problem-
free, multi-story office buildings typically
have levels that are 10 to 31 percent of the
outdoor air11 levels. The composition of
fungal species indoors tends to reflect that
of the outdoors.13 Some fungal species,
most notably Aspergillus and Penicillium,
are often found to account for 80 percent of
Figure 4. Risk of continued from page 38 indoor spores.10
cold infection from which are sometimes associated with sick Spores will germinate and grow in the
proximity. Risk at zero building syndrome (SBS). Non-communi- presence of moisture and nutrients13 in lo-
represents intimate
cable infections are almost entirely due to cations such as basements, drain pans,
(husband-wife)
contact. Estimated per data fungal or actinomycete spores and envi- and on refrigerator coils. As a result of
from Lidwell.
9 ronmental or agricultural bacteria. such growth, spores can be generated in-
Spores form the most important group of ternally in problem buildings, wet build-
non-communicable diseases. Outdoor ings, and certain agricultural facilities at a
spore levels vary with season and climate high enough rate to cause indoor spore lev-
and can reach very high levels when dry, els to exceed outdoor levels. If spore con-
windy conditions result in disturbance of centrations indoors consistently exceed
the soil where fungi grow.
Surprisingly, few cases of res-
piratory infection have ever
been attributed to inhalation
of outdoor air,4,5 probably be-
cause most people, especially
Americans and Europeans,
spend over 90 percent of their
time indoors.10 A small pro-
portion of actinomycete infec-
tions have occurred outdoors

Figure 5. Indoor spore levels by


ventilation system type. From the
11
California Healthy Buildings Study.

40 HPAC Heating/Piping/AirConditioning July 1998


outdoor levels, the building can be inferred trients, procedural cleaning and mainte-
to contain an indoor amplifier.14 nance, and the use of biocidal equipment.
In the California Healthy Buildings Table 4 identifies fungal pathogens that
Study,11 naturally ventilated, mechani- have been found to grow indoors on vari-
cally ventilated, and air conditioned build- ous surfaces or in HVAC equipment.
ings all had lower indoor spore levels than Unidentified multiple species (spp.) may
the outdoors (Fig. 5).
However, Fig. 5 may
reflect favorable local
conditions since many
studies have measured
much higher levels
than these in non-prob-
lem buildings.
Table 3 lists the re-
sults of various stud-
ies that include mea-
surements of outdoor
spore levels and typi-
cal, average, or repre-
sentative indoor lev-
els. These levels do
not necessarily pose a
health threat. Mea-
surements and guide-
lines vary almost as
widely as outdoor lev-
els vary seasonally
and geographically.
Microorganisms
will take advantage of
any opportunity to es-
tablish themselves
and multiply in a new
environment.4 Niches
for microbial growth
may be created inad-
vertently by engi-
neered systems that
generate moisture
such as humidifiers,
evaporative air cool-
ers, cooling coil drain
pans, and condensa-
tion on ductwork insu-
lation. Amplification
may result in airborne
concentrations above
the outdoors10 and may reach unhealthy not necessarily be pathogenic. Many fac-
levels.13 Legionnaires Disease provides a tors may dictate which pathogens will
sentinel example of pathogenic microbial grow indoors such as climate, indoor mate-
amplification by an engineered system. rials, degree of human occupancy, hygiene,
Amplifying factors can be controlled and moisture levels.1,8
through various means, including preven- Table 5 identifies some pathogenic en-
tive design through humidity and mois- vironmental bacteria that have been
ture control. Some other first and second found growing indoors or on HVAC
line defensive measures include filtration, equipment. Occasionally, some conta-
the removal of materials that provide nu- gious bacteria disemminated from hu-

July 1998 HPAC Heating/Piping/AirConditioning 41


C O N T R O L L I N G M I C R O B E S

mans can be found in water, equipment, people. Low-level indoor microbial ampli-
or in dust, but these are transient occu- fication in health care settings may cause
pants and unlikely to grow or survive building-related illness (BRI) without ac-
long outside of human hosts.1,5 tually representing SBS.
Technically, nosocomial infections re-
Nosocomial infections late to those who are hospitalized, but
All respiratory pathogens are poten- health care professionals themselves may
tially nosocomial, but those that occur al- be at risk. The Center for Disease Con-
most exclusively as nonsocomial infections trol(CDC) publishes guidelines for control
are listed in Table 1 such as primarily of infections15 among hospital employees,
nosocom i a l r e s p i r a t o r y pathogens. but appropriate engineering design and
maintenance can play a significant role in
reducing the risks for medical profession-
als as well as for patients.

Natural microbial decay


Various environmental factors destroy
airborne microbes.1 Direct sunlight con-
tains lethal levels of ultraviolet radiation.
Dehydration renders most microbes inac-
tive, although many spores may survive
indefinitely. High temperatures will inac-
tivate all pathogens, some more rapidly
than others. Freezing will destroy most
pathogens; except that some, especially
spores, may be preserved. Oxygen slowly
The other common nosocomial infections kills most airborne microorganisms
are identified with a purple boxed N in the through oxidation. Pollution levels that we
notes column. tolerate our entire lives can be fatal to mi-
In intensive-care units, almost a third of croorganisms. Plate-out, or adsorption, oc-
nosocomial infections are respiratory, but curs on all interior building surfaces, but
not all of these are airborne since some are this removal rate tends to be negligible.
transmitted by contact or by intrusive Each of these environmental processes
medical equipment.15 Nosocomial infec- reduces pathogen populations according to
tions can also be airborne but non-respira- the following general equation:1,6
tory such as when common microbes like N  N0 e-kt (1)
Staphylococcus settle on open wounds, where
burns, or medical equipment. N  population at time t
Patients who succumb to nosocomial in- N0  population at time t0
fections are often those whose natural de- k  rate constant for process
fenses have been compromised either as a e  2.718
result of disease, medication, injury, or by- The resulting exponential decay curve is
passed by intrusive procedures. In cases of known as a survival curve, or death curve.
immune system deficiency, even a pa- Often, a very small fraction of the micro-
tients own endogenous flora could cause bial population, usually about 0.01 per-
infection, while normally benign environ- cent, resists chemical or physical inactiva-
mental microbes can become pathogenic. tion for extended periods of exposure.1,16
The protection of patients from poten- This relation applies additively to all re-
tial pathogens requires the reduction of duction processesexcept that humidity
microbial contaminants below normal or levels will influence the effects of other fac-
ambient levels. This is usually accom- tors such as ultraviolet germicidal irradia-
plished through the use of isolation tion (UVGI) and heat on a species-depen-
rooms, HEPA filters, UVGI, and strict hy- dent basis. In the outdoors, sunlight,
giene procedures.15 In the health care en- temperature extremes, and wind ensure
vironment, particular attention must be that non-spore microbial populations de-
paid to the possibility of microbial growth cay and disperse rapidly, generally within
indoors and in the air handling units, minutes.1,16 In the indoors, these factors
even if levels are not a threat to healthy continued on page 44

42 HPAC Heating/Piping/AirConditioning July 1998


C O N T R O L L I N G M I C R O B E S

continued from page 42

are controlled for human comfort, result- typical air handling unit (AHU). Conta-
ing in airborne microbes surviving longer, gious viruses and bacteria come almost ex-
sometimes even days.1,4 clusively from humans, and they will ap-
After expulsion by sneezing or coughing, pear only in the return air. Spores and
most large droplets will settle out of the air environmental bacteria may enter from
within a matter of minutes. Fig. 6 illus- the outdoors, but once growth (amplifica-
trates this process and is based on fitted tion) occurs indoors, they may appear in
data. Many of the micron-sized droplets the return air at higher levels than in the
will rapidly evaporate to droplet nuclei outdoor air. Environmental bacteria are
that approach the size of the individual mi- rarely pathogenic for healthy people
crobe. Micron-sized particles can remain (Table 1), but they may provide a nutrient
Figure 6. suspended for hours and spread by diffu- source for pathogenic fungi.
Disappearance of
airborne sneeze
sion or air currents.8 Spores can initially enter a building by
droplets from room Airborne microbes lose viability over various routes, including inlet air or infil-
air by size. Based on time. In the absence of sunlight, the decay tration, or they may be brought in with
fitted, normalized data rates for each microbial group, based on building materials, carpets, clothes, food,
from Duguid.
7
rates measured in a variety of studies,16 pets, or potting soil. In a normal, dry build-
ing, the return air will have lower levels of
spores than the outdoor air,11,12 except
when snow covers the ground and outdoor
spore levels approach zero. When indoor
amplifiers are present, the return air could
be expected to contain higher levels of
spores than the outdoor air, except during
dry, windy, summer conditions when out-
door levels of spores can become very high.
Once spores germinate and growth oc-
curs in an AHU or anywhere inside the
building, new spores may be generated
and appear in the return air. Filters may
intercept spores, but moisture may cause
them to grow through the filter media.
Cooling coils can have a pronounced filter-
ing effect on spores,11,12 but the presence of
condensation may also cause microbial
growth and amplification10 downstream of
the coils, negating the effect.
Boosting outside air flow may be an op-
tion only if the ventilation system is not
the source of microbial contamination; in
which case, increasing air flow may exac-
erbate the problem.11 A fungus problem
that is not caused by the ventilation sys-
tem, such as a leaky roof or wall, requires
separate remedial action such as removing
the damaged material.l7

Engineered alternatives
Natural decay mechanisms operate too
slowly inside most buildings to prevent
Figure 7. are shown in Fig. 7. Curiously, bacteria de- secondary infections.16 Available engineer-
Viability of airborne cay faster in air than viruses apparently ing alternatives include purging with out-
microbes indoors in because they depend more on moisture for side air, filtration, UVGI, and isolation
absence of sunlight. their survival than do viruses. through pressurization control. Each of
Based on averages for each
1,16 these technologies has advantages and
microbial group.
Pathways and dissemination limitations, but optimization for any appli-
Fig. 8 illustrates some distinctions be- cation is always possible if the microbial
tween airborne pathogens in relation to a IAQ goals are clearly specified.

44 HPAC Heating/Piping/AirConditioning July 1998


Pressurization control is com-
monly used in biohazard facilities
and isolation rooms to prevent mi-
gration of microbes from one area
to another, but inherent costs and
operational instability at normal
air flow rates limit feasibility for
other applications.
Full outside air systems are often
used in health care facilities and TB
isolation rooms, subject to CDC
guidelines.15 Fig. 9 shows the effect
of full purge air flow on the reduc-
tion of pathogens in a room with an initial The continuous exposure appears to in- Figure 8.
concentration of 100 microbe CFU per cu hibit fungal growth and may kill the Sources and
meter. Comparing this with Fig. 10 shows spores as well. In applications involving pathways of
the results of HEPA filtration at the same the disinfection of air streams, the effec- microbial
recirculation flow rates. The results are tiveness of UVGI depends on factors that contamination
practically identical. include air velocity, local air flow pat- in a typical air
handling unit.
The use of HEPA recirculation, of terns, degree of maintenance, character-
course, carries a lower total energy pen- istic resistance of the microbes, and hu-
alty2 in hot or cold climates. But in mild or midity.16 A single pass through a UVGI
dry climates, high percentages of outside system may have a limited effect, but re-
air can prove economical, especially in ap- circulation, either through stand-alone
plications involving evaporative coolers. units or ventilation systems, will result in
Hospitals often have commitments to spe- multiple exposures or chronic dosing.
cific guidelines, but other facilities may se-
lect and size systems to suit their goals and
budgets.
HEPA filters, for example, are not the
only choice for controlling microbial IAQ.
High or medium efficiency filters are capa-
ble of removing airborne pathogens, espe- Figure 9.
100 percent
cially spores, without high operation or re- outside air:
placement costs. 2,16 Overall, particle effect of ach
removal efficiency might be improved by on reduction
locating medium efficiency filters in the re- of initial level
circulation loop vs. the outside air in- of room
takes16 or even downstream of the cooling microbial
coils. But, this choice will depend on each contamination.
individual systems operating parameters.
Combining purge air with HEPA fil-
tration results in performance that is es-
sentially additive, and cost optimization
becomes straightforward. Energy con- Figure 10.
sumption, replacement costs, and micro- HEPA filter
bial IAQ goals will dictate the economic recirculation:
choice for any particular installation.16 effect of
The performance of medium efficiency flowrate
filters in combination with purge air (in ach) on the
flow is not directly additive but depends reduction of
on the filter efficiency vs. particle size initial level
curves, the sizes of the pathogens of con- of room
microbial
cern, and the system operating parame- contamination.
ters.
UVGI can be an efficient method to use
in the right applications such as control-
ling microbial growth in cooling coils.18

July 1998 HPAC Heating/Piping/AirConditioning 45


C O N T R O L L I N G M I C R O B E S

Figure 11.
alistic but provides dramatic differ-
Effects of 25
percent outside entiation of the effectiveness of
air (1 ach) on pathogen removal.
indoor contami- Fig. 12 shows the effect of an
nant levels.16 ASHRAE medium efficiency filter
Outdoor spore (80 to 85 percent dust spot) to the
level = 100 cfu supply air of the model building
per cu meter. while maintaining 1 ach of outside
air. The filter model describes filter
efficiency vs. diameters in accor-
dance with typical vendor perfor-
mance curves.16 Spore levels indoors
are clearly reduced below outdoor
ambient levels. Some reduction of
Figure 12. bacteria and viruses can also be
Effect of noted, but their removal is still dom-
ASHRAE filter, inated by the purging effect of the
80 to 85 percent outside air. The filter used in this
efficiency analysis provides a baseline for com-
on indoor parison. High efficiency filters, such
contaminant
as the 90 to 95 percent filters used in
levels.16
Recirculation hospitals, 2 would result in even
with 25 percent higher removal rates.
outside air. Fig. 13 shows the impact of a
UVGI system with 25 W (W=watt)
per sq cm placed in the recirculation
loop. The outside air is maintained
at 1 ach, but no filters are included.
Spores are relatively unaffected by
Figure 13. the UVGI, but the viruses are
Effect of UVGI
markedly reduced. This model in-
on indoor
contaminant corporates chronic dosing effects
levels.16 Re- from recirculation with an exposure
circulation of 0.2 sec for each pass. The decay
with 25 percent rate Equation 1 is applied with
OA. UVGI power known rate constants16 for a wide
mW (W=watt) cross-section of the microbial spe-
per sq cm cies listed in Table 1.
The unusual performance charac-
teristics of each technology have
Chronic dosing with UVGI can have a been highlighted in these examples. In-
major impact on airborne viruses and clusion of these characteristics in any
bacteria.16 evaluation, along with the IAQ design
A graphic comparison of the relative ef- goals, ambient conditions, and internal
fectiveness of the three main alterna- generation rates, will dictate the choices
tivesoutside air purge, filtration, and for any given applicationsubject only
UVGIis provided in Fig. 11 through 13. to economic limitations.
Fig. 11 shows the effect of 1 air changer per
hr (ach) of outside air on reduction of room Other alternatives
air contaminant concentrations from an Various current or experimental tech-
initial value. Perfect mixing is assumed, nologies have the potential for reducing
along with 500 CFU per cu meter contami- airborne disease transmission or indoor
nation of each microbial group initially, amplification. Biocidal filters can limit
100 CFU per cu meter of spores in the out- or prevent fungal growth on the filter
side air, and no internal generation. Natu- media. Electrostatic filters (i.e., electrets
ral decay rates from Fig. 7 are incorpo- or electrically stimulated filters) are
rated in the model. The scenario of an available but have not seen widespread
initially contaminated room may not be re- continued on page 48

46 HPAC Heating/Piping/AirConditioning July 1998


C O N T R O L L I N G M I C R O B E S

continued from page 46 Washington, DC, 1997.


use. Carbon adsorbers have pore sizes 11) Godish, T. Sick Buildings: Definition, Di-
agnosis, and Mitigation. Boca Raton: Lewis
too small to remove viruses, but they are Publishers, 1995.
effective at removing VOCs produced by 12) Samson, R. A., ed. Health Implications of
some fungi and bacteria. Fungi in Indoor Environments. Amsterdam:
Other technologies currently under re- Elsevier, 1994.
search include low-level ozonation, nega- 13) Burge, H. Bioaerosols: Prevalence and
tive air ionization, and photocatalytic ox- health effects in the indoor environment.
idationa technology that may one day Journal of Allerg. Clin. Immunol. May 1990:
687-781.
result in a type of light-powered, self-
14) Rao, C. Y. and H. A. Burge. Review of
cleaning, microbial filter. quantitative standards and guidelines for fungi
in indoor air. Journal of Air & Waste Manage-
Conclusions ment. Assoc. Sep. 1996: 899-908.
Perfect solutions to the problem of air- 15) Castle, M. and E. Ajemian. Hospital in-
borne disease transmission do not yet ex- fection control. New York: John Wiley & Sons,
ist, but the available technologiesout- 1987.
side purge air, filtration, and UVGIcan 16) Kowalski, W. J. Technologies for control-
be successfully implemented when their ling respiratory disease transmission in indoor
environments: Theoretical performance and
characteristic effects are understood and economics. The Pennsylvania State Univer-
the goals clearly defined. Whether the sity.
application involves improvement of mi- 17) Kemp, S. J., et al. Filter collection effi-
crobial IAQ in an office building or mini- ciency and growth of microorganisms on filters
mizing the risk of infection in an operat- loaded with outdoor air. ASHRAE Transac-
ing room, these technologies can be tions Jan. 1995: 228.
optimized individually or in combination 18) Scheir, R. and F. B. Fencl. Using UVC
Technology to Enhance IAQ. HPAC Feb. 1996:
from a cost or performance standpoint. 28-29, 85, 87.
Finally, since microbes will never ignore
opportunities provided to them, appropri- Bibliography
ate design, regular surveillance, and main- 19) Ahearn, D. G., et al. Colonization by Cla-
tenance of these technologies in particular, dosporium spp. of painted metal surfaces asso-
and HVAC systems in general, should al- ciated with heating and air conditioning sys-
ways be proactive. HPAC tems. Journal of Ind. Microbiol Aug. 1991:
277-280.
20) Chang, J. C. S., K. K. Foarde and D. W.
References VanOsdell. Assessment of fungal (Penicillium
1) Mitscherlich, E. and E. H. Marth. Micro- chrysogenum) growth on three HVAC duct ma-
bial Survival in the Environment. Berlin: terials. Environment International Apr. 1996:
Springer-Verlag, 1984. 425.
2) Burroughs, H. E. Filtration: An invest- 21) Flanningan, et al. Allergenic and toxi-
ment in IAQ. HPAC Aug. 1997: 55-65. genic micro-organisms in houses. Pathogens in
3) Freeman, B. A. ed. Burrows Textbook of the Environment. Oxford: Blackwell Scientific
Microbiology. Philadelphia: W. B. Saunders Publications, 1991.
Co., 1985. 22) Hyvarinen, et al. Influence of cooling
4) Ryan, K. J. ed. Sherris Medical Microbiol- type on airborne viable fungi. Journal of
ogy. Norwalk: Appleton & Lange, 1994. Aerosol Science 26.S1 (1995): s887-s888.
5) Mandell, G. L. ed. Principles and Practice 23) Macher, J. M. and J. R. Girman. Multi-
of Infectious Diseases. New York: Wiley, 1985. plication of microorganisms in an evaporative
6) Hers, J. F. ed. Airborne Transmission and air cooler and possible indoor air contamina-
Airborne Infection. Proc. of VIth International tion. Environment International 16 (1990):
Symposium on Aerobiology. Technical Univer- 203-211.
sity at Enschede. The Netherlands: Oosthoek 24) Price, D. L., et al. Colonization of fiber-
Publishing Company, 1973. glass insulation used in heating, ventilation,
7) Duguid, J. P. The size and the duration of and air conditioning systems. Journal of Ind.
air-carriage of respiratory droplets and droplet- Microbiol. 13 (1994): 154-158.
nuclei. Journal of Hygiene 45: 471-479. 25) Reynolds, S. J., et al. Elevated airborne
8) Kundsin, R. B., ed. (1980). Airborne Conta- concentrations of fungi in residential and office
gion, NYAS, New York. environments. Am. Ind. Hygiene Association
9) Lidwell, O. M. and R. E. O. Williams. The Journal 51 (1990): 601-604.
epidemiology of the common cold. Journal of 26) Zabel, R. A. and F. Terracina. The role of
Hygiene 59 (1961): 309-334. Aureobasidium pullulans in the disfigurement
10) Woods, J. E. ed. Healthy Buildings/IAQ of latex paint films. Developments in Industrial
97. Proc. of ASHRAE Annual IAQ Conference. Microbiology, Society for Industrial Microbiol-
ogy, Pittsburgh, 1980.
48 HPAC Heating/Piping/AirConditioning July 1998
APPENDIX E
LIFE-CYCLE COST ANALYSIS
E.1 LIFE-CYCLE COST ANALYSIS Equipment replacement cost and the year of
replacement (if replacement occurs within the
The life-cycle cost (LCC) method considers all study period)
of the cost elements of an investment during its life Annual energy costs
cycle. The Department of Energys (DOE) Federal
Annual water costs (only if they vary from one
Energy Management Program (FEMP) requires the
alternative to another)
use of this method to evaluate energy and water con-
Annual nonfuel operating, maintenance, and
servation investments in federal buildings. The
repair costs (OM&R)
method is described at length in the Life-Cycle Cost-
ing Manual for the Federal Energy Management To simplify calculations, any of the preceding
Program, NIST Handbook 135 (NIST 1995). The cost elements can be reduced to only those costs that
annually published Energy Price Indices and Dis- differ from one alternative to another. For example, if
count Factors for LCC Analysis supplements Hand- both HVAC alternatives use the same central plant,
book 135 (NIST 2002). NIST computer software for the costs related to the initial investment and opera-
life-cycle cost analysis of buildings and building sys- tion of this plant could be excluded from the calcula-
tems is also available. tions. But if, for example, the chillers are different
The LCC method is the ideal economic method from one alternative to another, the costs of the chill-
to compare HVAC alternatives because these alterna- ers would be included in the calculations.
tives inherently include energy, water, and operating The calculated present value of each of the
costs. Adhering to the federal life-cycle costing pro- annual costs is based upon
gram presents the advantage of a uniform method for
economic analysis of HVAC alternatives with readily the length of the study period (usually 25 years)
available discount factors and price escalation rates, and
updated annually, for each region in the United the discount rate (either the annually published
States. real DOE discount rate, exclusive of general
The life-cycle cost method is specifically useful inflation, or the investors discount rate).
in assessing the long-term cost-effectiveness of
Present value is found by applying the following
design alternatives that have different initial invest-
factors:
ment costs; energy, operating, maintenance, and
repair costs; or different lives. Handbook 135 recom- The single present value (SPV) factor used to
mends the use of uncertainty assessment and sensi- calculate the present value of a future cash
tivity analysis, in addition to life-cycle cost amount, such as equipment replacement costs,
calculations. based upon the year of replacement and the
The life-cycle cost method includes the follow- selected discount rate;
ing cost elements: The uniform present value (UPV) factors for
each of the recurring annual energy costs at a
Initial investment cost for each alternative nonconstant escalation rate (based in the FEMP

231
232 HVAC DESIGN MANUAL FOR HOSPITALS AND CLINICS

process upon DOE projections of energy escala- The initial capital cost should include all equip-
tion rates, according to the location of the ment, auxiliaries, and building-related costs for
project); each complete system. Refer to the ASHRAE
The UPV factors for annually recurring costs HandbookHVAC Systems and Equipment,
based upon the selected discount factor and the Owning and Operating Costs, for a complete
length of study period, applicable to annual non- list of items to be included in an economic anal-
fuel operating, maintenance, and repair costs ysis (ASHRAE 2000a).
(OM&R) and to water consumption and/or dis-
posal. Energy cost computations should take base
loads into consideration. The owners representative
The summation of all present values for an alter- should provide utility usage and rates. Backup com-
native constitutes the total present value of that alter- putations for items listed in the operating cost should
native. The smaller present value alternative be included in the life-cycle cost report. Computa-
becomes the recommended alternative, unless intan- tions should be made on a monthly basis, taking into
gible advantages have to be considered or sensitivity account variations in the heating and cooling loads.
analysis should be performed. Energy usage and cost should be developed using
The purpose of an economic analysis is to deter- Weather Bureau tapes, or Air Force Manual AFM-
mine the comparative life-cycle costs of various 88-8, Engineering Weather Data, and the bin method
HVAC system alternatives. Such analysis should pro- procedure referenced in the latest ASHRAE Hand-
vide sufficient data to indicate the most economical bookFundamentals (Department of the Air Force
and energy-efficient system and to permit a compre- 1967; ASHRAE 2001a).
hensive review of all computations. The analysis Energy cost computations should consider the
should include and compare total initial capital cost, energy used by fans and cooling and heating coils, as
energy cost, operating cost, system reliability, flexi- well as refrigeration plant energy costs that result
bility, and adaptability of each alternative. Each sys- from the proposed air-conditioning system. The
tem alternative considered should satisfy the energy analysis should be conducted using a profes-
program requirements completely in terms of flexi- sionally recognized and proven computer program
bility, redundancy, reliability, and ease of mainte- based on hourly calculations.
nance. The total capital cost to provide the program Total present worth is equal to the sum of the
requirements for each alternative should be included first (construction) cost and the present worth of
as part of the life-cycle cost. maintenance, replacements, utilities, electricity, and
For comparison of systems, a life-cycle cost fuel payments for the analysis-life of the project. All
analysis should run from 15 to 30 years, correspond- of the present worth values should be based on
ing to the anticipated useful life of major equipment. appropriate construction schedules.
Replacement costs should be included for equipment An equivalent annual cost is often calculated.
with less than the chosen life cycle. The following This is the payment that will amortize the total
are the cost components: present worth at the given interest rate using a capital
recovery factor (CRF). Taxes or insurance are nor-
The escalation rate for fuel or energy costs (oil, mally not included in the annual owning cost.
gas, coal, electricity, etc.) can be obtained by Public Law 95-619 requires that life-cycle cost
using the procedures set by the Department of analyses for federal projects conform to procedures
Energy (DOE) in NIST Handbook 135. Alterna- set forth by the Department of Energy. Conducting
tively, owners historical data should be con- this type of analysis for other types of projects is
sulted. highly recommended.
APPENDIX F
VENTILATION STANDARDS
AND CURRENT TRENDS
F.1 INTRODUCTION PPD indices and specification of the condi-
tions for thermal comfort) for assessing ther-
The comfort and quality of the environment for mal comfort in spaces with average
an occupant in a building is controlled directly by temperatures (ISO 1994).
that buildings environmental control system,
namely, its ventilation system, whether it is forced, Energy consumption and reduced operating
natural, or mixed. Ideally, ventilation systems are costs have become dominant factors in the derivation
designed to maximize human comfort. However, of the codes and standards. Control-system perfor-
cost and energy consumption constraints are typi- mance evaluation is therefore critical, with life-cycle
cally imposed, and, as a result, the goal of maximum costs also requiring attention.
comfort is usually compromised. Therefore, codes However, standards that have focused on these
and standards are imposed or recommended for aspects run into problems in their acceptance. Perfor-
buildings and have been developed in order to pro- mance-oriented standards have not been widely
tect the health and welfare of occupants. These stan- accepted by contractors and enforcement officials
dards are based on recognized acceptable ranges for because of increased costs of implementation and
environmental characteristics. For example, comfort liability and barriers in technology transfer. Further,
can be described as follows: financial decisions based on life-cycle costing have
not been accepted by contractors and building devel-
Thermal comfort is a complex concept that is opers. These groups have resisted because of a lack
influenced by a number of parameters and is of incentives, such as amortization periods and
not always perceived the same by all humans. allowance of pass-through of operating costs, and
However, several attempts have been made in because of the high cost of capital.
order to develop empirical correlations for
relating comfort perceptions to specific phys-
iological responses, in a more comprehensive F.2 VENTILATION CODES AND
way than the previously presented comfort STANDARDS
indices. Among the various models and sug-
gestions for the quantitative estimation of F.2.1 General
thermal comfort, the most widely used is the
one suggested by Fanger. This work has The provision of indoor environments in com-
grown to be the most popular way of quanti- mercial and residential buildings of comfortable or
tatively expressing thermal comfort and ther- acceptable thermal quality is an enormous burden
mal sensation, known as the Predicted Mean
Vote (PMV) Theory and the associated index on energy consumption. Such provision requires
of Predicted Percent of Dissatisfied (PPD) approximately one-third of the total annual energy
people. The PMV and PPD indices have been consumption in buildings (HVAC, lighting, equip-
introduced and empirically derived, by ment, etc.) in the United States (USDOE 1978) while
Fanger during the 1970's. The method has in the European Union, buildings consume about
become since 1984, the basis of the Interna-
tional Standard ISO-7730 and the European 40% of the total energy budget (SOEC 1996). An
Standard EN 27730 (Moderate thermal envi- additional 10% may be required to maintain condi-
ronmentsDetermination of the PMV and tions that are acceptable for occupants in industrial

233
234 HVAC DESIGN MANUAL FOR HOSPITALS AND CLINICS

facilities (Kusuca 1976). Ventilation systems have F.2.2 United States


been reported to require as much as 50% or 60% of In the United States, regulatory authorities
the total energy consumed in buildings (Rohles et al. described above in F.2.1 may develop consensus
1978; Yaglou 1936; Nevins 1976). standards.
Building codes have been adopted and enforced U.S. agencies responsible for the development
by local, state, and federal government agencies to and enforcement of mandatory standards relevant to
protect the health, safety, and welfare of the general the building industry include the Department of
public. These codes generally take the form of stated Housing and Urban Development (HUD), the
minimal acceptable ventilation criteria to be pro- Department of Health and Human Services (DHHS,
vided by the ventilation system in the buildings. formerly the Department of Health, Education, and
Note that ventilation air, as used here and else- Welfare, or DHEW), and the Department of Energy
where in this document, refers to outdoor air or re- (DOE).
circulated, treated air. During the design phase, com- In most U.S. states, a Department of Public
pliance with building codes is usually the responsi- Health licenses hospitals and other health care facili-
bility of licensed professional engineers and ties. In many cases, especially when federal reim-
bursement for patient care is provided, hospitals
architects. However, after a building has been
must conform to U.S. Department of Health and
designed and constructed, responsibility is more
Human Services guidelines. These guidelines origi-
vague; the owner or manager usually assumes
nally had root in the Hill Burton act passed by Con-
responsibility for maintaining the quality of the gress after the Second World War in an attempt to
indoor environment, but there is normally no official provide standards of patient care. The U.S. Depart-
enforcement. ment of Health Education and Welfare (HEW) main-
There are two basic types of standard, the vol- tained the standards. During the last several years,
untary or consensus standard and the mandatory the American Institute of Architects Academy of
standard. Architecture for Health, with assistance from the
Consensus standards are those that have been U.S. Department of Health and Human Services, has
developed and published by authoritative bodies. In maintained the standards.
the United States, for example, such bodies include
F.2.3 Europe
the American National Standards Institute (ANSI),
the National Fire Protection Association (NFPA), In Europe, the situation is still rather vague. Dif-
and the American Society for Testing and Materials ferent national building regulations, codes, and stan-
(ASTM). Other organizations that publish standards dards are applicable in each member state of the
for the building industry are the American Society of European Union, published by the national profes-
Heating, Refrigerating and Air-Conditioning Engi- sional engineering associations, technical chambers,
neers (ASHRAE), the American Society of Mechan- etc. Some efforts are currently underway to prepare
ical Engineers (ASME), the Illuminating common European standards (European Committee
Engineering Society (IES), the American Concrete for Standardization, Brussels, Belgium) for the
Institute (ACI), the Air Conditioning and Refrigera- building industry, but these are not yet mandatory.
tion Institute (ARI), and the Sheet Metal and Air
Conditioning Contractors National Association F.2.4 Other Countries
(SMACNA). There is great inconsistency and deficiency in
The standards published by these organizations many countries, including some in Asia and Africa
are usually developed by a consensus method, hence and some Latin American countries on standards
the term consensus standard. They are usually requirements for health care facilities. It is hoped
adopted, after periods of open review, as guidelines that this condition will be remedied soon.
of recommended practice or minimal performance
criteria by which an organization may govern itself. F.3 VENTILATION BACKGROUND AND
However, if a voluntary standard is adopted within DETAILS
legal documents, such as government standards or
building codes, it may become mandatory. F.3.1 Background
Standards also are developed in response to state Historically, natural ventilation has been used in
or federal laws. These are known as mandatory the design of buildings. The use of outdoor air for
standards and are developed and promoted in the natural ventilation, combined with natural cooling
form of state or federal regulations after they have techniques and the use of daylight, have been essen-
been subjected to public hearings. tial elements of architecture since ancient times.
VENTILATION STANDARDS AND CURRENT TRENDS 235

Classical architecture with H, L, T, or U-shaped floor ceiling would mean 67 cfm (32 L/s) per person.
plans, the use of open courts and limited space depth, However, at full-load occupancies of 10 ft2 (0.9 m2)
maximized windows to facilitate communication of per person in the theater and 20 ft2 (l.9 m2) per per-
the indoor environment with the outdoors for day- son in the classroom, 5 ACH would result in 17 cfm
light and natural ventilation. This was common prac- (8 L/s) per person in the theater and 13 cfm (6 L/s)
tice even for large commercial buildings until the per person in the classroom.
end of the 19th century (Donaldson and Nagengast The inherent problems associated with specify-
1994). ing air changes per hour have been recognized in
Naturally ventilated buildings have been com- some standards for several years. In 1946, the Amer-
mon in several parts of the world from the ancient ican Standard Building Requirements for Light and
Hellenic architecture to the Arabian wind towers. Ventilation, A53.l, was published by the American
Natural ventilation was surpassed by mechanical Standards Association (ASA 1946) with primary cri-
ventilation combined with comfort air conditioning teria in cubic feet per minute per square foot of floor
in order to resolve practical problems for the year- area (L/s per square meter) (BOCA 1975). A revi-
round control of the indoor environmental condi- sion and update of A53.l was published in 1973 by
tions. The possibilities for HVAC in buildings ASHRAE (as ASHRAE Standard 62-73), with pri-
seemed to be trouble-free, until the time that con- mary criteria in cubic feet per minute per person (L/s
cerns about energy conservation and the sick build- per person). The latter standard was adopted by the
ing syndrome came into play. These problems have ANSI (formerly ASA) in 1977 and has been desig-
generated the need to pay a lot more attention to nated ANSI Standard B194.l. For the first time in a
design options and equipment maintenance and to ventilation standard, ASHRAE Standard 62-73 pro-
the development of strict standards and design guide- vided a quantitative definition of acceptable out-
lines that take into consideration all aspects of indoor door air and specified conditions under which
environmental quality and energy efficiency. recirculated air could be used. Both minimal and rec-
As far back as the 18th Century, ventilation ommended ventilation rates were specified in the
standards have been in place. Studies by Nevins ASHRAE standard to accommodate fuel economy
(1976), Klauss et al. (1970), and Arnold and (minimal values) or comfort in odor-free environ-
OSheridan (1979) showed that ventilation rates ments (recommended values). Energy savings at
increased from 4 cfm per person (1.9 L/s per per- design summer and winter conditions resulting from
son) in 1824 to 30 cfm per person (14.2 L/s per per- minimal ventilation rates specified in ASHRAE
son) in 1895. A minimal requirement of 30 cfm per Standard 62-73 were estimated to range from 27% to
person (14.2 L/s per person) dominated design of 81% for various occupied spaces, compared with
ventilation systems during the first quarter of the rates in Standard A53.l.
twentieth century, as evidenced by the fact that in In 1975, ASHRAE published Standard 90-75,
1925 the codes of 22 states required a minimal ven- Energy Conservation in New Building Design
tilation rate of 30 cfm (14.2 L/s) of outdoor air per (ASHRAE 1975), to address the need for energy effi-
person (Kusuda 1976). This standard was used until cient buildings. Based upon this standard, the
the 1930s when Yaglou et al. (1936) introduced the National Conference of States on Building Codes
concept of measuring ventilation rate in terms of and Standards, Inc. (NCSBCS), undertook, with the
cubic feet per minute (L/s) per person to achieve an three model-code groups recognized in the United
odor-free environment as a function of available States, to write a model Code for Energy Conserva-
airspace per person. tion in New Building Construction (BOCA 1977).
The Yaglou studies have served as a reference By 1980, legislation either had been passed or was
for the past 40 years. However, many ventilation being considered by 45 states for energy-conserva-
codes and standards specify ventilation requirements tion regulations based on these two documents
in terms of room air changes per hour (ACH), rather (Oglesby 1977).
than exchange rate per person. When ventilation ASHRAE Standard 90-75 was expected to
rates are specified in this way, differences in spatial reduce energy requirements in new buildings by 15-
dimensions and occupancy are lost. For example, 5 60% (Little 1976), but efforts to promote the stan-
ACH in a theater with a 20 ft (6.l m) ceiling height dard resulted in a conflict with ASHRAE Standard
and a sparse occupancy of 100 ft2 (9.3 m2) of floor 62-73. Standard 90-75 stated that the minimum
area per person would result in 167 cfm (79 L/s) per column in Standard 62-73 for each type of occu-
person, whereas the same room-air exchange rate pancy shall be used for design purposes. This
and occupancy in a classroom with an 8 ft (2.4 m) statement in Standard 90-75 effectively deleted the
236 HVAC DESIGN MANUAL FOR HOSPITALS AND CLINICS

recommended column in Standard 62-73 and ments of all relevant codes and standards. Under
caused serious concerns regarding the possibility of these circumstances, the usual procedure has been to
insufficient ventilation in new buildings. For exam- select the largest value that would satisfy the require-
ple, when smoking was allowed in a room ventilated ments of all the codes and standards.
at the minimal rate of 5 cfm (2.4 L/s) per person, the Because of concerns regarding energy consump-
carbon monoxide concentrations approached the tion and costs, some regulations have been promul-
limits specified by the EPA primary ambient-air gated or proposed that are in direct conflict with
quality standards, and particle concentrations those promulgated to protect the health or comfort of
exceeded the proposed limits by a factor of 30 to 60 occupants. One example was the 1977 Assembly Bill
(DHEW 1979; Banks 1978). There is still contro- 983 of Wisconsin, Ventilation Requirements for
versy about what are acceptable concentrations of Public Buildings and Places of Employment. Bill
pollutants and ventilation rates. 983 would have eliminated mandatory minimal ven-
In January 1981, ASHRAE adopted Standard tilation requirements specified in the state building
62-1981 in an effort to resolve some of the problems code (i.e., 5 cfm per person [2.4 L/s per person]) dur-
with Standard 90-75 and to reflect newer design ing the period October l to April l of each year.
requirements, equipment, systems, and instruments. Building owners would have been allowed to close
A comparison of Standard 62-1981, Standard 62-73, or otherwise regulate outside-air intakes to conserve
and the obsolete Standard A53.l shows that major energy during these periods. Bill 983 was passed by
revisions have been made in an effort to resolve the the 1977 General Assembly and vetoed by the gover-
apparent conflict between operating ventilation con- nor; the veto was overridden by the Senate and sus-
trol systems for energy savings and operating them tained by the House. This legislation was
for protection of the health and comfort of the occu- reintroduced as a rider to an appropriations bill in the
pants. The quality of outdoor air to be used for dilu- 1979 General Assembly. It was later amended to
tion and control of indoor air pollution has been allow reduced ventilation only through administra-
defined, not only in terms of the EPA primary stan- tive action; in that form, it passed. The state Depart-
dards, but also in terms of other recognized guide- ment of Industry, Labor and Human Relations,
lines and professional judgment. previously responsible for ventilation requirements,
Values for minimal and recommended ventila- will administer the law.
tion rates have been replaced with required values Ventilation and control of biologic contamina-
for smoking and nonsmoking areas. Nonsmoking tion in medical facilities, especially in some hospital
areas have proposed values similar to the existing treatment areas, has been the subject of much
minimal values, and those for smoking areas are sim- research since the middle of the nineteenth century
ilar to or greater than the values currently recom- (Banks 1978; Lieser 1975). Since 1969, regulations
mended. A method has been specified that will have allowed recirculation in sensitive areas such as
determine the amount of recirculation air required to operating rooms (OR). In this kind of installation, at
compensate for allowable reductions in outdoor air. least, two air filters are required, namely, a prefilter
The amount is determined as a function of air- and a final filter, rated at 25% and 90% efficiency,
cleaner efficiency. The operation of mechanical ven- respectively, according to ASHRAE Standard 52-76
tilation systems during periods of occupancy is spec- (1976). The filters must be properly maintained to
ified as a function of the source of indoor pollutants. secure their optimum performance. Each space in
An alternative method specifies both objective and which inhalation anesthetic agents are administered
subjective criteria for indoor air quality, but the must also be equipped with a separate scavenging
method of achieving control is left to the discretion system for exhausting waste anesthetic gases.
of the operator. With the advent of performance cri- Studies have shown that 80-90% of bacterial
teria for indoor pollutant control, conflicts between contamination found in a wound comes from the
various codes and standards have become more ambient air (Howorth 1985). Proper ventilation is
intensive. necessary to (1) remove anesthetic gases and odors
Comparison of ventilation requirements in released during an operation, which may perma-
ASHRAE Standard 62-73 (ASHRAE 1973), ASA nently or temporarily disturb the occupants; (2)
Standard A 53.1 (ASA 1946), ANSI/ASHRAE Stan- reduce bacteria, viruses, and dust concentration to
dard 62-1981 (ASHRAE 1981), and the more recent acceptable levels, so that the indoor air satisfies the
ANSI/ASHRAE Standard 62-1989 (ASHRAE 1989) aseptic levels in accordance with health guidelines
challenges the building designer and operator to for the patients and space occupants; and (3) provide
select a ventilation rate that will meet the require- optimum and comfortable working conditions for the
VENTILATION STANDARDS AND CURRENT TRENDS 237

occupants to facilitate their demanding work during distinct categories of operating rooms, depending on
an operation. the nature of the surgeries performed, namely, the
Airborne contaminants are usually attached to low risk ORs for routine and low risk surgeries and
dust particles or water molecules. Studies have the high risk ORs for demanding surgeries (i.e.,
shown that 99.9% of all bacteria present in a hospital orthopedic, heart, etc.). In general, the ventilation
are removed by 90-95% efficient filters. This is requirements for the low risk ORs do not differ sig-
because bacteria are typically present in colony
nificantly. However, there can be significant differ-
forming units that are larger than 1 mm. Viruses are
ences for the high risk class. For example, according
more difficult to control since airborne infective
viruses are much less than 1 mm in size. to the German Standard DIN 1946 (1999), the rec-
The number of air changes per hour must be at ommended rates are 60 m3 per m2 per h (1.6 L/s per
least 20, to maintain the OR at a positive pressure, ft2), if the room height is 3.0 m (9.8 ft), or else 20
while the outdoor air requirements for acceptable ACH. However, regulations in other countries, such
indoor air quality must be at least 51 m3/h (14.2 L/s) as France, Switzerland, and the U.K., recommend
per person according to ASHRAE Standard 62. Spe- much higher ventilation rates with laminar air flow
cial requirements and pressure relationships may supply. Most of the other European countries follow
determine different minimum ventilation rates and the German standard.
filter efficiencies (Balaras et al. 2002). Procedures
generating specific indoor contaminants may also F.3.3 U.S. Health Care Ventilation
require higher air-change rates. The surgical suite is StandardsDetails
maintained at a positive pressure in relation to the
other OR secondary use spaces. This minimizes the Ventilation standards promulgated by the AIA
chance of air entering into the surgical suite from the Guidelines and by ASHRAE have been different. An
more contaminated spaces. Zone pressurization attempt was made during the work of the SP 91
introduces specific control requirements that can be Committee in preparing this manual to understand
accomplished by different methodologies, such as the differences between the two standards and to
flow tracking and differential space pressurization. incorporate CFD (computational fluid dynamics)
The indoor air flow patterns in the surgical suite work done by Memarzadeh and Manning (2000).
must ensure that the air masses are directed from the Table F-1 illustrates the differences between the two
clean to the less clean zones and that there are no
and the attempt to reach common ground.
pockets where the air can be trapped. The main air
Table F-1 presents criteria for general pressure
flow pattern should not encounter any obstacles,
especially in the direction toward the main pollution relationships and ventilation of certain hospital areas
sources around the operating table (i.e., medical staff from two published documents: ASHRAE Applica-
and patient). The air velocity must be maintained at tions Handbook (1999a) and AIA Guidelines (2001).
low levels to avoid drafts and turbulence that will Relative humidity and space temperature criteria for
cause air mixing and the dispersion of bacteria and ASHRAE in Table F-1 were also drawn from the
airborne particles. Also, there is the danger that Handbook. The table also presents a compilation of
higher velocity flows could cause impingement on best practice criteria in design application. The
the wound site (Lewis 1993). best practice criteria are summarized in Table 4-1.
The ventilation system must operate continu- Tables 4-1 and F-1 are in a consistent format. To
ously during surgery and even when the OR is not
provide for this, some functional space nomenclature
being used but possibly at a reduced ventilation rate.
may be altered or located differently than in the
This is necessary to maintain continuous aseptic
indoor conditions and stand-by operation. However, source tables.
depending on the ventilation system, implementing a
proper control strategy during the off-use hours can F.4 AIR DIFFUSION CRITERIA
reduce the total air change rate and thus reduce In general, air is supplied to ventilate an
energy consumption (Woods et al. 1986). The air- enclosed space (i.e., a room or various zones in a
flow can be reduced to 30% of the full-load condi- building) for two main reasons:
tions during off-use hours.
To maintain acceptable oxygen concentration
F.3.2 European Health Care Ventilation and dilution and removal of carbon dioxide and
Standards Details other contaminants for safety of the occupants.
The European standards for hospital ORs differ However, it should be noted that supplying the
in the various member states. There are usually two specified or mandated rates for ventilation does
Table F-1. Comparison of Engineering Best Practice with AIA Guidelines* and ASHRAE Handbook**
(For a larger version of this table see insert.)
Pressure Relationship to Adjacent Minimum Air Changes of Outdoor Minimum Total Air Changes per All Air Exhausted Directly to
Areas (a) (2) Air per Hour (b) (3) Hour (c) (4) (5) Outdoors (6)
Function Space Manual Handbook AIA (1) Manual Handbook AIA (1) Manual Handbook AIA (1) Manual Handbook AIA (1)
Surgery And Critical Care
Operating Room (all outdoor air system) P 15 15 Yes
Operating Room (recirculating air system) P P 5 5 25 25 Optional
Operating/surgical cystoscopic rooms (10), (11) P Out 5 3 25 15
Delivery Room (all outdoor air system) P 15 15 Optional
Delivery Room (recirculating air system) P 5 25 Optional
Delivery Room (10) P Out 5 3 25 15
Recovery Room E 2 2 2 6 6 6 Optional
Critical and Intensive Care 2 2 6 6
Newborn Intensive Care 2 2 6 6
Treatment Room (13) 6 6
Nursery Suite P P 5 5 12 12 Optional
Trauma Room (f) (13) P Out 5 3 12 12 15 Optional
Trauma Room (crisis or shock) (f) (13a) P 3 15 Yes
Trauma Room (conventional ED or treatment) (f) (13a) P 2 6
Anesthesia Storage (see code requirements) Optional 8 Yes
Anesthesia Gas Storage N In 8 8 Yes Yes
Endoscopy (11) N In 2 2 6 6
Bronchoscopy N In 2 2 12 12 Yes Yes
ER Waiting Rooms N In 2 2 12 12 Yes Yes (14), (15)
Triage N In 2 2 12 12 Yes Yes (14)
Radiology Waiting Rooms N In 2 2 12 12 Yes Yes (14), (15)
Class A Operating (procedure) Room N Out 3 3 15 15
Nursing
Patient Room 2 2 2 6 4 6 (16) Optional
Toilet Room (g) N N ln Optional Optional 10 10 10 Yes Yes Yes
Intensive Care P 2 6 Optional
Newborn Nursery Suite 2 2 6 6
Protective Isolation (i) P 2 15 Yes
Infectious Isolation (h) 2 6 Yes
Protective Environment Room (11), (17) P Out 2 2 12 12
Airborne Infection Isolation Room (11), (18) N In 2 2 12 12 Yes Yes (15)
Isolation Alcove or Anteroom (17), (18) P/N In/Out 2 2 10 10 10 Yes Yes Yes
Labor/Delivery/Recovery 2 6 (16)
Labor/Delivery/Recovery/Postpartum 2 6 (16)
Labor/Delivery/Recovery/Postpartum (LDRP) (16) E 2 2 6 4 Optional
Patient Corridor E 2 2 4 4 2 Optional
Public Corridor N 2 2
Ancilliary
Radiology (19) x-ray (surgery and critical care) P 3 15 Optional
Radiology (19) x-ray (diagnostic and treatment) 2 2 6 6 6 Optional
Radiology (19) x-ray (surgery/critical care and catherization) P Out 3 3 15 15
Radiology (19) Darkroom N N In 2 2 10 10 10 Yes Yes (j) Yes
Laboratory, general (19) N N 2 2 6 6 6 Yes Yes
Laboratory, bacteriology N N 2 2 6 6 Yes Yes
Laboratory, biochemistry (19) P P Out 2 2 6 6 6 Optional Optional
Laboratory, cytology N N In 2 2 6 6 6 Yes Yes Yes
Laboratory, glasswashing N N In Optional Optional 10 10 10 Yes Yes Yes
Laboratory, histology N N In 2 2 6 6 6 Yes Yes Yes
Microbiology (19) N In 6 6 Yes Yes
Laboratory, nuclear medicine N N In 2 2 6 6 6 Yes Yes Yes
Laboratory, pathology N N In 2 2 6 6 6 Yes Yes Yes
Laboratory, serology P P Out 2 2 6 6 6 Yes Optional
Laboratory, sterilizing N N In Optional Optional 10 10 10 Yes Yes Yes
Laboratory, media transfer P P 2 2 4 4 Optional Optional
Autopsy N 2 12 Yes
Autopsy Room (11) N In 2 12 12 Yes Yes
Nonrefrigerated Body-Holding Room (k) N N In Optional Optional 10 10 10 Yes Yes Yes
Pharmacy P P Out 2 2 4 4 4 Optional
Administration
Admitting and Waiting Rooms N N 2 2 6 6 Yes Yes
Diagnostic And Treatment
Bronchoscopy, sputum collection, and pentamidine
administration N N 2 2 12 10 Yes Yes
Examination Room 2 2 6 6 6 Optional
Medication Room P P Out 2 2 4 4 4 Optional
Treatment Room 2 2 6 6 6 Optional
Physical Therapy and Hydrotherapy N N In 2 2 6 6 6 Optional
Soiled Workroom or Soiled Holding N N In 2 2 10 10 10 Yes Yes Yes
Clean Workroom or Clean Holding P P Out 2 2 4 4 4 Optional
Sterilizing And Supply
ETO-Sterilzer Room N In 10 10 Yes Yes
Sterilizer Equipment Room N N In Optional 10 10 10 Yes Yes Yes
Central Medical and Surgical Supply
Soiled or Decontamination Room N N In 2 2 6 6 6 Yes Yes Yes
Clean Workroom P Out 2 4 4
Sterile Storage P Out 2 4 4
Clean Workroom and Sterile Storage P 2 4 Optional
Equipment Storage 2 (Optional) 2 Optional
Service
Food Preparation Center (I) (20) 2 2 10 10 10 Yes Yes
Warewashing N N In Optional Optional 10 10 10 Yes Yes Yes
Dietary Day Storage In Optional Optional 2 2 2 Optional
Laundry, general N N 2 2 10 10 10 Yes Yes Yes
Soiled Linen Sorting and Storage N N In Optional Optional 10 10 10 Yes Yes Yes
Clean Linen Storage P P Out 2 (Optional) 2 (Optional) 2 2 2 Optional
Linen and Trash Chute Room N N Optional Optional 10 10 Yes Yes
Soiled Linen and Trash Chute Room In 10 Yes
Bedpan Room N N In Optional Optional 10 10 10 Yes Yes Yes
Bathroom N N In Optional Optional 10 10 10 Yes Optional*
Janitors Closet N N In Optional Optional 10 10 10 Yes Optional Yes
Table F-1. Comparison of Engineering Best Practice with AIA Guidelines* and ASHRAE Handbook** (Continued)
(For a larger version of this table see insert.)
Air Recirculated Within Room
Units (d) (7) Relative Humidity (8) (%) Design Temperature (9) (F/C) Proposed
Function Space Manual Handbook AIA (1) Manual Handbook AIA (1) Manual Handbook AIA (1) Comments
Surgery And Critical Care
Operating Room (all outdoor air system) No 45-55 62-80
Operating Room (recirculating air system) No No 30-60 68-75 A1
Operating/surgical cystoscopic rooms (10), (11) No No 30-60 30-60 68-75 68-73 (20-23) (12) A1
Delivery Room (all outdoor air system) No 45-55 62-80
Delivery Room (recirculating air system) No
Delivery Room (10) No No 30-60 30-60 68-75 68-73 (20-23) B1
Recovery Room No No No 30-60 45-55 30-60 70-75 75 70-75 (21-24) C1
Critical and Intensive Care No No 30-60 30-60 70-75 70-75 (21-24) C2
Newborn Intensive Care No No 30-60 30-60 72-78 72-78 (22-26) C2
Treatment Room (13) 30-60 70-75 75 (24) C2
Nursery Suite No No 30-60 30-60 75-80 75-80 D1
Trauma Room (f) (13) No No 45-55 30-60 62-80 70-75 (21-24)
Trauma Room (crisis or shock) (f) (13a) Yes 30-60 70-75 B2
Trauma Room (conventional ED or treatment) (f) (13a) No 30-60 70-75 B2
Anesthesia Storage (see code requirements) No
Anesthesia Gas Storage C3
Endoscopy (11) No No 30-60 30-60 68-73 68-73 (20-23) C2
Bronchoscopy No No 30-60 30-60 68-73 68-73 (20-23) C2
ER Waiting Rooms 30-60 70-75 70-75 (21-24) C2
Triage 70-75 70-75 (21-24) C2
Radiology Waiting Rooms 70-75 70-75 (21-24) C2
Class A Operating (procedure) Room No No 30-60 30-60 70-75 70-75 (21-24) A4
Nursing
Patient Room Optional 30-60 30 (winter), 50 (summer) 70-75 75 70-75 (21-24) B3
Toilet Room (g) No No C3
Intensive Care No 30-60 75-80
Newborn Nursery Suite No No 30-60 30-60 72-78 72-78 (22-26) C2
Protective Isolation (i) Optional
Infectious Isolation (h) No 30 (winter), 50 (summer) 75
Protective Environment Room (11), (17) No No 70-75 75 (24) C2
Airborne Infection Isolation Room (11), (18) No No 70-75 75 (24) C2
Isolation Alcove or Anteroom (17), (18) No No No D1
Labor/Delivery/Recovery 70-75 (21-24)
Labor/Delivery/Recovery/Postpartum 70-75 (21-24)
Labor/Delivery/Recovery/Postpartum (LDRP) (16) Optional 30-60 30 (winter), 50 (summer) 70-75 75 A2
Patient Corridor Optional D2
Public Corridor
Ancilliary
Radiology (19) x-ray (surgery and critical care) No
Radiology (19) x-ray (diagnostic and treatment) Optional 30-60 40-50 72-78 78-80 75 (24) D2
Radiology (19) x-ray (surgery/critical care and catherization) No No 30-60 30-60 70-75 70-75 (21-24) C2
Radiology (19) Darkroom No No No D2
Laboratory, general (19) No No 30-60 Comfort Range 70-75 Comfort Range 75 (24) D2
Laboratory, bacteriology No No 30-60 Comfort Range 70-75 Comfort Range D2
Laboratory, biochemistry (19) No No No 30-60 Comfort Range 70-75 Comfort Range 75 (24) D2
Laboratory, cytology No No No 30-60 Comfort Range 70-75 Comfort Range 75 (24) D3
Laboratory, glasswashing Optional Comfort Range Comfort Range D3
Laboratory, histology No No No 30-60 Comfort Range 70-75 Comfort Range 75 (24) C3
Microbiology (19) No No 30-60 70-75 75 (24) C4
Laboratory, nuclear medicine No No No 30-60 Comfort Range 70-75 75 (24) C5
Laboratory, pathology No No No 30-60 Comfort Range 70-75 75 (24) C4
Laboratory, serology No No No 30-60 Comfort Range 70-75 75 (24) C4
Laboratory, sterilizing No No 30-60 Comfort Range 70-75 C4
Laboratory, media transfer No No 30-60 Comfort Range 70-75 D2
Autopsy No
Autopsy Room (11) No No C4
Nonrefrigerated Body-Holding Room (k) No No 70 70 (21) C3
Pharmacy Optional 30-60 70-75 C4
Administration
Admitting and Waiting Rooms Optional 30-60 70-75 D4
Diagnostic And Treatment
Bronchoscopy, sputum collection, and pentamidine
administration Optional 30-60 70-75 D4
Examination Room Optional 30-60 70-75 75 (24) C4
Medication Room Optional 30-60 70-75 C4
Treatment Room Optional 30-60 30 (winter), 50 (summer) 70-75 75 75 (24) C6
Physical Therapy and Hydrotherapy Optional 30-60 Comfort Range 72-80 Comfort Range/up to 80 75 (24) C4
Soiled Workroom or Soiled Holding No No No 30-60 Comfort Range 72-78 Comfort Range D3
Clean Workroom or Clean Holding Optional C3
Sterilizing And Supply
ETO-Sterilzer Room No No 30-60 75 (24) C5
Sterilzer Equipment Room No No C4
Central Medical and Surgical Supply
Soiled or Decontamination Room No No No 30-60 Comfort Range 72-78 Comfort Range 68-73 (20-23) D5
Clean Workroom No No 30-60 30-60 72-78 75 (24) D8
Sterile Storage 30-60 (Max) 70 72-78 D7
Clean Workroom and Sterile Storage Optional Under 50 Comfort Range
Equipment Storage Optional
Service
Food Preparation Center (I) (20) No No No C3
Warewashing No No No C3
Dietary Day Storage No No C7
Laundry, general No No D3
Soiled Linen Sorting and Storage No No No C3
Clean Linen Storage Optional C3
Linen and Trash Chute Room No No C2
Soiled Linen and Trash Chute Room No D2
Bedpan Room No No C3
Bathroom No No 72-78 75 (24) C8
Janitors Closet No No No D3
* AIA GuidelinesGuidelines for Design and Construction of Hospital and Health Care Facilities, Chapter 7, Table 7.2, American Institute of Architects Academy, 2001.
** ASHRAE Handbook1999 ASHRAE HandbookHVAC Applications, Chapter 7, Table 3.
240 HVAC DESIGN MANUAL FOR HOSPITALS AND CLINICS

Notes to Table F-1, I

I. 1999 ASHRAE Handbook table references with some clarifications

P = Positive
N = Negative
+ = Continuous directional control not required

(a) Where continuous directional control is not required, variations should be minimized, and in no case should a lack of
directional control allow the spread of infection from one area to another. Boundaries between functional areas
(wards or departments) should have directional control. Lewis (1998) describes methods for maintaining directional
control by applying air-tracking controls.

(b) Ventilation in accordance with ASHRAE Standard 62, Ventilation for Acceptable Indoor Air Quality, should be used
for areas for which specific ventilation rates are not given. Where a higher outdoor air requirement is called for in
Standard 62 than in Table 3 (1999 ASHRAE HandbookHVAC), the higher value should be used.

(c) Total air changes indicated should be either supplied or, where required, exhausted.

(d) Recirculating HEPA filter units used for infection control (without heating or cooling coils) are acceptable.

(e) For operating rooms, 100% outside air should be used only when codes require it and only if heat recovery devices
are used.

(f) The term trauma/shock room as used here is the entry area to the emergency room used for general initial treatment
and stabilization of accident victims. The operating room within the Emergency Department that is routinely used for
emergency surgery should be treated as an operating room.

(g) See section on Patient Rooms for discussion on design of central toilet exhaust systems.

(h) The Airborne Infection (infectious) isolation rooms described in this table are those that might be used for infectious
patients in the average community hospital. The rooms are negatively pressurized. Some isolation rooms may have a
separate anteroom. Refer to the discussion in the chapter for more detailed information. Where highly infectious
respirable diseases such as tuberculosis are to be isolated, increased air change rates should be considered.

(i) Protective Environment isolation rooms are those used for immunosuppressed patients. The room is positively pres-
surized to protect the patient. Anterooms are generally required and should be negatively pressurized with respect to
the patient room.

(j) All air need not be exhausted if darkroom equipment has scavenging exhaust duct attached and meets ventilation
standards on NIOSH, OSHA, and local employee exposure limits.

(k) The nonrefrigerated body-holding room is only for facilities that do not perform autopsies on-site and use the space
for short periods while waiting for the body to be transferred.

(l) Food preparation centers should have an excess of air supply for positive pressure when hoods are not in operation.
The number of air changes may be reduced or varied for odor control when the space is not in use. Minimum total air
changes per hour should be that required to provide proper makeup air to kitchen exhaust systems. See Chapter 30
(1999 ASHRAE Handbook), Kitchen Ventilation.
VENTILATION STANDARDS AND CURRENT TRENDS 241

Notes to Table F-1, II

II. 2001 AIA Guidelines table references with some clarifications


(1) The ventilation rates in this table cover ventilation for comfort, as well as for asepsis and odor control in areas of acute
care hospitals that directly affect patient care and are determined based on health care facilities being predominantly No
Smoking facilities. Where smoking may be allowed, ventilation rates will need adjustments. Areas where specific venti-
lation rates are not given in the table shall be ventilated in accordance with ASHRAE Standard 62, Ventilation for Accept-
able Indoor Air Quality, and ASHRAE HandbookHVAC Applications. Specialized patient care areas, including organ
transplant units, burn units, specialty procedure rooms, etc., shall have additional ventilation provisions for air quality con-
trol as may be appropriate. OSHA standards and/or NIOSH criteria require special ventilation requirements for employee
health and safety within health care facilities.
(2) Design of the ventilation system shall provide air movement that is generally from clean to less clean areas. If any form of
variable air volume or load shedding system is used for energy conservation, it must not compromise the corridor-to-room
pressure balancing relationships or the minimum air changes required by the table.
(3) To satisfy exhaust needs, replacement air from the outside is necessary. Table 7.2 (2001 AIA Guidelines) does not attempt
to describe specific amounts of outside air to be supplied to individual spaces except for certain areas such as those listed.
Distribution of the outside air, added to the system to balance required exhaust, shall be as required by good engineering
practice. Minimum outside air quantities shall remain constant while the system is in operation.
(4) Number of air changes may be reduced when the room is unoccupied if provisions are made to ensure that the number of
air changes indicated is reestablished any time the space is being utilized. Adjustments shall include provisions so that the
direction of air movement shall remain the same when the number of air changes is reduced. Areas not indicated as having
continuous directional control may have ventilation systems shut down when space is unoccupied and ventilation is not
otherwise needed, if the maximum infiltration or exfiltration permitted in Note 2 is not exceeded and if adjacent pressure
balancing relationships are not compromised. Air quantity calculations must account for filter loading such that the indi-
cated air change rates are provided up until the time of filter change-out.
(5) Air change requirements indicated are minimum values. Higher values should be used when required to maintain indi-
cated room conditions (temperature and humidity), based on the cooling load of the space (lights, equipment, people, exte-
rior walls and windows, etc.). Certain operating rooms may require lower or higher temperature or humidity conditions.
(6) Air from areas with contamination and/or odor problems shall be exhausted to the outside and not recirculated to other
areas. Note that individual circumstances may require special consideration for air exhaust to the outside, e.g., in intensive
care units, in which patients with pulmonary infection are treated, and rooms for burn patients.
(7) Air Recirculated within Room Units refers to those local units that are used primarily for heating and cooling of air and
not disinfection of air. Because of cleaning difficulty and potential for buildup of contamination, recirculating room units
shall not be used in areas marked No. However, for airborne infection control, air may be recirculated within individual
isolation rooms if HEPA filters are used. Isolation and intensive care unit rooms may be ventilated by reheat induction
units in which only the primary air supplied from a central system passes through the reheat unit. Gravity-type heating or
cooling units, such as radiators or convectors, shall not be used in operating rooms and other special care areas. See
Appendix A (2001 AIA Guidelines) for a description of recirculation units to be used in isolation rooms. Recirculating
devices with HEPA filters may have potential uses in existing facilities as interim, supplemental environmental controls to
meet requirements for the control of airborne infectious agents. Limitations in design must be recognized. The design of
either portable or fixed systems should prevent stagnation and short-circuiting of airflow. The supply and exhaust loca-
tions should direct clean air to areas where health care workers are likely to work, across the infectious source, and then to
the exhaust, so that the health care worker is not in position between the infectious source and the exhaust location. The
design of such systems should also allow for easy access for scheduled preventive maintenance and cleaning.
(8) The ranges listed are the minimum and maximum limits where control is specifically needed. The maximum and mini-
mum limits are not intended to be independent of a spaces associated temperature. The humidity is expected to be at the
higher end of the range when the temperature is also at the higher end, and vice versa.
(9) Where temperature ranges are indicated, the systems shall be capable of maintaining the rooms at any point within the
range during normal operation. A single figure indicates a heating or cooling capacity of at least the indicated temperature.
This is usually applicable when patients may be undressed and require a warmer environment. Nothing in these guidelines
shall be construed as precluding the use of temperatures lower than those noted when the patients' comfort and medical
conditions make lower temperatures desirable. Unoccupied areas such as storage rooms shall have temperatures appropri-
ate for the function intended.
(10) National Institute for Occupational Safety and Health (NIOSH) Criteria Documents regarding Occupational Exposure to
Waste Anesthetic Gases and Vapors, and Control of Occupational Exposure to Nitrous Oxide indicate a need for both local
exhaust (scavenging) systems and general ventilation of the areas in which the respective gases are utilized.
(11) Differential pressure shall be a minimum of 0.01 in. w.g. (2.5 Pa). If alarms are installed, allowances shall be made to pre-
vent nuisance alarms of monitoring devices.
242 HVAC DESIGN MANUAL FOR HOSPITALS AND CLINICS

Notes to Table F-1, II (Continued)

The verification of airflow direction can include a simple visual method such as smoke trail, ball-in-tube, or flutter-
strip. These devices will require a minimum differential air pressure to indicate airflow direction.
(12) Some surgeons may require room temperatures that are outside of the indicated range. All operating room design condi-
tions shall be developed in consultation with surgeons, anesthesiologists, and nursing staff.
(13) The note in AIA Guidelines is clarified. (13a) The term trauma room as used here is the operating room space in the emer-
gency department or other trauma reception area that is used for emergency surgery. (13b) The first aid room and/or
emergency room used for initial treatment of accident victims may be ventilated as noted for the treatment room.
Treatment rooms used for bronchoscopy shall be treated as bronchoscopy rooms. Treatment rooms used for cryosurgery
procedures with nitrous oxide shall contain provisions for exhausting waste gases.
(14) In a ventilation system that recirculates air, HEPA filters can be used in lieu of exhausting the air from these spaces to the
outside. In this application, the return air shall be passed through the HEPA filters before it is introduced into any other
spaces.
(15) If it is not practical to exhaust the air from the airborne infection isolation room to the outside, the air may be returned
through HEPA filters to the air-handling system exclusively serving the isolation room.
(16) Total air changes per room for patient rooms, labor/delivery/recovery rooms, and labor/delivery/recovery/postpartum
rooms may be reduced to 4 when supplemental heating and/or cooling systems (radiant heating and cooling, baseboard
heating, etc.) are used.
(17) The protective environment airflow design specifications protect the patient from common environmental airborne infec-
tious microbes (i.e., Aspergillus spores). These special ventilation areas shall be designed to provide directed airflow from
the cleanest patient area to less clean areas. These rooms shall be protected with HEPA filters at 99.97 percent efficiency
for 0.3 m sized particle in the supply airstream. These interrupting filters protect patient rooms from maintenance-
derived release of environmental microbes from the ventilation system components. Recirculation HEPA filters can be
used to increase the equivalent room air exchanges. Constant volume airflow is required for consistent ventilation for the
protected environment. If the facility determines that airborne infection isolation is necessary for protective environment
patients, an anteroom should be provided. Rooms with reversible airflow provisions for the purpose of switching between
protective environment and airborne infection isolation functions are not acceptable.
(18) The infectious disease isolation room described in these guidelines is to be used for isolating the airborne spread of infec-
tious diseases, such as measles, varicella, or tuberculosis. The design of airborne infection isolation (AII) rooms should
include the provision for normal patient care during periods not requiring isolation precautions. Supplemental recirculat-
ing devices may be used in the patient room, to increase the equivalent room air exchanges; however, such recirculating
devices do not provide the outside air requirements. Air may be recirculated within individual isolation rooms if HEPA fil-
ters are used. Rooms with reversible airflow provisions for the purpose of switching between protective environment and
AII functions are not acceptable.
(19) When required, appropriate hoods and exhaust devices for the removal of noxious gases or chemical vapors shall be pro-
vided (see Section 7.31.D14 and 7.31.D15, 2001 AIA Guidelines, and NFPA 99).
(20) Food preparation centers shall have ventilation systems whose air supply mechanisms are interfaced appropriately with
exhaust hood controls or relief vents so that exfiltration or infiltration to or from exit corridors does not compromise the
exit corridor restrictions of NFPA 90A, the pressure requirements of NFPA 96, or the maximum defined in the table. The
number of air changes may be reduced or varied to any extent required for odor control when the space is not in use. See
Section 7.31.D1.p., 2001 AIA Guidelines.
VENTILATION STANDARDS AND CURRENT TRENDS 243

Notes to Table F-1, III

III. Notes
A1 The operating room ventilation rates are different between the 2001 AIA Guidelines for Design and Construction of Hos-
pital and Health Care Facilities (2001 AIA Guidelines) and 1999 ASHRAE HandbookHVAC Applications (1999
ASHRAE Handbook). Consider if the surgery performed is minor or major. No reduction of ventilation rate is suggested
even when 100% outside air is used. Ventilation rate recommendation based upon 1999 ASHRAE Handbook. Special
temperature and humidity conditions in certain situations may be required. The temperature setpoint should be able to be
adjusted by surgical staff over a range of 62 to 80F (17 to 27C). It should also be noted that 64 to 72F (18 to 22C) is the
usual temperature range for ORs unless special circumstances exist, and 45-45% humidity is a preferable target but 30-
60% is an acceptable range.
The required air change rates are also a function of space temperature setpoint, supply air temperature, sensible
and latent heat load in the space. Appendix I describes the recent research on this subject and describes different ven-
tilation system performances at different ACH. Continued use of 25 ACH (as recommended in ASHRAE Hand-
bookApplications) provides a safety margin to accommodate cooling load in modern operating rooms generated
due to increasing use of electronic equipment during surgery, which generates large sensible heat load.
The designer should review the type of clinical activity and severity of the surgery performed before selecting
the appropriate ventilation rates, temperature, and humidity conditions.
A2 The labor/delivery/recovery/postpartum ventilation rates are different between the 2001 AIA Guidelines and 1999
ASHRAE Handbook. The designer should review the type of clinical activity and severity of the surgery performed before
selecting the appropriate ventilation rates.
Ventilation rate recommendation based upon 2001 AIA Guidelines. Temperature and humidity is from 1999
ASHRAE Handbook. The design temperature is shown to have range.
A3 The Protective or Infectious Isolation room ventilation rates are different between the 2001 AIA Guidelines and 1999
ASHRAE Handbook. The designer should review the type of clinical activity and severity of the surgery performed before
selecting the appropriate ventilation rates: recommendation based upon 2001 AIA Guidelines, recommendation based
upon 1999 ASHRAE Handbook.
A4 New category added to account for operating rooms in day surgery application.
B1 The delivery room ventilation rates are different between the new 2001 AIA Guidelines and 1999 ASHRAE Handbook.
The designer should review the type of clinical activity and severity of the surgery performed before selecting the appro-
priate ventilation rates. Ventilation rate recommendation are based upon 1999 ASHRAE Handbook. 2001 AIA Guidelines
for temperature and humidity conditions are adopted.
B2 The trauma room ventilation rates are different between the 1999 ASHRAE Handbook and the 2001 AIA Guidelines. The
designer should review the type of clinical activity and severity of the surgery performed before selecting the appropriate
ventilation rates. Consider if the surgery performed is minor or major
Ventilation rate recommendation is based upon 1999 ASHRAE Handbook. Temperature and humidity require-
ments are also based upon 1999 ASHRAE Handbook.
B3 2001 AIA Guidelines and 1999 ASHRAE Handbook standards are different. However, recent 1999 ASHRAE Handbook
published research was used to determine ventilation rates in the new 2001 AIA Guidelines. Humidity and temperature
recommendations are based upon 1999 ASHRAE Handbook. Space temperature design range is defined.
C1 Similar standards between 2001 AIA Guidelines and 1999 ASHRAE Handbook. No pressure difference between recom-
mendation is made. The relative humidity requirement is more restrictive in 1999 ASHRAE Handbook and as a design
guide it is recommended. The design guide is more restricted for space temperature as well.
C2 Only defined in 2001 AIA Guidelines. Same condition adapted for best practices.
C3 Similar standards between 2001 AIA Guidelines and 1999 ASHRAE Handbook.
C4 Similarly between 2001 AIA Guidelines and 1999 ASHRAE Handbook. Wider temperature is recommended and humid-
ity ranges are also specified.
C5 Mostly defined in 2001 AIA Guidelines. New humidity and temperature ranges are also specified.
C6 In Treatment Room similar standard between 1999 ASHRAE Handbook and 2001 AIA Guidelines. However, 1999
ASHRAE Handbook temperature and humidity range is adopted. A range is provided for temperature setting.
C7 Similarity between 1999 ASHRAE Handbook and 2001 AIA Guidelines. However, 2001 AIA Guidelines recommenda-
tion that space be negative is not adopted.
C8 Similar between 2001 AIA Guidelines and 1999 ASHRAE Handbook. Toilet is exhausted directly outdoors.
244 HVAC DESIGN MANUAL FOR HOSPITALS AND CLINICS

Notes to Table F-1, III (Continued)

D1 Only defined in 1999 ASHRAE Handbook. The pressure with respect to adjacent space may be positive or negative
depending upon the type of anteroom.
D2 Only defined in 1999 ASHRAE Handbook.
D3 Similar standards between 2001 AIA Guidelines and 1999 ASHRAE Handbook. One has more details. Recommendation
based upon 1999 ASHRAE Handbook.
D4 Defined in 1999 ASHRAE Handbook. Humidity and design temperature added.
D5 Some similarities between 1999 ASHRAE Handbook and 2001 AIA Guidelines. However, 2001 AIA Guidelines has no
humidity recommendation and has a lower temperature range. 2001 AIA Guidelines suggests 68-73F (20-23C), which
appears too restrictive.
D6 Defined by 2001 AIA Guidelines. Minimum outside air is added.
D7 Similar between 2001 AIA Guidelines and 1999 ASHRAE Handbook. Humidity levels are adopted from 1999 ASHRAE
Handbook. Specific temperature range is provided.

not guarantee adequate dilution or removal of inevitable uncertainty associated with the complexity
contaminants if the air is not uniformly diffused of air movement. Furthermore, the increasing cost of
throughout the occupied space. In particular, the equipment and energy, combined with the growing
further the airflow pattern differs from a plug emphasis on environmentally friendly design and
or piston flow, the worse the dilution of the operation, has forced designers to consider alterna-
contaminant. tive means of designing ventilation systems, which
To provide a thermally controlled environment utilize computational or analytical techniques.
that is acceptable to the occupants. An accept- One such technique is based on computational
able thermal environment has been defined as fluid dynamics, known as CFD. The technique of
one in which at least 80% of the occupants, CFD presumes that the equations that govern the
clothed normally and engaged in sedentary or physical behavior of a flow/thermal system are
near-sedentary activities, would express thermal known, in the form of the Navier-Stokes, thermal
comfort, which is defined as that condition of energy, and/or species equations, with the appropri-
mind which expresses satisfaction with the ther- ate equation of state. The equations require the con-
mal environment (ASHRAE 1974). This crite- servation, both locally and globally, of mass,
rion is typically calculated using the Fanger momentum, thermal energy, and species concentra-
index, Predicted Percentage Dissatisfied (PPD), tion. The general form of the equations can be writ-
which is calculated in conjunction with another ten as:
index, namely, Predicted Mean Vote (PMV).

These indices are dependent on many factors: ---- ( ) + div ( V grad ) = S (1)
t
the activity and typical clothing of the occupants
and the combination of air temperature, mean Transient + Convection Diffusion = Source
radiant temperature, relative humidity, and air
where
velocity. Therefore, all these factors must be
appropriate for the occupants to feel comfort- = density
able. V = velocity vector
= dependent variable
Conventionally, air diffusion control has been = exchange coefficient (laminar + turbulent)
designed and installed to meet the criteria for ther- S = source or sink
mal comfort, with the assumption that the air-quality
The equations are partial differential equations
criteria will be met simultaneously.
(PDEs). The dependent variables to be calculated are
the velocity components (u, v, w), pressure (P), tem-
F.5 NEW TREND IN VENTILATION
perature (T), and some scalar (F), and the indepen-
SYSTEM DESIGN
dent variables are the space coordinates (x, y, z) and
In general, the design of air inlet and outlet and time (t). To solve the equations, initial and boundary
overall air distribution from ventilation systems has conditions must be specified around the boundary of
largely relied on the experience of the design engi- the system (domain). Because the equations are
neer and rules of thumb. Although this approach has highly nonlinear, they are not solvable by explicit,
proved successful, such designs have traditionally closed-form analytical methods. Approximate
carried significant safety margins to allow for the (numerical) methods, such as the finite difference
VENTILATION STANDARDS AND CURRENT TRENDS 245

method, finite volume method, or the finite element erwise couldn't be revealed with physical exper-
method, are typically used for solving the equations. iments.
In all these approaches, the domain is dis- The cost for a CFD analysis is less compared to
cretized (divided) into cells or elements and nodal the cost of performing experiments.
points are defined. Upon solution of the equations, The ability to consider hostile environments.
the values of the dependent variables (u, v, w, P, T, F) For CFD, it is never too toxic, too hot, or too
are specified at each node, and derived quantities fast. Parametric studies are easily performed
such as vorticity and stream function may also be with CFD.
obtained. In addition, surface film coefficients (h) or The quick and systematic screening of a large
shear stress (drag) may be calculated and used for number of design concepts, before a prototype
further design analysis. of the design is ever built.
From the three options for the numerical solu- Detailed local information as well as surface
tion, the finite volume and finite element methods information. Typically, physical tests provide
are currently the most popular. In finite volume, data only at selected points; an alternative tech-
fluxes are balanced across all cells of a control vol- nique must be used to obtain surface informa-
ume, ensuring the local and global conservation tion.
implicit in the physical process being modeled. Flux
balance is not necessarily conserved in a finite ele- A disadvantage of the use of CFD is that the
ment framework, but the computational grid result- codes are not black boxes and a clear and compre-
ing from discretization is, by default, irregular hensive understanding of the fluid mechanics and
(unstructured) and the procedure is suitable for prob- heat transfer phenomena is necessary. Training and
lems with complicated geometries and boundary experience in the use of CFD software is necessary
conditions and for coupled analysis, such as fluid- in order to be able to properly use this kind of tool
structure interaction. and to be able to interpret the results correctly. CFD
The CFD technique, however, has far more is particularly prone to the adage garbage in, gar-
applications than building services. Typical ques- bage out.
tions that can be answered by CFD are: Furthermore, it should be noted that CFD is
NOT trouble-free nor will it replace physical experi-
Where should the flow inlets and/or outlets be ments. For certain problems, the boundary and initial
located? conditions are not known or the physics may not be
What kinds of velocities are expected at a speci- understood to a point where users can be confident
fied portion of the system? that they have taken every factor into account after
What does the flow pattern look like? creating a CFD model.
What is the heat transfer coefficient (or Nusselt Moreover, turbulence, chemical reaction, radia-
number) on a specified portion of the system tion, and two-phase systems (such as boiling, con-
surface? densation, and multiphase flow through a pipe) are
What is the temperature distribution in a speci- very challenging as the equations to build a CFD
fied portion of the system? model are not well understood. For these cases,
What is the drag on a specified portion of the empiricism will continue to be the feasible method to
system surface? generate engineering design data.
What is the time response of the system with For all practical purposes, CFD does not replace
respect to heat transfer and flow development? physical experiments, but it can significantly reduce
How is a species or chemical reactant or product the amount of experimental work that engineers do.
transported by fluid flow? A typical approach that seems to be working for the
automobile industry is to perform laboratory-scale
Some of the advantages of a CFD analysis over experiments and model them with CFD in order to
experimental data, include: validate that CFD is predicting acceptably accurate
solutions. The engineer may then scale up the model
The ability to simulate realistic systems. computationally, as this is significantly cheaper and
The ability to set precise and ideal conditions on faster than doing so in the real world.
the boundary of a CFD model. Upon experimental validation of a specific CFD
Avoidance of problems related to the intrusion model, one can study different configurations with-
by the measuring device. For example, CFD out building excessive numbers of physical models.
may discover significant flow features that oth- Thus, when CFD works, the number of prototypes is
246 HVAC DESIGN MANUAL FOR HOSPITALS AND CLINICS

reduced, cutting manufacturing costs and reducing this value was close to the CDC value (1994) of 12
overall time to market. This leads to a quicker turn- ACH, the higher value was retained. Memarzadeh
around in the design cycle. The result is the avoid- and Manning (2000) concluded that 6 ACH and 4
ance of the need to divert significant amounts of time ACH (if baseboard heating is provided) are the mini-
and resources to building and evaluating prototypes. mum ventilation rates required to provide satisfac-
Ongoing work has been undertaken by numer- tory patient comfort. The analysis also showed that
ous organizations (and mainly the by the National the previously recommended ventilation rate of 2
Institutes of Health [NIH] in Bethesda, Maryland) to ACH would result in a stuffy room. In both of
demonstrate the use of CFD, also known as airflow these studies, analysis algorithms were incorporated
modeling, to assess the performance of the ventila- to the standard airflow modeling analysis to pro-
tion system as applied to building services and vali- vide the necessary information: in the former case, a
date the results with empirical data. The work particle tracking routine was developed, while com-
(Memarzadeh 1996, 1998; Memarzadeh and Jiang fort and uniformity index calculators, such as the
2000; Memarzedeh and Manning 2000) has used Fanger indices mentioned earlier, were added in the
CFD to tackle the design of ventilation systems in a latter case.
variety of different built environments.
In Memarzadeh (1996), CFD was used to con-
F.6 CONCLUSIONS
sider laboratory ventilation system design such that
hood containment was optimized. Over 100 alterna- This paper has outlined a brief history of the
tive designs were considered to derive applicable changing standards in ventilation systems in the built
guidelines, which would have been a massive under- environment, in particular those that relate to com-
taking experimentally. Similarly, Memarzadeh fort and air quality. The standards have been succes-
(1998), in a study that considered appropriate animal sively refined, with criteria such as ACH scrutinized
research facility ventilation design, considered over carefully, as they directly impact the energy con-
100 different design scenarios. In this case, a mini- sumption and operating costs for the ventilation sys-
mum cfm (L/s) per animal body weight was deter-
tem.
mined using CFD, a value which has been
subsequently confirmed experimentally. Recently, the technique of airflow modeling, in
In the case of Memarzadeh and Jiang (2000) and the shape of computational fluid dynamics (CFD),
Memarzadeh and Manning (2000), the results of the has been utilized to consider ventilation systems in a
study were used to help confirm or modify standards wide range of applications, and the relevance of the
in health care facilities (AIA 2001). Memarzadeh appropriate standard for that application has been
and Jiang (2000) concluded that 10 total ACH was readily considered. The implementation of airflow
the recommended ventilation rate, as higher rates of modeling has already had an impact on standards,
ventilation did not decrease exposure in the room. As and this trend is likely to continue.
APPENDIX G
POWER QUALITY ISSUES
G.1 EMERGENCY POWER are guidelines regarding which areas and systems
should be served from an emergency power source.
G.1.1 Overview
Hospitals are critical facilities that must con- G.1.2 Hospital Heating and Ventilation Sys-
tinue to operate during power outages. The main tems on Emergency Power
electrical service to a hospital building should be as
reliable as possible. Because of the high cost of The two main NFPA codes dealing solely with
emergency power generation, only certain elements electrical design, construction, and installation crite-
of an HVAC system need to be served by the emer- ria for health care facilities are Article 517 of NFPA
gency power supply system (EPSS). A reliable dis- 70 The National Electrical Code and Chapter 3 of
tribution system is an essential component of the NFPA 99 Standard for Health Care Facilities
emergency power supply system. In order to ensure (NFPA 2002a, 2002b). Both of these NFPA docu-
that emergency power systems are installed in a reli- ments dictate minimum requirements for heating and
able manner, the National Electrical Code (NFPA ventilation systems on emergency power in a hospi-
70) requires that all parts of the EPSS be clearly tal.
labeled and wired completely independent of all According to NFPA 99 (Chapter 3) and NFPA
other wiring systems. This is to prevent concurrent 70 (Article 517), the following hospital heating and
failure of both normal and emergency power in case ventilating loads should be fed from emergency
of a fire or other emergency condition. The following power.

Table G-1. Emergency Power for Hospital HVAC Systems


Emergency Heating Emergency
Area Required Ventilation Required
Operating suite, including operating rooms, recovery rooms, etc.  
Birthing rooms, delivery rooms  
Intensive care  
Nursery  
Dietary and food preparation areas *
General patient rooms **
Infection/Isolation rooms ** 
Sterilization areas
Emergency suites and trauma rooms 
Laboratory fume exhaust hoods 
Hyperbaric facilities 

247
248 HVAC DESIGN MANUAL FOR HOSPITALS AND CLINICS

Table G-1. Emergency Power for Hospital HVAC Systems (Continued)


Hypobaric facilities 
Nuclear medicine (areas where radioactive material is used) 
Ethylene oxide and anesthesia gas evacuation 
Coronary care areas  
Notes:
*Kitchen hood supply and/or exhaust, if required, to operate during a fire under the hood.
**Heating in general patient rooms is not required in the following situations: (1) the outside design temperature is above +20F (6.7C); (2) the out-
side design temperature is below +20F (6.7C) and selected rooms with emergency heating are provided for confined patients; or (3) the facility is
served from a dual (redundant) source of normal power.

G.1.3 Additional Equipment on Emergency manually back-fed with emergency power so


Power that chillers, towers, pumps, etc., can be selec-
In addition to the above, the following equip- tively operated manually if the generation plant
ment and systems should be considered for service has sufficient spare capacity.
by emergency power: Other systems whose function is necessary for
safe operation of the building or facilities during
Boiler plant, including boilers, boiler feed an extended electrical outage.
pumps, condensate transfer pumps, condensate
pumps, fuel oil pumps, combustion air handlers, G.2 VARIABLE FREQUENCY DRIVES
hot water circulation pumps, and boiler room
G.2.1 Specifying Variable Frequency Drives
control panels and control compressed air.
for Hospitals and Clinics
Critical areas, such as operating suites, should
have access to mechanical cooling during a pro- Prevalent use of variable frequency drives
longed power outage. This is especially true in (VFDs) can cause power quality problems that inter-
areas of the country subject to hot, humid cli- fere with sensitive electrical equipment used in
mates. Air-handling systems serving these areas health care facilities. In general, the power quality
should have a backup chiller on emergency problems are caused by electrical harmonic distor-
power that can be switched on and isolated from tion, which the solid state VFDs inject on the power
the central chilled water plant during a pro- system.
longed power outage. The hospital engineering Harmonics are defined as sinusoidal voltages
staff and designers should perform a risk assess- or currents having frequencies that are integer multi-
ment for inclusion of cooling capabilities on the ples of the frequency at which the supply system is
emergency power systems. Many facilities cur- designed to operate. Most power systems are
rently lack adequate capacity for even basic designed to operate at 60 Hz, which is referred to as
code requirements. Provisions for cooling on the fundamental frequency. Since harmonics are peri-
emergency power must include chilled water odic disturbances occurring in intervals of the funda-
pumping systems, cooling towers, control sys- mental frequency, they are broken down and
tems, etc. Significant expense may be required identified in waveforms that are multiples of the fun-
to provide reliable emergency power to a portion damental frequency. Thus a third harmonic compo-
of the chilled water plant. Additional generator nent of a voltage with a fundamental frequency of 60
capacity, electrical distribution, and transfer Hz would be a (3)*(60) Hz or a 180 Hz wave.
switches in usually tight footprints are typically Harmonic voltages and currents are generated
required. Hybrid (gas fired, steam absorption, by solid state (nonlinear) electrical equipment such
electric) plant solutions are a consideration to as rectifiers, most lighting, computer power supplies,
provide an emergency power provision that does battery chargers, and VFDs.
not require as much generator capacity. Harmonic distortion has been recognized in the
Domestic hot water that serves dietary and industry for the last 40 years. But before the recent
patient care areas. proliferation of static power rectifiers, nonlinear ele-
Domestic water booster pumps. ments in a building electrical circuit were generally
Chilled water pumps should be on emergency minimal, and their effects were small and usually
power where the volume of water in the piping overlooked. With the advent of more and more sen-
can act as a storage system, offering some assis- sitive electronic equipment and the increased use of
tance with mechanical cooling for a period of nonlinear equipment, the effects of harmonic distor-
time. In many cases the chilled water plant is tion can no longer remain unaddressed.
POWER QUALITY ISSUES 249

As nonlinear current flows through the electrical converts the dc signal into a variable-frequency ac
distribution system, it induces voltage distortion. voltage to control the speed of the induction motor.
When distorted voltage is delivered to equipment A voltage-source inverter (VSI) drive is often con-
designed for a sinusoidal voltage, the result can often sidered for this application, and concerns regarding
be overheating or malfunction. In addition, the this particular device will be outlined.
unbalanced nature of harmonic currents will cause These drives (the most common types up to 300
increased neutral currents, which can cause the wir- hp) use a large capacitor in the dc link to provide a
ing in motors and transformers to significantly over- relatively consistent dc voltage to the inverter. The
heat. inverter then chops this dc voltage to provide a vari-
able-frequency ac voltage for the motor. VSI drives
G.2.2 Application Considerations for VFDs can be purchased off the shelf and employ pulse-
Variable frequency drives (VFDs) inject har- width-modulation (PWM) techniques to improve the
monic currents into the power system due to the quality of the output voltage waveform. However,
nonlinear nature of switching in electronic power there is a concern regarding nuisance tripping due to
devices. The harmonic current combined with the capacitor switching transients. Small VFDs have a
system impedance frequency response characteris- VSI rectifier (ac to dc) and use a PWM inverter (dc
tic can create harmonic voltage distortion. The har- to ac) to supply the motor. This design requires a dc
monic voltages and currents can cause spurious capacitor to smooth the dc link voltage. The controls
operation of relays and controls, capacitor failures, for this type of drive have protection for dc overvolt-
motor and transformer overheating, and increased ages and undervoltages with narrow thresholds. It is
power system losses. These problems can also be not uncommon for the dc overvoltage control to
compounded by the application of power factor cor- cause tripping of the drive whenever the dc voltage
rection capacitors (especially on low-voltage sys- exceeds 1.17 per unit (for this particular application,
tems), which can create resonance conditions that 760 volts for a 480-volt application). Since the dc
magnify the harmonic distortion levels. capacitor is connected alternately across each of the
Several concerns associated with harmonic dis- three phases, drives of this type can be extremely
tortion levels need to be addressed in the project sensitive to overvoltages on the ac power side.
specifications. This will avoid significant harmonic- One event of particular concern is capacitor
related problems with both the VFD equipment and switching on the system. Voltage switching tran-
the controlled operations. These concerns include the sients result in a surge of current into the dc link
following: capacitor at a relatively low frequency (300-800 Hz).
This current surge charges the dc link capacitor,
Harmonic distortion on both the supply side and causing an overvoltage to occur (through Ohm's
motor side of the drive. law). The overvoltage (not necessarily magnified)
Equipment derating due to harmonic distortion exceeds the voltage tolerance thresholds associated
produced by VFDs. with the overvoltage protection, which most likely
Audible noise caused by high-frequency (sev- will trip the VFD out of service. This is called nui-
eral kilohertz) components in the current and sance tripping because the situation can occur day
voltage. after day, often at the same time.
Harmonic filter design and specification. Several methods are available to ameliorate such
Harmonic distortion that is destructive to emer- tripping; some are simple and some costly. Use of a
gency generators. The harmonic analysis of the harmonic filter to reduce overvoltages, an expensive
system must include an analysis of the negative alternative, is effective in protecting drives from
effects of harmonics on the emergency power component failure but may not completely eliminate
system. nuisance tripping of small drives. The most effective
(and inexpensive) way to eliminate nuisance tripping
Nuisance Tripping Concerns of small drives is to isolate them from the power sys-
A three-phase VFD system consists of three tem with series inductors (chokes). With a concomi-
basic components (rectifier, dc link, and inverter) tant voltage drop across the inductor, the series
and a control system. The rectifier converts the three- inductance of the choke(s) reduce(s) the current
phase 60-Hz ac input to a dc signal. Depending upon surge into the VFD, thereby limiting the dc overvolt-
the system, an inductor, a capacitor, or a combination age. The most important issue regarding this method
of these components smoothes the dc signal (reduces is that the designer should determine the precise
voltage ripple) in the dc link. The inverter circuit inductor size for each VFD; this requires a detailed
250 HVAC DESIGN MANUAL FOR HOSPITALS AND CLINICS

transient simulation that takes into account capacitor protected with an uninterruptible power supply
size, transformer size, etc. The choke size must be (UPS) system, which can handle complete interrup-
selected carefully. If the choke has too much imped- tions in the input signal.
ance, it can increase harmonic distortion levels and
notching transients at the drive terminals. Chokes for Transient Overvoltage Concerns
this application are commercially available in sizes Transient overvoltages occur in connection with
from 1.5% to 5% of the VFD impedance at various capacitor switching. Each time a capacitor is ener-
hp ratings. A size of 3% is sufficient to avoid nui- gized, a transient voltage oscillation occurs between
sance tripping due to capacitor switching operations. the capacitor and the power system inductance. The
Standard isolation transformers serve the same pur- result is a transient overvoltage that can be as high as
pose. 2.0 per unit (of the normal voltage) at the capacitor
location. The magnitude is usually less than 2.0 per
Voltage Sag Concerns unit due to dampening provided by system loads and
Despite the many advantages provided by losses.
VFDs, the concern for nuisance tripping during volt- The transient overvoltages caused by capacitor
age sag conditions remains. This power quality con- energizing are generally not a concern to electric
cern involves the control sensitivity to short-duration utilities because their magnitude is usually below the
voltage sags and momentary interruptions. Actually, level at which surge protective devices operate (1.5-
many different kinds of controls and even motor con- 2.0 per unit). However, these transients can be mag-
tactors are sensitive to these voltage sags. Voltage nified at a facility if the facility has low-voltage
sags caused by faults on the power system represent capacitor banks for (displacement) power factor cor-
one of the most important problems that can be expe- rection. The designer should check for this situation.
rienced by the sensitive loads (equipment used in a When the frequency of a transient overvoltage
clinical setting). matches the series-resonant frequency of a facilitys
Whenever there is a fault on the transmission or transformer coupled with the utility capacitor(s), a
distribution system serving a facility (faults cannot low-impedance, high-current (at the resonant fre-
be completely avoided regardless of the system quency) condition results. When the resonant-fre-
design), there will be either a voltage sag or an inter- quency current completes its path to ground through
ruption. If the fault occurs on a parallel distribution the capacitor, the voltage experiences a boost to
feeder circuit or on the transmission system, there the ground-reference voltage.
will be a voltage sag that lasts until the fault is The magnification of capacitor switching tran-
cleared by some protective device (typically 3-30 sients is most severe when the capacitor switched on
cycles depending on the fault location). A method of the higher voltage system is much larger (kVAR)
predicting the likelihood of faults in a certain region than the capacitor at the low-voltage bus. Generally,
along with knowledge of equipment sensitivity can this situation occurs most frequently for substation
be used to determine an area of vulnerability. A switching. The frequency of oscillation that occurs
combination of computer short-circuit simulations when the high-voltage capacitor is energized is close
and lightning susceptibility analysis should be used to the resonant frequency formed by the step-down
to determine the affected area. The VFD controls transformer in series with the low-voltage capacitor.
should be designed to handle these voltage sag con- There is little resistive load on the low-voltage sys-
ditions without tripping. Ride-through capability is tem to provide dampening of the transient, as is usu-
seldom mentioned in project specifications. This is ally the case with industrial plants (motors do not
an important consideration when VFDs are applied provide significant damping of these transients). It is
in critical facilities, such as hospitals and clinics, not uncommon for magnified transients at low-volt-
where nuisance tripping can cause significant prob- age capacitors to range from 3.0 to 4.0 per unit.
lems. The designer should evaluate the level of sensi- These transients have significant energy associated
tivity of the controls to voltage sags. If such concern with them and are likely to cause failure of protective
exists he/she should consider applying power condi- devices, metal oxide varistors (MOVs), electronic
tioning to the controls themselves. Ferroresonant components (silicon-controlled rectifiers, etc.), and
transformers can handle voltage sags down to capacitors. VFDs are particularly susceptible to these
approximately 60% of the nominal voltage. This is transients because of the relatively low peak-inverse
sufficient to handle virtually all voltage sags caused voltage ratings of the semiconductor switches and
by single line-to-ground faults on the power system. the low-energy ratings of the MOVs used to protect
If additional protection is needed, the controls can be the VFD power electronics.
POWER QUALITY ISSUES 251

The following should be evaluated, and identi- All VFDs, regardless of the manufacturer, will
fied in the specifications, to control such magnified produce electromagnetic emissions to some degree.
transient overvoltages: These emissions are primarily due to the steep wave
fronts and very rapid switching of power semicon-
Using vacuum switches with synchronous clos- ductors in the VFD. Typically this occurs when tran-
ing control to energize a capacitor bank and con- sistors, GTOs or other fast devices are gated on
trol capacitor switching transient. and off in dc chopper circuits and inverter power cir-
Providing high-energy MOV protection on 480- cuits for PWM, current source, and six-step drives.
volt buses. The energy capability of these arrest- Conductors to the VFDs and motor can act as an
ers should be at least 1 kJ. antenna and radiate the RF energy into the media.
Using tuned filters for power factor correction Therefore, it is possible for RF to be induced into
instead of just shunt capacitor banks. (Tuned fil- nearby antennas and other conductors and be carried
ters change the frequency response of the circuit
to the loads in other circuits. Holding a portable AM
and usually prevent magnification problems.
radio near a power outlet in close proximity to an
This solution combines power factor correction,
EMI source can be evidence of this situation.
harmonic control, and transient control.)
DDC control systems, telecommunication ser-
EMI and RFI Concerns vices, and other electronic equipment utilizing very
IEEE Standard 519, Recommended Practices high frequencies may experience noise interference
and Requirements for Harmonic Control in Electric or malfunctions when subject to EM/RF energy.
Power Systems, recommends limits for voltage dis- Specifications should clearly outline the corrective
tortion and harmonic current resulting from nonlin- measures required. The first and foremost corrective
ear loads (IEEE 1992). The IEEE standard, however, measure to avoid problems associated with EMI is
is not intended to cover the effects of radio frequency proper routing of drive conductors in separate metal-
(RF) interference. As a result, specifications will lic conduits, even separate raceways if practical, and
occasionally refer to FCC Rules and Regulations, as remote as possible from any other conductors or
Volume 2, Part 15, Subpart J, Class A (referred to as suspect equipment. This will usually be sufficient to
FCC rule) to establish limits on electromagnetic avoid EMI problems.
emissions for VFDs.
EM/RF filters can be engineered to trap or
The FCC rule was published in October 1982
inhibit high-frequency emissions into power system
primarily for computing devices. Computers will
generate RF energy and possibly cause interference conductors. Due to the nature of EMI, however, the
with nearby equipment. Generally, the rule sets con- effectiveness of any filter is highly sensitive to where
ducted and radiated RF limits for electronic devices it is installed. Further, it is not ensured that a filter
using timing signals or digital techniques with pulse will correct a given problem even though it may
rates in excess of 10,000 pulses per second. Techni- meet FCC limits. Most manufacturers will include
cally speaking, VFDs with high-frequency timing this footnote with their literature. Filters are expen-
circuits conform to this description, although they sive and usually require additional space. It is recom-
are not intended as a computing device described in mended that they be furnished only when they are
the FCC rule. The primary and more significant specifically required to avoid or solve a problem
source of electromagnetic interference (EMI) from a after exhausting all proper installation methods. In
VFD stems from the power circuits, and in this addition, filters are an additional component and
respect, drives become an incidental radiation must be considered in the overall reliability of a
device. The only requirement for incidental radiation power system. To contain RF radiation through the
devices in the FCC rule is that they shall be oper- media from VFD, complete shielding using a metal-
ated so that the RF energy emitted does not cause lic enclosure is required. This approach will usually
harmful interference. If so, the operator must elimi- contain most of the radiated RF within a reasonable
nate the interference. distance.
APPENDIX H
SAMPLE CONTROL STRATEGIES
H.1 SEQUENCE OF OPERATION OF 100% tem. During the start-up mode, supply fan(s) shall
OUTSIDE AIR-HANDLING UNIT slowly ramp up to speed in tandem to maintain the
WITH TWO SUPPLY FANS, A setpoint of the supply air static pressure located two-
COMMON EXHAUST FAN, AND A thirds downstream of the main ductwork. If a single
HOT WATER RUN-AROUND LOOP supply fan fails, the remaining fan shall compensate
HEAT RECOVERY SYSTEM by increasing speed to maintain the setpoint.
(See Figure H-1)
Restart of the failed fan shall be initiated
Start-Up Mode through the EMS front-end system. Upon initiating
the restart, the remaining operating fan shall ramp
The air-handling system shall be automatically
started or stopped by EMS (energy management sys- down to minimum speed. Once the operating fan
tem) whenever the H-O-A (Hand-Off-Auto switch) reaches minimum speed, a start signal shall be given
is in the auto position and manually started or to the restart fan. Both fans shall then be ramped up
stopped by the hand position. in speed until they synchronize with the master static
The air-handling unit consists of two supply loop. If the restarted fan fails to start, its isolation
fans and a common exhaust fan. If the outside air damper shall close and the failure shall be indicated
temperature is less than 45F (7C) (adjustable), the at the EMS front end. The operating fan shall ramp
preheat valve shall open to outside air one minute up alone and synchronize with the duct static control.
before the unit fan(s) starts. Once the fan status is
proven, the preheat valve shall slowly close and con- Temperature Control
trol as defined in the Temperature Control section The discharge temperature is maintained by
following. Upon a signal to start the unit, the supply sequencing the speed of the heat recovery pump,
and exhaust isolation dampers as well as the outside modulating preheat valve, and chilled water valve in
air damper shall open before the fans start. Isolation
sequence. As the discharge air temperature rises, the
damper end-switches shall prove that damper is open
heat recovery pump shall ramp down toward the
and allow the fan(s) to start through hardwired inter-
minimum speed. If the temperature continues to rise,
locks.
the preheat valve shall modulate closed. As the dis-
On a command to shut down a fan, hardwired
charge temperature rises further, the chilled water
time delay relays shall prevent the isolation damper
valve shall modulate open. The reverse shall occur
from closing for 30 seconds (adjustable), once the
fan shuts off. This shall prevent a buildup of pressure when the discharge temperature decreases. The
as the fan spins down, preventing the fans high static chilled water valve shall not open when the heat
limit from tripping. recovery pump is operating in the heating mode or
when the preheat valve is open.
Fan Speed Control The heat recovery pump shall start when the
Supply and exhaust airflow stations shall input outside air temperature is greater than the exhaust air
cfm (L/s, typical) air volume data to the EMS sys- temperature +5F (2.8C) (adjustable) or when the

253
254 HVAC DESIGN MANUAL FOR HOSPITALS AND CLINICS

Figure H-1 Air-handling unit with return fan and air side economizer.

outside air temperature falls 3.0F (1.7C) (adjust- when it senses a temperature of 38F (3C) (adjust-
able) below the setpoint of the preheat air tempera- able). Preheat valve shall modulate to maintain DAT
ture. setpoint to prevent overheating.

Central Humidification Duct Static


The humidifier shall be modulated to maintain A manual-reset, discharge-air, high static safety
exhaust air relative humidity. As the humidity of the located before the supply air isolation/smoke damper
exhaust air increases, the humidifier valve shall mod- shall disable both supply fans and input to the DDC
ulate closed. The reverse shall occur when the system upon sensing a static pressure higher than the
humidity of the exhaust air decreases. A high-limit normal operating set point.
humidistat shall limit the signal to the humidifier if A manual-reset, outside air intake, low-static
the humidity of the supply air exceeds 90% (hard- safety shall disable both supply fans and input to the
ware adjustable) The humidifier valve shall remain DDC system upon sensing a static pressure lower
closed whenever the chilled water coil is being used. than the normal operating set point.
Upon loss of airflow, a panel-mounted static pressure A manual-reset, exhaust-air, low-static safety
switch shall close the humidifier control valve. located before the exhaust fan shall disable the fan
and input to the DDC system upon sensing a static
Safeties pressure lower than the normal operating setpoint.
All AHU safety devices are hardwired and inde-
pendent of the EMS system. These devices shall shut Humidity High Limit
down equipment through hardwired interlocks and A discharge-air, autoreset, high-limit humidity
provide alarm status to the operator through the EMS control shall close the humidifier valve and input to
front end. the DDC system upon sensing a supply air humidity
of 90% (adjustable).
Freeze Protection
A manual-reset low-limit thermostat installed at Duct Smoke Detection
the discharge of the fan shall disable the supply and Smoke detectors located at the supply air dis-
exhaust fans and close the outside and isolation charge plenum and exhaust ducts shall initiate the
dampers, and the chilled water valve shall open fully duct smoke sequence as follows:
SAMPLE CONTROL STRATEGIES 255

Supply Air Smoke Alarm To prevent the humidifier from wetting the
When the supply fan smoke detector detects systems final filter, the distance between
smoke, the supply fans shall be disabled through the steam humidifier grid and the final fil-
hardwired interlocks and the supply air smoke ters should be as long as possible.
damper and outside air damper shall close through Safeties can also be installed through soft-
hardwired interlocks. All of the control functions of ware, but hardwired interlocks are more
the air-handling unit shall return to the normal condi- reliable because they eliminate operator and
tion when the smoke detector is manually reset. software errors.

Comments H.2 SEQUENCE OF OPERATION OF 100%


DDC controls can provide more flexibility OUTSIDE AIR-HANDLING UNIT
WITH EXHAUST FAN AND HOT
and tighter control than pneumatic controls.
WATER RUN-AROUND LOOP HEAT
DDC control is an excellent tool for trend-
RECOVERY SYSTEM (See Figure H-2)
ing data and troubleshooting.
Two supply fan systems can provide system Start-Up Mode
redundancy for critical care area such as
operating rooms and intensive care units. The air-handling system shall be automati-
cally started or stopped by the EMS or whenever
System design can be based on return air,
the H-O-A switch is in the auto position and man-
not 100% outside air.
ually started or stopped by the hand position.
Activating the preheat control valve before
The air-handling system consists of a supply fan
the fan starts can prevent the freezestat from
and an exhaust fan. If the outside air temperature is
tripping during start-up less than 45F (7C) (adjustable), the preheat valve
The heat recovery system can be another shall open to the outside air one minute before the
type such as an air-to-air heat exchanger, unit fan(s) starts. Once the fan status is proven, the
heat pipes, or desiccant type heat preheat valve shall close slowly and control as
exchanger. defined in the Temperature Control section follow-
Nuisance and freezestat tripping of the ing. Upon a signal to start the unit, the supply and
freezestat can be avoided by locating exhaust isolation dampers as well as the outside air
chilled water coils downstream of the sup- damper shall open before the fans start. Isolation
ply fan. damper end-switches shall prove that damper is open

Figure H-2 One hundred percent outside air-handling unit with exhaust fan and heat recovery system.
256 HVAC DESIGN MANUAL FOR HOSPITALS AND CLINICS

and allow the fan(s) to start through hardwired inter- a panel-mounted static pressure switch shall close
locks. the humidifier control valve.
On a command to shut down a fan, hardwired
time delay relays shall prevent the isolation damper Safeties
from closing for 30 seconds (adjustable) once the fan All AHU safety devices are hardwired and inde-
shuts off. This shall prevent a buildup of pressure as pendent of the EMS system. These devices shall shut
the fan spins down and prevent the fans high static down equipment through hardwired interlocks and
limit from tripping. provide alarm status to the operator through the EMS
front end.
Fan Speed Control
Freeze Protection
Supply and exhaust airflow stations shall input
cfm (L/s, typical) air volume data to the EMS sys- A manual-reset, low-limit thermostat installed at
the discharge of the fan shall disable the supply and
tem. During the start-up mode, the supply fan shall
exhaust fans and close the outside and isolation
slowly ramp up to speed in tandem to maintain the
dampers, and the chilled water valve shall open fully
setpoint of the supply air static pressure located two-
when it senses a temperature of 38F (3C) (adjust-
thirds downstream of the main ductwork.
able). The preheat coil valve shall modulate to dis-
Restart of the failed fan shall be initiated charge air temperature (DAT) setpoint to prevent
through the EMS front-end system. Upon initiating overheating.
the restart, the system shall start in the sequence out-
lined in the start-up mode. Duct Static
A manual-reset, discharge-air, high-static safety
Temperature Control located before the supply air isolation/smoke damper
The discharge temperature is maintained by shall disable both supply fans and input to the DDC
sequencing the speed of the heat recovery pump, system when it senses a static pressure higher than
modulating preheat valve, and chilled water valve in the normal operating setpoint.
sequence. As the discharge air temperature rises, the A manual-reset, outside air intake, low-static
heat recovery pump shall ramp down toward the safety shall disable both supply fans and input to the
minimum speed. If the temperature continues to rise, DDC system when it senses a static pressure lower
the preheat valve shall modulate closed. As the dis- than the normal operating setpoint.
charge temperature rises further, the chilled water A manual-reset, exhaust-air, low-static safety
valve shall modulate open. The reverse shall occur located before the exhaust fan shall disable the fan
with a decrease in discharge temperature. The chilled and input to the DDC system when it senses a static
water valve shall not open when the heat recovery pressure lower than the normal operating setpoint.
pump is operating in heating mode or when the pre-
heat valve is open. Humidity High Limit
A discharge-air, autoreset, high-limit humidity
The heat recovery valve shall open, and the
control shall close the humidifier valve and input to
pump shall start when the outside air temperature is
the DDC system upon sensing a supply air humidity
higher than the exhaust air temperature +5F (2.8C)
of 90% (adjustable).
(adjustable) or when the outside air temperature falls
3F (1.7C) (adjustable) below the setpoint of the Supply Air Smoke Alarm
preheat air temperature. When the supply fan smoke detector detects
smoke, the supply fan shall be disabled through
Central Humidification hardwired interlocks and the supply air smoke
The humidifier shall be modulated to maintain damper and outside air damper shall close through
exhaust air humidity. As the humidity of the exhaust hardwired interlocks.
air increases, the humidifier shall modulate closed. All of the control functions of the air-handling
The reverse shall occur when the humidity of the unit shall return to the normal condition when the
exhaust air decreases. A high-limit humidistat shall smoke detector is manually reset.
limit the signal to the humidifier if the humidity of
the supply air exceeds 90% (hardware adjustable). Comments
The humidifier valve shall remain closed whenever DDC control can provide more flexibility
chilled water coil is being used. Upon loss of airflow, and tighter control than pneumatic control.
SAMPLE CONTROL STRATEGIES 257

DDC is an excellent tool for trending data Fan Speed Control


and troubleshooting. Supply and exhaust airflow stations shall input
Activating the preheat valve before the sup- cfm (L/s, typical) air volume data to the EMS sys-
ply fan starts will help prevent the freezestat tem. During the start-up mode, the supply fan shall
slowly ramp up to speed to maintain the setpoint of
from tripping during start-up
the supply air static pressure located two-thirds
The heat recovery system can also be downstream of the main ductwork. In a dual fan situ-
another type such as an air-to-air heat ation, if a supply fan fails, the remaining fan shall
exchanger, heat pipe, or desiccant type heat also shut down.
recovery. Restart of the failed fan shall be initiated
Premature tripping of freezestat can be through the EMS front-end system. Upon initiating
avoided by locating the chilled water coil the restart, the system shall start under the sequence
downstream of the supply fan. outlined in the start-up mode.
To prevent the humidifier from wetting the
Temperature Control
systems final filter, the distance between
The discharge air temperature is maintained by
the steam humidifier grid and the final fil- operating the heating control valves, face and bypass
ters should be as long as possible. dampers, and chilled water control valves in
Safeties can also be installed through soft- sequence. Whenever the outside air temperature is
ware, but hardwired interlocks are more less than 40F (4C), the heating control valves shall
reliable because they eliminate operator and modulate to fully open positions, and the face and
software errors. bypass dampers shall modulate to maintain the set-
point of the discharge air temperature. When the out-
H.3 SEQUENCE OF OPERATION OF 100% side air temperature is higher than 40F (4C) and
the temperature of the outside air is equal to the set-
OUTSIDE AIR-HANDLING UNIT
point of the discharge air temperature, the face
WITH FACE AND BYPASS AND
damper shall be opened fully and the bypass damper
EXHAUST FAN
shall be fully closed. When the outside air tempera-
ture is higher than the setpoint of the discharge air
Start-Up Mode temperature, the face damper shall open fully, the
The air-handling system shall be automati- bypass damper shall be closed, the heating control
cally started or stopped by the EMS or whenever shall be fully closed, and the chilled water control
the H-O-A switch is in the auto position and man- valves shall modulate to maintain the setpoint of the
ually started or stopped by the hand position. discharge air temperature.
The air-handling system consists of a supply fan
Central Humidification
and an exhaust fan. If the outside air temperature is
The humidifier shall be modulated to maintain
less than 40F (4C) (adjustable), the preheat valve
exhaust air relative humidity. As the humidity of the
shall open under control before the unit fan(s) starts. exhaust air increases, the humidifier valve shall mod-
Once the fan status is proven, the face and bypass ulate closed. The reverse shall occur when the
dampers shall modulate and control as defined in the humidity of the exhaust air decreases. A high-limit
Temperature Control section that follows. Upon a humidistat shall limit the signal to the humidifier if
signal to start the unit, the supply and exhaust isola- the humidity of the supply air exceeds 90% (hard-
tion dampers as well as the outside air damper shall ware adjustable). The humidifier valve shall remain
open before the fans start. Damper end-switches closed whenever the chilled water coil is being used.
shall prove that damper is open and allow the fan(s) Upon loss of airflow, a panel-mounted static pressure
to start through hardwired interlocks. switch shall close the humidifier control valve.
On a command to shut down a fan, hardwired Safeties
time delay relays shall prevent the isolation damper All AHU safety devices are hardwired and inde-
from closing for 30 seconds (adjustable), once the pendent of the EMS system. These devices shall shut
fan shuts off. This shall prevent a buildup of pressure down equipment through hardwired interlocks and
as the fan spins down and prevent the fans high provide alarm status to the operator through the EMS
static limit from tripping. front end.
258 HVAC DESIGN MANUAL FOR HOSPITALS AND CLINICS

Freeze Protection Premature tripping of the freezestat can be


A manual-reset, low-limit thermostat installed at avoided by locating the chilled water coil
the cooling coil section shall disable the supply and downstream of the supply fan.
exhaust fans and close the outside and isolation To prevent the humidifier from wetting the
dampers, and the chilled water valve shall open fully systems final filter, the distance between
when it senses a temperature of 38F (3C) (adjust- the steam humidifier grid and the final fil-
able). Heating valves could go wide open with the ters should be as long as possible.
face damper closed. The preheat coil must be sized to heat the
outside air from the outdoor air design tem-
Duct Static perature to the design setpoint of the dis-
A manual-reset, discharge-air, high-static safety charge air temperature.
located before the supply air isolation/smoke damper The face and bypass dampers require peri-
shall disable both supply fans and input to the DDC odic maintenance to perform properly. Con-
system upon sensing a static pressure higher than the sider alternatives where regular
normal operating setpoint. maintenance is uncertain.
A manual-reset, outside air intake, low-static Safeties can also be installed through soft-
safety shall disable both supply fans and input to the ware, but hardware interlocks are more reli-
DDC system upon sensing a static pressure lower able because they eliminate operator and
than the normal operating setpoint. software errors.
A manual-reset, exhaust air, low-static safety
H.4 SEQUENCE OF OPERATION OF AIR-
located before each exhaust fan shall disable the cor-
HANDLING UNIT WITH RETURN
responding fan and input to the DDC system upon
AIR FAN AND AIR-SIDE
sensing a static pressure lower than the normal oper-
ECONOMIZER (See Figure H-3)
ating setpoint.
Start-Up Mode
Humidity High Limit
The air-handling system shall be automati-
A discharge-air, autoreset, high-limit humidity cally started or stopped by the EMS or whenever
control shall close the humidifier valve and input to the H-O-A switch is in the auto position and man-
the DDC system upon sensing a supply air humidity ually started or stopped by the hand position.
of 90% (adjustable). It is preferable to start return fan first to warm
up unit before starting supply fan. Upon a signal to
Supply Air Smoke Alarm start the unit, the supply fan smoke/isolation damper
When the supply fan smoke detector detects and the return air damper shall open, and the exhaust
smoke, the supply fans shall be disabled through air damper and economizer air damper shall close
hardwired interlocks and the supply air smoke before the fans start. The supply fan smoke/isolation
damper and outside air damper shall close through damper end-switches shall prove that dampers are
hardwired interlocks. open and allow the fan(s) to start through hardwired
All of the control functions of the air-handling interlocks. After supply fan and return have met the
unit shall return to the normal condition when the static pressure requirement of the system, the mini-
smoke detector is manually reset. mum outside air damper shall open, and the EMS
shall modulate dampers, heating valves, and chilled
Comments water valves in sequence to maintain the predeter-
DDC control can provide more flexibility mined setpoint of the discharge air temperature.
and tighter control than pneumatic control. On a command to shut down a fan, hardwired
DDC control is an excellent tool for trend- time delay relays shall prevent the isolation damper
ing data and troubleshooting. from closing for 30 seconds (adjustable), once the
The fans control sequence is based on fan shuts off. This shall prevent a buildup of pressure
VFDs. With todays technology, a first-cost as the fan spins down and prevent the fans high
VFD option is preferable to a variable pitch static limit from tripping.
fan.
Activating the preheat valve before the sup- Fan Speed Control
ply fan starts will help prevent the freezestat The supply and return airflow stations shall
from tripping during start-up. input cfm (L/s, typical) air volume data to the EMS
SAMPLE CONTROL STRATEGIES 259

Figure H-3 One hundred percent outside air-handling unit with two supply fans, and a common exhaust
fan and hot water run around loop heat recover.

system. During the start-up mode, both the supply The economizer mode shall be determined by
fan and return shall slowly ramp up to speed in tan- comparing the enthalpy of the return air with the
dem to maintain the setpoint of the supply air static enthalpy of the outside air. If the enthalpy of the out-
pressure located two-thirds downstream of the main side air is less than the enthalpy of the return air, the
ductwork. The return fan shall modulate to maintain unit shall be in the economizer mode, and the damp-
a predetermined minimum outside air cfm volume ers shall modulate, as required, to maintain the dis-
(based on supply and return cfm measurement. In a charge air temperature. If the enthalpy of the outside
dual fan situation, if a supply or return fan fails, the air is greater than the enthalpy of the return air, then
remaining fan shall also shut down. the economizer mode shall be switched off, and the
minimum outside air damper shall remain open for
Restart of the failed fan shall be initiated the minimum outside air requirement.
through the EMS system. Upon initiating the restart,
the system shall start in the sequence outlined in the Central Humidification
start-up mode. The humidifier shall be modulated to maintain
exhaust air relative humidity. As the humidity of the
Temperature Control exhaust air increases, the humidifier valve shall mod-
ulate closed. The reverse shall occur when the
The discharge temperature is maintained by humidity of the exhaust air decreases. A high-limit
modulating the preheat valves, economizer dampers, humidistat shall limit the signal to the humidifier if
and the chilled water valves in sequence. As the dis- the humidity of the supply air exceeds 90% (hard-
charge air temperature rises, the preheat valves shall ware adjustable). The humidifier valve shall remain
modulate closed. If the temperature continues to rise, closed whenever the chilled water coil is being used.
the economizer dampers shall modulate open to the Upon loss of airflow, a panel-mounted static pressure
outside air if the unit is in the economizer mode. If switch shall close the humidifier control valve.
the economizer dampers are fully open and the tem-
perature continues to rise, the chilled water valves Safeties
shall modulate open. The reverse shall occur when All AHU safety devices are hardwired and inde-
the discharge temperature decreases. pendent of the EMS system. These devices shall shut
260 HVAC DESIGN MANUAL FOR HOSPITALS AND CLINICS

down equipment through hardwired interlocks and Notes


provide alarm status to the operator through the EMS DDC control can provide more flexibility
front end. and a tighter control loop than pneumatic
control.
Freeze Protection Premature tripping of the freezestat can be
A manual-reset, low-limit thermostat installed at avoided by locating the chilled water coils
the discharge of the fan shall disable the supply and downstream from the supply fan.
exhaust fans and close the outside and isolation To prevent the humidifier from wetting the
dampers, and the chilled water valve shall open fully systems final filter, the distance between
when it senses a temperature of 38F (3C) (adjust- the steam humidifier grid and the final fil-
able). Preheat valve shall modulate to maintain DAT ters should be as long as possible.
setpoint to prevent overheating. Safeties can also be installed through soft-
ware, but hardwired interlocks are more
Duct Static reliable because they eliminate operator and
software errors.
A manual-reset, discharge-air, high-static safety
located before the supply air isolation/smoke damper H.5 SEQUENCE OF OPERATION OF HOT
shall disable supply fan and input to the DDC system DECK AND COLD DECK AIR-
when it senses a static pressure higher than the nor- HANDLING UNIT WITH RETURN
mal operating setpoint. AIR FAN AND AIR-SIDE
A manual-reset, outside air intake, low-static ECONOMIZER (DEHUMIDIFICATION
safety shall disable the supply fan and input to the AND COOLING OF ALL SUPPLY AIR
DDC system when it senses a static pressure lower WITH REHEAT FOR HOT STREAM)
than the normal operating setpoint.
Start-Up Mode
A manual-reset, exhaust-air, low-static safety
The air-handling system shall be automati-
located before the return fan shall disable the fan and
cally started or stopped by the EMS or whenever
input to the DDC system when it senses a static pres- the H-O-A switch is in the auto position and man-
sure lower than the normal operating setpoint. ually started or stopped by the hand position.
Upon a signal to start the unit, the hot deck and
Humidity High Limit cold deck supply fan smoke/isolation damper and the
A discharge-air, autoreset, high-limit humidity return air damper shall open, and the exhaust air
control shall close the humidifier valve and input to damper and economizer air damper shall close
the DDC system when it senses a supply air humid- before the fans start. Hot deck and cold deck supply
ity of 90% (adjustable). fan smoke/isolation end-switches shall prove that
damper is open and allow the fan(s) to start through
Supply Air Smoke Alarm hardwired interlocks. After the supply fan and the
When the supply fan smoke detector detects return fan have met the static pressure requirement of
smoke, the supply air smoke/isolation damper shall the system, the minimum outside air damper shall
close through hardwired interlocks. The outside air open, and the EMS shall modulate dampers, preheat-
damper and return air and supply fans shall be dis- ing valves, reheat valves, and chilled water valves in
abled through hardwired interlocks. For units with sequence to maintain the predetermined setpoint of
capacity 15,000 cfm (7080 L/s) or more, according the discharge air temperature.
to NFPA, return air smoke detectors and dampers are On a command to shut down a fan, hardwired
time delay relays shall prevent the isolation damper
required. Upon sensing smoke in the return air-
from closing for 30 seconds (adjustable), once the
stream, the return fan and return air dampers shall be
fan shuts off. This shall prevent a buildup of pressure
shut down or fan shall continue to operate with unit
as the fan spins down and prevent the fans high-
dampers positioned to exhaust smoke out of the static limit from tripping.
building, if designed as a part of the smoke control
system. Fan Speed Control
All of the control functions of the air-handling The supply and return airflow stations shall
unit shall return to the normal condition when the input cfm (L/s, typical) air volume data to the EMS
smoke detector is manually reset. system. The EMS shall monitor static pressure sen-
SAMPLE CONTROL STRATEGIES 261

sors in each of the hot and cold deck risers located ware adjustable). The humidifier valve shall remain
two-thirds downstream of the unit. During the start- closed whenever the chilled water coil is being used.
up mode, the supply fan shall slowly ramp up to Upon loss of airflow, a panel-mounted static pressure
required speed to maintain the setpoint of the supply switch shall close the humidifier control valve.
air static pressure based on the lower of the two sen-
sors. The return fan shall modulate in tandem to Safeties
maintain a predetermined minimum outside air cfm All AHU safety devices are hardwired and inde-
volume (based on supply and return cfm measure- pendent of the EMS system. These devices shall shut
ments. In a dual fan situation, if a supply or return down equipment through hardwired interlocks and
fan fails, the remaining fan shall also shut down. provide alarm status to the operator through the EMS
Restart of the failed fan shall be initiated front end.
through the EMS system. Upon initiating the restart,
Freeze Protection
the system shall start in the sequence outlined in the
A manual-reset, low-limit thermostat installed at
start-up mode.
the discharge of the fan shall disable the supply and
Temperature Control return fans and close the outside and isolation damp-
The cold deck discharge temperature is main- ers, and the chilled water valve shall open fully when
tained by modulating the preheat valves, economizer it senses a temperature of 38F (3C) (adjustable).
dampers, and the chilled water valves in sequence. Preheat valve shall modulate to maintain DAT set-
As the cold deck discharge air temperature rises, the point to prevent overheating.
preheat valves shall modulate closed. If the tempera-
Duct Static
ture continues to rise, the economizer dampers shall
A manual-reset, discharge-air, high-static safety
modulate open to the outside air if the unit is in the
located before the hot deck and cold deck supply air
economizer mode. If the economizer dampers are
isolation/smoke dampers shall disable the supply fan
fully open and the temperature continues to rise, the
and input to the DDC system when it senses a static
chilled water valves shall modulate open. The
pressure higher than the normal operating setpoint.
reverse shall occur when the cold deck discharge
A manual-reset, outside air intake, low-static
temperature decreases.
safety shall disable the supply fan and input to the
The economizer mode shall be determined by DDC system when it senses a static pressure lower
comparing the enthalpy of the return air with the than the normal operating setpoint.
enthalpy of the outside air. If the enthalpy of the out- A manual-reset, return-air, low-static safety
side air is less than the enthalpy of the return air, the located before the return fan shall disable the corre-
unit shall be in the economizer mode, and the damp- sponding fan and input to the DDC system when it
ers shall modulate, as required, to maintain the dis- senses a static pressure lower than normal operating
charge air temperature. If the enthalpy of the outside setpoint.
air is greater than the enthalpy of the return air, then
the economizer mode shall be switched off, and the Humidity High Limit
minimum outside air damper shall remain open for A discharge-air, autoreset, high-limit humidity
the minimum outside air requirement. control shall close the humidifier valve and input to
The hot deck discharge temperature is main- the DDC system upon sensing a supply air humidity
tained by modulating the reheat valves. The hot deck of 90% (adjustable).
discharge temperature shall be linearly reset based
on the outside air temperature. Supply Air Smoke Alarm
When the supply fan smoke detector detects
Central Humidification smoke, the hot deck and cold deck supply air smoke/
The humidifier shall be modulated to maintain isolation dampers shall close through hardwired
exhaust air relative humidity. As the humidity of the interlocks. The outside air damper and return air and
exhaust air increases, the humidifier valve shall mod- supply fans shall be disabled through hardwired
ulate closed. The reverse shall occur when the interlocks.
humidity of the exhaust air decreases. A high-limit All of the control functions of the air-handling
humidistat shall limit the signal to the humidifier if unit shall return to the normal condition when the
the humidity of the supply air exceeds 90% (hard- smoke detector is manually reset.
262 HVAC DESIGN MANUAL FOR HOSPITALS AND CLINICS

Notes Hot deck reheat and duct must be sized for


DDC control can provide more flexibility maximum heating and reheat load that
and tighter control loop than pneumatic exists when no cooling is required.
control. DDC control is an excellent tool for The control of dehumidification and cool-
trending data and troubleshooting. ing of all supply air with a hot stream dual
Premature tripping of the freezestat can be air system is simple, but the economy is
avoided by locating the chilled water coils poor because cooling is canceled by reheat
downstream from the supply fan. at hot/cold deck terminal unit controls.
To prevent the humidifier from wetting the Either high or low velocity duct distribution
systems final filter, the distance between may be used for a dual-duct system.
the steam humidifier grid and the final fil- Dual air systems require careful control of
ters should be as long as possible. reheat and positive tightness of hot/cold
Safeties can also be installed through soft- deck terminal mixing dampers to function
ware, but hardwired interlocks are more satisfactorily. Also, the distribution systems
reliable because they eliminate operator and are subject to instability due to the terminal
software errors. unit proportioning dampers.
APPENDIX I
OPERATING ROOM AIR DISTRIBUTION
The following paper, Comparison of Operating Room Ventilation Systems in the Protection of the Surgi-
cal site by Farhad Memarzadeh, P.E., Ph.D., and Andrew P. Manning, Ph.D., is from ASHRAE Transactions
108(2).

263
4549

Comparison of Operating Room Ventilation


Systems in the Protection of the Surgical Site

Farhad Memarzadeh, P.E., Ph.D. Andrew P. Manning, Ph.D.


Member ASHRAE Associate Member ASHRAE

ABSTRACT the OR), and HVAC factors (i.e., air change rate [ACH] and
direction of airflow). Figure 1 shows sources, routes, and
This paper uses airflow modeling and particle-tracking
interactions of many of the factors.
methodologies to compare the risk of contaminant deposition
on an operating room (OR) surgical site and back table for In terms of the bacteria that cause infection, it is agreed in
different ventilation systems. The ventilation system designs the literature that the primary source of such bacteria are squa-
considered incorporated commonly used diffuser types, in mes, or skin scales or particles, Woods et al. (1986). These
particular, conventional, laminar, nonaspirating, and particles are of the order of 10 microns in diameter and are
displacement diffuser types. Further, a range of different air shed from exposed regions of skin, both from the surgical staff
change rates were considered, from 15 to 150 ACH. The room and also by the patient. Therefore, in this study, only this
equipment layout and distribution was agreed upon by a panel source of contaminant is considered.
of physicians and engineers as being representative of a typical There are standards suggested for air-conditioning
newly designed operating room. The type of particle consid- systems for operating theaters in different countries. The stan-
ered in this study was a squame, or skin scale, which is around dard for operating room design in Germany, for example, is
10 microns in size. Particles were released from three locations DIN 1946/4, which had its latest revision in 1999. This stan-
in the room, which represented likely sources of generation,
and tracked to determine whether they would impinge on either
the surgical site or a back table. The results were tabulated
such that the lowest percentage of impacts would indicate the
most appropriate ventilation system. The results show that
ventilation systems that provide laminar flow conditions are
the best choice, although some care needs too be taken in their
design. A face velocity of around 30 to 35 fpm (0.15m/s to
0.18m/s) is sufficient from the laminar diffuser array, provided
that the size of the diffuser array is appropriate.

INTRODUCTION
The risk of postoperative infection is present in all surgi-
cal procedures, but it can be particularly serious in certain
operations, for example, joint replacement. There are several
factors that could affect such infection, namely, patient factors
(i.e., susceptibility to infection), surgical field factors (i.e., the Figure 1 Source and routes of infection in the operating
thermal plume from the site), room factors (i.e., cleanliness of room (Lewis 1993).

Farhad Memarzadeh is the chief of technical resources at the National Institute of Health, Bethesda, Md. Andrew P. Manning is the director
of engineering at Flomerics, Inc., Southboro, Mass.

ASHRAE Transactions: Research 3


dard contains some specific details for the design of the OR. OR floor area has to be between 25 and 60 m2, and the ceiling
The supply air discharge temperature should be set such that height has to be at least 3 m.
the return air temperature at the room is between 71.6F The 1999 ASHRAE Handbook suggests that
(22C) and 78.8F (26C). The standard defines a reference
the delivery of air from the ceiling, with a downward
supply airflow rate of 1413 cfm (0.67 m3/s). The actual movement to several exhaust inlets located on opposite
amount to be supplied to the room, however, is defined using walls, is probably the most effective air movement
the following two factors: pattern for maintaining the concentration at an accept-
able level.
relative airborne microorganism concentration, s, and
The handbook suggests that the temperature range should be
contamination factor or ratio in the protected area, s.
between 62F (16.67C) and 80F (26.67C), and that positive
The value of s is calculated from pressurization should be maintained. It also suggests that the
air should be supplied at the ceiling and exhausted or returned
V ZU* from at least two locations near the floor. It suggests that
s = s -----------
V - , (1) supply diffusers should be of the unidirectional type, and that
ZU
high-induction ceiling or side-wall diffusers should be
where avoided. The suggested ACH is 15 ACH for systems that use
all outdoor air and 25 ACH for recirculating air systems.
s = ks/ kR = contamination factor in the protected area,
Some studies have been published that consider the rela-
kR = average airborne microorganism concentration tive merits of different systems. However, studies such as
in the room at V ZU ,
Lidwell (1988) and Schmidt (1987) do not include specific
ks = average airborne microorganism concentration system design data for these systems, so it is difficult to estab-
in the protected area, lish definitive recommendations for the actual design of the
V ZU
*
= reference supply airflow volume flow rate ventilation system. Further, there are conflicting data regard-
(1413 cfm [0.67 m3/s]), ing the system that is generally recognized as the cleanest type
V ZU = actual supply air volume flow rate. of system. In particular, while laminar flow systems are recog-
nized in providing lower general concentration levels in the
For the relative airborne microorganism concentration,
room, they are sometimes blamed for higher infection rates
which is regarded as a measure of the given hygienic quality
than more conventional systems, for example, Salvati et al.
of the air, the limiting value, szul, is specified relative to the
(1982). The theory put forward by Lewis (1993) is that laminar
minimum requisite supply air volume flow rate, V ZU min , by
flow systems cause impingement on the wound site. However,
the following equation:
this seems to be based on the use of high laminar flow veloc-
s ities at supply: Schmidt (1987) defines a laminar system as
V ZU min = V ZU
* ----------
- (2) having velocities of at least 90 fpm (0.45m/s).
szul
The studies mentioned above were experiment-based.
The value of szul is evaluated on the type of OR and the However, an alternative technique, computational fluid
type of surgery performed in it. In particular, the code identi- dynamics (CFD) (sometimes known as airflow modeling), has
fies two types of OR: been proven to be very powerful and efficient in research
projects involving parametric study on room airflow and
Type A operating theatres require displacement flow contaminant dispersion (Ziang et al. 1995; Haghighat et al.
systems, namely, laminar flow systems. Type A operat- 1994). In addition, the output of the CFD simulation can be
ing theatres require especially high levels of sterility, for presented in many ways, for example, with the useful details
example, transplantations, cardiac surgery, joint pros- of field distributions, as well as overviews on the effects of
thetics, alloplasty. Here, the value of szul is taken as parameters involved. Therefore, CFD is employed as a main
two-thirds. approach in this study.
Type B operating theatres require mix flow or displace- The only CFD study identified in this literature search that
ment flow systems. Type B operating theatres require addressed contamination control in an operating room was Lo
high levels of sterility. Here, the value of szul is taken as (1997). However, this study made two assumptions, which
1. would make the conclusions less useful. In particular, the
study only considered an isothermal operating room and,
However, since under any given operating conditions, s secondly, the contaminant was considered as a concentration.
is not only a function of the air distribution system but also a Therefore, in the former case, the effect of significant thermal
number of other parametersin particular, of the supply plumes in the room was ignored. In the latter case, the assump-
airflow rate itselfthe minimum airflow rate for the OR can tion that the particles in the room can be considered to follow
only be determined by experiment. The experimental proce- the Brownian motion of the airflow is strictly applicable to
dure is defined by DIN 4799 (1990), which specifies that the particles, which are 1 micron or less in diameter (Crowe et. al

4 ASHRAE Transactions: Research


1998). While bacteria and viruses do conform to this criteria,
as noted above, bacteria are usually transported in operating
rooms by squames, which are considerably bigger (in the
range of 10 microns) and so do not necessarily follow Brown-
ian motion. For this reason, concentration sources were not
used in this study. A further reason was that the use of concen-
tration would make the question of impact of the particles on
the surgical site more difficult to determine.
In the study documented here, airflow modeling is used to
consider the dispersion of squame-sized particles in various
ventilation system design operating rooms. The particle track-
ing routine was previously developed for use in Memarzadeh
(2000). In order to establish the relative ranking of the differ-
ent systems, two target areas of concern are considered: the
Figure 2 Geometric model of operating room and
surgical site and back table. The reason for the latter target is
superimposed grid of cells for calculation.
that squames that strike this surface are likely to directly
contaminate instruments.

PURPOSE OF STUDY = dependent variable


The main purposes of the study presented in this paper are = exchange coefficient (laminar + turbulent)
to S = source or sink
Airflow modeling solves the set of Navier Stokes equa-
use advanced numerical modeling and empirical data to tions by superimposing a grid of many tens or even hundreds
evaluate the effects of some of the room parameters, of thousands of cells that describe the physical geometry, heat
such as and contamination sources, and air itself. Figure 2 shows one
of the operating room case geometries and the corresponding
ventilation flow rate,
space discretization, subdividing the operating room into
diffuser type and location,
cells. In this study, a finite-volume approach was used to
supply temperature, and
consider the discretization and solution of the equations.
exhaust location,
The simultaneous equations thus formed are solved iter-
on minimizing the risk of contamination of an operating atively for each one of these cells to produce a solution that
room surgical site and a back table from specific particu- satisfies the conservation laws for mass, momentum, and
late sources; energy. As a result, the flow can then be traced in any part of
the room, simultaneously coloring the air according to another
evaluate the same parameters to determine which venti- parameter such as temperature.
lation systems evacuate the room of particles most effec- The particle-tracking algorithm was based on the k-
tively; and turbulence model. Further, the k- turbulence model repre-
provide an architectural/engineering tool for good sented the most appropriate choice of model because of its
design practice that is generally applicable to conven- extensive use in other applications. No other turbulence model
tional operating room use. has been developed that is as universally accepted as the k-
turbulence model.
METHODOLOGY
Validation of Numerical Modeling and Analysis
Airflow Modeling
The 1998 publication, Ventilation Design Handbook on
Airflow modeling based on computational fluid dynam- Animal Research Facilities Using Static Microisolators
ics (CFD), which solves the fundamental conservation equa- (Memarzadeh 1998), by the National Institutes of Health
tions for mass, momentum, and energy in the form of the provided the most extensive empirical validation to date. The
Navier-Stokes equations, is now well established. methodology and the results generated in the 1998 publication
were peer reviewed by numerous entities, such as Harvard

---- ( ) + div ( V grad ) = S University, etc. In order to analyze the ventilation performance
t
(3) of different settings, numerical methods based on computa-
Transient + Convection Diffusion = Source tional fluid dynamics were used to create computer simula-
tions of more than 160 different room configurations. The
where performance of this approach was successfully verified by
= density comparison with an extensive set of experimental measure-
V = velocity vector ments. A total of 12.9 million experimental (empirical) data

ASHRAE Transactions: Research 5


values were collected to confirm the methodology. The aver- d wp 1 2 2 2
age error between the experimental and computational values m p ----------- = --- C D A P ( w w p ) ( u u p ) + ( v v p ) + ( w w p ) + m p g z
dt 2
was 14.36% for temperature and velocities, while the equiva-
lent value for concentrations was 14.50%. (4c)
To forward this research, several meetings were held to dx p
solicit project input and feedback from the participants. There -------- = u p (5a)
dt
were more than 55 international experts in all facets of the
animal care and use community, including scientists, veteri- dy p
narians, engineers, animal facility managers, and cage and -------- = v p (5b)
dt
rack manufacturers. The prepublication project report under-
went peer review by a ten-member panel from the participant dz p
-------- = w p (5c)
group, selected for their expertise in pertinent areas. Their dt
comments were adopted and incorporated in the final report.
where
The results from the 1998 publication were also reviewed
by several ASHRAE technical committees and were cited in u, v, w = instantaneous velocities of air in x, y, and z
the 1999 ASHRAE HandbookApplications and the 2001 directions
ASHRAE HandbookFundamentals. up, vp, wp = particle velocity in x, y, and z directions
xp, yp, zp = particle moving in x, y and z direction
Simulation of Contaminant Particles
gx, gy, gz = gravity in x, y, and z directions
The basic assumption in this study is that the squames can Ap = cross-sectional area of the particle
be simulated as particles being released from several sources mp = mass of the particle
surrounding the occupant. These particles are then tracked for
a certain period of time in the room. The methodology is simi- = density of the particle
lar to that employed previously in Memarzadeh and Jiang CD = drag coefficient
(2000), where tuberculosis carrying droplets were released dt = time interval
from around the patient in an isolation room to simulate
coughs, and were subsequently tracked. Since the airflow in a
ventilated room is turbulent, the squames are transported not 0.5
C D = ------ 1 + ------ Re
24 3
for Re 560 (6)
only by convection of the airflow but also by the turbulent Re 16
diffusion. The squames are light enough and in small enough
quantities that they can be considered not to exert an influence and
on airflow. Therefore, from the output of the CFD simulation,
the distributions of air velocities and the turbulent parameters C D = 0.44 for Re > 560 (7)
can be directly applied to predict the path of the airborne squa-
mes in convection and diffusion processes. The Reynolds number of the particle is based on the rela-
tive velocity between particle and air.
Particle Trajectories In laminar flow, particles released from a point source
with the same weight would initially follow the airstream in
The methodology for predicting turbulent particle disper- the same path and then fall under the effect of gravity. Unlike
sion used in this study was originally laid out by Gosman and laminar flow, the random nature of turbulence indicates that
Ioannides (1981) and validated by Ormancey and Martinon the particles released from the same point source will be
(1984), Shuen et al. (1983), and Chen and Crowe (1984). randomly affected by turbulent eddies. As a result, they will be
Experimental validation data were obtained from Snyder and diffused away from the streamline at different fluctuating
Lumley (1971). Turbulence was incorporated into the levels. In order to model the turbulent diffusion, the instanta-
Stochastic model via the k- turbulence model (Alani et al. neous fluid velocities in the three Cartesian directionsu, v,
1998). and ware decomposed into the mean velocity component
The particle trajectories are obtained by integrating the and the turbulent fluctuating component as
equation of motion in three coordinates:
u = u + u ', v = v + v ', w = w + w ,
du p 1 2 2 2
m p --------- = --- C D A P ( u u p ) ( u u p ) + ( v v p ) + ( w w p ) + m p g x where u and u ' are the mean and fluctuating components in
dt 2
x-direction. The same applies for y- and z-directions. The
(4a) stochastic approach prescribes the use of a random number
generator algorithm, which, in this case, is taken from Press et
d vp 1 2 2 2
m p --------- = --- C D A P ( v v p ) ( u u p ) + ( v v p ) + ( w w p ) + m p g y al. (1992) to model the fluctuating velocity. It is achieved by
dt 2 using a random sampling of a Gaussian distribution with a
(4b) mean of zero and a standard deviation of unity. Assuming

6 ASHRAE Transactions: Research


isotropic turbulence, the instantaneous velocities of air are 4
--- p D
then calculated from kinetic energy of turbulence: 3
= -------------------------------------------------------------------------------------------------------------------------------- , (13)
u = u + N (8a) 2 2 2 2 2 2
C D ( u + v + w ) ( ( u p ) + ( v p ) + ( w p ) )

v = v + N (8b)
where is the particle relaxation time, indicating the time
w = w + N (8c) required for a particle starting from rest to reach 63% of the
flowing stream velocity. The variable D is the diameter of the
where N is the pseudo-random number, ranging from 0 to1, particle.
with The interaction time is determined by the relative impor-
tance of the two events. If the particle moves slowly relative to
0.5
= ------ the gas, it will remain in the eddy during the whole lifetime of
2k
3
, (9)
the eddy, te. If the relative velocity between the particle and the
gas is appreciable, the particle will transverse the eddy in its
where k is the turbulent kinetic energy. transient time, tr, Therefore, the interaction time is the mini-
The mean velocities, which are the direct output of CFD, mum of the two:
determine the convection of the particles along the streamline,
while the turbulent fluctuating velocity, N, contributes to the t int = min ( t e , t r ) (14)
turbulent diffusion of the particle.
Particle Outcomes
Particle Interaction Time The methodology was refined to consider different parti-
cle outcomes, namely:
With the velocities known, the only component needed the particle is vented from the room via ventilation and
for calculating the trajectory is the time interval (tint) over
which the particle interacts with the turbulent flow field. The the particle hits one of the two designated targets,
concept of turbulence being composed of eddies is employed namely, the surgical site (defined later) or the top sur-
here. Before determining the interaction time, two important face of the back table.
time scales need to be introduced: the eddys time scale and the
particle transient time scale. Particles that are neither vented nor strike the target are
The eddys time scale is the lifetime of an eddy, defined as assumed to remain in the room when the overall particle track-
ing time limit is reached.
le
t e = ----------- (10) Testing of Particle Tracking and
N
Target Detection Methodology
where A simple test configuration was defined to confirm that
the particle tracking methodology was functioning as
3
--- intended. There are many aspects to be investigated, including
2
C k inertial, gravitational, and slip effects, but, in particular, the
l e = ------------ , (11)
simulation sample here was intended to test that the target
detection methodology worked correctly. The test was speci-
le = dissipation length scale of the eddy,
fied to incorporate typical flow and blockage effects present in
k = turbulent kinetic energy, the operating room, in particular, an inlet (supply), openings
= dissipation rate of turbulent kinetic energy, (vents), a block in the flow path (internal geometry and
obstructions), and a specific target.
C = constant in the turbulence model. The test configuration had dimensions of 20 in. 20 in.
The transient time scale for the particle to pass through the 40 in. (0.5 m 0.5 m 1.0 m). It contained a 20 in. 20 in.
eddy, tr, is estimated as (0.5 m 0.5 m) supply at one end, through which the flow rate
was varied, and an opening of half that size at the other end.
The opening was defined as representing atmospheric condi-
le tions: no flow rate was defined through the openings. There
t r = ln 1.0 ----------------------------------------------------------------------------------------------------------------
( u + v + w ) ( ( up ) + ( vp ) + ( wp ) )
2 2 2 2 2 2 were two blocks, of dimensions 20 in. 10 in. 20 in. (0.5 m
0.25 m 0.5 m) and 8 in. 4 in. 20 in. (0.2 m 0.1 m
(12) 0.5 m), which were included to represent typical obstruction.
A target of dimension 6 in. 20 in. (0.15 m 0.5 m) was also
and included.

ASHRAE Transactions: Research 7


Figure 3 Result of particle target test case.

In the tests, 20 particles were released with even spacing


across the center of the inlet supply. The test particles were 10 Figure 4 Layout of baseline operating roomMayo stand
mm in diameter, with a density of 1000 kg/m3. A flow rate of view.
1060 cfm (0.5m3/s) was considered. Different coordinate
orientations were considered to evaluate whether coordinate
biasing existed. In particular, the configuration was consid-
OUTLINE OF BASELINE MODEL
ered with the supply in the positive and negative x, y, and z
directions, respectively. Therefore, six cases were run to test A typical operating room layout in terms of the number of
the particle tracking methodology. surgical staff, lights, machinery, tables, and patient was
The results of a typical case are shown in Figure 3, in considered for the baseline model for the CFD simulations.
particular, the positive x. The blue lines represent the particle The general features of the baseline room are given in Figure
tracks. The figure clearly shows that the target stops two parti- 4 and Table 1 and are listed below.
cles and that the rest of the particles exit correctly through the A panel of physicians and engineers agreed upon the
end opening. layout of the room during the initial stages of the study. Items
These features are also exhibited by all the other cases. such as gas columns were not included with the belief that they
Based on the results from these tests, the particle tracking obstruct the free movement of large equipment in operating
methodology can be seen to be working correctly. rooms, limit the placement and position of the operating table,
and are difficult to keep clean. Also, the panel believes oper-
Calculation Procedure ating rooms should be going more toward connection of gas
lines at the ceiling, since such lines would not provide signif-
The calculation procedure was as follows:
icant blockage to airflow. Other significant items of equip-
Compute the field distribution of fluid velocity, temper- ment, for example, a C-arm, were not included in this study, as
ature, and turbulent parameters. the panel felt that they did not constitute typical equipment.
Specify the source locations from where a specified It is recognized that such items may influence the airflow and
number of particles are released. Note that the particles temperature distribution in the OR, and that they should be
are not continuously released: they are released from the considered in future studies.
source locations only at the start of the analysis time
Description in Brief
period (i.e., t = 0 s).
Perform computational analysis to calculate trajectory Room
for each particle for up to 3600 s from initial release.
The output of the analysis includes 20 ft 20 ft 12 ft (6.1 m 6.1 m 3.66 m) high
the percentage of particles that are vented from Five surgical staff members
the room via ventilation, varying with time, and
One patient
the percentage of particles that strike a desig-
One back table
nated target in the room, in particular, either the
One anesthesia machine
surgical site or the top surface of the back table,
at the end of the overall time period (3600 s). Two monitors (and stands)
Note that this quantity was not measured with One inactive machine
time because of the small number of particles Two surgical lights
that actually hit the targets. Dimensions of internal blockages are given in Table 1.

8 ASHRAE Transactions: Research


TABLE 1
Dimensions and Heat Dissipations of Major Items in Operating Room

Item Dimensions Heat Dissipation


Operating table 30 in. wide 30 in. high 72 in. long Noneoperating table only operates intermittently
Surgical lights (2) 2 ft diameter 1 ft hemisphere 150 W each
Surgical staff Height assumed as 5 ft 9 in. 100 W each
Two of the staff are leaning over surgery site
Anesthesia machine 30 in. 30 in. 48 in. high 200 W
Machine1 30 in. 30 in. 30 in. high Nonerepresents blockage only or intermittently
operating machinery
Mayo stand 10 in. 30 in., located 8 in. above patient level None
Back table 30 in. 30 in. high 60 in. long None
Monitor and stand (2) Stand: 12 in. 24 in. 40 in. high Monitors dissipate 200 W each
Monitor: 16 in. 18 in. 10 in. high
Patient With drape, patient covers most of table Exposed head dissipates 46 W (70% of 65 W);
Surgery site is 1 ft 1 ft area with
surface temperature = 100F
Overhead lights (4) 6 ft 1 ft 180 W each

Supply be made to work practically. Further, Cases 3 and 4 are based


on the DIN 1946/4 (1999) standard, while Cases 5 and 6
Two supply grilles each providing 750 cfm (0.35 m3/s) consider low level only and high level only exhaust systems,
for a total of 18.75 ACH respectively. Case 8 considered upward displacement units,
24 in. 14 in. (0.61 m 0.36 m) grilles which aim to provide low-velocity flow at low level, with
Supply discharge temperature, 67.5F (19.7C), set such exhausts placed at high level. Finally, Case 11 was suggested
that the exhaust air temperature was 72F (22.2C) by Milton Goldman, who presented a summary of operating
room contamination issues at a recent ASHRAE meeting
Exhaust (Goldman 2000). In this concept, a U-shaped array of laminar
flow diffusers above the table was used in combination with a
Four exhaust grilles each extracting 375 cfm (0.17 m3/s) nozzle that provides air horizontally along the length of the
24 in. 14 in. (0.61 m 0.36 m) grilles table toward the anesthesia screen. The intention of the nozzle
flow is to sweep away contaminants from the surgical site up
Heat Sources toward an exhaust located in the ceiling.
The various diffuser types considered in this project were
Heat sources were those that could be considered con- all modeled using a combination of several boundary condi-
stant, not intermittent, sources tions, which were validated prior to the room parametric study.
Total cooling load, 2166W (see Table 1) Great care was taken with regard to the correct representation
of the diffusers in the room, as well as the numerical grid used.
Model Considerations The numerical diffuser models were validated against avail-
Several different ventilation systems were considered in able manufacturers data to ensure that throw characteristics
this study. The different ventilation systems considered, which were matched accurately. This was performed for all the
are listed in Table 2, are intended to replicate approximately diffuser types (conventional grille, laminar flow, nonaspirat-
those outlined in Schmidt (1987). Cases 1 and 10 use conven- ing, displacement) and for an appropriate range of flow rates.
tional grilles as the basis of the ventilation system, which The number of grid cells used in these cases was of the
provide jets at a (relatively) high velocity at discrete locations order of 600,000 cells. Grid dependency tests were performed
in the room. Cases 2, 3, 4, 5, 6, 7, and 9 all provide variations to ensure that the results were appropriate and would not vary
on a laminar flow type ventilation system, which aim to on increasing the grid density. In particular, attention in the
provide vertically downward flow conditions. The changes tests was directed at the areas containing the main flow or heat
between the cases are typically associated with differences in sources in the room, for example, the diffusers and close to the
diffuser array size. The systems in these cases avoided the surgical site and back table. Grid was added appropriately in
higher velocities typically associated with them, namely, 90 these regions and their surroundings until grid independence
fpm (0.45 m/s) to determine if the laminar flow concept could was achieved.

ASHRAE Transactions: Research 9


TABLE 2
Details of Cases Considered in Study

Supply
Temp. to
Maintain
Volume 72F Supply
Flow Rate, (22.2C) Velocity, Diffuser Types Used
Case System Diffuser Details cfm (m3/s) ACH F (C) fpm (m/s) Notes in Cases

1 Conventional Supply and exhaust grilles: 24 1500 (0.71) 18.75 67.5 (19.7) 321.43 (1.63) Air is supplied at high level Conventional
in. 14 in. (0.61 m 0.36 m) (one side), exhausted at low (supply and exhaust)
level (two sides)
2 Laminar Entire ceiling has laminar flow 12000 150 71.5 (21.9) 30 (0.15) Exhaust grilles are located at Laminar
supplies (20 ft 20 ft [6.10 m (5.66) low level (two sides) (supply)
6.10 m]);
Exhausts are 14 in. 20 ft (0.36 Conventional
m 6.10 m) (exhaust)
3 Laminar Array of supply grilles immedi- 1200 15 66.2 (19.0) 37.5 (0.19) Exhaust grilles are located on Laminar
ately above table (4 ft 8 ft (0.57) one side and high and low (supply)
[1.22 m 2.44 m]) level
Conventional
(exhaust)
4 Laminar (mixed Array of supply grilles immedi- 1600 20 67.6 (19.8) 33.3 (0.17) Exhaust grilles are located on Laminar
level exhausts) ately above table (6 ft 8 ft (0.76) one side and high and low (supply)
[1.83 m 2.44 m]) level
Conventional
(exhaust)
5 Laminar (low level Array of supply grilles immedi- 1600 20 67.6 (19.8) 33.3 (0.17) Exhaust grilles are located on Laminar
exhausts) ately above table (6 ft 8 ft (0.76) one side at low level (supply)
[1.83 m 2.44 m])
Conventional
(exhaust)
6 Laminar (high level Array of supply grilles immedi- 1600 20 67.6 (19.8) 33.3 (0.17) Exhaust grilles are located on Laminar
exhausts) ately above table (6 ft 8 ft (0.76) one side at high level (supply)
[1.83 m 2.44 m])
Conventional
(exhaust)
7 Unidirectional flow Array of supply grilles immedi- 3000 (1.42) 37.25 69.7 (20.9) 25 (0.13) Curtains on all four sides, 10 Laminar
with curtains ately above operating table (10 ft ft x 12 ft 5 ft (3.05 m 3.66 (supply)
12 ft [3.05 m 3.66 m]); m 1.52 m) high (extends to
Exhaust grilles: 24 in. 14 in. ceiling) Conventional
[0.61 m 0.36 m] Air is exhausted on one side at (exhaust)
high and low levels
8 Upward Displacement supply diffusers: 3000 (1.42) 37.25 69.7 (20.9) 30 (0.15) Exhaust grilles are located on Upward displacement
displacement 6 ft 30 in. 60 in. (0.15 m bottom of 1 ft 1 ft 2 ft (0.3 (supply)
0.76 m 1.52 m) Exhaust m 0.3 m 0.61 m) stubs
grilles: Conventional
24 in. 14 in. (0.61 m 0.36 m) (exhaust)
9 Non-aspirating dif- Array of supply grilles immedi- 2000 (0.94) 25 68.5 (20.3) 31.25 (0.16) Air is exhausted at low level, Nonaspirating
fusers ately above operating table (8 ft 1 ft (0.3 m) from floor (supply)
8 ft [2.44 m 2.44 m]);
Exhaust grilles: 24 in. 14 in. Conventional
(0.61 m 0.36 m) (exhaust)
10 Low supply/ high Supply and exhaust grilles: 24 1500 (0.71) 18.75 67.5 (19.7) 321.43 (1.63) Air is supplied at low level Conventional
exhaust in. 14 in. (0.61 m 0.36 m) (two side), exhausted at high (supply and exhaust)
level (two sides)
11 Goldman concept U-shaped array of supply grilles 1520 (0.72) 19 67.5 (19.7) 31.25 (0.16) Nozzle is provided via chim- Laminar
immediately above operating (1500 (0.71) & 320 (1.63) ney and is located 5 ft (1.52 (Supply)
table (6 used) through m) above floor level
Nozzles: 3 in. (7.62e-2 m) dia. array, 20 Air is exhausted at low level Conventional
Exhaust grilles: 24 in. 14 in. (0.01) on two sides, and a ceiling (Exhaust)
(0.61 m 0.36 m) through level immediately above
nozzle) patient

10 ASHRAE Transactions: Research


Figure 5 Surgical site and Mayo Stand. Figure 6 Location of Main and Nurse particle release
sourcesplan view.

Contamination Consideration
The source of contaminants considered in this study was
squames. Squames are cells that are released from exposed
regions of the surgery staff (for example, neck, face, etc.) and
are the primary transport mechanism for bacteria in the OR.
They are approximately 25 microns (m) by 3 to 5 microns
thick. Approximately 1.15 106 to 0.9 to 108 are generated
during a typical (2 to 4 hours) procedure (Synder 1996). In this
study, the particles would be tracked to see how many of these
particles hit the back table (shown in Figure 4) or the surgical
site. For the purposes of this study, the surgical site was
considered as a 1 ft 1 ft (0.3 m 0.3 m) square where the
surface temperature was 100F (37.78C); it is shown in
Figure 5.
Obviously, keeping track of so many particles in the study
would not be feasible. Therefore, a representative number of Figure 7 Location of Surgery particle release sourceside
particles were introduced from three arrays of sources. The view.
locations of the sources, designated as Main, Nurse, and
Surgery, are shown in Figures 6 and 7. The Main source was
intended to represent the general volume that the squames
RESULTS
could be released from as the surgical staff passed around the
table. Particles from this source were released in a 3 3 3 The results are presented in both graphical and tabulated
pattern. The Nurse source was intended to represent the format for the different ventilation systems. There are three
general volume that the squames could be released from the potential particle outcomes:
circulating nurse. Particles from this source were released in
The particle vents from the room via exhaust grilles. In
a 2 2 2 pattern. Finally, the Surgery source was intended
this case, the particle tracking analysis is stopped.
to represent the general volume that the squames could be
The particle strikes the surgical site or top surface of
released from as the surgical staff leaned over the surgical site.
back table. In this case, the particle tracking analysis is
Because the particles could readily pass to the instruments at stopped.
this point, the Surgery source/top surface of back table target The particle remains in the room at the time where parti-
analysis was not performed in this study. The sizes of the cle tracking is stopped (3600 s).
sources are shown in Table 3.
A number of tests were performed to determine how The results are considered for two of the outcomes,
many particles were released from each point such that the namely the particle is vented via ventilation and the particle
analysis did not change. It was found necessary to release 500 strikes a designated target, in terms of percentages of total
particles from each of the source locations to ensure that the particles released. The other outcome is a trivial calculation,
results were consistent. namely:

ASHRAE Transactions: Research 11


TABLE 3
Details of Particle Sources

Source Physical Size Particle Array Position


Main 54 in. 58 in. 24 in. 333 Centered over bed
(1.37 m 1.47 m 0.61 m) (13500 particles) Extends from anesthesia screen to end of bed
Begins at 4 ft (1.22 m AFF)
Nurse 24 in. 24 in. 72 in. 222 Centered over circulating nurse
(0.61 m 0.61 m 0.83 m) (4000 particles) Begins at floor level
Surgery 14 in. 14 in. 6 in. 333 Centered over surgery site
(0.36 m 0.36 m 0.15 m) (13500 particles) Begins at 0.5 in. (1.27e-2 m) above surgery site

Figure 8 Percentage of particles vented from room via Figure 9 Flow field pattern in Case 1.
ventilation: Main source.

Percentage of particle remaining in room at end of particle tracking TABLE 4


analysis = 100 ((Percentage of particles vented from room at end of
Percentage of Particles Vented
particle tracking analysis) + (Percentage of particles that strike
surgical site or top surface of back table))
from Room After One Hour

In terms of the particles that remain in the room, the anal- Percentage of Particles
ysis shows that the particles either become trapped in recircu- Vented from Room After
lation regions (which they may exit after very long time One Hour
periods) or fall by gravity to the floor in low-velocity flow Case System ACH Main Nurse Surgical
regions.
1 Conventional 18.75 41.9 49.7 46.0
Percentage of Particles Removed 2 Laminar 150 99.4 98.4 94.8
by Ventilation Varying with Time
3 Laminar 15 77.3 49.7 73.3
Figure 8 shows the percentage of particles vented from
the room via ventilation from the Main sources. The Nurse and 4 Laminar (mixed) 20 80.4 54.2 86.7
Surgery source equivalents are similar. Further, the percent- 5 Laminar (low only) 20 85.9 60.8 86.0
ages of particles vented from the room via ventilation at the 6 Laminar (high only) 20 83.8 72.1 80.1
end of the tracking period, 3600 s, are given in Table 4.
The plots and table show that there is a wide range in the 7 Unidirectional flow with 37.25 63.5 65.0 64.9
level of effectiveness in removing the particles via ventilation. curtains
This is an expected result, but there are interesting points to be 8 Upward displacement 37.25 74.3 77.4 44.3
drawn from the results. First, cases that have the same ACH
9 Non-aspirating diffusers 25 72.4 74.1 60.7
show marked differences in terms of the percentage of parti-
cles removed via ventilation. For example, Case 10 demon- 10 Low supply/high exhaust 18.75 69.2 81.8 73.8
strates a more effective removal of particles than Case 1. The 11 Goldman concept 19 52.2 48.2 44.7
reason in this example is that the ventilation system in Case 1
12 ASHRAE Transactions: Research
results in the formation of two large recirculations in the room Percentage of Particles That Hit
where particles can become trapped (Figure 9), whereas, in Surgical Site or Top Surface of Back Table
Case 10, the ventilation system works with the thermal plume Table 5 shows the percentage of particles that strike the
in the center of the room in driving the particles up to the high surgical site or back table targets from the Main, Nurse, and
level exhausts (Figure 10). Secondly, taking Cases 3, 4, 5, 6, Surgery sources. As with the consideration of the vented out
and 9 as a group that adopts the same general approach to particles, there are several interesting points to be made.
ventilation, the percentage vented becomes more uniform in First, the percentages of particles that hit the surgical site
terms of particle release location, though not necessarily in from the Main or Nurse sites are low, in particular, less than
terms of magnitude, as the ACH is increased and the size of the 1%. This is because of the relative dominance of the thermal
supply array becomes bigger. The reason for this is that, for the plume caused by the surgical site. For example, Figure 11
smaller laminar arrays, the areas outside the direct influence of shows such a plume for Case 2. It is only when the particles are
the supply have very low velocity flow fields. Here the parti- released close to the site, in particular, the Surgery source, that
cles tend to drop via gravity to the floor level and remain in the the percentage becomes significant. Second, ACH is not as
room when the particle time limit is reached. significant in the Surgery source/surgical site analysis as

Figure 10 Flow field pattern in Case 10. Figure 11 Flow field pattern in Case 9.

TABLE 5
Percentage of Particles that Hit Surgical Site or Back Table

Percentage of Particles that Hit Surgical Site Percentage of Particles that Hit Back Table
Case System ACH Main Nurse Close Main Nurse
1 Conventional 18.75 0.2 0.3 4.7 1.4 2.4
2 Laminar 150 0.0 0.0 4.2 0.1 0.0
3 Laminar 15 0.2 0.0 4.1 0.1 0.6
4 Laminar (Mixed) 20 0.0 0.0 1.9 0.2 0.3
5 Laminar (Low Only) 20 0.0 0.0 2.1 0.0 0.2
6 Laminar (High Only) 20 0.0 0.0 2.7 0.2 0.2
7 Unidirectional flow with 37.25 0.5 0.0 5.2 2.4 0.2
curtains
8 Upward Displacement 37.25 0.0 0.1 3.4 0.0 0.0
9 Non-aspirating diffusers 25 0.0 0.0 2.1 0.1 0.2
10 Low supply/ High exhaust 18.75 0.0 0.0 6.9 0.2 0.9
11 Goldman Concept 19 0.1 0.2 4.6 1.1 9.8

ASHRAE Transactions: Research 13


design of the ventilation system. In particular, a lower percent-
age of particles hit the site in Case 4, which has an ACH of 20,
than Case 2, which has an ACH of 150. Third, with the excep-
tion of Case 11, the percentage of particles that hit the back
table from the Main or Nurse sites are relatively low. While
there is no thermal plume preventing the particles from hitting
the table, the particles only strike the target if they enter a
region of low velocity flow, where the particles settle by grav-
ity, or they are blown directly onto the table, which is the case
in the high Nurse source value of 9.8%. The results shown for
Cases 4, 5, and 6 indicate that a mixture of exhaust location
levels is better than low or high only. Finally, the cases that can
be placed together in a laminar flow type group, namely, Cases
2, 3, 4, 5, 6, and 9, do not show higher strike rates than the other
systems. In fact, Cases 4 and 9 represent the lowest strike
percentages of all the cases considered.
Figure 12 Thermal plume from surgical site in Case 2
CONCLUSIONS AND DISCUSSION (laminar design).
From the above results, the study showed:
particular, the operating lights and surgical staff represent a
Cases that have the same ACH show marked differences large heat density in the middle of the room. Particulates could
in terms of the percentage of particles removed via ven- get caught in buoyant plumes created by these heat-dissipating
tilation. objects, at which point control of them is lost. However, if a
The practice of increasing ACH to high levels results in laminar flow type system is employed, the particles are instead
excellent removal of particles via ventilation, but it does driven by the flow to be exhausted. Ideally then, the array size
not necessarily mean that the percentage of particles that should be large enough to cover the main heat-dissipating
strike surfaces of concern will continue to decrease. objects. This is illustrated in Figure 11, which shows the flow
The percentages of particles that hit the surgical site field for Case 9.
from the Main or Nurse sites are low, less than 1%. This Further, another factor is the thermal plume created by the
is because of the relative dominance of the thermal surgical site, shown for Case 2 in Figure 12. Provided that the
plume caused by the surgical site. Only when the parti- laminar flow regime is not strong enough such that the parti-
cles are released close to the site, in particular the Sur- cles are impinged on the surgical site against the thermal
gery source, does the percentage become significant. plume, a danger highlighted by Lewis (1993), then the plume
ACH is not as significant in the Surgery source/surgical should be sufficient to protect the surgical site.
site analysis as design of the ventilation system. In par-
ticular, a lower percentage of particles hit the site in a REFERENCES
case that has an ACH of 20 than one that has an ACH of
150. Alani A., D. Dixon-Hardy, and M. Seymour. 1998. Contami-
In a system that provides a laminar flow regime, a mix- nants transport modelling. EngD in Environmental
ture of exhaust location levels works better than either Technology Conference.
low or high level locations only. However, the difference ASHRAE. 1999. 1999 ASHRAE HandbookApplications.
is not significant enough that the low or high level loca- Atlanta: American Society of Heating, Refrigerating
tion systems are not viable options. and Air-Conditioning Engineers, Inc.
Systems that provide laminar flow regimes represent the Chen, P-P., and C.T. Crowe. 1984. On the Monte-Carlo
best option for an operating room in terms of contam- method for modelling particle dispersion in turbulence
ination control, as they result in the smallest percentage gas-solid flows. ASME-FED 10, 37 42.
of particles impacting the surgical site. However, care Crowe, C., M. Sommerfield, and Y. Tsuji. 1998. Multiphase
needs to be taken in the sizing of the laminar flow array. flows with droplets and particles. CRC Press.
A face velocity of around 30 to 35 fpm (0.15 to 0.18
DIN. 1999. DIN 1946/4, Heating, ventilation and air condi-
m/s) is sufficient from the laminar diffuser array, pro-
tioning: HVAC systems in hospitals.
vided that the array size itself is set correctly.
DIN. 1990. DIN 4799, Luftfuhrungssyteme fur Operation-
To expand on the issue of diffuser array size, it appears sraume.
that the main factor in the design of the ventilation system is Goldman, M. 2000. Operating room airflow and distribution.
the control of the central region of the operating room. In ASHRAE 2000 Winter Meeting, Dallas.

14 ASHRAE Transactions: Research


Gosman, D., and E. Ioannides. 1981. Aspects of computer Ziang, Z., Q. Chen, and F. Haghighat. 1995. Airflow and air
simulation of liquid-fuelled combustors. AIAA 19th quality in large enclosures. ASME Journal of Solar
Aerospace Science Meeting 81-0323, 1 10. Energy Engineering 117: 114-122.
Haghighat, F., Z. Jiang, and Y. Zhang. 1994. Impact of venti-
lation rate and partition layout on VOC emission rate: DISCUSSION
Time-dependent contaminant removal. International
Anand Seth, Director of Utilities and Engineering, Part-
Journal of Indoor Air Quality and Climate 4: 276-283.
ners Health Care Systems, Boston, Mass.: Excellent work.
Lewis, J.R. 1993. Operating room air distribution effective- It has been a long time since such work was done. If the inter-
ness. ASHRAE Transactions 99(2): 1191-1200. nal load is higher, would we recommend lower supply air
Lidwell, O.M. 1988. Air, antibiotics and sepsis in replace- temperature?
ment joints. Journal of Hospital Infection 11 (Supple-
Farhad Memarzadeh: If the governing standard dictated that
ment C): 18-40.
the same exhaust temperature was required, then the supply
Lo, L-M. 1997. Numerical studies of airflow movement and air temperature would automatically be decreased. In a
contaminant transport in hospital operating rooms. M.Sc general response, the important issue is control of the central
thesis, University of Minnesota. thermal plume. Control would be lost, at least to some extent,
Memarzadeh, F. 2000. Assessing the efficacy of ultraviolet if the supply temperature was not decreased accordingly with
germicidal irradiation and ventilation in removing load.
mycobacterium tuberculosis. National Institutes of Leon Kloostra, Chief Engineer, Titus, Richardson, Tex.:
Health, Office of the Director, Bethesda, Md. (1) What effect will OR lights mounted directly above the OR
Memarzadeh, F. 1998. Ventilation design handbook on ani- table give us? (2) Will airborne infection increase even with
mal research facilities using static microisolators. the best airflow design with the light mounted directly over the
National Institutes of Health, Office of the Director, OR table?
Bethesda, Md.
Memarzadeh: (1) The OR lights would still be part of the
Memarzadeh, F., and Z. Ziang. 2000. Methodology for mini- central thermal plume. They would have to be moved outside
mizing risk from airborne organisms in hospital isola- of the central region to have a significant impact. (2) There
tion rooms. ASHRAE Transactions. may be some impact to the infection rate, but it will be some-
Ormancey, A., and J. Martinon. 1984. Prediction of particle what dependant on the way the flow reacts to the new interac-
dispersion in turbulent flow. PhysicoChemical Hydrody- tion between the OR lights and other objects in their
namics 5: 229 224. proximity. The effect may be adverse or beneficial.
Press, W.H., S.A. Teukolsky, W.T. Vetterling, and B.P. Flan- Nicholas Smilanich, President, Sensor Development
nary. 1992. Numerical recipes in FORTRAN, 2d ed. Corporation, Rock River, Ohio: (1) Would model apply to
Cambridge: Cambridge University Press. VOCs distribution? (2) Would the model apply to fungus and
Salvati, E.A., R.P. Robinson, S.M. Zeno, B.L. Koslin, B.D. mold also?
Brause, and P.D. Wilson. 1982. Infection rates after Memarzadeh: (1) In the case of VOCs, it is very unlikely that
3175 total hip and total knee replacements performed the surgical site would be affected. Further, there would be no
with and without a horizontal unidirectional filtered air- deposition of VOCs in the room. (2) In the case of fungus and
flow system. Journal of Bone and Joint Surgery, Inc. mold, the two have a wide range of sizes. For example, Pencil-
64A(4): 525-535. lium is 3 to 5 microns, Stemphylium up to 75 microns. Here
Schmidt, P. 1987. Air control in operating theatres. Heizung the model will be applicable up to a certain level, then larger
Luftung Haus Technik 38(3): 145-153. sizes will be more susceptible to impingement into the surgi-
Shuen, J-S., L-D. Chen, and G.M. Faeth. 1983. Evaluation of cal site, and deposition within the room. Smaller particle sizes
a stochastic model of particle dispersion in a turbulent will be less susceptible.
round jet. AIChE Journal 29: 167-170. Scott M. Fanning, P.E., Principal, Fanning, Fanning and
Snyder, O.P. 1996. A safe hands wash program for retail Associates, Inc., Lubbock, Tex.: It appeared from the
food operations. Hospitality Institute of Technology and presentation that low return was preferred in limiting infection
Management, St. Paul, Minnesota. at the wound site. Please elaborate on the number and location
Snyder, W.H., and J.L. Lumley. 1971. Some measurement of of return air grilles for optimum asepsis control.
particle velocity autocorrelation functions in turbulent Memarzadeh: The lowest infection rate of the surgical site
flow. J. Fluid Mechanics 48: 41-71. actually occurs for a mixture of high and low exhausts, rather
Woods, J.E., D.T. Braymen, R.W. Rasmussen, P.E. Rey- than low only, though the difference is relatively small. As far
nolds, and G.M. Montag. 1986. Ventilation require- as optimal placement and number is concerned, further cases
ments in hospital operating roomsPart I: Control of would need to be run to determine these values, as the sample
airborne particles. ASHRAE Transactions 92(2). number with regards to this aspect is insufficient in this study.

ASHRAE Transactions: Research 15


REFERENCES
ACGIH. 1995. Industrial Ventilation, A Manual of ARI. 1999b. ARI 700-99, Specification for
Recommended Practice, 22nd ed., Appendix A. Fluorocarbon Refrigerants. Arlington, Va.: Air-
Cincinnati: American Conference of Conditioning and Refrigeration Institute.
Governmental Industrial Hygienists. Arthur D. Little, Inc. 1976. Impact Assessment of
ACGIH. 1988. Industrial Ventilation, A Manual of ASHRAE Standard 90-75, Energy Conservation
Recommended Practice, 20th ed. Cincinnati: and New Building Design. Federal Energy
American Conference of Governmental Administration, Washington, D.C. (Available
Industrial Hygienists. from National Technical Information Service,
AIA. 2001. Guidelines for Design and Construction Springfield, Va., as PB-252 639.)
of Hospitals and Health Care Facilities. ASA. 1946. American Standard Building
Washington, D.C.: American Institute of Requirements for Light and Ventilation (A 53.1).
Architects. New York: American Standards Association.
AIA. 1996-97. Guidelines for Design and ASHE. 1993, 1994. Facilities Engineering;
Construction of Hospital and Health Care Management Series. Chicago: American Society
Facilities, Section 1.4, Provisions for Disasters. for Healthcare Engineering.
Washington, D.C.: American Institute of ASHRAE. 2003. Guideline 16-2003, Selecting
Architects. Outdoor, Return, and Relief Dampers for Air-
AHA. 1985. Steam Purity: Resolving Observed Side Economizer Systems. Atlanta: American
Problems (catalog number 031801). Chicago: Society of Heating, Refrigerating and Air-
American Society for Hospital Central Service Conditioning Engineers, Inc.
Personnel of the American Hospital ASHRAE. 2001a. 2001 ASHRAE Handbook
Association. Fundamentals. Atlanta: American Society of
AMCA. 1990. AMCA 201-90, Fans and Fan Heating, Refrigerating and Air-Conditioning
Systems. Arlington Heights, Ill.: Air Movement Engineers, Inc.
and Control Association International, Inc. ASHRAE. 2001b. ANSI/ASHRAE Standard 15-2001,
American College of Surgeons. 1996. Guidelines for Safety Standard for Refrigeration Systems.
Optimal Office-Based Surgery, 2d ed. Chicago: Atlanta: American Society of Heating,
ACS. Refrigerating and Air-Conditioning Engineers,
American College of Surgeons. 1976. Definition of Inc.
Surgical Microbiologic Clean Air. Bulletin of ASHRAE. 2001c. ANSI/ASHRAE Standard 62-2001,
American College of Surgeons 61: 1921. Ventilation for Acceptable Indoor Air Quality.
ARI. 1999a. ARI 430-99, Central Station Air Atlanta: American Society of Heating,
Handling Units. Arlington, Va.: Air- Refrigerating and Air-Conditioning Engineers,
Conditioning and Refrigeration Institute. Inc.

279
280 HVAC DESIGN MANUAL FOR HOSPITALS AND CLINICS

ASHRAE. 2001d. ANSI/ASHRAE/IESNA Standard ASHRAE. 1976. ASHRAE Standard 52-76, Method
90.1-2001, Energy Standard for Buildings of Testing Air-Cleaning Devices Used in
Except Low-Rise Residential Buildings. Atlanta: General Ventilation for Removing Particulate
American Society of Heating, Refrigerating and Matter. New York: American Society of
Air-Conditioning Engineers, Inc. Heating, Refrigerating and Air-Conditioning
ASHRAE. 2000a. 2000 ASHRAE HandbookHVAC Engineers, Inc.
Systems and Equipment. Atlanta: American ASHRAE. 1974. ASHRAE Standard 55-74, Thermal
Society of Heating, Refrigerating and Air- Environmental Conditions for Human
Conditioning Engineers, Inc. Occupancy. New York: American Society of
ASHRAE. 2000b. ASHRAE Guideline 12, Heating, Refrigerating and Air-Conditioning
Minimizing the Risk of Legionellosis Associated Engineers, Inc.
with Building Water Systems. Atlanta: American ASPE. 1994. ASPE Data Book, Chapter 28, Water
Society of Heating, Refrigerating and Air- Treatment. Westlake, Calif.: American Society
Conditioning Engineers, Inc. of Plumbing Engineers.
ASHRAE. 1999a. 1999 ASHRAE HandbookHVAC ASTM. 2000. D1356-00a, Standard Terminology
Applications. Atlanta: American Society of Relating to Sampling and Analysis of
Heating, Refrigerating and Air-Conditioning Atmospheres. West Conshohocken, Penn.:
Engineers, Inc. ASTM International.
ASHRAE. 1999b. Standard 52.2, Method of Testing
Balaras, C.A., et al. 2002. HVAC systems and indoor
General Ventilation Air-Cleaning Devices for
conditions in hellenic hospital operating rooms.
Removal Efficiency by Particle Size. Atlanta:
ASHRAE Transactions 108(2): 23-37.
American Society of Heating, Refrigerating and
Banks, R.S. (ed.). 1978. Hospital ventilation
Air-Conditioning Engineers, Inc.
standards and energy conservation. Proceedings
ASHRAE. 1996. ASHRAE Guideline 1-1996, The
of the 1978 International Working Conference.
HVAC Commissioning Process. Atlanta:
Lawrence Berkeley Laboratory, Berkeley, Calif.
American Society of Heating, Refrigerating and
Air-Conditioning Engineers, Inc. Bartley, J.M. 2000. APIC State-of-the-Art Report:
ASHRAE. 1993. Air-Conditioning Systems Design The Role of Infection Control During
Manual. Atlanta: American Society of Heating, Construction in Healthcare Facilities.
Refrigerating and Air-Conditioning Engineers, Washington, D.C.: Association for Professionals
Inc. in Infection Control and Epidemiology, Inc.
ASHRAE. 1992. Standard 52.1, Gravimetric and BOCA. 1977. Model Code for Energy Conservation
Dust-Spot Procedures for Testing Air-Cleaning in New Building Construction. Building
Devices Used in General Ventilation for Officials and Code Administrators International,
Removing Particulate Matter. Atlanta: Inc. (BOCA), International Conference of
American Society of Heating, Refrigerating and Building Officials (ICBO), National Conference
Air-Conditioning Engineers, Inc. of States on Building Codes and Standards, Inc.
ASHRAE. 1991. Terminology of HVAC&R. Atlanta: (NCSBCS), and Southern Building Code
American Society of Heating, Refrigerating and Congress International, Inc. (SBCCI) for U.S.
Air-Conditioning Engineers, Inc. Department of Energy, Washington, D.C.
ASHRAE. 1981. ASHRAE Standard 62-1981, (Available from National Technical Information
Ventilation for Acceptable Indoor Air Quality. Service, Springfield, Va., as SAN/1230-l.)
Atlanta: American Society of Heating, BOCA. 1975. The BOCA Basic Building Code, 6th
Refrigerating and Air-Conditioning Engineers, ed. Chicago: Building Officials and Code
Inc. Administrators International, Inc.
ASHRAE. 1977. ASHRAE Standard 90-75, Energy Bregande, B. 1974. Major Issues in Construction and
Conservation in New Building Design (Section Design. In Ambulatory Surgical Centers:
12). New York: American Society of Heating, Development and Management. T.T. Donovan,
Refrigerating and Air-Conditioning Engineers, ed., pp. 4757. Germantown, Md: Aspen
Inc. Systems Corp.
REFERENCES 281

Brosseau, L.M., et al. 2000a. Methods and criteria Department of the Air Force. 1967. Facility Design
for cleaning contaminated ducts and air- and Planning: Engineering Weather Data
handling equipment. ASHRAE Transactions (AFM-88-8). Washington, D.C.
106(1): 188-199. DHEW. 1979. Minimum Requirements of
Brosseau, L.M. et al. 2000b. Duct cleaning: A review Construction and Equipment for Hospital and
of associated health effects and results of Medical Facilities (DHEW Publication No.
company and expert survey. ASHRAE (BRA) 79-14500). Washington, D.C.: U.S.
Transactions 106(1): 180-187. Department of Health, Education, and Welfare,
Butkus, A. S., D. L. Doyle, J. OBrien Gibbons, and Health Resources Administration,
L.V. Wilson. 1999. Grumman/Butkus Bulletin DIN. 1999. DIN 1946/4, Ventilation and Air
(September). ConditioningPart 4: Ventilation in Hospitals.
Carlson, N.G., and A.J. Streifel. 1996. Quality Berlin: Deutsches Institut fur Normung.
Assurance Methods Used During Remediation Donaldson, B., and B. Nagengast. 1994 Heat and
of Fiberglass Lined Duct Work with Fungal Cold: Mastering the Great Indoors. Atlanta:
Contamination. Presented at the American American Society of Heating, Refrigerating and
Industrial Hygiene Conference and Exposition Air-Conditioning Engineers, Inc.
(Washington, D.C.). Unpublished. Dorlands Illustrated Medical Dictionary, 29th ed.
Carrier. 1997. Light and Heavy Commercial 2000. Philadelphia: W.B. Saunders Co.
Products and Systems Catalog. Carrier Dupont, P. 1999. Air Distribution Systems. In A
Corporation, Syracuse, N.Y. Practical Guide to Ventilation Practices and
CDC. 2001. Draft Guideline for Environmental Systems for Existing Buildings. HPAC
Infection Control in Healthcare Facilities. Engineering SupplementContracting
Atlanta: Centers for Disease Control and Business, April/May.
Prevention. DuPont, P. 2000. Chilled Water Plants, Chapter 5.4.
CDC. 1999. Biosafety in Microbiological and In Handbook of Facilities Engineering and
Biomedical Laboratories, 4th ed. Washington, Management for Institutional, Commercial and
D.C.: National Institutes of Health and Centers Industrial Buildings, A. Seth et al. (eds.) New
for Disease Control and Prevention. York: McGraw-Hill.
CDC. 1999. Bioterrorism Readiness Plan: A Edgerton, S.A., D.V. Kenny, and D.W. Joseph. 1989.
Template for Healthcare Facilities. Atlanta: Determination of amines in the indoor air from
Centers for Disease Control and Prevention. steam humidification. Environmental Science &
CDC. 1994. Guidelines for Preventing the Technology 23(4).
Transmission of Mycobacterium Tuberculosis in Elovitz, K.E. 1993. Should engineers notify
Health-Care Facilities. MMWR occupants about chemicals in steam?
Recommendations and Reports 43(RR-13), Consulting-Specifying Engineer (September).
October 28. U.S. Department of Health and Farnsworth Group. 2001. Energy Analysis: Genesis
Human Services, Public Health Service. Health Care Facility East and West Campus,
Atlanta: Centers for Disease Control and Davenport, IA. St. Louis: Farnsworth Group.
Prevention. FEMA. 1984. Hospital Emergency Department
CDC. 1994. Guidelines for Preventing Transmission Management of Radiation Accidents.
of Mycobacterium Tuberculosis in Health-Care Washington, D.C.: Federal Emergency
Settings. Morbidity Mortality Weekly Report 43 Management Agency.
(RR-13). Atlanta: Centers for Disease Control Ferguson, K. 2000. Chapter 9.6 in Handbook of
and Prevention. Facilities Engineering and Management for
Coogan, J.J. 1996. Effects of surrounding spaces on Commercial, Institutional and Industrial
rooms pressurized by differential flow control. Buildings, A. Seth et al. (eds.). New York:
ASHRAE Transactions 102(1): 18-25. McGraw-Hill.
Davis, J.R. 1998. Avoiding litigation arising from Garay, P.N., and F.M. Cohn. 1992. High-Quality
IAQ complaints. Heating/Piping/Air Industrial Water Management Manual. Lilburn,
Conditioning 70(10): 8992. Ga.: The Fairmont Press.
282 HVAC DESIGN MANUAL FOR HOSPITALS AND CLINICS

Garner, J.S. 1996. Guideline for isolation Hospital Infection Control Practices Advisory
precautions in hospitals. Infection Control & Committee. 1996. Recommendations for
Hospital Epidemiology 17(1): 5380. isolation precautions in hospitals. American
Grattan, D.A., M.E. Koutek, and S.A. Russum. 1989. Journal of Infection Control 24: 24-52.
Amine levels in steam-humidified room air. Howorth, F.H. 1985. Prevention of airborne infection
Engineered Systems (September/October). during surgery. ASHRAE Transactions 91(1B):
Hakbaz, M., and M. Martyak. 2000. Healthcare 291-304.
Facilities Management Series: Unleashing the IEEE. 1992. Standard 519, Recommended Practices
Potential of the Facility Condition Assessment and Requirements for Harmonic Control In
Using Web Technology. Chicago: American Electric Power Systems. New York: Institute of
Society for Healthcare Engineering. Electrical and Electronics Engineers, Inc.
Hambraeus, A. 1988. Aerobiology in the operating ISO. 1994. EN 7730, Moderate Thermal
roomA review. Journal of Hospital Infection. EnvironmentsDetermination of the PMV and
Harteen, B.T., S. Blake, and W. Hughes. 2000. PPD Indices and Specification of the Conditions
Chapters 7.1.1 and 7.1.2 in Handbook of for Thermal Comfort, 2d ed. (Ref. No. ISO
Facilities Engineering and Management for 7730:1994(E)). Geneva: International Standards
Commercial, Institutional and Industrial Organization.
Buildings, A. Seth et al. (eds.). New York: JCAHO. 2002. Joint Commission Accreditation
McGraw-Hill. Manual for Hospitals. Oakbrook Terrace, Ill.:
Hayden, C.S., et al. 1998. Air Volume Migration Joint Commission on Accreditation of
from Negative Pressure Isolation Rooms During Healthcare Organizations.
Entry/Exit. Applied Occupational and
JCAHO. 2000. Comprehensive Accreditation
Environmental Hygiene 13(7): 518527.
Manual for Hospitals--The Official Handbook
Hayden, C.S., and P.A. Jensen. 1996. Isolation
(Standard EC.1.4. IntentItem l). Oakbrook
RoomsEffective Economical Achievement
Terrace, Ill.: Joint Commission on Accreditation
and Maintenance of Negative Air Pressure.
of Healthcare Organizations.
Report No. ECTB 212-05d. U.S. Department of
JCAHO. 1997. Hospital Accreditation Standards.
Health and Human Services, Public Health
Overview. Oakbrook Terrace, Ill.: Joint
Service, Centers for Disease Control and
Commission on Accreditation of Healthcare
Prevention, National Institute for Occupational
Organizations.
Safety and Health, Washington, D.C. (Also in
Health Care Facilities Management, January Klauss, A.K., et al. 1970. History of the changing
1997.) concepts in ventilation requirements. ASHRAE
Heirholzer, Jr., W.J. 1993. Workshop on Engineering Journal 12(6): 51-55.
Controls for Preventing Airborne Infections in Kowalski, W., and W. Bahnfleth. 1998. Airborne
Workers in Health Care and Related Facilities. Respiratory Diseases and Mechanical Systems
DHHS Publication No. (NIOSH) 94-106. U.S. for Control of Microbes. Heating/Piping/Air
Department of Health and Human Services, Conditioning 70(7).
Washington, D.C. Kowalski, W.J., W.P. Bahnfleth, and T.S. Whittam.
Hermans, R.D. 2000. Health care facility design 1999. Filtration of airborne microorganisms:
manualRoom design. ASHRAE Transactions Modeling and prediction. ASHRAE Transactions
106(2): 762-767. 105(2): 4-17.
Hermans, R.D., and A.J. Streifel. 1993. Ventilation Kuehn, T.J., et al. 1996. Identification of
Designs. In Proceedings of the Workshop on contaminants, exposures, effects, and control
Engineering Controls for Preventing Airborne options for construction renovation activities.
Infections in Workers in Health Care and ASHRAE Transactions 102(2): 89-101.
Related Facilities, DHHS (NIOSH) Publication Kusuda, T. 1976. Control of ventilation to conserve
No. 94-106. Beirbaum, P.J., and M. Lippmann energy while maintaining acceptable indoor air
(eds.). U.S. Department of Health and Human quality. ASHRAE Transactions 82(1): 1169-
Services, Washington, D.C. 1181.
REFERENCES 283

Laufman, H. 1999. Surgeons requirements for OR Memarzadeh, F., and A. Manning. 2000. Thermal
air quality. Unreviewed paper presented to SP comfort, uniformity, and ventilation
91 by the author. effectiveness in patient rooms: Performance
Laufman, H. 1994. Streamlining environmental assessment using ventilation indices. ASHRAE
safety in the operating room: A common bond Transactions 106(2): 748-761.
between surgeons and hospital engineers. ASHE Memarzadeh, F., and J. Jiang. 2000. Methodology
HealthCare Facility Management Series, for minimizing risk from airborne organisms in
December. hospital isolation rooms. ASHRAE Transactions
Laurel, V.L., et al. 1999. Pseudoepidemic of 106(2): 731-747.
Aspergillus nigeri infections traced to specimen Memarzadeh, F. 2000. Assessing the Efficacy of
contamination in the microbiology laboratory. Ultraviolet Germicidal Irradiation and
Journal of Clinical Microbiology 37(5): 1612 Ventilation in Removing Mycobacterium
1616. Tuberculosis. Bethesda, Md.: National Institutes
Levin, H. Commissioning: Life cycle design of Health.
perspective. In Proceedings of the Fifth National Memarzadeh, F. 1998. Ventilation Design Handbook
Conference on Building Commissioning on Animal Research Facilities Using Static
(Huntington Beach, Calif.). Portland, Ore.: Microisolators. Washington, D.C.: National
Portland Energy Conservation, Inc. Institutes of Health.
Lewis, J.R. 1993. Operating room air distribution Memarzadeh, F. 1996. Methodology for
effectiveness. ASHRAE Transactions 99(2): Optimization of Laboratory Hood. Washington,
1191-1200. D.C.: National Institutes of Health.
Lewis, J.R. 1988. Application of VAV, DDC, and Morrow, P.E. 1980. Physics of airborne particles and
smoke management to hospital nursing wards. their deposition in the lung. Annals of the New
ASHRAE Transactions 94(1): 1193-1208. York Academy of Sciences 353: 71-80.
Lieser, K.H. 1975. Sorption Mechanisms (pp. 91- Murray, W.A., A.J. Streifel, T.J. ODea, and F.S.
145). In Sorption and Filtration Methods for Rahame. 1988. Ventilation for protection of
Gas and Water Purification, Bonnevie- immune compromised patients. ASHRAE
Svendsen, M. (ed.). NATO Advanced Study Transactions 94(1): 1185-1192.
Institutes, Series E, Vol. 13. Leyden, NADCA. 2002. General Specifications for the
Netherlands: Noordhoff International Cleaning of Commercial Heating, Ventilating
Publishing. and Air Conditioning Systems. Washington,
Martone, W.J., et al. 1998. Incidence and nature of D.C.: National Air Duct Cleaners Association.
endemic and epidemic nosocomial infections Nevins, R.G. 1976. Air Diffusion Dynamics: Theory,
[referencing data from the U.S. National Center Design and Application. Birmingham, Mich.:
for Health Statistics]. In Hospital Infections Business News Publishing Company.
(Chapter 30, 4th ed.), J.V. Bennett and P.S. NFEC. 1990. Design Policy Letter DPL-90-0004:
Brachman (eds.). Philadelphia: Lippincott- Use of steam containing amines for food
Raven. processing, humidification, and medical
McCarthy, J.F., and M. Dykens. 2000. instrument sterilizers. Department of the Navy,
Commissioning programs for HVAC systems. In Naval Facilities Engineering Command,
Handbook of Facilities Engineering and Alexandria, Va.
Management for Commercial, Institutional, and NFPA. 2003. Standard 101, Life Safety Code.
Industrial Buildings (Section 6.2), A. Seth et al. Quincy, Mass.: National Fire Protection
(eds.). New York: McGraw-Hill. Association, Inc.
McGraw-Hill Encyclopedia of Science and NFPA. 2002a. NFPA 70, National Electrical Code.
Technology. 1997. New York: McGraw-Hill. Quincy, Mass.: National Fire Protection
Memarzadeh, F., and A.P. Manning. 2002. Association.
Comparison of operating room ventilation NFPA. 2002b. NFPA 99, Standard for Health Care
systems in the protection of the surgical site. Facilities. Quincy, Mass.: National Fire
ASHRAE Transactions 108(2): 3-15. Protection Association.
284 HVAC DESIGN MANUAL FOR HOSPITALS AND CLINICS

NFPA. 2002c. NFPA 110, Standard for Emergency Piette, M., and B. Nordman. 1996. Cost and benefits
and Standby Power Systems. Quincy, Mass.: from utility-funded commissioning of energy
National Fire Protection Association. efficient measures in 16 buildings. ASHRAE
NFPA. 2000a. NFPA 92A, Recommended Practice Transactions 102(1): 482491.
for Smoke-Control Systems. Quincy, Mass.: The Power of Prediction. Industry Week (July 4,
National Fire Protection Association. 1994), pp. 4547.
NFPA. 2000b. NFPA 92B, Guide for Smoke Rhame, F.S., A.J. Streifel, J.H. Kersey, and P.B.
Management Systems in Malls, Atria, and Large McGlave. 1984. Extrinsic risk factors for
Areas. Quincy, Mass.: National Fire Protection pneumonia in the patient at high risk of
Association. infection. The American Journal of Medicine,
NFPA. 1999. Standard 99, Health Care Facilities May 15: 42-52.
Standard. Quincy, Mass: National Fire Ricks, R.C. 1984. Hospital Emergency Department
Protection Association. Management of Radiation Accidents. Oak
NIOSH. 1999. International Chemical Safety Card, Ridge, Tenn.: Oak Ridge Associated
ICSC:0257, 2-Diethylaminoethanol. Universities.
Washington, D.C.: National Institute for Riley, E.C. 1980. The role of ventilation in the
Occupational Safety and Health. spread of measles in an elementary school. In
NIOSH. 1996. NEG and NIOSH Basis for an Airborne Contagion: Annals of the New York
Occupational Health Standard: 2- Academy of Sciences 353: 25-34.
Diethylaminoethanol (Publication No. 96-104).
Riley, E.C., G. Murphy, and R.L. Riley. 1978.
Washington, D.C.: National Institute for
Airborne spread of measles in a suburban
Occupational Safety and Health.
elementary school. American Journal of
NIOSH. 1983. Health Hazard Evaluation Report,
Epidemiology 107: 421-432.
HETA 83-020-1351, Johnson Museum, Cornell
Riskowski, G.L., R.G. Maghirang, and W. Wang.
University, Ithaca, New York. Washington,
1996. Development of ventilation rates and
D.C.: National Institute for Occupational Safety
design information for laboratory animal
and Health.
facilities: Part 2Laboratory tests. ASHRAE
NIST. 2003. Building Economics Analysis Software
Transactions 102(2): 195-209.
(http://www.bfrl.nist.gov/oae/software.html).
Rohles, F.H., Jr., J.E. Woods, and R.G. Nevins. 1974.
Gaithersburg, Md.: National Institute of
The effects of air movement and temperature on
Standards and Technology.
the thermal sensations of sedentary man.
NIST. 2002. Energy Price Indices and Discount
ASHRAE Transactions 80(1): 101-119.
Factors for LCC Analysis. Gaithersburg, Md.:
National Institute of Standards and Technology. Ryan, K.J. (ed.) 1994. Sherris Medical
NIST. 1995. Life-Cycle Costing Manual for the Microbiology, 3d ed. Norwalk, Conn.: Appleton
Federal Energy Management Program & Lange.
(Handbook 135). Gaithersburg, Md.: National Simon, J.D. 1997. Biological terrorism. Journal of
Institute of Standards and Technology. the American Medical Association 278: 428-
NSC. 1988. Fundamentals of Industrial Hygiene. 430.
Chicago: National Safety Council. SMACNA. 1995. IAQ Guidelines for Occupied
Oglesby, S., Jr., and G.B. Nichols. 1977. Buildings Under Construction. Chantilly, Va.:
Electrostatic Precipitation (pp. 189-256). In Air Sheet Metal and Air Conditioning Contractors
Pollution, 3d ed., Vol. IV, Engineering Control National Association, Inc.
of Air Pollution, A.C. Stern (ed.). New York: SOCMA. 1991. News release (December 16): Alkyl
Academic Press, Inc. Amines Council Announces Results for DEAE
PECI. 1996. Summary Report. In Proceedings of the Studies. Washington, D.C.: Synthetic Organic
Fourth National Conference on Building Chemical Manufacturers Association.
Commissioning (St. Petersburg Beach, Fla.). SOCMA. 1988. News release (December 14): Alkyl
Portland, Ore.: Portland Energy Conservation, Amines Council Announces Completion of
Inc. Studies of the Effects of Amines in Steam Used
REFERENCES 285

for Humidification. Washington, D.C.: Synthetic University of Minnesota. 2001. Construction


Organic Chemical Manufacturers Association. management for health care: Indoor air quality
SOEC. 1996. Energy balance sheets. In: (course material for short course). Minneapolis:
EUROSTAT, Statistical Document 4C, Energy UM.
and Industry, Accounts and Surveys. Belgium:
USDOE. 1978. Energy performance standards for
Statistical Office of the European Commission.
new buildings. Federal Register 44:68218-
Stedmans Medical Dictionary, 27th ed. 2000.
68220 (U.S. Department of Energy and U.S.
Baltimore: Williams & Wilkins.
Department of Housing and Urban
Streifel, A.J. 2000. Health-Care IAQ: Guidance for
Development).
infection control. Heating/Piping/
AirConditioning (HPAC) 72 (10 October): 28- USDHS. 1992. Managing Hazardous Materials
30, 33-34, 36. Incidents, Volume II, Hospital Emergency
Streifel, A.J. 1997. Recognizing IAQ risk and Departments. Washington, D.C.: U.S.
implementing an IAQ program (Chapter 7). In A Department of Human Services.
Guide to Managing Indoor Air Quality in
Verdicts and Settlements: Medical Malpractice.
Health Care Organizations, W. Hansen, ed.
1999. Infection at Surgical Site-Fungus.
Oakbrook Terrace, Ill.: Joint Commission Press.
Massachusetts Lawyers Weekly 2674 (August 2,
Streifel, A.J., and C. Hendrickson. 2002. Assessment
1999): 27.
of health risks: Related to construction. Heating/
Piping/Air Conditioning 74(2): 27-28, 30, 32. Wilk, S.M. 1985. Legal Issues. In Freestanding
Streifel, A.J., et al. 1989. Control of airborne fungal Emergency Centers, P.M. Friend and J.M.
spores in a university hospital. Environment Shiver (eds.). Rockville, Md.: Aspen Systems
International 15(1-6): 221-227. Corp.
Tabers Cyclopedic Medical Dictionary, 12th ed.
Woods, J.E., et al. 1986. Ventilation requirements in
1970. Philadelphia: F.A. Davis Company.
hospital operating roomsPart I: Control of
Trane. 1982. Fans and their application in air
airborne particles. ASHRAE Transactions
conditioning. The Trane Company, La Crosse,
92(2A): 396-426.
Wisc.
Trane. 1996. Air Handling Unit Product Catalog Yaglou, C.P., E.C. Riley, and D.I. Coggins. 1936.
(CLCH-DS-7). The Trane Company. La Crosse, Ventilation requirements. ASHVE Transactions
Wisc. 42: 133-162.
BIBLIOGRAPHY
AGCC. 1996. Natural Gas Cooling Equipment BOMA. [Latest Edition]. Model Mechanical Codes.
Guide. Arlington, Va.: American Gas Cooling Washington, D.C.: Building Owners and
Center. Managers Association.
Air Infiltration and Ventilation Center (AIVC). Carrier. 1983. Centrifugal Refrigeration Equipment
Technical Note 5 (An Air Infiltration Glossary). (TDP Manual 791-329). Syracuse, N.Y.: Carrier
http://www.aivc.org/ Corporation.
Air Infiltration and Ventilation Center (AIVC). Carrier. 1983. Reciprocating Liquid Chilling
Technical Note 28 (A Guide to Contaminant Equipment Technical Development Manual
Removal Effectiveness). [http://www.aivc.org/]. (TDP Manual 791-332). Syracuse, N.Y.: Carrier
Corporation.
AMA. 2000. Policy H-130.979: National Disaster
Medical System. American Medical CDC (Centers for Disease Control and Prevention).
Association, Chicago. 1995. Recommendations for civilian community
weapons depots: guidelines for medical
ASHRAE. 2002. 2002 ASHRAE Handbook
preparedness. Federal Register 60(123): June
Refrigeration. Atlanta: American Society of
27.
Heating, Refrigerating and Air-Conditioning
Chaddock, J.B. 1986. Ventilation and exhaust air
Engineers, Inc.
requirements for hospitalsPart 1: Standards
ASHRAE. 1997. ANSI/ASHRAE Standard 129, (RP-312). ASHRAE Transactions 92(2A): 350-
Measuring Air Change Effectiveness. Atlanta: 371.
American Society of Heating, Refrigerating and Cler, G.L. 1997. Tech Update: Gas Chiller Buyers
Air-Conditioning Engineers, Inc. Guide (TU-97-11). Boulder, Colo.: E-Source.
ASHRAE. 1993. ASHRAE Guideline 4-1993, Cole, E.C., and C.E. Cook. 1998. Characterization of
Preparation of Operating and Maintenance infectious aerosols in health-care facilities: An
Documentation for Building Systems. Atlanta: aid to effective engineering controls and
American Society of Heating, Refrigerating and preventive strategies. American Journal of
Air-Conditioning Engineers, Inc. Infection Control 26: 453464.
ASHRAE. 1982. Climatic Data for Region X: ECS. 1998. EN 1886, Ventilation for Buildings
Arizona, California, Hawaii, Nevada, 5th ed. Air Handling Units Mechanical Performance.
Alhambra, Calif.: Golden Gate and Southern Brussels, Belgium: The European Committee
California Chapters, American Society of for Standardisation.
Heating, Refrigerating and Air-Conditioning ECS. 1992. EN 14449, Guidelines for Ventilation
Engineers, Inc. Requirements in Buildings (Report No. 11,
Bloodborne Pathogen Exposure Control Program. European Concerted Action, Indoor Air Quality
2000. University of Ohio, Athens. and Its Impact on Man). Prepared by Working

287
288 HVAC DESIGN MANUAL FOR HOSPITALS AND CLINICS

Group 6, Commission of the European Ninomura, P., and J. Bartley. 2001. New ventilation
Communities, The European Committee for guidelines for health-care facilities. ASHRAE
Standardisation, Brussels, Belgium. Journal 43(6): 29-30, 32-33.
EPRI. 1996. Advanced Motor Drive News (Fall). NIOSH. 1973. The Industrial EnvironmentIts
Palo Alto, Calif.: Electric Power Research Evaluation & Control. Washington, D.C.: U.S.
Institute. Department of Health and Human Services,
EPRI. 1992. Adjustable Speed Drives: Applications Public Health Service, Centers for Disease
Guide (TR-101140). Palo Alto, Calif.: Electric Control and Prevention, National Institute for
Power Research Institute. Occupational Safety and Health (DHHS
EPRI. 1991. Adjustable Speed Drives: Directory NIOSH Pub. No. 74-117).
(CU-7544, 3d ed.). Palo Alto, Calif.: Electric NIST. CONTAM software series. Gaithersburg, Md.:
Power Research Institute. National Institute of Standards and Technology.
Federal Standard 209-E, Clean Room Environment. NIST. 1999. Energy Price Indices and Discount
1988. Philadelphia: Naval Publications Center. Factors for Life-Cycle Cost AnalysisApril
First, M.W., et al. 1999. Guidelines for the 1999 (NISTIR 85-3273-14r; Rev. 4/99).
application of upper-room ultraviolet germicidal Gaithersburg, Md.: U.S. Department of
irradiation for preventing transmission of Commerce, Technology Administration,
airborne contagionPart I: Basic principles. National Institute of Standards and Technology.
ASHRAE Transactions 105(1): 869-876. PG&E. 1999. Chilled Water Plant Design and
Performance Specification Guide. San
Fryer, L. 1995. Tech Update: Electric Chiller
Francisco: Pacific Gas and Electric Company.
Buyers Guide (TU-95-1). Boulder, Colo.: E-
Santoso, S., et al. 2003. Electrical Power Systems
Source.
Quality (2d ed.). New York: McGraw-Hill.
Gershon, R.M., et al. 1993. TB Control in the
Smit, K., et al. 1996. Electric Chiller Handbook
Hospital Environment. Chicago: American
(EPRI TR-105951). Palo Alto, Calif.: Electric
Society for Hospital Engineering, Health-Care
Power Research Institute.
Facilities Management Series.
Stellman, J.M. (ed.). 1998. Encyclopaedia of
Gill, K. 1993. Hospital retrofit: Dual-duct HVAC
Occupational Health and Safety (4th ed.).
systems. Heating/Piping/Air Conditioning
Geneva: International Labour Office.
65(11).
Streifel, A.J., and J.W. Marshall. 1997. Parameters
Hambraeus, A. 1988. Aerobiology in the operating for ventilation controlled environments in
roomA review. Journal of Hospital Infection. hospitals. In Design, Construction, and
Klote, J.H., and J.A. Milke. 1992. Design of Smoke Operation of Healthy Buildings. Atlanta:
Management Systems. Atlanta: American American Society of Heating, Refrigerating and
Society of Heating, Refrigerating and Air- Air-Conditioning Engineers, Inc.
Conditioning Engineers, Inc. Boston, Mass.: Tamura, G.T. 1994. Smoke Movement and Control in
Society of Fire Protection Engineers. High-Rise Buildings. Quincy, Mass.: National
Lawson, C. N. 1993. Commissioning hospitals for Fire Protection Association.
compliance. ASHRAE Transactions 99(2): 1183- Theory and Rationale of Industrial Hygiene Practice.
1190. 1985. In Pattys Industrial Hygiene and
Lawson, C.N. 1989. CommissioningThe Toxicology: The Work Environment (Vol. 3A).
construction phase. ASHRAE Transactions New York: John Wiley & Sons.
95(1): 887-892. Trane. 1974. Trane Air Conditioning Manual. La
Marley. 1982. Cooling Tower Fundamentals. Crosse, Wisc.: The Trane Company.
Mission, Kans.: The Marley Cooling Tower University of Wisconsin, Department of Engineering
Company. Professional Development, Madison, Wisc.
NFPA. 1999. NFPA 90A, Standard for the [http://epdweb.engr.wisc.edu/].
Installation of Air-conditioning and Ventilating USDHS. 1992. Medical Management Guidelines for
Systems. Quincy, Mass.: National Fire Acute Chemical Exposures. Washington, D.C.:
Protection Association. U.S. Department of Human Services, Public
290 HVAC DESIGN MANUAL FOR HOSPITALS AND CLINICS

Health Service, Agency for Toxic Substance and


Disease Registry.
Waeckerle, J.F. 2000. Domestic preparedness for
events involving weapons of mass destruction.
Journal of the American Medical Association
283: 2.
Warden, D. 1996. Dual fan, dual duct systems.
ASHRAE Journal 38(1): 36-41.
Zamuner, N. 1986. Operating room environment
with turbulent air flow. ASHRAE Transactions
92(2A): 343-349.
INDEX 291

A air-handling 3-5, 31, 38, 40, 43, 48, 50-53, 59, 76, 85, 87-
97, 99, 101-103, 106, 112, 113, 117, 119, 125, 126,
abdominal endoscopic surgery 21 133, 138, 155-157, 165, 168, 174, 180, 181, 183, 186,
acoustical considerations 101 187, 189, 192, 242, 248, 253-260, 262
acute care hospital 11, 15, 37, 62, 241 air-handling system 3, 38, 48, 50-53, 59, 92, 94, 95, 101,
administrative area 21, 47 106, 117, 119, 133, 138, 165, 174, 180, 181, 183, 186,
187, 189, 192, 242, 248, 253, 255, 257, 258, 260
age of air 5, 7, 129
air-handling unit casing 85, 87, 90, 93
AIA 2, 4, 6, 11, 12, 32, 37, 38, 40, 47, 58, 88, 94, 96, 105,
air-to-air heat recovery strategies 187
107, 110, 131, 159, 181, 186, 189, 197, 201, 203, 205,
207, 237-239, 241-244, 246 all-air system 47, 48
air all-water system 47, 48, 54
exhaust 6, 9, 12, 30, 103, 104, 106-111, 113, 135, 145, ambulatory surgery center 143
187, 189, 214, 253, 254, 256-258, 260, 261 anteroom 7, 9, 16, 34, 37, 38, 109, 110, 134-136, 218, 219,
makeup 6, 10, 30, 37, 40, 110, 120, 121, 125, 133, 180, 238, 239, 240, 242, 244
186, 240 arthroscopy 21
outdoor 6, 7, 9, 11, 14, 33, 37, 39, 48, 51-53, 55, 63, asepsis 7, 37, 241
77, 107-109, 174, 180, 181, 186, 187, 189, 234- ASHRAE 1, 2, 4-11, 13, 14, 31, 32, 37-40, 47, 59, 61-66,
238, 240, 258 72-74, 76-79, 88, 89, 96, 97, 100-102, 104, 105, 108,
recirculated 6, 12, 87, 235 111, 124, 131, 132, 134, 135, 154, 159, 161, 181, 186,
supply 5, 6, 12, 13, 16, 38, 47, 51, 53, 54, 76, 77, 93, 188, 199, 213, 232, 234-241, 243, 244, 263
96, 98-101, 103, 107-109, 111-113, 120, 122, aspergillosis 7, 136, 197, 198
131, 133-135, 138, 139, 156, 168, 174, 181, 187,
199, 253-262 assisted living 16
transfer 6, 13, 141 atria 27, 115, 121, 126, 157
air and water induction units 53 autopsy 25, 29, 35, 58, 105, 107, 140, 182, 238, 239
air and water systems 47, 53
air balance 171, 201, 215
B
air change rate 4, 5, 14, 30, 40, 110, 145, 181, 183, 237, bioaerosol 1, 7
240, 241 bioterrorism 4, 203, 206, 207
air cleaning system 9 birthing room 7, 8, 247
air diffusion criteria 237 blood 19
air distribution pattern 133, 134, 136 blow-through 91, 95, 96, 157
air distribution system 42, 95, 98, 100, 108 boiler 40, 62, 71-76, 79, 80, 82, 84, 85, 88, 92, 150, 155,
air handling 6, 139 156, 165, 174, 192, 193, 195, 248
air irritant 6 boiler codes 75
air mixing 40, 41, 88, 89, 101, 134, 135, 138, 237 boiler controls 75
air movement 3, 27, 37, 97, 99, 100, 125, 127, 129, 134, bone marrow transplant 17, 28, 136, 159, 160, 198, 200
137, 219, 241, 244 bronchoscopy 13, 20, 33, 35, 38, 105, 107, 145, 238, 242
air pressure building air infiltration 7, 9, 10, 12
negative 16, 133, 134, 145 burn unit 137, 241
positive 16, 136 bypass terminal unit 99
air recirculated within room units 33, 239, 241
air volume migration 6, 134 C
airborne droplet nuclei 6 capital investment planning 160
airborne infection isolation room 6, 7, 9, 12, 34, 38, 105, carbon dioxide 61, 80, 81, 84, 171, 237
107, 238, 239, 242 cast room 137
airborne infectious agent 1, 6-8, 38, 241 central heating plant vs. distributed heating plant 193
airborne pathogen 6, 7, 30, 88, 131, 217 central sterile services 18, 23
airborne respiratory diseases 4 chemical fume hood 41
airborne transmission 1, 6, 29, 217 chilled water distribution system 67
air-conditioning general building supply 5 chiller 48, 57, 61-67, 69, 70, 72, 106, 110, 147-149, 155,
air-conditioning process 5, 61 174, 180, 189, 192, 195, 231, 248
air-conditioning system 5, 55, 132, 145, 232 chiller performance 65
air-cooled refrigerant condensers 66 chiller plant controls 69
airflow direction 38, 199, 242 clean steam 7, 74, 77
airflow monitor 94 climatic effects on building systems 127
292 HVAC DESIGN MANUAL FOR HOSPITALS AND CLINICS

clinical 19 cooling coil 29, 37, 43, 55, 61, 67, 68, 88-90, 94-96, 103,
clinics 1, 2-4, 14, 22, 39, 61, 70, 71, 79, 94, 97, 104, 111, 110, 112, 113, 130, 138, 139, 156, 157, 160, 174, 180,
112, 120, 143-147, 153, 155, 248, 250 189, 192, 240, 258
codes and standards 31, 39, 40, 42, 117, 120, 153, 233, 235, cooling generator 40
236 cooling plants 47, 55
Europe 234 for clinics 70
United States 234 cooling tower 29, 40, 62, 63, 65-68, 88, 154-156, 165, 174,
comfort 2-4, 9, 10, 27, 37, 40-43, 54, 61, 64, 76, 79, 87, 94, 175, 179, 180, 189, 192, 248
99, 100, 106, 129, 130, 144, 145, 171-173, 181, 233, corridor 7, 8, 17, 25, 34, 37, 87, 103, 107, 109, 110, 115,
235, 236, 239, 241, 244, 246 118, 123, 133-135, 138, 144, 153, 156, 182, 218, 219,
commissioning 2, 3, 40, 45, 57, 61, 70, 124, 157, 160-172, 241, 242
195, 201 patient 8, 34, 238, 239
construction process and commissioning interface 167 public 8, 34, 238, 239
costs, offsets, and benefits 170 corrosion 3, 66, 76, 77, 79-82, 84, 87, 92, 157
retro-commissioning 57, 168-170 corrosion control 81
special health care facility considerations 168 crisis room 13, 139
commissioning documentation 166 criteria 1, 2, 12, 31, 37-40, 42, 44, 47, 48, 69, 72, 78, 79, 88,
commissioning process 61, 70, 160-163, 195, 201 92, 93, 95, 96, 100, 101, 106, 107, 109, 120, 121, 124,
communicable disease 133, 208 133, 162, 163, 165, 166, 199, 213, 214, 234-237, 241,
244, 246, 247
communication 2, 4, 5, 19, 22, 39, 42-44, 49, 83, 106, 147,
153, 160, 161, 197, 200, 201, 203, 205-209, 235 best practice 237
community acquired infection 7, 10, 11 critical HVAC equipment 8
comparison of operating room ventilation systems 4, 263 CT scan 7, 140, 198
computational fluid dynamics (CFD) 237, 244-246 CT scanning 140
cystoscopy 8, 20, 140
concept design 43, 44, 87
constant volume 2, 38, 47-49, 51, 55, 56, 94, 95, 98, 99,
107, 109-111, 174, 180, 183, 185, 187, 193, 215, 242
D
contaminant 4, 5, 7-10, 12, 14, 27, 28, 30, 31, 40, 41, 45, 53, damper 52, 53, 95, 97-99, 102, 105-108, 111-113, 116-126,
54, 80, 87, 88, 98, 100, 129-131, 134, 136, 139, 151, 156-158, 169, 183, 187, 253, 255-258, 260-262
152, 171, 237, 244 fire 53, 117-119, 123, 157
airborne 2, 5, 7, 9, 10, 30, 131, 134, 237 location in fire-rated wall, floors, and ceilings 118
location in smoke barriers 119
contamination 3, 7, 8, 23, 29, 37, 40, 41, 43, 60, 78, 92, 98,
maintenance 118, 119, 157
99, 104, 132, 133, 137, 138, 151, 152, 158, 159, 189,
other considerations 119
203-205, 207, 208, 236, 241 smoke 97, 112, 113, 116, 118-120, 124, 126, 157, 254-
continuity of services 153 256, 258, 260, 261
control special requirements 118, 119
atrium smoke control 126 DDC 69, 70, 89, 106, 108, 109, 113, 186, 187, 251, 254,
DDC 109, 251, 255, 256, 258, 260, 262 255-258, 260, 261
electrical 150 dedicated equipment connection 8
electronic 106 delivery room 7, 8, 17, 18, 33, 131, 144, 207, 238, 239, 243,
fan speed 108, 253, 256, 257, 259, 261 247
HVAC&R 164, 165 desiccant system 48, 103
smoke 3, 14, 27, 112, 115-126, 157, 165, 204, 211,
design conditions 8, 27, 32, 39, 64, 65, 73, 89, 213, 242
260
smoke exhaust 112 design temperature 33, 39, 72, 93, 239, 243, 244, 248, 258
supply air temperature 112 diagnosis 8, 10, 12, 14, 15, 19, 132, 173, 218
variable speed 180, 189, 192 diagnostic and treatment 12, 17, 34, 35, 208, 238, 239
control method 105, 116 diagnostic clinic 8
control of microbes 4, 217 dialysis 8, 19, 140, 145, 200
control sequences 111, 121, 183 dietary department 23
controllers differential pressure 12, 30, 38, 69, 89, 94, 106, 107, 109,
specialized for isolation room 109 110, 113, 118, 136, 154, 187, 192, 193, 195, 241
controls diffuser types 3, 100, 129
humidity in operating room 47, 110 dilution ventilation 9, 30, 40, 135
laboratory 111 directional airflow 30, 31, 154
temperature in operating room 47, 110 disaster
controls and instrumentation 3, 69 biological 203, 205-207
INDEX 293

chemical 205-207 equipment


evacuation 205, 206 medical 8, 9, 25, 39, 42, 43, 168, 213, 214
isolation space 30, 41, 207 equipment heat gains 4, 144, 214
nuclear 205-207 equipment interface 44
trauma 203, 205, 206, 209
equipment load 39, 64, 133, 138, 213
disaster classification 204
equipment redundancy and service continuity 39
disaster management 4 esophagoscopy 20
diseases 4, 6, 9, 12, 15, 19, 28, 38, 63, 125, 133, 198, 205, evaporative condensers 66
207, 218, 240, 242
exam room 9, 13, 143, 144, 145, 182
domestic water pump 40, 158 exfiltration 6, 7, 9, 12, 37, 110, 134, 241, 242
domestic water systems 78 exhaust air 12
draw-through 91, 95, 96, 103, 157 exhaust of contaminants and odors 41
dual duct 48, 49, 51, 95 existing facilities 2, 38, 53, 57, 195, 241
dual-fuel boiler 75 exposure classifications 29
duct cleaning 97, 98, 158
duct static pressure safeties 113 F
ducts 5, 14, 41, 42, 51, 52, 57, 94, 95, 97-99, 111, 113, 117- facility 2, 129
119, 122, 124, 130, 158, 168, 187, 188, 254
facility descriptions 3
ductwork 42-45, 48, 55, 57, 76, 79, 85, 92, 93, 96-98, 101, fan coil unit 76, 102
102, 113, 116-121, 123, 126, 140, 145, 148, 157, 158,
167, 168, 183, 185, 188, 189, 193, 253, 256, 257, 259 fan tracking 111
fan-powered boxes 49
dust and debris control 59
fan-powered terminal unit 99, 160
DX
film processing area 141
see unitary
filter 5, 8, 9, 16, 17, 29-31, 37, 38, 40, 43, 48, 51-55, 59, 60,
79-81, 85, 88, 89, 91-94, 96, 103, 129-132, 136, 139,
E 140, 148, 153, 155, 157, 159, 160, 189, 198-200, 208,
211, 236, 237, 240-242, 249, 251, 255, 257, 258, 260,
economizer 32, 48, 49, 51-53, 55, 63, 76, 92, 93, 106-109,
262
112, 120, 169, 180, 183, 189, 192, 193, 254, 258, 260,
261 filtration 1, 2, 9, 30-32, 40, 41, 45, 47, 48, 51-53, 55-59, 79,
87, 94, 130-132, 137, 138, 144, 145, 154, 157, 159,
education department 22, 23 198, 199, 204, 209, 211
elevator 25, 63, 115, 116, 122, 123, 155, 157, 200, 205, financing 195
206, 208 fire alarm system 113, 116-120, 126, 154, 165
emergency 207 flexibility for future changes 43
emergency room 37, 139, 174, 181, 182, 204, 206, 207, flow diagram 164, 190, 191, 194
240, 242
freestanding birthing center 144
emergency treatment areas 4, 203 freestanding emergency clinic 9
emergency/trauma center 18, 139 freestanding emergency facility 144
endoscopy 8, 9, 20, 21, 33, 140, 145, 238, 239 freeze considerations 89, 90
endoscopy area 8, 182 freeze protection 40, 76, 88, 90, 112, 117, 156, 254, 256,
energy 258, 260, 261
electrical usage 175, 176 cooling coil 112
primary cooling energy 174, 180 fuel choices 64
thermal energy usage profile 177 fungi 6, 7, 10, 12, 29, 31, 97, 132, 198, 219
unoccupied period 181, 186, 187
energy conservation 2, 37, 49, 56, 73, 77, 110, 163, 170, G
171, 173, 189, 192, 193, 235, 241
galvanic corrosion 81
energy costs 67, 95, 147, 149, 179-181, 189, 231, 232
gastrointestinal 19, 20, 133
energy recovery 165, 188
energy wheel 104 H
engineered smoke control 27, 112, 119 hazard control 27, 30
engineered smoke evacuation 3, 115 health 10, 19, 27, 48, 88, 106, 121, 147, 168, 201, 205, 213
engineering and maintenance 24 health and life safety 125
environmental control 3, 25, 27, 28, 38, 41, 49, 129, 233, health care facility 1, 19, 28-30, 32, 92, 94, 95, 97, 98, 101,
241 153, 154, 155, 158, 170, 173, 174, 180, 181, 186, 192,
epidemiology 6, 9, 58 195, 214, 215
294 HVAC DESIGN MANUAL FOR HOSPITALS AND CLINICS

heat recovery 4, 32, 37, 48, 54, 75, 110, 145, 187-189, 240, integrated design 43
253, 255, 257 intensive care
heat rejection device 61, 62 neonatal 11, 16, 17, 101, 137
heating 1, 3-6, 13, 24, 32, 37, 38, 40, 47, 48, 51, 52, 54, 55, intensive care room 10
61, 71-78, 80, 81, 85, 89, 90, 95, 96, 98-101, 104, 105,
108, 112, 130, 131, 133, 136-138, 156, 161, 165, 174, Interim 153
179-181, 186, 188, 189, 192, 193, 199, 205, 213- 215, invasive procedure 10-13, 29, 60, 130, 146
232, 234, 240-242, 246-248, 253, 256-258, 262 isolation 6
process heating system 3 isolation room 6, 7, 9, 12, 16, 34, 37-39, 41, 94, 99, 105,
heating and cooling coils 89 107, 109, 110, 130, 133-135, 145, 153, 154, 159, 164,
heating plant 72, 73, 192 189, 218, 238-243, 247
hematology 9, 10, 19, 136, 141
HEPA 16 J
HEPA filter 5, 9, 17, 31, 37, 38, 136, 140, 159, 199, 200, JCAHO compliance 153
240-242
first response 155
high-purity water aggressiveness 80 interim life safety 154, 197
hospital (institution) 1-7, 9-13, 15, 17-25, 28, 32, 41, 47, 48, pressure monitoring systems for isolation rooms 154
53, 57, 58, 61, 62, 71-75, 77-79, 88, 94, 97, 98, 105- prevention of Legionnaires disease 154
112, 115-117, 120, 125-127, 131, 132, 137, 139, 140, resolution of indoor air quality problems 154
143-147, 149, 153, 158, 159, 164, 173-177, 179, 183, statement of conditions 153
189, 192, 197, 200, 201, 203-211, 234, 237, 239, 240,
utilities management 154
241, 243, 247, 248, 250
hospital additional equipment
on emergency power 248 L
hospital systems on emergency power 247 laboratory 8-10, 19, 20, 28, 31, 34, 35, 49, 57, 78, 79, 84,
hot water 4, 40, 48, 49, 53-55, 71, 72, 74, 76-78, 89, 90, 98, 88, 91, 92, 111, 116, 145, 153, 174, 181, 198, 208,
153, 189, 192-194, 209, 211, 248, 253, 255, 259 238, 245-247
hot water demand 78, 79 acute care (emergency laboratory) 19
humidifier 29, 43, 71, 74, 79, 82, 85, 88, 92, 93, 96, 97, 103, biosafety 31, 111
111, 131, 138, 141, 254-258, 260- 262 blood transfusion 19
HVAC 1-5, 8, 9, 27-32, 37- 40, 42-45, 47, 48, 57, 58, 65, chemistry 19
66, 74, 78, 79, 87-89, 97, 102, 104, 105, 111, 115-117, clinical immunology 19
119, 122, 123, 133, 134, 138, 139, 143, 148, 149, 155- hematology 19
159, 162-164, 165, 171, 172, 174, 181, 195, 215, 217, microbiology 19
219, 231-233, 235, 239, 240, 241, 243, 247 special clotting section 19
HVAC systems 1-3, 13, 27, 32, 44, 47, 48, 57, 58, 76, 77, tissue typing 19
94, 100, 104, 112, 121, 139, 159, 160, 172, 174, 180, laboratory hoods 111, 198
181, 188, 195, 247
layout 3, 44, 48, 54, 71, 115, 125, 129, 155, 158
hydronic heat exchangers 72, 74, 76
LDR 7
I LDRP 7, 34, 238, 239
life safety 2, 3, 27, 28, 58, 115-117, 120, 122, 124, 125,
imaging 10, 12, 18, 19, 139 127, 143, 146, 153, 154, 161, 163, 181, 197, 203
immunocompromised host 9, 11, 12 life safety approach 115
immunocompromised infectious host 7, 9 life-cycle cost analysis 4, 32, 63, 64, 67, 95, 213, 231, 232
indoor air quality 2, 5, 6, 9, 37, 40, 47, 57, 154, 171, 172, lighting 3, 11, 21, 24, 64, 88, 106, 129, 163, 165, 174, 175,
173, 186, 236, 237, 240, 241 179, 180, 213, 214, 233
induction unit 48, 53, 109, 241 linen services 24
industrial hygiene 8, 10 load
infection control 2-4, 6, 12, 27-30, 37, 41, 45, 54, 55, 58, diversity factor 214
59, 105, 116, 125, 129, 133, 136, 144, 153, 155, 159,
lighting 129, 213
172, 173, 197-201, 206, 217, 218, 240, 241
medical equipment 39, 213
infection control issues 4 occupancy 213
infection control monitoring checklist 200 ventilation 214
infection control risk assessment (ICRA) 58, 60 load calculations 4, 39, 64, 213, 215
infiltration 6, 7, 9, 10, 12, 37, 59, 64, 110, 134, 137, 163, local exhaust 10, 14, 25, 37, 139, 241
241, 242
local ventilation exhaust 7, 10
installation 2, 3, 43, 45, 70, 75, 77, 78, 87, 90, 93, 97, 102,
108, 117-120, 124, 129, 133, 157, 163, 165, 168, 171, location of outside air intakes 40, 41
188, 189, 195, 196, 236, 247, 251 lower gastrointestinal 20
INDEX 295

M morgue 25, 140, 198


MRI 10, 49, 139, 140, 145, 181
machine room design 62
multiple parallel chiller 68
magnetic resonance imaging 10, 12
multiple series chiller 68
main lobby 22 multizone 48, 49, 52, 94, 95, 180, 183, 185, 187
maintenance 1-4, 15, 23-25, 28, 29, 32, 38, 39, 42-45, 47- mycosis 10
49, 52-58, 62-64, 66, 69, 71-73, 76-80, 82-85, 87-93,
95, 97, 102, 106, 108, 109, 112, 118-120, 122, 125,
129, 132, 133, 147-150, 153-160, 163-166, 169-174, N
181, 182, 187, 195, 197, 198, 199, 203, 231, 232, 235, nephroscopic 20
241, 242, 258
noise 3, 27, 42-44, 53, 54, 62, 77, 87, 91-93, 97, 101, 102,
construction plan review 155 152, 157, 197, 201, 249, 251
balancing features 156
noncommunicable diseases 6
central station air-handling units 157
chemical treatment 156 nosocomial infection 4, 7, 10, 11, 29, 42, 97, 98, 205
chillers and boilers 155 nosocomial infection costs 217
cooling coils 156 nursing
cooling towers 156 24-hour care 10, 11
domestic water pumps 158 acute medical/surgical patients 10
duct cleaning when existing ducts are used 158 critical patients 11, 13
ductwork design considerations 157 specialty care patients 11
emergency generators 158 nursing station 12, 133, 145
emergency recovery plan 158
nursing unit
filter replacement 159
fire dampers 157 psychiatric 137
fire protection systems 158
freeze protection features 156 O
general personnel access 156
obstetrical suite 18
mechanical room layout 155, 158
outside air intakes 158 occupancy patterns 182, 215
pumps 158 occupationally acquired infection 7, 10, 11
redundancy 158 occupiable space 11
roof-mounted equipment 155 operating 242
separate energy plants 156 operating cost 3, 32, 138, 147, 195, 231-233, 246
smoke dampers and smoke control dampers 157
stainless steel drain pans 156 operating room 1, 4, 8-13, 18, 21, 31, 33, 37, 44, 47, 94, 99,
valves 159 110, 111, 120, 125, 137, 138, 143, 144, 160, 166, 167,
182, 201, 207, 236-238, 240-243, 247, 255, 263
water heaters 158
fan-coil units 160 cardiac transplant 11
fan-powered terminal units 160 neurosurgery 11
predictive 148, 149 operating room air 4, 138
proactive 149 operating room ventilation 4, 243, 263
reactive 147 operation and maintenance 2, 3, 62, 64, 73, 79, 91, 147,
secondary air systems 160 163, 171
maintenance tools ophthalmology and optometry 145
dynamic balancing 152 opportunistic microorganism 11, 198
motor current analysis 148, 151 orthopedic 16, 17, 94, 139, 159, 160, 166, 218, 237
oil analysis 148, 151
outdoor air intake 63
refrigerant analysis 148, 152
shaft alignment 152 outpatient facilities 24
vibrational analysis 148, 149, 151 outpatient facility 15, 73, 153
materials management 23, 24, 140 outpatient surgery suite 21
medical gas 8, 10, 44, 144, 164, 165, 168, 203, 205, 209 outpatient surgical facility 11, 143
minimum 187 outside air economizer controls 106, 107
minimum air changes of outdoor air 33, 238 outside air quality 40
minimum total air changes per hour 33, 37, 238, 240 outside design conditions 39
minor operating room 10, 11 oxidation 80, 151
minor surgery 10
modes of transmission
P
direct contact and airborne 28 packaged rooftop 55, 62, 104
moisture carryover 89, 90, 96 packaged single-zone split system 55
296 HVAC DESIGN MANUAL FOR HOSPITALS AND CLINICS

packaged terminal air conditioners 48, 55 repair work 3


particle required services in emergency and disaster 207
infectious 6, 29, 129, 130, 198 power 205, 207- 209
patient sterilization 205, 207-209, 211
inpatient care unit 133 transportation 205, 206, 208, 209
ventilation 203-209, 211
patient care areas 45, 47, 49, 54, 94, 132, 199, 241, 248
water 203-205, 207-209
patient care units 11, 16
retrofit 45, 173, 174, 180, 181, 183, 187-190, 192, 195
patient privacy 42, 102
return fan 92, 94, 107, 108, 122, 254, 258, 260, 261
patient rooms 8, 10, 12, 37, 38, 45, 53, 76, 112, 115, 130,
risk 3, 4, 7, 8, 12, 17, 28, 31, 42, 45, 58-60, 64, 75, 92, 98,
133, 167, 182, 189, 240, 242, 247, 248
99, 111, 126, 127, 131, 133, 137, 139, 150, 151, 153,
pharmacy 9, 24, 35, 141, 144, 145, 166, 181, 209, 210, 211, 154, 155, 158, 166, 195, 197-201, 237, 248
238, 239
risk assessment 12, 58, 60, 155, 197, 199-201, 248
physical therapy 17, 35, 137, 238, 239
room air distribution 4, 12, 14, 95, 98-100, 136
piping 43-45, 48, 53, 54, 55, 57, 60-62, 66-68, 76-78, 80-
82, 84, 87, 89, 95, 97, 117, 140, 145, 156, 158, 163, room air distribution effectiveness 12, 14
164, 168, 187, 189, 193, 248 room air exchange 38, 199, 242
piping system 48, 53, 54, 67, 76, 77, 80-82, 84, 95, 156, room design 3, 38, 47, 62, 100, 242
158, 168, 187, 189, 193
plant and equipment rooms 43, 44 S
plant configuration 73 sample control strategies 4, 181
plant redundancy 72, 73 sealed room 7, 9, 12
plenums 40, 48, 97, 98 second filter bank 94
pneumonia 12, 132 sensor location 106, 112
pollutant 7, 8, 10, 12, 236 sequence of operation of 100% outside air-handling unit
pollution 7, 9, 10, 12, 59, 236, 237 with exhaust fan and hot water run-around loop heat
power quality issues 4 recovery system
prefiltration 89 start-up mode 255
preheating coil 89 sequence of operation of 100% outside air-handling unit
pressure relationship to adjacent areas 33 with face an bypass and exhaust fan 257
pressurization 1, 6, 12, 14, 27, 30, 32, 37, 45, 47, 48, 52, 53, sequence of operation of 100% outside air-handling unit with
56, 94, 95, 106-110, 112, 115, 117, 122-125, 127, 136, two supply fans, a common exhaust fan, and a hot water
139, 163, 164, 181, 183, 186, 199, 205, 207, 211, 237 run-around loop heat recovery system 253
pressurization criteria 106, 107 sequence of operation of air-handling unit with return air
primary care outpatient center 15, 143 fan and air-side economizer 258
procedure 7-13, 15, 16, 18-21, 23, 27, 29, 33, 38, 58-60, 72, sequence of operation of hot deck and cold deck air-han-
78, 98, 116, 121, 126, 130, 137, 139, 140, 143-146, dling unit with return air fan and air-side economizer
152-154, 163-165, 171, 187, 195, 197, 198, 201, 205- (dehumidification and cooling of all supply air with
208, 213, 236- 239, 241, 242, 245 reheat for hot stream) 260
procedures 232 service continuity 39
process cooling 3, 12, 129, 144, 145, 165 single chiller 67
protective environment rooms 12, 17, 37, 136 siting the central plant 62
sizing 32, 39, 40, 48, 49, 52, 63, 67, 71, 78, 93, 96, 215
R skilled nursing facility 13
skin squame 13
radiant panel system 54
small primary outpatient facility 15
radiology 9, 12, 20, 22, 33, 34, 139-141, 143-145, 153, 166,
174, 181, 182, 186, 198, 238, 239 smoke compartment 115, 117, 119, 120, 124
radiology room 12 smoke control
recovery 4, 7, 11, 17, 18, 21, 32-34, 37, 38, 48, 54, 74, 75, active 115, 116, 117, 120, 121, 123
110, 136, 138, 143-146, 158, 159, 165, 173, 174, 181, energy management 124
182, 187-189, 215, 232, 238-240, 242, 243, 247, 253, passive 120, 121
255, 257 testing and commissioning 124
relative 111 smoke control mode of operation 120, 121
relative humidity 5, 9, 27, 30-33, 37, 39, 41, 85, 92-94, 96, smoke control zones 121
100, 103, 159, 237, 239, 243, 244, 254, 257, 259, 261 smoke management 3, 119, 124, 157, 165
renal dialysis 19, 140 smoke spread 115, 116, 123, 126
renovation 3, 4, 45, 53, 58, 59, 153-155, 160, 171, 197, 198, smoke systems
201 dedicated versus nondedicated 120
INDEX 297

soiled utility 133, 141, 144 trash and compactor area 25


solid organ transplant 19, 139, 198 trauma room 13, 33, 37, 137, 139, 144, 238, 239, 242, 243,
sources of infectious organisms 28 247
space temperature 31, 37, 48, 49, 51, 53, 56, 99, 100, 110, treatment 3, 4, 5, 8, 10-19, 22, 25, 27-31, 34, 35, 37, 66, 79-
186, 187, 237, 243 85, 88, 100, 111, 132, 140, 145, 154, 156, 173, 186,
special exhaust connections 41 187, 197, 198, 203-210, 219, 236, 240, 242
stairwell pressurization 122, 125 treatment chemicals (corrosion) 3, 79, 80-85
steam 7, 8, 13, 24, 40, 44, 48, 49, 53-55, 64, 71, 73, 74-85, treatment clinic 9, 13, 144
88-90, 92, 93, 98, 111, 138, 140, 156, 174, 192, 193, treatment room 9, 13, 18, 20, 33, 35, 38, 144, 146, 181, 238,
205, 248, 255, 257, 258, 260, 262 239, 242, 243
steam autoclave 7, 13 triage 13, 18, 33, 205, 207- 211, 238, 239
steam classifications 79 triage space 206
steam for humidification 3, 7, 85 trunk ducts 41
steam for sterilization 80, 84, 85
steam generation 40, 71, 81, 85, 208 U
steam system 71, 77, 80, 82, 84, 192, 193 unitary (DX) 48
steam trap 77 unitary refrigerant-based systems for air conditioning 55
steam turbine generator 193 unoccupied period 186
step-down units 11, 13, 16 unplanned service interruptions 45
sterile 7, 9, 13, 18, 20, 21, 23, 29, 36, 41, 49, 85, 92, 125, upper gastrointestinal 20
132, 133, 136, 139, 140, 143, 144, 165, 166, 182, 238, ureteroscopic 20
239
UV 14, 31, 204, 217
sterile field 13, 138, 139
UVGI 14, 31, 130
sterilization and humidification 71, 79, 82, 83
subacute care units 17 V
supply 4-6, 8, 12, 13, 17, 24, 30, 31, 36-38, 40, 43, 49, 51,
53-56, 59, 62, 68, 70, 73, 76, 77, 79, 80, 82, 84, 85, 87, variable air volume 37, 47, 48, 51-53, 55, 56, 94, 101, 107-
91-101, 103, 106-113, 119, 122-124, 126, 127, 131, 111, 116, 180, 181, 183, 185, 241
133-135, 137-140, 145, 146, 154, 156, 157, 159, 165, variable air volume induction units 109
166, 174, 182, 183, 188, 189, 192, 199, 203, 205-207, variable flow system 68, 69
215, 237-242, 247-250, 253-258, 260-262
variable frequency drives 248, 249
supply fan 4, 55, 56, 91, 92, 96, 107-109, 111, 113, 122,
123, 183, 253-258, 260, 261 variable speed pumping 180, 193
supply outlet performance 100 VAV 47-49, 55, 56, 93-95, 99-102, 105, 107, 110, 111,
123, 124, 180, 181, 183, 186, 187
support services 21, 23, 144
ventilation 2-10, 12-14, 16, 24, 30-32, 37-41, 47, 48, 51-56,
surgery 58, 59, 61, 62, 64, 75, 87, 94, 96, 98, 100, 106-109,
cardiac 110, 138 126, 129-135, 137, 139, 140, 143-145, 156, 158, 160,
eye 138 165, 171, 173, 175, 179-181, 183, 186, 187, 197-199,
laser 9, 139 201, 203-209, 211, 214, 218, 219, 233-237, 240-244,
neurosurgery 11 246, 247, 263
surgical site 4, 132, 138, 139, 263 ventilation control 7, 55, 59, 129, 197, 199, 236
surgical site infection 132 ventilation design 3, 8, 16, 40, 129, 130, 133, 135, 246
surgical suite 17, 18, 137, 140, 141, 143, 237 ventilation effectiveness 6, 10, 12, 14, 47, 100, 130, 135,
surgicenter 146 186
swing beds 13 ventilation efficiency 7, 10, 14
system steam pressure requirements 74 ventilation rate 4, 11, 14, 37, 64, 95, 129, 130, 181, 186,
235-237, 240, 241, 243, 246
T ventilation standards 4, 37, 145, 235, 237, 240
vertical fire spread 126
terminal heating equipment 76
VFR pressurization 107
terminal reheat 48-51, 95
terminology 2, 5
W
terrorism 203, 204, 207, 209, 210
thermal surgical plume 13 waiting rooms 5, 33, 35, 206, 213, 217, 238, 239
total air changes 33, 37, 38, 187, 240, 242 waiting spaces 22
training 2, 3, 22, 60, 73, 147, 158, 161, 163-165, 171, 172, wash area (decontamination) 206
218, 245 waste anesthetic gas 14, 37, 236, 241
298 HVAC DESIGN MANUAL FOR HOSPITALS AND CLINICS

waste isolation 206, 209 X


water activity 14
X-ray 13, 20, 21, 28, 34, 41, 145, 181, 182, 207-211, 214,
water delivery temperature 79
238, 239
water heater features 78
worker protection 60
Table F-1. Comparison of Engineering Best Practice with AIA Guidelines* and ASHRAE Handbook**
(For table notes see pages 240-244 of Appendix F.)
Presssure Relationship to Adjacent Minimum Air Changes of Outdoor Air Minimum Total Air Changes per All Air Exhausted Directly to Air Recirculated Within Room
Areas (a) (2) per Hour (b) (3) Hour (c) (4) (5) Outdoors (6) Units (d) (7) Relative Humidity (8) (%) Design Temperature (9) (F/C) Proposed
Function Space Manual Handbook AIA (1) Manual Handbook AIA (1) Manual Handbook AIA (1) Manual Handbook AIA (1) Manual Handbook AIA (1) Manual Handbook AIA (1) Manual Handbook AIA (1) Comments
Surgery And Critical Care
Operating Room (all outdoor air system) P 15 15 Yes No 45-55 62-80
Operating Room (recirculating air system) P P 5 5 25 25 Optional No No 30-60 68-75 A1
Operating/surgical cystoscopic rooms (10), 11) P Out 5 3 25 15 No No 30-60 30-60 68-75 68-73 (20-23) (12) A1
Delivery Room (all outdoor air system) P 15 15 Optional No 45-55 62-80
Delivery Room (recirculating air system) P 5 25 Optional No
Delivery Room (10) P Out 5 3 25 15 No No 30-60 30-60 68-75 68-73 (20-23) B1
Recovery Room E 2 2 2 6 6 6 Optional No No No 30-60 45-55 30-60 70-75 75 70-75 (21-24) C1
Critical and Intensive Care 2 2 6 6 No No 30-60 30-60 70-75 70-75 (21-24) C2
Newborn Intensive Care 2 2 6 6 No No 30-60 30-60 72-78 72-78 (22-26) C2
Treatment Room (13) 6 6 30-60 70-75 75 (24) C2
Nursery Suite P P 5 5 12 12 Optional No No 30-60 30-60 75-80 75-80 D1
Trauma Room (f) (13) P Out 5 3 12 12 15 Optional No No 45-55 30-60 62-80 70-75 (21-24)
Trauma Room (crisis or shock) (f) (13a) P 3 15 Yes Yes 30-60 70-75 B2
Trauma Room (conventional ED or treatment) (f) (13a) P 2 6 No 30-60 70-75 B2
Anesthesia Storage (see code requirements) Optional 8 Yes No
Anesthesia Gas Storage N In 8 8 Yes Yes C3
Endoscopy (11) N In 2 2 6 6 No No 30-60 30-60 68-73 68-73 (20-23) C2
Bronchoscopy N In 2 2 12 12 Yes Yes No No 30-60 30-60 68-73 68-73 (20-23) C2
Yes (14),
ER Waiting Rooms N In 2 2 12 12 Yes (15) 30-60 70-75 70-75 (21-24) C2
Triage N In 2 2 12 12 Yes Yes (14) 70-75 70-75 (21-24) C2
Yes (14),
Radiology Waiting Rooms N In 2 2 12 12 Yes (15) 70-75 70-75 (21-24) C2
Class A Operating (procedure) Room N Out 3 3 15 15 No No 30-60 30-60 70-75 70-75 (21-24) A4
Nursing
Patient Room 2 2 2 6 4 6 (16) Optional Optional 30-60 30 (winter), 50 (summer) 70-75 75 70-75 (21-24) B3
Toilet Room (g) N N ln Optional Optional 10 10 10 Yes Yes Yes No No C3
Intensive Care P 2 6 Optional No 30-60 75-80
Newborn Nursery Suite 2 2 6 6 No No 30-60 30-60 72-78 72-78 (22-26) C2
Protective Isolation (i) P 2 15 Yes Optional
Infectious Isolation (h) 2 6 Yes No 30 (winter), 50 (summer) 75
Protective Environment Room (11), (17) P Out 2 2 12 12 No No 70-75 75 (24) C2
Airborne Infection Isolation Room (11), (18) N In 2 2 12 12 Yes Yes (15) No No 70-75 75 (24) C2
Isolation Alcove or Anteroom (17), (18) P/N In/Out 2 2 10 10 10 Yes Yes Yes No No No D1
Labor/Delivery/Recovery 2 6 (16) 70-75 (21-24)
Labor/Delivery/Recovery/Postpartum 2 6 (16) 70-75 (21-24)
Labor/Delivery/Recovery/Postpartum (LDRP) (16) E 2 2 6 4 Optional Optional 30-60 30 (winter), 50 (summer) 70-75 75 A2
Patient Corridor E 2 2 4 4 2 Optional Optional D2
Public Corridor N 2 2
Ancilliary
Radiology (19) x-ray (sugery and critical care) P 3 15 Optional No
Radiology (19) x-ray (diagnostic and treatment) 2 2 6 6 6 Optional Optional 30-60 40-50 72-78 78-80 75 (24) D2
Radiology (19) x-ray (surgery/critical care and catherization) P Out 3 3 15 15 No No 30-60 30-60 70-75 70-75 (21-24) C2
Radiology (19) Darkroom N N In 2 2 10 10 10 Yes Yes (j) Yes No No No D2
Laboratory, general (19) N N 2 2 6 6 6 Yes Yes No No 30-60 Comfort Range 70-75 Comfort Range 75 (24) D2
Laboratory, bacteriology N N 2 2 6 6 Yes Yes No No 30-60 Comfort Range 70-75 Comfort Range D2
Laboratory, biochemistry (19) P P Out 2 2 6 6 6 Optional Optional No No No 30-60 Comfort Range 70-75 Comfort Range 75 (24) D2
Laboratory, cytology N N In 2 2 6 6 6 Yes Yes Yes No No No 30-60 Comfort Range 70-75 Comfort Range 75 (24) D3
Laboratory, glasswashing N N In Optional Optional 10 10 10 Yes Yes Yes Optional Comfort Range Comfort Range D3
Laboratory, histology N N In 2 2 6 6 6 Yes Yes Yes No No No 30-60 Comfort Range 70-75 Comfort Range 75 (24) C3
Microbiology (19) N In 6 6 Yes Yes No No 30-60 70-75 75 (24) C4
Laboratory, nuclear medicine N N In 2 2 6 6 6 Yes Yes Yes No No No 30-60 Comfort Range 70-75 75 (24) C5
Laboratory, pathology N N In 2 2 6 6 6 Yes Yes Yes No No No 30-60 Comfort Range 70-75 75 (24) C4
Laboratory, serology P P Out 2 2 6 6 6 Yes Optional No No No 30-60 Comfort Range 70-75 75 (24) C4
Laboratory, sterilizing N N In Optional Optional 10 10 10 Yes Yes Yes No No 30-60 Comfort Range 70-75 C4
Laboratory, media transfer P P 2 2 4 4 Optional Optional No No 30-60 Comfort Range 70-75 D2
Autopsy N 2 12 Yes No
Autopsy Room (11) N In 2 12 12 Yes Yes No No C4
Nonrefrigerated Body-Holding Room (k) N N In Optional Optional 10 10 10 Yes Yes Yes No No 70 70 (21) C3
Pharmacy P P Out 2 2 4 4 4 Optional Optional 30-60 70-75 C4
Administration
Admiting and Waiting Rooms N N 2 2 6 6 Yes Yes Optional 30-60 70-75 D4
Diagnostic And Treatment
Bronchoscopy, sputum collection, and pentamidine administration N N 2 2 12 10 Yes Yes Optional 30-60 70-75 D4
Examination Room 2 2 6 6 6 Optional Optional 30-60 70-75 75 (24) C4
Medication Room P P Out 2 2 4 4 4 Optional Optional 30-60 70-75 C4
Treatment Room 2 2 6 6 6 Optional Optional 30-60 30 (winter), 50 (summer) 70-75 75 75 (24) C6
Physical Therapy and Hydrotherapy N N In 2 2 6 6 6 Optional Optional 30-60 Comfort Range 72-80 Comfort Range/up to 80 75 (24) C4
Soiled Workroom or Soiled Holding N N In 2 2 10 10 10 Yes Yes Yes No No No 30-60 Comfort Range 72-78 Comfort Range D3
Clean Workroom or Clean Holding P P Out 2 2 4 4 4 Optional Optional C3
Sterilizing And Supply
ETO-Sterilzer Room N In 10 10 Yes Yes No No 30-60 75 (24) C5
Sterilzer Equipment Room N N In Optional 10 10 10 Yes Yes Yes No No C4
Central Medical and Surgical Supply
Soiled or Decontamination Room N N In 2 2 6 6 6 Yes Yes Yes No No No 30-60 Comfort Range 72-78 Comfort Range 68-73 (20-23) D5
Clean Workroom P Out 2 4 4 No No 30-60 30-60 72-78 75 (24) D8
Sterile Storage P Out 2 4 4 30-60 (Max) 70 72-78 D7
Clean Workroom and Sterile Storage P 2 4 Optional Optional Under 50 Comfort Range
Equipment Storage 2 (Optional) 2 Optional Optional
Service
Food Preparation Center (I) (20) 2 2 10 10 10 Yes Yes No No No C3
Warewashing N N In Optional Optional 10 10 10 Yes Yes Yes No No No C3
Dietary Day Storage In Optional Optional 2 2 2 Optional No No C7
Laundry, general N N 2 2 10 10 10 Yes Yes Yes No No D3
Soiled Linen Sorting and Storage N N In Optional Optional 10 10 10 Yes Yes Yes No No No C3
Clean Linen Storage P P Out 2 (Optional) 2 (Optional) 2 2 2 Optional Optional C3
Linen and Trash Chute Room N N Optional Optional 10 10 Yes Yes No No C2
Soiled Linen and Trash Chute Room In 10 Yes No D2
Bedpan Room N N In Optional Optional 10 10 10 Yes Yes Yes No No C3
Bathroom N N In Optional Optional 10 10 10 Yes Optional* No No 72-78 75 (24) C8
Janitors Closet N N In Optional Optional 10 10 10 Yes Optional Yes No No No D3
* AIA GuidelinesGuidelines for Design and Construction of Hospital and Health Care Facilities, Chapter 7, Table 7.2, American Institute of Architechts Academy, 2001.
** ASHRAE Handbook1999 ASHRAE HandbookHVAC Applications, Chapter 7, Table 3.

You might also like