Transfer SwitchesMedium Voltage 12.

0-1
October 2015
Sheet 12001

Medium Voltage
Contents
Transfer Switches Transfer SwitchesMedium Voltage
Medium Voltage Vacuum Breaker Transfer Switches
i

ii
General Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12.0-2
Automatic Transfer Control (ATC). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12.0-4 1
Protection and Metering . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12.0-5
Auxiliary Equipment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12.0-5
Available Ratings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12.0-7
2
Technical Data. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12.0-8
Layout DimensionsStandard Metal-Clad . . . . . . . . . . . . . . . . . . . . . . . . 12.0-11 3
Layout DimensionsArc-Resistant Metal-Clad. . . . . . . . . . . . . . . . . . . . . 12.0-15
Specifications 4
See Eatons Product Specification Guide, available on CD or on the Web.
CSI Format: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1995 2010 5
Medium Voltage Vacuum Breaker
Transfer Switches . . . . . . . . . . . . . . . . . . Section 16495 Section 26 36 23.21
6

10

11

12

13

14

15

16

17

18

19

20
Medium Voltage Transfer Switch
Conforming to UL 1008A
21

CA08104001E For more information, visit: www.eaton.com/consultants


12.0-2 Transfer SwitchesMedium Voltage
Vacuum Breaker Transfer Switch (VCP-W-ATC) October 2015
Sheet 12 002
General Description

i Reliability and Control with Metal-Clad Standard Control Features


Vacuum Technology and The metal-clad switchgear with MV ATS control is provided by Eatons
drawout vacuum circuit breakers used ATC-900 automatic transfer controller.
ii Microprocessor-Based Logic for medium voltage transfer switch is Some of the standard features of
designed, manufactured and tested in ATC-900 are as follows. Refer to
accordance with the latest applicable Eatons Technical Data TD140001EN for
1 standards of: complete details of ATC-900
features and capabilities.
UL 1008A dated March 2012
standard for medium voltage Lights:
2 transfer switches Normal position
IEEE C37.20.2 dated 1999 Emergency position
3 standard for metal-clad switchgear
Normal source available
ANSI C37.55 dated 2002
conformance test procedures Emergency source available
4 NEMA SG-5power switchgear Undervoltage/overvoltage,
assemblies underfrequency/overfrequency
CSA C22.2 No. 31-04 dated sensing on Source 1
5 January 2004CSA standard for Undervoltage/overvoltage,
switchgear assemblies underfrequency/overfrequency
ANSI and IEEE standards for high sensing on Source 2
6 voltage AC circuit breakers Timers:
IEEE C37.04-1999, ANSI C37.06-2000 Time Delay Normal to Emergency
and 2009, and IEEE C37.09-1979
7 and 2009
Time Delay Emergency to Normal
Time Delay Engine Start
Medium Voltage Vacuum Available as an optionType 2B
Time Delay Engine cool-off
8 Breaker Transfer Switch arc-resistant design conforming to
IEEE C37.20.7 dated 2007, guide for Time Delay Emergency Failure
Eatons Electrical Sector is an innovator
testing metal-enclosed switchgear Time Delay Neutral
of low and medium voltage manual
9 transfer switches and has expanded
for internal arcing faults
Time Delay pre- and/or
these capabilities into medium voltage The MV ATS style is perfect for any post-transfer
automatic transfer switches (MV ATS) emergency or backup system and
10 conforming to UL 1008A that combine suitable for service entrance use. It Programmable engine test mode
proven vacuum technology and micro- provides reliable automatic transfer and test run timer
processor-based logic. to standby power when: Source 1 availableone Form C
11 contact
Why Use Vacuum Circuit Breakers The normal power source fails
Source 2 availableone Form C
Peak shaving is used
12 Instead of Load Interrupter contact
The power source is unreliable Communication via Modbus RTU,
Switches for Automatic Transfer?
Backup power is mandated by code USB (for flash drives), Modbus
Vacuum circuit breakers are suitable
13 for multiple switching (500010,000
or local regulations TCP/IP (optional)
Eaton manufactures all MV ATS basic Real-time clock and date
or even more) operations between
sources involved in automatic components and provides one year full Phase reversal on Source 2
14 transfer system. Duty cycle of load warranty, eliminating problems that Phase reversal on Source 1
interrupter switch is limited (5 to 50 can arise with multiple warranties for a Go to Emergency feature
operations) by IEEE C37.20.4 single piece of equipment. Assembly
15 and manufacturing is completed in
Preferred source selector for use on
Vacuum circuit breakers are rated for systems comprised of utility/utility
both load current switching as well ISO certified facilities.
or utility/generator
16 as interrupting fault currents, where
Seismic Qualified Overcurrent lockout feature
as the load interrupter switches are
Plant Exerciser with fail-safe feature
rated for load current switching only Eatons medium voltage circuit
17 breaker transfer switch assemblies Automatic or manual
Vacuum circuit breakers allow use of
various relay schemes (for example, are seismically tested or qualified by pushbutton re-transfer selection
phase and ground overcurrent, analysis based on actual testing done PT ratio set points
18 under and overvoltage, under and on similar equipment, to exceed the Closed Transition with Default to
overfrequency, directional overcur- requirements based upon 2009 IBC In-Phase Transition with Default to
rent, directional power, differential, parameters and CBC 2010. Time Delay Neutral (for closed
19 etc.) for protection and coordination transition switches only)
as desired for a given application.
Relaying schemes are either not
20 possible or very limited when using
load interrupter switches
Drawout circuit breakers are easily
21 maintainable

For more information, visit: www.eaton.com/consultants CA08104001E


Transfer SwitchesMedium Voltage 12.0-3
October 2015 Vacuum Breaker Transfer Switch (VCP-W-ATC)
Sheet 12 003
General Description

Additional Options Operation Maintenance


Lockout on phase and/or ground Operation is by a motor-charged The stored energy mechanism and i
overcurrents and/or internal stored energy spring mechanism control components are easily accessi-
bus faults charged by a universal electric motor, ble and can be inspected by removing
or a manual levering tool in an emer- the front panel. Minor maintenance ii
Load current, power and PF
gency. The stored energy mechanism when required, such as lubricating the
metering with optional DCT module
is a true mechanically and electrically mechanism and accessing the control
24 Vdc control power input trip-free design, meaning that while components, is simplified. 1
Up to four additional I/O modules, holding a mechanical trip command,
each with four programmable the breaker contacts will not close or Operation Sequence
digital inputs and digital outputs touch while receiving an electrical or Transfer is initiated by Eatons ATC-900 2
Overcurrent protection: mechanical close command. microprocessor-based logic controller
mounted on the door.
Normal Each CBS is electrically operated by 3
Emergency these control voltages: 120 Vac close The ATC-900 can be programmed
and ac capacitor trip, or 48 Vdc, for open or closed transition. The
Eatons Power Xpert
and IQ metering: normal and 125 Vdc or 250 Vdc. AC control voltage controller will not initiate the closed 4
is derived from potential transformers transfer until both power sources are
emergency
connected in the line side of each CBS. synchronized in voltage, frequency
Space heater and phase angle. If a power source is 5
The DC control voltage is provided by
Partial discharge InsulGard relay the user. lost, the closed transition control will
return to the open mode.
Circuit Breaker Switches Controls and indicators are functionally
ATC controller capabilities include:
6
grouped on the front control panel and
Switching is provided by Eatons include: closing spring status, close
VCP-W Vacuum Circuit Breakers in Continuous monitoring of all three
ANSI voltages of 5 and 15 kV.
and trip button, operation counter,
phases of all loads and voltage on 7
contact status indicators and a T
the source and bus
Circuit breaker switches (CBS) are handle latch (located at the bottom of
Generator testing under load
horizontal drawout types up to 15 kV. the control panel). Each CBS includes 8
a control switch, and red and green Simplified, custom programming
The CBS includes five major lights to indicate the CBS contact on the faceplate keypad to meet
components: vacuum interrupter
pole units, stored energy mechanism,
position. specific user requirements. There 9
are no DIP switches to set
push rod assembly, primary discon- Contacts
Visual status indications of both
necting contacts, and removable glass Primary disconnects are silver-plated sources and the load. 10
polyester insulating barriers. copper. Secondary contacts are silver-
Easy-to-use:
plated and automatically engage in
Vacuum Interrupters At-a-glance overview of the MV
Each CBS includes three vacuum
the CBS operating position. They can
ATS status and parameters and
11
be manually engaged in the CBS
interrupters, separately mounted in test position. key diagnostic data
a self-contained, self-aligning pole Real-time values for volts and 12
unit that is easily removed. A direct Safety frequency can be viewed on the
reading contact erosion indicator Double deadfront shields isolate the LED display plus the power
is clearly visible when the CBS is operator from high voltage when the source in use 13
withdrawn from the compartment. CBS is energized. The CBS can be Displays historical information
Each vacuum interrupter pole unit is connected or disconnected with the including Source 1 and Source 2
mounted on glass polyester supports compartment door closed by a run time, available time, and 14
for 5 kV and 15 kV ratings. manually operated levering device. connected time, load energized
The unique, nonsliding current Safety interlocks provide for the time, number of transfers, and the
transfer system from the movable mechanism to be held mechanically date, time and reason for the last 15
vacuum interrupter stem to the CBS trip-free during racking. Closing 100 transfers
consists of a series of tin-plated, high springs will discharge automatically
conductivity copper leaf conductors. when the CBS is being withdrawn.
Oscillographic data for last 16
10 transfers can be downloaded
The conductors are swaged onto the
via USB port or displayed in the
movable vacuum interrupter stem
and provide:
controllers display window 17
Improved current flow because the
multi-point contact offers very low 18
electrical resistance
No required maintenance because
the current transfer from the 19
movable stem to the CBS primary
conductor is a nonsliding and
nonrolling design 20
Longer vacuum interrupter life
21

CA08104001E For more information, visit: www.eaton.com/consultants


12.0-4 Transfer SwitchesMedium Voltage
Vacuum Breaker Transfer Switch (VCP-W-ATC) October 2015
Sheet 12 004
General Description

i
ATC-900 Open Transition Transfer ATC Controller While the load is connected to Source
2, the ATC-900 controller continues to
When the system is operating from the monitor Source 1. When Source 1
normal source, the ATC-900 controller
frequency and voltage return to within
ii indicates real-time values for volts
programmed limits of Source 1, and
and frequency on the front panel LED
display with an indication of the power after a programmed time delay, the
source in use. The ATC-900 controller load is transferred back to Source 1.
1 continuously monitors either single- When the closed transition mode is
phase or three-phase voltages for enabled, Source 1 is closed first, then
Source 1, Source 2 and the load.
2 The ATC-900 controller allows system
Source 2 is opened without power
interruption to the load. When in the
configuration selection for Source 1/ disabled mode, Source 2 is opened
Source 2 as Utility/Generator, or Dual
3 Generator, or Dual Utility.
first and then Source 1 is closed.
Note: See Page 12.0-8 for ATC-900 controller
When Source 1 voltage or frequency programming selections and ratings.
4 is detected to be below user-
programmed set points, transfer to Bus and Bus Insulation
Source 2 is initiated. The transfer
5 occurs when Source 2 voltage and Bus
frequency are detected to be within
programmed parameters. The main bus is copper. A set of either
1200 A or 2000 A main bus is provided
6 While the load is connected to Source 2, with provisions for future extension.
the ATC-900 controller continues to ATC-900
monitor Source 1. When Source 1 Bolted bus connections are silver-
7 voltage and frequency return to within plated for positive contact and low
ATC-900 Closed Transition Transfer resistance. Each joint is insulated
programmed parameters of Source 1,
and after a programmed time delay, load When the system is operating from with easily installed boots. The bus
8 transfer back to Source 1 is initiated. the normal source, Eatons ATC-900 is braced to withstand fault currents
controller indicates real-time values for equal to the close and latch rating of
The load transfer back to Source 1 is volts and frequency on the front panel the circuit breakers. All bus, bus sup-
9 open type because the Source 2 circuit LED display with an indication of the ports and connections will withstand
breaker switch is opened first after power source in use. The ATC-900 stresses produced by currents equal
which the Source 1 circuit breaker controller continuously monitors either to the momentary ratings of the circuit
10 switch is closed. single-phase or three-phase voltages breakers.
for Source 1, Source 2 and the load.
The ATC-900 controller allows system Temperature rise of the bus and con-
11 configuration selection for Source 1/ nections conforms to ANSI standards
Source 2 as Utility/Generator, or Dual and is documented by factory testing.
Generator, or Dual Utility. The copper ground bus extends the
12 entire length of the MV ATS. An
The ATC-900 controller provides for
selection of closed transition enabled optional fully rated neutral bus
13 or disabled. (insulated or noninsulated) extends
the entire length of the MV ATS.
When enabled, it is possible for load
to be transferred from Source 1 to Bus Insulation
14 Source 2 without interruption of power The main bus is insulated with epoxy,
to the load when both sources are applied in the fluidized bed process.
available. The source paralleling When applied in this process, the
15 during load transfer is less than epoxy is nonhygroscopic, inert, and
100 milliseconds. track, mold and fungus resistant.
16 When disabled, the two sources Thermal and electrical performance
cannot operate in parallel. is enhanced because the epoxy is
bonded directly to the bus bar conduc-
17 When Source 1 voltage or frequency tor, eliminating the air gap between
is detected to be below the user- insulation and conductor. Heat transfer
programmed set points, transfer to is greatly improved, resulting in the
18 Source 2 is initiated. The transfer bus system running cooler. No air
occurs when Source 2 voltage and gap exists for insulation damage or
frequency are detected to be within the corona discharge.
19 programmed parameters.
The main bus supports are glass
polyester for 5 kV and 15 kV ratings,
20 except the main bus supports for
63 kA ratings are porcelain.

21

For more information, visit: www.eaton.com/consultants CA08104001E


Transfer SwitchesMedium Voltage 12.0-5
October 2015 Vacuum Breaker Transfer Switch (VCP-W-ATC)
Sheet 12 005
General Description

Terminations and Outdoor Enclosures Current Transformers


Secondary Wiring Two outdoor enclosure styles are Ring-type current transformers are i
available. provided with thermal and mechanical
Eatons MV ATS includes terminal ratings coordinated with the circuit
blocks for secondary wire terminations Aisleless, mounted on an integral breakers. Current transformer accuracy ii
plus an inventory of spare terminal base frame with a weatherproof meets ANSI standards.
connections. One control circuit enclosure for field assembly. A weath-
cutout device is provided in each erproof door is provided on the circuit Standard current transformer location 1
CBS housing. breaker switch drawout side on the bus side and line side of the
5 kV and 15 kV CBS units provide
Sheltered aisle mounted on an inte-
Secondary wire is #14 AWG, Type SIS
gral base frame with a weatherproof
front accessibility so that adding or 2
rated 600 Vac, 90 C. The wires termi- changing transformers can be accom-
nate on terminal blocks, identified on enclosure for field assembly. The
plished when an Eatons MV ATS is
marker strips numbered in agreement enclosure is extended on the circuit 3
de-energized without breaking the
with the connection diagrams. breaker switch drawout side to form
high voltage connections and
an operating and/or maintenance
Incoming line and feeder cable lugs primary insulation.
aisle with sufficient space to permit 4
are provided. interchange of circuit breaker Shorting terminal blocks are provided
switches. A weatherproof door with on each current transformer secondary.
Protective Relays an inside quick release latch mecha- 5
Customer-requested protective relays nism is located at each end of the Arc-Resistant Switchgear
can be provided and installed in the inside, even when locked from the
Indoor MV ATS assembly conforming
MV ATS. Refer to Tab 4. outside. Interior lights, light switches,
and duplex ground fault receptacles
to UL 1008A can be supplied with 6
arc-resistant designs and features
Partial Discharge Sensing are provided in the aisle.
conforming to Type-2B accessibility
and Monitoring Each vertical section is provided with that provide arc-resistant protection 7
tubular-type space heaters operated at on the front, sides and rear of the
Refer to Tab 5, Section 5.3 for details
half voltage for long life. 500 V or 250 V equipment in accordance with
of partial discharge sensing and
rated heaters are used at 240 V or 120 V IEEE C37.20.7. 8
monitoring option.
respectively. Power is furnished from
Each individual vertical section of the
Metering a control power transformer mounted
in the MV ATS.
MV ATS assembly is provided with 9
Customer-requested metering can integral- and top-mounted pressure
be provided. Associated instrument As an option, heaters can be wired release flaps to facilitate a controlled
transformers are included. to provide temporary heating during upward release of arc-created over- 10
storage. pressures, smoke and gasses.
Current transformers are provided and
wired to shorting-type terminal blocks. Individual vertical sections are of 11
Auxiliary Equipment a unitized design to allow removal
Potential transformers are provided of a damaged vertical section after
Voltage and Control Power Transformers
including primary and secondary a fault incident, without requiring
fuses with disconnecting means Voltage transformers are drawout- the removal of the adjacent
12
for metering. drawer mounted for ratings up to 15 kV. vertical sections.
Up to three voltage transformers can be
A choice of Eaton microprocessor- mounted in a drawer. An enclosed arc chamber with arc duct 13
based metering is available, such as exit is provided above the switchgear
IQ Series or Power Xpert. Refer to Control power transformers up for exhaust collection and discharge.
Tab 2. to 15 kV, 15 kVA, single-phase are The arc exhaust is vented from the 14
drawout-drawer mounted. arc chamber to the exit location via
Enclosure Construction Drawers are in enclosed auxiliary the arc duct. Arc duct is optional.
Metal-clad integrity provides maxi- compartments and can be withdrawn
15
mum circuit separation and safety on rails for easy inspection, testing
through isolated grounded metal and fuse replacement. When a
compartments, complete isolation of drawer is withdrawn, the fuses
16
all conductors, and no live parts are are automatically disconnected,
exposed when a door is opened. grounded, and primary bus stabs 17
isolated by glass polyester shutters.
Communications A mechanical interlock is provided so
ATC-900 controller allows an MV ATS that the secondary circuit breaker must 18
to be included on a communications be open before the control power
network, providing for remote transformer drawer or control power
monitoring and control using a PC. transformer primary fuse drawer can 19
be withdrawn.
20

21

CA08104001E For more information, visit: www.eaton.com/consultants


12.0-6 Transfer SwitchesMedium Voltage
acuum Breaker Transfer Switch (VCP-W-ATC) October 2015
Sheet 12 006
General Description

Nameplates Accessories Factory Testing


i External engraved nameplates are Provided for testing, inspection,
Circuit Breaker Switch Element
screw mounted on the face of each maintenance and operation.
Alignment test with master cell to ver-
ii MV ATS assembly for each main
and feeder circuit. Nameplates are Standard Accessories ify all interfaces and interchangeability
laminated plastic with black 0.2-inch Maintenance tool for manually Circuit breaker operated over a
1 (5.1 mm) high characters on a white charging the circuit breaker closing range of minimum to maximum
background. spring and manually operating control voltage
the shutter One-minute dielectric test
A master nameplate includes MV
2 ATS designation, voltage and ampere
Levering crank for moving the
Circuit Breaker Switch Housing
circuit breaker between test and
ratings, short circuit rating, manufac- Alignment test with master circuit
connected positions
turers name, and shop order number.
3 Test jumper for electrically operating breaker to verify interfaces
Internal engraved nameplates are the circuit breaker while out of the One-minute dielectric test on
screw mounted within the MV ATS compartment primary and secondary circuits
4 to identify control components such Lifting yoke for lifting the circuit Operational sequence test to
as fuse blocks, relays, pushbuttons and breaker on or off compartment rails verify operation of wiring, relays
switches. and other devices
Rail extensions and rail clamps
5 Final inspection and quality check
Eaton MV ATS switches are provided
Optional Accessories
with all required markings and labels Three certified copies of the factory
Portable lifting device for lifting the
6 in accordance with UL 1008A.
circuit breaker on or off the rails test reports are provided.
Finish Ramp for rolling a circuit breaker Test Witnessing
7 Standard finish, inside and out, is
directly onto the floor from the
lower compartment
As an option, all factory tests can
a thermosetting, polyester powder be witnessed by the customer or
paint (ANSI 61 gray) applied electro- Test cabinet for testing electrically customer representative.
8 statically to all metal parts (steel and operated circuit breakers outside
aluminum) that are first precleaned housing Installation
and phosphatized. Dockable transport dolly for moving a Complete installation, startup, testing
9 circuit breaker outside of the cabinet and long-term maintenance is avail-
This finish provides excellent mechani-
Portable electrical levering device able from Eatons Electrical Services
cal strength and scratch resistance,
Integral levering device (refer to & Systems (EESS).
10 resists chalking caused by the suns
Tab 5, Pages 5.3-4 and 5.3-6)
ultraviolet rays, and meets the salt
spray requirements of ASTM B-117.
11

12

13

14

15

16

17

18

19

20

21

For more information, visit: www.eaton.com/consultants CA08104001E


Transfer SwitchesMedium Voltage 12.0-7
October 2015 Vacuum Breaker Transfer Switch (VCP-W-ATC)
Sheet 12 007
Available Ratings

Table 12.0-1. Medium Voltage Automatic Transfer Switch, Model VCP-W-ATC, Ratings per IEEE C37.20.2 and UL 1008A
Types and Ratings of Vacuum Circuit Breakers 1 Ratings per IEEE C37.20.2-1999 (Metal-Clad, Non-Arc Resistant) OptionalRatings per IEEE C37.20.7 i
Breaker Type Insulation Level Rated Momentary Enclosure Internal Arc Withstand

Rated Short Time Short-Circuit


Current Withstand (2-Second)
Short-Circuit Current Rated Arc Short-
Withstand (10 cycle)
[167 ms]
Circuit Withstand ii
Current

at Rated Maximum Voltage


Rated Short-Circuit Current

UL 1008A Operating Duty Class


Rated Maximum Voltage

(Class A = 2000 Operations)


Continuous Current
Withstand Voltage,

Rated Arc Duration


Withstand Voltage
Rated Interrupting

Lightning Impulse
Power Frequency

Rated Main Bus


60 Hz, 1 Minute
Time in Cycles
2

[LIWV] (BIL)

Accessibility Type
Rated Voltage
Range Factor

K*I 2 2.7 *K*I 3 1.6 *K* I Isc 2.6*Isc


(Ref. only) 4
3
I

kA rms Based on kV rms kV peak Amperes kA rms kA Crest kA rms kA rms kA peak Sec
kV rms
sym 60 Hz Sym Asym Sym
K

4.76 50 VCP-W 25 25 1 3 19 60 1200, 2000 25 68 40 2B 25 65 0.5 A 4


50 VCP-W 40 40 1 3 19 60 1200, 2000 40 108 64 2B 40 104 0.5 A
50 VCP-W 50 50 1 3 19 60 1200, 2000 50 135 80 2B 50 130 0.5 A
50 VCP-W 250 29 1.24 5 19 60 1200, 2000 36 97 58 2B 36 93.6 0.5 A
5
50 VCP-W 350 41 1.19 5 19 60 1200, 2000 49 132 78 2B 49 127.4 0.5 A
8.25 75 VCP-W 40 40 1 3 36 95 1200, 2000 40 111 66 2B 40 104 0.5 A 6
75 VCP-W 50 50 1 3 36 95 1200, 2000 50 135 80 2B 50 130 0.5 A
75 VCP-W 500 33 1.25 5 36 95 1200, 2000 41 111 66 2B 41 106.6 0.5 A
15 150 VCP-W 25 25 1 3 36 95 1200, 2000 25 68 40 2B 25 65 0.5 A 7
150 VCP-W 40 40 1 3 36 95 1200, 2000 40 108 64 2B 40 104 0.5 A
150 VCP-W 50 50 1 3 36 95 1200, 2000 50 135 80 2B 50 130 0.5 A 8
150 VCP-W 500 18 1.3 5 36 95 1200, 2000 23 62 37 2B 23 59.8 0.5 A
150 VCP-W 750 28 1.3 5 36 95 1200, 2000 36 97 58 2B 36 93.6 0.5 A
150 VCP-W 1000 37 1.3 5 36 95 1200, 2000 48 130 77 2B 48 124.8 0.5 A 9
1 Circuit breakers are rated to standards for HV AC circuit breakersANSI/IEEE C37.04, C37.06 and C37.09.
2 Please note that use of certain current transformers (for example, bar type CTs) and protective devices may limit the duration to a value less
than 2 seconds. 10
3 These values exceed 2.6*K*I required by IEEE C37.20.2-1999 and ANSI C37.06-2000.
4 These values exceed 1.55*K*I required by IEEE C37.20.2-1999.
11

12

13

14

15

16

17

18

19

20

21

CA08104001E For more information, visit: www.eaton.com/consultants


12.0-8 Transfer SwitchesMedium Voltage
Vacuum Breaker Transfer Switch (VCP-W-ATC) October 2015
Sheet 12 008
Technical Data

Table 12.0-2. ATC-900 Programmable Set Points


i Option Number Description Range Factory Default
General Settings
ii Set new password 00009999 0900
Selected language English, French or Spanish English
Nominal frequency 50 or 60 Hz As ordered
1 Nominal voltage 110600 V As ordered
Number of phases 1 or 3 As ordered

2 Number of generators 0, 1 or 2 1
Preferred source Source 1 or Source 2 Source 1
PT ratio 2:1500:1 As ordered
3 CT ratio 2005000
Daylight Saving Time On or Off 1
Operating mode Stand-alone/Master or Slave Master
4 Phase sequence check ABC, CBA or Off Off
Commitment to transfer in TDNE Yes or No No
5 Manual retransfer Auto, Manual or External As ordered
Modbus address 1247 1
Modbus baud rate 0 = 9600, 1, Even 9600
6 1 = 9600, 1, Odd
2 = 9600, 2, None
3 = 9600, 1, None
7 4 = 19,200, 1, Even
5 = 19,200, 1, Odd


6 = 19,200, 2, None
7 = 19,200, 1, None
8 Transition Settings
47 Closed transition
9 Closed transition On or Off
Closed voltage difference
On or Off
15%
As ordered
2%
Closed frequency difference 0.001500.3 Hz 0.3

10 32f/32d Openin-phase transition


In-phase On or Off Disable, in-phase default to alarm, in-phase default to open transition As ordered
In-phase frequency difference 0.03.0 Hz 1.0
11 Synchronization timer 160 minutes 5
32a/32d Opendelayed transition
Time delay neutral 0120 seconds 0
12 Load voltage decay 1 230% of nominal voltage 6%
Time Delays
1a Time delay normal to emergency 09999 seconds 0:00
13 3a Time delay emergency to normal 09999 seconds 5:00
35A Time delay pre-transfer 0120 seconds 0:01
14 35C Time delay post-transfer 0120 seconds 0:10
2A Time delay engine 1 start 0120 seconds 0:03
Time delay engine 2 start 0120 seconds 0:03
15 4A Time delay engine cool-off 09999 seconds 5:00
7A Time delay engine fail timer 06 seconds 0:06
16 Voltage unbalance time delay 1030 seconds 0:30
1 Load voltage decay feature requires a set of bus VTs (optional).

17

18

19

20

21

For more information, visit: www.eaton.com/consultants CA08104001E


Transfer SwitchesMedium Voltage 12.0-9
October 2015 Vacuum Breaker Transfer Switch (VCP-W-ATC)
Sheet 12 009
Technical Data

Table 12.0-2. ATC-900 Programmable Set Points (Continued)


Option Number Description Range Factory Default i
Source Settings
26P Source 1 undervoltage dropout
Source 1 undervoltage pickup
7097% of nominal
(dropout + 2%) to 99%
80%
90%
ii
of nominal
5P Source 2 undervoltage dropout
Source 2 undervoltage pickup
7097% of nominal
(dropout + 2%) to 99%
80%
90%
1
of nominal
26K Source 1 overvoltage dropout 105120% of nominal (0 = disabled) 115%
Source 1 overvoltage pickup 103% of nominal to (dropout - 2%) (0 = disabled) 105% 2
5K Source 2 overvoltage dropout 105120% of nominal (0 = disabled) 115%
Source 2 overvoltage pickup 103% of nominal to (dropout - 2%) (0 = disabled) 105%
26J Source 1 underfrequency dropout 9097% of nominal (0 = disabled) 94%
3
Source 1 underfrequency pickup (dropout + 1 Hz) to 99% of nominal (0 = disabled) 96%
5J Source 2 underfrequency dropout 9097% of nominal (0 = disabled) 94%
Source 2 underfrequency pickup (dropout + 1 Hz) to 99% of nominal (0 = disabled) 96% 4
26N Source 1 overfrequency dropout 103110% (0 = disabled) 106%
Source 1 overfrequency pickup 101% to (dropout - 1 Hz) (0 = disabled) 104%
5N Source 2 overfrequency dropout 103110% (0 = disabled) 106%
5
Source 2 overfrequency pickup 101% to (dropout - 1 Hz) (0 = disabled) 104%
26L Source 1 percent for unbalanced voltage dropout
Source 1 percent for unbalanced voltage pickup
520% of phase-to-phase voltage unbalance (0 = disabled)
3% to (dropout - 2%) (0 = disabled)
12%
10%
6
5L Source 2 percent for unbalanced voltage dropout 520% of phase-to-phase voltage unbalance (0 = disabled) 12%
Source 2 percent for unbalanced voltage pickup 3% to (dropout - 2%) (0 = disabled) 10%
Engine Test/Plant Exerciser (PE1 and PE2 are Independently Programmable)
7
6B Engine test pushbutton on panel
Test mode No load, load transfer, disabled Load transfer 8
Engine run test time 0600 minutes Load transfer
23M PE time delay normal to emergency 09999 seconds 1 minute
PE time delay emergency to normal
PE time delay engine cooldown
09999 seconds
09999 seconds
1 minute
5 minutes
9
PE1/PE2 test mode No load, load transfer, disabled Disabled
PE1/PE2 run time 0600 minutes 30 minutes
PE1/PE2 schedule Off, daily, 7-day, 14-day, 28-day or calendar date 10
(up to 12 user-specified dates)
PE1/PE2 calendar date Month: 112; Day: 131

PE1/PE2 day of week


1 Sunday, 2 Monday, 3 Tuesday, 4 Wednesday, 5 Thursday,
6 Friday or 7 Saturday
11
PE1/PE2 plant start time HH:MM AM/PM
Accessory I/O 12
Accessory I/O modules 04

13

14

15

16

17

18

19

20

21

CA08104001E For more information, visit: www.eaton.com/consultants


12.0-10 Transfer SwitchesMedium Voltage
Vacuum Breaker Transfer Switch (VCP-W-ATC) October 2015
Sheet 12 010
Technical Data

Typical One-Line Diagram


i
Load Bus
ii
Surge
1 Optional Arrestors
(Optional)
Items

2
To Load
3 Single-Phase
CPT (2) or (3)
5/10/15 kVA Bus VTs

4
120/240 V
Auxiliary Power
5

7
ATC 900

9
52-M1 52-M1
VCB 52-M1 Breaker Controls VCB 52-M2 Breaker Controls
10

11
Digitrip Power Xpert Digitrip Power Xpert
12 (3) CTs
3010
Dual
Meter (3) CTs
3010
Dual
Meter
(optional) (optional)
Powered Powered
13 (Note) (Note)

14 (2) or (3) VTs (2) or (3) VTs

15
Note:
16 Surge
External control power
is required if not using
Surge
Arrestors Arrestors
self-powered OC relay.
(optional) (optional)
17
Source 1 Source 2
18
Figure 12.0-1. Typical Medium Voltage Automatic Transfer Switch
19

20

21

For more information, visit: www.eaton.com/consultants CA08104001E


Transfer SwitchesMedium Voltage 12.0-11
October 2015 Vacuum Breaker Transfer Switch (VCP-W-ATC)
Sheet 12 011
Layout DimensionsStandard Metal-Clad

Layout Dimensions in Inches (mm)Standard Metal-Clad


i
Power Cable Entrance Power Cable Entrance
ii
7.00 72.00 72.00
(177.8) (1828.8) (1828.8)
1

2
18.50 C C C C
(469.9) L L L L
3
If Bottom Entry Main 1 Main 2 Load (Top or Load
96.25 Cables 101.25
If Top Entry Main 2 Main 1 Cables Bottom) (2444.8) (2571.8)
4
Secondary Secondary
Control Wires Control Wires
Entrance Entrance 5

7
Floor Plan Floor Plan
8

9
Line 1 VTs Line 1 VTs
Main 1
Main 1
Breaker Breaker 10
(1200A) (1200A)
Bus VTs Bus VTs
(Optional) (Optional) 11
95.00 115.00
(2413.0) (2921.0)
Bus CPT Bus CPT 12
(Optional) (Optional)
Main 2 Main 2
Breaker Breaker
(1200A) (1200A) 13
Line 2 VTs Line 2 VTs

14
Shipping Group
15
Front Elevation Front Elevation
16
Figure 12.0-2. Indoor 5 kV or 15 kV, 1200 A Main Breakers Figure 12.0-3. Outdoor Aisleless 5 kV or 15 kV, 1200 A Main Breakers
1 Circuit breakers are packaged and shipped separately. 2 Circuit breakers are packaged and shipped separately.
17
Table 12.0-3. Approximate Shipping Weight in Lb (kg) Table 12.0-4. Minimum Recommended Clearances in Inches (mm)
Equipment Switchgear Circuit Equipment Front Side Rear
Type Assembly Breaker Type 18
Indoor 4400 (1998) 350575 (159261) Indoor 70.00 (1778.0) 32.00 (812.8) 36.00 (914.4)
Outdoor aisleless 5600 (2542) 350575 (159261) Outdoor aisleless 70.00 (1778.0) 32.00 (812.8) 36.00 (914.4) 19

20

21

CA08104001E For more information, visit: www.eaton.com/consultants


12.0-12 Transfer SwitchesMedium Voltage
Vacuum Breaker Transfer Switch (VCP-W-ATC) October 2015
Sheet 12 012
Layout DimensionsStandard Metal-Clad

Layout Dimensions in Inches (mm)Standard Metal-Clad


i
Power Cable Entrance
ii
72.00
(1828.8)
1

2
Line 1 VTs
C C Main 1
3 L L Breaker
(1200A)
Load Bus VTs
Cables
4 (Optional)

120.00
(3048.0)
Secondary
5 Control Wires Bus CPT
Entrance (Optional)
169.38 Main 2
(4302.3) Breaker
6 (1200A)
Line 2 VTs
38.00
7 (965.2)

8 72.00
Shipping Group
Aisle Front Elevation
(1828.8)
9
38.00
10 (965.2)

Floor Plan
11
Figure 12.0-4. Outdoor Sheltered Aisle 5 kV or 15 kV, 1200 A Main Breakers
1 Circuit breakers are packaged and shipped separately.
12
Table 12.0-5. Approximate Shipping Weight in Lb (kg) Table 12.0-6. Minimum Recommended Clearances in Inches (mm)
Equipment Switchgear Circuit Equipment Front Side Rear
13 Type Assembly Breaker Type

Outdoor sheltered aisle 8000 (3632) 350575 (159261) Outdoor sheltered aisle N/A 38.00 (965.2) 36.00 (914.4)
14

15

16

17

18

19

20

21

For more information, visit: www.eaton.com/consultants CA08104001E


Transfer SwitchesMedium Voltage 12.0-13
October 2015 Vacuum Breaker Transfer Switch (VCP-W-ATC)
Sheet 12 013
Layout DimensionsStandard Metal-Clad

Layout Dimensions in Inches (mm)Standard Metal-Clad


i
Power Cable Entrance Power Cable Entrance
ii
7.00 108.00 108.00
(177.7) (2743.2) (2743.2)
1

2
C C C CL CL CL
L L L 3
Load Load
96.25 101.25
Cables
(2444.8)
Cables
(2571.8) 4
Secondary
Secondary
Control Wires Control Wires 5
Entrance Entrance

Floor Plan Floor Plan 8

9
Line VTs Line VTs Line VTs Line VTs
10

11
95.00 115.00
(2413.0) (2921.0) 12
Bus VTs Bus VTs
(Optional) (Optional)
Main Main Main Main 13
Breaker Breaker Breaker Breaker
(2000 A) (2000 A) (2000 A) (2000 A)
Bus CPT Bus CPT
(Optional) (Optional) 14

15

Front Elevation Front Elevation 16


Figure 12.0-5. Indoor 5 kV or 15 kV, 2000 A Main Breakers Figure 12.0-6. Outdoor Aisleless 5 kV or 15 kV, 2000 A Main Breakers
1 Circuit breakers are packaged and shipped separately. 2 Circuit breakers are packaged and shipped separately.
17
Table 12.0-7. Approximate Shipping Weight in Lb (kg) Table 12.0-8. Minimum Recommended Clearances in Inches (mm)
Equipment Switchgear Circuit Equipment Front Side Rear
18
Type Assembly Breaker Type

Indoor 6900 (3133) 410575 (186261) Indoor 70.00 (1778.0) 32.00 (812.8) 36.00 (914.4) 19
Outdoor aisleless 8700 (3950) 410575 (186261) Outdoor aisleless 70.00 (1778.0) 32.00 (812.8) 36.00 (914.4)

20

21

CA08104001E For more information, visit: www.eaton.com/consultants


12.0-14 Transfer SwitchesMedium Voltage
Vacuum Breaker Transfer Switch (VCP-W-ATC) October 2015
Sheet 12 014
Layout DimensionsStandard Metal-Clad

Layout Dimensions in Inches (mm)Standard Metal-Clad


i
Power Cable Entrance
ii
108.00
(2743.2)
1

2 Line VTs Line VTs


CL CL CL

3
Load
Cables

4 120.00
(3048.0)
Secondary
Control Wires Bus VTs
Entrance (Optional)
5 169.38 Main Main
(4302.3) Breaker Breaker
(2000 A) (2000 A)
Bus CPT
6 (Optional)
38.00
(965.2)

7
Aisle 72.00
(1828.8)
8 Front Elevation

9 38.00
(965.2)

Floor Plan
10
Figure 12.0-7. Outdoor Sheltered Aisle 5 kV or 15 kV, 2000 A Main Breakers
1
11 2
Aisles shipped separately.
Circuit breakers are packaged and shipped separately.

Table 12.0-9. Approximate Shipping Weight in Lb (kg) Table 12.0-10. Minimum Recommended Clearances in Inches (mm)
12 Equipment Switchgear Circuit Equipment Front Side Rear
Type Assembly Breaker Type
13 Outdoor sheltered aisle 12,300 (5584) 410575 (186261) Outdoor sheltered aisle N/A 38.00 (965.2) 36.00 (914.4)

14

15

16

17

18

19

20

21

For more information, visit: www.eaton.com/consultants CA08104001E


Transfer SwitchesMedium Voltage 12.0-15
October 2015 Vacuum Breaker Transfer Switch (VCP-W-ATC)
Sheet 12 015
Layout DimensionsArc-Resistant Metal-Clad

Layout Dimensions in Inches (mm)Arc-Resistant Metal-Clad


i
Power Cable Entrance Rear Extension Power Cable Entrance Rear Extension
for Top for Top ii
Entry Cables Entry Cables
75.00 Only 111.00 Only
(1905.0) (2819.4)
1
(Top
12.00 (Top
12.00
Main 2 Main 1 Entry) (304.8) Entry) (304.8)
2
109.50 109.50
(Bottom (Bottom
Entry) (2781.3) Entry) (2781.3)
(Top
Entry
(Top
Entry
3
C C Cables) C C C Cables)
L L L L L

Main 1 Main 2 Load Load


4
Cables 96.25 96.25
Cables
(2444.8) (2444.8)
(Bottom (Bottom
Entry Entry 5
Secondary Cables) Secondary Cables)
Control Wires Control Wires
Entrance Entrance
6

7
Floor Plan Floor Plan
8
Arc Exhaust Plenum 32.00 32.00
(812.8) Arc Exhaust Plenum
(812.8)
9

Main 1
10
Breaker Line 1 VTs Line 1 VTs Bus VTs Line 2 VTs
(1200A) (Optional)
11
95.00 95.00
(2413.0) (2413.0)
12
Main 2 Main 1 Main 2
Breaker Line 2 VTs Breaker Bus CPT Breaker
(1200A) (1200 or
2000 A)
(Optional) (1200 or
2000 A) 13

14
Shipping Group Shipping Group
Front Elevation Front Elevation 15
Figure 12.0-8. Indoor 5/15 kV, Arc-Resistant MV ATS Figure 12.0-9. Indoor 5/15 kV, Arc-Resistant MV ATS
without Optional CPT with Optional CPT and/or Optional Bus VTs
1 Circuit breakers are packaged and shipped separately. 3 Circuit breakers are packaged and shipped separately.
16
Table 12.0-11. Approximate Shipping Weight in Lb (kg) Table 12.0-12. Minimum Recommended Clearances in Inches (mm)
17
Equipment Switchgear Circuit Equipment Front Side Rear
Type Assembly Breaker Type
1200 A 2000 A 1200 A 2000 A
Indoor 70.00 (1778.0) 32.00 (812.8) 36.00 (914.4) 18
Indoor Figure 12.0-8 6400 2
2 2
Indoor Figure 12.0-9 8950 9250
19
Top Entry Cables 425
Figure 12.0-8, add
Top Entry Cables
Figure 12.0-9, add
600 725 20
2 Refer to Table 5.5-2 for circuit breaker weights.
21

CA08104001E For more information, visit: www.eaton.com/consultants


12.0-16 Transfer SwitchesMedium Voltage
Vacuum Breaker Transfer Switch (VCP-W-ATC) October 2015
Sheet 12 016
Layout DimensionsArc-Resistant Metal-Clad

Layout Dimensions in Inches (mm)Arc-Resistant Metal-Clad


i Arc exhaust plenum and arc duct exit for 5 and 15 kV metal-clad
switchgearrefer to Tab 5, Pages 5.5-39, 5.5-40 and 5.5-41.
ii

10

11

12

13

14

15

16

17

18

19

20

21