Medium Voltage
Contents
Transfer Switches Transfer SwitchesMedium Voltage
Medium Voltage Vacuum Breaker Transfer Switches
i
ii
General Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12.0-2
Automatic Transfer Control (ATC). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12.0-4 1
Protection and Metering . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12.0-5
Auxiliary Equipment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12.0-5
Available Ratings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12.0-7
2
Technical Data. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12.0-8
Layout DimensionsStandard Metal-Clad . . . . . . . . . . . . . . . . . . . . . . . . 12.0-11 3
Layout DimensionsArc-Resistant Metal-Clad. . . . . . . . . . . . . . . . . . . . . 12.0-15
Specifications 4
See Eatons Product Specification Guide, available on CD or on the Web.
CSI Format: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1995 2010 5
Medium Voltage Vacuum Breaker
Transfer Switches . . . . . . . . . . . . . . . . . . Section 16495 Section 26 36 23.21
6
10
11
12
13
14
15
16
17
18
19
20
Medium Voltage Transfer Switch
Conforming to UL 1008A
21
i
ATC-900 Open Transition Transfer ATC Controller While the load is connected to Source
2, the ATC-900 controller continues to
When the system is operating from the monitor Source 1. When Source 1
normal source, the ATC-900 controller
frequency and voltage return to within
ii indicates real-time values for volts
programmed limits of Source 1, and
and frequency on the front panel LED
display with an indication of the power after a programmed time delay, the
source in use. The ATC-900 controller load is transferred back to Source 1.
1 continuously monitors either single- When the closed transition mode is
phase or three-phase voltages for enabled, Source 1 is closed first, then
Source 1, Source 2 and the load.
2 The ATC-900 controller allows system
Source 2 is opened without power
interruption to the load. When in the
configuration selection for Source 1/ disabled mode, Source 2 is opened
Source 2 as Utility/Generator, or Dual
3 Generator, or Dual Utility.
first and then Source 1 is closed.
Note: See Page 12.0-8 for ATC-900 controller
When Source 1 voltage or frequency programming selections and ratings.
4 is detected to be below user-
programmed set points, transfer to Bus and Bus Insulation
Source 2 is initiated. The transfer
5 occurs when Source 2 voltage and Bus
frequency are detected to be within
programmed parameters. The main bus is copper. A set of either
1200 A or 2000 A main bus is provided
6 While the load is connected to Source 2, with provisions for future extension.
the ATC-900 controller continues to ATC-900
monitor Source 1. When Source 1 Bolted bus connections are silver-
7 voltage and frequency return to within plated for positive contact and low
ATC-900 Closed Transition Transfer resistance. Each joint is insulated
programmed parameters of Source 1,
and after a programmed time delay, load When the system is operating from with easily installed boots. The bus
8 transfer back to Source 1 is initiated. the normal source, Eatons ATC-900 is braced to withstand fault currents
controller indicates real-time values for equal to the close and latch rating of
The load transfer back to Source 1 is volts and frequency on the front panel the circuit breakers. All bus, bus sup-
9 open type because the Source 2 circuit LED display with an indication of the ports and connections will withstand
breaker switch is opened first after power source in use. The ATC-900 stresses produced by currents equal
which the Source 1 circuit breaker controller continuously monitors either to the momentary ratings of the circuit
10 switch is closed. single-phase or three-phase voltages breakers.
for Source 1, Source 2 and the load.
The ATC-900 controller allows system Temperature rise of the bus and con-
11 configuration selection for Source 1/ nections conforms to ANSI standards
Source 2 as Utility/Generator, or Dual and is documented by factory testing.
Generator, or Dual Utility. The copper ground bus extends the
12 entire length of the MV ATS. An
The ATC-900 controller provides for
selection of closed transition enabled optional fully rated neutral bus
13 or disabled. (insulated or noninsulated) extends
the entire length of the MV ATS.
When enabled, it is possible for load
to be transferred from Source 1 to Bus Insulation
14 Source 2 without interruption of power The main bus is insulated with epoxy,
to the load when both sources are applied in the fluidized bed process.
available. The source paralleling When applied in this process, the
15 during load transfer is less than epoxy is nonhygroscopic, inert, and
100 milliseconds. track, mold and fungus resistant.
16 When disabled, the two sources Thermal and electrical performance
cannot operate in parallel. is enhanced because the epoxy is
bonded directly to the bus bar conduc-
17 When Source 1 voltage or frequency tor, eliminating the air gap between
is detected to be below the user- insulation and conductor. Heat transfer
programmed set points, transfer to is greatly improved, resulting in the
18 Source 2 is initiated. The transfer bus system running cooler. No air
occurs when Source 2 voltage and gap exists for insulation damage or
frequency are detected to be within the corona discharge.
19 programmed parameters.
The main bus supports are glass
polyester for 5 kV and 15 kV ratings,
20 except the main bus supports for
63 kA ratings are porcelain.
21
21
12
13
14
15
16
17
18
19
20
21
Table 12.0-1. Medium Voltage Automatic Transfer Switch, Model VCP-W-ATC, Ratings per IEEE C37.20.2 and UL 1008A
Types and Ratings of Vacuum Circuit Breakers 1 Ratings per IEEE C37.20.2-1999 (Metal-Clad, Non-Arc Resistant) OptionalRatings per IEEE C37.20.7 i
Breaker Type Insulation Level Rated Momentary Enclosure Internal Arc Withstand
Lightning Impulse
Power Frequency
[LIWV] (BIL)
Accessibility Type
Rated Voltage
Range Factor
kA rms Based on kV rms kV peak Amperes kA rms kA Crest kA rms kA rms kA peak Sec
kV rms
sym 60 Hz Sym Asym Sym
K
12
13
14
15
16
17
18
19
20
21
2 Number of generators 0, 1 or 2 1
Preferred source Source 1 or Source 2 Source 1
PT ratio 2:1500:1 As ordered
3 CT ratio 2005000
Daylight Saving Time On or Off 1
Operating mode Stand-alone/Master or Slave Master
4 Phase sequence check ABC, CBA or Off Off
Commitment to transfer in TDNE Yes or No No
5 Manual retransfer Auto, Manual or External As ordered
Modbus address 1247 1
Modbus baud rate 0 = 9600, 1, Even 9600
6 1 = 9600, 1, Odd
2 = 9600, 2, None
3 = 9600, 1, None
7 4 = 19,200, 1, Even
5 = 19,200, 1, Odd
6 = 19,200, 2, None
7 = 19,200, 1, None
8 Transition Settings
47 Closed transition
9 Closed transition On or Off
Closed voltage difference
On or Off
15%
As ordered
2%
Closed frequency difference 0.001500.3 Hz 0.3
17
18
19
20
21
13
14
15
16
17
18
19
20
21
2
To Load
3 Single-Phase
CPT (2) or (3)
5/10/15 kVA Bus VTs
4
120/240 V
Auxiliary Power
5
7
ATC 900
9
52-M1 52-M1
VCB 52-M1 Breaker Controls VCB 52-M2 Breaker Controls
10
11
Digitrip Power Xpert Digitrip Power Xpert
12 (3) CTs
3010
Dual
Meter (3) CTs
3010
Dual
Meter
(optional) (optional)
Powered Powered
13 (Note) (Note)
15
Note:
16 Surge
External control power
is required if not using
Surge
Arrestors Arrestors
self-powered OC relay.
(optional) (optional)
17
Source 1 Source 2
18
Figure 12.0-1. Typical Medium Voltage Automatic Transfer Switch
19
20
21
2
18.50 C C C C
(469.9) L L L L
3
If Bottom Entry Main 1 Main 2 Load (Top or Load
96.25 Cables 101.25
If Top Entry Main 2 Main 1 Cables Bottom) (2444.8) (2571.8)
4
Secondary Secondary
Control Wires Control Wires
Entrance Entrance 5
7
Floor Plan Floor Plan
8
9
Line 1 VTs Line 1 VTs
Main 1
Main 1
Breaker Breaker 10
(1200A) (1200A)
Bus VTs Bus VTs
(Optional) (Optional) 11
95.00 115.00
(2413.0) (2921.0)
Bus CPT Bus CPT 12
(Optional) (Optional)
Main 2 Main 2
Breaker Breaker
(1200A) (1200A) 13
Line 2 VTs Line 2 VTs
14
Shipping Group
15
Front Elevation Front Elevation
16
Figure 12.0-2. Indoor 5 kV or 15 kV, 1200 A Main Breakers Figure 12.0-3. Outdoor Aisleless 5 kV or 15 kV, 1200 A Main Breakers
1 Circuit breakers are packaged and shipped separately. 2 Circuit breakers are packaged and shipped separately.
17
Table 12.0-3. Approximate Shipping Weight in Lb (kg) Table 12.0-4. Minimum Recommended Clearances in Inches (mm)
Equipment Switchgear Circuit Equipment Front Side Rear
Type Assembly Breaker Type 18
Indoor 4400 (1998) 350575 (159261) Indoor 70.00 (1778.0) 32.00 (812.8) 36.00 (914.4)
Outdoor aisleless 5600 (2542) 350575 (159261) Outdoor aisleless 70.00 (1778.0) 32.00 (812.8) 36.00 (914.4) 19
20
21
2
Line 1 VTs
C C Main 1
3 L L Breaker
(1200A)
Load Bus VTs
Cables
4 (Optional)
120.00
(3048.0)
Secondary
5 Control Wires Bus CPT
Entrance (Optional)
169.38 Main 2
(4302.3) Breaker
6 (1200A)
Line 2 VTs
38.00
7 (965.2)
8 72.00
Shipping Group
Aisle Front Elevation
(1828.8)
9
38.00
10 (965.2)
Floor Plan
11
Figure 12.0-4. Outdoor Sheltered Aisle 5 kV or 15 kV, 1200 A Main Breakers
1 Circuit breakers are packaged and shipped separately.
12
Table 12.0-5. Approximate Shipping Weight in Lb (kg) Table 12.0-6. Minimum Recommended Clearances in Inches (mm)
Equipment Switchgear Circuit Equipment Front Side Rear
13 Type Assembly Breaker Type
Outdoor sheltered aisle 8000 (3632) 350575 (159261) Outdoor sheltered aisle N/A 38.00 (965.2) 36.00 (914.4)
14
15
16
17
18
19
20
21
2
C C C CL CL CL
L L L 3
Load Load
96.25 101.25
Cables
(2444.8)
Cables
(2571.8) 4
Secondary
Secondary
Control Wires Control Wires 5
Entrance Entrance
9
Line VTs Line VTs Line VTs Line VTs
10
11
95.00 115.00
(2413.0) (2921.0) 12
Bus VTs Bus VTs
(Optional) (Optional)
Main Main Main Main 13
Breaker Breaker Breaker Breaker
(2000 A) (2000 A) (2000 A) (2000 A)
Bus CPT Bus CPT
(Optional) (Optional) 14
15
Indoor 6900 (3133) 410575 (186261) Indoor 70.00 (1778.0) 32.00 (812.8) 36.00 (914.4) 19
Outdoor aisleless 8700 (3950) 410575 (186261) Outdoor aisleless 70.00 (1778.0) 32.00 (812.8) 36.00 (914.4)
20
21
3
Load
Cables
4 120.00
(3048.0)
Secondary
Control Wires Bus VTs
Entrance (Optional)
5 169.38 Main Main
(4302.3) Breaker Breaker
(2000 A) (2000 A)
Bus CPT
6 (Optional)
38.00
(965.2)
7
Aisle 72.00
(1828.8)
8 Front Elevation
9 38.00
(965.2)
Floor Plan
10
Figure 12.0-7. Outdoor Sheltered Aisle 5 kV or 15 kV, 2000 A Main Breakers
1
11 2
Aisles shipped separately.
Circuit breakers are packaged and shipped separately.
Table 12.0-9. Approximate Shipping Weight in Lb (kg) Table 12.0-10. Minimum Recommended Clearances in Inches (mm)
12 Equipment Switchgear Circuit Equipment Front Side Rear
Type Assembly Breaker Type
13 Outdoor sheltered aisle 12,300 (5584) 410575 (186261) Outdoor sheltered aisle N/A 38.00 (965.2) 36.00 (914.4)
14
15
16
17
18
19
20
21
7
Floor Plan Floor Plan
8
Arc Exhaust Plenum 32.00 32.00
(812.8) Arc Exhaust Plenum
(812.8)
9
Main 1
10
Breaker Line 1 VTs Line 1 VTs Bus VTs Line 2 VTs
(1200A) (Optional)
11
95.00 95.00
(2413.0) (2413.0)
12
Main 2 Main 1 Main 2
Breaker Line 2 VTs Breaker Bus CPT Breaker
(1200A) (1200 or
2000 A)
(Optional) (1200 or
2000 A) 13
14
Shipping Group Shipping Group
Front Elevation Front Elevation 15
Figure 12.0-8. Indoor 5/15 kV, Arc-Resistant MV ATS Figure 12.0-9. Indoor 5/15 kV, Arc-Resistant MV ATS
without Optional CPT with Optional CPT and/or Optional Bus VTs
1 Circuit breakers are packaged and shipped separately. 3 Circuit breakers are packaged and shipped separately.
16
Table 12.0-11. Approximate Shipping Weight in Lb (kg) Table 12.0-12. Minimum Recommended Clearances in Inches (mm)
17
Equipment Switchgear Circuit Equipment Front Side Rear
Type Assembly Breaker Type
1200 A 2000 A 1200 A 2000 A
Indoor 70.00 (1778.0) 32.00 (812.8) 36.00 (914.4) 18
Indoor Figure 12.0-8 6400 2
2 2
Indoor Figure 12.0-9 8950 9250
19
Top Entry Cables 425
Figure 12.0-8, add
Top Entry Cables
Figure 12.0-9, add
600 725 20
2 Refer to Table 5.5-2 for circuit breaker weights.
21
10
11
12
13
14
15
16
17
18