I. Company Profile
Shandong Luneng Mount Tai Electric Equipment Co., Ltd is located in the Hi-tech Development Zone in
Taian and occupies an area of 300,000 square meters. The company has four subsidiary companies; they
are Shandong Luneng Cable Co., Ltd, Taian Taishan Electric Co., Ltd, Taishan High-voltage Switchgear
Co., Ltd, Xintiancheng Electric Co., Ltd. It is a professional manufacturer of power transformer, power
cable and gas insulated switch and other electric equipments. It has the State-level Enterprise Technology
Center and possesses the authority of import and export. It has been granted the following honors: Key
Transformer Manufacturer for Power Grid Company of China, High-and-new Technology Enterprise of
State Ministry of Science and Technology, State-level Contract-keeping and Credit-abiding Enterprise,
Key Enterprise of Shandong Province, Enterprise with AAA Credit, Member of The Catalogue of
Recommended Enterprises in the Building and Rebuilding of Urban and Rural Power Grid of China,
Member of China Petrifaction Equipment Suppliers, Key Recommended Enterprise of
Electro-mechanical Equipment for Hydroelectric Projects and so on. In 2003, the companys technical
innovation plan of traction transformer was listed in the plan of the State Torch Program. The 500 kV
oil-immersed power transformer and dry type transformer of the company have been given the honors of
Quality Trustworthy Product, Satisfactory Product for Client, Shandong Famous Brand. The low
loss oil-immersed power transformers up to 220 kV and resin-casting transformers up to 35 kV have been
awarded Free-of-check Product in Shandong Province. In 2000, the company has passed certificates of
the ISO9001 Quality Management System and ISO14001 Environmental Management System and the
CPCCC Product Certificate of State Electric Energy. Meanwhile, the 500kV, 330kV and 220 kV
transformers manufactured by the company have passed the Holland KEMA test certificates
The main products manufactured by the company can be divided into eight voltage classes: 750 kV, 500
kV, 330 kV, 220 kV, 110 kV, 66 kV, 35 kV and 10 kV. All together there are 18 series and more than 1196
different kinds of power transformers as well as special transformers like traction transformer. The
company independently investigated and designed 35-750 kV power transformer, combined transformer,
railway balance transformer, rectifier transformer, furnace transformer and resin-casting dry type
transformer, 252 kV gas insulated switch (GIS), breaker, isolated switch and so on. Many new products
have passed the state and province appraisal and keep ahead in power transformer industry. The products
are sold all over the country, such as Beijing, Shanghai, Tianjin, Guangdong, Jiangsu, and Shandong and
so on. So far, the oversea markets for the company are growing gradually, the products have been sold to
Russia, India, Vietnam, Syria, UAE Dubai, Tanzania, Zambia ect. They are mainly applied in power
supply, water conservancy, railway, metallurgy, petroleum, chemical industry and other industries. The
product in a large degree meets the electric market requirement and has been highly praised by customers.
The company is equipped with the following key manufacturing devices, Switzerland Astronic and Italy
l.a.e. core cutting lines, German Hedrich Vacuum Casting Equipment, Kerosene Vapor-phase Drying
System, Foil Winding Machine, Automatic Insulation Machining Center and so on. The advanced testing
equipments ensure the product well-qualified. Making full use of State Grids superiority, we have
employed some experts in transformer to demonstrate the technology and techniques. On the basis of
digesting and absorbing the advanced technologies at home and abroad, we optimized the design of
transformer to guarantee our products top rank. The close cooperation with Hua Luogeng Applied
Mathematics and Information Science Center of Chinese Academy of Science, Xian Jiaotong University,
Shenyang Transformer Institute reinforces the research and exploitation of long-term tasks and provides
technical reserves for long developments.
For realizing a new leap, the company takes To provide updated electric equipment for the society as its
duty and building permanent enterprise as its strategic ideology. Making full use of Shandong Luneng
Mount Tai Electric Equipment Co., Ltd and State-level Enterprise Technology Center, taking as its future
development orientation the high safety, reliability and environmental-friendliness in UHV electric
equipment, the company set up a modernized electric equipment production base which makes it a large
manufacturing enterprise group.
ISO 9001 Quality Management System ISO 14001 Environmental Management System
KEMA Certificate for 500 kV Product KEMA Certificate for 330 kV Product
KEMA Certificate for 220 kV Product KEMA Certificate for Dry-type Transformer
II. Electric Field Distribution, Magnetic Field Distribution, PDM/CAPP System
1. Electric Field Distribution Analysis
The transformer in operation must withstand the effects of normal working voltage and various
over-voltages. The insulation structure at even electric field can be easily designed by conventional
method, but the partial discharge usually takes place in the influence of uneven electric field
concentration. The finite element analysis of electric field of specific part is performed by A01431A
computational procedure. The partial discharge level reduces effectively by adopting special measures,
which improves electric field distribution.
2. Magnetic Field Distribution Analysis
One of the protruding problems in transformer is the magnetic leakage that not only increases the
transformer losses, but also leads to partial overheating, which has great influence on transformer safety
operation. The finite element analysis of transformer leakage magnetic field is performed by using A1630
computational procedure. Besides, various shielding measures are taken to effectively reduce transformer
on-load loss and prevent possible partial overheating, which ensures the safety operation of transformer.
3. PDM/CAPP System
In order to update the technical management level, the company implements the PDM management
system which helps to establish the powerful digital product R & D collaboration environment and the
reutilizable enterprise repository. The effective product development process management and product
information management are adopted to improve the serialization of product and the generalization and
standardization of parts, shorten the designing cycle and elevate the accuracy and authenticity of the
information transferred between various departments and the cooperation efficiency between different
departments in new product research and development.
III. The Characteristics of Oil-immersed Transformer
On the basis of digesting and absorbing the internal and external advanced technologies, according to the
characteristics of urban and rural power grid in China, the company on itself develops and manufactures
the 66-750 kV oil-immersed transformers whose performance and index are superior to those specified in
GB standards and relevant IEC standards. The transformer has the characteristics of low loss, low noise,
no lifting of core. There are outstanding innovations in the respects of safety, reliability and economy,
which make it first-rate at home. The product mainly has the following characteristics:
1. Remarkable Energy-saving Effect
Compared with the parameters in GB /T6451-1999, the no-load loss reduces by 35% and the on-load loss
reduces by 15%-25%.
2. Transformer Core
The core applies multi-level step-lap craft and the lamination is 45mitered joint holeless binding
structure. The silicon steel is cut by slitting line and cut-to-length line imported from Swiss Astronic. The
burr at the edge is less than 0.01 mm. Additionally the advanced core assembly tilting platform and the
strict assembly techniques with upper yoke non-pre-stacked ensure the grain orientation of the cold rolled
silicon steel and reduce the no-load loss effectively. The adsorption of three-phase five-limb core
structure and plate type clamping structure reduces the stray loss. The use of unique imported polyester
strip binding technique in core clamping ensures the clamping degree of core. Meanwhile, the
well-rounded craft makes sure that the core, drawplate, supporting beam and foot pad to be a firm unit
and that the core is under the optimal pressure state, which reduces the no-load loss as well as noise.
3. Transformer Winding
All transformer windings are wounded on high strength insulation cylinder. The interleaved or
inner-shield structures will be are adopted. The LV winding is wounded by using transposed conductor or
semi-rigid copper conductor, while the HV and MV windings adopt composite conductor wrapped by
high strength Dennison paper which improves the distribution of impulse voltage and reduces the eddy
loss and circular current loss. Special software is used to calculate the impulse characteristics of electric
field of winding, which ensures the reliable electric characteristic and impulse strength of windings and
increases the transformer short circuit withstanding ability. There are auxiliary strips (i.e. reinforcing
strips) inside all the windings and lockable strip outside. The radial clamp of winding is designed
with0tolerence.The adoption of conductor tensile device during winding and unique slanting padding
block in transposed place greatly enhances the mechanical strength and short-circuit withstand ability of
windings.
In addition, all windings are arranged with oil ducts which reduce the winding temperature rise and
prolong their service lives.
Separate regulating winding (for Autotransformer) is used to balance the ampere-turn of each winding,
which improves the stability and prevents deformation. It reduces the axial electromotive force caused by
external short circuit effectively and improves transformers dynamic stability.
4. Active Part Insulation
The active part assembly and coil winding are carried out in a fully sealed, constant temperature and
pressure workshop which ensures that the partial discharge level is less than IEC recommended value and
meets the cleanness and constant humidity requirements for manufacturing 1000 KV power transformer.
At the same time, the large kerosene vapor-phase drying device is applied to decrease the water content in
insulating pieces below 0.4% and improve the cleanness. The lower supporting plate and upper pressing
plate of active part adopt electric laminating paperboard with high mechanical strength and outstanding
electric performance. All strips and blocks will be subjected to sealing pressure treatment twice to reduce
partial discharge.
The steel clamps and steel pressing nails have sufficient strength and the pressing nail bowl of paper pulp
insulation is used to support the blocks, strips and pressing nails, to balance the force on winding and
improve the stability of active part. The active part makes use of integral assembly and constant pressure
drying technique to shorten the time of active part assembly after stabilization treatment.
5. Leads
The HV and MV tapping leads are fixed by bracket and brought to tap changer, while the LV lead copper
busbar is fixed on the upper surface between core clamp and lower tank, which improves the stability of
the lead. The outlet of winding and welded part of lead will be subjected to roundness treatment which
helps to improve the requirement of low partial discharge.
6. Tank
The tank applies bell-type structure. The table-flap type stiffener or plate type stiffener is welded on tank
wall, which increases the mechanical strength of tank (withstand vacuum 0.100 kPa, positive pressure100
kPa). Special machining will be done on sealed parts of tank, and the shot-blast treatment will be
conducted on tank body in order to clear away the oxide skin of surface and the sharp angles, burrs, and
welding residues generated during machining. The mixed paint with high performance is adopted to
enhance the adhesiveness of paint film and make it good-looking and everlasting .The inner-side of large
transformer tank applies magnetic shielding or copper magnetic composite shielding technology. The
coolers and components are tested by simulating the prevailing atrocious environmental conditions on site
to guarantee the elimination of leakages. All flange faces are machined precisely and equipped with notch
and position-limiting structure. Meanwhile, the oil-resistant, weather-proof, ozone-resistant,
well-qualified nitrile rubber gasket is adopted to avoid leakages. In addition, according the clients
requirements, the sealed weld joint tank rim structure is used during the treatment of bolted connection
between upper tank and lower tank.
The product manufactured by our company has the characteristics of low partial discharge, low noise, low
loss and high reliability, depending on the advancement of science and technology, having the aid of
quality guarantee system, with the strong responsibilities of all working staffs and their pioneer spirit and
highly effective work. All the oil-immersed transformers now in service have no damages and leakages.
Applicable Scope
Standing in the vanguard of technology, grasping the pulse of market, the oil-immersed transformer
manufactured by our company is widely applied in the following industries:
There are power, chemical industry, metallurgy, mining, aerospace base, thermoelectricity,
hydroelectricity, various substations and other aspects.
V. Technical Parameters
1. Technical Parameters for 500 kV Transformer
500KV Three-phase Two-winding Transformer
Standards: GB/1094, GB/T6451, IEC60076
Rated Rated voltage(kV) Loss No-load Short-circuit Mass(t) Overall dimension(mm)
Vector
Type power No-load Load current Impedance Active
HV LV Group Oil Total L W H
(kVA) (kW) (kW) (%) (%) part
13.8;
SFP10-240000/500 240000 105 599.3 0.2 129.1 39.8 199.2 8600 4990 9600
15.75
13.8;15.7
SFP10-300000/500 300000 122.5 705.5 0.2 152.6 47 235.5 9100 5260 10100
5;18
15,75;18;
SFP10-360000/500 360000 140 807.5 0.15 175 54 270 9500 5510 10600
20
525
15,75;18; YNd11 14-16
SFP10-420000/500 420000 550 149.1 858.5 0.15 196.5 60.6 303.1 9850 5730 11000
20
15,75;18;
SFP10-480000/500 480000 164.5 952 0.15 217.1 67 335 10200 6000 11400
20
15,75;18;
SFP10-600000/500 600000 217 1198.5 0.1 256.7 79.2 396 10800 6260 12100
20;24
SFP10-720000/500 720000 18;20;24 252 1377 0.1 294.3 90.8 454 11300 6560 12600
Notes:
1. The parameters above are for references only. Our company reserves the right of modification.
2. Our company could provide products according to clients requirement.
3. The overall dimensions and significant parameters are for the step-down transformer; our company can
provide those parameters for the step-up transformer.
500 kV Single-phase Three-winding Autotransformer with OLTC on MV Line Terminal
Rated Rated voltage (kV) Loss No-load Short Mass(t) Overall dimension
Vector
Type power No-load Load current Impedance Active
HV MV LV Group Oil Total L W H
(kVA) (kW) (kW) (%) (%) part
ODFPSZ10-120000/500 120000 44 212.5 0.2 B-C 63.6 32.3 115.4 6160 5000 9000
15.75;
12
ODFPSZ10-167000/500 167000 5003 2303 35; 52.5 255 0.2 81.5 41.4 147.8 6690 5410 9800
B-H
ODFPSZ10-250000/500 250000 5253 81.25 36; I,ao, Io 73.5 340 0.15 110.3 56 200 7400 5980 10800
34-38
ODFPSZ10-333000/500 333000 5503 % 63; 91 442 0.1 136.8 69.5 248 7950 6430 11700
C-H
66
ODFPSZ10-400000/500 400000 104.6 483.7 0.1 20-22 156.9 79.7 284.5 8400 6730 12100
Notes:
1. The power distributions for HV, MV and LV are 100/100/50 % respectively;
2. The parameters above are for reference only. Our company reserves the right of modification;
3. Our company will provide products according to clients requirements;
4. The overall dimensions and significant parameters are for the step-down transformer; our company
can provide those parameters for the step-up transformer.
ODFPS10-120000/500 120000 42 208 0.2 B-C B-C 61 29.5 110 6100 5000 9000
15.75; 12 12
ODFPS10-167000/500 167000 5003 49 246.5 0.2 77.8 37.8 140.1 6600 5400 9800
2303 35; B-H B-H
ODFPS10-250000/500 250000 5253 I,ao, Io 70 331.5 0.15 105.1 51 189.6 7300 5900 10800
22.5% 36; 34-38 42-46
ODFPS10-333000/500 333000 5503 87 429 0.1 130.4 63.3 235.1 7850 6340 11600
63; 66 C-H C-H
ODFPS10-400000/500 400000 99.5 471.6 0.1 20-22 28-30 149.5 72.5 269.7 8210 6640 12100
Notes:
5. The power distributions for HV, MV and LV are 100/100/50 % respectively;
6. The parameters above are for reference only. Our company reserves the right of modification;
7. Our company will provide products according to clients requirements;
8. The overall dimensions and significant parameters are for the step-down transformer; our company
can provide those parameters for the step-up transformer.
OSFPSZ10-90000/330 90000 44.1 246.5 0.5 55.6 27.3 103 9700 5390 6150
B-H
OSFPSZ10-120000/330 120000 54.6 306 0.5 69 33.9 127.8 10400 5790 6610
330 10.5; 24-26
100/
OSFPSZ10-150000/330 150000 81.25% 11; 64.4 362.1 0.45 B-C 81.5 40.1 151.1 11000 6120 6980
121 YNaod11 100/
OSFPSZ10-180000/330 180000 345 35; 73.5 415.7 0.45 10-11 93.5 45.9 173.3 11500 6410 7310
30
81.25% 38.5 C-H
OSFPSZ10-240000/330 240000 91 516 0.4 116 57 215 12300 6880 7850
12-14
OSFPSZ10-360000/330 360000 123.2 700.4 0.4 157.2 77.3 291.4 13700 7620 8690
Notes:
1. The power distributions for HV, MV and LV are 100/100/30 % respectively;
2. The parameters above are for reference only. Our company reserves the right of modification;
3. Our company will provide products according to clients requirements;
4. The overall dimensions and significant parameters are for the step-down transformer; our company
can provide those parameters for the step-up transformer.
330 kV Three-phase Three-winding Autotransformer with OCTC on Series Winding Terminal
Rated Rated voltage (kV) Loss No-load Short Mass(t) Overall dimension
Vector
Type power No-load Load current Impedance Active
HV MV LV Group Oil Total L W H
(kVA) (kW) (kW) (%) (%) part
OSFPS10-90000/330 90000 44.1 246.5 0.5 55.6 27.3 103 9700 5390 6150
B-H
OSFPS10-120000/330 120000 54.6 306 0.5 69 33.9 127.8 10400 5790 6610
330 10.5; 24-26
100/
OSFPS10-150000/330 150000 81.25% 11; 64.4 362.1 0.45 B-C 81.5 40.1 151.1 11000 6120 6980
121 YNaod11 100/
OSFPS10-180000/330 180000 345 35; 73.5 415.7 0.45 10-11 93.5 45.9 173.3 11500 6410 7310
30
81.25% 38.5 C-H
OSFPS10-240000/330 240000 91 516 0.4 116 57 215 12300 6880 7850
12-14
OSFPS10-360000/330 360000 123.2 700.4 0.4 157.2 77.3 291.4 13700 7620 8690
Notes:
1. The power distributions for HV, MV and LV are 100/100/30 % respectively;
2. The parameters above are for reference only. Our company reserves the right of modification;
3. Our company will provide products according to clients requirements;
4. The overall dimensions and significant parameters are for the step-down transformer; our company
can provide those parameters for the step-up transformer.
3. Technical Parameters for 220 kV Transformer
220 kV Two-winding Transformer with OCTC
Rated voltage
Rated Loss No-load Short Mass(t) Overall dimension
(kV) Vector
Type power current Impedance Gauge (mm)
Group No-load Load Active
(kVA) HV LV (%) (%) Oil Total L W H
(kW) (kW) part
SFP10-50000/220 50000 36.4 178.5 0.28 43.6 23.9 82.5 7800 4710 6740 20002000
SFP10-63000/220 63000 43.4 208.0 0.27 51.5 25.0 96.0 7810 4720 6780 20002000
SFP10-90000/220 90000 57.4 272.0 0.25 67.3 26.2 125.1 7820 4750 6830 1435/22000
220/ 10.5;
SFP10-120000/220 120000 70.0 327.0 0.23 89.5 27.5 150.5 8030 4790 7690 1435/22000
242 11;
SFP10-150000/220 150000 Ynd11 84.0 282.0 0.20 12-14 96.0 28.6 160.3 9370 4840 7710 1435/22000
2 13.8;
SFP10-180000/220 180000 95.9 433.0 0.20 109.2 29.2 172.3 10700 5010 7790 1435/22000
2.5% 15.75
SFP10-240000/220 240000 119.0 535.0 0.15 122.7 32.3 184.5 12010 5160 7850 1435/22000
SFP10-300000/220 300000 140.0 637.0 0.15 134.5 34.5 196.7 13100 5320 7910 1435/22000
SFP10-360000/220 360000 161.0 731.0 0.15 147.8 37.3 209.5 13980 5570 7990 1435/22000
Notes:
1. According to the requirement, the vector group can be YNd11 or others;
2. The parameters above are for reference only. Our company reserves the right of modification;
3. Our company will provide products according to clients requirements;
4. The overall dimensions and significant parameters are for the step-down transformer; our company
can provide those parameters for the step-up transformer.
SFPZ`-50000/220 50000 39.9 178.5 0.26 8090 4680 6840 7800 4710 6740 20002000
SFPZ-63000/220 63000 47.6 208.0 0.24 8150 4710 6860 7810 4720 6780 20002000
220 10.5;
SFPZ-90000/220 90000 8 11; 61.6 272.0 0.22 8280 4790 6910 7820 4750 6830 1435/22000
Ynd11 12-14
SFPZ-120000/220 120000 1.25 35; 74.9 327.0 0.20 8615 4910 7650 8030 4790 7690 1435/22000
% 38.5
SFPZ-150000/220 150000 86.6 282.0 0.18 9940 4930 7720 9370 4840 7710 1435/22000
SFPZ-180000/220 180000 100.8 442.0 0.15 11280 5020 7810 10700 5010 7790 1435/22000
Notes:
1. According to the requirement, HV can use other different values;
2. The parameters above are for reference only. Our company reserves the right of modification;
3. Our company will provide products according to clients requirements;
4. The overall dimensions and significant parameters are for the step-down transformer; our company
can provide those parameters for the step-up transformer.
SFPSZ-50000/220 50000 46.2 212.0 0.26 52.5 32.9 92.7 7860 5050 5620 20002000
HV-MV
SFPSZ-63000/220 63000 53.9 246.0 0.24 60.4 34.5 103.4 8780 5150 6020 20002000
220 10.5; 12-14
SFPSZ-90000/220 90000 8 69 11; YNyn 70.0 331.1 0.22 HV-LV 80.0 38.3 135.2 10620 5590 7070 1435/22000
SFPSZ-120000/220 120000 1.25 121 35; 0d11 85.4 408.0 0.20 22-24 102.2 42.9 173.3 11080 5820 7420 1435/22000
% 38.5 MV-LV
SFPSZ-150000/220 150000 100.1 484.0 0.18 123.8 44.0 199.8 11730 5910 7550 1435/22000
7-9
SFPSZ-180000/220 180000 115.5 595.0 0.15 139.9 46.3 231.6 12380 6140 7600 1435/22000
Notes:
1. The power distributions of HV, MV and LV windings are 100/100/50% respectively;
2. According to clients requirement, HV can use other different values;
3. The parameters above are for reference only. Our company reserves the right of modification;
4. Our company will provide products according to clients requirements;
5. The overall dimensions and significant parameters are for the step-down transformer; our company
can provide those parameters for the step-up transformer.
SFP-50000/220 50000 220/ 10.5; YNd11 36.4 178.5 0.28 12-14 43.6 23.9 82.5 7800 4710 6740 20002000
242 11;
SFP-63000/220 63000 43.4 208.0 0.27 51.5 25.0 96.0 7810 4750 6780 20002000
2 13.8
SFP-90000/220 90000 57.4 272.0 0.25 67.3 26.2 125.1 7820 4750 6830 1435/22000
2.5% 15.75
SFP-120000/220 120000 70.0 327.0 0.23 89.5 27.5 150.5 8030 4790 7690 1435/22000
SFP-150000/220 150000 84.0 382.0 0.20 96.0 28.6 160.3 9370 4840 7710 1435/22000
SFP-180000/220 180000 95.9 433.0 0.20 109.2 29.2 172.3 10700 5010 7790 1435/22000
SFP-240000/220 240000 119.0 535.0 0.15 122.7 32.3 184.5 12010 5160 7850 1435/22000
SFP-300000/220 300000 140.0 637.0 0.15 134.5 34.5 194.7 13100 5320 7910 1435/22000
SFP-360000/220 360000 161.0 731.0 0.15 147.8 37.3 209.5 13980 5570 7990 1435/22000
Notes:
1. According to the requirement, HV can use other different values;
2. The parameters above are for reference only. Our company reserves the right of modification;
3. Our company will provide products according to clients requirements;
4. The overall dimensions and significant parameters are for the step-down transformer; our company
can provide those parameters for the step-up transformer.
SFPS-50000/220 50000 42.0 212.0 0.26 50.5 21.9 86.4 5650 5010 5200 20002000
SFPS-63000/220 63000 10.5; 49.7 246.0 0.24 HV-MV 58.8 22.9 97.0 6420 5120 5610 20002000
220/ 11; 12-14
SFPS-90000/220 90000 64.4 331.0 0.22 78.3 27.2 129.1 8410 5570 6690 1435/22000
242 69 13.8 YNyn HV-LV
SFPS-120000/220 120000 79.1 408.0 0.20 101.2 31.3 165.4 10650 5830 7440 1435/22000
2 121 15.75 0d11 22-24
SFPS-150000/220 150000 93.1 484.0 0.18 120.3 37.7 196.6 11200 5950 7540 1435/22000
2.5% 35; MV-LV
SFPS-180000/220 180000 38.5 106.4 552.0 0.15 7-9 138.9 42.2 226.9 11690 6150 7570 1435/22000
SFPS-240000/220 240000 130.9 680.0 0.15 157.1 47.0 257.5 12190 6360 7820 1435/22000
Notes:
1. The power distributions of HV, MV and LV windings are 100/100/50% respectively;
2. According to clients requirement, the vector group can be Ynd11 or others;
3. According to clients requirement, the MV can use other different values;
4. The parameters above are for reference only. Our company reserves the right of modification;
5. The overall dimensions and significant parameters are for the step-down transformer; our company
can provide those parameters for the step-up transformer.
Notes:
1. The power distributions of HV, MV and LV windings are 100/100/50% respectively;
2. According to clients requirement, the MV can use other different values;
3. The parameters above are for reference only. Our company reserves the right of modification;
4. The overall dimensions and significant parameters are for the step-down transformer; our company
can provide those parameters for the step-up transformer.
HV-MV 1435/220
SFSZ-120000/220 120000 85.4 408.0 0.20 93.5 38 177 9100 7000 7260
12-14 00
220 11;
69 YNyn HV-LV 1435/220
SFSZ-150000/220 150000 8 35; 100.1 484.0 0.18 114.5 48 213.9 9300 7100 7460
121 0d11 22-24 00
2.5% 38.5
MV-LV 1435/220
SFSZ-180000/220 180000 115.5 595.0 0.15 121 53 221.9 9800 7250 7600
7-9 00
Notes:
1. The power distributions of HV, MV and LV windings are 100/100/50% respectively;
2. According to clients requirement, the MV can use other different values;
3. The parameters above are for reference only. Our company reserves the right of modification;
4. The overall dimensions and significant parameters are for the step-down transformer; our company
can provide those parameters for the step-up transformer.
SSZ-120000/220 120000 220 69 11; YNyn 85.4 408.0 0.20 HV-MV 99.5 41 187.6 9500 7200 7260 1435/22000
8 121 35; 0d11 12-14 1000
SSZ-150000/220 150000 100.1 484.0 0.18 121 51 226.7 7300 7460 1435/22000
1.25 38.5 HV-LV 0
% 22-24
SSZ-180000/220 180000 115.5 595.0 0.15 MV-LV 128 56 235.2 105 7400 7600 1435/22000
7-9
Notes:
1. The power distributions of HV, MV and LV windings are 100/100/50% respectively;
2. According to clients requirement, the MV can use other different values;
3. The parameters above are for reference only. Our company reserves the right of modification;
4. The overall dimensions and significant parameters are for the step-down transformer; our company
can provide those parameters for the step-up transformer.
HV-MV
SFSZ-120000/220 120000 85.4 408.0 0.20 93.5 38 177 9100 7000 7260 1435/22000
220 12-14
11;
SFSZ-150000/220 150000 8 69 YNyn 100.1 484.0 0.18 HV-LV 114.5 48 213.9 9300 7100 7460 1435/22000
35;
1.25 121 0d11 22-24
38.5
% MV-LV
SFSZ-180000/220 180000 115.5 595.0 0.15 121 53 221.9 9800 7250 7600 1435/22000
7-9
Notes:
1. The power distributions of HV, MV and LV windings are 100/100/50% respectively;
2. According to clients requirement, the MV can use other different values;
3. The parameters above are for reference only. Our company reserves the right of modification;
4. The overall dimensions and significant parameters are for the step-down transformer; our company
can provide those parameters for the step-up transformer.
H-M
2208 23.5 38603300
SFPSZ10-H-120000/220 YNyn0d11 H-L 0.20 90 405 336.5 345
1.25%/115/35 8.0 3460
M-L
H-M 14.2
2208 24803380
SFPSZ10-H-150000/220 YNyn0d11 H-L 0.18 104 405 24.0 344.0 352+54
1.25%/121/10.5 3620
M-L 7.8
Notes:
1. According to the requirement, the vector group can be YNd11 or others;
2. The parameters above are for reference only. Our company reserves the right of modification;
3. Our company will provide products according to clients requirements;
4. The overall dimensions and significant parameters are for the step-down transformer; our company
can provide those parameters for the step-up transformer.
2202 34202790
SSP-H-120000/220 YNd11 H-L 0.20 86 340 13.0 336.5 342.5
2.5%/13.8 3350
2202 32002670
SSP-H-100000/220 YNd11 H-L 0.23 79 306 13.2 330 337.2
2.5%/13.8 3160
Notes:
1. According to the requirement, the vector group can be YNd11 or others;
2. The parameters above are for reference only. Our company reserves the right of modification;
3. Our company will provide products according to clients requirements;
4. The overall dimensions and significant parameters are for the step-down transformer; our company
can provide those parameters for the step-up transformer.
4. Technical Parameters for 110 kV Transformer
SSZ10Three-phase Three-winding Transformer with OLTC
Standards: GB/1094, GB/T6451, IEC60076
Rated Rated voltage (kV) Loss No-load Short Mass(kg) Overall dimension
Vector Gauge
power No-load Load current Impeda
HV MV LV Group Oil Total L(mm) W(mm) H (mm) (mm)
(kVA) (kW) (kW) (%) nce (%)
16000 16.8 90.1 0.42 HV-MV 13800 50700 6980 4970 4810 1475
6.3 10.5
20000 110/121 19.8 106.3 0.40 14300 53200 7140 5130 4760 /
35 6.6 YNyn HV-LV
25000 8 22.2 125.8 0.38 15800 60100 7160 5300 4970 2040
38.5 10.5 0d11 17-18
31500 1.25% 27.7 148.8 0.36 17600 69100 7320 5390 5050
11 MV-LV
40000 33.0 178.5 0.36 6.5 21100 83200 7420 5580 5390
6300 110/121 35 6.3 YNyn 8.4 45.1 0.52 HV-MV 8100 28100 6740 4270 4380
8000 8 38.5 6.6 0d11 9.9 53.6 0.51 10.5 9200 31600 6770 4280 4430
1.25% 10.5 HV-LV
10000 11.8 62.9 0.50 10100 34200 6770 4440 4540
11 17-18
12500 13.6 74.0 0.48 11400 39500 6880 4760 4680
MV-LV
16000 16.8 90.1 0.42 6.5 12600 44800 6980 4600 4810 1475
25000 22.2 125.8 0.38 13400 53700 7160 4760 4970 2040
Notes:
1. The power distributions of HV, MV and LV windings are 100/100/100 respectively;
2. According to the requirement, the connection symbol can be Ynd11y10;
3. According to clients requirement, MV can use other different values;
4. The maximum current tapping can be in the tap position -5;
5. The overall dimensions and significant parameters are for the step-down transformer; our company
can provide those parameters for the step-up transformer;
6. The parameters above are for reference only. Our company reserves the right of modification;
7. According to clients requirement, our company can change the series number of the product.
16000 15.6 90.1 0.41 HV-MV 9700 36900 6210 4540 4850 1475
6.3 10.5
20000 18.8 106.3 0.38 10900 42100 6390 4580 4930 /
110/121 35 6.6 YNyn HV-LV
25000 21.6 125.8 0.35 11400 46100 6520 4620 5110 2040
22.5% 38.5 10.5 0d11 17-18
31500 25.6 148.8 0.33 12800 52100 6570 4710 4980
11 MV-LV
40000 29.8 178.5 0.32 6.5 14900 60800 6690 5040 5390
Notes:
1. The power distributions of HV, MV and LV windings are 100/100/100 respectively;
2. According to the requirement, the connection symbol can be Ynd11y10;
3. According to clients requirement, MV can use other different values;
4. The maximum current tapping can be in the tap position -10;
5. The parameters above are for reference only. Our company reserves the right of modification;
6. According to clients requirement, our company can change the series number of the product.
16000 15.6 90.1 0.41 HV-MV 9500 36400 6110 4440 4820 1475
6.3 10.5
20000 18.8 106.3 0.38 10800 41800 6290 4480 4910 /
110/121 35 6.6 YNyn HV-LV
25000 21.6 125.8 0.35 11300 45900 6470 4520 5100 2040
22.5% 38.5 10.5 0d11 17-18
31500 25.6 148.8 0.33 12600 51700 6590 4610 4950
11 MV-LV
40000 29.8 178.5 0.32 6.5 14700 60200 6750 4840 5340
Notes:
1. The power distributions of HV, MV and LV windings are 100/100/100 respectively;
2. According to the requirement, the connection symbol can be Ynd11y10;
3. According to clients requirement, MV can use other different values;
4. The maximum current tapping can be in the tap position -5;
5. The overall dimensions and significant parameters are for the step-down transformer; our company
can provide those parameters for the step-up transformer;
6. The parameters above are for reference only. Our company reserves the right of modification;
7. According to clients requirement, our company can change the series number of the product.
16000 14.00 73.1 0.41 7500 27760 5100 3300 4900 1475
6.3
20000 16.5 88.4 0.40 HV-LV 7610 29000 5400 3500 5000 /
110/121 6.6
25000 YNd11 19.2 104.6 0.38 10.5 7700 35000 5700 3700 5000 2040
22.5% 10.5
31500 23.0 125.8 0.36 8040 40680 5070 4195 4895
11
40000 27.8 147.9 0.34 8110 45800 5335 4125 5425
Notes:
1. According to the requirement, the connection symbol can be Ynd11y10;
2. The maximum current tapping can be in the tap position -10;
3. The parameters above are for reference only. Our company reserves the right of modification;
4. According to clients requirement, our company can change the series number of the product.
25000 21.1 104.6 0.40 10055 40580 6010 4385 5550 2040
Notes:
1. According to the requirement, the connection symbol can be Ynd11y10;
2. The maximum current tapping can be in the tap position -10;
3. The parameters above are for reference only. Our company reserves the right of modification;
4. According to clients requirement, our company can change the series number of the product.
5. Technical Parameters of 66 kV Transformer
S10 Series 66 kV Two-winding Transformer with OCTC
Standards: GB/1094, GB/T6451, IEC60076
Rated Rated voltage (kV) Loss No-load Short Mass(kg) Overall dimension
Vector Gauge
power No-load Load current Impedance
HV MV LV Group Oil Total L(mm) W(mm) H (mm) (mm)
(kVA) (kW) (kW) (%) (%)
16000 13.6 73.1 0.43 7150 26500 4900 3290 5000 1475
6.3
20000 16.8 88.4 0.41 7250 27700 5000 3200 4800 /
66/69 6.6 0.5
25000 YNd11 19.8 104.6 0.40 7350 33500 5300 3400 4900 2040
22.5% 10.5
31500 22.2 125.8 0.38 8610 38750 5300 3800 5300
11
40000 27.7 147.9 0.36 7750 43700 5500 4100 5410
Notes:
1. According to the requirement, the connection symbol can be Ynd11y10;
2. The parameters above are for reference only. Our company reserves the right of modification;
3. According to clients requirement, our company can change the series number of the product.
10000 66/69 6.3 YNd11 10.8 50.2 0.47 0.5 6700 21950 5100 3200 4200
81.25% 6.6
12500 12.8 59.5 0.45 7250 26580 5500 3500 4310
10.5
16000 15.4 73.1 0.43 8060 29500 5710 3550 4250 1475
11
20000 18.2 88.4 0.42 8570 33500 5780 3750 4500 /
25000 21.1 104.6 0.40 9580 38700 5910 4200 4950 2000
Notes:
1. According to the requirement, the connection symbol can be Ynd11y10;
2. The parameters above are for reference only. Our company reserves the right of modification;
3. According to clients requirement, our company can change the series number of the product.
6. Technical Parameters of 35 kV Transformer
SZ9 Series 35 kV Power Transformer with OLTC
Standards: GB/1094, GB/T6451, IEC60076
Rated voltage (kV) Loss Mass(kg) Overall dimension
Rated No-load Short
HV Vector Gauge
power No-load Load current Impeda Active
HV Tapping LV Group Oil Total L(mm) W(mm) H (mm) (mm)
(kVA) (kW) (kW) (%) nce (%) Part
Range
2000 2.25 19.12 0.85 6.5 2620 1680 5750 3095 2285 2710 1070
2500 2.67 20.52 0.82 3695 2370 8070 3205 2500 2810 1000
7.0
3150 3.19 24.56 0.76 3825 2455 8600 3695 2340 2920 1070
Yd11
4000 3.85 28.98 0.74 4550 2450 9680 3250 2530 2950 1070
5000 4.55 34.00 0.72 6025 3215 12305 3565 2555 3200 1070
6300 6.3 5.46 36.55 0.70 6800 2885 12610 3520 3050 3110 1475
7.5
35 22.5 6.6
8000 7.70 40.37 0.63 8050 3380 14515 3770 3250 3200 1475
38.5 % 10.5
10000 9.10 47.77 0.60 9670 3920 18300 4420 3290 3340 1475
11
12500 10.71 56.52 0.59 12310 4910 22110 4620 3730 3540 1475
16000 12.89 68.02 0.56 13185 5665 25200 4820 3790 3600 1475
YNd11 8.0
20000 25.24 80.41 0.51 15800 5750 26200 5210 3840 3840 1475
25000 18.17 93.55 0.50 19800 7400 33100 5200 4000 4200 1475
31500 21.43 113.05 0.49 24670 9790 41980 5220 4210 4310 2040
Notes:
1. Our company can provide the gauge according to clients requirement;
2. The parameters above are for reference only. Our company reserves the right of modification.
10000 35 22.5 6.3 YNd11 8.26 45.05 0.43 7.5 9520 4620 18880 3630 3590 3700 1475
38.5 % 10.5
12500 9.80 53.55 0.42 10610 5340 24000 3750 3760 3705 1475
11
16000 11.90 65.45 0.41 12610 6750 28600 4480 3840 3765 1475
20000 14.07 79.05 0.40 15700 7985 33000 4630 3900 3850 1475
25000 16.73 93.50 0.34 8.0 18000 9650 36800 4930 4100 4195 1475
31500 19.95 112.20 0.32 19800 10790 42000 5180 4200 4350 2040
40000 23.86 134.22 0.27 28300 11660 43100 5250 4250 4435 20410
Notes:
1. Our company can provide the gauge according to clients requirement;
2. The parameters above are for reference only. Our company reserves the right of modification.
100 0.24 1.92 1.53 420 410 1100 1165 900 1870 660
125 0.27 2.25 1.48 450 435 1245 1265 1080 1950
160 0.29 2.68 1.40 650 465 1470 1310 1080 1970
200 0.34 3.15 1.31 680 510 1510 1350 1100 1980
250 0.40 3.74 1.19 720 540 1615 1400 1120 2040
35 5% 0.4 Yyn0 6.5
315 0.48 4.51 1.16 1010 565 2010 1640 1130 2080
400 0.57 5.44 1.10 1055 620 2170 1720 1140 2120 820
500 0.68 6.55 1.08 1120 720 2565 2030 1160 2160
630 0.81 7.82 1.06 1560 810 2980 2070 1220 2240
800 0.97 9.35 0.89 1650 940 3680 2220 1260 2340 1070
1000 1.16 11.48 0.85 1750 1080 4490 2370 1290 2440
1250 1.37 13.86 0.72 2015 1170 4860 2390 1340 2580
1600 1.66 16.58 0.63 2150 1260 5580 2430 1420 2620
Notes:
1. Our company can provide the gauge according to clients requirement;
2. The parameters above are for reference only. Our company reserves the right of modification.
7. Technical Parameters of 10 kV Transformer
S11 Series 10 kV Distribution Transformer with OCTC
Standards: GB/1094, GB/T6451, IEC60076
Rated voltage (kV) Loss Mass(kg) Overall dimension
Rated No-load Short
HV Vector Gauge
power No-load Load current Impeda Active
HV Tapping LV Group Oil Total L(mm) W(mm) H (mm) (mm)
(kVA) (W) (W) (%) nce (%) Part
Range
100 205 1500 0.48 315 110 550 1130 830 1320
125 240 1800 0.45 420 170 640 1340 830 1420
160 280 2200 0.42 515 190 860 1380 835 1480
200 340 2600 0.39 520 195 860 1400 960 1485 300
250 390 3050 0.36 640 205 970 1410 990 1495 400
6 4/4.5 550
315 5% 0.4 Yyn0 470 3650 0.33 720 210 1190 1400 1040 1580
10 660
400 560 4300 0.30 900 240 1445 1470 1030 1730
820
500 670 5100 0.30 1200 350 1800 1670 1210 1750 1070
630 840 6200 0.27 1370 425 2265 2070 1300 1785
800 980 7500 0.24 1535 442 2486 1990 1320 1839
1000 1190 10300 0.21 1740 520 3100 2100 1300 1950
1250 1365 12800 0.18 1975 575 3275 2300 1310 2030
1600 1680 14500 0.18 2360 705 3935 2300 1340 2130
2000 1985 17170 0.39 2915 720 4730 2125 1705 2550
2500 2347 20263 0.30 5 3560 1790 6200 2390 2560 2650
Notes:
1. Our company can provide the gauge according to clients requirement;
2. The parameters above are for reference only. Our company reserves the right of modification.
800 1.12 8.42 1.02 1450 520 2670 2040 1275 1855 820
6
1000 1.32 9.86 0.93 1720 590 2995 2150 1350 1965 820
6.3 3
1250 1.56 11.73 0.85 2100 645 3540 2080 1420 2190 820
10 3.15
1600 1.88 14.03 0.76 2510 930 4475 2125 1533 2280 820
10.5 6.3
5% Yd11 5.5
2000 11 2.24 16.83 0.76 3170 1105 5820 2560 2170 2470 1070
2500 2.64 19.55 0.68 3720 1295 6350 2670 2195 2590 1070
3150 3.12 22.95 0.68 4355 1370 7285 2490 2340 2660 1070
4000 10 3.84 27.20 0.59 5155 1750 8685 2480 2970 2400 1070
3.15
5000 10.5 4.56 31.20 0.59 6050 2150 10760 2935 3175 2980 1070
6.3
6300 11 5.44 34.85 0.51 7010 2580 12790 3250 3445 3150 1070
Notes:
1. Our company can provide the gauge according to clients requirement;
2. The parameters above are for reference only. Our company reserves the right of modification.
200 0.38 2.89 1.53 4 580 285 1150 1625 850 1490 550
250 0.46 3.40 1.44 690 335 1430 1735 1030 1510 660
315 0.54 4.08 1.36 795 390 1685 1830 1050 1620 660
400 0.65 4.93 1.27 935 423 1848 1870 1090 1740 660
500 6 0.78 5.87 1.19 1200 467 2321 1970 1180 1740 660
42.5
630 6.3 0.4 Yyn0 0.99 7.23 1.10 1380 539 2728 2125 1210 1790 820
%
10
800 1.21 8.84 1.02 1650 627 2986 2305 1310 1875 820
4.5
1000 1.42 10.37 0.93 1930 760 3215 2425 1380 1940 820
1250 1.66 12.33 0.85 2260 795 3760 2550 1400 2230 820
1600 2.13 14.71 0.76 3650 965 4535 2550 1440 1445 820
2000 2.56 17.39 0.68 3050 1095 5420 2560 2130 2445 820
Notes:
1. Our company can provide the gauge according to clients requirement;
2. The parameters above are for reference only. Our company reserves the right of modification.
VII. Railway Traction Transformer
The Characteristics of Railway Traction Transformer
On the basis of digesting and absorbing the advanced technology in and out of China, according to the
characteristics of the national railway electrification reconstruction, the company develops the traction
transformer itself. The performance and index of the traction transformer have the superiority over the
technical parameters and specification stated in GB standard and relevant IEC 60076 standards. The
transformer complies with the required characteristics of railway electrification which include low loss,
low noise, no leakage, free-of-maintenance, high short circuit withstand ability, high over-load ability and
low impedance. The product has the following characteristics
1. Core of transformer
The core is laminated with the HI-B cold-rolled grain-oriented silicon sheet steel exported from Japan.
The silicon sheet steel is cut by Astronic Core Cutting Machine exported from Switzerland, the use of
which makes sure that the burr at the edge of cutting is less than 0.01 mm. The application of advanced
core reversal platform and the non-stacking upper yoke technique ensure the grain orientation of the
cold-rolled silicon sheet steel and reduce the no-load loss effectively. The plate type clamp is used for
clamping core limbs with polyester belt, which improves the tightening of core and makes the core under
the best stress withstand condition. This not only reduces the no-load loss, but also the noise level.
2. Winding of transformer
The windings of transformer are wounded around the high-strength insulation cylinder. In order to
improve the short circuit withstanding ability of transformer, all spacers and strips will be subjected to
roundness treatment. Outside the winding, the lockable strips will be provided; inside the winding, the
auxiliary strips will be provided. All windings are subjected to lacquer dipping and solidification
treatment. The axial pressing stress of winding is strictly controlled according to the technique
requirement. After compressing, electromagnetic center height of each winding remains in the same level
and relevant winding disc will be strictly controlled according to the requirement of ampere-turn balance
to minimize the axial force and conductor stress under the state of short circuit. To meet the high
over-load requirement of railway power supply during short circuit, the winding will be designed with
low current density and expanded oil duct with 0 tolerance for radial tightening, which greatly
improves the mechanical strength and short circuit withstanding ability of winding. Besides, the oil
guiding structures are arranged inside HV and LV windings, which reduce the winding hot spot
temperature rise and prolong its service life.
3. Active Part Insulation
The active part assembly and coil winding are carried out in a fully sealed, constant temperature and
pressure workshop which meets the requirement of cleanness and constant humidity requirements for
manufacturing 1000 KV power transformer. At the same time, the large kerosene vapor-phase drying
device is applied to decrease the water content in insulating pieces and improve the cleanness. The lower
supporting plate and upper pressing plate of active part adopt electric laminating paperboard with high
mechanical strength and outstanding electric performance. All strips and blocks will be subjected to
sealing pressure treatment twice to reduce partial discharge.
The steel clamps and steel pressing nails have sufficient strength and the pressing nail bowl of paper pulp
insulation is used to support the blocks, strips and pressing nails, to balance the force on winding and
improve the stability of active part. The active part makes use of integral assembly and constant pressure
drying technique to shorten the time of active part assembly after stabilization treatment. The
concentricity of each winding will be regulated to make the magnetic center in consistence with each
other, which guarantees that the stress on winding is equally distributed to improve the short circuit
withstanding ability of winding.
4. Tank
The bell type tank will be adopted. The use of large press brake makes the corrugation much easier, which
avoids the use of iron stiffener, improves the mechanical strength of the tank, reduces the welding seams
and improves the radiating effectiveness of main body. Special treatment which will be conducted to the
sealed parts of the tank and complete shot-blast treatment to tank will helps to clean all sharp angles,
burrs and welding slag to improve the adhesiveness of paint and make the tank good-looking and
everlasting. The radiators and other accessories will be tested by simulating the abominable ambient
conditions on site to eliminate leakages. All flange faces are machined precisely and equipped with notch
and position-limiting structure. Meanwhile, the oil-resistant, weather-proof, ozone-resistant,
well-qualified nitrile rubber gasket is adopted to avoid leakages.
5. Cooler and Auxiliary Devices
Generally speaking, the transformer is designed to be ONAF type. When the fan motor starts, the
transformer is operated under the state of full load; when the fan motor stops for natural cooling, the load
can be 67% of full load. According to clients requirement, the transformer can also be designed to be
ONAN type with the ONAF conditions reserved.
The panel type radiator will be compactly and properly arranged with fan motor fixed on bracket to
reduce the shock of radiator.
The conservator will be rubber bladder type with oil-resistant, airtight rubber bladder installed inside,
which ensures that the air and oil dont contact directly and realizes the complete sealing. Besides, the
expansion type conservator made of stainless steel which has the characteristics of free of maintenance
and reliable operation can also be used.
Applicable Scope
The railway traction transformer manufactured by our company is extensively used in various new-built
electrified railway and railway electrification reconstruction. It is applied the conditions of tempestuous
load fluctuation of electrified railway and frequent external short circuit. It is also applied to various
special environments such as high temperature, low temperature, heavy pollution, high plateau and so on.
1. It is applicable to AT power supply which simplifies the main connection of traction transformer;
2. The autotransformer at the exit of substation will be left out, which reduces the losses of circuit and
input of devices.
3. The voltage of 220 kV (110 kV) will be reduced to 27.5 kV directly for traction locomotive.
4. The capacity of transformer can be fully used;
5. The working voltage of feeder switch is reduced, which not only reduces investment, but also
improves the reliability of power supply.
6. The transformer will be recommended to be used when the capacity of power grid is big enough and
the effect of single-phase operation to power grid can be ignored.
Notes:
1. The above product can be manufactured as highland type; our company can also provide the product
with other capacities;
2. The parameters above are for reference only. Our company reserves the right of modification;
110 kV Single-phase Traction Transformer
Rated Voltage (kV) Loss (kW) Short Mass(kg) Overall Dimension (mm)
Rated
No-load circuit Vector Gauge
Power Active
HV LV No-load Load Current impedance Group Oil Total L W H (mm)
(kVA) Part
(%)
31500 22 112 0.45 24960 12260 49650 4750 4900 4800 14351435
Notes:
1. The above product can be manufactured as highland type; our company can also provide the product
with other capacities;
2. The parameters above are for reference only. Our company reserves the right of modification;
10000 12.5 59 0.9 13300 8900 31800 5430 2905 4030 1475
20000 20.0 104 0.6 10.5 22290 10600 39900 6260 3620 4670
2040
25000 11022.5% 27.5 25.0 123 0.55 YNA 26350 11200 47200 6320 3920 4835
31500 29.0 148 0.50 8.4 38500 12200 53000 6450 4130 5040
40000 35.0 174 0.45 46060 13600 66000 6600 4320 5200
50000 41.0 316 0.40 54450 17200 73000 6830 4500 5400
63000 50.0 260 0.35 64750 19800 86000 6990 4880 5600
Notes:
1. The above product can be manufactured as highland type; our company can also provide the product
with other capacities;
2. The parameters above are for reference only. Our company reserves the right of modification;
110 kV VV0 Connected Railway Traction Transformer
Short Overall Dimension
Rated Voltage (kV) Loss (kW) Mass(kg)
Rated Power No-load circuit Vector (mm) Gauge
10000+10000 19.5 110 0.7 21330 11080 44350 5700 4600 4800
10000+12500 21.3 120 0.7 23300 12100 48450 5800 4730 4920
Notes:
1. The above product can be manufactured as highland type; our company can also provide the product
with other capacities;
2. The parameters above are for reference only. Our company reserves the right of modification;
20000 20. 99 0.5 10.5 17250 7150 31870 5700 3300 4950
25000 110 27.5 24 117 0.45 YNd11 18030 8170 33060 5500 4100 4950
31500 28 141 0.4 8.4 21760 10150 39500 5600 4100 4950
14352000
40000 34 165 0.35 30500 15870 59200 5700 4500 5250
Notes:
1. The above product can be manufactured as highland type; our company can also provide the product
with other capacities;
2. The parameters above are for reference only. Our company reserves the right of modification;
VIII. Main Components for Transformer
1. Rubber Bladder Type Conservator with Tubular OLI or Pointer Type Oil Gauge
The oil level indicator is provided with contacts of highest oil level and lowest oil level. According to
clients requirement, the metallic expansion type conservator can also be equipped.
2. Dehydrating Breather
Its used for absorbing the moisture in the air, and it should be dried and exchanged according to its
situations.
3. Gas Relay
The gas relay used for transformer main body has two kinds of contact, one for alarming and the other for
tripping, of which the tripping loop can be connected in parallel or in series. The gas relay for OLTC only
has tripping contact
Insulation level: L175/-; AC28(35)/3 Protection level: IP00, IP20, IP23, or others
Parameter List
Rated Losses (W) No-load LP Impedance Overall Dimension (mm) Total
Power Current dB Voltage Mass
No-load Load L LI H W
(kVA) (%) (A) (%) (Kg)
315 880 3470 1.8 45 1195 660 1170 1100 1400
400 980 3990 1.8 45 1195 660 1240 1200 1550
4
500 1160 4880 1.8 45 1255 660 1310 1200 1830
630 1340 5870 1.6 45 1300 820 1385 1200 2120
630 1300 5960 1.6 45 1390 820 1385 1200 1910
800 1520 6950 1.6 50 1450 820 1350 1200 1340
1000 1770 8130 1.4 50 1520 820 1410 1200 2760
1250 2090 9690 1.4 50 6 1570 820 1525 1200 3480
1600 2450 11730 1.4 50 1615 1070 1688 1400 4000
2000 3320 14450 1.2 50 1810 1070 1596 1400 4870
2500 4000 17170 1.2 50 1900 1070 1670 1400 5850
3150 4300 22900 1.2 50 2020 1070 1820 1600 6700
Note:
The overall dimension doesnt include on-load tap changer.
SC(B)10 Series 10 kV Distribution Transformer with OCTC
Product Standards: GB/T10228; GB6450; IEC726; DIN42523
Parameter List
Rated Losses (W) No-load LP Impedance Overall Dimension (mm) Total
Power Current dB Voltage Mass
No-load Load L LI H W
(kVA) (%) (A) (%) (Kg)
30 190 710 3.2 45 880 550 815 1000 330
50 270 1000 2.8 45 880 550 970 1000 480
63 360 1200 2.7 45 880 550 1015 1000 510
80 370 1380 2.6 45 980 550 1030 1000 590
100 400 1570 2.4 45 980 550 1030 1000 640
125 470 1840 2.2 45 980 550 1145 1000 760
160 540 2130 2.2 45 4 1135 550 1019 1000 950
200 620 2530 2.0 45 1000 550 1185 1000 1000
250 720 2750 2.0 45 1135 550 1225 1000 1226
315 880 3470 1.8 45 1195 660 1170 1100 1400
400 980 3990 1.8 45 1195 660 1240 1200 1550
500 1160 4880 1.8 45 1255 660 1310 1200 1830
630 1340 5870 1.6 45 1300 820 1385 1200 2120
630 1300 5960 1.6 45 1390 820 1385 1200 1910
800 1520 6950 1.6 50 1450 820 1350 1200 1340
1000 1770 8130 1.4 50 1520 820 1410 1200 2760
1250 2090 9690 1.4 50 6 1570 820 1525 1200 3480
1600 2450 11730 1.4 50 1615 1070 1688 1400 4000
2000 3320 14450 1.2 50 1810 1070 1596 1400 4870
2500 4000 17170 1.2 50 1900 1070 1670 1400 5850
3150 4300 22900 1.2 50 2020 1070 1820 1600 6700
Note:
The data above are used for choosing the type and design of equipment.
Parameter List
Rated Losses (W) No-load LP Impedance Overall Dimension (mm) Total
Power Current dB Voltage Mass
No-load Load L LI H W
(kVA) (%) (A) (%) (Kg)
30 360 1050 3.2 45 1250 550 1210 750 530
50 480 1270 3.2 45 1335 660 1110 750 680
80 650 1750 3.2 45 1410 660 1280 750 980
100 700 2300 2.0 45 1410 660 1280 750 1020
125 760 2440 2.0 45 1440 660 1270 750 1130
160 860 2800 2.0 45 1520 660 1500 1100 1280
200 960 3050 2.0 45 1520 660 1580 1100 1400
250 1080 3500 2.0 45 1520 660 1680 1100 1500
315 1160 4170 2.0 45 1520 660 1732 1100 2000
400 1560 5360 2.0 45 1560 660 1660 1000 2155
500 1800 6590 2.0 45 6 1710 820 1605 1200 2400
630 1840 7680 1.8 45 1830 820 1775 1200 3150
800 2160 9100 1.8 50 1920 820 2070 1200 3600
1000 2400 10460 1.8 50 1920 820 2210 1400 4675
1250 2800 12670 1.6 50 2050 820 2040 1400 5200
1600 3200 15390 1.6 50 2085 1070 2300 1400 7240
2000 3760 18110 1.4 50 2085 1070 2350 1400 7330
2500 4400 21680 1.4 50 2130 1070 2484 1400 8200
Note:
The data above are used for choosing the type and design of equipment.
Parameter List
Rated Losses (W) No-load LP Impedance Overall Dimension (mm) Total
Power Current dB Voltage Mass
No-load Load L LI H W
(kVA) (%) (A) (%) (Kg)
800 2230 9350 1.9 50 1920 820 1900 1200 2000
1000 2460 10880 1.9 50 6 1920 820 1940 1200 2500
1250 3100 12840 1.7 50 2050 820 2040 1200 3200
1600 3650 15390 1.7 50 2200 1070 2020 1400 4500
2000 4200 18110 1.5 50 2290 1070 2280 1400 5800
2500 4800 21680 1.5 50 7 2290 1070 2370 1400 7600
3150 6000 24400 1.3 60 3050 1070 2370 1400 8700
4000 6960 29330 1.3 60 2800 1070 2600 1400 11370
5000 8320 34770 1.1 65 8 2700 1070 2370 1400 12935
6300 9840 40630 1.1 65 3120 1070 2850 1400 16000
8000 11200 45050 1 70 3180 1070 2950 1400 17800
10000 12800 55250 1 70 3160 2040 2920 2160 20500
12500 16800 56220 0.8 75 9 3480 2040 2850 2160 31250
16000 20000 62740 0.8 80 3980 2040 3200 2160 38000
20000 23750 73290 0.8 80 3980 2040 3360 3290 42000
10
25000 28500 88120 0.5 80 4220 2040 3390 2160 45000
Notes:
1. The data above are just for reference;
2. Our company can provide other products according to clients requirement;
3. Our company reserves the right to modify the parameters stated.
Rated HV: 35, 38.5 kV Rated LV: 3.15, 6, 6.3, 10, 10.5, 11 kV
Tapping Range: 42.5% , or others Connection symbol: Yd11 or Ynd11 or others
Insulation level: L1170/-; AC70/3 Protection level: IP00, IP20, IP23, or others
Parameter List
Rated Losses (W) No-load LP Impedance Overall Dimension (mm) Total
Power Current dB Voltage Mass
No-load Load L LI H W
(kVA) (%) (A) (%) (Kg)
315 1160 4170 2.0 45 1520 660 1732 1100 2000
400 1360 5360 2.0 45 1560 660 1660 1000 2155
500 1600 6590 2.0 45 1710 820 1605 1200 2400
630 1840 7680 1.8 45 1830 820 1775 1200 3150
800 2160 9100 1.8 50 1920 820 2070 1200 3600
6
1000 2400 10460 1.8 50 1920 820 2210 1400 4675
1250 2800 12670 1.6 50 2050 820 2040 1400 5200
1600 3200 15390 1.6 50 2085 1070 2300 1400 7240
2000 3760 18110 1.4 50 2085 1070 2350 1400 7330
2500 4400 21680 1.4 50 2130 1070 2484 1400 8200
Notes:
1. The overall dimension doesnt include on-load tap changer.
2. The on-load tap changer can be divided into air type and vacuum type. When placing the order, please
indicate which type will be used;
3. When placing the order, please indicate the installation position of on-load tap changer;
4. The data above are just for reference;
5. Our company can provide other products according to clients requirement;
6. Our company reserves the right to modify the parameters stated.
Rated HV: 35, 38.5 kV Rated LV: 3.15, 6, 6.3, 10, 10.5, 11 kV
Parameter List
Rated Losses (W) No-load LP Impedance Overall Dimension (mm) Total
Power Current dB Voltage Mass
No-load Load L LI H W
(kVA) (%) (A) (%) (Kg)
800 2230 9350 1.9 50 1920 820 1900 1200 2000
1000 2460 10880 1.9 50 6 1920 820 1940 1200 2500
1250 3100 12840 1.7 50 2050 820 2040 1200 3200
1600 3650 15390 1.7 50 2200 1070 2020 1400 4500
2000 4200 18110 1.5 50 2290 1070 2280 1400 5800
2500 4800 21680 1.5 50 7 2290 1070 2370 1400 7600
3150 6000 24400 1.3 60 3050 1070 2370 1400 8700
4000 6960 29330 1.3 60 2800 1070 2600 1400 11370
5000 8320 34770 1.1 65 8 2700 1070 2370 1400 12935
6300 9840 40630 1.1 65 3120 1070 2850 1400 16000
8000 11200 45050 1 70 3180 1070 2950 1400 17800
10000 12800 55250 1 70 3160 2040 2920 2160 20500
12500 16800 56220 0.8 75 9 3480 2040 2850 2160 31250
16000 20000 62740 0.8 80 3980 2040 3200 2160 38000
20000 23750 73290 0.8 80 3980 2040 3360 3290 42000
25000 28500 88120 0.5 80 10 4220 2040 3390 2160 45000
Notes:
1. The overall dimension doesnt include on-load tap changer.
2. The on-load tap changer can be divided into air type and vacuum type. When placing the order, please
indicate which type will be used;
3. When placing the order, please indicate the installation position of on-load tap changer;
4. The data above are just for reference;
5. Our company can provide other products according to clients requirement;
6. Our company reserves the right to modify the parameters stated.
X Manufacturing and Testing Equipments
Manufacturing Equipments
Dept. Equipment Manufacturer Specification Quantity
Digital Control Insulation
Japan HEIAN ER-131PMC 1 pcs
Manufacturing Center
Shenyang Shenjing
Impregnating Curing
Water-supply Equipment QQ-1600 2 pcs
System
Plant
Juli Company with
Vertical Winding Machine JLM200 6pcs
Winding German Technology
Workshop Horizontal Winding Juli Company with
JWM160 20pcs
Machine German Technology
Wound core winding Shanghai Tongli Electric
JTR-1 2pcs
machine Equipment plant
Pressure Charter America ENPACK PUT1201E 2pcs
Ningbo HaiYue Electric
Curing oven HB-2 2pcs
Company
Qingdao Double Star
Sandblasting Equipment QL2630 1set
Group
Wuxi Compressor
Screw Compressors LGFD-12/8-X 2pcs
Company
Digital Flame Cutting
Tank MESSER Company COMCUT 2pcs
Machine
Workshop
Electrostatic Spraying Shandong Blue Arrow
JT-360 1set
Systems Technologies
Blasting Painting System Qingdao Huaqing Group QH2-800 1set
Corrugated Tank Xian Kai Yuen Electrical
BWYX-1300 1pcs
Production Line Equipment Company
Assembling Switzerland Shear Line Swiss ASTRONIC 1000mm 1pcs
Workshop Core Shear Line Italy l.a.e Company TE60 1pcs
German GEORGE
Core Shear Line 800mm 1pcs
Company
Xian Kai Yuen Electrical
Roller Trimming XBJ1-05/05 2pcs
Equipment Company
Cold welding clamp German KLAUKE PK12040C 2pcs
Core balers America ENERPAC VT-19 2pcs
Dual-Beam Bridge Type Finland KONECRANES
250/50T 2pcs
Crane Company
Dual-Beam Bridge Type German DEMAG
50/16T 4pcs
Crane Company
Pressure Changing Type Shenyang Tianyi
Vacuum Drying Vacuum Technology ZGB- 6pcs
Equipment Company
Shenyang Youbang
Kerosene Vapor Drying
Vacuum Company with VPD-300 2pcs
Equipment
German Technology
Vacuum Oil Purifying
Sweden ABB Company VH060 1pcs
Machine
Vacuum Oil Purifying
Sweden ABB Company VH040 1pcs
Machine
German HEDRICH
Vacuum Casting Device PEK-150/150 2pcs
Company
Foil-around Machine France B.R. Company FBR-1200 2pcs
Dry-tranform
Double-layer foil winding Xian Kai Yuen Electrical
er workshop BRJ-1400 2pcs
machine Equipment Company
Ningbo HaiYue Electric
Curing oven HB-2 6pcs
Company
Server HP HPML370G3 4pcs
laser printer HP HP3300 2pcs
Technical
Color Laser Printer HP HP8550 1pcs
Dept.
Graphics Printer / / 4pcs
Computer Lenovo / 80pcs
Testing Equipments
No Equipment Type Qty Use Manufacturer
No-load, load
15000kVA Harbin Electrical
1 Frequency generator 1 set and temperature
50Hz .3kV Machinery Plant
rise test
Non-PD IF generator Induced and PD Harbin Electrical
2 750kVA 200Hz 3kV 1set
sets test Machinery Plant
Wuhan High
Impulse voltage
3 4000kV 600kJ 1set Lightning Voltage Research
generator
Impulse test Institute
4 peak voltage meter TDS3012B 1pcs U.S. NI Company
Compensation 189 Compensation Beijing capacitor
5 BMF-12.5-150-1W
capacitor pcs test plant
Induction Voltage
6 TSA-1000 1pcs Yingkou Tebian
Regulator
Intermediate LuNeng Mount
7 10000kVA/40 1pcs
transformer Tai
Dandong
Performance test
8 CT HL28 60kV 3pcs transformer
factory
Dandong
9 PT HJ12 60kV 3pcs transformer
factory
Insulation Resistance Insulation Wuhan Kangda
10 KD2677 2pcs
Tester Characteristics Company
Photoconductive
Dielectric loss
11 dielectric loss tester GW-2A 2pcs Baoding Jin Di's
measurement
computer
Power frequency
Power frequency Jiangsu Leiyu
12 YD-1000/500 1pcs voltage
voltage machine Company
withstand test
Automatic Variable Voltage Ratio
13 ZBY-111 1pcs Wuhan test
Ratio Tester Test
DC Resistance
14 DC Resistance Tester JD2510 3pcs Baoding Jin Di's
Test
Ningxia
On-load tap-changer On-load tap Electronic
15 5535 1pcs
Tester changer test Instrument
Factory
Wuhan High
Power Harmonics No-load current
16 DSC-1 1pcs Voltage Research
Meter harmonic
Institute
Broadband Power
17 D6000T 1pcs Swiss LEM
Analyzer
Performance test
Transformer Baoding Huibang
18 HB2810A 1pcs
characteristics tester Co
Jiangxi Hongan
19 Sound Level Meter HS5670 1pcs Sound level test
CO.
Swiss Harvalad
20 PD instrument JFD-2B 1pcs PD test
company
Winding deformation Winding Shandong Power
21 RZBX-1 1pcs
Instrument deformation test Design Institute
Chromatographic Chromatographi
22 SP3420 1pcs CN-US Co.
analyzer c analyze
XI Product Quality Guarantee and After-sale Service Commitment
The company persists in the tenet of "To supply updated electrical equipment for the society ". The
company has strong technical force, advanced manufacturing facilities, perfect testing devices, excellent
product quality control system and it has passed the ISO9001 quality certificate in 2000.
For the success in the furious competition in the market and meeting customers' demand, the company
adheres to the market orientation and focuses on the customer. It has been highly praised by the customer
with its quick response, excellent services and well-qualified products.
Our company solemnly declares to all customers:
The product's lifetime is no less than 30 years.
On receiving the bidding documents, we will evaluate the product according to the technical specification.
After signing contract, technicians will be organized to analyze the technical specification in time and all
the requirements will be brought into effect one by one.
We will select qualified subcontractor of components, and we will strictly carry out the quality control
and inspection for raw material and components according to requirements of quality system.
Based on the principle of being responsible for customer, we require all the subcontractors of components
to produce well-qualified products according to end-user's contract and technical specification.
For the fittings selected by clients, we will provide all corresponding technical conditions and documents
in agreement with customer's requirement.
All performance indexes and technical parameters of the transformer will completely meet and be
superior to National standards and IEC standards.
All key parts with quality defects occurred during manufacturing and inconsistent with contract or
technical specification will be repaired or replaced unconditionally. We will firstly solve all the quality
problems taken place during installation to meet the requirements of project schedule, and then we will
analyze the responsibilities.
The customer is welcomed to witness the manufacture and test of products during manufacture and we
shall provide all conveniences.
We will provide best after-sale services and guide installation and debugging of the transformer freely.
Receiving client's requirements, our serving staffs will arrive at the site within the shortest time.
Our company has established mature periodic return visit system. We will send the writing questionnaire
or visit the site at regular intervals.
Service Hotline:
Telephone0086-538-8639963 Fax0086-538-8639891
Contact person:
Name: Mi Jianmeng Job Title: Service Engineer