Shandong Luneng Mount Tai Electric Equipment Co., Ltd.

I. Company Profile

Shandong Luneng Mount Tai Electric Equipment Co., Ltd is located in the Hi-tech Development Zone in
Taian and occupies an area of 300,000 square meters. The company has four subsidiary companies; they
are Shandong Luneng Cable Co., Ltd, Taian Taishan Electric Co., Ltd, Taishan High-voltage Switchgear
Co., Ltd, Xintiancheng Electric Co., Ltd. It is a professional manufacturer of power transformer, power
cable and gas insulated switch and other electric equipments. It has the State-level Enterprise Technology
Center and possesses the authority of import and export. It has been granted the following honors: Key
Transformer Manufacturer for Power Grid Company of China, High-and-new Technology Enterprise of
State Ministry of Science and Technology, State-level Contract-keeping and Credit-abiding Enterprise,
Key Enterprise of Shandong Province, Enterprise with AAA Credit, Member of The Catalogue of
Recommended Enterprises in the Building and Rebuilding of Urban and Rural Power Grid of China,
Member of China Petrifaction Equipment Suppliers, Key Recommended Enterprise of
Electro-mechanical Equipment for Hydroelectric Projects and so on. In 2003, the companys technical
innovation plan of traction transformer was listed in the plan of the State Torch Program. The 500 kV
oil-immersed power transformer and dry type transformer of the company have been given the honors of
Quality Trustworthy Product, Satisfactory Product for Client, Shandong Famous Brand. The low
loss oil-immersed power transformers up to 220 kV and resin-casting transformers up to 35 kV have been
awarded Free-of-check Product in Shandong Province. In 2000, the company has passed certificates of
the ISO9001 Quality Management System and ISO14001 Environmental Management System and the
CPCCC Product Certificate of State Electric Energy. Meanwhile, the 500kV, 330kV and 220 kV
transformers manufactured by the company have passed the Holland KEMA test certificates
The main products manufactured by the company can be divided into eight voltage classes: 750 kV, 500
kV, 330 kV, 220 kV, 110 kV, 66 kV, 35 kV and 10 kV. All together there are 18 series and more than 1196
different kinds of power transformers as well as special transformers like traction transformer. The
company independently investigated and designed 35-750 kV power transformer, combined transformer,
railway balance transformer, rectifier transformer, furnace transformer and resin-casting dry type
transformer, 252 kV gas insulated switch (GIS), breaker, isolated switch and so on. Many new products
have passed the state and province appraisal and keep ahead in power transformer industry. The products
are sold all over the country, such as Beijing, Shanghai, Tianjin, Guangdong, Jiangsu, and Shandong and
so on. So far, the oversea markets for the company are growing gradually, the products have been sold to
Russia, India, Vietnam, Syria, UAE Dubai, Tanzania, Zambia ect. They are mainly applied in power
supply, water conservancy, railway, metallurgy, petroleum, chemical industry and other industries. The
product in a large degree meets the electric market requirement and has been highly praised by customers.
The company is equipped with the following key manufacturing devices, Switzerland Astronic and Italy
l.a.e. core cutting lines, German Hedrich Vacuum Casting Equipment, Kerosene Vapor-phase Drying
System, Foil Winding Machine, Automatic Insulation Machining Center and so on. The advanced testing
equipments ensure the product well-qualified. Making full use of State Grids superiority, we have
employed some experts in transformer to demonstrate the technology and techniques. On the basis of
digesting and absorbing the advanced technologies at home and abroad, we optimized the design of
transformer to guarantee our products top rank. The close cooperation with Hua Luogeng Applied
Mathematics and Information Science Center of Chinese Academy of Science, Xian Jiaotong University,
Shenyang Transformer Institute reinforces the research and exploitation of long-term tasks and provides
technical reserves for long developments.
For realizing a new leap, the company takes To provide updated electric equipment for the society as its
duty and building permanent enterprise as its strategic ideology. Making full use of Shandong Luneng
Mount Tai Electric Equipment Co., Ltd and State-level Enterprise Technology Center, taking as its future
development orientation the high safety, reliability and environmental-friendliness in UHV electric
equipment, the company set up a modernized electric equipment production base which makes it a large
manufacturing enterprise group.

ISO 9001 Quality Management System ISO 14001 Environmental Management System

KEMA Certificate for 500 kV Product KEMA Certificate for 330 kV Product

KEMA Certificate for 220 kV Product KEMA Certificate for Dry-type Transformer
II. Electric Field Distribution, Magnetic Field Distribution, PDM/CAPP System
1. Electric Field Distribution Analysis
The transformer in operation must withstand the effects of normal working voltage and various
over-voltages. The insulation structure at even electric field can be easily designed by conventional
method, but the partial discharge usually takes place in the influence of uneven electric field
concentration. The finite element analysis of electric field of specific part is performed by A01431A
computational procedure. The partial discharge level reduces effectively by adopting special measures,
which improves electric field distribution.
2. Magnetic Field Distribution Analysis
One of the protruding problems in transformer is the magnetic leakage that not only increases the
transformer losses, but also leads to partial overheating, which has great influence on transformer safety
operation. The finite element analysis of transformer leakage magnetic field is performed by using A1630
computational procedure. Besides, various shielding measures are taken to effectively reduce transformer
on-load loss and prevent possible partial overheating, which ensures the safety operation of transformer.
3. PDM/CAPP System
In order to update the technical management level, the company implements the PDM management
system which helps to establish the powerful digital product R & D collaboration environment and the
reutilizable enterprise repository. The effective product development process management and product
information management are adopted to improve the serialization of product and the generalization and
standardization of parts, shorten the designing cycle and elevate the accuracy and authenticity of the
information transferred between various departments and the cooperation efficiency between different
departments in new product research and development.
III. The Characteristics of Oil-immersed Transformer

On the basis of digesting and absorbing the internal and external advanced technologies, according to the
characteristics of urban and rural power grid in China, the company on itself develops and manufactures
the 66-750 kV oil-immersed transformers whose performance and index are superior to those specified in
GB standards and relevant IEC standards. The transformer has the characteristics of low loss, low noise,
no lifting of core. There are outstanding innovations in the respects of safety, reliability and economy,
which make it first-rate at home. The product mainly has the following characteristics:
1. Remarkable Energy-saving Effect
Compared with the parameters in GB /T6451-1999, the no-load loss reduces by 35% and the on-load loss
reduces by 15%-25%.
2. Transformer Core
The core applies multi-level step-lap craft and the lamination is 45mitered joint holeless binding
structure. The silicon steel is cut by slitting line and cut-to-length line imported from Swiss Astronic. The
burr at the edge is less than 0.01 mm. Additionally the advanced core assembly tilting platform and the
strict assembly techniques with upper yoke non-pre-stacked ensure the grain orientation of the cold rolled
silicon steel and reduce the no-load loss effectively. The adsorption of three-phase five-limb core
structure and plate type clamping structure reduces the stray loss. The use of unique imported polyester
strip binding technique in core clamping ensures the clamping degree of core. Meanwhile, the
well-rounded craft makes sure that the core, drawplate, supporting beam and foot pad to be a firm unit
and that the core is under the optimal pressure state, which reduces the no-load loss as well as noise.
3. Transformer Winding
All transformer windings are wounded on high strength insulation cylinder. The interleaved or
inner-shield structures will be are adopted. The LV winding is wounded by using transposed conductor or
semi-rigid copper conductor, while the HV and MV windings adopt composite conductor wrapped by
high strength Dennison paper which improves the distribution of impulse voltage and reduces the eddy
loss and circular current loss. Special software is used to calculate the impulse characteristics of electric
field of winding, which ensures the reliable electric characteristic and impulse strength of windings and
increases the transformer short circuit withstanding ability. There are auxiliary strips (i.e. reinforcing
strips) inside all the windings and lockable strip outside. The radial clamp of winding is designed
with0tolerence.The adoption of conductor tensile device during winding and unique slanting padding
block in transposed place greatly enhances the mechanical strength and short-circuit withstand ability of
windings.
In addition, all windings are arranged with oil ducts which reduce the winding temperature rise and
prolong their service lives.
Separate regulating winding (for Autotransformer) is used to balance the ampere-turn of each winding,
which improves the stability and prevents deformation. It reduces the axial electromotive force caused by
external short circuit effectively and improves transformers dynamic stability.
4. Active Part Insulation
The active part assembly and coil winding are carried out in a fully sealed, constant temperature and
pressure workshop which ensures that the partial discharge level is less than IEC recommended value and
meets the cleanness and constant humidity requirements for manufacturing 1000 KV power transformer.
At the same time, the large kerosene vapor-phase drying device is applied to decrease the water content in
insulating pieces below 0.4% and improve the cleanness. The lower supporting plate and upper pressing
plate of active part adopt electric laminating paperboard with high mechanical strength and outstanding
electric performance. All strips and blocks will be subjected to sealing pressure treatment twice to reduce
partial discharge.
The steel clamps and steel pressing nails have sufficient strength and the pressing nail bowl of paper pulp
insulation is used to support the blocks, strips and pressing nails, to balance the force on winding and
improve the stability of active part. The active part makes use of integral assembly and constant pressure
drying technique to shorten the time of active part assembly after stabilization treatment.
5. Leads
The HV and MV tapping leads are fixed by bracket and brought to tap changer, while the LV lead copper
busbar is fixed on the upper surface between core clamp and lower tank, which improves the stability of
the lead. The outlet of winding and welded part of lead will be subjected to roundness treatment which
helps to improve the requirement of low partial discharge.
6. Tank
The tank applies bell-type structure. The table-flap type stiffener or plate type stiffener is welded on tank
wall, which increases the mechanical strength of tank (withstand vacuum 0.100 kPa, positive pressure100
kPa). Special machining will be done on sealed parts of tank, and the shot-blast treatment will be
conducted on tank body in order to clear away the oxide skin of surface and the sharp angles, burrs, and
welding residues generated during machining. The mixed paint with high performance is adopted to
enhance the adhesiveness of paint film and make it good-looking and everlasting .The inner-side of large
transformer tank applies magnetic shielding or copper magnetic composite shielding technology. The
coolers and components are tested by simulating the prevailing atrocious environmental conditions on site
to guarantee the elimination of leakages. All flange faces are machined precisely and equipped with notch
and position-limiting structure. Meanwhile, the oil-resistant, weather-proof, ozone-resistant,
well-qualified nitrile rubber gasket is adopted to avoid leakages. In addition, according the clients
requirements, the sealed weld joint tank rim structure is used during the treatment of bolted connection
between upper tank and lower tank.
The product manufactured by our company has the characteristics of low partial discharge, low noise, low
loss and high reliability, depending on the advancement of science and technology, having the aid of
quality guarantee system, with the strong responsibilities of all working staffs and their pioneer spirit and
highly effective work. All the oil-immersed transformers now in service have no damages and leakages.

IV. The Characteristics of Combinable Transformer


The oil-immersed combinable transformer manufactured by our company is developed on the basis of
digesting and absorbing the advanced technology at home and abroad and aiming at the atrocious
landform and difficult transportation of the mountainous area in the country. The product is composed of
three single transformers sharing one set of cooling system and oil preservation system. Besides, it has the
characteristics of compact external structure, small floor coverage. The dimension and mass of a single
transformer are greatly reduced, which brings convenience to transportation.
1. Transformer Core
The core applies single phase structure, with one main limb and two side limbs. The multi-level step-lap
craft and the 45 mitered joint holeless binding structures for lamination are adopted.
2. Leads
The HV, MV and LV leads can be Y connected inside the tank, they can also be connected outside
for the convenience of client. The lead is calculated by field strength analysis. The application of
reasonable shielding measure greatly reduces the partial discharge. The joint of lead is cold welded,
which guarantees the cleanness, good-looking, firmness and reliability of the transformer.
3. Tank
Three single bell type tanks are employed. The table-flapped iron stiffener or plate stiffener is welded on
tank wall to improve the mechanical strength of the tank. When dealing with the bolted connection
between upper tank and lower tank, the tank rim can be sealed with solder according to clients
requirement.

Applicable Scope
Standing in the vanguard of technology, grasping the pulse of market, the oil-immersed transformer
manufactured by our company is widely applied in the following industries:
There are power, chemical industry, metallurgy, mining, aerospace base, thermoelectricity,
hydroelectricity, various substations and other aspects.

V. Technical Parameters
1. Technical Parameters for 500 kV Transformer
500KV Three-phase Two-winding Transformer
Standards: GB/1094, GB/T6451, IEC60076
Rated Rated voltage(kV) Loss No-load Short-circuit Mass(t) Overall dimension(mm)
Vector
Type power No-load Load current Impedance Active
HV LV Group Oil Total L W H
(kVA) (kW) (kW) (%) (%) part

13.8;
SFP10-240000/500 240000 105 599.3 0.2 129.1 39.8 199.2 8600 4990 9600
15.75

13.8;15.7
SFP10-300000/500 300000 122.5 705.5 0.2 152.6 47 235.5 9100 5260 10100
5;18

15,75;18;
SFP10-360000/500 360000 140 807.5 0.15 175 54 270 9500 5510 10600
20
525
15,75;18; YNd11 14-16
SFP10-420000/500 420000 550 149.1 858.5 0.15 196.5 60.6 303.1 9850 5730 11000
20

15,75;18;
SFP10-480000/500 480000 164.5 952 0.15 217.1 67 335 10200 6000 11400
20

15,75;18;
SFP10-600000/500 600000 217 1198.5 0.1 256.7 79.2 396 10800 6260 12100
20;24

SFP10-720000/500 720000 18;20;24 252 1377 0.1 294.3 90.8 454 11300 6560 12600

Notes:
1. The parameters above are for references only. Our company reserves the right of modification.
2. Our company could provide products according to clients requirement.
3. The overall dimensions and significant parameters are for the step-down transformer; our company can
provide those parameters for the step-up transformer.
500 kV Single-phase Three-winding Autotransformer with OLTC on MV Line Terminal
Rated Rated voltage (kV) Loss No-load Short Mass(t) Overall dimension
Vector
Type power No-load Load current Impedance Active
HV MV LV Group Oil Total L W H
(kVA) (kW) (kW) (%) (%) part

ODFPSZ10-120000/500 120000 44 212.5 0.2 B-C 63.6 32.3 115.4 6160 5000 9000
15.75;
12
ODFPSZ10-167000/500 167000 5003 2303 35; 52.5 255 0.2 81.5 41.4 147.8 6690 5410 9800
B-H
ODFPSZ10-250000/500 250000 5253 81.25 36; I,ao, Io 73.5 340 0.15 110.3 56 200 7400 5980 10800
34-38
ODFPSZ10-333000/500 333000 5503 % 63; 91 442 0.1 136.8 69.5 248 7950 6430 11700
C-H
66
ODFPSZ10-400000/500 400000 104.6 483.7 0.1 20-22 156.9 79.7 284.5 8400 6730 12100

Notes:
1. The power distributions for HV, MV and LV are 100/100/50 % respectively;
2. The parameters above are for reference only. Our company reserves the right of modification;
3. Our company will provide products according to clients requirements;
4. The overall dimensions and significant parameters are for the step-down transformer; our company
can provide those parameters for the step-up transformer.

500 kV Single-phase Three-winding Autotransformer with OCTC on MV Line Terminal


Rated Rated voltage (kV) Loss No-load Short Mass(t) Overall dimension
Vector
Type power No-load Load current Impedance Active
HV MV LV Group Oil Total L W H
(kVA) (kW) (kW) (%) (%) part

ODFPS10-120000/500 120000 42 208 0.2 B-C B-C 61 29.5 110 6100 5000 9000
15.75; 12 12
ODFPS10-167000/500 167000 5003 49 246.5 0.2 77.8 37.8 140.1 6600 5400 9800
2303 35; B-H B-H
ODFPS10-250000/500 250000 5253 I,ao, Io 70 331.5 0.15 105.1 51 189.6 7300 5900 10800
22.5% 36; 34-38 42-46
ODFPS10-333000/500 333000 5503 87 429 0.1 130.4 63.3 235.1 7850 6340 11600
63; 66 C-H C-H
ODFPS10-400000/500 400000 99.5 471.6 0.1 20-22 28-30 149.5 72.5 269.7 8210 6640 12100

Notes:
5. The power distributions for HV, MV and LV are 100/100/50 % respectively;
6. The parameters above are for reference only. Our company reserves the right of modification;
7. Our company will provide products according to clients requirements;
8. The overall dimensions and significant parameters are for the step-down transformer; our company
can provide those parameters for the step-up transformer.

2. Technical Parameters for 330 kV Transformer


330 kV Three-phase Three-winding Autotransformer with OLTC on Series Winding Terminal
Rated Rated voltage (kV) Loss No-load Short Mass(t) Overall dimension
Vector
Type power No-load Load current Impedance Active
HV MV LV Group Oil Total L W H
(kVA) (kW) (kW) (%) (%) part

OSFPSZ10-90000/330 90000 44.1 246.5 0.5 55.6 27.3 103 9700 5390 6150
B-H
OSFPSZ10-120000/330 120000 54.6 306 0.5 69 33.9 127.8 10400 5790 6610
330 10.5; 24-26
100/
OSFPSZ10-150000/330 150000 81.25% 11; 64.4 362.1 0.45 B-C 81.5 40.1 151.1 11000 6120 6980
121 YNaod11 100/
OSFPSZ10-180000/330 180000 345 35; 73.5 415.7 0.45 10-11 93.5 45.9 173.3 11500 6410 7310
30
81.25% 38.5 C-H
OSFPSZ10-240000/330 240000 91 516 0.4 116 57 215 12300 6880 7850
12-14
OSFPSZ10-360000/330 360000 123.2 700.4 0.4 157.2 77.3 291.4 13700 7620 8690

Notes:
1. The power distributions for HV, MV and LV are 100/100/30 % respectively;
2. The parameters above are for reference only. Our company reserves the right of modification;
3. Our company will provide products according to clients requirements;
4. The overall dimensions and significant parameters are for the step-down transformer; our company
can provide those parameters for the step-up transformer.
330 kV Three-phase Three-winding Autotransformer with OCTC on Series Winding Terminal
Rated Rated voltage (kV) Loss No-load Short Mass(t) Overall dimension
Vector
Type power No-load Load current Impedance Active
HV MV LV Group Oil Total L W H
(kVA) (kW) (kW) (%) (%) part

OSFPS10-90000/330 90000 44.1 246.5 0.5 55.6 27.3 103 9700 5390 6150
B-H
OSFPS10-120000/330 120000 54.6 306 0.5 69 33.9 127.8 10400 5790 6610
330 10.5; 24-26
100/
OSFPS10-150000/330 150000 81.25% 11; 64.4 362.1 0.45 B-C 81.5 40.1 151.1 11000 6120 6980
121 YNaod11 100/
OSFPS10-180000/330 180000 345 35; 73.5 415.7 0.45 10-11 93.5 45.9 173.3 11500 6410 7310
30
81.25% 38.5 C-H
OSFPS10-240000/330 240000 91 516 0.4 116 57 215 12300 6880 7850
12-14
OSFPS10-360000/330 360000 123.2 700.4 0.4 157.2 77.3 291.4 13700 7620 8690

Notes:
1. The power distributions for HV, MV and LV are 100/100/30 % respectively;
2. The parameters above are for reference only. Our company reserves the right of modification;
3. Our company will provide products according to clients requirements;
4. The overall dimensions and significant parameters are for the step-down transformer; our company
can provide those parameters for the step-up transformer.
3. Technical Parameters for 220 kV Transformer
220 kV Two-winding Transformer with OCTC
Rated voltage
Rated Loss No-load Short Mass(t) Overall dimension
(kV) Vector
Type power current Impedance Gauge (mm)
Group No-load Load Active
(kVA) HV LV (%) (%) Oil Total L W H
(kW) (kW) part

SFP10-50000/220 50000 36.4 178.5 0.28 43.6 23.9 82.5 7800 4710 6740 20002000

SFP10-63000/220 63000 43.4 208.0 0.27 51.5 25.0 96.0 7810 4720 6780 20002000

SFP10-90000/220 90000 57.4 272.0 0.25 67.3 26.2 125.1 7820 4750 6830 1435/22000
220/ 10.5;
SFP10-120000/220 120000 70.0 327.0 0.23 89.5 27.5 150.5 8030 4790 7690 1435/22000
242 11;
SFP10-150000/220 150000 Ynd11 84.0 282.0 0.20 12-14 96.0 28.6 160.3 9370 4840 7710 1435/22000
2 13.8;
SFP10-180000/220 180000 95.9 433.0 0.20 109.2 29.2 172.3 10700 5010 7790 1435/22000
2.5% 15.75
SFP10-240000/220 240000 119.0 535.0 0.15 122.7 32.3 184.5 12010 5160 7850 1435/22000

SFP10-300000/220 300000 140.0 637.0 0.15 134.5 34.5 196.7 13100 5320 7910 1435/22000

SFP10-360000/220 360000 161.0 731.0 0.15 147.8 37.3 209.5 13980 5570 7990 1435/22000

Notes:
1. According to the requirement, the vector group can be YNd11 or others;
2. The parameters above are for reference only. Our company reserves the right of modification;
3. Our company will provide products according to clients requirements;
4. The overall dimensions and significant parameters are for the step-down transformer; our company
can provide those parameters for the step-up transformer.

220 kV Two-winding Power Transformer with OLTC


Rated voltage
Rated Loss No-load Short Mass(t) Overall dimension
(kV) Vector
Type power current Impedance Gauge (mm)
Group No-load Load Active
(kVA) HV LV (%) (%) Oil Total L W H
(kW) (kW) part

SFPZ`-50000/220 50000 39.9 178.5 0.26 8090 4680 6840 7800 4710 6740 20002000

SFPZ-63000/220 63000 47.6 208.0 0.24 8150 4710 6860 7810 4720 6780 20002000
220 10.5;
SFPZ-90000/220 90000 8 11; 61.6 272.0 0.22 8280 4790 6910 7820 4750 6830 1435/22000
Ynd11 12-14
SFPZ-120000/220 120000 1.25 35; 74.9 327.0 0.20 8615 4910 7650 8030 4790 7690 1435/22000
% 38.5
SFPZ-150000/220 150000 86.6 282.0 0.18 9940 4930 7720 9370 4840 7710 1435/22000

SFPZ-180000/220 180000 100.8 442.0 0.15 11280 5020 7810 10700 5010 7790 1435/22000

Notes:
1. According to the requirement, HV can use other different values;
2. The parameters above are for reference only. Our company reserves the right of modification;
3. Our company will provide products according to clients requirements;
4. The overall dimensions and significant parameters are for the step-down transformer; our company
can provide those parameters for the step-up transformer.

220 kV Three-winding Power Transformer with OLTC


Rated Rated voltage (kV) Loss No-load Short Mass(t) Overall dimension
Vector Gauge
Type power No-load Load current Impeda Active
HV MV LV Group Oil Total L W H (mm)
(kVA) (kW) (kW) (%) nce (%) part

SFPSZ-50000/220 50000 46.2 212.0 0.26 52.5 32.9 92.7 7860 5050 5620 20002000
HV-MV
SFPSZ-63000/220 63000 53.9 246.0 0.24 60.4 34.5 103.4 8780 5150 6020 20002000
220 10.5; 12-14
SFPSZ-90000/220 90000 8 69 11; YNyn 70.0 331.1 0.22 HV-LV 80.0 38.3 135.2 10620 5590 7070 1435/22000

SFPSZ-120000/220 120000 1.25 121 35; 0d11 85.4 408.0 0.20 22-24 102.2 42.9 173.3 11080 5820 7420 1435/22000
% 38.5 MV-LV
SFPSZ-150000/220 150000 100.1 484.0 0.18 123.8 44.0 199.8 11730 5910 7550 1435/22000
7-9
SFPSZ-180000/220 180000 115.5 595.0 0.15 139.9 46.3 231.6 12380 6140 7600 1435/22000

Notes:
1. The power distributions of HV, MV and LV windings are 100/100/50% respectively;
2. According to clients requirement, HV can use other different values;
3. The parameters above are for reference only. Our company reserves the right of modification;
4. Our company will provide products according to clients requirements;
5. The overall dimensions and significant parameters are for the step-down transformer; our company
can provide those parameters for the step-up transformer.

220 kV Three-winding Power Transformer with OCTC


Rated voltage
Rated Loss No-load Short Mass(t) Overall dimension
(kV) Vector Gauge
Type power current Impeda
Group No-load Load Active (mm)
(kVA) HV LV (%) nce (%) Oil Total L W H
(kW) (kW) part

SFP-50000/220 50000 220/ 10.5; YNd11 36.4 178.5 0.28 12-14 43.6 23.9 82.5 7800 4710 6740 20002000
242 11;
SFP-63000/220 63000 43.4 208.0 0.27 51.5 25.0 96.0 7810 4750 6780 20002000
2 13.8
SFP-90000/220 90000 57.4 272.0 0.25 67.3 26.2 125.1 7820 4750 6830 1435/22000
2.5% 15.75
SFP-120000/220 120000 70.0 327.0 0.23 89.5 27.5 150.5 8030 4790 7690 1435/22000

SFP-150000/220 150000 84.0 382.0 0.20 96.0 28.6 160.3 9370 4840 7710 1435/22000

SFP-180000/220 180000 95.9 433.0 0.20 109.2 29.2 172.3 10700 5010 7790 1435/22000
SFP-240000/220 240000 119.0 535.0 0.15 122.7 32.3 184.5 12010 5160 7850 1435/22000

SFP-300000/220 300000 140.0 637.0 0.15 134.5 34.5 194.7 13100 5320 7910 1435/22000

SFP-360000/220 360000 161.0 731.0 0.15 147.8 37.3 209.5 13980 5570 7990 1435/22000

Notes:
1. According to the requirement, HV can use other different values;
2. The parameters above are for reference only. Our company reserves the right of modification;
3. Our company will provide products according to clients requirements;
4. The overall dimensions and significant parameters are for the step-down transformer; our company
can provide those parameters for the step-up transformer.

220 kV Three-phase Three-winding Power Transformer with OCTC


Rated Rated voltage (kV) Loss No-load Short Mass(t) Overall dimension
Vector Gauge
Type power No-load Load current Impeda Active
HV MV LV Group Oil Total L W H (mm)
(kVA) (kW) (kW) (%) nce (%) part

SFPS-50000/220 50000 42.0 212.0 0.26 50.5 21.9 86.4 5650 5010 5200 20002000

SFPS-63000/220 63000 10.5; 49.7 246.0 0.24 HV-MV 58.8 22.9 97.0 6420 5120 5610 20002000
220/ 11; 12-14
SFPS-90000/220 90000 64.4 331.0 0.22 78.3 27.2 129.1 8410 5570 6690 1435/22000
242 69 13.8 YNyn HV-LV
SFPS-120000/220 120000 79.1 408.0 0.20 101.2 31.3 165.4 10650 5830 7440 1435/22000
2 121 15.75 0d11 22-24
SFPS-150000/220 150000 93.1 484.0 0.18 120.3 37.7 196.6 11200 5950 7540 1435/22000
2.5% 35; MV-LV
SFPS-180000/220 180000 38.5 106.4 552.0 0.15 7-9 138.9 42.2 226.9 11690 6150 7570 1435/22000

SFPS-240000/220 240000 130.9 680.0 0.15 157.1 47.0 257.5 12190 6360 7820 1435/22000

Notes:
1. The power distributions of HV, MV and LV windings are 100/100/50% respectively;
2. According to clients requirement, the vector group can be Ynd11 or others;
3. According to clients requirement, the MV can use other different values;
4. The parameters above are for reference only. Our company reserves the right of modification;
5. The overall dimensions and significant parameters are for the step-down transformer; our company
can provide those parameters for the step-up transformer.

220 kV Three-phase Three-winding Autotransformer with OCTC


Rated Rated voltage (kV) Loss No-load Short Mass(t) Overall dimension
Vector Gauge
Type power No-load Load current Impeda Active
HV MV LV Group Oil Total L W H (mm)
(kVA) (kW) (kW) (%) nce (%) part
OSFPS-90000/220 90000 37.8 260.0 0.24 HV-MV 44.0 21.9 87.5 8910 5820 6980 1435/22000
10.5;
SFPS-120000/220 120000 46.9 321.0 0.22 8-10 57.8 26.7 108.9 9040 5850 7060 1435/22000
220/ 11;
YNa0 HV-LV
SFPS-150000/220 150000 2 121 13.8 54.6 382.5 0.20 68.9 31.8 130.3 9920 5910 7110 1435/22000
d11 28-34
SFPS-180000/220 180000 2.5% 15.75 62.3 437.5 0.18 80.1 37.3 152.6 10820 5980 7150 1435/22000
MV-LV
38.5
SFPS-240000/220 240000 74.2 562.5 0.15 18-24 92.3 40.3 171.5 11720 6050 7200 1435/22000

Notes:
1. The power distributions of HV, MV and LV windings are 100/100/50% respectively;
2. According to clients requirement, the MV can use other different values;
3. The parameters above are for reference only. Our company reserves the right of modification;
4. The overall dimensions and significant parameters are for the step-down transformer; our company
can provide those parameters for the step-up transformer.

220 kV Three-phase Three-winding ONAF Power Transformer with OLTC


Rated Rated voltage (kV) Loss No-load Short Mass(t) Overall dimension
Vector Gauge
Type power No-load Load current Impeda Active
HV MV LV Group Oil Total L W H (mm)
(kVA) (kW) (kW) (%) nce (%) part

HV-MV 1435/220
SFSZ-120000/220 120000 85.4 408.0 0.20 93.5 38 177 9100 7000 7260
12-14 00
220 11;
69 YNyn HV-LV 1435/220
SFSZ-150000/220 150000 8 35; 100.1 484.0 0.18 114.5 48 213.9 9300 7100 7460
121 0d11 22-24 00
2.5% 38.5
MV-LV 1435/220
SFSZ-180000/220 180000 115.5 595.0 0.15 121 53 221.9 9800 7250 7600
7-9 00

Notes:
1. The power distributions of HV, MV and LV windings are 100/100/50% respectively;
2. According to clients requirement, the MV can use other different values;
3. The parameters above are for reference only. Our company reserves the right of modification;
4. The overall dimensions and significant parameters are for the step-down transformer; our company
can provide those parameters for the step-up transformer.

220 kV Three-phase Three-winding ONAN Power Transformer with OLTC


Rated Rated voltage (kV) Loss No-load Short Mass(t) Overall dimension
Vector Gauge
Type power No-load Load current Impeda Active
HV MV LV Group Oil Total L W H (mm)
(kVA) (kW) (kW) (%) nce (%) part

SSZ-120000/220 120000 220 69 11; YNyn 85.4 408.0 0.20 HV-MV 99.5 41 187.6 9500 7200 7260 1435/22000
8 121 35; 0d11 12-14 1000
SSZ-150000/220 150000 100.1 484.0 0.18 121 51 226.7 7300 7460 1435/22000
1.25 38.5 HV-LV 0

% 22-24

SSZ-180000/220 180000 115.5 595.0 0.15 MV-LV 128 56 235.2 105 7400 7600 1435/22000

7-9

Notes:
1. The power distributions of HV, MV and LV windings are 100/100/50% respectively;
2. According to clients requirement, the MV can use other different values;
3. The parameters above are for reference only. Our company reserves the right of modification;
4. The overall dimensions and significant parameters are for the step-down transformer; our company
can provide those parameters for the step-up transformer.

220 kV Three-phase Three-winding ONAF Power Transformer with OLTC


Rated Rated voltage (kV) Loss No-load Short Mass(t) Overall dimension
Vector Gauge
Type power No-load Load current Impeda Active
HV MV LV Group Oil Total L W H (mm)
(kVA) (kW) (kW) (%) nce (%) part

HV-MV
SFSZ-120000/220 120000 85.4 408.0 0.20 93.5 38 177 9100 7000 7260 1435/22000
220 12-14
11;
SFSZ-150000/220 150000 8 69 YNyn 100.1 484.0 0.18 HV-LV 114.5 48 213.9 9300 7100 7460 1435/22000
35;
1.25 121 0d11 22-24
38.5
% MV-LV
SFSZ-180000/220 180000 115.5 595.0 0.15 121 53 221.9 9800 7250 7600 1435/22000
7-9

Notes:
1. The power distributions of HV, MV and LV windings are 100/100/50% respectively;
2. According to clients requirement, the MV can use other different values;
3. The parameters above are for reference only. Our company reserves the right of modification;
4. The overall dimensions and significant parameters are for the step-down transformer; our company
can provide those parameters for the step-up transformer.

220 kV Three-phase Three-winding Combined Power Transformer


Losses (kW) Short-circuit Transport
Vector Winding No-load Active Transport
Type Voltage Ratio Impedance Dimensions
Group Combination Current No-load Load Part Mass Mass
(%) (mm)

H-M
2208 23.5 38603300
SFPSZ10-H-120000/220 YNyn0d11 H-L 0.20 90 405 336.5 345
1.25%/115/35 8.0 3460
M-L
H-M 14.2
2208 24803380
SFPSZ10-H-150000/220 YNyn0d11 H-L 0.18 104 405 24.0 344.0 352+54
1.25%/121/10.5 3620
M-L 7.8

Notes:
1. According to the requirement, the vector group can be YNd11 or others;
2. The parameters above are for reference only. Our company reserves the right of modification;
3. Our company will provide products according to clients requirements;
4. The overall dimensions and significant parameters are for the step-down transformer; our company
can provide those parameters for the step-up transformer.

220 kV Combined Power Transformer


Losses (kW) Short-circuit
Vector Winding No-load Active Transport Transport
Type Voltage Ratio Impedance
Group Combination Current No-load Load Part Mass Mass Dimensions(mm)
(%)

2202 34202790
SSP-H-120000/220 YNd11 H-L 0.20 86 340 13.0 336.5 342.5
2.5%/13.8 3350

2202 32002670
SSP-H-100000/220 YNd11 H-L 0.23 79 306 13.2 330 337.2
2.5%/13.8 3160

Notes:
1. According to the requirement, the vector group can be YNd11 or others;
2. The parameters above are for reference only. Our company reserves the right of modification;
3. Our company will provide products according to clients requirements;
4. The overall dimensions and significant parameters are for the step-down transformer; our company
can provide those parameters for the step-up transformer.
4. Technical Parameters for 110 kV Transformer
SSZ10Three-phase Three-winding Transformer with OLTC
Standards: GB/1094, GB/T6451, IEC60076
Rated Rated voltage (kV) Loss No-load Short Mass(kg) Overall dimension
Vector Gauge
power No-load Load current Impeda
HV MV LV Group Oil Total L(mm) W(mm) H (mm) (mm)
(kVA) (kW) (kW) (%) nce (%)

6300 8.4 45.1 0.52 8900 30800 6740 4740 4380

8000 9.9 53.6 0.51 10200 34600 6770 4760 4340

10000 11.8 62.9 0.50 11300 37500 6770 4850 4540

12500 13.6 74.0 0.48 12700 44100 6880 4880 4680

16000 16.8 90.1 0.42 HV-MV 13800 50700 6980 4970 4810 1475
6.3 10.5
20000 110/121 19.8 106.3 0.40 14300 53200 7140 5130 4760 /
35 6.6 YNyn HV-LV
25000 8 22.2 125.8 0.38 15800 60100 7160 5300 4970 2040
38.5 10.5 0d11 17-18
31500 1.25% 27.7 148.8 0.36 17600 69100 7320 5390 5050
11 MV-LV
40000 33.0 178.5 0.36 6.5 21100 83200 7420 5580 5390

50000 39.5 212.5 0.33 24200 97600 7740 5620 5620

63000 45.7 255.0 0.32 25400 108800 7800 5740 5730

75000 52.9 290.6 0.30 26300 117400 7680 5810 5790

90000 61.3 333.2 0.28 27200 125700 7950 5890 5820

Noise Level: ONAN < 60 dB

SFSZ10Three-phase Three-winding Transformer with OLTC


Standards: GB/1094, GB/T6451, IEC60076
Rated Rated voltage (kV) Loss No-load Short Mass(kg) Overall dimension
Vector Gauge
power No-load Load current Impeda
HV MV LV Group Oil Total L(mm) W(mm) H (mm) (mm)
(kVA) (kW) (kW) (%) nce (%)

6300 110/121 35 6.3 YNyn 8.4 45.1 0.52 HV-MV 8100 28100 6740 4270 4380

8000 8 38.5 6.6 0d11 9.9 53.6 0.51 10.5 9200 31600 6770 4280 4430
1.25% 10.5 HV-LV
10000 11.8 62.9 0.50 10100 34200 6770 4440 4540
11 17-18
12500 13.6 74.0 0.48 11400 39500 6880 4760 4680
MV-LV
16000 16.8 90.1 0.42 6.5 12600 44800 6980 4600 4810 1475

20000 19.8 106.3 0.40 12800 47400 7140 4720 4760 /

25000 22.2 125.8 0.38 13400 53700 7160 4760 4970 2040

31500 27.7 148.8 0.36 14500 61300 7320 4890 5050

40000 33.0 178.5 0.36 17800 75100 7420 5130 5390

50000 39.5 212.5 0.33 21100 88700 7740 5350 5450


63000 45.7 255.0 0.32 22100 98900 8870 5620 5730

75000 52.9 290.6 0.30 23000 107000 7800 5650 5790

90000 61.3 333.2 0.28 24200 118000 7940 5710 5840

Noise Level: ONAF < 65 dB

Notes:
1. The power distributions of HV, MV and LV windings are 100/100/100 respectively;
2. According to the requirement, the connection symbol can be Ynd11y10;
3. According to clients requirement, MV can use other different values;
4. The maximum current tapping can be in the tap position -5;
5. The overall dimensions and significant parameters are for the step-down transformer; our company
can provide those parameters for the step-up transformer;
6. The parameters above are for reference only. Our company reserves the right of modification;
7. According to clients requirement, our company can change the series number of the product.

SS10 Three-phase Three-winding Transformer with OCTC


Standards: GB/1094, GB/T6451, IEC60076
Rated Rated voltage (kV) Loss No-load Short Mass(kg) Overall dimension
Vector Gauge
power No-load Load current Impedance
HV MV LV Group Oil Total L(mm) W(mm) H (mm) (mm)
(kVA) (kW) (kW) (%) (%)

6300 7.8 45.1 0.52 6400 20800 5520 4400 4410

8000 9.1 53.6 0.50 7300 25100 5740 4430 4550

10000 10.9 62.9 0.48 7600 28600 5930 4480 4670

12500 12.6 74.0 0.43 8400 32200 5980 4510 4780

16000 15.6 90.1 0.41 HV-MV 9700 36900 6210 4540 4850 1475
6.3 10.5
20000 18.8 106.3 0.38 10900 42100 6390 4580 4930 /
110/121 35 6.6 YNyn HV-LV
25000 21.6 125.8 0.35 11400 46100 6520 4620 5110 2040
22.5% 38.5 10.5 0d11 17-18
31500 25.6 148.8 0.33 12800 52100 6570 4710 4980
11 MV-LV
40000 29.8 178.5 0.32 6.5 14900 60800 6690 5040 5390

50000 36.6 212.5 0.31 16500 69800 6850 5280 5360

63000 42.6 255.0 0.30 17100 78500 6950 5300 5670

75000 48.8 290.6 0.28 20500 94100 7120 5390 5950

90000 56.6 333.2 0.26 24000 117100 7420 5420 6180

Noise Level: ONAN< 60dB

Notes:
1. The power distributions of HV, MV and LV windings are 100/100/100 respectively;
2. According to the requirement, the connection symbol can be Ynd11y10;
3. According to clients requirement, MV can use other different values;
4. The maximum current tapping can be in the tap position -10;
5. The parameters above are for reference only. Our company reserves the right of modification;
6. According to clients requirement, our company can change the series number of the product.

SFS10 Three-phase Three-winding Transformer with OCTC


Standards: GB/1094, GB/T6451, IEC60076
Rated Rated voltage (kV) Loss No-load Short Mass(kg) Overall dimension
Vector Gauge
power No-load Load current Impedance
HV MV LV Group Oil Total L(mm) W(mm) H (mm) (mm)
(kVA) (kW) (kW) (%) (%)

6300 7.8 45.1 0.52 6300 20500 5420 4300 4410

8000 9.1 53.6 0.50 7200 25000 5640 4330 4540

10000 10.9 62.9 0.48 7500 28200 5830 4380 4620

12500 12.6 74.0 0.43 8300 31800 5880 4410 4750

16000 15.6 90.1 0.41 HV-MV 9500 36400 6110 4440 4820 1475
6.3 10.5
20000 18.8 106.3 0.38 10800 41800 6290 4480 4910 /
110/121 35 6.6 YNyn HV-LV
25000 21.6 125.8 0.35 11300 45900 6470 4520 5100 2040
22.5% 38.5 10.5 0d11 17-18
31500 25.6 148.8 0.33 12600 51700 6590 4610 4950
11 MV-LV
40000 29.8 178.5 0.32 6.5 14700 60200 6750 4840 5340

50000 36.6 212.5 0.31 16400 69500 6850 5080 5330

63000 42.6 255.0 0.30 16900 78100 6950 5100 5620

75000 48.8 290.6 0.28 20400 93700 7020 5180 5920

90000 56.6 333.2 0.26 23800 116500 7320 5320 6140

Noise Level: ONAF< 65dB

Notes:
1. The power distributions of HV, MV and LV windings are 100/100/100 respectively;
2. According to the requirement, the connection symbol can be Ynd11y10;
3. According to clients requirement, MV can use other different values;
4. The maximum current tapping can be in the tap position -5;
5. The overall dimensions and significant parameters are for the step-down transformer; our company
can provide those parameters for the step-up transformer;
6. The parameters above are for reference only. Our company reserves the right of modification;
7. According to clients requirement, our company can change the series number of the product.

S10 Two-winding Transformer with OCTC


Standards: GB/1094, GB/T6451, IEC60076
Rated Rated voltage (kV) Loss No-load Short Mass(kg) Overall dimension
Vector Gauge
power No-load Load current Impedance
HV MV LV Group Oil Total L(mm) W(mm) H (mm) (mm)
(kVA) (kW) (kW) (%) (%)

6300 7.00 34.9 0.51 4500 16000 4200 2850 4500

8000 8.40 42.5 0.49 5045 18615 4400 3000 4650

10000 9.80 50.2 0.45 6365 33140 4700 3200 4900

12500 11.6 59.5 0.43 7000 26500 5005 3390 5100

16000 14.00 73.1 0.41 7500 27760 5100 3300 4900 1475
6.3
20000 16.5 88.4 0.40 HV-LV 7610 29000 5400 3500 5000 /
110/121 6.6
25000 YNd11 19.2 104.6 0.38 10.5 7700 35000 5700 3700 5000 2040
22.5% 10.5
31500 23.0 125.8 0.36 8040 40680 5070 4195 4895
11
40000 27.8 147.9 0.34 8110 45800 5335 4125 5425

50000 32.5 183.6 0.32 9600 55000 5650 4400 5800

63000 37.9 221.0 0.31 12180 63000 6000 4420 5380

90000 47.1 289.0 0.29 16000 83000 6600 4850 5885

120000 53.2 358.7 0.26 19750 102500 7050 5200 6300

Noise Level: ONAN<60 dB ONAF< 65dB

Notes:
1. According to the requirement, the connection symbol can be Ynd11y10;
2. The maximum current tapping can be in the tap position -10;
3. The parameters above are for reference only. Our company reserves the right of modification;
4. According to clients requirement, our company can change the series number of the product.

SZ10 Two-winding Transformer with OLTC


Standards: GB/1094, GB/T6451, IEC60076
Rated Rated voltage (kV) Loss No-load Short Mass(kg) Overall dimension
Vector Gauge
power No-load Load current Impedance
HV MV LV Group Oil Total L(mm) W(mm) H (mm) (mm)
(kVA) (kW) (kW) (%) (%)

6300 7.7 34.9 0.53 4250 15500 4600 2820 3450


8000 110/121 6.3 YNd11 9.1 42.5 0.51 HV-LV 5050 18500 4900 3000 3700
81.25% 6.6 10.5
10000 10.8 50.2 0.47 7000 30000 6000 3300 4500
10.5
12500 12.8 59.5 0.45 7610 25800 5600 3600 4310
11
16000 15.4 73.1 0.43 8460 30950 5810 3560 4350 1475

20000 18.2 88.4 0.42 8990 35000 5580 3850 4620 /

25000 21.1 104.6 0.40 10055 40580 6010 4385 5550 2040

31500 25.2 125.8 0.38 10150 43810 5820 4340 5100

40000 30.4 147.9 0.36 12500 52500 6180 4610 5450

50000 35.2 183.6 0.34 14500 62000 6550 4900 5750

63000 41.7 221.0 0.33 17070 73680 7000 5200 6100

90000 51.8 289.0 0.31 22305 96300 7650 5685 6670

120000 58.7 358.7 0.28 24000 117100 7420 5420 6180

Noise Level: ONAN<60 dB ONAF< 65dB

Notes:
1. According to the requirement, the connection symbol can be Ynd11y10;
2. The maximum current tapping can be in the tap position -10;
3. The parameters above are for reference only. Our company reserves the right of modification;
4. According to clients requirement, our company can change the series number of the product.
5. Technical Parameters of 66 kV Transformer
S10 Series 66 kV Two-winding Transformer with OCTC
Standards: GB/1094, GB/T6451, IEC60076
Rated Rated voltage (kV) Loss No-load Short Mass(kg) Overall dimension
Vector Gauge
power No-load Load current Impedance
HV MV LV Group Oil Total L(mm) W(mm) H (mm) (mm)
(kVA) (kW) (kW) (%) (%)

8000 8.4 42.5 0.51 4850 17800 4100 2800 4300

10000 9.9 50.2 0.49 6070 21100 4200 2890 4600

12500 11.8 59.5 0.45 6700 25300 4650 3150 4850

16000 13.6 73.1 0.43 7150 26500 4900 3290 5000 1475
6.3
20000 16.8 88.4 0.41 7250 27700 5000 3200 4800 /
66/69 6.6 0.5
25000 YNd11 19.8 104.6 0.40 7350 33500 5300 3400 4900 2040
22.5% 10.5
31500 22.2 125.8 0.38 8610 38750 5300 3800 5300
11
40000 27.7 147.9 0.36 7750 43700 5500 4100 5410

50000 33.0 183.6 0.34 9150 52380 5600 4250 5700

63000 39.5 221.0 0.32 11600 60000 5800 4320 5600

Noise Level: ONAN<60 dB ONAF< 65dB

Notes:
1. According to the requirement, the connection symbol can be Ynd11y10;
2. The parameters above are for reference only. Our company reserves the right of modification;
3. According to clients requirement, our company can change the series number of the product.

SZ10 Series 66 kV Two-winding Transformer with OLTC


Standards: GB/1094, GB/T6451, IEC60076
Rated Rated voltage (kV) Loss No-load Short Mass(kg) Overall dimension
Vector Gauge
power No-load Load current Impedance
HV MV LV Group Oil Total L(mm) W(mm) H (mm) (mm)
(kVA) (kW) (kW) (%) (%)

8000 9.1 42.5 0.51 5000 18000 4800 2900 3600

10000 66/69 6.3 YNd11 10.8 50.2 0.47 0.5 6700 21950 5100 3200 4200
81.25% 6.6
12500 12.8 59.5 0.45 7250 26580 5500 3500 4310
10.5
16000 15.4 73.1 0.43 8060 29500 5710 3550 4250 1475
11
20000 18.2 88.4 0.42 8570 33500 5780 3750 4500 /

25000 21.1 104.6 0.40 9580 38700 5910 4200 4950 2000

31500 25.2 125.8 0.38 9700 41750 5720 4300 5000

40000 30.4 147.9 0.36 11910 50000 5980 4600 5650


50000 35.2 183.6 0.34 13810 59050 6450 5100 6000

63000 41.7 221.0 0.33 16260 70200 7560 5770 6570

Noise Level: ONAN<60 dB ONAF< 65dB

Notes:
1. According to the requirement, the connection symbol can be Ynd11y10;
2. The parameters above are for reference only. Our company reserves the right of modification;
3. According to clients requirement, our company can change the series number of the product.
6. Technical Parameters of 35 kV Transformer
SZ9 Series 35 kV Power Transformer with OLTC
Standards: GB/1094, GB/T6451, IEC60076
Rated voltage (kV) Loss Mass(kg) Overall dimension
Rated No-load Short
HV Vector Gauge
power No-load Load current Impeda Active
HV Tapping LV Group Oil Total L(mm) W(mm) H (mm) (mm)
(kVA) (kW) (kW) (%) nce (%) Part
Range

2000 2.25 19.12 0.85 6.5 2620 1680 5750 3095 2285 2710 1070

2500 2.67 20.52 0.82 3695 2370 8070 3205 2500 2810 1000
7.0
3150 3.19 24.56 0.76 3825 2455 8600 3695 2340 2920 1070
Yd11
4000 3.85 28.98 0.74 4550 2450 9680 3250 2530 2950 1070

5000 4.55 34.00 0.72 6025 3215 12305 3565 2555 3200 1070

6300 6.3 5.46 36.55 0.70 6800 2885 12610 3520 3050 3110 1475
7.5
35 22.5 6.6
8000 7.70 40.37 0.63 8050 3380 14515 3770 3250 3200 1475
38.5 % 10.5
10000 9.10 47.77 0.60 9670 3920 18300 4420 3290 3340 1475
11
12500 10.71 56.52 0.59 12310 4910 22110 4620 3730 3540 1475

16000 12.89 68.02 0.56 13185 5665 25200 4820 3790 3600 1475
YNd11 8.0
20000 25.24 80.41 0.51 15800 5750 26200 5210 3840 3840 1475

25000 18.17 93.55 0.50 19800 7400 33100 5200 4000 4200 1475

31500 21.43 113.05 0.49 24670 9790 41980 5220 4210 4310 2040

Notes:
1. Our company can provide the gauge according to clients requirement;
2. The parameters above are for reference only. Our company reserves the right of modification.

SF10 Series 35 kV Power Transformer with OCTC


Standards: GB/1094, GB/T6451, IEC60076
Rated voltage (kV) Loss Mass(kg) Overall dimension
Rated No-load Short
HV Vector Gauge
power No-load Load current Impeda Active
HV Tapping LV Group Oil Total L(mm) W(mm) H (mm) (mm)
(kVA) (kW) (kW) (%) nce (%) Part
Range

10000 35 22.5 6.3 YNd11 8.26 45.05 0.43 7.5 9520 4620 18880 3630 3590 3700 1475
38.5 % 10.5
12500 9.80 53.55 0.42 10610 5340 24000 3750 3760 3705 1475
11
16000 11.90 65.45 0.41 12610 6750 28600 4480 3840 3765 1475

20000 14.07 79.05 0.40 15700 7985 33000 4630 3900 3850 1475

25000 16.73 93.50 0.34 8.0 18000 9650 36800 4930 4100 4195 1475

31500 19.95 112.20 0.32 19800 10790 42000 5180 4200 4350 2040
40000 23.86 134.22 0.27 28300 11660 43100 5250 4250 4435 20410

Notes:
1. Our company can provide the gauge according to clients requirement;
2. The parameters above are for reference only. Our company reserves the right of modification.

S10 Series 135kV Distribution Transformer with OCTC


Standards: GB/1094, GB/T6451, IEC60076
Rated voltage (kV) Loss Mass(kg) Overall dimension
Rated No-load Short
HV Vector Gauge
power No-load Load current Impeda Active
HV Tapping LV Group Oil Total L(mm) W(mm) H (mm) (mm)
(kVA) (kW) (kW) (%) nce (%) Part
Range

30 0.11 0.78 1.75 200 220 705 1040 810 1740

50 0.17 1.15 1.70 220 250 785 1070 830 1770

80 0.22 1.62 1.62 315 280 920 1090 850 1790

100 0.24 1.92 1.53 420 410 1100 1165 900 1870 660

125 0.27 2.25 1.48 450 435 1245 1265 1080 1950

160 0.29 2.68 1.40 650 465 1470 1310 1080 1970

200 0.34 3.15 1.31 680 510 1510 1350 1100 1980

250 0.40 3.74 1.19 720 540 1615 1400 1120 2040
35 5% 0.4 Yyn0 6.5
315 0.48 4.51 1.16 1010 565 2010 1640 1130 2080

400 0.57 5.44 1.10 1055 620 2170 1720 1140 2120 820

500 0.68 6.55 1.08 1120 720 2565 2030 1160 2160

630 0.81 7.82 1.06 1560 810 2980 2070 1220 2240

800 0.97 9.35 0.89 1650 940 3680 2220 1260 2340 1070

1000 1.16 11.48 0.85 1750 1080 4490 2370 1290 2440

1250 1.37 13.86 0.72 2015 1170 4860 2390 1340 2580

1600 1.66 16.58 0.63 2150 1260 5580 2430 1420 2620

Notes:
1. Our company can provide the gauge according to clients requirement;
2. The parameters above are for reference only. Our company reserves the right of modification.
7. Technical Parameters of 10 kV Transformer
S11 Series 10 kV Distribution Transformer with OCTC
Standards: GB/1094, GB/T6451, IEC60076
Rated voltage (kV) Loss Mass(kg) Overall dimension
Rated No-load Short
HV Vector Gauge
power No-load Load current Impeda Active
HV Tapping LV Group Oil Total L(mm) W(mm) H (mm) (mm)
(kVA) (W) (W) (%) nce (%) Part
Range

30 90 600 0.63 195 70 300 1120 620 1085

50 120 870 0.60 210 85 390 1110 720 1160

63 140 1040 0.57 260 90 450 1100 740 1240

80 175 1250 0.54 290 100 510 1125 760 1285

100 205 1500 0.48 315 110 550 1130 830 1320

125 240 1800 0.45 420 170 640 1340 830 1420

160 280 2200 0.42 515 190 860 1380 835 1480

200 340 2600 0.39 520 195 860 1400 960 1485 300

250 390 3050 0.36 640 205 970 1410 990 1495 400

6 4/4.5 550
315 5% 0.4 Yyn0 470 3650 0.33 720 210 1190 1400 1040 1580
10 660
400 560 4300 0.30 900 240 1445 1470 1030 1730
820
500 670 5100 0.30 1200 350 1800 1670 1210 1750 1070

630 840 6200 0.27 1370 425 2265 2070 1300 1785

800 980 7500 0.24 1535 442 2486 1990 1320 1839

1000 1190 10300 0.21 1740 520 3100 2100 1300 1950

1250 1365 12800 0.18 1975 575 3275 2300 1310 2030

1600 1680 14500 0.18 2360 705 3935 2300 1340 2130

2000 1985 17170 0.39 2915 720 4730 2125 1705 2550

2500 2347 20263 0.30 5 3560 1790 6200 2390 2560 2650

Notes:
1. Our company can provide the gauge according to clients requirement;
2. The parameters above are for reference only. Our company reserves the right of modification.

S10 Series 10 kV Power Transformer with OCTC


Standards: GB/1094, GB/T6451, IEC60076
Rated voltage (kV) Loss Mass(kg) Overall dimension
Rated No-load Short
HV Vector Gauge
power No-load Load current Impeda Active
HV Tapping LV Group Oil Total L(mm) W(mm) H (mm) (mm)
(kVA) (kW) (kW) (%) nce (%) Part
Range
630 0.92 6.89 1.10 4.5 1300 490 2480 1980 1180 1805 820

800 1.12 8.42 1.02 1450 520 2670 2040 1275 1855 820
6
1000 1.32 9.86 0.93 1720 590 2995 2150 1350 1965 820
6.3 3
1250 1.56 11.73 0.85 2100 645 3540 2080 1420 2190 820
10 3.15
1600 1.88 14.03 0.76 2510 930 4475 2125 1533 2280 820
10.5 6.3
5% Yd11 5.5
2000 11 2.24 16.83 0.76 3170 1105 5820 2560 2170 2470 1070

2500 2.64 19.55 0.68 3720 1295 6350 2670 2195 2590 1070

3150 3.12 22.95 0.68 4355 1370 7285 2490 2340 2660 1070

4000 10 3.84 27.20 0.59 5155 1750 8685 2480 2970 2400 1070
3.15
5000 10.5 4.56 31.20 0.59 6050 2150 10760 2935 3175 2980 1070
6.3
6300 11 5.44 34.85 0.51 7010 2580 12790 3250 3445 3150 1070

Notes:
1. Our company can provide the gauge according to clients requirement;
2. The parameters above are for reference only. Our company reserves the right of modification.

S10 Series 10 kV Distribution Transformer with OLTC


Standards: GB/1094, GB/T6451, IEC60076
Rated voltage (kV) Loss Mass(kg) Overall dimension
Rated No-load Short
HV Vector Gauge
power No-load Load current Impeda Active
HV Tapping LV Group Oil Total L(mm) W(mm) H (mm) (mm)
(kVA) (kW) (kW) (%) nce (%) Part
Range

200 0.38 2.89 1.53 4 580 285 1150 1625 850 1490 550

250 0.46 3.40 1.44 690 335 1430 1735 1030 1510 660

315 0.54 4.08 1.36 795 390 1685 1830 1050 1620 660

400 0.65 4.93 1.27 935 423 1848 1870 1090 1740 660

500 6 0.78 5.87 1.19 1200 467 2321 1970 1180 1740 660
42.5
630 6.3 0.4 Yyn0 0.99 7.23 1.10 1380 539 2728 2125 1210 1790 820
%
10
800 1.21 8.84 1.02 1650 627 2986 2305 1310 1875 820
4.5
1000 1.42 10.37 0.93 1930 760 3215 2425 1380 1940 820

1250 1.66 12.33 0.85 2260 795 3760 2550 1400 2230 820

1600 2.13 14.71 0.76 3650 965 4535 2550 1440 1445 820

2000 2.56 17.39 0.68 3050 1095 5420 2560 2130 2445 820

Notes:
1. Our company can provide the gauge according to clients requirement;
2. The parameters above are for reference only. Our company reserves the right of modification.
VII. Railway Traction Transformer
The Characteristics of Railway Traction Transformer
On the basis of digesting and absorbing the advanced technology in and out of China, according to the
characteristics of the national railway electrification reconstruction, the company develops the traction
transformer itself. The performance and index of the traction transformer have the superiority over the
technical parameters and specification stated in GB standard and relevant IEC 60076 standards. The
transformer complies with the required characteristics of railway electrification which include low loss,
low noise, no leakage, free-of-maintenance, high short circuit withstand ability, high over-load ability and
low impedance. The product has the following characteristics
1. Core of transformer
The core is laminated with the HI-B cold-rolled grain-oriented silicon sheet steel exported from Japan.
The silicon sheet steel is cut by Astronic Core Cutting Machine exported from Switzerland, the use of
which makes sure that the burr at the edge of cutting is less than 0.01 mm. The application of advanced
core reversal platform and the non-stacking upper yoke technique ensure the grain orientation of the
cold-rolled silicon sheet steel and reduce the no-load loss effectively. The plate type clamp is used for
clamping core limbs with polyester belt, which improves the tightening of core and makes the core under
the best stress withstand condition. This not only reduces the no-load loss, but also the noise level.
2. Winding of transformer
The windings of transformer are wounded around the high-strength insulation cylinder. In order to
improve the short circuit withstanding ability of transformer, all spacers and strips will be subjected to
roundness treatment. Outside the winding, the lockable strips will be provided; inside the winding, the
auxiliary strips will be provided. All windings are subjected to lacquer dipping and solidification
treatment. The axial pressing stress of winding is strictly controlled according to the technique
requirement. After compressing, electromagnetic center height of each winding remains in the same level
and relevant winding disc will be strictly controlled according to the requirement of ampere-turn balance
to minimize the axial force and conductor stress under the state of short circuit. To meet the high
over-load requirement of railway power supply during short circuit, the winding will be designed with
low current density and expanded oil duct with 0 tolerance for radial tightening, which greatly
improves the mechanical strength and short circuit withstanding ability of winding. Besides, the oil
guiding structures are arranged inside HV and LV windings, which reduce the winding hot spot
temperature rise and prolong its service life.
3. Active Part Insulation
The active part assembly and coil winding are carried out in a fully sealed, constant temperature and
pressure workshop which meets the requirement of cleanness and constant humidity requirements for
manufacturing 1000 KV power transformer. At the same time, the large kerosene vapor-phase drying
device is applied to decrease the water content in insulating pieces and improve the cleanness. The lower
supporting plate and upper pressing plate of active part adopt electric laminating paperboard with high
mechanical strength and outstanding electric performance. All strips and blocks will be subjected to
sealing pressure treatment twice to reduce partial discharge.
The steel clamps and steel pressing nails have sufficient strength and the pressing nail bowl of paper pulp
insulation is used to support the blocks, strips and pressing nails, to balance the force on winding and
improve the stability of active part. The active part makes use of integral assembly and constant pressure
drying technique to shorten the time of active part assembly after stabilization treatment. The
concentricity of each winding will be regulated to make the magnetic center in consistence with each
other, which guarantees that the stress on winding is equally distributed to improve the short circuit
withstanding ability of winding.
4. Tank
The bell type tank will be adopted. The use of large press brake makes the corrugation much easier, which
avoids the use of iron stiffener, improves the mechanical strength of the tank, reduces the welding seams
and improves the radiating effectiveness of main body. Special treatment which will be conducted to the
sealed parts of the tank and complete shot-blast treatment to tank will helps to clean all sharp angles,
burrs and welding slag to improve the adhesiveness of paint and make the tank good-looking and
everlasting. The radiators and other accessories will be tested by simulating the abominable ambient
conditions on site to eliminate leakages. All flange faces are machined precisely and equipped with notch
and position-limiting structure. Meanwhile, the oil-resistant, weather-proof, ozone-resistant,
well-qualified nitrile rubber gasket is adopted to avoid leakages.
5. Cooler and Auxiliary Devices
Generally speaking, the transformer is designed to be ONAF type. When the fan motor starts, the
transformer is operated under the state of full load; when the fan motor stops for natural cooling, the load
can be 67% of full load. According to clients requirement, the transformer can also be designed to be
ONAN type with the ONAF conditions reserved.
The panel type radiator will be compactly and properly arranged with fan motor fixed on bracket to
reduce the shock of radiator.
The conservator will be rubber bladder type with oil-resistant, airtight rubber bladder installed inside,
which ensures that the air and oil dont contact directly and realizes the complete sealing. Besides, the
expansion type conservator made of stainless steel which has the characteristics of free of maintenance
and reliable operation can also be used.

Applicable Scope
The railway traction transformer manufactured by our company is extensively used in various new-built
electrified railway and railway electrification reconstruction. It is applied the conditions of tempestuous
load fluctuation of electrified railway and frequent external short circuit. It is also applied to various
special environments such as high temperature, low temperature, heavy pollution, high plateau and so on.

The characteristics of 220 kV, 110 kV single-phase traction transformers

1. It is applicable to AT power supply which simplifies the main connection of traction transformer;
2. The autotransformer at the exit of substation will be left out, which reduces the losses of circuit and
input of devices.
3. The voltage of 220 kV (110 kV) will be reduced to 27.5 kV directly for traction locomotive.
4. The capacity of transformer can be fully used;
5. The working voltage of feeder switch is reduced, which not only reduces investment, but also
improves the reliability of power supply.
6. The transformer will be recommended to be used when the capacity of power grid is big enough and
the effect of single-phase operation to power grid can be ignored.

The Characteristics of 110 kV, YN.A Connected Railway Traction Transformer


1. The three-phase apparent power of primary side is converted to two-phase apparent power of
secondary side, which increase the efficiency by 1.25 times compared with the transformer with same
nominal power;
2. HV winding apply YN connection and the neutral point will be brought out, which matches the 110
kV large current grounding system;
3. The LV side is Delta connected winding which suppresses higher harmonic and makes the main flux
and electric potential waveform have good sinusoidal angle and improve the power supply quality of
transmission system;
4. Compared with common connected transformer, the no-load loss reduces by 25% and load loss by
15%;
5. The LV side of transformer has a reactive compensation joint which reduces the voltage level of
electric equipment for compensation. So the expense of the device is greatly reduced.
6. When the current at secondary side I j during operation, the current of HV side is equilibrium
system; when I = j, the current of HV side is symmetry system, which has no effect to the power
supply of power grid and no interruption to communication lines.
7. The unbalanced rated of HV side is small:
l The current percentage of HV neutral: IN/Iav <8%
l The current percentage of HV phase: (Imax-Imin)/Iav<6%
Whereas:
Imax is maximum value among the three phases of HV side;
Imin is the minimum value among the three phases of HV side;
IN is the current value of HV neutral;
Iav is the average current value of the three phases of HV side.

The Characteristics of 110 kV VV0 Connected Railway Traction Transformer


1. The VV0 connected traction transformer is designed with unique structure which helps to improve the
short circuit withstanding ability of transformer;
2. Compared with conventional traction transformer, the VV0 connected traction transformer
manufactured by our company has high efficiency of power utilization which reaches 100% and saves
a big amount of operation cost;
3. Our company can select the capacity of two single-phase traction transformers according to the load
situation of electrified railway, which will not cause the waste of capacity and will reduce the
operation cost of the equipment;
4. Compared with three-limb core, the single-phase windings is assembled on two core limbs
respectively, which reduces the number of ampere-turn to half and greatly improves the short circuit
withstanding ability;
5. A special tap changer is used to guarantee the regulations of two limbs performed simultaneously.
Meanwhile, the busbar voltages of two single-phase transformers will be adjusted according to circuit
characteristics.
6. Proper current density will be chosen to meet the requirements of frequent short circuit, asymmetric
load and severe over-load operation.

The Characteristics of 110 kV YNd11 Connected Railway Traction Transformer


1. The winding of each phase has the same number of turns and the product structure is symmetric
arranged, which makes the manufacture easier;
2. The HV neutral will be brought out and grounded; the two terminals of HV winding applies graded
insulation structure, which reduces the use of electrification system;
3. The Delta connected winding and loop of tertiary current harmonic is used, which ensures good
waveform of magnetic flux and induced voltage;
4. The product is applicable to BT power supply;
5. The product can also be designed according to three-phase unequal-capacity structure.
The Over-load Capability of Railway Traction Transformer
The railway traction transformer manufactured by our company has the characteristics of high short
circuit withstanding ability, high over-load ability. The product will be subjected to temperature rise test at
300 % rated current to meet the operational requirements of traction transformer.
Relevant measures:
1. The current density of the product is strictly controlled under 2.6 A/mm2 ;
2. The strict temperature rise calculation is performed to ensure the winding hot spot temperature rise
lower than 140;
3. The oil duct is properly designed to emit the heat occurred inside the active part and improve the
over-load ability;
4. Standby coolers will be provided and the air-cooled conditions will be set aside.

Technical Parameters of Railway Traction Transformer


220 kV Single-phase Traction Transformer
Rated Voltage (kV) Loss (kW) Short Mass(kg) Overall Dimension (mm)
Rated
No-load circuit Vector Gauge
Power Active
HV LV No-load Load Current impedance Group Oil Total L W H (mm)
(kVA) Part
(%)

25000 19 70 0.8 28650 16330 59470 5250 4630 7330


10.5
31500 26 89 0.8 34070 19420 70720 5560 4900 7760 14352000
22022.5% 27.5 II0
40000 31 103 0.7 40750 23230 84590 5900 5200 8240
8.4
45000 35 117 0.6 44510 25380 92400 6100 5360 8500

Notes:
1. The above product can be manufactured as highland type; our company can also provide the product
with other capacities;
2. The parameters above are for reference only. Our company reserves the right of modification;
110 kV Single-phase Traction Transformer
Rated Voltage (kV) Loss (kW) Short Mass(kg) Overall Dimension (mm)
Rated
No-load circuit Vector Gauge
Power Active
HV LV No-load Load Current impedance Group Oil Total L W H (mm)
(kVA) Part
(%)

10000 9 46 0.55 10900 5640 23400 4300 4400 4400

12500 11.5 55 0.55 12800 6430 26430 4370 4500 4500


10.5
16000 13.5 69 0.5 15000 7420 30060 4470 4600 4600 10701435
110 27.5 II0
20000 15 89 0.5 17680 8770 35560 4570 4700 4700
8.4
25000 18 91 0.45 21110 10370 42000 4670 4800 4700

31500 22 112 0.45 24960 12260 49650 4750 4900 4800 14351435

Notes:
1. The above product can be manufactured as highland type; our company can also provide the product
with other capacities;
2. The parameters above are for reference only. Our company reserves the right of modification;

110 kV YN.A Connected Railway Traction Transformer


Rated Voltage (kV) Loss (kW) Short Mass(kg) Overall Dimension (mm)
Rated
No-load circuit Vector Gauge
Power Active
HV LV No-load Load Current impedance Group Oil Total L W H (mm)
(kVA) Part
(%)

10000 12.5 59 0.9 13300 8900 31800 5430 2905 4030 1475

12500 14.5 70 0.9 15670 9800 32000 6060 3100 4380

16000 16.5 86 0.6 18860 10100 36160 6170 3450 4450

20000 20.0 104 0.6 10.5 22290 10600 39900 6260 3620 4670
2040
25000 11022.5% 27.5 25.0 123 0.55 YNA 26350 11200 47200 6320 3920 4835

31500 29.0 148 0.50 8.4 38500 12200 53000 6450 4130 5040

40000 35.0 174 0.45 46060 13600 66000 6600 4320 5200

50000 41.0 316 0.40 54450 17200 73000 6830 4500 5400

63000 50.0 260 0.35 64750 19800 86000 6990 4880 5600

Notes:
1. The above product can be manufactured as highland type; our company can also provide the product
with other capacities;
2. The parameters above are for reference only. Our company reserves the right of modification;
110 kV VV0 Connected Railway Traction Transformer
Short Overall Dimension
Rated Voltage (kV) Loss (kW) Mass(kg)
Rated Power No-load circuit Vector (mm) Gauge

(kVA) Current impedance Group Active (mm)


HV LV No-load Load Oil Total L W H
(%) Part

10000+10000 19.5 110 0.7 21330 11080 44350 5700 4600 4800

10000+12500 21.3 120 0.7 23300 12100 48450 5800 4730 4920

10000+16000 23 130 0.6 25940 13500 54000 6100 4900 5100

12500+12500 23 130 0.6 25940 13500 54000 6100 4900 5100


10.5
16000+16000 27.5 155 0.6 30300 15800 63100 6430 5160 5370
11022.5% 27.5 VV0 14352000
16000+20000 30 170 0.6 33100 17260 69000 6600 5320 5530
8.4
20000+20000 33 185 0.6 35800 18700 74700 6780 5470 5680

20000+25000 36 202 0.5 39100 20450 81600 6980 5630 5850

25000+25000 39 219 0.5 42310 22140 88310 7160 5780 6000

25000+31500 43 240 0.4 46380 24270 96800 7380 5960 6190

Notes:
1. The above product can be manufactured as highland type; our company can also provide the product
with other capacities;
2. The parameters above are for reference only. Our company reserves the right of modification;

110 kV YNd11 Connected Railway Traction Transformer


Rated Voltage (kV) Loss (kW) Short Mass(kg) Overall Dimension (mm)
Rated
No-load circuit Vector Gauge
Power Active
HV LV No-load Load Current impedance Group Oil Total L W H (mm)
(kVA) Part
(%)

10000 12.5 56 0.55 9200 5500 19600 4800 3350 4800

12500 14.5 67 0.55 13360 5580 24270 4850 3700 4900

16000 17 82 0.5 14100 6320 26540 5100 3750 4300 14351435

20000 20. 99 0.5 10.5 17250 7150 31870 5700 3300 4950

25000 110 27.5 24 117 0.45 YNd11 18030 8170 33060 5500 4100 4950

31500 28 141 0.4 8.4 21760 10150 39500 5600 4100 4950
14352000
40000 34 165 0.35 30500 15870 59200 5700 4500 5250

50000 39 205 0.35 5800 4600 5250

63000 47 246 0.35 39810 13030 61200 5900 4700 5250

Notes:
1. The above product can be manufactured as highland type; our company can also provide the product
with other capacities;
2. The parameters above are for reference only. Our company reserves the right of modification;
VIII. Main Components for Transformer
1. Rubber Bladder Type Conservator with Tubular OLI or Pointer Type Oil Gauge
The oil level indicator is provided with contacts of highest oil level and lowest oil level. According to
clients requirement, the metallic expansion type conservator can also be equipped.

2. Dehydrating Breather
Its used for absorbing the moisture in the air, and it should be dried and exchanged according to its
situations.
3. Gas Relay
The gas relay used for transformer main body has two kinds of contact, one for alarming and the other for
tripping, of which the tripping loop can be connected in parallel or in series. The gas relay for OLTC only
has tripping contact

4. Pressure Relief Valve


It is equipped with normally-closed contact for tripping.
5. Cooler
Forced-oil circulating type cooler which has the characteristics of good heat-emitting effect, low noise
and good-looking appearance will be used.
6. Bushing
500 kV: Oil-paper capacitance type, creepage distance2.5 cm/kV;
330 kV: Oil-paper capacitance type, creepage distance2.5 cm/kV;
220kV: oil-paper capacitance type, creepage distance2.5cm/kv
110kV: oil-paper capacitance type, creepage distance2.5cm/kv
35kv: monomer porcelain insulation type with additional insulation, creepage distance2.5cm/kv.
10kv: monomer porcelain insulation type, creepage distance2.5cm/kv.
The pollution level of the above bushings is level III. According to clients requirements, our company
can supply other bushings with different pollution levels.

7. Air-cooled Control Cubicle


According to clients demand, different terminals and controllers will be supplied.

8. On-load or No-load Tap Changer


The M-type or V-type on-load tap changer which is exported from ABB or MR or manufactured by the
best manufacturer in China will be used. They have the characteristics of long duration, reliability and
convenient operation. The electric operations will be 200,000 times and mechanical operations 800,000
times. The no-load tap-changer for 220 kV completely-sealed transformers has the outstanding
performance. It can operate safely.

9. Normally, the transformer is equipped with three temperature measurement devices:


1) Mercury Thermometer
It is used to measure oil temperature directly on main body of transformer.
2) Resistance Thermometer
It is used to measure temperature remotely, that is to connect resistance temperature display to central
control room.
3) Signal Thermometer
This thermometer is fixed at an appropriate place on the main body of transformer. The top oil
temperature can be read directly from the dial. The thermometer has the function of temperature set.
When the temperature reaches its limit, an alarm signal will be sent out. The thermometer is connected
with control cubicle, so the fan motor will be open or close according to the temperature of top oil.
Our company can also provide other components, such as winding temperature indicator, sudden pressure
relay, oil filter for tap changer, transformer on-line monitor device and so on, which must be clearly stated
in the technical specification.

IX. Resin-casting Dry-type Transformer

The Structure of Resin-casting Dry-type Transformer


1. HV Winding
The HV winding apply sectional layer type structure. It is wounded by copper conductor and glass fiber
on mandrel. During the process of winding, the cooling air duct which is cast in winding will be well
arranged. All insulating and filling materials will be impregnated in the resin to guarantee the
performance of insulation system. Some plasticizer will be put into resin to make its mechanical strength
higher. The winding is able to withstand high voltage and will not cause partial discharge.
2. LV Winding
The LV winding apply helical structure. Other aspects are the same as HV winding.
3. Core
The core is made of well-qualified cold-rolled grain-oriented silicon steel sheet. The outer surface of the
core is painted with black elastomeric resin paint which greatly reduces the no-load loss and noise level of
the transformer. The steel sheet is cut by Astronic Core Cutting Machine imported from Swiss which
ensures that the burr at the edge is less than 0.01 mm.
4. Clamp
The clamp is cut from steel plate. The lifting lugs and clamps will not be welded. They will form a
integral part which improves the mechanical strength and make the lifting and assembly safer.

The Characteristics of Resin-casting Dry-type Transformer


1. Safe, no pollution and uninflammable and explosion-protective; the transformer can be installed in
load center;
2. Free of maintenance, easy installation, simple operation;
3. High moisture-proof ability; the transformer can be put into operation without drying; at the same
time, it is suitable to humid and contaminative environment;
4. Low losses, low partial discharge, low noise.
5. High mechanical strength, short circuit withstand ability and impulse withstand ability;
6. The LV winding apply foil wrapping to ensure compact structure, ampere-turn balance and low
magnetic leakage at terminals.
Technical Parameter
SC(B)Z10 Series 10 kV Distribution Transformer with OLTC
Product Standards: GB/T10228; GB6450; IEC726; DIN42523
Rated HV: 6, 6.3, 6.5, 10, 10.5, 11 kV Rated LV: 0.4 kV

Tapping Range: 42.5% or other Connection symbol: Dyn11 or Yyn0 or others

Insulation level: L175/-; AC28(35)/3 Protection level: IP00, IP20, IP23, or others
Parameter List
Rated Losses (W) No-load LP Impedance Overall Dimension (mm) Total
Power Current dB Voltage Mass
No-load Load L LI H W
(kVA) (%) (A) (%) (Kg)
315 880 3470 1.8 45 1195 660 1170 1100 1400
400 980 3990 1.8 45 1195 660 1240 1200 1550
4
500 1160 4880 1.8 45 1255 660 1310 1200 1830
630 1340 5870 1.6 45 1300 820 1385 1200 2120
630 1300 5960 1.6 45 1390 820 1385 1200 1910
800 1520 6950 1.6 50 1450 820 1350 1200 1340
1000 1770 8130 1.4 50 1520 820 1410 1200 2760
1250 2090 9690 1.4 50 6 1570 820 1525 1200 3480
1600 2450 11730 1.4 50 1615 1070 1688 1400 4000
2000 3320 14450 1.2 50 1810 1070 1596 1400 4870
2500 4000 17170 1.2 50 1900 1070 1670 1400 5850
3150 4300 22900 1.2 50 2020 1070 1820 1600 6700
Note:
The overall dimension doesnt include on-load tap changer.
SC(B)10 Series 10 kV Distribution Transformer with OCTC
Product Standards: GB/T10228; GB6450; IEC726; DIN42523

Rated HV: 6, 6.3, 6.5, 10, 10.5, 11 kV Rated LV: 0.4 kV

Tapping Range: 22.5% , 5% or others Connection symbol: Dyn11 or Yyn0 or others


Insulation level: L175/-; AC28(35)/3 Protection level: IP00, IP20, IP23, or others

Parameter List
Rated Losses (W) No-load LP Impedance Overall Dimension (mm) Total
Power Current dB Voltage Mass
No-load Load L LI H W
(kVA) (%) (A) (%) (Kg)
30 190 710 3.2 45 880 550 815 1000 330
50 270 1000 2.8 45 880 550 970 1000 480
63 360 1200 2.7 45 880 550 1015 1000 510
80 370 1380 2.6 45 980 550 1030 1000 590
100 400 1570 2.4 45 980 550 1030 1000 640
125 470 1840 2.2 45 980 550 1145 1000 760
160 540 2130 2.2 45 4 1135 550 1019 1000 950
200 620 2530 2.0 45 1000 550 1185 1000 1000
250 720 2750 2.0 45 1135 550 1225 1000 1226
315 880 3470 1.8 45 1195 660 1170 1100 1400
400 980 3990 1.8 45 1195 660 1240 1200 1550
500 1160 4880 1.8 45 1255 660 1310 1200 1830
630 1340 5870 1.6 45 1300 820 1385 1200 2120
630 1300 5960 1.6 45 1390 820 1385 1200 1910
800 1520 6950 1.6 50 1450 820 1350 1200 1340
1000 1770 8130 1.4 50 1520 820 1410 1200 2760
1250 2090 9690 1.4 50 6 1570 820 1525 1200 3480
1600 2450 11730 1.4 50 1615 1070 1688 1400 4000
2000 3320 14450 1.2 50 1810 1070 1596 1400 4870
2500 4000 17170 1.2 50 1900 1070 1670 1400 5850
3150 4300 22900 1.2 50 2020 1070 1820 1600 6700
Note:
The data above are used for choosing the type and design of equipment.

SC10 Series 35 kV Distribution Transformer with OCTC


Product Standards: GB/T10228; GB6450; IEC726; DIN42523

Rated HV: 35, 38.5 kV Rated LV: 0.4 kV


Tapping Range: 22.5% , 5% or others Connection symbol: Yd11 or Ynd11 or others
Insulation level: L1170/-; AC70/3 Protection level: IP00, IP20, IP23, or others

Parameter List
Rated Losses (W) No-load LP Impedance Overall Dimension (mm) Total
Power Current dB Voltage Mass
No-load Load L LI H W
(kVA) (%) (A) (%) (Kg)
30 360 1050 3.2 45 1250 550 1210 750 530
50 480 1270 3.2 45 1335 660 1110 750 680
80 650 1750 3.2 45 1410 660 1280 750 980
100 700 2300 2.0 45 1410 660 1280 750 1020
125 760 2440 2.0 45 1440 660 1270 750 1130
160 860 2800 2.0 45 1520 660 1500 1100 1280
200 960 3050 2.0 45 1520 660 1580 1100 1400
250 1080 3500 2.0 45 1520 660 1680 1100 1500
315 1160 4170 2.0 45 1520 660 1732 1100 2000
400 1560 5360 2.0 45 1560 660 1660 1000 2155
500 1800 6590 2.0 45 6 1710 820 1605 1200 2400
630 1840 7680 1.8 45 1830 820 1775 1200 3150
800 2160 9100 1.8 50 1920 820 2070 1200 3600
1000 2400 10460 1.8 50 1920 820 2210 1400 4675
1250 2800 12670 1.6 50 2050 820 2040 1400 5200
1600 3200 15390 1.6 50 2085 1070 2300 1400 7240
2000 3760 18110 1.4 50 2085 1070 2350 1400 7330
2500 4400 21680 1.4 50 2130 1070 2484 1400 8200
Note:
The data above are used for choosing the type and design of equipment.

SC10 Series 35 kV Power Transformer with OCTC


Product Standards: GB/T10228; GB6450; IEC726; DIN42523
Rated HV: 35, 38.5 kV Rated LV: 3.15, 6, 6.3, 10, 10.5, 11 kV

Tapping Range: 42.5% , or others Connection symbol: Yd11 or Ynd11 or others


Insulation level: L1170/60; AC70/20 Protection level: IP00, IP20, IP23, or others

Parameter List
Rated Losses (W) No-load LP Impedance Overall Dimension (mm) Total
Power Current dB Voltage Mass
No-load Load L LI H W
(kVA) (%) (A) (%) (Kg)
800 2230 9350 1.9 50 1920 820 1900 1200 2000
1000 2460 10880 1.9 50 6 1920 820 1940 1200 2500
1250 3100 12840 1.7 50 2050 820 2040 1200 3200
1600 3650 15390 1.7 50 2200 1070 2020 1400 4500
2000 4200 18110 1.5 50 2290 1070 2280 1400 5800
2500 4800 21680 1.5 50 7 2290 1070 2370 1400 7600
3150 6000 24400 1.3 60 3050 1070 2370 1400 8700
4000 6960 29330 1.3 60 2800 1070 2600 1400 11370
5000 8320 34770 1.1 65 8 2700 1070 2370 1400 12935
6300 9840 40630 1.1 65 3120 1070 2850 1400 16000
8000 11200 45050 1 70 3180 1070 2950 1400 17800
10000 12800 55250 1 70 3160 2040 2920 2160 20500
12500 16800 56220 0.8 75 9 3480 2040 2850 2160 31250
16000 20000 62740 0.8 80 3980 2040 3200 2160 38000
20000 23750 73290 0.8 80 3980 2040 3360 3290 42000
10
25000 28500 88120 0.5 80 4220 2040 3390 2160 45000
Notes:
1. The data above are just for reference;
2. Our company can provide other products according to clients requirement;
3. Our company reserves the right to modify the parameters stated.

SCZ(B)10 Series 35 kV Distribution Transformer with OLTC


Product Standards: GB/T10228; GB6450; IEC726; DIN42523

Rated HV: 35, 38.5 kV Rated LV: 3.15, 6, 6.3, 10, 10.5, 11 kV
Tapping Range: 42.5% , or others Connection symbol: Yd11 or Ynd11 or others

Insulation level: L1170/-; AC70/3 Protection level: IP00, IP20, IP23, or others
Parameter List
Rated Losses (W) No-load LP Impedance Overall Dimension (mm) Total
Power Current dB Voltage Mass
No-load Load L LI H W
(kVA) (%) (A) (%) (Kg)
315 1160 4170 2.0 45 1520 660 1732 1100 2000
400 1360 5360 2.0 45 1560 660 1660 1000 2155
500 1600 6590 2.0 45 1710 820 1605 1200 2400
630 1840 7680 1.8 45 1830 820 1775 1200 3150
800 2160 9100 1.8 50 1920 820 2070 1200 3600
6
1000 2400 10460 1.8 50 1920 820 2210 1400 4675
1250 2800 12670 1.6 50 2050 820 2040 1400 5200
1600 3200 15390 1.6 50 2085 1070 2300 1400 7240
2000 3760 18110 1.4 50 2085 1070 2350 1400 7330
2500 4400 21680 1.4 50 2130 1070 2484 1400 8200
Notes:
1. The overall dimension doesnt include on-load tap changer.
2. The on-load tap changer can be divided into air type and vacuum type. When placing the order, please
indicate which type will be used;
3. When placing the order, please indicate the installation position of on-load tap changer;
4. The data above are just for reference;
5. Our company can provide other products according to clients requirement;
6. Our company reserves the right to modify the parameters stated.

SCZ10 Series 35 kV Power Transformer with OLTC


Product Standards: GB/T10228; GB6450; IEC726; DIN42523

Rated HV: 35, 38.5 kV Rated LV: 3.15, 6, 6.3, 10, 10.5, 11 kV

Tapping Range: 42.5% , or others Connection symbol: Yd11 or Ynd11 or others


Insulation level: L1170/60; AC70/20 Protection level: IP00, IP20, IP23, or others

Parameter List
Rated Losses (W) No-load LP Impedance Overall Dimension (mm) Total
Power Current dB Voltage Mass
No-load Load L LI H W
(kVA) (%) (A) (%) (Kg)
800 2230 9350 1.9 50 1920 820 1900 1200 2000
1000 2460 10880 1.9 50 6 1920 820 1940 1200 2500
1250 3100 12840 1.7 50 2050 820 2040 1200 3200
1600 3650 15390 1.7 50 2200 1070 2020 1400 4500
2000 4200 18110 1.5 50 2290 1070 2280 1400 5800
2500 4800 21680 1.5 50 7 2290 1070 2370 1400 7600
3150 6000 24400 1.3 60 3050 1070 2370 1400 8700
4000 6960 29330 1.3 60 2800 1070 2600 1400 11370
5000 8320 34770 1.1 65 8 2700 1070 2370 1400 12935
6300 9840 40630 1.1 65 3120 1070 2850 1400 16000
8000 11200 45050 1 70 3180 1070 2950 1400 17800
10000 12800 55250 1 70 3160 2040 2920 2160 20500
12500 16800 56220 0.8 75 9 3480 2040 2850 2160 31250
16000 20000 62740 0.8 80 3980 2040 3200 2160 38000
20000 23750 73290 0.8 80 3980 2040 3360 3290 42000
25000 28500 88120 0.5 80 10 4220 2040 3390 2160 45000
Notes:
1. The overall dimension doesnt include on-load tap changer.
2. The on-load tap changer can be divided into air type and vacuum type. When placing the order, please
indicate which type will be used;
3. When placing the order, please indicate the installation position of on-load tap changer;
4. The data above are just for reference;
5. Our company can provide other products according to clients requirement;
6. Our company reserves the right to modify the parameters stated.
X Manufacturing and Testing Equipments
Manufacturing Equipments
Dept. Equipment Manufacturer Specification Quantity
Digital Control Insulation
Japan HEIAN ER-131PMC 1 pcs
Manufacturing Center
Shenyang Shenjing
Impregnating Curing
Water-supply Equipment QQ-1600 2 pcs
System
Plant
Juli Company with
Vertical Winding Machine JLM200 6pcs
Winding German Technology
Workshop Horizontal Winding Juli Company with
JWM160 20pcs
Machine German Technology
Wound core winding Shanghai Tongli Electric
JTR-1 2pcs
machine Equipment plant
Pressure Charter America ENPACK PUT1201E 2pcs
Ningbo HaiYue Electric
Curing oven HB-2 2pcs
Company
Qingdao Double Star
Sandblasting Equipment QL2630 1set
Group
Wuxi Compressor
Screw Compressors LGFD-12/8-X 2pcs
Company
Digital Flame Cutting
Tank MESSER Company COMCUT 2pcs
Machine
Workshop
Electrostatic Spraying Shandong Blue Arrow
JT-360 1set
Systems Technologies
Blasting Painting System Qingdao Huaqing Group QH2-800 1set
Corrugated Tank Xian Kai Yuen Electrical
BWYX-1300 1pcs
Production Line Equipment Company
Assembling Switzerland Shear Line Swiss ASTRONIC 1000mm 1pcs
Workshop Core Shear Line Italy l.a.e Company TE60 1pcs
German GEORGE
Core Shear Line 800mm 1pcs
Company
Xian Kai Yuen Electrical
Roller Trimming XBJ1-05/05 2pcs
Equipment Company
Cold welding clamp German KLAUKE PK12040C 2pcs
Core balers America ENERPAC VT-19 2pcs
Dual-Beam Bridge Type Finland KONECRANES
250/50T 2pcs
Crane Company
Dual-Beam Bridge Type German DEMAG
50/16T 4pcs
Crane Company
Pressure Changing Type Shenyang Tianyi
Vacuum Drying Vacuum Technology ZGB- 6pcs
Equipment Company
Shenyang Youbang
Kerosene Vapor Drying
Vacuum Company with VPD-300 2pcs
Equipment
German Technology
Vacuum Oil Purifying
Sweden ABB Company VH060 1pcs
Machine
Vacuum Oil Purifying
Sweden ABB Company VH040 1pcs
Machine
German HEDRICH
Vacuum Casting Device PEK-150/150 2pcs
Company
Foil-around Machine France B.R. Company FBR-1200 2pcs
Dry-tranform
Double-layer foil winding Xian Kai Yuen Electrical
er workshop BRJ-1400 2pcs
machine Equipment Company
Ningbo HaiYue Electric
Curing oven HB-2 6pcs
Company
Server HP HPML370G3 4pcs
laser printer HP HP3300 2pcs
Technical
Color Laser Printer HP HP8550 1pcs
Dept.
Graphics Printer / / 4pcs
Computer Lenovo / 80pcs

Swiss Astronic Core Cutting Machine Vertical Winding Machine


Core and winding assembly machine Kerosene Vapor Drying Equipment

Testing Equipments
No Equipment Type Qty Use Manufacturer
No-load, load
15000kVA Harbin Electrical
1 Frequency generator 1 set and temperature
50Hz .3kV Machinery Plant
rise test
Non-PD IF generator Induced and PD Harbin Electrical
2 750kVA 200Hz 3kV 1set
sets test Machinery Plant
Wuhan High
Impulse voltage
3 4000kV 600kJ 1set Lightning Voltage Research
generator
Impulse test Institute
4 peak voltage meter TDS3012B 1pcs U.S. NI Company
Compensation 189 Compensation Beijing capacitor
5 BMF-12.5-150-1W
capacitor pcs test plant
Induction Voltage
6 TSA-1000 1pcs Yingkou Tebian
Regulator
Intermediate LuNeng Mount
7 10000kVA/40 1pcs
transformer Tai
Dandong
Performance test
8 CT HL28 60kV 3pcs transformer
factory
Dandong
9 PT HJ12 60kV 3pcs transformer
factory
Insulation Resistance Insulation Wuhan Kangda
10 KD2677 2pcs
Tester Characteristics Company
Photoconductive
Dielectric loss
11 dielectric loss tester GW-2A 2pcs Baoding Jin Di's
measurement
computer
Power frequency
Power frequency Jiangsu Leiyu
12 YD-1000/500 1pcs voltage
voltage machine Company
withstand test
Automatic Variable Voltage Ratio
13 ZBY-111 1pcs Wuhan test
Ratio Tester Test
DC Resistance
14 DC Resistance Tester JD2510 3pcs Baoding Jin Di's
Test
Ningxia
On-load tap-changer On-load tap Electronic
15 5535 1pcs
Tester changer test Instrument
Factory
Wuhan High
Power Harmonics No-load current
16 DSC-1 1pcs Voltage Research
Meter harmonic
Institute
Broadband Power
17 D6000T 1pcs Swiss LEM
Analyzer
Performance test
Transformer Baoding Huibang
18 HB2810A 1pcs
characteristics tester Co
Jiangxi Hongan
19 Sound Level Meter HS5670 1pcs Sound level test
CO.
Swiss Harvalad
20 PD instrument JFD-2B 1pcs PD test
company
Winding deformation Winding Shandong Power
21 RZBX-1 1pcs
Instrument deformation test Design Institute
Chromatographic Chromatographi
22 SP3420 1pcs CN-US Co.
analyzer c analyze
XI Product Quality Guarantee and After-sale Service Commitment
The company persists in the tenet of "To supply updated electrical equipment for the society ". The
company has strong technical force, advanced manufacturing facilities, perfect testing devices, excellent
product quality control system and it has passed the ISO9001 quality certificate in 2000.
For the success in the furious competition in the market and meeting customers' demand, the company
adheres to the market orientation and focuses on the customer. It has been highly praised by the customer
with its quick response, excellent services and well-qualified products.
Our company solemnly declares to all customers:
The product's lifetime is no less than 30 years.
On receiving the bidding documents, we will evaluate the product according to the technical specification.
After signing contract, technicians will be organized to analyze the technical specification in time and all
the requirements will be brought into effect one by one.
We will select qualified subcontractor of components, and we will strictly carry out the quality control
and inspection for raw material and components according to requirements of quality system.
Based on the principle of being responsible for customer, we require all the subcontractors of components
to produce well-qualified products according to end-user's contract and technical specification.
For the fittings selected by clients, we will provide all corresponding technical conditions and documents
in agreement with customer's requirement.
All performance indexes and technical parameters of the transformer will completely meet and be
superior to National standards and IEC standards.
All key parts with quality defects occurred during manufacturing and inconsistent with contract or
technical specification will be repaired or replaced unconditionally. We will firstly solve all the quality
problems taken place during installation to meet the requirements of project schedule, and then we will
analyze the responsibilities.
The customer is welcomed to witness the manufacture and test of products during manufacture and we
shall provide all conveniences.
We will provide best after-sale services and guide installation and debugging of the transformer freely.
Receiving client's requirements, our serving staffs will arrive at the site within the shortest time.
Our company has established mature periodic return visit system. We will send the writing questionnaire
or visit the site at regular intervals.
Service Hotline:
Telephone0086-538-8639963 Fax0086-538-8639891
Contact person:
Name: Mi Jianmeng Job Title: Service Engineer

Shandong Luneng Mount Tai Electric Equipment Co., Ltd