You are on page 1of 31

Chapter 20

Exergoeconomic Analysis of Thermal


Systems
Chapter Outline
20.1 Introduction 393 20.6.2 Relations for Devices in a Single Generating
20.2 Economic Aspects of Exergy 394 Station 409
20.2.1 Exergy and Economics 395 20.6.3 Generalization of Results 410
20.2.2 Energy and Exergy Prices 396 20.7 Exergoeconomics Extended: Exergy, Cost, Energy, and
20.3 Modeling and Analysis 397 Mass Analysis 411
20.3.1 Fundamental Relationships 397 20.7.1 The EXCEM Analysis Concept 411
20.3.1.1 Thermodynamic Balances 397 20.7.2 Development of a Code for EXCEM Analysis 412
20.3.1.2 Economic Balances 398 20.7.3 Illustrative Examples of EXCEM Analysis 412
20.3.2 Definition of Key Terms 398 20.7.3.1 Pump 412
20.3.3 Ratio of Thermodynamic Loss Rate to Capital 20.7.3.2 Steam Turbine 412
Cost 398 20.7.3.3 Coal-Fired Electrical Generating
20.4 Key Difference between Economic and Station 413
Thermodynamic Balances 399 20.7.3.4 Exergy Loss and Cost Generation 413
20.5 Example: Coal-Fired Electricity Generation 400 20.8 Specific Exergy Cost Analysis 415
20.5.1 Plant Description and Data 400 20.8.1 SPECO Analysis Methodology 415
20.5.1.1 Thermodynamic Data 400 20.8.2 Illustrative Example: SPECO Analysis of
20.5.1.2 Economic Data 400 Hydrogen Production via Biomass Gasification 416
20.5.2 Data Categorization 401 20.8.2.1 System Descriptions 416
20.5.3 Results and Discussion 401 20.8.2.2 Exergy Analysis 420
20.6 Case Study: Electricity Generation from Various 20.8.2.3 SPECO Analysis 420
Sources 405 20.9 Closing Remarks 422
20.6.1 Results and Discussion 406 Problems 422

KEYWORDS
ABSTRACT Exergy; Economics; Exergoeconomic, Thermoeconomic, SPECO
In this chapter, exergy-based economic-analysis methods for analysis; EXCEM analysis; Hydrogen production; Biomass
analyzing thermal systems are described, such as exer- gasification; Electricity generation.
goeconomic; thermoeconomic; specific energy cost; and exergy,
cost, energy, and mass and analyses. Such techniques seek to
determine of the appropriate allocation of economic resources so
as to optimize the design and/or operation of a system; and/or the 20.1 INTRODUCTION
economic feasibility and profitability of a system. The relations In the analysis and design of energy systems, techniques
between thermodynamic losses and capital costs are considered are often used that combine scientific disciplines (mainly
and examined in the chapter for systems and their constituent
thermodynamics) with economic disciplines (mainly
devices, and applied to electrical generating stations operating
on a range of fuels (coal, oil, uranium). The approach utilized
cost accounting) to achieve optimum designs. For energy
suggests that correlations exist between capital costs and ther- conversion devices, cost accounting conventionally considers
modynamic losses for devices, and that the existence of such unit costs based on energy. Many researchers have recom-
correlations likely implies that designers knowingly or mended that costs are better distributed among outputs if cost
unknowingly incorporate the recommendations of second-law accounting is based on the thermodynamic quantity exergy.
analysis into process designs indirectly One rationale for this statement is that exergy, but not

Exergy. http://dx.doi.org/10.1016/B978-0-08-097089-9.00020-6
2013 Ibrahim Dincer and Marc A. Rosen. Published by Elsevier Ltd. All rights reserved. 393
394 Exergy

energy, is often a consistent measure of economic value. In l Several detailed reviews of these analysis techniques
addition, exergy-based economic-analysis methodologies have been published (e.g., Bejan, 1982; Tsatsaronis,
exist (e.g., exergoeconomics, thermoeconomics). 1987; Kotas, 1995; Rosen and Dincer, 2003aed). These
Another approach for discussing the merits of thermo- reviews include discussions, comparisons, and critiques
economics identifies as important the ratio of thermody- of the different techniques.
namic loss rate to capital cost. The approach involves l Many articles on specific topics in this field have been
examining data for devices in systems, and showing that published, both separately and in volumes devoted in
correlations exist between capital costs and specific second large part to exergy methods.
law-based thermodynamic losses (i.e., total and internal
In this chapter, the relations between thermodynamic losses
exergy losses).
and capital costs are considered and examined for systems
A brief summary of existing analysis techniques, which
and their constituent devices. For illustration, several
integrate exergy and economics, is presented here. The
modern electrical generating stations are examined, and
goals of most such techniques include the determination of
possible generalizations in the relation between thermo-
the following:
dynamic losses and capital costs are suggested. The
l Appropriate allocation of economic resources to opti- considered electrical generating stations operate on a range
mize the design and/or operation of a system of fuels (coal, oil, uranium).
l Economic feasibility and profitability of a system (by This chapter provides insights into the relations
obtaining the actual costs of products, and their appro- between energy and exergy losses and capital costs for
priate prices) electrical generating stations, in particular, and for energy
systems, in general. These insights can assist in integrating
As pointed out earlier, cost accounting for energy thermodynamics and economics in the analysis and design
conversion devices conventionally considers unit costs based of energy systems.
on energy. Since exergy is a consistent measure of economic This chapter also highlights the merits of second-law
value more often than energy, various researchers have rec- analysis over the more conventional first-law analyses.
ommended that costs are better distributed among outputs Proponents of second-law analysis conventionally argue
based on exergy. In addition, many of these researchers have that its use can help improve process performance.
developed methods of performing economic analyses based Generally, however, the application of second-law analysis
on exergy, which are referred to by a variety of names (e.g., to existing mature technologies does not lead to signifi-
thermoeconomics, second-law costing, cost accounting, and cant design modifications or performance improvements.
exergoeconomics). These analysis techniques have the Consequently, these arguments and demonstrations alone
following common characteristics: do not convince many nonusers of second-law analysis of
the merits of using second-law along with conventional
l They combine exergy and economic disciplines to
first-law analysis techniques.
achieve the objectives listed above.
The approach presented here examines thermodynamic
l They recognize that exergy, not energy, is the
and economic data for mature devices, and shows that
commodity of value in a system, and they conse-
correlations exist between capital costs and thermodynamic
quently assign costs and/or prices to exergy-related
losses for devices. The existence of such correlations likely
variables.
implies that designers knowingly or unknowingly incor-
Tsatsaronis (1987) identifies four main types of analysis porate the recommendations of second-law analysis into
methodologies, depending on which of the following forms process designs indirectly (Rosen, 1986).
the basis of the technique:
l Exergy-economic cost accounting
20.2 ECONOMIC ASPECTS OF EXERGY
l Exergy-economic calculus analysis
l Exergy-economic similarity number Exergy is a useful concept in economics. In macroeco-
l Product/cost efficiency diagrams nomics, exergy offers a way to reduce resource depletion
and environmental destruction by using an exergy tax. In
A number of researchers have developed methods of per-
microeconomics, exergy has been combined beneficially
forming economic analyses based on exergy. These are not
with cost-benefit analysis to improve designs. By mini-
all reviewed here, but the following important points are
mizing the life cycle cost, we find the best system given
noted:
prevailing economic conditions and, by reducing exergy
l General discussions of the analysis techniques appear in losses, we often reduce environmental effects.
several textbooks (e.g., Bejan, 1982; Szargut et al., Designing efficient and cost-effective systems, which
1988; Kotas, 1995). also meet environmental requirements, is one of the
Chapter | 20 Exergoeconomic Analysis of Thermal Systems 395

foremost challenges that engineers face. Given the worlds and it has had a very profound impact on the energy conversion
finite natural resources and large energy demands, it is system community, to a point that it is difficult today to find
important to understand the mechanisms that degrade a design standard which does not make direct or indirect use of
energy and resources and to develop systematic approaches exergetic concepts in its search for an optimal configuration.
for improving systems while simultaneously reducing The same method has been extended to complex systems, like an
environmental impact. Exergy combined with economics industrial settlement, a complete industrial sector, and even entire
(both macro and micro) provides a powerful tool for the nations, and most recently has been brought to the attention of
systematic study and optimization of systems. energy agencies as a proposed legislative tool for energy planning
and policy making.
Extending these thoughts to economics, Sciubba (2001)
20.2.1 Exergy and Economics goes on to state that exergy analysis:
A number of researchers of the thermoeconomic aspects of
has always been regarded as unable to determine real design
energy systems cite Georgescu-Roegen (1971) as the father
optima, and therefore its use has been associated with customary
of the thermodynamics of economics and a pioneer in this
monetary cost-analysis; it was only recently that a complete and
field. Exergy and microeconomics forms the basis of
theoretically sound tool, based on a combination of mixed
thermoeconomics (Evans and Tribus, 1962), which is also
economic and thermodynamic methods and properly named
called exergoeconomics (Bejan et al., 1996) and exer-
thermoeconomics, was developed to industry standards. In this
gonomics (Yantovskii, 1994). The concept of utility is
approach, efficiencies are calculated via an exergy analysis, and
a central concept in macroeconomics and is also closely
non-energetic expenditures (financial, labour, and environ-
related to exergy. An exergy tax is an example of how
mental remediation costs) are explicitly related to the technical
exergy can be introduced into macroeconomics.
and thermodynamic parameters of the process under consider-
Some noteworthy comments by researchers in the areas
ation: the optimisation consists of determining the design point
of exergy and economics, and their relations to optimiza-
and the operative schedule that minimise the overall (monetary)
tion activities, are presented below.
cost, under a proper set of financial, normative, environmental,
Wall (1993) captures many of the key relations
and technical constraints. In spite of a long tradition of contrary
between exergy and economics when he points out that
opinion, exergy seems indeed to possess an intrinsic, very strong
the concept of exergy is crucial not only to efficiency
and direct correlation with economic values: one of the goals of
studies but also to cost accounting and economic analyses.
the Extended Exergy Accounting method (EEA) is to exploit this
Costs should reflect value, and since value is not generally
correlation to develop a formally complete theory of value based
associated with energy but with exergy, assignments of
indifferently on an exergetic or on a monetary metric (that is,
cost to energy lead to misappropriations, which are
a general valuing or pricing method in which kJ/kg or kJ/kW are
common and often gross. Using exergy content as a basis
consistently equivalent to $/kg and $/kW respectively), and it is
for cost accounting can help management price products
based on the fundamental idea that, while exergetic and monetary
and evaluate profits. Exergy can also assist in making
costs may have the same morphology (they represent the amount
operating and design engineering decisions and design
of resources that must be consumed to produce a certain
optimization. Exergy provides a rational basis for evalu-
output), their topology (structure) may be different, leading to the
ating fuels and resources; process, device, and system
possibility of different optimal design points.
efficiencies; dissipations and their costs; and the value and
cost of systems outputs. Finally, Sciubba (2001) comments how remarkable it is
Sciubba (2001) summarized exergy and its relation to that:
several economic and environmental factors:
another topic of paramount importance in the engineering field
Already fifty years ago, energy conversion systems were the target can be successfully tackled by EEA methods: this is the envi-
of a detailed analysis based on second law concepts. The analysis ronmental issue, taken in its extended meaning of impact of
indicated that the relevant design procedures of the time neglected anthropic activities on the pre-existing environment. A critical
to recognise that the irreversibility in processes and components analysis of the leading engineering approaches to the environ-
depend on the energy degradation rate and not only on the ratio mental issue is also reported in that work. It is stated that EEA,
between the intensities of the output and input flows, and that there which proposes a different quantifier (the extended exergy
is a scale of energy quality that can be quantified by an entropy content) for the analysis of processes and plants, can be
analysis. In essence, the legacy of this approach, universally regarded as a successful combination of the methods put forth.
accepted today, is that the idea of conversion efficiency based The EEA has indeed incorporated some elements of existing
solely on the first law considerations is erroneous and misleading. methods like Life-Cycle Analysis, Cumulative Exergy Analysis,
This method evolved throughout the years into the so-called Emergy Analysis, Extended Exergy Analysis, Complex Systems,
availability analysis, later properly renamed exergy analysis, and can thus be properly considered as a synthesis of the
396 Exergy

pre-existing theories and procedures of Engineering Cost considerably with several factors, including the capacity
Analysis, from which it has endeavoured to extract the most (or maximum power output), fuel consumption, and
successful characteristics, as long as they were suitable for fixed and variable costs for the system.
a consistent and expanded formulation based on the new concept l Gasoline and diesel fuel: Gasoline consists mainly of
of Extended Exergy. octane (C8H18), for which the exergy content is about
94% of the energy value. The exergy content of diesel
Sciubba (2001) proceeds to explain the how the name of
fuel (42.7 MJ/kg) is about 104% of its energy content,
EEA developed, noting that:
based on lower heating value. The exergy value is
the attribute extended refers to the additional inclusion in the higher than the energy value since, among other
exergetic balance of previously neglected terms (corresponding to reasons, the partial pressure of carbon dioxide is
the so-called non-energetic costs, to labor and to environmental included in the exergy calculation.
remediation expenditures); the word accounting has been sug- l Fuel oil: The exergy content of fuel oil is about 97% of
gested as a reminder that exergy does not satisfy a balance proper, its energy content (based on lower heating value). This
in that the unavoidable irreversibilities which characterize every value is approximately valid for heavier oils.
real process irrevocably destroy a portion of the incoming exergy; it l Town gas: This consists of roughly 65% hydrogen,
is also a reminder that the exergy destruction is the basis for the 20% carbon dioxide, and other substances. The specific
formulation of a theory of cost, because it clearly relates the idea energy and exergy contents of town gas are about 92.2 MJ/
that to produce any output, some resources have to be consumed. kg and 75.5 MJ/kg, respectively. Thus, the exergy content
constitutes about 82% of the energy content.
Sciubba (2001) also deals specifically with the problem
l Coal: The exergy content and price of coal varies
of an optimal design satisfying two requirements: (1)
dramatically for each coal type.
performing as specified by design data and abiding by all
l Wood products: The fuel value of wood products varies
constraints, and (2) displaying the most desirable behavior
considerably depending on water content. In the case of
under a certain set of operative conditions. This opti-
wood with a 50% water content, the energy and exergy
mality is not always expressed by a well-posed (in
values are 12.4 and 12.1 MJ/kg, respectively. These
a mathematical sense) objective function: in practice,
values are valid when the resulting water vapor used is
vaguely formulated optimization criteria are often the basis
condensed. It is difficult to calculate a relevant price due
of the design, which nevertheless cannot be regarded as
to the relatively small amounts of wood that are sold for
anything else than an optimal one, however fuzzy or
space heating purposes.
incompletely identified this optimum may be.
l District heating: The exergy of a given quantity of
district heat can be calculated as:
20.2.2 Energy and Exergy Prices Ex Q1  Tod =Tsu  Tod  InTsu =Tre 
The selection of energy sources for industrial and other where subscripts od, su, and re represent outdoor, supply,
uses is primarily governed by prices. Energy conversion and return, respectively. The supply and return tempera-
systems thus place demands on the energy supply system. tures within the district heating system are regulated with
Sometimes, energy conversion systems are shown to be respect to the outdoor temperature. For example, the supply
uneconomical over the long term, for example, prices are temperature is maintained at about 85 C at outdoor
incorrect or insufficient as a basis for planning. One temperatures above 2 C and is subsequently raised in
example of this situation is when prices are set based on inverse proportion to the outdoor temperature, up to 120 C
short-sighted political assessments or on insufficient at an outdoor temperature of 20 C. Thus, the exergy
knowledge of the resource in question and the conse- content varies with the outdoor temperature.
quences of its use. It is therefore important to find more For Goteborg, the mean exergy content is calculated at
sound methods for price setting. about 17% of the total heat quantity required for the heating
Prices based on exergy values can be designed to foster season. The district heating subscriber in Goteborg is
resource saving and efficient technology. The prices of charged a fixed rate plus an estimated energy rate. It can be
physical resources ought to be set more in relation to their seen that the price of exergy is thus six times more than that
physical value, that is, exergy. The differences between the of energy.
energy and exergy values for several common fuels, which The relative energy and exergy prices for various energy
can affect price setting, are briefly summarized below, commodities studied by Wall (1997) are listed in Table
based on a case study for Goteborg, Sweden (Wall, 1997): 20.1, after converting values from SEK to U.S. dollars
l Electricity: Electrical energy is in theory totally using the exchange rate for the year 2000. The highest
convertible to work. The energy price is therefore also energy price is that of gasoline, which is a refined fuel with
the exergy price. The price of electricity varies special areas of use. The lowest energy price is that of
Chapter | 20 Exergoeconomic Analysis of Thermal Systems 397

Here, input and output refer, respectively, to quanti-


TABLE 20.1 Average Relative Energy and Exergy Prices* ties entering and exiting through system boundaries;
of Some Common Energy Forms for Goteborg, Sweden generation and consumption refer, respectively, to quan-
Energy Exergy tities produced and consumed within the system; and
Energy commodity price, $/GJ price, $/GJ accumulation refers to buildup (either positive or nega-
tive) of the quantity within the system. Differential and
Electricity 1.00 1.00
integral forms of the general balance may be written. The
Gasoline 1.67 1.78 terms in Equation 20.1 are written as rates in the
Diesel 0.85 0.81 differential form:
Fuel oil #1 0.81 0.83 Input rate Generation rate  Output rate
Fuel oil #3e4 0.65 0.66  Consumption rate
Town gas 0.90 1.10
Accumulation rate (20.2)
Coal 0.28 0.29
and as amounts in the integral form:
Fire wood 0.29 0.29
Paper 0.21 0.22 Amount input Amount generated  Amount output
Wood paper 0.47 0.49  Amount consumed
District heating 0.83 4.89 Amount accumulated
*The energy price for electricity is taken as 1 $/GJ and the energy and (20.3)
exergy prices for other commodities are accordingly calculated relative to
the price for electricity. The differential balance describes what is happening
in a system at a given instant of time, and the integral
balance describes what happens in a system between two
paper, which is also probably the most expensive and least instants of time. Differential balances are usually applied
efficient to handle as fuel. The prices of coal and wood to continuous processes, and integral balances are usually
products are low. applied to batch processes. For steady-state processes,
The differences in energy and exergy prices in Table the accumulation rate term in the differential balance is
20.1 are small for each of the energy sources except district zero.
heating. The district heating subscriber pays much more for
exergy than other energy users. In such cases, a consumers 20.3.1.1 Thermodynamic Balances
heating bill often can be reduced by using a heat pump. Not Energy can be neither generated nor consumed, while
only is it often cost-effective for a consumer to obtain heat exergy is consumed during a process due to irreversibilities.
via a heat pump rather than subscribe to district heating, but Consequently, Equation 20.1 can be written for these
it is also cost-effective to use heat pumps in district heating quantities as follows:
systems. In this case, the energy and exergy prices for
district heating would be different than listed in Table 20.1. Energy input  Energy output Energy accumulation
A conscientious energy policy could speed up development (20.4)
of a movement toward efficient and resource-saving tech- Exergy input  Exergy output  Exergy consumption
nologies by basing prices on exergy, rather than energy.
Exergy accumulation
20.3 MODELING AND ANALYSIS (20.5)
The exergoeconomic methodology is described by consid- The output terms in Equations 20.4 and 20.5 can be
ering the balance equations for appropriate quantities. separated into product and waste components as follows:

Energy output Product energy output


20.3.1 Fundamental Relationships
Waste energy output (20.6)
As pointed out earlier, a general balance for a quantity in
a system may be written as:
Input Generation  Output  Consumption Exergy output Product exergy output
Accumulation (20.1) Waste exergy output (20.7)
398 Exergy

20.3.1.2 Economic Balances The capital cost is defined here using the cost balances
in Equations 20.8 and 20.9 and is denoted by K. Capital
Cost is an increasing, nonconserved quantity. The general cost is simply that part of the cost generation attributable to
balance in Equation 20.1 can be written for cost as follows: the cost of equipment:
Cost input Cost generation  Cost output KhCapital cost of equipment (20.12)
Cost accumulation (20.8)
Capital cost is, for simplicity, the only economic term
Cost input, output, and accumulation represent, considered here. It is noted that with this approach there is
respectively, the cost associated with all inputs, outputs, no need to know either the costs associated with inputs or
and accumulations for the system. Cost generation corre- the cost allocations among outputs. It can be argued that it
sponds to the appropriate capital and other costs associated is more rational to use the entire cost generation term, as
with the creation and maintenance of a system. That is, defined by Equation 20.9, in place of capital cost. The
principal reason that capital costs are used here is that
Cost generation Captial cost of equipment the use of the cost generation term significantly increases
the complexity of the analysis, since other numerous
All other creation and maintenance
economic details (interest rates, component lifetimes,
costs (20.9) salvage values, etc.) must be fully known. There are two
main justifications for this simplification:
Other costs include, for example, interest and insurance
costs. The cost generation rate term in a differential cost l Capital costs are often the most significant component
balance represents the total cost generation levelized over of the total cost generation. Hence, the consideration of
the operating life of the system. The amount of cost only capital costs closely approximates the results when
created term in an integral cost balance represents the cost generation is considered.
portion of the total cost generation accounted for in the time l Cost generation components other than capital costs
interval under consideration. often are proportional to capital costs. Hence, the trends
described are in qualitative agreement with those iden-
tified when the entire cost generation term is considered.
20.3.2 Definition of Key Terms For a thermal system operating normally in a continuous
Two types of thermodynamic losses are considered. These steady-state steady-flow process mode, the accumulation
are defined here, with the aid of differential forms of the terms in Equations 20.1e20.5 and 20.8 are zero. Hence, all
thermodynamic balances already described in Equations losses are associated with the already discussed terms L_ en
20.4e20.7. For simplicity, it is assumed here that no losses and L_ ex. The energy and exergy loss rates can be obtained
are associated with the accumulation terms in the energy through the following equations:
and exergy balances in Equations 20.4 and 20.5. X
L_en Energy Flow Rates
Energy losses can be identified directly from the energy
inputs
balances in Equations 20.4 and 20.6. For convenience, the X
energy loss rate for a system is denoted in the present  Energy Flow Rates (20.13)
analysis as L_ en, (loss rate based on energy). As there is only products
one loss term, the waste energy output, in Equation 20.6 X
L_ex Exergy Flow Rates
is as follows: inputs
L_en hWaste energy output rate (20.10) X
 Exergy Flow Rates (20.14)
products
Exergy losses can be identified from the exergy
balances in Equations 20.5 and 20.7. There are two types of
where the summations are over all input streams and all product
exergy losses: (1) the waste exergy output in Equation
output streams. Equations 20.13 and 20.14 are obtained by
(20.7), which represents the loss associated with exergy
rearranging Equations 20.4e20.7, 20.10, and 20.11.
that is emitted from the system, and (2) the exergy
consumption in Equation 20.5, which represents the
internal exergy loss due to process irreversibilities. These 20.3.3 Ratio of Thermodynamic Loss Rate to
two exergy losses sum to the total exergy loss. Hence, the Capital Cost
loss rate based on exergy, L_ ex, is defined as follows:
A parameter, R, is defined as the ratio of thermodynamic
L_ex hExergy consumption rate loss rate L_ to capital cost K as follows:
Waste exergy output rate (20.11) _
RhL=K (20.15)
Chapter | 20 Exergoeconomic Analysis of Thermal Systems 399

The value of R generally depends on whether it is based on reasonable to allocate part of the total costs to it.
energy loss rate (in which case it is denoted Ren,), or exergy Figure 20.2 presents energy, exergy, and cost balances for
loss rate (Rex), as follows: Nanticoke Generating Station, a typical coal-fired electrical
_
Ren hL=K (20.16) Stack gas

and
Rex hL_ex =K (20.17) Fuel

Note that one can consider four main thermodynamic


Electricity
loss rates (Rosen and Dincer, 2003aed): (1) energy (L_ en); Air
(2) exergy (L_ ex); (3) internal exergy (L_ ex-i), that is, exergy
Cooling water
consumptions due to process irreversibilities within the
system; and (4) external exergy (L_ ex-e), that is, the waste FIGURE 20.1 A coal-fired electrical generating station. Minor flows
outputs of exergy across a system boundary. Note that L_ ex-i such as ash and miscellaneous heat losses are not shown.

L_ ex-e L_ ex for a system and, since energy is conserved, (a) Air Ash Stack
all energy losses are associated with external waste emis- 0 0 gas
sions. Also, capital cost (K) values for the equipment in 62
a system are considered and, to simplify the economic
portion of the work, other costs (e.g., interest and insurance Coal
costs) are not considered. Values of the parameter R based 1427
on energy loss rate, and on total, internal, and external (843) Electricity 511
exergy loss rates are considered. In investigating sets of
R values, maximum (Rmax), minimum (Rmin), mean (Rm), CW 0 CW 11
standard deviation (SD(R)), and coefficient of variation
(CV(R)), which is the ratio of standard deviation to mean, (b) Air Ash Stack gas
are considered. 0 0 0

20.4 KEY DIFFERENCE BETWEEN Electricity


ECONOMIC AND THERMODYNAMIC Coal 8.5
+4.90
3.6
BALANCES
An important difference exists between the cost balance CW 0 CW 0
and the energy and exergy balances. In the latter two, the
values associated with all quantities are defined by scien- (c) Air Ash Stack gas
tific relationships. For the cost balance, however, only cost 0 0 74
input and generation are defined. The distribution of costs
over outputs and accumulations is not defined. Costs are Electricity 511
allocated subjectively, depending on the type and purpose Coal
of the system and other economic considerations. For 1368
example, costs may be distributed proportionally to all
outputs and accumulations of a quantity (such as mass, CW
746
energy, or exergy), or all nonwaste outputs and accumula-
CW 0
tions of a quantity.
Consider, for example, a coal-fired electrical generating FIGURE 20.2 Energy, cost, and exergy balances for the coal-fired
Nanticoke Generating Station. The rectangle in the center of each diagram
station operating in a steady-state steady-flow mode
represents the station. Widths of flow lines are proportional to the relative
(Figure 20.1). Clearly, subjective decisions must be made magnitudes of the represented quantities. CW, cooling water. (a) Exergy
regarding the allocation of costs among outputs (i.e., the balance showing flow rates (positive values) and consumption rate
electricity, stack gas, and cooling water outputs may each (negative value in parentheses, denoted by hatched region) of exergy (in
be allocated part of the input and generation costs). The MW). (b) Cost balance showing flow rates (positive values) and creation
rate (positive value in parentheses, denoted by hatched region) of cost (in
allocations depend on the uses for the outputs. The exhaust
Canadian /kWh). (c) Energy balance showing flow rates of energy (in
cooling water, for example, may be treated either as MW). (Adapted from Rosen and Scott, 1987, where further details are
a waste, in which case it may be reasonable to allocate none available.) Costs have been modified to 2002 Canadian cents (as explained
of the costs to it, or as a byproduct, in which case it may be in the text).
400 Exergy

FIGURE 20.3 Process flow diagram for


a single unit of the coal-fired electrical
S20 Q5 + Q6
generating station. Symbols identifying
devices are explained in the legend and iden- P8
tifying flows are explained in Table 11.4a. B C D D E
S5A
Lines exiting turbines represent flows of
extraction steam. A, steam generator and S4 S15
reheater; B, high-pressure turbine; C, inter- S33
S2 A S21
mediate-pressure turbine; D, low-pressure
turbines; E, generator and transformer; F, S1
S14
condenser; G, hot well pump; H, low-pressure S36 S37
F
heat exchangers; I, open de-aerating heat S42 S8 S22 S25 S34 S35 S13
exchanger; J, boiler feed pump; K, high- S10
P1
pressure heat exchangers. I
K S41 S39 H S11 G
S40
S12 J S38
P15

generating station (for details, see Section 11.6 of this shown in Figure 20.3, and the corresponding symbols
book). Thermodynamic data for this station are used in the identifying the streams are described in Table 20.3.
example in the next section. In Figure 20.2, the input and The main findings of the energy and exergy analyses of
generation costs are allocated to the product electricity, and the station in Section 11.6 are as follows:
the exhaust cooling water and stack gas are treated as
l For the overall plant, the energy efficiency, defined as
wastes.
the ratio of net electrical energy output to coal energy
The costs shown in Figure 20.2 are in 2002 Canadian
input, is 37.4%, and the corresponding exergy efficiency
cents. These costs are evaluated by modifying the original
35.8%.
data, in 1982 Canadian cents, using the Consumer Price
l In the steam generators, the energy and exergy effi-
Index (CPI) tabulated by Statistics Canada (accessible via
ciencies are evaluated considering the increase in
www.statcan.gc.ca). The CPI data, which represent
energy or exergy of the water as the product. The steam
changes in prices of all goods and services purchased for
generators appear significantly more efficient on an
consumption, indicate that $1.00 in 1982 has the same
energy basis (94.6%) than on an exergy basis (49.5%),
buying power as $1.82 in 2002.
indicating that although most of the input energy is
transferred to the preheated water, the energy is
20.5 EXAMPLE: COAL-FIRED ELECTRICITY degraded as it is transferred. Most of the exergy losses in
GENERATION the steam generators are associated with internal
consumptions (mainly due to combustion and heat
The exergoeconomic methods described in this chapter are transfer).
illustrated for the case of a coal-fired electrical generating l In the condensers, a large quantity of energy enters
station. (about 775 MW for each unit), of which close to 100%
is rejected; and a small quantity of exergy enters (about
20.5.1 Plant Description and Data 54 MW for each unit), of which about 25% is rejected
and 75% internally consumed.
The thermodynamic and economic data used in the analysis l In other plant devices, energy losses are very small
and the corresponding sources of the data are given, and the (about 10 MW total), and exergy losses are moderately
means by which the data are categorized and relevant small (about 150 MW total) and almost completely
quantities evaluated are described. associated with internal consumptions.

20.5.1.1 Thermodynamic Data


20.5.1.2 Economic Data
Thermodynamic data for the coal-fired Nanticoke Gener-
ating Station are used. The station is described in Section In this example, typical economic data for similar power
11.6 of this book but, to assist the reader, some of the main plants instead of exact economic data are used. Conse-
process data for a station unit are summarized in Table quently, capital cost data are used for the coal-fired Harry
20.2. A detailed flow diagram for a single station unit is Allen Station in southern Nevada. This station contains
Chapter | 20 Exergoeconomic Analysis of Thermal Systems 401

TABLE 20.2 Main Process Data for a Unit (500 MW Net Electrical Output) in a Coal-Fired Generating Station*

Mass flow rates (kg/s) Temperatures ( C) Pressures (MPa)


47.9 (for coal at full load) 120 (for flue gas) 16.9 (for primary boiler steam)
454 (for primary boiler steam) 253 (for boiler feedwater) 4.0 (for reheat boiler steam)

411 (for reheat boiler steam) 538 (for primary boiler steam) 0.005 (for condenser)
18,636 (for cooling water) 538 (for reheat boiler steam)
8.3 (for rise in cooling water)

*Based on data for Nanticoke Generating Station in Section 11.5 of this book.

three units of 500 MWe net output each, which are similar l None of the steam exhausted or extracted from the
to the Nanticoke units. Capital cost data from Bechtel turbines is considered waste emission (Case I)
Power Corporation (1982) and Nevada Power Company are l Only the steam exhausted to the condenser from the
used, as listed by Tsatsaronis and Winhold (1985) in Table low-pressure turbine is considered waste emission
20.6, in a paper describing an exergoeconomic analysis of (Case II)
the Harry Allen Station. The relevant data are given in l All steam exhausted or extracted from the turbines is
Table 20.4, following the device categorization described in considered waste emission (Case III)
the next subsection. The costs shown in Table 20.4 (as well
Also, two cases are considered for the preheating devices:
as Tables 20.5 and 20.6 and Figures 20.4 and 20.5) are in
2002 U.S. dollars. These costs are evaluated by modifying l No waste emissions exist (Case I)
the original data in 1982 U.S. dollars in Tsatsaronis and l The stream flowing from the preheating devices to the
Winhold (1985) and Bechtel Power Corporation (1982), condenser (S38 in Figure 11.4a) is considered waste
using the CPI tabulated by the U.S. Department of Labors emission (Case II)
Bureau of Labor Statistics (accessible at www.bls.gov/cpi).
Since the station operates normally in a continuous steady-
The CPI data, which represents changes in prices of all
state steady-flow process mode, the accumulation terms in
goods and services purchased for consumption, indicate
Equations 20-1e20.5 and 20.8 are zero. Hence, all losses
that $1.00 in 1982 has the same buying power as $1.86 in
are associated with the already discussed terms L_ en and L_ ex.
2001.
The energy and exergy loss rates are evaluated by consid-
ering devices or groups of devices in Figure 11.4a and the
20.5.2 Data Categorization data in Table 11.4a. In Equations 20.13 and 20.14 the
summations are over all input streams and all product
In the present analysis, the generating station is subdivided output streams.
into the following devices:
l Turbine generators
l Steam generators (including the steam generator and 20.5.3 Results and Discussion
reheater, and the air preheater and fan)
Values of L_ en, L_ ex, and K for the unit of the coal-fired
l Preheating devices (including all heat exchangers and
electrical generation station considered are presented in
pumps used for preheating)
Table 20.5. Plots of thermodynamic loss rate are presented
l Condensers
in Figure 20.4 as a function of capital cost for the overall
l Overall station (including the above devices, plus all
generating station and the following station devices:
other plant devices)
turbine generators, steam generators (Cases I, II, and III),
Waste emissions are output cooling water for the preheating devices (Cases I and II), and condensers.
condenser, stack gas for the steam generator, and both Energy loss rate (Figure 20.4a) and exergy loss rate
quantities for the total plant. Miscellaneous heat losses are (Figure 20.4b) are considered. Figure 20.4 is based the
treated as waste emissions for all devices. data in Table 20.5.
Ambiguity exists regarding what the material waste Values of the thermodynamic-loss-rate-to-capital-cost
emissions for the turbine generators and preheating devices ratios Ren and Rex for the devices in the generating station
should be. Consequently, three cases are considered for the are listed, along with values of K, L_ en, and L_ ex, in Table
turbine generators: 20.5, and plotted in Figure 20.5. Note that the value of R for
402 Exergy

TABLE 20.3 Flow Data for a Unit (500 MWe Net Output) in a Coal-Fired Generating Stationa

Mass flow Temperature Pressure Energy flow Exergy flow


Flowb ratec (kg/s) ( C) (MPa) V.F.d rate5 (MW) ratee (MW)
S1 41.74 15.00 0.101 solid 1367.58 1426.73
S2 668.41 15.00 0.101 1.0 0.00 0.00
S3 710.15 1673.59 0.101 1.0 1368.00 982.85

S4 710.15 119.44 0.101 1.0 74.39 62.27


S5A 453.59 538.00 16.2 1.0 1585.28 718.74
S8 42.84 323.36 3.65 1.0 135.44 51.81
S10 367.85 35.63 0.0045 0.0 36.52 1.20
S11 367.85 35.73 1.00 0.0 37.09 1.70
S12 58.82 188.33 1.21 0.0 50.28 11.11

S13 18636.00 15.00 0.101 0.0 0.00 0.00


S14 18636.00 23.30 0.101 0.0 745.95 10.54
515 410.75 323.36 3.65 1.0 1298.59 496.81
S20 367.85 360.50 1.03 1.0 1211.05 411.16
S21 410.75 538.00 4.00 1.0 1494.16 616.42
S22 15.98 423.23 1.72 1.0 54.54 20.02

S25 26.92 360.50 1.03 1.0 88.64 30.09


S33 309.62 35.63 0.0045 0.93 774.70 54.07
S34 10.47 253.22 0.379 1.0 32.31 9.24
S35 23.88 209.93 0.241 1.0 71.73 18.82
S36 12.72 108.32 0.0689 1.0 35.77 7.12
S37 11.16 60.47 0.0345 1.0 30.40 5.03

S38 58.23 55.56 0.0133 0.0 11.37 0.73


S39 367.85 124.86 1.00 0.0 195.94 30.41
S40 453.59 165.86 1.00 0.0 334.86 66.52
S41 453.59 169.28 16.2 0.0 347.05 77.57
S42 453.59 228.24 16.2 0.0 486.75 131.93
Q5 5.34 0.00

Q6 5.29 0.00
P1 0.57 0.57
P8 523.68 523.68
P15 12.19 12.19
a
Based on data obtained for Nanticoke Generating Station by computer simulation (Rosen and Scott, 1998; Rosen, 2001) using given data (Ontario Hydro,
1973, 1983; Scarrow and Wright, 1975; Bailey, 1981; Merrick, 1984).
b
Flow numbers correspond to those in Figure 20.3, except for S3, which represents the hot product gases for adiabatic combustion. Letter prefixes indicate
material flows (S), heat flows (Q), and electricity flows (P).
c
Material flow compositions, by volume, include: 100% C for S1; 79% N2, 21% O2 for S2; 79% N2, 6% O2, 15% CO2 for S3 and S4; 100% H2O for other
material flows.
d
Vapor fraction (V.F.) indicates fraction of a vapor-liquid flow that is vapor (not applicable to S1 since it is solid). V.F. is listed as 0.0 for liquids and 1.0 for
superheated vapors.
e
Energy and exergy values are evaluated using a reference-environment model, similar to the model used by Gaggioli and Petit, 1977, having a temperature of
15 C, a pressure of 1 atm, and a composition of atmospheric air saturated with H2O at 15 C and 1 atm and the following condensed phases: water, limestone,
and gypsum.
Chapter | 20 Exergoeconomic Analysis of Thermal Systems 403

TABLE 20.4 Breakdown by Device of Capital Costs (in 106 $) for a Unit of the Coal-Fired Generating Stationa

Turbine generators 63.93

Main condensers and auxiliaries 8.69


Steam generators 153.95
Steam generators and reheaters, air preheaters 148.74
Air fan 5.21
Preheating devices 16.02
Low-pressure pumps 1.30

Intermediate-pressure pumps 2.42


High-pressure pumps and driving turbine 6.38
Preheater #1 0.56
Preheater #2 0.56
Preheater #3 0.47
Preheater #4 0.61
Preheater #5 0.52

Preheater #6 0.54
Preheater #7 2.66
Other plant devices 31.95
Other plant equipment 19.08
b
Unaccounted processing units 12.87
All main devices in overall plant 274.54
a
Costs have been modified to 2002 U.S. dollars (as explained in the text), and are based on literature for the Harry Allen Station (Bechtel Power Corporation,
1982; Tsatsaronis and Winhold, 1985), particularly Table 6 of Tsatsaronis and Winhold (1985) (which presents costs for the total three units in the station).
b
Unaccounted processing units is an approximated value, which accounts for the portions of the remaining costs in Table 6 of Tsatsaronis and Winhold (1985)
that should be applied to the other plant devices group.

a device is given by the slope of the line in Figure 20.4 for ratio is based on energy loss (i.e., for Ren) and small when
the device. based on exergy loss (i.e., for Rex). This observation is
For each of the eight device cases considered, Table supported by the range of maximum to minimum values,
20.6 presents statistical data for the two thermodynamic- which is much greater for Ren values than for Rex values.
loss-rate-to-capital-cost ratios, Ren and Rex. The statistical That is,
quantities considered in Table 20.6 are minimum, Ren max  Ren min >> Rex max  Rex min (20.18)
maximum, mean, standard deviation, and coefficient of
variation. As CV(R) is a measure of the relative variation in The observation is also supported by the coefficients of
a set of values about the mean and is independent of scale variation, which indicate that the relative variation is much
of measurement, it permits comparisons of the variations in greater in the set of Ren values than in the set of Rex values.
several sets of data. That is,
In the present undertaking, n 8, since each set of R CVRen >> CVRex (20.19)
values contains eight values, corresponding to the values
for the turbine generators (Cases I, II, and III), the steam For the turbine generators and preheating devices, the
generators, the preheating devices (Cases I and II), the main energy loss rate L_ en is sensitive to the definition of material
condensers and auxiliaries, and the overall station. waste outputs (recall that three cases of material waste
The statistical data in Table 20.6 indicate that the outputs are considered for the turbine generators, and two
relative spread in thermodynamic-loss-rate-to-capital-cost cases for the preheating devices). The exergy loss rate L_ ex is
ratios for different devices in the station is large when the relatively less sensitive. Since the capital cost K is constant
404 Exergy

FIGURE 20.4 Thermodynamic loss rate as a function of capital cost


for several devices in a 500 MW unit of the coal-fired Nanticoke
(a)
electrical generating station. (a) Energy loss rate and (b) exergy loss 1500
rate. Costs have been modified to 2002 U.S. dollars (as explained in the
text). (63.93, 1224.0)
1200

Energy rate, Len (MW)


900 (8.69, 746.0) (274.54, 820.0)
(63.93, 775.0)

600

300
(16.02, 0.0 and
16.02, 11.4)
(63.93, 0.0)(153.95, 74.0)
0
0 50 100 150 200 250 300
Capital cost, K (106, 2002 US$)
(b)
1500
all main devices
steam generator
1200 turbine gen. (case I)
turbine gen. (case II)
(274.54,
turbine gen. (case III)
Exergy loss rate Lex (MW)

916.0)
preheat sec. (case I)
900
preheat sec. (case II) (153.95,
condenser 720.0)
600

(63.93, 304.0)
300
(63.93, 162.0)
(8.69, 53.0) (63.93,108.0)
0
0 50 100 150 200 250 300
(16.02, 23.0 Capital cost, K (106, 2002 US$)
and 16.02,
24.02)

20
bas ed on energy los s *
bas ed on total exergy los s
Ratio, R (W/$)

10

0
Overall Steam Preheating Preheating Turbine Turbine Turbine Condensers
plant generators section section generators generators generators
(Case I) (Case II) (Case I) (Case II) (Case III)
FIGURE 20.5 Values of thermodynamic-loss-rate-to-capital-cost ratio, R, for several devices in a 500 MW unit of the coal-fired Nanticoke Generating
Station. Costs have been modified to 2002 U.S. dollars (as explained in the text). Note that * shows R 85.8 W/$ based on energy loss.
Chapter | 20 Exergoeconomic Analysis of Thermal Systems 405

TABLE 20.5 Capital Cost and Thermodynamic Loss Data for Several Devices in a Unit of the Coal-Fired Generating
Stationa

Deviceb K (106 $) L_ en (MW) Ren (W/$) L_ ex (MW) Rex (W/$)


Steam generators 153.95 74.0 0.481 720.0 4.68
Turbine generators
l Case I 63.93 0.0 0.0 108.0 1.69
l Case II 63.93 775.0 12.1 162.0 2.53
l Case III 63.93 1224.0 19.1 304.0 4.76

Main condensers 8.69 746.0 85.8 53.0 6.10


(and auxiliaries)

Preheating devices
l Case I 16.02 0.0 0.00 23.0 1.44
l Case II 16.02 11.4 0.71 24.2 1.51
Overall station 274.54 820.0 2.99 916.0 3.34
a
Costs have been modified to 2002 U.S. dollars (as explained in the text).
b
Device descriptions and capital costs correspond to those detailed in Table 20.4.

for each device for all cases considered, the corresponding that sense represent the appropriate optimum, as deter-
thermodynamic-loss-rate-to-capital-cost ratios (Ren and mined by market and other forces.
Rex) exhibit sensitivities similar to those exhibited by L_ en
and L_ ex.
The above results suggest that, for devices in modern 20.6 CASE STUDY: ELECTRICITY
coal-fired electrical generating stations, a systematic GENERATION FROM VARIOUS SOURCES
correlation exists for capital cost and exergy loss, but not The methodology from the previous section (Rosen, 1991,
for capital cost and energy loss. Rosen and Dincer, 2002) is applied to single units of oil-
The results further suggest for these devices that values fired (Lennox), coal-fired (Lakeview and Nanticoke), and
of Rex approximately conform to a particular value, denoted nuclear (Bruce B) electrical generating stations in Ontario.
here by Rex. The value of Rex does not necessarily identify Data has been obtained from Ontario Power Generation,
the ideal value of Rex. The meaning of Rex may be better formerly Ontario Hydro (1969, 1973, 1979, 1983, 1985,
understood by considering that coal-fired electrical gener- 1991, 1996). Table 20.7 presents selected primary charac-
ating stations are, and have been for some time, widely teristics of the four stations.
used. Consequently, the design of the overall plant and For all four stations, devices are separated according to
individual devices can be viewed as successful, and in the breakdown used in the previous section (Rosen, 1990,

TABLE 20.6 Statistical Data for Thermodynamic Loss-Rate-to-Capital-Cost Ratio Values for Several Devices in a Unit of
the Coal-Fired Generating Stationa

Parameter Based on energy loss Based on exergy loss


Minimum, Rmin (W/$) 0.0 1.44
Maximum, Rmax (W/$) 85.8 6.10

Mean, R (W/$)2 15.1 3.26


Standard deviation, SD(R) (W/$)b 27.4 1.64
Coefficient of variation, CV(R) (%)2 181.5 50.31
a
Costs have been modified to 2002 U.S. dollars (as explained in the text).
b
The mean R for the set of n values, R1, R2, . Rn, is a measure of the center of the set. The standard deviation, SD(R), of the set is a measure of the absolute
variation in the set of R values about the mean R. The coefficient of variation, CV(R), is the standard deviation as a percentage of the mean.
406 Exergy

TABLE 20.7 Selected Information for Four Electrical Generating Stations

Station Fuel Net electrical power output (MW) Energy efficiency (%) Exergy efficiency (%)
Lennox Oil 512 37.0 34.8
Lakeview Coal 307 35.5 33.2

Bruce B Uranium 842 31.0 31.0


Nanticoke Coal 500 37.4 35.8

Source: Rosen (1990, 1991).

1991). For the Bruce B station, however, the steam gener- (Table 20.10) are in 1976 Canadian dollars, and for the
ators include the nuclear reactor, the primary heat-trans- Nanticoke station (Table 20.11) are in 1982 U.S. dollars.
port-loop pump, and the moderator cooler, instead of the air The 1982 U.S.eCanada exchange rate is used to convert
preheater and fan. In addition, the de-aerator and the high- the costs in Table 20.11 to Canadian dollars. The CPI and
pressure (HP) and low-pressure (LP) preheaters are exchange-rate data indicate that $1.00 (Canadian) in 1969
considered for all four stations. In both preheater instances, has the same buying power as $5.02 (Canadian) in 2002,
two cases are considered: (I) no material wastes exit, and $1.00 (Canadian) in 1973 has the same buying power as
(II) the flow exiting the preheaters is treated as a waste. $4.14 (Canadian) in 2002, $1.00 (Canadian) in 1976 has the
Additional devices considered for some stations include the same buying power as $3.14 (Canadian) in 2002, and
condensate pumps (for Lennox, Nanticoke, and Bruce B) $1.00 (U.S.) in 1982 has the same buying power as
and the boiler feed pumps (for Lennox, Lakeview, and $2.27 (Canadian) in 2002.
Bruce B). The results of the previous work suggest a systematic
Two additional device breakdowns are considered for correlation may exist between capital cost and exergy loss
Lennox only: (1) the gland seal condenser (GSC) and (2) (both total and internal) for devices in modern electrical
the LP preheaters with the GSC. In both instances, two generating stations, but not between capital cost and energy
cases are considered: (I) no material wastes exit, and (II) loss or external exergy loss. This observation is supported
flows to the condenser are treated as wastes. Also, two by the maximum, minimum, and coefficient of variation
additional device breakdowns, each with two cases, are data in Table 20.12, which show the relative spread in
considered for Bruce B only: (1) the HP and LP preheaters values for Rex and Rex-i to be smaller than the spreads for
(case I, no material wastes exit and case II, flows from the Ren or Rex-e.
LP preheaters to the de-aerator and from the HP preheaters Values for Rex and Rex-i are seen to be similar for most
to the condenser are treated as wastes); and (2) the moisture cases, as are the statistical quantities calculated for sets of
separator and heat exchangers (case I, no material wastes Rex and Rex-i values (see Table 20.12).
exit and case II, flows from the moisture separator and heat The results of the previous section suggest that the
exchanger that do not enter the LP turbine are treated as values of Rex and Rex-i for a group of devices in a coal-fired
wastes). station may approximately conform to particular appro-
priate values, R*ex and R*ex-i. This statement appears to be
applicable to the technologies analyzed in the present
20.6.1 Results and Discussion
section. The similar behavior between Rex and Rex-i, as
Values for devices of K and several L_ and R parameters are discussed previously, likely implies that values for R*ex and
listed in Tables 20.8e20.11 for the four generating stations. R*ex-i behave similarly, and are similar in value. The values
Statistical data for R values are presented for the four of R*ex and R*ex-i do not necessarily identify ideal values
stations individually and combined in Table 20.12 (using of Rex and Rex-i. The meaning of R*ex and R*ex-i may be
Case I values where multiple cases exist). better understood by considering that coal-fired, oil-fired,
The costs shown in Tables 20.8e20.11 are in 2002 and nuclear electrical generating stations are, and have been
Canadian dollars. These costs are evaluated by modifying for some time, widely used. Consequently, the design of the
the original data using the CPI tabulated by Statistics overall plant and individual devices can be viewed as
Canada (accessible at www.statcan.gc.ca). The original successful, and in that sense represent an appropriate
costs for the Lennox station (Table 20.8) are in 1973 optimum. Thus, R*ex and R*ex-i likely reflect the appropriate
Canadian dollars, for the Lakeview station (Table 20.9) are trade-off between exergy losses and capital costs, which is
in 1969 Canadian dollars, for the Bruce B station practiced in successful plant designs.
Chapter | 20
Exergoeconomic Analysis of Thermal Systems
TABLE 20.8 Device Parameter Values for Lennox Oil-Fired Generating Station (Using 2002 Canadian $)

Device Case no. K (106$) L_ en (MW) Ren (W/$) L_ ex (MW) Rex (W/$) L_ ex-i (MW) Rex-i (W/$) L_ ex-e (MW) Rex-e (W/$)
Steam generators 60.80 207.56 3.41 819.24 13.47 769.74 12.66 49.5 0.81
Turbines I 67.22 0 0 67.70 1.01 67.70 1.01 0 0
II 6722 676.95 10.07 107.66 1.60 67.70 1.01 39.96 0.59
III 67.22 1087.95 16.18 3.56 67.70 1.01 171.65 2.55
Preheating section I 5.37 0 0 18.05 3.36 18.05 3.36 0 0
II 5.37 6.25 1.16 18.29 3.44 18.05 3.36 0.24 0.044
Condenser 3.13 657.37 210.25 39.53 12.64 23.57 7.54 15.96 5.11
High-pressure preheater I 1.77 0 0 5.06 2.85 5.06 2.85 0 0
II 1.77 39.64 22.34 13.89 7.83 5.06 2.85 8.83 4.98
Low-pressure preheater I 1.35 0 0 5.43 4.02 5.43 4.02 0 0
II 1.35 6.12 4.53 5.67 4.19 5.43 4.02 0.24 0.18
Low-pressure preheater I 1.56 0 0 5.93 3.79 5.93 3.79 0 0
& gland seal condenser II 1.56 6.25 4.00 6.17 3.95 5.93 3.79 0.24 0.15

Gland seal condenser I 0.20 0 0 0.5 2.52 0.5 2.52 0 0


II 0.20 0.13 0.66 0.5 2.52 0.5 2.52 0 0

De-aerator 0.51 0 0 2.97 5.86 2.97 5.86 0 0


Condensate pumps 0.59 0 0 0.01 0.017 0.01 0.017 0 0
Boiler feed pumps 0.93 0 0 4.08 4.39 4.08 4.39 0 0
Overall station 192.9 865.02 4.49 959.51 4.98 894.02 4.63 65.49 0.34

Note: Costs have been modified to 2002 Canadian dollars (as explained in the text).

407
408 Exergy

TABLE 20.9 Device Parameter Values for Lakeview Coal-Fired Generating Station (Using 2002 Canadian $)

Case L_ en Ren L_ ex Rex L_ ex-i Rex-i (W/ L_ ex-e Rex-e (W/


6
Device no. K (10 $) (MW) (W/$) (MW) (W/$) (MW) $) (MW) $)
Steam generators 29.30 192.60 6.57 555.19 18.95 510.12 17.41 45.07 1.54
Turbines I 26.19 0 0 36.44 1.39 36.44 1.39 0 0
II 26.19 371.43 15.38 50.46 1.93 36.44 1.39 14.02 0.53
III 26.19 591.58 22.58 117.60 4.49 36.44 1.39 81.16 3.08
Preheating section I 4.16 0 0 10.05 2.41 10.05 2.41 0 0
II 4.16 2.64 0.63 10.13 2.43 10.05 2.41 0.08 0.019
Condenser 1.35 364.88 269.4 13.94 10.29 8.25 6.09 5.69 4.17
High-pressure preheater I 1.05 0 0 3.25 3.09 3.25 3.09 0 0
II 1.05 21.73 20.62 7.68 7.29 3.25 3.09 4.43 4.18
Low-pressure preheater I 0.55 0 0 4.03 7.30 4.03 7.30 0 0
(without gland seal II 0.55 2.59 4.69 4.10 7.43 4.03 7.30 0.07 0.13
condenser)
De-aerator 0.28 0 0 0.56 2.03 0.56 3.03 0 0

Boiler feed pumps 2.31 0 0 2.14 0.93 2.14 3.03 0 0


Overall station 86.09 557.48 6.48 618.62 7.19 567.86 6.56 50.76 0.59

Note: Costs have been modified to 2002 Canadian dollars (as explained in the text).

TABLE 20.10 Device Parameter Values for Bruce B Nuclear Generating Station (Using 2002 Canadian $)

Case K L_ en Ren L_ ex Rex L_ ex-i Rex-i L_ ex-e Rex-e


Device no. (106$) (MW) (W/$) (MW) (W/$) (MW) (W/$) (MW) (W/$)
Steam generators 6.24 147 2.36 1575.48 25.25 1573.45 25.22 2.03 0.03

Turbines I 261.5 0 0 41.17 0.16 41.17 0.16 0 0


II 261.5 1650.05 6.31 138.42 0.53 41.17 0.16 97.25 0.37
III 261.5 2460.16 9.44 338.31 1.29 41.17 0.16 297.14 1.14
Preheating section I 13.63 0 0 25.15 1.84 25.15 1.84 0 0
II 13.63 17.29 1.28 25.71 1.88 25.15 1.84 0.56 0.04
Condenser 5.76 1621.87 281.6 97.16 16.89 74.76 12.98 22.40 3.89
High-pressure preheater I 5.02 0 0 2.86 0.57 2.86 0.57 0 0
II 5.02 129.47 25.77 27.43 5.44 2.86 0.57 24.48 4.87
Low-pressure preheater I 3.36 0 0 17.76 5.28 17.76 5.28 0 0
II 3.36 17.29 5.15 18.32 5.45 17.76 5.28 0.56 0.17
High- and low-pressure preheater I 8.38 0 0 20.62 2.46 20.62 2.46 0 0
II 8.38 146.76 17.51 45.66 5.45 20.62 2.46 25.04 2.99
De-aerator 1.82 0 0 1.36 0.75 1.36 0.75 0 0
Condensate pumps 1.54 0 0 0.40 0.26 0.40 0.26 0 0
Boiler feed pumps 1.89 0 0 2.24 1.19 2.24 1.19 0 0
Moisture separator and heat I 5.09 0 0 11.25 2.21 11.25 2.21 0 0
exchanger II 5.09 191.35 37.61 61.07 12.00 11.25 2.21 49.82 9.79
Overall station 391.3 1768.87 4.52 1875.68 4.79 1851.25 4.73 24.43 0.06

Note: Costs have been modified to 2002 Canadian dollars (as explained in the text).
Chapter | 20 Exergoeconomic Analysis of Thermal Systems 409

TABLE 20.11 Device Parameter Values for Nanticoke Coal-fired Generating Station (Using 2002 U.S. $)

Ren L_ ex Rex L_ ex-i Rex-i L_ ex-e Rex-e


Device Case no. 6
K (10 $) L_ en (MW) (W/$) (MW) (W/$) (MW) (W/$) (MW) (W/$)
Steam generators 188.05 74 0.39 720 3.83 658 3.50 62 0.33
Turbines I 78.09 0 0 108 1.38 108 1.38 0 0
II 78.09 775 9.95 162 2.07 108 1.38 54 0.69
III 78.09 1224 15.67 304 3.90 108 1.38 196 2.51
Preheating section I 19.56 0 0 23.0 1.18 23.0 1.18 0 0
II 19.56 11.4 0.58 24.02 1.24 23.0 1.18 1.2 0.06
Condenser 10.61 746 70.42 53 5.02 43 4.05 10 0.94
High-pressure preheater I 3.91 0 0 6.36 1.63 6.36 1.63 0 0
II 3.91 50.3 12.89 17.5 1.63 6.36 1.63 11.1 2.84
Low-pressure preheater I 2.68 0 0 10.8 4.03 10.8 4.03 0 0
II 2.68 11.4 4.25 11.5 4.03 10.8 4.03 0.73 0.27
De-aerator 0.64 0 0 0.56 0.88 0.56 0.88 0 0
Condensate pumps 1.59 0 0 0.07 0.04 0.07 0.04 0 0
Overall station 335.35 820 2.45 916 2.73 843 2.51 73 0.22

Note: Costs have been modified to 2002 Canadian dollars (as explained in the text).

20.6.2 Relations for Devices in a Single based thermodynamic methodologies) in balance with the
Generating Station overall system as opposed to in isolation, is not new. Others
have emphasized the importance of thermoeconomically
For a given station, the mean thermodynamic-loss-rate- optimizing a thermal system based on the interaction among
to-capital-cost ratios based on total (or internal) exergy devices and the entire system (Hua et al., 1989).
loss (see Table 20.12) are similar to the overall-station The previous discussions suggest that the relations Rm,ex
ratio values based on total (or internal) exergy loss (see z (Rex)s and Rm,ex-i z (Rex-i)s may be important charac-
Tables 20.8e20.11). That is, Rm,ex z (Rex)s and Rm,ex-i z teristics of successful electrical generating stations, and
(Rex-i)s, where the mean is for all station devices may be generalizable to other successful technologies.
considered, and the subscript s refers to the overall Values of the hypothetical terms R*ex and R*ex-i for
station. In addition, Tables 20.8e20.12 show that a cor- devices in a station are likely similar to values for Rm,ex,
responding similarity based on energy loss is not evident, Rm,ex-i, (Rex)s, and (Rex-i)s. Note that appropriate values
and based on external exergy loss is likely not evident for these terms may vary spatially and temporally.
(although the small magnitudes of the values involved Here, variations are observed for the (Rex)s and (Rex-i)s
make it difficult to confirm the lack of similarity for values in Tables 20.8e20.11 and the Rm,ex and Rm,ex-i
external exergy loss). values in Table 20.12, which consider generating
The observation that the mean R value for the devices in a stations using different fuels and built in different
given station is approximately equal to the overall-station locations and times.
R value (based on total and internal exergy loss) may indi- In Table 20.12, where the data for stations are grouped
cate that devices in a successful station are arranged to together, the following relations are observed: Rm,ex z
achieve an optimal overall station configuration. (Rm,ex)s and Rm,ex-i z (Rm,ex-i)s. Here, (Rm,ex)s and (Rm,ex-i)s
However, such an indication is evident from the relations for are the means for the four overall-station cases, and are
the devices between capital cost and exergy loss (total and listed at the bottom of Table 20.12. These relations parallel
internal), but not between energy loss or external exergy loss the similar relations identified earlier for individual
and capital cost. In other words, the relations between capital stations, and suggest that generating stations located
cost and total and internal exergy loss suggest that the within a larger system, here the electrical utility sector, may
collective characteristics of the station match and benefit the have characteristics similar to the typical station in that
overall station. sector. Furthermore, these characteristics are evident from
The idea, suggested by the earlier observations, of opti- relations between capital costs and total or internal exergy
mizing devices (using combined economic and second law- losses, but not energy losses.
410 Exergy

TABLE 20.12 Statistical Data for R Values for Several Electrical Generating Stations (Using 2002 Canadian $)

Based on Based on Based on Based on external


energy loss total exergy loss internal exergy loss exergy loss
Lennox (oil)
Minimum, Rmin (W/$) 0 0.017 0.017 0
Maximum, Rmax (W/$) 210.25 13.47 12.66 5.11
Mean, Rm (W/$) 18.54 5.01 4.48 0.53
Stand. dev., SD(R) (W/$) 54.48 4.22 3.35 1.49
Coeff. of var., CV(R) (%) 333.00 84 75 281
Lakeview (coal)
Minimum, Rmin (W/$) 0 0.93 0.93 0
Maximum, Rmax (W/$) 269.4 18.95 17.44 4.17
Mean, Rm (W/$) 31.38 5.95 5.25 0.70
Stand. dev., SD(R) (W/$) 89.29 5.84 5.14 1.41
Coeff. of var., CV(R) (%) 285 98 98 2001

Bruce B (nuclear)
Minimum, Rmin (W/$) 0 0.16 0.16 0
Maximum, Rmax (W/$) 281.6 25.25 25.22 3.89
Mean, Rm (W/$) 24.52 5.24 4.90 0.38
Stand. dev., SD(R) (W/$) 82.74 7.98 7.50 1.14
Coeff. of var., CV(R) (%) 337.00 152.00 153.00 338.00
Nanticoke (coal)
Minimum, Rmin (W/$) 0 0.04 0.04 0
Maximum, Rmax (W/$) 70.42 5.02 4.05 0.94
Mean, Rm (W/$) 8.14 2.30 2.13 0.17
Stand. dev., SD(R) (W/$) 23.37 1.68 1.46 0.32
Coeff. of var., CV(R) (%) 287.00 73.00 68.00 191
All stations combined
Minimum, Rmin (W/$) 0 0.017 0.017 0
Maximum, Rmax (W/$) 269.4 18.95 17.41 5.11
Mean, Rm (W/$) 21.00 4.70 4.30 0.45
Stand. dev., SD(R) (W/$) 63.00 5.10 4.50 1.10
Coeff. of var., CV(R) (%) 300.00 110.00 100.00 240
Mean of overall-station R values (W/$) 4.49 4.92 4.61 0.30

It is also noted that the values in Table 20.6 do not vary rates and capital costs for electrical generating stations may
significantly when the R values are re analyzed for two be general. In particular, values of R*ex may exist for other
alternate device-groupings: (1) all devices except the technologies.
overall station and (2) the devices that represent the most The value of R*ex may vary for different situations
broken down components of the station. (e.g., technology, time, location, resource costs, knowl-
edge). For example, the values of R*ex may be different for
different technologies. Also, during periods when energy-
20.6.3 Generalization of Results resource costs increase (as was the case in many locations
Before general conclusions can be drawn from the present in the 1970s and in the 2000s), the value of R*ex likely
analysis, data for additional and different technologies must decreases (i.e., greater capital is invested to reduce losses).
be collected and analyzed. Nevertheless, possible general- For any technology, it appears that the design of a device
ities are now discussed. may be made more successful if it is modified so that its
Based on the results of the present analysis and values value of Rex approaches R*ex. This idea is illustrated in
of capital costs and thermodynamic losses for other devices Figure 20.6, which shows a line intersecting the origin
(e.g., El-Sayed et al., 1983; Tsatsaronis and Park, 2002), it representing R*ex, and a second curve representing the
is suggested that the observed relations between exergy loss possible combinations of exergy loss and capital cost for
Chapter | 20 Exergoeconomic Analysis of Thermal Systems 411

Possible combinations for many devices that marginal costs based on exergy have
* x
e
=R
of total exergy similar values, while marginal costs based on energy vary
Exergy loss rate, Lex
loss and cost Re x
widely.

Rex > R *ex The exergoeconomic concepts discussed in this section


may prove particularly useful for the introduction of new
technologies.
Rex < R *ex
20.7 EXERGOECONOMICS EXTENDED:
EXERGY, COST, ENERGY, AND MASS
Capital cost, K
ANALYSIS
FIGURE 20.6 Illustration of the tendency of Rex for a device to approach
Rex , the value of Rex for which the appropriate trade-off between losses Traditionally, the merit of a system or process has been
and capital costs is attained. based on conventional parameters including technical
performance and efficiency, economic viability, and
health and safety implications. In recent years, new
a device. The shape and position of the latter curve illustrates concerns like environmental damage and scarcity of
the trade-off between cost and efficiency by showing that resources have increased the considerations involved. The
losses generally can be reduced through increased capital evaluation of the merit of a system or process requires
investment. Specifically, this curve indicates that the total methodologies that take into account all of these factors,
exergy input is wasted if no investment is made, that is, as well as others. A systems viewpoint is required for
Total exergy loss rate/Total exergy input rate as completeness.
Capital cost/0 Here, a methodology for evaluating systems and
processes that extends exergoeconomics is described that
and that performance approaches the ideal if a very large
incorporates four key parameters: exergy, cost, energy, and
investment is made, that is,
mass (EXCEM). EXCEM analysis and can be useful for the
Total exergy loss rate/0 as Capital cost/N evaluation of systems. This method is intended to form the
basis of a unified methodology for exergy, energy,
A balance is obtained between exergy loss and capital cost
economic, and environmental decisions. Previous work has
in real systems. The expected combination of exergy loss
been reported on EXCEM analysis (e.g., Rosen, 1986,
and capital cost is the one for which Rex R*ex, which is
1990).
represented by the intersection of the two curves in
The basic rationale underlying an EXCEM analysis is
Figure 20.6. If the cost is less, Rex > R*ex, cost will be
that an understanding of the performance of a system
increased to reduce loss, and vice versa.
requires an examination of the flows of each of the quan-
If successful technologies conform to an appropriate
tities represented by EXCEM into, out of, and at all points
R*ex, then it follows that technologies who fail in the
within a system.
marketplace may do so because they deviate too far from
the appropriate R*ex. Thus, research and development
should perhaps strive to identify devices for which the
difference between the values of Rex and R*ex is large and
20.7.1 The EXCEM Analysis Concept
develop ways to narrow the difference. The EXCEM analysis concept is illustrated in Figure 20.7.
The work discussed in this case study can likely be Of the quantities represented by EXCEM, only mass and
extended to marginal costs. Here, the marginal cost would energy are subject to conservation laws. Cost increases or
be the cost increase resulting from saving one unit of remains constant, while exergy decreases or remains
energy or exergy (i.e., from reducing the energy or exergy constant. Balances can be written for each of the EXCEM
loss by one unit). The results would be expected to indicate quantities.

FIGURE 20.7 The EXCEM analysis methodology.


Exergy Exergy
Cost System Cost
Energy Energy
Mass Mass
412 Exergy

20.7.2 Development of a Code for EXCEM 20.7.3 Illustrative Examples of EXCEM


Analysis Analysis
To make the EXCEM analysis methodology more useful The illustrations considered herein are intended to clarify
and convenient to use, it can be applied in a computer code. the general concepts associated with EXCEM analysis,
For example, one EXCEM analysis code, developed by particularly cost allocation. Mass, energy, and exergy
enhancing a state-of-the-art process simulator (Aspen Plus) balances are not extensively discussed. The three devices
for EXCEM analysis, has been described previously (e.g., in Figure 20.8 are considered. while operating at steady
Rosen and Scott, 1985). state.
That EXCEM code provides valid and accurate results,
is convenient to use, and is widely applicable. The meth-
odology used to enhance Aspen Plus for EXCEM analysis 20.7.3.1 Pump
is general and can be used, with modifications where The application of EXCEM analysis to a pump (Fig-
necessary, to enhance other process-simulation and related ure 20.8a) is relatively straightforward. A fluid and elec-
codes. Original analyses of several mechanical and chem- tricity are input and the fluid at higher pressure and heat
ical engineering processes with the code demonstrate the (unless the pump is adiabatic) are output. If the pump is
following: adiabatic, all costs associated with inputs and generation is
l EXCEM analysis methodology often provides valuable allocated to the one output. If the pump is not adiabatic, all
insights into performance and efficiency, economics, input and generation costs are still logically allocated to the
and the potentials for environmental damage for output fluid stream because heat loss is a waste.
processes.
l Some findings from EXCEM analyses are not obtain-
able with conventional analyses (e.g., energy analyses
20.7.3.2 Steam Turbine
and energy economics), while most findings of The application of EXCEM analysis to a steam turbine
conventional analyses are obtained more directly and (Figure 20.8b) requires more thought because a subjective
conveniently with EXCEM analyses. decision must be made regarding the allocation of costs.
l Exergy-related aspects of EXCEM are often the most The shaft work, low-enthalpy steam, and heat outputs may
revealing. each be allocated part of the input and generation costs. The

(a)
Exergy
Exergy
Cost
Cost
Energy LP HP
fluid Energy
fluid
Mass
Mass

(b)
Exergy HP steam
Exergy
Cost
Cost
Energy Shaft
work
Energy
Mass
LP steam Mass

(c)
Stack gas
Exergy
Exergy
Cost Fuel Cost
Energy Electricity
Air Energy
Mass Mass
Cooling water
Chapter | 20 Exergoeconomic Analysis of Thermal Systems 413

allocations depend on the uses for the outputs. The low- exergy losses are considered. Costs associated with inputs
enthalpy steam, for example, may or may not be a waste. do not need to be specified.
An illustrative example is used in the discussions.
These data are drawn from a simplified steady-state
20.7.3.3 Coal-Fired Electrical Generating Station
analysis of a cogeneration plant for electricity and heat
The application of EXCEM analysis to a coal-fired elec- (Reistad and Gaggioli, 1980). The plant is shown in
trical generating station (Figure 20.8c) requires more effort Figure 20.10, with exergy consumption and cost creation
than the previous examples because intermediate streams, rates and exergy, energy, and cost flow rates. Inputs to the
as well as inputs and outputs, must be examined. The boiler of air and feedwater, for which the associated flow
analysis of such a system can be viewed as a set of indi- rates of energy, exergy, and cost are approximately zero,
vidual EXCEM analyses of the devices comprising the are omitted from the diagram. The operating condition
overall system. As with the steam-turbine example, cost considered yields 17.9 kg/s (150,000 lb/hour) of steam [at
allocations require subjective decisions. 44.2 atm (650 psia) and 399 C (750 F) exiting the boiler,
Figure 20.9 illustrates a summary of the results of an and 0.065 atm (0.95 psia) and 37.8 C (100 F) exiting the
EXCEM analysis of a typical coal-fired electrical gener- turbine generator]. Energy and exergy values are evalu-
ating station (the coal-fired Nanticoke Generating Station ated relative to a reference environment having a temper-
described in Section 20.5). In Figure 20.9, the input and ature of 10 C, pressure of 1 atm, and composition as
generation costs are allocated to the product electricity. The described in the reference-environment model of Gaggioli
exhaust cooling water is a waste. Alternatively, if the and Petit (1977).
exhaust cooling water is a byproduct, part of the total costs To obtain the cost generation rate in this example, the
would be allocated to it. capital cost is multiplied by the amortization factor and
divided by the load factor. The amortization factor spreads
the total costs associated with a device over the life of the
20.7.3.4 Exergy Loss and Cost Generation
device, taking into account the time value of money.
The relation between exergy and cost is demonstrated using Amortization and load factors of 0.08 and 0.7, respectively,
plots of exergy loss as a function of cost generation. Either are used.
internal exergy losses (i.e., consumptions) or total exergy Exergy loss rates are plotted as a function of cost creation
losses (i.e., consumptions plus waste emissions) can be rates for the boiler and turbine generator in Figure 20.11a.
considered. The intensive properties of the reference For each device, total and internal exergy loss rates are
environment need to be completely specified when total considered. Figure 20.11b plots, at different points in the
exergy losses are considered. Only the temperature of the plant, cumulative exergy loss rate as a function of cumulative
reference environment needs to be specified when internal cost creation rate. The slopes and magnitudes of the

Exergy Stack Stack gas


gas Exergy

Electricity

Coal Coal

Electricity CW
CW

Cost Ash
Air Mass Stack gas
Coal

Electricity
Coal
CW CW

FIGURE 20.9 Summary of the results of an EXCEM analysis of a coal-fired electrical generating station. Overall balances of flow rates of exergy, cost,
energy, and mass are shown. The rectangle in the center of each diagram represents the station. Widths of arrows are proportional to the relative
magnitudes of the represented quantities. Rates of exergy consumption and cost creation are denoted by the shaded regions in the appropriate diagrams.
CW, cooling water.
414 Exergy

FIGURE 20.10 A cogeneration plant for the production Stack Low Pressure
of electrical energy and low-pressure steam. Flow rates of gas steam
energy (values in parentheses), exergy (values in square (10.7) (57.3)
brackets), and cost (values in angle brackets) are indicated [4.0] [5.0]
for streams. Rates of exergy consumption (negative values <0> <0>
in square brackets) and cost creation (positive values in
angle brackets) are indicated for devices. Energy and BOILER TURBINE
exergy values are in MW, and cost values are in M$/year. [48.5] GENERATOR
Costs are in 2001 U.S. dollars. <+2.45> High pressure [10.2] Power
Fuel
(82.4) steam <+0.17> (14.4)
[82.1] (71.7) [14.4]
<8.47> [29.6] <11.09>
<10.92>

individual lines indicate characteristics of the corresponding The type of plot in Figure. 20.11a showing total exergy
devices. Plots of the type in Figure 20-11a and b demonstrate loss rate versus cost creation rate illustrates the trade-off
that exergy and cost are the only EXCEM quantities subject between cost and efficiency. The total exergy input is
to nonconservation laws. Since, for any device, the associ- wasted if no investment (cost generation) is made. Perfor-
ated values of cost creation and exergy loss are positive, the mance approaches the ideal if a very large investment is
lines in these plots always rise to the right. made.

(a) (b)
75 75
Cumulative exergy
Exergy loss rate (MW)

loss rate (MW)

T.G.
50 50

25 25
T.G.
Boiler
Boiler

0 0
0 1 2 3 0 1 2 3
Cumulative cost
Cost creation
Creation rate (M$/yr)
rate (M$/yr)
(c) (d)
100
75
Exergy flow rate (MW)
Cumulative energy

T.G. 75
loss rate (MW)

T.G.
50
50 Boiler

25
25
Boiler

0 0
0 1 2 3 8 10 12
Cumulative cost Cost flow
creation rate (M$/yr) rate (M$/yr)
FIGURE 20.11 Comparison for a cogeneration plant of rates of cost flow and creation with rates of exergy loss and consumption, as well as rates of
energy loss. Solid lines denote total losses, and broken lines internal losses. TG, turbine generator. Costs are in 2001 U.S. dollars.
Chapter | 20 Exergoeconomic Analysis of Thermal Systems 415

A balance is obtained between exergy loss and cost analysis, a cost balance is usually formulated for the overall
creation in real systems. A plot of cumulative energy loss system operating at steady state:
rate versus cumulative cost creation rate is presented in
Figure 20.11c and compared with the plot in Figure 20.11b. C_ P;T C_ F;T Z_ (20.20)
The curve in Figure 20.11c analogous to the broken curve
in Figure 20.11b is a straight line along the x-axis (because where C_ denotes the cost rate, Z_ the levelized capital
energy is conserved), and is not particularly informative. investment and operating and maintenance (OM) costs, and
The solid curve in Figure 20.11c exhibits some similarity to the subscripts P,T, and F,T denote total products and total
the solid curve in Figure 20.11b. However, the solid curve fuel (and other) inputs.
in Figure 20.11c is not as illuminating and can be For a system operating at steady state, there may be
misleading because it weighs all energy losses equally. a number of entering and exiting material streams as well as
Different forms of energy are not necessarily equal in that heat and work interactions with the surroundings. Since
some forms of energy cannot be completely converted into exergy measures the true thermodynamic value of such
other forms, even in an ideal process. Different forms of effects and cost should only be assigned to commodities of
exergy are relatively more equal since one form of exergy value, it is meaningful to use exergy as a basis for assigning
can be converted into any other form of exergy in an ideal costs in energy systems. Such exergy costing provides
process. a rational basis for assigning costs to the interactions that
The idea that costing should be based on exergy rather a thermal system experiences with its surroundings and to
than energy, because exergy often is a consistent measure the sources of inefficiencies within it.
of value (i.e., a large quantity of exergy is often associated In exergy costing, a cost is associated with each exergy
with a valuable commodity) while energy is only some- stream. Thus, for entering and exiting streams of matter
times a consistent measure of value, is supported by the with associated rates of exergy transfer Ex _ in and Ex_ out ,
observations made when comparing Figure 20.11b and c. _
power W and the exergy transfer rate associated with heat
More general versions of Figure 20.11a and b, in which transfer Ex_ q, respectively, we can write the following:
flow rates of exergy and cost at different points in the plant
are plotted, are shown in Figure 20.11d. The intensive
properties of the reference environment must be completely C_ in cin Ex
_ in (20.21)
specified and costs associated with all inputs must be C_ out cout Ex
_ out (20.22)
known to construct Figure 20.11d. A monotonically
increasing composite line is again traced. However, the line C_ w cw W_ (20.23)
does not necessarily begin at the origin of the plot. The
C_ q cq Ex
_ q (20.24)
properties of the reference environment and costs associ-
ated with inputs determine the origin of the composite line. where c, denotes unit cost and the subscript w represents
work. A cost balance can then be written as follows:
X X
20.8 SPECIFIC EXERGY COST ANALYSIS C_ out;k C_ w;k C_ in;k C_ q;k Z_ (20.25)
In this chapter, we describe the specific exergy cost
Z_ Z_ k Z_ k
T CI OM
(SPECO) methodology as an approach to exergy-based (20.26)
economics, and apply it to an illustrative example. The present worth rate of a system (P_ W)
_ is given as
follows:
20.8.1 SPECO Analysis Methodology P_ W_ system C_ system  S_system PWFi; n (20.27)
SPECO analysis allows systems to be examined from an
where S_ is the salvage value rate and PWF the present value
exergy-based economic viewpoint. The method has been
factor, which can be expressed as follows:
applied to assess and improve various devices, such as
power plants. The SPECO method has been described by PWF 1=1 in (20.28)
various authors (Bejan et al., 1996; Tsatsaronis and Moran, _ can be written as follows:
1997). The annual capital cost (CA)
Cost accounting uses cost balances, and generally is con- C_ A_ system P_ W_ system CRF (20.29)
cerned with determining the actual cost of products or services,
providing a rational basis for pricing goods or services, where
providing a means for allocating and controlling expenditures, CRF i1 in =1 in  1 (20.30)
and providing information to assist in making and evaluating
design and operating decisions. In a conventional economic 1 i 1 in =1 r (20.31)
416 Exergy

Here, in, r, i, and n, denote nominal interest rate, infla- a different time, a normalization is performed with the aid of
tion rate, real interest rate, and system lifetime (in years), an appropriate cost index (CI):
respectively. Also, we can write: Cost at the reference year orginal cost
 
f C A_ system cost index for the reference year
Z_
T
(20.32)
3600s h1 sh year 1 cost index for the year when the orginal cost was obtained
(20.41)
where s is the annual number of operation hours of system,
and f is the factor for OM costs. When f 1,
CA_ system 20.8.2 Illustrative Example: SPECO Analysis
Z_ system
CI
(20.33) of Hydrogen Production via Biomass
s
The hourly levelized capital investment cost of the kth Gasification
component (Z_ k ) can be written as follows:
CI
Biomass is playing an increasingly important role in
hydrogen production in recent years. Two main approaches
PECk
Z_ k Z_ system P
CI CI
(20.34) exist to derive hydrogen from biomass: (1) thermochemical
PECk and (2) biochemical. Gasification is a thermochemical
system
method that is commonly employed. Gasification systems
The hourly OM cost of the kth component is obtained have been investigated thermodynamically, but economic
from the annual OM costs (Z_ k ):
OM
assessments are also necessary for determining the advan-
tages of a hydrogen production method. An exergy-based
PECk
Z_ k Z_ system P economic approach is useful, as it provides information
OM OM
(20.35)
PECk important to the design and operation of a cost-effective
system
system, and permits exergy-aided cost minimization.
To obtain the present cost of annual fuel needs, D, the In this section, we examine from an exergy-based
total fuel cost for n years (Pe) can be calculated as economics perspective two gasifiers for hydrogen produc-
follows: tion: (1) a downdraft gasifier and (2) a circulating fluidized
bed gasifier, based on a previous exergy and SPECO
Pe Df1 e=1 in  1g=e  i (20.36) analysis (Kalinci et al., 2012). The former is often advan-
tageous at small capacities and the latter at larger capac-
where ities. This illustrative example analysis is based on systems
e rfuel  r (20.37) and data reported in the literature, but the systems are
modified for cogeneration of hydrogen and power. SPECO
F_ A_ Pe CRF (20.38) analysis is used, and exergy-related parameters and cost
C_ fuel F_ A=s
_ (20.39) flows for streams and components are determined. In this
analysis, we examine components and streams, and assess
Here, F_ A_ is the annual fuel cost. the performance of the systems and their costs.
If data for equipment is available for different capacities
and different dates, purchased equipment costs can be 20.8.2.1 System Descriptions
modified as follows:
Descriptions follow of the two gasifier systems for
C C0 X=X0 a (20.40) hydrogen production from biomass considered in this
illustrative example:
where C and X denote purchased equipment cost and
equipment size, respectively, and 0 denotes reference l Downdraft gasifier (DG): A diagram of this system,
equipment. Also, a is a scaling exponent, which is usually which is modified from that of Lv et al. (2008), is
less than unity, expressing the fact that the percentage shown in Figure 20.12. The biomass input, pine wood,
increase (or decrease) in equipment cost is smaller than the is pretreated by cutting it to the proper size and then
percentage increase (or decrease) in equipment size. In the input to the gasifier and gasified with oxygen-rich air
absence of other cost information, an exponent value of and steam. The steam is produced utilizing heat from
0.6 may be used, following the six-tenths rule (Bejan et al., the gasifier wall and is at atmospheric pressure and
1996). 120 C. Oxygen-rich air is produced in an air separation
All cost data used in an economic analysis must be unit (ASU). The significant energy in the exhaust gas
brought to the same reference year: the year used as a basis for from the gasifier is used to produce steam in a heat
the cost calculations. For the cost data based on conditions at exchanger before the gas enters a gas cleaning unit.
Chapter | 20 Exergoeconomic Analysis of Thermal Systems 417

21 19
6 7 9 11 13 15 Hydrogen
HX2
1 Biomass 4
2 Oxygen HX1 We HX3 HX4 HX5
3 Steam 5 8 10 12 14 16
Syngas compressor Off-gas
Downdraft Gas cleaning HTS MTS LTS PSA
gasifier
22 18 17
23 20 Water

Wge
Qge

Steam turbine 24 Gas engine

Gas line
Steam line
FIGURE 20.12 Process for hydrogen production with a downdraft gasifier. (Modified from Lv et al., 2008).

The cooled gas is then compressed to a pressure that Zn type catalyst in the medium-temperature shift
varies depending on the plant to which it is sent, for (MTS) and low-temperature shift (LTS) reactions. The
example, 20 bar is sufficient for the gas turbine inlet in hydrogen-rich gas is purified in a pressure swing
a power plant while 35 bar is required for a hydrogen adsorption (PSA) unit. The produced hydrogen is at
plant. In the study we choose 35 bar in a compressor 25 C and 32 bar, and the off-gas, at 25 C and 1 bar, is
outlet. The CO shift reaction operates at a lower sent to a gas engine for power generation.
temperature and modifies the H2/CO ratio of the l Circulating fluidized bed gasifier (CFBG): A flow
syngas to improve the hydrogen yield of the plant. The diagram of this system, which is based on that of Hul-
CO shift reactions using a variety of catalysts, for teberg and Karlsson (2009) and includes a steam/
example, Z409R in the high-temperature shift (HTS) oxygen blown gasifier, is shown in Figure 20.13. A
reaction with an exit temperature of 600 C, and a Cu/ pressurized (30 bar) CFBG is used due to the process

28 27 25
4 6 8 10 12 14 16 17 Hydrogen

1. Oxygen
2. Biomass HX1 HX4 HX5
3. Steam 7 HX2 9 11 13 15 18

Gasifier Tar craker De-sulpherization HTS MTS LTS PSA

5. Oxygen 24 23
26 Water

29 PSA off-gas

Dryer
22 21 HX6 20

19. Air
31 30

32
Off-gas combustion
Wet biomass Gas line
Steam line
CT HPT
33

FIGURE 20.13 Process for hydrogen production with a circulating fluidized bed gasifier. (Modified from Hulteberg and Karlsson, 2009).
418 Exergy

TABLE 20.13 Exergy and Cost Flow Rates of Streams in the Downdraft Gasifier System

State Stream m_ T P _
Ex C_ c
(kg/s) (K) (kPa) (MW) ($/h) ($/GJ)
1 Biomass 0.074 298.15 101.325 1.521 18.45 3.37
2 O2 0.025 298.15 101.325 0.002 10.14 1198.58
3 Steam 0.013 393.15 101.325 0.007 0.42 17.95

4 Syngas 0.112 1073.15 101.325 1.080 29.61 7.62


5 Syngas 0.112 526.15 101.325 1.024 28.07 7.62
6 Syngas 0.094 333.15 101.325 0.854 28.27 9.20
7 Syngas 0.094 452.15 3500 0.892 44.91 13.99
8 Syngas 0.094 633.15 3500 0.904 45.52 13.99
9 Syngas 0.094 873.15 3400 1.059 45.72 11.99

10 Syngas 0.094 529.15 3400 1.021 44.08 11.99


11 Syngas 0.094 598.15 3300 1.017 44.28 12.09
12 Syngas 0.094 457.05 3300 1.005 43.76 12.09
13 Syngas 0.094 463.15 3200 1.005 43.96 12.15
14 Syngas 0.094 298.15 3200 0.999 43.69 12.15
15 H2 0.004 298.15 3200 0.507 25.64 14.05

16 Off-gas 0.090 298.15 101.325 0.450 22.83 14.09


17 Water 0.066 298.15 101.325 0.0 2.13 *
18 Water 0.066 300.15 3500 0.0002 2.36 2850.24
19 Water 0.066 428.17 3500 0.006 2.88 125.11
20 Water 0.066 517.7 3500 0.017 3.59 58.74
21 Water 0.066 517.7 3500 0.045 5.45 33.82

22 Water 0.066 901 3500 0.099 11.85 33.25


23 Water 0.066 706.75 3500 0.081 11.38 39.01
24 Water 0.066 318.94 10 0.021 2.70 35.72
W_ ASU 0.0315 6.96 61.34
W_ COMP : 0.060 13.25 61.34
W_ ST 0.058 8.89 42.56

W_ GE 0.177 18.51 29.05


Q_ GE 0.125 13.13 29.18

size. The fuel, wood biomass, is milled to small parti- use the Cu/Zn type catalyst. The gas is then quenched to
cles (5 mm) and then dried in a rotary dryer at 120 C near ambient temperature and water is condensed and
before gasification. Oxygen is produced in an ASU. The removed. The gaseous components enter a PSA, which
produced syngas at 30 bar and 850 C passes through separates the gaseous species into hydrogen (with
a tar cracker where thermal tar decomposition and 99.99% purity) and other constituents. Waste heat is
catalytic tar decomposition occur, followed by sulfur used to generate steam at 50 bar and 500 C using heat
removal and wateregas shift. While the HTS reactor exchangers. The steam is expanded to 30 bar through
uses the FeCr type catalyst, the MTS and LTS reactors a primary turbine for power generation, and then split so
Chapter | 20 Exergoeconomic Analysis of Thermal Systems 419

TABLE 20.14 Exergy and Cost Flow Rates of Streams in the Circulating Fluidized Bed Gasifier System
:
State Stream m T P E_ x_ C_ c
(kg/s) (K) (kPa) (MW) ($/h) ($/GJ)
1 Oxygen 2.504 298.15 30 0.966 1079.02 310.28
2 Biomass 8.500 393.15 30 174.872 2118.87 3.37
3 Steam 2.908 714.20 30 3.563 394.04 30.72

4 Syngas 13.911 1123.20 30 133.046 4675.43 9.76


5 Oxygen 2.448 363.00 30 0.958 1070.40 310.37
6 Syngas 16.359 1573.20 30 130.064 5879.09 12.56
7 Syngas 16.359 623.15 30 109.527 4950.79 12.56
8 Syngas 16.294 623.15 30 107.94 5160.98 13.28
9 Syngas 16.294 619.85 30 107.88 5158.11 13.28

10 Syngas 16.294 773.15 30 106.603 5191.42 13.53


11 Syngas 16.294 529.70 30 102.681 5000.42 13.53
12 Syngas 16.294 598.15 30 101.841 5033.73 13.73
13 Syngas 16.294 457.10 30 100.45 4964.98 13.73
14 Syngas 16.294 488.20 30 100.018 4998.29 13.88
15 Syngas 14.325 298.15 30 97.72 4883.45 13.88

16 Cond. H2O 1.969 298.15 1 0.00492 0 0


17 H2 0.521 298.15 30 63.468 3875.36 16.96
18 Off-gas 13.804 298.15 1 31.62 1934.78 17.00
19 Air 32.304 309.600 1 0.017 9.49 155.07
20 Off-gas 46.108 873.2 1 16.26 1945.08 33.23
21 Off-gas 46.108 773.15 1 12.74 1524.00 33.23

22 Off-gas 48.709 557.7 1 7.72 923.49 33.23


23 Feed water 16.731 298.15 1 0 540.47 *
24 Water 16.731 300 50 0.0956 545 1583.57
25 Water 16.731 435.9 50 1.84 663.49 100.16
26 Water 16.731 478.3 50 2.91 734.89 70.15
27 Water 16.731 537.1 50 6.29 928.21 40.99

28 Water 16.731 537.1 50 6.35 931.40 40.74


29 Water 16.731 617 50 19.1 1948.61 28.34
30 Water 16.731 768.15 50 22.616 2514.22 30.88
31 Water 16.731 714.15 30 20.49 2277.87 30.88
32 Water 13.823 714.15 30 16.93 1882.10 30.88
33 Water 13.823 318.96 0.1 4.89 543.62 30.88

W_ HPT 1.66 439.02 73.46


W_ CT 12.04 1510.14 34.84
W_ ASU 9.73 2149.44 61.36
420 Exergy

TABLE 20.15 Capital Investment and OM Cost Rate for the Downdraft Gasifier System

Z_ ($/h) Z_ Z_ k ($/h)
CI OM
Capital investment PEC ($) PEC/PECt (%) ($/h)
ASU 120790.99 11.50 1.56 1.62 3.18
Downdraft gasifier 22648.31 2.16 0.29 0.30 0.60

Gas cleaning 7549.44 0.72 0.10 0.10 0.20


Compressor 128901.11 12.27 1.66 1.73 3.39
CO-shift 22648.31 2.16 0.29 0.30 0.60
PSA 181186.48 17.24 2.33 2.43 4.77
HX1 185173.18 17.62 2.38 2.49 4.87
HX2 4917.38 0.47 0.06 0.07 0.13

HX3 7818.42 0.74 0.10 0.11 0.21


HX4 7201.18 0.69 0.09 0.10 0.19
HX5 9999.35 0.95 0.13 0.13 0.26
Pump 8692.85 0.83 0.11 0.12 0.23
Steam turbine 7828.71 0.75 0.10 0.11 0.21
GE- Jenbacher 335369.21 31.92 4.32 4.51 8.82

Total 1050724.93 100.00 13.53 14.12 27.65

Operation costs C_ ($/yr)


Catalyst 25024.38
Labour cost 29354.11
Interest 37426.49

Maintenance 17318.93
Other 3816.03
Total 112939.95

that part enters the gasifier and the remainder passes efficiencies are 70.6% and 74.2% for the DG and CFBG
through a secondary turbine for additional power gasifier units, respectively, while the corresponding exergy
generation. efficiencies for the overall systems are 42.6% and 36.6%.
The exergy destruction rates are 0.88 and 112.17 MW, and
the electrical power export rates to the grid are 144 and 1.17
20.8.2.2 Exergy Analysis MW, for the DG and CFBG systems, respectively.
The system is taken to operate at steady state in a reference
environment having a temperature T0 of 25 C and pressure
20.8.2.3 SPECO Analysis
P0 of 101.325 kPa. The main assumptions made in the
analysis are that kinetic and potential energy effects and We now apply the SPECO method to the two gasification
component heat losses can be neglected, gases behave systems. In this analysis, salvage value is neglected, the
ideally, and the syngas produced by the gasifier is at parameter f 1 since the OM costs are calculated sepa-
chemical equilibrium. rately, the cost of fuel (biomass, electric, and water) are
Exergy rates of the streams for the DG and CFBG evaluated separately from OM costs, and component costs
systems are given in Tables 20.13 and 20.14, respectively. are taken from the literature. The capital investment and
The biomass fuel is pine wood in both systems. The exergy OM costs are taken from their reference studies, and the
Chapter | 20 Exergoeconomic Analysis of Thermal Systems 421

TABLE 20.16 Capital Investment and OM Cost Rate for the Circulating Fluidized Bed Gasifier System

Z_ ($/h) Z_ Z_ k ($/h)
CI OM
Capital investment PEC ($) PEC/PECt (%) ($/h)
Biomass pretreatment 20592700 9.68 265.15 107.35 372.50
ASU O2 comp 42720000 20.08 550.06 222.70 772.75

Gasifier cyclone 39315000 18.48 506.22 204.95 711.16


Tar cracking 7367000 3.46 94.86 38.40 133.26
Desulferization (filters, scrubbers, guard beds) 11620000 5.46 149.62 60.57 210.19
Shift reactors-total (hts,mts,lts) 5523700 2.60 71.12 28.79 99.92
PSA 51230000 24.08 659.63 267.06 926.69
HX1 4915000 2.31 63.29 25.62 88.91

HX2 17900 0.01 0.23 0.09 0.32


HX3 128000 0.06 1.65 0.67 2.32
HX4 146400 0.07 1.89 0.76 2.65
HX5 201800 0.09 2.60 1.05 3.65
HX6-steam boiler 7990000 3.75 102.88 41.65 144.53
Combustion cumber 45000 0.02 0.58 0.23 0.81

Water pump 250600 0.12 3.23 1.31 4.53


Air fan 27600 0.01 0.36 0.14 0.50
Steam turbine 11204000 5.27 144.26 58.41 202.67
Expansion turbine 9490000 4.46 122.19 49.47 171.66
Total 212784700 100.00 2739.79 1109.23 3849.03

Operating cost C_ ($/y)


Ash deposition 339900.28
Personel 1171800.00
Management 175770.00
License and catalyst 6051211.33
Personel overhead 908145.00

Administration 227036.25
Total 8873862.86

combustion chamber cost is calculated from the purchase escalation rate are those reported on October 5, 2010, by the
equipment cost equation (Bejan et al., 1996). These costs Central Bank of the Republic of Turkey as 8.91% and
are modified using Equations 20.34 and 20.35, with a cost 19.25%, respectively. Also, the nominal interest rate is
index that allows the reference year to be consistent at considered to be 15.48%. According to these data, the real
2010. We treat energy, biomass, and water costs as sepa- interest rate can be calculated as 6% using Equation 20.25.
rate from OM costs, because of their significance. The other important parameter is the capital recovery factor
The systems considered are from different countries, but (CRF), which is used to determine the equal amounts of
we calculate both stream and hydrogen unit costs as if the a series of money transactions and the present value. We
facilities operate in Turkey. The process lifetime is consid- calculate the CRF as 0.103 using the above data and Equa-
ered to be 15 years, while the inflation rate and energy tion 20.24. Also, the unit energy, water, and biomass costs
422 Exergy

TABLE 20.17 Summary of Economic Results for the Downdraft Gasifier and Circulating Fluidized Bed Gasifier Systems

Parameter DG system CFBG system


Z_ ($/h)
k
27.65 3849.03
C_ biomass ($/h) 18.45 2118.87

C_ water ($/h) 2.55 540.47


C_ w ($/h) (to the grid) 31.88 -258.39
C_ T ($/h) 16.77 6249.98
H2 (kg/h) 14.4 1875
CH2 ($/kg) 1.16 3.33
CH2 ($/GJ) 9.62 27.55

are 31.38 $/GJ, 4.59 $/t and 35.42 $/t. The capital investment biomass costs from 20 and 29 $/t; the corresponding costs
and OM costs are calculated with Equations 20.19e20.29 are 0.11 $/kWh and 35.4 $/t here.
and given in Tables 20.15 and 20.16. The fuel cost and other
stream cost rates are calculated using Equations
20.9 CLOSING REMARKS
20.14e20.18 and 20.30e20.33, respectively.
The cost rates and unit costs of all streams are given in This chapter provides insights into the relations between
Tables 20.13 and 20.14. It can be seen that the investment energy and exergy losses and capital costs for energy
and OM costs increase as the system capacities increase. systems. The methods are useful in analysis and design that
The Z_ values are 27.65 and 3849.03 $/hour for the DG and integrates thermodynamics and economics.
CFBG systems, respectively. The unit biomass costs are A systematic correlation often exists between exergy
3.37 $/GJ for both systems, as they use the same fuel. The loss rate (total or internal) and capital cost for coal-fired,
systems yield two main products: H2 and electric power. oil-fired, and nuclear generating stations. Furthermore,
The unit steam costs are 17.95 and 30.72 $/GJ for the DG a correlation appears to exist between the mean thermo-
and CFBG systems, respectively. These values imply that dynamic-loss-rate-to-capital-cost ratios for all of the
steam production within the plants is more economic than devices in a station and the ratios for the overall station,
using a steam turbine. The unit costs of producing syngas when the ratio is based on total or internal exergy losses,
are 7.62 and 9.76 $/GJ for the DG and CFBG systems, but not when it is based on energy losses. This correlation
respectively. may imply that devices in successful electrical generating
Another important parameter is the electric energy use stations are configured to achieve an overall optimal design
rate. The required electric energy rates are 0.0915 and by appropriately balancing the thermodynamic (exergy
12.53 MW for the DG and CFBG systems, respectively. based) and economic characteristics of the overall station
The systems produce 0.235 and 13.7 MW, respectively, and and its devices. This idea may extend to the electrical utility
0.144 and 1.17 MW can be sold to the grid at 31.88 and sector and the generating stations that comprise it, as well
258.39 $/hour, respectively. When electric gain is sub- as other technologies (e.g., cogeneration).
tracted from the total cost rates, the hydrogen unit costs are
calculated as 1.16 and 3.33 2.45 $/kg for the DG and CFBG
PROBLEMS
systems, respectively.
The results of the cost rates for the systems are 20.1 What is exergoeconomics? What is the difference
summarized in Table 20.17. The maximum hydrogen flow between exergoeconomics and thermoeconomics?
rate is 1875 kg/s for the CFBG, but its unit hydrogen cost is 20.2 What are the advantages of costing based on exergy
higher at 3.33 $/kg. The hydrogen production cost is compared to costing based on energy?
affected by many factors (biomass, water and unit power 20.3 How are the exergy losses in a system related to
costs, inflation, facility lifetime, operation time, etc.). economic losses?
Hydrogen production costs from biomass in the literature 20.4 Is it possible to perform an exergoeconomic analysis
range from approximately 1 to 6 $/kg. In the literature, of a system that has no fuel cost, such as a solar
electricity costs range from 0.05 to 0.095 $/kWh and energy system? If so, how useful is such an analysis
Chapter | 20 Exergoeconomic Analysis of Thermal Systems 423

compared to an exergoeconomic analysis of a fuel- 20.11 Describe the EXCEM analysis method. Can an
driven system such as a coal power plant? energy analysis be performed with this method?
20.5 Is it possible for a designer to use the recommen- 20.12 Obtain a published article on exergoeconomic
dations of exergy analysis to improve the perfor- analysis of a power plant. Using the operating and
mance of a system without conducting an exergy cost data provided in the article, perform a detailed
analysis of the system? Explain with examples. exergoeconomic analysis of the plant and compare
20.6 Explain how the exergy-based price of various fuels your results to those in the original article.
can be determined. Provide examples. 20.13 Obtain actual operating and cost data from an
20.7 If your local power company decides to price energy system and perform an exergoeconomic
electricity based on exergy, how would your elec- analysis. Discuss the results.
tricity bill change? 20.14 Calculate the exergy destruction rate in each
20.8 Write general energy, exergy, and cost balances and component of the two systems presented in Section
explain their differences. Are there any similarities 20.8. Based on the exergy destruction rate deter-
between cost and entropy balances? mine which component performs worst in each
20.9 An energy engineer claims that an exergoeconomic system from exergy perspective and suggest ways
analysis of a fossil-fuel power plant is not advan- for improving exergy destruction rate.
tageous compared to an energy-based economic 20.15 For the two systems presented in Section 20.8,
analysis since the exergy of a fossil fuel is approx- conduct SPECO analysis and calculate cost rate (C) _
imately equal to its heating value. Do you agree? and unit cost (c) of each component of the systems.
Explain. 20.16 For the two systems presented in Section 20.8,
20.10 In the exergoeconomic case studies in this chapter, conduct EXCEM analysis and compare your
what correlations exist between capital cost, exergy results with the SPECO analysis presented in the
loss, and energy loss? chapter.

You might also like