You are on page 1of 3

Govindharajalu D

From: kcon <kcon@vsnl.com>


Sent: 09 May 2016 13:27
To: Bhavani Sankar Y
Cc: Subrahmanyam A; Ansuman Choudhury; Govindharajalu D; Sourav Ghosh
Subject: RE: AMC - Bulk water system - WTP

As per IS 3370 (Part 1) 2009 Concrete Structures for Storage of liquids Code of practice.

On Page no 12 , It is only and clearly written that The minimum ventilation shall be ensured.

As per MJP Practice 1 no of caul type ventilator should be provided for 16 sqm area of roof slab of sump.

Total roof slab area : 66 m x 35m = 2310 sqm, Hence no of ventilators = 2310 / 16 = 144 no (Equispaced)

Caul Type CI ventilator, 100 dia

Roof Slab

And this is essentially a structural design issue.

From: Bhavani Sankar Y [mailto:bhavanisankar@tataprojects.com]


Sent: Monday, May 09, 2016 12:17 PM
To: kcon@bom5.vsnl.net.in
Cc: 'info'; Subrahmanyam A; Ansuman Choudhury; Govindharajalu D; Sourav Ghosh
Subject: RE: AMC - Bulk water system - WTP

Dear sir,
The vents indicated on the pure water sump are atmospheric vents. I request you to indicate these atmospheric vent
size calculations. Further, you are aware that no mechanical fans will be used for sump venting.

Please furnish the atmospheric vent size calculations indicated on the pure water sump. .

With Regards,

Y.Bhavani Sankar
General Manager (Engg),
TATA PROJECTS LIMITED.
Corporate Office
1-7-80 to 87
Prenderghast Road,Secunderabad -500003, India

Tel: +91-40-6623 8915 ; Fax: +91-40-66312533 Mob: 9948085250


Email: bhavanisankar@tataprojects.com
Website: www.tataprojects.com
1
From: kcon [mailto:kcon@vsnl.com]
Sent: 09 May 2016 12:07
To: Bhavani Sankar Y
Cc: 'info'; Subrahmanyam A; Ansuman Choudhury; Govindharajalu D; Sourav Ghosh
Subject: RE: AMC - Bulk water system - WTP

Bhavani,

The replies are in blue color.

Thx & Reg

Shirish

From: Bhavani Sankar Y [mailto:bhavanisankar@tataprojects.com]


Sent: Friday, May 06, 2016 3:06 PM
To: kcon@bom5.vsnl.net.in; Shirish Jayant Kardile
Cc: info; Subrahmanyam A; Ansuman Choudhury; Govindharajalu D; Sourav Ghosh
Subject: AMC - Bulk water system - WTP

Dear sir,

Please confirm the following:


1. As per P&ID the waste back wash water pipeline size from filters to Wash water recirculation sump is indicated
as 1000 dia RCC NP2 pipe (KCon drg No. 263) , where as in GA for wash water disposal arrangement (Kcon drg
No. 275), the size is indicated as 1100dia RCC NP2. Please confirm the correct size.
Diam 1100mm, as mentioned in Dr No.275 is correct
2. Please furnish the Vent size calculation for Pure water sump.
Volume of P. W. Sump is 8000 cum. Air changes recommended are 5. Total air rate =
40,000 cum/hr ( Sump empty). No of exhaust fans = 6 (six), Capacity of each fan = 40,000 /
6 = 6667 cum/hr

Also please note that IE approved the revised Process calculation for WTP, P&ID and HFD on 4-5-2016.

With Regards,

Y.Bhavani Sankar
General Manager (Engg),
TATA PROJECTS LIMITED.
Corporate Office
1-7-80 to 87
Prenderghast Road,Secunderabad -500003, India

Tel: +91-40-6623 8915 ; Fax: +91-40-66312533 Mob: 9948085250


Email: bhavanisankar@tataprojects.com
Website: www.tataprojects.com

2
Notice: Information contained and transmitted by this email is confidential and proprietary to Tata Projects.
Information contained is for use only by the recipients. If you are not the intended recipient, you are notified
that dissemination or copying of this email or its contents therein is strictly prohibited; you are requested to
delete this email immediately and notify the sender.
Notice: Information contained and transmitted by this email is confidential and proprietary to Tata Projects.
Information contained is for use only by the recipients. If you are not the intended recipient, you are notified
that dissemination or copying of this email or its contents therein is strictly prohibited; you are requested to
delete this email immediately and notify the sender.

You might also like