As per IS 3370 (Part 1) 2009 Concrete Structures for Storage of liquids Code of practice.
On Page no 12 , It is only and clearly written that The minimum ventilation shall be ensured.
As per MJP Practice 1 no of caul type ventilator should be provided for 16 sqm area of roof slab of sump.
Total roof slab area : 66 m x 35m = 2310 sqm, Hence no of ventilators = 2310 / 16 = 144 no (Equispaced)
Roof Slab
Dear sir,
The vents indicated on the pure water sump are atmospheric vents. I request you to indicate these atmospheric vent
size calculations. Further, you are aware that no mechanical fans will be used for sump venting.
Please furnish the atmospheric vent size calculations indicated on the pure water sump. .
With Regards,
Y.Bhavani Sankar
General Manager (Engg),
TATA PROJECTS LIMITED.
Corporate Office
1-7-80 to 87
Prenderghast Road,Secunderabad -500003, India
Bhavani,
Shirish
Dear sir,
Also please note that IE approved the revised Process calculation for WTP, P&ID and HFD on 4-5-2016.
With Regards,
Y.Bhavani Sankar
General Manager (Engg),
TATA PROJECTS LIMITED.
Corporate Office
1-7-80 to 87
Prenderghast Road,Secunderabad -500003, India
2
Notice: Information contained and transmitted by this email is confidential and proprietary to Tata Projects.
Information contained is for use only by the recipients. If you are not the intended recipient, you are notified
that dissemination or copying of this email or its contents therein is strictly prohibited; you are requested to
delete this email immediately and notify the sender.
Notice: Information contained and transmitted by this email is confidential and proprietary to Tata Projects.
Information contained is for use only by the recipients. If you are not the intended recipient, you are notified
that dissemination or copying of this email or its contents therein is strictly prohibited; you are requested to
delete this email immediately and notify the sender.