You are on page 1of 11

Technical Parameter

NO.1 ZRC-YJV22-6/10kV(,copper
core XLPE insulated, steel tape armored PVC sheathed, flame retardant, low smoke and
low halogen)
conductor
GB/T3956-200820.9
GB/T3956-2008
Extruded round copper conductor according to GB/T3956-2008 type2,and extruded
modulus of conductor is less than 0.9. the conductor structure and performance accord
with the specification of GB/T3956-2008
conductor screen, insulation, insulation screen
(POW50POW30)
SIKORA

Conductor screen ,insulation and insulation screen use three-layer extruded technics.
(using POW50POW30 XLPE product line of MV, HV come from Finland)completely
block out drying type chemistry XLPE by using conductor warm-up, heat up using nitrogen,
cooling using nitrogenusing scanner named SIKORA of online section eccentricity come
from Germany to check continuously.
XLPEGB/T12706.2
Insulation adopt XLPE insulationwhose performance according to GB/T12706.2.
Metal screen
0.1mm
90%
Metal screen is made up of flexible copper tape with overlap bundled. Connecting way
of copper tape is electric welding. Nominal thickness of copper tape in 3-core cable is
0.1mm, whose thickness at the thinnest point is not less than 90% of nominal value.

Copper tape bundled smooth and clean3-core copper screen layer contract all right
for completing insulated core.
Core, inner bedding ,and filler

We adopt non-moisture absorption flexible filler in 3-core clearance after completing
cable, which has round shape.

GB/T12706.2
Inner bedding of armored cable adopts extruded inner bedding layer, whose material is
low smoke low halogen PVC sheath material and thickness accord with GB/T12706.2.
armoring

3-core cable adopts galvanized steel tape armoring
outer sheath
GB/T12706.2
Sheath material is red low smoke low halogen, insect and rodent resistant PVC, whose
performance meet GB/T12706.2
Technical Data: Voltage:6000/10000V,
Temperature range: -20 to +90
Relevant Standards: IEC60502(is equivalent to)GB/T12706
IEC60228(is equivalent to)GB/T3956
IEC 60331(is equivalent to)GB/T18380
IEC 60332(is equivalent to)GB/T18380
IEC60811 (is equivalent to)GB/T2951
GB/T6995
Conductor

Semi-conductive inner screen
XLPE insulation
Semi-conductive outer screen
Steel tape screen
Wrapping tape

Filler

Inner sheath
Galvanized tape armoring
Outer sheath

Sizes and Dimensions


All sizes and dimensions are approximate and for information only. BAC will confirm
actual dimensions at time of order if required:
Conductor Number Diameter Nom. Approx. Gland
Size Of Strands Of Conductor(mm) O.D.(mm) Nett Size
(mm2) Weight(kg/km)
ZRC-YJV22 19/2.92 13.0 58.22.0 6224 NO
3x120mm2
ZRC-YJV22 30/2.62 14.5 61.62.0 7222 NO
3x150mm2
ZRC-YJV22 37/2.62 16.1 65.72.0 8538 NO
3x185mm2
ZRC-YJV22 59/3 23.5 85.12.0 16429 NO
3x400mm2
NO.2 YJV-12/20kV(,)
copper core with Cross Linking PolyEthyleneinsulation,PVC sheath ,low smoke and low
halogen
conductor
GB/T3956-200820.9
GB/T3956-2008
Extruded round copper conductor according to GB/T3956-2008 type2,and extruded modulus of
conductor is less than 0.9. the conductor structure and performance accord with the specification of
GB/T3956-2008
conductor screen, insulation, insulation screen
(POW50POW30)
SIKORA

Conductor screen , insulation and insulation screen use three-layer extruded technics. (using
POW50POW30 XLPE product line of MV, HV come from Finland)completely block out drying type
chemistry XLPE by using conductor warm-up, heat up using nitrogen, cooling using nitrogenusing
scanner named SIKORA of online section eccentricity come from Germany to check continuously.
XLPEGB/T12706.2
Insulation adopt XLPE insulationwhose performance according to GB/T12706.2.
Metal screen
0.1mm
90%
Metal screen is made up of flexible copper tape with overlap bundled. Connecting way of copper
tape is electric welding. Nominal thickness of copper tape in single core cable is 0.1mm, whose
thickness at the thinnest point is not less than 90% of nominal value.

Copper tape bundled smooth and clean3-core copper screen layer contract all right for
completing insulated core.
outer sheath
GB/T12706.2
Sheath material is red low smoke low halogen, insect and rodent resistant PVC, whose
performance meet GB/T12706.2.
Technical Data: Voltage:18000/20000V,
Temperature range: -20 to +90
Relevant Standards: IEC60502(is equivalent to)GB/T12706
IEC60228(is equivalent to)GB/T3956
IEC 60331(is equivalent to)GB/T18380
IEC 60332(is equivalent to)GB/T18380
IEC60811 (is equivalent to)GB/T2951
GB/T6995
Conductor
Semi-conductive conductor screen
XLPE insulation
Semi-conductive insulation screen
Copper tape screen
Wrapping tape
Outer sheath

Sizes and Dimensions


All sizes and dimensions are approximate and for information only. BAC will confirm
actual dimensions at time of order if required:
Conductor Number Diameter Nom. Approx. Gland
Size of of O.D.(mm) Nett Size
(mm2) Strands Conductor(mm) Weight(kg/km)
YJV- 19/2.92 13.0 35.12.0 2026 NO
1x120mm2
NO.3 ZRC-VV-0.6/1kV()
Flame-proof C type, copper core with PVC insulation, PVC sheath, low smoke and low
halogen
conductor
GB/T3956-2008
Structure, performance and appearance of conductor meet GB/T3956-2008
insulation
GB/T12706
Insulation adopts flame retardant, low smoke low halogen PVC, whose nominal thickness
meets GB/T12706.
outer sheath
GB/T12706
Outer sheath of cable is black low smoke low halogen, insect and rodent resistant PVC,
whose nominal thickness meets GB/T12706
Technical Data: Voltage:600/1000V,
Temperature range: -20 to +70
Relevant Standards: IEC60502(is equivalent to)GB/T12706
IEC60228(is equivalent to)GB/T3956
IEC 60331(is equivalent to)GB/T18380
IEC 60332(is equivalent to)GB/T18380
IEC60811 (is equivalent to)GB/T2951
GB/T6995

Conductor
Insulation
Filler
Wrapping tape
Outer sheath

3 3 core circular shape

31 2 3 4
3 core sector-shape(1 conductor 2 insulation, 3 wrapping tape 4 outer sheath)

Sizes and Dimensions


All sizes and dimensions are approximate and for information only. BAC will confirm
actual dimensions at time of order if required:
Conductor Number Diameter Nom. Approx. Gland
Size of of O.D.(mm) Nett Size
(mm2) Strands Conductor(mm) Weight(kg/km)
ZRC-VV 37/2.6 13.5*24.0 44.71.5 6035 NO
3x185mm2
ZRC-VV 7/2.14 6.4 23.81.0 1056 NO
3x25mm2
ZRC-VV 7/1.7 5.1 20.21.0 705 NO
3x16mm2
ZRC-VV 1/2.25 2.3 14.21.0 263 NO
3x4mm2
ZRC-VV 1/1.78 1.8 12.21.0 183 NO
3x2.5mm2
NO.4 ZRC-VV22-0.6/1kV()
Flame-proof C type, copper core with PVC insulation, PVC sheath, low smoke and low
halogen
conductor
GB/T3956-2008
Structure, performance and appearance of conductor meet GB/T3956-2008
insulation
GB/T12706
Insulation adopts flame retardant, low smoke low halogen PVC, whose nominal thickness
meets GB/T12706.
Core and filler

The laying-up direction of cable insulation core is right hand

non-moisture materials are filled in the cable cores
GB/T12706.1-2008
Inner bedding is wrapped over the core of armored cable, whose thickness meets
GB/T12706.1-2008.
armoring

Single core cable adopts double-layer stainless steel tape armoring; multi-core cable
adopts double-layer galvanized steel tape armoring
GB/T12706.1-2008
The thickness of steel tape meets GB/T12706.1-2008. Wrapping tape of steel tape is round
and smooth

Wrapping tape is lapped in the interval of double-layer steel tape. The surface of
armoring layer is smooth without ruffle bulge or other defects
outer sheath
GB/T12706
Sheath of cable is black low smoke low halogen, insect and rodent resistant PVC, whose
nominal thickness meets GB/T12706.

Technical Data: Voltage:600/1000V,


Temperature range: -20 to +70
Relevant Standards: IEC60502(is equivalent to)GB/T12706
IEC60228(is equivalent to)GB/T3956
IEC 60331(is equivalent to)GB/T18380
IEC 60332(is equivalent to)GB/T18380
IEC60811 (is equivalent to)GB/T2951
GB/T6995

Conductor

Insulation
Filler
Inner bedding
Steel tape armoring

Outer sheath

2 2 core

Copper conductor
Insulation
Filler
Wrapping tape
Inner bedding
Steel tape armoring
Outer sheath

3 3 core circular tape

2
3
4
5
6

31 2 3 4 5 6
3 core sector-shape(1conductor, 2 insulation, 3 wrapping tape, 4 inner bedding, 5
steel tape armoring 6 outer sheath)

1. Conductor
Insulation

Filler
Inner bedding

Galvanized steel tape armoring
Outer sheath

3+1 3+1 circular shape


Conductor

Insulation
Filler
Inner bedding
Steel tape armoring

Outer sheath

4 4 core circular
Sizes and Dimensions
All sizes and dimensions are approximate and for information only. BAC will confirm
actual dimensions at time of order if required:
Conductor Number Diameter Nom. Approx. Gland
Size of of O.D.(mm) Nett Size
(mm2) Strands Conductor(mm) Weight(kg/km)
ZRC-VV22 1/1.78 1.8 14.21.0 262 NO
3x2.5mm2
ZRC-VV22 1/2.25 2.3 16.21.0 355 NO
3x4mm2
ZRC-VV22 1/2.25 2.3 17.31.0 427 NO
4x4mm2
ZRC-VV22 1/2.76 2.8 17.31.0 438 NO
3x6mm2
ZRC-VV22 7/1.35 4.1 20.11.0 622 NO
3x10mm2
ZRC-VV22 7/1.35 4.1 20.91.0 706 NO
3x10mm2+1x6mm 1/2.76 2.8
2
ZRC-VV22 7/1.7 5.1 22.21.0 841 NO
3x16mm2
ZRC-VV22 7/2.14 6.4 25.91.0 1217 NO
3x25mm2
ZRC-VV22 7/2.62 7.0 27.21.0 1504 NO
3x35mm2
ZRC-VV22 19/1.89 6.8*12.0 27.31.0 1859 NO
3x50mm2
ZRC-VV22 14/2.6 8.2*14.1 30.81.0 2514 NO
3x70mm2
ZRC-VV22 19/2.6 9.6*16.8 36.91.0 3730 NO
3x95mm2
ZRC-VV22 24/2.6 10.8*19.1 39.61.0 4517 NO
3x120mm2
ZRC-VV22 37/2.6 13.5*24.0 48.71.5 6768 NO
3x185mm2
ZRC-VV22 48/2.6 15.5*27.6 54.11.5 8649 NO
3x240mm2
ZRC-VV22 60/2.62 20.6 67.62.0 11245 NO
3x300mm2
ZRC-VV22 1/2.25 2.3 15.51.0 296 NO
2x4mm2
ZRC-VV22 1/2.76 2.8 16.51.0 357 NO
2x6mm2
ZRC-VV22 7/1.35 4.1 19.11.0 496 NO
2x10mm2
ZRC-VV22 7/1.6 5.1 21.11.0 658 NO
2x16mm2
ZRC-VV22 7/2.14 6.4 24.51.0 934 NO
2x25mm2
ZRC-VV22 7/3 8.3 29.11.0 1475 NO
2x50mm2
NO.5 ZRC-YJV-0.6/1kV()
Flame-proof C type, copper core with PVC insulation, PVC sheath, low smoke and low
halogen
conductor
GB/T3956-2008
Structure, performance and appearance of conductor meet GB/T3956-2008 GB/T3956-2008
insulation
GB/T12706
Insulation adopts XLPE material, whose nominal thickness meets GB/T12706
outer sheath
GB/T12706
Outer sheath of cable is black low smoke low halogen, insect and rodent resistant PVC,
whose nominal thickness meets GB/T12706
Technical Data: Voltage:600/1000V,
Temperature range: -20 to +90
Relevant Standards: IEC60502(is equivalent to)GB/T12706
IEC60228(is equivalent to)GB/T3956
IEC 60331(is equivalent to)GB/T18380
IEC 60332(is equivalent to)GB/T18380
IEC60811 (is equivalent to)GB/T2951
GB/T6995

31 2 3 4
3 core sector shape (1 conductor, 2 insulation, 3 wrapping tape, 4 outer sheath)

Sizes and Dimensions


All sizes and dimensions are approximate and for information only. BAC will confirm
actual dimensions at time of order if required:
Conductor Number Diameter Nom. Approx. Gland
Size of of O.D.(mm) Nett Size
(mm2) Strands Conductor(mm) Weight(kg/km)
ZRC-YJV 48/2.6 15.5*27.6 482.0 7317 NO
3x240mm2

You might also like