Assistant Divisional Engineer 400KV / APTRANSCO / Hyderabad S.No QUESTIONS ANSWERS 1. What are the Protections adopted 1. Main-1 Protection : Distance Protection in 400KV Lines (21M1/L1) 2. Main-2 Protection : Distance/ Differential (21M2/L2 or 87M2/L2) 3. Over Voltage Stage-1 Prot (59-1) 4. Over Voltage Stage-2 Prot (59-2) 5. Auto reclosure with check synchronization (79 + 25) 6. Sensitive IDMT Directional E/F Relay (67N) 2. What are the Protections adopted 1. Main Protection: Differential Protection for 400/220KV ICT (87T) 2. Backup Protection: IDMT Directional Over Current & Earth Fault Protection on HV side (67HV) 3. Backup Protection: IDMT Directional Over Current & Earth Fault Protection on LV side (67LV) 4. Over Flux Protection on HV side (99T HV) 5. Over Flux Protection on LV side (99T LV) 6. Additional Protection: REF Protection or High Impedance Differential Protection (64T/87T) 7. Additional Protection: Neutral Displacement Protection (151N) 8. Additional Protection: Under Impedance/ Distance Protection (21T) 9. Additional Protection: Neutral Current Protection(51) 10. Over Load Alarm Protection (51 O/L) 3. What are the Protections adopted 1. Main Protection: Differential Protection for 400KV Shunt Reactor. (87R) 2. Backup Protection: Under Impedance/ Distance Protection or Definite Time Over Current & Earth Fault Protection(21R/51) 3. REF Protection (64R) 4. What are the inbuilt Protections 1. Gas Detector or Oil Surge detector or Say available for 400KV ICT / Shunt Buchholz Relay or Oil Surge relay Reactor? 2. Similarly for OLTC Buchholz Relay or Oil Surge relay 3. Oil Temperature 4. Winding Temperature 5. Oil Level 6. Pressure Relief. 5. Meaning of LBB/BFR Local Breaker Backup Protection / Breaker Failure Relay 6. What are the requirements for 1. Any protective relay operates will initiate LBB operation LBB. 2. After initiation, timer starts & waits for 200ms. 3. After elapse of stipulated time still initiation is there and currents are available in LBB then it will Operate and give trip signal to adjacent Breakers connected to the Bus. 7. Why we need Bus bar Protection? To Provide High Speed Sensitive Clearance of Bus bar Faults by tripping all the Circuit Breakers connected to faulty Bus. 8. Why line protection need For redundancy and Reliability. duplicate Distance protection? 9. How many zones are required in Minimum 3 Zones and some manufacturers Distance Protection are giving more than 3 zones. 10. on which principle the Merz-Price Principle differential relay operates 11. Why 2nd harmonic restraint When a Power Transformer with its required for Differential Relay secondary circuit open, is switched on, it acts as a simple Inductance and a magnetizing in rush current which will be several times, Transformer full load current will flow. As the inrush current flows in the Primary of the Transformer only, it appears to the Differential relay as an internal fault. A Harmonic analysis of typical magnetic inrush current wave is shown below 2nd : 63.0 % rd 3 : 26.8 % th 4 : 5.1 % 5th : 4.1 % th 6 : 3.7 % th 7 : 2.4 % as seen from the above, the second harmonic component is predominant in the Magnetizing Inrush Current. A Differential Relay which Extracts the 2nd Harmonic Current and fed to the restraint coil to make the relay inoperative due to Magnetic inrush current. 12. Name at Least 2 types of 1. Quadrilateral Characteristics for distance 2. Mho schemes. 3. Optical/Lens 4. Bullet 5. Triangular 13. Differentiate switched Distance In an Ideal Non switched scheme, there will scheme and non switched be 6 starters, 3 for Phase Faults and 3 for distance scheme. ground faults. There will be independent Measuring units for both Phase faults and earth faults for each phase, for all 3 zones, totaling 18 units. This scheme is faster and more accurate but is costly. In the switched scheme, only one measuring unit will be used for all types of faults. This single measuring unit is switched to the correct fault loop impedance by switching-in the respective voltages and currents by the starter. Switched scheme is relatively slow in operation and has the risk of total scheme failure in the event of failure of the only one measuring unit is available. 14. What is the accuracy limit of < 5% Zone-1 reach 15. Why Fuse Failure Protection is The distance relays being voltage restraint required as an inbuilt feature in O/C relays, loss of Voltage due to main PT Distance Protection. fuse failure or inadvertent removal of Fuse in one or more phases will cause the relay operation. The fuse failure relay will sense such condition by the presence of residual voltage with out residual current and blocks the relay. 16. What types of unit protections 1. Phase Comparison Protection are available for Line? 2. Phase segregated Line Differential Relay 17. Need of Over Voltage Protection Normally 400KV transmission lines are for Transmission Lines. meant for Transmission of Bulk Power to Long Distances to Load center area. If the line is idle charged condition or lightly loaded condition the sending end voltage is more than the receiving end voltage due to line mutual capacitance. This is called Ferranti effect. This may cause the failure of equipment. To safe guard the equipment, over voltage protection is adopted. 18. Necessity of Over Flux Protection If Flux increases causes on increase of the for Transformers. iron losses and disproportionately large increase in magnetizing current. This leads to a rapid temperature rise in the bolts and destroying their insulation and damaging coil insulation. To safe guard the Transformer, over flux protection is provided. 19. What is the Percentage of Around 85% Transient Faults in Transmission Lines in total faults? 20. In which condition Auto Zone-1 and Phase to Earth Faults only reclosure Relay operates. 21. Meaning of dead time In auto- The time between the Auto-reclosing Scheme reclosure operation. being energized and the operation of the contacts which energize the Circuit Breaker closing circuit. 22. Meaning of reclaim time In auto- The Time Following a successful closing reclosure operation operation measured from the instant the Auto-Reclosing relay closing contacts make which must elapse before the Auto-Reclosing relay initiates another reclosing attempt. In other words, it may be said to be the time between 1st and 2nd Auto-Reclosure. 23. What are the conditions required 1. Zone 2/3/4 of Distance protection for blocking Auto reclosure Relay. 2. LBB/BFR relay Operation 3. Over Voltage Protection 4. Circuit Breaker Problems 5. Bus bar Protection 6. carrier Fail conditions 7. Line Reactor Protection 8. Direct Transfer Trip signal received. 24. LBB relay is Current Operated or It is current operated. Voltage operated or both 25. Why Main and Check Bus bar Bus bar differential protection should have protection is required. over all sensitivity above heaviest loaded feeder current, unless separate check zone has been provided. Normally high impedance Bus bar protection needs check zone protection to over come this problem. The trip command is only given when both a discriminating & check zone system operates. 26. For 400KV lines Yes, for ICT 21T may be utilized as a Backup Main-1 is 21L & Main-2 is 87L Protection. utilized. For 400/220 KV ICT Main-1 is 87T & B/U 21T is it possible to utilize. 27. What is the principle of Operation Circulating Current Principle. of REF relay? 28. How many Configurations 1. I- Configuration available in One & Half Breaker 2. D- Configuration System 29. What are the CT methods 1. 3 CT Method available in One & Half Breaker 2. 4 CT Method System? 3. 5 CT Method 4. 6 CT Method (GIS Version) 5. 6 CT Method (AIS Version) 30. Which CT Method is More 3 CT Method Economical? 31. Which CT Method is fault free in 6 CT method ( GIS Version) Protection and not having blind zones? 32. Explain the Relevance of STUB When a Line is supplied via 2 Circuit Protection? Breakers in a One & Half Circuit Breaker arrangement, the line protection includes the area between the two CTs. However, when the line isolator is open the line CVTs for the Distance Protection are connected to the line and cannot provide the correct voltage for the STUB end.(i.e the area between the line isolator and CTs) (stub = dead end) To provide protection for a fault in this area, Distance Protection is Provided with a STUB protection which gives a bus over current trip if the line isolator is open and the current exceeds the set value in any phase. 33. Explain the Relevance of TEED The Main CT, Tie CT & Line CT are Physically Protection located in T shape in case of 5 CT Method. For identification of Fault in between these three CTs, then it is connected to Differential relay in the principle of Main CT current + Tie CT current = Line Current. 34. Explain the need of SOFT This is required where there are line voltage protection transformers, to provide fast tripping in the Event of accidental line energisation with maintenance earthing clamps left in position. 35. If power swing occurs whether It will block Distance scheme will operate or block 37. Why Over Load Relay is provided Over Load relay shall be set at 100% of in ICT Protection rated current with delay of 5 seconds. This shall be connected to give alarm only, for alertness and arranging a load relief. 38. In which case the Auto Where Transformation ratio HV to LV is less Transformers are utilized. than 2. 39. Condition for ND Relay Operation Due to Unbalanced Load condition the in case of Transformer shifting of Neutral will takes place from zero Protection. voltage to some voltage. This may cause failure of Transformer. To safe guard the Transformer this relay will be provided in LV winding. 40. Give the drawing of SLD of One & Half Breaker System (one dia Only) with CT, CVT, LA/SA, CB, WT/LT, Isolators & Earth Switches, Bus CVT with nomiclatures.
Katja Kruckeberg, Wolfgang Amann, Mike Green-Leadership and Personal Development - A Toolbox For The 21st Century Professional-Information Age Publishing (2011)