Professional Documents
Culture Documents
Abstract This paper presents stochastic method for measurement of such small offset is challenging task. For
measurement of DC voltage offset in 0.4kV distribution network measuring purpose, our 0.4kV signal could be treated as a
influence on magnetizing current even harmonics presence in the noise, and finally it exposes poor signal-to-noise ratio
power transformer. Variety of phenomenon, like geomagnetic 0.001/4002,5ppm. It is almost impossible to measure such
field, asymmetry of different loads, photovoltaic converters in
small signal in so large noise without some state of the art
smart grid, etc. can produce small DC voltage offset in power
transformer. Order of magnitude of this offset is around 1mV in oversampling measurement method. Significant step forward
0.4kV distribution network. Such extremely low DC signal level in DC offset voltage measurement is given in [1], where in
detection (in presence of high AC amplitude) presents analysis of even harmonics (II, IV, VI and VIII) of
challenging measurement task. By using stochastic method, even magnetizing current DC offset could be evaluated directly. In
the direct measurement of such small offset is possible. It is also this paper, stochastic adding A/D conversion (in further text
possible to measure even harmonics of magnetizing current in
SAADK) is utilized for direct and parallel measurement:
power transformer in order to measure input voltage DC offset
component indirectly, since even harmonics in magnetizing 1 Input voltage DC offset
current are consequence of DC component in input voltage. 2 True RMS of input voltage
3 Amplitude and phase of even harmonics of magnetizing
Index Terms Power Transformer, Measurement, Peak-to- current
Peak, Even Harmonics. In order to obtain valid simulation model, first task was to
achieve full correlativity between input voltage and
magnetizing current. For that purpose, input sine voltage
I. INTRODUCTION
together with DC offset is introduced throughout hysteresis
Presence of small DC voltage offset in distribution power transfer function. After numerical mapping of voltage
network (several mV order of magnitude in 0.4kV network), samples, we obtain adequate current samples. Further signal
can be important indicator that there are some anomalies processing is continued over both samples by using stochastic
present in distribution network [1]. DC offset could be a method. Paper is organized as follows: in section II simulation
consequence of photovoltaic solar panels connected to the model is presented. Section III explains stochastic method. In
grid. Value range of this offset is covered by norm [2]. section IV simulation results are evaluated. Section V is
Together with power inverters in photovoltaic sources [3], discussion. In section VI conclusion is given. Section VII
geomagnetic disturbances [4] can cause DC offset appearance. gives references.
If it appears, DC offset can have unfavorable influence on
efficiency and reliability of the power transformer. As the
consequence of DC offset presence, there is higher reactive II. SIMULATION MODEL
power consumption as well as iron losses. Since DC voltage
offset is about 1mV, and distribution power network is 0.4kV, In order to have simulation model as realistic as possible
and closer to real transformer, it is essential to make adequate
Velibor Pjevalica is with the JP Srbijagas, (e-mail: correlation between input voltage and induced magnetizing
velibor.pjevalica@srbijagas.com). current. Correlation is established over hysteresis loop. In
Nebojsa Pjevalica is with the Faculty of Technical Sciences, University of order to make model simpler, but not losing in generality,
Novi Sad, Trg D. Obradovia 6, 21000 Novi Sad, Serbia (e-mail:
pjeva@uns.ac.rs) hysteresis loop is defined as symbolical. Left hand side and
Nenad Petrovic is with the School of Electrical Engineering Stari grad, (e- right hand side of hysteresis loop are given, respectively:
mail: nploewenstein@ gmail.com).
ut A1 arctanit
Nikola Teslic is with the Faculty of Technical Sciences, University of
Novi Sad, Trg D. Obradovia 6, 21000 Novi Sad, Serbia (e-mail: (1)
nikola.teslic@rt-rk.uns.ac.rs)
ut A1 arctanit (2)
In here, parameter A1 is scaling factor between voltage and III. STOCHASTIC METHOD
current and is phase shift. Input signal is the sum of sine
signal and DC offset. Such input signal is introduced Stochastic adding A/D conversion with two noise
throughout hysteresis loop defined by (1) and (2). In fig. 1. it generators [5, 6] (abbreviated SAADK) is oversampling
is symbolically shown model with hysteresis defined by (1) measurement method. With this method, we digitally measure
and (2). average value of the integral of two analog y1(t) and y2(t)
signals product. Block scheme of the SAADK converter is
given in fig. 2.
1
y1 (t)=f1 (t)
A/D
A h1 (t)
2
ACC
y2 (t)=f2 (t)
A/D
B h2 (t)
u t
it tan (4) s2
1 21 2
R (7)
A1 N 8
6 Obtained magnetizing current signal is analyzed in
frequency domain. In formula (7), R is input range of the A/D converter.
7 Simulations are repeated according to given procedure for Concerning that voltage DC offset order of magnitude is 1mV
different DC offset values in order to see regularity how DC on 0.4kV distributive network, scaling i.e. voltage sensing
offset at the input is transferred on magnetizing current even must be done with the precise voltage divider with scale
harmonics. 2.5:400 i.e. 1:160. With this scale, input DC voltage offset
will be reduced to 1mV/160=6.25V. Upper absolute
measurement value boundary must be at least one order of
magnitude less than calculated 6.25V so it is at least 0.5V.
If there is A/D converter at the input with resolution of 14
bits, sampling frequency of 1MHz and input voltage range in DC offset = -10mV DC offset = -10mV
Amplitude Phase to phase of mains
A/D converter is R=2.5V and if measurement lasts 100s,
30 deg
upper absolute measurement error for measuring DC offset is:
35A 25 deg
30A
2
20 deg
2,5 25A
141
1 2 1 2,5 2
15 deg
20A
s (8)
100 2 10 4 8 15A 10 deg
10A
5 deg
s 0.19V (9) 5A
0 0
2 4 6 8 2 4 6 8
Overall number of the measuring samples is 100,000,000 and Fig. 2. Amplitudes and phases of the corresponding harmonic related to
it takes 100 seconds to obtain them with 1MHz sampling mains phase with DC offset voltage of -10mV
frequency. Direct DC offset measurement on distribution
network is demanding task due to very low signal-to-noise DC offset = -5mV DC offset = -5mV
Amplitude Phase to phase of mains
ratio. With stochastic method, however, it can be obtained in 25A
100 seconds.
20A
25 deg
3A 25 deg
UEFF -1mV 1mV
2.5A 20 deg
0.10V 0.12V
2A
15 deg
1.5A
Together with DC offset measurement, magnetizing current 10 deg
1A
spectral measurement is done as well. In figures from 2 to 7
amplitudes and phases of even harmonics (0, II, IV, VI and 0.5A 5 deg