PH120

What is PH120
?
It is easy to see why a PH120 cable An alternative would be for install-
would be used where a 120 min ers (and Speciers) to ask for Stan-
cable is actually required. After dard 30min or Enhanced 120min
all what is the dierence between grade cable.
PH120 and 120 minutes?
The UK market does just this and
The terminology is very similar categorises between STANDARD
but the meaning is very dierent. Grade (30) and ENHANCED
Grade (120) as stated in BS5839-1.
PH120 refers to the selectable
time duration in re test method Whilst writing I would urge all
BSEN50200 PH30/60/90/120 So, Fire Performance cables installers to carefully check their
and is referenced in IS3218 which should meet: specications, refrain from using
selects the test duration time in the terminology PH when buying
minutes. This re test has ame 1. BSEN50200 PH120 and FP Cables.
and shock only in the test method BSEN50200 + Annex A (known in
and most notably no water spray. the UK market as Standard cable) Having to remove wrongly se-
lected cables, and it does happen,
For sure the test duration is 120 2. BSEN50200 PH120 and quite often by genuine mistake,
minutes but there is no water BS8434-2:2008 (Known in the UK can be costly both nancially and
spray. If water spray was added to market as Enhanced cable) for reputation.
this test then the cable could be
There is also a dierence in the
classied dierently, probably as
price. A PH120 only cable will be
a 30 minute survival time as the
water spray makes that much dif-
ference to the re survivability of
cheaper than a 120 minute cable
or a cable that meets and is certi- Should you
the cable under test.
ed by BASEC & LPCB to BS8434-
2:2008. We only get what we pay have any
for and anything that is too good
The re test would be BSEN50200
+ Annex E (Flame/Shock/Water to be true has to have a catch questions
Spray) a 30 minute duration test somewhere.
dened by Annex E.
Price should not be the driver for
Prysmian
120 minutes, for the purposes of
IS3218, refers to a re test method
the selection Fire Performance
Cables (FP), the Codes of Practice technical help
BS8434-2:2008. This re test has
ame, shock and water spray and
have been written to correctly
select the cable taking the emo- line can be
tion of price out of the selection
it is this all important inclusion of
water spray that is the dierence process. contacted for
between PH120 and 120 minutes.

Wherever PH prexes the time


I do not know where the term
PH comes from; I do know it has
guidance.
then the re test has no water created confusion over the correct
spray. selection of life safety cables for
re alarm and emergency lighting
systems in the Irish market.

Martyn Corbishley is Business Development Manager, Prysmian Cables

ELECTRIC.IE The Magazine & Website for the Irish Electrical Industry 9