Professional Documents
Culture Documents
GenLeap
DC Generator Power System
CONTROLLER PRODUCT MANUAL
Confidential: This document contains confidential information proprietary to Leap Power. If you are not the
intended recipient, you are hereby notified that any dissemination, copying or distribution of this document, or the
taking of any action in reliance on the contents of this communication, is strictly prohibited. 2009 Leap Power,
LLC. All rights reserved.
1 of 49 CONFIDENTIAL
2009 Leap Power, LLC
Date 10/28/11 This document contains proprietary information.
All rights reserved.
Saved9/5/2014
888 S. Grenville Ave, Suite 302,
Richardson, Tx 7081, USA
+1-469-757-1787 (T).
sales@leap-power.com
GEN000231D www-leap-power.com.
2 of 49 CONFIDENTIAL
Saved9/5/2014
888 S. Grenville Ave, Suite 302,
Richardson, Tx 7081, USA
+1-469-757-1787 (T).
sales@leap-power.com
GEN000231D www-leap-power.com.
Table of Contents
1.1 Introduction ............................................................................................................................................ 5
1.2 Getting Started ....................................................................................................................................... 5
1.2.1 Installation ........................................................................................................................... 5
1.2.1.1 System Network Setup .......................................................................................................... 5
1.2.2 First Startup .......................................................................................................................... 7
1.2.3 Logging In ............................................................................................................................ 7
1.2.4 Connecting to eConLeap controller ............................................................................. 9
1.2.5 Menu (left side bar) ............................................................................................................ 9
1.2.6 Access levels....................................................................................................................... 10
1.3 System Operating Modes & Control Methods ..................................................................................... 10
1.3.1 Standby Power Mode ....................................................................................................... 10
1.3.1.1 Voltage control method...................................................................................................... 11
1.3.1.2 Timer control method ........................................................................................................ 11
1.3.2 Primary Power Mode (Off-Grid).................................................................................... 11
1.3.3 Battery Extension Mode ................................................................................................... 13
1.3.4 Manual Mode:.................................................................................................................... 13
1.3.5 Redundant Operation with dual generator sets ............................................................... 13
1.4 System Setup & Configuration............................................................................................................. 14
1.4.1 Setup .................................................................................................................................... 14
1.4.2 Configuration..................................................................................................................... 25
1.4.3 Operations .......................................................................................................................... 28
1.5 Monitoring & Control .......................................................................................................................... 29
1.5.1 Alarms ................................................................................................................................. 29
1.5.2 Logs ...................................................................................................................................... 31
1.5.3 Status ................................................................................................................................... 32
1.5.4 Inventory ............................................................................................................................ 33
1.5.5 Debugging .......................................................................................................................... 34
1.6 Software Upgrade ................................................................................................................................. 36
1.7 Manual Connections & Controls.......................................................................................................... 37
1.7.1 Ebox Control Panel & Manual Switches ...................................................................... 37
3 of 49 CONFIDENTIAL
Saved9/5/2014
888 S. Grenville Ave, Suite 302,
Richardson, Tx 7081, USA
+1-469-757-1787 (T).
sales@leap-power.com
GEN000231D www-leap-power.com.
4 of 49 CONFIDENTIAL
Saved9/5/2014
888 S. Grenville Ave, Suite 302,
Richardson, Tx 7081, USA
+1-469-757-1787 (T).
sales@leap-power.com
GEN000231D www-leap-power.com.
1.1 Introduction
This manual provides details of controller setup, configuration, monitoring and operation.
Customer may access GenLeap via ethernet interface using eConleap Mini controller or via
LCD touch screen display. Other optional interfaces like RS232, SNMP, dry contacts, wireless
access and mod bus interface are also available with GenLeap . Please reference the
GenLeap product manual for your configuration and associated functions and features.
5 of 49 CONFIDENTIAL
Saved9/5/2014
888 S. Grenville Ave, Suite 302,
Richardson, Tx 7081, USA
+1-469-757-1787 (T).
sales@leap-power.com
GEN000231D www-leap-power.com.
The system requirements depend on the browser that will be used to access the GenLeap
system.
6 of 49 CONFIDENTIAL
Saved9/5/2014
888 S. Grenville Ave, Suite 302,
Richardson, Tx 7081, USA
+1-469-757-1787 (T).
sales@leap-power.com
GEN000231D www-leap-power.com.
Setting Value
Baud 57600 baud
Flow Disable
Parity None
Data Bits 8-bit
Stop Bits 1
Timeout 50ms
1.2.3 Logging In
On startup, it is necessary to log in for security, tracking and data protection. Three access levels
are available for security administration:
Check the Auto Login option if you desire the settings to be saved for next time. User login
settings can be change later by logging out on exit
7 of 49 CONFIDENTIAL
Saved9/5/2014
888 S. Grenville Ave, Suite 302,
Richardson, Tx 7081, USA
+1-469-757-1787 (T).
sales@leap-power.com
GEN000231D www-leap-power.com.
Figure 2- Login
8 of 49 CONFIDENTIAL
Saved9/5/2014
888 S. Grenville Ave, Suite 302,
Richardson, Tx 7081, USA
+1-469-757-1787 (T).
sales@leap-power.com
GEN000231D www-leap-power.com.
Some customers may need to setup a RS-232 port to access the controller for higher
configuration and troubleshooting needs. Many factory default settings are accessible through
RS232 port and it's GUI application. Please reference GenLeap GUI application programming
and user manual for details.
Status: Status of key variables are shown on the status page. Status of system and each module
is shown under the horizontal bar menu.
Operation: System operations like start/stop and battery tests are available under Generator or
Battery operations menu.
Inventory: A static inventory allowing tracking of the site modules and capacities is available
under the inventory menu.
Setup: A system setup can be accessed from any module (horizontal bar) menu. The system
setup allows configuration of the mode of operation and battery charging method. Customer
can setup site information from this setup menu.
Logs: Alarm, Data and Event logs can be downloaded. Maximum storage capacity 4G is
available.
Dashboard: Dashboard, shown on the right side bar, provides a high level summary of the
system's operating parameters. The dash board can be placed anywhere on the computer
without having the full web pages turned on.
9 of 49 CONFIDENTIAL
Saved9/5/2014
888 S. Grenville Ave, Suite 302,
Richardson, Tx 7081, USA
+1-469-757-1787 (T).
sales@leap-power.com
GEN000231D www-leap-power.com.
Customer may setup different operating modes based on the configurations purchased for on-
grid or off-grid systems. Customer can also select the battery charging modes (or generator
transition modes) to provide a seamless transition between multiple power sources.
Information such as site ID and locations may be assigned to each site by the administrator.
GenLeap system can be deployed in the following modes of operation:
10 of 49 CONFIDENTIAL
Saved9/5/2014
888 S. Grenville Ave, Suite 302,
Richardson, Tx 7081, USA
+1-469-757-1787 (T).
sales@leap-power.com
GEN000231D www-leap-power.com.
In the standby mode, GenLeap and batteries must be exercised regularly when there are no
AC outages for an extended period (>30 days) to keep the DC Generator cranking and fuel
supply checked. The system provides a timer function to enable this maintenance feature
automatically. A factory default 30 days exercise function and battery test is set in the system
for all Standby systems.
11 of 49 CONFIDENTIAL
Saved9/5/2014
888 S. Grenville Ave, Suite 302,
Richardson, Tx 7081, USA
+1-469-757-1787 (T).
sales@leap-power.com
GEN000231D www-leap-power.com.
The Generator starts based on a pre set voltage threshold. The DC Generator provides an
extended backup subject to the availability of the fuel. A typical setting involves battery
discharge at 52Vdc and DC Generator start at 47Vdc.
The reserve batteries will be charged to the programmed stop charge voltage (default 52Vdc)
and discharged to the stop discharge voltage (default 47Vdc) during the voltage mode cycling.
Simultaneously, the DC Generator will start at battery stop discharge point (default 47Vdc) and
provide load and/or charging power up to the DC Generator stop or battery stop charge
voltage (default 52Vdc). GenLeap Voltage Mode operations allows 3 levels of Generator Start
and Two levels of Generator Stop conditions to maximize the system efficiency and utilization.
For example, if the system load is very small, customer may elect to deviate from the normal
CDC cycle and continue to discharge the batteries. On the other hand, if the load has suddenly
increased and additional power is required, customer may bring the generator on line before it
reaches the start threshold.
In the event of a complete failure of batteries, the DC Generator will continue to operate until
the fuel supply is exhausted. Similarly, in the event of DC Generator failure (or no gas supply),
the batteries will be discharged to Low Voltage Battery Disconnect (LVBD) set point. Normally,
the battery cut off voltage is set at 43 Vdc.
In the voltage control method, the capacity of the battery bank and the rate of discharge
installed by the customer determines the depth of discharge and the duration that batteries will
provide backup. Other factors like temperature and load variation will impact the duration and
the depth of discharge of the battery backup.
-54V
Battery
Discharge
-52V
-48V Battery
GenLeap ON Charge
12 of 49 CONFIDENTIAL
Saved9/5/2014
888 S. Grenville Ave, Suite 302,
Richardson, Tx 7081, USA
+1-469-757-1787 (T).
sales@leap-power.com
GEN000231D www-leap-power.com.
Time control method allows customers to decide how many hours each power/reserve source
should be operational. The total 24 hours operation can be divided between DC Generator,
batteries and an external power source like Solar (SunLeap). Timer mode allows customer to
adapt to its environment. A schedule such as charging of batteries at night under lower
temperature improves the battery life. While discharging them during day under higher
temperatures could provide higher capacity.
Timer mode also provides extensive scheduling capability with the Enhanced eConLeap
controller option. The scheduling capability permits the customer to select a specific time of the
day or calendar to start/stop the DC Generator operation. This capability allows operators to
schedule GenLeap maintenance exercise (test) at non peak hours on a specific day or allow
the shaving of peak billing hours when primary power source may be more expensive to
operate.
13 of 49 CONFIDENTIAL
Saved9/5/2014
888 S. Grenville Ave, Suite 302,
Richardson, Tx 7081, USA
+1-469-757-1787 (T).
sales@leap-power.com
GEN000231D www-leap-power.com.
1.4.1 Setup
Setup Menu shown in Figure 4 & 5 allows selection of operating mode and charger control
method. GenLeap systems can be configured as a standalone generator for non charging
applications or used as a complete DC power plant for battery charging (telecom) applications.
The customer must choose between charging vs non-charging application at the time of the
order to allow proper system wiring and calibration. A battery charger plant cannot be operated
without 48Vdc main batteries, LVBD, distribution, shunts and other controls.
Setup menu allows administrator to setup GenLeap in fully programmed modes like Primary
Auto or Standby Modes. Generator & battery charge discharge cycles can be controlled with
voltage methods or timer control methods. Similarly, two generator cycle times can be defined
by selecting the period each generator will operate using a timer control method or voltage
control method.
Voltage
Control
Primary
Auto
Timer
Control
Standby
Power
Battery
Extension
a. An administration level access is required to operate the system in Manual RUN Mode.
b. When changing the operation mode or setup configuration, following steps 1.4.1.1 to 1.4.1.4
must be followed. Please note that during change of Operation Mode or Restart (Reset)
14 of 49 CONFIDENTIAL
Saved9/5/2014
888 S. Grenville Ave, Suite 302,
Richardson, Tx 7081, USA
+1-469-757-1787 (T).
sales@leap-power.com
GEN000231D www-leap-power.com.
Controller command, eConLeap controller will go through a self reboot. During the reboot,
customer connection will be lost until the reboot is complete. You may need to reload the web
page to return to the web GUI. The reboot process takes approximately one minute.
c. Dashboard provides the current mode of operation, status of batteries, and status of generator
cycle.
d. All alarms must be cleared prior to starting the system. The system will only start if the
alarms have been cleared.
e. If a communication failure occurs during setup, an invalid setup or configuration alarm will
be raised. It is recommended to resubmit the configuration and wait for confirmation on the
dash board.
When executing the Primary AUTO Mode setup utilizing voltage control method in the above
screen (Figure 4), the following configuration details are required (Figure 5). In case customer
skips the following voltage method configuration setup, the default settings (recommended) in
15 of 49 CONFIDENTIAL
Saved9/5/2014
888 S. Grenville Ave, Suite 302,
Richardson, Tx 7081, USA
+1-469-757-1787 (T).
sales@leap-power.com
GEN000231D www-leap-power.com.
the example below will be activated. The customer must calculate the battery capacity in
accordance with the intended depth of discharge and operating hours to ensure that the cycles
resemble the plan charge discharge time period during voltage mode operation.
16 of 49 CONFIDENTIAL
Saved9/5/2014
888 S. Grenville Ave, Suite 302,
Richardson, Tx 7081, USA
+1-469-757-1787 (T).
sales@leap-power.com
GEN000231D www-leap-power.com.
V1= 49 I2= 40 60
V2= 47 I3= 0 60
V0= 54 I1= -6 60
V1= 53 I2= -3 60
20 20
17 of 49 CONFIDENTIAL
Saved9/5/2014
888 S. Grenville Ave, Suite 302,
Richardson, Tx 7081, USA
+1-469-757-1787 (T).
sales@leap-power.com
GEN000231D www-leap-power.com.
Three different voltage mode settings are used for starting the generator.
Start Generator if battery Voltage & Current meet one of the three (0, 1, & 2) Conditions:
First Condition:
AND
Current0- If battery discharging current is above -99 Amps. A large negative number should be
used for current to make sure that the generator starts at this voltage regardless of the current.
AND
Delay for 60 Second to start after battery voltage reaches the threshold. Delay is used to
eliminate any transient or instantaneous change in the voltage or current.
OR
Second Condition:
AND
Current1- If battery discharging current is above 40 Amps. If below 40A load, the batteries will
continue to provide power.
AND
Delay for60 Second to start after battery voltage reaches the threshold OR
Third Condition:
AND
AND
Delay for 60 Second to start after battery voltage and current reaches the threshold
Note: Condition 3 will not be used for generator start since every time generator will start on
Condition 1.
18 of 49 CONFIDENTIAL
Saved9/5/2014
888 S. Grenville Ave, Suite 302,
Richardson, Tx 7081, USA
+1-469-757-1787 (T).
sales@leap-power.com
GEN000231D www-leap-power.com.
STOP Generator if battery Voltage & Current meet one of the two (1 & 2) Conditions:
First Condition:
AND
Current0- If battery charging current is above -6 Amps. If below -6A, the batteries will continue
to be charged. Charging current is always negative and a large negative number will always
stop the generator at 54Vdc
AND
Delay for 60 Second to start after battery voltage and current reaches the threshold
OR
Second Condition:
AND
Current1- If battery charging current is above -3 Amps. If below -10A, the batteries will
continue to be charged. Charging current is always negative.
AND
Delay for 60 Second to start after battery voltage and current reaches the threshold
Voltage mode configuration allows customers to program a timer for ON/OFF Delay.
ON Delay allows generator to stay OFF for configured time and OFF Delay allows it to stay ON
for the selected time before and after each cycle.
19 of 49 CONFIDENTIAL
Saved9/5/2014
888 S. Grenville Ave, Suite 302,
Richardson, Tx 7081, USA
+1-469-757-1787 (T).
sales@leap-power.com
GEN000231D www-leap-power.com.
Causes:
Start Condition 0: Battery module requests start 50 seconds after shutdown. This time will be
enforced every time since V should always be < 100 and current > -999 regardless of charge or
discharge.
Start Condition 1: Battery module requests start 1 second after V < 44. Effectively starting every
time voltage falls below 44 volts.
Stop Condition 0: Battery module requests shut off 1800 seconds after startup provided a
voltage > 40 volts.
Stop Condition 1: Battery module requests shut off 20 seconds after voltage >56 amps AND
current < 4 amps.
Enable Delay- ON delay: Start 600 seconds after battery module requests startup.
Enable Delay- OFF delay: Stop 6000 seconds after battery module requests stop.
Primary Voltage method will utilize battery voltage and current as the key parameters for its
operation. However, time delays allow the user to configure a hybrid configuration that allows
a charging method based on voltage within a time window. In case of dual redundant or
backup generators, a time window selection allows the user to decide how dual generators and
batteries should cycle. Following figure shows cycling between two generators using voltage
control method:
Cycle Time T
Customer selectable Generator A
cycle time
-54V
Battery
Discharge
-52V
GenLeap A ON
-48V
Battery
Charge
GenLeapB ON
20 of 49 CONFIDENTIAL
Saved9/5/2014
888 S. Grenville Ave, Suite 302,
Richardson, Tx 7081, USA
+1-469-757-1787 (T).
sales@leap-power.com
GEN000231D www-leap-power.com.
21 of 49 CONFIDENTIAL
Saved9/5/2014
888 S. Grenville Ave, Suite 302,
Richardson, Tx 7081, USA
+1-469-757-1787 (T).
sales@leap-power.com
GEN000231D www-leap-power.com.
22 of 49 CONFIDENTIAL
Saved9/5/2014
888 S. Grenville Ave, Suite 302,
Richardson, Tx 7081, USA
+1-469-757-1787 (T).
sales@leap-power.com
GEN000231D www-leap-power.com.
23 of 49 CONFIDENTIAL
Saved9/5/2014
888 S. Grenville Ave, Suite 302,
Richardson, Tx 7081, USA
+1-469-757-1787 (T).
sales@leap-power.com
GEN000231D www-leap-power.com.
24 of 49 CONFIDENTIAL
Saved9/5/2014
888 S. Grenville Ave, Suite 302,
Richardson, Tx 7081, USA
+1-469-757-1787 (T).
sales@leap-power.com
GEN000231D www-leap-power.com.
1.4.2 Configuration
Customer shall not change any Generator, Battery or Environment menu configurations unless
recommended by Leap Power's application engineer or qualified service technician. Any
changes in these thresholds can result in failure of the engine or generator safety stop. Customer
may select LVBD disconnect and reconnect settings based on their batteries selection. Please
note that the LVBD disconnect voltage and temperature thresholds are mutually exclusive but
both reconnect conditions must be met to reconnect the batteries. All maintenance items shall be
reset under Service thresholds by the customer to ensure service alarms work properly. Any
maintenance items like air filter change, oil change and fuel filter change should be logged by
resetting the counter. The tracking of service items allow system to generate service alarms on
time.
25 of 49 CONFIDENTIAL
Saved9/5/2014
888 S. Grenville Ave, Suite 302,
Richardson, Tx 7081, USA
+1-469-757-1787 (T).
sales@leap-power.com
GEN000231D www-leap-power.com.
26 of 49 CONFIDENTIAL
Saved9/5/2014
888 S. Grenville Ave, Suite 302,
Richardson, Tx 7081, USA
+1-469-757-1787 (T).
sales@leap-power.com
GEN000231D www-leap-power.com.
27 of 49 CONFIDENTIAL
Saved9/5/2014
888 S. Grenville Ave, Suite 302,
Richardson, Tx 7081, USA
+1-469-757-1787 (T).
sales@leap-power.com
GEN000231D www-leap-power.com.
1.4.3 Operations
Customer may test different voltage and current settings prior to changing their factory default
configuration. Generator operations (admin permission required) allows setting a new
generator target voltage, generator current, battery charge voltage, battery charging current
limit and discharge current limit. These values do not change customer configuration during
testing unless customer elects to permanently write to configuration file by electing "Persist". It
is always recommended to make a copy of the original configuration before overwriting your
configuration file.
Figure 8- Operations
28 of 49 CONFIDENTIAL
Saved9/5/2014
888 S. Grenville Ave, Suite 302,
Richardson, Tx 7081, USA
+1-469-757-1787 (T).
sales@leap-power.com
GEN000231D www-leap-power.com.
29 of 49 CONFIDENTIAL
Saved9/5/2014
888 S. Grenville Ave, Suite 302,
Richardson, Tx 7081, USA
+1-469-757-1787 (T).
sales@leap-power.com
GEN000231D www-leap-power.com.
30 of 49 CONFIDENTIAL
Saved9/5/2014
888 S. Grenville Ave, Suite 302,
Richardson, Tx 7081, USA
+1-469-757-1787 (T).
sales@leap-power.com
GEN000231D www-leap-power.com.
1.5.2 Logs
Logs provide downloading option for Event, Data and Alarm logs in a tab separated format. A
log file may be copied to excel or access file by copy and paste.
31 of 49 CONFIDENTIAL
Saved9/5/2014
888 S. Grenville Ave, Suite 302,
Richardson, Tx 7081, USA
+1-469-757-1787 (T).
sales@leap-power.com
GEN000231D www-leap-power.com.
1.5.3 Status
Figure 11- Status
32 of 49 CONFIDENTIAL
Saved9/5/2014
888 S. Grenville Ave, Suite 302,
Richardson, Tx 7081, USA
+1-469-757-1787 (T).
sales@leap-power.com
GEN000231D www-leap-power.com.
1.5.4 Inventory
Inventory items shall be completed during installation of GenLeap and other modules.
Inventory items shall be completed during installation of GenLeap and other modules.
33 of 49 CONFIDENTIAL
Saved9/5/2014
888 S. Grenville Ave, Suite 302,
Richardson, Tx 7081, USA
+1-469-757-1787 (T).
sales@leap-power.com
GEN000231D www-leap-power.com.
1.5.5 Debugging
GenLeap allows clearing of latching alarms through debug page. All non-latching alarms are
cleared at stop or once the alarm condition is cleared. However, due to safety concerns, latching
alarms require Administrator to follow an alarm clearing and power reboot process. Please note
that any unsaved configuration can be lost during the power down and reboot process. Please
save your configuration to the controller and your computer. Following faults can be reset and
cleared through debug/Generators/Alarm Reset page.
A bit value >3 indicates a warning and >7 sets a critical (latching) alarm for the following fault
conditions:
GenEngineEstop: An alarm "ECU Fault" indicates an engine fault. If a safety stop condition is
generated from Engine Control Unit (ECU), administrator must clear the engine safety stop
along with the system safety estop. Engine estop can be cleared by writing a value "0" on
Debug/Alarm-Reset page. All alarms initiating estop condition must be cleared before clearing
an eStop. A clear safety stop under Operation/Generator menu or engine control unit Reset
under Operation/Controller menu must be executed to clear the engine safety stop condition.
34 of 49 CONFIDENTIAL
Saved9/5/2014
888 S. Grenville Ave, Suite 302,
Richardson, Tx 7081, USA
+1-469-757-1787 (T).
sales@leap-power.com
GEN000231D www-leap-power.com.
GenOutFxInOutVolts & Current: This latching alarm indicates an incorrect alternator or battery
voltage or current. A battery voltage too high or too low may create this alarm. A tripped
breaker, wrong shunt or disconnected LVBD may cause the system to start and shut down.
GenOutFxFuelLvl: Indicates a problem with fuel inflow, fuel pump, stop solenoid and fuel filter
lever position.
In addition to the above latching alarms, ECU provides a list of alarms covered under system
main alarm "ECU Fault" under Debug/Generator menu. A value >7 on this page provides the
source of the ECU Fault.
35 of 49 CONFIDENTIAL
Saved9/5/2014
888 S. Grenville Ave, Suite 302,
Richardson, Tx 7081, USA
+1-469-757-1787 (T).
sales@leap-power.com
GEN000231D www-leap-power.com.
Please make sure that CAT5/6 LAN cable connection is properly secured.
1) Download a copy of the latest software to your PC. It will show extension release number
followed by extension .tar.
Our software update releases for the eConLeap Mini Controller follows the naming
convention of update_3.0.0.X, where X is a digit representing a specific version or release of the
software. For example, the latest software is update_3.0.0.23. The software update bundles are
located on our ftp server or may be requested by contacting technical support at info@leap-
power.com.
Make sure you can ping the Mini Controller to address 192.168.1.230. This can be simply done
by plugging your pc directly to the eConLeap router port 2 & 3 (not port 1).
3) FTP the release to the eConLeap Mini Controller or transfer the file to the /sdcard folder
for upgrading the eConLeapMini Controller..
The username/password will be plg/plg. Make sure that you transfer in binary mode.
For example, If your software is located on the c:\ drive.
Follow the instruction below:
cd c:\
ftp 192.168.1.230
C:\>ftp 192.168.1.230
Connected to 192.168.1.230.
220 FriendlyArm FTP server (Version 6.4/OpenBSD/Linux-ftpd-0.17) ready.
User (192.168.1.230:(none)): ***
Password:***
36 of 49 CONFIDENTIAL
Saved9/5/2014
888 S. Grenville Ave, Suite 302,
Richardson, Tx 7081, USA
+1-469-757-1787 (T).
sales@leap-power.com
GEN000231D www-leap-power.com.
Once the download of the new release is completed on the mini-controller and it's in the /sdcard folder,
install the software as follows;
a) Telnet to the Mini Controller. The username is root (password is not required).
telnet 192.168.1.230
b) cd /sdcard
c) /swupdate.ksh update_3.0.0.23.tar
5) Remove the current configuration. (just for update_3.0.0.23.tar release remove leapdb.xml).
a) cd /sdcard
b) rm leapdb.xml
NOTE: By removing leapdb.xml you are removing all configuration changes that you have made on the
system. You will have to re-configure the leapgen system.
SW1 switch provides Remote (Web) and ECU (RS232) modes of operation. The ECU mode
should be activated by trained technicians only. The system must be in Remote position when
the customer is ready to start or operate the system via Ethernet connection. The DHCP
connection on front of the Ebox should be always connected to the remote monitoring center
and should not be removed during system maintenance. A separate Ethernet connection is
available for local configuration and provisioning during installation.
SW2 switch allows the customer to select between the modes of remote and local operation of
the unit. The customer can select between RUN, AUTO and Remote positions. AUTO mode
37 of 49 CONFIDENTIAL
Saved9/5/2014
888 S. Grenville Ave, Suite 302,
Richardson, Tx 7081, USA
+1-469-757-1787 (T).
sales@leap-power.com
GEN000231D www-leap-power.com.
allows the customer to run the system in primary mode with voltage control method. See
section 1.4.1 and Figure 5 for more details. If SW2 is in Remote position, the system cannot be
operated in the manual local mode or via RS232 GUI.
WARRNING: System can start without notice if placed in RUN or AUTO positions via SW2.
Selecting RUN and AUTO mode allows the customer to disable Web interface and operate
through RS232 GUI or manual mode. RS232 GUI shall be mainly used by experienced
technicians or engineers for high level diagnosis and calibration.
It is always safe to switch the eBox ON/OFF Switch in OFF position, SW1 in estop position and
SW2 in Remote position when doing system installation or maintenance. During installation, it
is recommended that customer tests the system in manual RUN mode before working in AUTO
or Web mode.
38 of 49 CONFIDENTIAL
Saved9/5/2014
888 S. Grenville Ave, Suite 302,
Richardson, Tx 7081, USA
+1-469-757-1787 (T).
sales@leap-power.com
GEN000231D www-leap-power.com.
39 of 49 CONFIDENTIAL
Saved9/5/2014
888 S. Grenville Ave, Suite 302,
Richardson, Tx 7081, USA
+1-469-757-1787 (T).
sales@leap-power.com
GEN000231D www-leap-power.com.
Following wiring diagram is used with single or dual generator setup with Leap Power's
supplied distribution.
40 of 49 CONFIDENTIAL
Saved9/5/2014
888 S. Grenville Ave, Suite 302,
Richardson, Tx 7081, USA
+1-469-757-1787 (T).
sales@leap-power.com
GEN000231D www-leap-power.com.
In case the distribution was not a part of Leap's supplied system and the customer plans to use
the generator for battery charging, the following wiring must be connected with the
distribution. Please note that the battery shunt, battery low voltage disconnect (LVBD), battery
temperature sensor (RTD), and battery voltage sense leads MUST always be connected for
battery charger plant to be operational. Leap Power recommended parts are following:
1. LVBD: The DC contactor must be single pole double throw latching type with 24VDC coil
voltage. The LVBD shall be connected to two 24Vdc control wires (+ve & -ve) and two
communication wire (NC-1, NC-2) with the eBox P1 connector. The contactor rating shall be
according to the DC generator rated voltage and current.
2. Battery Current Shunt: A 50mv 100A to 300A shunt is recommended for 5KW to 10KW
Genleap models. A two wire battery current shunt connection to JCSB receptacle shall be
maintained all the time.
Recommended From: DC
TO: Front Panel of Ebox in GenLeap
Parts (10kw) Distribution
Shunt 200A/50 Ext Dist, Bat
1 JCSB-1
mV Shunt +Ve
Shunt 200A/50 Ext Dist, Bat
2 JCSB-2
mV Shunt -Ve
LVBD-NC-1,
3 P1-8
Distribution
LVBD-NC-2,
4 DC Contactor P1-7
Distribution
250A/24V-
Latching Type LVBD Coil +Ve,
5 P1-9
Distribution
LVBD Coil -Ve,
6 P1-10
Distribution
Battery Voltage
7 Main 48VDC P1-3
Sense +Ve
Battery Sense
Battery Voltage
8 Wiring P1-4
Sense -Ve
9 RS232- eBox RS-232 JC2- DB9 Serial Female
Front Panel
10 RS-232 JC1- DB9 Serial Female
System Output Generator Output Anderson output connector (gray) or two wires
11
48Vdc/200A +Ve & -Ve with lugs (supplied with GenLeap)
RTD, PT100
Main Battery
12 Temperature P1-5 & 6 (supplied with GenLeap)
Temp +Ve POST
Sensors
Ethernet Connected to RJ45 connection on the eBox
13 Cat5e Cable
Connection (supplied with GenLeap)
41 of 49 CONFIDENTIAL
Saved9/5/2014
888 S. Grenville Ave, Suite 302,
Richardson, Tx 7081, USA
+1-469-757-1787 (T).
sales@leap-power.com
GEN000231D www-leap-power.com.
All wiring to P1 connector with eBox is supplied with GenLeap. Customers are only required to
make the necassary connection with the DC distribution. All wire lengths are based on a standard 5 feet
distance between GenLeap eBox and DC distribution. Custom cables can be ordered from Leap
Power's factory.
42 of 49 CONFIDENTIAL
Saved9/5/2014
888 S. Grenville Ave, Suite 302,
Richardson, Tx 7081, USA
+1-469-757-1787 (T).
sales@leap-power.com
GEN000231D www-leap-power.com.
The system requires either the AUTO or RUN wired inputs to be activated before the engine
will be allowed to run. SWI switch must be in start position and SW2 switch should be RUN or
AUTO mode. The machine will not start or continue running if alarms are configured or set to
inhibit running. The system will run but will not enter charging mode ( runs at slow speed) if
alarms are set that are configured to inhibit charging. Please see the section 1.7.3 for how to
view the VirOutFns for fault status.
Auto Mode:
If the Auto input is activated, the generator will be allowed to start and control voltage. The
engine will automatically start when batteries are properly connected and battery voltage is
below the start threshold for enough time. See calibration items in the area of Strt Threshold
Voltage 0 in section 1.4.1. There are voltage & current thresholds below which timers start
counting time below this voltage with a minimum of this current present. If the counter
exceeds the start time, the system is commanded to start. There are similar settings for auto
shutdown. Please reference section 1.4.1 for further details.
Run Mode:
If the SWI is in start position and SW2 is in RUN position, the system will be activated for RUN
mode via RS-232 Run Command based on time selected by the operator.
User commands it to run for a number of minutes ( 1 to 254) or forever ( setting to 255
minutes) using the Remote Run Time variable. The RS-232 must change the number
from 255 to another desired run time OR zero once it is desired to exit run forever
mode.
The RS-232 interface will be allowed to command the machine to stop (or inhibit
starting) for a number of minutes. This command is in either AUTO or RUN mode. If
the Remote Stop Time variable is set to a nonzero number, the engine will be
commanded to stop for this number of minutes. If the number is 255, the timer will not
count down minutes. If the timer reaches zero and something else is commanding it to
run, it will initiate the start sequence. The RS-232 stop command will override any run
command. The system must be set to zero "Remote STOP Time" to allow it to operate in
AUTO mode or WEB mode. A value of 255 will put engine in permanent STOP mode.
43 of 49 CONFIDENTIAL
Saved9/5/2014
888 S. Grenville Ave, Suite 302,
Richardson, Tx 7081, USA
+1-469-757-1787 (T).
sales@leap-power.com
GEN000231D www-leap-power.com.
44 of 49 CONFIDENTIAL
Saved9/5/2014
888 S. Grenville Ave, Suite 302,
Richardson, Tx 7081, USA
+1-469-757-1787 (T).
sales@leap-power.com
GEN000231D www-leap-power.com.
RS232 GUI provides detailed overview of variables inhibiting engine operation for safety
reasons or limiting its performance. The system faults with their sum of bits are shown in
Figure 15 below under Run Time/VirOutFns.
45 of 49 CONFIDENTIAL
Saved9/5/2014
888 S. Grenville Ave, Suite 302,
Richardson, Tx 7081, USA
+1-469-757-1787 (T).
sales@leap-power.com
GEN000231D www-leap-power.com.
The value (7, 15, ...) is simply the sum of the item's bits. A value of 7 or greater would limit the
generator RUN or AUTO and put the engine under emergency stop (estop) condition. Each
item has its own status bits and can be configured to set any combination of its bits. It can also
be configured to clear any combination of its bits when the item is deactivated. One can choose
what level of warning or alarm each input can set and clear.
46 of 49 CONFIDENTIAL
Saved9/5/2014
888 S. Grenville Ave, Suite 302,
Richardson, Tx 7081, USA
+1-469-757-1787 (T).
sales@leap-power.com
GEN000231D www-leap-power.com.
Saved9/5/2014
888 S. Grenville Ave, Suite 302,
Richardson, Tx 7081, USA
+1-469-757-1787 (T).
sales@leap-power.com
GEN000231D www-leap-power.com.
16. Review section under Alarms. Follow trouble shooting guide to clear all the alarms. Reset
the system thru controller reboot or reset. A complete 12V power down may be required.
17. Position SW1 and SW2 switch in Remote position. Follow system configuration menu.
18. Check voltage mode configuration in section 1.4.1 & Figure 4. Apply load to the system and
start discharging batteries. If batteries below threshold, the generator will start automatically.
During initial test, you may want to use small batteries to keep the charge/discharge cycles
short.
19. Make sure you save your configurations on your computer and in the controller.
DC Distribution/Power Distribution
ECU Harness Assembly
Generator A & B Output Connection
Regulators & Output Filter (C5)
Ebox Assembly JT (P) JT (S) DB9 Female
JC1
Generator B
ECU
PD-2BP
Generator B
Crank Battery
PD2-BS
J1
(18 Pos) JSCB (P) JSCB (S)
48V Bat Shunt
J1P
J1S
48V BAT Sense
J8P J8S
STC-1B
J1EP J1ES
Coolant Temp
Sensor
J1S
ON/ J1P
SW1 SW2
OFF
J2 (30 Pos)
Generator A
Generator A
Mini STC-106
PD2-AP
PD2-AS
J3S J3P
STC-1 Stop Solenoid Stop Solenoid
P1
Relay 2 J2S
Fuel Pump
Relay 4 STARTER
48 of 49 CONFIDENTIAL
Saved9/5/2014
888 S. Grenville Ave, Suite 302,
Richardson, Tx 7081, USA
+1-469-757-1787 (T).
sales@leap-power.com
GEN000231D www-leap-power.com.
49 of 49 CONFIDENTIAL
Saved9/5/2014