Professional Documents
Culture Documents
$%%
07-05-2002
MCB tripping characteristics
120
60
40 1 I 40 2 I
20 Basics:
10
6
minutes
2
General Time / current relation
1
40
1. Thermal tripping
20
10
seconds
6 2. Electromagnetic tripping
4
0,6
0,4 - Thermal tripping current rsp.
I
Tripping time
$%%
MCB tripping characteristics
120
60
40
Basics:
20
10
6 Magnetic tripping:
minutes
4
AC, 100 Hz = factor 1.1
2
1
AC, 200 Hz = factor 1.2
40
AC, 400 Hz = factor 1.5
20
DC = factor 1.5
seconds
10
6 Thermal tripping is not dependent
4
2 on frequency
ABB STOTZ KONTAKT DESTO/X2 RH - 3
1
0,6
0,4
DC-current increases the
0,2 magnetic tripping values
Tripping time
0,1
0,06
AC by factor 1,5
0,04
DC
0,02
$%%
0,01
1 1,5 2 3 4 5 6 8 10 15 20 30
Multiple of rated current
MCB tripping characteristics
120
60
40 1
40
I I
40 2
"B"-characteristic
20
10
acc. EN 60898 rsp. IEC 898: standard for
6 miniature circuit breakers to be used in
minutes
4
residential or similar applications
2
1
40 I
40 1 Thermal non tripping: 1,13 x In
20
I
40 2 Thermal tripping: 1,45 x In
seconds
10
6
4
I3 Magnetic non tripping: 3 x In
2
I4 Magnetic tripping: 5 x In
ABB STOTZ KONTAKT DESTO/X2 RH - 4
1
0,6
0,4
Applications:
B
Tripping time
0,2
low duty applications without
0,1
starting or inrush currents
0,06
0,04
0,02
I3 I4
$%%
0,01
1 1,5 2 3 4 5 6 8 10 15 20 30
Multiple of rated current
MCB tripping characteristics
120
60
40
C"-characteristic
20
2
residential or similar applications
1
40 I
40 1 Thermal non tripping: 1,13 x In
20
I
40 2 Thermal tripping: 1,45 x In
seconds
10
6
4 I3 Magnetic non tripping: 5 x In
2
I4 Magnetic tripping: 10 x In
ABB STOTZ KONTAKT DESTO/X2 RH - 5
1
0,6
0,4
Applications:
C
Tripping time
0,2
low duty applications with medium
0,1
starting or inrush currents and low
0,06
0,04 loop impendance
0,02
$%%
0,01
1 1,5 2 3 4 5 6 8 10 15 20 30
Multiple of rated current
MCB tripping characteristics
120
60
40
D"-characteristic
20
2
residential or similar applications
1
40 I
40 1 Thermal non tripping: 1,13 x In
20
10
I
40 2 Thermal tripping: 1,45 x In
seconds
6
4 I3 Magnetic non tripping: 10 x In
2
I4 Magnetic tripping: 20 x In
ABB STOTZ KONTAKT DESTO/X2 RH - 6
1
0,6
0,4
Applications:
D
Tripping time
0,2
high duty applications with very high
0,1
starting or inrush currents but low
0,06
0,04 loop impendance
0,02
0,01
$%%
1 1,5 2 3 4 5 6 8 10 15 20 30
60
40
"B,C;D"-characteristics
20
2
residential or similar applications.
1
40
10
6 average applications
4
Restricted thermal protection,
2
allowing I3 : 1,45 x In
ABB STOTZ KONTAKT DESTO/X2 RH - 7
1
Extreme high I4 of D characteristic
0,6
0,4 may lead to delayed tripping time,
BC D
Tripping time
$%%
0,01
1 1,5 2 3 4 5 6 8 10 15 20 30
Multiple of rated current
MCB tripping characteristics
120
60
40
STOTZ
20
10
ZKcharacteristics
6
minutes
4
acc. EN 60947-2 rsp. IEC 947-2:
2
standard for industrial switchgear
1
40
20
The
tailormade solution for
seconds
10
6
4 commercial and industrial
2
applications
ABB STOTZ KONTAKT DESTO/X2 RH - 8
1
0,6
0,4 Z K Compared to tripping characteristics B,C, D
BC D the STOTZ characteristics K and Z
Tripping time
0,2
offer a higher degree of protection.
0,1
0,06 This means a higher degree of safety
0,04
in both, planning and operation
0,02
$%%
0,01
1 1,5 2 3 4 5 6 8 10 15 20 30
60
40
Z"-characteristic
20
10
6
4 I4 Magnetic tripping: 3 x In
2
A sensitive characteristic to
ABB STOTZ KONTAKT DESTO/X2 RH - 9
1
protect highly sensitive equipment such as:
0,6
0,4 Z
BC D
Tripping time
0,2
0,14mm2 cable sets
0,1 applications with limit switches
0,06 reed contacts in burglar alarm systems
0,04
sensor technology
0,02 actuators in bus systems
printed boards with its semiconductors
$%%
0,01
1 1,5 2 3 4 5 6 8 10 15 20 30
60
40
K"-characteristic
20
acc. EN 60947-2 rsp. IEC 947-2:
10 standard for industrial switchgear
6
40 I1 Thermal non tripping: 1,05 x In
minutes
2
I
40 2 Thermal tripping: 1,2 x In
1
40
I3 Magnetic non tripping S270: 8 x In
20
I4 Magnetic tripping S270: 12 x In
10
seconds
6 I3
4
Magnetic non tripping S280: 10 x In
2
I4 Magnetic tripping S280: 14 x In
ABB STOTZ KONTAKT DESTO/X2 RH - 10
BC D
Tripping time
0,2
Motors, fan sets
0,1 Power supply units: i.e 24V DC supply for intelligent
0,06 building automation systems
0,04 Charging sets; i.e for electrical forklift trucks
0,02 Extra low voltage lamps, high performance tools,
electronic ballasts
0,01 Welding- and control power transformer
$%%
1 1,5 2 3 4 5 6 8 10 15 20 30
Multiple of rated current
ABB STOTZ KONTAKT DESTO/X2 RH - 11 MCB tripping characteristics
$%%