You are on page 1of 1

"CB OPEN" NC

CONTACT
+

AUTO-MANUAL SELECTOR SWITCH


AC

AUTO MAN AUTO MAN


220VAC

"CB OPEN" PUSH


DC BUTTON SW.

24VDC
TO TRIP
CIRCUIT
"CB CLOSE" PUSH
TR BUTTON SW.
TIME DELAY

PILOT LIGHT
PILOT LIGHT X
X AC "ON"
AC "OFF"
TO CLOSING
CIRCUIT

BILL OF MATERIALS: SEQUENCE OF OPERATION:

1. 1-Pc., AC MCB, 220VAC, 6A 1. During AC Outage, Relay "DC" will be energized through AC relay NC contact giving signal to operate the RMU Trip
2. 1-Pc. DC MCB, 24VAC, 6A Circuit through DC relay NO contact.
3. 1-Pc., AC Finder Relay, 220VAC, 2NC+2NO 2. During AC restoration, Relay "AC" and Timer "TR" will be energized and DC relay will be deenergized. After a
4. 1-Pc., DC Finder Relay, 24VDC, 2NC+2NO predetermimed time (e.g. 120 sec.), TR contacts will activate causing to operate RMU Closing circuit.
5. 1-Pc., Timer 0-300 sec., 220VAC, 2NC+2NC
6. 1-Pc., Selector Switch, 2-Auto/2-Manual Contacts
7. 1-Pc., Pilot Lamp-Green, 220VAC
8. 1-Pc., Pilot Lamp-Red, 24VDC
9. 1-Roll, 1.5mm2-Gray, Single-core Control Cable

You might also like