ACI 423.

3R-96

Recommendations for Concrete Members


Prestressed with Unbonded Tendons
Reported by ACI Committee 423

Charles W. Dolan Henry Cronin, Jr. Kenneth B. Bondy


Chairman Secretary Subcommittee Chairman

Robert N. Bruce Mohammad Iqba Denis C. Pu


C. Dale Buckner Francis J. Jacques Julio Ramirez
Ned H. Burns Daniel P. Jenny Ken B. Rear
Gr egory P. Chacos Paul Johal Bruce Russell
Jack Christiansen Susan Lane David Sanders
Todd Christopherson Ward N. Marianos Thomas C. Schacffer
St even Close Leslie Martin Morris Schupack
Thomas E. Cousins Alan H. Mattock Kenneth Shushkewich
Apostolos Fifitis Gerrard McGuire Patrick J. Sullivan
Mark W. Fantozzi Mark Moore Luc R. Taerwe
Martin J. Fradua Antoine Naaman Carl H. Walker
Catherine W. French Kenneth Napior Jim Zhao
Clifford Freyermuth Thomas E. Nehil Paul Zia
William L. Gamble Pani Mrutyunjaya
Hans Ganz H. Kent Preston

This report is resented as a guide for the design of f l e xural structural mem- tensioning; prestressed concrete; prestressing; prestressing steels; shear
bers in buildings with unbonded tendons. Suggestions are presented for properties; stresses; structural analysis; structural design; unbonded pre-
needed revisions and additions to the ACI 318 Building Code regard his stressing
subject. Consideration is given to determination of fire endurancedesign
for seismic forces, and catastrophic loadings, in addition to design for rav- CONTENTS
ity and lateral loads. Recommendations are presented concerning details
and properties of tendons, protection against crosion, and constuction
Chapter 1Introduction, p. 423.3R-2
p rocedures.
1.1General
Keywords: anchorage (structural); beams (supports); bond (concrete to 1.2Objective
reinforcement); concrete construction; concrete slabs; cover; 1.3Scope
cracking (fracturing); earthquake-resistant structures; fire resistance; at 1.4Notations and definitions
concrete plates; at concrete slabs; joints (junctions); loads (forces); post-
Chapter 2Design consideration,, p. 423.3R-2
ACI Committee Reports, Guides, Standard Practices, Design 2.1General
Handbooks, and Commentaries are intended for guidance in
2.2Continuous members
planning, designing, executing, and inspecting construction.
This document is intended for the use of individuals who are 2.3Corrosion protection
competent to evaluate the significance and limitations of its con- 2.4Fire resistance
tent and recommendations and who will accept responsibility for 2.5Earthquake loading
the application of the material it contains. The American Con-
crete Institute disclaims any and all responsibility for the appli- Chapter 3Design
, , p. 423.3R-6
cation of the stated principles. The Institute shall not be liable for 3.1General
any loss or damage arising therefrom.
Reference to this document shall not be made in contract docu-
ments. If items found in this document are desired by the Archi- ACI 4823.3R-96 supersedes ACI 423.3R-89 and became effect ive February 1, 1996.
Cop yright 1996, American Concrete Institute.
tect/Engineer to be a part of the contract documents, they shall All rights reserved including rights of reproduction and use in any form or by any
means, including the making of copies by any photo process, or by electronic or
be restated in mandatory language for incorporation by the Ar- mechanical device, printed, written, or oral, or recording for sound or visual reproduction
chitect/Engineer. or for use in any knowledge or retrieval system or device, unless permission in writing
is obtained from the copyright proprietors.

423.3R-1
423.3R-2 ACI COMMITTEE REPORT

3.2One-way systems and information of professional engineers who must add


3.3Two-way systems their engineering judgment to applications of the recommen-
3.4Tendon stress at factored load dations.
3.5Prestress losses
3.6Average prestress 1.3Scope
3.7Supporting walls and columns 1.3.1 The recommendations are intended to cover special
3.8Serviceability requirements considerations pertinent to design with unbonded tendons.
3.9Design strength Considered in this report are the design of beams, girders,
3.10Anchorage zone reinforcement and slabs, continuous members, and details and properties of
tendons and anchors and their protection from corrosion dur-
Chapter 4Materials, p. 423.3R-14 ing construction and throughout the life of the structure.
4.1Tendons 1.3. 2 The recommendations are not intended for unbonded
4.2Protection materials construction stages of elements utilizing bonded tendons,
4.3Protection of anchorage zones members subject to direct tension such as tiebacks, cable
4.4Concrete cover stays, arch ties, or circumferential tendons for pressure ves-
sels, or ground-supported post-tensioned slabs for light resi-
Chapter 5Construction, p. 423.3R-15 dential construction for which independent design methods
5.1Construction joints have been developed.1
5.2Closure strips
5.3Placement of tendons 1.4Notations and definitions
5.4Concrete placement and curing Symbols have the meaning given in ACI 116R or ACI 318
5.5Stressing operations or are defined in the text. Definitions of terms as used in this
5.6Form removal and reshoring report follow.
5.7Welding and burning Anchorage--- In post-tensioning, a device used to anchor
the prestressing steel to the concrete member.
Chapter 6References, p. 423.3R-17 Bonded tendons--- Tendons that are bonded to the concrete
6.1Specified and recommended references through grouting or other approved means, and therefore are
6.2Cited references not free to move relative to the concrete.
Coating--- Material used to protect against corrosion and
CHAPTER 1INTRODUCTION lubricate the prestressing steel.
CouplerDevice for connecting reinforcing bars or pre-
1.1General stressing steel end to end.
This report is intended to update the previous ACI-ASCE DuctHole formed in the concrete for the insertion of
Committee 423 report entitled Recommendations for Con- prestressing steel that is to be post-tensioned.
crete Members Prestressed with Unbonded Tendons, (ACI Prestressing steelHigh-strength steel used to prestress
423.3R-89) published in 1989. In the interval since the pub- concrete, commonly seven-wire strands, single wires, bars,
lication of that report and the three previous reports that it re- rods, or groups of wires or strands.
placed, many of its recommendations have been incor- Sheath---An enclosure in which the prestressing steel is
porated into the ACI Building Code (ACI-318). As a result, placed to prevent bonding during concrete placement and, in
design with unbonded tendons is covered in ACI 318-95 in the case of tendons that are to remain unbonded, to protect
nearly the same degree of completeness as is design with the corrosion-inhibiting coating on the prestressing steel.
bonded tendons. Tendo nThe complete assembly used to impart pre-
Nonetheless, these recommendations have been prepared stressing forces to the concrete, consisting of anchorages and
to provide an up-to-date and comprehensive guide for de- prestressing steel with sheathing when required.
sign, materials, and construction for concrete members pre- Unbonded tendonsTendons in which the prestressing
stressed with unbonded tendons. Suggested revisions and steel is permanently free to move (between anchors) relative
additions to the ACI Building Code are also included in this to the concrete to which they are applying prestressing forc-
report. es.

1.2Objective CHAPTER 2DESIGN CONSIDERATIONS


1.2.1 The objective of this report is to present recommen-
dations for materials, design, and construction for concrete 2.1General
structures prestressed with unbonded tendons that are com- Strength and serviceability limitations (including stresses)
mensurate with the safety and serviceability requirements of should conform to the provisions of ACI 318, but some rec-
the ACI Building Code (ACI-318). ommendations are offered that differ from the contents of the
1.2.2 This report is a guide, not a building code or specifi- ACI Building Code or relate to areas not covered by the
cation. The recommendations are presented for the guidance building code.
CONCRETE MEMBERS PRESTRESSED WITH UNBONDED TENDONS 423.3R-3

2.2Continuous members Table 2.1Suggested concrete thickness requirements


2.2.1 For slabs or beams continuous over two or more for various fire endurances10
spans with one-way prestressing only, a loading condition or
Slab thickness (mm)
fire exposure that causes failure of all the tendons in one
Aggregate
span will lead to a loss of prestress and much of the load-car- type 1 hr 11/2 hr 2 hr 3 hr 4 hr
rying capacity in the other spans. Consideration should be Carbonate 80 105 115 145 165
given to the consequence of such a catastrophic failure in any Siliceous 90 105 125 155 175
specific span to the overall stability of the structural system. Lightweight 65 80 95 115 130
ACI 318 has responded to this concern, as well as to other
considerations such as crack width limitation, in Section
18.9.2. Section 18.9.2 specifies minimum bonded reinforce-
ment equal to 0.40 percent of the area of that part of the cross Table 2.2Suggested concrete cover thickness for slabs
section between the flexural tension face and the center of prestressed with post-tensioned reinforcement10
gravity of the gross section. It is recommended that Grade 60 Cover thickness, mm
(Grade 400) reinforcement be used for this purpose. This Restrained or Aggregate type 1 hr 11/2 hr 2 hr 3 hr 4 hr
unrestrained
amount of bonded reinforcement is approximately equal to
Unrestrained Carbonate 20 30 35 50
the minimum reinforcement requirement for conventionally Unrestrained Siliceous 20 35 40 55
reinforced slabs (Section 10.5.3 of ACI 318). Unrestrained Lightweight 20 25 35 40
One-way slabs may also incorporate unbonded partial Restrained Carbonate 20 20 20 25 35
length tendons, lapped tendons, or tendons with intermediate Restrained Siliceous 20 20 20 25 35
Restrained Lightweight 20 20 20 20 25
anchorages that would serve to limit the extent of the loss of See also Section 4.4 for divisibility requirements.
load-carrying capacity. The Uniform Building Code requires
an alternate load-carrying capacity provided by bonded rein-
forcement of D + 0.25L, with a factor of 1.0, for one-way This specification provides for two levels or degrees of cor-
elements post-tensioned with unbonded tendons. Depending rosion protection, with additional corrosion protective mea-
on the span configuration and the loads, the D + 0.25L crite- sures required for tendons used in aggressive environments.
rion is sometimes satisfied in slabs by the bonded reinforce- Concrete cover for unbonded tendons should be detailed
ment requirements of Section 18.9.2 of ACI 318. considering the factors discussed in Section 4.4. Guidance
In negative moment regions of T-beams or other members for the protection of tendons during storage, transit and in-
where compression width is limited, the amount of rein- stallation can be found in the Post-Tensioning Institute pub-
forcement provided is limited (Section 18.8 of ACI 318) to lication Field Procedures Manual for Unbonded Single
avoid the possibility of a compression failure at factored Strand Tendons.8
loads. Structures exposed to aggressive environments include all
In accordance with Section 18.9.4.3 of ACI 318, bonded structures subjected to direct or indirect applications of deic-
reinforcement for both beams and slabs should be detailed in er chemicals, seawater, brackish water, or spray from these
accordance with the provisions of Chapter 12 of ACI 318 sources, structures in the immediate vicinity of seacoasts ex-
with sufficient lap between positive and negative moment posed to salt air, and non-waterproofed backfilled structures.
bars to insure that the bonded reinforcement will function as Stressing pockets and construction joints at intermediate an-
an independent load-carrying system. chorages which are not maintained in a normally dry condi-
2.2.2 In the case of two-way slabs of the usual proportions, tion after construction should also be considered exposed to
catastrophic loading beyond design capacity in one bay is an aggressive environment. The designer should evaluate the
generally not as critical to other spans as in one-way sys- conditions carefully to determine if the environment in
tems. For two-way slabs, the load-carrying capacity of the which the structure is located is considered aggressive in any
tendons in each direction should be considered. Tests2-6 have way. Nearly all enclosed buildings (office buildings, apart-
demonstrated two-way flexural behavior under various par- ment buildings, warehouses, manufacturing facilities) are
tial loading patterns and the capacity of two-way post-ten- considered to be normal environments.
sioned systems to endure some types of catastrophic
loadings; this behavior is intrinsically recognized in ACI 2.4Fire resistance
318, as well as in the Uniform Building Code and some local Fire resistive ratings may be determined in accordance
building codes by reduction in the amount of bonded rein- with the heat transmission and dimensional provisions of
forcement required in comparison with one-way systems. Section 2.4.1 or by the rational design procedures for deter-
mining fire endurance discussed in Section 2.4.29,10 (also re-
2.3Corrosion protection fer to ACI 216R and ASTM E 119). ASTM E 119 includes
Unbonded prestressing tendons should be protected a guide for classifying construction as restrained or unre-
against corrosion during storage, transit, construction, fabri- strained. The guide indicates that either restraint to thermal
cation, and after installation. Corrosion protection should expansion or continuity restraint results in greatly improved
conform to the requirements of the Post-Tensioning Insti- fire endurance and that nearly all cast-in-place concrete con-
tute, Specification for Unbonded Single Strand Tendons.7 struction may be considered to be restrained.
423.3R-4 ACI COMMITTEE REPORT

Table 2.3Suggested cover thickness for beams prestressed with post-tensioned reinforcement8
Cover thickness, mm, for fire endurance of:
Restrained or Beam width,
Steel type Concrete type* 1 hr 11/2 hr 2 hr 3 hr 4 hr
unrestrained mm
Unrestrained Cold-drawn NW 200 45 50 65 120
Unrestrained Cold-drawn LW 200 40 45 50 95
Unrestrained H.S.A. bars NW 200 40 40 40 65
Unrestrained H.S.A. bars LW 200 40 40 40 60
Restrained Cold-drawn NW 200 40 40 40 50 65
Restrained Cold-drawn LW 200 40 40 40 45 50
Restrained H.S.A bars NW 200 40 40 40 40 40
Restrained H.S.A. bars LW 200 40 40 40 40 40
Unrestrained Cold-drawn NW > 300 40 45 50 65 75
Unrestrained Cold-drawn LW > 300 40 40 45 50 65
Unrestrained H.S.A. bars NW > 300 40 40 40 40 50
Unrestrained H.S.A LW > 300 40 40 40 40 50
Restrained Cold-drawn NW > 300 40 40 40 45 50
Restrained Cold-drawn LW > 300 40 40 40 40 45
Restrained H.S.A. bars NW > 300 40 40 40 40 40
Restrained H.S.A. bars LW > 300 40 40 40 40 40
* NW = normal weight; LW = lightweight
For beams with widths between 8 and 12 in., cover thickness can be determined by interpolation.
1 in. = 25.4 mm.
HSA = High strength alloy.

2.4.1 Minimum dimensions for various fire resistive lizing strand tendons, ACI 216R can be used. Beams or joists
classifications8 that are narrower than 8 in. (200 mm) with post-tensioned
2.4.1.1 SlabsTo meet minimum heat-transmission re- high-strength alloy steel bars should have the same cover as
quirements, i.e., temperature rise of 250 F (140 C) of the un- reinforced concrete joists of the same size and fire endur-
exposed surface, the thicknesses requirements for concrete ance.
slabs should be the same whether the concrete is plain, rein- 2.4.1.3 Anchor protectionThe cover to the prestress-
forced, or prestressed. Table 2.1 gives slab thickness recom- ing steel at the anchor should be at least 1/4 in. (6 mm) greater
mended for this purpose. Cover thicknesses for post- than that required away from the anchor. Minimum cover to
tensioning tendons in unrestrained slabs are determined by the steel bearing plate or anchor casting should be at least 1
the elapsed time during a fire test until the tendons each a in. (25 mm) in beams and 3/4 in. (20 mm) in slabs.
critical temperature. For cold-drawn prestressing steel, that 2.4.2 Rational design for fire enduranceRational ana-
temperature is 800 F (430 C). For restrained slabs, there are lytical procedures for the determination of the fire endurance
no steel temperature limitations, but the heat transmission of post-tensioned prestressed concrete structures have been
end-point temperature limitation [250 F (140 C)] is the same developed from analyses of results of fire tests conducted in
as for unrestrained slabs. Fire tests of restrained slabs indi- accordance with the criteria for standard fire tests, ASTM E
cate that slabs with post-tensioned reinforcement behave 119. Basic data on the strength-temperature relationships for
about the same as reinforced concrete slabs of the same di- steel and concrete are utilized together with information on
mensions. Accordingly, the cover for post-tensioning ten- temperatures within concrete beams and slabs during stan-
dons in slabs could be essentially the same as the cover for dard fire tests. Rational design procedures for concrete
reinforcing steel in slabs. Applying these criteria to post-ten- beams and slabs which are post-tensioned with unbonded
sioned slabs, cover thicknesses are as recommended in Table tendons are essentially the same as those for pretensioned
2.2. prestressed concrete elements.9 Curved tendons, rather than
2.4.1.2 BeamsMinimum dimensions for beams with straight or deflected tendons, introduce only minor differ-
post-tensioned reinforcement for various fire endurances are ences that do not change the design procedures. Tests of
functions of the types of steel and concrete, beam width, and post-tensioned elements indicate that the temperatures of the
cover. For very wide beams, the cover requirements should tendons in positive moment regions at the end of a fire test
be about the same as those for slabs. For restrained beams can be considered essentially the same regardless of whether
spaced more than 4 ft (1200 mm) on centers, the temperature the tendons are bonded or unbonded. Further, these tests in-
of 800 F (430 C) for cold-drawn prestressing steel must not dicate that the prestressing steel stress fps at failure during
be exceeded to achieve a fire-endurance classification of 1 hr fire tests can be estimated as a function of the ultimate steel
or less; for classifications longer than 1 hr, this temperature strength at temperature by the relationship
must not be exceeded for the first half of the classification
period or 1 hr, whichever is longer. The recommended cover
f ps f ps
thicknesses in Table 2.3 are based on these criteria. For post- -----------
- = --------
tensioned beams or joists less than 8 in. (200 mm) wide uti- f pu f pu
CONCRETE MEMBERS PRESTRESSED WITH UNBONDED TENDONS 423.3R-5

where fps = stress in post-tensioning tendons at nominal so either an undercoat or a ceiling might be most appropriate.
strength, psi (MPa). This stress may be calculated for un- Very often the best solution at the design stage is the addition
bonded tendons by Eq. (18-4) or Eq. (18-5) in ACI 318 (see of some reinforcing steel that improves not only the fire en-
also Section 3.4). durance but also the overall strength and ductility of the
floor.
fpu = specified tensile strength of tendons, psi (MPa)
fps = stress in post-tensioned tendons at nominal strength 2.5Earthquake loading
at high temperatures, psi (MPa) Most concrete structures located in areas subject to seis-
fpu = tensile strength of tendons at high temperatures, psi mic disturbances that include post-tensioned elements in the
(MPa) gravity load-carrying structural system are provided with
shearwalls, braced frames, or reinforced concrete ductile
For continuous beams or slabs utilizing continuous draped moment-resisting space frames for resisting lateral forces
unbonded tendons exposed to fire from below, the value of due to wind and earthquakes. Most model building codes in
fps in the negative moment regions should be taken the same the U.S. currently contain minimum seismic design criteria
as those in the positive moment region. The capacity at any based upon the requirements and commentary published by
point along the length of an unbonded tendon is limited by the Seismology Committee of the Structural Engineers As-
the capacity at the point where the steel temperature is high- sociation of California11 and/or the NEHRP Recommended
est. Provisions for the Development of Seismic Regulations for
On this basis, it is possible to determine the retained theo- New Buildings.
retical moment strength at a specified period of fire endur- While all the model codes permit the use of unbonded
ance (say 2 hr) in the positive moment region and in both post-tensioning tendons in the structural elements carrying
negative moment regions of a given panel in a building. The gravity or vertical loads, acting as horizontal diaphragms be-
maximum moment capacity at exterior columns should not tween energy dissipating elements under earthquake load-
exceed that which can be transmitted to the column. To eval- ing, there are some differences when it comes to how much
uate the retained theoretical moment strength, it may be as- of the post-tensioning force can be utilized to resist seismic
sumed that if a fire occurs beneath the floor, a redistribution forces. NEHRP (1991),12 BOCA (1993),13 and the Standard
of moments will occur, yielding the negative moment bond- Building Code (1994)14 permit a limited amount of post-ten-
ed reinforcement. If the applied midspan moment is less than sioning to be considered in resisting earthquake induced
the retained moment capacity after redistribution, the fire en- forces. Specifically, these provisions are as follows in NE-
durance will be adequate. This is HRP (1991):
Section 11.1.1.4: Post-tensioning tendons shall be per-
M = Mt+ + 1/2 (Mt1
- + Mt2
-) mitted in flexural members of frames provided the average
2 prestress fpc, calculated for an area equal to the members
wL
M = total static moment (unfactored) = ---------- shortest cross-sectional dimension multiplied by the perpen-
8
dicular dimension, does not exceed 350 psi. (See Fig. 2.1
where for applicable cross-sectional area.)
Section 11.1.1.5: For members in which prestressing ten-
Mt+ = retained midspan moment dons are used together with ASTM A 706 or with A 615
- = retained negative moment at Column 1
Mt1 (Grades 40 or 60) reinforcement to resist earthquake-in-
Mt2 = retained negative moment at Column 2 duced forces, prestressing tendons shall not provide more
than one quarter of the strength for both positive moments
If, however, the applied midspan moment is greater than and negative moments at the joint face. Anchorages for ten-
the retained moment capacity, changes should be made in the dons must be demonstrated to perform satisfactorily for seis-
design. Several options for improving the fire endurance are mic loadings. Anchorage assemblies shall withstand,
available, including: without failure, a minimum of 50 cycles of loading ranging
between 40 and 85 percent of the minimum specified
1. Increase the concrete cover in the positive moment re- strength of the tendon. Tendons shall extend through exterior
gion. joints and be anchored at the exterior face of the joint or be-
2. Increase the number of prestressing tendons. yond.
3. Add positive moment reinforcing steel. The Uniform Building Code (for zones 3 and 4) has not
4. Add negative moment reinforcing steel. explicitly addressed these provisions in this area; bonded
5. Of course, there are other solutions, such as the use of a nonprestressed reinforcement must be used, which conforms
thicker slab, lightweight concrete, or the addition of a fire-re- to special limitations on the maximum yield strength and the
sistant ceiling. Also, combinations of the options just listed minimum tensile strength.
can be used. The most appropriate solution depends on in- The model codes also contain a provision that all framing
place cost, architectural acceptability, and perhaps other elements not required by design to be part of the lateral force
considerations. For example, to upgrade the fire endurance resisting system, must be capable of resisting moments in-
of an existing floor, Options 1 through 4 are not applicable, duced by the distortions of the structure resulting from later-
423.3R-6 ACI COMMITTEE REPORT

nonprestressed (bonded) reinforcement.17-23 In addition to


these laboratory tests, which deal with members having both
bonded and unbonded tendons, several midrise and high-rise
structures incorporating unbonded tendons in earthquake re-
sisting frame members resisted high lateral forces during the
1971 San Fernando, the 1989 Loma Prieta, and the 1994
Northridge earthquakes with no structural distress.24 In the
design of these structures, the contribution of the tendons as
tensile reinforcement under seismic loading was neglected,
Fig. 2.1Applicable for T-sections but the moments induced in the frame by tendon action were
considered. Grade 60 reinforcing bars were provided for mo-
ment capacity and to supply energy dissipation. Since the
tendons were not stressed beyond the elastic range, they re-
duced the deterioration of shear capacity by providing a
nearly constant shear friction force at beam-column joints.
Unbonded tendon anchorages following the construction
failure of a flat plate lift-slab structure demonstrated the in-
tegrity of the anchorages even after collapse of the structure,
tensile failure of the strand, and shattering of the end
blocks.25
Post-tensioned beams may be proportioned to be more
slender than conventionally reinforced members. This re-
duction in beam section stiffness can offset the increase in
stiffness resulting from prestressing (reduced inelastic hinge
lengths), and the overall performance of the frame compares
favorably with conventional ductile frames.
Results of high-intensity reversed cyclic loading tests26 of
specimens representing concrete ductile moment-resistant
frames with unbonded post-tensioned beams indicated that
post-tensioning did not adversely affect the seismic charac-
Fig. 2.2Comparison of lateral load-edge deflection teristics of the specimens. This test report recommends that
relationships for reinforced and prestressed concrete the nominal average prestress, based on the rectangular
slab-interior column specimen11 cross-sectional area of the beam, should be limited to ap-
proximately 350 psi (2.4 MPa). The stiffness after seismic
loading of the post-tensioned frame specimens was larger
al forces in addition to the moments caused by vertical loads; than the stiffness of the non-post-tensioned specimen. Post-
this applies to prestressed concrete elements as well as to tensioning improved the behavior of nonprestressed rein-
those composed of other materials. It has been shown that forcement in the beam-column connection.
under-reinforced prestressed concrete elements (i.e., those Standard specifications for anchorage systems for un-
with combined steel indexes not greater than 0.361 as pro- bonded tendons10 contain static and dynamic test require-
vided in Section 18.8.1 of ACI 318) can meet ductility re- ments that are more severe than would be anticipated in an
quirements of this code provision.15 Fig. 2.116 shows that earthquake of high intensity. These specifications also re-
after low-intensity reversed cyclic loading of interior col- quire anchorages for unbonded tendons to meet fatigue test
umn-slab specimens, conventionally reinforced slabs re- requirements.
quired the addition of closely spaced stirrup reinforcement to
attain ductility comparable to that of a post-tensioned slab. CHAPTER 3DESIGN
Since strains in an unbonded tendon are distributed over the
length of the tendon, the tendons would not be expected to 3.1General
be stressed beyond the elastic range, even in a severe earth- The design provisions of Chapter 18 of ACI 318 apply to
quake. As a result, the tendons do not dissipate much energy. the contents of this chapter, but some recommendations are
Both laboratory tests and field experience indicate that this offered that differ from those of the Building Code.
objection may be overcome by the use of elements contain-
ing a combination of unbonded tendons and nonprestressed 3.2One-way systems
bonded reinforcement. 3.2.1 Minimum bonded reinforcementThe minimum
Laboratory tests of post-tensioned structural elements bonded reinforcement specified in Section 18.9.2 of ACI 318
have indicated that energy dissipation characteristics under is considered adequate to limit crack widths due to dead load
seismic loadings conforming with accepted standards can be and live load by crack distribution.27-29 As discussed in Sec-
achieved by appropriate combinations of prestressed and tion 2.2.1 of this report, this amount of reinforcement also
CONCRETE MEMBERS PRESTRESSED WITH UNBONDED TENDONS 423.3R-7

provides an alternate load-carrying system in the event of a 3.2.2 Tendon spacingThe minimum bonded reinforce-
catastrophic failure or abnormal loading in one span of a ment requirements for one-way slabs under current code pro-
continuous one-way post-tensioned element with unbonded visions, as discussed previously, typically result in the use of
tendons. For this reason, it is recommended that bonded re- No. 4 bars (No. 15) at 21 in. (500 mm) centers for both pos-
inforcement used as part of the design moment strength or itive and negative moments for a 41/2 in. (115 mm) thick slab.
intended to provide an alternate load path in one-way sys- For an 8 in. (200 mm) deep one-way slab, No. 4 bars (No. 15)
tems be detailed in accordance with the provisions of Chap- are required at about 12 in. (300 mm) centers; larger bars are
ter 12 of ACI 318. Slab reinforcement spacing requirements required at somewhat wider spacings. In consideration of
specified in Section 7.6.5 of ACI 318 are not applicable to this amount and spacing of bonded reinforcement, a maxi-
bonded reinforcement in unbonded post-tensioned slabs. mum tendon spacing of eight times the slab thickness [five
In one-way slabs, economical use of the minimum bonded feet (1500 mm) maximum] is recommended for one-way
reinforcement specified in Section 18.9.2 of ACI 318 leads slabs with normal live loads and uniformly distributed loads,
to the use of design tensile stresses in the range of 9 f c psi without the additional restriction of a minimum prestress
(0.8 f c MPa) to l2 f c psi (1.0 f c MPa). Tests have level of 125 psi (0.9 MPa) specified for two-way slabs in
shown satisfactory performance of slabs with this level of Section 3.3.5. Special tendon spacing considerations may be
design tensile stress in conjunction with the bonded rein- required for slabs with significantly concentrated loads.
forcement requirements of Section 18.9.2.27 However, the In certain cases, such as external tendon retrofits, tendon
use of lower design tensile stresses may be preferable from spacings greater than eight times the slab thickness or 5 ft
the durability standpoint for applications such as parking (1500 mm) may be beneficial. In such cases these limits may
structure decks in severe climates.30 be exceeded provided it can be shown by rational analysis
Section 18.8.3 of ACI 318 requires a total amount of bond- that the slab system can adequately carry the design loads.
ed and unbonded tendons adequate to develop a factored 3.2.3 Minimum stirrupsA minimum amount of stirrup
load at least 1.2 times the cracking load based on the modu- reinforcement is necessary in all post-tensioned joists, waf-
lus of rupture fr of 7.5 f c psi (0.7 f c MPa) specified in fle slabs, and T-beams to provide a means of supporting ten-
Section 9.5.2.3 of ACI 318. This provision is included to dons in the tendon design profile. When tendons are not
guard against an abrupt flexural failure at cracking due to adequately supported by stirrups, local deviations of the ten-
rupture of the reinforcement. In contrast to this brittle failure dons from the smooth parabolic curvature assumed in design
mode, tests of one-way slabs and beams have demonstrated may result during placement of the concrete. When the ten-
that unbonded tendons do not rupture and generally do not dons in such cases are stressed, the deviations from the in-
even yield at the time of flexural cracking.27-29 Further, the tended curvature tend to straighten out, and this process may
minimum amount of bonded reinforcement required by Sec- impose large tensile stresses in webs of post-tensioned
tion 18.9.2 of ACI 318 for one-way post-tensioned members beams, joists, or waffle slabs.
equals or exceeds the minimum reinforcement requirements Severe cracking has been observed in several instances
for conventionally reinforced members. Since all one-way where no stirrups were provided. Unintended curvature of
post-tensioned members will have some unbonded post-ten- the tendons may be avoided by securely tying tendons to stir-
sioned reinforcement in addition to the minimum bonded re- rups that are rigidly held in place by other elements of the re-
inforcement, the total minimum reinforcement will in all inforcing cage. For bundles of two to four monostrand
cases exceed the minimum for conventionally reinforced tendons, ties to a minimum of No. 3 (No. 10 mm diameter)
one-way members by a substantial margin. stirrups at 2 ft 6 in. (760 mm) centers are suggested, and for
For this reason, and considering the fact that unbonded bundles of five or more monostrand tendons, ties to a mini-
tendons do not yield or rupture at cracking, it is recommend- mum of No. 4 stirrups (No. 15) at 3 ft 6 in. (1070 mm) cen-
ed that Committee 318 waive the minimum reinforcement ters are recommended. This amount and spacing of stirrups
requirement of Section 18.8.3 (1.2 times the cracking load) is recommended even when the magnitude of the shear stress
for one-way beams and slabs with unbonded tendons, and is such that no stirrups are required under the provisions of
that Section 18.8.3 be revised to exclude application to one- Section 11.5.5 of ACI 318. In most cases, closer stirrup spac-
way beams and slabs with unbonded tendons. Section 18.8.3 ings will be required to satisfy the shear reinforcement re-
usually does not control reinforcement requirements in post- quirements of ACI 318.
tensioned T-beams and one-way joists. 3.2.4 Prestressed shrinkage and temperature reinforce-
For applications of Eq. (18-6) of ACI 318 to negative mo- mentIn Section 7.12 of ACI 318, prestressed shrinkage
ment areas in T-beam and joist construction, the flange width and temperature reinforcement may be used that has a mini-
should be the minimum width that will provide section prop- mum average compressive stress of at least 100 psi (0.7
erties that will satisfy the 0.45 f c service load compres- MPa) on the gross concrete area using the effective stress in
sive stress limitation at the bottom of the beam or stem. The the prestressing steel, after losses, in conformance with Sec-
top fiber tensile stress limitation should also be checked. The tion 18.6 of ACI 318.
total bonded and unbonded reinforcement supplied should In monolithic cast-in-place post-tensioned beam and slab
also satisfy flexural design strength requirements without construction, the portion of a slab that is used as a beam
exceeding the limiting ratio of prestressed and nonpre- flange should satisfy the minimum reinforcement require-
stressed reinforcement of ACI 318, Section 18.8.1. ments of Chapter 18 of ACI 318 applicable to the beam. In
423.3R-8 ACI COMMITTEE REPORT

Fig. 3.2Effective flange widths for normal forces

cordance with the provisions of Section 13.7 of ACI 318 (ex-


cluding Sections 13.7.7.4 and 13.7.7.5) or by more precise
methods, including finite element techniques or classical
elastic theory. The equivalent frame method of analysis has
been shown by tests of large structural models to satisfacto-
rily predict factored moments and shears in prestressed slab
systems.2,4-6,31,32 The referenced research also shows that
Fig. 3.1Details for use of unbonded tendons as shrinkage yield-line theory predicts the flexural strength of two-way
and temperature reinforcement in one-way beam and slab post-tensioned slabs reasonably well. Analysis using pris-
construction matic sections or other approximations of stiffness which
differ substantially from the equivalent frame method may
addition, in positive moment areas, the slab should be rein- provide erroneous results on the unsafe side. Section
forced in accordance with Section 7.12.2 of ACI 318 unless 13.7.7.4 is excluded from application to prestressed slab sys-
a compressive stress of 100 psi (0.7 MPa) is maintained un- tems because it relates to reinforced slabs designed by the di-
der prestress plus dead load. In the central region of the bay rect design method and because moment redistribution for
between beam flanges, additional tendons should be used to prestressed slabs is covered in Section 18.10.4 of ACI 318.
provide 100 psi compression (0.7 MPa) in the portion of the Section 13.7.7.5 is excluded from application to prestressed
slab that is not used as a part of the beam. Tendons used for slab systems because the distribution of moments between
shrinkage and temperature reinforcement should be posi- column strips and middle strips required by Section 13.7.7.5
tioned vertically as close as practicable to the center of the is based on analysis of elastic slabs plus tests of reinforced
slab. In cases where shrinkage and temperature tendons are concrete slabs. Simplified methods of analysis using average
used for supporting the principal tendons, variation from the coefficients do not apply to prestressed concrete slab sys-
slab centroid is permissible. However, the resultant eccen- tems. All other provisions of Section 13.7, specifically in-
tricity of the shrinkage and temperature tendons should not cluding the arrangement of live loads specified in Section
extend outside the kern limits of the slab. Fig. 3.1 illustrates 13.7.6, are applicable for the analysis of post-tensioned flat
details for the use of unbonded tendons as shrinkage and plates.
temperature reinforcement in one-way beam and slab con- If the probability of cracking of the slab is small, the lateral
struction. load stiffness should be assessed using ACI 318, Section
3.2.5 T-beam flange widthThe effective flange width of 13.7. If, however, there is a high probability of extensive
post-tensioned T-beams in bending may be taken in accor- cracking, the cracked section bending stiffness should be
dance with Section 8.10 of ACI 318, or may be based on used and the torsional stiffness taken as one-tenth that calcu-
elastic analysis procedures. Flange widths in excess of those lated from Eq. (13-6) of ACI 318.15 The cracked section
specified for conventionally reinforced concrete T-beams in bending stiffness should always be used for the computation
ACI 318, Section 8.10 have been used (see ACI 318 Com- of drift under seismic loads. Strength under lateral loads may
mentary, Fig. 7.12.3). The effective flange width for normal be evaluated using the load factor combinations of Section
forces near post-tensioning anchorages may be assumed in 9.2 of ACI 318 in conjunction with the provisions of Section
accordance with Fig. 3.2 as 2bn + bno. 18.10.3 of ACI 318. Evaluation of strength requirements un-
der lateral loads may disclose the need for reinforcement for
3.3Two-way systems moment reversals. Such reinforcement should be located
3.3.1 AnalysisPrestressed slab systems reinforced in within a distance of 1.5h outside opposite faces of the col-
more than one direction for flexure should be analyzed in ac- umn.
CONCRETE MEMBERS PRESTRESSED WITH UNBONDED TENDONS 423.3R-9

3.3.2 Limits for reinforcementIt is recommended that Nc


Committee 318 waive the requirement of Section 18.8.3 of A s = ------------
-
0.5 f y
ACI 318 for a total amount of prestressed and nonprestressed
reinforcement sufficient to develop 1.2 times the cracking
where the specified yield strength of nonprestressed rein-
load for two-way post-tensioned systems with unbonded ten-
forcement fy shall not exceed 60,000 psi (400 MPa), and Nc
dons. Due to the very limited amount and extent of the initial
is the tensile force in concrete due to unfactored dead load
cracking in the negative moment region near columns of
plus live load D + L. Details of placement for the reinforce-
two-way flat plates, load-deflection patterns do not reflect ment provided in this section are included in Section 3.3.5.
any abrupt change in stiffness at this point in the loading his- Slab reinforcement spacing requirements specified in Sec-
tory. tion 7.6.5 of ACI 318 are not applicable to bonded reinforce-
Only at load levels beyond the design (factored) loads is ment in unbonded post-tensioned slabs.
the additional cracking extensive enough to cause an abrupt 3.3.4 Shear and moment transferFig. 3.3 shows the re-
change in the load-deflection pattern. Tests have also shown sults of single column-slab specimen punching shear tests
that it is not possible to rupture (or even yield) unbonded and results of multipanel slabs tested in shear.35 Eq. (11-39)
post-tensioning tendons in two-way slabs prior to a punching expressed in terms of the perimeter of critical section for
shear failure.2,4-6,15,31,33-35 The use of unbonded tendons in slabs bo is
combination with the minimum bonded reinforcement re-
quirements of Sections 18.9.3 and 18.9.4 of ACI 318 has V c = ( p f c + 0.3 f pc )b o d + V p (11-39)
been shown to assure post-cracking ductility and that a brit-
tle failure mode will not develop at first cracking. where p is the smaller of 3.5 (0.29) or (sd/bo + 1.5) [(sd/bo
3.3.3 Minimum bonded reinforcementMinimum bonded + 1.5)/12] and:
reinforcement in negative moment areas of two-way systems s = 40 for interior columns
is governed by Eq. (18-8) of ACI 318 = 30 for edge columns
= 20 for corner columns
As = 0.00075hl (18-8) bo = perimeter of critical section defined in Section
11.12.1.2 of ACI 318
fpc = average value of fpc for the two directions
This amount of bonded reinforcement is required within a
Vp = vertical component of all effective prestressing
slab width between lines that are 1.5h outside opposite faces
forces crossing the critical section
of the column support. Tests on square panel specimens have
In addition, no portion of the column cross section shall be
shown a steel area of 0.00075 Ac to be adequate to assure closer to a discontinuous edge than four times the slab thick-
sufficient punching shear strength, where Ac is the tributary ness, and fc shall not exceed 5000 psi (35 MPa).
cross-sectional area of the slab between panel centerlines An upper limit of 500 psi (3.5 MPa) and a lower limit of
perpendicular to the bonded reinforcement.4-6,34-36 This val- 125 psi (0.9 MPa) are specified for fpc. For values of precom-
ue was expressed in the code as 0.00075hl, where l is the pression less than 125 psi (0.9 MPa), shear is limited to the
span in the direction of the reinforcement, to generalize the value obtained using Section 11.12.2.1 of ACI 318 as for
expression for rectangular panels, placing more bars in the nonprestressed construction. For thin slabs, Vp must be care-
direction of the longer span. The use of hl as opposed to Ac fully evaluated, as field placing practices can have a great ef-
is appropriate to determine bonded reinforcement require- fect on the profile of the tendons through the critical section.
ments at the interior columns and reinforcement perpendicu- Vp may be conservatively taken as zero.
lar to the slab edge at exterior columns. Moment transfer from prestressed concrete slabs to interi-
Tests4-6,34-36 show that it is appropriate to provide bonded or column connections can be evaluated using the proce-
reinforcement parallel to the slab edge at exterior columns dures of Section 11.12.6 and 13.3.3 of ACI 318.15 In this
on the basis of 0.00075 Ac where Ac is the tributary cross- case, for normal weight concretes, the factored shear stress
sectional area of the slab perpendicular to the direction of the vu should not exceed the value of vc calculated from Eq. (11-
39) of the code expressed in terms of shear stress rather than
bonded reinforcement between the center of the exterior
force. The value of fpc used in Eq. (11-39) should be the av-
span and the slab edge. At exterior columns of flat plates
erage precompression in the direction of moment transfer.
with square panels and no projection of the slab beyond the
All reinforcement, bonded and unbonded, within lines one
exterior column face, the bonded reinforcement parallel to and one-half times the slab thickness on either side of the
the slab edge should be 50 percent of the bonded reinforce- column, is effective for transferring the portion of the mo-
ment perpendicular to the slab edge. ment not transferred by shear. No increase in forces for un-
Bonded reinforcement in positive moment areas of two- bonded tendons should be assumed in calculations of the
way flat plates is required where the computed tensile stress moment transfer capacity. Tendons bundled through the col-
in the concrete at service load exceeds 2 f c psi, (0.17 f c umn or over the lifting collar in lift slabs are an effective
MPa). The amount of positive moment bonded reinforce- means of increasing the moment transfer strength of lift-slab
ment, when required, is specified by Eq. (18-7) of ACI 318 connections. The moment transfer strength of lift-slab con-
423.3R-10 ACI COMMITTEE REPORT

nections is also controlled by details of the lift-slab collar-to- The limited test data available35,37 do not show beneficial
column connection. effects on shear strength due to use of shear reinforcement
The procedures of Sections 11.12.6 and 13.3.3 of ACI 318 with conventional anchorage details in post-tensioned flat
are also applicable to calculations of the moment transfer plates. The use of stud shear reinforcement with special an-
from prestressed concrete slabs to exterior column connec- chorage details and stirrups with special anchorage details
tions for moments normal to a discontinuous edge. However, has been shown to increase shear strength substantially.38-41
bonded reinforcement, detailed as closed ties or hooks so 3.3.5 Tendon and bonded reinforcement distribution and
that it can act as torsional reinforcement, should be provided spacingWithin the limits of tendon distributions that have
when the calculated upward factored shear stress vu at the been tested, research indicates that the moment and shear
strength of two-way prestressed slabs is controlled by total
discontinuous edge exceeds 2 f c psi (0.17 f c MPa),
tendon strength and by the amount and location of nonpre-
and, until further research data become available, the maxi-
stressed reinforcement, rather than by tendon distribution.3-
mum calculated shear stress at such exterior columns should 6,15,32 While it is important that some tendons pass within the
be limited to 4 f c psi (0.33 f c MPa). However, tests
shear perimeter over columns, distribution elsewhere is not
completed in 1982 of four edge column specimens of a post- critical, and any rational method which satisfies statics may
tensioned flat plate with banded tendon details, support the be used. For uniform loading, the maximum spacing of sin-
use of Eq. (11-39) of ACI 318 for shear design.36 gle tendons or groups of tendons in one direction should not
exceed 8 times the slab thickness, with a maximum spacing
of 5 ft (1500 mm). In addition, tendons should be spaced to
provide a minimum average prestress of 125 psi (0.9 MPa)
on the local slab section tributary to the tendon or tendon
group (the section one-half of the spacing on either side of
the center of the tendon or tendon group). The spacing of sin-
gle strand tendons is usually governed by the minimum av-
erage prestress requirements. For groups of two or more
tendons, the 8h criterion usually controls maximum tendon
spacing. Special consideration of tendon spacing may be re-
quired to accommodate concentrated loads.
When more than two strands are bundled in a group, addi-
tional cover may be necessary to assure proper concrete
placement under the tendon group. Horizontal curvature of
bundled monostrand tendons should be avoided. If this is not
possible, additional transverse reinforcement and accesso-
ries may be required at points of horizontal curvature to
maintain the horizontal plane of tendon bundles during
stressing.
Fig. 3.3Two-way post-tensioned flat plate shear test data Transverse reinforcement may also be required to control
versus Eq. (11-39) of ACI 31835 horizontal splitting cracking that may occur due to in-plane
forces from horizontally curved banded tendons.
230 mm 270 mm 300 mm The predominant and recommended method of placing
510 mm
tendons in two-way slab systems is the banded distribution
illustrated in Fig. 3.4. The use of a banded tendon distribu-
tion greatly simplifies the process of placing tendons, and
therefore provides a significant reduction in field labor cost.
Recommended details of reinforcement for banded tendon
distribution are given in the following paragraphs.
The number of tendons required in the design strip (center-
to-center of adjacent panels) may be banded close to the col-
umn in one direction and distributed in the other direction.
At least two tendons should be placed inside the design shear
section at columns in each direction.
For lift-slab construction, the same general details of ten-
don distribution apply, and provision should be made for ten-
dons to pass through or over the lifting heads.
The maximum spacing of tendons or bundles of tendons
6.5 mm 1660
that are distributed should be 8h but not to exceed the spac-
ing that provides a minimum average prestress of 125 psi
Fig. 3.4Banded tendon distribution6 (0.9 MPa). Even though no tendons are provided in one di-
CONCRETE MEMBERS PRESTRESSED WITH UNBONDED TENDONS 423.3R-11

rection between bands, this maximum spacing assures one- f c


way reinforcement for this part of the slab. Except for small fps (psi) = fse + 10,000 + --------------- fse + 30,000 (18-5)
300
triangular sections adjacent to the slab edges, the area be-
tween bands is also prestressed in both directions. f c
Recommended details for nonprestressed reinforcement fps (MPa) = fse + 70 + --------------- fse + 200 (18-5) SI
300
are as follows:
a. Minimum As at columns is As = 0.00075hl [Eq. (18-8) in Research43 indicates that redistribution, of equalizing of
ACI 318] where l is the length of span in the direction paral- unbonded tendon stresses does not occur. This research rec-
lel to that of the reinforcement being determined. At least ommends that equations (18-4) and (18-5) be used to calcu-
four bars should be provided in each direction in negative late fps at each individual design section along the member,
moment areas at columns. As indicated in Section 3.3.3, the rather than averaging the values between positive and nega-
amount of bonded reinforcement parallel to the slab edge at tive moment sections as recommended in ACI 423.3R-89.
exterior columns should be based on 0.00075 Ac where Ac Tendon stress at factored load is a function of the type of
is the tributary cross-sectional area of the slab perpendicular tendon, total wobble and curvature and construction care.
to the bonded reinforcement between the center of the exte- Reference (44) indicates that for most typical configurations,
rior span and the slab edge. designs using variable force will not vary significantly from
b. Bonded reinforcement should be placed within a slab designs using the average force method. For these reasons,
width between lines that are 1.5h outside opposite faces of the committee recommends using the variable force method
columns (ACI 318, Section 18.9.3.3). Maximum spacing of for tendons longer than 100 ft (30 m) stressed from one end
these bars is 12 in. (300 mm). or for tendons longer than 200 ft (60 m) stressed from two
c. The minimum length for negative moment bars is one- ends. The average force method is acceptable for all other
sixth the clear span on each side of support. conditions.
d. Where service load positive moment gives stress in ex-
cess of 2 f c psi (0.17 f c MPa) minimum bonded rein-
3.5Prestress losses
forcement is specified by Eq. (18-7) of ACI 318
Prestress losses, considering the factors noted in Section
18.6 of ACI 318, should be calculated by the design engineer
As = Nc/0.5fy
and stated on the design drawings. Articles have been pub-
lished that make it possible to calculate reasonably accurate
where Nc is the tensile force in concrete due to unfactored
values for the various code-defined sources of loss without
dead load plus live load D + L.
excessive effort.45 For typical applications, the values of pre-
e. The minimum reinforcement for positive moment
stress loss given in Table 3.1 may be used in lieu of more de-
(when required) should have a length at least one-third the
tailed loss calculations. The loss values in Table 3.1 are
clear span with the bars centered in the positive moment ar-
based on use of normal weight concrete and on average val-
ea.
ues of concrete strength, prestress level, and exposure condi-
f. Where bonded reinforcement is used along with un-
tions.
bonded tendons based on strength requirements (rather than
Prestress losses may vary significantly above or below the
minimum As), attention should be given to the cutoff points,
values in Table 3.1 in cases where the concrete is stressed at
and they should be specified as per Chapter 12 of ACI 318.
low strengths, where concrete is highly prestressed, or in
very dry or very wet exposure conditions. The loss values in
3.4Tendon stress at factored load
Table 3.1 do not include losses due to friction or anchor seat-
Eq. (18-4) of ACI 318 was developed primarily from re-
ing losses. Design calculations should consider friction loss-
sults of tests of beams and is limited to members with span-
es in accordance with Section 18.6.2 of ACI 318. Some
depth ratios of 35 or less29
portion of the friction loss can usually be offset by use of
f c temporary initial tendon stresses in excess of 0.70 fpu. Spe-
fps (psi) = fse + 10,000 + --------------- (18-4)
100 cial consideration should be given to friction losses whenev-
er tendons in excess of 100 ft (30 m) long are stressed from
f c only one end.
fps (MPa) = fse + 70 + --------------- (18-4) SI
100
Tests have shown that Eq. (18-4) apparently overestimates Table 3.1Approximate prestress loss values10
the amount of stress increase in unbonded tendons in one-
Prestress loss, psi
way slabs, two-way flat plates, and flat slabs with higher Post-tensioning tendon material
span-depth ratios.42 Until a generally acceptable formula is Slabs Beams and joists
developed, the capacity of one-way slabs, flat plates, and flat Stress-relieved 270k strand and
stress-relieved 240k wire 30,000 35,000
slabs should be calculated using ACI 318 formula [Eq. (18- Bar 20,000 25,000
5)] for design stress in unbonded tendons Low-relaxation 270K strand 15,000 20,000
423.3R-12 ACI COMMITTEE REPORT

less significant for one-way slabs than for two-way slabs,


which usually do not have bonded positive moment rein-
forcement in interior panels. For applications such as park-
ing structures where control of cracking is very significant
from the standpoint of improving durability against applica-
tion of deicing chemicals, average prestress levels of the or-
der 200 psi (1.4 MPa) are recommended.
3.6.2 Maximum average prestressA high value of aver-
age prestress may induce excessive shortening due to elastic
deformation and creep. A maximum average prestress of 500
psi (3.5 MPa) is considered appropriate for solid slabs if
shortening will not cause problems. Detailing, as discussed
in Section 3.7, to assure that restraint to immediate and long-
term shortening does not interfere with the imposition of the
calculated average prestress in the concrete, is of increasing
importance as the average prestress is increased toward the
maximum value.

3.7Supporting walls and columns


When columns and walls have significant stiffness in the
direction of prestress, consideration should be given to the
effects of the mutual restraining actions of the slab, columns,
and walls.46 These restraining actions may result in cracks in
either the slab or the supporting elements or both. This effect
can be quite serious for long slabs with high shrinkage and
creep.47 Likewise, the effects of the prestressing forces on
Fig. 3.5Anchorage zone reinforcement for groups of 1/2 in. stiff supporting elements should be investigated. However,
(13 mm) 270 k (1860 MPa) monostrand tendon anchorages design and construction options are available to reduce the
effects of the shortening on both the slab and the supporting
elements, as discussed in the following paragraphs. The mo-
For calculation of friction losses for greased unbonded ments or stresses that occur over a period of time due to
strand tendons in plastic sheathing using the formulas in Sec- creep and shrinkage shortening are themselves reduced ap-
tion 18.6.2 of ACI 318, the friction factor , usually ranging proximately 50 percent by creep.48
from 0.05 to 0.25, and the wobble factor K, usually ranging Dimensional changes due to changes in temperature occur
from 5 to 15 x 10-4/ft (15 to 50 x 10-4/m) may be used for de- over a relatively short time period, and their effect would not
sign calculations. It may be necessary to obtain more precise be reduced by creep of the concrete. The restraining effects
values for the friction-factor and wobble-factor coefficients due to dimensional changes can be accommodated in the fol-
to calculate tendon elongations during stressing to conform lowing ways:
with the 7-percent tolerance specified in Section 18.18.1 of a. Design or locate supporting elements to minimize re-
ACI 318 for comparing tendon force as measured by gage straint. Relatively long flexible columns may reduce re-
straint forces to the point where they can be accommodated
pressure and tendon elongation.
easily by column reinforcement. Lateral load-resisting ele-
ments can often be located near the center of movement so
3.6Average prestress that no restraint develops. Special consideration should be
3.6.1 Minimum average prestressThe average prestress given to irregular layouts where a small slab area cannot de-
is defined as the total prestress force (after losses) divided by form with the overall deformations of the slab. In such cases,
the total area of concrete. There has been much satisfactory it is advisable to provide a complete structural separation be-
experience in recent years in one-way slabs and flat plates tween the two slab areas. Small areas may be designed as re-
with an average prestress of about 125 psi (0.9 MPa). Lower inforced concrete when it is determined that post-tensioning
values have also been used successfully for short span appli- cannot be used effectively.
cations. These short span applications can be characterized b. Special consideration should be given to the effects of
as having flexural stresses substantially below 6 f c psi slab shortening on restraining walls and columns whenever
(0.5 f c MPa), minimal volume-change effects, and verti- slab lengths between construction joints exceed 150 ft (45
cal element stiffness such that restraint to shortening is min- m). In such cases, the structure may be segmented with pour
imized. strips or temporary joints to minimize the movement and re-
In view of the amount and distribution of bonded rein- straint developed during post-tensioning and due to early
forcement required in one-way slabs as discussed in Sections volume changes. Reinforcement, either prestressed or non-
3.2.1 and 3.2.2, minimum average prestress is considered prestressed, should be provided to achieve continuity when
CONCRETE MEMBERS PRESTRESSED WITH UNBONDED TENDONS 423.3R-13

the strip is closed with concrete. These strips should prefer- described in Reference 50 ranged from 2460 psi (17 MPa) to
ably be left open for a sufficient length of time to help mini- 2960 psi (20 MPa) to be representative of typical concrete
mize the effects of slab shortening. The design of strengths at the time of stressing tendons. Similar reinforce-
reinforcement should be based on the amount of reinforce- ment should also be provided for anchorages located within
ment required to achieve continuity, taking into consider- 12 in. (300 mm) of slab corners. A minimum of two tendons
ation the deflection or camber that is expected to occur prior at the slab edge perpendicular to the banded tendons at both
to casting the closure strip. Temporary shoring may be used the stressing end and dead end should be stressed preferably
to assure full continuity for both dead and live loads. before the banded tendons are stressed.
c. Detail the connection between the flexural elements and The tests described in Reference 49 were limited to an-
columns to permit movement. chorages of 1/2 in. (13 mm) diameter, 270 ksi (1860 MPa)
d. Add or improve the layout of reinforcement. Bonded re- strand unbonded tendons in normal weight concrete. For an-
inforcement placed parallel to restraining walls is highly ef- chorage of 0.6-in. (15 mm) diameter, 270 ksi (1860 MPa)
fective in distributing potential restraint cracks. A rein- strand tendons, or for anchorages used in lightweight con-
forcement ratio of 0.15 percent with bars placed half at the crete slabs, the amount and spacing of reinforcement should
top and half at the bottom over a width of about one-third of be conservatively adjusted to provide for the larger anchor-
the span normal to the wall can be considered adequate for age force and for the smaller splitting tensile strength of
this purpose. The effect of potential diagonal cracks at slab lightweight concrete. References 51 and 52 present studies
corners, reentrant slab corners, and corners of walls can be of the behavior of post-tensioned anchorage zones.
similarly reduced by providing either diagonal or orthogonal For anchorage zones of groups of unbonded tendons in
bonded reinforcement. Diversion of prestress into support- beams, the splitting tensile force may be taken as10
ing elements can be counteracted by overlapping tendons in d
these areas. Overlapping of tendons is recommended around Fst (kips) = 0.30 1 ------a- Pj
d sp
openings to counteract potential diagonal cracks at the cor-
ners of the openings in accordance with Fig. 5.1. d
In two-way flat plates, the average prestress is often on the Fst (kN) = 1.33 1 ------a- Pj
d sp
order of 125 psi (0.9 MPa). Stresses of this magnitude do not
usually produce large dimensional changes due to elastic in which
shortening or concrete creep. However, even in these appli-
cations, care should be exercised when the building dimen- da = depth of anchor casting (for a single line of anchors)
sions, or the dimensions between joints, become large, or or depth of section covered by a group of anchors
when the flexural elements are supported by rigid elements dsp = total depth of symmetric concrete prism above and
that could produce substantial restraint forces if not properly below a single anchor or group of anchors
detailed. Pj = tendon jacking force for all tendons anchored in a
group
3.8Serviceability requirements
Design for performance at service load should consider Reinforcement required for splitting tensile forces calcu-
the factors included in Sections 9.5.4 and 18.10.2 of ACI lated in accordance with the previous equation should be
318. Serviceability limitations, including specified limits on proportioned with fs = 0.6 fy, where fy should not exceed 60
deflections should be satisfied. ksi (400 MPa). Splitting reinforcement may not be required
It is important that the deflection limits of Section 9.5.4 re- for tendon groups anchored in columns where confinement
fer to computed deflections only and not to measurements is provided by column loads and column reinforcement, or
made on the actual structure. Field surveys of apparent de- for anchorages where lateral confinement is provided by a
flections can be influenced by many construction factors beam perpendicular to the trajectory of the tendons which is
which are beyond the control of the designer and impossible monolithic with the slab and increases the depth of the sec-
to isolate from true deflections caused by applied loads. tion by at least the slab thickness above or below the slab.
Reinforcement may be in the form of spirals, stirrups, or-
3.9Design strength thogonal reinforcement, or combinations of these. Groups of
The strength of prestressed systems should be at least anchorages should be restrained with reinforcement (direc-
equal to the required strength provisions contained in Sec- tion perpendicular to tendons) extending through the entire
tions 9.2, 9.3, 18.10.3, and 18.10.4 of ACI 318. group of anchorages. All orthogonal reinforcement should
be mechanically anchored around reinforcement running
3.10Anchorage zone reinforcement parallel to the tendons. Spirals, stirrups, or orthogonal rein-
Anchorage zones in normal weight concrete slabs for forcement should have sufficient extra length to develop full
groups of six or more 1/2 in. (13 mm) diameter single strand bond with the concrete, or should be mechanically anchored
unbonded tendons with horizontal anchor spacing of 12 in. by 135 deg bends around reinforcement. The clear distance
(300 mm) or less should be reinforced in accordance with between bars or pitch of spirals used as anchorage zone rein-
Fig. 3.549 or with a similar detail using closed stirrups. The forcement should be at least the maximum size of the aggre-
concrete strengths for the specimens tested in the research gate plus 1/2 in. (12 mm) but not less than 11/2 in. (40 mm).
423.3R-14 ACI COMMITTEE REPORT

CHAPTER 4MATERIALS the Post-Tensioning Institute Specification for Unbonded


Single Strand Tendons.7
4.1Tendons Galvanizing may be used to protect prestressing bar ten-
4.1.1 SpecificationsPrestressing steel for unbonded dons that are to be left exposed. These coatings should be ap-
post-tensioning tendons should meet the requirements of plied by the hot-dip process and in accordance with ASTM
Section 3.5.5 of ACI 318. The total elongation under ulti- A 123. Other related components such as anchorages, fit-
mate load of the tendon and anchorage assembly should not tings, couplers, and coupler bars may be protected by elec-
be less than 2 percent measured in a minimum gage length of trodeposited coatings of zinc, as per ASTM B 633 (Type LS)
10 ft (3.0 m). or of cadmium, as per ASTM B 633 (Type NS). This type of
4.1.2 AnchoragesThe anchorages of unbonded tendons tendon, particularly if exposed, requires periodic inspection
shall develop at least 95 percent of the minimum specified for corrosion protection integrity and is not recommended
ultimate strength of the prestressing steel without exceeding for locations where it can be damaged easily.
the anticipated set. This is substantially in excess of the max- 4.2.2 SheathingSheathing for unbonded single strand
imum possible design stress of unbonded tendons fps, dis- tendons should conform to the requirements of the Post-Ten-
cussed in Section 3.4. sioning Institute Specification for Unbonded Single Strand
4.1.3 Tests of tendons and anchor fittings Tendons.7
4.1.3.1 Static tests10The test assembly should consist of 4.2.3 DuctsDucts for unbonded tendons are similar to
standard production-quality components and the tendons those for post-tensioned grouted tendons. They should be
should be at least 10 ft (3.0 m) long. The test assembly mortar and grease-tight and nonreactive with concrete, pre-
should be tested in a manner to allow accurate determination stressing steel, or the filler material. Ducts should be com-
of the yield strength, ultimate strength, and percent elonga- pletely filled with an approved corrosion-preventive
tion of the complete tendon. The specimen used for the static greaselike material7 injected under pressure. It is also neces-
test need not be one that has been subjected to fatigue load- sary that a permanent grease cap be attached to and cover the
ing. tendon anchorage, and that both the grease caps and the ten-
4.1.3.2 Fatigue tests10A fatigue test should be per- don duct be grease-tight so that the corrosion preventive ma-
formed on a representative test assembly, and the tendon terial cannot escape into the surrounding concrete.
should withstand without failure 500,000 cycles from 60 to
66 percent of its minimum specified ultimate strength, and 4.3Protection of anchorage zones
also 50 cycles from 40 to 80 percent of its minimum speci- The anchorages of unbonded single strand tendons should
fied ultimate strength. Each cycle involves the change from be protected adequately from corrosion and fire. Except in
the lower stress level to the upper stress level and back to the special cases, anchorages should preferably be encased in
lower. concrete with details complying with the Post-Tensioning
The specimen used for the second fatigue test (50 cycles) Institute Specification for Unbonded Single Strand Ten-
need not be the same used for the first fatigue (500,000 cy- dons.7
cles). Systems incorporating multiple strands, wires, or bars Where concrete or grout encasement cannot be used, the
may be tested using a test tendon of smaller capacity than the tendon anchorage should be completely coated with a corro-
full-size tendon. The test tendon should duplicate the behav- sion-resistant paint or grease equivalent to that applied to the
ior of the full-size tendon and generally should not have less tendons. A suitable enclosure should be placed where neces-
than 10 percent of the capacity of the full-size tendon. sary to prevent the entrance of moisture or the deterioration
4.1.4 Couplers10Unbonded tendons should be coupled or removal of this coating. The anchorage encasement
only at locations specifically indicated and/or approved by should provide fire resistance at least equal to that required
the engineer. Couplers should not be used at points of sharp for the structure.
tendon curvature. All couplers should develop at least 95
percent of the minimum specified ultimate strength of the 4.4Concrete cover
prestressing steel without exceeding the anticipated set. The Specification of concrete cover for unbonded tendons
couplers should not reduce the elongation at rupture below should consider the placement tolerances specified in Sec-
the requirements of the tendon itself. tion 5.3.2 and the exposure conditions. The use of good-
Couplers should meet the fatigue test requirement recom- quality concrete, adequate cover, good construction practic-
mended in Section 4.1.3.2. Couplers and/or components es, and a limit on the amount of water-soluble chloride ions
should be enclosed in housings long enough to permit the in the concrete (refer to ACI 318 Section 4.4.1) are all nec-
necessary movements. All coupler components should be essary to assure long-term durability, particularly in aggres-
completely protected with a coating material prior to final sive environments. Use of at least the additional cover
encasement in concrete. specified in ACI 318, Section 7.7.3.2, and consideration of a
somewhat higher average prestress level, is recommended
4.2Protection materials for applications exposed to deicer chemicals or for locations
4.2.1 Coating7Unbonded single strand tendons should in the immediate vicinity of seacoasts. Extra cover cannot be
utilize a corrosion inhibiting coating in conformance with a substitute for good-quality concrete.
CONCRETE MEMBERS PRESTRESSED WITH UNBONDED TENDONS 423.3R-15

Although research50,53-55 and experience30,56 have demon- For larger openings where it is necessary to terminate
strated the durability of structures with unbonded tendons some tendons at the opening, the crack inhibiting layout of
exposed to seawater and other aggressive environments, it is tendons shown in Fig. 5.146 is recommended rather than the
not recommended that unbonded tendons be utilized in ap- crack promoting layout. In some cases, it may be prefera-
plications directly exposed to seawater or other severe corro- ble to isolate small slab sections adjacent to openings with
sive environments unless special corrosion-protection slab joints, as shown in Fig. 5.2.46 The isolated slab sections
measures are taken. There are proprietary protection systems should be reinforced as required with conventional bonded
available that provide enhanced corrosion protection to the reinforcement.
total tendon assembly for highly corrosive environ- For larger openings, it is always desirable to reinforce the
ments.57,58 top and bottom of the slab at openings with diagonal bars to
control cracking initiated at the corners of the opening. In
CHAPTER 5CONSTRUCTION some cases, additional structural reinforcement may be nec-
essary around the slab perimeter to distribute any loads ap-
5.1Construction joints plied at the opening to the slab. Loads at openings can
Construction joints may be used to divide the floor system normally be accommodated by use of tendons and additional
into segments of suitable size for placement of concrete. In- bonded reinforcement around the perimeter. However, addi-
termediate stressing anchors may be used at construction tional beams may sometimes be required to carry the loads
joints, or the tendons may run through the joint without an- at perimeters of openings, and a structural analysis should be
chors. made to determine whether these loads can be carried by use
Special care should be taken to insure a watertight joint to of additional tendons and additional bonded reinforcement
prevent leaks and subsequent corrosion of tendon compo- or whether beams are required. It is generally preferable to
nents and reinforcement in the joint vicinity. locate openings in the midspan areas of one-way slabs and
two-way flat plates to minimize the effect of the opening on
5.2Closure strips the shear capacity of the slab at walls or columns. When
Open strips may temporarily separate adjacent slabs dur- openings are located where they may reduce shear capacity,
ing construction as discussed in Section 3.7. a more exact analysis of the capacity of the actual slab con-
figuration is essential. In flat plates, Section 18.12.4 of ACI
5.3Placement of tendons 318 requires that: A minimum of two tendons shall be pro-
5.3.1 Tendon profileThe placement of tendons should vided in each direction through the critical shear section over
closely follow the specified profile within the tolerances rec- columns, as discussed in Section 3.3.5.
ommended in Section 5.3.2. Any inadvertent local reversed
curvature should be corrected prior to concreting. Tendon
5.4Concrete placement and curing
profiles are maintained by tying to reinforcing steel, chairs,
Concrete should be placed in such a manner that tendon
or other supports with wire ties. Ties should be installed so
alignment and reinforcing steel positions remain unchanged.
that they do not visibly imprint or dent the polyethylene or
Special attention must be given to vibration of concrete at
polypropylene sheathing. Recommendations for spacing of
tendon anchorages to insure uniform compaction at these
ties for bundles of unbonded tendons are presented in Sec-
points. Voids behind the bearing plate, or insufficient con-
tion 3.2.3.
crete strength, will cause concrete failure. Careful vibration
5.3.2 TolerancesVertical deviations in tendon location
and proper curing will eliminate most of these difficulties.
should be kept to 1/4 in. (6 mm) for slab thickness dimen-
sions less than 8 in. (20 mm), 3/8 in. (10 mm) in concrete Voids behind the bearing plate should be repaired prior to the
with dimensions between 8 in. (20 mm) and 2 ft (600 mm), stressing operation.
and 1/2 in. (12 mm) in concrete with dimensions over 2 ft Curing in accordance with the recommendations in ACI
(600 mm). These tolerances should be considered in estab- 308 and ACI 517.2R should be followed to avoid various
lishing minimum tendon cover dimensions, particularly in types of shrinkage-related cracking and to insure proper
applications exposed to deicer chemicals or saltwater envi- quality concrete. Calcium chloride or additives containing
ronments where use of additional cover is recommended to
compensate for placing tolerances. Slab behavior is relative-
ly insensitive to horizontal location of tendons.
5.3.3 OpeningsDeviations of tendons in the horizontal
plane that may be necessary to avoid interferences such as
openings, ducts, chases, inserts, etc., should be considered in
view of potential cracking due to lateral forces. Appropriate
means to avoid or control cracking include an adequately
large radius of curvature, sufficient clearance of the tendons
from the edge of an opening, a straight tendon extension be-
yond the opening corners, and hairpin reinforcement to Fig. 5.1Tendon layouts(a) Crack inhibiting layout; and
transfer the lateral forces to the surrounding concrete.59 (b) crack promoting layout
423.3R-16 ACI COMMITTEE REPORT

l = length of tendon in in. (mm)


Aps = area of prestressing steel in in.2 (mm2)
Es = modulus of elasticity of prestressing steel, psi (MPa)

The moduli of elasticity of various post-tensioning tendon


materials may be assumed as follows:10

Seven-wire strand: Es = 28,000,000 psi (193,000 MPa)


Wire: Es = 29,000,000 psi (200,000 MPa)
Bars: Es = 30,000,000 psi (207,000 MPa)

A table of elongation values for various tendons on a


project and/or a graphical presentation of expected elonga-
tions should be provided as part of the shop drawings for a
project.
It is a requirement of ACI 318 that the tendon force mea-
sured by gage pressure agree within 7 percent of the tendon
force calculated by elongation measurements. The cause of
variations in force determination in excess of 7 percent must
be ascertained and corrected. The modulus of elasticity of
seven-wire strand varies somewhat from the 28,000,000 psi
Fig. 5.2Isolated slab sections
(193,000 MPa) average value suggested. Since a variation of
1,000,000 psi (6900 MPa) in the modulus of elasticity repre-
sents a difference of about 4 percent in elongation, it is al-
calcium chloride or other chlorides should not be used in pre- ways preferable to use the actual modulus of elasticity of the
stressed concrete construction or in the material used to pro- strand used on the project when comparing tendon elonga-
tect end anchorages. Set accelerators that do not contain tion and gage pressure in the field.
calcium chloride are commercially available and may be
The tendon elongation is affected by the variation in force
used when required.
due to friction losses throughout the tendon length. For this
reason, friction losses should be considered in translating
5.5Stressing operations tendon elongation measurements into tendon forces. The
The stressing operation may begin when test cylinders elongation measurement provides a measure of the average
cured under job-site conditions and representative of the force throughout the length of the tendon, whereas the gage
concrete strength in the immediate vicinity of the anchorages pressure gives the force in the tendon at the anchorage.
indicate that the concrete has attained the strength specified Methods for calculating the effects of friction along the
for stressing (usually 60 to 80 percent of the 28-day length of the tendon are presented in ACI 318, Section 18.6.2
strength). Alternatively, nondestructive testing methods may ACI 318R, Section R18.18.1 requires that gages used to
be used to verify approximately the strength of the concrete measure jacking forces be calibrated. This calibration should
in the structure. ACI 318 does not currently include nonde- be done by an approved laboratory within 6 months prior to
structive methods in its criteria for acceptance of concrete. used.
However, such methods may be satisfactory for evaluating Stressing equipment for post-tensioning tendons incorpo-
the concrete in the immediate vicinity of the anchorages. rate reasonable factors of safety. Occasionally, flaws in ma-
Stressing of tendons should be monitored in two ways. terial are undetected or the equipment may have been
First, the gage reading on the pump should be translated into misused. For this reason, extreme caution should be exer-
force in the tendon at the anchorage. This information is gen- cised at all times, as stressing is carried out at extremely high
erally provided in a tendon stressing data table or curve sup- pressure. The primary safety rule is to keep personnel from
plied as part of the shop drawings. Second, the elongation of being directly in back, over, or under stressing equipment.
the tendon may be calculated using the formula Failure during the stressing operation may cause serious
Pl injury to any personnel in back of or in the immediate vicin-
l = --------------- ity of the stressing equipment. Should stressing reveal that
A ps E s
voids exist behind the bearing plate, release all pressure on
where the equipment at once, remove the faulty concrete, and patch
the void with suitable material. The patching material must
l = elongation in in. (mm) attain the required strength before the tendon is restressed.
P = average prestress force (considering friction effects Calcium chloride or admixtures that contain chloride ions
along the length of the tendon) in lb (N) should not be used in the patching operation.
CONCRETE MEMBERS PRESTRESSED WITH UNBONDED TENDONS 423.3R-17

5.6Form removal and reshoring E 119 Standard Methods of Fire Tests of Building Con-
Shoring must be left in place until the stressing operation struction and Materials
is completed. Edge or pocket forms and bulkheads should be
removed well ahead of the stressing operation. Beam or side International Conference of Building Officials
forms may be removed prior to stressing with permission Uniform Building Code
from the engineer.
Removal of shoring and forms may follow immediately These publications may be obtained from the following
after the stressing operation. After stressing, reshoring may organizations:
be required to prevent overloading during additional con-
struction. Usually, reshoring practices are a precaution American Concrete Institute
against overloading. Do not wedge shoring beyond a snug fit 38800 Country Club Drive
against prestressed members. P. O. Box 9094
Farmington Hills, MI 48333
5.7Welding and burning
When welding or burning near tendons, care must be ex- ASTM
ercised to prevent the prestressing steel from overheating, to 100 Barr Harbor Drive
keep electric arc jumps from occurring, and to keep molten West Conshohocken, PA 19428-2959
slag from coming in contact with the prestressing steel.
Grounding of welding equipment to the prestressing steel International Conference of Building Officials
should not be allowed. 5360 South Workman Mill Road
Whittier, CA 90601
5.8General procedures
Guidance for the protection of tendons during storage, 6.2Cited references
transit, and installation can be found in Reference 8. 1. Design and Construction of Post-Tensioned Slabs-on-
Ground, Post-Tensioning Institute, Phoenix, AZ, 1980, 89
CHAPTER 6REFERENCES pp.
2. Design of Post-Tensioned Slabs, Post-Tensioning In-
6.1Recommended references stitute, Phoenix, 1977, 52 pp.
The documents of the various standards-producing organi- 3. Ritz, Peter; Marti, Peter; and Thurlimann, Bruno, Ex-
zations referred to in this document follow with their serial periments on Flexure of Unbonded Prestressed Plates (Ver-
designation, including year of adoption or revision. Since suche ber das Biegeverhalten von vorgespanntgen Platten
some of these documents are revised frequently, generally in Ohne Verbund), Institut fr Baustatik und Konstruktion,
minor detail only, the user of this document should check di- Zrich, 1975, 114 pp.
rectly with the sponsoring group if it is desired to refer to the 4. Burns, Ned H., and Hemakom, Roongroj, Test of Scale
latest revision. Model Post-Tensioned Flat Plate, Proceedings, ASCE, V.
103, ST6, June 1977, pp. 1237-1255. Also, see Reference 5.
American Concrete Institute 5. Hemakom, R., Strength and Behavior of Post-Ten-
116R Cement and Concrete Terminology sioned Flat Plates with Unbonded Tendons, PhD disserta-
201.2R Guide to Durable Concrete tion, University of Texas, Austin, 1975, 272 pp. Also, see
216R Guide for Determining the Fire Endurance of Con- Reference 4 and Burns, Ned H., and Hemakom, Roongroj,
crete Elements Test of Flat Plate with Banded Tendons, Proceedings,
308 Standard Practice for Curing Concrete ASCE, V. 111, No. 9, Sept. 1985, pp. 1899-1915.
318 Building Code Requirements for Structural Con- 6. Winter, C. Victor, Test of Four Panel Post-Tensioned
crete and Commentary Flat Plate with Unbonded Tendons, thesis, University of
423.2R Tentative Recommendations for Prestressed Con- Texas, Austin, 1977. Also;, Kosut, Gary M.; Burns, Ned H.;
crete Flat Plates and Winter, C. Victor, Test of Four-Panel Post-Tensioned
517.2R Accelerated Curing of Concrete at Atmospheric Flat Plate, Proceedings, ASCE, V. 111, No. 9, Sept. 1985,
Pressure State of the Art pp. 1916-1929.
7. Specification for Unbonded Single Strand Tendons,
ASTM Revised 1993, Post-Tensioning Institute, Phoenix, 1993, 20
pp.
A 123 Standard Specifications for Zinc (Hot-Galvanized) 8. Field Procedures Manual for Unbonded Single Strand
Coatings on Products Fabricated from Rolled, Tendons, Second Edition, Post-Tensioning Institute, Phoe-
Pressed, and Forced Steel Shapes, Plates, Bars, and nix, AZ, 1994, 62 pp.
Strip 9. Design for Fire Resistance of Precast, Prestressed Con-
B 633 Standard Specification for Electrodeposited Coat- crete, Second Edition, Publication No. MNL-124-89, Pre-
ings of Zinc on Iron and Steel cast-Prestressed Concrete Institute, Chicago, 1989, 96 pp.
423.3R-18 ACI COMMITTEE REPORT

10. Post-Tensioning Manual, 5th Edition, Post-Tension- 26. Hawkins, Neil M., and Ishizuka, Takayuki, Concrete
ing Institute, Phoenix, 1985, 406 pp. Ductile Moment Resistant Frames, Proceedings, Ninth
11. Recommended Lateral Force Requirements and World Conference on Earthquake Engineering, Tokyo, Ja-
Commentary, Seismology Committee, Structural Engi- pan, 1988.
neers Association of California, San Francisco, 1974 (Re- 27. Burns, Ned H.; Charney, Finley A.; and Vines, Wen-
vised 1990), 203 pp. 12. NEHRP, Recommended dell R., Tests of One-Way Post-Tensioned Slabs with Un-
Provisions for the Development of Seismic Regulations for bonded Tendons, Journal, Prestressed Concrete Institute,
New Buildings, Federal Emergency Management Agency, V. 23, No. 5, Sept.-Oct. 1978, pp. 66-83. Also, Charney, Fin-
1991. ley Allen, Strength and Behavior of a Partially Prestressed
13. BOCA, National Building Code, Building Officials Concrete Slab with Unbonded Tendons, MSc thesis, Uni-
and Code Administrators International, Inc., Country CLub versity of Texas, Austin, 1976, 179 pp., and Vines, Wendell
Hills, IL, 1993, 342 pp. R., Strength and Behavior of a Post-Tensioned Concrete
14. SBC, Standard Building Code, Southern Building Slab with Unbonded Tendons, MSc thesis, University of
Code Congress International, Inc., Birmingham, AL, 1994, Texas, Austin, 1976, 176 pp.
762 pp. 28. Yamazaki, Jun; Kattula, Basil T.; and Mattock, Alan
15. Parme, Alfred L., American Practice in Seismic De- H., Comparison of the Behavior of Post-Tensioned Pre-
sign, Journal, Prestressed Concrete Institute, V. 17, No. 4, stressed Concrete Beams With and Without Bond, Struc-
July-Aug. 1972, pp. 31-44. tures and Mechanics Report No. SM69-3, University of
16. Hawkins, Neil M., Lateral Load Resistance of Un- Washington, Seattle, 1969, 92 pp.
bonded Post-Tensioned Flat Plate Construction, Journal, 29. Burns, Ned H., and Pierce, David M., Strength and
Prestressed Concrete Institute, V. 26, No. 1, Jan-Feb. 1981, Behavior of Prestressed Concrete Members with Unbonded
pp. 94-116. Tendons, Journal, Prestressed Concrete Institute, V. 12,
No. 5, Oct. 1967, pp. 15-29.
17. Chung, H. W., Unbonded Tendons in Post-Tensioned
30. Walker, H. Carl, Durability of Parking Structure
Concrete Beams Under Repeated Loading, ACI JOURNAL,
Floors, Concrete International: Design and Construction,
Proceedings V. 70, No. 12, Dec. 1973, pp. 814-816.
V. 2, No. 3, Mar. 1980, pp. 47-50.
18. Miyamoto, Y., et al., Bending Fatigue Strength of
31. Scordelis, A. C.; Lin, T. Y.; and Itaya, R., Behavior
Unbonded Prestressed Concrete Beams, Railway Technical
of a Continuous Slab Prestressed in Two Directions, ACI
Research Report No. 844, Japan National Railway, 1973. (in
JOURNAL, Proceedings V. 56, No. 6, Dec. 1959, pp. 441-460.
Japanese)
32. Cleland, D. J.; Franklin, Y.; and Long, A. E., The
19. Inomata, Shunji, Comparative Study on Behavior of
Punching Strength of Unbonded Post-Tensioned Slabs at the
Prestressed and Reinforced Concrete Beams Subject to
Columns, International Conference on Concrete Slabs,
Loading Reversals, Journal, Prestressed Concrete Institute,
University of Dundee, 1979, 14 pp.
V. 16, No. 1, Jan.-Feb. 1971, pp. 21-37.
33. Gerber, Loris L., and Burns, Ned H., Ultimate
20. Blakeley, Roger W. G., and Park, Robert, Seismic Strength Tests of Post-Tensioned Flat Plates, Journal, Pre-
Resistance of Prestressed Concrete Beam-Column Assem- stressed Concrete Institute, V. 16, No. 6, Nov.-Dec. 1971,
blies, ACI JOURNAL, Proceedings V. 68, No. 9, Sept. 1971, pp. 40-58.
pp. 677-692. 34. Smith, Stephen W., and Burns, Ned H., Post-Ten-
21. Thompson, Kevin H., and Park, Robert, Cyclic Load sioned Flat Plate to Column Connection Behavior, Journal,
Tests on Prestressed and Reinforced Concrete Beam-Col- Prestressed Concrete Institute, V. 19, No. 3, May-June 1974,
umn Joints, Journal, Prestressed Concrete Institute, V. 22, pp. 74-91.
No. 5, Sept.-Oct. 1977, pp. 84-110. 35. Kosut, Gary M., Shear Strength of a Post-Tensioned
22. Priestley, M. J. N., and Tao, J., (1993) Seismic Re- Flat Plate at the Column Connections, MS Research Report,
sponse of Precast Concrete Frames with Partially Debonded University of Texas at Austin, 1977, 104 pp. Also, see Ref-
Tendons, Journal, Prestressed Concrete Institute, Jan.-Feb. erence 4.
1993. 36. Sunidja, Harianto; Foutch, Douglas A.; and Gamble,
23. Priestley, M. J. N., and MacRae, G. A., Precast Seis- William A., Response of Prestressed Concrete Plate-Edge
mic Resisting Frames Using Unbonded Prestressing Teno- Column Connections, Structural Research Series No. 498,
dns, FIP 1994 XII Congress, Proceedings, pp. E10-E15, Report No. UILU-ENG-82-2006, University of Illinois, Ur-
1994. bana, Mar. 1982.
24. ACI Northern California and Western Nevada Chap- 37. Pillai, S. Unnikrishna; Kirk, Wayne; and Scavuzzo,
ter, The Performance of Reinforced Concrete Structures Leonard, Shear Reinforcement at Slab-Column Connec-
during the Northridge Earthquake, Mar. 1994, 18 pp. tions in a Reinforced Concrete Flat Plate Structure, ACI
25. Suarez, Mario G., and Schupack, Morris, Evaluation JOURNAL, Proceedings V. 79, No. 1, Jan.-Feb. 1982, pp. 36-
of the Performance of Single Strand Unbonded Tendons in 42.
the Collapse of the LAmbiance Plaza Lift-Slab Building, 38. Dilger, W.H., and Ghali, A., Shear Reinforcement for
Project Report, Post-Tensioning Institute, Phoenix, Apr. Concrete Slabs, Proceedings, ASCE, V. 107, ST12, Dec.
1988, 4 pp. 1981, pp. 2403-2420.
CONCRETE MEMBERS PRESTRESSED WITH UNBONDED TENDONS 423.3R-19

39. Mokhtar, Abdel-Salam; Ghali, Amin; and Dilger, sioned Monostrand Anchorages, Post-Tensioning Institute,
Walter H., Stud Shear Reinforcement for Flat Concrete Phoenix, Dec. 1987.
Plates, ACI JOURNAL, Proceedings V. 82, No. 5, Sept.-Oct. 50. Tanaka, Yoshito; Kurauchi, Makoto; and Masuda,
1985, pp. 676-683. Yoji, Ten Year Marine Atmosphere Exposure Test of Un-
40. Muller, Franz-Xaver; Muttoni, Aurelio; and Thurli- bonded Prestressed Concrete Prisms, Post-Tensioning In-
mann, Bruno, Durchstanzversuche an Flachdeken mit stitute, Phoenix, May 1988, 58 pp.
Aussparungen, Institut fr Baustatik und Konstrucktion 51. Breen, J. E.; Burdet, O. L.; Roberts, C. L.; Sanders, D.
ETH, Zrich, Dec. 1984. H.; and Wollmann, G., Anchorage Zone Reinforcement for
41. Brandli, Werner; Muller, Franz-Xavier; and Thurli- Post-Tensioned Concrete Girders, NCHRP Report #356,
mann, Bruno, Bruchversuch an Stahlbeton und Spannbe- 1994, 205 pp.
tonplatten bei Randund Eckstutzen, Institut fr Baustatik 52. Sanders, D. H., and Breen, J. E., Generalized Ap-
und Konstrucktion ETH, Zrich, May 1982. proach to Design of Post-Tensioned Concrete Anchorage
Zones, Transportation Research Record, No. 1371, Mar.
42. Mojtahedi, Soussan, and Gamble, William L., Ulti-
1993, pp. 83-91.
mate Steel Stresses in Unbonded Prestressed Concrete,
53. Schupack, M., Behavior of 20 Post-Tensioned Test
Proceedings, ASCE, V. 104, ST7, July 1978, pp. 1159-1165.
Beams Subject to up to 2200 Cycles of Freezing and Thaw-
43. Burns, Ned; Helwig, Todd; and Tsujimoto, Tetsuya,
ing in the Tidal Zone at Treat Island, Maine, Performance
Effective Prestress Force in Continuous Post-Tensioned of Concrete in Marine Environment, SP-65, American Con-
Beams with Unbonded Tendons, ACI Structural Journal, crete Institute, Detroit, 1980, pp. 133-152.
V. 88, No. 1, Han.-Feb. 1991, pp. 84-90. 54. O'Neil, Edward F., Durability and Behavior of Pre-
44. Bondy, Kenneth B., Variable Prestress Force in Un- stressed Concrete Beams: Report 4, Post-Tensioned Con-
bonded Post-Tensioned Concrete Members, Concrete In- crete Beam Investigation with Laboratory Tests from June
ternational, American Concrete Institute, Jan. 1992, pp. 27- 1961 to September 1975, Technical Report No. 6-570, U.S.
33. Army Engineer Waterways Experiment Station, Vicksburg,
45. Zia, Paul; Preston, H. Kent; Scott, Norman L.; and Feb. 1977, 172 pp.
Workman, Edwin B., Estimating Prestress Losses, Con- 55. Poston, Randall W.; Carrasquillo, Ramon L.; and
crete International: Design & Construction, V. 1, No. 6, Breen, John E., Durability of Post-Tensioned Bridge
June 1979, pp. 32-38. Decks, ACI Materials Journal, V. 84, No. 4, July-Aug.
46. Aalami, Bijan, and Barth, Florian, Restraint Cracks 1987, pp. 315-326.
and their Mitigation in Unbonded Post-Tensioned Building 56. Schupack, Morris, Survey of the Durability Perfor-
Structures, Cracking of Prestressed Concrete Structures, mance of Post-Tensioning Tendons, Post-Tensioning Insti-
SP-113, American Concrete Institute, Detroit, 1989, pp. tute, Phoenix, Jan. 1978, 10 pp. Also, ACI JOURNAL,
157-202. Also, Separate Publication, Post-Tensioning Insti- Proceedings V. 75, No. 10, Oct. 1978, pp. 501-510.
tute, Phoenix. 57. Schupack, Morris, Protection of Post-Tensioning
47. Branson, D. E., and Christiason, M. L., Time Depen- Tendons in Concrete Structures, Civil Engineering
dent Concrete Properties Related to DesignStrength and ASCE, V. 52, No. 12, Dec. 1982, pp. 43-45.
Elastic Properties, Creep, and Shrinkage, Designing for Ef- 58. Schupack, M., Corrosion Protection for Unbonded
fects of Creep, Shrinkage, Temperature in Concrete Struc- Tendons, Concrete International, Feb. 1991, pp. 51-57.
tures, SP-27, American Concrete Institute, Detroit, 1971, pp. 59. Falconer, Daniel W., and Wilson, Philip W., Inspec-
257-277. tion of Unbonded Tendons, Concrete International: Design
and Construction, V. 10, No. 2, Feb. 1988, pp. 53-56.
48. Ghali, Amin; Dilger, Walter; and Neville, Adam M.,
60. Building Code Requirements for Reinforced Con-
Time-Dependent Forces Induced by Settlement of Supports
crete (ACI 318-95) and Commentary (ACI 318R-95),
in Continuous Reinforced Concrete Beams, ACI JOURNAL,
American Concrete Institute, Detroit, 1995, 347 pp.
Proceedings V. 66, No. 11, Nov. 1969, pp. 907-915.
49. Sanders, David H.; Breen, John E.; and Duncan, Roy
These revisions were submitted to letter ballot of the Committee and approved in
R. III, Strength and Behavior of Closely Spaced Post-Ten- accordance with ACI balloting procedures.