Project: ETAP Page: 1

12.6.5C
Location: Date: 16-03-2017
Contract: SN: INDOKOMAS2
Engineer: Revision: Base
Study Case: SC
Filename: Generator Analysis Config.: Normal

Short-Circuit Summary Report

3-Phase Fault Currents

Device Capacity (kA)


Bus Device Making
Short-Circuit Current (kA)
ID kV ID Type Peak Ib sym Ib asym Idc I"k ip Ib sym Ib asym Idc Ik
Bus1 0.380 Bus1 Bus 69.784 168.939 50.886
0.380 CB1 CB 220.000 100.000 103.971 69.784 168.939 62.766 76.904 44.438
Bus3 0.380 Bus3 Bus 67.780 161.514 49.399
0.380 CB3 CB 220.000 100.000 103.971 67.780 161.514 61.343 72.494 38.631
Bus5 0.380 Bus5 Bus 69.784 168.939 50.886
0.380 CB5 CB 220.000 100.000 103.971 69.784 168.939 62.766 76.905 44.438
Bus12 0.380 Bus12 Bus 74.479 171.023 17.478
0.380 CB13 CB 220.000 100.000 103.971 74.479 171.023 65.313 83.283 51.674
0.380 CB15 CB 220.000 100.000 103.971 74.479 171.023 65.313 83.283 51.674
0.380 CB16 CB 220.000 100.000 103.971 74.479 171.023 65.313 83.283 51.674
Bus13 0.380 Bus13 Bus 74.479 171.023 17.478
0.380 CB13 CB 220.000 100.000 103.971 74.479 171.023 65.313 83.283 51.674
Bus14 0.380 Bus14 Bus 74.479 171.023 17.478
0.380 CB15 CB 220.000 100.000 103.971 74.479 171.023 65.313 83.283 51.674
Bus15 0.380 Bus15 Bus 74.479 171.023 17.478
0.380 CB16 CB 220.000 100.000 103.971 74.479 171.023 65.313 83.283 51.674

ip is calculated using method C


Ib does not include decay of non-terminal faulted indunction motors
Ik is the maximum steady state fault current
Idc is based on X/R from Method C and Ib as specified above

LV CB duty determined based on service rating.


Total through current is used for device duty.
* Indicates a device with calculated duty exceeding the device capability.
# Indicates a device with calculated duty exceeding the device marginal limit. ( 95 % times device capability)
Project: ETAP Page: 2
12.6.5C
Location: Date: 16-03-2017
Contract: SN: INDOKOMAS2
Engineer: Revision: Base
Study Case: SC
Filename: Generator Analysis Config.: Normal

Short-Circuit Summary Report

3-Phase
Short-Circuit
Device Capacity
Current
Bus ID Device ID Icw (kA) Tkr (sec.) Ith (kA)
Bus1 CB1 65.000 1.00 63.606
Bus3 CB3 85.000 1.00 61.659
Bus5 CB5 65.000 1.00 63.606
Bus12 CB13 85.000 1.00 43.974
Bus12 CB15 85.000 1.00 43.974
Bus12 CB16 85.000 1.00 43.974
Bus13 CB13 85.000 1.00 43.974
Bus14 CB15 85.000 1.00 43.974
Bus15 CB16 85.000 1.00 43.974

Icw = Rated short-time withstand current


Tkr = Rated short-time
Ith = Thermal equivalent short-time current
* Indicates a device with calculated duty exceeding the device capability.
# Indicates a device with calculated duty exceeding the device marginal limit. ( 95 % times device capability)