SANYO ELEVATORS AND ESCALATORS CO.

LTD USER GUIDE

Appendix 2

FUJI Inverter Experienced Parameter Setting Table


Set the parameters of LIFT inverter (asynchronous) according to the table below

(only for reference) Simulative Value

Paramet Name Value Note


er
F01 Speed 2 Simulative running
F03 Max. speed * According to motor nameplate
F04 Rated speed * According to motor nameplate
F05 Rated voltage 380V
F07 Acceleration/ deceleration time 1 3.5S Acceleration time of low speed
F08 Acceleration/ deceleration time 2 2.1S Deceleration time of low speed
F23 Start time 0.4Hz
F24 Duration 0.3s
F25 Stop speed 0.1Hz
F42 Control selection 0 PG vector control (asynchronous)
E01 X1 terminal function selection 0
E02 X2 terminal function selection 1
E03 X3 terminal function selection 2
E10 Acceleration/ deceleration time 3 0s Acceleration time of median speed
E11 Acceleration/ deceleration time 4 0s Deceleration time of median speed
E12 Acceleration/ deceleration time 5 0s Acceleration time of high speed
E13 Acceleration/ deceleration time 6 0s Deceleration time of high speed
E14 Acceleration/ deceleration time 7 0s Crawl deceleration time
E20 Y1 terminal function selection 35 Inverter output
E27 Terminal 30A/B/C (Relay output) 99 Whole alarm
E48 LED monitor details 2 Set speed
E61 Terminal 12 (Function selection) 4 Torque deflection instruction
E63 Terminal V2 (Function selection) 2 Simulative speed instruction
C05 Multi-speed 1 0 Crawl speed at terminalUnit: HZ
C06 Multi-speed 2 0 Inspection speed
C07 Multi-speed 3 0 Crawl speed
C10 Multi-speed 6 0 Median speed
C11 Multi-speed 7 0 High speed
C31 Simulative input deflection 0
adjustment (terminal 12)
C32 Simulative input gain adjustment 100
(terminal 12)
C33 Simulative input filter adjustment 0.05s
Page 146 of 158
SANYO ELEVATORS AND ESCALATORS CO.LTD USER GUIDE
(terminal 12)
P01 Motor pole No. * According to motor nameplate
P02 Motor capacity * According to motor nameplate
P03 Motor rated current * According to motor nameplate
P06 Motor no-load current * Default
P12 Motor rated speed difference
L01 Pulse encoder (selection) 0
L02 Pulse No. 1024 According to practice
L19 S curve 1 0 S curve at acceleration beginning
L22 S curve 4 0 S curve at median speed acceleration
end
L23 S curve 5 0 S curve at median speed
deceleration beginning
L24 S curve 6 0 S curve at high speed acceleration
end
L25 S curve e 7 0 S curve at high speed deceleration
beginning
L26 S p curve 8 0 S curve deceleration end
L27 S curve 9 0
L28 S curve 10 0
L36 P constant at high speed 8
L37 I constant at high speed 0.5s
L38 P constant at low speed 10
L39 I constant at low speed 0.5s
L40 Speed switch 1 5HZ
L41 Speed switch 2 10HZ
L60 Torque deflection drive side gain 50 Adjustable at jobsite
L61 Torque deflection brake side gain 50 Adjustable at jobsite

Synchronous speed Rated speed


Motor rated speed difference frequency=Basic frequency [Hz]
Synchronous speed [r/min]

Page 147 of 158


SANYO ELEVATORS AND ESCALATORS CO.LTD USER GUIDE

Appendix 3

FUJI Inverter Experienced Parameter Setting Table


Set the parameters of LIFT inverter with PR card (synchronous) according to

the table below (only for reference) Simulative Value


Parameter Name Value Note
F01 Speed 2 Simulative running
F03 Max. speed * According to motor nameplate
F04 Rated speed * According to motor nameplate
F05 Rated voltage 380V
F07 Acceleration/ deceleration time 1 3.5S Acceleration time of low speed
F08 Acceleration/ deceleration time 2 2.1S Deceleration time of low speed
F23 Start time 1.2Hz
F24 Duration =L66
F25 Stop speed 0.1Hz
F42 Control selection 1 PG vector control (synchronous)
E01 X1 terminal function selection 0
E02 X2 terminal function selection 1
E03 X3 terminal function selection 2
E10 Acceleration/ deceleration time 3 0s Acceleration time of median speed
E11 Acceleration/ deceleration time 4 0s Deceleration time of median speed
E12 Acceleration/ deceleration time 5 0s Acceleration time of high speed
E13 Acceleration/ deceleration time 6 0s Deceleration time of high speed
E14 Acceleration/ deceleration time 7 0s Crawl deceleration time
E20 Y1 terminal function selection 35 Inverter output
E27 Terminal 30A/B/C (Relay output) 99 Whole alarm
E48 LED monitor details 2 Set speed
E61 Terminal 12 (Function selection) 0 Torque deflection instruction
E63 Terminal V2 (Function selection) 2 Simulative speed instruction
C05 Multi-speed 1 0 Crawl speed at terminalUnit: HZ
C06 Multi-speed 2 0 Inspection speed
C07 Multi-speed 3 0 Crawl speed
C10 Multi-speed 6 0 Median speed
C11 Multi-speed 7 0 High speed
C31 Simulative input deflection 0
adjustment (terminal 12)
C32 Simulative input gain adjustment 100
(terminal 12)
C33 Simulative input filter adjustment 0.05s
(terminal 12)
P01 Motor pole No. * According to motor nameplate
P02 Motor capacity * According to motor nameplate
P03 Motor rated current * According to motor nameplate

Page 148 of 158


SANYO ELEVATORS AND ESCALATORS CO.LTD USER GUIDE
P06 Motor no-load current * Default
P12 Motor rated speed difference
L01 Pulse encoder (selection) 5 PR
L02 Pulse No. 2048 According to practice
L19 S curve 1 0 S curve at acceleration beginning
L22 S curve 4 0 S curve at median speed
acceleration end
L23 S curve 5 0 S curve at median speed
deceleration beginning
L24 S curve 6 0 S curve at high speed acceleration
end
L25 S curve e 7 0 S curve at high speed deceleration
beginning
L26 S p curve 8 0 S curve at deceleration end
L27 S curve 9 0
L28 S curve 10 0
L36 P constant at high speed 8
L37 I constant at high speed 0.5s
L38 P constant at low speed 10
L39 I constant at low speed 0.5s
L40 Speed switch 1 5HZ
L41 Speed switch 2 10HZ
L05 ACR P constant 2.5 1.5~4.0
L06 ACR I constant 0.8ms
L65 Unbalanced load compensation 1 1. valid 2. invalid
(validity selection)
L66 Unbalanced load compensation 0.5
(Calculation timing )
L67 Unbalanced load compensation 0.5
(Lower starting time)
L68 Unbalanced load compensation 15 4~20
(ASR P constant)
L69 Unbalanced load compensation 0.010s
(ASR I constant)
L73 Unbalanced load compensation 3.0 3~5
(ASR gain)

Synchronous speed Rated speed

Motor rated speed difference frequency=Basic frequency [Hz]


Synchronous speed [r/min]

Page 149 of 158